LENNOX Package Units(both Units Combined) Manual L0806654

User Manual: LENNOX LENNOX Package Units(both units combined) Manual LENNOX Package Units(both units combined) Owner's Manual, LENNOX Package Units(both units combined) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 12

,t,: 2005 Lennox industries inc.
Dallas, Texas, USA 0( °s
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Shipping & Packing List ......................... 1
Unit Dimensions ............................... 2
Parts Arrangement ............................. 3
General ....................................... 3
Requirements .................................. 4
Location Selection .............................. 4
Rigging & Setting Unit .......................... 4
Clearances .................................... 4
Existing Common Vent Systems .................. 5
Condensate Drain .............................. 6
Filters ......................................... 6
Supply & Return Connections .................... 6
Compressors .................................. 7
Electrical ...................................... 7
Defrost System ............................... 11
Unit Start-Up and Operation .................... 11
Condenser Fan Clearances ..................... 12
Maintenance .................................. 12
INSTALLATION
INSTRUCTIONS
13CHPX SERIES UNITS
PACKAGED HEAT PUMPS (2-5 TONS)
Field trial units
505,136M (38152A071)
10/05
Technical
JLJ _,Publications
Litho U.S.A.
1-Assembled packaged heat pump unit
As soon as the unit is received, it should be inspected for
possible damage during transit. If you find any damage,
immediately contact the last carrier.
Ak WARNING
Ak WARNING
A, CAUTION
A,WARNING
10/05
[111[[11[1[11[[1[1[1[1111[11111111[[111[
Page 1
505136M
[llll[llll[[lllll[llll[l[lllll[[IHlll[[[lll
( _ 2-1/2 (64)
AA
SUPPLY AIR
(70)
--I_ /OP
DOWN-FLOW
RETURN AIR
OPENING
y F
DD
BB
-- Model
Number
13CHPXA-24
C 13CHPXA-30
___ 13CHPXA-36
13CHPXA-42
13CHPXA-48
CC 13CHPXA-60
TOP VIEW
74
74
84
Corner Weights Center Of
Gravity
FF
94 125 97 15.5
94 125 97 15.5
101 126 105 16
108 136 176 140 20
112 137 177 144 20
117 143 184 151 20
9 B D,
A
FRONT VIEW
HORIZONTAL HORIZONTAL
SUPPLY AIR RETURN AIR
OPENING OPENING
- '_--- E---_ H
TD_T
2-3/4 _, _, 2-3/4
(70) (70)
--D.K _ j I_D.
BACK VIEW
in,
28.5
28.5
29.5
33
33.5
33.5
o
oELEOTRIOALINLET
L---,-
2-I/2(64)_i _ CONDENSATE DRAIN
END VIEW
END VIEW
A B CD E F
Model No. in. mm in. mm in. mm in. mm in. mm in. mm
13C H PXAV-24
13CHPXAV-30 34-1/4 870 65-3/8 1661 36-1/2 927 11-1/4 286 17-1/4 438 20 508
13CHPXAV-36
13C H PXAV-42
13CHPXAV-48 38-1/4 972 75 1905 46 1168 11-1/4 286 19-1/4 489 22 559
13C H PXAV-60
F G H J K L
Model No. in. mm in. mm in. mm in. mm in. mm in. mm
13CHPXAV-24
13CHPXAV-30 20 508 8-1/2 216 3 76 20-1/4 514 4-1/2 114 19 483
13CHPXAV-36
13C H PXAV-42
13CHPXAV-48 22 559 9-1/4 241 3-1/4 83 22-1/4 572 4 102 16-1/4 413
13C H PXAV-60
Page 2
COIL
MOTOR
CONTROL
SECTION
ELE
HEATING SECTION)
PRESSURE SWITCH
PRESSURE SWITCH
REVERSING
These installation instructions are intended as a general
guide only, for use by an experienced, qualified contractor.
The 13CHPX units are single-package heat pump units
designed for outdoor installation on a rooftop or a slab. The
units are equipped with a transformer and blower control
for applications which do not include electric heat. Electric
heat sections are available for separate order.
The unit must be sized based on heat loss and heat gain
calculations made according to the methods of the Air
Conditioning Contractors of America (ACCA).
The units are shipped assembled. All piping, refrigerant
charge, and electrical wiring are factory-installed and
tested. The units require electric power, condensate drain
and duct connections at the point of installation.
