InterLogix 1036525 En Rev F Esl 500N Series Smoke Detector Installation Sheet Sheetx User Manual

2017-11-02

User Manual: InterLogix 1036525-En-Rev-F-Esl-500N-Series-Smoke-Detector-Installation-Sheet

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadInterLogix 1036525-En-Rev-F-Esl-500N-Series-Smoke-Detector-Installation-Sheet - 1036525-EN Rev F ESL 500N Series Smoke Detector Installation Sheetx User Manual
Open PDF In BrowserView PDF
ESL 500N Series Smoke Detector
Installation Sheet
Additional features
Depending on the model, the smoke detector may also provide
the following features.
CleanMe: Enables a CleanMe compatible control panel to
receive a warning signal, indicating that the optical chamber
needs to be replaced. This feature is available on the 500N
Series two-wire detectors only.
The 500N Series two-wire detectors enable the CleanMe
function by recognizing voltage polarity at installation. If the +
and − terminal connections are reversed, the CleanMe function
is enabled. New 500N Series detectors are compatible on the
same loop with previous 500 Series detectors if proper wiring
is observed. See “Wiring” on page 4.

Description

Integral temporal-three sounder: In the 500N models with
sounder, a piezoelectric horn produces an interrupted 85 dBA
tone when the detector alarms or when the polarity is reversed.
Sounder follows input voltage in reverse polarity.

Note: This document is intended for licensed electricians or
alarm installers. We cannot provide technical support to
unqualified persons. If you have any questions, contact us
using the “Contact information” on page 8.

In order for all sounders to activate when the panel alarms, the
panel must reverse the supply voltage polarity to the loop on
alarm. If the panel does not implement polarity reversal, an
ESL 405 Polarity Reversal Relay Module must be used. (Refer
to the installation sheet for the ESL 405 Polarity Reversal
Relay Module.)

The ESL 500N Series conventional two-wire and four-wire
photoelectric smoke detectors have intelligent software and
digitally processed sensing capabilities. This intelligence,
coupled with the ESL patented optical sensing chamber,
means the ESL 500N Series quickly and accurately detects
smoke. CleanMe compatible software, self-diagnostics, and
dust (drift) compensation are standard in every unit. The ESL
500N Series offers application flexibility with optional auxiliary
relays, rate-of-rise/fixed temperature heat sensors, isolated
heat sensors and/or 85 dBA temporal-three sounders.

Auxiliary and end-of-line relays: Auxiliary relays are Form C
and operate at 1 A at 30 VDC to allow for the addition of
auxiliary notification devices to the smoke loops. Products with
an “R” in the suffix signify the auxiliary relay feature.
An end-of-line relay operates as a power supervision relay and
is normally energized and will release with the loss of power.
Products with an “E” in the suffix signify the end-of-line feature.

Standard features
All models ship standard with the features described below.

Heat sensors: Some models come with rate-of-rise or fixed
temperature heat sensors which allow the unit to detect
changes in temperature that may signal a fire event. Models
with an “XT” in the suffix have a heat sensor included.

Detector-base lock: Discourages unauthorized removal of the
smoke detector by requiring a screwdriver to remove the
detector from the base.
Self-diagnostics: Includes automatic sensitivity testing. Once
a day and immediately upon first power up, each 500N Series
detector performs a full diagnostic test that includes a dynamic
test of the sensing chamber and internal electronics. This
meets NFPA 72 field sensitivity testing requirements without
the need for external meters.

Some models are available with an isolated heat sensor. If the
unit senses a temperature change it will alert the panel and
signal an alarm independent of smoke in the photoelectric
chamber. The heat alarm output is on the alarm relay and the
smoke detector output is on the auxiliary relay. Models with an
“H” in the suffix have an isolated heat sensor which is both rate
of-rise and fixed temperature.

Drift compensation (dust compensation): The detectors
automatically adjust sensitivity, up to a maximum of 1.0%/ft.,
as the detectors become dirty.

