LENNOX Air Conditioner/heat Pump(outside Unit) Manual L0805502
User Manual: LENNOX LENNOX Air conditioner/heat pump(outside unit) Manual LENNOX Air conditioner/heat pump(outside unit) Owner's Manual, LENNOX Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 16
Download | |
Open PDF In Browser | View PDF |
INSTALLATION MANUAL ,?u2006 Lennox industries ]nc+ Dallas, Texas, USA HSXB15 Series Units CONDENSING UNITS 504,710M 03/06 Supersedes 11/05 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING A IMPORTANT _ j_jj Technical Publications Litho U.S.A. HSXB15 Outdoor Unit .......................... Shipping & Packing List ........................ General Information ........................... Parts Arrangement & Unit Dimensions ........... Setting The Unit ............................... Electrical ..................................... Refrigerant Piping ............................. Flushing Existing Line Set & Indoor Coil .......... Refrigerant Metering Device .................... Manifold Gauge Set ........................... Service Valves ................................ Leak Testing .................................. Evacuation ................................... Start-Up ...................................... Refrigerant Charging ........................... System Operation ............................. Maintenance .................................. Optional Accessories .......................... Homeowner Information ........................ Thermostat Operation .......................... Start-Up & Performance Check List .............. 1 1 2 2 3 4 4 7 9 9 9 10 10 11 11 13 15 15 15 16 16 WARNING HSXB15 outdoor units use R-410A HFC refrigerant. This unit must be installed with a matching indoor coil and line set as outlined in the Lennox Engineering Handbook, HSXB15 outdoor units are designed for use in expansion valve systems only. They are not designed to be used with other refrigerant flow control devices, The filter drier is factory-installed. The Lennox Engineering Handbook lists indoor TXV kits that must be ordered separately. 1 - Assembled HSXB15 outdoor unit 2 - Grommets (for liquid and suction lines) 1 - Bushing (for low voltage wiring) Check equipment for shipping damage. If you find any damage, immediately contact the last carrier. 03/06 IIIB+IIIIIIIIIIIHIIIIIIIIIIIll Page 1 504,710M IIIIIIIIIIIIIIIIIIIIIIIIIIIIIII COMPRESSOR RUN CAPACITOR SYSTEM OPERATION MONITOR CONTACTOR / VAPOR LINE " GROUND LUG INLET AIR ,_ VAPOR VALVE INLET AIR - AND GAUGE PORT COMPRESSOR POWER TERMINALS LIQUID LINE " SERVICE VALVE AND GAUGE PORT "_ FILTER DRIER DISCHARGE LINE LOW PRESSURE SWITCH HIGH PRESSURE SWITCH "_ INLETAIR TOP VIEW PARTS ARRANGEMENT ELECTRICAL t INLETS _'_,, VAPOR LINE INLET'_. \\ LIQUID LINE INLET\xX\_ C X _ tDISCHARGE AIR ......................................................................... ....................................................................................................... 4-1/2 A (114) 2-9/16 (65) D - (,) II I _-_142)_1_ 2 F -_C142_ 1-3/8..._ !_ (35) "Yll (51) rE. I_,..J 6-1/16L,= "'-I (154)I_' SIDE VIEW Figure 1 HSXB15 Model Dim. -024 -030,-036,-042 -048 -060 A 27-7/8 (708) 30-7/8 (784) 34-7/8 (886) 40-7/8 (1038) B 25-7/8 (657) 32-1/8 (816) 32-1/8 (816) 32-1/8 (816) C 29-7/8 (759) 34-1/16 (865) 34-1/16 (865) 34-1/16 (865) D 12-1/4 (311 ) 12-3/4 (324) 13-3/4 (349) 19-3/4 (502) E 22-7/16 (570) 26-5/8 (676) 26-5/8 (676) 26-5/8 (676) These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation. Table 1 Torque Requirements Part Recommended Service valve cap Sheet metal screws 8 ft.- lb. 16 in.- lb. Torque 11 NM 2 NM F 14-7/16 (367) 18-5/8 (473) 18-5/8 (473) 18-5/8 (473) G 22-1/8 (562) 28-1/8 (718) 28-1/8 (718) 28-1/8 (718) Machine screws #10 28 in.- lb. 3 NM H 2-7/8 (73) 3-7/8 (98) 3-7/8 (98) 3-7/8 (98) Compressor bolts 90 in.- lb. 10 NM J 5-1/2 (140) 7-1/2 (191) 7-1/2 (191) 7-1/2 (191) Gauge port seal cap 8 ft.- lb. 11 NM Page 2 504710M 03/06 CAUTION Referto unitdimensions(figure1,on page2) forsizing mounting slab,platforms or supports.Refertofigure2 for installation clearances. Installation Slab Mounting Clearances notes see "_ see notes When installing a unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground would not collect around the unit. See figure 3. Slab may be level or have a slope tolerance away from the building of not more than 2 degrees or 2 inches per 5 feet (51 mm per 1524 mm)+ Slab Mounting INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [51 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE. see notes DISCHARGE AIR ,_ STRUCTURE BUILDING i- NOTES A service access clearance of 30" (762 mm) must be maintained in front of the service access panel, Clearance to one side must be 36+' (914 mm), Clearance to one of the remaining two sides may be 12" (305 mm) and the final side may be 6+'(152 mm), MOUNTING SLAB / A clearance of 24" (610 mm) must be maintained between two units. 