LENNOX Furnace/Heater, Gas Manual L0806918

User Manual: LENNOX LENNOX Furnace/Heater, Gas Manual LENNOX Furnace/Heater, Gas Owner's Manual, LENNOX Furnace/Heater, Gas installation guides

Open the PDF directly: View PDF PDF.
Page Count: 4

DownloadLENNOX  Furnace/Heater, Gas Manual L0806918
Open PDF In BrowserView PDF
ZENNDX

GAS KITS & ACCESSORIES

2003 Lennox Industries Inc.
Dalias, Texas, USA

504,659M
6/2003

INSTALLATION
INSTRUCTIONS
ALL G40UH, G41UF, G50UH & G50UHi

I

HIGH ALTITUDE KIT

FOR HIGH ALTITUDE
KIT (47M82) USED WITH
UNITS & G51MP-135
UNITS FUELED BY NATURAL

GAS

WARNING

,CAUTION

1 - Set the thermostat to the lowest setting. Shut off the
gas supply to the furnace, then disconnect the
electrical power.
2 - Remove the heating compartment access panel and
burner box cover, if necessary. Turn the automatic
gas valve knob, or switch the gas valve lever, to the
OFF position. See figures 3, 4,5 and 6.
Package 1 of I contains the following:
7 - Main burner orifices (0.081)
1 - Gas converter sticker

3 - Disconnect the gas supply from the gas valve. Mark
the wires for identification and disconnect the wiring
at the gas valve.

1 - Nameplate conversion sticker

High altitude kit (47M82) is used to convert all G40UH,
G41UF, G50UH and G50UHi units and G51MP-135
units which are fueled by natural gas for operation at
altitudes from 7501 to 10,000 ft. (2287 to 3048 m).Units
installed in these high altitude applications also require
installation of a replacement pressure switch, which is
ordered separately. Refer to table 1 for pressure switch
requirements.

4 - Remove the four manifold securing screws. Remove
the manifold/gas valve assembly. Replace the main
burner orifices with the provided orifices (.081). See
figure 1.
5 - Re-install the manifold/valve assembly. Reconnect
wiring to the gas valve.
MANIFOLD/GAS VALVE ASSEMBLY REMOVAL
(G41UF Unit Shown)

TABLE 1
Pressure Switch Requirements
Altitude
Model Number

750140,000 ft.
(2287 - 3048 m)

G40UH/G50UH(i)=045
G40UH/G50UH(i)=070

BURNERS

ORIFICES

Pressure
Switch
56L32

G40UH/G50UH(i)-090
G40UH/G50UH(i)=110
G40UH/G50UH(i)q 35
G40UH/G50UH(i)q 55

15M22
MANIFOLD / GAS
VALVE
ASSEMBLY

G41UF=045
G41UF=070
G41UF=090
G41UF-110

46M94

G41UF-135

46M95

G51MP=135

56M06

NOTE - Pressure switch is factory set. No adjustment

FIGURE 1

necessary.

06/03
Page
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII

504,659M
1

IIIIIIIIIIIIIIIIIIIIIIIIII

6 - All units installed at altitudes above 7,500 ft. (2286m)
require a replacement pressure switch assembly.
See table 1 for the proper switch assembly. Refer to
figure 2 for pressure switch location.

Pressure Switch Replacement
GASKET

G40UH and
GSOUH(i) Units

a - Remove the tubing from the barbed fitting on the
pressure switch(es)

COLLECTOR
BOX

b - Remove screw(s) which secure pressure switch
assembly(ies).
Install replacement pressure
switch(es) using existing screw(s).

TUBING

GASKET_

COMBUSTION
AIR ORIFICE

c-

PRESSURE
SWITCH

Securely attach flexible tubing to fitting on
replacement pressure switch assembly(ies).
See figure 2.

AWARNING

COMBUSTION
AIR INDUCER

7 - Reconnect the gas supply to the manifold and turn on
gas supply to unit.

G41UF Units

A IM PORTANT

PRESSURE
SWITCH

CAUTION

COLLECTOR
BOX
TUBING
COMBUSTION
AIRINDUCER

G51MP-135
8 - Replace burner box cover, if necessary.
COLLECTOR
BOX

PRESSURE
SWITCH \

/

/
/

TUBING

AIR INDUCER

10-Affix
nameplate
nameplate,

conversion

sticker

next to unit

11 - Complete the information required on the converter
sticker: date, name, and address. Affix sticker to the
exterior of the unit in a visible area.

/

COMBUSTION

9 - Restore the electical power to the unit,

12 - Follow the steps given in the start-up and adjustment
section.
_
PRESSURE
SWITCH

TUBING

13 - Energize the thermostat several times to ensure the
ignition control is operating and that the SureLight ®
ignitor glows.

FIGURE 2

14 - Replace the heating compartment access panel.

Page 2

White Rodgers 36E Series Gas Valve

BEFORELIGHTING- Smellall

around the appliance

MANIFOLD
PRESSURE
ADJUSTMENT
SCREW

area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
Use only your hand to turn the gas control knob or the
control lever. Never use tools. If the knob or lever will not
turn by hand, do not try to repair it. Call a qualified service
technician. Force or attempted repair may result in a fire
or explosion.

OUTLET
PRESSURE
TAP
INLET
PRESSURE
TAP

GAS VALVE SHOWN IN OFF POSITION

FIGURE 4
A - Placing the Unit into Operation
White Rodgers 36F Series Gas Valve

A IMPORTANT

MANIFOLD
PRESSURE
ADJUSTMENT
SCREW

G40UH, G41UF, G50UH(i) and G51MP series units are
equipped with a Surelight ® ignition system. The
Surelight ¢ ignition system automatically
lights the
burners each time the thermostat calls for heat.

OUTLET
PRESSURE
TAP

INLET
PRESSURE
TAP

GAS VALVE SHOWN IN OFF POSITION
FIGURE

1 - STOP] Read the safety information at the beginning
of this section.

5

White Rodgers 36G Series Gas Valve
OUTLET

2 - Set the thermostat to its lowest setting.
3 - Turn offall electrical power to the furnace.
4 - Do not try to light the burners by hand.
5 - Remove the unit access panel.
6 - Turn the knob on the gas valve clockwise _'

(or

POST

move the lever) to the OFF position. Do not force.
See figures 3, 4, 5 and 6.
7 - Wait five (5) minutes for any gas to clear out. If you
then smell gas, STOP? Immediately call your gas
supplier from a neighbor's phone. Follow the gas
supplier's instructions. If you do not smell gas, go to
the next step.

GAS VALVESHOWNIN OFFPOSITION
FIGURE 6
9 - Replace the unit access panel.
10 - Turn on all electrical power to the unit,
11 - Set the thermostat to desired setting.
12-If

Honeywell

VR8205 Series Gas Valve

the furnace will not operate,

see the section

"Turning Off Gas to the Unit" and call your service
technician or gas supplier.

8 - Turn the knob on the gas valve counterclockwise
(or move the lever) to the ON position.

MANIFOLD
PRESSURE
ADJUSTMENT
SCREW

P22#&E

B - Turning Off Gas To the Unit
1 - Set the thermostat to its lowest setting.
2 - Turn off all the electrical power to the unit.

REGULATOR
ADJUSTMENT

3 - Remove the heat section access panel.
4-

Turn the knob on the gas valve clockwise11_'

(or

move the lever) to the OFF position. Do not force.

PRESSURE
INLET T_

C - Verifying the Gas Line Pressure

GAS VALVE SHOWN IN OFF POSITION

FIGURE 3

Check the gas line pressure while the unit is operating.
Maintain a minimum of 4.5" w.c. (1.12 kPa) and a
maximum of 10.5" w.c. (2.61 kPa). See figures 3.4, 5
and 6 for the location of the inlet pressure tap on the gas
valve.
Page 3

D - Measuring & Adjusting the Manifold Pressure

E - Verifying

1 - Connect a manometer to outlet tap on gas valve,
2 - Start unit and allow 5 minutes for the unit to stabilize.
3 - Check the burner flame, The flame should be stable
and should not lift from the burners. The flame should
be blue and should burn continuously from all
burners.
4-

After allowing the unit to stabilize for 5 minutes,
check the manifold pressure. Manifold pressure for
natural gas-fired units installed at altitudes of 7501 10000 ft. above sea level is 3.5" w.c. (0.87kPa). See
figures 3, 4, 5 and 6 for the location of the pressure
adjustment screws.

,IMPORTANT

the Gas Rate

The gas input must not exceed the amount shown on the
unit's rating plate. In cases where gas is not metered, the
service technician who is performing the conversion will
need to install a temporary meter to perform this
procedure. Check the input by the following method:
Contact the utility company for the heating value of the
gas. Shut offall other appliances during the input check.
Locate the meter just upstream in regulated pressure
[4.5" w.c. to 10.5" w.c. (1.12kPa to 2.61 kPa)]. To check the
Btu input rate, time the dial hand on the gas meter for at
least one revolution, using the one cubic foot dial.
To assure accurate measurements, use temperature and
pressure correction factors for the meter.
To determine the number of seconds required for the flow
of one cubic foot of gas, use the following formula:
(BTU Content)
Heating Value Of Gas X 3600
Furnace Btuh Input
Example:

1000 BTU gas
Furnace input 100,000 BTUH

Seconds for one cubic foot =

NOTE - Turn off the unit and remove the manometer as
soon as you have obtained an accurate reading. Replace
the pressure tap plug.

Page 4

1000 X 3600
100,000

= 36 seconds



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 4
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Sun Jul 20 21:09:15 2008
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu