LENNOX Air Conditioner/heat Pump(outside Unit) Manual L0806534
User Manual: LENNOX LENNOX Air conditioner/heat pump(outside unit) Manual LENNOX Air conditioner/heat pump(outside unit) Owner's Manual, LENNOX Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 24
Download | |
Open PDF In Browser | View PDF |
,t_2008 Lennox Dallas, , industries Texas, INSTALLATION INSTRUCTIONS ® Inc, USA Elite ® Series XP13 Units HEAT PUMPS 505,327M _ j_jj 04108 Technical Publications Litho U.S.A. Supersedes 03/08 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING A CAUTION A IMPORTANT Shipping and Packing List ...................... XP13 Heat Pumps ............................. Unit Dimensions ............................... General Information ........................... Recovering Refrigerant from Existing System ..... Removing Existing Outdoor Unit ................. Positioning New Outdoor Unit ................... Removing and Installing Panels ................. New or Replacement Line Set ................... Brazing Connections ........................... Removing Indoor Unit Metering Device ........... Flushing the System ........................... Installing New Indoor Unit Metering Device ........ Testing for Leaks .............................. Evacuating the System ......................... Servicing Unit Delivered Void of Charge ........... Electrical Connections ......................... Start-Up and Charging Procedures ............... System Operation ............................. Defrost System ............................... Maintenance .................................. Homeowner Information ........................ Start-Up and Performance Checklist ............. 1 1 2 3 5 5 6 7 9 10 11 12 13 13 15 15 15 17 17 21 22 22 24 Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier. 1 -- Assembled XP13 outdoor unit A IMPORTANT The XP13 Heat Pumps, which will also be referred to in this instruction as the outdoor unit, uses HFC-410A refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox XP13 Engineering Handbook. This outdoor unit is designed for use in systems that use check thermal expansion valve (CTXV) refrigerant metering devices. 04/08 IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII Page 1 505,327M IIIIIIIIIIIIIIIIIIIIIIIIIIIIII RUN CAPACITOR DEFROST BOARD CONTACTOR SUCTIONLINE -CONNECTION LIQUID LINE CONNECTION REVERSING VALVE HIGH PRESSURE FILTER DRIER/ LIQUID LINE CONNECTIONS VAPOR LINE VAPOR VALVE AND GAUGE PORT/SUCTION LINE CONNECTIONS TOP VIEW XP13 PARTS ARRANGEMENT ii DISCHARGE AIR C i} t LIQUID LINE C:=::::3 _ ELECTRICAL VAPOR LINE 2 (51) 4N/4(1 08) 4-3/4 (121) tt SIDE VIEW UNIT SUPPORT FEET UNIT SUPPORT 1(25) SIDE VIEW FEET \ 8N/2 9N/2 (216) (241) T 13-7/8 (352) @ @ ® 20-5/8 (524) 8-3/4 8N/4 (222) (210) _l 4-1/2 (197) L (114) 13-1/2 (343) 3-1/4 3-5/8 (83) (92) XP13-018, 024, 030 AND 036 BASE SECTION XP13 XP13 BASE WITH ELONGATED A B C -018 -024 31 (787) 27 (686) 28 (711) 31 (787) 27 (686) 28 (711) -030 31 (787) 27 (686) 28 (711) -036 35 27 (686) 28 (711) -042 -048 -060 (889) 35 (889) 30-1/2 35 30-1/2 (775) 35 (889) 30-1/2 (775) 35 (889) 45 (889) (1143) Page 2 505327M 04/08 (775) 35 (889) LEGS WARNING IMPORTANT 1/12 TURN I_ TURN 9 8 These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation. 4 Figure 1. Cap Tightening Distances Xk IMPORTANT When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners. Table 1. Torque Requirements Parts Recommended Service valve cap 8 ft Sheet metal screws 16 in Ib 2 NM Machine screws #10 28 in Ib 3 NM Compressor bolts 90 in Ib 10 NM Gauge port seal cap 8ft Ib To Access Angle Type Service Port: Torque A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately sized wrench 11 NM Ib 2 Connect gauge to the service port 11 NM USING MANIFOLD GAUGE SETS When checking the system charge only use a manifold gauge set that features low loss antiblow back fittings See figure 2 for a typical manifold gauge connection setup Manifold gauge sets used with HFC410A refrigerant systems must be capable of handling the higher system operating pressures The gauges should be rated for use with pressures of 0 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating 3 When testing is completed replace service port cap and tighten as follows: • With Torque Wrench: Finger tighten and then tighten per table 1 • Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 1 To Open and Close AngleType Service Valve: A valve stem cap protects the valve contamination and assures a leak free seal OPERATING SERVICE VALVES The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging. Each valve is equipped with a service port which has a factory-installed valve stem. stem from 1 Remove stem cap with an appropriately sized wrench 2 Use a service wrench with a hex head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go 3 Replace the stem cap and tighten as follows: • With Torque Wrench: Tighten finger tight and then tighten per table 1 • Without Torque Wrench: Finger tighten and use an appropriately sized wrenched to turn an additional 1/12 turn clockwise as illustrated in figure 1 Page 3 XP13 SERIES DISTRIBUTOR CBECK 7 REV_#s,_T:Uv_E NOTE - ARROWS INDICATE OF REFRIGERANT FLOW. _ _GAUGEM_,FOLD _ ,' ''--!, INDOOR UNIT Ill _'_ IIBFc-°_o II b"STRAP THE SUCTION LINE TO THE JOIST OR RAFTER AT 8 FEET INTERVALS THEN STRAP THE LIQUID LINE TO THE SUCTION L,NE __ - I I_1 > > I1 Figure 15. Refrigerant Line Set: Installing Horizontal Runs Model (XP13) and size of unit (e.g. -060). Page 9 XP13 SERIES IMPORTANT -REFRIGERANT LINES MUST NOT CONTACT WALL. LIQUID LINE OUTSIDE WALL SUCTION LINE _WARNING NOTE -SIMILAR INSTALLATION PRACTICES SHOULD BEUSED IFLINE SET IS TO BE INSTALLED ONEXTERIOR OFOUTSIDE WALL. ,WARNING WOOD BLOCK STRAP ;LEI 1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line. SUCTION LINE WRAPPED WITH ARMAFLEX 2. Remove service cap and core from both the suction and liquid line service ports. UID LINE IMPORTANT! REFRIGERANT LINES MUST NOT CONTACT STRUCTURE. 3. Connect gauge low pressure side to liquid line service valve. 4. To protect components during brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth underneath the valve body to protect the base paint. Also, shield the light maroon R-410A sticker. PIPE FIBERGLASS INSULATION Figure 16. Refrigerant Line Set: Installing Vertical Runs (New Construction Shown) WARNING AUTOMOTIVE MUFFLER-TYPE HANGER ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE MUFFLER-TYPE HANGER WALL STUD X STRAP 5. Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of the valve stem port connection on the suction service valve. LIQUID LINE TO SUCTION LINE NOTE - The RFCIV or TXV metering device at the indoor unit will allow low pressure nitrogen to flow through the system.) LIQUID LINE METAL SLEEVE \ SUCTION LINE - WRAPPED IN ARMAFLEX NOTE - Use silver alloy brazing rods with five or six percent minimum silver alloy for copper-to-copper brazing or 45 percent silver alloy for copper-to-brass or copper-to-steel brazing. Figure 17. Refrigerant Line Set: Transition from Vertical to Horizontal Use the following procedure to braze the line set to the new air conditioner unit. Figure 18 is provided as a general guide for preparing to braze the line set to the air conditioner unit. Page 10 505327M 04/08 6. Braze the liquid line to the liquid line service valve. Turn off nitrogen flow. Repeat procedure starting at paragraph 4 for brazing the suction line to the suction service valve. i,_,,IP REMOVE CAP AND CORE FROM BOTH LIQUID AND SUCTION SERVICE PORTS CUT AND DEBUR SERVICE PORT MUST BE OPEN TO ALLOW EXIT POINT FOR NITROGEN INDOOR SERVICE VALVE UNIT UNIT outdoor I _ LIQUID LINE SERVICEJ q VALVE ,4i WRAP INSTALL CORE ONLY FOR BOTH SERVICE PORTS after have coolED.they / ( SER VALVE _Z£ Figure 18. Brazing Connections 7. After all connections have been brazed, disconnect 2. Remove any shipping clamps holding the liquid line manifold gauge set the from service ports and remove and distributor assembly. wrapping. Reinstall the service port core for both of the 3. Using two wrenches, disconnect liquid line from liquid outdoor unit's service valves. line orifice housing. Take care not to twist or damage distributor tubes during this process. 4. Remove and discard fixed orifice, valve stem assembly if present and Teflon washer as illustrated in Remove the existing HCFC-22 refrigerant flow control figure 20. orifice or thermal expansion valve from the indoor coil. The 5. Use a field-provided fitting to temporary reconnect the existing indoor unit HCFC-22 metering device is not liquid line to the indoor unit's liquid line orifice housing. approved for use with HFC-410A refrigerant and may prevent proper flushing. DISTRIBUTOR TUBES REPLACEMENT PARTS LIQUID LINE ORIFICE If replacement parts are necessary for the indoor unit, order kit 69J46. The kit includes: • 10 -- Brass nuts for liquid line assemblies • 20 -- Teflon rings • 10 -- Liquid line orifice housings • 10 -- Liquid line assemblies LIQUID LINE ORIFICE HOUSINGS RINGS (20) / (10) d BRASS NUT RETAINER LIQUID LINE ASSEMBLY (INCLUDES STRAINER) (_ VALVE STEM CAP (Uncased Coil Shown) Figure 20. Typical Fixed Orifice Removal TYPICAL TXV REMOVAL PROCEDURE LINE ASSEMBLIES STRAINER) AND DISCARD VALVE STEM ASSEMBLY PISTON (10) VALVE STEM (INCLUDES REMOVE /OR,F,? ./(,FPRESENT, iRASS NUTS (10, LIQUID RING FIXED D,S& ,B2TOR.. "' __ TEFLON TEFLON HOUSING LIQUID LINE ASSEMBLY 1. On fully cased coils, remove the coil access and plumbing panels. Figure 19. 69J46 Kit Components 2. Remove any shipping clamps holding the liquid line and distributor assembly. TYPICAL FIXED ORIFICE REMOVAL PROCEDURE 1. On fully cased coils, remove the coil access and plumbing panels. 3. Disconnect the equalizer line from the TXV equalizer line fitting on the suction line. Page 11 XP13 SERIES 4, Remove the suction line sensing bulb as illustrated in figure 21. A IMPORTANT 5, Disconnect the liquid line from the TXV at the liquid line assembly, TWOPIECE (Uncased Coil Shown) PATCH PLATE (UNCASED COIL ONLY STUB END LIQUID LINE ORIFICE HOUSING DISTRIBUTOR TUBES SENSING LINE If the original system used: • • MALE EQUALIZER FITTING LINE HCFC-22 refrigerant, then flush the system using the procedure provided in this section. HFC-410A refrigerant, then proceed to Installing New Refrigerant Metering Device. / / J SUCTION SENSING BULB LINE CONTAINS CLEAN HCFC-22 BE USED FOR FLUSHING _( LIQUID LINE _ INVERTED HCFC-22 SUCTION SERVICE 6, Disconnect the TXV from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process, GAUGE MANIFOLD CYLINDER LOW PRESSURE # hI Figure 21. Typical TXV Removal TO HIGH PRESSURE LINE VALVE _ CLOSED EXISTING OOR 7, Remove and discard TXV and the two Teflon rings as illustrated in figure 21, LIQUID LINE SERVICE VALVE RECOVERY CYLINDER 8, Use a field-provided fitting to temporary reconnect the liquid line to the indoor unit's liquid line orifice housing, RECOVERY MACHINE NOTE - THE INVERTED HCFC-22 CYLINDER MUST CONTAIN AT LEAST THE SAME AMOUNT OF REFRIGERANT AS WAS RECOVERED FROM THE EXISTING SYSTEM, IMPORTANT Figure 22. Typical Flushing Connection REQUIRED EQUIPMENT Equipment required to flush the existing line set and indoor unit coil: Xk CAUTION • Two clean HCFC-22 recovery bottles, • Oilless recovery machine with pump-down feature, • Two gauge sets (one HFC-410A), FLUSHING PROCEDURE 1, Connect the following: A IMPORTANT for HCFC-22; one for • HCFC-22 cylinder with clean refrigerant to the suction service valve, • HCFC-22 gauge set to the liquid line valve, • Recovery machine with an empty recovery tank to the gauge set, 2, Set the recovery machine for liquid recovery and start the recovery machine, Open the gauge set valves to Page 12 505327M 04/08 allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil. 3, Invert the cylinder of clean HCFC-22 and open its valve to allow liquid refrigerant to flow into the system through the suction line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine. 4, After all of the liquid refrigerant has been recovered, switch the recovery machine to suction recovery so that all of the HCFC-22 suction is recovered. Allow the recovery machine to pull a vacuum on the system, 5, Close the valve on the inverted HCFC-22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off, an additional 1/2 turn clockwise as illustrated in figure 23, or 20 ft-lb, 6, Attach the suction line sensing bulb in the proper orientation as illustrated in figure 25 using the clamp and screws provided, TWO PIECE (Uncased Coil Shown) PATCH PLATE UNCASED COIL ONLY) LIQUID LINE HOUSING DISTRIBUTOR TUBES. ._ORI FIC E STUB CTXV END - XP13 units use CTXV for metering refrigerant only. This section provides instructions on installing CTXV refrigerant metering device, 1/2 TURN MALE EQUALIZER LINE FITTING (SEE FIGURE 26 FOR FURTHER SUCTION LINE LIQUID LINE SENSING BULB INSULATION IS REQUIRED IF MOUNTED EXTERNAL TO THE COIL CASING SEE FIGURE 25 FOR BULB POSITIONING. Figure 23. Tightening Distance TYPICAL CTXV INSTALLATION PROCEDURE The CTXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field-provided plenum, install the CTXV in a manner that will provide access for field servicing of the CTXV. Refer to Figure 24 for reference during installation of CTXV unit, Figure 24. Typical TXV Installation NOTE - Insulating the sensing bulb once installed may be required when the bulb location is external to the coil casing. 1, Remove the field-provided fitting that temporary reconnected the liquid line to the indoor unit's distributor assembly, 2, Install one of the provided Teflon rings around the stubbed end of the CTXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil. 3, Attach the stubbed end of the CTXV to the liquid line orifice housing, Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 23, or 20 ft-lb, 4, Place the remaining Teflon washer around the other end of the CTXV. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil, SUCTION I' '_,,,,- THAN BULB OR 9 / BULB \ SUCTION LINE ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT _--,_--"_:",..,_ '_ >.,, ,,'_,%_ " ,. __ _'.1,_" Y (BULB NOTE 5, Attach the liquid line assembly to the CTXV. Finger tighten and use an appropriately sized wrench to turn ON LINES SMALLER 7/8", MOUNT SENSING AT EITHER THE 3 O'CLOCK POSITION. LINE POSITION. NEVER MOUNT ON BOTTOM OF LINE. EITHER THE 4 OR 8 O'CLOCK "_.\\_ i }'_L I - NEVER MOUNT Y j_ ON _X/ BULB) BOTTOM Figure 25. TXV Sensing OF LINE. Bulb Installation Page 13 XP13 SERIES 7, Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the suction line as illustrated in figure 26, IMPORTANT After the line set has been con nected to the indoor unit and air conditioner, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks: IMPORTANT WARNING FLARE SEAL CAP -_ I LARE NUT COPPER OR I BONNET J MALE BRASS EQUALIZER WARNING _ LINE FITTING SUCTION LINE Figure 26. Copper Flare Seal Bonnet Removal 8, Connect the equalizer line from the TXV to the equalizer suction port on the suction line. Finger tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated in figure 23. WARNING NOTE - To prevent any possibility of water damage, properly insulate all parts of the TXV assembly that may sweat due to temperature differences between the valve and its surrounding ambient temperatures. See the XP13 Engineering Handbookforapproved kit match-ups and application information, CTXV The reference CTXV kits include: 1--CTXV 2 -- Teflon rings 1 -- 1 1/4" wide copper mounting strap for sensing bulb 2 -- #10 hex head bolts and nuts for securing sensing bulb AND NUTS (2) @ TEPLON COPPER MOUNTING RINGS (2) /% STRAP (1) Figure 27. CTXV Kit Components Page 14 505327M 04/08 1. Connect an HFC-410A manifold gauge set high pressure hose to the suction valve service port. (Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the suction port better protects the manifold gauge set from high pressure damage.) 2. With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC-410A cylinder (suction only). 3. Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit. Weigh in a trace amount of HFC-410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC-410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder. 4, Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set, 6, When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves, 7, Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit, 5, Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit, 6, After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector, 7, After leak testing disconnect ports, gauges from service 8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves. 9, When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder d HFC-410A refrigerant, Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit. Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non-condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts, Xk WARNING 10, Close manifold gauge valves and shut off the HFC-410A cylinder and remove the manifold gauge set, If the system is void of refrigerant, clean the system using the procedure described below, A IMPORTANT 1. Use nitrogen to pressurize the system and check for leaks. Repair all leaks. 2, Evacuate the system to remove as much of the moisture as possible. 3, Use nitrogen to break the vacuum and install a new filter drier in the system. 4. Evacuate the system again. Then, weigh the appropriate amount of HFC-410A refrigerant as listed on unit nameplate into the system. 5, Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not verified, the compressor will fail in the future. 