© 2017 United Technologies Corporation

1/8

P/N 1036525-EN • REV F

Compatibility
Please refer to the ESL Compatibility Index for a complete
listing of control panels and proper identifiers. For a copy of the
compatibility index, see “Contact information” on page 8.
Remember, four-wire smoke detectors do not require a
compatibility listing.

Selecting a location

Where to locate the required smoke detectors in new
construction. All of the smoke detectors specified for existing
construction are required and, in addition, a smoke detector is
required in each bedroom.

Selecting a suitable location is critical to the operation of
smoke detectors. This equipment should be installed in
accordance with NFPA 72. Figure 1 shows required and
additional locations.
Figure 1: Detector location

(1)

(2)

(4)

(4)

(3)

(5)

(1)

(2)

(3)

(4)
(4)

A

smoke detector should be installed in the living room or near
the stairway to the upper level, or in both locations. The
basement smoke detector should be installed in close
proximity to the stairway leading to the floor above. Where
installed on an open-joisted ceiling, the alarm should be placed
on the bottom of the joists. The alarm should be positioned
relative to the stairway to intercept smoke coming from a fire in
the basement before the smoke enters the stairway.

(4)

(4)
B

Are more smoke detectors desirable? The required number
of smoke detectors might not provide reliable early warning
protection for those areas separated by a door from the areas
protected by the required smoke detectors. For this reason, it
is recommended that the householder consider the use of
additional smoke detectors for those areas for increased
protection. The additional areas include the basement,
bedrooms, dining room, furnace room, utility room, and
hallways not protected by the required smoke detectors. The
installation of smoke detectors in kitchens, attics (finished or
unfinished), or garages is not normally recommended, as these
locations occasionally experience conditions that can result in
improper operation.
Note: Regulations pertaining to smoke detector installation
vary from state to state. For more information, contact your
local fire department or local authority having jurisdiction.

C

(4)

(4)

(3)

Additional considerations. In addition to NFPA 72, use the
following location guidelines to optimize performance and
reduce the chance of false alarms from the detector:
•

Locate ceiling-mounted smoke detectors in the center of a
room or hallway at least 4 in. (10 cm) from any walls or
partitions.

•

Locate wall-mounted smoke detectors so the top of the
alarm is 4 to 12 in. (10 to 31 cm) below the ceiling.

•

Do not locate detectors in or near bathrooms or kitchens.

•

Locate smoke alarms in a suitable environment with
temperature and humidity as defined in “Specifications” on
page 8.

•

Locate smoke detectors away from air conditioners,
heating registers, and any other ventilation source that
may interfere with smoke entering the alarm.

•

Mount smoke detectors on a firm, permanent surface.

(1)

(6)

(1)
(2)
(3)

Dining Room
Kitchen
Living Room

(4)
(5)
(6)

Bedroom
TV Room
Basement

Required smoke detectors
Additional alarms required for new construction

Where to locate the required smoke detectors in existing
construction. The major threat from fire in a family living unit
occurs at night when everyone is asleep. The principal threat
to persons in sleeping areas comes from fires in the remainder
of the unit. Therefore, a smoke detector is best located
between the bedroom areas and the rest of the unit. In units
with only one bedroom area on one floor, the smoke detector
should be located as shown in Figure 1-A.
In family living units with more than one bedroom area or with
more than one floor, more than one smoke detector is
required, as shown in Figure 1-B.
In addition to smoke detectors outside of the sleeping areas,
the installation of a smoke detector on each additional story of
the family living unit, including the basement, is required.
These installations are shown in Figure 1-C. The living area

2/8

Installing the detector
All wiring must conform to the National Electric Code (NEC)
and/or local codes having jurisdiction. Use 12 to 24 AWG (16
to 22 AWG recommended) wire to install the detector.
1.

If you are using the detector-base lock, remove the
detector knockout and break off the tab on the mounting
base. See Figure 2.