Use of this unit as a construction heater or air conditioner
is not recommended during any phase of construction.
Very low return air temperatures, harmful vapors and
operation of the unit with clogged or misplaced filters will
damage the unit.
FAN
COIL
If this unit has been used for heating or cooling of buildings
or structures under construction, the following conditions
must be met or the warranty will be void:
A room thermostat must control the unit. The use of
fixed jumpers that will provide continuous heating or
cooling is not allowed.
A pre-filter must be installed at the entry to the return air
duct.
The return air duct must be provided and sealed to the
unit.
• Return air temperature range between 55°F (13°C)
and 80°F (27°C) must be maintained.
Air filters must be replaced and pre-filter must be re-
moved upon construction completion.
The unit components, duct system, air filters and evap-
orator coil must be thoroughly cleaned following final
construction clean-up.
The unit operating conditions (including airflow, cool-
ing operation, and heating operation) must be verified
according to these installation instructions.
Page 3
Theseunits mustbe installedin accordancewith all
applicablenationalandlocalsafetycodes.
Theseinstructionsareintendedasageneralguideanddo
notsupersedelocalcodesinanyway.Consultauthorities
havingjurisdictionbeforeinstallation.
Ifcomponentsaretobeaddedtoaunittomeetlocalcodes,
theyaretobeinstalledat thedealer'sand/orcustomer's
expense.
Theseunitsaredesignlistedby ULin boththe United
StatesandCanadaasfollows:
• Foruseasaheatpump.
• Foroutdoorinstallationonly.
• Forinstallationoncombustiblematerial.
WARNING
5 - The unit foundation should be raised a minimum of 3"
above finish grade. In areas which have prologed pe-
riods of temperature below freezing and snowfall,
elevate the unit above the average snow line. Take
care to allow free drainage of condensate from de-
frost cycles to prevent ice accumulation. Do not lo-
cate the unit near walkways to prevent the possible
icing of surfaces due to defrost condensate.
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. An
optional lifting lug kit (92M51) may be purchased
separately for use in rigging the unit for lifting. Spreaders
MUST be used across the top of the unit. Recommended
spreader length: 2, 2-1/2, 3-ton units -- 44"; 3-1/2, 4, 5-ton
units -- 54".
Accessory Lift Kit
Use the following guidelines to select a suitable location for
these units.
1 - Unit is designed for outdoor installation only. Unit must
be installed so all electrical components are protected
from water.
2-Condenser coils must have an unlimited supply of air.
3 - For ground level installation, use a level pre-fabricated
pad or use a level concrete slab with a minimum thick-
ness of 4 inches. The length and width should be at
least 6 inches greater than the unit base. Do not tie the
slab to the building foundation.
4 - Maintain level within a tolerance of 1/4 inch maximum
across the entire length or width of the unit.
Figure 1
CAUTION
Units may also be moved or lifted with a forklift while still in
the factory supplied packaging.
NOTE -Length of forks must be a minimum of 42 inches.
All units require certain clearances for proper operation
and service. Refer to figure 2 for the clearances required
for combustible construction, servicing, and proper unit
operation.
Page 4
Service Clearances
3 (156)*
REAR
FRONT
48 (1219)
*Rear clearance is 18" (457)when required for
accessory maintenance.
NOTE- Top Clearance - 36 in. (914 mm)
NOTE- Entire perimeter of unit base requires
support when elevated above mounting surface.
Figure 2
NOTE -Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet.
In the U.S. units may be installed on combustible floors
made from wood or class A, B, or C roof covering material.
In Canada, units may be installed on combustible floors.
Install the unit so that snow accumulation will not restrict
the airflow. Allow a required minimum horizontal clearance
of 4 feet from electric meters, gas meters, regulators and
relief equipment. In addtion to the above requirements,
ensure that unwanted ice caused by condensate is not
allowed to accumulate around the unit. Do not locate the
unit on the side of the building where the prevailing winter
winds could trap moisture, causing it to freeze on the walls
or on overhangs (under eaves).
The 13CHPX packaged heat pump may replace an exist-
ing furnace which is being removed from a venting system
commonly run with separate gas appliances. In this case,
the existing vent system is likely to be too large to properly
vent the remaining attached appliances.
