ESL2500 Manual 2711E ESL 2501 Fire Alarm Control Panel Install & Operations 1997
2015-08-27
: InterLogix Esl 2501 Fire Alarm Control Panel Install & Operations Manual 1997 ESL 2501 Fire Alarm Control Panel_Install & Operations Manual_1997 library
Open the PDF directly: View PDF .
Page Count: 84
Download | |
Open PDF In Browser | View PDF |
E S L I N S T A L L A T I O N A N D O P E R A T I O N S M A N U A L ESL 2501 Fire Alarm Control Panel ESL a pArPRODUCT oduct o f SENTR s e n t OL rol OF Sentrol 1-800-547-2556 1 2 Sentrol 1-800-547-2556 TABLE OF CONTENTS 1.0 SYSTEM OVERVIEW ......................................................................................................... 6 1.1 Features .................................................................................................................................................................. 6 1.2 Panel Equipment ..................................................................................................................................................... 7 1.3 Panel Listings ........................................................................................................................................................... 7 1.4 Customized Panels ................................................................................................................................................... 8 2.0 SYSTEM CONFIGURATIONS .............................................................................................. 8 2.1 2501 (FACP) ............................................................................................................................................................ 8 2.2 Power Boost ............................................................................................................................................................ 9 2.3 System Networking ................................................................................................................................................. 9 2.4 Door Holders ........................................................................................................................................................ 10 2.5 Low Battery Annunciation ..................................................................................................................................... 10 2.6 Hibernation Mode ................................................................................................................................................. 10 2.7 Drill Test ................................................................................................................................................................ 10 2.8 Trouble Resound Time ........................................................................................................................................... 10 2.9 Comm Test ............................................................................................................................................................ 10 2.10 Dual LRM Operation ............................................................................................................................................ 10 2.11 Ground Fault Indication Operation ...................................................................................................................... 11 3.0 GENERAL SYSTEM INSTALLATION GUIDELINES ............................................................... 18 3.1 General Installation Procedure ............................................................................................................................... 18 3.2 BMB Operation Verification .................................................................................................................................... 20 3.3 ZEM Address Selection ........................................................................................................................................... 21 3.4 Zone Function Jumpers ......................................................................................................................................... 22 3.5 Add-On Modules for Expanded Capabilities ............................................................................................................ 22 3.6 2500 Keypad Address Settings ............................................................................................................................... 23 3.7 2500-DAC ............................................................................................................................................................. 23 3.8 2500-RA and 2500-RADVR ..................................................................................................................................... 23 3.9 2500-LEM/LRM ...................................................................................................................................................... 24 3.10 Installing the ZEM, BMB, and DAC ....................................................................................................................... 29 3.11 Installing the BELL, ZRM and LEM/LRM ................................................................................................................. 30 3.12 Installing the Zone Description Card .................................................................................................................... 31 4.0 FIELD WIRING ............................................................................................................... 32 4.1 Detail Installation Guide ......................................................................................................................................... 34 4.2 Field Wiring Checkout Procedures .......................................................................................................................... 37 4.3 Alarm Initiating Devices .......................................................................................................................................... 37 4.3.1 Two-Wire Smoke Detectors .......................................................................................................................... 37 4.3.2 Four-Wire Smoke Detectors .......................................................................................................................... 37 4.3.3 Sprinkler System Waterflow and Supervisory Devices .................................................................................... 38 4.4 Alarm Notification Appliances ................................................................................................................................. 38 4.5 Zone Expansion Module (ZEM) Connection ........................................................................................................... 38 4.5.1 ESL 2502A-ZEM ........................................................................................................................................... 38 4.5.2 ESL 2502-ZEM and ESL 2504-ZEM ............................................................................................................... 38 4.6 Supplementary Contacts Connection ..................................................................................................................... 39 4.6.1 Supplementary Alarm Contacts .................................................................................................................... 39 4.6.2 Supplementary Trouble Contacts .................................................................................................................. 39 4.6.3 Zone Relay Module (ZRM) ............................................................................................................................ 39 4.7 Connection to Supervising Station Fire Alarm Systems ............................................................................................ 39 4.7.1 Connecting the 2500-DAC .......................................................................................................................... 39 5.0 PROGRAMMING ............................................................................................................. 41 5.1 Introduction .......................................................................................................................................................... 41 5.1.1 Programming Indicators .............................................................................................................................. 41 5.1.2 Programming Buttons ................................................................................................................................. 41 Sentrol 1-800-547-2556 3 5.2 System Programming ............................................................................................................................................. 41 5.3 Time & Date Programming .................................................................................................................................... 42 5.4 Battery Saver Programming ................................................................................................................................... 43 5.5 CleanMe® Mode Programming .............................................................................................................................. 43 5.6 BMB Programming Matrix ...................................................................................................................................... 44 5.6.1 DAC Programming Matrix ............................................................................................................................. 55 5.7 Function Map Description...................................................................................................................................... 57 5.7.1 ZRM Override ............................................................................................................................................... 57 6.0 INITIAL ACCEPTANCE TESTING ....................................................................................... 58 6.1 Alarm Zone Testing ................................................................................................................................................ 58 6.2 Notification Appliance Circuit Testing ...................................................................................................................... 61 6.3 Ground Fault Test .................................................................................................................................................. 62 6.4 System Testing Using Test Modes ............................................................................................................................ 62 6.5 Remote Keypad Check-Out .................................................................................................................................... 63 6.6 BMP Lamp Test ...................................................................................................................................................... 63 6.7 Digital Alarm Communicator Check-Out ................................................................................................................. 63 6.8 LEM/LRM Check-Out .............................................................................................................................................. 63 7.0 INSPECTION AND TESTING ............................................................................................ 64 7.1 Maintenance ......................................................................................................................................................... 64 7.1.1 Batteries ....................................................................................................................................................... 64 8.0 PRECAUTIONS AND WARNINGS ..................................................................................... 64 9.0 TROUBLESHOOTING ...................................................................................................... 64 10.0 HOUSEHOLD FIRE WARNING SYSTEMS ........................................................................ 66 10.1 Installation ........................................................................................................................................................... 66 10.2 Detector Location ................................................................................................................................................ 66 10.3 Notification Appliance Location ............................................................................................................................ 66 10.4 Escape Plan ......................................................................................................................................................... 66 10.5 Household Fire Warning System Maintenance ..................................................................................................... 66 11.0 PANEL SPECIFICATIONS ............................................................................................... 68 11.1 General .............................................................................................................................................................. 68 11.2 2500-BMB - Basic Master Board ......................................................................................................................... 68 11.3 2500-ZEM - Zone Expander Module ................................................................................................................. 68 11.4 2500-ZRM - Zone Relay Module ........................................................................................................................ 68 11.5 2500-BELL - Bell Expander Module .................................................................................................................... 68 11.6 Power Booster .................................................................................................................................................... 68 11.7 2500 LEM/LRM .................................................................................................................................................... 68 11.8 2500-RA .............................................................................................................................................................. 69 11.9 2500-RADVR ....................................................................................................................................................... 69 11.10 2500-DAC ......................................................................................................................................................... 69 APPENDIX A COMPATIBLE EQUIPMENT ............................................................................... 70 APPENDIX B BATTERY CALCULATION WORKSHEET ............................................................. 73 APPENDIX C 2501 (FACP) OPERATING INSTRUCTIONS .......................................................... 79 This manual does not cover, nor does it purport to cover, every detail that might pertain to the ESL 2501 Fire Alarm Control Panel; nor does it cover, or purport to cover, every possible contingency that might be encountered in connection with the installation, utilization, operation or maintenance of the ESL 2501 Fire Alarm Control Panel. This manual is intended only to advise the user of the intended use of the unit and the intended means by which it can be used to implement a fire alarm system design for commercial, institutional and residential applications. Consult Sentrol Technical Services at 1-800-648-7424 regarding any condition, question or concern not explicitly covered in this manual. 4 Sentrol 1-800-547-2556 TABLE OF CHARTS, GRAPHICS AND SCHEMATICS Figure 1.3 Signaling System Table ................................................................................................................................. 7 Figure 1.4 Custom Panel Building Table ........................................................................................................................ 8 Figure 2.2 Power Boost Installation Diagram ............................................................................................................... 12 Figure 2.3a Slave Panel Installation Diagram ............................................................................................................... 13 Figure 2.3b Slave Panel Installation with a ZEM Diagram ............................................................................................. 14 Figure 2.3c Slave Panel with Power Boost Installation Diagram .................................................................................... 15 Figure 2.4 Door Holder Installation Diagram ............................................................................................................... 16 Figure 2.10 Dual LRM Installation Diagram ................................................................................................................... 17 Figure 3.0 2501 (FACP) Interconnect Diagram ............................................................................................................ 25 Figure 3.1a Panel Standoff with Locking Clip ............................................................................................................... 19 Figure 3.1b Internal Panel Configuration with DAC ..................................................................................................... 26 Figure 3.1c Internal Panel Configuration with LEM/LRM .............................................................................................. 27 Figure 3.2a BMB Daughter Board Layout .................................................................................................................... 20 Figure 3.2b BMB Daughter Board LED Table ............................................................................................................... 20 Figure 3.2c Additional System Troubles ........................................................................................................................ 21 Figure 3.2d System Troubles Indicated by the ESL 2500 Keypad .................................................................................. 21 Figure 3.3 ZEM Address Selection Chart ...................................................................................................................... 21 Figure 3.4 Function Jumper Diagram ......................................................................................................................... 28 Figure 3.5a Peripheral Device Guidelines Table ........................................................................................................... 22 Figure 3.5b Connecting BMB to Keypad ..................................................................................................................... 22 Figure 3.5c Connecting BMB to RA/RADVR ................................................................................................................. 22 Figure 3.5d Connecting BMB to LEM/LRM ................................................................................................................... 23 Figure 3.5e Connecting BMB to ZXPTR ....................................................................................................................... 23 Figure 3.6 2500 Keypad Address Switch Settings ......................................................................................................... 23 Figure 3.8 2500-RA/RADVR Address Switch Settings .................................................................................................... 23 Figure 3.10 ZEM, BMB, and DAC Installation Diagram ................................................................................................. 29 Figure 3.11 BELL, ZRM and LEM/LRM Installation Diagram .......................................................................................... 30 Figure 3.12 Zone Description Card Diagram ............................................................................................................... 31 Figure 4.0a Class B System Installation Diagram without ZEM ...................................................................................... 32 Figure 4.0b Class B System Installation Diagram with ZEM ........................................................................................... 33 Figure 4.1a Power-Limited Routing with DAC .............................................................................................................. 34 Figure 4.1b Power-Limited Routing with LEM/LRM ...................................................................................................... 35 Figure 4.1c Wire Resistance Table ................................................................................................................................ 36 Figure 4.1d Alarm Notification Appliance Circuit (NAC) Wire Size Table ......................................................................... 36 Figure 4.1e Unified Earth Ground ............................................................................................................................... 37 Figure 4.7.1 2500-DAC Installation Diagram ............................................................................................................... 40 Figure 5.1a BMB Daughter Board Layout .................................................................................................................... 41 Figure 5.1b On-Board Programming Interface ............................................................................................................. 41 Figure 5.3 Time & Date Programming Example ........................................................................................................... 42 Figure 5.6 LED Location Diagram for Programming Location and Programmed Value ................................................. 43 Figure 9.0 Troubleshooting Guide ............................................................................................................................... 65 Figure 10.0a Detector Location - 3 Sleeping Areas ....................................................................................................... 67 Figure 10.0b Detector Location - Per Floor .................................................................................................................. 67 Figure 10.0c Detector Location - Ceiling/Wall Mount .................................................................................................. 67 Figure A.1 UL Listed Non-Coded Manual Alarm Stations and Heat Detectors ................................................................ 70 Figure A.2 UL Listed Four-Wire Smoke Detectors .......................................................................................................... 70 Figure A.3 Two-Wire Smoke Detector Compatibility ..................................................................................................... 71 Figure A.4 2501 (FACP) Compatible Indicating Devices................................................................................................ 72 Figure A.5 Ordering Information Table ........................................................................................................................ 72 Figure B.1 Battery Calculation Worksheet .................................................................................................................... 