Industries Inc.
INSTALLATIONINSTRUCTIONS
,501,042M
2/73
ELECTRIC UNIT
KIT
INSTALLATION INSTRUCTIONS FOR FUSE PANEL KITS (PR-241/242/243)
FOR ES2 AND ECB6 SERIES UNITS
I-SHIPPING AND PACKING LIST
Package I of I Contains
1-Fuse panel with fuse blocks and fuses
NOTE-Refer to Table I for unit application and number of
fuse blocks and 50 AMP fusesprovided.
I I-PURPOSE
This kit provides fusing for subdivided circuits on units rated
more than 48 ampers per NEC Section 424_22 (C).
Ill-INSTALLATION
1-Mount fuse panel complete with fuse blocks and fuses in an
accessible location close to the unit.
2-Bring in power to fuse box and complete wiring as dictated
in Field Wiring Diagrams in this instruction.
TABLE 1
UNIT MODEL NO.
E2D-511
ES2-511
ECB6-48-2
ECB6-51165-48-2
ES2D-681
ES2-681
ECB6-64-2
ECB6-51/65-64-2
ECB6-80-2
ECB6-51!65-80-2
ECB6-65-96-1
ECB6-112-1
PR KIT NO.
PR-241
PR-242
PR-243
50 AMP FUSES
(PROVIDED)
4
6
FUSE BLOCKS
(PROVIDED)
3
4
FUSE
PANEL
100 AMP
100 AMP
150 AMP
Page 1
230/60/1
L1 L2
APPUCATIONWIRINGFOR
PR-241 FUSEPANEL
524,213W
*25 Amp Fuses And
Fuse Reducers Not
Supplied
50A
"25A
100 AMP FUSE
PANEL (P-8-9858)
ECB6 UNIT
0oA 1
ECB6-48-2
ECB6-51 /65-48-1
230/60/1
L1 L2 "30 Amp Fuses And
Fuse Reducers Not
Supplied
50A 50A
*30A "30A
100 AMP FUSEE
PANEL (P-8-98_) 1
rTO ES2 UNIT-
Refer To Unit Wiring Diagram For Proper Connections
ESD2-511-2 & ES2-511-2
230/60/1
L1 L2
ECB6-64-2
ECB6-51/65-64-1
230/60/1
L1 L2
I
50A 50A
_; /60A
100 AMP FUSE I
PANEL (P-8-gS581]
[
,i
TO ES2 UNIT-
Refer To Unit Wiring Diagram For Proper Connections
ESD2.681.2
ES2-681-2
Page 2
APPUCATION WIRING FOR
PR-242 FUSE PANEL
524,214W
230/60/1
L1 L2 *25 Amp FusesAnd Fuse
Reducers Not Supplied
I_ 50A 50A
r ......................1
ECB6.51 /65.80.1
ECB6-80-2
Page 3
APPLICATION WIRING FOR
PR-243 FUSE PANEL
524,215W
230/60/1
L1 L2
50A 50A I
I150 AMP FUSE ! |
ECB6-65-96-1
230/60/1
L1 L2 *25 Amp FusesAnd Fuse
Reducers Not Supplied
50A 50A
ECB6.112.1
Page4