Liebert® Challenger ITR
Installation Manual - Nominal Capacities 23 or 33 kW, 50 & 60Hz
i
TABLE OF CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 System Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1.1 Self Contained Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1.2 Chilled Water Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1.3 Split Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.1 Room Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3 Location Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3.1 Remote Sensor Installation Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.4 Equipment Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.4.1 Handling With Skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.4.2 Removal of Skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.5 Piping Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5.1 Drain Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.6 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.7 Balancing the Air Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.7.1 Ducted Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.7.2 Plenum Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.8 Checklist for Completed Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.0 AIR-COOLED MODELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.1 Condenser Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.1 Line Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.2 Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.3 Lee-Temp/Flood Back Head Pressure Control Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.4 Fan Speed Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4.1 Materials Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4.2 Dehydration/Leak Test and Charging Procedures for R22 (standard) or R407C (Optional) . 18
3.4.3 Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.5 Lee-Temp/Flood Back Head Pressure Control Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.5.1 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.5.2 Materials Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.5.3 Dehydration/Leak Test and Charging Procedures for R22 (Standard) or R407C (Optional). 21
3.5.4 Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.0 WATER-COOLED MODELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
4.1 Piping Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.2 Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.3 Water Regulating Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.3.1 Water Regulating Valve Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.3.2 Water Regulating Valve Manual Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.3.3 Testing Valve Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.0 GLYCOL/GLYCOOL-COOLED MODELS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
5.1 Drycooler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
ii
5.2 Drycooler Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.3 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.3.1 Line Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.3.2 Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.3.3 Pump and Drycooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.4 Glycol Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.4.1 Expansion Tanks, Fluid Relief Valves and Other Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.5 Filling Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.5.1 Preparing the System for Filling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.5.2 Glycol Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.5.3 Filling the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.6 Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.7 Glycol Regulating Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.7.1 Glycol Regulating Valve Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.7.2 Testing Valve Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.0 CHILLED WATER MODELS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
6.1 Piping Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7.0 SPLIT SYSTEM MODELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
7.1 Location Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.1.1 Air-Cooled Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.1.2 Water/Glycol-Cooled Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.2 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.2.1 Line Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.2.2 Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.3 Piping Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.3.1 Refrigerant Loop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.3.2 Quick Connect Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7.4 Outdoor Air-Cooled Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
7.5 Centrifugal Air-Cooled Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.5.1 Installing the Indoor Condensing Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.5.2 Ducting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.6 Water and Glycol-Cooled Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.6.1 Piping Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.6.2 Condenser Water Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.6.3 Regulating Valve Adjustment and Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.6.4 Glycol Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
8.0 R407C REFRIGERANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
8.1 Calculating Subcooling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
iii
FIGURES
Figure 1 Removing Liebert Challenger ITR from skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 2 Cabinet dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 3 Optional floor stand dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 4 Piping connections for air-cooled units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 5 Piping connections for split system fan coil units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 6 Piping connections for water/glycol and GLYCOOL units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 7 Piping connections for chilled water self-contained units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 8 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 9 Air-cooled condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 10 Air-cooled fan speed control general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 11 Air-cooled, Lee-Temp general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 12 Water-cooled general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 13 Johnson Controls valve adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 14 Drycoolers and pump packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 15 Pump packages—expansion tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 16 Glycol general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 17 GLYCOOL general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 18 Chilled water general arrangement - horizontal flow (BR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 19 Refrigerant piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 20 Outdoor air-cooled condensing unit—horizontal air discharge models . . . . . . . . . . . . . . . . . . . . . 43
Figure 21 Outdoor air-cooled condensing unit—top air discharge models . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 22 Electrical field connections, prop fan condensing module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 23 Detail of ceiling hanging bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 24 Centrifugal air-cooled condensing unit dimensional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Figure 25 Centrifugal air-cooled condensing unit dimensional data (con't.) . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 26 Split systems general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 27 Water/glycol-cooled condensing unit dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 28 Water/glycol-cooled condensing unit (con't.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
iv
TABLES
Table 1 Unit shipping weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 2 Piping connection size. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Table 3 Air-cooled condenser statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 4 Recommended line sizes — OD copper (inches)* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 5 Equivalent lengths (feet) for various pipe fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 6 Indoor unit refrigerant charge lb (kg) R22 or R407C (per unit serial tag) . . . . . . . . . . . . . . . . . . 17
Table 7 Line charges - refrigerant per 100 ft (30 m) of Type “L” copper tube. . . . . . . . . . . . . . . . . . . . . . . 17
Table 8 Condenser refrigerant (per serial tag) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 9 Refrigerant control settings psi (kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 10 Refrigerant control settings psi (kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 11 Room dew point temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 12 Indoor unit glycol volume approximate gallons (liters) max. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 13 Volume in standard Type “L” copper piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 14 Ethylene glycol concentrations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 15 Mounting hole dimensional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 16 Drycooler data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 17 Glycol pump data* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 18 Refrigerant control settings psi (kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 19 Unit refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 20 Line charges - refrigerant per 100 ft (30 m) of Type “L” copper tube. . . . . . . . . . . . . . . . . . . . . . . 40
Table 21 Recommended refrigerant lines (R22 or R407C) sizes OD copper . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 22 Line coupling sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 23 Equivalent lengths (feet) for various pipe fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 24 Horizontal air discharge cabinet and floor planning dimensional data. . . . . . . . . . . . . . . . . . . . . 44
Table 25 Horizontal air discharge piping and electrical connection data . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Table 26 Cabinet and floor planning dimensional data - prop fan condensing modules, top
air discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 27 Piping and electrical connections - top air discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 28 Indoor centrifugal condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Table 29 Airflow CFM (CMH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Table 30 Water and glycol-cooled unit connection sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 31 Water and glycol-cooled condensing unit data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 32 R407C pressure/temperature chart for operation and superheat (discharge/hot gas
and suction gas). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Table 33 R407C pressure/temperature chart for subcooling only (liquid measurements). . . . . . . . . . . . . . 57
Introduction
1
1.0 INTRODUCTION
1.1 System Descriptions
Liebert Challenger ITR environmental control systems are available in three main system configu-
rations:
self contained system with a scroll compressor in the room unit
self contained chilled water system
split system with an evaporator section and a remote condensing unit
All three types are available in horizontal flow configurations. Each model requires three-phase
power. Units are available in 208, 230, 460, or 575 V, 60 Hz; and 200, 230 or 380/415 V, 50 Hz.
The following features are included as standard in all room units regardless of the type of system:
V-frame coil, infrared humidifier, finned tubular stainless steel electric reheat, 2" filter, individual
high voltage fused protection, and fan assembly.
Each configuration can operate with either Advanced Microprocessor Controls (A), or Advanced
Microprocessor Controls with Graphics (G). A brief description of each, including operational differ-
ences, is listed below. Check model numbers to see what is supplied with your unit.
1.1.1 Self Contained Systems
Air-Cooled Models
Complete refrigeration system including hot gas bypass and crankcase heater with standard con-
denser and fan speed control for 95°F (35°C) ambient at sea level.
Water-Cooled Models
Compete refrigeration system including hot gas bypass with water/glycol-cooled condenser and two-
way water regulating valve with bypass.
Glycol-Cooled Models
The water-cooled model as described above plus pump package and 95°F (35°C) design ambient dry-
cooler.
GLYCOOL Models
Complete refrigeration system including hot gas bypass with glycol condenser and three-way water reg-
ulating valve plus an integrally piped Econ-O-Coil with three-way modulating control valve.
1.1.2 Chilled Water Models
Chilled Water models include chilled water piping, three-way modulating valve and actuator assembly.
1.1.3 Split Systems
Each Air-Cooled split system consists of an evaporator section and one of the following condensing units.
Prop Fan
Includes scroll compressor, condenser coil, prop fan, high pressure switch, and Lee-Temp head pres-
sure control. Unit is designed for outdoor location.
Centrifugal Fan
Includes scroll compressor, condenser coil, centrifugal blower assembly, high pressure switch, head
pressure control valve, Lee-Temp receiver and liquid line solenoid valve. Unit must be mounted
indoors. Duct flanges are optional.
Water/Glycol Condensing Units
Each water-cooled split system consists of an evaporator section and a water/glycol condensing unit,
which includes scroll compressor, coaxial condenser, water regulating valve, and high pressure switch.
Design pressure is 150 psi (1034 kPa) as standard and 350 psi (2413 kPa) as optional.
Each glycol-cooled split system consists of an evaporator section, a water/glycol condensing unit (as
described above), a pump package and a 95°F (35°C) design ambient drycooler.
Installation
2
2.0 INSTALLATION
2.1 Room Preparation
The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the
ceiling can be a polyethylene film type. Use a rubber or plastic base paint on concrete walls and floors.
Doors should not be undercut or have grilles in them.
Outside (or fresh) air should be kept to an absolute minimum. Outside air adds to the heating, cool-
ing, humidifying and dehumidifying loads of the site. It is recommended that outside air be kept
below 5% of the total air circulated in the room and be preconditioned.
2.2 Equipment Inspection
Upon arrival of the unit, inspect all items for visible and concealed damage. Damage should be imme-
diately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales
representative.
2.3 Location Considerations
The Liebert Challenger ITR can sit on top of an accessible elevated flooring system. It may be neces-
sary to furnish additional pedestal support below the unit to ensure maximum structural support (see
Table 1). A separate floor stand for the unit may be used as support, independent of the elevated floor
and installed prior to the flooring system.
Provide approximately 34" (864 mm) service clearance in the front and rear of the unit.
The unit can be installed between equipment racks or at the end of a row of racks. Consideration
should be given before installing refrigerant and liquid lines next to, under or above electronic equip-
ment. Avoid placing the Liebert Challenger ITR in an alcove. Placing units too close together will
reduce the effectiveness of the air distribution.
2.3.1 Remote Sensor Installation Location
The remote temperature and humidity sensor should be installed in the cold aisle in front of the
equipment to be cooled. It should be mounted at the farthest point from the cooling unit that supply
air needs to reach but still within the unit's area of influence. The sensor should be installed at the
highest point that equipment will draw in cooled air.
2.4 Equipment Handling
NOTE
Locate and remove shipping screw on fan motor base.
!
WARNING
Risk of equipment tipping over. Can cause damage, injury or death.
The instructions listed below must be adhered to when handling this unit with or without the
skid. There is the potential for this unit to tip over if handled improperly.
Installation
3
2.4.1 Handling With Skid
Always keep the Liebert Challenger ITR upright, indoors and protected from damage.
Do not use the extended rear door frame to lift the unit.
If possible, transport the unit using a fork lift; otherwise, use a crane with belts or cables, avoid-
ing pressing on the top edges of the packaging.
If using a fork lift, make sure that the forks, if adjustable, are spread to the widest allowable dis-
tance to still fit under the skid.
NOTICE
Do not attempt to lift the Liebert Challenger ITR with the extended rear door frame.
Attempting to do so will damage the unit. Lift the unit only from its main base.
NOTICE
While on the skid, the Liebert Challenger ITR is too tall to fit through a standard height
doorway (83 inches or 2108 mm tall). Any attempt to move the unit, while on the skid,
through a standard doorway will damage the unit.
2.4.2 Removal of Skid
1. Remove the plywood skirting that keeps the skid and unit in place.
2. Raise the Liebert Challenger ITR off the skid. Liebert recommends using a fork lift (see Figure 1)
or similar machine to ensure that the unit is lifted properly.
3. Once the unit is raised, the skid can be removed.
Figure 1 Removing Liebert Challenger ITR from skid
NOTE
Lift the Liebert Challenger ITR only from its main base. Do not use the extended rear door
frame to lift the unit.
Table 1 Unit shipping weights
Model
Domestic Export
Model
Domestic Export
lb (kg) lb (kg) lb (kg) lb (kg)
50Hz Models 60Hz Models
BR059E 650 (295) 750 (340) BR060E 650 (295) 750 (340)
BR065A 745 (340) 845 (385) BR067A 745 (340) 845 (385)
BR070WG 815 (370) 915 (415) BR071WG 815 (370) 915 (415)
BM058G 855 (390) 955 (435) BM061G 855 (390) 955 (435)
BR101C 660 (300) 760 (345) BR102C 660 (300) 760 (345)
Remove plywood skirting holding
unit and skid in place.
Raise unit with fork lift
or similar machine.
Installation
4
Figure 2 Cabinet dimensions
DPN001523
Pg. 2, Rev. 1
Filter Access
by Opening Door
UNIT
TOP VIEW
32-1/2"
(826mm)
5/8"
(16mm)
9-5/8"
(244mm)
8-1/2"
(216mm)
31-1/2"
(800mm)
1-7/8"
(48mm)
12-1/2"
(318mm)
30-1/2"
(775mm)
30-1/2"
(775mm)
32-1/2"
(826mm)
32-1/2"
(826mm)
1-5/8"
(41mm)
13"
(330mm)
Projection of
Display Bezel
Standard Piping Location
45-1/8"
(1147mm)
5-1/2"
(140mm)
15-1/16"
(382mm)
76"
(1930mm)
91-1/16"
(2313mm)
Blower Outlet with
1" (25.4mm) Flange
Shaded area indicates
a recommended
clearance of 34" (864mm)
for component access
Shaded area indicates a recommended
clearance of 34" (864mm) for component access
UNIT DIMENSIONAL DATA
FRONT VIEW
UNIT DIMENSIONAL DATA
REAR VIEW
10-1/4"
(260mm)
7/8" (22.2mm) Flange for
Duct or Plenum Connection
43-5/16"
(1100mm)
11-3/4"
(298mm)
Remove Blocker Panel
for Air Discharge Left
and/or Right Side Panels
Standard Electrical Outlet
Location Through Unit
12-5/8"
(321mm)
Discharge Air Opening
Plenum Overhang
Unit Weight
50 Hz Models 60 Hz Models lb. (kg)
BR059E BR060E 649 (294)
BR065A BR067A 744 (337)
BR070WG BR071WG 814 (369)
BR101C BR102C 659 (299)
BM058G BM061G 854 (387)
Installation
5
Figure 3 Optional floor stand dimensions
30-1/2"
(775mm) 30-1/2"
(775mm)
1"
(25.4mm)
See Specification Sheet
for height of floor stand ordered. SL-11897
Pg. 7
Installation
6
2.5 Piping Considerations
Consideration should be given before installing refrigerant and liquid lines next to, under or above
electronic equipment.
2.5.1 Drain Line
A 3/4" (19.1 mm) female pipe thread (FPT) connection is provided for the evaporator coil condensate
drain. This drain line also drains the humidifier, if applicable. The drain line must be located so it will
not be exposed to freezing temperatures. The drain should be at least the full size of the drain connec-
tion and pitched a minimum of 1/8" per ft. (11 mm per meter).
NOTE
This line may contain boiling water. Select appropriate drain system materials.
The Challenger ITR comes standard with a condensate pump will require a field-supplied trap
downstream from the pump. The drain line must comply with all applicable codes.
Table 2 Piping connection size
Air-Cooled Unit Connection Sizes—in.
Model No. BR/BM
60Hz (50Hz)
Liquid Line O.D. Copper
L
Hot Gas Line O.D. Copper
HG
067A (065A) 1/2 7/8
Split System Fan Coil Unit Connection Sizes—in.
Model No. BR/BM
60Hz (50 Hz)
Liquid Line
L
Suction Line
SC
060E (059E) 1/2 O.D. Cu 1-1/8 O.D. Cu
All Units: Connection Sizes—in.
Humidifier Line
O.D. Copper
H
Condensate
Drain Line
C
Condensate Pump Line
O.D. Copper
P
Hot Water Reheat
O.D. Copper
1/4 1/2 OD Cu 1/2 Supply HWS Return HWR
5/8 5/8
Water/Glycol-Cooled Unit Connection Sizes—in.
Model No. BR/BM
60Hz (50 Hz)
Supply Line
S
Return Line
R
071WG (070WG) 1-1/8 1-1/8
GLYCOOL Unit Connection Sizes —in.
Model No. BR/BM
60Hz (50 Hz)
Supply Line
S
Return Line
R
061G (058G) 1-1/8 1-1/8
Chilled Water Unit Connection Sizes—in.
Model No. BR/BM
60Hz (50 Hz)
Supply Line
CWS
Return Line
CWR
102C (101C) 1-1/8 1-1/8
Installation
7
Figure 4 Piping connections for air-cooled units
Piping outlet locations through the
plenum are the same as the unit.
See below for descriptions and
connection sizes.
Hot Water Return
5/8" OD CU (optional)
Hot Water Supply
5/8" OD CU (optional)
Liquid Refrigerant Line
1/2" OD CU on Models BR067A/BR065A
Humidifier Water
Supply Line 1/4" OD CU
Hot Gas Refrigerant Line
7/8" OD CU on Models
BR067A/BR065A
Condensate Pump
Line 1/2" OD CU
Monitoring Panel
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.) DPN001525
REV 0
Installation
8
Figure 5 Piping connections for split system fan coil units
Piping outlet locations through the
plenum are the same as the unit.
See below for descriptions and
connection sizes.
Hot Water Supply
5/8" OD CU (optional)
Condensate Pump Line
1/2" OD CU
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
Hot Water Return
5/8" OD CU (optional)
Liquid Refrigerant Line
1/2" OD CU on Models
BR060E/BR059E
Humidifier Water Supply Line
1/4" OD CU
Suction Refrigerant Line
1 1/8" OD CU on
Models BR060E/BR059E
Monitoring Panel
DPN001534
REV 0
Installation
9
Figure 6 Piping connections for water/glycol and GLYCOOL units
Piping outlet locations through the
plenum are the same as the unit.
See below for descriptions and
connection sizes.
Hot Water Supply
5/8" OD CU (optional)
Condensate Pump Line
1/2" OD CU
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
Hot Water Return
5/8" OD CU (optional)
Condenser Supply Line
1-1/8" OD CU on
Models BR071WG/BR070WG
Humidifier Water Supply Line
1/4" OD CU
Condenser Return Line
1 1/8" OD CU on
Models BR071WG/BR070WG
DPN001528
REV 0
Monitoring Panel
Installation
10
Figure 7 Piping connections for chilled water self-contained units
Installation
11
2.6 Electrical Connections
Three-phase electrical service is required for all models in either 208, 230, 460, or 575 V, 60 Hz; or
200, 230, or 380/415 V, 50 Hz. Electrical service shall conform to national and local electrical codes.
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec-
trical schematic when making connections.
A manual electrical disconnect switch should be installed within 5 feet (1.6 m) of the Liebert Chal-
lenger ITR in accordance with codes. A factory-supplied, locking disconnect switch is factory-mounted
within the unit behind the front door.
NOTICE
Three-phase power must be connected to the Liebert Challenger ITR line voltage terminals in
the proper sequence so that scroll the compressor rotates in the proper direction.
Figure 8 Electrical connections
1. Electric conduit knockouts on top and bottom of electric box. Knockout size 1-3/4" (44.5mm).
2. Three phase connection. Electric service connection terminals when factory disconnect switch
is supplied.
3. Factory-installed locking disconnect switch.
4. Three-phase electric service not by Liebert.
5. Earth ground connection (50/60Hz). Connection terminal for field-supplied earth grounding wire.
6. Earth ground bar (50Hz only). Connection terminals with factory ground from each high
voltage component for field supplied earth grounding wire.
7. Control and monitoring section of electric box.
8. Remote unit shutdown. Replace existing jumper between Terminals 37 + 38 with normally
closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. Two
additional contact pairs available as an option (labeled as 37B & 38B, 37C & 38C). Replace
existing jumper for appropriate pair as done for 37 & 38.
!
WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit. Use a voltmeter
to make sure power is turned off before making any electrical connections.
75 76 82 83 84 85 88 89 91 92 93 94 95 96 97 1
37C 38C 37B 37 38 24 50 51 55 56 77 78 4
7
2
3
4
5
71
70
15
6
11
13
12
17
16
14
1310
9
889
1
1
2338B
Terminal Block*
(for customer connections)
Electrical Handy Box*
(factory-installed with cover)
DPN001524
REV 0
Installation
12
9. Special alarm connections. Field-supplied 24V Class 1 wiring for special alarm. Connection
made by adding normally open contacts between terminals 24 + 50. Optional additional
connections available with Advanced or Advanced with Graphics controls and appropriate
optional accessories (connections 51, 55, and 56).
10. Liebert SiteScan® connection. Terminals 77 (-) and 78 (+) are for connection of a 2-wire, twisted
pair, communication cable (available from Liebert or others) to optional Liebert SiteScan.
11. Remote condensing unit connection. Field-supplied 24V Class 1 wiring to remote condensing
unit terminals 1, 2, 3, & 4 from (R2) relay (split system only).
12. Smoke detector alarm connections. Field-supplied 24V Class 1 wiring to remote alarm circuits.
Factory-wired contacts from optional smoke detector are #91-comm., #92-NO, and #93-NC.
13. Common alarm connection. Field-supplied 24V Class 1 wiring to common alarm terminals 75 + 76
(and optional 94 + 95, and 96 + 97), which are factory-connected to common alarm relay (R3).
14. Reheat and Humidifier Lockout. Optional emergency power lockout of reheat and/or humidifier:
connections provided for remote 24V AC source.
15. Heat rejection connection. Field-supplied 24V Class 1 wiring to interlock heat rejection from
pigtails 70 + 71 which are factory-connected to compressor side switch (self-contained units only
and to Glycool relay (R5), Glycool units only).
16. Main Fan Auxiliary Switch. Optional main fan auxiliary side switch. Terminals located in field
wiring compartment for remote indication that the evaporator fan motor/unit is on. Field to
connect 24V maximum.
17. Optional Condensate Alarm (Dual Float Condensate Pump only). Relay terminals located in field
wiring compartment for remote indication.
*Located inside Liebert Challenger ITR on top.
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.
2.7 Balancing the Air Distribution
2.7.1 Ducted Applications
For ducted applications, the duct work may be attached to the top perimeter of the Liebert Challenger
ITR (see Figure 2).
The duct work must allow access to the motors/blowers for maintenance. The duct work must be
designed within the capacity of the Liebert Challenger ITR, otherwise air flow and performance will
be compromised.
2.7.2 Plenum Installation
A solid plenum or plenum with discharge grille(s) may be installed. The plenum and instructions for
its installation ship separately from the Liebert Challenger ITR.
Installation
13
2.8 Checklist for Completed Installation
___ 1. Unpack and check received material.
___ 2. Proper clearance for service access has been maintained around the equipment.
___ 3. Equipment is level and mounting fasteners are tight.
___ 4. Piping completed to refrigerant or coolant loop (if required). Piping has been leak checked,
evacuated and charged (if required).
___ 5. Check piping within the Liebert Challenger ITR and outside of the unit. Remove potential of
rub-through or chaffing.
___ 6. Condensate pump installed.
___ 7. Drain line connected.
___ 8. Water supply line connected to humidifier (if required).
___ 9. Field provided pan with drain installed under all ceiling mounted fluid condensing units (if
installed).
___ 10. Ducting completed (if applicable).
___ 11. Filter(s) installed.
___ 12. Line voltage to power wiring matches equipment serial tag.
___ 13. Power wiring connections completed between disconnect switch, evaporator and condensing
unit, including earth ground.
___ 14. Power line circuit breakers or fuses have proper ratings for equipment installed.
___ 15. Control wiring connections completed to evaporator and condensing unit.
___ 16. Verify water detection is properly installed around all units (if installed).
___ 17. All wiring connections are tight.
___ 18. Control panel DIP switches set based on customer requirements.
___ 19. Foreign materials have been removed from, in and around all equipment installed (literature,
shipping materials, construction materials, tools, etc.).
___ 20. Fans and blowers rotate freely.
___ 21. Inspect all piping connections for leaks during initial operations. Correct as needed.
___ 22. Verify that a blank start-up sheet has been sent with the unit(s) and is ready to be completed
by the installer.
Air-Cooled Models
14
3.0 AIR-COOLED MODELS
3.1 Condenser Location
The air-cooled condenser should be located for maximum security and maintenance accessibility.
Avoid ground level sites with public access or areas that contribute to heavy snow or ice accumula-
tions. Utilize centrifugal condensers whenever interior building locations must by used. To assure
adequate air supply, it is recommended that condensers be located in a clean air area, away from
loose dirt and foreign matter that may clog the coil. In addition, condensers should not be located in
the vicinity of steam, hot air, or fume exhausts. Also, condensers should be located no closer than
three feet (1 meter) from a wall, obstruction, or adjacent unit.
Install condensers in a level position to assure proper refrigerant flow and oil return. For roof instal-
lation, mount condensers on steel supports in accordance with local codes. To minimize sound and
vibration transmission, mount steel supports across load bearing walls. For ground installation, a
concrete pad will provide adequate support. Condenser legs have mounting holes for securing the con-
denser to the steel supports or concrete pad.
3.2 Electrical Connections
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec-
trical schematic when making connections. Make all wiring and electrical connection in accordance
with local and national codes.
3.2.1 Line Voltage
Line voltage electrical service is required for all air-cooled condensers at the location of the condenser.
This power supply does not have to be the same voltage as the indoor unit. This separate power source
may be 208, 230, 460, or 575 V, 60 Hz; or 200, 230, or 380/415 V, 50 Hz. The disconnect switch may be
factory-supplied and mounted in the electrical panel or field-supplied and mounted per local and
national codes.
3.2.2 Low Voltage
A control interlock between the condenser and the indoor unit is required and is connected between
70 and 71 in the handy box of the indoor unit and the electric panel of the air-cooled condenser. NEC
Class 1 wiring is required.
3.2.3 Lee-Temp/Flood Back Head Pressure Control Condensers
Lee-Temp condensers require a separate power supply for the heated receivers. This power supply is
connected to the electrical connection box on the end of the receiver.
!
WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit. Use a voltmeter
to make sure power is turned off before making any electrical connections.
Air-Cooled Models
15
Figure 9 Air-cooled condensers
Table 3 Air-cooled condenser statistics
Model
Number
of Fans
Connection Sizes
(OD Copper) Net Weight
lb (kg)
“A” Dimension
in (mm)Hot Gas (in.) Liquid (in.)
083 1 7/8 5/8 295 (133.8) 42 (1067)
104 1 1-1/8 5/8 315 (142.8) 42 (1067)
Secure each leg to condenser frame at all
points shown using hardware provided.
Liquid line
* B
TYPICAL FOOTPRINT
Lee-Temp heater pad
connection box
*B - Inverted traps are to be field-supplied and installed
(typ). When installing traps, provide clearance for swing
end of access door. Traps are to extend above base of
coil by a minimum of 7-1/2" (190 mm)
Liquid line
Hot gas line
Electric service
supplied by
others
Electric
service
supplied by
others
Hot gas
line
* B
LEE-TEMP CONDENSER
FAN SPEED CONDENSER
44"
(1118mm)
18" (457.2mm)
43-9/16"
(1106mm)
51-7/16"
(1306.5mm)
37-7/8"
(962mm)
Common to all models. See Table 3
below for key to “A” dimension.
CONDENSER MOUNTING
1"
(25.4mm)
1-3/4"
(44.5mm)
4-1/4"
(108mm)
4-1/4"
(108mm)
1-3/4"
(44.5mm)
1"
(25.4mm)
1-3/4"
(44.5mm)
1" typ.
(25.4mm)
1-3/4"
(44.5mm)
37-11/16"
(957.3mm)
1-3/4"
(44.5mm)
A
9/16" (14.3mm)
diameter holes
8 places for
1/2" (12.7mm)
diameter bolts
43-3/16"
(1097mm)
SINGLE FAN
AIR-COOLED CONDENSERS
1" typ.
(25.4mm)
Air-Cooled Models
16
3.3 Refrigerant Piping
All refrigeration piping should be installed with high temperature brazed joints. Prevailing good
refrigeration practices should be employed for piping supports, leak testing, dehydration and charg-
ing of the refrigeration circuits.
Unit refrigeration components and piping are shipped from the factory with a nitrogen holding
charge.
Traps should be installed in the hot gas line on vertical risers at the base and every 25 feet (7.6
meters) in elevation. These traps will collect condensed refrigerant and refrigerant oil during the off
cycle of the unit and ensure flow of refrigerant oil during operation.
A check valve is factory-supplied with the unit to be field-installed on the discharge side of the scroll
compressor. Be sure to install the check valve with the refrigerant flow in the proper direction. When
soldering or brazing the valve, it is very important to protect the internal parts by wrapping the valve
with a damp cloth to keep the valve temperature below 250°F (121°C).
Approval is required whenever:
a refrigerant piping run exceeds 150 ft. (46 m) equivalent length
an R22 system condenser must be located more than 15 ft. (4.6 m) below the level of the cooling
coil
an R407C system condenser must be located below the level of the cooling coil.
Total discharge line pressure drop must not exceed 10 PSIG (69 kPa).
Consult your local Liebert representative when considering installations outside these guidelines.
NOTE
The refrigeration piping should be isolated from the building by the use of vibration isolating
supports.
NOTE
Piping, including inverted trap(s), must be routed to allow unobstructed access to the panel
per the NEC.
NOTE
When installing field piping, care must be taken to protect all refrigerant lines from the
atmosphere, especially when using refrigerants with POE oils. Do not allow the piping to stand
open to air for more than 15 minutes. Units designed for R407C have a compressor that
contains POE oil that is very hygroscopic; that is, it quickly absorbs water from the air. The
longer the compressor piping is left open to air, the harder it will be to fully evacuate. If left
open too long, the POE oil may need to be replaced before achieving the required vacuum level.
NOTE
Keep the evaporator unit and condenser closed with their factory charge of dry nitrogen while
all field piping is installed. Keep the field piping clean and dry during installation, and do not
allow it to stand open to the atmosphere. When all the field interconnecting piping is in place,
vent the condenser dry nitrogen charge and connect to the field piping. Finally, vent the
evaporator unit dry nitrogen charge and make its piping connections last.
Follow all proper brazing practices including a dry nitrogen purge to maintain system
cleanliness.
Table 4 Recommended line sizes — OD copper (inches)*
Equivalent Length
23 & 33 kW 067A (065A)
Hot Gas Line Liquid Line
50 ft. (15 m) 7/8 1/2
100 ft. (30 m) 7/8 5/8
150 ft. (45 m) 7/8 5/8
*Recommended vertical line sizes must be used for proper oil return at all cooling and dehumidification steps.
Air-Cooled Models
17
3.4 Fan Speed Control Systems
Fan Speed Control provides an infinite number of speed variations on specially designed, permanent
split-capacitor motors. The control module varies the air quantity passing over the condenser coil by
monitoring refrigerant pressure.
3.4.1 Materials Supplied
1. Built-in pre-wired condenser control box
2. Air-cooled condenser
3. Piping access cover to be reinstalled when piping is complete
4. Bolts (four per leg) 3/8" x 5/8"
5. Terminal block for two-wire, 24-volt interlock connection between unit and condenser
6. Condenser legs, four on one-fan models
Table 5 Equivalent lengths (feet) for various pipe fittings
Copper Pipe
O.D. in.
90 Degree
Elbow Copper
90 Degree
Elbow Cast
45 Degree
Elbow Tee
Gate
Valve
Globe
Valve
Angle
Valve
1/2 0.8 1.3 0.4 2.5 0.26 7.0 4.0
5/8 0.9 1.4 0.5 2.5 0.28 9.5 5.0
3/4 1.0 1.5 0.6 2.5 0.3 12.0 6.5
7/8 1.45 1.8 0.8 3.6 0.36 17.2 9.5
1-1/8 1.85 2.2 1.0 4.6 0.48 22.5 12.0
1-3/8 2.4 2.9 1.3 6.4 0.65 32.0 16.0
1-5/8 2.9 3.5 1.6 7.2 0.72 36.0 19.5
Refrigerant trap = 4 times equivalent length of pipe per this table.
Table 6 Indoor unit refrigerant charge lb (kg) R22 or R407C (per unit serial tag)
Model
R22 R407C
Approximate Charge
lb (kg)
Approximate Charge
lb (kg)
67A/65A 1.5 (0.68) 1.4 (0.6)
Table 7 Line charges - refrigerant per 100 ft (30 m) of Type “L” copper tube
O.D.
R22 R407C
Liquid Line
lb (kg)
Hot Gas Line
lbs (kg)
Liquid Line
lb (kg)
Hot Gas Line
lb (kg)
1/2" 7.3 (3.3) 1.3 (0.6) 6.9 (2.9) -
5/8" 11.7 (5.3) 2.1 (1.0) 11.0 (4.6) 2.2 (0.9)
3/4" 16.6 (7.5) 3.0 (1.4) 15.7 (6.5) 3.1 (1.3)
7/8" 24.4 (11.1) 4.4 (2.0) 23.0 (9.6) 4.5 (1.9)
Table 8 Condenser refrigerant (per serial tag)
Model
R22 R407C
Approximate Charge
lb (kg)
Approximate Charge
lb (kg)
Fan Speed Lee-Temp* Fan Speed Lee-Temp*
083 5 (2.27) 27 (12.3) 8 (3) 25 (12)
104 8 (3.63) 39 (17.7) 9 (4) 37 (17)
* Charge includes the receiver charge.
Air-Cooled Models
18
3.4.2 Dehydration/Leak Test and Charging Procedures for R22 (standard) or R407C (Optional)
Fan Speed Control Type Condenser
Dehydration/Leak Test
1. Make sure unit is OFF. Open all disconnects and remove all fuses except control fuses. On units
supplied with circuit breakers, open all breakers except for the transformer.
2. Add a jumper to the Fan Safety Switch between Common and Normal Open and disconnect the
wire connected to the Normally Closed. Turn unit disconnect ON. (Fan operation not required.)
3. Connect refrigeration gauges to the suction and discharge service valves of the compressor. Open
all compressor service valves.
4. To energize the liquid line solenoid valves through the control system power, set the control
temperature setpoint (see operation manual) to 60°F (15°C) and set the % relative humidity
setpoint higher than the conditioned room ambient to ensure that solenoid valves and hot gas
bypass valves are open during the dehydration process.
5. Pressurize the system circuit(s) to 150 PSIG (1034 kPa) by using dry nitrogen with a trace of
refrigerant. Check system for leaks with suitable leak finder.
6. After completion of leak testing, release the test pressure (per local code) and pull a deep vacuum
on the system with a suitable pump.
7. After four hours, check the pressure readings, and if they have not changed, break vacuum with
refrigerant. Pull another vacuum to 250 microns or less. Recheck the pressure after two hours.
After completing this step, pressurize the circuits with refrigerant (R407C liquid or R22 vapor per
unit nameplate) until suction and discharge pressures have equalized.
!
CAUTION
All local codes for handling refrigerant must be followed.
NOTE
As R22 and R407C are similar in properties, proper safety equipment and proper
refrigeration tools are required on both types. Check unit nameplate for correct refrigerant
type before topping off or recharging a system.
NOTE
Refrigerant R407C uses a POE (polyol ester) lubricant. The R407C refrigerant must be
introduced and charged from the cylinder only as a liquid.
NOTE
When installing field piping, care must be taken to protect all refrigerant lines from the
atmosphere, especially when using refrigerants with POE oils. Do not allow the piping to stand
open to air for more than 15 minutes. Units designed for R407C have a compressor which
contains POE oil that is very hygroscopic; that is, it quickly absorbs water from the air. The
longer the compressor piping is left open to air, the harder it will be to fully evacuate. If left
open too long, the POE oil may need to be replaced before achieving the required vacuum level.
NOTE
The above allows the technician to use unit 24 VAC power and controls to open liquid line
solenoid valve(s) and hot gas bypass solenoid valve(s) for the dehydration process. If no
power is at the unit disconnect, the technician is to use a separate 24 VAC source rated at
75 VA and connect to the system liquid line solenoid valve(s) and hot gas bypass solenoid
valve(s) directly.
Air-Cooled Models
19
Figure 10 Air-cooled fan speed control general arrangement
SL -11 89 7 PG 5
Con de nser
Co il
Sc hra d e r
Va lv e
Fu si bl e
Pl ug
In v e rted Trap s* on disch ar ge
an d retu rn li ne s to ex te nd
ab ov e ba se of co il by a
mi ni mu m of 7 1 /2" (1 90 mm )
Tr ap s* ev er y
25 ft. (7.6 m)
of ris e
Ev ap or at or
Co il
Ex pa nsio n
Va lv e
Hot Ga s
Bypass
Va lv e
So le no id
Va lves
Si ght
Gl as s
Fi lt er
Dryer
Li qu id Ret ur n
Sh ut o ff *
Va lv e
Se ns in g
Bu lb
Ex ter na l
Eq ua li zers
Scr ol l
Co mp re ss or
Se rv ic e
Va lves
Hot Ga s
Bypass
Hot Ga s
Di sch ar ge
Che ck Va lv e
(S hi pp ed Lo os e fo r
Fi el d I n st al la ti on )
SI NG LE CIRC UI T SH OW N
FA CT OR Y
PI PI NG
FI EL D
PI PI NG
*Comp on ent s ar e no t su pp li ed by Li eb ert bu t
ar e re co mm en d ed fo r pr op er ci rcui t op er at io n
an d ma in te n a nc e.
Air-Cooled Models
20
3.4.3 Charging
1. Make sure unit is OFF. Open all disconnect switches and, on units supplied with circuit breakers,
open all breakers. Replace all fuses for the Fan and Compressors or close breakers.
2. Remove jumper on the Fan Safety Switch and reconnect the system wire connections. Ensure that
all operational components are clear of debris. Turn unit ON. (Fan operation is required.) Check
the evaporator fan for proper rotation and correct if necessary.
3. Connect the refrigerant gauge charging hose to the drum of refrigerant and to the suction and
discharge service valves of the compressor.
4. Calculate the amount of charge for the system. Weigh in as much of the system charge as
possible. Refer to the unit, condenser and refrigerant line charge tables.
5. Set the control temperature setpoint (see operation manual) to 60°F (15°C) and set the % relative
humidity setpoint higher than the conditioned room ambient to ensure that solenoid valves and
hot gas bypass valves are open during the charging procedure. You may have to bypass the
LP Switch (low pressure switch) to start the compressors and stop short cycling. Reset the Head
Pressure switch(es) if open.
6. Add refrigerant (R407C liquid, or R22 vapor per unit nameplate) to the suction side of the
compressor until there is sufficient pressure to energize the low-pressure switch.
Then you may remove the manual bypass you applied earlier.
7. Charge the unit until the liquid line sight glass becomes clear. Then add one additional pound of
refrigerant.
8. As head pressure builds, the condenser fan starts rotating. The fan becomes fully energized when
sufficient head pressure is developed. (Fan starts to rotate at 190 psi and is full speed at 250 psi.)
3.5 Lee-Temp/Flood Back Head Pressure Control Systems
The Lee-Temp system consists of a modulating type head pressure control valve and insulated
receiver with heater pad to ensure operation at ambient temperatures as low as -30°F (-34.4°C).
3.5.1 Piping
Lee-Temp systems have two factory-supplied, field-installed check valves: one on the discharge side of
the scroll compressor and one on the inlet side of the receiver. Be sure to install the check valves with
the refrigerant flow in the proper direction. When soldering or brazing the valves, it is very important
that the internal parts be protected by wrapping the valve with a damp cloth to keep the valve tem-
perature below 250°F (121°C).
NOTE
When adding refrigerant to an operating system, it may be necessary to add the refrigerant
through the compressor suction service valve. Because the refrigerant leaving the
refrigerant cylinder must be in a liquid state, care must be exercised to avoid damage to the
compressor. It is suggested that a sight glass be connected between the charging hose and
the compressor suction service valve. This will permit adjustment of the cylinder hand
valve so that liquid can leave the cylinder while allowing vapor to enter the compressor.
Table 9 Refrigerant control settings psi (kPa)
Low Pressure
Cut Out
Low Pressure
Cut In
High Pressure
Cut Out
20 (137.9) 65 (448.2) 360 (2482)
Air-Cooled Models
21
3.5.2 Materials Supplied
1. Built-in pre-wired condenser control box
2. Air-cooled condenser
3. Piping access cover to be reinstalled when piping is complete
4. Bolts (four per leg) 3/8" x 5/8"
5. Terminal block for two-wire 24V interlock connection between the unit and the condenser
6. Condenser legs: four on one-fan models
7. Lee-Temp system:
a. Insulated storage receiver
b. Head pressure control valve with integral check valve
c. Adapter assembly
d. Rotalock valve
e. Pressure relief valve
f. Liquid level sight glass
g. Check valve
8. Bolts - (six per receiver) 3/8" x 1"
3.5.3 Dehydration/Leak Test and Charging Procedures for R22 (Standard) or R407C (Optional)
Lee-Temp Control Type Condenser
NOTE
Lee-Temp heater pad requires a separate, continuous electrical source of either 115 VAC or
200/208/230 VAC.