2.

Remove the red plastic cover from the detector. The
detector is shipped with a cover for protection against
construction site dust.

P/N 1036525-EN • REV F

3.

Run system wiring to the detector location and mount
electrical boxes if necessary. The detector fits standard
single-gang boxes and 3-1/2 in. and 4 in. round ceiling
boxes.

4.

Line up and attach the mounting base to the electrical box,
wall, or ceiling using the screws provided. Use wall
anchors if necessary. See Figure 3.

5.

Strip the system wires and connect them to the
appropriate terminals on the detector. See “Wiring” on
page 4.

6.

Attach the detector to the mounting base as follows:

Figure 4: Mounting

a. Line up the raised tab on the side of the detector with
the arrow on the mounting base. See Figure 4.
b. Insert the smoke detector into the base and turn
clockwise approximately 15 degrees. It should snap firmly
into place.
7.

Removing the detector
To remove the detector from the mounting base: Grasp the
detector and turn it counterclockwise approximately 15
degrees. The detector should snap off of the mounting base.

Apply power and test the detector. See “Smoke testing” on
page 5.

Figure 2: Detector-base lock

To remove the detector from the mounting base when the
detector-base lock is used: Insert a small screwdriver into
the locking tab slot on the side of the base and press in while
simultaneously turning the detector counterclockwise 15
degrees. See Figure 5.
Figure 5: Unlocking the detector

Figure 3: Detector installation

P/N 1036525-EN • REV F

3/8

Wiring
Figure 6: 500N Series two-wire wiring

Two-wire
initiating
circuit

+
_
Last
detector

First
detector

EOL
device

Listed alarm control
CleanMe
Disabled

CleanMe
Enabled

CleanMe
Disabled

NC
COM
NO

Model
521NB/521NBXT
521NCSXT
521NC/521NCXT

Model
521NB/521NBXT
521NCSXT
521NC/521NCXT

Caution: Risk of system failure. The system may not operate if
the detector is not connected to the control unit initiating device
circuit as specified in the detector or control unit literature.

Model
521NB/521NBXT
521NCSXT
521NC/521NCXT

Note: The 500N Series two-wire detectors are polarity
sensitive.
Note: CleanMe is enabled by wiring units in reverse polarity.

Figure 7: 500N Series four-wire wiring
ESL
204-12/24V
Power
Supervision
Relay

Power
First
detector

NO COM

Last
detector

NO COM

NC
COM

Listed alarm control

NO

Model
541NB
541NBXT

Model
541NCSRXT
541NCSRH
541NCRXT

Initiating
circuit
EOL device

Note: The 500N Series four-wire detectors are not CleanMe compatible.
Figure 8: 500N series four-wire E model wiring

Power
NO COM

NO COM

First
detector

Last
detector
NO

Listed alarm control

COM

Model
541NB
541NBXT

NC

Model
541NCSXTE
541NCXTE

Initiating
circuit
EOL device

Note: The 500N Series four-wire detectors are not CleanMe compatible.

4/8

P/N 1036525-EN • REV F

Figure 9: Testing the detector

Understanding the LED
The LED on the detector indicates the status of the detector as
follows.
•

Flashing every 9 seconds = Normal operation

•

On = Detects smoke, sending an alarm

•

Off or flashing once every 1.5 seconds = Trouble or
maintenance is required. Test the detector. See
“Sensitivity testing” below.

Smoke testing
Smoke detectors should be tested in place annually using one
of the following methods:

Cleaning the detector

•

Use Smoke! In A Can (P/N SM-200), a canned aerosol
simulated smoke, and follow the directions on the can.

Clean the detector cover with a dry or damp (water) cloth as
needed to keep it free from dust and dirt.

•

Hold a smoldering punk or cotton wick close to the unit
and gently direct the smoke into the detector for 20
seconds or until an alarm is indicated.

When necessary, clean the detector interior and replace the
optical chamber as follows:
1.

Disconnect the alarm notification appliances, service
release devices, and extinguishing systems.

2.

Slide a flat-blade screwdriver into the slot on the detector
cap and gently push the handle down to pry the cap up
and off. See Figure 10.

3.

Press in on the sides of the optical chamber and pull it up
and away from the detector and discard. See Figure 11.

4.

Use a vacuum to remove dust and dirt from the optical
chamber base.

5.

Line the new optical chamber up with the optical chamber
base and snap it down into place.

6.

Replace the detector cap as follows:

Be sure to extinguish the smoke source after testing!
The detector LED should stay on and an alarm should be
indicated at the control panel. Use the system reset switch to
reset the detector.

Sensitivity testing
The detector provides a sensitivity test that allows you to check
the detector sensitivity using a test magnet and the LED
indicator on the detector as follows:
1.

2.

Hold the test magnet up to the raised TEST letters on the
top of the detector for 2 seconds. See Figure 9. Once the
test starts, the alarm LED flashes one to nine times.

a. Line the tabs on the cap with the slots on the detector.

Count the number of times the LED flashes and use the
following table to determine the status of the detector
sensitivity and what action to take, if any.

b. Insert the cap into the smoke detector and turn
clockwise approximately 15 degrees. It should snap firmly
into place.

Flashes

Indication

Action

7.

0 to 1

Unserviceable
hardware fault

Reset and rerun the sensitivity test. If
the error persists, replace the unit.

Test the detector sensitivity (See “Sensitivity testing”
above).

8.

Unit is becoming
insensitive

Clean and reset the unit. Rerun the
sensitivity test. If the error persists,
replace the unit.

Reconnect all alarm notification appliances, service
release devices and extinguishing systems.

2 to 3

4 to 7

Unit is within normal N/A
sensitivity range

8 to 9

Unit is becoming
too sensitive

Note: The control panel alarm and all auxiliary functions
should be verified for a complete test of the system.
Figure 10: Removing the detector cap

Verify that the optical chamber is
snapped down securely. Clean the
unit.

After the test:
•

If the sensitivity is within limits and all other tests pass, the
detector goes into alarm and must be reset from the
control panel.

•

If the sensitivity is not within limits or an unserviceable
hardware fault has been detected, the detector LED
flashes every 1.5 seconds until the detector is serviced.

P/N 1036525-EN • REV F

5/8

Figure 11: Removing the optical chamber

In case of fire
In the event of a fire, do the following:
•

Leave immediately. Don’t stop to pack or search for
valuables.

•

In heavy smoke, hold your breath and stay low, crawl if
necessary. The clearest air is usually near the floor.

•

If you have to go through a closed door, carefully feel the
door and doorknob to see if undue heat is present. If they
seem cool, brace your foot against the bottom of the door
with your hip against the door and one hand against the
top edge. Open it slightly. If you feel a rush of hot air, slam
the door quickly and latch it. Unvented fire tends to build
up considerable pressure. Be sure all members of the
household realize and understand this danger.

•

Use your neighbor’s phone or a street fire alarm box to call
the fire department. The job of extinguishing the fire
should be left to the professionals.

(1)

(2)

(3)

(1)
(2)
(3)

Optical chamber base
Optical chamber
Detector cap

Be prepared
Practice the following steps to prepare you and your family in
the event of a fire:

Maintenance

•

These smoke detectors are designed for easy field service and
maintenance. When installed and used properly, they require
minimal maintenance.

Perform fire drills regularly. Use them to assure
recognition of an alarm signal.

•

Draw a floor plan and show two exits from each room. It is
important that children be instructed carefully, because
they tend to hide in times of crisis.

•

Establish one meeting place outside the home. Insist that
everyone meet there during an alarm. This will eliminate
the tragedy of someone reentering the house for a missing
member who is actually safe.

•

If you have children or physically challenged people
residing in your household, use window decals to help
emergency personnel identify the sleeping quarters of
these individuals.

