Extinguishing Control Panel
BC06-1EXT, BC06-2EXT
• For application in single-zone
extinguishing systems
• 4 detector zones in conventional
technology
• Differentiation between the activation
of automatic detectors and manual
call points on the same detector line
• Clear display and operation on the
panel front
• Tested to EN 54-2, -4, EN 12094-1 by
VdS

Fire is a permanent threat to life and property. Therefore, immediate response to a fire is imperative. The
main objective of the Fire Detection Control Panel
Series BC06 is to alarm and to react in time and, consequently, save lives and protect property. For decades
LST have focused their aims to undertaking unrivaled
efforts in order to realise new innovations in the security
area. Research, development and production are loca-

ted within LST premises, thus guaranteeing flexible and
reliable individual solutions.
Using a powerful processor system and a large number
of integrated functions, the Fire/Extinguishing Control
Panels Series BC06 ensure topmost efficiency and
speed – prerequisites for saving lives and minimising
damage to property.

Description
Already in the basic version the combined Fire/Extinguishing Control Panels BC06-1EXT and BC06-2EXT are
equipped with four detector lines and the Extinguishing
Board EXB1-1 and, owing to its sophisticated factory
settings, are immediately ready for operation. This allows for quick and efficient application of the product.
The conventional technology allows for the connection
of automatic and non-automatic fire detectors as well
as a wide range of special detectors with contact output. Alarms from manual call points and from automatic
detectors that are connected together to one detector
line can be differentiated and thus evaluated differently
by the fire/extinguishing control panel, by means of an
optional coding module.

The optional evacuation function serves for the actuation of alarming devices independent from activated
alarms.
Thanks to the integrated extinguishing module, the
BC06 can be used as an extinguishing control panel
according to EN 12094-1 with one flooding zone. The
module provides appropriate inputs and outputs for controlling and monitoring a flooding zone. The display and
operating elements that are necessary for the status
indication and the operation of the extinguishing module
are integrated into the keypad.
A printer for the event log can be connected via the
optional Serial Interface Modul SIM06-1.

The Fire/Extinguishing Control Panel BC06-2EXT difThanks to the two auxiliary inputs whose parameters fers from the BC06-1EXT by the additionally integrated
can be freely set as well as the eight open-collector out- 4-digit electronic alarm counter.
puts, manifold tasks in the field of fire alarm technology
can be realised.

Building Safety. Building Security.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

0786–CPD–20300

A

BC06EXT_DBL_LST_EN_0826.PDF • PAGE 1

Clear concept
The combined Fire/Extinguishing Control Panels • All events that occur can be output in English via a
connected printer or PC. Thus, all system conditions
BC06-1EXT and BC06-2EXT have been designed for
and user operations that occurred are documented in
use in small fire detection and extinguishing control sysa clearly laid out way.
tems with one flooding zone, and already in the basic
• The Fire/Extinguishing Control Panel BC06-2EXT inversion they provide the following features:
cludes a 4-digit, non-resettable alarm counter which
• 4 conventional detector lines permit the connection
indicates the total number of alarms by means of an
of automatic detectors and manual call points in conLC display in the operating field.
ventional technology as well as special detectors with • A possible breakdown of the central processing board
contact output. Each detector line can be individually
is securely detected and displayed by the system.
parameterised as detector zone for fire alarms, as • The processor-monitored power supply ensures perdetector zone for fault messages or as input for a
manent supervision and charging of the batteries.
disable device or a flooding switch.
This way, even during a power failure the untroubled
• If automatic detectors and manual call points are conand uninterrupted operation (for more than 72 hours
nected together on one detector line, their activatidepending on the design of the batteries) is guaranons can be differentiated and evaluated differently by
teed.
the control panel. To this aim, the manual call points • Three hierarchised authorization levels for operation
must be equipped with a special coding module.
and parameterisation provide a high degree of secu• Two individually monitored, separately actuated siren
rity against unauthorized access.
outputs with an output current of 1A and 0.5A respec- • The control panel is easily operated and the parametively, allow for the connection of acoustic or optical
ters are set via the display and operating field. LEDs
signalling devices.
indicate the current menu and the selected parame• Dry relay outputs indicate the alarm and fault condititer. This facilitates user guidance during commissioons of the control panel. In addition, 8 open-collector
ning, operation and maintenance.
outputs whose parameters can be freely set as well • The initial commissioning of the control panel is sigas two auxiliary inputs are available for general contnificantly facilitated by the practical factory settings.
rol tasks.
This guarantees easy and time-saving commissio• The Extinguishing Board EXB1-1, which is already inning.
stalled in the control panel, allows for the actuation
of an extinguishing system according to EN 12094-1 The extremely flat wall-mount cabinet allows for an easy
with one flooding zone. In the course of commissio- mounting in virtually any place of the building. Thanks to
ning the control panel, the required functions and de- its modern, ageless design, architectural requirements
lay times are parameterised according to the used and demands of the respective regulations are ideally
extinguishing agent as well as the country specific combined. Thanks to the compact design, the standard
case can accommodate batteries with up to 7Ah also
regulations.
The extinguishing board provides 8 further open-coll- in the event of full extension (central processing board,
extinguishing board and an auxiliary module) of the conector outputs with fixed preset functions.
• Logical combinations of detector zones for the ac- trol panel. Series BC06 thus stands for modularity and
tivation of external alarming devices and for the ac- easy expansion.
tuation of the extinguishing system allow for a high
degree of flexibility. Thus, no additional expenses This product complies with all relevant standards of
arise for external relays or logic gates. Thanks to the EN 54 and EN 12094-1 and is tested by the VdS. LST‘s
wide range of parameterisation possibilities, individu- high quality level is secured by a permanently monitored
al requirements even under the most difficult ambient quality management system certified to ISO 9001.
conditions can be combined into a reasonable fire
protection strategy.

Building Safety. Building Security.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

A
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 2

Extinguishing control
By means of the Extinguishing Board EXB1-1, the
ents of the extinguishing system
Fire/Extinguishing Control Panels BC06-1EXT and • A disable device for the indication of the mechanical
BC06-2EXT provide numerous inputs and outputs with
blocking of the extinguishing agent‘s network
fixed or parameterisable function. With that, the follo- • A flooding switch that indicates the flow of the extinwing components of an extinguishing system can be acguishing agent
tuated and monitored in accordance with EN 12094-1: • A device for switching to the manual mode – for example, a key switch
• Activation devices for the manual activation of the • Signalling devices for indicating the activated conditiflooding process
on and the released condition
• Emergency hold devices for the manual delay of the • The control device for activating the flooding – for
flooding process
example, a solenoid valve
• Emergency abort devices for aborting the flooding • Auxiliary outputs for actuating flaps or for turning off
process
devices and systems
• Fault detection devices for monitoring the compon-

Display and operating elements
The operating field of the Fire/Extinguishing Control Panels BC06-1EXT and BC06-2EXT provides 13 LEDs for The buttons on the operating field have the following
displaying the operating conditions and 4 buttons for functions:
the operation of the extinguishing system.
• Disable/enable the extinguishing module
• Start/terminate the manual mode
The LEDs indicate the following operating conditions:
• Disable/enable the activation devices
• Pre-activation/activation of the extinguishing module • Disable/enable the signal output
• Released condition of the extinguishing output
• Extinguishing output fault
• Extinguishing module fault/disablement
• Extinguishing medium fault/fault of the fault input
• Emergency hold/emergency hold device fault
• Activation device fault/disablement
• Signal output activated/signal output faulty/disabled
• Manual mode of the extinguishing module
• Fault of the activated condition output

Building Safety. Building Security.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

A

BC06EXT_DBL_LST_EN_0826.PDF • PAGE 3

Functions of EN 12094-1
All mandatory functions of EN 12094-1 are integrated
into the Fire/Extinguishing Control Panels BC06-1EXT
and BC06-2EXT. Furthermore, the most important optional functions of this standard are supported:
• Parameterisable pre-discharge-warning time for the
delay of the activation
• Detector zone „extinguishing medium active“ selectable for detecting the flow of the extinguishing
medium
• Monitoring of components of the extinguishing system
• Input for connection of an emergency hold device

•
•
•
•

Monitoring of a disable device
Parameterisable flooding time
Possibility to switch to the „manual only mode“
Transmission of the triggering signal to further actuations within the extinguishing system – for example,
warning devices
• Transmission of the triggering signal to further actuations outside the extinguishing system – for example,
for turning off the air conditioning system
• Emergency abort device can be connected
• Activation of alarming devices with different alarm
signals

Specifications
Mains voltage

230VAC +10/-20%, 47...63Hz

Output/nominal voltage

typ. 27.6VDC

Output current

max. 2.2A

Output current siren outputs
output 1
max. 1A
output 2
max. 0.5A
(the sum of the currents of the signalling devices that are connected to the two outputs must not exceed 1A!)
Output current, extinguishing output

max. 1A

Output current, activated condition output/signal output

max. 500mA per output

Own current consumption (incl. extinguishing board) at 24V

typ. 80mA (without optional componentries, line termination 5.6kΩ)
typ. 65mA (without optional componentries, line termination 47µF)

Line voltage

typ. 20V (line termination 5.6kΩ)
typ. 23V (line termination 47µF)

Line current without fire detectors

typ. 3.7mA (line termination 5.6kΩ)
typ. 0mA (line termination 47µF)

Line termination

5.6kΩ or 47µF

Line resistance

max. 50Ω per core

Ambient temperature

-5°C to +50°C

Relative humidity

max. 95% (no condensation)

Dimensions W × H × D

330 × 330 × 90 (mm)

Colour

grey-white, RAL 9002

Weight without batteries

approx. 3kg

Approvals

0786-CPD-20300
VdS pending

Fire Detection Control Panel BC06-1EXT
Order number

210223

Order name

Fire Detection Control Panel BC06-1EXT/INT1

Fire Detection Control Panel BC06-2EXT
Order number

210224

Order name

Fire Detection Control Panel BC06-2EXT/INT1

Building Safety. Building Security.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

A
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 4



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Encryption                      : Standard V1.2 (40-bit)
User Access                     : Print, Copy, Annotate, Fill forms, Extract, Assemble, Print high-res
Page Count                      : 4
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:adffbea9-6505-43c0-8be1-753d7a3e52a0
Create Date                     : 2008:06:27 11:11:38Z
Modify Date                     : 2008:06:27 11:15:43+02:00
Metadata Date                   : 2008:06:27 11:15:43+02:00
Creator Tool                    : Adobe InDesign CS (3.0)
Version ID                      : 1
Rendition Class                 : proof:pdf
Derived From Instance ID        : 2f6e0b16-42c2-11dd-a6c2-b18684546ca3
Derived From Document ID        : adobe:docid:indd:2d87b49f-391c-11dd-aeb7-99314d0b321c
Derived From Version ID         : 1
Document ID                     : adobe:docid:indd:0cb15da3-4429-11dd-9b01-9678118a5f1f
Marked                          : True
Format                          : application/pdf
Title                           : Datenblätter LST
Rights                          : (c) LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH
Trapped                         : False
Creator                         : Adobe InDesign CS (3.0)
Producer                        : Adobe PDF Library 6.0
EXIF Metadata provided by EXIF.tools

Navigation menu