LENNOX Air Handler (indoor Blower&evap) Manual L0805377

User Manual: LENNOX LENNOX Air Handler (indoor blower&evap) Manual LENNOX Air Handler (indoor blower&evap) Owner's Manual, LENNOX Air Handler (indoor blower&evap) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 14

DownloadLENNOX  Air Handler (indoor Blower&evap) Manual L0805377
Open PDF In BrowserView PDF
LENNOX

INSTALLATION
INSTRUCTIONS

,?,_2003 Lennox (ndustries inc.
Dallas, Texas, USA

Merit® CB28UH
UPFLOW HORIZONTAL
504,739M
05/03

TeCh nical
blications

BLOWER COIL UNITS

Litho

CB28UH Series Units ...........................
General .......................................
Shipping & Packing List .........................
Unit Dimensions ...............................
Requirements ..................................
Installation ....................................
Field Piping Connections ........................
Condensate Drain ..............................
Filters .........................................
Sealing the Unit ................................
Blower Speed Adjustments ......................
Electrical .....................................
System Wiring Diagrams .......................
CB28UH
Upflow Position
(WithOptionalElectncHeat)

U.S.A.

1
1
1
2
4
4
6
6
7
7
7
10
11

RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE

IMPORTANT
The Lennox Merit® CB28UH series blower coil units are
designed for installation with optional field-installed electric heat and a matched remote outdoor unit, These units
are for indoor installation only.
The CB28UH units are designed for upflow/horizontal
positional installations and are shipped (completely assembled) from the factory for upflow and horizontal righthand discharge.

• , WARNING

These instructions are intended as a general guide and
do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.

CB28UH Series
Package 1 of I contains
1 - Assembled blower coil unit

05/03

IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII

504,739M

IIIIIIIIIIIIIIIIIIIIIIIIIIIIIII

DETAIL OF PIPING PLATE

SUPPLY

3/4

......

......................../

3/4
(19)

(_

CONDENSATE
DRAINS
(2)

/

CB28UH
UPFLOW POSITION

mo_izontol)

A,N

CONDENSATE
DRAIN

AUXILIARY DRAIN ON LEFT
MAIN DRAIN ON RIGHT

(Upfl ow)
LINE VOLTAGE
INLETS

LOW VOLTAGE
INLETS
Top and
,.,_!ght Side)
VIEW

(Top and Left Side)
TOP

Model
No.

AUX,_,AR%'/--T
.........
CONDENSATE

CB28UH-018/024
CB28UH-030

5/8

J_

c-_

(16)

/
I
OPTIONAL
ELECTRIC
HEAT

f

mm

inch

mm

inch

A

45-1/4

1149

49-1/4

1251

52-1/2

1334

B

16-1/4

413

21-1/4

540

21-1/4

540

C

20-5/8

524

20-5/8

524

22-5/8

575

D

14-3/4

375

19-3/4

502

19-3/4

502

E

19

483

19

483

21

533

F

15

351

20

508

2O

508

/
i
I

/

SUCTION

L,NE
_=_

I

LIQUID
LINE
i ,

o,o

(16)

Return

F

Air

Lo,o

FRONT VIEW

(16)

mm

(Field
Installed)

FILTER
ACCESS

CB28UH-048
CB28UH-060

inch

DRAIN (Upflow)

I

CB28UH-036
CB28UH-042

5/8
Return Air
I
(25)

(16)

E ---------_ '_SlDE VIEW

Torque Table
Part

Recommended

Torque

Blower Motor Bolts

48 in./Ibs.

5.42 NM

Blower Set Screw

155 in./Ibs.

17.51 NM

Drain Pan Plug

84 in./Ibs.

9.49 NM

TXV Chatleff Nuts

20 ft./Ibs.

27.11 NM

Sheet Metal

16 in Jibs.

1.80 NM

Machine Screws #10

28 in./Ibs.

