INSTALLATION INSTRUCTIONS
Wireless Plug Load Controller
Wireless Plug Load Controller with SmartCast® Technology
Includes: CPLC-JB-CWC
LPN00544X0001A0_C
1 of 5
UNIT DESCRIPTION
The Wireless Plug Load Controller is used
to control 120V AC receptacles in response
to attached occupancy sensor and through
wireless commands from other Cree
Smartcast® Technology devices. The Wireless
Plug Load Controller also offers contact
closure output (CCO) to control third party
equipment.
INSTALLATION
NOTE: For ease of installation, Cree
recommends using a Junction Box with a ½"
knockout.
STEP 1:
Disconnect power to circuit by turning circuit
breaker OFF before installation.
STEP 2:
Remove Junction Box cover.
STEP 3:
Remove knockout and firmly install plastic
relay box into Junction Box until it snaps and
is securely attached
STEP 4:
Strip existing Junction Box wires ½".
STEP 5:
Make wiring connection per the Electrical
Connections section.
STEP 6:
Attach Junction Box cover.
STEP 7:
Install sensor into ceiling by drilling a 2" hole
into the ceiling.
1
Blue LED is Inside the Relay Box, Light will
Shine Through at the LED Placement Shown
Below.
Test/Reset
Button Inside
Blue LED
Placement
This End Insert into
Junction Box
Occupancy
Sensor
Wireless Plug
Load Controller
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. DANGER- Risk of shock- Disconnect power before installation.
DANGER – Risque de choc – Couper l’alimentation avant l’installation.
2. Must be installed in accordance with the NEC or your local electrical
code. If you are not familiar with these codes and requirements, consult a
qualied electrician.
Ce produit doit être installé conformément à NEC ou votre code électrique
local. Si vous n’êtes pas familier avec ces codes et ces exigences, veuillez
contacter un électricien qualié.
3. Indoor use only and Suitable for Damp Locations.
Pour usage interieur seulement et convient aux emplacements humides.
4. This equipment should be installed and operated with a minimum distance
20cm between the radiator and your body.
L’équipement doit etre installe d’une facon qu’une distance minimum de 20cm
soit maintenue entre l’emetteur et toute partie du corps.
SAVE THESE INSTRUCTIONS FOR
FUTURE REFERENCE
Suitable for use in other Environmental Air Space
(Plenums) in accordance with section 300.22,(c) of the
National Electrical Code.
Voltage: 120 VAC, 60Hz.
AC Load Type:
• 20 A Resistive load @ 120VAC
1 HP Motor load @ 120VAC
• 20A Standard ballast load @ 120VAC
• 20A Tungsten (incandescent) load @ 120VAC
• 20A General use @ 120VAC
Contact Closure Output (CCO) load:
• Up to 24VDC, 0.5A resistive load on dry contacts
(N/O, COM, N/C)
• For connection to Class 2 circuit only.
Install using a junction box that has a 1/2" knockout.
NOTE:
Not for use with equipment that requires constant power or equipment that
presents a hazard if automatically energized. Devices requiring soft shutdown
(such as computers) or other power related requirements (such as projectors,
DVRs or Clocks) may not be compatible.
LPN00544X0001A0_C
2 of 5
STEP 8:
Unscrew the small trim ring near the sensor
and place sensor assembly through the
ceiling. See Figure 2.
STEP 9:
Secure the sensor assembly by screwing the
small trim ring removed in Step 8 back onto
the sensor assembly. Tighten the larger trim
ring above the ceiling until it is snugged tight
against the ceiling. See
Figure 2.
STEP 10:
Switch the circuit breaker ON.
STEP 11:
The blue LED should repeat a two blink
sequence. If the blue LED is blinking
but does not respond with the two-blink
sequence, please follow the RESET
instructions to return the Wireless Plug Load
Controller to factory defaults.
STEP 12:
Verify the LOAD wiring with the following
TEST instructions:
Press and hold the Test/Reset button
for 5 sec then release. The blue LED
should respond with a five-blink
sequence. Once TEST mode has been
entered, LOAD enters State 1. See
Figure 1.
Press and hold Test/Reset button for
1 sec then release to transition to
the next state. The sequence repeats
after State 2. Please refer to the load
table below.
To exit test mode at any time, press
and hold the Test/Reset button for
5 sec then release. The five-blink
sequence ends when TEST mode is
exited.
Plug Load
Controller
State
LOAD
STATUS
CCO Status
N/O N/C
State 1 Off Open Closed
State 2 On Closed Open
STEP 13:
Perform commissioning using Cree
Configuration Tool (OneButton® Setup). The
table below shows different blink patterns
and their meanings.
Status LED
indicator Operating Mode
1 Blink Normal mode
2 Blink Ready for OneButton® Setup
3 Blink OneButton® Setup in process
4 Blink Select mode
5 Blink TEST Mode
Solid ON or
OFF
Error- contact Cree Customer
Service
RESET (FACTORY DEFAULTS)
STEP 1:
Press and hold Test/Reset button until the
LED flashes fast (approximately 30 seconds).
STEP 2:
Release the Test/Reset button for 1 second
(Fast flashing continues). Press and hold
Test/Reset for 1 second until fast flashing
stops. If the blue LED does not respond with
the two-blink sequence, please repeat the
RESET procedure.
TROUBLESHOOTING:
Out of the box, if the LOAD does not turn on
when power is applied:
1. Check blue LED to make sure it is
blinking. If Blue LED is on solid or off,
call Cree Customer Service.
2. If not in two blink mode, then
perform a RESET (See RESET
section).
3. If in two blink mode, then perform
TEST mode (See Step 12)
4. If TEST mode fails, check wiring with
power off.
5. If wiring is correct and the LOAD is
still off, call Cree Customer Service.
FCC NOTICE
This device complies with Part 15 of the
FCC Rules. Operation is subject to the
following two conditions: (1) this device
may not cause harmful interference, and
(2) this device must accept any interference
received, including interference that may
cause undesired operation. Any changes or
modifications not expressly approved by the
party responsible for compliance could void
the user’s authority to operate the device.
This device has been tested and found to
comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide
reasonable protection against harmful
interference when the device is operated
in a commercial environment. This device
generates, uses, and can radiate radio
frequency energy and, if not installed and
used in accordance with the instruction
manual, may cause harmful interference
to radio communications. Operation of this
device in a residential area is likely to cause
harmful interference in which case the user
will be required to correct the interference at
his own expense.
In addition, this device complies with ICES-
005 of the Industry Canada (IC) Regulations.
INDUSTRY CANADA STATEMENT
This device complies with Industry Canada
licence-exempt RSS standard(s). Operation
is subject to the following two conditions: (1)
this device may not cause interference, and
(2) this device must accept any interference,
including interference that may cause
undesired operation of the device. In
addition, this device complies with ICES-005
of the Industry Canada (IC) Regulations.
Le présent appareil est conforme aux CNR
d’Industrie Canada applicables aux appareils
radio exempts de licence. L’exploitation est
autorisée aux deux conditions suivantes : (1)
l’appareil ne doit pas produire de brouillage,
et (2) l’utilisateur de l’appareil doit accepter
tout brouillage radioélectrique subi,
même si le brouillage est susceptible d’en
compromettre le fonctionnement.
2Large Trim Ring
Small Trim Ring
Ceiling
Occupancy
Sensor
LPN00544X0001A0_C
3 of 5
ELECTRICAL CONNECTIONS FOR CONTROLLED RECEPTACLES:
STEP 1:
Make the following Electrical Connections:
a. Connect the 12AWG black lead of the Wireless Plug Load Controller to the Line voltage in the junction box.
b. Connect the white lead of the Wireless Plug Load Controller to the Neutral voltage in the junction box.
c. Connect the red lead of the Wireless Plug Load Controller to the controlled outlet’s Line voltage.
FOR CCO (CONTACT CLOSURE OUTPUT) CONNECTIONS:
a. Connect the 18AWG black lead exiting form the side of the Wireless Plug Load Controller to the “Common” of the third party equipment to
be controlled in series.
b. Connect the blue wire of the Wireless Plug Load Controller to the other line of the third party equipment to be controlled in series for a
normally ON connection.
or
Connect the brown wire of the Wireless Plug Load Controller to the other line of the third party equipment to be controlled in series for a
normally OFF connection.
STEP 2:
All receptacles controlled by Wireless Plug Load Controller must be marked with “ “ and text “controlled” where it is visible to end user as per
NEC NFP70 2017 requirements. For convenience, labels are included that are intended for application on surfaces made from materials as called
out in Note 4 below.
**NOTE 1: Contact Closure Output (CCO) leads can be used to control third party equipment in one of the 2 configurations:
Using N/O (Normally Open) and COM (Common) which forms continuity when controlled receptacle is on.
Using N/C (Normally Closed) and COM (Common) which forms continuity when controlled receptacle is off.
**NOTE 2: More than one controlled receptacle may be daisy chained off the Plug Load Controller.
**NOTE 3: Not for use with equipment that requires constant power or equipment that presents a hazard if automatically energized.
**NOTE 4: Controlled Receptacle label supported materials: ABS (Acrylonitrile Butadiene Styrene), Textured ABS, Polypropylene, Polycarbonate,
Polyphenylene oxide/ether, Painted Enamel, Alkyd paint, Epoxy powder paint.
Line (Black)
Neutral (White)
120 VAC
60 Hz
Switched Line
(Red)
I5A/20A Controlled
Receptacle
N/O (Blue)
Com (Black)
N/C (Brown)
CCO Leads
** See Note 1
24 VDC
O.5A
Resistive
Load
An Example CCO Connection
(CCO load ON when controlled
receptacle is ON)
Junction
Box
C
O
N
T
R
O
L
L
E
D
C
O
N
T
R
O
L
L
E
D
I5A/20A Controlled
Receptacle
C
O
N
T
R
O
L
L
E
D
Duplex receptacle
with both outlets
Controlled
Split wired Duplex receptacle
with one outlet Controlled
Occupancy Sensor
Controlled Duplex Receptacle without and with split wiring
LPN00544X0001A0_C
4 of 5
www.cree.com/lighting
© 2017 Cree, Inc. All rights reserved. For informational purposes only. Content is subject to change. See
www.cree.com/lighting/products/warranty for warranty and specifications. Cree®, OneButton® and
SmartCast® are registered trademarks, and the Cree logo is a trademark of Cree, Inc.
ELECTRICAL CONNECTIONS:
**NOTE 1: Contact Closure Output (CCO) leads can be used to control third party equipment in one of the 2 configurations:
Using N/O (Normally Open) and COM (Common) which forms continuity when controlled receptacle is on.
Using N/C (Normally Closed) and COM (Common) which forms continuity when controlled receptacle is off.
**NOTE 2: More than one controlled receptacle may be daisy chained off the Plug Load Controller.
**NOTE 3: Not for use with equipment that requires constant power or equipment that presents a hazard if automatically energized.
**NOTE 4: Controlled Receptacle label supported materials: ABS (Acrylonitrile Butadiene Styrene), Textured ABS, Polypropylene, Polycarbonate,
Polyphenylene oxide/ether, Painted Enamel, Alkyd paint, Epoxy powder paint.
I5A/20A Uncontrolled
Receptacle
Line (Black)
Neutral (White)
120 VAC
60 Hz
Switched Line
(Red) I5A/20A Controlled
Receptacle
N/O (Blue)
Com (Black)
N/C (Brown)
CCO Leads
** See Note 1
24 VDC
O.5A
Resistive
Load
An Example CCO Connection
(CCO load ON when controlled
receptacle is OFF)
Junction Box
Occupancy Sensor
C
O
N
T
R
O
L
L
E
D
C
O
N
T
R
O
L
L
E
D
Controlled and Uncontrolled Duplex Receptacle