Kidde Fire Systems Water Pump 96 Fe13Ma 001 Users Manual Front Matter_96

2015-02-09

: Kidde-Fire-Systems Kidde-Fire-Systems-Kidde-Fire-Systems-Water-Pump-96-Fe13Ma-001-Users-Manual-568190 kidde-fire-systems-kidde-fire-systems-water-pump-96-fe13ma-001-users-manual-568190 kidde-fire-systems pdf

Open the PDF directly: View PDF PDF.
Page Count: 30

FE-13
Fire Suppression
Systems
Owners Manual
P/N 96-FE13MA-001
October 2002
R
LISTED
UL Listing File No. EX 4674
FE-13
Fire Suppression
Systems
Owners Manual
P/N 96-FE13MA-001
October 2002
THIS PAGE INTENTIONALLY LEFT BLANK.
i
This manual is written for those who own or are responsible for Kidde® FE-13™ Fire Suppression System cylinders.
IMPORTANT
Kidde assumes no responsibility for the application of any systems other than those addressed in this manual. The
technical data contained herein is limited strictly for information purposes only. Kidde believes this data to be accurate, but
it is published and presented without any guarantee or warranty whatsoever. Kidde disclaims any liability for any use that
may be made of the data and information contained herein by any and all other parties.
Kidde FE-13 Fire Series Fire Suppression Systems are to be designed, installed, inspected, maintained, tested and
recharged by qualified, trained personnel in accordance with the following:
Standard of the National Fire Protection Association No. 2001, titled Clean Agent Fire Extinguishing Systems.
All instructions, limitations, etc. contained in this manual, P/N 96-FE13MA-000 and/or 96-FE13MA-002.
All information contained on the system container nameplate(s).
Storage, handling, transportation, service, maintenance, recharge and test of agent storage containers shall be per-
formed only by qualified and trained personnel in accordance with the information in this manual and Compressed Gas
Association pamphlets C-1, C-6 and P-1:
C-1, Methods for Hydrostatic Testing of Compressed Gas Cylinders.
C-6, Standards for Visual Inspection of Compressed Gas Cylinders.
P-1, Safe Handling of Compressed Gases In Containers.
CGA pamphlets are published by the Compressed Gas Association, Crystal Square Two, 1725 Jefferson Davis Highway,
Arlington, VA 22202-4102.
Any questions concerning the information presented in this manual should be addressed to:
Kidde-Fenwal Inc.
400 Main Street
Ashland, MA 01721
Phone: (508) 881-2000
Fax: (508) 881-8920
FOREWORD
ii
THIS PAGE INTENTIONALLY LEFT BLANK.
iii
TABLE OF CONTENTS
Foreword ....................................................................................................................................................... i
Installation Form............................................................................................................................................ v
Safety Summary............................................................................................................................................ vii
Paragraph Title Page
1 GENERAL INFORMATION ....................................................................................................... 1-1
1-1 Introduction ................................................................................................................................ 1-1
1-2 Moving of Containers ................................................................................................................. 1-1
1-2.1 Moving by Trucks....................................................................................................................... 1-1
1-2.2 Rough Handling ......................................................................................................................... 1-1
1-2.3 Storage ......................................................................................................................................1-1
1-3 Safety Cap ................................................................................................................................. 1-2
1-4 About the System ...................................................................................................................... 1-2
1-5 FE-13 Overview ......................................................................................................................... 1-2
2 INSTALLATION AND MAINTENANCE ..................................................................................... 2-1
2-1 Introduction ................................................................................................................................ 2-1
2-2 Installation ................................................................................................................................. 2-1
2-3 Instructions in Case of Fire........................................................................................................ 2-1
2-4 Post-Operation Instructions ....................................................................................................... 2-1
2-5 Inspection and Maintenance of the System............................................................................... 2-2
2-5.1 Monthly ...................................................................................................................................... 2-2
2-5.2 Semi-Annual Inspection............................................................................................................. 2-2
2-6 Additional Requirements ........................................................................................................... 2-2
2-7 Additional Specifications and Documentation ............................................................................ 2-2
iv
THIS PAGE INTENTIONALLY LEFT BLANK.
v
ATTENTION INSTALLER
This form must be signed by the system owner indicating that he/she has received a copy of this Owner’s Manual
P/N 96-FE13MA-001. Have the system installer fill-out this form.
Note: Retain a copy of this form for your records.
1. System Installed:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
2. Listing of Major System Components:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
3. Description of Hazard Protected by System:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
____________________________________________ _____________
Owner or Authorized Representative Date
____________________________________________
Title
vi
THIS PAGE INTENTIONALLY LEFT BLANK.
vii
SAFETY SUMMARY
Safety precautions are essential whenever electrical or mechanical equipment is involved. Take precautions when han-
dling, servicing, and charging FE-13™ fire suppression systems cylinders. Using this equipment with the respect and
caution demanded will considerably lessen the possibility of personal injury. If safety precautions are overlooked or ig-
nored, personal injury or property damage may occur.
The following symbols are used throughout this manual. Always heed these precautions. They are essential to the safe
use of the equipment described in this manual.
WARNING
!
The warning symbol identifies immediate hazards and provides specific instructions or procedures which
if not correctly followed will result in severe personal injury or death.
CAUTION
!
This caution symbol identifies specific instructions or procedures which if not correctly followed could
result in minor personal injury or equipment or property damage.
The following safety precautions should always be followed:
WARNING
!
Pressurized (charged) cylinders are extremely hazardous and if not handled properly are capable of causing
bodily injury, death or property damage.
1. Read and understand this manual and the other documents referenced herein.
2. The valve outlet safety cap and the actuation port protection cap MUST be installed on the cylinder valve at all times
and only removed when performing charging, testing, or salvaging operations in accordance with the procedures
contained in this manual.
3. Wear safety glasses when working with pressurized cylinders and charging equipment
4. Make sure that all control heads, pressure operated control heads, or other type of actuation devices have been
removed from the cylinder valves. Ensure the protection caps are installed before performing any charging, leak tests
or salvage operations.
Don’t get careless. Never assume a cylinder is empty. Treat all cylinders as if they are fully charged.
Smoking is prohibited in FE-13 fill and charging areas.
viii
THIS PAGE INTENTIONALLY LEFT BLANK.
1-1 96-FE13MA-001
October 2002
FE-13™ Fire Suppression System Owner's Manual
1-1 INTRODUCTION
This document is provided to instruct and familiarize the
owner with the Kidde® FE-13™ Fire Suppression System.
This manual covers:
Information about the system
How the FE-13 system operates
How FE-13 works
Installation of the system
Instructions in case of fire
Post-operation instructions
Inspection and maintenance of the system
Responsibilities and related equipment require-
ments
Additional specifications and documentation
Note: IMPORTANT–This owner's manual does not cover
every detail of step-by-step installation procedures
for the Kidde FE-13 Fire Suppression System.
The system consists of components tested within
the limitations defined in the detailed design, in-
stallation, operation and maintenance manual
(P/N 96-FE13MA-000 and -002) which is available
from Kidde. The system designer must be consulted
whenever changes are planned for the system or
area of protection.
A certified Kidde distributor must be consulted af-
ter the system has been discharged.
The technical data contained herein is limited strictly
for informational purposes only.
CAUTION
!
It is the owner's responsibility to read this
manual and to ensure proper system operation
and personnel safety.
Follow the instructions in this manual and on the FE-13
cylinder nameplates. Review this information semi-annu-
ally, or as needed. Place this manual in an accessible place
near the FE-13 system for ready reference.
Kidde believes this data to be accurate, however, it is pub-
lished and presented without any guarantee or warranty
whatsoever. Kidde disclaims any liability for the informa-
tion contained herein by any, and all, other parties.
NAME OF KIDDE DISTRIBUTOR IS:
________________________________________________
ENTER EMERGENCY NUMBER FOR THE LOCAL FIRE
DEPARTMENT HERE:
________________________________________________
Before handling Kidde products, all personnel must be thor-
oughly trained in the safe handling of the containers as well
as in the proper procedures for installation, removal, filling
and connection of other critical devices, such as solenoids,
cable assemblies, pressure switches and safety caps.
READ, UNDERSTAND and ALWAYS FOLLOW the opera-
tion and maintenance manuals, owners manuals, service
manuals, etc., that are provided with the individual systems.
WARNING
!
Pressurized (charged) containers are extremely
hazardous and if not handled properly, are
capable of violent discharge. This may result
in serious bodily injury, death and property
damage.
The discharge of clean agent systems to extinguish a fire
can result in a potential hazard to personnel from the natural
form of the clean agent or from the products of combustion
that result from exposure of the agent to the fire or hot sur-
faces. Unnecessary exposure of personnel, either to the
natural agent or to the products of decomposition, shall be
avoided.
1-2 MOVING OF CONTAINERS
1-2.1 Moving by Trucks
Containers must be shipped in the upright position and prop-
erly secured in place. Containers must not be rolled,
dragged, slid or allowed to be slid from tailgates of vehicles.
A suitable hand truck, fork truck, roll platform or similar de-
vice must be used.
1-2.2 Rough Handling
Containers must not be dropped or permitted to strike vio-
lently against each other or other surfaces.
1-2.3 Storage
Containers must be stored standing upright and secured in
place.
CHAPTER 1
GENERAL INFORMATION
1-2
96-FE13MA-001 October 2002
FE-13™ Fire Suppression System Owner's Manual
1-3 SAFETY CAP
WARNING
!
These instructions must be followed in the exact
sequence as written to prevent serious injury,
death and/or property damage.
Each FE-13 container is factory equipped with a safety cap
installed on the container outlet and securely chained to the
container to prevent loss. This device is a safety feature and
will provide controlled, safe discharge when installed in the
event the container is accidentally actuated.
The safety cap must be installed on the container outlet AT
ALL TIMES except when the containers are connected to
the system piping.
The safety cap is intentionally chained to the container to
prevent loss while in service and must not be removed from
its chain.
For additional information on safe handling of compressed
gas containers, see CGA Pamphlet P1 titled “Safe Han-
dling of Compressed Gases in Containers.” (CGA pam-
phlets may be purchased from the Compressed Gas
Association, Crystal Square Two, 1725 Jefferson Davis
Highway, Arlington, VA, 22202).
1-4 ABOUT THE SYSTEM
The FE-13 system is designed for suppression of Class A,
B and C fires.
Class A Surface Fires—cellulosic material (wood, pa-
per, etc.)
Class B–flammable liquids
Class C–electrical equipment
Because FE-13 poses minimum risk to personnel due to
low toxicity, it is used extensively where people normally
occupy the fire hazard area. Examples of typical FE-13 sys-
tem applications include:
Industrial high ceiling spaces
• Locomotives
Mining equipment
Offshore oil platforms
Oil and Gas processing facilities
Pumping stations
Refinery control area.
Note: IMPORTANT–Per NFPA 2001, FE-13 systems with
use concentrations below the No Obeserved Adverse
Effect Level (NOAEL, 30% v/v) are permitted for use
in occupied areas. FE-13 systems with use con-
centrations above the NOAEL are not permitted for
use in occupied areas.
1-5 FE-13 OVERVIEW
FE-13 suppression agent is a compound of carbon, fluorine
and hydrogen (trifluoromethane CHF3). In its normal state,
FE-13 is a colorless, odorless gas, which is electrically non-
conductive. The agent is stored as a liquid under pressure.
When FE-13 is discharged, it expands throughout the dis-
tribution piping system and at the nozzle, returning to the
gaseous state. In the proper concentration, FE-13 sup-
presses fire by breaking the chain reaction of the combus-
tion process. FE-13 suppresses flame rapidly, helps prevent
reignition, leaves no residue and requires no cleanup after
discharge.
FE-13 will decompose upon contact with temperatures
greater than approximately 1300°F (700°C). Decomposed
FE-13 has a sharp, acrid odor, which is easily recognized
even in small amounts. Decomposed products, including
decomposed fuel, are toxic and minimized with rapid sup-
pression of fire. FE-13 systems are designed to provide
rapid discharge (normally 10 seconds or less) and flame
suppression in order to minimize equipment damage and
reduce danger to personnel.
2-1 96-FE13MA-001
October 2002
FE-13™ Fire Suppression System Owner's Manual
2-1 INTRODUCTION
The FE-13™ Fire Suppression System is designed to dis-
charge a specific amount of FE-13 through nozzles located
within the hazard area. The amount of FE-13 necessary for
the system has been carefully calculated to meet strict re-
quirements set by Underwriters Laboratories and the Na-
tional Fire Protection Association. Additional requirements
may apply depending upon the application, design specifi-
cations and the Authority Having Jurisdiction.
Simply, the FE-13 Fire Suppression System consists of:
FE-13 container(s), discharge piping and nozzles
Actuation devices–electric, pneumatic, cable or
manual
Detection, alarm devices and control panel.
The system must be provided with means for manual op-
eration using one or both of the following UL Listed de-
vices:
Electric actuation station
Automatic detector (control panel required).
Automatic system operation (if provided) can be electric
using UL Listed heat detectors, photoelectric, ionization
smoke detectors or optical flame detectors.
An electrical control head is used to open the valve, which
is part of the agent storage container. Pressure from the
discharge may be used to open the container valves on
additional containers.
If the system has a control panel, refer to the appropriate
Kidde control panel manual as applicable.
2-2 INSTALLATION
The Kidde FE-13 Fire Suppression System must be installed
only by an authorized Kidde distributor. The system must
be installed using genuine Kidde components and installa-
tion materials in accordance with the Design, Installation,
Operation and Maintenance Manual (P/N 96-FE13MA-000
or -002).
Note: The installer must have a current Kidde installation
certificate.
The following items must be checked after the system is
installed:
All areas requiring protection are protected.
A means of manually discharging the FE-13 sys-
tem is provided in a readily accessible location
where it can be operated while leaving the vicinity
of the hazard area. The manual control must be
clearly labeled. The installer of the FE-13 system
should answer any questions regarding the com-
ponents and coverage of the system.
The installer must also demonstrate that the installed sys-
tem conforms to the requirements of the Kidde FE-13 De-
sign, Installation, Operation and Maintenance Manual,
(P/N 96-FE13MA-000 or -002) and the requirements of the
insurance carrier and the Authorities Having Jurisdiction in
the area.
2-3 INSTRUCTIONS IN CASE OF FIRE
1. Direct all occupants to leave the fire area immediately.
Note: Important–Operate the system manually using the
manual release if required.
2. Suspend all operations in the fire area.
3. Have someone contact the fire department immediately,
no matter how small the fire appears to be. Post the
STREET ADDRESS of the building and the fire
department's phone number beside each telephone.
Be familiar with the location of the nearest fire depart-
ment from outside.
4. Make sure all persons have evacuated the fire area in
accordance with individual emergency procedures.
The remote manual release is a device which works elec-
trically. Follow the instructions on the device, i.e., “LIFT
COVER, PULL DOWN” etc. Exit the vicinity of the hazard
immediately.
After the fire is suppressed, do not re-enter the fire area
until the fire department arrives and gives approval.
2-4 POST-OPERATION INSTRUCTIONS
After the system has discharged, contact the Kidde dis-
tributor to reset and recharge the system. Insist that the
system be recharged immediately and with the proper type
and quantity of agent.
CHAPTER 2
INSTALLATION AND MAINTENANCE
2-2
96-FE13MA-001 October 2002
FE-13™ Fire Suppression System Owner's Manual
2-5 INSPECTION AND MAINTENANCE OF THE
SYSTEM
CAUTION
!
The owner of the Kidde FE-13 Fire Suppres-
sion System must comply with these instruc-
tions. Failure to do so may result in inadequate
system performance, property damage and per-
sonal injury.
See Kidde manual 96-FE13MA-000 or -002 for
additional inspection information.
2-5.1 Monthly
1. Inspect all system components, nozzles, distribution
piping and conduit runs for physical damage and/or dis-
placement.
2. Inspect all detectors and control panels for evidence of
damage or missing components. Have damaged or
missing parts replaced immediately (contact the Kidde
distributor). Refer to applicable control panel manual
for additional pertinent inspection procedures.
3. Inspect each container. Container(s) must not show evi-
dence of corrosion or damage.
4. Inspect remote manual release. For electric manual
release devices, check visually to ensure the device is
in the normal or ready position. The path to the remote
release must be clear and unobstructed.
If any discrepancies are noted while making this inspec-
tion, SUSPEND ALL OPERATIONS IN THE PROTECTED
AREA. Contact the Kidde distributor for service and/or re-
pair.
2-5.2 Semi-Annual Inspection
The system must be thoroughly inspected on a semi-an-
nual basis by a certified Kidde distributor. As part of the
semi-annual inspection, the system must be functionally
tested per the instructions in the Kidde FE-13 Fire Sup-
pression System Design, Installation, Operation and Main-
tenance Manual (P/N 96-FE13MA-000 or -002). These
instructions call for functional test of the system and verifi-
cation of the agent quantity in each container. Agent will
not be discharged as a part of the inspection.
For more information regarding inspection and mainte-
nance, contact the Kidde distributor or Kidde directly.
2-6 ADDITIONAL REQUIREMENTS
Portable fire extinguishers are required in addition to the
FE-13 system and for areas not protected by the system.
Consult with the insurance carrier, local Authorities Having
Jurisdiction and the portable fire extinguisher distributor for
sizes, types, spacing and location requirements.
Read, understand and follow the instructions in this manual
and on the container nameplates. Review these instruc-
tions with employees semi-annually, or more frequently.
Place this manual in an accessible area near the FE-13
system for ready reference. Post the name, phone number
and address of the Kidde distributor near the telephone.
Also, post the emergency telephone number of the fire de-
partment and the building street address near all telephones.
If any condition exists which would render the FE-13 sys-
tem inoperative or ineffective, SUSPEND ALL OPERA-
TIONS IN THE PROTECTED AREA IMMEDIATELY. Have
the condition corrected by the Kidde distributor before re-
suming operations.
2-7 ADDITIONAL SPECIFICATIONS AND
DOCUMENTATION
The system must be designed, installed, operated and main-
tained only in accordance with the following documents and
specifications:
Kidde FE-13 Design, Installation, Operation and
Maintenance Manual, P/N 96-FE13MA-000 or -002,
available from the Kidde distributor or Kidde.
Kidde-Fenwal, Inc.
400 Main Street
Ashland, MA 01721
Phone: 508-881-2000
Fax: 508-881-8920
National Fire Protection Association Standard No.
2001, current edition, available from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02269
Copies of the Material Safety Data Sheet (MSDS)
for FE-13 are available in the back of this manual
(Appendix A).
A-1October 2002
FE-13™ Fire Suppression System Owner's Manual
96-FE13MA-001
APPENDIX A
MATERIAL SAFETY DATASHEETS
A-2 October 2002
FE-13™ Fire Suppression System Owner's Manual
96-FE13MA-001
THIS PAGE INTENTIONALLY LEFT BLANK.
The MSDS format adheres to the standards and regulatory requirements
of the United States and may not meet regulatory requirements
in other countries.
DuPont Page 1
Material Safety Data Sheet
----------------------------------------------------------------------
FE-13
3017FR Revised 5-OCT-2001
----------------------------------------------------------------------
----------------------------------------------------------------------
CHEMICAL PRODUCT/COMPANY IDENTIFICATION
----------------------------------------------------------------------
Material Identification
Corporate MSDS Number : DU001064
CAS Number : 75-46-7
Formula : CHF3
CAS Name : Trifluoromethane
Company Identification
MANUFACTURER/DISTRIBUTOR
DuPont Fluoroproducts
1007 Market Street
Wilmington, DE 19898
PHONE NUMBERS
Product Information : 1-800-441-7515 (outside the U.S.
302-774-1000)
Transport Emergency : CHEMTREC 1-800-424-9300(outside U.S.
703-527-3887)
Medical Emergency : 1-800-441-3637 (outside the U.S.
302-774-1000)
----------------------------------------------------------------------
COMPOSITION/INFORMATION ON INGREDIENTS
----------------------------------------------------------------------
Components
Material CAS Number %
METHANE, TRIFLUORO- 75-46-7 100
----------------------------------------------------------------------
HAZARDS IDENTIFICATION
----------------------------------------------------------------------
Potential Health Effects
Inhalation of high concentrations of vapor is harmful and
may cause heart irregularities, unconsciousness, or death.
Intentional misuse or deliberate inhalation may cause death
without warning. Vapor reduces oxygen available for
breathing and is heavier than air. Liquid contact can cause
frostbite.
HUMAN HEALTH EFFECTS:
Overexposure by inhalation may include nonspecific
discomfort such as nausea, headache, or weakness; temporary
nervous system depression with anesthetic effects such as
dizziness, headache, confusion, incoordination, and loss of
consciousness; or with gross overexposure (>20%), possibly
3017FR DuPont Page 2
Material Safety Data Sheet
(HAZARDS IDENTIFICATION - Continued)
temporary alteration of the heart’s electrical activity with
irregular pulse, palpitations, or inadequate circulation.
Individuals with preexisting diseases of the central nervous
or cardiovascular system may have increased susceptibility
to the toxicity of excessive exposures. Eye or skin contact
with the liquid may cause frostbite.
Carcinogenicity Information
None of the components present in this material at concentrations
equal to or greater than 0.1% are listed by IARC, NTP, OSHA or ACGIH
as a carcinogen.
----------------------------------------------------------------------
FIRST AID MEASURES
----------------------------------------------------------------------
First Aid
INHALATION
Immediately remove to fresh air. Keep person calm. Call
a physician. If not breathing, give artificial
respiration. If breathing is difficult, give oxygen.
SKIN CONTACT
Flush with water. Treat for frostbite if necessary by
gently warming affected areas.
EYE CONTACT
In case of liquid contact, immediately flush eyes with
plenty of water for 15 minutes. Call a physician.
INGESTION
Ingestion is not considered a potential route of
exposure.
Notes to Physicians
Because of possible disturbances of cardiac rhythm,
catecholamine drugs, such a epinephrine, should be
considered only as a last resort in life-threatening
emergencies.
----------------------------------------------------------------------
FIRE FIGHTING MEASURES
----------------------------------------------------------------------
# Flammable Properties
Flash Point: No flash point
Flammable Limits in air, % by Volume:
LEL : None per ASTM E681
UEL : None per ASTM E681
Autoignition: Not determined
3017FR DuPont Page 3
Material Safety Data Sheet
(FIRE FIGHTING MEASURES - Continued)
Fire and Explosion Hazards:
Containers may rupture under fire conditions. Decomposition
may occur.
Contact of welding or soldering torch flame with high
concentrations of refrigerant can result in visible changes
in the size and color of torch flames. This flame effect
will only occur in concentrations of product well above the
recommended exposure limits, therefore, stop all work and
ventilate to disperse refrigerant vapors from the work area
before using any open flames.
HFC-23 is not flammable in air at temperatures up to 100
deg. C (212 deg. F) at atmospheric pressure. However,
mixtures of HFC-23 with high concentrations of air at
elevated pressure and/or temperature can become combustible
in the presence of an ignition source. HFC-23 can also
become combustible in an oxygen enriched environment (oxygen
concentrations greater than that in air). Whether a mixture
containing HFC-23 and air, or HFC-23 in an oxygen enriched
atmosphere become combustible depends on the
inter-relationship of 1) the temperature, 2) the pressure,
and 3) the proportion of oxygen in the mixture. In general,
HFC-23 should not be allowed to exist with air above
atmospheric pressure or at high temperatures; or in an
oxygen enriched environment. For example, HFC-23 should NOT
be mixed with air under pressure for leak testing or other
purposes.
Extinguishing Media
As appropriate for combustibles in area.
Fire Fighting Instructions
Use water spray or fog to cool containers. Self-contained
breathing apparatus (SCBA) is required if cylinders rupture
or release under fire conditions. Water runoff should be
contained and neutralized prior to release.
----------------------------------------------------------------------
ACCIDENTAL RELEASE MEASURES
----------------------------------------------------------------------
Safeguards (Personnel)
NOTE: Review FIRE FIGHTING MEASURES and HANDLING (PERSONNEL)
sections before proceeding with clean-up. Use appropriate
PERSONAL PROTECTIVE EQUIPMENT during clean-up.
3017FR DuPont Page 4
Material Safety Data Sheet
(ACCIDENTAL RELEASE MEASURES - Continued)
Accidental Release Measures
Material evaporates at atmospheric pressure (vaporizes).
Ventilate area, especially low places where heavy vapors
might collect. Remove open flames. Wear self-contained
breathing apparatus (SCBA) for large spills or when a
release occurs.
DuPont Fire Emergency Exposure Limits (FEEL) are established
to facilitate the safe release of a fire extinguishant into
spaces normally occupied by people to extinguish a fire or
prevent an explosion and specify airborne concentrations of
brief durations which should not result in permanent adverse
health effects or interfere with escape. For more
information on the applicability of FEEL’s, contact DuPont.
The DuPont Fire Emergency Exposure Limit (FEEL) for this
material is 20% v/v for up to 15 minutes with a 1 minute
not-to-exceed ceiling of 23% v/v.
----------------------------------------------------------------------
HANDLING AND STORAGE
----------------------------------------------------------------------
Handling (Personnel)
Avoid breathing high concentrations of vapor. Avoid contact
of liquid with eyes and prolonged skin exposure. Use with
sufficient ventilation to keep employee exposure below
recommended limits.
Storage
Clean, dry area. Do not heat above 51.7 deg C (125 deg F).
----------------------------------------------------------------------
EXPOSURE CONTROLS/PERSONAL PROTECTION
----------------------------------------------------------------------
Engineering Controls
Normal ventilation for routine manufacturing procedures is
generally adequate. Local exhaust should be used when large
amounts are released. Mechanical ventilation should be used
in low or enclosed places.
Personal Protective Equipment
Impervious gloves should be used when handling liquid.
Chemical splash goggles should be worn when handling liquid.
Under normal manufacturing conditions, no respiratory
protection is required when using this product. Self-
contained breathing apparatus (SCBA) is required if a large
spill or release occurs.
Exposure Guidelines
3017FR DuPont Page 5
Material Safety Data Sheet
Exposure Limits
FE-13
PEL (OSHA) : None Established
TLV (ACGIH) : None Established
AEL * (DuPont) : 1000 ppm, 8 & 12 Hr. TWA
* AEL is DuPont’s Acceptable Exposure Limit. Where governmentally
imposed occupational exposure limits which are lower than the AEL
are in effect, such limits shall take precedence.
----------------------------------------------------------------------
PHYSICAL AND CHEMICAL PROPERTIES
----------------------------------------------------------------------
Physical Data
Boiling Point : -82.1 C (-115.8 F)
Vapor Pressure : 686 psig at 25 deg C (77 deg F)
Vapor Density : 2.4 (Air = 1)
% Volatiles : 100 WT%
Solubility in Water : 0.1 WT% @ 25 C (77 F)
Odor : Slight ethereal
Form : Compressed gas or liquefied gas
Color : Clear, colorless
Density : 1.44 g/cc at -82 deg C (-115.7 deg F)
----------------------------------------------------------------------
STABILITY AND REACTIVITY
----------------------------------------------------------------------
Chemical Stability
Material is stable. However, avoid open flames and high
temperatures.
Incompatibility with Other Materials
Incompatible with alkali or alkaline earth metals - powdered
Al, Zn, Be, etc.
Decomposition
Decomposition products are hazardous. This material can be
decomposed by high temperatures (open flames, glowing metal
surfaces, etc.) forming HF, COF2, or CO. These materials
are toxic and irritating. Contact should be avoided.
Polymerization
Polymerization will not occur.
3017FR DuPont Page 6
Material Safety Data Sheet
----------------------------------------------------------------------
TOXICOLOGICAL INFORMATION
----------------------------------------------------------------------
Animal Data
Inhalation 4-hour LC50: >663,000 ppm in rats
HFC-23 is untested for skin and eye irritancy, and for
animal sensitization.
Effects from single high inhalation exposure to HFC-23
include anaesthetic effects, and nonspecific effects such as
weight loss were observed at concentrations >22%. No
cardiac sensitization was observed in dogs after breathing
800,000 ppm for periods of 5-10 minutes following
epinephrine challenge. In another test, dogs exposed to up
to 30% or up to 50% (with aditional oxygen), had no positive
responses. No cardiac sensitization occurred in baboons
exposed by inhalation to 10%, 30%, 50%, or 70% HFC-23 before
or after an epinephrine challenge; there was a dose-related
decrease in heart rates and differences in respiratory rates
during exposure.
No animal tests are available to define the carcinogenic
hazards of HFC-23. The maternal and developmental NOAEL was
50,000 ppm. HFC-23 is not considered a unique developmental
hazard to the conceptus. There were no developmental or
reproductive effects.
Tests have shown that HFC-23 does not produce genetic damage
in bacterial or mammalian cell cultures. It has not
produced genetic damage in tests on animals.
----------------------------------------------------------------------
DISPOSAL CONSIDERATIONS
----------------------------------------------------------------------
Waste Disposal
Reclaim by distillation or remove to permitted waste
facility. Dispose of in accordance with all Federal, State,
and local regulations.
----------------------------------------------------------------------
TRANSPORTATION INFORMATION
----------------------------------------------------------------------
Shipping Information
DOT/IMO/IATA
Proper Shipping Name : Trifluoromethane
Hazard Class : 2.2
UN No. : 1984
DOT/IMO Label : Nonflammable Gas
3017FR DuPont Page 7
Material Safety Data Sheet
(TRANSPORTATION INFORMATION - Continued)
Shipping Containers
Cylinders
Ton Tanks
Tank Trucks
----------------------------------------------------------------------
REGULATORY INFORMATION
----------------------------------------------------------------------
U.S. Federal Regulations
TSCA Inventory Status : Reported/Included.
TITLE III HAZARD CLASSIFICATIONS SECTIONS 311, 312
Acute : Yes
Chronic : No
Fire : No
Reactivity : No
Pressure : Yes
HAZARDOUS CHEMICAL LISTS
SARA Extremely
Hazardous Substance - No
CERCLA Hazardous Substance - No
SARA Toxic Chemical - No
----------------------------------------------------------------------
OTHER INFORMATION
----------------------------------------------------------------------
NFPA, NPCA-HMIS
NPCA-HMIS Rating
Health : 1
Flammability : 0
Reactivity : 1
Personal Protection rating to be supplied by user depending on use
conditions.
----------------------------------------------------------------------
The data in this Material Safety Data Sheet relates only to the
specific material designated herein and does not relate to use in
combination with any other material or in any process.
Responsibility for MSDS : MSDS Coordinator
> : DuPont Fluoroproducts
Address : Wilmington, DE 19898
Telephone : (800) 441-7515
# Indicates updated section.
3017FR DuPont Page 8
Material Safety Data Sheet
(Continued)
This information is based upon technical information believed to be
reliable. It is subject to revision as additional knowledge and
experience is gained.
End of MSDS
(Use this report to indicate deficiencies, user remarks and recommendations relating to the publication. Fold on dotted line, tape and mail to
KIDDE-FENWAL, Inc., 400 Main Street, Ashland, MA 01721, Attn. Documentation Manager or FAX to 508-881-8920)
DATE:
1. PART NUMBER 2. VOLUME NO. 3. TITLE (NOMENCLATURE)
4. CHANGE NO. OR REV. DATE 5. SYSTEM/EQUIPMENT 6. PRIORITY OF COMMENT
7. USER EVALUATION
MANUAL IS: EXCELLENT GOOD FAIR POOR COMPLETE INCOMPLETE
8. PROBLEM QUESTION SUGGESTION COMMENT: (check one)
9. RECOMMENDED CHANGE TO PUBLICATION
PAGE PARAGRAPH LINE FIGURE TABLE RECOMMENDED CHANGES AND REASON
NO. NO. NO. NO. NO. (Use Blank Continuation Sheets as Required)
10. ORIGINATOR 11. COMPANY NAME
12. ADDRESS
13. KIDDE-FENWAL USE ONLY
a. Received b. Action Necessity c. Priority d. Comments
TECHNICAL MANUAL USER FEEDBACK FORM
KIDDE-FENWAL, Inc.
400 Main Street
Ashland, MA 01721
Attn. Documentation Manager
Place
Stamp
Here
FOLD
FOLD
06-236168-001 Rev. AA ©2002 Kidde-Fenwal, Inc. Printed in USA
LIMITED WARRANTY STATEMENT
Kidde-Fenwal, Inc. represents that this product is free from defects in material and workmanship, and it will repair or replace
any product or part thereof which proves to be defective in workmanship or material for a period of twelve (12) months from
the date of purchase but not to exceed eighteen (18) months after shipment by Kidde-Fenwal Inc. For a full description of
Kidde-Fenwal’s LIMITED WARRANTY, which, among other things, EXCLUDES warranties of MERCHANTABILITY and
FITNESS FOR A PARTICULAR PURPOSE and liability for CONSEQUENTIAL DAMAGES, please read the entire LIMITED
WARRANTY on the Kidde-Fenwal Quotation, Acceptance of Order and/or Original Invoice which will become part of your
sales agreement. Please contact Kidde-Fenwal directly for a return material authorization (RMA) number before returning
material to the factory at Ashland, Massachusetts, shipment prepaid. Kidde-Fenwal will repair or replace and ship prepaid.
These instructions do not purport to cover all the details or variations in the equipment
described, nor do they provide for every possible contingency to be met in connection
with installation, operation and maintenance. All specifications subject to change without
notice. Should further information be desired or should particular problems arise which
are not covered sufficiently for the purchaser’s purposes, the matter should be referred
to KIDDE-FENWAL INC., Ashland, Masssachusetts
Kidde is a registered trademark of Kidde-Fenwal, Inc.
FE-13 is a trademark of DuPont.

Navigation menu