3.16 NM

Page 2

DETAIL OF PIPING PLATE

CB28UH HORIZONTAL
POSITION
(RIGHT-HAND
AIR DISCHARGE)
FILTER

C

I
1;;,
AUXILIARY

CONDENSATE

DRAIN

(Horizontal)

I

(

MAN 5
I\

)

LIQUID
LINE

C ONDDREN SATE
(Horizontal)

I

SUCTION

OPTIONAL
ELECTRIC
(Field
installed)

LINE

HEAT

TOP VIEW

\

LINE VOLTAGE
INLETS

3/4

11-1/16

(19)

A

\

4

\

(16)
518

all= _I-

Side)
(Top and Right

f

\
5/8

1

(16)

(25)

\

D

B
\

FILTER
ACCESS

5/8
(16)
END

3/4
(19)

f

\

LOW VOLTAGE INLETS
(Bottom and Right Side)

VIEW

FRONT

VIEW

CB28UH HORIZONTAL
POSITION
(LEFT-HAND
AIR DISCHARGE)

END

VIEW

DETAIL OF PIPING PLATE

I- ..........

FILTER

1

C

OPTIONAL
(Field

3/4

11-1/t6

LOW

ELECTRIC
Installed)

HEAT
SUCTION

TOP

VOLTAGE

LINE

LIQUID
LINE

(19)
3/4

f

INLETS
(Top
and

si8 -=114

LeftSide)/

(16)

.__1

/

VIEW

(19)

MAIN

--II

;l#p

A

f

DRAIN

AUXILIARY

ON
DRAIN

RIGHT
ON

LEFT

FILTER

D

MAIN

B

CONDENSATE
DRAIN

............

3/4

I

LINE V )LTAGE INLETS
(Bottom and Left Side)

(19)

518
(16)

518
(16)

AUXILIARY
DRAIN

END VIEW

Model
No.

( 215)

(Horizontal)

FRONT

A

END

VIEW

B

C

D

VIEW

E

F

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

CB28UH-018/024
CB28UH-030

45-1/4

1149

16-1/4

413

20-5/8

524

14-3/4

375

19

483

15

351

CB28UH-036
CB28UH-042

49-1/4

1251

21-1/4

540

20-5/8

524

19-3/4

502

19

483

20

508

CB28UH-048
CB28UH-060

52-1/2

1334

21-1/4

540

22-5/8

575

19-3/4

502

21

533

20

508

Page 3

UPFLOW CONFIGURATION

Installation
ofLennoxblowercoilunitswithorwithoutoptionalelectricheatmustconform
withstandards
intheNationalFireProtection
Association(NFPA)"Standardfor
Installation
of Air Conditioning
andVentilation
Systems
NFPANo,90A,"and"Standardfor Installation
of ResidenceTypeWarmAir HeatingandAir Conditioning
SystemsNFPANo.90B,"manufacturer's
installation
instructionsandlocalmunicipalbuildingcodes,
Thisunitiscertified
forinstallation
clearances
tocombustiblematerialas listedontheunitratingplate,

9
HORIZONTAL
DRAIN PAN*
UPFLOW/
DRAIN PAN

.e

*FOR OPTIMUM PERFORMANCE,
REMOVE HORIZONTAL DRAIN PAN.

CB28UHunitsarefactory-configured
forupflowor horizontalright-handdischargeinstallation,Forhorizontal
left-handdischarge,
somefieldmodification
is required.

FIGURE 1
Horizontal Right-Hand Discharge Application
1 -Remove access panel. Remove corrugated padding
from the space between the blower and coil assembly.

ACAUTION

2 -No further adjustment is necessary. Set unit so that it is
sloped 1/4 inch toward the drain pan end of the unit.

Upflow Application
1 - Remove access panel. Remove corrugated padding
from the space between the blower and coil assemblies.

NOTE - For horizontal applications, an auxiliary drain pan
is required. Refer to local codes.
NOTE - For horizontal applications in high humidity
areas, seal around the exiting drain pipe, liquid line and
suction line to prevent infiltration of humid air.
RIGHT-HAND

DISCHARGE CONFIGURATION

NO ADJUSTMENT

2 -To ensure proper operation, remove the horizontal
drain pan from units in upflow configurations,

UPFLOW/DRAIN

PAN

IS NECESSARY

HORIZONTAL

3 -Place unit in desired location. Make sure that unit is
level. Connect return and supply air plenums as required using sheet metal screws, See figure 1,
4 - Mount units that have no retum air plenum on a stand
at least 14" from the floor for proper air return. Lennox
offers an optional upflow unit stand. (45K31 for
CB28UH-018, 024, 030; 45K32 for CB28UH-036
through -060.)