1, Connect manifold gauge set to the service valve ports as follows: • low pressure gauge to suction line service valve • high pressure gauge to liquid line service valve 2, Connect micron gauge, 3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set, 4, Open both manifold valves and start the vacuum pump. 5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29,01 inches of mercury), NOTE - During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in sure indicates a relatively large leak, If this occurs, repeat the leak testing procedure. NOTE - The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure, In the U,S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC), Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size, 1, Install line voltage power supply to unit from a properly sized unit disconnect switch, 2, Ground the unit at the unit disconnect switch or to earth ground, Page 15 XP13 SERIES NOTE - To facilitate conduit, a hole is provided in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting. 3, Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations, I WARNING 4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit. See figures 30 and 31, ( 24V, Class II circuit connections are made in the low voltage junction box.) THERMOSTAT | || J! 20B-ZSO/_I Wire run length AWG # Insulation type less than 100' (30m) 18 color-coded, more than 100' (30m) 16 rating 35°C minimum temperature LINE VOLTAGE FIELD INSTALLED NOTE - Units are approved for use only with copper conductors. Refer to figure 28 for high voltage field wiring diagram. (A complete unit wiring diagram is located inside the unit control box cover.) WARNING! _ T DUAL BLACK r BLACK BLACK ORANGE Figure 28. Typical Field Wiring DESCRIPTION (EY COMPONENT _I COMPRESSOR Be MOTOR-0UTD00R FAN CI2 CAPACITORDUAL :MCI CONTROL-DEFROST _R_.]_IHEATER-COMPRESSOR (I.-ICONTACTOR-COMPRESSOR .I VALVE-REVERSING ;4 SWlTCH-HIGHPRESSURE $6 S_ITCH-DEFROST _€0 THERNGGTAT-CRANKCASE _87 SWITCH-LOW PRESSURE CONTROL FAN THERMOSTAT r- -- RED F--- _ BLACK L_Ow L0-PS COMPRESSOR CRANKCASE A NOTEFOR USE WITH COPPER CONOUCTORS ONLY.REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE. YI_OUT HEATER HI-PS 208-250160/I i_tr- ; _ I II Ill ----J ii GROUND LUG F L2 LI _ h, I_'GROUND CONNECTION MUST OPTIONAL SWITCH i __J !F'_---'_REVERSING _VALVE OMCI FAN OUT - IL_ I i i Ill I IPRESSURE III II I II ZOB-ZSO/60/I : [ LO-PS _LINE FIELD I COMMON Y_OUT -J YI PRESSURE RI-PS Figure 29. Typical Wiring Diagram Page 16 505327M 04/08 I WHEN CODES. DENOTES OPTIONAL COMPONENTS / HI-PS EOUIPMENT BE JUMPERED IS NOT USED WARNINGELECTRIC SHOCK HAZARD, CAN CAUSE INJURY OR DEATN_ UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL I DEFROST_ THERMOSTAT LZ_- VOLTAGE INSTALLED z_NOTE - For use with copper conductors only. Refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size. DEFROST CAPACITOR _OLASS FIELD - ELECTRIC SHOCK HAZARD. Can cause INJU- OUTDOOR !I?JPURPLE _ RY or DEATH, Unit must be grounded in accordance with national and local codes. NOTE - For proper voltages, select thermostat wire gauge oer the following chart: FAN I A VOLTAGE INSTALLED CLASS II VOLTAGE FIELD INSTALLED THERMOSTAT INDOORUNIT OUTDOOR 5, Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit's nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected, UNIT ®1 ©1 24V POWER @1 24V POWER COMMON_r__ 1ST-STAGE _ _L AUXILIARY HEAT 'L. @1 _L COMMON 6. Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit. 1ST_STAGE AUXILIARYHEAT @1 -- 7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate, 8, Check system for sufficient refrigerate by using the procedures listed under Testing and Charging System, TESTING AND CHARGING SYSTEM @1 INDOOR BLOWER REVERSING @1 VALVE COMPRESSOR @1 This system uses HFC-410A refrigerant which operates at much higher pressures than HCFC-22. The pre-installed liquid line filter drier is approved for use with HFC-410A only. Do not replace it with components designed for use with HCFC-22. This unit is NOT approved for use with coils which use capillary tubes as a refrigerant metering device, SETTING UP TO CHECK CHARGE (SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC THERMOSTAT AND INDOOR UNIT,) Figure 30. Outdoor and Blower Unit Thermostat Designations THERMOSTAT INDOOR UNIT OUTDOOR UNIT ® ®+ ©4 COMMON @4 \ "-, "'. AUXILIARY HEAT INDOOR BLOWER REVERSING @ ® -- • high pressure gauge to liquid service port 1 ST-STAG E AUXILIARY HEAT ® @ COMPRESSOR THERMOSTAT COOLING MODE INDOOR AIRFLOW CHECK Check airflow using the Delta-T (DT) process using the illustration in figure 32, @4 (SOME CONNECTIONS OUTDOOR _ THERMOSTAT HEAT RELAY / VALVE SPECIFIC EMERGENCY "-//_[-- J 1, Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC-410A, 2. Connect the manifold gauge set to the unit's service ports as illustrated in figure 2. • low pressure gauge to vapor service port _ l- EMERGENCY HEAT @4 ,ST STAGE k@" ®4 @4 24V POWER \ COMMON HEATING MODE INDOOR AIRFLOW Blower airflow (CFM) may be calculated electric heat and measuring: MAY NOT APPLY. REFER_O AND INDOOR CHECK UNIT.) Figure 31. Outdoor and Blower Unit Thermostat Designations (with emergency heat) by energizing • Temperature rise between the return air and supply air temperatures at the indoor coil blower unit, • Measuring voltage supplied to the unit, • Measuring amperage being drawn by the heat unit(s). Then, apply the measurements taken in following formula to determine CFM: IMPORTANT Amps x Volts x 3.41 CFM = 1, Rotate fan to check for binding. 2, Inspect all factory- and field-installed wiring for loose connections. 1.08 x Temperature rise (F) CALCULATING CHARGE If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit, To calculate the total refrigerant charge: 3, After evacuation is complete, open both the liquid and vapor line service valves to release the refrigerant charge contained in outdoor unit into the system. 4, Replace the stem caps and tighten to the value listed in table 1, Amount specified on nameplate + Adjust amount, for variation in line set length listed on table in figure 33. Additional charge specified per indoor unit match-up listed in tables 3 through 9. + = Total charge Page 17 XP13 SERIES Temp. I DT ofair 180 entering,._J78 indoor _ I _ coilOF _jru 24 23 _ _ 21 20 19 _174 m _72 _70 1. Determine the desired DT--Measure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle). 24 24 23 23 22 22 22 20 19 18 17 16 15 23 23 22 22 21 21 20 19 18 17 16 15 14 22 21 20 19 22 21 19 18 21 20 18 18 21 20 19 19 18 17 16 15 19 19 18 17 16 16 15 14 17 17 16Z_15 14 13 12 17 17 16 15 15 14 13 12 14 15 11 11 13 12 10 10 2. Find temperature drop across ceil--Measure the coil's dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (TDrop) = A minus C. 3. Determine if fan needs adjustment--If the difference between the measured TDrop and the desired DT (TDropi])T) is within ±3 °, no adjustment is needed. See examples: Assume DT = 15 and A temp. = 72 °, these C temperatures would necessitate stated actions: Wet-bulb °F 57 58 59 60 61 62 63 64 65 66 67 68 69 70 J n A C° 53 ° ,0o All temperatures expressed in °F INDOOR are COIL 58 ° 62 ° DRY BULB Liquid Line Set Diameter 3/8" (9.5 mm) ACTION Increase the airflow 14 10 15 15 = = -1 -5 (within +3 ° range) no change Decrease the airflow indoor unit instructions to increase/ Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3 °. Indoor Coil Airflow Guide LENNOX 1. Check Liquid and suction line pressures 't,__,_7_!_ _'_ 2. Compare unit pressures with Table 10, Normal Operating Pressures. 3. Conduct leak check; previously outlined. evacuate as 4. Weigh in the unit nameplate charge plus any charge required for line set differences over feet, per 5 feet (g per 1.5 m) from 3 ounce °F 4 per Line Set Length Ounces adjust = = WET WEIGH Charge DT 15 4. Adjust the fan speed--See decrease fan speed. BULB Figure 32. Checking Refrigerant 19 TDrop- 15 feet (4.6 m) line set* M@ululJ per 5' (85 g per 1.5 m) NOTE - *If line length length isis less greater ft. (4.6 m), add this this amount. If line than than 15 ft.15(4.6 m), subtract amount. This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information. Figure 33. Using Weigh In Method 1 SUBCOOUNG2 USE COOLING MODE Check the airflow as illustrated in figure 32 to be sure the indoor airflow is as required. (Make any air flow adjustments before continuing with the following procedure,) Measure outdoor ambient temperature; check charge, determine whether to use cooling mode or heating mode to 3 Connect gauge set, 4 Check Liquid and Vapor line pressures. Compare pressures with Normal Operating Pressures table 10, (The reference table is a general guide. Expect minor pressure variations. Significant differences may mean improper charge or other system problem.) 5 Set thermostat for heat/cool demand, depending on mode being used: Using cooling mode--When the outdoor ambient temperature is 60°F (15°C) and above. Target subcooling values in table below are based on 70 to 80°F (21-27°C) indoor return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode setpoint to 68°F (20°C). When pressures have stabilized, continue with step 6. 60°F (15 °) -USE HEATING MODE Using heating mode--When the outdoor ambient temperature is below 60°F (15°C). Target subcooling values in table below are based on 65-75°F (18-24°C) indoor return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to 77°F (25°C). When pressures have stabilized, continue with step 6. 6 Read the liquid line temperature; 7 Read the liquid line pressure; then find its corresponding listed in table 11 and record it in the SAT ° space. LIQ o - 8 Subtract LIQ ° temp. from SAT ° temp. to determine subcooling; record it in SC ° space. SC o 9 Compare SC ° results with table below, being sure to note any additional charge for line set and/or match-up. SAT o = record in the LIQ ° space. temperature in the temperature/pressure chart 10 If subcooling value is greater than shown in tables 3 through 10 for the applicable unit, remove refrigerant; if less than shown, add refrigerant. 11 If refrigerant is added or removed, repeat steps 6 through 10 to verify charge. Figure 34. Using Subcooling Page 18 505327M 04/08 Method Table 3. XP13-018 INDOOR Target Subcooling Heat Cool (+5OF) (+1OF) 25 5 MATCHUPS CBX26UH-018 INDOOR *Add charge Ib 1 oz 1 Target Subcooling Heat Cool {±5OF) {±1OF) MATCHUPS *Add charge Ib oz CBX26UH-024 25 5 0 1 CH33 31A CH33-31B 10 10 5 5 0 1 2 0 CBX27UH-018/024 CBX32MV-018/024 15 30 8 3 0 0 2 0 CH33-36C CH33_42 10 10 4 11 0 2 0 3 CBX32MV-024/030 15 8 1 2 CH33-44, Table 4. XP13-024 INDOOR Target Subcooling Heat Cool {±5OF) (±1OF) MATCHUPS *Add charge 10 11 2 5 CR33-36 CR33_48 -48 10 30 4 5 0 2 1 3 CR33-50/60 CX34-38 SN# 6007K and after 30 5 11 5 2 2 5 2 CX34 38 before SN# 6007K CX34-44/48 10 10 5 5 2 2 2 2 Ib oz CBX26UH-024 26 5 0 1 CBX26UH-030 CBX27UH-018/024 26 12 3 3 1 0 3 11 CBX27UH-030 12 3 1 4 CBX32M-030 CBX32M-036 12 12 3 3 0 1 11 4 INDOOR Ib oz 12 12 6 3 0 0 5 11 CH23 65 CBX26UH-042 32 32 6 6 0 1 12 2 CH33-25A CH33 31A 16 12 6 3 0 0 7 7 CBX26UHq348 10 12 4 5 CH33 31B 12 3 0 15 CBX27UH-042 CBX27UH-048 15 15 5 5 0 0 0 0 CH33-36A CH33 36B 16 16 6 7 0 0 7 15 15 5 0 0 CH33 12 5 0 0 CBX32MV CH33-43B 15 10 5 12 0 4 0 8 CR33-30, -36 CX34 25 12 12 4 6 0 0 3 5 CH33_43C CH33_44 10 10 6 6 1 0 1 16 CX34 31 CX34-36 12 16 3 7 0 0 11 11 CH33-48 CH33_49C 10 10 6 12 1 3 1 12 CR33_48 32 5 0 5 CR33-50/60 CX34 43 32 10 9 6 2 1 6 1 CX34 49 CX34-50/60 10 10 12 6 3 1 7 1 10 9 2 6 CBX32MV CBX32MV 018/024 024/030 36C Table 7. XP13-042 CBX32Mq336, Table 5. XP13-030 INDOOR Target Subcooling Heat Cool {±5OF) {±1OF) MATCHUPS CBX26UH-030, CBX27UH-030 -036 *Add charge Ib oz 25 15 4 4 0 0 11 11 15 4 0 11 15 15 4 4 0 0 11 11 15 20 4 3 0 0 11 8 CH33-31A 15 4 0 CH33-31B CH33 36A 20 20 4 3 CH33-36C CH33-42B 15 20 CBX27UH-036 CBX32M 030, CBX32M-042 036 MATCHUPS CX34 042 036 60 Target Subcooling Heat Cool (±5OF) {±1OF) *Add charge Table 8. XP13-048 INDOOR MATCHUPS Target Subcooling Heat Cool {±5OF) {±1OF) *Add charge Ib oz 11 CBX26UH-048 CBX26UHq360 10 5 11 12 0 3 8 8 0 0 11 8 CBX27UH-048 CBX27UH-060 10 10 9 9 0 0 7 7 3 4 0 0 11 11 CBX32M-048 CBX32MV-048 10 10 9 9 0 0 7 7 15 15 4 3 0 0 11 12 C33-43 CX34-31 15 4 0 11 CX34 36 CX34-38 SN# 6007K and after 27 4 2 4 0 0 CX34-38 before SN# 6007K CX34_42 20 27 4 2 0 0 CBX32MV-024/030, CH33 25A CR33 30, CX34-25 -036 36 0 4 0 3 CH33_43C CH33-49C 13 10 4 9 0 0 3 7 0 11 CH33-60 10 7 0 5 CR33_48 36 4 0 0 11 0 CR33-50/60, CX34-60 35 10 7 7 0 0 5 5 -60 Table 9. XP13-060 Table 6. XP13-036 INDOOR Target Subcooling Heat Cool {±5OF) (±1OF) MATCHUPS *Add charge INDOOR Ib 25 10 5 5 2 2 2 2 CBX27UH-042 10 10 2 8 *Amount 042 of charge 10 10 required nameplate. (Remember in additional 5 5 to charge 2 2 shown to consider line set length difference.) 2 2 on unit Target Subcooling Heat Cool (±5OF) (±1OF) *Add charge Ib oz CBX26UH-060 CBX27UH-060 10 10 9 8 3 1 3 12 CBX32MV oz CBX26UH-036 CBX27UH-036 CBX32M 036, CBX32MV-036 MATCHUPS 10 8 1 12 CBX32MV-068 CH33 62 060 10 10 9 9 2 2 5 7 CR33 60 35 4 0 0 CX34-60 CX34 62 15 10 4 9 0 2 0 1 Page 19 XP13 SERIES Table 10. Normal Operating Pressures - Liquid +10 and Vapor +5 PSIG* IMPORTANT Mode,tLiquid -018Line Pressure b024 L-030 / Vapor Line Pressure L.038 °F (°C)** 1.042 1.048 j.080 Cooling Operation 65 (18) 228 / 140 232 / 139 245 / 135 251 / 134 239 / 135 244 / 139 248 / 129 75 (24) 265 / 142 268 / 142 284 / 137 292 / 138 277 / 136 283 / 141 289 / 131 85 (29} 311 / 144 317 / 144 328 / 140 339 / 140 321 / 139 318 / 143 336 / 132 95 (35) 350 / 147 366 / 146 377 / 144 392 / 143 379 / 142 369 / 145 385 / 133 105 (41) 402 / 149 412 / 148 429 / 145 443 / 145 423 / 144 420 / 148 440 / 136 115 (45} 458 / 152 464 / 152 486 / 147 508 / 149 484 / 147 484 / 150 500 / 140 Heating Operation 60 (16} 350 / 135 331 / 130 341 / 126 361 / 112 376/118 350/124 370/127 50 (10} 328/116 315/109 324/107 331 / 106 355/107 323/106 348/105 40 (4.5} 310 / 96 299 / 89 307 / 88 304 / 96 336 / 89 294 / 92 328 / 85 30 (-1) 294 / 81 283 / 72 294 / 72 295 / 77 325 / 74 291 / 73 317 / 72 20 (-7) 278 / 67 267 / 55 278 / 55 285 / 57 309 / 60 277 / 59 *These are most-popular-match-up **Temperature of the air entering pressures. the outdoor Indoor match up, indoor air quafity, and indoor load cause pressures 305 / 59 to var_ coil. Table 11. HFC-410A Temperature (°F) - Pressure (Psig) °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig 32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 110 365.0 125 445.9 141 545.6 33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3 34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 112 375.1 127 457.6 143 559.1 35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 113 380.2 128 463.5 144 565.9 36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 114 385.4 129 469.5 145 572.8 37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 115 390.7 130 475.6 146 579.8 38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 116 396.0 131 481.6 147 586.8 39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 117 401.3 132 487.8 148 593.8 40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 118 406.7 133 494.0 149 601.0 41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 119 412.2 134 500.2 150 608.1 42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4 43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7 44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1 45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5 46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0 47 134.6 78 228.0 109 360.0 140 539.0 Page 20 505327M 04/08 INSTALLING DEFROST THERMOSTAT SERVICE VALVE CAPS Disconnect gauge set and re-install both the liquid and suction service valve caps, INSTALL OUTDOOR UNIT SERVICE VALVES _ CAPS / Figure 35. Installing Service Valve Caps The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously. The defrost thermostat is located on the liquid line between the check/expansion valve and the distributor, When defrost thermostat senses 42°F (5,5°C) or cooler, the thermostat contacts close and send a signal to the defrost control board to start the defrost timing, It also terminates defrost when the liquid line warms up to 70°F (21°C), DEFROST CONTROL The defrost control board includes the combined functions of a time/temperature defrost control, defrost relay, diagnostic LEDs and terminal strip for field wiring connections, The control provides automatic switching from normal heating operation to defrost mode and back, During compressor cycle (call for defrost), the control accumulates compressor run times at 30-, 60-, or 90-minute field-adjustable intervals. If the defrost thermostat is closed when the selected compressor run time interval ends, the defrost relay is energized and defrost begins. SERVICE LIGHT OPERATION The thermostat is not included with the unit and must be purchased separately, Some outdoor thermostats incorporate isolating contacts and an emergency heat function (which includes an amber indicating light), The service light thermostat will enable the emergency heat light function on the room thermostat. EMERGENCY The unit is equipped with a large-capacity bifiow filter drier which keeps the system clean and dry, If replacement is necessary, order another of the same design and capacity. The replacement filter drier must be suitable for use with HFC-410A refrigerant, The XP13 defrost system includes two components: a defrost thermostat and a defrost control board (figure 36). FAN OBSl ODS_ DIAGNOSTIC LEDS COMPRESSOR DELAY PINS HEAT (AMBER LIGHT) FILTER DRIER (_ 9 TEST PINS REVERSING VALVE An emergency heat function is designed into some room thermostats. This feature is applicable when isolation of the outdoor unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode, Emergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power outage if power has been off for over an hour and the outdoor temperature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent compressor slugging. PIo FIELD SELECT TIMING PINS - 0-O{_T P2 24V TERMINAL STRIP CONNECTIONS LOW PRESSURE SWITCH DEFROST THERMOSTAT j ¥I-0UT o HIGH PRESSURE SWITCH (_ I,;,W;,t;q q J;,IP__) Figure 36. Outdoor Unit Defrost Control DEFROST CONTROL TIMING PINS Board Each timing pin selection provides a different accumulated compressor run time period for one defrost cycle, This time period must occur before a defrost cycle is initiated, The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes (see figure 36), The defrost timing jumper is factory-installed to provide a 60-minute defrost interval. If the timing selector jumper is not in place, the control defaults to a 90-minute defrost interval, The maximum defrost period is 14 minutes and cannot be adjusted, A TEST option is provided for troubleshooting, The TEST mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at power-up, the control will ignore the test pins. When the jumper is placed across the TEST pins for two seconds, the control will enter the defrost mode, If the jumper is Page 21 XP13 SERIES removed before an additional 5-second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5-second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and re-applied. COMPRESSOR DELAY The defrost board has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is removed. NOTE - The 30-second compressor when jumpering the TEST pins. TIME DELAY NOTE - The defrost control board ignores input from the low-pressure switch terminals as follows: • during the TESTmode, • during the defrost cycle, • during the 90-second start-up period, • and for the first 90 seconds each time the reversing valve switches heat/cool modes. DIAGNOSTIC LEDS The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition. WARNING feature is ignored The timed-off delay is five minutes long. The delay helps to protect the compressor from short-cycling in case the power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds. PRESSURE SWITCH CIRCUIT The defrost control incorporates two pressure switch circuits. The high pressure switch (S4) is factory-connected to the board's HI PS terminals (see figure 36). The board also includes a low pressure, or loss-of-charge-pressure, switch (S87). Switches are shown in wiring diagrams in figures 29 and 36. During a single demand cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted by any pressure switch wired to the control board. In addition, the diagnostic LEDs will indicate a locked-out pressure switch after the fifth occurrence of an open pressure switch as listed in table 12. The unit will remain locked out until power to the board is interrupted, then re-established or until the jumper is applied to the TEST pins for 0.5 seconds. Table 12. Defrost Control Board Diagnostic LED Mode Green LED (DS2) Red LED (DS1) No power to control Normal operation / power to control Anti-short cycle lockout OFF Simultaneous OFF Slow FLASH Alternating Slow FLASH Low pressure switch fault OFF Slow FLASH Low pressure switch lockout OFF ON High pressure switch fault Slow FLASH OFF High pressure switch lockout ON OFF Before the start of each heating and cooling season, the following service checks should be performed by a qualified service technician. First, turn off electrical power to the unit prior to performing unit maintenance. • NOTE - It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, etc.) • Visually inspect the refrigerant lines and coils for leaks. • Check wiring for loose connections. • Check voltage at the indoor and outdoor units (with units operating). • Check the amperage draw at the outdoor fan motor, compressor, and indoor blower motor. Values should be compared with those given on unit nameplate. • Check, clean (or replace) indoor unit filters. • Check the refrigerant charge and gauge the system pressures. Check the condensate drain line for free and unobstructed flow; clean, if necessary. • • Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tables and procedure. • Check drive belt for wear and proper tension. NOTE - If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this instruction. Page 22 505327M 04/08 Inspect and clean the outdoor and indoor coils. The outdoor coil may be flushed with a water hose. When removing debris from around the unit, be aware of metal edges on parts and screws. Although special care has been taken to keep exposed edges to a minimum, physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level. 1, Air Filter--Ask your Lennox dealer to show you where your indoor unit's filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed. 2, Disposable Filter--Disposable filters should replaced with a filter of the same type and size. be NOTE - If you are unsure about the filter required for your system, call your Lennox dealer for assistance. ,& IMPORTANT 3. Reusable Filter--Many indoor units are equipped with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille. NOTE - The filter and all access panels must be in place any time the unit is in operation. 4. Electronic Air Cleaner--Some systems are equipped with an electronic air cleaner, designed to remove airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for maintenance instructions. 5. Indoor Unit--The indoor unit's evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.) A IMPORTANT Cleaning of the outdoor unit's coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your air conditioning or heat pump system. HEAT PUMP OPERATION Your new Lennox heat pump has several characteristics that you should be aware of: • Heat pumps satisfy heating demand by delivering large amounts of warm air into the living space. This is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of considerably hotter air to heat the space. • Do not be alarmed if you notice frost on the outdoor coil in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45°F (7°C). An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost. • During the defrost cycle, you may notice steam rising from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however, the unit will return to normal operation at the conclusion of the defrost cycle. EXTENDED POWER OUTAGE The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant slugging during cold weather operation. If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the Emergency Heat setting to obtain temporary heat without the risk of serious damage to the heat pump. In emergency heat mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm-up period, the thermostat can be switched to the heat setting and normal heat pump operation may resume. THERMOSTAT OPERATION Though your thermostat may vary somewhat from the description below, its operation will be similar. Temperature 6. Outdoor Unit--Make sure no obstructions restrict airflow to the outdoor unit. Leaves, trash or shrubs crowding the unit cause the outdoor unit to work harder and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit. Setting Levers Most heat pump thermostats have two temperature selector levers: one for heating and one for cooling. Set the levers or dials to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit off and back on before pressures equalize puts stress on the unit compressor. Page 23 XP13 SERIES Fan Switch Preservice Check If your system fails to operate, check the following before calling for service: • Check to see that all electrical disconnect switches are ON, In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling, This mode is generally preferred when humidity control is a priority, The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or auxiliary heat are operating. This mode is required when constant air circulation or filtering is desired. • Make sure the room thermostat temperature selector is properly set. • Make sure the room thermostat properly set. • Replace any blown fuses, or reset circuit breakers. • Make sure unit access panels are in place. • Make sure air filter is clean. • Identify the unit model number before calling, System Switch Set the system switch for heating, cooling or auto operation. The auto mode allows the heat pump to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings, Many heat pump thermostats are also equipped with an emergency heat mode which locks out heat pump operation and provides temporary heat supplied by the auxiliary heat, OPTIONAL ACCESSORIES Refer to the Engineering Handbook for optional accessories that may apply to this unit, The following may or may not apply: Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode. • Compressor crankcase heater • • Mounting bases Timed off control Temperature • Stand-off kit • Sound cover Indicator The temperature temperature, indicator displays the actual system switch is room • Low ambient kit Programmable Thermostats • Monitor kit Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling, Refer to the user's information manual provided with your particular thermostat for operation details. • SignatureStat'" • Loss of charge kit • • High pressure switch kit Mild weather kit • Compressor monitor room thermostat !i!i!i i'_!_i; i_i;_ii_!!ii_i!ii! ii_ ii!ili_ii!i_ _i!a!i!i ¸!i!i_!i_i_ii!_! !ii_'i !_ _!!! !!i!!i!ii!i _ii!_i!_i!_ !!!_i i!ii! _iii _i_ _!_i!_i!_i! _i!_i!_i !_i!_i!_i !_i!_i !_!_i!_i!_i !_i!_i !_!_i!_i!_i i!_i!_i !_ !_i !_i!_i !_i!_i!_i i!_i!_i !_ !_i !_i!_i i!_i !_i!_i!_i !_ !_i !_i!_i i!_i !_i!_i!_i !_ !_i !_i!_i i!_i !_i!_i!_i !_i!_i !_i !_i!_i !_i!_i!_i i!_i !_i!_i !_i !_i!_i !_i!_i!_i !_i!_i !_i !_i!_i !_i!_i!_i !_i!_i !_i!_i!_i !_i!_i!_i !_i!_i !_i!_i!_i !_i!_i!_i !_i!_i !_!_i!_i!_i !_i!_i !_!_i!_i!_i i!_i!_i !_i!_i !_!_i!_i!_i i!_i!_i !_ !_i !_i!_i !_i!_i!_i i!_i!_i !_ !_i !_i!_i i!_i !_i!_i!_i !_ !_i !_i!_i i!_i !_i!_i!_i !_i!_i !_i !_i!_i !_i!_i!_i i!_i !_i!_i !_i !_i!_i !_i!_i!_i !_i!_i !_i !_i!_i !_i!_i!_i !_i!_i !_i!_i!_i !_i!_i!_i !_i!_i !_i!_i!_i !_i!_i!_i !_i!_i !_!_i!_i!_i !_i!_i !_!_i!_i!_i i!_i!_i !_i!_i !_!_i!_i!_i i!_i!_i !_ !_i !_i!_i !_i!_i!_i i!_i!_i !_ !_i !_i!_i i!_i !_i!_i!_i !_ !_i !_i!_i i!_i !_i!_i!_i !_i!_i !_i !_i!_i i!_i !_i!_i!_i !_i!_i !_i !_i!_i !_i!_i!_i !_i!_i !_i !_i!_i !_i!_i!_i !_i!_i !_i !_i!_i !_i!_i!_i !_i!_i !_i!_i!_i !_i!_i!_i !_i!_i !_!_i!_i!_i !_i!_i !_!_i!_i!_i i!_i!_i !_i!_i !_!_i!_i!_i i!_i!_i !_ !_i !_i!_i !_i!_i!_i i!_i!_i !_ !_i !_i!_i i!_i !_i!_i!_i !_ !_i !_i!_i i!_i !_i!_i!_i !_ !_i !_i!_i i!_i !_i!_i!_i !_i!_i !_i !_i!_i !_i!_i!_i i!_i !_i!_i !_i !_i!_i !_i!_i!_i !_i!_i !_i !_i!_i !_i!_i!_i !_i!_i !_i!_i!_i !_i!_i!_i !_i!_i !il Job Name Job no. Date Job Location City State Installer City State Unit Model No, Serial No. Service Technician Nameplate Voltage Rated Load Ampacity Compressor Amperage: Maximum Fuse or Circuit Breaker Electrical Connections Tight? Indoor Blower RPM Indoor Filter clean? _ S.P. Drop Over Indoor (Dry) Supply Voltage (Unit Off) Outdoor Coil Entering Air Temp. Vapor Pressure; Refrigerant Lines: - Leak Checked? _] Properly Insulated? _] Outdoor Fan Checked? Service Valves: _] Caps Tight? _] Voltage With Compressor Operating --- Fully Opened? SEQUENCE Heating Correct? _ OF OPERATION THERMOSTAT Calibrated? _ Cooling Correct? Page 24 505327M 04/08 Properly Set? _ Level?
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 24 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Jun 30 05:04:49 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools