Liebert Upstation Gxt Users Manual User

UPStation GXT to the manual 5f5ddbce-0ffd-42ea-af9f-36fd1b9a2c34

2015-02-09

: Liebert Liebert-Upstation-Gxt-Users-Manual-571431 liebert-upstation-gxt-users-manual-571431 liebert pdf

Open the PDF directly: View PDF PDF.
Page Count: 20

DownloadLiebert Liebert-Upstation-Gxt-Users-Manual- User Manual  Liebert-upstation-gxt-users-manual
Open PDF In BrowserView PDF
POWER PROTECTION

UPStation GXT™ 6kVA Maintenance Bypass
USER MANUAL

Transformerless
with Configurable
Output Distribution

TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Standard Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
BYPASS SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CONFIGURABLE OUTPUT DISTRIBUTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
15 Amp Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20 Amp Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30 Amp Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Other Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5
5
5
5

CABLE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
WIRING PREPARATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
POWER CABLE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

WALL-MOUNT DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
DIAGRAM FOR ATTACHING UNIT TO WALL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

HARDWIRE OUTPUT OPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
OPERATING PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Start-Up and Initialization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ON MAINTENANCE BYPASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ON UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Shutting Down the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ON UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ON MAINTENANCE BYPASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Transferring System From UPS to Maintenance Bypass Operation . . . . . . . . . . . . . . . 12
Transferring System From Maintenance Bypass to UPS Operation . . . . . . . . . . . . . . . 12
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

i

IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE
INSTRUCTIONS

!

This manual contains important instructions that
should be closely followed during installation and
maintenance of this UPStation GXT 6kVA
Maintenance Bypass.

To reduce the risks of fire, connect
only to a circuit provided with
maximum branch circuit
overcurrent protection of 40A in
accordance with applicable
national and local electrical codes.

Install the bypass equipment in a clean
environment, free of conductive contaminants,
moisture, flammable liquids, gases, and corrosive
substances.

This product is designed for commercial / industrial
use only. This product is not intended for use with
life support and other designated “critical” devices.
Maximum load must not exceed that shown on the
Maintenance Bypass Cabinet rating label.

!

CAUTION

WARNING

LETHAL VOLTAGES MAY BE
PRESENT WITHIN THIS UNIT
EVEN WHEN IT IS APPARENTLY
NOT OPERATING. OBSERVE ALL
CAUTIONS AND WARNINGS IN
THIS MANUAL. FAILURE TO DO
SO MAY RESULT IN SERIOUS
INJURY OR DEATH. NEVER
WORK ALONE.

The UPStation GXT 6 kVA Maintenance Bypass is
designed for use on properly grounded (earthed)
208/240VAC 60Hz supply, for installation by
qualified personnel. This UPS equipment is
intended to be installed by a qualified / certified
electrician who must review and approve customer
supplied wiring, circuit breakers, intended loads
and verify correct input, output and grounded
(earth) connections to ensure compliance with
technical standards and national and local
electrical codes. Installation instructions and
warning notices are in the Cable Installation
section of this manual beginning on page 6.

1

GLOSSARY OF SYMBOLS

Risk of electrical shock

Indicates Warning or Caution followed by important instructions

i

Requests the user to consult the manual

Equipment grounding conductor

On

Off

2

GENERAL DESCRIPTION
Congratulations on your purchase of Liebert's
UPStation GXT 6 kVA Maintenance Bypass. As
with every Liebert product, we stand behind our
quality. If you have any questions concerning this
Maintenance Bypass, please feel free to contact
your local sales representative, or call the
appropriate Technical Support number listed on
the back of this manual.

Features

To ensure proper installation and operation of this
unit, please read this manual thoroughly.

Standard Components

•
•
•
•
•

•
•
•
•

While installation must be completed by a
qualified / certified electrician, general operation
may be performed without special training.

Supports up to 30A loads
Compact design
Highly configurable
Multiple power path indicators
High-speed, break-before-make transfer
switch
Provisions for hardwire output
Power indicator lamps
Branch rated circuit breakers
Easily accessible terminal blocks

Options

SYSTEM DESCRIPTION

• Field-installable output distribution kits

The Liebert UPStation GXT 6 kVA Maintenance
Bypass is intended for use with the UPStation GXT
6 kVA UPS. Typical applications include
supporting workstations, servers, network, telecom
or other sensitive electronic equipment.
The UPStation GXT 6 kVA Maintenance Bypass
was designed to provide maximum system
availability to business-critical equipment. The
bypass allows for transfer of connected loads to an
alternate power path, allowing full isolation of the
UPS. After connected loads are switched to
alternate power and the UPS is isolated, the UPS
can be turned off and removed from service with
no interruption of power to connected loads.
The Configurable Output Distribution was
designed to provide maximum flexibility to
business-critical equipment.
Various output receptacle options are available
from 15 A to 30 A. Hardwire options are also
available with a branch rated circuit breaker.
NOTE
The 120V loads need to be balanced on
the UPS output. To do this, when
connecting 120V equipment to the
Maintenance Bypass (MB), start at one
end of the MB and fill in toward the
other end.

3

Maintenance Bypass component layout
UPS input power
present (amber)

Bypass availability
indicator (amber)

UPS input
switch
(SW2)

Bypass
switch
(SW1)

Output
breaker
(CB1)

UPS output
availability
indicator
(green)
1 2

Configurable
Output
Distribution

Hardwire
output
terminal
block
(TB4)

3 4

GND3

GND1

1 2 3 1 2 3 1 2 3 4

GND2
TOP VIEW

Utility
input
TB1

UPS
input
TB2

UPS
output
TB3

INSIDE VIEW— RECEPTACLE
PLATES AND END PLATE REMOVED

4

MAJOR COMPONENTS
20 Amp Options

The following is a general description of each
component and its functions. Please review this
section carefully, as it will give you a better
understanding as to how the UPStation GXT 6 kVA
Maintenance Bypass operates.

5-20R2 (T-Slot)
L5-20R
L6-20R-208
L6-20R-240

BYPASS SWITCH

L14-20R-240

The Bypass Switch allows easy and rapid transfer
of connected loads between the UPS and bypass
source.

20A, 120V, 1 Pole Breaker for 1/2" & 3/4" conduit
20A, 208V, 2 Pole Breaker for 1/2" & 3/4" conduit
20A, 240V, 2 Pole Breaker for 1/2" & 3/4" conduit

CONFIGURABLE OUTPUT DISTRIBUTION

30 Amp Options

Several receptacle and hardwire options are
available as user-selectable output distribution.
These are factory-configured when ordered and
also allow for field upgrades. Common receptacle
and hardwire options include:

L5-30R
L6-30R-208
L6-30R-240
L14-30R-240

15 Amp Options

30A, 120V, 1 Pole Breaker for 1/2" & 3/4" conduit

5-15R2

30A, 208V, 2 Pole Breaker for 1/2" & 3/4" conduit

L5-15R2

30A, 240V, 2 Pole Breaker for 1/2" & 3/4" conduit

6-15R2-208

Other Options

6-15R2-240

Single Position Blanking Plate

L6-15R2-208

Hardwire Options

L6-15R2-240

Single Position Plate with 1/2", 3/4" and 1"
conduit knockouts

15A, 120V, 1 Pole Breaker for 1/2" & 3/4" conduit
15A, 208V, 2 Pole Breaker for 1/2" & 3/4" conduit

Double Position Plate with 1-3/4" and 2"
conduit knockouts

15A, 240V, 2 Pole Breaker for 1/2" & 3/4" conduit

5

CABLE INSTALLATION
WIRING PREPARATION
!

POWER CABLE INSTALLATION
Refer to the chart below when selecting cables:

CAUTION

Power Cable and Protection Ratings

Please read this section
thoroughly before attempting to
install wiring to this unit.
Be sure that the unit is not
connected to any AC mains power
source or UPS before installing
any wiring to this unit. This should
be installed by a qualified/certified
electrician.

Max Input Current
Input Protection
Max Output Current

208V

240V

30 A
40 A
30 A

30 A
40 A
30 A

Max: 16 mm2 (6 AWG)
Terminal Block Details Min: 2.5 mm2 (14 AWG)
Torque: 2 Nm (16 in/lb)

For access to terminal blocks, see diagrams on
page 4.

NOTE
Customer must supply power cables
between Maintenance Bypass and UPS,
utility and load. (GMB12 models are
supplied with an attached input power
cord complete with L14-30 plug.)

NOTE
The 120V loads need to be balanced on
the UPS output. To do this, when
connecting 120V equipment to the
Maintenance Bypass, start at one end of
the output modules and fill in toward the
other end. Load balancing must be
performed with the UPStation
GXT6000T - 208X and 240X. It is not
required on the GXT6000T-208 because
the unit has no 120V output.

6

Connecting Maintenance Bypass to UPStation GXT6000T - 208
208
VAC

1

GND3

Output
TB4

2

3

4

MAINTENANCE BYPASS
NOTE
When using the Maintenance
Bypass with an UPStation
GXT6000T-208, a jumper
(included with the accessory
kit) must be connected to the
TB3 (UPS output) terminal
block on the Maintenance
Bypass between TB3-1 and
TB3-2, as shown.

GND1

Utility
TB1

GND2

1
Utility
input

2

UPS input
TB2

3

1

2

3

UPS output
TB3

1

2

3

4

L1
L2

NOTE
GMB12 models are supplied
with an attached input power
cord complete with L14-30
plug.

L1

L2

L1

Input

L2

Output
GXT6000T - 208

7

+

-

Ext. battery

Connecting Maintenance Bypass to UPStation GXT6000T - 208X
120V
208V
120V
Output TB4
1

2

3

4

GND3
MAINTENANCE BYPASS

GND1

Utility
TB1

GND2

1

2

UPS input
TB2

3

1

2

3

UPSoutput
TB3

1

2

3

4

Utility L2
input
L1
N
GEC
NOTE
GMB12 models are supplied
with an attached input power
cord complete with L14-30 plug.

L1

L2

N

L1

Input

L2
Output

GXT6000T - 208X

8

L2A

+

-

Ext. battery

Connecting Maintenance Bypass to UPStation GXT6000T - 240X
120V
240V

120V

Output TB4
1

2

3

4

GND3
MAINTENANCE BYPASS

GND1

Utility
TB1

GND2

1

2

UPS input
TB2

3

1

2

3

UPSoutput
TB3

1

2

3

4

Utility L2
input
L1
N
GEC

NOTE
GMB12 models are supplied
with an attached input power
cord complete with L14-30 plug.

L1

L2

Input

N

L1

L2

Output
GXT6000T - 240X

9

+
Ext. battery

-

WALL-MOUNT DIAGRAM
DIAGRAM FOR ATTACHING UNIT TO WALL
Use the following diagram, which shows the location and measurements of factory-cut mounting slots,
when preparing to attach the GXT Maintenance Bypass to a wall. Liebert recommends using 1/4-20
mounting screws. Rubber pads are supplied for placing the Maintenance Bypass on the floor.
178mm
7.00"

514mm
20.25"

C
L
10

HARDWIRE OUTPUT OPTION
6. Connect the remaining wires in accordance
with the wiring diagram (located inside the
base enclosure).

This product is intended to be installed by a
qualified electrician only.
1. COMPLETELY REMOVE ALL POWER FROM
THE FRAME. If the Maintenance Bypass is
connected to the UPS, disconnect external
battery supply.
2. Remove the end cover plate to access the
terminal block (see Accessing terminal
block below).
3. Without disconnecting from the terminal block,
unscrew and pull out the hardwire plate(s).
4. Route all wires from the hardwire plate(s) to
the terminal block.
5. Connect the GROUND wire to the grounding
bar strip (GND1).

NOTE
When wiring 120 V loads, LINE must be
alternated between TB4-1 and TB4-3 to
balance the 120V load. Connect all
neutral wires to TB4-4.
7. Replace the receptacle plates and the end
cover plate, using care to not damage the
wires.

Accessing terminal block

11

OPERATING PROCEDURES
START-UP AND INITIALIZATION

TRANSFERRING SYSTEM FROM
UPS TO MAINTENANCE BYPASS
OPERATION

Follow these steps in order to start up the
GXT 6kVA UPS while connected to the
Maintenance Bypass.

1. On UPS verify that Bypass LED is lit, if not,
press UPS OFF/Bypass button for at least
one second.
2. On Maintenance Bypass verify that the
Bypass lamp is illuminated.
3. Rotate Bypass switch SW1 to the Bypass
position.
4. Set UPS Input switch SW2 to the Off position
(position O). This will remove power from UPS
input.

ON MAINTENANCE BYPASS
1. Set the Maintenance Bypass switch (SW1) to
UPS position.
2. Close (position I) UPS Input switch (SW2).
3. Close (position I) Output Circuit breaker
(CB1).

ON UPS
1.
2.
3.
4.

Close (position I) battery circuit breaker.
Close (position I) input circuit breaker.
Close (position I) output circuit breaker.
After the start-up sequence the UPS will
automatically default to its internal bypass.
The bypass LED will be lit.
5. Press UPS On/Alarm/Battery Test button for at
least one second to turn the UPS on. The
UPS ON LED will be lit.
6. Connected equipment may now be switched
on.

!

CAUTION

The connected load is now
powered by the bypass source and
is not protected.

TRANSFERRING SYSTEM FROM
MAINTENANCE BYPASS TO UPS
OPERATION
1. On Maintenance Bypass close (position I)
UPS Input switch (SW2).
2. On UPS close (position I) input, output and
battery circuit breakers.
3. After the start-up sequence the UPS will
automatically default to its internal bypass.
The bypass LED will be lit.
4. Press UPS ON/Alarm/Battery Test button for
at least one second to turn the UPS on. The
UPS ON LED will be lit.
5. On Maintenance Bypass verify that UPS
Output LED is illuminated.
6. Rotate Bypass switch SW1 to the UPS
position.

SHUTTING DOWN THE UPS
Use the following procedure to power down the
system.

ON UPS
1. Press Output OFF/Bypass button for at least
1 second, twice, within 4 seconds.
2. Open (position O) UPS output, input and
battery circuit breakers.

ON MAINTENANCE BYPASS
1. Open (position O) output breaker (CB1).
2. Open (position O) UPS input switch (SW2).

12

SPECIFICATIONS
Typical Transfer Time
(to or from maintenance bypass)

< 6 milliseconds

Input Voltage

Nominal 208VAC or 240VAC

Total Current

30A max.

Operating Ambient Temperature

0° to +40° C

Storage Ambient Temperature

-20° to +60° C

Dimensions, W x D x H, in (mm)

8.2 x 21.0 x 6.2 (209 x 534 x 158)

Chassis Weight (no receptacles)

10 lbs.

Distribution Module Weights (each)

2 lbs.

Connections to UPS

Hardwire Terminal Blocks

Humidity

0 to 95%, non-condensing

Agency/Standards

UL 1778, c-UL

13

POWER PROTECTION

UPStation GXT 6kVA Maintenance Bypass
USER MANUAL
The Company Behind the Products
With over a million installations around the globe,
Liebert is the world leader in computer protection
systems. Since its founding in 1965, Liebert has
developed a complete range of support and
protection systems for sensitive electronics:
•
•
•

•
•

Environmental systems—close-control air
conditioning from 1 to 60 tons
Power conditioning and UPS with power
ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both
environmental and power protection in a
single, flexible package
Monitoring and control—from systems of any
size or location, on-site or remote
Service and support through more than 100
service centers around the world and a 24/7
Customer Response Center

While every precaution has been taken to ensure
the accuracy and completeness of this literature,
Liebert Corporation assumes no responsibility and
disclaims all liability for damages resulting from
use of this information or for any errors or
omissions.
© 2002 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to change without notice.
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.

SL-23447 (8/02) Rev. 2

Technical Support/Service
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@liebert.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@liebert.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@liebert.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246

Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
Fax: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
Fax: +852 2 831 0114



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Subject                         : Nfinity Maintenance Bypass Cabinet
Modify Date                     : 2002:08:06 20:09:53-04:00
Create Date                     : 2002:08:06 19:49:32Z
Page Count                      : 20
Creation Date                   : 2002:08:06 19:49:32Z
Mod Date                        : 2002:08:06 20:09:53-04:00
Producer                        : Acrobat Distiller 5.0.5 (Windows)
Author                          : Mike Barber
Metadata Date                   : 2002:08:06 20:09:53-04:00
Creator                         : Mike Barber
Title                           : User Manual
Description                     : Nfinity Maintenance Bypass Cabinet
Page Mode                       : UseOutlines
EXIF Metadata provided by EXIF.tools

Navigation menu