!
CAUTION
All local codes for handling refrigerant must be followed.
NOTE
As R22 and R407C are similar in properties, proper safety equipment and proper refrigeration
tools are required on both types. Check unit nameplate for correct refrigerant type and oil type
before topping off or recharging a system.
NOTE
Refrigerant R407C uses a POE (polyol ester) lubricant. The R407C refrigerant must be
introduced and charged from the cylinder only as a liquid.
NOTE
When installing field piping, care must be taken to protect all refrigerant lines from the
atmosphere, especially when using refrigerants with POE oils. Do not allow the piping to stand
open to air for more than 15 minutes. Units designed for R407C have a compressor which
contains POE oil that is very hygroscopic; that is, it quickly absorbs water from the air. The
longer the compressor piping is left open to air, the harder it will be to fully evacuate. If left
open too long, the POE oil may need to be replaced before achieving the required vacuum level.
Air-Cooled Models
22
Dehydration/Leak Test
1. Make sure unit is OFF. Open all disconnect switches and pull all fuses except control fuses. On
units supplied with circuit breakers, open all breakers except for the transformer.
2. Add a jumper to the Fan Safety Switch between Common and Normal Open and disconnect the
wire connected to the Normally Closed. Turn unit disconnect ON. (Fan operation not required.)
3. Connect refrigeration gauges to the suction and discharge service valves of the compressor and open.
4. Attach a “jumper” hose from the Rotalock fitting on the outlet of the receiver and the Schrader fitting
on the liquid header of the condenser. Front seat the Rotalock valve approximately two turns.
5. To energize the liquid line solenoid valve(s) through the control system, set the temperature
setpoint (see operation manual) to 60°F (15°C) and set the % relative humidity setpoint higher
than the conditioned room ambient to ensure that solenoid valves and hot gas bypass valves are
open during the dehydration process.
6. Pressurize system circuit(s) to 150 PSIG (1034 kPa) by using dry nitrogen with a trace of
refrigerant. Check system for leaks with suitable leak finder.
7. After completion of leak testing, release test pressure (per local code) and pull a vacuum on the
system.
8. After 4 hours, check pressure readings and, if they have not changed, break vacuum with
refrigerant. Pull a second and third vacuum of 250 microns or less. Recheck pressure after
2 hours.
3.5.4 Charging
1. Make sure unit is OFF. Open all disconnect switches and, on units supplied with circuit breakers,
open all breakers. Replace all fuses for the Fan and Compressors or close breakers.
2. Remove jumper on the Fan Safety Switch and reconnect the system wire connections. Ensure that
all operational components are clear of debris. Turn unit ON. (Fan operation is required.) Check
the evaporator fan for proper rotation and correct if necessary.
3. Connect the refrigerant gauge charging hose to the drum of refrigerant and to the suction and
discharge service valves of the compressor(s).
4. Calculate the amount of charge for the system. Weigh in as much of the system charge as
possible. Refer to the unit, condenser and refrigerant line charge tables.
5. Set the control temperature setpoint (see operation manual) to 60°F (15°C) and set the % relative
humidity setpoint higher than the conditioned room ambient to ensure that solenoid valves and
hot gas bypass valves are open during the charging procedure. You may have to bypass the
LP Switch (low pressure switch) to start the compressors and stop short cycling. Reset the Head
Pressure switch(es) if open.
6. Add refrigerant (R407C liquid or R22 vapor per unit nameplate) to the suction side of the
compressor until there is sufficient pressure to energize the low pressure switch.
Then you may remove the manual bypass you applied earlier.
7. Charge the unit until the proper charge is weighed in.
NOTE
The above allows the technician to use unit 24 VAC power and controls to open liquid line
solenoid valve(s) and hot gas bypass solenoid valve(s) for the dehydration process. If no power
is at the unit disconnect, the technician is to use a separate 24 VAC source rated at 75 VA and
connect to the system liquid line solenoid valve(s) and hot gas bypass solenoid valve(s) directly.
NOTE
When adding refrigerant to an operating system, it may be necessary to add the refrigerant
through the compressor suction service valve. Because the refrigerant leaving the
refrigerant cylinder must be in a liquid state, care must be exercised to avoid damage to the
compressor. It is suggested that a sight glass be connected between the charging hose and
the compressor suction service valve. This will permit adjustment of the cylinder hand
valve so that liquid can leave the cylinder while allowing vapor to enter the compressor.
Table 10 Refrigerant control settings psi (kPa)
Low Pressure Cut Out Low Pressure Cut In High Pressure Cut Out
20 (137.9) 65 (448.2) 360 (2482)
Air-Cooled Models
23
Figure 11 Air-cooled, Lee-Temp general arrangement
FACTORY PIPING
FIELD PIPING
SINGLE CIRCUIT SHOWN
SL-10061 PG 4 SL-10071 PG 4
Piping Assembly * *
Condenser Coil
Rotalock Valve **
1/4" ( 6.4mm)
Pressure Relief
Valve * *
Sight Glass
Lee-Temp
Receiver
Head Pressure
Control with
Integral Check
Valve
Check Valve
Liquid Return
from Condenser
Inverted Trap * on
discharge line to
extend above base
of coil by a
minimum of 7 1/2"
(190mm)
Traps * Every
25 Ft. (7.6m)
of rise on Hot
Gas Line only
Evaporator Coil
Sensing Bulb
Expansion Valve
Hot Gas
Bypass
Valve
Solenoid Valves
Sight Glass
Filter Drier
Liquid Return
Shutoff
Valve *
External Equalizers
Service
Valves
Scroll Compressor
Hot Gas
Bypass
Hot Gas Discharge
Check Valve * *
* Components are not supplied by Liebert
but are recommended for proper
circuit operation and maintenance.
* * Components supplied by Liebert
and must be field installed.
OPTIONAL PIPING
Water-Cooled Models
24
4.0 WATER-COOLED MODELS
4.1 Piping Considerations
Manual shut-off valves should be installed at the supply and return lines of each unit. This will pro-
vide for routine maintenance or emergency isolation of the unit.
When the water source for the condenser is of poor quality, it is good practice to provide cleanable fil-
ters in the supply line. These filters will trap the particles in the water supply and extend the service
life of the water-cooled condenser.
To provide for the emergency of water leaks and the consequences of sub-floor flooding, floor drains
should be provided with wet traps or a water detection system such as a Liqui-tect sensor that is
installed near the base of the unit or below the elevated floor.
4.2 Condenser
The condenser is designed to operate in conjunction with either a cooling tower or city water. The
maximum water pressure is 150 psig (1034 kPa). A high pressure system rated at 350 psig (2413 kPa)
is available as an option.
Water-Cooled Models
25
Figure 12 Water-cooled general arrangement
SL-11898 PG 5
Evaporator
Coil
Expansion
Valve
Sensing
Bulb
External
Equalizers
Hot Gas
Bypass
Valve Scroll
Compressor
Service
Valves
Hot Gas
Bypass
Solenoid
Valve
Sight
Glass
Filter
Drier
Hot Gas
Bypass
Tube
in Tube
Condenser
Bypass
Valve
2-Way Water
Regulating
Valve
3-Way Water
Regulating Valve
(optional)
Fluid
Return
From
Unit
Fluid
Supply
To
Unit
Fluid
Return
From
Unit
Fluid
Supply
To
Unit
Shutoff*
Valves
Hose Bibs*
FACTORY
PIPING
FIELD
PIPING
*Components are not supplied by Liebert but
are recommended for proper circuit operation
and maintenance.
Tube
in Tube
Condenser
Water-Cooled Models
26
4.3 Water Regulating Valve
The water regulating valve automatically regulates the amount of fluid necessary to remove the heat
from the refrigeration system, permitting more fluid to flow when load conditions are high and less
fluid to flow when load conditions are low. The valve consists of a brass body, balance spring, valve
seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.
4.3.1 Water Regulating Valve Adjustment
The Liebert Challenger ITR may be equipped with either a standard Johnson Controls valve, 150 psig
(1034 kPa) or with a high-pressure Johnson Controls valve, 350 psig (2413 kPa).
The valve may be adjusted with a standard refrigeration service valve wrench or screw driver.
To lower the head pressure setting, turn the square adjusting screw clockwise until the high pressure
gauge indicates the desired setting.
To raise the head pressure setting, turn the adjusting screw counterclockwise until the desired set-
ting is obtained.
Figure 13 Johnson Controls valve adjustment
4.3.2 Water Regulating Valve Manual Flushing
The valve may be flushed by inserting screwdrivers or similar tools under the opposing sides of the
main spring and lifting. This action will open the valve seat and flush any dirt particles from the seat.
If this fails, the valve must be disassembled for cleaning the seat.
4.3.3 Testing Valve Function
When the refrigeration system has been off for 10-15 minutes, the water flow should stop.
Should the water continue to flow, the valve is either improperly adjusted or the pressure sensing
capillary is not properly connected to the condenser.
Range
spring
Valve spring
guide
Top
retainer
Range adjustment screw
Insert screwdrivers underneath
the valve spring guide
Glycol/GLYCOOL-Cooled Models
27
5.0 GLYCOL/GLYCOOL-COOLED MODELS
5.1 Drycooler Location
The drycooler should be located for maximum security and maintenance accessibility. Avoid ground-
level sites with public access or areas which contribute to heavy snow or ice accumulations. To assure
adequate air supply, it is recommended that drycoolers be located in a clean air area, away from loose
dirt and foreign matter that may clog the coil. In addition, drycoolers should not be located in the
vicinity of steam, hot air or fume exhausts. Also, drycoolers should not be located closer than 3 feet
(1 meter) from a wall, obstruction or adjacent unit.
5.2 Drycooler Installation
For roof installation, mount drycoolers on steel supports in accordance with local codes. To minimize
sound and vibration transmission, mount steel supports across load bearing walls. For ground instal-
lation, a concrete pad will provide adequate support. Drycooler legs have mounting holes for securing
the drycooler to steel supports or concrete pad.
5.3 Electrical Connections
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec-
trical schematic when making connections. Make all wiring and electrical connections in accordance
with local and national codes.
5.3.1 Line Voltage
Line voltage electrical service is required for all drycoolers at the location of the drycooler. This power
supply does not have to be the same voltage as the indoor unit. This separate power source may be
208, 230, 460, or 575 V, 60 Hz; or 200, 230, or 380/415 V, 50 Hz. The disconnect switch is factory-sup-
plied and mounted in the electric panel.
5.3.2 Low Voltage
A control interlock between the drycooler and the indoor unit is required and is connected between 70
and 71 in the handy box of the indoor unit and the pump and drycooler control box of the drycooler.
NEC Class 1 wiring is required.
5.3.3 Pump and Drycooler
All wiring to the pump and drycooler from the control box should be done in accordance with the elec-
trical schematic on the inside lid of the drycooler control box and with local and national codes.
!
WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit. Use a voltmeter
to make sure power is turned off before making any electrical connections.
Glycol/GLYCOOL-Cooled Models
28
5.4 Glycol Piping
NOTICE
Galvanized pipe must not be used in or with systems or units that contain glycol. The
phosphates in the inhibitor can react with the zinc in the galvanized pipe, precipitating an
insoluble material that can eventually foul the system.
To help prevent piping failures, supply and return lines must be supported in a way that
keeps their weight from bearing on the piping of the unit, drycooler or pumps.
To avoid the possibility of burst pipes, it is necessary to install a relief valve in the system.
This valve may be obtained from the supplier as an option or obtained from another vendor.
Fluid-cooled condensers have small internal flow passages. To avoid clogging and other
resulting system operation problems, install a 16-20 mesh filter in the fluid supply line to the
indoor unit. The filter should be located where it can be easily serviced or replaced.
Do not install unit on open-loop systems. Debris carried by the fluid will clog the brazed plate
condenser.
It is recommended that manual service shut-off valves be installed at the supply and return connec-
tions to each unit. This enables routine service and/or emergency isolation of the unit. In addition,
multiple pump packages require a check valve at the discharge of each pump to prevent back flow
through the standby pump(s).
To facilitate filling, installation of hose bibs at the lowest point of the system is recommended.
Consideration of the minimum glycol temperature to be supplied from the drycooler will determine if
the need exists to insulate the glycol supply and return lines. Insulation will prevent condensation on
the glycol lines in low ambient conditions.
All fluid piping must comply with local codes. Care in sizing pipes will help reduce pumping power
and operating costs.
5.4.1 Expansion Tanks, Fluid Relief Valves and Other Devices
An expansion tank must be provided for expansion and contraction of the fluid due to temperature
change in this closed system. Vents are required at system high points to vent trapped air when fill-
ing the system. A relief valve is a also a necessary piping component.
Depending on the complexity of the system, various other devices may be specified. Pressure gauges,
flow switches, automatic air separator, tempering valves, standby pumps, sensors for electrical con-
trols, and flow switches are just a few of these devices.
NOTICE
Immediately following the use of water for leak testing or system cleaning, charge the tested
system with the proper percentage of glycol and water for the application’s coldest design
ambient. Complete system drain-down cannot be assured, and equipment damage could
result from freezing of residual water.
Table 11 Room dew point temperatures
Dry Bulb
°F (°C)
Wet Bulb
°F (°C)
Relative
Humidity
Dew Point*
°F (°C)
70 (21.1)
70 (21.1)
57.2 (14.0)
58.5 (14.7)
45
50
48.0 (8.9)
50.5 (10.3)
72 (22.2)
72 (22.2)
58.9 (24.9)
60.0 (15.5)
45
50
50.0 (10.0)
52.4 (11.3)
75 (23.8)
75 (23.8)
61.2 (16.2)
62.5 (16.9)
45
50
52.4 (11.3)
55.0 (12.7)
* Minimum glycol temperature before condensation will occur.
Glycol/GLYCOOL-Cooled Models
29
5.5 Filling Instructions
5.5.1 Preparing the System for Filling
It is important to remove any dirt, oil or metal filings that may contaminate the cooling system piping
in order to prevent contamination of the fresh glycol solution and fouling of the drycooler piping. The
system should be flushed thoroughly using a mild cleaning solution or high-quality water and then
completely drained before charging with glycol. Cleaning new systems is just as important as clean-
ing old ones. New systems can be coated with oil or a protective film; dirt and scale are also common.
Any residual contaminants could adversely affect the heat transfer stability and performance of your
system. In many cases, in both old and new systems, special cleaners are needed to remove scale, rust
and hydrocarbon foulants from pipes, manifolds and passages. Clean heat transfer surfaces are
important in maintaining the integrity of the heating/cooling system. For more information on clean-
ers and degreasers, contact your sales representative. Follow the manufacturer's instructions when
using these products.
Calculate the internal volume of the system as closely as possible. See Table 12 and Table 14 for
unit volumes. Use volume in Table 13 for glycol piping volumes.
Table 12 Indoor unit glycol volume approximate gallons (liters) max.
Model (50 Hz) Glycol-Cooled GLYCOOL
071WG/(070WG) 2.0 (7.5)
061G/(058G) 4.0 (15.1)
Table 13 Volume in standard Type “L” copper piping
Diameter (in.) Volume
Outside Inside Gal/Ft L/M
1/2 0.123 0.008 (0.01)
5/8 0.555 0.012 (0.15)
3/4 0.666 0.018 (0.22)
7/8 0.785 0.025 (0.31)
1-1/8 1.025 0.043 (0.53)
Glycol/GLYCOOL-Cooled Models
30
5.5.2 Glycol Solutions
When considering the use of any glycol products in a particular application, you should review the lat-
est Material Safety Data Sheets and ensure that the use you intend can be accomplished safely. For
Material Safety Data Sheets and other product safety information, contact the supplier nearest you.
Before handling any other products mentioned in the text, you should obtain available product safety
information and take necessary steps to ensure safety of use.
NOTICE
When mishandled, glycol products pose a threat to the environment. Before using any glycol
products, review the latest Material Safety Data Sheets and ensure that you can use the
product safely.
Glycol manufacturers request that the customer read, understand and comply with the
information on the product packaging and in the current Material Safety Data Sheets. Make
this information available to anyone responsible for operation, maintenance and repair of the
drycooler and related equipment.
No chemical should be used as or in a food, drug, medical device, or cosmetic, or in a product or pro-
cess in which it may contact a food, drug, medical device, or cosmetic until the user has determined
the suitability and legality of the use. Since government regulations and use conditions are subject to
change, it is the user's responsibility to determine that this information is appropriate and suitable
under current, applicable laws and regulations.
NOTICE
Automotive antifreeze is unacceptable and must NOT be used.
Typical inhibited formula ethylene glycol and propylene glycol manufacturers and suppliers are
Union Carbide (Ucartherm) or Dow Chemical (Dowtherm SR-1, Dowfrost). These glycols are supplied
with corrosion inhibitors and do not contain a silicone anti-leak formula. Commercial ethylene glycol,
when pure, is generally less corrosive to the common metals of construction than water itself. Aque-
ous solutions of these glycols, however, assume the corrosivity of the water from which they are pre-
pared and may become increasingly corrosive with use if not properly inhibited.
There are two basic types of additives: corrosion inhibitors and environmental stabilizers. The corro-
sion inhibitors function by forming a surface barrier that protects the metals from attack. Environ-
mental stabilizers, while not corrosion inhibitors in the strictest sense of the word, decrease corrosion
by stabilizing or favorably altering the overall environment. An alkaline buffer such as borax is a sim-
ple example of an environmental stabilizer since its prime purpose is to maintain an alkaline condi-
tion (pH above 7).
The percentage of glycol to water must be determined by using the lowest design outdoor temperature
in which the system is operating. Table 14 indicates the solution freeze point at several concentra-
tion levels of ethylene glycol. Propylene glycol concentrations should be 1% higher than the ethylene
glycol table values to find the freeze point. For example, 41% propylene glycol freezes at -10°F (-23°C).
NOTICE
The quality of water used for dilution must be considered because water may contain corrosive
elements that reduce the effectiveness of the inhibited formulation. Water classified as soft
(low in chloride and sulfate ion content less than 100 parts per million each) should be used.
NOTE
Glycol solutions should be considered for protection of the coil. When it is not used, damage can
occur from either freezing or corrosion from water.
Table 14 Ethylene glycol concentrations
% Glycol by Volume 0 * 10 20 30 40 50
Freezing Point °F (°C) 32 (0) 25 (-3.9) 16 (-8.9) 5 (-15.0) -10 (-23.3) -32 (-35.5)
Apparent Specific Gravity
@ 50°F (10°C) 1 1.014 1.028 1.042 1.057 1.071
* A minimal amount of glycol should be considered for inhibitive coil protection.
Glycol/GLYCOOL-Cooled Models
31
5.5.3 Filling the System
Installation of hose bibs at the lowest point of the system is recommended. When filling a glycol sys-
tem keep air to a minimum. Air in glycol turns to foam and is difficult and time-consuming to remove.
(Anti-foam additives are available and may be considered.) Open all operating systems to the loop.
With the top vent(s) open, fill the system from the bottom of the loop. This will allow the glycol to
push the air out of the top of the system, minimizing trapped air. Fill to approximately 80% of calcu-
lated capacity. Fill slowly from this point, checking fluid levels until full.
NOTE
For glycol solution preparation and periodic testing, follow manufacturer's recommendations.
Do not mix products of different manufacturers.
Glycol/GLYCOOL-Cooled Models
32
Figure 14 Drycoolers and pump packages
Notes
1. Single pump packages are 17-1/4"
(438 mm) wide. Dual pump packages are
32-1/4" (819 mm) wide.
2. Mounting holes are 15-1/4" (387 mm)
apart on single pump packages and 30-
1/4" (768 mm) apart on dual pump
packages.
3. Connection sizes apply to primary pump
supplier.
DRYCOOLER
Provided on
dual pump
package only
30-1/4"
(768mm)
A
B
19"
(483mm)
43-3/16"
(1097mm)
43-9/16"
(1105mm)
37-7/8"
(1095mm)
GLYCOL PUMP PACKAGE
See Note 1
A
B
C
3/4"
(19mm)
37-11/16"
(957mm) 1/2" (12.7mm) diameter
anchor bolts (typ)
B
C
PUMP PACKAGE
MOUNTING ANGLES
TYPICAL
FOOTPRINT UNIT ANCHOR PLAN
See Table 16 for keys to
dimensions “A”, “B” and “C”.
See Table 15 for keys to
dimensions “A”, “B” and “C”.
1/2" diameter holes
for mounting (4 typ)
Note: Angles located
inside, bottom of pump
package. View used for
mounting reference.
1"
(25.4mm)
1"
(25.4mm)
1-3/4"
(25.4mm)
1-3/4"
(25.4mm)
4-1/4"
(25.4mm)
4-1/4"
(25.4mm)
For expansion tank dimensions,
see Figure 15 on page -33.
Glycol/GLYCOOL-Cooled Models
33
Figure 15 Pump packages—expansion tank
Table 15 Mounting hole dimensional data
PUMP PACKAGE
A
in (mm)
B
in (mm)
C
in (mm)
SINGLE (0.75 - 7.5 hp) 15-1/4 (387.4) 2-1/2 (63.5) 22-1/2 (571.5)
DUAL (0.75 - 5 hp) 30-1/4 (768.4) 2-1/2 (63.5) 22-1/2 (571.5)
DUAL (7.5 hp) 39-5/16 (998.5) 1-3/4 (44.5) 26-7/8 (682.6)
Table 16 Drycooler data
Model
No.
No. of
Fans
Weight
lb (kg)
Drycooler
Conn. Sizes
(Suct. & Disc.) in.
“A” Dimension
in. (mm)
“B” Dimension
in. (mm)
“C” Dimension
in. (mm)
Coil Internal
Volume, gal. (l)
-069 1 410 (186) 1-1/4 51-1/2 (1308) 44 (1118) 42 (1067) 2.4 (9.2)
-092 1 430 (195) 1-1/2 51-1/2 (1308) 44 (1118) 42 (1067) 3.7 (13.9)
-109 1 450 (204) 2 51-1/2 (1308) 44 (1118) 42 (1067) 4.9 (18.6)
-112 1 470 (213) 2 51-1/2 (1308) 44 (1118) 42 (1067) 5.8 (22.0)
-139 2 565 (256) 2 91-1/2 (2324) 84 (2134) 82 (2083) 4.8 (18.2)
-197 2 605 (274) 2 91-1/2 (2324) 84 (2134) 82 (2083) 9.0 (34.1)
Table 17 Glycol pump data*
Pump Pump Suction
Connection in.
Pump Discharge
Connection in. Hp Hz
1-1/2
2
3
5
60
60
60
60
1-1/4
1-1/4
1-1/2
1-1/2
3/4
3/4
1
1-1/4
1
1-1/2
2
3
50
50
50
50
1-1/4
1-1/4
1-1/4
1-1/2
3/4
3/4
3/4
1-1/4
* Connection sizes apply to primary pump supplier
O
SL-10065 PG 7B SL-10070 PG 6B
30-1/2"
(774.7mm)
6-13/16"
(173mm)
17-1/4"
(438.2mm)
2-3/4"
(69.9mm)
4"
(101.6mm)
2-1/2"
(63.5mm)
7"
(177.8mm)
1/2" FPT
Fitting
1/2" FPT
Fitting
1" (25.4mm)
1" (25.4mm)
1-1/2"
(38.1mm)
1-1/2"
(38.1mm) 6-1/8"
(155.6mm)
9"
(228.6mm)
8.8 Gallon Expansion Tank
(33.3 Liter)
O1/2 " (12.7mm) (8) Holes
3"
(76.2mm)
Glycol/GLYCOOL-Cooled Models
34
Figure 16 Glycol general arrangement
SL-11898 PG 6
Glyco l
Pump
Pump
Housing
Unions*
Isolation
Valves*
Expansion
Valve
Drycooler
Electric
Box Drycooler
Coil
Fluid
Return
to Pump
Fluid
Supply
from
Pump
Unions*
Fill *
Expansion Tank Field Installed at
Highest Point in System.
Expansion
Port*
Air Vents*
at Top of
Risers
Hose
Bibs* Flow Regulating
Valve*
Pressure
Port*
Sight
Glass
Filter
Drier
Evaporator
Coil
Sensing
Bulb
External
Equalizers
Hot Gas
Bypass
Valve Scroll
Compressor
Service
Valves
Hot Gas
Bypass
Solenoid
Valve
Hot Gas
Bypass
Tube
in Tube
Condenser
Tube
in Tube
Condenser
Bypass
Valve
2-Way Water
Regulating
Valve
Fluid
Return
from
Unit
Fluid
Supply
to Unit
Isolation
Valves*
Hose
Bibs*
Fluid
Supply
to Unit Fluid
Return
From
Unit
3-Way Water
Regulating Valve
(optional)
FACTORY
PIPING
*Components are not supplied by Liebert but
are recommended for proper circuit operation
and maintenance.
FIELD
PIPING
Hose
Bibs*
Glycol/GLYCOOL-Cooled Models
35
Figure 17 GLYCOOL general arrangement
SL-11901 PG 5
Pump
Housing
Glyco l
Pump
Unions*
Isolation
Valves*
Expansion
Valve
Evaporator
Coil
Drycooler
Coil
Drycooler
Electric
Box
Unions*
Pressure
Port*
Hose
Bib*
Fill *
Fluid
Return to
Pump
Fluid
Supply
from
Pump
Air Vents*
at Top of
Risers
Flow Regulating
Valve*
Pressure
Port*
Sight
Glass
Sensing
Bulb
External
Equalizers
Hot Gas
Bypass
Valve Scroll
Compressor
Service
Valves
Hot Gas
Bypass
Solenoid
Valve
Filter
Drier
Hot Gas
Bypass
Econ-O-Coil
3-Way Water
Regulating
Valve
3-Way Chilled
Glyco l Valve
Valve
Actuator
Econ-O-Cycle
Comparator
Econ-O-Coil
Circuit
Tube
in Tube
Condenser
Fluid
Supply to
Unit
Fluid
Return
from
Unit Isolation
Valves*
Hose
Bibs*
FACTORY PIPING
FIELD PIPING
*Components are not supplied by Liebert but
are recommended for proper circuit operation and maintenance.
Expansion Tank Field Installed at
Highest Point in System
Glycol/GLYCOOL-Cooled Models
36
5.6 Condenser
The condenser is designed to operate in conjunction with a drycooler. The maximum coolant pressure
is 350 psig (2413 kPa).
5.7 Glycol Regulating Valve
The glycol regulating valve automatically regulates the amount of coolant necessary to remove the
heat from the refrigeration system, permitting more fluid to flow when load conditions are high and
less fluid to flow when load conditions are low. The valve consists of a brass body, balance spring,
valve seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.
5.7.1 Glycol Regulating Valve Adjustment
The Liebert Challenger ITR may be equipped with either a standard Johnson Controls valve, 150 psig
(1034 kPa) or with a high-pressure Johnson Controls valve, 350 psig (2413 kPa). For details on adjust-
ing the valve, refer to 4.3.1 - Water Regulating Valve Adjustment.
5.7.2 Testing Valve Function
When the refrigeration system has been off for approximately 10-15 minutes, the coolant flow should
stop.
Should the coolant continue to flow, the valve is either improperly adjusted or the pressure sensing
capillary is not connected properly to the condenser.
NOTE
For pressures above 150 psig (1034 kPa), the high pressure option for high pressure valve(s)
is required.
Table 18 Refrigerant control settings psi (kPa)
Low Pressure
Cut Out
Low Pressure
Cut In
High Pressure
Cut Out
20 (137.9) 65 (448.2) 360 (2482)
Chilled Water Models
37
6.0 CHILLED WATER MODELS
6.1 Piping Considerations
Manual shut-off valves should be installed at the supply and return lines to each unit. This will pro-
vide for routine service and emergency isolation of the unit.
Consideration of the minimum water temperature to be supplied from the chiller will determine if the
need exists to insulate supply and return lines. Insulation will prevent condensation on the supply
and return lines.
To provide for the emergency of water leaks and the consequences of sub-floor flooding, floor drains
should be provided with wet traps or a water detection system, such as a Liqui-tect, that is installed
near the base of the unit or below the elevated floor.
Figure 18 Chilled water general arrangement - horizontal flow (BR)
A
B
AB
FIELD PIPING
SL-11899
Pg. 5
Air
Flow
Chilled
Water
Coil
Bleed
Valve
Valve
Actuator
Valve
Flow
Switch
(optional)
Chilled
Water
Supply
Chilled
Water
Return
Hose
Bibs*
Hose
Bibs*
Shutoff
Valves*
3-WAY VALVE
Air
Flow
Bleed
Valve
Chilled
Water
Coil
Valve
Actuator
Shutoff
Valves*
Chilled
Water
Return
Chilled
Water
Supply
2-WAY VALVE
2-Way
Chilled
Water
Valve
SINGLE CIRCUIT SHOWN
*Components are not supplied by Emerson but
are recommended for proper circuit operation
and maintenance.
FACTORY PIPING
3-Way
Chilled
Water
Split System Models
38
7.0 SPLIT SYSTEM MODELS
Three (3) condensing unit styles are available: two (2) air-cooled and one (1) water/glycol-cooled con-
densing unit.
7.1 Location Considerations
7.1.1 Air-Cooled Condensing Units
To assure an adequate air supply, it is recommended that all condensing units be located in a clean
air area, away from loose dirt and foreign matter that may clog the coil.
Condensing units must not be located in the vicinity of steam, hot air, or fume exhausts or closer than
18" from a wall, obstruction, or adjacent unit.
The outdoor condensing unit should be located for maximum security and maintenance accessibility.
Avoid ground-level sites with public access or areas that will contribute to heavy snow accumulations.
Do not allow the discharge air to blow into another condensing unit.
A solid base, capable of supporting the weight of the condenser and at least 2" (51 mm) higher than
the surrounding grade and at least 2" (51 mm) larger than the condensing unit base dimensions,
should be installed at the pre-determined location. In snow areas, a base of sufficient height to clear
snow accumulation must be installed.
The centrifugal fan air-cooled condensing unit may be located above the dropped ceiling or any remote
indoor area. If noise is of concern, the condensing unit should be located away from personnel. Normal
operating sound may be objectionable if the condensing unit is placed near quiet work areas.
To mount the unit in the ceiling, refer to 7.5.1 - Installing the Indoor Condensing Unit for hang-
ing guidelines and to Figure 23 - Detail of ceiling hanging bracket for dimensional data.
7.1.2 Water/Glycol-Cooled Condensing Units
The condensing unit may be located above the dropped ceiling or any remote indoor area. If noise is of
concern, the condensing unit should be located away from personnel. Normal operating sound may be
objectionable if the condensing unit is placed near quiet work areas. To mount the unit the in ceiling,
refer to 7.5.1 - Installing the Indoor Condensing Unit.
7.2 Electrical Connections
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec-
trical schematic when making connections. Make all wiring and electrical connections in accordance
with local and national codes.
7.2.1 Line Voltage
Line voltage electrical service is required for all condensing units at the location of the condensing
unit. This power supply does not have to be the same voltage as the indoor unit. This separate power
source may be 208, 230, 460 or 575V, 60 Hz; or 200, 230, or 380/415V, 50 Hz. A disconnect switch is
required and must be mounted per local and national codes to isolate the unit for maintenance.
7.2.2 Low Voltage
The control cable between the condensing unit and the evaporator unit is connected between termi-
nals 1,2 and 3 on the terminal strip in the evaporator unit and the condensing unit control box. A
fourth wire is required on systems with hot gas bypass. NEC Class 1 wiring is required. Glycol-cooled
units also require a two-wire control connection to the drycooler and pump package.
!
WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit. Use a
voltmeter to make sure power is turned off before making any electrical connections.
Split System Models
39
7.3 Piping Considerations
7.3.1 Refrigerant Loop
All split systems require two refrigerant lines (an insulated copper suction line and a copper liquid
line) between the evaporator and the condensing unit.
Two possible methods exist for installing the copper suction and liquid lines.
1. Using an optional Sweat Adapter Kit and hard piping between the two units.
2. Using optional pre-charged line sets.
All refrigeration piping should be installed with high temperature brazed joints. Prevailing good
refrigeration practices should be employed for piping supports, leak testing, evacuation, dehydration,
and charging of the refrigeration circuits. The refrigeration piping should be isolated from the build-
ing by the use of vibration isolating supports.
It is important to handle the pre-charged lines with care so they will not get kinked or damaged. Use
tube benders and make all bends before making connections to either end. Coil any excess tubing in a
horizontal plane with the slope of the tubing toward the condensing unit.
To prevent tube damage when sealing openings in walls and to reduce vibration transmission, use a
soft flexible material to pack around the tubes.
When installing remote condensing units mounted above the evaporator, the suction gas line should
be trapped at the evaporator. This trap will retain refrigerant oil in the off cycle. When the unit
starts, oil in the trap is carried up the vertical riser and returns to the compressor.
Refrigerant charge requirements: Total refrigerant charge will be required only if units are evacuated
during installation or maintenance. Total refrigerant charge = evaporator + lines + condensing unit.
!
CAUTION
All local codes for handling refrigerant must be followed.
NOTE
As R22 and R407C are similar in properties, proper safety equipment and proper refrigeration
tools are required on both types. Check unit nameplate for correct refrigerant type before
topping off or recharging a system.
NOTE
Refrigerant R407C uses a POE (polyol ester) lubricant. The R407C refrigerant must be
introduced and charged from the cylinder only as a liquid.
NOTE
When installing field piping, care must be taken to protect all refrigerant lines from the
atmosphere, especially when using refrigerants with POE oils. Do not allow the piping to stand
open to air for more than 15 minutes. Units designed for R407C have a compressor which
contains POE oil that is very hygroscopic; that is, it quickly absorbs water from the air. The
longer the compressor piping is left open to air, the harder it will be to fully evacuate. If left
open too long, the POE oil may need to be replaced before achieving the required vacuum level.
NOTE
Complete all piping and evacuate lines before connecting quick connects when using an
optional sweat adapter kit and field installed hard piping.
Follow all proper brazing practices including a dry nitrogen purge to maintain system
cleanliness.
NOTE
All condensing units and 3-ton evaporator units are fully charged with refrigerant. All
23 and 33 kW evaporator units include a nitrogen holding charge only. See Table 19 for field
charge required. If field-supplied refrigerant piping is installed, refrigerant must be added to
the system.
Split System Models
40
Once all piping is complete, check for leaks and dehydrate the field piping as follows:
1. Pressurize the field piping to 150 PSIG (1034 kPa) using dry nitrogen with a trace of refrigerant.
Check system for leaks with a suitable leak detector.
2. After completion of leak testing, release the test pressure (per local code) and pull a deep vacuum
on the field piping with a suitable pump.
3. After 15 minutes, check the pressure readings and, if they have not changed, break vacuum with
dry nitrogen. Pull a second vacuum to 250 microns or less. Recheck the pressure after 15 minutes.
Table 19 Unit refrigerant charge
Model
R22 Charge R407C Charge
Model
R22 Charge R407C Charge
lb (kg) lb (kg) lb (kg) lb (kg)
060E 0.81 (0.37) 0.8 (0.4) PF_Z67A-_L 51.69 (23.45) 50.1 (22.7)
059E 0.81 (0.37) 0.8 (0.4) PF_Z66A-_L 51.69 (23.45) 50.1 (22.7)
MC_65/64A 27.00 (12.25) 26.1 (11.8) PF_067A-_H 51.69 (23.45) 50.1 (22.7)
PF_067A-_L 26.63 (12.08) 25.8 (11.7) PF_066A-_H 51.69 (23.45) 50.1 (22.7)
PF_066A-_L 26.63 (12.08) 25.8 (11.7) MC_69/68W 5.88 (2.67) n/a
Table 20 Line charges - refrigerant per 100 ft (30 m) of Type “L” copper tube
O.D.
R22 R407C
Liquid Line
lb (kg)
Suction Line
lb (kg)
Liquid Line
lb (kg)
Suction Line
lb (kg)
1/2" 7.3 (3.3) 0.2 (0.1) 6.9 (2.9) -
5/8" 11.7 (5.3) 0.3 (0.2) 11.0 (4.6) 0.4 (0.2)
7/8" 24.4 (11.1) 0.7 (0.3) 23.0 (9.6) 1.0 (0.4)
1-1/8" 41.6 (18.9) 1.2 (0.6) 39.3 (16.3) 1.7 (0.7)
1-3/8" 63.3 (28.7) 1.9 (0.8) 59.8 (24.8) 2.7 (1.1)
Table 21 Recommended refrigerant lines (R22 or R407C) sizes OD copper
Equivalent Feet (m)
3.5 Tons
036E (035E)
23 & 33 kW
060E (059E)
Suction Liquid Suction Liquid
0-50 (0-15) 7/8" 1/2" 1-1/8" 1/2"
51-100 (16-30) 1-1/8" 1/2" 1-1/8" 5/8"
101-150 (31-45) 1-1/8" 5/8" 1-3/8" 5/8"
Table 22 Line coupling sizes
Line Size
OD Cu, in.
Coupling
Size
Torque
lb-ft.
1/2 & 5/8 #10 35-45
1-1/8 #12 50-65
Split System Models
41
Figure 19 Refrigerant piping diagram
Table 23 Equivalent lengths (feet) for various pipe fittings
Copper Pipe
OD in.
90 Degree
Elbow Copper
90 Degree
Elbow Cast
45 Degree
Elbow Tee
Gate
Valve
Globe
Valve
Angle
Valve
1/2 0.8 1.3 0.4 2.5 0.26 7.0 4.0
5/8 0.9 1.4 0.5 2.5 0.28 9.5 5.0
3/4 1.0 1.5 0.6 2.5 0.3 12.0 6.5
7/8 1.45 1.8 0.8 3.6 0.36 17.2 9.5
1-1/8 1.85 2.2 1.0 4.6 0.48 22.5 12.0
1-3/8 2.4 2.9 1.3 6.4 0.65 32.0 16.0
1-5/8 2.9 3.5 1.6 7.2 0.72 36.0 19.5
Refrigerant trap = 4 times equivalent length of pipe per this table
Evaporator
Condensing
Unit
Evaporator Condensing
Unit
Suction Line Piping
Condensing unit above evaporator .
Traps recommended at the base of riser and
every 25 feet (7.6m) of vertical rise.
Suction Line Piping
Condensing unit
below evaporator
NOTE
When remote condensing units are installed below the
evaporator, the suction gas line should be trapped with
an inverted trap to the height of the evaporator. This
prevents refrigerant migration to the compressors
during off cycles. Maximum recommended vertical drop
to condensing unit is 15 ft. ( 4.6m).
Pitch down 1/2" (13mm) per 10 ft. (3m)
Split System Models
42
7.3.2 Quick Connect Fittings
Be especially careful when connecting the quick connect fittings. Read through the following steps
before making the connections.
1. Remove protector caps and plugs.
2. Carefully wipe coupling seats and threaded surfaces with a clean cloth.
3. Lubricate the male diaphragm and synthetic rubber seal with refrigerant oil.
4. Thread the coupling halves together by hand to ensure that the threads mate properly.
5. Tighten the coupling body hex nut and union nut with the proper sized wrench until the coupling
bodies “bottom out” or until a definite resistance is felt.
6. Using a marker or pen, make a line lengthwise from the coupling union nut to the bulkhead.
7. Tighten the nuts an additional quarter turn; the misalignment of the lines shows how much the
coupling has been tightened. This final quarter turn is necessary to ensure that the joint will not
leak. Refer to Table 22 for torque requirements.
8. Add charge for the additional piping (refer to Table 20).
NOTE
When hard piping is used, complete all piping and evacuate lines before
connecting quick connects.
Split System Models
43
7.4 Outdoor Air-Cooled Condensing Units
Figure 20 Outdoor air-cooled condensing unit—horizontal air discharge models
A
B
C
INDICATES A MINIMUM
CLEARANCE OF 18" (457mm)
FOR PROPER AIR FLOW.
SHADED AREA
INDICATES A MINIMUM
CLEARANCE OF 18" (457mm)
FOR PROPER AIR FLOW
SHADED AREA
INDICATES A RECOMMENDED
CLEARANCE OF 24" (610mm)
FOR COMPONENT ACCESS
AND REMOVAL.
LEFT
AIR
INTAKE
REMOVABLE (FRONT) PANEL FOR
ACCESS TO HIGH VOLTAGE &
LOW VOLTAGE CONNECTIONS,
AND REFRIGERATION COMPONENTS.
RIGHT
AIR
DISCHARGE
REMOVABLE (R IGHT) PAN EL
FOR ACCESS TO
REFRIGERATION COMPONENT.
Fan Rotation
CCW
(left side)
SL-11081 PG 4
C
C
SHADED AREA
Liquid Line
Suction Line
Quick Connect
(Male Coupling .
Electrical Entrance for
Electrical Entrance for
Low Voltage Connection
SL-11081PG 6
Quick Connect
(Male Coupling).
Except as noted
B
C
A
F
G
D
E
High Voltage
Connection
UNIT DIMENSIONS
(See Table 24)
Split System Models
44
Table 24 Horizontal air discharge cabinet and floor planning dimensional data
Model Numbers Dimensional Data in. (mm) Module
Weight
lb (kg) net60 Hz 50 Hz A B C
PFC067A-_L PFC066A-_L 53 (1343) 36-1/4 (918) 18 (457) 351 (159)
PFH067A-_L
Table 25 Horizontal air discharge piping and electrical connection data
Model Numbers Dimensional Data in. (mm) Piping Connections in. (mm)
60 Hz 50 Hz A B C D E F G
PFC067A-_L PFC066A-_L 2 (51) 6 (152) 8-1/2 (216) 4-3/4 (121) 7-3/4 (197) - 8-1/2 (216)
PFH067A-_L
Split System Models
45
Figure 21 Outdoor air-cooled condensing unit—top air discharge models
SL-11081PG 5
C
A
2"
B
LEFT
AIR
INTAKE
(51mm)
D
GUARD
HEIGHT TOP
AIR
DISCHARGE
RIGHT
AIR
INTAKE
SHADED AREA
INDICATES A RECOMMENDED
CLEARANCE OF 18" (457mm)
FOR PROPER AIR FLOW
SHADED AREA
INDICATES A RECOMMENDED
CLEARANCE OF 24" (610mm)
FOR COMPONENT ACCESS
AND REMOVAL.
SHADED AREA
INDICATES A RECOMMENDED
CLEARANCE OF 18" (457mm)
FOR PROPER AIR FLOW REMOVABLE FRONT PANEL FOR
ACCESS TO HIGH VOLTAGE &
LOW VOTLAGE CONNECTIONS,
AND REFRIGERATION COMPONENTS.
36 1/8 "
423/32 "
25 3/32 "
46 7/32 "
53 3/16 "
4" TYP.
32 1/8 "
2" TYP.
2"
2"
(918mm) (102mm)
(51mm)
(1351mm)
(120mm)
(637mm)
(1174mm)
(51mm)
(51mm)
(816mm)
FOOTPRINT
DIMENSIONS
1/2" Bolt-Down Holes
(6 places)
SL-11081 PG 7
* System 2 (23 & 33kW)
Electrical Entrance for
High Voltage Connection
Electrical Entrance
for Low Voltage
Connection
Liquid Line
Quick Connect
(Male Coupling)
Suction Line
Quick Connect
(Male Coupling)
* System 1 (3 Ton)
* System 1 and System 2 on 8Ton only.
GF
B
C
A
D
E
UNIT DIMENSIONS
(see Table 26)
PIPING & ELECTRICAL
CONNECTIONS
(see Table 27)
Split System Models
46
Table 26 Cabinet and floor planning dimensional data - prop fan condensing modules, top air discharge
Model Numbers Dimensional Data, in. (mm) Module
Weight
lb (kg) net60 Hz 50 Hz A B C D
PFC067A-_H PFC066A-_H
53 (1343) 36-1/4 (918) 38-1/2 (978) 5-1/2 (140) 488 (222)PFH067A-_H
PFCZ67A-_L PFCZ66A-_L
Table 27 Piping and electrical connections - top air discharge
Model Numbers Dimensional Data in. (mm) Piping Connections, in. (mm)
60 Hz 50 Hz A B C D E F
PFC067A-_H PFC066A-_H
2 (51) 6 (152) 8-1/2 (216) 4-3/4 (121) 7-3/4 (197) 8-1/2 (216)PFH067A-_H
PFCZ67A-_L PFCZ66A-_L
Split System Models
47
Figure 22 Electrical field connections, prop fan condensing module
NOTE: Refer to specification sheet for full load amp
and wire size amp ratings.
SL-11081 PG 8
Factory-wired
to components on
electric panel.
Heat rejection connection. Field-
supplied 24V NEC class 2 wiring.
Wire connections from evaporator module:
1. 24V GND
2. 24V Supply
3 High Pressure Alarm
4. Hot Gas Bypass Connection
(only on units with hot gas bypass.
If no hot gas bypass, connection is
provided in the evaporator module.
Connect wire 4 with wire 2 to the
24V supply).
Electric service
connection to contactor
or terminal block
Single- or 3-phase
electric service; not
by Liebert
High voltage electric
power supply entrance
Low voltage electric
power supply entrance
Earth ground connection
terminal for field wiring.
SL-11081PG 8A
TOP AIR
DISCHARGE MODELS
(23 & 33kW High Ambient
and 23 & 33kW Quiet-Line)
HORIZONTAL AIR DISCHARGE MODELS
Single- or
3-phase
electric
service; not
by Liebert
Field-supplied 24V NEC
Class 2 wiring to
evaporator module
Single- or
3-phase
electric
service;
not by Liebert
Field-supplied unit
disconnect switch
Field-supplied 24V
NEC Class 2 wiring
to evaporator
module
Split System Models
48
7.5 Centrifugal Air-Cooled Condensing Units
7.5.1 Installing the Indoor Condensing Unit
Refer to drawings for unit dimensions and component locations.
The indoor condensing unit is usually mounted above the ceiling and must be securely mounted to the
roof structure. The ceiling and ceiling supports of existing buildings may require reinforcements. Be
sure to follow all applicable codes. Use field-supplied threaded suspension rods and
3/8"-16 factory hardware kit.
Recommended clearance between ceiling grids and building structural members is unit height plus
three inches.
Install the four field-supplied rods by suspending them from suitable building structural members.
Locate the rods so that they will align with the four mounting holes in the flanges that are part of the
unit base.
Using a suitable lifting device, raise the unit up and pass the threaded rods through the four mount-
ing holes in the flanges that are part of the unit base.
Attach the threaded rods to the unit flanges using the supplied nuts and grommets. (See Figure 23 -
Detail of ceiling hanging bracket, Threaded Rod and Hardware Kit Installation). The rubber
grommets provide vibration isolation.
1. Use the plain nuts to hold unit in place. Adjust these nuts so that the weight of the unit is
supported evenly by the four rods, does not rest on the ceiling grid, and is level.
2. Use the Nylock nuts to “jam” the plain nuts.
!
WARNING
Risk of structure collapse. Can cause equipment damage, injury or death.
Before beginning installation, make sure that the supporting roof structure is capable of
supporting the weight of the unit(s) and the accessories during installation and service. (See
Table 28 - Indoor centrifugal condensing unit.)
Be sure to securely anchor the top ends of the suspension rods. Make sure all nuts are tight.
NOTE
The units must be level in order to operate properly.
Table 28 Indoor centrifugal condensing unit
Model Net Weight
lb (kg)60 Hz 50 Hz
MC_65A MC_64A 449 (204)
MC_69W MC_68W 282 (128)
Split System Models
49
Figure 23 Detail of ceiling hanging bracket
7.5.2 Ducting
The total external static pressure for the inlet and outlet ducts, including grille, must not exceed
0.5 inches of H2O. Hood intake dimensions should be the same as the condensing unit duct dimen-
sions.
If the condensing unit is located close to the outside of the building, rain hoods must be installed. In
addition, install a triple layer bird screen over rain hood openings to eliminate the possibility of
insects, birds, water, or debris entering the unit.
Use flexible ductwork or nonflammable cloth collars to attach ductwork to the unit and to control
vibration transmission to the building. Attach the ductwork to the unit using the flanges provided.
Locate the unit and ductwork so that the return air does not short circuit to the supply air inlet.
Avoid directing the hot exhaust air toward adjacent doors or windows.
Normal operating sound may be objectionable if the condensing unit is placed directly over quiet work
areas. Ductwork that runs through a conditioned space or is exposed to areas where condensation
may occur must be insulated. Whenever possible, ductwork should be suspended using flexible hang-
ers. Ductwork should not be fastened directly to the building structure. In applications where the ceil-
ing plenum is used as the heat rejection domain, the discharge air must be directed away from the
condensing unit air inlet and a screen must be added to the end of the discharge duct to protect ser-
vice personnel.
For multiple unit installations, space the units so that the hot condensing unit exhaust air is not
directed toward the air inlet of an adjacent unit.
Table 29 Airflow CFM (CMH)
23 & 33 kW
60 Hz 3500 (5947)
50 Hz 3500 (5947)
3/8" threaded rod
(field-supplied)
3/8" hex nut
3/8" washer
Sleeve
Isolator
3/8" fender washer
3/8" hex nut
3/8" hex nut
Nylock Unit base pan (ref)
Split System Models
50
Figure 24 Centrifugal air-cooled condensing unit dimensional data
SL-11087 PG 4
51 13/16 "
1 3/4 "
21 1/4 "
1 5/8 "
48 "
33 5/8 "
54 "
32 "
8 15/16 "
15 3/4 "
3 3/8 "
14 1/2 "
24 "
(812.8mm)
(1371.6mm)
(41.1mm)
(1219.2mm)
(400mm)
(227mm)
CABINET
DIMENSION
CABINET
DIMENSION
(539.8mm)
(44.5mm)
(854.1mm) (1316mm)
(610mm)
(368.3mm)
(85.7mm)
CABINET
DIMENSION
THREADED ROD
CENTERS THREADED ROD
CENTERS
Shaded area indicates a
recommended clearance of
30" (762mm) for component
access and removal.
Hanger Bracket
Customer-supplied
threaded rods for module
support from ceiling
(typ. 4)
1/2" (12.7mm) dia. holes for
threaded rods (typ. 2 each end)
Air
Outlet
Air Inlet
7/8" (22.2mm) & 1 1/8" (28.6mm)
dia. knockouts electrical entrance for high
voltage connection (Single Point Power Kit).
7/8" (22.2mm) & 1 1/8" (28.6mm)
dia. knockouts electrical entrance for high
voltage connection.
Suction Line male quick
conect location.
Liquid Line male quick
connect location
Single Point Power Kit
connection to Evaporator.
7/8" (22.2mm) dia. electrical entrance
for low voltage connection.
7/8" (22.2mm) dia. knockout
electrical entrance for altermate
control panel low voltage routing.
NOTE: Unit is spaced evenly in
reference to threaded
rod centers.
Split System Models
51
Figure 25 Centrifugal air-cooled condensing unit dimensional data (con't.)
DPN000226
Rev. 0
Field-supplied unit disconnect
switch when factory unit
disconnect switch is not supplied.
Electric service
not by Emerson
Optional factory-installed
disconnect switch
Line voltage electric power
supply conduit voltage
Connection terminal
for field supplied earth
grounding wire
Removable access panels
AIR COOLED
Field-supplied 24V NEC
Class 2 wiring
between condensing
unit and fan/coil unit
Low voltage electric power
supply conduit entrance
Heat rejection connection. Field-supplied
24V NEC Class 2 wiring. See Note 2.
Wire connections from evaporator module.
1. 24V GND
2. 24V supply
3. High pressure alarm (optional)
4. Hot gas bypass connection (only on
units with hot gas bypass)
NOTES:
1. Refer to specification sheet for full load amp and wire size amp ratings.
2. Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75’ (23m)
or not to exceed 1 volt drop in control line.
Split System Models
52
Figure 26 Split systems general arrangement
SL-11900 PG 5
Condenser
Coil
1/2" (12.7mm) NPT
Pressure Relief Valve
Sight
Glass
Check Valve
Lee-Temp
Receiver
High Pressure
Switch
Scroll
Compressor
Head Pressure
Control with
Integral Check
Valve
Liquid Line
Solenoid Valve
Suction Line
Male Quick
Connect
Coupling*
Liquid Line
Male Quick
Connect
Coupling*
Suction Line
Female Quick
Connect
Coupling*
Liquid Line
Female Quick
Connect
Coupling*
Filter
Drier
Service
Access
Ports
Sensing
Bulb
Expansion
Valve
External
Equalizer
Evaporator
Coil
High Pressure
Switch
Scroll
Compressor
Suction Line
Male Quick
Connect
Coupling*
Liquid Line
Male Quick
Connect
Coupling*
Suction Line
Female Quick
Connect
Coupling*
Liquid Line
Female Quick
Connect
Coupling*
Filter
Drier
Service
Access
Ports
Sensing
Bulb
External
Equalizer
Evaporator
Coil
Expansion
Valve
Tube in
Tube
Condenser
Water/Glycol
Supply
Line
Water/Glycol
Return
Line
2-Way Water
Regulating
Valve
Fluid Supply
to Unit
Fluid Return
from Unit
Shutoff
Valves*
Hose Bibs*
Tube inTube
Condenser
Fluid
Return
from Unit
Fluid Supply
to Unit 3-Way Water
Regulating Valve (optional)
AIR COOLED
WATER COOLED
GLYCOL COOLED
OPTIONAL PIPING
FACTORY
PIPING
SINGLE CIRCUIT SHOWN
*Components are not supplied by Liebert but
are recommended for proper circuit operation
and maintenance.
Pressure Balancing
Valve
Liquid Injection
Valve Bulb
Liquid Injection
Valve
Hot Gas
Bypass Control
Valve
Hot Gas
Bypass Solenoid
Valve
Receiver Heater
Pressure Limiting
Switch
Liquid Injection
Valve
Liquid Injection
Valve Bulb
Hot Gas Bypass
Control Valve
Hot Gas Bypass
Solenoid Valve
NOTE: Refer to installation manual for
field piping guidelines.
1
1
1
Split System Models
53
7.6 Water and Glycol-Cooled Condensing Units
For installation guidelines, refer to Installing the Indoor Condensing Unit on page 48.
7.6.1 Piping Considerations
It is recommended that manual service shut-off valves be installed at the supply and return line to
each unit. This will provide for routine service or emergency isolation of the unit.
When the water source for the condenser is of poor quality, it is good practice to provide cleanable fil-
ters in the supply line. These filters will trap the particles in the water supply and extend the service
life of the water-cooled condenser.
7.6.2 Condenser Water Requirements
The standard maximum water pressure is 150 psig (1034 kPa). For applications above this pressure,
consult the factory about high pressure systems.
The system will operate in conjunction with a cooling tower, city water, or drycooler.
7.6.3 Regulating Valve Adjustment and Testing
Refer to 4.3.1 - Water Regulating Valve Adjustment and 4.3.3 - Testing Valve Function.
7.6.4 Glycol Systems
For split system glycol systems, use drycooler and pump data found in 5.0 - Glycol/GLYCOOL-
Cooled Models. See Table 16 - Drycooler data.
Electrical control interconnect to drycooler is wired from water/glycol condensing unit.
Table 30 Water and glycol-cooled unit connection sizes
Connection Size and Type
Condenser Water Inlet 1-1/8" OD Cu
Condenser Water Outlet 1-1/8" OD Cu
Suction Line 1-7/16" - 16 male #12 quick connect
Liquid Line 1-1/16" - 12 male #10 quick connect
Table 31 Water and glycol-cooled condensing unit data
Model
Net Weight Glycol Volume
lb kg gal liters
MC_69W
MC_68W 282 128 2.0 7.6
Split System Models
54
Figure 27 Water/glycol-cooled condensing unit dimensions
SL-11087PG 6
32 " 32 "
29 13/16 " 33 5/8 "
24 "
(812.8mm)
(610mm)
(854.1mm)
(757.2mm)
CABINET
DIMENSION
THREADED ROD
CENTERS
(812.8mm)
CABINET
DIMENSION
CABINET
DIMENSION
THREADED ROD
CENTERS
Hanger Bracket
Shaded area indicates a
recommended clearance of
30" (762mm)for component access
and removal.
Removable Access Panel
1/2" (12.7mm) dia. holes for
module rigging (typ. 2 each end).
Customer supplied threaded rods
for module support from ceiling
(typ. 4).
NOTE:Unitisevenlyspacedin reference
to threaded rod centers.
1" (25.4mm) NPT Female Water/Glycol
Outlet Connection
1" (25.4mm) NPT Female Water/Glycol
Inlet Connection
7/8" (22.2mm) dia. knockout electrical entrance
for alternate control panel low voltage routing.
7/8" (22.2mm) dia. electrical entrance
for low voltage connection.
Suction Line male quick
connect location
Liquid Line male quick
connect location
7/8" (22.2mm) & 1 1/8" (28.6mm)
dia. knockouts electrical entrance for
line voltage connection
7/8" (22.2mm) & 1 1/8" (28.6mm)
dia. knockouts electrical entrance for
line voltage connection (Single Point
Power Kit)
7"
33/4 "
87/16 "
(214.4mm)
(95.2mm) (177.8mm)
Split System Models
55
Figure 28 Water/glycol-cooled condensing unit (con't.)
DPN000228_Rev0
Heat rejection connection.
Field-supplied 24V NEC
Class 2 wiring. Wire
connections from evaporator
mod:
1. 24V ground
2. 24V supply
3. High pressure alarm (optional)
4. Hot gas bypass
connection (only on units with
hot gas bypass)
Remote drycooler
connection; field-supplied
24V NEC Class 1 wiring
(glycol-cooled units only)
WATER/GLYCOL Optional factory-installed
disconnect switch
Field-supplied 24V NEC Class1
wiring to fan/coil unit
Field-supplied unit disconnect
switch when factory unit
disconnect switch is not supplied
Field-supplied 24V NEC Class1
wiring to drycooler
(glycol-cooled units only)
Removable
Access
Panel
Connection terminal
for field-supplied
earth grounding wire
Line-voltage electric power
supply conduit entrance
Field-supplied 24V NEC
Class 1 wiring between
glycol condensing unit
and drycooler
Low-voltage electric
power supply conduit entrance
Electric service;
not by Liebert
NOTES
1. Refer to specification sheet for full load amp. and wire size amp. ratings.
2. Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75' (23m)
or not to exceed 1 volt drop in control line.
R407C Refrigerant
56
8.0 R407C REFRIGERANT
Table 32 R407C pressure/temperature chart for operation and superheat (discharge/hot gas and suction
gas)
Temperature Gauge Pressure Temperature Gauge Pressure Temperature Gauge Pressure
°F °C Psig kPa °F °C Psig kPa °F °C Psig kPa
0.0 -17.8 18.9 130 35.0 1.7 54.8 378 70.0 21.1 114.9 792
1.0 -17.2 19.6 135 36.0 2.2 56.1 387 72.0 22.2 119.3 822
2.0 -16.7 20.4 141 37.0 2.8 57.5 396 74.0 23.3 124 853
3.0 -16.1 21.2 146 38.0 3.3 58.9 406 76.0 24.4 128 885
4.0 -15.6 22.0 152 39.0 3.9 60.3 415 78.0 25.6 133 917
5.0 -15.0 22.8 157 40.0 4.4 62.2 429 80.0 26.7 138 950
6.0 -14.4 23.6 163 41.0 5.0 63.1 435 82.0 27.8 143 984
7.0 -13.9 24.5 169 42.0 5.6 64.6 445 84.0 28.9 148 1019
8.0 -13.3 25.4 175 43.0 6.1 66.1 456 86.0 30.0 153 1054
9.0 -12.8 26.2 181 44.0 6.7 67.6 466 88.0 31.1 158 1091
10.0 -12.2 27.1 187 45.0 7.2 69.1 476 90.0 32.2 164 1128
11.0 -11.7 28.0 193 46.0 7.8 70.7 487 92.0 33.3 169 1167
12.0 -11.1 28.9 200 47.0 8.3 72.2 498 94.0 34.4 175 1206
13.0 -10.6 29.9 206 48.0 8.9 73.8 509 96.0 35.6 181 1246
14.0 -10.0 30.8 213 49.0 9.4 75.4 520 98.0 36.7 187 1287
15.0 -9.4 31.8 219 50.0 10.0 77.1 531 100.0 37.8 193 1329
16.0 -8.9 32.8 226 51.0 10.6 78.7 543 102.0 38.9 199 1372
17.0 -8.3 33.8 233 52.0 11.1 80.4 554 104.0 40.0 205 1416
18.0 -7.8 34.8 240 53.0 11.7 82.1 566 106.0 41.1 212 1461
19.0 -7.2 35.8 247 54.0 12.2 83.9 578 108.0 42.2 219 1507
20.0 -6.7 36.9 254 55.0 12.8 85.6 590 110.0 43.3 225 1553
21.0 -6.1 38.0 262 56.0 13.3 87.4 603 112.0 44.4 232 1601
22.0 -5.6 39.0 269 57.0 13.9 89.2 615 114.0 45.6 239 1650
23.0 -5.0 40.1 277 58.0 14.4 91.0 628 116.0 46.7 247 1701
24.0 -4.4 41.3 284 59.0 15.0 92.9 640 118.0 47.8 254 1752
25.0 -3.9 42.4 292 60.0 15.6 94.8 653 120.0 48.9 262 1804
26.0 -3.3 43.6 300 61.0 16.1 96.7 666 122.0 50.0 269 1858
27.0 -2.8 44.7 308 62.0 16.7 98.6 680 124.0 51.1 277 1912
28.0 -2.2 45.9 317 63.0 17.2 100.5 693 126.0 52.2 285 1968
29.0 -1.7 47.1 325 64.0 17.8 102.5 707 128.0 53.3 294 2025
30.0 -1.1 48.4 333 65.0 18.3 104.5 721 130.0 54.4 302 2083
31.0 -0.6 49.6 342 66.0 18.9 106.5 735 132.0 55.6 311 2143
32.0 0.0 50.9 351 67.0 19.4 108.6 749 134.0 56.7 320 2203
33.0 0.6 52.1 359 68.0 20.0 110.7 763 136.0 57.8 329 2265
34.0 1.1 53.5 369 69.0 20.6 112.8 778 138.0 58.9 338 2329
- - - - - - - - 140.0 60.0 347 2393
NOTE
Use this table for superheat and for control adjustment (e.g., pressure switches). See
Table 33 for subcooling.
R407C Refrigerant
57
8.1 Calculating Subcooling
Example
Measure the liquid pressure (e.g., 200 psig). Find the liquid saturation temperature at that pressure
on Table 33 (e.g., 93°F). Measure the temperature of the liquid line (e.g., 90°F). Subtract the actual
temperature from the liquid saturation temperature to obtain the subcooling (e.g., 93 – 90 = 3°F). If
the actual temperature is greater than the liquid saturation temperature, then there is no subcooling,
and the fluid may be a mixture of liquid and vapor.
Why There Are Two R407C Temperature and Pressure Tables
R407C is a blend of refrigerants that exhibits a temperature “glide” of approximately 8 to 12°F
(4 to 7°C. This “glide” is the difference between the liquid and vapor saturation temperatures at a
given pressure. Use the correct table for the saturation temperature you need. Table 32 is for super-
heat or operating controls. Table 33 is for subcooling only.
Table 33 R407C pressure/temperature chart for subcooling only (liquid measurements)
Temperature Pressure Gauge Temperature Pressure Gauge Temperature Pressure Gauge
°F °C Psig kPa °F °C Psig kPa °F °C Psig kPa
36.0 2.2 73 500 59.0 15.0 114 786 94.0 34.4 203 1402
37.0 2.8 74 511 60.0 15.6 116 801 96.0 35.6 209 1444
38.0 3.3 76 522 61.0 16.1 118 815 98.0 36.7 216 1488
39.0 3.9 77 533 62.0 16.7 120 830 100.0 37.8 222 1532
40.0 4.4 79 544 63.0 17.2 123 845 102.0 38.9 229 1578
41.0 5.0 81 556 64.0 17.8 125 860 104.0 40.0 236 1624
42.0 5.6 82 567 65.0 18.3 127 875 106.0 41.1 242 1671
43.0 6.1 84 579 66.0 18.9 129 891 108.0 42.2 249 1720
44.0 6.7 86 591 67.0 19.4 131 906 110.0 43.3 257 1769
45.0 7.2 87 602 68.0 20.0 134 922 112.0 44.4 264 1819
46.0 7.8 89 615 69.0 20.6 136 938 114.0 45.6 271 1870
47.0 8.3 91 627 70.0 21.1 138 954 116.0 46.7 279 1922
48.0 8.9 93 639 72.0 22.2 143 987 118.0 47.8 287 1975
49.0 9.4 95 652 74.0 23.3 148 1021 120.0 48.9 294 2029
50.0 10.0 96 664 76.0 24.4 153 1055 122.0 50.0 302 2085
51.0 10.6 98 677 78.0 25.6 158 1090 124.0 51.1 310 2141
52.0 11.1 100 690 80.0 26.7 163 1126 126.0 52.2 319 2198
53.0 11.7 102 704 82.0 27.8 169 1163 128.0 53.3 327 2256
54.0 12.2 104 717 84.0 28.9 174 1201 130.0 54.4 336 2315
55.0 12.8 106 730 86.0 30.0 180 1239 132.0 55.6 345 2376
56.0 13.3 108 744 88.0 31.1 185 1279 134.0 56.7 354 2437
57.0 13.9 110 758 90.0 32.2 191 1319 136.0 57.8 363 2500
58.0 14.4 112 772 92.0 33.3 197 1360 138.0 58.9 372 2563
--------140.0 60.0 381 2628
NOTE
Use this table for subcooling calculation ONLY. See Table 32 for superheat or control
adjustment.
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical
continuity, ensures network resiliency and adaptability through
a family of technologies—including Liebert power and cooling
technologies—that protect and support business-critical systems.
Liebert solutions employ an adaptive architecture that responds
to changes in criticality, density and capacity. Enterprises benefit
from greater IT system availability, operational flexibility and
reduced capital equipment and operating costs.
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2008 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks
or registered trademarks of their respective owners.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
Liebert.monitoring@emerson.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@emersonnetworkpower.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@emersonnetworkpower.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
EmersonNetworkPower.com
Emerson Network Power.
The global leader in enabling Business-Critical Continuity.
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2008 Emerson Electric Co.
Monitoring
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power Power Switching & Controls
Precision Cooling
Services
Racks & Integrated Cabinets
Outside Plant
Surge Protection
SL-11956_REV0_07-08

Navigation menu