Conduct the following test while each appliance is operat-
ing and the other appliances (which are not operating) re-
main connected to the common venting system. If the
venting system has been installed improperly, you must
correct the system as indicated in the general venting re-
quirements section.
1 - Seal any unused openings in the common venting sys-
tem.
2 - Inspect the venting system for proper size and horizontal
pitch. Determine that there is no blockage, restriction,
leakage, corrosion, or other deficiencies which could
cause an unsafe condition.
3 - Close all building doors and windows and all doors be-
tween the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dry-
ers and any appliances not connected to the common
venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will oper-
ate at maximum speed. Do not operate a summer ex-
haust fan. Close fireplace dampers.
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5 - After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening.
Use the flame of a match or candle, or smoke from a
cigarette, cigar, or pipe.
6 - After determining that each appliance connected to the
common venting system is venting properly, (step 3)
return all doors, windows, exhaust fans, fireplace
dampers, and any other gas-burning appliances to
their previous mode of operation.
7 - If a venting problem is found during any of the preced-
ing tests, the common venting system must be modi-
fied to correct the problem.
Resize the common venting system to the minimum
vent pipe size determined by using the appropriate
tables in Appendix G. (These are in the current stan-
dards of the National Fuel Gas Code
ANSI-Z223.1/NFPA 54 in the USA, and the appropri-
ate Category 1 Natural Gas and Propane appliances
venting sizing tables in the current standards of the
CSA B149 Natural Gas and Propane Installation
Codes in Canada.)
Page 5
The13CHPXunitisequippedwitha3/4inchFPTcoupling
forcondensatelineconnection,Plumbingmustconformto
localcodes,Usea sealingcompoundon malepipe
threads,
Thedrainlinemustbeproperlytrappedandroutedto a
suitabledrain.Seefigure3forproperdrainarrangement,
Thedrainlinemustpitchto an opendrainor pumpa
minimumof 1inchper10feetto preventcloggingof the
line,Sealarounddrainconnectionwithsuitablematerialto
preventairleakageintoreturnairsystem.
Drainpipingshouldnotbesmallerthandrainconnectionat
coil.Anopenventindrainlinewillsometimesberequired
dueto linelength,frictionand staticpressure.Drains
shouldbeconstructedinamannertofacilitatefutureclean-
ing,
NOTE -The condensate drain fine MUST be trapped to
provide proper drainage,
CAUTION
Typical Condensate Drain
Minimum Pitch
1in. (25 ram) per
10' (3 m) of line
open
VTtII
Trap must be deep enough to offset maximum mounting
static difference(Generally,3 inches minimum), frame
Figure 3
Filters are not factory-supplied with the unit; however,
optional internally installed filter kits are available. Filter kit
92M54 is used with 2, 2-1/2 and 34on units. Filter kit 92M55
is used with 3-1/2, 4 and 5-ton units. The filter kits
accommodate the use of 1". 2" or 4" filters. If the optional
filter kit is not used, a filter must be field-installed,
Filters must always be installed ahead of evaporator coil
and must be kept clean or replaced, Dirty filters will reduce
the airflow of the unit, Filter sizes are shown in table 1.
Table 1
Unit Filter Size
Unit Model Filter Size Filter Quantity
-24, -30, -36 20 in. X 25 in. 1
-42, -48, -60 16 in. X 25 in. 2
The duct system should be designed and sized according
to the methods in Manual Q of the Air Conditioning
Contractors of America (ACCA).
A closed return duct system shall be used. This shall not
preclude use of economizers or outdoor fresh air intake, It
is recommended that supply and return duct connections
at the unit be made with flexible joints,
The supply and return air duct systems should be
designed for the CFM and static requirements of the job,
They should NOT be sized by simply matching the
dimensions of the duct connections on the unit.
Ducting installed outdoors MUST be insulated and
waterproofed.
CAUTION
The 13CHPX unit is shipped ready for horizontal air
discharge (side duct connections). If bottom air discharge
is desired, the covers must be removed from the supply
and return air openings on the bottom of the unit and
re-installed to cover the side openings.
Removing Supply and Return
Air Opening Covers
®
®
1. Remove screw and lift.
2. Slide cover to free back pin. Base-_ J
Figure 4
Page 6
Units are shipped with the compressormountings
factory-adjustedandreadyforoperation,
All wiring should be done in accordance with the
current National Electric Code ANSI/NFPA No. 70 in the
United States. In Canada, wiring must be done in
accordance with the current CSA C22.2 Part 1. Local
codes may take precedence.