48" (1219 mm) clearance required on top of unit. Maximum soffit overhang is 36" (914 mm). Figure --r GROUNDLEVEL 2 Figure 3 CAUTION Roof Mounting Install unit at a minimum of 4 inches above surface of the roof, Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters. Either redwood or steel supports are recommended. Page 3 HSXB15 SERIES 4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit, See figure 4, In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC). Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. Typical Wiring Diagram Outdoor Unit Thermostat /-q Indooj.Unit /.--. p..... t RJ ___ L_J R- System Operation J (R) v v ® I A, WARNING Field Low Voltage @ heat [_Y1 Q Outdoor coolinq indoor tG) (G) blower ./_C Q common Outdoor Unit NOTE - see unit widng diagram for power supply connections. If indoor unit is not equipped with blower relay It must be field-provided and installed (P-8-3251 or equivalent). Figure 4 1, Install line voltage power supply to unit from a properly sized disconnect switch, Outdoor 2, Ground unit at unit disconnect switch or to an earth ground, B4 OUTDOOR NOTES • Connect conduit to the control box using a proper conduit fitting. • Units are approved for use only with copper conductors. • 24V, Class II circuit connections are made in the low voltage junction box, Refer to figure 5 for field wiring diagram. • A complete unit wiring diagram is located inside the unit's front access panel, AWG # Insulation type less than 100' (30m) 18 more than 100' (30m) 16 color-coded, temperature , o , , rating 35 C minimum 3, Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1,5 m) from the floor, It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations, 64OUTDOOR FAN G) 03/06 GROUND KI COMPRESSOR ]APACITOR HIGH ]OMMON CONTACTOR LUG,S. L2 L1 z_ BLACK=COMMON ORANGE-RUN PURPLE- 206=230/60/I Cl2 DUAL CAPACITOR CAPADITOR _NOTEFOR USE WITH COPPER ONLY,REFER TO UNIT CONDUCTORS RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE Z_WARNINOELECTRIC SHUCK HAZARD,CAN CAUSE INJURY OR DEATH,UNIT NUST BE GROUNDED IN ACCORDANCE WiTH NATIONAL AND LOCAL CODES. _LINE VOLTAGE FIELD INSTALLED Figure 5 If the HSXB15 unit is being installed with a new indoor coil and line set, the connections should be made as outlined in this section. If an existing line set and/or indoor coil (used with mineral oil) is going to be used to complete the HSXB15 system, refer to the following section which includes flushing procedures. Page 4 504710M Diagram FAN LESS NOTE - For proper voltages, select thermostat wire gauge per the following chart: Wire run length Unit Field Wiring Fieldrefrigerantpipingconsistsof liquidandvaporlines fromtheoutdoorunit(sweatconnections) totheindoorcoil (flareorsweatconnections). UseLennoxL15(sweat,nonflare)serieslinesetsasshownintable2 or usefield-fabricatedrefrigerant lines.Valvesizesarealsolistedintable2. points to consider when placing and installing a high-efficiency outdoor unit: 1. Placement - Be aware that some localities are adopting sound ordinances based on how noisy the unit is from the adjacent property not at the original installation. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. Table 2 Refrigerant Model No. Line Sets Valve Field Size Connections Recommended Liquid Line Liquid Line Vapor Line Line Set Vapor Line 2. Line Set Isolation - The following illustrations demonstrate procedures which ensure proper refrigerant line set isolation. Figure 6 shows how to place the outdoor unit and line set. Figure 7 shows how to install line sets on horizontal runs. Figure 8 shows how to install line sets on vertical runs. Finally, figure 9 shows how to make a transition from horizontal to vertical. L15 Line Sets -024 3/8 in. 3/4 in. 3/8 in. 3/4 in. L15-41 -030 -036 (10mm) (19mm) (10mm) (19mm) 15 ft. - 50 ft. (4.6 m - 15 m) -042 3/8 in. 7/8 in. 3/8 in. 7/8 in. L15-65 -048 (10 mm) (22 ram) (10 ram) (22 ram) 15 ft.-50 ft. (4.6 m - 15 m) -060 3/8 in. 1-1/8 in. 3/8 in. 1-1/8 in. Field (10 mm) (29 ram) (10 ram) (29 ram) Fabricated Outside NOTE - Units are designed for line sets of up to 50' (15m). Refrigerant Connections - HSXB15 with New Indoor Coil and Line Set Unit Placement Install unit away from windows and neighbors' windows Matched and Installation _ _x -- NX" If an existing indoor coil that was equipped with an RFCI metering device is being replaced, the liquid line must also be replaced prior to the installation of the HSXB15 unit. If refrigerant lines are routed through a wall, seal and isolate the opening so vibration does not transmit to building, Installing Refrigerant Line During the installation of any heat pump or a/c system, it is important to properly isolate the refrigerant lines to prevent unnecessary vibration. Line set contact with the structure (wall, ceiling or floor) causes some objectionable noise when vibration is translated into sound. As a result, more energy or vibration can be expected. Closer attention to line set isolation must be observed. Following are some Refrigerant To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties. Two 90 ° elbows installed in line set will reduce line set vibration. Figure Line Sets: Installing Horizontal 6 Runs WIRE TIE (Around vapor line only) 8 feet STRAPPING MATERIAL (Around vapor line only) \ feet METAL SLEEVE TAPE OR WIRE TIE Strap the vapor line to the joist or rafter at 8 ft. intervals then strap the liquid line to the vapor line. FLOOR JOIST OR ROOF RAFTER TAPE OR WIRE TIE Figure 7 Page 5 HSXB15 SERIES Refrigerant Line Sets: Installing Vertical Runs (new construction shown) NOTE - Similar installation practices should be used if line set is to be installed on exterior of outside wall. OUTSIDE WALL IMPORTANT - Refrigerant lines must not contact wall. VAPOR LINE LI UID LINE WIRE TIE s INSIDEWALL STRAP SLEEVE VAPOR LINE WRAPPED WITH ARMAFLEX IMPORTANT! Refrigerant lines must not contact structure. WIRE TIE LIQUID WOOD BLOCK OiTSIDE WALL iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_ WIRE TIE STRAP CAULK PVC PIPE FIBERGLASS INSULATION SLEEVE Figure Refrigerant Line Sets: Transition 8 From Vertical ANCHORED HEAVY NYLON WIRE TIE AUTOMOTIVE MUFFLER-TYPE HANGER WALL STUD WALL STUD METAL SLEEVE Strap Liquid Line To Vapor Line Strap Liquid Line To Vapor Line LIQUID LINE UID LINE VAPOR LINE - WRAPPED IN ARMAFLEX METAL SLEEVE Figure Page 6 504710M 03/06 To Horizontal 9 VAPOR LINE - WRAPPED IN ARMAFLEX WARNING IMPORTANT Brazing Connection Procedure 1, Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line. 2+ Before making line set connections, use dry nitrogen to purge the refrigerant piping. This will help to prevent oxidation and the introduction of moisture into the system. IMPORTANT 3+ Wrap a wet cloth around the valve body and copper tube stub to protect it from heat damage during brazing. Wrap another wet cloth underneath the valve body to protect the base paint. NOTE - The tube end must stay bottomed in the fitting during final assembly to ensure proper seating, sealing and rigidity. 4+ Install the field-provided thermal expansion valve (approved for use with R-410A refrigerant) in the liquid line at the indoor coil. 5+ Use silver alloy brazing rods (5 or 6 percent minimum silver alloy for copper-to-copper brazing or 45 percent silver alloy for copper-to-brass or copper-to-steel brazing) which are rated for use with R-410A refrigerant. Wrap a wet cloth around the valve body and the copper tube stub. Remove light maroon washers from service valves and shield light maroon stickers in order to protect them during brazing. Braze the line set to the service valve. ,WARNING NOTE - If the indoor unit line and set is new, skip this section and go on to the Manifold Gauge Set section. CAUTION Required Equipment You will need the following equipment in order to flush the existing line set and indoor coil: two clean HCFC-22 recovery bottles, an oilless recovery machine with a pump down feature, and two sets of gauges (one for use with HCFC-22 and one for use with the R-410A). Flushing Procedure 1. Remove existing HCFC-22 refrigerant using the appropriate procedure below (see figure 10): If the existing outdoor unit is not equipped with shut-off valves, or if the unit is not operational AND you plan to use the existing R-22 refrigerant to flush the system • Disconnect all power to the existing outdoor unit. • Connect to the existing unit, a clean recovery cylinder and the recovery machine according to the instructions provided with the recovery machine. • Remove all R-22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant. • Disconnect the liquid and vapor lines from the existing outdoor unit. Page 7 HSXB15 SERIES Flushing Connections Inverted R-22 Cylinder (Contains clean R-22 to be used for flushing) Low Pressure EXISTING VAPOR LINE - High Pressure HSXB15 UNIT VaP°i_eLi_/aelve_[ EXISTING INDOOR COIL EXISTING LIQUID LINE _ Sk_r_ii_ el-_ve I fr" NOTE - The inverted R-22 cylinder must contain at least the same amount of refrigerant as was recovered from the existing system. Tank Inlet Return Discharge RECOVERY CYLINDER RECOVERY MACHINE Figure 10 ff the existing outdoor unit is equipped with manual shut-off valves AND you plan to use NEW R-22 refrigerant to flush the system • Start the existing R-22 system in the cooling mode and close the liquid line valve, • Pump all of the existing R-22 refrigerant back into the outdoor unit, (It may be necessary to bypass the low pressure switches to ensure complete refrigerant evacuation.) • When the low side system pressures reach 0 psig, close the vapor line valve. • Disconnect all power to the existing outdoor unit. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system. • Disconnect the liquid and vapor lines from the existing outdoor unit, 2. Remove the existing outdoor unit. Set the new R-410A unit and follow the brazing connection procedure which begins on the previous page to make line set connections. DO NOT install the expansion valve at this time. Make low voltage and line voltage connections to the new outdoor unit. DO NOT turn on power to the unit or open the outdoor unit service valves at this time. 3. Remove the existing refrigerant flow control orifice or thermal expansion valve before continuing with flushing procedures. Theexisting devicesare not approved for use with R-410A refrigerant and may prevent properflushing, Usea field-provided fitting to reconnect the lines. Page 8 504710M 03/06 IMPORTANT 4. Remove the pressure tap valve cores from the HSXB15 unit's service valves. Connect an HCFC-22 cylinder with clean refrigerant to the vapor service valve, Connect the HCFC-22 gauge set to the liquid line valve and connect a recovery machine with an empty recovery tank to the gauge set, 5. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor coil. 6. Invert the cylinder of clean HCFC-22 and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machine. 7. After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the HCFC-22 vapor is recovered. Allow the recovery machine to pull a vacuum on the system, NOTE -A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor coil, A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush. Each time the system is flushed, you must allow the recovery machine to pull a vacuum on the system at the end of the procedure. 8, Close the valve on the inverted HCFC-22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off, 9, Use dry nitrogen to break the vacuum on the refrigerant lines and indoor coil before removing the recovery machine, gauges and HCFC-22 refrigerant drum. Reinstall pressure tap valve cores into HSXB15 service valves. The liquid line and vapor line service valves and gauge ports are used for leak testing, evacuating, charging and checking charge, Each valve is equipped with a service port which has a factory-installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal, Front-Seated Service Valve (Liquid Line) The front-seated service valve is shown in figure 12. When this valve is closed, the service port is open to the line set. Access the service port and open and close valves as described in the following paragraphs, 10. Install the field-provided expansion valve (approved for use with R-410A refrigerant) in the liquid line at the indoor coil. Front-Seated Liquid Line Service (Valve Shown Closed) Valve SERVICE Insert hex wrench here HSXB15 units are used in check expansion valve systems only. See the Lennox Engineering Handbook for approved TXV match-ups and application information, STEM CAP Check expansion valves equipped with Chatlefffittings are available from Lennox. Refer to the Engineering Handbook for applicable expansion valves for use with specific match-ups. To indoor coil To outdoor coil (Valve Shown Open) If you install a check expansion valve with an indoor coil that includes a fixed orifice, remove the orifice before installing the check expansion valve. insert hex wrench here SERVICE PORT See figure 11 for installation of the check expansion valve, STEM CAP Metering Device O-RING EXPANSION / // Installation O-RING VALVE & To indoor coil (See NOTE) Service port Is open to line set when valve is closed (front seated) STRAINER DISTRIBUTOR _'_%... Figure _ LIQUID LINE STUB To Access NOTE - If necessa04 remove R-22 flow control device (fixed odfice/thermal expansion valve) from existing line set before installing R-410A approved expansion valve and o-ring. Figure To outdoor coil Schrader 12 Port: 1, Remove access panel, 2. Remove service port cap with an adjustable wrench, 3, Connect gauge to the service port. 11 4, When testing is completed, replace service port cap, Tighten finger tight, then torque per table 1 (Page 2), Manifold gauge sets used with systems charged with R-410A refrigerant must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures d 0 - 800 on the high side and a low side d 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating, To Open Front-Seated Service Valves: 1, Remove stem cap with an adjustable wrench, 2, Use a service wrench with a hex-head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to backthe stem out counterclockwise as far as it will go, 3, Replace the stem cap, Tighten finger tight, then torque per table 1 (Page 2), To Close Front-Seated Service Valves: 1. Remove the stem cap with an adjustable wrench. Page 9 HSXB15 SERIES 2, Use a service wrench with a hex-head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to turn the stem clockwise to seat the valve. Tighten it firmly, 6, After a few minutes, open a refrigerant port to check that an adequate amount of refrigerant has been added fordetection (refrigerant requirements will varywith line lengths). Checkalljoints for leaks. Purge dry nitrogen and R-410A mixture. Correct any leaks and recheck. 3, Replace the stem cap, Tighten finger tight, then torque per table 1 (Page 2). A IMPORTANT After the line set has been connected to the indoor and outdoor units, the line set connections and indoor unit must be checked for leaks, I WARNING I A.WARNING Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper piping and compressor parts, IMPORTANT 1, Connect manifold gauge set to the service valve ports: • low pressure gauge to vapor line service valve • high pressure gauge to liquid line service valve 2, Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of R-410A, 3, Connect micron gauge. Using an Electronic Leak Detector 1, Connect the high pressure hose of the manifold gauge set to the vapor valve service port. (Normally, the high pressure hose is connected to the liquid line port, however, connecting it to the vapor port helps to protect the manifold gauge set from damage caused by high pressure,) 2+ With both manifold valves closed, connect the cylinder of R-410A refrigerant, Open the valve on the R-410A cylinder (vapor only). 