73 Sentrol 1-800-547-2556 5 1.0 1.1 FEATURES SYSTEM OVERVIEW The ESL Model 2501 Fire Alarm Control Panel (FACP) is designed to provide a reliable and cost-effective means of implementing a fire alarm system compliant with the requirements of the National Fire Alarm Code for protected premises fire alarm systems in commercial, industrial, residential and institutional applications. The ESL Model 2501 Fire Alarm Control Panel is a modular system. In its simplest configuration, called the 2501 FACP, it consists of an enclosure, power supply and Basic Master Board (BMB). The 2501 provides all of the required basic system functions for alarm, fault (trouble) and supervisory monitoring, together with one initiating zone circuit and two notification appliance circuits. Its 7 amp, 24 VDC, system power supply provides ample current for most applications; with 1.5 amps available from each of the two integral notification appliance circuits, 1.0 amp available from the auxiliary power supply terminals (24 VDC, 0.5 amps 12 VDC in battery saver mode) and the remaining 3 amps, available as two additional notification appliance circuits, when a 2500 BELL Card is added to the system. The unique modular design makes it easy to add features when they are needed. These include a remote interface keypad, remote annunciator, digital communicator, LEM/ LRM, extra control relays, additional notification appliance circuits and additional initiating device circuits. Up to 24 Class B, Style B initiating device circuits can be added to the 2501 basic unit if needed. Furthermore, the ESL 2501 Fire Alarm Control Panel is equipped with a Remote Keypad Port. This allows the use of an optional ESL 2500 Keypad for enhanced user interface. • Expandable Modular Design: up to 25 Class B Zones • Patented Direct On-line Power Supply provides regulated, filtered 24VDC at 7 amps output. • Single zone panel can be used as 3 amp (NAC) power booster with 1 amp auxiliary power available for 24 V panels or 0.5 amp for 12 V panels. • An additional bell card 2500-BELL can be used to provide two additional notification appliance circuits (1.5 amps each for 6.0 amps total and 1 amp auxiliary power). • Panel network capability: Each zone input can connect to an independent panel. • Approved for Sprinkler Supervisory and Waterflow Alarm. • Functions are easily programmable through pushbutton switches on BMB or optional keypad. • Battery saver mode allows smaller, less expensive batteries to meet 24 or 60 hour standby requirements. • Optional Plug-in Two-line Dialer for Supervising Station reporting. • Automatically senses and reports when ESL 521 series smoke detectors need cleaning over standard 2-wire zones. • Built-in walk test and alarm verification by zone. • All output circuits power-limited, except battery and relay output connections. • Programmable notification appliance circuit output with a variety of cadences; Temporal 3, March Time, California March Time, Steady, Non-Silenceable Steady and Latching Non-Silenceable Steady. One enclosure is used for most system configurations. One cabinet can hold up to 3 expander modules, as well as the necessary standby batteries for either 24 or 60 hour operation. The three (3) expander modules provide up to twelve (12) Class B zones plus one (1) from the BMB for a total panel configuration of thirteen (13) Class B zones. To accommodate system configurations beyond 13 zones, a second enclosure can be installed. For larger installations, the panels can be networked using non-latching zones or the power booster option to provide maximum system flexibility. The versatility of the ESL 2501 Fire Alarm Control Panel is further enhanced by its compatibility with the complete line of ESL smoke detectors, manual fire alarm stations and notification appliances. This allows the assembly of a complete fire alarm system from components produced by a single manufacturer with designed-in compatibility and reliability. See Appendix A for the list of UL Listed compatible devices. 6 Sentrol 1-800-547-2556 1.2 PANEL EQUIPMENT 1.3 PANEL LISTINGS The flexibility of the ESL 2501 Fire Alarm Control Panel is derived from its modular design and the array of function modules available for integration into the 2501 basic unit. These modules are listed below. The ESL 2501 Fire Alarm Control Panel is equipped with a “Battery Saving Switching Mechanism” U.S. Patent No.: 5,804,891. The 2501 (FACP) functions in accordance with the National Fire Alarm Code (NFPA 72) and the California State Fire Marshal (7165-1459:111) for the following: Model Number 2501 2502-ZEM Description Type of Signaling System Single Zone Panel, 7 Amp Power Supply Local (L) 2500-BELL 2 Additional Bell Circuits, 3 Amp Expander 2500-KPD LCD Keypad 2500-ZRM2 2-Zone, Relay Module 2500-ZRM4 4-Zone, Relay Module Printer Interface Module System Housing with Nameplates 2500-PS 7 Amp Power Supply, for replacement 2500-RA 2500-RADVR 2500-LEM/LRM Proprietary (P) A, M, WF, SS Protected Premises Unit NC, California March Time, ANSI Temporal 3 Household A, M, WF, and SS NC, California March Time, ANSI Temporal 3, and Digital Alarm Communicator (DAC) Auxiliary A, M, WF NC Single Zone Panel, replacement circuit board 2500-SH 2500-DAC A, M, WF, and SS NC, California March Time, ANSI Temporal 3 Central/Remote Station A, M, WF, and SS Digital Alarm (CS/RS) Protected Communicator (DAC) Premises unit 4-Zone, Class B, Expander 2500-BMB Type of Signal 2-Zone, Class B, Expander 2504-ZEM ZXPTR Type of Alarm Service Full Featured Dual Line Dialer A = Automatic Detection (smoke detectors, heat detectors, etc.) DAC = Digital Alarm Communicator M = Manual Fire Alarm Box (Pull Stations) NC = Non-Coded SS = Sprinkler Supervisory WF = Water Flow Alarm Remote Annunciator Remote Annunciator with Outputs Configurable Local Energy or Line Reversal Module Figure 1.3 Signaling System Table NOTE: For standby current calculations, see Appendix B Battery Calculation Worksheet. Sentrol 1-800-547-2556 7 2.0 1.4 CUSTOMIZED PANELS Your 2501 (FACP) may be custom built according to the number of zones desired. The following chart shows what equipment is needed for the desired number of zones. Class B Panel Zones No. Desired *2501 1 1 3 1 5 1 7 1 9 1 11 1 13 1 15 1 17 1 19 1 21 1 23 1 25 1 Over 13 2 Zone 4 Zone zones, add Expansion Expansion add’t panel Boards Boards housing (2502-ZEM) (2504-ZEM) p/n 2500-SH 1 1 2 1 2 3 1 1 1 3 1 4 1 4 1 5 1 5 1 6 1 Figure 1.4 Custom Panel Building Table Additional enhancements may be added to the panel of your choice from the following: Adds two more notification appliance circuits and allows use of the full 7 amps of 24 VDC power available with the 2501 (FACP). • 2500-ZRM2 Adds SPDT relays (2) to 2502-ZEM • 2500-ZRM4 Adds SPDT relays (4) to 2504-ZEM • 2500-KPD Adds an LCD keypad to your 2501 (FACP) • ZXPTR Adds a printer interface module • 2500-RA Adds remote visible and audible annunciation, system status and zone status (4 RA’s per system are allowed) • 2500-RADVR Same as 2500-RA, except in addition, there is one active low output per zone intended to indicate alarm condition. These lines are not supervised. • 2500-LEM/LRM Local Energy Module for connection to a listed master box. Can also be configured as a Line Reversal Module for connection to appropriate devices. • 2500-DAC Dual Line Dialer with complete reporting capability for all 25 zones. 8 2.1 2501 (FACP) The basic version of the 2501 Fire Alarm Control Panel can be expanded to accommodate up to 25 Class B, Style B initiating device circuits. Figure 1.4 presents in tabular form the number of Expansion Boards of each type needed to attain a given number of initiating device circuits. 1 1 * 2501 can also be used as a 3.0 amp (NAC) power booster (6.0 amps with 2500-BELL) • 2500-BELL SYSTEM CONFIGURATIONS The 2501 (FACP) can be enhanced by adding two additional notification appliance circuits (NAC) with the 2500-BELL expansion card. This card adds two additional bell circuits and allows use of the full 7 amps of 24 VDC power available from the 2501 (FACP) power supply (6 amps are used for the notification appliance circuits (NAC), up to 1 amp is used for auxiliary power). Further enhancement of the 2501 (FACP) is provided by the (2500-ZRM2) or (2500-ZRM4) zone follower relay cards. These add-on cards provide SPDT relays rated 30 VDC at 2 amps resistive in a zone follower configuration. These relay contacts are “dry” and, hence, unsupervised. They should only be used in conjunction with a supervised circuit or to control non-critical or “fail-safe” functions. A printed copy of the events that occur in the 2501 (FACP) can be obtained by the addition of the ZXPTR printer interface module. The BMB and DAC function maps can be printed when this module is installed. This module allows a standard printer with a Centronics interface to be connected to the 2501 (FACP). Events will be printed as they occur or the entire event history can be printed at the user’s discretion. The 2500-KPD LCD keypad may be added to the 2501 (FACP) to program all the system functions and allow for on premises remote panel manipulation. Up to 3 supervised keypads and 1 unsupervised keypad may be added. The 2500-KPD LCD keypad gives you access to additional functionality of the 2501 (FACP). The keypad also allows access to the event history and programming and testing of other system peripherals. Access to all critical items are restricted by the use of passcodes to prevent access by non-authorized users. For localities requiring remote annunciators, the 2500-RA and 2500-RADVR can be added. Up to four devices can be added. Each device is configurable for zones 1-13 or zones 14-25 and all devices are supervised. The device indicates the system status and the zone status on a zone by zone basis. In addition to these capabilities, the RADVR has low current (sinks up to 40mA) active low zone follower outputs. These outputs are intended to Sentrol 1-800-547-2556 interface with MPI-206 Accessory Relay Boards or similarly isolated devices for driving graphic displays as desired or where mandated by local authorities. For localities that utilize Listed Master Boxes in a municipal system, the 2500-LEM/LRM can be installed. This device provides the required connectivity to the Listed Master Box. The connection is supervised and will automatically restore when the master box is reset. In addition, the module can be configured as a Line Reversal Module for applications that require this functionality. The connections are also supervised and auto-restore when the device or connections are returned to a normal state. Another enhancement to the 2501 FACP is the 2500DAC, Digital Alarm Communicator. This is a full featured DAC that reports all system events in the following selectable formats: Pulse - 20 baud extended, Pulse - 20 baud non-extended, Pulse - 40 baud extended, SIA, Contact ID, and Pager. The DAC is programmable with a 2500-KPD. Front panel programming is not supported. In addition to these report formats, the DAC accepts two supervised phone lines. For remote programming capabilities, contact Sentrol Technical Services at 1-800800-2027. 2.2 POWER BOOST With the adoption of the Americans with Disabilities Act (ADA) it has become necessary to provide equivalent fire alarm notification for those with hearing impairments. This requirement is usually addressed with visible notification appliances (strobe lights). Frequently, existing systems cannot provide sufficient current to operate all of the visible notification appliances necessary to comply with the ADA and a “power booster” is needed to provide additional notification appliance power. The base model 2501 can be connected to be an add-on power booster for any UL Listed fire alarm control panel including the 2501 (FACP). Power Booster terminals are a feature of the panel. The panel will act as a 3 amp (NAC) power booster with two notification appliance circuits. With the addition of the 2500-BELL to the base model, two more notification appliance circuits are added providing a 6 amp (NAC) power booster with four notification appliance circuits. See Figure 2.2 for Power Booster wiring. In the power booster configuration, an alarm on the master fire alarm control panel will activate an alarm on the power booster fire alarm control panel. Interconnect wiring is supervised and will generate a system trouble on the master panel if the interconnect wiring is compromised. Any system trouble on the power boost panel will generate a bell and system trouble on the master panel. The interconnect loop will generate a bell and system trouble at the Master panel if the wiring should become compromised. 2.3 SYSTEM NETWORKING If the facility to be protected requires more than 25 initiating device circuits in order to fulfill the owner/ operator’s fire protection objectives, ESL 2501 control panels can be connected together in what is commonly referred to as a “master-slave” configuration. One unit is designated the “master” and the other acts as the “slave”. One initiating device circuit on the “master” unit is programmed as a non-latching initiating device circuit (See Section 5) and the wiring for this circuit is connected to the general alarm-operated and troubleoperated contacts of the “slave” unit BMB. This wiring connection is illustrated in Figures 2.3a and 2.3b. Any initiating device circuit of the “master” unit can be used to receive signals from the “slave” unit in this manner. When a detector initiates an alarm on an initiating device circuit of the “slave” unit, its alarm-operated contacts transfer and, hence, appear as a shorting contact initiating device alarm initiation at the “master” unit. The interconnection between the master and slave units is supervised and the End Of Line (EOL) resistor (provided) MUST BE INSTALLED, as shown. Refer to Figure 2.3a for installation wiring as a Master-Slave panel and Figure 2.3b for installation wiring with a ZEM. The Master-Slave configuration may also be implemented with a power boost capability. This configuration is used in applications where a local networked system is desired. Refer to Figure 2.3c for the installation wiring. After the installation wiring is accomplished, the panel must be programmed as indicated on the wiring installation diagram (see Section 5). The Master-Slave configuration will now operate in the following manner. All zone inputs on the Master are dedicated for Slave panel operation. Program all bell outputs as required to meet your system design requirements. In the Zone Bell Definition Table for each Slave panel, program all Bells associated to Zone 1 only. In this configuration, an alarm condition on a Slave unit will communicate through its Alarm and Trouble dry contacts that the Slave is in alarm. The Master will signal through the Bell outputs that the system is in alarm and all system bell outputs (Slaves and Master) will activate. The only method to silence the system bells is to activate the Alarm Silence on the Master unit. This will result in the bells silencing on all panels. The Master will indicate on board its control board that the bells are silenced by illuminating the bell silenced LED. A Slave panel cannot be locally silenced. The previous description covers all of the necessary wiring for a Master panel to supervise and report the conditions of up to 25 other Slave panels, allowing for very large system coverage and expansion when needed. Sentrol 1-800-547-2556 9 detect any alarms or other troubles and the notification appliances will not sound. 2.4 DOOR HOLDERS The 2501 (FACP) is suitable for door holder applications. See Figure 2.4 for Door Holder Installation. Battery saver mode is not allowed when using door holders. They are rated for 24 VDC operation only with the 2501 (FACP). The 2501 should be programmed (see Section 5) so that the common trouble contacts transfer on loss of AC only. This will release the door holders on loss of AC. The door holders will also release on alarm. 2.5 LOW BATTERY ANNUNCIATION The 2501 (FACP) will automatically perform a battery check 15 seconds after power up. If the voltage of either battery is below 11.0 VDC, the 2501 (FACP) will illuminate the System Trouble and the No/Low Battery Trouble LEDs and sound the trouble sounder. When the voltage of either battery drops below 10.5 VDC, the 2501 (FACP) will log the condition to the event log. The 2501 (FACP) will not record a restoral unless both battery voltages return to a value above 11.0 VDC. After the initial power up battery test, the 2501 (FACP) will perform the same battery test every hour. If the batteries are disconnected after the power up battery test, the 2501 (FACP) will illuminate the System Trouble and No/Low Battery Trouble LEDs and sound the trouble sounder within 10 seconds. The 2501 (FACP) will not perform a scheduled battery test while the notification appliances (NAC) are active. It will perform the battery test after the notification appliances become inactive. The 2501 (FACP) will indicate hibernation mode by flashing the yellow LOW/NO AC and LOW/NO BATT LEDs at one (1) second intervals, the SYSTEM TROUBLE LED will be illuminated, and the local sounder will emit the trouble sound. The panel will automatically exit out of hibernation mode and return to normal operation when the Low/No AC condition is restored. After normal operating power has been restored, the panel will continue to indicate that it had been in hibernation by illuminating the SYSTEM TROUBLE LED and sounding the trouble sounder until a SYSTEM RESET is performed. 2.7 DRILL TEST A drill test may be performed by providing a dry contact closure between the Drill Test terminal and the Negative terminal. The ESL 2501 will sound the NACs with the programmed cadences. The communicator will not be activated and the common alarm and trouble contacts are not activated. An event is not generated in the event log. 2.8 TROUBLE RESOUND TIME The trouble sounder has a default resound interval of 15 minutes. It may be programmed to three additional values: 1, 4, or 24 hours. See Section 5.0 Programming. To force a battery test, press the SYSTEM RESET pushbutton. The 2501 (FACP) will automatically perform a battery test 10 seconds later. 2.9 COMM TEST 2.6 HIBERNATION MODE When the system uses a 2500-DAC Digital Alarm Communicator, an automatic comm test is performed every 24 hours as a minimum. The system can be programmed for a longer comm test interval if desired. The system automatically toggles between phones so that each phone line is tested at least once every 48 hours. No electronic or electrical system can be expected to operate properly if there is insufficient electrical power. For this reason the National Fire Alarm Code (NFPA 72) requires that fire alarm control panels have both a primary and secondary source of electrical power, usually a dedicated 110 VAC branch circuit and battery back-up. If the 110 VAC electrical power is lost AND the system has been operating on battery secondary power for an extended period of time, beyond that contemplated by the code, eventually the battery set will become depleted. Under these conditions the fire alarm control panel can no longer be expected to operate reliably. This will occur when the battery voltage is at 19.0 VDC. The panel will automatically log the event and then go into hibernation mode. While in hibernation, the 2501 (FACP) will not 10 2.10 DUAL LRM OPERATION For localities requiring dual Line Reversal Module applications, the 2501 FACP can be programmed to transmit separate supervisory and alarm signals. This is accomplished with the 2500-BELL expansion module. The FACP is programmed to operate the Bell expansion module as a dual LRM. Bell 3 will activate for a fire alarm and Bell 4 will activate for a supervisory alarm. For a Fire Alarm, the Bell 3 output circuit will reverse transmitting Sentrol 1-800-547-2556 the alarm signal to the connected device. All other System Alarm functions are as required. For a Supervisory Alarm, the Bell 4 output circuit will reverse transmitting a Supervisory Alarm to the connected device. All other Supervisory Alarm functions are as required. See Section 5 for programming information. See Figure 2.10 Dual LRM Installation Diagram for installation information. The connections are supervised and will result in a System and Bell 3 and/or Bell 4 Trouble if the lines are compromised. For system trouble transmission, the System Trouble dry contacts are available. 2.11 GROUND FAULT INDICATION OPERATION The FACP is equipped with ground fault detection circuitry. If required, the ground fault detection circuitry may be disabled by programming the BMB. Refer to Section 5.0 Programming for assistance with programming this feature. The FACP will function normally in the presence of a ground fault. Some localities are required by local jurisdiction to annunciate this condition. Sentrol 1-800-547-2556 11 Caution: Break the wire at each terminal to ensure that the connections are supervised - Do not loop the wire under the terminals. Supervised Signaling Line NEG DRILL TEST 2.7K EOL - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 JP2 COMMON AL NC COM MASTER BMB 2.7K EOL NEG DRILL TEST 2.7K EOL 2.7K EOL Power Booster NAC Circuits - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 IN FOR ZONE 1 CLASS B LRM/LEM JP3 + + - - Supervised Signaling Line + + - - + + - - Notification Appliances AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 JP2 Zone 1 programmed as power booster A- A+ BBELL 4 B+ A- Optional BELL EXPANDER POWER BOOST BMB NOTE: Use EOL resistors (provided) for all initiating and NAC circuits. Figure 2.2 Power Boost Installation Diagram 12 A+ BBELL 3 Sentrol 1-800-547-2556 B+ IN FOR ZONE 1 CLASS B LRM/LEM JP3 GREEN WHITE +12V DAT A DAT B NEG COMMON ALARM COMMON TROUBLE NO COM NC NC COM NO NOTE: The power booster is compatible with all UL Listed reversing NAC circuits. The normal standby current draw is 1 mA. The alarm current draw is 23 mA. Use the correct EOL for the listed panel selected to achieve the power booster functionality. Caution: Break the wire at each terminal to ensure that the connections are supervised - Do not loop the wire under the terminals. + + - - + + - - To UL Listed Proprietary Receiving Unit 2.7K EOL Notification Appliances DRILL NEG TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 JP2 Supervised Signaling Line IN FOR ZONE 1 CLASS B Zone 1 Programmed MASTER NOTE: Connect to anyBMB UL Listed as Non-Latching Proprietary Receiving Unit 2.7K EOL NEG DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 JP2 IN FOR ZONE 1 CLASS B LRM/LEM JP3 SLAVE BMB GREEN WHITE +12V DAT A DAT B NEG 2.7K EOL COMMON ALARM COMMON TROUBLE NO COM NC NC COM NO Supervised Signaling Line COMMON AL NC COM JP3 NOTE: Use EOL resistors (provided) for all initiating and NAC circuits. Figure 2.3a Slave Panel Installation Diagram Sentrol 1-800-547-2556 13 Caution: Break the wire at each terminal to ensure that the connections are supervised - Do not loop the wire under the terminals. + + - - + + - - 2.7K EOL Notification Appliances NEG DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 JP2 COMMON AL NC COM IN FOR ZONE 1 CLASS B LRM/LEM JP3 MASTER BMB NORM Connectors from Power Supply Databus Connector WT DIS SWT 4 Pin to 4 Pin Cable Assembly GND BELL BELL4 BELL3 CPU FAULT SILENCE TROUBLE TROUBLE FAULT Databus Connector LOW LOW BELL1 BELL2 DET NO AC NO BATT TROUBLE TROUBLE MAINT NEG ZEM DRILL TEST - PWR + SWITCH AUX N BOOSTER AUX12/24 12/24 SLAVE BMB TB1 2.7K EOL COMMON ALARM COMMON TROUBLE NO COM NC NC COM NO Databus Connector ZONE 1 BB+ ZONE 2 B+ B- ZONE 3 B+ B- ZONE 4 B+ B- Supervised Signaling Line This configuration is not available at this time. Supervised Signaling Line NOTE: Use EOL resistors (provided) for all initiating and NAC circuits. Figure 2.3b Slave Panel Installation with a ZEM Diagram 14 Sentrol 1-800-547-2556 Caution: Break the wire at each terminal to ensure that the connections are supervised - Do not loop the wire under the terminals. DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 JP2 JP3 Zone 1 Programmed as Non-Latching MASTER BMB IN FOR ZONE 1 CLASS B LRM/LEM Supervised Signaling Line NEG COMMON AL NC COM Supervised Signaling Line + + - - + + - Notification Appliances Program All Bells Steady Program All Zones as Non-Latching 2.7K EOL 2.7K EOL NEG DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 JP2 SLAVE/POWER BOOST BMB LRM/LEM Zone 1 Programmed as Power Booster Program Bells as Desired Program All Bells Associated to Zone 1 Only in the Bell Association Table IN FOR ZONE 1 CLASS B GREEN WHITE +12V DAT A DAT B NEG COMMON ALARM COMMON TROUBLE NO COM NC NC COM NO 2.7K EOL JP3 NOTE: Use EOL resistors (provided) for all initiating and NAC circuits. Figure 2.3c Slave Panel with Power Boost Installation Diagram Sentrol 1-800-547-2556 15 Caution: Break the wire at each terminal to ensure that the connections are supervised - Do not loop the wire under the terminals. DOOR HOLDER COM + NEG DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 JP2 LRM/LEM BMB GREEN WHITE +12V DAT A DAT B NEG COMMON ALARM COMMON TROUBLE NO COM NC NC COM NO JP3 IN FOR ZONE 1 CLASS B NOTE: Program common trouble contacts for open on loss of AC. See Section 5.0 Programming. Battery saver mode not applicable for door holder use. Figure 2.4 Door Holder Installation Diagram 16 Sentrol 1-800-547-2556 Supervisory Field Connections DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 COMMON ALARM COMMON TROUBLE NO COM NC NC COM NO A- AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 A- A+ BBELL 3 B+ B+ A+ BBELL 4 BELL EXPANDER GREEN WHITE +12V DAT A DAT B NEG NEG LRM/LEM Alarm Field Connections BMB NORM Databus Connector Connectors from Power Supply WT DIS SWT CPU BELL GND BELL4 BELL3 FAULT SILENCE TROUBLE TROUBLE FAULT LOW LOW BELL1 BELL2 DET NO AC NO BATT TROUBLE TROUBLE MAINT This application is used for separate Fire Alarm and Supervisory Alarm reporting. See Section 5.0 Programming. Program Communicator Type for Dual LRM. NOTE: Use EOL resistors (provided) for all initiating and NAC circuits. Figure 2.10 Dual LRM Installation Diagram Sentrol 1-800-547-2556 17 3.0 GENERAL SYSTEM INSTALLATION GUIDELINES First and foremost, CAREFULLY READ AND MAKE SURE YOU UNDERSTAND THE ENTIRE MANUAL BEFORE BEGINNING THE INSTALLATION. The reliable performance of the fire alarm system is dependent upon proper system design, installation and maintenance. Before installing the panel, a fire alarm system must be designed. The design of fire alarm systems is often regulated by the state or municipality through legislation requiring fire alarm system designers be certified or licensed. Make certain that the design and designer of the system comply with the relevant local laws, regulations and building codes and sub-codes. The design of a fire alarm system requires a thorough evaluation of the fire hazards and risks inherent in the facility to be protected. The design of the fire alarm system must also reflect the explicit fire safety objectives of the owner/operator of the site. The design of the fire alarm system must comply with the minimum compliance requirements in the relevant local codes and regulations. These local codes and regulations usually, by reference, adopt the National Fire Alarm Code. Consequently, the fire alarm system design must also comply with the applicable edition of the National Fire Alarm Code, NFPA 72; available from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269-9101, tel: 1-800-344-3555. Also, if questions arise call Sentrol Technical Services at 1-800-800-2027. The design of the system includes: • The type, quantity and location of alarm initiating within the facility being protected. • The type, quantity and location of alarm notification appliances, both audible and visible, within the facility being protected. • The connections between the fire alarm system and other building systems such as the HVAC system, door closers, elevator controls and security systems. • The programmed system response to alarm signals for each initiating device or notification appliance circuit. • The type, size and installation method of the wiring conductors interconnecting system components. • The type, size and installation method of the wiring conductors connecting the fire alarm system control unit to the primary power supply. • The capacity of the fire alarm system secondary power supply (battery set). • A dedicated, locked and labeled branch circuit (unswitched) for primary power supply. All design criteria should be documented in the system design. Sentrol has provided a number of design aids in 18 this manual. Figure 3.0, 2501 (FACP) Interconnect Diagram, identifies the intended use for each wiring terminal. Section 5 provides instructions for programming the FACP. Section 10 provides a review of the design of household fire warning systems. Appendix B provides a battery secondary power supply calculation worksheet. Additional design guidance is available from the local building code, local fire code and the National Fire Alarm Code, NFPA 72. 3.1 GENERAL INSTALLATION PROCEDURE The ESL 2501 Fire Alarm Control Panel has been designed to be easy to install. Below we have outlined an installation procedure that will lead to timely completion of the installation and result in trouble-free operation. Step 1. Planning: Referring to Figure 3.0, ESL 2501 Fire Alarm Control Panel Interconnection Diagram, for specific guidance, prepare a carefully laid-out and complete wiring diagram of the entire system as designed. This drawing should show the point-to-point connections being made to all fire alarm system devices, including, but not limited to: smoke detectors, manual fire alarm boxes, fire alarm notification appliances (both visible and audible), sprinkler system supervisory devices, sprinkler system waterflow initiating devices and the connection to the off-premises fire alarm signal receiving station, if included in the system design. This wiring diagram should show the calculations used for computing the capacity of the battery secondary power supply according to the Battery Calculation Worksheet, provided in Appendix B. All drawings and calculations should be maintained as part of the permanent record of the fire alarm system installation. All power-limited connections must be made with component recognized energy limited cable. Step 2. Equipment Inspection: Carefully unpack the system components and inspect for damage incurred in shipping. Immediately report any damage to the place of purchase for disposition. Step 3. Mount Cabinet: Mount the cabinet in a clean, dry, vibration free area, where the temperature range does not exceed 0 to 49oC (32 to 120oF). Mount only in interior locations. Allow adequate space for 180 degree door swing and free access to all sides for conduit entry. Locate the top of the cabinet approximately six (6) feet above the floor, with the hinge mounting on the left. Mounting holes in the back of the cabinet are designed so the cabinet can be mounted without removing any control equipment. Mount the cabinet to the wall by first installing the top center mounting screw leaving enough space so the cabinet can be hooked over the screw head. Use screws or bolts no smaller than #10 or 3/16 inches in diameter. For easier access, remove the door by gently lifting it from the hinges. Sentrol 1-800-547-2556 Step 4. Install Fire Alarm System Devices: Refer to the installation instructions provided with the compatible fire alarm system devices (smoke detectors, heat detectors, manual fire alarm boxes, audible notification appliances, visible notification appliances and other similar devices) and install these devices as permitted by their installation instructions. Note that the UL Listing of some devices permits their installation without a junction box if also permissible under the local building code. Also note that the installation of fire alarm systems is covered in Article 760 of the National Electrical Code (NEC), NFPA 70. Article 760 of the NEC stipulates the types of wire permissible for fire alarm installations employing conduit as well as those using Listed Fire Alarm Cable. The initiating device circuits and notification appliance circuits are power-limited circuits. Use an installation method permitted by Article 760 of the NEC to connect fire alarm devices to the fire alarm system control panel. Keep in mind that where ever conduit or cable enters a junction box or electrical enclosure it must be provided with a Listed bushing or connector, as appropriate. Refer to Section 4.1, Detail Installation Guide, for further information. DO NOT connect field wiring until after the fire alarm control unit has been properly checked. Step 5. Physical Assembly Check: Verify that all boards are properly snapped into place over the locking clip. To add a board to the panel, firmly press the board onto the standoffs until the board snaps over the locking clip. To remove a board from the standoffs, press the locking clip in with needle-nose pliers or a flat head screwdriver (see Figure 3.1a). PRESS Examine the installation of all modules, chassis, and subassemblies to insure proper mechanical and electrical connections and programming switches have been selected. Step 6. Basic 2501 System Check: Prior to connecting field wiring to the unit, it is necessary to make certain that the 2501 is operating properly. This is achieved by performing the System Check. Install the 2.7k Ω 5% End of Line (EOL) resistor (provided) to Zone 1, BELL 1 and BELL 2. Make sure all switches are in their normal positions. Connect the power supply cable assemblies between the BMB and power supply. Connect the AC flying leads to an unswitched 120 VAC 50/60 Hz power supply. See Figure 3.0, 2501 (FACP) Interconnect Diagram. Connect the red wire to the positive (+) spade lug of Battery 1 and the black wire to the negative (-) spade lug of Battery 1. Connect the red with white stripe wire to the positive (+) spade lug of Battery 2 and the black with white stripe wire to the negative spade lug of Battery 2. No fault indicator should be present. If faults are present, see the Troubleshooting Guide Section 9.0. System check is now complete. NOTE: If new batteries with low terminal voltage are used, the Low/No battery LED may activate and the Trouble Sounder will sound. Silence the Trouble Sounder and charge the batteries. The Low Battery indicator will deactivate after the batteries are fully charged; no longer than 48 hours. Step 7. Check Field Wiring: Check the integrity of all field wiring following directions defined in the Field Wiring Checkout Procedures found in Section 4.2. This check must be performed before connecting wiring to the system. Be certain all external wiring is correct (no opens, shorts, or grounds) and is terminated with the end-of-line devices provided. Step 8. Connection of Field Wiring: Remove power from the system and connect the first circuit to the control unit. Restore power and verify that the circuit is working properly. If not, refer to Section 9, Troubleshooting Guide, for specific steps for isolating and identifying the source of the problem. Repeat, connecting the field wiring one circuit at a time, as shown on the system wiring diagram created in Step 1. DO NOT MAKE ALL CONNECTIONS AT ONCE! Connecting one circuit at a time allows for the quick identification of wiring errors and prevents the possibility of a wiring error causing damage to the system electronics. During the connection process document any changes made in the system wiring on the system wiring diagram. Step 9. Test System: An installation of a fire alarm system is NOT complete until the acceptance testing and system documentation is completed. Acceptance testing involves the actuation of all of the initiating devices and the verification that each device causes the appropriate response. The acceptance testing also includes the verification that each and every notification appliance is operational and operates when intended. Each function the system is intended to perform must be verified. The documentation must include a completed Record of Completion form (Figure 1-7.2.1 in NFPA 72-1996) and a set of As-Built drawings that show exactly how the system is actually wired and the serial numbers of all devices used. Refer to Section 6 and 7 of this manual for additional, more detailed information. Sentrol 1-800-547-2556 19 3.2 BMB OPERATION VERIFICATION BMB DAUGHTER BOARD DESCRIPTION The Daughter Board LEDs (D1 - D6) are used to indicate the status of the system and to program the BMB function map (see Chapter 5.0 Programming). See Figure 3.2a for push-button and LED locations. See Figure 3.2b for a description of the LEDs on the BMB Daughter Board. SYS SUP D3 PROG SW7 LED D5 SW3 SW2 SYS TRBL DOWN SW8 ZONE 1 ALARM J1 D2 RESET VALUE VALUE UP SW4 D1 SW1 D6 SYS ALM J2 AC PWR ALARM TROUBLE LOCATION LOCATION UP SW5 D4 ZONE 1 TRBL The large push-buttons are primarily used to handle alarm and trouble conditions in the system. The SYSTEM RESET push-button is used to reset any zones that are in an alarm condition. If the SYSTEM RESET push-button is pressed and no alarm condition has occurred, the BMB will perform a battery test within 15 seconds. This allows the installer to test the batteries without waiting for the standard battery test which is performed every hour. The ALARM SILENCE push-button is used to silence any audibles that have not been programmed as nonsilenceable. If an alarm condition occurs after the audibles have been silenced, the audibles will sound again. The TROUBLE SILENCE push-button will silence all activated trouble conditions when pressed. If a trouble condition occurs after the trouble has been silenced, the local sounder will sound again. These three push-buttons are also used in programming mode (see Section 5.2, System Programming). DOWN Located on the bottom of the Daughter Board is one small push-button labeled PROG. This push-button is used only for BMB function map programming (see Section 5.2, System Programming). SW6 Description AC PWR (D6) Detects ample AC power. The LED will be lit. SYS ALM (D1) Used to indicate an alarm condition for any one of the 25 zones. SYS TRBL (D2) Used to indicate a trouble has occurred in the system. This trouble may be a zone trouble, BMB diagnostic trouble, or a communication problem with a peripheral. SYS SUP (D3) Used to indicate that one or more of the zones in alarm is a supervisory zone. ZONE 1 TRBL (D4) Used to indicate a trouble condition on the BMBs integral Zone 1. ZONE 1 ALARM (D5) Used to indicate an alarm condition on the BMBs integral Zone 1. BMB MAIN BOARD LED DESCRIPTION The BMB main board has 10 yellow LEDs that are used to indicate system troubles that are not zone related (see Figure 5.6, LED Location Diagram for Programming Location and Programmed Value). These LEDs are also used for function map programming (see Chapter 5.0, Programming). NOTE: Not all system troubles are indicated on the 10 yellow LEDs located on the BMB main board. See Figure 3.2d for a list of system troubles that are indicated through the use of an ESL 2500 keypad. Figure 3.2b BMB Daughter Board LED Table 20 Sentrol 1-800-547-2556 System Trouble Description 3.3 ZEM ADDRESS SELECTION CPU Fault Indicates that the BMB microprocessor is defective and the system is completely inactive. BELL SILENCE Indicates that a bell (NAC) has been silenced. BELL 1, BELL 2, BELL 3, BELL 4 TROUBLE Indicates that there is a short or open in the wiring or that the EOL is missing. GND FAULT Indicates an earth ground connection to the system. (see Section 6.3, Ground Fault Test). LOW NO AC Indicates the loss of AC power or that the AC voltage is not high enough to power the system. LOW NO BATT Indicates that the battery voltage is low or the batteries are missing. If the battery voltage drops far enough and there is no AC power, the system will go into hibernation mode. During hibernation mode, the BMB will flash LOW NO AC, LOW NO BATT, and AC PWR LEDs. If conditions permit, the panel will leave hibernation mode. DET MAINT Indicates when one of the smoke detectors in the system signals that it needs to be cleaned (see Section 5.5, CleanMe Mode Programming). Figure 3.2c Additional System Troubles Keypad System Trouble Many facilities need more than one initiating device circuit in order to implement a design that complies with all of the code requirements. Additional initiating device circuits (up to 25 additional circuits before it is necessary to begin networking multiple control panels) are added by adding Zone Expander Modules (ZEMs) to the basic 2501 FACP. When this is done the ZEM must be programmed with an electronic “name” in order for the BMB computer to know which ZEM is initiating the alarm signal. The first added ZEM should be given address “1” by putting S1 in the ON position and S2, S3 and S4 in the OFF position. The next ZEM should be given the address “2”, with S1 through S4 being positioned OFF-ON-OFF-OFF, respectively. Figure 3.3 shows the addressing for the ZEMs. ZEM NUMBER S1 S2 S3 S4 1 ON OFF OFF OFF 2 OFF ON OFF OFF 3 ON ON OFF OFF 4 OFF OFF ON OFF 5 ON OFF ON OFF 6 OFF ON ON OFF Description NO AC POWER Indicates the loss of AC power or that the AC voltage is not high enough to power the system. LOW BATTERY Indicates that the battery voltage is low or the batteries are missing. BELL Indicates that there is a short or open in the wiring or that the EOL is missing. GROUND FAULT Indicates an earth ground connection to the system. BELL SILENCE Indicates that a bell (NAC) has been silenced. DRILL TEST Indicates that a drill test is being performed. HIBERNATION Indicates that the panel has gone into hibernation mode. LEM/LRM Indicates a problem with the LEM/LRM module. TELCO Indicates a problem with a 2500-DAC phone line. EXPANDER Indicates a missing ZEM module. DAC Indicates a problem with the 2500-DAC module. KEYPAD Indicates a missing supervised keypad. RA Indicates a missing supervised RA. COMM Indicates a 2500-DAC communication failure. MEMORY Indicates a function map memory failure with either the BMB or 2500-DAC. Enter programming mode to clear. Figure 3.3 ZEM Address Selection Chart When using multiple 2502 Class B zone expansion modules, it will be necessary to leave some panel zones unused to ensure that the modules LED’s line up with the correct zone identifiers on the front panel display. For example, if two 2502-ZEM’s are used, zones 2 and 3 will be used, then 4 and 5 will be skipped, and zones 6 and 7 will be used for the second 2502-ZEM. Please call Sentrol Technical Services at 1-800-800-2027 with any questions. NOTE: For best zone LED alignment results, do not use multiple two zone expansion modules (2502-ZEM) when a four zone module (2504-ZEM) can be used. Only the combinations listed above are allowed. Any other combinations will not be recognized by the 2501 (FACP). If two (2) or more modules are set to the same address, the 2501 (FACP) will not recognize the incorrectly addressed modules. Figure 3.2d System Troubles Indicated by the ESL 2500 Keypad Sentrol 1-800-547-2556 21 Every zone on the 2501 (FACP) has a zone function jumper that allows for easy testing. This jumper allows for four (4) settings: Normal Walk Test Silent Walk Test Disconnect NORM WT SWT DIS During installation, set the zone function jumpers to the Normal (NORM) position, see Figure 3.4, Function Jumper diagram. (See Section 6.4 for instructions on testing the 2501 (FACP) with the zone function jumpers). The ZXPTR Parallel Printer Interface Module allows the connection of a Centronics compatible printer to the ESL 2501 FACP (see Figure 3.5e). This provides the ability to print “real time” events, reprint past event history and print function maps. Refer to the ZXPTR Installation Instructions for information on operation and connection. The following table provides guidelines for the installation of peripheral devices. These guidelines or the number of devices and the total length of databus cable must not be deviated from for proper operation. This table is valid for 18 AWG cable. Do not exceed 1000 Ft. in any one run of cable. Do not exceed 2000 Ft. of total cable length. An external supply may be required at lengths over 500 Ft. if more than one device is at the end of the cable run. Total Data Cable Length Max. Number of Peripherals at End Up to 500 Ft (7) Seven 1000 Ft (7) Seven* 2000 Ft (7) Seven* 3.5 ADD-ON MODULES FOR EXPANDED CAPABILITIES The 2500 Keypad is installed where the owner/operator needs system interface and access. Interconnection between the FACP and the Keypad is by means of a four (4) conductor cable. The connection between the ESL 2501 Fire Alarm Control Panel and the ESL 2500 Keypad is illustrated in Figure 3.5b. The 2500-RA and 2500-RADVR are installed where required by local jurisdiction or when the owner/operator needs remote system status and zone status. Interconnection between the FACP and the remote annunciators is by means of a four (4) conductor cable. The connection between the ESL2501 Fire Alarm Control Panel and the remote annunciators is illustrated in Figure 3.5c. The 2500-LEM/LRM is installed where a municipal system is in place. Interconnection between the FACP and the LEM/LRM module is by means of a five (5) conductor cable. The connection between the ESL2501 Fire Alarm Control Panel and the LEM/LRM is illustrated in Figure 3.5d. * Power Supply required at end of cable run. Figure 3.5a Peripheral Device Guidelines Table B+ BZONE 1 JP2 JP2 IN FOR FOR IN ZONE 11 ZONE CLASS B B CLASS GREEN WHITE +12V DAT A DAT B NEG LRM/LEM JP3 JP3 BMB Keypad Databus Cable Databus Connector OW BELL1 BELL2 DET ATT TROUBLE TROUBLE MAINT Figure 3.5b Connecting BMB to Keypad B+ BZONE 1 JP2 JP3 IN FOR ZONE 1 CLASS B LRM/LEM Functional modules are added to the basic 2501 FACP by snapping them onto the module mounting rails of the system enclosure. The modules obtain power and communicate via four conductor data bus cables installed between the BMB and the first module, from the first module to the second, etc., until all modules are connected to the data bus. The assembly of the ESL 2501 Fire Alarm Control Panel is illustrated in Figures 3.0, 3.1b, 3.1c, 3.4, 3.10 and 3.11 in this manual. A zone description card is supplied for each zone module, as shown in Figure 3.12, to identify each zone in terms relevant to the specific application. BMB GREEN WHITE +12V DAT A DAT B NEG 3.4 ZONE FUNCTION JUMPERS RA/RADVR Databus Cable Databus Connector J1 OW BELL1 BELL2 DET ATT TROUBLE TROUBLE MAINT Figure 3.5c Connecting BMB to RA/RADVR 22 Sentrol 1-800-547-2556 The 2501 (FACP) supports three supervised keypads at addresses 1 through 3 (Figure 3.6). More than one unsupervised keypad is allowed. All unsupervised keypads must be at address 4 with switch 4 turned ON (Figure 3.6). B+ BZONE 1 JP2 JP2 LRM/LEM BMB J5 J2 J2 LAMP TEST GREEN WHITE +12V DAT A DAT B NEG JP3 JP3 IN INFOR FOR ZONE ZONE11 CLASS CLASSBB TROUBLE LEM/LRM NORMAL LEM Databus Connector 3.7 2500-DAC DISCONNECT LEM The DAC requires programming via a 2500-KPD keypad. Refer to Section 5.0 Programming for assistance with programming the DAC. A manual comm test switch is provided to perform system verification and testing. The on board status LEDs can be tested by performing a system lamp test from the front panel or the optional system keypad. B+ B- OW BELL1 BELL2 DET ATT TROUBLE TROUBLE MAINT JP2 IN FOR ZONE 1 Connecting BMB to LEM/LRM Figure 3.5d CLASS B B ( + ) 12V DATA B A ( - ) NEG DATA A GREEN WHITE +12V DAT A DAT B NEG JP3 3.8 2500-RA AND 2500-RADVR MOOSE a product of sentrol, inc The RA and RADVR have dip switches for setting the address of the specific remote annunciator. Switch four (4) is used to set whether the RA displays zones 1 - 13 or zones 14 - 25. See the figure below for valid addresses. A lamp test can be performed by pressing and holding the local silence button for 3 seconds when the system status is normal. 2 1 ON OFF 1234 1234 3.6 2500 KEYPAD ADDRESS SETTINGS Zones 1 - 13 The keypad has a four position DIP switch on the circuit board to set the address and supervision. To change the keypad to unsupervised, move DIP switch 4 to the ON position. To change the address, the DIP switch setting must be positioned according to the figure below: ON OFF 1234 2 1 4 3 ON 1234 Zones 14 - 25 OFF Figure 3.8 2500-RA/RADVR Address Switch Settings 1234 1234 3 4 The 2501 FACP supports four supervised remote annunciators at addresses 1 through 4. ON OFF 1234 1234 UNSUPERVISED Figure 3.6 2500 Keypad Address Switch Settings Sentrol 1-800-547-2556 23 3.9 2500-LEM/LRM The LEM/LRM module has a slide switch that must be set to determine the functionality of the module. Set the switch accordingly. In addition, another slide switch must be set to the normal position for proper operation. This switch can also be set in the Disconnect position resulting in a system trouble. This prevents the 2501 FACP from triggering the device connected to the FACP during installation and testing. A lamp test switch is provided on the module to test the condition of the trouble LED. 24 Sentrol 1-800-547-2556 product of sentrol Black Red Red with White Stripe Black with White Stripe + - Spade Lugs to Battery #2 Fuse Type: AGC 15 32V + - Databus Connector (Power-Limited) B+ ZONE 1 BA+ A- B+ ZONE 2 BA+ A- Model 2502A** Terminal Labeling Unit shown is a model 2504 with four Class B zones. A model 2502 (two Class B zones) will be the same except TB1 will be four positions (Zone 1 and Zone 2 only). Model 2502A** (two Class A zones) will have eight terminal block positions labeled as shown. The ESL 2501 (FACP) is equipped with a “Battery Saving Switching Mechanism” U.S. Patent No.: 5,804,891. CleanMe® is a registered trademark of Sentrol and is protected under the following U.S. Patent No.: 5,708,414. P11 from power supply J11 TROUBLE SILENCE ZONE 1 TRBL ZONE 1 ALM BMB DIS SWT ZONE 2 B+ B- NC RELAY 2 ZONE 3 B+ B- RELAY 4 RELAY 3 ZONE 4 B+ B- NO COM NC NO COM NC NO COM NC Databus COM RELAY 1 Connector NO ZEM WT NORM Zone Function Select Jumper P6 from power supply ZEM AA+ BBELL 3 AA+ ZONE 1 Optional BELL EXPANDER Supervised and Power-Limited ZONE 1 BB+ B+ BB+ BELL 1 Supervised and Power-Limited A+ BBELL 4 AA+ BELL 1 B+ B+ BZONE 1 2.7k EOL Zone 1 JP3 JP2 Green White Black Wire Nut Connect to Power-Limited Supervised Lines Only ** Not available at this time. 64600403C No other initiating devices shall be connected to these circuits unless approved by the local authority having jurisdiction. * Consult smoke detector for information This unit may be programmed for alarm verification that will result in a delay of the system alarm signal. The total delay (control unit plus smoke detector) shall not exceed 60 seconds. If installed in accordance with the California State Fire Marshals Office, the total delay is not to exceed 30 sec. Circuit Control unit Smoke Detector (zone) delaymodel delaysec. sec. WARNING Not suitable for remote station protected premises service where separate transmission circuits are required for fire, supervisory (if applicable) and trouble signals. All circuits except drill test, the auxiliary alarm control, and the system trouble contacts are supervised. Safety Ground (Green) AC Rtn (White) AC In (Black) (Wires 120 VA 50/60Hz) NOTE Connection from Power Supply. Power Supply is mounted under the BMB. AC wiring is located on the Power Supply board behind the BMB. Refer to the ESL2501 Fire Alarm Control Panel Installation and Operation Manuals 64812711 and 64812828 for additional information. For service contact: Databus Connector (Power-Limited) This unit is shown with an optional zone follower module (ZRM-4). A two zone follower module is available for the 2502 and 2502A**. J5 IN FOR ZONE 1 J13B CLASS Owners Instruction Notice: “Not to be removed by anyone except occupant.” WARNING Initiating circuit shown Class B (Style B). Notification circuits shown Class B (Style Y). Optional notification circuits capable of Class A (Style Z). See installation instructions for more information. LOW BELL1 BELL2 DET BELL4 BELL3 GND LOW CPU BELL FAULT SILENCE TROUBLE TROUBLE FAULT NO AC NO BATT TROUBLE TROUBLE MAINT A- BB+ BELL 2 2.7k EOL Supervised and Power-Limited 2.7k EOL ALARM ALARM ALARM ALARM ZONE 1 ZONE 2 ZONE 3 ZONE 4 TRBL TRBL TRBL TRBL AA+ BELL 2 Databus Connector POWER Optional ZRM TB1 J6 Connectors from Power Supply * Suitable for installation as Style D Proprietary Multiplex System or Central Station Type 3 Multiplex System. Installation limits under jurisdiction of local authority. Testing - In a household fire warning system, test weekly. Disconnect the AC power source during testing. If after testing low battery condition exists, replace the batteries. This equipment should be installed in accordance with the National Fire Protection Association’s standard 72 (NFPA, Batterymarch Park, Quincy, MA 02269). Printed information describing proper installation, operation, testing, maintenance, evacuation planning and repair service is to be provided with this equipment. The following applies to NFPA 72 household installations: SYS TRBL SYS SUP ALARM SILENCE Programming Switch SYS ALM AC PWR SYSTEM RESET Power-Limited - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 Connect to Power-Limited Supervised Lines Only Power ON Standby Condition DRILL NEG TEST Optional Drill Test Switch BMB Standoff (1 of 6) System Trouble Contacts Auxiliary Alarm Contacts Not Supervised. For Connection to Power-Limited Sources Only. Spade Lugs to Battery #1 Devices that operate over the full range of 8.5 to 33 VDC will draw more current when they are powered by 12 VDC versus 24 VDC. WARNING Note: The typical battery life is 3 to 5 years, depending on usage. When replacing batteries, always replace both batteries, even if only one appears dead. See manufacturer’s specifications for the recommended batteries used. Recommended batteries are YuasaExide models NP18-12B and NP7-12. (+) battery leads fused at 15 Amp. 12V 17.2AH See instruction manual part number 64812711 BATTERIES Type of system: NFPA 72 - Central Station Signaling Systems (protected premises) with 2500-DAC NFPA 72 - Local NFPA 72 - Household fire warning system NFPA 72 - Remote Station Signaling Systems (protected premises) with 2500-DAC NFPA 72 - Proprietary Protected Premises Unit * Type of signaling service: Manual fire alarm, automatic fire alarm, elevator recall, waterflow alarm, supervisory fire alarm, (NFPA 72). Type of signal: Non-coded, DACT Compatibility identifier: C01 Initiating circuit resistance = 30 Ohm max. C01A Initiating circuit resistance = 30 Ohm max.** CSFM Number: 7165-1459:111 ESL 2501 Fire Alarm Control Panel a DATABUS ESL Zone 2 LRM/LEM GREEN WHITE +12V DAT A DAT B NEG Sentrol Controls Group 1510 Tate Blvd. SE, Hickory, NC 28603 Sales: 800.547.2556 Technical Service: 800.800.2027 Zone 3 Sentrol 1-800-547-2556 Zone 4 COMMON ALARM COMMON TROUBLE NC COM NO NO COM NC Zone 5 Power-Limited Figure 3.0 2501 (FACP) Interconnect Diagram 25 NEG DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 COMMON ALARM COMMON TROUBLE NC COM NO NO COM NC BB+ BELL 1 B+ BZONE 1 AA+ ZONE 1 J13 A- A- B+ A+ BBELL 4 A+ BBELL 3 B+ BELL EXPANDER LINE 2 LINE 1 J4 J3 J5 LRM/LEM J5 DAC Placement GREEN WHITE +12V DAT A DAT B NEG BMB Placement AA+ BELL 1 DAC J1 DATABUS BMB Databus Cable Routing ALIVE Databus Connector Databus Cable Routing TRBLE LINE1 FAULT LINE2 FAULT SW1 LINE1 IN USE NORM Databus Connector LINE2 IN USE WT DIS PROGRAM Connectors from Power Supply SWT CPU BELL GND BELL4 BELL3 FAULT SILENCE TROUBLE TROUBLE FAULT POWER ALARM ZONE 1 TRBL ALARM ZONE 2 TRBL ALARM ZONE 3 TRBL POWER ALARM ZONE 4 TRBL ZEM ZEM and ZRM Placement ALARM ZONE 1 TRBL ALARM ZONE 2 TRBL ALARM ZONE 3 TRBL COM RELAY 1 ZRM NC NO J4 NC COM RELAY 1 NC COM NO NC RELAY 2 COM ZRM COM NO RELAY 3 NC COM NO NO RELAY 4 RELAY 4 NC COM NO NO NO TB1 TB1 NC COM ZONE 4 B+ B- NEG ALARM ZONE 4 TRBL NC COM TB1 ZONE 3 B+ B- ALARM ZONE 3 TRBL COM RELAY 4 ZONE 2 B+ B- ALARM ZONE 2 TRBL Z5 IN TRB IN +24V ZEM NO RELAY 3 COM ZONE 1 BB+ Z4 IN NC RELAY 2 COM NO RELAY 3 ALARM ZONE 1 TRBL Z3 IN NO NC ZRM POWER ALARM ZONE 4 TRBL Z2 IN NC NO RELAY 2 Z1 IN ZEM NC RELAY 1 LOW LOW BELL1 BELL2 DET NO AC NO BATT TROUBLE TROUBLE MAINT ZONE 1 BB+ ZONE 2 B+ B- ZONE 3 B+ B- ZONE 4 B+ B- ZONE 1 BB+ ZONE 2 B+ B- ZONE 3 B+ B- ZONE 4 B+ B- Batteries Figure 3.1b Internal Panel Configuration with DAC 26 Sentrol 1-800-547-2556 Databus Cable Routing NEG DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 A- A- B+ A+ BBELL 4 A+ BBELL 3 B+ J5 BELL EXPANDER J2 LEM/LRM Placement J2 LAMP TEST GREEN WHITE +12V DAT A DAT B NEG COMMON ALARM COMMON TROUBLE NO COM NC NC COM NO BMB Placement LRM/LEM J13 TROUBLE LEM/LRM NORMAL LEM BMB Databus Cable Routing DISCONNECT NORM Connectors from Power Supply Databus Connector WT DIS ALARM ZONE 1 TRBL ALARM ZONE 2 TRBL ALARM ZONE 3 TRBL POWER ALARM ZONE 4 TRBL ZEM ZEM and ZRM Placement ALARM ZONE 1 TRBL ALARM ZONE 2 TRBL RELAY 1 COM RELAY 1 ZRM NC NC COM RELAY 1 NC COM NO NC RELAY 2 COM ZRM COM NO RELAY 3 COM NO ALARM ZONE 4 TRBL ZEM NO RELAY 3 NC COM NO RELAY 4 NO RELAY 4 RELAY 4 NC NC COM COM NO NO NO ZONE 4 B+ B- TB1 TB1 NC COM TB1 ZONE 3 B+ B- ALARM ZONE 3 TRBL NC RELAY 2 COM COM ZONE 2 B+ B- ALARM ZONE 2 TRBL NO NO RELAY 3 ALARM ZONE 1 TRBL NC NC RELAY 2 POWER ALARM ZONE 4 TRBL ZEM NO ZONE 1 BB+ B- LOW LOW BELL1 BELL2 DET NO AC NO BATT TROUBLE TROUBLE MAINT ALARM ZONE 3 TRBL NC ZRM B+ B- SWT CPU BELL GND BELL4 BELL3 FAULT SILENCE TROUBLE TROUBLE FAULT POWER LEM B+ ZONE 1 BB+ ZONE 2 B+ B- ZONE 3 B+ B- ZONE 4 B+ B- ZONE 1 BB+ ZONE 2 B+ B- ZONE 3 B+ B- ZONE 4 B+ B- Batteries Figure 3.1c Internal Panel Configuration with LEM/LRM Sentrol 1-800-547-2556 27 DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 LRM/LEM COMMON ALARM COMMON TROUBLE NO COM NC NC COM NO JP2 IN FOR ZONE 1 CLASS B JP3 DATABUS GREEN WHITE +12V DAT A DAT B NEG NEG BMB NORM WT DIS SWT NORM DIS ALARM ALARM ALARM ALARM ZONE 1 ZONE 2 ZONE 3 ZONE 4 TRBL TRBL TRBL TRBL POWER WT ZEM NORM DIS NORM WT DIS SWT WT NORM DIS SWT WT SWT NORM WT DIS SWT NC Databus COM RELAY 1 Connector NO Databus Connector SWT NC Function Jumper RELAY 2 Optional ZRM ZEM COM NO RELAY 3 NC RELAY 4 Zone 5 Zone 4 Zone 3 Zone 2 COM NO NC COM NO TB1 ZONE 1 BB+ Figure 3.4 Function Jumper Diagram 28 Sentrol 1-800-547-2556 ZONE 2 B+ B- ZONE 3 B+ B- ZONE 4 B+ B- 3.10 INSTALLING THE ZEM, BMB, AND DAC NEG DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 GREEN WHITE +12V DAT A DAT B NEG LRM/LEM COMMON ALARM COMMON TROUBLE NC COM NO NO COM NC BMB Databus Connector NORM Databus Connector Connectors from Power Supply WT DIS SWT GND BELL4 BELL3 CPU BELL FAULT SILENCE TROUBLE TROUBLE FAULT LOW LOW BELL1 BELL2 DET NO AC NO BATT TROUBLE TROUBLE MAINT LINE 2 LINE 1 J2 J3 J5 DAC J1 DATABUS ALIVE TRBLE LINE1 FAULT LINE2 FAULT SW1 LINE1 IN USE J4 Z1 IN POWER ALARM ZONE 1 TRBL ALARM ZONE 2 TRBL ALARM ZONE 3 TRBL Z2 IN Z3 IN Z4 IN Z5 IN TRB IN +24V PROGRAM LINE2 IN USE NEG ALARM ZONE 4 TRBL TB1 ZEM ZONE 1 BB+ ZONE 2 B+ B- ZONE 3 B+ B- ZONE 4 B+ B- Figure 3.10 ZEM, BMB, and DAC Installation Diagram Sentrol 1-800-547-2556 29 3.11 INSTALLING THE BELL, ZRM AND LEM/LRM A- A+ BBELL 4 B+ A- A+ BBELL 3 B+ BELL EXPANDER J2 LAMP TEST TROUBLE LEM/LRM NEG DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 NORMAL LRM/LEM COMMON ALARM COMMON TROUBLE NO COM NC NC COM NO GREEN WHITE +12V DAT A DAT B NEG DISCONNECT BMB B- Databus Connector WT DIS SWT GND BELL4 BELL3 CPU BELL FAULT SILENCE TROUBLE TROUBLE FAULT POWER ALARM ZONE 1 TRBL ALARM ZONE 2 TRBL ALARM ZONE 3 TRBL LOW LOW BELL1 BELL2 DET NO AC NO BATT TROUBLE TROUBLE MAINT ALARM ZONE 4 TRBL TB1 ZEM ZONE 1 BB+ ZONE 2 B+ B- ZONE 3 B+ B- ZONE 4 B+ B- NC RELAY 1 COM NO NC RELAY 2 ZRM COM NO RELAY 3 NC COM NO RELAY 4 NC COM NO Figure 3.11 BELL, ZRM and LEM/LRM Installation Diagram 30 Sentrol 1-800-547-2556 LEM B+ NORM Connectors from Power Supply Databus Connector LEM 3.12 INSTALLING THE ZONE DESCRIPTION CARD Place Zone Description Card for Zone 1 Here ZONE DESCRIPTION Place Zone Description Card for First ZEM Here ZONE DESCRIPTION NOTE: THIS IS VIEWED FROM INSIDE OF DOOR Figure 3.12 Zone Description Card Diagram Sentrol 1-800-547-2556 31 + + - - Figure 4.0a Class B System Installation Diagram without ZEM Sentrol 1-800-547-2556 Notification Appliances + + - COMMON ALA NC COM DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 BB+ BELL 2 BMB AA+ BELL 2 AA+ BELL 1 2.7K EOL BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 JP3 JP2 IN FOR ZONE 1 CLASS B Zone 1 is shown with 4-wire detectors, wired in Class B (Style B) 2.7K EOL NOTE: Use EOL resistors (provided) for all initiating and NAC circuits. NEG NAC Circuit 1 shown with Class B (Style Y) wiring 2.7K EOL + + - - LRM/LEM 32 204-12/24V Power supervision relay 449C 449C Caution: Break the wire at each terminal to ensure that the connections are supervised - Do not loop the wire under the terminals. 4.0 FIELD WIRING Class B Wiring Diagram + + - - Figure 4.0b Class B System Installation Diagram with ZEM 429C 429C - - + + - - + + Sentrol 1-800-547-2556 33 4 Pin to 4 Pin Cable Assembly ZONE 3 B+ B- 2.7K EOL ZONE 2 B+ B- 2.7K EOL Databus Connector ZONE 4 B+ B- SWT WT NORM DIS Caution: Break the wire at each terminal to ensure that the connections are supervised - Do not loop the wire under the terminals. Zone 5 is shown with 2-wire heat detectors and pull stations, wired in Class B (Style B) 2.7K EOL Heat Sensor BELL2 DET LOW LOW BELL1 NO AC NO BATT TROUBLE TROUBLE MAINT Pull Station GND CPU BELL BELL4 BELL3 FAULT SILENCE TROUBLE TROUBLE FAULT BMB Zone 2 is shown with 2-wire detectors, wired in Class B (Style B) TB1 NOTE: Use EOL resistors (provided) for all initiating and NAC circuits. 2.7K EOL ZONE 1 BB+ Zone 2 ZEM (2504) Zone 3 Databus Connector Zone 4 Databus Connector Connectors from Power Supply Zone 5 4.1 DETAIL INSTALLATION GUIDE The initiating device circuits and notification appliance circuits of the ESL 2501 Fire Alarm Control Panel are classified as power limited circuits. These circuits can be installed using any of the methods permitted by Article 760 of the National Electrical Code (NEC), NFPA 70-1996, for power limited fire alarm (PLFA) circuits. See 760-52 of NFPA 70-1996. Non-power limited fire alarm system wiring may be installed using any of the methods permitted by Article 760 of the National Electrical Code (NEC), NFPA 70-1996, for non-power limited fire alarm (NPLFA) circuits. See 760-21to 760-31 of NFPA 70-1996. The circuit conductors of a power limited fire alarm circuits must be separated from non-power limited fire alarm circuits and ordinary light and power circuits pursuant to the requirements of Article 760-54 of the NEC. Figures 4.1a and 4.1b show one method of routing conductors that can be used to comply with the required 1/4 inch separations. The following circuits are classified as non-power limited fire alarm (NPLFA) circuits: • Wiring connected to “dry” TROUBLE relay contacts • Wiring connected to “dry” ALARM relay contacts • Wiring extending from the Digital Alarm Communicator (DAC) to the telephone system • Wiring extending from “dry” Zone Relay contacts • Wiring extending from the 2500-RADVR output connector Power-Limited (Bell Circuit, #2 and #4) Power-Limited (Aux Power and Power Booster Circuits) Power-Limited Zone 1 Initiating Circuits (NAC Circuit #1 and #3) 120VAC Power-Limited Telephone Line 2 Earth Ground For Connection to Power-Limited Sources Only Drill Test Common Alarm and Common Trouble Contacts NEG DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 B+ BZONE 1 AA+ ZONE 1 JP2 A- B+ A+ BBELL 4 A+ BBELL 3 B+ BELL EXPANDER LINE 2 LINE 1 J2 J3 Power-Limited Telephone Line 1 J5 LRM/LEM A- IN FOR ZONE 1 CLASS B GREEN WHITE +12V DAT A DAT B NEG COMMON ALARM COMMON TROUBLE NO COM NC NC COM NO JP3 DAC J1 DATABUS BMB ALIVE TRBLE LINE1 FAULT Battery Connection Circuits LINE2 FAULT SW1 LINE2 IN USE WT DIS SWT J4 GND BELL4 BELL3 CPU BELL FAULT SILENCE TROUBLE TROUBLE FAULT POWER ALARM ZONE 1 TRBL ALARM ZONE 2 TRBL ALARM ZONE 3 TRBL POWER ALARM ZONE 4 TRBL ZEM Power-Limited 24VDC, 12VDC, and 27.6VDC RELAY 1 ALARM ZONE 1 TRBL ALARM ZONE 2 TRBL ZEM NC COM RELAY 1 NC ZRM NO RELAY 3 NC COM NO NO NC COM NO NC RELAY 2 ZRM COM NO RELAY 3 NC COM NO RELAY 4 RELAY 4 NC NC NC COM COM NO NO NO ZONE 4 B+ B- NEG ALARM ZONE 4 TRBL COM Zone Relay Module Circuits TB1 TB1 ZONE 3 B+ B- Z5 IN TRB IN +24V ALARM ZONE 3 TRBL RELAY 1 COM COM TB1 ZONE 2 B+ B- Z4 IN NC RELAY 2 RELAY 4 ZONE 1 BB+ Z3 IN ALARM ZONE 2 TRBL NO COM NO RELAY 3 Z2 IN ALARM ZONE 1 TRBL ZEM NC NC ZRM Z1 IN POWER ALARM ZONE 4 TRBL COM NO RELAY 2 LOW LOW BELL1 BELL2 DET NO AC NO BATT TROUBLE TROUBLE MAINT ALARM ZONE 3 TRBL PROGRAM Databus Connector ZONE 1 BB+ ZONE 2 B+ B- ZONE 3 B+ B- ZONE 4 B+ B- ZONE 1 BB+ ZONE 2 B+ B- ZONE 3 B+ B- ZONE 4 B+ B- Power-Limited (Zones 2-13) Initiating Circuits Cable Tie Holder Install Tie Wrap Here Cabling Figure 4.1a Power-Limited Routing with DAC 34 LINE1 IN USE NORM Connectors from Power Supply Sentrol 1-800-547-2556 Power-Limited (Bell Circuit, #2 and #4) Power-Limited (Aux Power and Power Booster Circuits) Power-Limited Zone 1 Initiating Circuits (NAC Circuit #1 and #3) 120VAC Earth Ground For Connection to Power-Limited Sources Only NEG DRILL TEST - PWR + SWITCH AUX NEG BOOSTER AUX12/24 12/24 AA+ BELL 2 BB+ BELL 2 AA+ BELL 1 BB+ BELL 1 AA+ ZONE 1 B+ BZONE 1 COMMON ALARM COMMON TROUBLE NO COM NC NC COM NO LEM/LRM Circuits A- A- B+ A+ BBELL 4 A+ BBELL 3 B+ BELL EXPANDER LRM/LEM J2 LAMP TEST GREEN WHITE +12V DAT A DAT B NEG Drill Test Common Alarm and Common Trouble Contacts TROUBLE LEM/LRM NORMAL LEM BMB DISCONNECT Battery Connection Circuits LEM B+ NORM Connectors from Power Supply Databus Connector B- WT DIS SWT GND BELL4 BELL3 CPU BELL FAULT SILENCE TROUBLE TROUBLE FAULT POWER ALARM ZONE 1 TRBL ALARM ZONE 2 TRBL ALARM ZONE 3 TRBL POWER ALARM ZONE 4 TRBL ZEM Power-Limited 24VDC, 12VDC, and 27.6VDC ALARM ZONE 1 TRBL ALARM ZONE 2 TRBL RELAY 2 RELAY 1 ALARM ZONE 4 TRBL ZEM NC COM RELAY 1 COM NO NO NC NC RELAY 2 NC ZRM NO RELAY 3 RELAY 2 COM NC COM COM NO NO RELAY 4 ZRM COM NO RELAY 3 NC COM NO RELAY 4 RELAY 4 NC NC COM COM NO NO NO ZONE 4 B+ B- Zone Relay Module Circuits TB1 TB1 NC COM TB1 ZONE 3 B+ B- ALARM ZONE 3 TRBL NO NO ZONE 2 B+ B- ALARM ZONE 2 TRBL NC COM RELAY 3 ALARM ZONE 1 TRBL NC COM RELAY 1 ZONE 1 BB+ POWER ALARM ZONE 4 TRBL ZEM NC ZRM LOW LOW BELL1 BELL2 DET NO AC NO BATT TROUBLE TROUBLE MAINT ALARM ZONE 3 TRBL ZONE 1 BB+ ZONE 2 B+ B- ZONE 3 B+ B- ZONE 4 B+ B- ZONE 1 BB+ ZONE 2 B+ B- ZONE 3 B+ B- ZONE 4 B+ B- Power-Limited (Zones 2-13) Initiating Circuits Cable Tie Holder Install Tie Wrap Here Cabling Figure 4.1b Power-Limited Routing with LEM/LRM Sentrol 1-800-547-2556 35 • The ground connection to the ESL 2501 is made via the green wire of the FACP power supply. Using a Listed splice connector, secure a minimum 14 gauge solid ground wire to the green wire, the earth ground connection, on the control panel. Attach the earth ground wire to a bonded earth ground. Be sure to keep the wire runs short and avoid 90o or sharp turns. Bends must have a minimum radius of eight inches. The ground wires must be routed separately and toward the earth. Always use eight-foot copper clad ground rods. Never run parallel to metal without properly bonding to that metal. Verify wire sizes are adequate for all notification and initiating circuits. The maximum allowable initiating zone resistance is 30 Ohms. See Figure 4.1c below: Gauge Ohms per 1000 Ft @ 20OC of single conductor copper wire 12 1.6 14 2.5 16 4.0 18 6.4 20 10 22 16 • Run initiating device circuit wires separately. Most supervised circuits use voltage or current sensing initiating device methods that are very sensitive to induced voltages on the wiring. Therefore, under no circumstances run AC power, speaker, public address, intercom, or switch control wiring with inductive loads in the same conduit or the immediate vicinity of the control wiring. • Do not overlook adequate lightning protection. Lightning damage commonly occurs from four sources: 1. Through alarm loop wiring 2. Through AC power inputs 3. Through telephone connections (if used) 4. Through earth ground or power ground connections. Figure 4.1c Wire Resistance Table Many audible/visual notification appliances cannot tolerate more than a 20% voltage drop from the specified device voltages. See Figure 4.1d below to determine maximum distance for wire gauge used. Total current device Max. ft. of paired wire from B+ to EOL resistor load (Amps) 18AWG 16AWG 14AWG 12AWG .100 1500 2500 4000 6200 .500 300 500 800 1290 1.000 150 250 400 620 Figure 4.1d Alarm Notification Appliance Circuit (NAC) Wire Size Table (Maximum voltage drop allowable: 2VDC) • • 36 Incoming AC voltage should be stable at a nominal 120 Volts. This is especially important in new construction where incoming power may be high or unstable with temporary connections often causing large, inductive voltage spikes. Ground the system properly. All of the voltage transient suppression in the ESL 2501 Fire Alarm Control Panel is referenced to earth ground. It is important that the earth ground connection of the FACP be of the lowest possible impedance and that the possibility of voltage differences between the FACP ground and that of the telephone and public utility power systems be minimized. For this reason the ideal ground for the fire alarm panel is the “unified earth ground”. A unified earth ground bonds together the ground rods for the power lines, telephone, and fire alarm control panel. See Figure 4.1e. This reduces the chance of step voltage blowout, a problem that may occur during lightning strikes. Refer to NEC Article 250 for proper grounding requirements. The ESL 2501 uses state-of-the-art suppression techniques to minimize the potential for damage due to lightning via each of these routes. However, this does not obviate the need to ensure that proper lightning suppression equipment has been installed at the point where both the public utility power and telephone service enter the building. Refer to Article 250 of the NEC for these criteria. There is no known protective device available which is capable of protecting equipment from damage caused by “direct hit” strikes of lightning due to extremely high energy released (10 million to 100 million Volts @ 10,000 to 30,000 Amps). The effects of the electro-magnetic pulse (EMP) from a lightning strike can be minimized by avoiding running wiring long distances across the ceiling or roof of a building prone to lightning strike or along vertical structural steel members expected to conduct lightning currents. Lightning protection designed, installed and maintained in accordance with the requirements of NFPA 77 will minimize the effects of a lightning strike on the building structure as well as the fire alarm system. Additional protection is suggested in areas subject to above average lightning activity or induced voltage spikes and fluctuations due to power line load switching. Sentrol 1-800-547-2556 Incoming Power Lines Control Panel Control Panel Earth Ground Incoming Phone Lines 4.3 ALARM INITIATING DEVICES This section describes how to field wire initiating devices such as smoke detectors, pull stations, heat detectors, and waterflow alarm devices. Each zone may be programmed individually; refer to Programming, Section 5.0. Refer to Figures 4.0a & 4.0b for Class B (Style B) wiring. Power Line Earth Ground Phone Line Earth Ground Unified Earth Ground with Bonded Ground Rods 4.3.1 TWO-WIRE SMOKE DETECTORS Figure 4.1e Unified Earth Ground NOTE: 4.2 FIELD WIRING CHECKOUT PROCEDURES • Connect only two-wire smoke detectors UL Listed as compatible to the 2501 (FACP). Refer to Appendix A. • Two-wire detectors receive their power directly from the zone terminals and transmit the alarm signal through the same wires. Be certain to observe polarity when installing detectors. • Up to twenty (20) detectors may be wired to each zone. All initiating devices must be wired correctly for proper supervision with an end-ofline 2.7K Ω 1/2W resistor (provided) installed after the last device. • Wiring the ESL 521 Series two-wire detector with automatic maintenance reporting is the same as wiring standard two-wire detectors and the CleanMe® signal is automatically monitored. Up to twenty (20) ESL 521 Series smoke detectors may be wired to each zone. Refer to the documentation included with the ESL 521 Series detector for additional installation instructions. Note that an ESL 505 module is not required for the 2501 (FACP) zones. NOTE: MAKE SURE THAT AC AND BATTERY POWER ARE DISCONNECTED BEFORE PROCEEDING. 1. Test all field wiring before connecting any equipment. A. Insure no unwanted voltages are present on circuit conductors and ground. They are a hazard and may prevent proper system operation. B. All wiring except those intentionally and permanently grounded must be tested for isolation from ground using an insulation testing device such as a “Megger”. NOTE: Caution must be exercised when using voltage generating test instruments such as a “Megger”. Damage to equipment could result if the equipment is connected (wired) during wiring tests. C. 2. 3. All wiring, other than those intentionally connected together, must be tested for conductor-to-conductor isolation using an insulation testing device. With each circuit pair short-circuited at the end of the circuit, measure circuit resistance with an Ohmmeter. Perform testing as described previously after any addition, deletion, or mechanical or electrical damage to the system has occurred. See Figures 4.0a & 4.0b for Class B (Style B) connection to the panel. 4.3.2 FOUR-WIRE SMOKE DETECTORS NOTE: • Four-wire detector power is supplied by “SWITCHED AUX 12/24”. DO NOT exceed 1.0 Amp total between “SWITCHED AUX 12/24” AND “AUX 12/24”. When in battery saver mode, do not exceed 0.5 amp total. • Always supervise four-wire detector power with an end-of-line power supervisory device (ESL model 204-12/24 V) after the last unit. See Figures 4.0a & 4.0b for Class B (Style B) connection to the panel. Sentrol 1-800-547-2556 37 NOTE: There are two important cautions that should be observed. First, if the detectors being used are equipped with integral Trouble (Fault) relay contacts these contacts must be wired such that the first Trouble (Fault) contact is beyond (further from the control panel) the last Alarm contact in the circuit. Second, the battery saver function drops the system operating power supply to 12 volts, DC Be certain that the detectors being used will operate at that potential. If the battery saver function is switched off the switched auxiliary power potential will remain at 24 volts. 4.3.3 SPRINKLER SYSTEM WATERFLOW AND SUPERVISORY DEVICES Normally open contact type waterflow alarm devices may be connected, along with conventional manual alarm stations or heat detectors. All zones to which waterflow alarm devices are connected must be programmed so that the system alarm indicating devices cannot be silenced. See Programming, Section 5.0. Supervisory signals for status reporting of waterflow control valves, supplies, etc. must be connected to a separate zone, and programmed for supervisory status. See Programming, Section 5.0. 4.4 ALARM NOTIFICATION APPLIANCES Use only polarized UL Listed compatible notification appliances rated for 24 VDC (see list of devices in Appendix A). See Figures 4.0a & 4.0b for Class B (Style Y) connection to the panel. The BMB provides two notification appliance circuits that may be expanded to four (two additional) with the ESL2500-BELL. Refer to Figure 4.0a for wiring indicating devices to the BMB. 4.5 ZONE EXPANSION MODULE (ZEM) CONNECTION The Zone Expansion Module (ZEM) allows for the addition of up to 24 initiating device circuits when the four circuit, Class B modules are used. Since there is one initiating device circuit integral with the BMB, this results in a total capacity of 25 initiating device circuits per ESL 2501 FACP. Refer to Figure 1.4, Custom Panel Building Table for the available ZEM add-on configurations. The ESL2501 Fire Alarm System enclosure can accommodate three (3) ZEMs. When the 2501 is configured with additional ZEMs they are housed in an additional enclosure, part number 2500-SH. 4.5.1 ESL 2502-ZEM AND ESL 2504-ZEM The ESL 2502-ZEM is a two zone Class B expander module and the ESL 2504-ZEM is a four zone Class B expander module. Refer to Section 3.5, Installing the ZEM, BMB, and DAC for correct installation of the ZEM card. Connect the left most databus connector on the ZEM to the databus connector on the BMB or to the right most databus connector on a previously installed ZEM using the provided six inch 4 pin to 4 pin cable assembly. Assure that all unused zones are terminated with a 2.7KΩ 5% end-of-line resistor (provided). See Figures 4.0a & 4.0b for Class B (Style B) wiring. For zone type selection see System Programming, Section 5.2. When using multiple 2502 Class B zone expansion modules, it will be necessary to leave some panel zones unused to ensure that the modules LED’s line up with the correct zone identifiers on the front panel display. For example, if two 2502-ZEM’s are used, zones 2 and 3 will be used, then 4 and 5 will be skipped, and zones 6 and 7 will be used for the second 2502-ZEM. Please call Sentrol Technical Services at 1-800-800-2027 with any questions. NOTE: For best zone LED alignment results, do not use multiple two zone expansion modules (2502-ZEM) when a four zone module (2504-ZEM) can be used. NOTE: Maximum notification current is 1.5 Amps per notification appliance circuit; TOTAL OPERATING CURRENT CANNOT EXCEED 6.0 AMPS. Choose the correct wire size so that the maximum voltage drop of 2 VDC at furthest device on circuit is not exceeded. (see Figure 4.1c). 38 Sentrol 1-800-547-2556 4.6 SUPPLEMENTARY CONTACTS CONNECTION 4.7 CONNECTION TO SUPERVISING STATION FIRE ALARM SYSTEMS This section describes how to wire Supplementary Alarm and Trouble Contacts and the optional Zone Relay Modules. NOTE: Supplementary Alarm and Trouble Contacts are for power-limited applications only. (See Section 4.1, Installation Recommendations/Precautions). The ESL 2501 FACP is designed to permit transmission of fire alarm signals from the protected premises to a Supervising Station Fire Alarm Panel at a Central Station or Remote Supervising Station by means of an add-on module that utilizes Digital Alarm Communicator (DAC) technology, the 2500-DAC. 4.6.1 SUPPLEMENTARY ALARM CONTACTS 4.7.1 CONNECTING THE 2500-DAC Dry, Form “C” contacts are provided for controlling supplementary alarm functions from the BMB. Contacts are rated 2A @ 30 VDC resistive. The terminals are Common Alarm NC, COM, and NO. Contacts transfer in alarm. The 2500-DAC, Digital Alarm Communicator, is installed in a dedicated location, adjacent to the BMB of the ESL 2501 Fire Alarm Control Panel. It provides for the connection of both the primary and stand-by telephone lines via the standard telco connectors. Figure 4.7.1 illustrates the wiring required to provide signaling to a Supervising Station Fire Alarm System from a single ESL 2501 FACP. 4.6.2 SUPPLEMENTARY TROUBLE CONTACTS Dry, Form “C” contacts are provided for controlling supplementary trouble (fault) functions from the BMB. Contacts are rated 2A @ 30 VDC resistive. The terminals are Common Trouble NC, COM, and NO. The trouble relay is normally energized and will de-energize if AC and/or battery power or any other system trouble occurs. For use with door holders, the supplementary trouble contacts are programmable for transfer on loss of AC only. Additionally, if the system is programmed for use with a 2500-DAC, the contacts are automatically programmed so that they will not transfer on loss of AC only. The batteries must also be low. This provides the required delayed reporting at loss of AC. See Section 5.0 Programming. 4.6.3 ZONE RELAY MODULE (ZRM) (OPTIONAL) The Zone Relay Module (ZRM) is a zone follower and each relay follows its corresponding zone on a Zone Expansion Module (ZEM). Zone 1 on the BMB does not have a corresponding Zone Relay Module and will only trigger the Common Alarm relay. The ZRM’s plug directly into the ZEM’s and only require wiring the terminals labeled NO, COM, and NC. Each relay has dry, Form “C” contacts rated 2A @ 30 VDC resistive. NOTE: Circuits connected to a ZRM must be power-limited. Sentrol 1-800-547-2556 39 Phone Lines Ground Fault Cable B+ BZONE 1 JP2 IN FOR ZONE 1 CLASS B J5 J5 BMB LINE 2 LINE 1 J2 J3 DAC J1 Cable Assembly DATABUS Databus Connector LRM/LEM J13 GREEN WHITE +12V DAT A DAT B NEG JP3 ALIVE TRBLE LINE1 FAULT LINE2 FAULT SW1 LINE1 IN USE PROGRAM LINE2 IN USE OW BELL1 BELL2 DET ATT TROUBLE TROUBLE MAINT Z1 IN Z2 IN Z3 IN Z4 IN Figure 4.7.1 2500-DAC Installation Diagram 40 Sentrol 1-800-547-2556 Z5 IN TRB IN +24V NEG J4 5.1.1 PROGRAMMING INDICATORS 5.0 PROGRAMMING 5.1 INTRODUCTION At the heart of the ESL 2501 Fire Alarm Control Panel is a microcomputer that controls all system functions and the response of the system to incoming signals. A portion of the microcomputer program is a function map that serves two purposes. First it tells the microcomputer what types of modules are installed, ensuring the correct response when a signal is generated by a given module. Second, it controls how the system will respond to a given in-coming signal condition. Items that can be programmed are: types of zone inputs, bell-zone associations, bell cadence definitions, battery saver mode, AC frequency (60Hz or 50Hz), zone expanders installed, communicator type, number of supervised keypads, keypad ability to silence the panel, time of day, communicator information, zone names, and passcodes. The programming buttons and indicators allow the installer to modify the most commonly used items in the function map. A keypad allows modification of all items in the function map (with the appropriate passcode. See the keypad manual for more details). Section 5.6, Programming Matrix indicates which items are only programmable from the keypad. When programming the function map from the panel, flip the daughter board’s overlay over to facilitate programming (see Figure 5.1b). All button and LED references in the programming sections refer to the ON-BOARD PROGRAMMING INTERFACE side of the overlay. Also, install the PROGRAMMING LOCATION LEDS guide on the Basic Master Board (BMB). SYS SUP D3 PROG UP SW4 D2 RESET VALUE VALUE SW7 ZONE 1 ALARM J1 SYS TRBL DOWN D5 SW3 SW2 D1 SW1 D6 SYS ALM J2 AC PWR The 64, 32, 16, 8, 4, 2, and 1 yellow LEDs (located on the BMB in the lower right-hand corner) display the current programming location in the programming mode. A location LED overlay is included in the accessories envelope included with each panel. 5.1.2 PROGRAMMING BUTTONS The Basic Master Board (BMB) has 1 push-button (PROG) to activate and terminate the system programming mode, 1 push-button (LOC/VAL) to switch between location and value, and 2 push-buttons (UP, DOWN) to increment or decrement the location/value (see Figure 5.1a). 5.2 SYSTEM PROGRAMMING The Basic Master Board (BMB) automatically recognizes when a Zone Expander Module (ZEM) is added to the panel and programs the module automatically based upon the module’s address. If two or more modules are set to the same address, the 2501 (FACP) will indicate trouble communicating with the modules and will not be able to indicate alarms or troubles correctly. Likewise, if a ZEM module is removed without changing the function map to inform the panel that it is not installed, the panel will indicate trouble communicating with the module. D4 ZONE 1 TROUBLE LOCATION TRBL LOCATION UP DOWN ALARM SW8 The 2501 (FACP) has 16 LEDs that are used for displaying the system status. Of these, 13 are used for displaying information while in the front panel programming mode. The Location (LOC) green LED (located on the daughter board) starts flashing when the programming mode is entered. It is used to indicate that the UP/DOWN buttons will affect the programming location number. The VALUE red LED (located on the daughter board) flashes to indicate that the UP/DOWN buttons affect the location’s value. The 1 and 2 red LEDs, 4 and 8 yellow LEDs (located on the daughter board) display the programmed value of the current location in the programming mode. SW5 To program the panel using the Basic Master Board (BMB): SW6 Figure 5.1a BMB Daughter Board Layout 1. Flip the daughter board’s overlay over so it displays the side marked ON-BOARD PROGRAMMING INTERFACE. Install the PROGRAMMING LOCATION LEDS overlay on the Basic Master Board (BMB). If desired, place the location LED overlay on the LEDs. 2. Push and hold the PROG button until the LOC LED begins flashing (approximately 5 seconds). When the system goes into programming mode, it displays Location 1 and the current value. ON-BOARD PROGRAMMING INTERFACE LED’s 1 - 8 below = Value LED’s LED’s on BMB = Location LED’s 1 LOC PROG 8 VALUE LOC/VAL TOGGLE UP DOWN 4 2 Figure 5.1b On-Board Programming Interface (Daughter Board Overlay turned over) Sentrol 1-800-547-2556 41 3. 4. 5. Press the LOC/VAL button to switch between location and value. When the LOC LED is flashing, pressing the UP or DOWN buttons will increment or decrement the location displayed. When the VALUE LED is flashing, pressing the UP or DOWN buttons will increment or decrement the value of the selected location. (See Section 5.6, Programming Matrix, for programmable values of each location). By pushing and holding the UP or DOWN button, you may quickly scroll through the location/value numbers. To exit out of programming mode, press and hold the PROG button until the LOC or VALUE LEDs stop flashing (approximately 5 seconds). To save any value changes made, move to a new location. The changes to the current location is not saved if the system times out (10 minutes without a button press) or if programming mode is exited by using the PROG button. All changes made to other locations are saved, only the current location changes are not saved. 5.3 TIME & DATE PROGRAMMING The time and date are programmed through Basic Master Board programming. The date format must be entered as m/dd/yyyy. The time must be set in military time format, 24:00 hours. (See programming example below.) See Section 5.6, Programming Matrix for the time and date programming locations and default values. EXAMPLE: To set the date to October 9, 1997 and the time to 5:35 pm LOCATION 64 32 16 8 4 2 1 VALUE 8 4 2 1 Month (10) 1st Digit of Day (0_) 2nd Digit of Day (_9) 1st Digit of Year (1_ _ _) The Panel automatically exits out of programming mode if no activity occurs for 10 minutes. If an alarm occurs during programming, the panel automatically exits out of programming. To program the function map with a keypad, see the ESL 2500 Keypad Instruction Manual 64812808. See Section 5.6, Programming Matrix for the programming locations and default values. 2nd Digit of Year (_9_ _) 3rd Digit of Year (_ _9_) 4th Digit of Year (_ _ _7) 1st Digit of Hour (1_) 2nd Digit of Hour (_7) 1st Digit of Minute (3_) NOTE: While in the programming mode, all other indicating devices will operate as normal. If a zone goes into alarm while you are in the programming mode, the alarm sounds and the panel automatically exits out of programming mode. 2nd Digit of Minute (_ 5) For example, the month is contained at location 80. The location is indicated by the LEDs that are lit from the table above, 64 + 16 = 80. The value is indicated by the LEDs that are lit; 8 + 2 = 10 or October. Figure 5.3 Time & Date Programming Example NOTE: If an invalid date is entered, the 2501 (FACP) changes the incorrect value to the closest valid value before saving changes. There is no visible or audible indication given if an incorrect value is entered during time and date programming. 42 Sentrol 1-800-547-2556 5.4 BATTERY SAVER PROGRAMMING The 2501 (FACP) implements a programmable feature called the battery saver mode. The purpose of this mode is to allow the panel to utilize smaller, less expensive batteries while still meeting standby requirements. This mode is selected by programming the panel for battery saver mode (see Section 5.2 System Programming and Section 5.6 Programming Matrix). After selection of this feature the operation is completely transparent to the user. The operation of the panel when battery saver mode is selected is as follows. The panel will automatically switch the batteries into parallel upon loss of AC or a low AC condition. The connection of these batteries in parallel effectively doubles the standby capacity of the batteries. The batteries will remain in this condition until AC is restored or the level is sufficient to restore normal operation. While the panel is in standby on the secondary source (batteries in parallel), the panel continues to operate normally. If an alarm occurs, the panel automatically switches the batteries back to a series configuration. This provides the 24 VDC alarm voltage for the indicating (NACs). NOTE: The AUX 12/24 and SWITCHED AUX 12/24 are always 12 VDC if battery saver mode is selected and 24 VDC if battery saver mode is not selected. The proper battery calculations must be performed based on the battery saver mode selection (see Appendix B). ESL manufactures a complete line of 12V devices including 12V door holders and smoke detectors. 5.5 CLEANME® MODE PROGRAMMING The 2501 (FACP) supports a unique feature implemented by the ESL 521 series Two-Wire CleanMe ® Smoke Detector. This feature allows the control panel to receive a signal from the 521 series detector, notifying the control panel that the detector has drifted outside of its UL Listed sensitivity range or has a hardware fault problem. The CleanMe® signal enables the installer to receive a warning signal at the panel and the Supervising Station if the system is monitored. This gives the installer time to clean the detector by replacing the optical chamber with a new one thereby reducing unwarranted alarms. There is no action required to implement this feature. The control panel automatically recognizes the signal if present and will turn on the detector maintenance LED and annunciate a system trouble. If a DAC is present, the Supervising Station, if monitored, will be notified. Programming Value LEDs (4) (binary values are indicated on each LED) +12V TROUBLE M NC 1 VALUE LOC PROG 8 LOC/VAL TOGGLE 4 UP DOWN 2 1 BMB Programming Switch 64 32 16 8 4 2 1 LOW BELL1 BELL2 DET BELL4 BELL3 GND LOW CPU BELL FAULT SILENCE TROUBLE TROUBLE FAULT NO AC NO BATT TROUBLE TROUBLE MAINT Programming Location LEDs (7) (binary values are indicated on each LED) Figure 5.6 LED Location Diagram for Programming Location and Programmed Value Sentrol 1-800-547-2556 43 5.6 BMB PROGRAMMING MATRIX Programming Locations Loc Description Default 64 32 Programmed Value 16 8 4 2 1 Value Description 0 Normal Fire 1 Water Flow 2 Fire Supervisory 3 Non-Latching 4 Verified Fire 5 Power Boost (Zone 1 only) 0 None 1 Bell 1 2 Bell 2 4 Bell 3 8 Bell 4 8 4 Zone Definitions 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24 Zone 25 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Zone Bell Association 26 27 28 29 30 31 32 33 34 35 36 37 38 39 44 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 15 15 15 15 15 15 15 15 15 15 15 15 15 15 For multiple bells, add together. ex: Bells 1 & 2 (1 + 2 = 3) Sentrol 1-800-547-2556 2 1 Programming Locations Loc Description Default 64 32 Programmed Value 16 8 4 2 1 Value Description 8 4 2 1 Zone Bell Association (cont.) 40 41 42 43 44 45 46 47 48 49 50 Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24 Zone 25 15 15 15 15 15 15 15 15 15 15 15 Notification Appliance Circuit Definition 51 52 53 54 Bell 1 Definition Bell 2 Definition Bell 3 Definition Bell 4 Definition 1 1 0 0 0 Not Used 1 Temporal Code 3 2 March Time 3 California March 4 Steady 5 Non-Silenceable Steady 6 Latching Non-Silenceable Steady 0 60 Hz Operation 1 50 Hz Operation 0 Not Installed 1 ZEM 0 Not Installed 1 2500-DAC 2 LEM 3 LRM 4 Dual LRM Battery Saver Mode 55 Batt Saver Mode 0 AC Cycles 56 AC Sync 0 Zone Expander Module Definition 57 58 59 60 61 62 Expander 1 Expander 2 Expander 3 Expander 4 Expander 5 Expander 6 1 1 1 1 1 1 Communicator Type 63 Communicator Type 0 Sentrol 1-800-547-2556 45 Programming Locations Loc Description Default 64 32 Programmed Value 16 8 4 2 1 Value Description 8 4 Common Trouble Relay 64 Function 0 Trouble Resound Time 65 Resound Time 1 Supervised Keypads 66 Keypads 0 Normal 1 AC Loss Only 1 15 Minutes 2 1 Hour 3 4 Hours 4 24 Hours 0 None 1 Keypad 1 2 Keypad 2 4 Keypad 3 0 For multiple keypads, add together. ex: Keypads 1 & 2 (1 + 2 = 3) 0 1 2 4 8 Remote Annunciators 67 RAs 0 None RA 1 RA 2 RA 3 RA 4 For multiple RAs, add together. ex : RAs 1 & 2 (1 + 2 = 3) Keypad Silence and Reset 68 Silence & Reset 1 0 Disable 1 Enable 0 Disable 1 Enable Ground Fault Detection 69 Ground Fault Detection 0 Reserved 70 Reserved 0 71 Reserved 0 72 Reserved 0 73 Reserved 0 74 Reserved 0 75 Reserved 0 76 Reserved 0 77 Reserved 0 78 Reserved 0 79 Reserved 0 46 0 Sentrol 1-800-547-2556 2 1 Programming Locations Loc Description Default 64 32 Programmed Value 16 8 4 2 1 Value Description 8 4 2 1 0 Date Programming 1 80 Month (m/dd/yyyy) 1 81 1st Digit of Day (m/dd/yyyy) 0 82 2nd Digit of Day (m/dd/yyyy) 1 83 1st Digit of Year (m/dd/yyyy) 1 84 2nd Digit of Year (m/dd/yyyy) 9 85 3rd Digit of Year (m/dd/yyyy) 9 4th Digit of Year (m/dd/yyyy) 7 86 2 3 4 5 6 7 8 9 10 11 12 Time Programming 0 1 87 1st Digit of Hour (HH:MM) 0 2nd Digit of Hour (HH:MM) 0 1st Digit of Minute (HH:MM) 0 2 3 88 89 90 4 2nd Digit of Minute 0 (HH:MM) 5 6 7 8 9 Sentrol 1-800-547-2556 47 The Following Locations Are Only Accessible With a Keypad Loc Description Default Value Description Communications 91 Auto Comm Test on Power-up 0 0 1 92 Auto Comm Test Hour 0 0 - 23 93 Auto Comm Test Minute 0 0 - 59 94 Days Between Auto Comm Tests 0 0 1 - 255 95 96 97 98 99 Reserved Reserved Reserved Reserved Reserved 0 0 0 0 0 0 0 0 0 0 100 101 102 103 Zone Alarm Report Sequence Zone Trouble Report Sequence System Trouble Report Sequence System Event Report Sequence 3 3 3 3 0 1 2 3 4 5 6 7 8 9 10 11 Disabled Enabled Disable Auto Comm Test Number of Days No Report Account 1 Account 2 Account 1, then 2 if 1 fails Account 2, then 1 if 2 fails Account 1 and 2 Account 3 Account 3 and 1 Account 3 and 2 Account 3 and 1, then 2 if 1 fails Account 3 and 2, then 1 if 2 fails Account 3 and 1 and 2 104 - 109 Account Number 1 000000H 000000H - FFFFFFH (0H - FH per digit) 110 - 115 Account Number 2 000000H 000000H - FFFFFFH (0H - FH per digit) 116 - 121 Account Number 3 000000H 000000H - FFFFFFH (0H - FH per digit) ZRM Override 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 48 Zone 1, ZRM 1 Zone 1, ZRM 2 Zone 1, ZRM 3 Zone 1, ZRM 4 Zone 1, ZRM 5 Zone 1, ZRM 6 Zone 2, ZRM 1 Zone 2, ZRM 2 Zone 2, ZRM 3 Zone 2, ZRM 4 Zone 2, ZRM 5 Zone 2, ZRM 6 Zone 3, ZRM 1 Zone 3. ZRM 2 Zone 3, ZRM 3 Zone 3, ZRM 4 Zone 3, ZRM 5 Zone 3, ZRM 6 Zone 4, ZRM 1 Zone 4, ZRM 2 Zone 4, ZRM 3 Zone 4, ZRM 4 Zone 4, ZRM 5 Zone 4, ZRM 6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Sentrol 1-800-547-2556 0 No Overrides 1 Override Relay 1 2 Override Relay 2 4 Override Relay 3 8 Override Relay 4 For Multiple relays, add together. ex : Relays 1 & 3 (1 + 4 = 5) The Following Locations Are Only Accessible With a Keypad Loc Description Default Value Description 0 No Overrides 1 Override Relay 1 2 Override Relay 2 4 Override Relay 3 8 Override Relay 4 ZRM Override (cont.) 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 Zone 5, ZRM 1 Zone 5, ZRM 2 Zone 5, ZRM 3 Zone 5, ZRM 4 Zone 5, ZRM 5 Zone 5, ZRM 6 Zone 6, ZRM 1 Zone 6, ZRM 2 Zone 6, ZRM 3 Zone 6, ZRM 4 Zone 6, ZRM 5 Zone 6, ZRM 6 Zone 7, ZRM 1 Zone 7. ZRM 2 Zone 7, ZRM 3 Zone 7, ZRM 4 Zone 7, ZRM 5 Zone 7, ZRM 6 Zone 8, ZRM 1 Zone 8, ZRM 2 Zone 8, ZRM 3 Zone 8, ZRM 4 Zone 8, ZRM 5 Zone 8, ZRM 6 Zone 9, ZRM 1 Zone 9, ZRM 2 Zone 9, ZRM 3 Zone 9, ZRM 4 Zone 9, ZRM 5 Zone 9, ZRM 6 Zone 10, ZRM 1 Zone 10, ZRM 2 Zone 10, ZRM 3 Zone 10, ZRM 4 Zone 10, ZRM 5 Zone 10, ZRM 6 Zone 11, ZRM 1 Zone 11, ZRM 2 Zone 11, ZRM 3 Zone 11, ZRM 4 Zone 11, ZRM 5 Zone 11, ZRM 6 Zone 12, ZRM 1 Zone 12. ZRM 2 Zone 12, ZRM 3 Zone 12, ZRM 4 Zone 12, ZRM 5 Zone 12, ZRM 6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Sentrol 1-800-547-2556 49 The Following Locations Are Only Accessible With a Keypad Loc Description Default Value Description 0 No Overrides 1 Override Relay 1 2 Override Relay 2 4 Override Relay 3 8 Override Relay 4 ZRM Override (cont.) 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 50 Zone 13, ZRM 1 Zone 13, ZRM 2 Zone 13, ZRM 3 Zone 13, ZRM 4 Zone 13, ZRM 5 Zone 13, ZRM 6 Zone 14, ZRM 1 Zone 14, ZRM 2 Zone 14, ZRM 3 Zone 14, ZRM 4 Zone 14, ZRM 5 Zone 14, ZRM 6 Zone 15, ZRM 1 Zone 15, ZRM 2 Zone 15, ZRM 3 Zone 15, ZRM 4 Zone 15, ZRM 5 Zone 15, ZRM 6 Zone 16, ZRM 1 Zone 16. ZRM 2 Zone 16, ZRM 3 Zone 16, ZRM 4 Zone 16, ZRM 5 Zone 16, ZRM 6 Zone 17, ZRM 1 Zone 17, ZRM 2 Zone 17, ZRM 3 Zone 17, ZRM 4 Zone 17, ZRM 5 Zone 17, ZRM 6 Zone 18, ZRM 1 Zone 18, ZRM 2 Zone 18, ZRM 3 Zone 18, ZRM 4 Zone 18, ZRM 5 Zone 18, ZRM 6 Zone 19, ZRM 1 Zone 19, ZRM 2 Zone 19, ZRM 3 Zone 19, ZRM 4 Zone 19, ZRM 5 Zone 19, ZRM 6 Zone 20, ZRM 1 Zone 20, ZRM 2 Zone 20, ZRM 3 Zone 20, ZRM 4 Zone 20, ZRM 5 Zone 20, ZRM 6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Sentrol 1-800-547-2556 The Following Locations Are Only Accessible With a Keypad Loc Description Default Value Description 0 No Overrides 1 Override Relay 1 2 Override Relay 2 4 Override Relay 3 8 Override Relay 4 00H - FFH 00H - Not Reported ZRM Override (cont.) 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 Zone 21, ZRM 1 Zone 21. ZRM 2 Zone 21, ZRM 3 Zone 21, ZRM 4 Zone 21, ZRM 5 Zone 21, ZRM 6 Zone 22, ZRM 1 Zone 22, ZRM 2 Zone 22, ZRM 3 Zone 22, ZRM 4 Zone 22, ZRM 5 Zone 22, ZRM 6 Zone 23, ZRM 1 Zone 23, ZRM 2 Zone 23, ZRM 3 Zone 23, ZRM 4 Zone 23, ZRM 5 Zone 23, ZRM 6 Zone 24, ZRM 1 Zone 24, ZRM 2 Zone 24, ZRM 3 Zone 24, ZRM 4 Zone 24, ZRM 5 Zone 24, ZRM 6 Zone 25, ZRM 1 Zone 25, ZRM 2 Zone 25, ZRM 3 Zone 25, ZRM 4 Zone 25, ZRM 5 Zone 25, ZRM 6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Pulse Report Codes 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 Zone 1 Alarm Zone 2 Alarm Zone 3 Alarm Zone 4 Alarm Zone 5 Alarm Zone 6 Alarm Zone 7 Alarm Zone 8 Alarm Zone 9 Alarm Zone 10 Alarm Zone 11 Alarm Zone 12 Alarm Zone 13 Alarm Zone 14 Alarm Zone 15 Alarm Zone 16 Alarm Zone 17 Alarm Zone 18 Alarm 31h 32h 33h 34h 35h 36h 37h 38h 39h 3Ah 3Bh 3Ch 3Dh 3Eh 3Fh 61h 62h 63h Sentrol 1-800-547-2556 51 The Following Locations Are Only Accessible With a Keypad Loc Description Default Value Description Pulse Report Codes (cont.) 52 290 291 292 293 294 295 296 Zone 19 Alarm Zone 20 Alarm Zone 21 Alarm Zone 22 Alarm Zone 23 Alarm Zone 24 Alarm Zone 25 Alarm 64h 65h 66h 67h 68h 69h 6Ah 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 Zone 1 Trouble Zone 2 Trouble Zone 3 Trouble Zone 4 Trouble Zone 5 Trouble Zone 6 Trouble Zone 7 Trouble Zone 8 Trouble Zone 9 Trouble Zone 10 Trouble Zone 11 Trouble Zone 12 Trouble Zone 13 Trouble Zone 14 Trouble Zone 15 Trouble Zone 16 Trouble Zone 17 Trouble Zone 18 Trouble Zone 19 Trouble Zone 20 Trouble Zone 21 Trouble Zone 22 Trouble Zone 23 Trouble Zone 24 Trouble Zone 25 Trouble F3h F3h F3h F3h F3h F3h F3h F3h F3h F3h F3h F3h F3h F3h F3h F6h F6h F6h F6h F6h F6h F6h F6h F6h F6h 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 Zone 1 Restoral Zone 2 Restoral Zone 3 Restoral Zone 4 Restoral Zone 5 Restoral Zone 6 Restoral Zone 7 Restoral Zone 8 Restoral Zone 9 Restoral Zone 10 Restoral Zone 11 Restoral Zone 12 Restoral Zone 13 Restoral Zone 14 Restoral Zone 15 Restoral Zone 16 Restoral Zone 17 Restoral E3h E3h E3h E3h E3h E3h E3h E3h E3h E3h E3h E3h E3h E3h E3h E6h E6h Sentrol 1-800-547-2556 00H - FFH 00H - Not Reported 00H - FFH 00H - Not Reported 00H - FFH 00H - Not Reported The Following Locations Are Only Accessible With a Keypad Loc Description Default 339 340 341 342 343 344 345 346 Zone 18 Restoral Zone 19 Restoral Zone 20 Restoral Zone 21 Restoral Zone 22 Restoral Zone 23 Restoral Zone 24 Restoral Zone 25 Restoral E6h E6h E6h E6h E6h E6h E6h E6h 347 348 Ground Fault Ground Fault Restoral 349 350 Value Description 00H - FFH 00H - Not Reported 00h 00h 00H - FFH 00H - Not Reported AC Fail AC Fail Restoral FAh EAh 00H - FFH 00H - Not Reported 351 352 Low Battery Low Battery Restoral F9h E9h 00H - FFH 00H - Not Reported 353 354 Hibernation Hibernation Restoral 00h 00h 00H - FFH 00H - Not Reported 355 356 BMB Memory Fail BMB Memory Fail Restoral 00h 00h 00H - FFH 00H - Not Reported 357 358 DAC Memory Fail DAC Memory Restoral 00h 00h 00H - FFH 00H - Not Reported 359 Keypad Lockout 00h 00H - FFH 00H - Not Reported 360 361 Keypad Missing Keypad Missing Restoral 00h 00h 00H - FFH 00H - Not Reported 362 363 DAC Missing DAC Missing Restoral 00h 00h 00H - FFH 00H - Not Reported 364 365 Expander Missing Expander Missing Restoral 00h 00h 00H - FFH 00H - Not Reported 366 367 RA Missing RA Missing 00h 00h 00H - FFH 00H - Not Reported 368 369 LEM/LRM Trouble LEM/LRM Trouble Restoral 00h 00h 00H - FFH 00H - Not Reported 370 371 Bell Trouble Bell Trouble Restoral 00h 00h 00H - FFH 00H - Not Reported 372 373 Telco Trouble Telco Trouble Restoral 00h 00h 00H - FFH 00H - Not Reported 374 375 Communications Trouble Communications Trouble Restoral 00h 00h 00H - FFH 00H - Not Reported Sentrol 1-800-547-2556 53 The Following Locations Are Only Accessible With a Keypad 54 Loc Description Default 376 377 Comm Test Trouble Comm Test Trouble Restoral 00h 00h 378 System Startup 00h 379 380 Local Program Begin Local Program End 00h 00h 381 Event Log Reset 00h 382 383 RPM Begin RPM End 384 385 Value Description 00H - FFH 00H - Not Reported 00H - FFH 00H - Not Reported 00H - FFH 00H - Not Reported 00H - FFH 00H - Not Reported 00h 00h 00H - FFH 00H - Not Reported RPM Denied RPM Aborted 00h 00h 00H - FFH 00H - Not Reported 386 387 Auto Comm Test Normal Auto Comm Test Abnormal 00h 00h 00H - FFH 00H - Not Reported 388 Manual Comm Test 10h 00H - FFH 00H - Not Reported Sentrol 1-800-547-2556 5.6.1 DAC PROGRAMMING MATRIX Programming Locations Programmed Value Loc Description Default Value 1 Enable RPM 1 0 1 Disabled Enabled 2 Auto Answer Rings 5 0 15 Number of Rings Before Answer 3 Second Call Bypass Time (Sec) 40 0 255 The amount of time for the answering machine bypass time window. This allows the remote programmer to bypass an answering machine by making two calls to the premises. The first call must ring three times or less and not be answered. The answering machine bypass time window starts ten seconds after the last ring of the first call. If the first ring of the second call occurs within the answering machine bypass time window, the panel answers the second call on the first ring. Remote Programming must be enabled. 4 Disable Call Waiting 0 0 1 5 Seconds Between Attempts 1 6 Telco Lines to be Monitored 3 0 255 0 1 2 3 7 Telco L1 On Hook Time (Sec) 2 1 15 8 Telco L2 On Hook Time (Sec) 2 1 15 9 Telco L1 Off Hook Time (Sec) 3 1 15 10 Telco L2 Off Hook Time (Sec) 3 1 15 11 Telco Line 1 Dialer Type 1 0 1 2 US Pulse Touchtone Foreign Pulse 12 Telco Line 2 Dialer Type 1 0 1 2 US Pulse Touchtone Foreign Pulse 13 Telco N1 Dial Attempt 5 1 10 Maximum Dial Attempts on Phone Number 1 14 Telco N2 Dial Attempt 5 1 10 Maximum Dial Attempts on Phone Number 2 15 Telco N3 Dial Attempt 5 1 10 Maximum Dial Attempts on Phone Number 3 16 Telco N1 Reporting Format 0 0 1 2 3 4 5 Pulsed 20 baud, non-extended Pulsed 20 baud, extended Pulsed 40 baud, extended SIA Contact ID Pager Sentrol 1-800-547-2556 Description Not Disabled Disabled Time in Seconds Between Call Attempts When Reporting None Line 1 Line 2 Both Lines 55 Programming Locations Programmed Value Loc Description Default Value 17 Telco N2 Reporting Format 0 0 1 2 3 4 5 Pulsed 20 baud, non-extended Pulsed 20 baud, extended Pulsed 40 baud, extended SIA Contact ID Pager 18 Telco N3 Reporting Format 0 0 1 2 3 4 5 Pulsed 20 baud, non-extended Pulsed 20 baud, extended Pulsed 40 baud, extended SIA Contact ID Pager 19-50 Telephone Number 1 all F's 0-F 51-82 Telephone Number 2 all F's 0-F 83-114 Telephone Number 3 all F's 0-F 115-146 RPM Number all F's 0-F Description DAC 1500 Mode FM 147 Current Time - Hour 0 0 24 Set DAC Clock 148 Current Time - Minute 0 0 59 Set DAC Clock 149 Comm Test Time - Hour 12 0 24 Set Time for Auto Comm Test 150 Comm Test Time - Minute 0 0 59 Set Time for Auto Comm Test 151-154 Account Code 1 0 0 F 155-158 Account Code 2 0 0 F 159-166 Pulse Report Codes 56 0 FF 00 E0 F6 E6 F7 E7 08 FA Sentrol 1-800-547-2556 Zone Alarm Zone Restore System Trouble System Trouble Res. Tel. Line Trouble Tel. Line Trouble Res. Auto Comm Test Abnormal Comm Test 5.7.1 ZRM OVERRIDE 5.7 FUNCTION MAP DESCRIPTION Zone Definition - This defines what type of devices are connected to a zone and how the zone will respond when one or more of the devices signals an alarm condition. Zone Bell Association - This associates a NAC or group of NACs to be activated when the specified zone is in alarm. Notification Appliance Circuit Definition - Defines the cadence a NAC will use when activated. Setting the cadence to Not Used will also deactivate supervision of the NAC. Battery Saver Mode - If set to On, the batteries will be put into parallel mode to conserve power. This only happens when AC has failed and no NACs are active. AC Cycles - Specifies the frequency of the supplied AC power to be used for time-keeping. Zone Expander Module Definition - Specifies if a zone expander is installed. Communicator Type - Specifies the type of communicator installed. Normally, the relays on a ZRM are configured as alarm followers for the corresponding zones on the ZEM that the ZRM is installed. Programming zones to override a ZRM’s relays allows the installer to program the BMB to have a more sophisticated relay control rather than wiring numerous relays in parallel or serial. If no zones are programmed to override a particular ZRM relay, that relay will act as a zone follower for its associated zone. The BMB can trip multiple relays based on one zone input (relays 1, 6, 22 can activate when zone 1 goes into alarm by setting location 122 to 1, location 123 to 2, and location 127 to 2). The BMB can also have multiple zones trip the same relay (zones 3, 12, 25 can activate relay 3 when any of the three go into alarm by setting location 134 to 4, location 188 to 4, and location 266 to 4). The BMB can also be programmed for a combination of both (zones 1, 2, 3 can activate relay 1, 3 and zones 4, 5, 6 can activate relay 6, 7 by setting location 122 to 5, location 128 to 5, location 134 to 5, location 140 to 6, location 146 to 6, and location 152 to 6). One use for this ability is to have all fire zones activate relay 1 and all supervisory zones activate relay 6. All fire zones would have their associated ZRM override for ZRM 1 set to the value 1. All supervisory zones would have their associated ZRM override for ZRM 2 set to the value 2. ZEM 1 ZEM 2 ZEM 3 ZRM 1 ZRM 2 ZRM 3 Zones 2-5 Relays 1-4 Zones 6-9 Relays 5-8 Zones 10-13 Relays 9-12 ZEM 4 ZEM 5 ZEM 6 ZRM 4 ZRM 5 ZRM 6 Zones 14-17 Relays 13-16 Zones 18-21 Relays 17-20 Zones 22-25 Relays 21-24 Sentrol 1-800-547-2556 57 6.0 INITIAL ACCEPTANCE TESTING Following the installation of all of the system components and the programming of the FACP, a complete, 100% acceptance test must be performed and the results documented. A permanent record of the initial acceptance tests must be made and retained with the system documentation. Refer to Chapter 7 of NFPA 72-1996, the National Fire Alarm Code. Upon the completion of the Initial Acceptance Test, restore all circuits and system components to their design condition. Install the 2501 FACP Operating Instructions, Appendix C, in an easily accessible and readable location adjacent to the FACP. Advise the owner/operator of the site and the monitoring firm that the system is now “on-line”. If an alarm condition occurs and the sounder is on, either the SYSTEM RESET or the ALARM SILENCE push-button may be pressed. If the SYSTEM RESET push-button is pressed first, the local sounder will deactivate, the bells will silence and the system LEDs will extinguish. All zones in alarm will be reset. If the ALARM SILENCE pushbutton is pressed first, the proper system and zone LEDs and the trouble sounder will become active. If the SYSTEM RESET push-button is pressed after the alarm is silenced, the zone(s) that went into alarm will be reset. NOTE: The 2501 (FACP) uses three (3) different types of tones to distinguish between an alarm, a trouble, and a supervisory trouble. The output tones for the Sounder will be as follows: • • • Alarm tone will have a steady tone Trouble tone will have a pulsing tone Supervisory tone will have a rapid pulsing tone A. PROGRAM ZONE 1 AS NORMAL FIRE, “0”, WITH A CLASS “B” TYPE CONFIGURATION: 6.1 ALARM ZONE TESTING TEST 1 - ZONE 1 SHORTED SETUP 1. 2. 3. 4. 5. 6. 7. Connect the control to a primary power source (110 to 120 VAC). Connect the Zone One (Alarm initiating) input to Normally Open switches or Sensors. This connection must be in parallel to the 2.7k Ohm 5% end-of-line (EOL) resistor (provided). (Trouble with the circuit may occur if the resistor is connected in series). Connect the EOL, 2.7k Ohm 5% resistor (provided), to each of the Bell circuits. A Trouble Indication will occur if the EOL is not connected. Connect (observe polarity) an audible device into BELL 1 & BELL 2 terminals. This connection is in parallel to the EOL . Connect the 4-wire bus connector between the BMB and each ZEM that is to be coupled into the system. Each ZEM must have an EOL, 2.7k Ohm 5% resistor (provided), for each zone connected in order to prevent a trouble condition. Connect the batteries, minimum of two 12 Volt 7 Ah sealed lead acid batteries. Failure to connect a battery will result in a trouble condition. 1. Place a short across Zone 1 on the BMB by placing a short across the EOL at the terminals. • The system will go into alarm • The polarity of the voltage at BELL 1 and BELL 2 will reverse and pulse a Temporal 3 cadence • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Sounder will sound an alarm tone 2. Press the ALARM SILENCE button • The output at BELL 1 and BELL 2 will stop • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Trouble LED is lit • The Zone 1 Trouble LED is lit • The Sounder will change to a trouble tone 3. Press the TROUBLE SILENCE button • The Sounder will turn off • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Trouble LED is lit • The Zone 1 Trouble LED is lit 4. Remove the short across Zone 1 terminal • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Trouble LED is lit • The Zone 1 Trouble LED is off 5. Press the SYSTEM RESET button • All LEDs are off TESTING AND SYSTEM RESPONSE Visually observe the LEDs located on the Basic Master Board (BMB) to verify that no troubles, alarms, or supervisory conditions exist. If a condition is detected, check the zone LEDs to identify if the problem is zone or system related. Correct the problem and then press the SYSTEM RESET button to reset the panel and clear the condition. 58 Sentrol 1-800-547-2556 TEST 2 - ZONE 1 OPEN TEST 2 - ZONE 1 OPEN 1. Create an open circuit on Zone 1 on the BMB by disconnecting one side of the EOL at the terminals. • The system will go into trouble • The Trouble LED is lit • The Zone 1 Trouble LED is lit • The Sounder will sound a trouble tone 1. Create an open circuit on Zone 1 on the BMB by disconnecting one side of the EOL at the terminals. • The system will go into trouble • The Trouble LED is lit • The Zone 1 Trouble LED is lit • The Sounder will sound a trouble tone 2. Press the TROUBLE SILENCE button • The Sounder will turn off • The Trouble LED is lit • The Zone 1 Trouble LED is lit 2. Press the TROUBLE SILENCE button • The Sounder will turn off • The Trouble LED is lit • The Zone 1 Trouble LED is lit 3. Replace the EOL connection to Zone 1’s terminal • The Trouble LED is off • The Zone 1 Trouble LED is off 3. Replace the EOL connection to Zone 1’s terminal • The Trouble LED is off • The Zone 1 Trouble LED is off B. ZONE 1 PROGRAMMED WATERFLOW, “1”. C. PROGRAM ZONE 1 AS A FIRE SUPERVISORY, “2”. TEST 1 - ZONE 1 SHORTED TEST 1 - ZONE 1 SHORTED 1. 1. Create a short on Zone 1 on the BMB by placing a short across the EOL at the terminals. • The system will go into Fire Supervisory • The Sounder will sound a supervisory tone • The Fire Supervisory LED is lit • The Zone 1 Alarm LED is lit 2. Press the ALARM SILENCE button • The Fire Supervisory LED is lit • The Zone 1 Alarm LED is lit • The Trouble LED is lit • The Zone 1 Trouble LED is lit • The Sounder will change to a trouble tone 3. Press the TROUBLE SILENCE button • The Sounder will turn off • The Fire Supervisory LED is lit • The Zone 1 Alarm LED is lit • The Trouble LED is lit • The Zone 1 Trouble LED is lit 4. Remove the short across Zone 1 terminal • All LEDs are off 2. 3. 4. Create a short on Zone 1 on the BMB by placing a short across the EOL at the terminals. • The system will go into alarm • The polarity of the voltage at BELL 1 and BELL 2 will reverse and pulse a Temporal 3 cadence • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Sounder will sound an alarm tone Press the ALARM SILENCE button • The output at BELL 1 and BELL 2 will stop • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Trouble LED is lit • The Zone 1 Trouble LED is lit • The Sounder will change to a trouble tone Press the TROUBLE SILENCE button • The Sounder will turn off • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Trouble LED is lit • The Zone 1 Trouble LED is lit Remove the short across Zone 1 terminal • All LEDs are off TEST 2 - ZONE 1 OPEN 1. Violate Zone 1 on the BMB by disconnecting one side of the EOL at the terminals. • The system will go into trouble • The Trouble LED is lit • The Zone 1 Trouble LED is lit • The Sounder will sound a trouble tone 2. Press the TROUBLE SILENCE button • The Sounder will turn off • The Trouble LED is lit • The Zone 1 Trouble LED is lit Sentrol 1-800-547-2556 59 3. Replace the EOL connection to Zone 1’s terminal • The Trouble LED is off • The Zone 1 Trouble LED is off E. PROGRAM ZONE 1 AS ALARM VERIFICATION, “4” TEST 1 - ZONE 1 SHORTED 1. Create a short on Zone 1 on the BMB by placing a short across the EOL at the terminals. • The system will go into alarm within 5 seconds • The polarity of the voltage at BELL 1 and BELL 2 will reverse and pulse a Temporal 3 cadence • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Sounder will sound an alarm tone 2. Press the ALARM SILENCE button • The output at BELL 1 and BELL 2 will stop • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Trouble LED is lit • The Zone 1 Trouble LED is lit • The Sounder will change to a trouble tone 3. Press the TROUBLE SILENCE button • The Sounder will turn off • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Trouble LED is lit • The Zone 1 Trouble LED is lit 4. Remove the short across Zone 1 terminal • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Trouble LED is lit • The Zone 1 Trouble LED is off 5. Press the SYSTEM RESET button • All LEDs are off D. PROGRAM ZONE 1 AS NON-LATCHING, “3” TEST 1 - ZONE 1 SHORTED 1. 2. Create a short on Zone 1 on the BMB by placing a short across the EOL at the terminals. • The system will go into alarm • The polarity of the voltage at BELL 1 and BELL 2 will reverse and pulse a Temporal 3 cadence • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Sounder will sound an alarm tone Press the ALARM SILENCE button • The output at BELL 1 and BELL 2 will stop • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Trouble LED is lit • The Zone 1 Trouble LED is lit • The Sounder will change to a trouble tone 3. Press the TROUBLE SILENCE button • The Sounder will turn off • The Alarm LED is lit • The Zone 1 Alarm LED is lit • The Trouble LED is lit • The Zone 1 Trouble LED is lit 4. Remove the short across Zone 1 terminal • All LEDs are off TEST 2 - ZONE 1 OPEN TEST 2 - ZONE 1 OPEN 1. 1. Create an open circuit on Zone 1 on the BMB by disconnecting one side of the EOL at the terminals. • The system will go into trouble • The Trouble LED is lit • The Zone 1 Trouble LED is lit • The Sounder will sound a trouble tone Create an open circuit on Zone 1 on the BMB by disconnecting one side of the EOL at the terminals. • The system will go into trouble • The Trouble LED is lit • The Zone 1 Trouble LED is lit • The Sounder will sound a trouble tone 2. 2. Press the TROUBLE SILENCE button • The Sounder will turn off • The Trouble LED is lit • The Zone 1 Trouble LED is lit Press the TROUBLE SILENCE button • The Sounder will turn off • The Trouble LED is lit • The Zone 1 Trouble LED is lit 3. 3. Replace the EOL connection to Zone 1’s terminal • The Trouble LED is off • The Zone 1 Trouble LED is off Replace the EOL connection to Zone 1’s terminal • The Trouble LED is off • The Zone 1 Trouble LED is off NOTE: Repeat tests A through D for zones 2 through 25 and verify system response. 60 Sentrol 1-800-547-2556 6. Set BELL 1 through BELL 4 to NON-SILENCEABLE STEADY. • Connect an audible device or digital multimeter to the outputs for verification. • Violate Zone 1 by shorting the EOL at the terminals and verify the Steady output. • Press Alarm Silence and verify that the bells do not silence. • Remove the short and press SYSTEM Reset. 7. Set Bell 1 through Bell 4 to Latching Non-Silenceable Steady and Zone 1 to Non-Latching. • Connect an audible device or digital multimeter to the outputs for verification. • Violate Zone 1 by shorting the EOL at the terminals and verify the Steady output. • Press ALARM SILENCE and verify that the bells do not silence. • Remove the short and verify that the bells remain active. • Press SYSTEM RESET. 6.2 NOTIFICATION APPLIANCE CIRCUIT TESTING There are two (2) Notification Appliance Circuits (NACs) for audible and visible notification appliances integral on the BMB. Consistent with the new requirements of the National Fire Alarm Code - 1996 the default setting for the BELL 1 / BELL 2 circuit is the Temporal 3 Code 3 (ANSI S3.41, Standard Emergency Evacuation Signal). The BELL 3 / BELL 4 circuit default setting is “not used”. If visible notification appliances are needed for ADA compliance they can be connected to this circuit once it has been reprogrammed for either steady or nonsilencable operation. Other signal options are available, as required by 3-7.1(b) of NFPA 72-1996, for when the planned action in response to a fire emergency is not evacuation but relocation, or where the Authority Having Jurisdiction requires some other signal. BELL CADENCE TESTING 1. 2. 3. 4. 5. BELL 1 and BELL 2 activate when an alarm occurs during testing. • Connect an audible device or digital multimeter to the outputs for verification. • Violate Zone 1 by shorting the EOL at the terminals and verify the Temporal 3 output. • Remove the short and press SYSTEM RESET. Set BELL 3 and BELL 4 to activate using the Temporal 3 code. • Connect an audible device or digital multimeter to the outputs for verification. • Violate Zone 1 by shorting the EOL at the terminals and verify the Temporal 3 output. • Remove the short and press SYSTEM RESET. Set BELL 1 through BELL 4 to activate using the Standard Marchtime Code. • Connect an audible device or digital multimeter to the outputs for verification. • Violate Zone 1 by shorting the EOL at the terminals and verify the Standard March Time Code output. • Remove the short and press SYSTEM RESET. Set BELL 1 through BELL 4 to activate using the California Marchtime Code (10 sec ON, 5 sec OFF). • Connect an audible device or digital multimeter to the outputs for verification. • Violate Zone 1 by shorting the EOL at the terminals and verify the California March Time Code output. • Remove the short and press SYSTEM RESET. Set BELL 1 through BELL 4 to STEADY. • Connect an audible device or digital multimeter to the outputs for verification. • Violate Zone 1 by shorting the EOL at the terminals and verify the Steady output. • Remove the short and press SYSTEM RESET. NOTE: Set BELL 1 through 4 to the appropriate cadence before performing Bell Line Testing. BELL LINE TESTING TEST 1 - BELL 1 OUTPUT SHORTED 1. Create a short circuit on BELL 1 on the BMB by placing a short across the EOL at the terminals. • The BELL 1 Trouble LED is lit • The System Trouble LED is lit • The Sounder will sound a trouble tone 2. Press the TROUBLE SILENCE button • The Sounder will turn off • The BELL 1 Trouble LED is lit • The System Trouble LED is lit 3. Remove the short from Zone 1’s terminals • The BELL 1 Trouble LED is off • The System Trouble LED is off TEST 2 - BELL 1 OUTPUT OPEN 1. Create an open circuit on BELL 1 on the BMB by disconnecting one side of the EOL at the terminals. • The BELL 1 Trouble LED is lit • The System Trouble LED is lit • The Sounder will sound a trouble tone 2. Press the TROUBLE SILENCE button • The Sounder will turn off • The BELL 1 Trouble LED is lit • The System Trouble LED is lit 3. Reconnect the EOL to Zone 1’s terminals • The BELL 1 Trouble LED is off • The System Trouble LED is off NOTE: Repeat Tests 1 and 2 for all four BELL outputs and verify system response Sentrol 1-800-547-2556 61 6.3 GROUND FAULT TEST B. 1. TEST 1 - PROGRAM ZONE 1 AS NORMAL (“0”) 2. 3. Connect a 1 meter long, 18 gauge wire between a terminal and the earth ground point • The GRD FAULT LED on the BMB is lit • The System Trouble LED is lit • The Sounder will sound a trouble tone Press the TROUBLE SILENCE button • The Sounder will turn off • The GRD FAULT LED on the BMB is lit • The System Trouble LED is lit 1. Place Zone 1 function jumper in silent walk test mode. • The system will go into trouble • The Zone 1 Trouble LED is lit • The System Trouble LED is lit • The Sounder will sound a trouble tone 2. Press the TROUBLE SILENCE button • The Sounder will turn off 3. Violate Zone 1 on the BMB by placing a short across the EOL at the terminals. • The System Alarm LED is lit for 5 seconds • The Zone 1 Alarm LED is lit for 5 seconds 4. Remove the short across Zone 1 terminal 5. The system will automatically reset to allow for the next device or zone to be tested Remove the ground wire from the terminal • The GRD FAULT LED on the BMB is off • The System Trouble LED is off NOTE: Repeat above test for all terminals except common alarm and common trouble (unless they are connected to supervised lines) and verify system response. SILENT WALK TEST MODE TESTING NOTE: Repeat above test for Alarm Verification (“4”). 6.4 SYSTEM TESTING USING TEST MODES TEST 2 - PROGRAM ZONE 1 AS NON-LATCHING (“3”) 1. Place Zone 1 function jumper in silent walk test mode. • The system will go into trouble • The Zone Trouble LED is lit • The System Trouble LED is lit • The Sounder will sound a trouble tone 2. Press the TROUBLE SILENCE button • The Sounder will turn off 3. Violate Zone 1 on the BMB by placing a short across the EOL at the terminals. • The System Alarm LED is lit • The Zone 1 Alarm LED is lit • The Zone 1 Trouble LED is lit • The System Trouble LED is lit 4. Remove the short across Zone 1 terminal • The System Alarm LED is off • The Zone 1 Alarm LED is off • The Zone Trouble LED is lit • The System Trouble LED is lit 5. Press the SYSTEM RESET button • All LEDs are off A. WALK TEST MODE TESTING PROGRAM ZONE 1 AS NORMAL (“0”) 1. Place Zone 1 function jumper in walk test mode. • The system will go into trouble • The Zone 1 Trouble LED is lit • The System Trouble LED is lit • The Sounder will sound a trouble tone 2. Press the TROUBLE SILENCE button • The Sounder will turn off 3. Violate Zone 1 on the BMB by placing a short across the EOL at the terminals. • The Alarm LED will light for 5 seconds • The Zone 1 Alarm LED will light for 5 seconds • The polarity of the voltage at BELL 1 and BELL 2 will reverse and pulse a Temporal 3 cadence for 2 seconds 4. The system will automatically reset to allow for the next device or zone to be tested. NOTE: Repeat above test for Waterflow (“1”), Fire Supervisory (“2”), Non-Latching (“3”), and Alarm Verification (“4”). Under Supervisory, the bells do not ring. However, the sounder will sound for 5 seconds and shut off with the LEDs. 62 NOTE: Repeat above test for Waterflow (“1”) and Fire Supervisory (“2”). Please note that under Supervisory, the Supervisory Alarm LED is lit instead of the System Alarm LED. Sentrol 1-800-547-2556 C. DISCONNECT MODE TESTING 6.5 REMOTE KEYPAD CHECK-OUT TEST 1 - PROGRAM ZONE 1 AS NORMAL (“0”) 1. Place Zone 1 function jumper in disconnect test mode. • The system will go into trouble • The Trouble LED is lit • The System Trouble LED is lit • The Sounder will sound a trouble tone 2. Press the TROUBLE SILENCE button • The Sounder will turn off 3. Violate Zone 1 on the BMB by placing a short across the EOL at the terminals. • The Zone 1 Alarm LED is lit • The Zone 1 Trouble LED is lit • The System Trouble LED is lit 4. Remove the short across Zone 1 terminal • The Zone 1 Alarm LED is lit • The Zone 1 Trouble LED is lit • The System Trouble LED is lit 5. Press the SYSTEM RESET button • All LEDs are off Verify that the Keypad has been properly installed and connected to the 2501 FACP. Verify that the Keypad password is properly programmed. Activate initiating devices and verify that the proper designations are displayed at the Keypad. Try silencing alarm signals without the password and with an incorrect password and verify that alarm signals continue. Repeat with the correct password and verify that the signals silence. Use each operator function from the Keypad and verify that all functions operate. To perform a lamp test of the keypad, access Lamp Test from the Main Menu. During lamp test, all dots on the display and all lightable keys will turn on as well as the keypad’s sounder for 5 seconds. See the keypad manual for specific instructions on how to access the Lamp Test. 6.6 BMB LAMP TEST NOTE: Repeat above test for Alarm Verification (“4”). TEST 2 - PROGRAM ZONE 1 AS WATERFLOW (“1”) 1. Place Zone 1 function jumper in disconnect test mode. • The system will go into trouble • The Trouble LED is lit • The System Trouble LED is lit • The Sounder will sound a trouble tone 2. Press the TROUBLE SILENCE button • The Sounder will turn off 3. Violate Zone 1 on the BMB by placing a short across the EOL at the terminals. • The Zone 1 Alarm LED is lit • The Zone 1 Trouble LED is lit • The System Trouble LED is lit 4. Remove the short across Zone 1 terminal • The Zone 1 Alarm LED is off • The Trouble LED is lit • The System Trouble LED is lit 5. Press the SYSTEM RESET button • All LEDs are off To test the lamps on the BMB, the ZEM’s and any other peripherals located in the can, the system must not have an alarm or trouble condition. Press and hold both the ALARM SILENCE and TROUBLE SILENCE keys. All the LEDs will illuminate as long as both keys are pressed and an alarm or trouble does not occur. 6.7 DIGITAL ALARM COMMUNICATOR CHECK-OUT Verify that the DAC has been properly installed and connected to the 2501 FACP. Connect the proper telephone lines to the DAC. Verify that the DAC is programmed correctly. Initiate a manual comm test by pressing the Comm Test push-button located on the DAC. Verify that a manual Comm Test report was received. Additional testing can be performed as required. To perform a lamp test, see Section 6.6 Lamp Test. 6.8 LEM/LRM CHECK-OUT NOTE: Repeat above test for Fire Supervisory (“2”) and Non-Latching (3). Verify that the LEM/LRM has been properly installed and connected to the 2501 FACP. Connect the signaling lines to the proper device type. Verify that the FACP is programmed correctly. Initiate the proper alarm (Fire or Supervisory). Verify that the signal is received by the connected device. To perform a lamp test, push the “push to test” push-button on the LEM/LRM module. The LED should remain activated until the push-button is released. Sentrol 1-800-547-2556 63 7.0 INSPECTION AND TESTING No piece of equipment can be expected to operate reliably without regular maintenance. The ESL 2501 Fire Alarm Control Panel is designed to provide years of reliable performance. Nevertheless, like all other building systems it must be maintained properly. The appropriate inspection and testing requirements differ depending upon whether the 2501 FACP is being used for household fire warning or in a commercial, architectural, institutional or non-household residential application. Household fire warning systems are inspected and tested in accordance with NFPA 72-1996, Chapter 2 (see Section 10). All other systems are inspected and tested in accordance with NFPA 72-1996, Chapter 7. Inspect and test the fire alarm system in accordance with the inspection and test procedures and schedules established by the local AHJ or presented in Chapter 7 NFPA 72-1996. Prior to commencing the inspection and test of a fire alarm system make certain that: • • • The owner/operator has advised the facility occupants and that a fire watch has been established The public fire service has been notified The off-premises supervising station fire alarm system operator has been advised and that an alternate means for reporting a fire has been established NOTE: When replacing batteries, always replace both batteries - even if only one appears dead. The typical battery life is 3 to 5 years, depending on usage. See manufacturer’s specifications for particular battery used. 8.0 PRECAUTIONS AND WARNINGS The equipment described in this manual is Listed by Underwriters Laboratories, Inc., for use in fire alarm signaling systems, only when installed in accordance with this manual and the National Fire Protection Association’s National Fire Alarm Code (NFPA 72); the National Electrical Code (NFPA 70); the Life Safety Code (NFPA 101); and the local Authority Having Jurisdiction (AHJ). The installer must be familiar with and understand all applicable codes before beginning installation. To ensure proper operation of this equipment: • DO NOT deviate from any installation instructions contained in this manual. • DO NOT assume any installation details not shown in this manual. • DO NOT alter any mechanical or electrical features of the equipment supplied. • BE FAMILIAR with the building code, fire prevention code, and/or other Authority Having Jurisdiction (AHJ) in the locale of the installation. Document all inspection and testing. Some fire alarm system components do not have to be tested at each scheduled inspection. Keep track of which devices are tested to ensure that different devices are tested at the subsequent inspection. IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE THAT THE WIRING AND DEVICES INSTALLED IN THE SYSTEM MEET CURRENT NATIONAL ELECTRICAL CODE, NFPA STANDARDS, STATE AND LOCAL BUILDING CODE REQUIREMENTS. Subsequent to the completion of the inspection and testing of the system make certain that the occupant, public fire service and supervising station fire alarm system operator are advised that the system has been placed back “on-line” and to treat all subsequent alarms as indications of a fire in progress. WARNING: Under abnormal conditions, AC line voltages may be present on any terminal. Touching any component could be hazardous and result in loss of life. A short circuit can result in arcing that could cause the ejection of molten metal, causing injuries to testing personnel. 7.1 MAINTENANCE The 2501 (FACP) is relatively maintenance free, other than performing regular testing to make sure all the systems are operating properly. Batteries require special attention. To minimize this possibility, only qualified technicians familiar with electrical hazards should perform these procedures. Safety glasses should be worn by such personnel, and instruments used for voltage measurement should be designed for the purpose and should be in good mechanical and working order. If any application or installation information is not understood, or is not covered herein, please contact Sentrol Technical Services at 1-800-800-2027. 7.1.1 BATTERIES The 2501 (FACP) uses two sealed lead-acid batteries as the secondary power source. The batteries must be replaced if the Low Battery LED remains on for more than 48 hours (meaning one or more of the battery cells are dead or the batteries will not hold a charge). If the batteries are dead, they must be replaced with batteries of the same voltage and capacity rating, with a maximum of 12 V, 17.2 Ah. Assure that any battery used allows a minimum clearance of 1/4" from its terminals to any non-power-limited circuit, including the system cabinet. 64 9.0 TROUBLESHOOTING This section provides a quick reference troubleshooting guide for the 2501 (FACP). This guide will aide in diagnosing and locating most system faults quickly and efficiently. If you cannot resolve the fault with the assistance of this guide, call Sentrol Technical Services at 1-800-800-2027. Sentrol 1-800-547-2556 Troubleshooting Guide Trouble Indicators Possible Cause Corrective Action End-of-line resistor value incorrect or missing Meter circuit to verify proper resistance Loss of power to power supervision relay Meter voltage on circuit Polarity reversal relay wired incorrectly Check circuit diagram to confirm wiring Loose connection or broken wire Check for opens in circuit Disconnect/Walktest function jumper not in normal position Put Disconnect/Walktest function jumper in normal position Faulty water flow switch Repair or replace water flow switch Initiating device missing from circuit Check for any devices that may have been removed from the initiating circuit “Class B” wires connected to wrong terminals Make sure wires are connected to “Class B” terminals Incompatible two wire detector Check UL compatibility listing to verify the detector is listed for use with the panel it is connected to Overcurrent or lightning damage Check for burn marks or other signs of overcurrent damage. Return to factory for service. Replace board if traces are damaged. Supervisory trouble LED Rapid trouble beep Zone alarm LED Zone supervisory device tripped Check initiating device on zone System trouble LED Zone trouble LED Rapid trouble beep Open in zone circuit Check zone for broken wires or opens in circuit Disconnect/Walktest function jumper not in normal position Put Disconnect/Walktest function jumper in normal position Loss of AC (line voltage) If line voltage is too low, upgrade or move to new circuit Low AC power Less than 94 VAC input to power supply - no load Less than 102 VAC with maximum load Check for loose or broken connections If power supply has no output, replace unit Return to factory for service Battery low Less than 24 VDC Replace batteries Battery missing or less than 20 VDC Replace batteries Open in battery harness If there is an open or break in the battery harness, repair it or replace it Ground on any circuit, other than supplementary alarm or trouble contacts Remove one wire at a time until ground fault LED and system trouble LED goes out. Repair circuit causing fault condition. End-of-line resistor value incorrect or missing Meter circuit to verify proper resistance Polarity reversed in circuit Check circuit diagram to confirm wiring and polarity Loose connection or broken wire Check for opens in circuit Indicating device missing from circuit Check for any devices that may have been removed from the indicating circuit Style “Z” wires crossed in circuit Make sure polarity is observed completely through circuit Style “Y” wires connected to wrong terminals Make sure wires are connected to Style “Y” terminals Overcurrent or lightning damage Check for burn marks or other signs of overcurrent damage. Return to factory for service. Replace board if traces are damaged. Bad ZEM connection Check data bus connections ZEM malfunction Check for signs of damage to the BMB or ZEM. BMB malfunction Return to factory for service or replace boards. Zone 1 - 25 trouble LED System trouble LED Trouble sounder slow intermittent Low/No AC power System trouble LED Trouble sounder slow intermittent Low/No battery LED System trouble LED Trouble sounder slow intermittent Ground fault LED System trouble LED Trouble sounder slow intermittent Indicating trouble LED System trouble LED System trouble LED Trouble sounder slow intermittent (with no other indicators) Figure 9.0 Troubleshooting Guide Sentrol 1-800-547-2556 65 10.0 HOUSEHOLD FIRE WARNING SYSTEMS A properly designed household fire warning system, implemented with the ESL 2501 Fire Alarm Control Panel, is intended to provide enhanced life-safety for the occupants in the event of a fire. It is intended to provide a warning sufficiently early in the development of a fire to enable the occupants to escape before conditions become life-threatening. Once the warning has been provided the occupants must still escape. Consequently, in order to derive the intended benefit from the household fire warning system, the household must have a pre-arranged fire escape plan. A fire escape plan includes at least two escape routes from all sleeping areas as well as a preplanned meeting place outside the building. The intent of this system is not to preserve property but to facilitate timely escape of the occupants. Since it takes precious time for smoke to travel from a fire to a smoke detector, the highest level of life safety is attained when a smoke detector is installed in each room. If fewer detectors are used the smoke must travel further before encountering a smoke detector. A fire warning system with fewer detectors responds more slowly, allowing the fire to grow larger before the occupants are warned of its existence. This translates to substantially lower levels of life-safety. 10.1 INSTALLATION This system should be installed in accordance with Chapter 2 of the National Fire Alarm Code 72-1996. A copy of this Standard may be purchased from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269 10.2 DETECTOR LOCATION The minimum level of protection requires one smoke detector between each bedroom area and the rest of the house and on each additional story, including the basement but excluding any crawl spaces and unfinished attics. In new construction, a smoke detector also shall be installed in each sleeping room. Detectors should be located at the top of each stairway leading to an occupied area. In addition, it is recommended that heat or smoke detection be located in the following areas if they are separated by a door from the areas protected by the required smoke detectors: living room, dining room, attic, utility room, basement, furnace room, garage, and hallways. 66 10.3 NOTIFICATION APPLIANCE LOCATION If smoke detectors have been used that do not contain an integral signaling device with a minimum output of 85 dBA at 10 feet, a separate notification appliance must be installed adjacent to each sleeping area. In new construction, where a smoke detector is also required in each sleeping room, all detectors must be arranged so that the signaling devices in all detectors operate whenever any single smoke detector unit is activated. In addition, it is recommended that additional signaling devices be installed on each level and on the outside of the premises. Check local codes before installing an outside device to assure they are permitted or if a timed cutoff is required. 10.4 ESCAPE PLAN 1. Have at least two (2) possible escape routes from each room of the house. 2. Before opening any door check for heat or smoke. NEVER OPEN A DOOR THAT IS HOT TO THE TOUCH. 3. If there is no alternative escape path available and there is smoke in you escape path, crawl with your head as close to the floor as possible. You can use a wet cloth over your mouth and nose to reduce the amount of smoke you inhale as you escape. 4. Have a prearranged meeting place outside the house. 5. Call the FIRE DEPARTMENT from outside the house as soon as possible. 6. NEVER re-enter a burning building. 7. Practice your escape plan and meeting place with ALL family members. 10.5 HOUSEHOLD FIRE WARNING SYSTEM MAINTENANCE All automatic systems need regular maintenance in order to provide continued performance and the Household Fire Warning System needs regular maintenance as well. The head of the household should test the fire warning system at least monthly to verify that it is in working order. If the system is monitored by an off-premises monitoring firm, it is important to call the monitoring company before the test of the system to ensure that the test is not misconstrued to be a fire alarm. It is also necessary to call the monitoring firm after the test to ensure that alarms are not misconstrued to be tests. Any deviation from “normal working” noticed by the building occupants should be quickly corrected by a qualified, professional Sentrol 1-800-547-2556 fire alarm system service contractor. In addition to the tests by the head of the household, the owner should arrange for a complete inspection and test of the entire system by a qualified, professional fire alarm system service contractor annually. S bedroom S bedroom S living room H T H T bath bath S T S den S family room S bedroom kitchen required smoke detector required notification appliance H S additional smoke detector T additional heat detector Figure 10.0a Detector Location - 3 Sleeping Areas 2nd floor S H S 1st floor H S basement H Figure 10.0b Detector Location - Per Floor 4 in. (100 mm) ceiling acceptable here 4 in. (100 mm) minimum never here 12 in. (300 mm) maximum top of detector acceptable here side wall NOTE: measurements shown are to the closest edge of the detector Figure 10.0c Detector Location - Ceiling/Wall Mount Sentrol 1-800-547-2556 67 11.3 2500-ZEM - ZONE EXPANDER MODULE 11.0 PANEL SPECIFICATIONS 11.1 GENERAL Operating Temperature: ............. 0 to 49OC (32 to 120OF) Housing Type ............... Steel with hinged/removable, locking door Size ...................................... 14.72 in x 21.80 in x 5.20 in ................................... (55.37 cm x 37.39 cm x 13.20 cm) Finish .............................................................. Red enamel Weight ................................................................... 16.0 lbs 11.2 2500-BMB - BASIC MASTER BOARD A. POWER Input Power ................................................. 110 - 120 VAC Standby Power ...................................................... 24 VDC Auxiliary Power Output ..................... 24 VDC, 1.0 A max. ................................................... 26.4 VDC max. - no load NOTE: Auxiliary power output supply is shared with power for indicating circuit. Consider total requirement. (Iaux + I IND #1 + I IND #2 + I IND #3 + I IND #4 = 7.0A) Optional Standby Battery 24 Volts Battery Charger Rate ................................... 800 mA max. Battery Charge Voltage ................................... 28.4 V max. B. ALARM INITIATING CIRCUITS Number of Circuits ............................... One - Model 2501 Type ......................................... Class B, Latched (Style B) End-of-Line Resistance ............................. 2.7k Ohm, 1/2 W Loop Powered Device Current ............................... 5.0 mA Maximum Current ................................................ 248 mA Maximum Voltage............................................... 13.9 Volts Normal Circuit Voltage ...................................... 12.0 Volts Minimum Voltage ................................................. 9.6 Volts Maximum Ripple Voltage ................................ 500 mV AC Max Line Resistance ........ 30 Ohms (Compat. Ident. C01) ...................... 30 Ohms (Compatibility, Identifier C01A)* * Not available at this time. 11.4 2500-ZRM - ZONE RELAY MODULE Number of Circuits ......................................... Two - ZRM2 ....................................................................... Four - ZRM4 Contact Ratings ............. 5 A @ 12 VDC, 120 VAC resistive ...................................... 2 A @ 30 VDC, 240 VAC resistive 11.5 2500-BELL - BELL EXPANDER MODULE A. NOTIFICATION APPLIANCE CIRCUITS Number of Circuits .......................... Two Class B (Style Y) Maximum Current per Circuit ....................... 1.5 Amperes Maximum Total Current ................................ 6.0 Amperes Output Voltage ........................................ 24 VDC Nominal ............................................. less than 1.0 V p-p AC ripple End-of-Line Resistance ........................... 2.7k Ohms, 1/2 W 11.6 POWER BOOSTER Normal Standby Current ....................................... 1.0 mA Alarm Current ......................................................... 23 mA Normal Circuit Voltage ................................ 24 V Nominal End-of-Line Resistance ......................... 2.7k Ohms, 1/2 W * * The EOL is dependent upon the UL Listed reversing NAC * Not available at this time. C. NOTIFICATION APPLIANCE CIRCUITS Number of Circuits .......................... Two Class B (Style Y) Maximum Current per Circuit ....................... 1.5 Amperes Maximum Total Current ................................ 6.0 Amperes Output Voltage ........................................ 24 VDC Nominal ............................................. less than 1.0 V p-p AC ripple End-of-Line Resistance ........................... 2.7k Ohms, 1/2 W D. SUPPLEMENTARY ALARM/TROUBLE CONTACTS System Trouble .......................... 2.0 A @ 30 VDC resistive System Alarm ............................. 2.0 A @ 30 VDC resistive E. SOUNDER OUTPUT Alarm ...................................................... Constant Output Fault ............................................ ~0.25 sec on: 2.5 sec off Supervisory ............................... ~0.25 sec on: 0.25 sec off 68 A. INITIATING CIRCUITS Number of Circuits .................. Four - Class B Model 2504 .................................................. Two - Class B Model 2502 Type .......................................... Class B, latched (Style B) End-of-Line Resistance ........................... 2.7k Ohms, 1/2 W Loop Powered Device Current .................................. 5 mA Maximum Current ................................................ 248 mA Maximum Voltage............................................... 13.9 Volts Normal Circuit Voltage ...................................... 12.0 Volts Minimum Voltage ................................................. 9.6 Volts Maximum Ripple Voltage .................................. 500 mVAC Max Line Resistance ......... 30 Ohms (Compat. Ident. C01 ..................... 30 Ohms (Compatibility Identifier (C01A)* circuit that is used to signal the power booster. Use the correct EOL for the UL Listed panel that is connected to the power boost terminals. 11.7 2500-LEM/LRM A. LEM Normal Standby Voltage....................................... 0.5 VDC Output Voltage (in Alarm) ...................... 24 VDC Nominal Alarm Current .................................. 110 mA (1.5 A peak) Standby Current .................................................... 6.5 mA B. LRM Normal Standby Voltage....................................... 7.8 VDC Output Voltage (in Alarm) ...................... 24 VDC Nominal Alarm Current ............................... 9.15 mA (12 mA peak) Standby Current .................................................... 2.8 mA End-of-Line Resistance ........................... 2.7k Ohms, 1/2 W Sentrol 1-800-547-2556 11.8 2500-RA Number of Zones .............................. 13 Alarm, 13 Trouble Standby Current ............................................. 50 mA ± 5% Alarm Current ............................................... 160 mA max 11.9 2500-RADVR Number of Zones .............................. 13 Alarm, 13 Trouble Standby Current ............................................. 50 mA ± 5% Alarm Current ............................................... 160 mA max Active Low Output (in Alarm) ............................... -40 mA Output (in Standby) ............................................ 1.35 mA 11.10 2500-DAC Standby Current ............................................... 88 ± 7 mA Alarm Current ............................................... 138 mA max Sentrol 1-800-547-2556 69 APPENDIX A COMPATIBLE EQUIPMENT The following ESL Four-Wire Smoke Detectors are UL Listed and voltage compatible with the 2501 (FACP): ESL Model Series The equipment listed here is compatible with the 2501 (FACP). USE ONLY UL LISTED COMPATIBLE EQUIPMENT WITH THE 2501 (FACP) SERIES TO ASSURE PROPER OPERATION. Should you have any questions about compatibility, call Sentrol Technical Services: 1-800-800-2027. Suffix Letters 445 C, CT, CR, CRT, CS, CST, CSR, CSRT, and CSH 449 C, CT, CRT, CST, CSRT, CSRH, CSST, CSSTE and CTE 741 with 702E, 702U base U 742 with 702E, 702U base U 204-12/24V EOL Power Supervision Device INITIATING DEVICES Figure A.2 UL Listed Four-Wire Smoke Detectors (Any of these Four-Wire detectors can be mixed and matched on a system). ESL Model Suffix Letters 103-20 Single action SPST manual fire alarm station 103-21 Single action DPST manual fire alarm station 103-22 Dual action SPST manual fire alarm station 103-22S Dual action SPST manual fire alarm station NY stripe 103-23 Dual action DPST manual fire alarm station 103-24 Dual action, pre-signal DPST manual fire alarm station 103-31 Single action SPST with key reset 103-32 Single action DPST with key reset 103-42 Dual action SPST with key reset 103-60 Weatherproof, single action SPST with key reset manual fire alarm station 103-80 Explosion-proof dual action DPDT with key reset 104-13 135o fixed temp rate of rise, single circuit heat detector 104-14 194o fixed temp rate of rise, single circuit heat detector 104-15 135o fixed temp, single circuit heat detector 104-16 194o fixed temp, single circuit heat detector Figure A.1 UL Listed Non-Coded Manual Alarm Stations and Heat Detectors 70 Sentrol 1-800-547-2556 Detector Series ESL 400 Detector Models Maximum Line Resistance (Ohms) Control Unit Compatibility Identifier Detector Compatibility Identifier Number per Circuit Base Compatibility Identifier 429C, 429CT 30 C01 S10A 20 N/A 429CRT, 429CST, 429CSST* 30 C01A S11A 20 N/A ESL 500 521B, 521BXT 30 C01 S09A or S10A 20 N/A ESL 600 611U, 611UD, 611UT 30 C01 S10 40 N/A (Use 600 Series Bases) 612, 612UD, 613U5 30 C01 S10 40 N/A 601U (base) N/A N/A N/A N/A S00 602U (base) N/A N/A N/A N/A S03 611UD, 612UD 30 C01 S10 20 N/A 609U10 (base) N/A N/A N/A 20 S00 ESL 609 Duct Detectors ESL 709 Duct Detectors ESL 700 (Use 700 Series Bases) 609U11 (base) N/A N/A N/A 20 S02 709-DW-21 (721UD) 30 C01 S10A 20 S10A 709-DW-31(731UD)* 30 C01 S11A 20 S11A 711U, 711UT, 712U 30 C01 S10A 20 N/A 721U, 721UD, 712UT, 30 C01 S10A 20 N/A 722U, 713-5U, 713-6U 30 C01 S10A 20 N/A 701E, 701U (bases) N/A N/A N/A N/A S00 702E, 702U (bases) N/A N/A N/A N/A S00 731U, 731UD, 732U* 30 C01A S11A 20 N/A 702RE, 702RU (bases) N/A N/A N/A N/A S00 Figure A.3 Two-Wire Smoke Detector Compatibility (any of these Two-Wire Smoke Detectors may be mixed and matched on the system.) * Not available at this time. Sentrol 1-800-547-2556 71 NOTIFICATION APPLIANCES The following devices are UL Listed notification appliances and signaling devices for use with the 2501 (FACP). ESL Model Series Description 106-06, 106-10 Vibrating Bell 107-81, 107-82, 107-85, 107-86, 107-87 Horn 108-81, 108-82, 108-83, 108-84, 108-85, 108-86, 108-87, 108-88 Strobes 109-81, 109-82, 109-83, 109-84, 109-85, 109-86, 109-87, 109-88, 109-89, 109-90, 109-91, 109-92, 109-93, 109-94, 109-95 Horn Strobes 110-81, 110-82, 110-83, 110-84 Speakers 111-81, 111-82, 111-83, 111-84, 111-85, 111-86 Speakers Strobes AU-360-M1, AU-360-M2, AU-360-M1-DMR, AU-360-E, AU-380-M1, AU-380-M2, AU-380-M1-DMR, AU-380-E, Voice Evacuation Communication Panel AU-DMR11, AU-562-2 2500-DAC Digital Alarm Communicator Transmitter Figure A.4 2501 (FACP) Compatible Indicating Devices (All Indicating Devices 24 VDC) Ordering Information DHR-1224C DHR-1224B DHR-24120C DHR-24120B DHF-1224C DHF-1224B DHF-24120C DHF-24120B DHS-1224C DHS-1224B DHS-24120C DHS-24120B Description EXAMPLE: 12 or 24 V DC/AC, recess mount, chrome, with 3” extension rod 12 or 24 V DC/AC, recess mount, brass, with 3” extension rod 24 or 120 V DC/AC, recess mount, chrome, with 3” extension rod 24 or 120 V DC/AC, recess mount, brass, with 3” extension rod 12 or 24 V DC/AC, semi-flush mount, chrome 12 or 24 V DC/AC, semi-flush mount, brass 24 or 120 V DC/AC, semi-flush mount, chrome 24 or 120 V DC/AC, semi-flush mount, brass 12 or 24 V DC/AC, surface mount, chrome 12 or 24 V DC/AC, surface mount, brass 24 or 120 V DC/AC, surface mount, chrome 24 or 120 V DC/AC, surface mount, brass Extension Rods DH-ER1C DH-ER1B DH-ER3C DH-ER3B 1” chrome 1” brass 3” chrome 3” brass Accessories DHW DH-BP DH-ARMC DH-ARMB Extension rod wrenches Back Plate (Chrome or Brass) Door holder, armature assembly, chrome Door holder, armature assembly, brass Figure A.5 Ordering Information Table 72 Sentrol 1-800-547-2556 DHF-24210-B DH = Door Holder 24120 = Model/Voltage F = Flush S = Surface Mount R = Recess Mount C = Chrome Plating B = Brass Plating NOTE: These door holders may only be used in the 24 VDC configuration. The Aux terminals may be used to supply power. Battery saver mode is not acceptable when connecting door holders to the ESL 2501. APPENDIX B BATTERY CALCULATION WORKSHEET 2501 (FACP) STANDBY BATTERY POWER WORKSHEET 2501 (FACP) Component Standby Current per Device Total Standby Current 135 mA 135 mA 200 mA 335 mA Notification Appliance Circuit #1 6 mA* mA mA mA (1500 mA max) Notification Appliance Circuit #2 6 mA* mA mA mA (1500 mA max) mA mA mA mA (1000 mA max) Zone Expander (Model 2504) 4 Class B Zones 40 mA mA 840 mA with all zones violated mA Zone Expander (Model 2502) 2 Class B Zones 30 mA mA 830 mA with all zones violated mA Relay Follower Module (Model 2500-ZRM2) 2 Relay Zone Follower 0 mA 0 mA Relay Follower Module (Model 2500-ZRM4) 4 Relay Zone Follower 0 mA 2500 BMB (includes Zone 1) Number of Devices N/A Auxiliary System Power 0 mA Alarm Current per Device Total Alarm Current 30 mA with both zones violated (15 mA per zone) mA 60 mA with all zones violated (15 mA per zone) mA Bell Expander Module (NAC) #3 (Model 2500-BELL) 6 mA* mA mA mA (1500 mA max) Bell Expander Module (NAC) #3 (Model 2500-BELL) 6 mA* mA mA mA (1500 mA max) 50 mA 55 mA mA 25 mA** 50 mA** mA Remote Annunciator (Model 2500-RA) 53 mA 168 mA Remote Annunciator (Model-RADVR) 53 mA 168 mA Digital Alarm Communicator (Model 2500-DAC) 95 mA 138 mA Local Energy Module (Model 2500-LEM/LRM) 30 mA 144 mA (1.8 A peak) Line Reversal Module (Model 2500-LEM/LRM) 26 mA 54 mA (56 mA peak) Printer Interface Module (Model ZXPTR) Centronics Printer Interface Keypad/Remote Annunciator (Model 2500-KPD) Keypad, Programming Device, and/or Remote Annunciator Total Current Requirements * supervision current only ** standby and alarm current for the keypad is 100 mA for 4 minutes after each keypress or after initiating an alarm or trouble condition Figure B.1 Battery Calculation Worksheet Sentrol 1-800-547-2556 73 the indicated mathematical operation. This provides you with the Standby Amp-hours your system requires. The REQUIRED # OF HOURS IN STANDBY varies by locale. Check with the proper Authority Having Jurisdiction to determine your requirements. Transfer the Total Alarm Current Requirements to the TOTAL ALARM CURRENT entry and perform the indicated mathematical operation. This provides you with the Alarm Amp-hours your system requires. The REQUIRED # OF MINUTES IN ALARM varies by locale. Check with the proper Authority Having Jurisdiction to determine your requirements. Carry the calculated values to the proper entries to arrive at the Minimum Battery Power Required for your system. Due to the natural aging effects on batteries due to time, temperature, cycles and the level of discharge during cycles, a de-rating factor is applied to help predict the battery capacity more closely. Please consult the appropriate manufacturer data sheets for the appropriate de-rating factor to apply and then perform the indicated mathematical operation. The final result is the Total Standby Battery Capacity required. BATTERY CAPACITY The following steps should be used to determine the correct battery capacities for your system. 7. 1. First you must determine the exact configuration of your system from the as built drawings generated during the installation process. Determine the number of notification appliances and the standby current for each notification appliance on each notification appliance circuit. Complete the appropriate entries on the worksheet. Determine the number of devices and the standby current for each device attached to the Auxiliary power terminals on the Basic Master Board. Complete the appropriate entries on the worksheet. From the as built drawings, determine the number of each type of expansion module (Zone Expander Module, Relay Follower Module, Bell Expander Module, Printer Interface Module, Keypad and Remote Annuciator) on the system and complete the appropriate entries on the worksheet. Total the rows across the worksheet and total the Total Standby Current and Total Alarm Current columns to arrive at the Total Standby Current Requirements and Total Alarm Current Requirements for your system. Transfer the Total Standby Current Requirements to the TOTAL STANDBY CURRENT entry and perform 2. 3. 4. 5. 6. mA X .001 Amp/mA CONVERSION FACTOR TOTAL STANDBY CURRENT mA X .001 Amp/mA X TOTAL ALARM CURRENT CONVERSION FACTOR X 8. 9. NOTE: This system always requires two batteries. The calculations performed indicate the Amp-Hour rating that each battery must carry. Do not mix batteries of different capacities. hours = Ah Standby Amp - hours REQUIRED # OF HOURS IN STANDBY minutes x .0167 hour/min = REQUIRED # OF MINUTES IN ALARM Ah Alarm Amp - hours CONVERSION FACTOR Standby Amp - hours + Alarm Amp - hours = Minimum Battery Power Required + Minimum Battery Power Required 74 = x Battery Capacity = Derating Coefficient x = Ah Total Standby Battery Required (17.2 Ah Maximum) Sentrol 1-800-547-2556 Ah The following table lists the maximum continuous loads that can be supported by the two 7 Ah or two 17.2 Ah batteries. If the total standby current exceeds those listed in the table, you do not meet 24 hour standby requirements. Notice that the Battery Saver Mode doubles the amount of current available to the load. This allows for the use of smaller batteries and the system still meets the 24 hour standby requirements. Other battery sizes are possible, but two 17.2 Ah batteries are the maximum battery size supported. If your standby time is different, the above calculations can be used to calculate the Total Standby Battery Power Required. If the answer exceeds the battery size you have chosen, then appropriate batteries must be installed or the system configuration must be adjusted to meet the battery power requirements. Required Batteries Maximum Continuous Load for 24/60 hour Standby Normal Mode Battery Saver Mode 24 hour 60 hour 24 hour 60 hour Two 7.0 Ah 240mA 100mA 480mA 200mA Two 17.2 Ah 500mA 200mA 1000mA 400mA Sentrol 1-800-547-2556 75 BATTERY CALCULATION WORKSHEET EXAMPLE 2501 (FACP) STANDBY BATTERY POWER WORKSHEET EXAMPLE: Battery Calculation System will be one of the 2501, and two each of the Model 2504-ZEMs, 4wire smoke detectors on Zone 1 and 2 with power supervision relays, 2-wire smoke detectors on Zone 3 through 9, Model 2500-ZRM4 relay follower modules for zones 2 through 9, Bells on Notification Appliance Circuit (NAC) #1 and Strobes on Notification Appliance Circuit (NAC) #2. 2501 (FACP) Component 2500 BMB (includes Zone 1) Number of Devices Total Standby Current Total Alarm Current 135 mA 135 mA 200 mA 335 mA 2 Bells 6 mA* 6 mA 70 mA 140 mA (1500 mA max) Notification Appliance Circuit #2 2 Strobes 6 mA* 6 mA 180 mA 360 mA (1500 mA max) mA 56 mA mA 56 mA (1000 mA max) 40 mA 80 mA 840 mA with all zones violated 480 mA 30 mA mA 830 mA with all zones violated mA 0 mA 0 mA 30 mA with both zones violated (15 mA per zone) mA 0 mA 0 mA 60 mA with all zones violated (15 mA per zone) 120 mA Bell Expander Module (NAC) #3 (Model 2500-BELL) 6 mA* mA mA mA (1500 mA max) Bell Expander Module (NAC) #3 (Model 2500-BELL) 6 mA* mA mA mA (1500 mA max) 50 mA 55 mA mA 25 mA 50 mA mA Remote Annunciator (Model 2500-RA) 53 mA 168 mA Remote Annunciator (Model-RADVR) 53 mA 168 mA Digital Alarm Communicator (Model 2500-DAC) Local Energy Module (Model 2500-LEM/LRM) Line Reversal Module (Model 2500-LEM/LRM 95 mA 138 mA 30 mA 144 mA (1.8 A peak) 54 mA (56 mA peak) Zone Expander (Model 2504) 4 Class B Zones 2 Supervisory Relays 2 Zone Expander (Model 2502) 2 Class B Zones Relay Follower Module (Model 2500-ZRM2) 2 Relay Zone Follower Relay Follower Module (Model 2500-ZRM4) 4 Relay Zone Follower Printer Interface Module (Model ZXPTR) Centronics Printer Interface Keypad/Remote Annunciator (Model 2500-KPD) Keypad, Programming Device, and/or Remote Annunciator Total Current Requirements 2 26 mA 283 mA * supervision current only 76 Alarm Current per Device Notification Appliance Circuit #1 Auxiliary System Power N/A Standby Current per Device Sentrol 1-800-547-2556 1491 mA 283 mA X mA X .001 Amp/mA X TOTAL ALARM CURRENT CONVERSION FACTOR 24 X CONVERSION FACTOR TOTAL STANDBY CURRENT 1491 .001 Amp/mA hours = 6.792 Ah Standby Amp - hours REQUIRED # OF HOURS IN STANDBY 15 minutes x .0167 hour/min = REQUIRED # OF MINUTES IN ALARM .373 Ah Alarm Amp - hours CONVERSION FACTOR Standby Amp - hours + Alarm Amp - hours = Minimum Battery Power Required 6.792 + Minimum Battery Power Required x 7.165 x .373 Battery Capacity = Derating Coefficient 1.15 7.165 = Ah Total Standby Battery Required (17.2 Ah Maximum) = 8.24 Ah The following table lists the maximum continuous loads that can be supported by the two 7 Ah or two 17.2 Ah batteries. If the total standby current exceeds those listed in the table, you do not meet 24 hour standby requirements. Notice that the Battery Saver Mode doubles the amount of current available to the load. This allows for the use of smaller batteries and the system still meets the 24 hour standby requirements. Other battery sizes are possible, but two 17.2 Ah batteries are the maximum battery size supported. If your standby time is different, the above calculations can be used to calculate the Total Standby Battery Power Required. If the answer exceeds the battery size you have chosen, then appropriate batteries must be installed or the system configuration must be adjusted to meet the battery power requirements. Required Batteries Maximum Continuous Load for 24/60 hour Standby Normal Mode Battery Saver Mode 24 hour 60 hour 24 hour 60 hour Two 7.0 Ah 240mA 100mA 480mA 200mA Two 17.2 Ah 500mA 200mA 1000mA 400mA In this example, the two 7 Ah batteries in Normal Mode would not be sufficient to meet the 24 hour standby based on the 283 mA of continuous standby current required. However, if Battery Saver Mode is used, two 7 Ah batteries are sufficient. If the Battery Saver Mode is used, the power supervision relays must be rated for 12 VDC operation. This results from the decision to use Battery Saver Mode. Battery Saver Mode selects the Auxiliary terminals to be 12 VDC output instead of 24 VDC output. Sentrol 1-800-547-2556 77 NOTES ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ 78 Sentrol 1-800-547-2556 APPENDIX C 2501 (FACP) OPERATING INSTRUCTIONS Refer to the ESL 2501 Fire Alarm Control Panel Installation Manual for more information, Part # 64812711. NORMAL STANDBY CONDITION TROUBLE CONDITION •Yellow system trouble LED is “ON” •Yellow local zone LED is “ON” •Integral sounder sounds a slow intermittent signal •System common trouble relay contacts transfer •Green “AC POWER” LED “ON” •All other LEDs “OFF” •All switches in “NORMAL” position ALARM CONDITION TROUBLE SILENCE SWITCH OPERATED •Red local zone alarm LED “ON” •Integral sounder sounds a steady signal •Common alarm relay contacts transfer and latch •Indicating circuits turn “ON” •Integral sounder is “OFF” when system trouble is present •System common trouble relay contacts not affected •Will NOT silence supervisory alarm, supervisory trouble or system alarm signals ALARM DISCONNECT SWITCH OPERATED (PRIOR TO ALARM CONDITION) For Maintenance Use Only •Disconnects local zone alarm from common alarm relay •Disconnects local zone alarm from the alarm indicating circuits •Red local zone alarm LED turns “ON” •Alarm signal from any other zone is NOT affected ALARM DISCONNECT SWITCH OPERATED (AFTER ALARM CONDITION) For Maintenance Use Only •Alarm indicating circuits are turned “OFF” •Red local zone alarm LED remains “ON” •Alarm signal from any other zone is NOT affected SUPERVISORY ALARM SIGNAL •Integral sounder sounds a fast intermittent signal •Red local zone alarm LED is “ON” •Indicating circuits are NOT activated •Red supervisory LED is “ON” SUPERVISORY TROUBLE SIGNAL •Integral sounder sounds a fast intermittent signal •Yellow local zone trouble LED is “ON” •System common trouble relay contacts transfer •Yellow supervisory LED is “ON” REMOTE TEST (FIRE DRILL) RESET SWITCH OPERATED •Initiating circuit power removed (smoke detectors reset) •Indicating circuits turn “OFF” •Integral sounder turns “OFF” •Common alarm relay is reset •System restored to normal unless initiating devices are NOT reset •Indicating circuits turn “ON” •Integral sounder sounds a slow intermittent signal •Common alarm relay contacts do NOT transfer •Keying the test switch will pulse the indicating circuits The following applies to Household Fire Warning Systems only: TESTING – In a Household Fire Warning System, Test Monthly. Disconnect the AC power source during testing. If, after testing, a low battery condition exists, replace the batteries. “This equipment should be installed in accordance with the National Fire Protection Association's Standard 72 (NFPA, Batterymarch Park, Quincy, MA 02269). Printed information describing proper installation, operation, testing, maintenance, evacuation planning and repair service is to be provided with this equipment.” WARNING: Owner’s instruction notice: “Not to be removed by anyone except occupant.” FOR SERVICE CONTACT: _______________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________ A Product of Sentrol 1510 Tate Blvd. SE, Hickory, NC 28603 • Sales: 800-547-2556 • Technical Service: 800-800-2027 Remove this page, frame and mount adjacent to control unit. Sentrol 1-800-547-2556 79 Part 64812828E 80 Sentrol 1-800-547-2556 NOTES ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ Sentrol 1-800-547-2556 81 NOTES ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ 82 Sentrol 1-800-547-2556 Sentrol 1-800-547-2556 83 SENTROL CONTROLS GROUP PO Box 2904, 1510 Tate Blvd. SE Hickory, NC 28603 Tel.: 503.692.4052 Fax: 503.691.7566 SENTROL 84 U.S. & Canada: 800.547.2556 Technical Service: 800.800.2027 FaxBack: 800.483.2495 Sentrol 1-800-547-2556 Sentrol reserves the right to change specifications without notice. ©1997 Sentrol 64812711E
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.1 Linearized : No Page Count : 84 Create Date : 1999:01:18 11:03:44 Producer : Acrobat Distiller 3.01 for Power Macintosh Subject : ESL2500 Manual-2711E Creator : Adobe PageMaker 6.52 Title : ESL2500 Manual-2711E Author : Linda JettEXIF Metadata provided by EXIF.tools