Use wiring with a temperature limitation of 75_C min.; run
the 208 or 230 volt, 60 hertz electric power supply through a
fused disconnect switch to control box of unit and connect
as shown in the wiring diagram located on the inside of the
control access panel. Refer to figure 5 for electrical access.
E ectricaJ Access
EnVy /,
Enlry
Figure 5
Unit must be electrically grounded in accordance with local
codes or in the absence of local codes with the National
Electric Code, ANSI/NFPA No. 70 (latest edition) or CSA
C22.2 Part 1 (latest edition).
Power supply to the unit must be N.E,C, Class 1, and must
comply with all applicable codes. A fused disconnect
switch should be field provided for the unit, The switch must
be separate from all other circuits, If any of the wire
supplied with the unit must be replaced, replacement wire
must be of the type shown on the wiring diagram.
Electrical wiring must be sized to carry minimum circuit
ampacity marked on the unit, USE COPPER
CONDUCTORS ONLY. Each unit must be wired with a
separate branch circuit and be properly fused.
WARNING
CAUTION
WARNING
See figure 7 for typical field wiring connections and figure 8
for typical unit wiring diagram.
Optional Electric Heat
Optional electric heat is available and must be purchased
separately. Install the electric heat section as outlined in the
installation instructions packaged with the electric heat
section,
Thermostat
The room thermostat should be located on an inside wall
where it will not be subject to drafts, sun exposure or heat
from electrical fixtures or appliances. Follow
manufacturer's instructions enclosed with thermostat for
general installation procedure, Color coded insulated wires
(# 18 AWG) should be used to connect thermostat to unit,
Six wires are required for heat pump operation (including a
common wire, if required by the thermostat).
Blower Control Board
The circulating air blower is controlled by a blower control
board located in the unit control box. Blower operation is
NOT delayed after a call for either heating or cooling, A
blower "off" delay of 90 seconds begins when the
thermostat demand is satisfied. These delays are not
adjustable. See figure 6.
Page 7
Blower Drive Control
RiO
R7
i<_>
QI R4 @
RS @
R1
RII
dl]d3 IdS
@ R6
3
R5 0
C2 _ D3 3 _N_X
Z1 _ D1
D5 OWl C3_ _/ _:X
Z2
1005 83 175 x
@
HSC]
Figure 6
Typical Single-Phase Unit Wiring Connections
_N_LLED
THE_X_T_
[]
®
[]
-JJ_
_D_JMD
Figure 7
Page 8
r,Q
r.O
O0
13CHPX Series Packaged Heat Pump Units
Typical Wiring Diagram
SL01_S SidES CHANT
COOLt_ IWPUT (SLK)
24 LO_I
30 WED
36 HtGH
42 LOW
48 M£D
60 HIGH
MOTOR
_PEED TAT
@----t,.
ILl
208/23 V-I-60
L2
DER.AY
No Pwer to Collrol
#orm] 0_ercttio_ IPOle( to
Control
Anli-Stort Cycle Lo¢IoII
Lll Prt$1ufl SlillS fa.lf
LOl Pfllllrl Slttcl Loltoet
Hig_ Prll$lre Dittos F(IIII
High Presllfe Switch tolkolt
mll_l ]mlllOFF OFF
Slm_ltoleo. Slol Flock
Alter.to Slol Flash
OFF $1ol FIo:h
OfF ON
SlowFlesh OFF
ON OFF
COMPRESSOR
COMPRESSOR
CONTACTOR
P*I
_. Kl-I ( _
UEFMOST i
DUAL CONTROL _i
CAPACITOR C4_
CONDENSER
ToR
P-2
(<
P-S
GLOII'_R
CONTROL
B3
)L
RL_
CAPACI TOR MOTOR
F-
THERMOSTAT
Note: Becausethe Pro:sure Switckes ore mnitored only w_ea"Yl" ttiput) i: Derive, the code
,f°r _re.ure switch,ope_will..t he _ee_ _hea "_1" is off. I.teod, tke "NoremlOperotion"or S_ "-''-_'-''----
hat_ _h_rt Cyde codeIfll be sell. lEOe'; (') (,) ®t
Also, ehel prosperoGlitch ope..d co_sedoshort eych Iockoet. tie pro.ere seitch*o en
codelilt be Sell ntil if doses, thee tke short cycle Iockoet (ode ill] tioGAenllsl it _S oireody
expired.