DRAIN PAN

FIGURE 2

Page 4

3 -If theunitis to besuspended,
it mustbesupported
alongthe entirelengthof the cabinet.If youusea
strap,attacha pieceofangleironorsheetmetaltothe
unit(eitheraboveor below)so thatthefulllengthof
thecabinetis supported.
Usesecuringscrewswhich
arenolongerthan1/2inchtoavoiddamaging
thecoil
orfilter,Seefigure3.Connectthereturnandsupply
airplenumsas requiredusingsheetmetalscrews,
SUSPENDING
HORIZONTAL
UNIT
1/2 in Screws max.

Electrical Inlet
Clearance

8 -Rotate top cap 180 ° front to back and align with unused screw holes, Holes must align with front and
back coil end plates. Note that top cap has a 45 ° bend
on one side and 90° bend on the other. The 90 ° bend
must be on the same side as the horizontal drain
pan. See figures 4 and 5,
NOTE - Use extreme care when re-installing screws into
coil end plate engaging holes. Misaligned screws may
damage coil.
9 -Remove the condensate shield from the right front
and install it on the left front as shown in figure 4,
FIELD MODIFICATION FOR
LEFT-HAND DISCHARGE

SHEET METAL

I
tl

"

I
I

CABINET

I
I

II

90 °
BEND

FRONT VIEW

END VIEW

FIGURE 3

CAUTION

COIL SHOWN IN UP-FLOW POSITION
FOR EASY CONVERSION

FIGURE 4

/
Horizontal Left-Hand Discharge Application
NOTE - For horizontal applications, an auxiliary drain pan
is required. Refer to local codes.
1 - Remove access panel. Remove corrugated padding
from the space between the blower and coil assembly
before operation.
2-Pull coil assembly from unit, Pull off the horizontal
drain pan,
3 -Remove drain plugs from back drain holes on horizontal drain pan and reinstall them on front holes.

BACK COIL
END SEAL
90 ° BEND

FIGURE 5
10 -From the upflow position, flip cabinet 90 ° to the left
and set into place. Put coil assembly back in place,
Secure coil in place by putting the cabinet support rail
back in place, See figures 4 and 6,
LEFT-HAND DISCHARGE

4 -Rotate drain pan 180° front to back and install it on the
opposite side of coil. Follow the instruction steps with
the corresponding numbers in figure 4.

CONFIGURATION

SECURING FLANGE ON
CABINET SUPPORT RAIL

HORIZONTAL
DRIP SHIELD

5-Remove screws from top cap, Remove horizontal
drip shield screw located in the center of the back coil
end seal. See figure 4,
6 -Rotate horizontal drip shield 180 ° front to back.
7-Remove plastic plug from left hole on coil front end
seal and reinstall plug in back hole. Re-install horizontal drip shield screw in front coil end seal, Drip shield
should drain downward into horizontal drain pan inside
coil, See fgure 4,

HORIZONTAL
DRAIN PAN

FIGURE 6

Page 5

NOTE - For horizontal applications in high humidity
areas, seal around the exiting drain pipe, liquid line and
suction line to prevent infiltration of humid air.
11 -Knock out drain seal plate from access door. Secure
plate to cabinet front flange with screw provided,
12 -Flip access door and replace it on the unit,
13 -Set unit so that it is sloped 1/4 inch toward the drain
pan end of the unit, Connect return and supply air plenums as required using sheet metal screws,
14 -If you are going to suspend the unit, the entire length
of the cabinet must be supported. If you use a chain
or strap, attach a piece of angle iron or sheet metal to
the unit (either above or below it), so that the full
length of the cabinet is supported. Use securing
screws which are no longer than 1/2 inch to avoid
damaging the coil or filter, See figure 3. Use sheet
metal screws to connect the return and supply air
plenums,

All CB28UH coils are equipped with a factory-installed, internally mounted expansion valve. Use Lennox L15
(sweat) series line sets as shown in table 1 or use fieldfabricated refrigerant lines, L10 (flare) line sets may be
used by cutting off flare nut. Refer to the piping section of
the Lennox Unit Information Service Manual for proper
size, type and application of field-fabricated lines,
TABLE 1
REFRIGERANT LINE KITS
CB28UH

LIQUID

VAPOR

L15

UNIT

LINE

LINE

LINE SETS

3/8 in

5/8 in

(8 ram)

(16 ram)

-018/-024

L15-26

must be in place to guard against damage to the
paint,
4 - With heat shield in place, sweat in the suction line
connection to the line set. After procedure is completed, remove heat shield,
5 - Place heat shield against piping plate and around the
liquid line connection, Sweat in the liquid line connection to the line set,
6 - Refer to instructions provided with outdoor unit for
leak testing, evacuating and charging procedures.

Connect main condensate drain and route downward to
an open drain or sump, Do not connect drain to a closed
waste system, Refer to figure 7 for typical condensate
trap configuration,
TYPICAL CONDENSATE
MINIMUM 1 INCH (25 ram)
PITCH PER 10 FEET
J
(3048 ram) OF LINE _

Trap

must be deep

difference

COIL
DRAIN PAN

enough

(Generally,

DRAIN CONNECTION

PIPE DIAMETER
DIFFERENCE

to offset

-042/-048

-060

static

FIGURE 7
It is recommended that the auxiliary drain be connected to
a drain line for all units. If auxiliary drain is not connected,
it must be plugged with provided cap, See figure 8 for auxiliary and main drain locations,
LEFT-HAND
DISCHARGE

20 ft, - 50 ft,

UPFLOW

RIGHT-HAND
DISCHARGE

(6 m - 15 m)
[

-030/-036

maximum

2 inches [51ram] minimum).

I

L15-41

3/8 in

3/4 in,

(10 mm)

(19 mm

3/8 in

7/8 in.

(10 ram)

(22 ram)

3/8 in

1-1/8 in,

FIELD

(10 mm)

(29 ram)

FABRICATED

20 ft, - 50 ft,
(6 m - 15 m)
L15-65

ool

oo

% ..............................................

30 ft. - 50 ft,
(9 m - 15 m)

NO TE - CB28UH series evaporators use nitrogen or dry
air as a holding charge. If there is no pressure when the
rubber plugs are removed, check the coil or line set for
leaks before installing. After installation, pull a vacuum
on the line set and coil before releasing the unit charge
into the system.

AUXILIARY

DRAIN ON LEFT

MAIN DRAIN ON RIGHT

FIGURE 8
The following practices are recommended to ensure condensate removal:
1 -Drain piping should not be smaller than the drain connections at drain pan,
2 -A trap must be installed in the main drain line,

1 - Use a wet rag to protect TXV bulb (or remove it) when
brazing suction line,

3 -The trap must be deep enough to offset the difference
in static pressure between drain pan and atmosphere, Generally, two inches is satisfactory for medium static applications.

2 - Be aware of filter access panel when connecting
lines, Filter must be accessible,

4 -Horizontal runs must be sloped 1 inch per 10 feet of
drain line to offset friction,

3 - Place heat shield (damp rag) against the piping plate
and around the suction line connection, Heat shield

5 -An open vent in drain line will sometimes be required to
prevent vapor lock.

Page 6

6 -Drainsshouldbeconstructed
ina mannertofacilitate
futurecleaningandnot interferewithfilteraccess.
Seefigure7.
7 -Auxiliarydrainshouldrunto an areawherehomeownerwill noticeit draining.Refertolocalcodes.
8 -Alldrainconnections
thatarenotusedduringinstallationmustbeplugged
andproperlytorquedto7ft.Ibs.
topreventleaks.

TABLE 2
FILTER DIMENSIONS
FILTER SIZE
Inches (mm)

UNIT MODEL NO.
CB28UH-018/-024

15 x 20 (381 x 508)

CB28UH-030/-042

20 x 20 (508 x 508)

CB28UH-048/-060

20 x 22 (508 x 559)

It is very important to seal the unit so that warm air is not
allowed into the cabinet. Warm air introduces moisture,
which results in condensation problems. This is especially important when the unit is installed in an unconditioned
area.

A IMPORTANT

Make sure the liquid line and suction line entry points are
sealed with either the provided material or with Permagum. Permagum may also be used to seal around the
main and auxiliary drains and around open areas of electrical inlets.

Each unit includes a factory-installed filter. Note that filter
access cover fits over access panel.

Minimum Blower Speeds (With Electric Heaters)

Filters should be inspected monthly and must be cleaned
or replaced when dirty to assure proper operation.
This unit is equipped with standard throw-away type filters

For the minimum allowable speed for the CB28UH series
units with electric heat, refer to the ECB29 installation instructions.

which should be replaced when they become dirty.

Air Volume Adjustment

To remove filter, take off filter access door, slide filter out of
the guides on either side of cabinet, insert new filter and
replace the filter access door. See table 2 for replacement
filter sizes.

Blower speed selection is accomplished by changing the
taps at the harness connector at the blower motor. Refer
to unit wiring diagram in figure 9. Refer to tables 3 through
8 for blower performance data.

TABLE 3
CB28UH-018/024 BLOWER PERFORMANCE
Air Volume

External Static Pressure

(208/230v)
and Motor Watts at Specific

Low

Blower Taps

Medium

High

Pa

cfm

L/s

Watts

cfm

L_

Watts

cfm

L/s

Watts

.00

0

700

330

245

895

420

310

1030

485

375

.05

10

690

325

240

875

415

305

1010

475

370

.10

25

680

320

235

865

410

300

990

470

365

.15

35

665

315

230

850

400

290

970

460

355

.20

50

655

310

225

830

390

285

955

450

350

.25

60

640

300

220

810

385

280

925

440

345

.30

75

625

295

220

795

375

270

900

425

335

.40

100

595

280

210

750

355

255

850

400

320

.50

125

555

260

195

700

330

240

800

380

305

.60

150

510

240

185

640

300

225

725

340

290

.70

175

395

185

165

............

620

295

265

.75

185

........................

570

270

255

in. w.g.

NOTE -AII air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Page 7

CB28UH-030
External Static
Pressure
Pa

cfm

Low
L/s

,00

0

1015

.05

10

995

.10

25

.15

35

.20

TABLE 4
BLOWER PERFORMANCE (208/230v)
Air Volume and Motor Watts at Specific Blower Taps
Wa_s

cfm

High
L/s

535

410

1230

580

450

530

400

1205

570

445

1095

515

390

1190

560

440

1075

505

380

1165

550

430

345

1050

495

375

1140

540

425

435

335

1025

485

365

1105

520

415

425

325

1005

475

355

1080

510

405

860

405

305

950

450

335

1025

485

390

800

380

285

890

420

315

960

450

370

150

740

350

265

810

385

290

875

415

350

.70

175

670

315

240

735

345

270

790

375

330

.75

185

610

290

225

675

320

255

725

340

315

Watts

cfm

480

385

1135

470

375

1120

980

465

365

960

455

355

50

945

445

.25

6O

925

.30

75

900

.40

100

.50

125

.60

in. w.g.

Medium
L_

Watts

NOTE-Att air data is measuredextemaIto unitwith air filter in place.Electricheatershave no appreciableair resistance.
TABLE

CB28UH-036

5

BLOWER PERFORMANCE

(208/230v)

Air Volume and Motor Wa_s at Specific Blower Taps

External Static
Pressure

Low

Medium

High

in. w.g.

Pa

cfm

L/s

Watts

cfm

L_

Watts

cfm

L/s

Watts

.00

0

935

440

420

1145

540

510

1505

710

655

.05

10

930

440

415

1140

535

500

1485

700

640

.10

25

925

435

410

1130

535

490

1475

695

630

.15

35

915

435

395

1125

530

480

1455

685

615

.20

50

910

430

390

1115

525

475

1435

680

600

.25

60

905

425

380

1110

525

465

1420

670

585

.30

75

900

425

370

1100

520

455

1395

660

570

.40

100

885

415

355

1080

510

430

1350

640

540

.50

125

865

410

335

1060

500

415

1300

615

510

.60

150

845

400

315

1030

485

390

1235

585

480

.70

175

820

390

300

............

1160

550

455

.75

185

........................

1015

480

425

NOTE -Att air data is measured extemaIto unitwith air filter in place.Electricheatershave no appreciableair resistance.

CB28UH-042

BLOWER

TABLE 6
PERFORMANCE

(208/230v)

Air Volume and Motor Wa_s at Specific Blower Taps

External Static
Pressure

Low

Medium

High

Pa

cfm

L/s

Watts

cfm

L_

Watts

cfm

L/s

Watts

.00

0

1295

610

520

1520

720

595

1775

840

730

.05

10

1275

605

510

1505

710

585

1750

825

720

.10

25

1255

590

495

1480

700

570

1720

810

710

.15

35

1230

580

480

1455

685

555

1690

795

700

.20

50

1215

575

470

1430

675

540

1650

780

685

.25

60

1195

565

455

1405

665

525

1620

765

675

.30

75

1170

555

440

1380

650

515

1595

750

660

.40

100

1125

530

415

1320

625

485

1515

715

635

.50

125

1065

500

385

1260

595

460

1420

670

605

.60

150

1005

475

360

1175

555

425

1325

625

575

.70

175

910

430

330

1075

505

395

1210

570

545

.80

200

........................

900

425

480

in, w.g.

NOTE- All air data is measuredexternal to unit with air filter in place. Electric heaters have no appreciable air resistance.

Page 8

TABLE 7
BLOWER PERFORMANCE

CB28UH-048

(208/230v)

Air Volume and Motor Wa_s at Specific Blower Taps

External Static
Pressure
Pa

cfm

Low
L/s

Wa_s

cfm

High
L/s

Wat_

.00

0

1590

.05

10

1570

845

805

2055

970

1005

835

790

2035

960

995

.10

25

.15

35

1750

825

785

2005

945

980

1730

815

775

1980

935

.20

970

640

1710

805

765

1945

920

955

700

635

1685

795

755

1915

905

940

690

625

1660

785

745

1885

890

930

1415

670

615

1610

760

725

1820

860

900

1370

645

600

1550

730

705

1750

825

875

150

1310

620

580

1490

705

685

1670

790

845

.70

175

1240

585

560

1405

665

660

1575

745

820

.75

185

1210

570

550

1360

640

645

1520

720

800

Wat_

cfm

750

665

1790

740

660

1770

1555

735

655

1530

720

645

50

1510

710

.25

60

1485

.30

75

1460

.40

100

.50

125

.60

in. w.g.

Medium
L_

NOTE- Alt air data is measuredextemaIto unitwith air filter in place.Etectdcheatershave no appreciableair resistance.
CB28UH-060

BLOWER

TABLE 8
PERFORMANCE

(208/230v)

Air Volume and Motor Watts at Specific

External Static
Pressure

Low

Medium-Low

Medium

Blower Taps
Medium-High

High

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

.00

0

1570

740

575

1800

850

700

2005

945

825

2135

1005

930

2245

1060

1080

.05

10

1550

730

570

1780

840

690

1980

935

815

2110

995

925

2220

1050

1070

.10

25

1530

725

560

1760

830

680

1950

920

805

2080

985

915

2190

1035

1060

.15

35

1520

715

560

1735

820

670

1930

910

795

2055

970

905

2165

1020

1050

.20

50

1495

705

550

1710

805

660

1910

900

790

2025

955

895

2135

1010

1040

.25

60

1475

695

545

1690

795

655

1880

890

780

1995

940

885

2105

995

1030

.30

75

1460

690

540

1670

785

650

1855

875

770

1965

930

875

2075

980

1020

.40

100

1415

670

530

1615

760

630

1795

850

750

1910

900

855

2005

945

995

.50

125

1370

645

520

1560

735

615

1735

820

730

1850

875

835

1935

910

975

.60

150

1310

620

505

1495

705

595

1670

790

710

1780

840

810

1855

875

950

.70

175

1250

590

490

1425

675

575

1600

755

690

1705

805

785

1780

840

925

.80

200

1175

555

470

1360

640

560

1520

715

665

1620

765

755

1685

795

900

.90

225

1025

485

440

1280

605

545

1420

670

645

1520

715

725

1595

750

875

.95

235

1240

585

535

1365

645

630

1460

690

705

1545

730

860

NOTE - All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Page 9

Wiringmustconform
tothecurrentNational
ElectricCode
ANSI/NFPA
No. 70,or CanadianElectricCodePartI,
CSAStandardC22.1,andlocalbuildingcodes.Referto
followingwiringdiagrams.Seeunitnameplate
for minimumcircuitampacityandmaximumovercurrent
protectionsize.

dancewith tables310-16and 310-17in the National
ElectricCode,ANSI/NFPA
No.70or tables1 through4
in the CanadianElectricCode,PartI, CSAStandard
C22.1.
Thisunitisprovidedwithknockoutforconduit.Referto
figure9 for unitschematicwiringdiagram.
Separateopeningshavebeenprovided
for24Vlowvoltageandlinevoltage.Referto thedimensionillustration
forspecificlocation.

Selectthe propersupplycircuitconductorsin accor-

Page 10

,A WARNING

CB28UH

Typical Wiring

FIELD WIRING FOR ECB
SERIES UNITS WITHOUT
CIRCUI[
BREAKERS

Diagram

FIELD
UNITS
CIRCUIT

WIRING FOR ECB SERIES
WITH CIRCUIT BREAKERS

5

CIRCUII

AcB3 A
LB=
A L3=
A
A
Z_

A

: li_1
. g_
_

I =ill....i=ill....i_

- Single Phase

Z

CIRCUI]

Z_cBzA

--

]

A cB A

.II...._ m

L .,I.IIT m

EQUIPMENT

GROUND

L5 IS NOT PRESENT
ON
IP} ELECTRIC
HEATERS

A
ZB_

THE NUMBER
OF CIRCUITS
VARY
ACCOROING
TO HEATER
MODEL,
REFER
TR FAN EDIL
NAMEPLATE
FOR ACTUAL
NUMBER
EMPLOYED

A

EQUIPMENI

GROUND

LOCATED

IN

INDOOR

UNIf

CONNECT
POWER WIRES FROM HEALER LABELED
LI,L2
ON "P"
VOLTAGE
UNITS
AND LI,L2,L3
ON "Y"
VOLTAGE
UNITS
TO TB2 TERMINAL
STRIP
IN INDOOR
UNIT.

24V
BLUE

POWER

R

/_

A
.

-B

k
d

>_

ICON

> 4
>:_ ...................................................
!

LOCATION

MOTOR
PLUG
5 SPD

TO CHANGE

SPEEDS

MOTOR
PLUG
5 SPD

A
COMMON

COMMON

HI

HI

MEO

HI

MED
MEO

MED
LOW

lOW

LOW

MOTOR

---

LINE
--

CLASS

SHOWN

VOLTAGE
II

FIELO

VOLTAGE

WIRING
FIELD

WIRING
@

aoo_

FIGURE 9

Page 11

LH_o

USA

L2 LI

COOLING

ONLY APPLICATION

4i

K5 INDOOR
BLOWER RELAY

•--_-----L

NOTE-USE COPPER
CONDUCTORS ONLY,

I (Black)
L2 (Orange)

REFER TO UNIT RATING PLATE
FOR MINIMUM CIRCUIT AMPACITY
AND MAXIMUM OVERCURRENT
PROTECTION SIZE

CIRCUIT 1
FIELD-SUPPLIED
WIRE NUTS

TRANSFORMER

©

GROUND

,ll

LINE VOLTAGE FIELD INSTALLED
THERMOSTAT

_j

I

F-

l

t_

TBI
TERMI NAL

._1

I

l_

Ir

CLASS 2 VOLTAGE FIELD INSTALLED
NEC/CEC
NOTE-ALL REMAINING WIRES
FACTORY INSTALLED

I

BLOCK

/_k TO EXTERNAL LOAD 24VAC
AT .50 AMP MAXIMUM

J

VV

Z_ FACTORY

COOLING

APPLICATION

WITH ELECTRIC

INSTALLED JUMPERS

HEAT

L2 LI

IL

NOTE-USE COPPER
CONDUCTORS ONLY,

K5 INDOOR
BLOWER RELAY
HEAT ELEMENT

REFER TO UNIT RATING PLATE
FOR MINIMUM CIRCUIT AMPACITY
AND MAXIMUM OVERCURRENT
PROTECTION SIZE

_1

CIRCUIT

NOTE-ALL REMAINING WIRES
FACTORY INSTALLED
CIRCUIT BREAKERS
OR TERMINAL
BLOCK
TRANSFORMER
K52
HEAT RELAY _1

LINE VOLTAGE FIELD INSTALLED
CLASS 2 VOLTAGE FIELD INSTALLED
NEC/CEC

FUSE

==_
GROUND

',1--

TO EXTERNAL LOAD 24VAC
AT .50 AMP MAXIMUM

/_

THERMOSTAT

j
r

Ir

I
L_

L

THERMOSTAT HEAT ANTICIPATION
SETTING .4 AMP (ELECTRIC HEAT)

TBI
_)
TERMINALIO
BLOCK
'T
L.

t _l
I

I

i

.

I
__1

J

_

WHEN TWO STAGE THERMOSTAT IS USED
CONNECT SECOND STAGE HEAT BULB TO
TERMINAL "W2," AND REMOVE JUMPER
BETWEEN TERMINALS "R" AND "W2."

Ak FACTORY

INSTALLED

JUMPERS

VV

Ax

CONNECTION USED ON (Y VOLTAGE)
/k 3L3PHASE
ELECTRIC HEATERS ONLY.
FIGURE 10
Page 12

HEAT PUMP ONLY APPLICATION

L2

I

l-

K3 INDOOR
BLOWER RELAY

[]

CIRCUIT 1

[],A
CIRCUIT BREAKERS
OR TERMINAL
BLOCK
TRANSFORMER

FUSE

GROUND
TBI
TERMINAL
BLOCK

I
1

/k]

I

L
L
CLASS 2 VOLIAGE FIELD INSIALLED
NEC/CEC
NOTE-ALL REMAINING WIRES FACTORY

I

I

I

I
J

I
I
I

I

i

i

I
I
I
I
I

i

I
I
I
I
I/

q[
w

INSTALLED

_>

u_

o

z
Z_TO
Z_
/_Y2

EXTERNAL

LOAD 24VAC AT .50 AMP MAXIMUM

FACTORY INSTALLED JUMPERS
USED ONLY WHEN TWO SPEED COMPRESSOR

AA

IS USED (HP21).

Z_

USING SERVICE LIGHT OPTION (S54) WITH SOME ELECTRONIC THERMOSTATS MAY REQUIRE MOVING S54 COMMON WIRE TO Y1 IN HEAT PUMP
UNIT.

Z_

COMMON

Z_

AMBIENT COMPENSATING

HEAT PUMP CLASS 2
VOLTAGE TERMINALS

USED ONLY ON SOME THERMOSTATS.
THERMISTOR

CONNECTION

USED ONLY ON SOME THERMOSTATS.

FIGURE 11
Page 13

L2

LI

It

CIRCUIT

HEAT PUMP APPLICATION
WITH ELECTRIC HEAT

K3 INDOOR
BLOWER RELAY
HEAT ELEMENT

'I

r_,A
CIRCUIT
BREAKERS
OR TERMINAL
BLOCK

TRANSFORMER

K32
HEAT

RELAY

©

_1

GROUND

CLASS 2 VOLTAGE FIELD INSTALLED
NEC/CBC

FUSE

NOTE - ALL REMAINING

WIRES ARE FACTORY

INSTALLED

_TBI

A

TERM[ NAL
BLOCK

//_

THERMOSTAT HEATANTICIPATION
SETTING 0.4 AMP ELECTRIC HEAT

Z_

FACTORY

INSTALLED

JUMPERS

/I
I
1

I
I

J

SI
THERMOSTAT

,/_

-----

K22
EM HEAT RELAY

cpcp pl

$23
0UTO00R
THERMOSTAT
(IF USED)

I

'_(

I
I

J i
I
T

I

]
1
I
.I

t
I

I

'

Ii

/_

WHEN
tS USED,
CONNECT
LEADS "R'
TO AND
TERMINALS
"R"
ANDOUTDOOR
"W2" AND THERMOSTAT
REMOVE JUMPER
BETWEEN
TERMINALS
"W2."

Z_

EMERGENCY HEAT RELAY (USED ONLY tF OUTDOOR T'STAT IS USED) FIELD PROVIDED
AND INSTALLED NEW INDOOR UNIT, 24VAC 5VA MAX NEC/CEC CLASS 2

LO ',,_
LnZ

o

/_k

USING SERVICE LIGHT OPTION ($54) WITH SOME ELECTRONIC THERMOSTATS MAY REQUIRE MOVING $54 COMMON WIRE TO Y1 IN HEAT PUMP UNIT.

c_n-

N

Z_

COMMON

z_Y2
Z_

USED ONLY ON SOME THERMOSTATS.

USED ONLY WHEN TWO SPEED COMPRESSOR
AMBIENT

COMPENSATING

THERMISTOR

IS USED (HP21).

CONNECTION

USED ONLY ON SOME THERMOSTATS.

FIGURE 12
Page 14

i-- i-,__j

i i II ,
_

c,.

°°i
z,



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 14
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Mon Jun 30 04:20:10 2008
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu