Effective November, 2001

Heat Detectors
Series 600
The Heat Detectors Series 600 are supplied
with the following standard features:
• Low Profile
• Rate-of-Rise and Fixed Temperature
• Visual Indication
• One or Two-Circuit, Normally Open
• Operation Testing
• Easy Installation

Description
The Series 600 Heat Detector is attractive, durable and
features combination rate-of-rise and fixed temperature
operation. Heat detectors are available in 135°F and 200°F
temperature ratings.
Rate-of-rise detects heat by quickly responding to a rapid
temperature increase. Rate-of-rise units have a wide spacing
allowance of 50-foot centers. See specification table for
details.

3-1/4" or 4"
Octagonal Box

Fixed temperature reacts to heat by responding to a specific
temperature setting.
Series 600 Detectors use the same reliable pneumatic rate-ofrise element of former models, but offer added aesthetic
appeal.
The pneumatic rate-of-rise element responds to a rapid rise in
temperature, approximately 15°F. (8°C) per minute, by
expansion of air within the sealed chamber faster than it can
escape through a calibrated vent. The resultant increase in
pressure depresses the diaphragm, causing the electrical
contact to close the circuit.
The fixed temperature element uses a fusible alloy. When
activated, the external heat collector drops away to provide
quick visual confirmation that the element has operated.
The units protrude only 1-3/8 inch from the ceiling surface with
a junction box mounting. They have pleasing contours and an
all-white finish that conforms to ceiling aesthetics.

Installation
Each detector includes a patented reversible mounting plate.
In one position, it easily attaches to 3.25" or 4" octagonal box,
or plaster ring.
In reverse, the plate can be used for open wiring without a
junction box. A 1/4" space between detector and mounting
surface allows for wire connections. All mounting screws are
concealed.
The detector attaches easily to the mounting plate with a push
and twist motion. No tools are required.

All rights reserved (11/01).

Mounting plate is molded of white self-extinguishing thermoplastic rated at 221°F (105°C). The plate is extremely strong
yet adapts to uneven mounting surfaces.

Series 600 Testing Methods
Models 601/621 and 602/622 can be tested by the quick
application of heat from any convenient source. A portable hair
dryer is recommended. However, do not apply heat that
exceeds the fixed temperature rating of the detector.
Models 603/623 and 604/624 cannot be tested. However, the
fusible alloy element used is considered so reliable that testing
is not necessary.

Effective: November, 2001

Model 601 and 621

Model 602 and 622

Model 603 and 623

Model 604 and 624

No Marking
Model 601 (1 circuit)
Model 621 (dua circuit)

Gray Ring
Model 602 (1 circuit)
Model 622 (dual circuit)

Gray Spot
Model 603 (1 circuit)
Model 623 (dual circuit)

Gray Ring and Dot
Model 604 (1 circuit)
Model 624 (dual circuit)

Rate-of-Rise and Fixed
Temperature, 135°F (57°C)

Rate-of-Rise and Fixed
Temperature, 200°F (94°C)

Fixed Temperature only,
135°F (57°C)

Fixed Temperature only,
200°F (94°C)

Applications: Normal
temperature fluctuations
and ceiling temperatures
not exceeding 100°F (38°C)

Applications: Normal temperature fluctuations and ceiling
temperatures exceeding 100°F
(38°C) but not 150°F (66°C)

Applications: Unusually violent
temperature fluctuations
and ceiling temperatures
not exceeding 100°F (38°C)

Applications: Unusually violent
temperature fluctuations and
ceiling temperatures exceeding
100°F (38°C) but not 150°F (66°C)

Maximum Spacing
Allowance* 50 x 50 ft. - UL
30 x 30 ft. - FM

Maximum Spacing
Allowance* 50 x 50 ft. - UL
30 x 30 ft. - FM

Maximum Spacing
Allowance* 25 x 25 ft. - UL
20 x20 ft. - FM

Maximum Spacing
Allowance* 15 x 15 ft. - UL

*Refer to National Fire Alarm Code Standard NFPA 72 for application requirements

Screw Terminals

Important Special Notes
Application: Heat detectors should be used for property
protection. Reliance should not be placed on heat detectors for
Life Safety.
CAUTION: When life safety is involved, smoke detectors
MUST also be used. Detectors must not be painted.
Battery Back-Up: Heat detectors should be electronically
supervised with battery back-up at the panel.
The rate-of-rise mechanism may be subject to reduced
sensitivity over time. Annual testing of the rate-of-rise mechanism is recommended.

Electrical Ratings
6-125 Volts A.C., 3.0 Amps.
6-28 Volts D.C., 1.0 Amps.
125 Volts D.C., 0.3 Amps.
250 Volts D.C., 0.1 Amps.

Listings/Approvals
•
•
•
•
•

Listed by Underwriters Laboratories (UL)
Factory Mutual Approved (FM)
California State Fire Marshal Approval (CSFM)
City of New York (MEA) Listing No. 188-94-E
Listed by Underwriters’ Laboratories of Canada (ULC)

This literature is provided for informational purposes only. CHEMETRONICS assumes no responsibility for the product’s suitability for a
particular application. The product must be properly applied to work correctly. If you need more information on this product, or if you have a
particular problem or question, contact CHEMETRONICS, Ashland, MA; Telephone (800) 496-8383.

Chemetronics
400 Main Street
Ashland, MA 01721 USA
Phone: (800) 496-8383
Fax: (800) 496-7272
Website: www.chemetronics.com
All rights reserved (11/01).



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:08:23
Create Date                     : 1999:11:15 13:54:47Z
Creator Tool                    : Adobe PageMaker 6.5
Modify Date                     : 2008:09:10 16:32:31-04:00
Metadata Date                   : 2008:09:10 16:32:31-04:00
Format                          : application/pdf
Description                     : Heat Detector Series 600
Creator                         : Gross
Title                           : Heat Detector Series 600
Keywords                        : 
Producer                        : Acrobat Distiller 4.0 for Windows
Document ID                     : uuid:206091c9-1c96-894e-9837-8cb679374649
Instance ID                     : uuid:cf129791-5658-dc44-bea5-518201a8a187
Page Count                      : 2
Subject                         : Heat Detector Series 600
Author                          : Gross
EXIF Metadata provided by EXIF.tools

Navigation menu