The smoke detector should be tested monthly. See “Sensitivity
testing” and “Smoke testing” on page 5.

Fire prevention and escape
The purpose of an early warning smoke detector is to detect
the presence of fire in its early stages and sound an alarm
giving the occupants time to exit the premises safely.
Avoid fire hazards
No detection device can protect life in all situations. Therefore,
safeguards should be taken to avoid potentially dangerous
situations as follows:
•

Do not smoke in bed.

•

Do not leave children home alone.

•

Never clean with flammable liquids such as gasoline.

•

Properly store materials. Use general good housekeeping
techniques to keep your home neat and tidy. A cluttered
basement, attic, or other storage area invites fire.

•

Use combustible materials and electrical appliances
carefully and only for their intended uses.

•

Do not overload electrical outlets.

•

Do not store explosive and/or fast burning materials in
your home.

•

6/8

Even after proper precautions have been taken, fires can
start. Be prepared.

Limitations of smoke detectors
WARNING: Risk of personal injury or death. Smoke detectors
cannot provide warnings for fires resulting from explosions,
smoking in bed or other furniture, ignition of flammable liquids,
vapors, and gases, or children playing with matches or lighters.
Failure to properly install, test, and maintain a smoke detector
system may cause it to fail resulting in loss of life or property.
Smoke detectors are very reliable, but may not work under all
conditions. No fire alarm provides total protection of life or
property. Smoke detectors are not a substitute for life
insurance.
Smoke detectors require a source of power to work. This
smoke detector will not operate and the alarm will not sound if
the detector is not installed properly.
Smoke detectors may not be heard. A sound sleeper or
someone who has taken drugs or alcohol may not awaken if
the detector is installed outside a bedroom. Closed or partially
closed doors and distance can block sound. This detector is
not designed for the hearing impaired.

P/N 1036525-EN • REV F

Smoke detectors may not always activate and provide
warning early enough. Smoke detectors only activate when
enough smoke reaches the detector. If a fire starts in a
chimney, wall, roof, on the other side of closed doors, or on a
different level of the property, enough smoke may not reach
the detector for it to alarm.

Model numbers
Figure 12: Model number codes

Features
Style

Smoke detectors are a significant help in reducing loss, injury,
and even death. However, no matter how good a detection
device is, nothing works perfectly under every circumstance
and we must warn you that you cannot expect a smoke
detector to ensure that you will never suffer any damage or
injury.

Wiring
Features

Current studies have shown smoke detectors may not awaken
all sleeping individuals. It is the responsibility of individuals in
the household that are capable of assisting others to provide
assistance to those who may not be awakened by the alarm
sound, or to those who may be incapable of safely evacuating
the area unassisted.

B

6.5 to 20 VDC operation for Two-wire devices

B

6.5 to 33 VDC operation for Four-wire devices

C

8.5 to 33 VDC operation

E

End-of-line relay

H

Isolated rate-of-rise and fixed temp. sensors

R

Auxiliary relay

S

85 dBA sounder

XT Multiple criteria algorithm, rate-of-rise and fixed temp. sensors

Style
N

New style

Wiring
2

Two-wire

4

Four-wire

Product ordering
Model

Description

Alarm
current (mA)

Reverse
polarity (mA)

521NB

Two-wire, photoelectric, 6.5 to 20 VDC, S09A

20

–

521NBXT

Two-wire, photoelectric, 6.5 to 20 VDC, fixed temperature and rate-of-rise heat, S09A

20

–

521NC

Two-wire, photoelectric, 8.5 to 33 VDC, S10A

20

–

521NCXT

Two-wire, photoelectric, 8.5 to 33 VDC, fixed temperature and rate-of-rise heat, S10A

20

–

521NCRXT

Two-wire, photoelectric, 8.5 to 33 VDC, fixed temperature and rate-of-rise heat, aux. relay, S11A

25

–

521NCSXT

Two-wire, photoelectric, 8.5 to 33 VDC, fixed temperature and rate-of-rise heat, temporal-three
sounder, S10A

30

13

541NB

Four-wire, photoelectric, 6.5 to 33 VDC

20

–

541NBXT

Four-wire, photoelectric, 6.5 to 33 VDC, fixed temperature and rate-of-rise heat

20

–

541NCSRXT

Four-wire, photoelectric, 8.5 to 33 VDC, fixed temperature and rate-of-rise heat, aux. relay,
temporal-three sounder

35

13

541NCSXTE

Four-wire, photoelectric, 8.5 to 33 VDC, fixed temperature and rate-of-rise heat, built-in end-ofline relay, temporal-three sounder

45

28

541NCSRH

Four-wire, photoelectric, 8.5 to 33 VDC, isolated fixed temperature and rate-of-rise heat, aux.
relay, temporal-three sounder, nonlatching LED with automatic reset

35

13

541NCRXT

Four-wire, photoelectric, 8.5 to 33 VDC, fixed temperature and rate-of-rise heat, aux. relay

25

–

541NCXTE

Four-wire, photoelectric, 8.5 to 33 VDC, fixed temperature and rate-of-rise heat, built-in end-ofline relay

25

–

541NCSXT

Four-wire, photoelectric, 8.5 to 33 VDC, fixed temperature and rate-of-rise heat, temporal-three
sounder

30

13

P/N 1036525-EN • REV F

7/8

Specifications
Voltage

6.5 to 20 VDC for S09A
8.5 to 33 VDC for S10A, S11A

Maximum ripple
(6/12/24 V)

10% (Vp-p)

Typical average
standby current

70 µA

Typical alarm current
(6/12/24 V)

Up to 60 mA maximum if not limited by
control panel

Aux. relay contacts

1 A at 30 VDC; Form C

Alarm contacts

500 mA at 36 VDC (resistive)

Photoelectric
sensitivity

2.0% +1.08 −1.02

Operating temperature

32 to 100°F (0 to 37°C)

Operating humidity

0 to 95% noncondensing

Field wiring size

12 to 24 AWG (16 to 22 AWG recommended)

Electrical boxes

Fits standard single-gang and 3-1/2 in. and
4 in. round ceiling electrical boxes

Heat detector
Rate-of-rise

15°F/min and >105°F (8.3°C/min and
>40.6°C)
135°F (57.2°C)

Fixed threshold
UL two-wire
compatibility identifiers

S09A, S10A, S11A

Drift compensation
adjustment

1.0%/ft. max.

Detector head
dimensions

5.5 in. (14.0 cm) diameter; 2 in. (5.0 cm)
deep

Mounting dimensions

5.25 in. (13.3 cm) diameter; 0.3 in. (0.8 cm)
deep

Reset time

1 second minimum

Regulatory information
Listings

CSFM
UL 268 and CAN/ULC-S531

Contact information
For contact information, see www.interlogix.com.

8/8

P/N 1036525-EN • REV F



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Author                          : c4201
Create Date                     : 2017:08:02 10:50:50-04:00
Modify Date                     : 2017:08:03 14:23:36-07:00
XMP Toolkit                     : Adobe XMP Core 5.6-c015 84.159810, 2016/09/10-02:41:30
Creator Tool                    : PScript5.dll Version 5.2.2
Metadata Date                   : 2017:08:03 14:23:36-07:00
Producer                        : Acrobat Distiller 11.0 (Windows)
Format                          : application/pdf
Title                           : Microsoft Word - 1036525-EN Rev F ESL 500N Series Smoke Detector Installation Sheet.docx
Creator                         : c4201
Document ID                     : uuid:1bcb669b-95db-4641-bb12-ac70a9c2ea5c
Instance ID                     : uuid:5694d6ca-3d28-4ce7-8d8e-5c155610dc4b
Page Count                      : 8
EXIF Metadata provided by EXIF.tools

Navigation menu