3+ Open the high pressure side of the manifold to allow R-410A into the line set and indoor unit. Weigh in a trace amount of. [A trace amount is a maximum of 2 ounces (57 g) refrigerant or 3 pounds (31 kPa) pressure.] Close the valve on the R-41OA cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect R-410A cylinder, 4. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set, 5+ Adjust dry nitrogen pressure to 150 psig (1034 kPa), Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor coil, Page 10 504710M 03/06 4, Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set, 5, Open both manifold valves and start the vacuum pump. 6, Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29,01 inches of mercury), During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure. A rapid rise in pressure indicates a relatively large leak, If this occurs, repeat the leak testing procedure, NOTE - The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure, Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure. 7, When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit, Close the manifold gauge valves, This system is charged with R410A refrigerant which operates at much higher pressures than HCFC-22, The expansion valve and liquid line filter drier provided with the unit are approved for use with R-410A. Do not replace them with components designed for use with HCFC-22. This unit is NOT approved for use with coils which include metering orifices or capillary tubes, WARNING 8, Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit. 9, Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves. 10, When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of R-410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit, Close manifold gauge valves and shut off the R-410A cylinder and remove the manifold gauge set, 1, Rotate fan to check for frozen bearings or binding, 2, Inspect all factory- and field-installed wiring for loose connections, 3, After evacuation is complete, open the liquid line and vapor line service valves to release the refrigerant charge (contained in outdoor unit) into the system. 4, Replace the stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn, 5, Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit's nameplate. If not, do not start the equipment until you have consulted the power company and the voltage condition has been corrected. 6, Set the thermostat for a high stage cooling demand (Y1 and Y2 demand). Turn on power to the indoor blower and close the outdoor unit disconnect switch to start the unit, 7, Recheck voltage while the unit is running. Power must be within range shown on the nameplate, IMPORTANT Factory Charge Units are factory charged with the amount of R-410A refrigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with 15 feet (4.6 m) line set. For varying lengths of line set, refer to table 3 for refrigerant charge adjustment, Table 3 Refrigerant Charge per Line Set Lengths Liquid Line Set Diameter Ounces per 5 feet (grams per 1.52 meter) adjust from 15 ft. (4.57m) line set* 3/8 in. (9.5mm) 3 ounces per 5 feet (85 grams per 1.52 meter) *Add the amount shown if line length is greater than 15' (4.57m), subtract the amount shown if less than 15'. Units Delivered Void of Charge A IMPORTANT If the system is void of refrigerant, clean the system using the following procedure: 1, Use dry nitrogen to pressurize the system and check for leaks, Repair leaks, if possible, 2, Evacuate the system to remove as much of the moisture as possible (triple evacuation), 3, Use nitrogen to break the vacuum and install the provided filter drier in the system. 4. Evacuate the system again. Then, weigh the appropriate amount of R-410A refrigerant (listed on unit nameplate) into the system. 5. Start the unit and monitor the system to determine the amount of moisture remaining in the oil. Use test kit 10N46 to verify that the moisture content is within the kit's dry color range, 6. If the moisture content is not within the dry color range, add a new filter drier between the liquid valve and the TXV. You may have to add a new filter drier several times to achieve the required level of dryness, If system dryness is not verified, the compressor will fail in the future. Checking Charge The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is determined by the unit's refrigerant metering device and the outdoor ambient temperature. Measure the liquid line temperature and the outdoor ambient temperature as outlined below: Page 11 HSXB15 SERIES 1, Connect the manifold gauge set to the service valves: • low pressure gauge to vapor valve service port • high pressure gauge to liquid valve service port Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of R-410A. 2, Set the room thermostat to call for heat. This will create the necessary load for properly charging the system in the cooling cycle, 2, Attach high pressure gauge set and operate unit for several minutes to allow system pressures to stabilize. 3. Compare stabilized pressures with those provided in table 5, "Normal Operating Pressures." Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system. Pressures higher than those listed indicate that the system is overcharged, Pressures lower than those listed indicate that the system is undercharged. A temperature/pressure chart for R-410A refrigerant is provided in table 6 for your convenience, Verify adjusted charge using the approach method, 4. Use the same digital thermometer you used to check the outdoor ambient temperature to check the liquid line temperature. 5. The difference between the ambient and liquid temperatures should match values given in table 4, If the values don't agree with the those in table 4, add refrigerant to lower the approach temperature, or recover refrigerant from the system to increase the approach temperature. Be aware d the R-410A refrigerant cylinder. It will be light maroon-colored. Refrigerant should be added through the vapor valve in the liquid state. 3, Use a digital thermometer to record the outdoor ambient temperature. 4, When the heating demand has been satisfied, switch the thermostat to cooling mode with a set point of 68°F (20°C). When pressures have stabilized, use a digital thermometer to record the liquid line temperature. 5, The outdoor temperature will determine which charging method to use. Proceed with the appropriate charging procedure. Charge Using the Weigh-in Method Outdoor Temperature < 65°F (18°C) If the system is void of refrigerant, or if the outdoor ambient temperature is cool, the refrigerant charge should be weighed into the unit, Do this after any leaks have been repaired. 1, Recover the refrigerant from the unit, Table 4 2, Conduct a leak check, then evacuate as previously outlined, Approach 3, Weigh in the unit nameplate charge, If weighing facilities are not available or if you are charging the unit during warm weather, follow one of the other procedures outlined below, HSXB15-024 Approach Temperature Liquid Line - Outdoor Ambient °F (°C) 8 + 1 (4.5 + .5) HSXB15-030 8 + 1 (4.5 + .5) Charge HSXB15-036 6 + 1 (3.3 +.5) HSXB15-042 9 + 1 (5+ .5) HSXB15-048 8 + 1 (4.5 + .5) HSXB15-060 12 + 1 (6.7 + .5) Using the Approach Model No. Values Method - Outdoor Temperature _>65°F (18°C) The following procedure is intended as a general guide and is for use on expansion valve systems only. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging. 1, Record outdoor ambient temperature thermometer, NOTE - For best results, the same electronic thermometer should be used to check both outdoor ambient and fiquid line temperatures, using a digital Table 5 Normal Mode TXV Operating HSXB15-024 Pressures HSXB15-030 (Liquid Outdoor Coil Entering Air Temp. °F (°C) HSXB15-036 Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor 65 (18.3) 253 132 232 130 235 128 241 131 226 130 240 130 75 (23.9) 288 135 271 132 276 130 282 133 266 132 279 132 85 (29.4) 330 137 314 135 320 132 326 135 310 135 321 135 95 (35.0) 376 140 360 137 367 134 373 137 356 137 368 137 105 (40.6) 425 143 412 140 421 137 424 139 407 139 418 140 Page 12 504710M 03/06 +10 and Vapor +5 psig) HSXB15-042 HSXB15-048 HSXB15-060 Table 6 R-410A Temperature Filter Drier (°F) - Pressure A filter drier is factory-installed with each HSXB15 unit. This filter drier is installed to ensure a clean, moisture-free system. A replacement filter drier is available as Lennox part no, 37L5201, (Psig) °F Psig °F Psig °F Psig °F Psig 32 100.8 63 178.5 94 290.8 125 445.9 33 102.9 64 181.6 95 295.1 126 451.8 34 105.0 65 184.3 96 299.4 127 457.6 35 107.1 66 187.7 97 303.8 128 463.5 36 109.2 67 190.9 98 308.2 129 469.5 37 111.4 68 194.1 99 312.7 130 475.6 38 113.6 69 197.3 100 317.2 131 481.6 39 115.8 70 200.6 101 321.8 132 487.8 40 118.0 71 203.9 102 326.4 133 494.0 41 120.3 72 207.2 103 331.0 134 500.2 42 122.6 73 210.6 104 335.7 135 506.5 43 125.0 74 214.0 105 340.5 136 512.9 44 127.3 75 217.4 106 345.3 137 519.3 45 129.7 76 220.9 107 350.1 138 525.8 46 132.2 77 224.4 108 355.0 139 532.4 47 134.6 78 228.0 109 360.0 140 539.0 48 137.1 79 231.6 110 365.0 141 545.6 49 139.6 80 235.3 111 370.0 142 552.3 50 142.2 81 239.0 112 375.1 143 559.1 51 144.8 82 242.7 113 380.2 144 565.9 52 147.4 83 246.5 114 385.4 145 572.8 53 150.1 84 250.3 115 390.7 146 579.8 54 152.8 85 254.1 116 396.0 147 586.8 55 155.5 86 258.0 117 401.3 148 593.8 Y 56 158.2 87 262.0 118 406.7 149 601.0 C 57 161.0 88 266.0 119 412.2 150 608.1 58 163.9 89 270.0 120 417.7 151 615.4 59 166.7 90 274.1 121 423.2 152 622.7 60 169.6 91 278.2 122 428.8 153 630.1 61 172.6 92 282.3 123 434.5 154 637.5 62 175.4 93 286.5 124 440.2 155 645.0 System Operation Monitor The diagnostic indicator detects the most common fault conditions in the air conditioning system, When an abnormal condition is detected, the module communicates the specific condition through its ALERT and TRIP lights, The module is capable of detecting both mechanical and electrical system problems, See figure 13 for the system operation monitor, A, IMPORTANT System Operation Monitor LED R LED's Figure 13 LED Functions See table 7 for LED troubleshooting The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously. High Pressure Switch HSXB15 units are equipped with a high pressure switch that is located in the liquid line of the compressor. The switch (SPST, manual reset, normally closed) removes power from the compressor when discharge pressure rises above factory setting at 640 + 10 psi. Low Pressure Switch HSXB15 units are also equipped with a low pressure switch that is located in the vapor line of the compressor. The switch (SPST, auto-reset, normally closed) removes power from the compressor when vapor line pressure drops below factory setting at 40 + 5 psi. diagnostic codes. Power LED (green) - indicates voltage within the range of 19-28VAC is present at the power connection of the module. Alert LED (yellow) - communicates an abnormal system condition through a unique flash code. The alert LED will flash a number of times consecutively, pause and then repeat the process. The number of consecutive flashes, defined as the Flash Code, correlates to a particular abnormal condition Trip LED (red) - indicates there is a demand signal from the thermostat but no current to the compressor is detected by the module. Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated. TRIP and ALERT LEDs flashing at the same time indicates that the control circuit voltage is too low for operation. Reset ALERT flash code by removing 24VAC power from monitor. Last ALERT flash code will display for 1 minute after monitor is powered on. Page 13 HSXB15 SERIES Table 7 Status LED Troubleshooting LED Description Troubleshooting Green "Power" Module has power. Supply voltage is present at module terminals. Red "Trip" Thermostat demand signal Y1 is present, but the compressor is not running. I Compressor protector is open. 2 Outdoor unit power disconnect is open. 3 Compressor circuit breaker or fuse(s) is open. 4 Broken wire or connector is not making contact. s Low pressure switch open if present in the system. 6 Compressor contactor has failed to close. Yellow "Alert" Flash Code 1 Long Run Time - Compressor is running extremely long run cycles I Low refrigerant charge. 2 Evaporator blower is not running. 3 Evaporator coil is frozen. 4 Faulty metering device. s Condenser coil is dirty 6 Liquid line restriction (filter drier blocked if present) 7 Thermostat is malfunctioning. Yellow "Alert" Flash Code 2 System Pressure Trip - Discharge or suction pressure out of limits or compressor overloaded I High head pressure. 2 Condenser coil poor air circulation (dirty, blocked, damaged). 3 Condenser fan is not running. 4 Return air duct has substantial leakage. s If low pressure switch is present, check Flash Code 1 information. Yellow "Alert" Flash Code 3 Short Cycling - Compressor is running only briefly I Thermostat demand signal is intermittent. 2 Time delay relay or control board is defective. 3 If high pressure switch is present, check Flash Code 2 information. 4 If low pressure switch is present, check Flash Code 1 information. Yellow "Alert" Flash Code 4 Locked I Run capacitor has failed. 2 Low line voltage (contact utility if voltage at disconnect is low). 3 Excessive liquid refrigerant in the compressor. 4 Compressor bearings are seized. Yellow "Alert" Flash Code 5 Open Circuit Rotor Information 1 Outdoor unit power disconnect is open. 2 Unit circuit breaker or fuse(s) is open. 3 Unit contactor has failed to close. 4 High pressure switch is open and requires manual reset. s Open circuit in compressor supply wiring or connections. 6 Unusually long compressor protector reset time due to extreme ambient temperature. 7 Compressor windings are damaged. Yellow "Alert" Flash Code 6 Open Start Circuit only in run circuit - Current I Run capacitor has failed. 2 Open circuit in compressor start wiring or connections. 3 Compressor start winding is damaged. Yellow "Alert" Flash Code 7 Open Run Circuit only in start circuit - Current I Open circuit in compressor start wiring or connections. 2 Compressor start winding is damaged. Yellow "Alert" Flash Code 8 Welded Contactor - Compressor always runs 1 Compressor contactor failed to open. 2 Thermostat demand signal not connected to module. Yellow "Alert" Flash Code 9 Low Voltage - Control circuit < 17VAC I Control circuit transformer is overloaded 2 Low line voltage (contact utility if voltage at disconnect is low.) • Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated. • TRIP and ALERT LEDs flashing at the same time indicates that the control circuit voltage is too low for operation. • Reset ALERT flash code by removing 24VAC power from monitor. Last ALERT flash code will display for 1 minute after monitor is powered on. Page 14 504710M 03/06 In order to ensure peak performance, your system must be properly maintained, Clogged filters and blocked airflow prevent your unit from operating at its most efficient level. WARNÁNG Before the start of each heating and cooling season, the following service checks should be performed by a qualified service technician. First, turn off electrical power to the unit prior to performing unit maintenance. • Inspect and clean the outdoor and indoor coils, The outdoor coil may be flushed with a water hose, 1. Ask your Lennox dealer to show you where your indoor unit's filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed, 2. Disposable filters should be replaced with a filter of the same type and size, NOTE - If you are unsure about the filter required for your system, call your Lennox dealer for assistance, IMPORTANT NQ TE - It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e,g,, pet urine, cottonwood seeds, etc,) • Visually inspect the refrigerant lines and coils for leaks, • Check wiring for loose connections, • Check voltage at the indoor and outdoor units (with units operating), • Check the amperage draw at the outdoor fan motor, compressor, and indoor blower motor, Values should be compared with those given on unit nameplate. • Check, clean (or replace) indoor unit filters. • Check the refrigerant charge and gauge the system pressures. Check the condensate drain line for free and unobstructed flow; clean, if necessary, • • Adjust blower speed for cooling, Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tables and procedure. • Check drive belt for wear and proper tension, NQTE- If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this instruction, NQTEQutdoor fan motor is prelubricated sealed, No further lubrication is needed, Freezestat Low ambient kit Low ambient cut-off kit • SignatureStat" NOTE - The filter and all access panels must be in place any time the unit is in operation, 4. Some systems are equipped with an electronic air cleaner, designed to remove the majority of airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for maintenance instructions. 5. Inspect and clean indoor coil, The indoor evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.) A IMPORTANT and Refer to the Engineering Handbook for optional accessories that may apply to this unit, The following may or may not apply: • Compressor crankcase heater • Mounting bases • Start kit • Timed off control • • • 3. Many indoor units are equipped with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before it is returned to the unit or grille, room thermostat 6. Inspect and clean outdoor coil: • Make sure no obstructions restrict airflow to the outdoor unit. Leaves, trash or shrubs crowding the unit cause the outdoor unit to work harder and use more energy, Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit, • The outdoor coil may require frequent cleaning (depending on environmental conditions). Clean the outdoor coils with an unpressurized water hose to remove surface contaminants and debris. Page 15 HSXB15 SERIES If necessary, clean the outdoor coil more frequently, especially if it is exposed to substances which are corrosive or which block airflow across the coil (ie, pet urine, cottonwood seeds, etc), Thermostat operations vary from one thermostat to another. The following provides general operation procedures. Refer to the user's information manual provided with your thermostat for specific operation details, Temperature Setting tion. The auto mode allows the system to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings. Temperature Indicator The temperature indicator temperature, displays the actual room Programmable Thermostats Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling, Refer to the user's information manual provided with your thermostat for detailed programming and operation details, Preservice Check Levers Set the lever or dial to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit off--then back on--before pressures can equalize will put unusual stress on the unit's compressor, If your system fails to operate, check the following before calling for service: • Make sure all electrical disconnect switches are ON, Fan Switch In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling, This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or furnace is operating. This mode is required when constant air circulation or filtering is desired. • Make sure the room thermostat Temperature Selector and System Switch (Heat, Cool, Auto) are properly set. • Check for and replace any blown fuses, or reset any tripped circuit breakers. • • Make sure unit access panels are in place. Make sure air filter is clean. System • Write down the unit model number and have it handy before calling, Switch Set the system switch for heating, cooling or auto opera- Job Name Job no, Date Job Location City State City State Service Technician Installer Unit Model No. Serial No. Nameplate Voltage Rated Load Ampacity. Amps: Maximum Fuse or Circuit Breaker Electrical Connections Tight? Indoor Blower RPM _ Compressor Indoor Filter clean? S.P. Drop Over Indoor (Dry) Discharge Pressure Vapor Pressure Supply Voltage (Unit Off) Outdoor Coil Entering Air Temp. Refrigerant Charge Checked? .... Outdoor Fan Checked? Vo tage Wth Compressor Operat ng .................................................................... _ ....................... Thermostat Ca brated? _) Properly Set? _) Page 16 504710M Outdoor Fan 03/06 Level?
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 16 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Jun 30 04:28:13 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools