Kamstrup A S FLOW2100 Water Flow Meter User Manual 15 FlowIQ2100 UserMan

Kamstrup A/S Water Flow Meter 15 FlowIQ2100 UserMan

Contents

15_FlowIQ2100_UserMan

Download: Kamstrup A S FLOW2100 Water Flow Meter User Manual 15 FlowIQ2100 UserMan
Mirror Download [FCC.gov]Kamstrup A S FLOW2100 Water Flow Meter User Manual 15 FlowIQ2100 UserMan
Document ID1827799
Application IDte9/of+05n3nV6/MNHD6NA==
Document Description15_FlowIQ2100_UserMan
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize89.9kB (1123806 bits)
Date Submitted2012-11-01 00:00:00
Date Available2012-11-01 00:00:00
Creation Date2012-10-12 08:01:53
Producing SoftwareAdobe PDF Library 10.0.1
Document Lastmod2012-10-12 08:02:05
Document Title15_FlowIQ2100_UserMan
Document CreatorAdobe InDesign CS6 (Windows)

Optional customer label, e.g. water company logo (15x38 mm)
Optical eye for reading and configuration
Expiry year of battery
Graphic flow indicator
Temperature class according to OIML R 49
Type number
(includes information on
meter size, overall length etc.)
Nominal meter size
Software version
Serial no. and prod. year
Configuration
(with information on display
resolution and encryption level etc.)
Bar code with serial number
FCC identification
Accuracy class 2 according to OIML R 49
Environment class: Electrical E2 and Mechanical M1 according to MID
Environment class B and C according to OIML R 49
(indoors/outdoors)
55121224_A1_GB_10.2012
Caution: Changes or modifications not expressly approved
by the party responsible for compliance could void the
user’s authority to operate the equipment.
RF Exposure compliance statement: This device may be
used with no restrictions, since the source-based timeaveraged output power is ≤ 60/f(GHz) mW.
The coupling’s
sealing surface must
be clean and even.
FCC Cautions
With your smart phone you can enter this QR code and
watch our installation film online. Or you can watch the film
on http://www.kamstrup.dk/hardlink/mc21/index.html.
ALWAYS use new gaskets
(PE or EPDM).
The piping must be parallel and match the meter.
Torque
If a pipe installation is skew to the effect that the prescribed
tightening torques would be exceeded, a telescopic
coupling ought to be installed.
1”
Max. 30 Nm
Installation guide for
flowIQ 2100
1”: Max. 30 Nm
www.kamstrup.com
1. General information
Read this guide before installing the water meter.
flowIQ 2100 is a compact electronic water meter used for
water consumption measurement in the tap water supplies
of homes, commercial and industrial buildings.
flowIQ 2100 is intended for maintenance-free operation for
up to 16 years.
flowIQ 2100 is hermetically closed, and it is, therefore,
impossible to service the meter without breaking the seal.
This means that all service including battery change must
be carried out by an authorized Kamstrup Service Centre.
Certain changes of configuration, however, are possible via
the built-in optical eye without dismounting the meter from
the installation. Further details appear from data sheet and
technical description.
1.6 Info codes and display
If a tight connection cannot be obtained within these
limits, the pipe installation must be corrected in order to
remove strains. Alternatively a telescopic coupling must be
installed.
Such couplings can be supplied by Kamstrup A/S.
For sealing you can use the sealing wire holes on the lower
side of the threaded connections. Mounting the meter you
must make sure that the threaded length of the couplings
does not prevent proper tightening of the sealing surface
and that PN10 or PN16 couplings are used.
For sealing you can use the sealing wire holes on the lower
side of the threaded connections.
Mounting the meter you must make sure that the threaded
length of the couplings does not prevent proper tightening
of the sealing surface and that PN10 or PN16 couplings are
used.
When flowIQ 2100 leaves Kamstrup A/S, it has been tested
and verified and the counter has been reset.
The number of gallons is displayed by nine big digits
A number of info codes can be displayed, of which DRY
and RADIO OFF will be activated and flash upon delivery.
Furthermore, the two small squares in the bottom righthand corner flash to indicate that the meter is active.
Info code DRY indicates that there is air in the meter, the
info code disappears when the meter is water-filled.
The info code RADIO OFF indicates that the meter is still in
transport mode with the built-in radio transmitter turned
off. The transmitter turns on automatically when the first
quarter gallon of water has run through the meter. The radio
transmitter remains on, and the info code signal in the
display switches off.
The small revolving symbol in the left side of the display
indicate water flow through the meter. If the water is
stagnant, the symbol will be off.
The table below describes the different info codes in the
display.
Service
When the meter has been mounted in the system neither
welding nor freezing is allowed. Dismount the meter from
the system before starting such work.
In order to facilitate replacement of the meter, closing
valves should be mounted on both sides of the meter.
Under normal operating conditions no pipe strainer is
required in front of the meter. Non-return valves must be
mounted according to local regulations.
Info code flashes in
the display
LEAK
flowIQ 2100 can be mounted at all angles and positions.
Kamstrup A/S recommend that the display is mounted so
that it is easy to read, if possible.
Thus, the meter can be mounted in a usual horizontal
installation. It can be mounted vertically in an ascending
pipe, it can be mounted at any angle and it can be mounted
with its display pointing downwards, e.g under a roof.
Mounting the meter in a downpipe, you must be aware that
the display will in that case be ”upside down”.
2023
63123456
S/N: 63123456/2011
Con: 010600002313
Class: 2 (E2, M1)(B/C)
Q3:
1.6 m3/h
Q3/Q1: 100/1, SW:E1
PN16, PS16 – IP68
M11 0200
DK-0200-MI001-015
1.2 Installation requirements
1.4 Straight inlet
Prior to installation of flowIQ 2100 in a new system the
system should be cleaned and flushed thoroughly. Remove
the adhesive wafers from the meter’s inlet and outlet and
mount the meter with couplings.
If an existing install, remove all traces of old gaskets
and insert new gaskets in original quality. Kamstrup A/S
recommends EPDM or PE gaskets.
Install the meter according to the flow direction indicated
by an arrow on the side of the meter case. An electrical
grounding wire must be installed according to local
electrical regulation and for safety reasons.
flowIQ 2100 requires neither straight inlet nor straight
outlet to meet OIML R49. A straight inlet section will only
be necessary in case of heavy flow disturbances before the
meter.
During installation it must be secured that the meter is
mounted without mechanical tension in the connection
pipes. The piping must be in line and match the meter. Do
not attempt to install the meter in a misaligned pipe system
or in an opening that is too long. Forcing the piping into
place with the meter will seriously damage the meter.
In a properly aligned piping system with new gaskets, you
should be able to mount and tighten the couplings by hand.
After hand-tightening the coupling nuts, using an open-end
wrench, tighten an extra ¼ to ½ turn on each coupling.
Maximum allowable torque is 30 Nm.
Meaning
The Water has not been stagnant
in the meter for minimum one
continuous hour during the latest
24 hours.
This can be a sign of a leaky faucet
or toilet cistern.
BURST
The water flow has exceeded a
preprogrammed limit for minimum
30 minutes which is a sign of a
burst pipe.
TAMPER
Attempt of fraud. The meter is no
Wa
te
ic
longer valid for billing purposes.
so
DRY
The meter is not water-filled.
REVERSE
The water flows through the meter
in the wrong direction.
63123456
RADIO OFF
The meter is still in transport mode
with the built-in radio transmitter
turned off. The transmitter turns on
automatically when the first litre of
water has run through the meter.
(two square ”dots”) Two small squares that flash
alternately indicate that the meter
MULTICAL® 21
is active.
T50: 0.1°C...50°C
Type: 02166A0A819
er
et
Medium temperature
cold water meter:
33°F...120°F
Pressure stage:
PN16
Mechanical environment: M1 (MID) Fixed installation with
minimum vibration.
Electromagnetic
environmental class:
E1 and E2 (MID). Residential and
commercial
Protection class:
IP68
Climatic environment:
35°F...130°F. Condensing
humidity. (indoors mounted in
utility rooms and outdoors in
meter wells). Installation in direct
sunlight must be avoided. The
meter must be protected from
freezing.
1.3 Installation angle of flowIQ 2100
Ul
tra
1.1 Permissible operating conditions / measuring
ranges
Recommended water meter position.
Recommended water meter position.
Used for ”well installation”. Air build-up may occur.
The meter functions optimally, but the display is ”upside
down”.
1.5 Operating pressure
In order to avoid cavitation and secure correct measurement
under all circumstances the operating pressure in the pipe
installation must observe the test conditions of OIML R 49,
which means that the static pressure immediately after the
meter (downstream) must always be minimum 5 PSI
(0.3 bar).

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.3-c011 66.145661, 2012/02/06-14:56:27
Create Date                     : 2012:10:12 08:01:53+02:00
Metadata Date                   : 2012:10:12 08:02:05+02:00
Modify Date                     : 2012:10:12 08:02:05+02:00
Creator Tool                    : Adobe InDesign CS6 (Windows)
Instance ID                     : uuid:588fe146-f2a7-4ec6-b535-9cda56ec9b63
Original Document ID            : xmp.did:CE01E6A1DFEFE0118D6AC478EE4E4D07
Document ID                     : xmp.id:FEEF15F13114E211AD468C69BE79E3DE
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:FDEF15F13114E211AD468C69BE79E3DE
Derived From Document ID        : xmp.did:E2C7173A5AF9E011BD52D490A9604B11
Derived From Original Document ID: xmp.did:CE01E6A1DFEFE0118D6AC478EE4E4D07
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Windows)
History Changed                 : /
History When                    : 2012:10:12 08:01:53+02:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 10.0.1
Trapped                         : False
Page Count                      : 2
Creator                         : Adobe InDesign CS6 (Windows)
EXIF Metadata provided by EXIF.tools
FCC ID Filing: OUY-FLOW2100

Navigation menu