>
A15
WI& 12 CAN GS USSD TO STAGE
ELECTRIC HEAT ACCESSORY ON
IS & SONWWODELS
S, 7.6 & IOKW HEATER ACCSSSORISS
_UNCTiON _F WI ONLY,
GRN
P-S P-5
CONTACTOR
YEL
FAN
El
Z4V
.nc, G4 "_T-PSz_
(IF USES)
_L NOTE:
iF ANY OF THE ORIGINAL
P-4
R[V, VALVE
LI
S_'rEH $79
,,,.ss, _ r-- NPS,_
o[reOSTS 6._---- OF
T*STAT_/O------- --
YIOUT
LINE VOLTAGE FIELD INSTALLED
WIRE iS REPLACED THE
SAME SIZE AND TYPE WIRE
MUST BE USED.
USE COPPER CONDUCTOR
ONLY, HIE 7_C WIRE
z_CONNECTION MUST BE JUMPERED
WHEN PRESSURE SWITCH IS NOT USED,
WARNING-
ELECTRIC DHOCN HAZARD. UNIT
MUST BE GROUNDED IN ACCORDANCE
WITH NATIONAL AND LOCAL CODES.
13CHPX units are equipped with a defrost control board
that includes the combined functions of time/temperature
defrost control, defrost relay, diagnostic LEDs and a low
voltage terminal strip. See figure 9.
The control provides automatic switching from normal
heating operation to defrost mode and back. During the
compressor cycle (call for defrost), the control accumu-
lates compressor run time at 30, 60 or 90-minute field-ad-
justable intervals. If the defrost thermostat is closed when
the selected compressor run time interval ends, the defrost
relay is energized and the defrost begins.
The defrost timing jumper is factory-installed to provide a
60-minute defrost interval. If the timing selector jumper is
not in place, the control defaults to a 90-minute defrost in-
terval. The maximum defrost period is 14 minutes and is
not adjustable. See figure 9 for the location of the defrost
interval timing pins.
A test option is provided for troubleshooting. The test
mode may be started any time the unit is in the heating
mode and the defrost thermostat is closed or jumpered. If
the jumper is in the TEST position at power up, the control
will ignore the test pins. When the jumper is placed across
the TEST pins for 2 seconds, the control will enter the de-
frost mode. If the jumper is removed before an additional
5-second period has elapsed (7 seconds total), the unit
will remain in defrost mode until the defrost thermostat
opens or 14 minutes have passed. If the jumper is not re-
moved until after the additional 5-second period has
elapsed, the defrost will terminate and the test option will
not function again until the jumper is removed and reap-
plied.
The defrost control board includes a compressor delay
function which cycles the compressor off for 30 seconds
while going into and coming out of the defrost cycle. This
function is activated when the jumper is removed from the
compressor delay pins.
NO TE -- The 30-second compressor delay is not function-
al when the TEST pins are jumpered.
Defrost Interval
Timing Pins
Test Pins
Compressor
Delay Pins
Reversing Valve -
Low Pressure/
Loss of Charge --
Switch
Defrost T'stat j
High Pressure i
Switch
Defrost Control Board
PI (_ FAll
- LO*PS
_Diagnostic
LEDs
24V Terminal
Strip
Connections
Figure 9
The defrost thermostat is located on the liquid line be-
tween the check/expansion valve and the distributor.
When the defrost thermostat senses a liquid line tempera-
ture of 42°F or cooler, the thermostat contacts close and
send a signal to the defrost control board to begin the de-
frost timing. The defrost thermostat also terminates the
defrost when the liquid line temperature warms to 70°F.
The defrost control board includes HI-PS and LO-PS ter-
minals to receive signals from the unit high pressure
switch and loss of charge switch.
During a single demand cycle, the defrost control locks
out compressor operation after the fifth time that the cir-
cuit is interrupted by any pressure switch wired to the con-
trol board. In addition, the diagnostic LEDs indicate a
locked-out pressure switch after the fifth open pressure
switch occurrence. Compressor operation remains
locked out until power to the board is interrupted, then re-
established, or until the jumper is applied to the TEST pins
for 0.5 seconds.
NOTE -- The defrost control board ignores input from the
loss of charge switch terminals as follows:
During the test mode;
During the defrost cycle;
During the 90-second start-up period;
During the first 90 seconds following
a reversing valve switch between the
heating and cooling modes.
EXCEPTION -- ff the TEST pins are jumpered and the
5-minute delay is being bypassed, the LO-PS terminal
signal is not ignored during the 90-second start-up pe-
riod.
The defrost control board includes two diagnostic
LEDs. LED codes indicate operating status. The diag-
nostics codes are given in table 2.
Table 2
Defrost Control Board Diagnostic LEDs
Mode Green LED Red LED
(DS2) (DS1)
No power to OFF OFF
board
Normal
Operation /Simultaneous Slow Flash
Power to Board
Anti-Short Cycle Alternating Slow Flash
Lockout
Loss of Charge
Pressure Switch OFF Slow Flash
Fault
Loss of Charge
Pressure Switch OFF ON
Lockout
High Pressure Slow Flash OFF
Switch Fault
High Pressure ON OFF
Switch Lockout
Page 10
Each13CHPXpackagedheatpumpis factory-charged
withR-410Arefrigerant.Thecompressoris hermetically
sealed, internallysprung and base-mountedwith
rubber-insulatedhold-downbolts.
Pre-Start Check List:
1 - Make sure refrigerant lines do not rub against the cabi-
net or each other.
2- Inspect all electrical wiring, both factory- and field-
installed, for loose connections.
3 - Check voltage at the disconnect switch. Voltage must
be within the range listed on the unit nameplate. If not,
consult power company and have voltage condition
corrected before starting unit.
4 - Recheck voltage with unit running. If power is not with-
in the range listed on the unit nameplate, stop the unit
and consult the power company. Check unit amper-
age. Refer to unit nameplate for correct running amps.
5 - Make sure filter is in place before unit start-up.
6 - Before placing the unit into full operation, energize the
unit for three false starts. Energize the compressor
just long enough for it to make a few revolutions, wait
five to seven minutes before repeating a second and
third time.
Cooling Sequence of Operation
When the thermostat calls for cooling, the "O" circuit is
energized to activate the reversing valve. The "R" to "Y"
circuit is closed to energize the compressor contactor. The
contactor brings on both the compressor and outdoor fan.
The thermostat also closes the "R" to "G" circuit to energize
the circulating air blower. When the cooling demand is
satisfied, the thermostat opens the circuits, as well as the
compressor contactor. The compressor and outdoor fan
immediately stop. The circulating air blower continues
operating through a 90-second delay.
Unit compressors have internal protection. If there is an
abnormal rise in the compressor temperature, the
protector will open and the compressor will stop.
Heating Sequence of Operation
When the thermostat calls for heating, the "R" to "Y" circuit
is closed to energize the compressor contactor. The
contactor brings on both the compressor and outdoor fan.
The reversing valve is not energized in the heating mode.
The thermostat also closes the "R" to "G" circuit to energize
the circulating air blower. When the heating demand is
satisfied, the thermostat opens these circuits, as well as
the compressor contactor. The compressor and outdoor
fan immediately stop. The circulating air blower continues
operating through a 90-second delay.
System Performance
Verify system performance using table 3 and table 4 as a
general guide. Minor variations in these pressures may be
expected due to differences in installations. Significant dif-
ferences could mean that the system is not properly
charged or that a problem exists with some component in
the system.
Used carefully, these tables could serve as a useful service
guide. Data is based on 80°F dry bulb /67°F wet bulb return
air. Allow unit operation to stabilize before taking pressure
readings.
Table 3
Cooling Mode -- Normal Operating Pressures
80°F db /67°F wb RETURN AiR Air Temperature Entering Outdoor Coil (°F)
UNIT PRESSURE 65 70 75 80 82 85 90 95 100 105 110 115
13CHPX-24 143 144 146 147 148 149 150 152 153 154 156 157
13CHPX-30 140 141 142 144 144 145 146 147 149 150 152 153
13CHPX-36 142 143 144 145 145 146 146 147 148 149 150 151
Suction
13CHPX-42 135 136 138 139 140 141 143 144 147 149 151 154
13CHPX-48 142 143 145 146 147 148 149 151 152 153 155 156
13CHPX-60 137 138 140 141 142 143 145 146 148 149 151 153
13CHPX-24 222 244 265 288 297 311 333 354 379 397 424 447
13CHPX-30 229 251 273 295 304 318 341 361 387 406 434 457
13CHPX-36 246 269 291 314 323 337 360 382 407 426 454 478
13CHPX-42 Liquid 231 251 271 291 299 313 335 351 380 398 425 448
13CHPX-48 236 259 282 305 314 328 351 374 397 415 443 466
13CHPX-60 246 271 296 322 332 347 373 398 424 444 475 500
Page 11
70°F RETURN AIR
UNIT
13CHPX-24
13CHPX-30
13CHPX-36
13CHPX-42
13CHPX-48
13CHPX-60
13CHPX-24
13CHPX-30
13CHPX-36
13CHPX-42
13CHPX-48
13CHPX-60
Table 4
Heating Mode -- Normal Operating Pressures
Air Temperature Entering Outdoor Coil (°F)
PRESSURE 0 5 10 15 20 25 30 35 40 45 50 55 60
37 44 52 62 66 74 81 88 96 106 110 118 125
32 40 47 58 63 70 78 86 93 104 109 116 124
32 39 47 57 61 69 76 83 91 101 105 113 120
Suction 33 41 49 60 65 73 80 88 96 107 112 120 127
32 39 47 57 62 69 77 84 92 102 107 114 122
30 37 44 54 58 65 73 80 87 97 101 108 116
283 291 300 312 317 326 335 343 352 364 369 378 387
273 281 290 301 306 314 322 330 339 350 355 363 371
259 266 273 283 287 294 302 309 316 326 330 337 345
Liquid 300 309 319 332 338 347 357 366 376 389 395 404 414
279 284 291 302 307 314 322 330 337 348 353 360 368
318 328 339 353 359 370 380 390 401 415 421 432 442
Motors
The top of the condenser fan should be 1-1/2 inchs from the
bottom of the top grille. This dimension should be checked
and the fan should be adjusted accordingly any time servic-
ing of the outdoor fan system is required.
Periodic inspection and maintenance normally consists of
changing or cleaning filters and (under some conditions)
cleaning the main burners.
Filters
Not supplied. Inspect once a month. Replace disposable or
clean permanent type as necessary. DO NOT replace per-
manent type with disposable.
Indoor, outdoor fan and vent motors are permanently
lubricated and require no further lubrication. Motors
should be cleaned yearly to prevent the accumulation of
dust and dirt on the windings or motor exterior.
Coil
Dirt and debris should not be allowed to accumulate on the
coil surfaces or other parts in the air conditioning circuit.
Cleaning should be performed as often as necessary. Use
a brush, vacuum cleaner attachment, or other suitable
means. If water is used to clean the coil, be sure the power
to unit is shut off prior to cleaning.
NOTE -Care should be used when cleaning the coil so that
the coil fins are not damaged.
Do not permit the hot condenser air discharge to be ob-
structed by overhanging structures or shrubs.
Accessories
Description
Filter Kit (2-ton to 3-ton capacity units)
Filter Kit (3-1/2-ton to 5-ton capacity units)
LENNOX Cat.
Number
92M54
92M55
Page 12
Page 1 of 12 - LENNOX  Package Units(both Units Combined) Manual L0806654
Page 2 of 12 - LENNOX  Package Units(both Units Combined) Manual L0806654
Page 3 of 12 - LENNOX  Package Units(both Units Combined) Manual L0806654
Page 4 of 12 - LENNOX  Package Units(both Units Combined) Manual L0806654
Page 5 of 12 - LENNOX  Package Units(both Units Combined) Manual L0806654
Page 6 of 12 - LENNOX  Package Units(both Units Combined) Manual L0806654
Page 7 of 12 - LENNOX  Package Units(both Units Combined) Manual L0806654
Page 8 of 12 - LENNOX  Package Units(both Units Combined) Manual L0806654
Page 9 of 12 - LENNOX  Package Units(both Units Combined) Manual L0806654
Page 10 of 12 - LENNOX  Package Units(both Units Combined) Manual L0806654
Page 11 of 12 - LENNOX  Package Units(both Units Combined) Manual L0806654
Page 12 of 12 - LENNOX  Package Units(both Units Combined) Manual L0806654

Navigation menu