Omron Sysmac Cj1W Eip21 Users Manual CS And CJ Series .CS1W (100Base TX) .CJ1W .CJ2H CPU6_ EIP .CJ2M CPU3_ TX/1
CJ2M-CPU3@ to the manual 96fea41f-c557-4a36-922a-fbeb65ac0a13
2015-01-24
: Omron Omron-Sysmac-Cj1W-Eip21-Users-Manual-332556 omron-sysmac-cj1w-eip21-users-manual-332556 omron pdf
Open the PDF directly: View PDF .
Page Count: 464
Download | |
Open PDF In Browser | View PDF |
Cat. No. W465-E1-05 SYSMAC CS and CJ Series CS1W-EIP21 (100Base-TX) CJ1W-EIP21 (100Base-TX) CJ2H-CPU6@-EIP (100Base-TX) CJ2M-CPU3@ (100Base-TX/10Base-T) EtherNet/IP Units OPERATION MANUAL CS1W-EIP21 (100Base-TX) CJ1W-EIP21 (100Base-TX) CJ2H-CPU6@-EIP (100Base-TX) CJ2M-CPU3@ (100Base-TX/10Base-T) EtherNet/IP Units Operation Manual Revised February 2010 iv Notice: OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual. The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property. !DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Additionally, there may be severe property damage. !WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Additionally, there may be severe property damage. !Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage. OMRON Product References All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product. The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense. The abbreviation “PLC” means Programmable Controller. “PC” is used, however, in some Programming Device displays to mean Programmable Controller. Visual Aids The following headings appear in the left column of the manual to help you locate different types of information. Note Indicates information of particular interest for efficient and convenient operation of the product. 1,2,3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc. Trademarks and Copyrights EtherNet/IP is a registered trademark of the ODVA (Open DeviceNet Vendor Association). Ethernet is a trademark of the Xerox Corporation. Microsoft, Windows, Windows NT, Windows 2000, Windows XP, and Windows Vista are registered trademarks of the Microsoft Corporation. Other names of systems or products that appear in this document are trademarks or registered trademarks of the respective company. OMRON, 2007 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication. v vi TABLE OF CONTENTS PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxi 1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxii 2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxii 3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxii 4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxiv 5 Application Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxiv 6 Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxvi SECTION 1 Overview of EtherNet/IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1-1 EtherNet/IP Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1-2 Devices Required for Constructing a Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1-3 Support Software Required to Construct a Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1-4 Communications Services Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1-5 Network Configurator Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 SECTION 2 Unit Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 2-1 EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications . . . . . . . . . . . . . . . . . . . . . . 14 2-2 Nomenclature and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 2-3 Selecting the Network Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 SECTION 3 Installation and Initial Setup . . . . . . . . . . . . . . . . . . . . . . . . . 33 3-1 Overview of Initial Setup Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 3-2 Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 3-3 Mounting to a PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 3-4 Network Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 3-5 Connecting to the Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 3-6 Creating I/O Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 3-7 Setting the Local IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 3-8 TCP/IP and Link Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 3-9 Tag Data Link Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 3-10 Other Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 3-11 Communications Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 vii TABLE OF CONTENTS SECTION 4 Memory Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 4-1 Overview of Memory Allocated to the EtherNet/IP Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 4-2 CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 4-3 DM Area Allocations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 4-4 User Settings Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 4-5 Auxiliary Area Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 SECTION 5 Determining IP Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 5-1 IP Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 5-2 IP Addresses in FINS Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 5-3 Private and Global Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 SECTION 6 Tag Data Link Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 6-1 Overview of Tag Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 6-2 Setting Tag Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 6-3 Ladder Programming with Tag Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183 SECTION 7 Message Communications Functions . . . . . . . . . . . . . . . . . . 187 7-1 7-2 7-3 7-4 7-5 7-6 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FINS Message Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Explicit Message Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Message Communications Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Message Communications Error Indications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Message Communications Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188 190 192 193 194 195 SECTION 8 FINS Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197 8-1 8-2 8-3 8-4 8-5 8-6 8-7 Overview of FINS Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FINS/UDP Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FINS/TCP Method. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Routing Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using FINS Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communicating between OMRON PLCs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Precautions on High Traffic in FINS Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198 200 202 207 211 220 232 SECTION 9 Message Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . 233 viii 9-1 Sending Explicit Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234 9-2 Receiving Explicit Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248 TABLE OF CONTENTS SECTION 10 Communications Performance and Communications Load 261 10-1 Communications System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262 10-2 Adjusting the Communications Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268 10-3 I/O Response Time in Tag Data Links. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283 10-4 Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports . . . . . . . . . . . . . . . . . . . . 291 10-5 Message Service Transmission Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294 SECTION 11 FTP Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301 11-1 Overview and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302 11-2 FTP Server Function Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303 11-3 Using the FTP Server Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305 11-4 FTP Server Application Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307 11-5 Using FTP Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308 11-6 Checking FTP Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314 11-7 Using File Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315 11-8 FTP File Transfer Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 11-9 Host Computer Application Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321 SECTION 12 Automatic Clock Adjustment Function . . . . . . . . . . . . . . . . 323 12-1 Automatic Clock Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 324 12-2 Using the Automatic Clock Adjustment Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325 12-3 Automatic Clock Adjustment Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328 12-4 Automatic Clock Adjustment Error Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328 SECTION 13 Maintenance and Unit Replacement . . . . . . . . . . . . . . . . . . . 331 13-1 Maintenance and Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332 13-2 Simple Backup Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333 13-3 Using the Backup Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 SECTION 14 Troubleshooting and Error Processing. . . . . . . . . . . . . . . . . 339 14-1 Checking Status with the Network Configurator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340 14-2 Using the LED Indicators and Display for Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . 347 14-3 Connection Status Codes and Error Processing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358 14-4 Error Log Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 14-5 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368 14-6 Troubleshooting with FINS Response Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 371 ix TABLE OF CONTENTS Appendices A CS/CJ-series Ethernet Unit Function Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 B Ethernet Network Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 377 C TCP Status Transitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379 D CIP Message Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381 E FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports . . . . . . . . 391 F EDS File Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419 G Precautions for Using Windows XP, Vista, or Windows 7 . . . . . . . . . . . . . . . . . . . . . . . . . . 423 Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 427 Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435 x About this Manual: This manual describes the operation of the CS/CJ-series EtherNet/IP Units and the built-in EtherNet/IP ports on a CJ2 CPU Unit for constructing applications and includes the sections described below. Please read this manual carefully and be sure you understand the information provided before attempting to install or operate the EtherNet/IP Unit or built-in EtherNet/IP port. Be sure to read the precautions provided in the following section. Precautions provides general precautions for using the CS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports. Section 1 introduces the functions and protocols used in EtherNet/IP Unit or built-in EtherNet/IP port communications services. Section 2 provides the specifications of EtherNet/IP Units and introduces recommended network configuration devices. Section 3 explains how to install and make the initial settings required for operation of the EtherNet/IP Unit or built-in EtherNet/IP port. Section 4 describes the words allocated in the CIO Area and the DM Area for EtherNet/IP Units or built-in EtherNet/IP ports. Section 5 explains how to manage and use IP addresses. Section 6 describes tag data link functions and related Network Configurator operations. Section 7 describes message communications using FINS messages and explicit messages. Section 8 provides information on communicating on EtherNet/IP Systems and interconnected networks using FINS commands. The information provided in the section deals only with FINS communications in reference to EtherNet/IP Units or built-in EtherNet/IP ports. Section 9 describes message communications using FINS commands sent from the ladder program in the CPU Unit of the PLC. Section 10 describes the communications performance in an EtherNet/IP network, and shows how to estimate the I/O response times and transmission delays. Section 11 describes the functions provided by the FTP server. Section 12 provides an overview of the automatic clock adjustment function, including details on specifications, required settings, operations from CX-Programmer, and troubleshooting. Section 13 describes cleaning, inspection, and Unit replacement procedures, as well as the Simple Backup Function. Section 14 describes error processing, periodic maintenance operations, and troubleshooting procedures needed to keep the EtherNet/IP network operating properly. We recommend reading through the error processing procedures before operation so that operating errors can be identified and corrected more quickly. Appendices provide information on EtherNet/IP network parameters, the buffer configuration, TCP status transitions, ASCII characters, maintenance, and inspections. xi Relevant Manuals The following table lists CS- and CJ-series manuals that contain information relevant to EtherNet/IP Units or built-in EtherNet/IP ports. Manual number W465 Model CS1W-EIP21 CJ1W-EIP21 CJ2H-CPU6@-EIP CJ2M-CPU3@ W420 CS1W-ETN21 CJ1W-ETN21 W421 CS1W-ETN21 CJ1W-ETN21 W343 CS1W-ETN01 CS1W-ETN11 CJ1W-ETN11 CS1G/H-CPU@@H CS1G/H-CPU@@-V1 CS1W-SCU@@-V1 CS1W-SCB@@-V1 CJ2H-CPU6@-EIP CJ2H-CPU6@ CJ2M-CPU@@ CJ1G/H-CPU@@H CJ1G-CPU@@ CJ1M-CPU@@ CJ1W-SCU@@-V1 CP1E-E@@D@-@ CP1E-N@@D@-@ CP1H-X@@@@-@ CP1H-Y@@@@-@@ CJ2H-CPU6@-EIP CJ2H-CPU6@ CJ2M-CPU@@ W342 W472 W473 xii CJ2H-CPU6@-EIP CJ2H-CPU6@ CJ2M-CPU@@ Name Contents EtherNet/IP Units Operation Manual (this manual) Provides information on operating and installing EtherNet/IP Units, including details on basic settings, tag data links, and FINS communications. Refer to the Communications Commands Reference Manual (W342) for details on FINS commands that can be sent to CS-series and CJ-series CPU Units when using the FINS communications service. Refer to the Ethernet Units Operation Manual Construction of Applications (W421) for details on constructing host applications that use FINS communications. Ethernet Units Oper- Provides information on operating and installing ation Manual 100Base-TX Ethernet Units, including details on basic Construction of Net- settings and FINS communications. Refer to the Commuworks nications Commands Reference Manual (W342) for details on FINS commands that can be sent to CS-series and CJ-series CPU Units when using the FINS communications service. Ethernet Units Oper- Provides information on constructing host applications for ation Manual 100Base-TX Ethernet Units, including functions for sendConstruction of ing/receiving mail, socket service, automatic clock adjustApplications ment, FTP server functions, and FINS communications. Ethernet Units Oper- Describes the installation and operation of the 10Base-5 ation Manual and 10Base-T Ethernet Units. Communications Commands Reference Manual CJ-series CJ2 CPU Unit Hardware User’s Manual Describes the C-series (Host Link) and FINS communications commands used when sending communications commands to CS-series, CJ-series, CP-series, and SYSMAC One NSJ-series CPU Units. Provides hardware information for the CJ2 CPU Units. Information is included on features, system configuration, component names, component functions, installation, setting procedures, and troubleshooting. Use together with the CJ-series CJ2 CPU Unit Software User’s Manual (W473). CJ-series CJ2 CPU Provides software information for the CJ2 CPU Units. Unit Software User’s Information is included on CPU Unit operation, internal Manual memory, programming, setting procedures, and CPU Unit functions. Use together with the CJ-series CJ2 CPU Unit Hardware User’s Manual (W472). Manual number W474 W339 Model CJ2H-CPU6@-EIP CJ2H-CPU6@ CJ2M-CPU@@ CS1G/H-CPU-@@H CS1G/H-CPU-@@-V1 CJ1G/H-CPU@@H CJ1M-CPU@@ CJ1G-CPU@@ NSJ@-@@@@(B)-G5D NSJ@-@@@@(B)-M3D CS1G/H-CPU@@H CS1G/H-CPU-@@V1 W393 CJ1G/H-CPU@@H CJ1G-CPU@@ W394 CS1G/H-CPU@@H CS1G/H-CPU-@@V1 CJ1G/H-CPU@@H CJ1G-CPU@@ NSJ@-@@@@(B)-G5D NSJ@-@@@@(B)-M3D W340 CS1G/H-CPU@@H CS1G/H-CPU-@@V1 CJ1G/H-CPU@@H CJ1G-CPU@@ NSJ@-@@@@(B)-G5D NSJ@-@@@@(B)-M3D CXONE-AL@@C-V4 CXONE-AL@@D-V4 W463 W446 WS02-CXPC@-V9 W464 CXONE-AL@@C-V4/ CXONE-AL@@D-V4 Name Programmable Controllers Instructions Reference Manual Contents Describes the ladder diagram programming instructions supported by CS-series and CJ-series PCs. Use this manual for CJ2 CPU Units. Provides an outline of, and describes the design, installation, maintenance, and other basic operations for the CSseries PLCs. Information is also included on features, system configuration, wiring, I/O memory allocations, and troubleshooting. Use together with the Programmable Controllers Programming Manual (W394). Programmable Con- Provides an outline of, and describes the design, installation, maintenance, and other basic operations for the CJtrollers Operation series PLCs. Information is also included on features, Manual system configuration, wiring, I/O memory allocations, and troubleshooting. Use together with the Programmable Controllers Programming Manual (W394). Programmable Con- Describes programming, tasks, file memory, and other functions for the CS-series, CJ-series, and NS-J-series trollers ProgramPLCs. ming Manual Use together with the Programmable Controllers Operation Manual (W339 for CS-series PLCs and W393 for CJseries PLCs). Programmable Con- Describes the ladder diagram programming instructions trollers Instructions supported by CS-series and CJ-series PCs. Use together Reference Manual with the Programmable Controllers Operation Manual (W339 for CS-series PLCs and W393 for CJ-series PLCs), and the Programmable Controllers Programming Manual (W394). CS-One Setup Man- Describes the setup procedures for the CX-One. Informaual tion is also provided on the operating environment for the CX-One. CX-Programmer Provides information on how to use the CX-Programmer, Operation Manual a Windows-based programming device. Use together with the Programmable Controllers Operation Manual (W339 for CS-series PLCs and W393 for CJ-series PLCs), Programmable Controllers Programming Manual (W394) and the Programmable Controllers Instructions Reference Manual (W340) to perform programming. CS/CJ/CP/NSJDescribes the operating procedures of the CX-Integrator series CX-Integrator that can be used to set up and monitor networks. Ver. 2.@ Operation Manual Programmable Controllers Operation Manual !WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given. xiii xiv Read and Understand this Manual Please read and understand this manual before using the product. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NONINFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. xv Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: • Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this manual. • Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. • Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. PROGRAMMABLE PRODUCTS OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof. xvi Disclaimers CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. PERFORMANCE DATA Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. ERRORS AND OMISSIONS The information in this manual has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions. xvii xviii Unit Versions of CS/CJ-series Unit Versions A “unit version” has been introduced to manage Units in the CS/CJ Series according to differences in functionality accompanying Unit upgrades. Notation of Unit Versions on Products The unit version is given to the right of the lot number on the nameplate of the products for which unit versions are being managed, as shown below. ■ CS1W-EIP21/CJ1W-EIP21 Product nameplate CS1WUNIT Unit version Example for unit version 1.0 Lot No. Lot No. 040401 0000 OMRON Corporation Ver.1.0 MADE IN JAPAN ■ CJ2H-CPU@@-EIP/CJ2M-CPU3@ Product nameplate CJ2HUNIT Indicates that the unit version of the CPU Unit is 1.0. Lot No. 080701 CPU Ver. 1.0 EIP Ver.2.0 OMRON Corporation Indicates that the unit version of the built-in EtherNet I/P port is 2.0. MADE IN JAPAN In this manual, the version of the EtherNet/IP port built into the CJ2HCPU@@-EIP/CJ2M-CPU3@ CPU Unit is given as the unit version. Confirming Unit Versions with Support Software CX-Programmer version 4.0 can be used to confirm the unit version using the Unit Manufacturing Information. Note The unit versions of Pre-Ver.1.0 Units cannot be confirmed in Unit Manufacturing Information. The following dialog box is displayed. In the IO Table Window, right-click and select Unit Manufacturing information - CPU Unit. The following Unit Manufacturing information Dialog Box will be displayed. xix Unit version Note Using Unit Version Label The unit version will be displayed in the Unit Manufacturing Information Dialog Box. The following unit version label is provided with the EtherNet/IP Unit. This label can be attached to the front of the EtherNet/IP Unit to differentiate between EtherNet/IP Units with different unit versions. Unit Versions and CX-Programmer Versions Use the following versions of the CX-Programmer to make the Unit settings for the EtherNet/IP Unit. Unit version Unit version 1.0 Unit version 2.0 Ver. 7.1 or lower ----- CX-Programmer Ver. 8.0 OK* OK Ver. 8.02 or higher OK OK * The following auto update must be applied to use CX-Programmer version 8.0: CX-Common Components/CPS Upgrade Software 2008.08 0302 Unit Version Notation Product nameplate Ver. 1.0 or later number shown to right of the lot number In this manual, the unit version of a EtherNet/IP Unit is given as shown in the following table. Notation used in this manual Ethernet Unit Ver. 1.0 or later (See note.) Note CIP Revisions and Unit Versions Some Support Software products call the EtherNet/IP Unit version the “revision.” “Revision” is also sometimes used in this manual. The CIP revisions corresponding to the unit versions of the EtherNet/IP Unit are given in the following table. Unit version Version 1.0 Version 2.0 xx Special remarks Information without reference to specific Unit Versions applies to all versions of the Unit. CIP revision Revision 1.01 Revision 2.01 or 2.02 PRECAUTIONS This section provides general precautions for using the CS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports. The information contained in this section is important for the safe and reliable application of EtherNet/IP Units or built-in EtherNet/IP ports. You must read this section and understand the information contained before attempting to set up or operate an EtherNet/IP Unit or built-in EtherNet/IP port. 1 2 3 4 5 6 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 Applicable Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2 Concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxii xxii xxii xxiv xxiv xxvi xxvi xxvi xxi 1 Intended Audience 1 Intended Audience This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent). • Personnel in charge of installing FA systems. • Personnel in charge of designing FA systems. • Personnel in charge of managing FA systems and facilities. 2 General Precautions The user must operate the product according to the performance specifications described in the operation manuals. Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative. Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms. This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation. !WARNING It is extremely important that a PLC and all PLC Units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a PLC System to the above-mentioned applications. 3 Safety Precautions !WARNING Do not attempt to take any Unit apart while the power is being supplied. Doing so may result in electric shock. !WARNING Do not touch any of the terminals or terminal blocks while the power is being supplied. Doing so may result in electric shock. !WARNING Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in malfunction, fire, or electric shock. xxii Safety Precautions 3 !WARNING Provide safety measures in external circuits (i.e., not in the Programmable Controller), including the following items, to ensure safety in the system if an abnormality occurs due to malfunction of the Programmable Controller or another external factor affecting the operation of the Programmable Controller. “Programmable Controller” indicates the CPU Unit and all other Units and is abbreviated “PLC” in this manual. • Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits. • The PLC will turn OFF all outputs when its self-diagnosis function detects any error or when a severe failure alarm (FALS) instruction is executed. As a countermeasure for such errors, external safety measures must be provided to ensure safety in the system. • The PLC will turn OFF all outputs when its self-diagnosis function detects any error or when a severe failure alarm (FALS) instruction is executed. Unexpected operation, however, may still occur for errors in the I/O control section, errors in I/O memory, and other errors that cannot be detected by the self-diagnosis function. As a countermeasure for all such errors, external safety measures must be provided to ensure safety in the system. • Provide measures in the computer system and programming to ensure safety in the overall system even if errors or malfunctions occur in data link communications or remote I/O communications. !Caution Execute online editing only after confirming that no adverse effects will be caused by extending the cycle time. Otherwise, the input signals may not be readable. • Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits. !Caution Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes. Serious accidents may result from abnormal operation if proper measures are not provided. !Caution Confirm safety at the destination node before changing or transferring to another node the contents of a program, the PLC Setup, I/O tables, I/O memory, or parameters. Changing or transferring any of these without confirming safety may result in injury. !Caution Tighten the screws on the terminal block of the AC Power Supply Unit to the torque specified in the operation manual. The loose screws may result in burning or malfunction. xxiii Operating Environment Precautions 4 4 Operating Environment Precautions !Caution Do not operate the control system in the following locations: • Locations subject to direct sunlight. • Locations subject to temperatures or humidity outside the range specified in the specifications. • Locations subject to condensation as the result of severe changes in temperature. • Locations subject to corrosive or flammable gases. • Locations subject to dust (especially iron dust) or salts. • Locations subject to exposure to water, oil, or chemicals. • Locations subject to shock or vibration. !Caution Take appropriate and sufficient countermeasures when installing systems in the following locations: • Locations subject to static electricity or other forms of noise. • Locations subject to strong electromagnetic fields. • Locations subject to possible exposure to radioactivity. • Locations close to power supplies. 5 Application Precautions Observe the following precautions when using the EtherNet/IP Unit or built-in EtherNet/IP port. !WARNING Always heed these precautions. Failure to abide by the following precautions could lead to serious or possibly fatal injury. • Always connect to a ground of 100 Ω or less when installing the Units. Not connecting to a ground of 100 Ω or less may result in electric shock. • Always turn OFF the power supply to the CPU Unit and Slaves before attempting any of the following. Not turning OFF the power supply may result in malfunction or electric shock. • Mounting or dismounting Power Supply Units, I/O Units, CPU Units, Memory Packs, or Master Units. • Assembling the Units. • Setting DIP switches or rotary switches. • Connecting cables or wiring the system. • Connecting or disconnecting the connectors. !Caution Failure to abide by the following precautions could lead to faulty operation of the EtherNet/IP Unit, built-in EtherNet/IP port, or the system, or could damage the Ethernet Unit. Always heed these precautions. • Interlock circuits, limit circuits, and similar safety measures in external circuits (i.e., not in the Programmable Controller) must be provided by the customer. xxiv 5 Application Precautions • Always use the power supply voltages specified in the operation manuals. An incorrect voltage may result in malfunction or burning. • Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstable. An incorrect power supply may result in malfunction. • Install external breakers and take other safety measures against short-circuiting in external wiring. Insufficient safety measures • Make sure that all the Backplane mounting screws, terminal block screws, and cable connector screws are tightened to the torque specified in the relevant manuals. Incorrect tightening torque may result in malfunction. • Leave the label attached to the Unit when wiring. Removing the label may result in malfunction if foreign matter enters the Unit. • Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction. • Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminals. Connection of bare stranded wires may result in burning. • Observe the following precautions when wiring the communications cable. • Separate the communications cables from the power lines or high-tension lines. • Do not bend the communications cables past their natural bending radius. • Do not pull on the communications cables. • Do not place heavy objects on top of the communications cables. • Always lay communications cable inside ducts. • Use appropriate communications cables. • Make sure that the terminal blocks, expansion cable connectors, and other items with locking devices are locked in place. • Wire all connections correctly according to instructions in this manual. • Double-check all wiring and switch settings before turning ON the power supply. Incorrect wiring may result in burning. • Mount terminal blocks and connectors only after checking the mounting location carefully. • Check the user program (ladder program and other programs) and parameters for proper execution before actually running it on the Unit. Not checking the program may result in unexpected operation. • Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation. • Changing the operating mode of the PLC. • Force-setting/force-resetting any bit in memory. • Changing the present value of any word or any set value in memory. • After replacing a Unit, resume operation only after transferring to the new CPU Unit, Special I/O Unit, or CPU Bus Unit the contents of the DM Area, HR Area, programs, parameters, and other data required for resuming operation. Not doing so may result in an unexpected operation. • Before touching a Unit, be sure to first touch a grounded metallic object in order to discharge any static build-up. Not doing so may result in malfunction or damage. xxv 6 Conformance to EC Directives • When transporting the Unit, use special packing boxes and protect it from being exposed to excessive vibration or impacts during transportation. • CPU Bus Units will be restarted when routing tables are transferred from a Programming Device to the CPU Unit. Restarting these Units is required to read and enable the new routing tables. Confirm that the system will not be adversely affected before allowing the CPU Bus Units to be reset. • When the settings (IP address or tag data link settings) of the EtherNet/IP Unit or built-in EtherNet/IP port are transferred from a Programming Device, all of the destination EtherNet/IP Units or built-in EtherNet/IP ports (nodes) will be reset in order to enable the transferred settings. Transfer settings to the EtherNet/IP Units or built-in EtherNet/IP ports only after verifying that restarting the Units will not cause any problems in the system. • If a repeater hub is used for EtherNet/IP tag data links (cyclic communications), the network's communications load will increase, data collisions will occur frequently, and stable communications will be impossible. Always use a switching hub when using tag data links in the network. • Before resetting a CPU Bus Unit or Special I/O Unit, always verify that restart the Unit will not cause any problems in the system. 6 6-1 Conformance to EC Directives Applicable Directives • EMC Directives • Low Voltage Directive 6-2 Concepts EMC Directives OMRON devices that comply with EC Directives also conform to the related EMC standards so that they can be more easily built into other devices or the overall machine. The actual products have been checked for conformity to EMC standards (see the following note). Whether the products conform to the standards in the system used by the customer, however, must be checked by the customer. EMC-related performance of the OMRON devices that comply with EC Directives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel on which the OMRON devices are installed. The customer must, therefore, perform the final check to confirm that devices and the overall machine conform to EMC standards. Note Applicable EMS (Electromagnetic Susceptibility) and EMI (Electromagnetic Interference) Standards in the EMC (Electromagnetic Compatibility) standards are as follows: EtherNet/IP Unit CS1W-EIP21 CJ1W-EIP21 EMS EN61000-6-2 EMI EN61000-6-4 (Radiated emission: 10-m regulations) Low Voltage Directive Always ensure that devices operating at voltages of 50 to 1,000 V AC and 75 to 1,500 V DC meet the required safety standards for the PLC (EN61131-2). xxvi SECTION 1 Overview of EtherNet/IP This section introduces the functions and protocols used in EtherNet/IP Unit or built-in EtherNet/IP port communications services. 1-1 EtherNet/IP Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1-2 Devices Required for Constructing a Network . . . . . . . . . . . . . . . . . . . . . . . . 4 1-3 Support Software Required to Construct a Network. . . . . . . . . . . . . . . . . . . . 4 1-4 Communications Services Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1-5 Network Configurator Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 1-5-1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 1-5-2 Network Configurator Requirements . . . . . . . . . . . . . . . . . . . . . . . . 10 1-5-3 Precautions When Using the Network Configurator . . . . . . . . . . . . 11 1 Section 1-1 EtherNet/IP Unit Features 1-1 EtherNet/IP Unit Features CX-One Support Software (3) Switching hub (2) Twisted-pair cable (1) Built-in EtherNet/IP port on 100 m max. (1) CS1W-EIP21 EtherNet/IP Unit for CS-series Ethernet (LAN) port CS-series PLC (1) CJ1W-EIP21 EtherNet/IP Unit CJ-series PLC CJ2 CPU Unit (CJ2H-CPU@@-EIP/ CJ2M-CPU3@) CJ-series PLC EtherNet/IP System Configuration Example EtherNet/IP is an industrial multi-vendor network that uses Ethernet components. The EtherNet/IP specifications are open standards managed by the ODVA (Open DeviceNet Vendor Association), just like DeviceNet. EtherNet/IP is not just a network between controllers; it is also used as a field network. Since EtherNet/IP uses standard Ethernet technology, various general-purpose Ethernet devices can be used in the network. The EtherNet/IP Unit and built-in EtherNet/IP port have the following features. High-speed, High-capacity Data Exchange through Data Links The EtherNet/IP protocol supports implicit communications, which allows cyclic communications (called tag data links in this manual) with EtherNet/IP devices. Data can be exchanged at high speed between Controllers and devices, using high-volume tag sets (up to 640 words for the CJ2M and up to 184,832 words for other CPU Units) between PLCs. Tag Data Link (Cyclic Communications) Cycle Time Tag data links (cyclic communications) can operate at the cyclic period specified for each application, regardless of the number of nodes. Data is exchanged over the network at the refresh cycle set for each connection, so the communications refresh cycle will not increase even if the number of nodes is increased, i.e., the synchronicity of the connection’s data is preserved. Since the refresh cycle can be set for each connection, each application can communicate at its ideal refresh cycle. For example, a processes interlocks can be transferred at high speed while the production commands and the status monitor information are transferred at low speed. Note Communicating with FINS Messages (FINS/TCP and FINS/UDP) The communications load to the nodes must be within the Units’ allowed communications bandwidth. Data can be exchanged with other OMRON FA devices using SEND, RECV, and CMND instructions from the ladder program, because EtherNet/IP supports OMRON’s standard FINS message communications services. There are two kinds of message services, using UDP/IP and TCP/IP (called FINS/UDP and FINS/TCP), allowing flexible data exchange for different applications. Note There are no particular restrictions when sending FINS messages to OMRON Ethernet Units (CS1W-ETN21 or CJ1W-ETN21) in an Ethernet network. Network Connections with Controller Link Mutual connections of Controller Link and EtherNet/IP are also supported (using the FINS communications service). The Controller Link connection allows a PLC on the Controller Link network to be monitored from a PLC on the EtherNet/IP network. Conversely, data can be exchanged with a PLC on the EtherNet/IP network from a PLC on the Controller Link network. 2 Section 1-1 EtherNet/IP Unit Features FTP Server A built-in FTP server is provided to enable transferring files in the PLC to and from a host computer. This enables transferring large amounts of data from a client without any additional ladder programming. Automatic PLC Clock Adjustment The clocks built into PLCs connected to Ethernet can be automatically adjusted to the time of the clock in the SNTP server. If all of the clocks in the system are automatically adjusted to the same time, time stamps can be used to analyze various production histories. Note Manage the Network with an SNMP Manager Note Specify Servers with Host Names Note A separate SNTP server is necessary to automatically adjust the PLC clocks. Internal status information from the EtherNet/IP Unit or built-in EtherNet/IP port can be passed to network management software that uses an SNMP manager. A separate SNMP manager is necessary for network management. DNS client functionality allows you to use host names instead of IP addresses to specify SNTP servers and SNMP managers. This is useful, for example, when server IP addresses change for system revisions because the IP addresses are automatically found when host names are used. (1) A separate DNS server is necessary to use host names with the DNS client. (2) The DNS server is specified directly using its IP address. Set Classless IP Address with CIDR A subnet mask can be set to use classless IP addresses, allowing more flexibility in address settings. Plentiful Troubleshooting Functions A variety of functions are provided to quickly identify and handle errors. • Self-diagnosis at power ON • PING command to check the connection with another node • Error Log functions record the time of occurrence and other error details Note The CIP (Common Industrial Protocol) is a shared industrial protocol for the OSI application layer. The CIP is used in networks such as EtherNet/IP, ControlNet, and DeviceNet. Data can be routed easily between networks that are based on the CIP, so a transparent network can be easily configured from the field device level to the host level. The CIP has the following advantages. • Destination nodes are specified by a relative path, without fixed routing tables. • The CIP uses the producer/consumer model. Nodes in the network are arranged on the same level and it is possible to communicate with required devices whenever it is necessary. The consumer node will receive data sent from a producer node when the connection ID in the packet indicates that the node requires the data. Since the producer can send the same data with the same characteristics in a multicast (either multicast or unicast can be selected), the time required for the transfer is fixed and not dependent on the number of consumer nodes. 3 Section 1-2 Devices Required for Constructing a Network 1-2 Devices Required for Constructing a Network The basic configuration for an EtherNet/IP System consists of one switching hub to which nodes are attached in star configuration using twisted-pair cable. CX-One Support Software (3) Switching hub (2) Twisted-pair cable (1) Built-in EtherNet/IP port on 100 m max. (1) CS1W-EIP21 EtherNet/IP Unit for CS-series Ethernet (LAN) port (1) CJ1W-EIP21 EtherNet/IP Unit CJ2 CPU Unit (CJ2H-CPU@@-EIP/ CJ2M-CPU3@) CS-series CJ-series CJ-series PLC PLC PLC The devices shown in the following table are required to configure a network with CS1W-EIP21 and CJ1W-EIP21 EtherNet/IP Units or the built-in EtherNet/ IP port in CJ2H-CPU@@-EIP/CJ2M-CPU3@ CPU Units. Network device (1) CS1W-EIP21 EtherNet/IP Units for CS-series PLCs, CJ1W-EIP21 EtherNet/IP Units for CJ-series PLCs, or built-in EtherNet/IP port in CJ2H-CPU@@-EIP/ CJ2M-CPU3@ CPU Units (2) Twisted-pair cable (3) Switching Hub Recommended Switching Hubs The twisted-pair cable connects EtherNet/IP Units or built-in EtherNet/IP ports to the switching hub, with an RJ45 Modular Connector at each end. Use an STP (shielded twisted-pair) cable of category 5, 5c, or higher. This is a relay device that connects multiple nodes in a star-shaped LAN. For details on recommended devices for constructing a network, refer to 2-3-1 Recommended Network Devices. Note 1-3 Contents These are Communications Units or built-in ports that connect a CS-series or CJ-series PLC to an EtherNet/IP network. If a repeater hub is used for EtherNet/IP tag data links (cyclic communications), the network’s communications load will increase, data collisions will occur frequently, and stable communications will be impossible. Always use a switching hub when using tag data links in the network. Support Software Required to Construct a Network This section describes the Support Software that is required to construct an EtherNet/IP network. Make the tag data link settings and Unit setup settings for the EtherNet/IP Unit or built-in EtherNet/IP port. Both of these settings are stored in the EtherNet/IP Unit’s non-volatile memory (See note.). Support Software is provided for each, as described below. Note Unit Setup: CXProgrammer 4 Unlike the Ethernet Units, the EtherNet/IP Unit’s TCP/IP settings are not stored in the CPU Unit’s CPU Bus Unit System Setup Area. The settings are stored in the EtherNet/IP Unit itself. The CX-Programmer is used to set basic parameters, such as the local IP address of the EtherNet/IP Unit or built-in EtherNet/IP port and the subnet mask. (The CX-Programmer is included in the CX-One.) The CX-Programmer can also be used to check if data I/O is being performed correctly for tag data links. Section 1-3 Support Software Required to Construct a Network Computer CX-Programmer EtherNet/IP Unit or built-in EtherNet/IP port Edit Parameters Dialog Box Unit settings (Built-in non-volatile memory) CS/CJ-series CPU Unit Refer to the CX-Programmer Operation Manual (Cat. No. W446) for information on the CX-Programmer. Tag Data Link Settings: Network Configurator The Network Configurator is used to set the tag data links for the EtherNet/IP Unit or built-in EtherNet/IP port. (The Network Configurator is included in CXOne version 3.0 or higher.) The main functions of the Network Configurator are given below. 1) Setting and Monitoring Tag Data Links (Connections) The network device configuration and tag data links (connections) can be created and edited. After connecting to the network, the device configuration and tag data link settings can be uploaded and monitored. 2) Multivendor Device Connections EDS files can be installed and deleted to enable constructing, setting, and managing networks that contain EtherNet/IP devices from other companies. The IP addresses of EtherNet/IP devices can also be changed. Computer Network Configurator EtherNet/IP Unit or built-in EtherNet/IP port Tag Data Link Settings (Built-in non-volatile memory) Edit Device Parameters Dialog Box Transferred CS/CJ-series CPU Unit For details on the Network Configurator, refer to SECTION 6 Tag Data Link Functions. Routing Table Settings: CX-Integrator Propriety OMRON FINS network system can be constructed from OMRON Communications Units. When FINS services are used, the CX-Integrator allows you to set routing tables to define transmission paths. (The CX-Integrator is included in the CX-One.) If FINS services are not used, then routing tables are not required. 5 Section 1-4 Communications Services Overview Personal computer running Windows CX-Integrator Routing table settings EtherNet/IP Unit or built-in EtherNet/IP port Routing Table Area CS/CJ-series CPU Unit Refer to the CX-Integrator Operation Manual (Cat. No. W464) for information on the CX-Integrator. 1-4 Communications Services Overview The following communications services are supported. CIP (Common Industrial Protocol) Communications Services 1) Tag Data Links (Cyclic Communications) A program is not required to perform cyclic data exchanges with other devices in the EtherNet/IP network. Normally, the tag data links in an EtherNet/IP Unit or built-in EtherNet/IP port are started by grouping the tags created with the Network Configurator into a tag set, and establishing a connection with the target device using that group of tags. One connection is used per group (tag set). Up to 32 connections for the CJ2M and up to 256 connections for other CPU Units) can be registered. The following table gives the tag and tag set specifications. CS1W-EIP21 CJ1W-EIP21 CJ2H-CPU@@-EIP Total size of all tags ≤ 184,832 words Tags CJ2M-CPU3@ Maximum size of 1 tag ≤ 722 words (The maximum size is 721 words when the tag set includes the PLC status.) Number of registrable tags ≤ 256 6 Total size of all tags ≤ 640 words Tag sets CS1W-EIP21 CJ2M-CPU3@ CJ1W-EIP21 CJ2H-CPU@@-EIP Maximum size of 1 tag set ≤ Maximum size of 1 tag set ≤ 722 words 20 words (The maximum size is 721 (The maximum size is 19 words when the tag set words when the tag set includes the PLC status.) includes the PLC status.) Number of tags per tag set ≤ 8 (7 tags/tag set when the tag set includes the PLC status) Maximum size of 1 tag ≤ 20 words (The maximum size is 19 Note Input and output variables cannot be combined. words when the tag set includes the PLC status.) Number of registrable tags ≤ Number of registrable tag Number of registrable tag 32 sets ≤ 256 sets ≤ 32 Section 1-4 Communications Services Overview Connection information • Target IP address • Target tag set • Originator tag set • Packet interval (RPI) Connection Tag Set (Inputs) Tag Set (Outputs) Tag set name: SP1_IN Tag set name: SP1_IN PLC Status PLC Status Tag a Tag i Tag b Tag ii Data flow Tag c : Tag g Originator device Note Target device EtherNet/IP In this example, a connection is established with the originator’s tag list containing tags a to g (inputs), which are grouped in a tag set called SP1_IN, and the target’s tag list containing tags i and ii (outputs), which are grouped in a tag set called SP1_OUT. 2) Message Communications (Unconnected Message Service) User-specified CIP commands can be sent to devices on the EtherNet/IP network. CIP commands, such as those for reading and writing data, can be sent and their responses received by executing the CMND instruction from the CS/ CJ-series CPU Unit’s user program (without using a connection). EtherNet/IP Unit CS/CJ-series CPU Unit CMND CIP command Ethernet (EtherNet/IP) Response CIP messages (CIP commands and responses) can also be transferred to another CIP-based network via the EtherNet/IP Unit or built-in EtherNet/IP port using the CIP routing function for message communications. In the CS/CJ Series, CIP routing is possible only through two EtherNet/IP Units or built-in EtherNet/IP port. 7 Section 1-4 Communications Services Overview EtherNet/IP CS/CJ-series CPU Unit EtherNet/IP Unit Ethernet (EtherNet/IP), etc. EtherNet/IP Unit FINS Communications Service FINS commands can be sent to or received from other PLCs or computers on the same Ethernet network by executing SEND(090), RECV(098), or CMND(490) instructions in the ladder diagram program. This enables various control operations such as the reading and writing of I/O memory between PLCs, mode changes, and file memory operations. Note There are no particular restrictions when sending FINS messages to OMRON Ethernet Units (CS1W-ETN21 or CJ1W-ETN21) in an Ethernet network. Ethernet (EtherNet/IP) IP UDP or TCP FINS IP UDP or TCP FINS CS/CJ-series CPU Unit Ethernet Unit EtherNet/IP Unit EtherNet/IP Unit User program SEND(090), RECV(098), or CMND(490) instruction Various control operations (such as the reading and writing of I/O memory between PLCs, mode changes, and file memory operations) can be executed from the host computer by sending the corresponding FINS command with a UDP/IP or TCP/IP header attached. For example, it is possible to connect online via Ethernet from FINS communications applications such as the CX-Programmer, and to perform remote programming and monitoring. (See note.) Note 8 Use CX-Programmer version 4.0 to use TCP/IP. For lower versions of CX-Programmer, FinsGateway Version 2003 or higher is required to use TCP/IP. Section 1-4 Communications Services Overview Ethernet (EtherNet/IP) IP UDP or TCP FINS CS/CJ-series CPU Unit EtherNet/IP Unit The FINS gateway function enables access to PLCs on not only the same Ethernet network but on various other networks, including SYSMAC LINK and Controller Link. 9 Network Configurator Overview 1-5 Section 1-5 Network Configurator Overview 1-5-1 Overview The Network Configurator Ver. 3.0 or higher is a software package designed for building, setting, and controlling a multi-vendor EtherNet/IP Network using OMRON's EtherNet/IP. It is included in CX-One version 4.0 or higher. The Network Configurator provides the following functions for building, setting, and controlling EtherNet/IP. Network Control The Network configuration can be created and edited regardless of whether the Network Configurator is online or offline. The Network configuration can be read from a file or the network. Hardware (EDS File) Control EDS files used by the Network Configurator can be installed and deleted. 1-5-2 Network Configurator Requirements Item Operating environment Network connection method Serial interface Ethernet interface Location on Network Number of Units that can be connected to Network Main func- Network control tions functions Hardware control functions Supported file formats 10 Specification Refer to the CX-One Setup Manual (W463). CXONE-AL@@C-V4/CXONE-AL@@D-V4 CS1/CJ1 CJ2 CPU Unit’s Peripheral or RS-232C port CPU Unit’s USB or RS-232C port EtherNet/IP Unit’s Ethernet port CPU Unit’s Ethernet port EtherNet/IP Unit’s Ethernet port A single node address is used (only when directly connected to EtherNet/IP). A single Network Configurator per network (More than one Configurator cannot be used in the same system.) • The network configuration can be created and edited regardless of whether the Network Configurator is online or offline. • The network configuration can be read from a file or the network. The EDS files used by the Network Configurator can be installed and deleted. Configurator network configuration files (*.nvf) Configuration files (*.ncf) created using the Network Configurator for EtherNet/IP (version 2) can be imported by selecting External Data - Import from the File Menu. Section 1-5 Network Configurator Overview 1-5-3 Precautions When Using the Network Configurator Only an OMRON EtherNet/IP Unit can be set as the originator for a connection using the Network Configurator. • The Network Configurator can be connected to the EtherNet/IP network through the following ports: • CS1/CJ1-series CPU Unit’s serial port (peripheral or RS-232C) or Ethernet port on EtherNet/IP Unit • CJ2-series CPU Unit’s serial port (USB or RS-232C), Ethernet port on EtherNet/IP Unit or built-in EtherNet/IP port • The Network Configurator can be connected directly to the EtherNet/IP network from the computer’s Ethernet port. When connecting directly to the EtherNet/IP network, an Ethernet port must be set up in the computer in advance. In this case, the Network Configurator will be connected to the EtherNet/IP network as a single node. If there isn’t an unused node address available, the Network Configurator can’t be connected directly to the EtherNet/IP network. 11 Network Configurator Overview 12 Section 1-5 SECTION 2 Unit Specifications This section provides the specifications of EtherNet/IP Units and introduces recommended network configuration devices. 2-1 2-2 2-3 EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications . . . . . . . . . . . 14 2-1-1 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2-1-2 Unit Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2-1-3 Communications Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2-1-4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 2-1-5 Software Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Nomenclature and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 2-2-1 Nomenclature and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 2-2-2 Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Selecting the Network Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2-3-1 Recommended Network Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2-3-2 Network Devices Manufactured by OMRON . . . . . . . . . . . . . . . . . 28 2-3-3 Switching Hub Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2-3-4 Switching Hub Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 2-3-5 Precautions When Selecting a Switching Hub . . . . . . . . . . . . . . . . . 29 13 EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications 2-1 2-1-1 Section 2-1 EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications General Specifications The general specifications conform to those of the CS-series and CJ-series PLCs. 2-1-2 Unit Specifications CS-series EtherNet/IP Units Item Model number Type Applicable PLCs Unit classification Mounting location Number of Units that can be mounted Specifications CS1W-EIP21 100Base-TX (See note.) CS-series PLCs CS-series CPU Bus Unit CPU Rack or Expansion Rack 8 max. (including Expansion Racks) CPU Unit Allocated CIO Area words used words (CPU Bus Unit words) 25 words/Unit (one unit number’s words) These words contain control bits and flags, the target node PLC’s operating and error information, Unit status, communications status, registered/normal target node information, and FINS/TCP connection status. 100 words/Unit (one unit number’s words) These words contain the IP address display/setting area Allocated DM Area words (CPU Bus Unit words) User-set area Any usable data area words Target node PLC’s operating and error information, and registered/normal target node information CPU Bus Unit System Not used. Setup Non-volatile memory within EtherThe following settings are stored in the EtherNet/IP Unit’s non-volatile memory. Net/IP Unit (See note.) Note Unlike the regular Ethernet Units, the CPU Bus Unit Setup Area in the CPU Unit is not used for these settings. 1. Unit setup (communications settings for the EtherNet/IP Unit, such as the IP address, DNS server settings, host name, baud rate, FINS/UDP settings, and FINS/ TCP settings) 2. Tag data link settings (device parameters) Transfer Media access method CSMA/CD specificaModulation method Baseband tions Transmission paths Star form Baud rate 100 Mbit/s (100Base-TX) Transmission media Shielded twisted-pair (STP) cable Categories: 100 Ω at 5, 5e Transmission distance 100 m (distance between hub and node) Number of cascade There is no limitation when a switching hub is used. connections Current consumption (Unit) 410 mA max. at 5 V DC Weight 171 g max. Dimensions 35 × 130 × 101 mm (W × H × D) Other general specifications Other specifications conform to the general specifications of the CS-series Note 14 If tag data links are being used, use 100Base-TX. Otherwise, 10Base-T can be used, but this is not recommended. EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications Section 2-1 CJ-series EtherNet/IP Unit Item Model number Type Applicable PLCs Unit classification Mounting location Number of Units that can be mounted CPU Unit Allocated CIO Area words used words (CPU Bus Unit words) Allocated DM Area words (CPU Bus Unit words) User-set area CPU Bus Unit System Setup Non-volatile memory within EtherNet/IP Unit (See note.) Transfer specifications Media access method Modulation method Transmission paths Baud rate Transmission media Transmission distance Number of cascade connections Current consumption (Unit) Weight Dimensions Other general specifications Note Specifications CJ1W-EIP21 100Base-TX (See note.) CJ-series PLCs CJ-series CPU Bus Unit CPU Rack or Expansion Rack 8 max. (including Expansion Racks) Note Up to seven EtherNet/IP Units can be connected to a CJ2H-CPU@@-EIP CPU Unit. Up to two EtherNet/IP Units can be connected to a CJ2M CPU Unit. 25 words/Unit (one unit number’s words) These words contain control bits and flags, the target node PLC’s operating and error information, Unit status, communications status, registered/normal target node information, and FINS/TCP connection status. 100 words/Unit (one unit number’s words) These words contain the IP address display/setting area. Any usable data area words Target node PLC’s operating and error information, and registered/normal target node information Not used. The following settings are stored in the EtherNet/IP Unit’s non-volatile memory. Note Unlike the regular Ethernet Units, the CPU Bus Unit Setup Area in the CPU Unit is not used for these settings. 1. Unit Setup (communications settings for the EtherNet/IP Unit, such as the IP address, DNS server settings, host name, baud rate, FINS/UDP settings, and FINS/ TCP settings) 2. Tag data link settings (device parameters) CSMA/CD Baseband Star form 100 Mbit/s (100Base-TX) Shielded twisted-pair (STP) cable Categories: 100 Ω at 5, 5e 100 m (distance between hub and node) There is no limitation when a switching hub is used. 410 mA max. at 5 V DC 94 g max. 31 × 90 × 65 mm (W × H × D) Other specifications conform to the general specifications of the CJ-series. If tag data links are being used, use 100Base-TX. Otherwise, 10Base-T can be used, but this is not recommended. 15 EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications Section 2-1 CJ2 CPU Built-in EtherNet/IP Port Item Model number Type Unit classification CPU Unit Allocated CIO Area words used words (CPU Bus Unit words) Allocated DM Area words (CPU Bus Unit words) User-set area CPU Bus Unit System Setup Non-volatile memory for the CJ2 built-in EtherNet/IP port Specifications CJ2H-CPU@@-EIP CJ2M-CPU3@ 100Base-TX (See note.) CJ2 CPU Unit built-in port (CJ2 CPU Bus Unit) 25 words/Unit (one unit number’s words) These words contain control bits and flags, the target node PLC’s operating and error information, Unit status, communications status, registered/normal target node information, and FINS/TCP connection status. 100 words/Unit (one unit number’s words) These words contain the IP address display/setting area. Any usable data area words Target node PLC’s operating and error information, and registered/normal target node information Not used. The following settings are stored in the non-volatile memory for the built-in EtherNet/ IP port. Note Unlike the regular Ethernet Units, the CPU Bus Unit Setup Area in the CPU Unit is not used for these settings. Transfer specifications Media access method Modulation method Transmission paths Baud rate Transmission media Transmission distance Number of cascade connections Current consumption (Unit) Weight Dimensions Other general specifications Note 16 1. Unit Setup (communications settings for the built-in EtherNet/IP port, such as the IP address, DNS server settings, host name, baud rate, FINS/UDP settings, and FINS/TCP settings) 2. Tag data link settings (device parameters) CSMA/CD Baseband Star form 100 Mbit/s (100Base-TX) Shielded twisted-pair (STP) cable Categories: 100 Ω at 5, 5e 100 m (distance between hub and node) There is no limitation when a switching hub is used. For CJ2 CPU Units, refer to the CJ2 CPU Hardware Operation Manual (W472). Other specifications conform to the general specifications of the CJ2 or built-in EtherNet/IP port CJ2 CPU Unit. If tag data links are being used, use 100Base-TX. Otherwise, 10Base-T can be used, but this is not recommended. EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications 2-1-3 Section 2-1 Communications Specifications CIP Tag data service links (Cyclic communications) Item CS1/CJ1 CJ2H Number of connections 256 Packet interval (refresh 0.5 to 10,000 ms (in 0.5-ms units) cycle) Can be set independently for each connection. (Data is refreshed over the network at the preset interval and does not depend on the number of nodes.) Allowed communications bandwidth per Unit 6000 pps (See note 1.) Number of tags that can be registered Tag types 256 Note Including the heartbeat. CJ2M 32 1 to 10,000 ms (in 0.5ms units) Can be set independently for each connection. (Data is refreshed over the network at the preset interval and does not depend on the number of nodes.) 3000 pps (See note 1.) Note Including the heartbeat. 32 CIO Area, DM Area, EM Area, Holding Area, Work Area, and network symbols (See note 8.) 8 (7 tags when the tag set contains the PLC status) Number of tags per connection (= 1 tag set) Maximum link data size 184,832 words per node Maximum data size per 252 words or 722 words (See note 2.) connection Note Data synchronicity is maintained within each connection. Number of registrable tag sets 256 (1 connection = 1 tag set) Maximum size of 1 tag set 722 words (The PLC status uses 1 word when the tag set contains the PLC status.) Maximum number of tags that can be refreshed per CPU Unit cycle (See note 3.) Output/Transmission (CPU → EtherNet/IP): 256 Input/Reception (EtherNet/IP → CPU): 256 Output/Transmission (CPU → EtherNet/IP): 6,432 words Input/Reception (EtherNet/IP → CPU): 6,432 words Output/Transmission (CPU → EtherNet/IP): 19 Input/Reception (EtherNet/IP → CPU): 20 (See note 4.) Output/Transmission Data that can be refreshed per CPU Unit (CPU → EtherNet/IP): 7,405 words cycle (See note 3.) Input/Reception (EtherNet/IP → CPU): 7,405 words Changing tag data link Supported (See note 5.) parameters during operation Multicast packet filter Supported function (See note 6.) 640 words 20 words Note Data synchronicity is maintained within each connection. 32 (1 connection = 1 tag set) 20 words (The PLC status uses 1 word when the tag set contains the PLC status.) Output/Transmission (CPU → EtherNet/IP): 32 Input/Reception (EtherNet/IP → CPU): 32 Output/Transmission (CPU → EtherNet/IP): 640 words Input/Reception (EtherNet/IP → CPU): 640 words 17 Section 2-1 EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications Item CIP Explicit service messaging CS1/CJ1 CJ2H CJ2M Class 3 (connected) UCMM (unconnected) Number of connections: 128 Number of clients that can communicate at one time: 32 max. Number of servers that can communicate at one time: 32 max. CIP routing CS1W-EIP21 CJ1W-EIP21 CJ2H-CPU@@-EIP CJ2M-CPU3@ Supported 16 connections max. SNMPv1, SNMPv2c MIB-II Conforms to A5 10BASE-T or 100BASE-TX Auto Negotiation or fixed settings FINS service (See note 7.) FINS/UDP FINS/TCP SNMP Agent MIB EtherNet/IP conformance test Ethernet interface Note Number of clients that can communicate at one time: 16 max. Number of servers that can communicate at one time: 16 max. (1) In this case, pps means “packets per second” and indicates the number of packets that can be processed in one second. (2) To use 505 to 1,444 bytes as the data size, the system must support the Large Forward Open standard (an optional CIP specification). The SYSMAC CS/CJ-series Units support this standard, but before connecting to nodes of other companies, confirm that those devices also support it. (3) If the maximum data size is exceeded, the data refreshing with the CPU Unit will extend over two or more cycles. (4) If status layout is selected in the user settings, the maximum number of tags that can be received is 19 tags. (5) If parameters are changed in the EtherNet/IP Unit, however, the EtherNet/IP Unit will be restarted. When other nodes are communicating with the affected node, the communications will temporarily time out and automatically recover later. (6) Because the EtherNet/IP Unit is equipped with an IGMP client (version 2), unnecessary multicast packets can be filtered by using a switching hub that supports IGMP snooping. (7) The EtherNet/IP Unit uses the TCP/UDP port numbers shown in the following table. Service Tag data links Class 3, UCMM DNS FINS/UDP service FINS/TCP service FTP SNTP SNMP SNMP trap Protocol UDP TCP/UDP UDP UDP TCP TCP UDP UDP UDP Port number 2222 44818 53 9600 9600 20, 21 123 161 162 Remarks Fixed value Port numbers in the Unit Setup can be changed with the CX-Programmer. (8) Network symbols can be used only with a CJ2H-CPU6@-EIP or CJ2MCPU3@ CPU Unit. 18 Section 2-1 EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications 2-1-4 Dimensions CS1W-EIP21 EIP21 MS NS COMM 100M 10M UNIT NO. NODE NO. 0 0 1 ×161 130 mm IP ×160 ADDRESS 192.168.250.1 SUBNET MASK 255.255.255.0 100BASE-TX 10BASE-T 35 mm 101 mm CJ1W-EIP21 65 mm 31 mm EIP21 MS NS COMM 100M 10M EF01 6789 2345 ABCD IP ADDRESS EF01 EF01 6789 ABCD ABCD 90 mm x161 6789 2345 2345 UNIT No. NODE No. x160 192.168.250.1 SUBNET MASK 255.255.255.0 100BASE-TX 10BASE-T CJ2H-CPU@@-EIP 2.7 mm 66.2 mm 90 mm 2.7 mm 65 mm 79.8 mm 74.5 mm 19 Section 2-1 EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications CJ2M-CPU3@ 76.16 mm 2.7 mm 90 mm 2.7 mm 75 mm 62 mm 84.5 mm 2-1-5 Software Configuration Memory Card/ EM file memory Interface with CPU Unit FINS FINS FINS encapsulization Cyclic Tag data link function FTP FINS Service (FINS/UDP and FINS/TCP) FINS Explicit messaging Automatic clock adjustment CIP Encapsulation UDP TCP ARP IP LAN controller driver LAN controller 20 ICMP IGMP Section 2-2 Nomenclature and Functions 2-2 2-2-1 Nomenclature and Functions Nomenclature and Functions CS1W-EIP21 EIP21 MS NS COMM 100M 10M LED Indicators UNIT NO. NODE NO. 0 Node address setting switches 1 ×161 IP Unit number setting switch 0 ×160 ADDRESS Label showing IP address 192.168.250.1 SUBNET MASK 255.255.255.0 Backplane Connector 100BASE-TX 10BASE-T Ethernet connector CJ1W-EIP21 EIP21 MS NS COMM 100M 10M EF012 6789 345 ABCD EF012 EF012 ADDRESS ABCD 6789 IP x161 6789 345 345 ABCD 192.168.250.1 SUBNET MASK UNIT No. NODE No. x160 LED Indicators Unit number setting switch Node address setting switches Label showing IP address 255.255.255.0 100BASE-TX 10BASE-T Ethernet connector 21 Section 2-2 Nomenclature and Functions Built-in EtherNet/IP Port in CJ2H-CPU@@-EIP LED Indicators Unit number setting switch Node address setting switches Label showing IP address Ethernet connector Built-in EtherNet/IP Port in CJ2M-CPU3@ LED Indicators Unit number setting switch Node address setting switches Label showing IP address Ethernet connector Ethernet Address Notation A specific Ethernet address is allocated to all devices connected to the Ethernet network. The EtherNet/IP Unit’s address is listed in 12-digit hexadecimal on the right side of the Unit. CS1W-EIP21 ETHERNET/IP UNIT Lot No. OMRON Corporation MADE IN JAPAN @@@@@@@@@@@@ Ethernet Address Ethernet address (12 digits) Note (1) The Ethernet Address can also be checked with the CONTROLLER DATA READ command. For details, refer to Appendix E FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports. (2) An IP address label is included with the EtherNet/IP Unit, so the user can record the user-set IP address and subnet mask on the label, and affix the label to the front of the Unit. When this label is affixed to the front of the Unit, it is easy to confirm the Unit’s IP address and subnet mask. 22 Section 2-2 Nomenclature and Functions EIP21 MS NS COMM 100M 10M EF012 6789 345 UNIT No. Example label IP ADDRESS 192.168.250.1 SUBNET MASK ABCD 255.255.255.0 EF012 EF012 ADDRESS ABCD 6789 IP x161 6789 345 345 NODE No. x160 Affix the label on the front of the EtherNet/IP Unit, between the node address switches and the Ethernet connector. ABCD 192.168.250.1 SUBNET MASK 255.255.255.0 100BASE-TX 10BASE-T Indicators A EtherNet/IP Units or built-in EtherNet/IP port is equipped with the following indicators that indicate the operating status of the node itself and the overall network. CS1W-EIP21 EIP21 MS NS COMM 100M 10M CJ1W-EIP21, CJ2H-CPU@@-EIP, and CJ2M-CPU3@ EIP21 MS NS COMM 100M 10M Status Indicators: MS, NS, COMM, 100M, and 10M The MS (Module Status) indicator indicates the status of the node itself and the NS (Network Status) indicator indicates the status of the network. The COMM, 100M, and 10M indicators indicate the status of Ethernet communications. The MS and NS indicators can be green or red. The COMM, 100M, and 10M indicators are yellow. These indicators can be lit, flashing, or not lit. The following table shows the meaning of these indicator conditions. Refer to SECTION 14 Troubleshooting and Error Processing for details on using these indicators for troubleshooting. 23 Section 2-2 Nomenclature and Functions Indicator Name MS Module Status NS Color Red Green --Network Status Red Green COMM --Communication Yellow 100M 100 Mbps Yellow 10M 10 Mbps Yellow Seven-segment Display LED status Lit Flashing Lit Not lit Lit Flashing Lit Flashing Not lit Lit Not lit Lit Not lit Lit Not lit Indicated operating status Fatal error Recoverable error Normal Power supply OFF Fatal error Recoverable error Tag data link and message connections established Tag data link and message connections not established Offline or power supply OFF Transferring data Not transferring data 100BASE-TX link established 100BASE-TX link not established 10BASE-TX link established 10BASE-TX link not established When the power is turned ON (or the Unit is restarted), all of the segments will flash twice, the IP address set in the EtherNet/IP Unit or built-in EtherNet/IP port will be displayed on the 7-segment display just once, from right to left. Afterwards, the rightmost 8 bits of the IP address is displayed in hexadecimal during normal operation. Example 1: Displaying IP Address 192.168.250.10 The IP address is displayed in decimal, flowing from right to left. If the Unit is operating normally, the last digit of the Unit's IP address is displayed in hexadecimal. Flashing: The tag data link is stopped. Lit: The tag data link is operating. 24 Section 2-2 Nomenclature and Functions If an error occurs, the error code will be displayed alternately with the rightmost byte of the affected device’s IP address. For details on error codes, refer to SECTION 14 Troubleshooting and Error Processing. Displaying Multiple Error Sources • A d6 error (failed to establish connection) occurred with IP address 192.168.250.8. • A d6 error (failed to establish connection) occurred with IP address 192.168.250.9. • A d5 error (verification error, target nonexistent) occurred with IP address 192.168.250.64. • A C6 error (multiple switches ON) and EA error (EtherNet/IP expansion setting error) occurred at the local EtherNet/IP Unit or built-in EtherNet/IP port, IP address 192.168.250.10. The error code is displayed and then the last digit of the target node's IP address is displayed in hexadecimal. Displays errors that occurred within the Unit. The last digit of the Unit's IP address is displayed in hexadecimal. • There is no particular priority to the order in which the errors are displayed. All of the errors are displayed repeatedly in order. 25 Section 2-2 Nomenclature and Functions Right and Left Dot LEDs If an error occurred in two or more devices with the same rightmost byte in their IP addresses, the Right Dot LED will be lit while the devices’ error is being displayed. Example: Displaying the Following Errors • A d6 error (failed to establish connection) occurred with IP address 10.0.1.8. • A d6 error (failed to establish connection) occurred with IP address 10.0.2.8. 2-2-2 Switch Settings Unit Number Setting Switch The Unit Number Setting Switch sets the unit number of the EtherNet/IP Unit or built-in EtherNet/IP port as a CPU Bus Unit. The unit number determines which data area words are allocated to the Unit to contain data such as control bits, flags, status information, and connection information. 6543 DCB 210FE A987 Setting method One-digit hexadecimal Setting range 0 to F Note The unit number is factory-set to 0. The unit number can be set to any number in the setting range (0 to F), as long as the same number is not set on another CPU Bus Unit in the same PLC. Note (1) Use a small screwdriver to make the setting, and be sure not to damage the rotary switch. (2) Always turn OFF the PLC’s power supply before setting the unit number. (3) The unit number is factory-set to 0. (4) If the same unit number is set on more than one CPU Bus Unit mounted in a PLC, a unit number duplication error will occur in the PLC and the EtherNet/IP Unit or built-in EtherNet/IP port will not be able to start operating. 26 Section 2-2 Nomenclature and Functions The Node Address Setting Switch sets the node address of the EtherNet/IP Unit or built-in EtherNet/IP port. 3210F 7654 6543 X161 EDC DCB 210FE BA98 Node Address Setting Switch X160 A987 Setting method Two-digit hexadecimal Setting range 01 to FE Note The node address is factory-set to 01. With the default settings, the values set on these switches become the last two digits of the local IP address of the EtherNet/IP Unit or built-in EtherNet/IP port. Default IP address = 192.168.250.node address With the factory-default node address setting of 01, the default IP address is 192.168.250.1. The node address can be set to any number in the setting range (01 to FE), as long as the same address is not set on another node in the network. Note If the node address setting is changed during operation, the MS Indicator will flash red. 27 Section 2-3 Selecting the Network Devices 2-3 Selecting the Network Devices 2-3-1 Recommended Network Devices The following table shows the devices recommended for use with the EtherNet/IP. Part Switching Hub Twisted-pair cable Connectors (Modular plug) Boots Maker Cisco Systems, Inc. Model number Consult the manufacturer. Contec USA, Inc. Phoenix Contact Consult the manufacturer. Consult the manufacturer. 100BASE-TX Fujikura F-LINK-E 0.5mm × 4P EtherNet/IP compliant cable STP Plug Panduit Corporation MPS588 Tsuko Company Note Inquires Cisco Systems, Inc. Main Corporate HQ CONTEC USA Inc. Phoenix Contact USA Customer Service Fujikura America, Inc. --Panduit Corporation US Headquarters Tsuko Company Japan Headquarters MK boot (IV) LB (1) Always use a switching hub when using tag data links in the network. (2) If a repeater hub is used for EtherNet/IP tag data links (cyclic communications), the network’s communications load will increase, data collisions will occur frequently, and stable communications will be impossible. 2-3-2 Network Devices Manufactured by OMRON The following network devices are manufactured by OMRON for EtherNet/IP networks. Name Model Switching Hub W4S1-03B W4S1-05B W4S1-05C 2-3-3 Function Packet priority control (QoS): EtherNet/IP control data priority Failure detection: Broadcast storm, LSI error detection, 10/ 100Base-TX, Auto-Negotiation Number of Error detection ports output 3 None 5 None 5 Provided. Switching Hub Types Unmanaged Layer 2 (L2) Switching Hubs These switching hubs use the Ethernet MAC address to switch ports. Ordinary switching hubs have this function. Switching hub functions and settings cannot be changed. Managed Layer 2 (L2) Switching Hubs These switching hubs use the Ethernet address to switch ports. Switching hub functions and settings can be changed using special software tools for switching hubs running on a network node. Analytical data can also be collected. These switching hubs provide more-advanced functions that unmanaged layer 2 switching hubs. 28 Section 2-3 Selecting the Network Devices 2-3-4 Switching Hub Functions This section describes the switching hub functions that are important when using an EtherNet/IP network. When using an EtherNet/IP Unit, set the following two functions. • Multicast filtering • QoS (Quality of Service) for TCP/UDP port numbers (L4) Multicast Filtering Multicast filtering transfers multicast packets to the specific nodes only. This function is implemented in the switching hub as IGMP Snooping or GMRP. “Specific nodes” are nodes equipped with an IGMP client that have made transfer requests to the switching hub. (OMRON EtherNet/IP Units are equipped with an IGMP client.) When the hub does not use multicast filtering, multicast packets are sent to all nodes, just like broadcast packets, which increases the traffic in the network. Settings must be made in the switching hub to enable this function. There must be enough multicast filters for the network being used. QoS (Quality of Service) Function for TCP/UDP Port Numbers (L4) This function controls the priority of packet transmissions so that packets can be sent with higher priority to a particular IP address or TCP (UDP) port. The TCP and UDP protocols are called transport layer protocols, leading to the name L4 (layer 4) QoS function. When tag data links and message communications are executed on the same network, tag data links can be sent at higher priority to prevent problems such as transmission delays due to message communications traffic and packet losses due to buffer overflow. Settings must be made in the switching hub to enable this function and give higher priority to tag data link packets. Support for the above two functions is as follows for the different types of switching hubs. Hub Unmanaged L2 switching hub Managed L2 switching hub OMRON W4S1-series Switching Hubs Note 2-3-5 Multicast filtering None Provided. L4 QoS None Provided. None Provided. Remarks --Both functions must be set with a special software tool. L4 QoS is set using a switch. No software tool is necessary. If the Network Configurator is used to set the connection type in the connection settings to a multicast connection, multicast packets will be used. If the connection type is set to a point-to-point connection, multicast packets will not be used. Precautions When Selecting a Switching Hub The functions supported by the switching hub may affect tag data link transmission delays and the configuration. In addition, if the switching hub supports advanced functions, special settings are required for those functions. 29 Section 2-3 Selecting the Network Devices When selecting a switching hub, it is necessary to consider whether the switching hub will be selected based on the kind and amount of communications that will be performed in the network or the kind of switching hub that you want to use. Refer to the following precautions when selecting a switching hub. Refer to 10-2 Adjusting the Communications Load to estimate the communications load for tag data links. Selecting the Switching Hub Based on the Types of Network Communications Executing Tag Data Links Only We recommend using an L2 switching hub without multicast filtering or an L2 switching hub with multicast filtering. Using an L2 switching hub with multicast filtering prevents increased traffic due to unnecessary multicast packets, so the tag data links can operate at higher speed. If either of the following conditions exists, the amount traffic will be the same for both kinds of L2 switching hubs (with or without multicast filtering). • The tag data links are set to share the same data with all nodes in the network. (The multicast packets are transferred to all nodes in the network, just like a broadcast.) • The tag data link settings are all one-to-one (unicast) and multicast packets cannot be used. If multicast filters are being used, settings must be made in the switching hub. There must be enough multicast filters for all of the networks being used. Executing Tag Data Links and Message Communications We recommend using an L2 switching hub with multicast filtering and L4 QoS. By setting tag data links for higher-priority transmission, it is possible to prevent problems such as transmission delays due to message communications traffic and packet losses due to buffer overflow. Settings must be made in the switching hub to enable this function and give higher priority to tag data link packets. Special settings must be made in the switching hub when using the multicast filtering function and L4 QoS function. Selecting the Switching Hub Based on the Hub’s Supported Functions L2 Switching Hub without Multicast Filtering We recommend this kind of switching hub when only tag data links are executed and any of the following conditions is met. • The tag data links are set to share the same data with all nodes in the network. (The multicast packets are transferred to all nodes in the network, just like a broadcast.) • The tag data link settings are all one-to-one (unicast) and multicast packets cannot be used. • There is little traffic in the tag data links. No special settings are required for an L2 switching hub without multicast filtering. L2 Switching Hub with Multicast Filtering We recommend this kind of switching hub when only tag data links are executed and the following condition is met. • There are many 1:N links (where N represents some number of nodes in the network) in the tag data link settings, i.e., there are many multicast packets used, or there is heavy traffic in the tag data links. Special settings are required for an L2 switching hub with multicast filtering. There must be enough multicast filters for the network being used. 30 Selecting the Network Devices L3 Switching Hub with Multicast Filtering and L4 QoS Functions Section 2-3 We recommend this kind of switching hub when both tag data links and message communications are executed. By setting tag data links for higher-priority transmission, it is possible to prevent problems such as transmission delays due to message communications traffic and packet losses due to buffer overflow. Settings must be made in the switching hub to enable this function and give higher priority to tag data link packets. Special settings must be made in the switching hub when using the multicast filtering function and L4 QoS function. There must be enough multicast filters for the network being used. Note (1) Ask the switching hub manufacturer for setting procedures for the switching hub. (2) Install the switching hub so that its environmental resistance capabilities are not exceeded. Ask the switching hub manufacturer for information on the environmental resistance of the switch hub. 31 Selecting the Network Devices 32 Section 2-3 SECTION 3 Installation and Initial Setup This section explains how to install and make the initial settings required for operation of the EtherNet/IP Unit or built-in EtherNet/IP port. 3-1 3-2 3-3 3-4 3-5 3-6 Overview of Initial Setup Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 3-1-1 Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 3-2-1 CS-series EtherNet/IP Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 3-2-2 CJ-series EtherNet/IP Units and CJ2 Built-in EtherNet/IP Port. . . . 37 Mounting to a PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 3-3-1 Mounting to a CS-series PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 3-3-2 Mounting to a CJ-series PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 3-3-3 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 3-3-4 Handling Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Network Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 3-4-1 Basic Installation Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 3-4-2 Recommended Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 3-4-3 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 3-4-4 Using Contact Outputs (Common to All Units) . . . . . . . . . . . . . . . . 43 Connecting to the Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 3-5-1 Ethernet Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 3-5-2 Connecting the Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Creating I/O Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 3-6-1 I/O Table Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 3-6-2 Connecting Programming Devices to the PLC. . . . . . . . . . . . . . . . . 46 3-6-3 Procedure for Creating I/O Tables . . . . . . . . . . . . . . . . . . . . . . . . . . 46 3-7 Setting the Local IP Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 3-8 TCP/IP and Link Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 3-8-1 Setting Procedure with the CX-Programmer . . . . . . . . . . . . . . . . . . 52 3-8-2 Making TCP/IP Settings with the Network Configurator . . . . . . . . 55 Tag Data Link Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 3-9-1 Network Configurator Setting Procedure . . . . . . . . . . . . . . . . . . . . . 57 3-10 Other Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 3-11 Communications Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 3-11-1 PING Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 3-11-2 EtherNet/IP Unit or Built-in EtherNet/IP Port Operation. . . . . . . . . 65 3-11-3 Host Computer Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 3-9 33 Overview of Initial Setup Procedures 3-1 3-1-1 Section 3-1 Overview of Initial Setup Procedures Procedures Initial Settings 1,2,3... 1. Set the unit number and node address with the switches on the front of the EtherNet/IP Unit or, for the built-in EtherNet/IP port, on the front of the CPU Unit. Refer to 3-2 Switch Settings. 2. Mount the Unit in the CPU Rack. A maximum of seven EtherNet/IP Units can be connected to a CJ2HCPU@@-EIP CPU Unit (making eight EtherNet/IP ports including the builtin EtherNet/IP port). A maximum of two EtherNet/IP Units can be connected to a CJ2M-CPU3@ CPU Unit. Refer to 3-3 Mounting to a PLC. 3. Wire the Ethernet network with twisted-pair cable. Refer to 3-4 Network Installation and 3-5 Connecting to the Network. 4. Prepare a computer with Support Software installed on it and a serial cable or an Ethernet cable (twisted-pair cable) to connect to the PLC. These are required to perform network settings using the Support Software (e.g., Network Configurator, CX-Programmer, and CX-Integrator). 5. Connect the PLC to the computer and create the I/O tables using the CXProgrammer. I/O tables do not need to be created for the built-in EtherNet/ IP port on the CJ2H-CPU@@-EIP or CJ2M-CPU3@. Refer to 3-6 Creating I/O Tables. 6. Set the IP address of the EtherNet/IP Unit or built-in EtherNet/IP port using one of the following methods. a) Using the Unit without setting the IP address: • The default IP address is 192.168.250.Node_address. b) Setting a particular IP address: • If you want to store the setting in the CPU Unit, set it in the EtherNet/ IP Unit’s allocated DM area within the CPU Unit. • If you want to store the setting in the Unit, set the IP address in the Edit Parameters Dialog Box of the I/O Table Dialog Box from the CX-Programmer, and transfer the setting to the Unit. Refer to 3-7 Setting the Local IP Address and 3-8 TCP/IP and Link Settings. 7. When necessary, set the following items in the Edit Parameters Dialog Box and transfer them: TCP/IP, Ethernet, FINS/UDP, FINS/TCP, FTP, Auto Adjust Time, Status Area, SNMP, and SNMP Trap Refer to 3-10 Other Parameters. 8. When necessary, set the routing tables. If the FINS communications service is being used and multiple network Communications Units are mounted in the PLC, set the routing tables from the CX-Integrator, and transfer the table. Refer to the CX-Integrator Operation Manual (Cat. No. W464) for the setting procedure. 34 Overview of Initial Setup Procedures Section 3-1 9. Test communications. Send a PING command to the EtherNet/IP Unit or built-in EtherNet/IP port. Refer to 3-11 Communications Test. Settings Required for Tag Data Link Service (Cyclic Communications) 1. Using the EtherNet/IP Datalink Tool in the Network Configurator to Set the Parameters With this method, there is no flexibility in the settings, but you can easily set the data link parameters using only memory addresses, and the settings will conform to Controller Link data link parameters. Refer to 3-9 Tag Data Link Parameters or SECTION 6 Tag Data Link Functions. 2. Using the Tag Data Link Setting Function in the Network Configurator to Set the Parameters With this method, you can set the connections that define the tag data links for each EtherNet/IP node. Tag data links can be set with a high degree of flexibility using both memory addresses and network variables. Refer to SECTION 6 Tag Data Link Functions for information on how to make these settings. Settings Required for the Message Communications Service Execute a CMND(490) instruction in the CS/CJ-series CPU Unit’s user program. Refer to SECTION 9 Message Communications. 35 Section 3-2 Switch Settings 3-2 3-2-1 Switch Settings CS-series EtherNet/IP Units Setting the Unit Number The unit number is used to identify individual CPU Bus Units when more than one CPU Bus Unit is mounted to the same PLC. Use a small screwdriver to make the setting, taking care not to damage the rotary switch. The unit number is factory-set to 0. UNIT No. Note Setting range: 0 to F (1) Turn OFF the power supply before setting the unit number. (2) If the unit number is being set for the first time or changed, then I/O tables must be created for the PLC. (3) With CS-series and CJ-series PLCs, words are automatically allocated in the CIO Area and DM Area according to the unit numbers that are set. For details, refer to SECTION 4 Memory Allocations. Setting the Node Address When there are multiple EtherNet/IP Units or Ethernet Units connected to the Ethernet network for the FINS communications service, the EtherNet/IP Units are identified by node addresses. Use the node address switches (NODE NO.) to set the node address between 01 and FE hexadecimal (1 to 254 decimal). Do not set a number that has already been set for another node on the same network. NODE NO. Setting range: 01 to FE (1 to 254 decimal) × 161 × 160 The left switch sets the sixteens digit (most significant digit) and the right switch sets the ones digit (least significant digit). The node address is factoryset to 01. Note Relationship to IP Addresses Turn OFF the power supply before setting the node address. When IP addresses are generated automatically (either dynamic or passive), the rightmost byte of the host ID of the IP address is set to the same value as the node address. (Refer to Section 5 Determining IP Addresses.) If the same node address value cannot be used, the IP address table method or the combined method must be used for address conversion. (For details, refer to SECTION 5 Determining IP Addresses.) If the FINS communications service is not being used on the Ethernet network, then it is all right for the same node address to be set on two or more EtherNet/IP Units. The setting, however, must be made within a range of 01 to FE. If a value outside of this range is set, the MS indicator will light red, the 7segment display will indicate code H4 (node address setting error), and the EtherNet/IP Unit will stop operating. 36 Section 3-2 Switch Settings 3-2-2 CJ-series EtherNet/IP Units and CJ2 Built-in EtherNet/IP Port Setting the Unit Number The unit number is used to identify individual CPU Bus Units when more than one CPU Bus Unit is mounted to the same PLC. Use a small screwdriver to make the setting, taking care not to damage the rotary switch. The unit number is factory-set to 0. UNIT No. Note Setting range: 0 to F (1) Turn OFF the power supply before setting the unit number. (2) If the unit number is being set for the first time or changed, then I/O tables must be created for the PLC. (3) With CS-series and CJ-series PLCs, dedicated areas are automatically allocated in the CIO Area and DM Area according to the unit numbers that are set. For details, refer to SECTION 4 Memory Allocations. Setting the Node Address With the FINS communications service, when there are multiple EtherNet/IP Units connected to the Ethernet network, the EtherNet/IP Units are identified by node addresses. Use the node address switches to set the node address between 01 and FE hexadecimal (1 to 254 decimal). Do not set a number that has already been set for another node on the same network. × 16 1 NODE No. × 16 0 Setting range: 01 to FE (1 to 254 decimal) The left switch sets the sixteens digit (most significant digit) and the right switch sets the ones digit (least significant digit). The node address is factoryset to 01. Note Relationship to IP Addresses Turn OFF the power supply before setting the node address. When IP addresses are generated automatically (either dynamic or passive), the rightmost byte of the host ID of the IP address of the EtherNet/IP Unit or built-in EtherNet/IP port is set to the same value as the node address. (Refer to Section 5 Determining IP Addresses.) If the same node address value cannot be used, the IP address table method or the combined method must be used for address conversion. (For details, refer to SECTION 5 Determining IP Addresses.) If the FINS communications service is not being used on the Ethernet network, then it is all right for the same node address to be set on two or more EtherNet/IP Units or built-in EtherNet/IP ports. The setting, however, must be made within a range of 01 to FE. If a value outside of this range is set, the MS indicator will light red, the 7-segment display will indicate code H4 (node address setting error), and the EtherNet/IP Unit or built-in EtherNet/IP port will stop operating. 37 Section 3-3 Mounting to a PLC 3-3 3-3-1 Mounting to a PLC Mounting to a CS-series PLC EtherNet/IP Units can be mounted to any slot in a CS-series CPU Rack or a CS-series Expansion CPU Rack, but the number of slots to which they can be mounted depends on the Backplane. Up to four EtherNet/IP Units can be mounted to a single PLC. If it is mounted in combination with other CPU Bus Units (e.g., Controller Link Units), the maximum total number of CPU Bus Units that can be mounted is 8. Note Tighten PLC Backplane mounting screws to a torque of 0.9 N⋅m, and the Unit’s screws to a torque of 0.4 N⋅m. PS CPU CS1W-BC023/BC033/BC053/BC083/BC103 CPU Backplane CS-series CPU Rack with 2, 3, 5, 8, or 10 slots Can be mounted in any slot. PS 2, 3, 5, 8, or 10 slots (Expansion Backplane not possible with 2-slot CPU Backplane.) CS1W-BI033/BI053/BI083/BI103 CS-series Expansion Backplane CS-series Expansion Rack with 3, 5, 8, or 10 slots. Can be mounted in any slot. Up to eight Units can be mounted to the slots shown in the diagrams on the left. 3, 5, 8, or 10 slots PS CS1W-BI033/BI053/BI083/BI103 CS-series Expansion Backplane CS-series Expansion Rack with 3, 5, 8, or 10 slots. Can be mounted in any slot. 3, 5, 8, or 10 slots Note 3-3-2 CPU: CPU Unit PS: Power Supply Unit The CS1W-EIP21 EtherNet/IP Unit’s maximum current consumption is 410 mA. Be sure that the total current consumption of all the Units connected to the same CPU Backplane or Expansion Backplane does not exceed the output capacity of the Power Supply Unit. Mounting to a CJ-series PLC EtherNet/IP Units can be mounted in a CJ-series CPU Rack or a CJ-series Expansion CPU Rack. Connect the EtherNet/IP Unit in any of the positions shown below using the sliders on the top and bottom of the Unit. Up to seven EtherNet/IP Units can be mounted for a CJ2H-CPU@@-EIP CPU Unit (enabling up to eight EtherNet/IP ports if you include the built-in EtherNet/IP port). Up to two EtherNet/IP Units can be mounted for a CJ2M-CPU3@ CPU Unit. If EtherNet/IP Units are mounted in combination with other CPU Bus Units (e.g., Controller Link Units), the maximum total number of CPU Bus Units that can be mounted is 16. 38 Section 3-3 Mounting to a PLC CPU Rack 10 Units max. End cover P C I S P C U Expansion Backplane 10 Units max. End cover P I S I Up to eight EtherNet/IP Units can be mounted. Expansion Backplane 10 Units max. End cover P I S I Expansion Backplane 10 Units max. End cover P I S I PS: Power Supply Unit CPU: CPU Unit IC: I/O Control Unit II: I/O Interface Unit Note The CJ1W-EIP21 EtherNet/IP Unit’s maximum current consumption is 410 mA. Be sure that the total current consumption of all the Units connected to the same CPU Backplane or Expansion Backplane does not exceed the output capacity of the Power Supply Unit. 3-3-3 Mounting Mount the EtherNet/IP Unit to the Backplane using the following procedure. 1,2,3... 1. Hook the claw on the top of the Unit onto the Backplane. Claw Backplane 2. Insert the Unit into Backplane connectors and securely tighten the screw at the bottom of the Unit. Tighten the screws to a torque of 0.4 N·m. 39 Section 3-3 Mounting to a PLC 3. When removing the Unit, first loosen the screw at the bottom of the Unit. Fixing screws Note When mounting the Unit, provide the clearance shown below to facilitate easy mounting or dismounting. Duct 20 mm min. Backplane 20 mm min. Duct Phillips screwdriver 3-3-4 Handling Precautions • Always turn OFF the power supply to the PLC before mounting or dismounting a Unit or connecting or disconnecting cables. • Provide separate conduits or ducts for the I/O lines to prevent noise from high-tension lines or power lines. • Leave the label attached to the Unit when wiring. Removing the label may result in malfunction if wire clippings or other foreign matter enters the Unit. Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction. Remove the label after wiring. EIP21 MS NS COMM 100M 10M NODE NO. UNIT NO. 0 161 1 0 IP AD DRES 192.16 SUBN 160 S 8.250. ET MA 255.25 40 1 SK 5.255. 100BAS E10BASE TX -T 0 Section 3-4 Network Installation 3-4 3-4-1 Network Installation Basic Installation Precautions • Take the greatest care when installing the Ethernet System, being sure to follow ISO 8802-3 specifications. You must obtain a copy of these specifications and be sure you understand them before attempting to install an Ethernet System. Unless you are already experienced in installing communications systems, we strongly recommend that you employ a professional to install your system. • Do not install Ethernet equipment near sources of noise. If a noisy environment is unavoidable, take adequate measures against noise interference, such as installing network components in grounded metal cases or using optical cable in the system. • When installing an EtherNet/IP network that combines an information system with the control system, and the communications load may be heavy due to tag data links, we recommend configuring the network so that the load does not affect communications. For example, install the tag data links in a segment that is separate from the information network. Note The maximum current consumption of the CS1W-EIP21 and CJ1W-EIP21 EtherNet/IP Units is 410 mA. Be sure that the total current consumption of all the Units connected to the same CPU Backplane or Expansion Backplane does not exceed the output capacity of the Power Supply Unit. 3-4-2 Recommended Products The following table shows the devices recommended for use with the EtherNet/IP Unit 2-3 Selecting the Network Devices. 3-4-3 Precautions Precautions on Laying Twisted-pair Cable • Noise resistance may be reduced by ground loops, which can occur due to improper shield connections and grounding. Ground the shield at one location, as shown in the following diagram. • Do not connect the shield to the EtherNet/IP Unit’s connector. • If a cable connects two hubs, connect the shields at only one end. Hub Connector GR Hub Connector Connector Connector Connect shield. Connector Do not connect shield. GR EIP Unit STP STP Connector Power Supply Unit GR terminal (Shield) (Shield) EIP Unit STP Connector Power Supply Unit GR terminal (Shield) 41 Section 3-4 Network Installation • Press the cable connector in firmly until it locks into place at both the switching hub and the EtherNet/IP Unit. • Do not lay the twisted-pair cable together with high-voltage lines. • Do not lay the twisted-pair cable near devices that generate noise. • Do not lay the twisted-pair cable in locations subject to high temperatures or high humidity. • Do not lay the twisted-pair cable in locations subject to excessive dirt and dust or to oil mist or other contaminants. Switching Hub Installation Environment Precautions • Do not ground the switching hub in the same location as a drive-system component such as an inverter. • Always use a dedicated power supply for the switching hub’s power supply. Do not use the same power supply used for other equipment, such as an I/O power supply, motor power supply, or control power supply. • Before installation, check the switching hub’s environment-resistance specifications, and use a switching hub appropriate for the ambient conditions. Contact the switching hub manufacturer for details on switching hub’s environment-resistance specifications. Switching Hub Connection Methods Connect two hubs to each other as follows: Connect an MDI port to an MDI-X port with a straight cable; connect two MDI ports with a cross cable; and connect two MDI-X ports with a cross cable. Note It is very difficult to distinguish cross cables and straight cables by appearance. Incorrect cables will cause communications to fail. We recommend using cascade connections with straight cables whenever possible. MDI ports MDI-X port (cross) Switching Hub Switching Hub Straight cable Cross cable Switching Hub Switching Hub Some switching hubs can automatically distinguish between MDI and MDI-X. When this kind of switching hub is being used, straight cable can be used between switching hubs. Note Adjust the link settings of the EtherNet/IP Unit or built-in EtherNet/IP port to match the communications settings of the connected switching hub. If the settings do not match, the link will become unstable and prevent normal communications. The following table shows the allowed settings for each switching hub communications mode. Switching hub setting Autonegotiation Auto-negotiation 10 Mbps Full duplex (fixed) Half duplex 42 Best --OK EtherNet/IP Unit setting 10 Mbps (fixed) 100 Mbps (fixed) Full Half Full Half duplex duplex duplex duplex --OK --OK OK --------OK ----- Section 3-4 Network Installation Switching hub setting Autonegotiation 100 Mbps Full duplex (fixed) Half duplex --OK EtherNet/IP Unit setting 10 Mbps (fixed) 100 Mbps (fixed) Full Half Full Half duplex duplex duplex duplex ----Best --------OK Note Best = Recommended; OK = Allowed; --- = Not allowed. 3-4-4 Using Contact Outputs (Common to All Units) When an EtherNet/IP Unit or built-in EtherNet/IP port and Contact Output Unit are mounted in the same Rack or connected to the same PLC, communications errors may occur due to noise generated by the contact outputs. Use one or more of the following measures when installing Contact Output Units and EtherNet/IP Units on the same Rack. Mounting Location Mount (or connect) any Contact Output Units as far away from the EtherNet/IP Unit or built-in EtherNet/IP port as possible. Contact Output Unit EtherNet/IP Unit To switching hub Contact outputs Cable Location Separate the transceiver cable or twisted-pair cable connecting the EtherNet/ IP Unit as far from the wiring to the Contact Output Units as possible. The coaxial cable must also be placed as far away from the Contact Output Units and their wiring as possible. Contact outputs Contact Output Unit EtherNet/IP Unit To switching hub 43 Section 3-5 Connecting to the Network 3-5 3-5-1 Connecting to the Network Ethernet Connectors The following standards and specifications apply to the connectors for the Ethernet twisted-pair cable. • Electrical specifications: Conforming to IEEE802.3 standards. • Connector structure: Connector pin 1 2 3 4 5 6 7 8 Hood 3-5-2 RJ45 8-pin Modular Connector (conforming to ISO 8877) Signal name Transmission data + Transmission data – Reception data + Not used. Not used. Reception data – Not used. Not used. Frame ground Abbr. TD+ TD– RD+ ----RD– ----FG Signal direction Output Output Input ----Input ------- Connecting the Cable !Caution Turn OFF the PLC’s power supply before connecting or disconnecting twistedpair cable. !Caution Allow enough space for the bending radius of the twisted-pair cable as shown in below. 35 mm 44 Section 3-5 Connecting to the Network 1,2,3... 1. Lay the twisted-pair cable. 2. Connect the cable to the switching hub. Be sure to press in the cable until it locks into place. 3. Connect the twisted-pair cable to the connector on the EtherNet/IP Unit. Be sure to press the connectors (both the switching hub side and Ethernet side) until they lock into place. Example: CS1W-EIP21 RJ45 Modular Connector EtherNet/IP Unit 45 Section 3-6 Creating I/O Tables 3-6 3-6-1 Creating I/O Tables I/O Table Overview I/O tables are used to identify Units mounted to the PLC, and to allocate I/O to them. With CS-series and CJ-series PLCs, whenever there is a change to the Unit configuration it is necessary to create I/O tables and register the mounted Units in the CPU Unit. The I/O tables can be created in the following ways. • Using the CX-Programmer offline. • Using the CX-Programmer online to create the I/O table based on the Units mounted to the PLC. • Using the Programming Console to create the I/O table based on the Units mounted to the PLC. • Using the CPU Unit's automatic I/O allocation at startup. (This method is available for the CJ Series only.) 3-6-2 Connecting Programming Devices to the PLC To create the I/O tables, connect a Programming Device (such as a CX-Programmer or Programming Console) to the PLC. Applicable Programming Devices The following Programming Devices can be used with CS/CJ-series PLCs. Programming Console Model number C200H-PRO27-E Key Sheet (required) CS1W-KS001-E CQM1-PRO01-E Recommended cable (required) CS1W-CN224 (cable length: 2.0 m) CS1W-CN624 (cable length: 6.0 m) CS1W-CN114 (cable length: 0.1 m) Note A Programming Console cannot be used with the CJ2H-CPU@@(-EIP) and CJ2M-CPU3@ CPU Units. Use the CX-Programmer. CX-Programmer For information on how to connect and operate the CX-Programmer, refer to the CX-Programmer Operation Manual (Cat. No. W446). Connecting a Programming Console To connect a Programming Console, attach a CS/CJ-series Key Sheet and then connect the Console to the CPU Unit’s peripheral port. (It cannot be connected to the RS-232C port.) 3-6-3 Procedure for Creating I/O Tables Programming Console This section provides the procedure for creating the I/O tables using a Programming Console. For details on using the Programming Console, refer to the Programming Console’s operation manual. Note 46 (1) With the CJ Series, it is necessary to create I/O tables only when the user is allocating I/O manually. With the CS Series, it is always necessary to create I/O tables. Section 3-6 Creating I/O Tables (2) With the CJ2H-CPU@@-EIP and CJ2M-CPU3@ CPU Units, the built-in EtherNet/IP port is set in the I/O tables by default and cannot be changed. It is not necessary to register it in the I/O tables. Use the following procedure to create the I/O tables. Initial screen SHIFT CH *DM 000000 I/O TBL ? CHG 000000 I/O TBL WRIT ???? WRITE Password 000000CPU BU ST? 0:CLR 1:KEEP or (Save or clear the CPU Bus Unit System Setup.) 000000 I/O TBL WRIT OK CX-Programmer (Version 8.0 or Higher) This section describes how to register an EtherNet/IP Unit or built-in EtherNet/ IP port in the I/O tables using the CX-Programmer (version 8.0 or higher). Refer to the CX-Programmer Operation Manual (Cat. No. W446) for details on the operating procedures. This section describes how to register the CJ1W-EIP21 in the I/O tables by creating the I/O tables on a computer with the CX-Programmer. In this example, the computer is connected to the PLC using a serial cable. The CJ1W-EIP21 is connected to a CJ1H-CPU67 CPU Unit. 1,2,3... 1. Start the CX-Programmer, and then select PLC − Auto Online − Direct Connection from the menus. 47 Creating I/O Tables Section 3-6 2. The Direct Online Dialog Box will be displayed. Select a serial connection, select the name of the applicable computer serial port, and then press the Connect Button. 3. If the connection process is successful, the system will be connected online. Here, check the operating mode of the PLC. If the operating mode is not PROGRAM mode, change the mode by selecting PLC − Operating Mode − Program from the menus. 4. Double-click IO Table and Unit Setup Icon in the project workspace in the CX-Programmer. The PLC IO Table Window will be displayed. Select Options − Create from the menus. 48 Section 3-6 Creating I/O Tables 5. The EtherNet/IP Unit will be displayed at the position it is mounted in the PLC. Note If it is not displayed, select Options − Transfer from PLC from the menus. Note Creating I/O tables is not required if the built-in EtherNet/IP port of a CJ2 CPU Unit is used. It is registered as a built-in port/Inner Board with a model number of CJ2B-EIP21 for the CJ2H and a model number of CJ2M-EIP21 for the CJ2M. You cannot delete a built-in port from the I/O tables. 49 Section 3-7 Setting the Local IP Address 3-7 Setting the Local IP Address This section describes the 3 ways to set the local I/O address of an EtherNet/ IP Unit or built-in EtherNet/IP port. Method 1: Using the default IP address: The default IP address is 192.168.250.Node_address. (The node address is set with the rotary switches on the front of the EtherNet/IP Unit or, for the built-in EtherNet/IP port, on the front of the CPU Unit.) → This method can be used to make a temporary or preliminary connection to the Ethernet. In this case, leave the TCP/IP Configuration and the allocated DM area IP address settings at their default values (0.0.0.0). Method 2: Setting an IP address in the CPU Unit’s allocated DM area: → If you want to set a particular local IP address and store that setting in the CPU Unit, set it in the EtherNet/IP Unit’s allocated DM area. The IP address can be set from the CX-Programmer, Programming Console, or ladder program. Method 3: Setting the TCP/IP Configuration from the CX-Programmer: → If you want to set a particular local IP address and store that setting in the EtherNet/IP Unit, set the IP address from the CX-Programmer. When FINS communications are being used, it is necessary to show the correspondence between the IP addresses and FINS node addresses. Refer to SECTION 5 Determining IP Addresses for an explanation of IP addresses as well as the correspondence between FINS node addresses and IP addresses. The three setting methods are described in the following paragraphs. Method 1: Using the Default IP Address (192.168.250.Node_address) When the EtherNet/IP Unit or built-in EtherNet/IP port is just mounted in the PLC and the I/O table is created, the EtherNet/IP Unit or built-in EtherNet/IP port will operate with its default IP address. This default address is enabled when the local IP address in the allocated DM area and the TCP/IP Configuration are both set to their defaults (0.0.0.0). The default IP address is 192.168.250.Node_address, where Node_address is the node address set with the rotary switches on the front of the EtherNet/IP Unit. This address is also used as the FINS node address. The following table shows the various settings in the Unit Setup when the IP address and TCP/IP Configuration are all set to their default values. Setting IP address Subnet mask Default gateway Preferred DNS server Alternate DNS server Host name Domain name Baud rate 50 Operating status 192.168.250.Node_address 255.255.255.0 (class C mask) None (IP routing disabled) None None None None Auto-detect Section 3-7 Setting the Local IP Address Method 2: Setting the Address in the CPU Bus Unit's Allocated DM Area With this method, an IP address is not set in the TCP/IP Configuration (left at its default setting), and an IP address is set in the allocated DM Area words (the IP Address Display/Setting Area in words m+98 and m+99). The IP address can be written in the two IP Address Display/Setting Area words using the CX-Programmer or the Programming Console. To enable the new IP Address setting, the EtherNet/IP Unit or built-in EtherNet/IP port must be restarted or the PLC’s power must be turned OFF and then ON again. Beginning word m = D30000 + (100 x unit number) 15 14 13 12 11 10 9 8 7 m+98 (1) (2) m+99 (5) (6) IP Address: (1)(2).(3)(4).(5)(6).(7)(8) (Hex) 6 5 4 3 (3) (7) 2 1 0 (4) (8) The following table shows the various Unit Setup when only the IP Address Display/Setting Area is set, and the other TCP/IP Configuration settings are left at their default values. Setting IP address Subnet mask Default gateway Preferred DNS server Alternate DNS server Host name Operating status IP address set in words m+98 and m+99 (IP Address Display/Setting Area) of the DM Area words allocated to the EtherNet/IP Unit as a CPU Bus Unit Determined by class of the IP address None (IP routing disabled) None None None Domain name Baud rate None Auto-detect Method 3: Setting the TCP/IP Configuration from the Network Configurator This method can be used to set IP addresses from the CX-Programmer. For details, refer to 3-8 TCP/IP and Link Settings. If the IP address is set in the TCP/IP Tab Page, that IP address setting will be displayed in the IP Address Display/Setting Area (words m+98 and m+99) in the DM Area words allocated to the Unit/port. 51 Section 3-8 TCP/IP and Link Settings 3-8 TCP/IP and Link Settings This section describes the TCP/IP-related settings, such as the local IP address and subnet mask for the EtherNet/IP Unit or built-in EtherNet/IP port. Use the CX-Programmer to make these settings. The settings are stored in non-volatile memory in the Unit. Note 3-8-1 Unlike the Ethernet Units, the TCP/IP settings of the EtherNet/IP Unit and built-in EtherNet/IP port are not stored in the CPU Unit’s CPU Bus Unit System Setup Area. Setting Procedure with the CX-Programmer 1,2,3... 1. When the EtherNet/IP Unit is registered in the I/O tables of the CX-Programmer, the EtherNet/IP Unit and built-in EtherNet/IP port will be displayed in the I/O tables. Refer to 3-6 Creating I/O Tables for details. 2. Right-click the EtherNet/IP Unit or built-in EtherNet/IP port in the I/O table and select Edit - Unit Setup from the menus. The Edit Parameters Dialog Box will be displayed. 3. Make the necessary settings on the TCP/IP Tab Page of the Edit Parameters Dialog Box. (The IP address is set here.) 52 Section 3-8 TCP/IP and Link Settings 4. Place the CX-Programmer online with the PLC and transfer the settings to the EtherNet/IP Unit or built-in EtherNet/IP port. 5. After transferring the settings, a message will ask if you want to restart the EtherNet/IP Unit or built-in EtherNet/IP port. The Unit/port must be restarted to enable the settings. 6. Check the 7-segment display for the EtherNet/IP Unit or built-in EtherNet/ IP port. 7. If the 7-segment display is tested again after it goes OFF, and finally displays the IP address, it indicates that the EtherNet/IP Unit has recognized the new TCP/IP Configuration settings (the IP address in this case). Note (1) The EtherNet/IP Unit or built-in EtherNet/IP port must restart in order to enable the parameter settings that are transferred to it. Verify that restarting the Unit/port will not cause any problems in the system before restarting it. (2) If the target node address (IP address) is not set correctly, invalid device parameters may be set in the wrong PLC, so check the connected PLC before downloading parameters. Settings on the TCP/IP Tab Page Settings for the following items are provided on the TCP/IP Tab Page of the Edit Parameters Dialog Box in the CX-Programmer. • IP address • Subnet mask • Default gateway • Broadcasting • Preferred DNS server • Alternate DNS server • Domain name • IP router table 53 Section 3-8 TCP/IP and Link Settings IP Address Sets the local IP address of the EtherNet/IP Unit or built-in EtherNet/IP port. Set the local IP address on the TCP/IP Tab Page when not setting the IP address in the CPU Unit’s allocated DM Area or using the default IP address (default IP address = 192.168.250.Node_address). When the IP address is set on the TCP/IP Tab Page, it will be stored as the IP address in the DM Area words allocated to the Unit/port as a CPU Bus Unit. Subnet Mask For the subnet mask, all bits corresponding to the bits in the IP address used as the network ID are set to 1, and the bits corresponding to the host number are set to 0. The EtherNet/IP Unit or built-in EtherNet/IP port supports CIDR (Classless Inter-Domain Routing). The subnet mask can be set to 192.0.0.0 to 255.255.255.252. (CIDR is supported by unit version 2.0 or later.) If no subnet mask is set, or if an illegal value is set, the following values will be used depending on the IP address class. In normal applications, we recommend setting the subnet mask defined for the class. Class Class A Class B Class C Subnet mask 255.0.0.0 255.255.0.0 255.255.255.0 With the default setting (0.0.0.0), a subnet mask corresponding to the IP address class is used. The following table shows the various parameters in the Unit Setup when only the IP address and subnet mask are set and other settings are left at their default values. Setting Default gateway Preferred DNS server Alternate DNS server Host name Domain name Broadcasting IP router table Operating status None (IP routing disabled) None None None None 4.3 BSD specifications None Default Gateway Sets the default gateway’s IP address. This setting is not required when the default gateway is not being used. Broadcasting Sets the IP address specification method for broadcasting with FINS/UDP. • All 1’s (4.3BSD): Broadcasting is performed with the host ID set to all 1’s. • All 0’s (4.2BSD): Broadcasting is performed with the host ID set to all 0’s. Normally, use the default setting of all 1’s (4.3BSD). Preferred DNS Server and Alternate DNS Server When accessing another node from the EtherNet/IP Unit or built-in EtherNet/ IP port using the host name, the DNS server searches for the other node’s IP address from the other node’s host name to the DNS server. These settings register the IP addresses of the preferred and alternate DNS servers that will perform the search. At this time, the EtherNet/IP Unit is not equipped with any 54 Section 3-8 TCP/IP and Link Settings functions that require a DNS server, so these settings are not used. (The functionality required to use a DNS server is not provided on EtherNet/IP Units with unit version 1.0. The DNS server cannot be used with these Units.) Domain Name Sets the domain name of the domain to which the EtherNet/IP Unit or built-in EtherNet/IP port belongs. The EtherNet/IP Unit or built-in EtherNet/IP port does not use a domain name in actual communications. IP Router Table Set the IP router table to route EtherNet/IP communications for specific nodes through an IP router other than the default gateway. Settings on the Ethernet Tab Page The following settings are provided on the Ethernet Tab Page of the Unit Setup for the EtherNet/IP Unit or built-in EtherNet/IP port. • Link settings (baud rate and half/full duplex) Link Setting Sets the communications baud rate. Setting Auto (default) 10 Mbps, Half Duplex 10 Mbps, Full Duplex 100 Mbps, Half Duplex 100 Mbps, Full Duplex Meaning The baud rate with the switching hub is detected automatically. If possible, the Unit operates in 100Base-T (full duplex). Operates in 10Base-T, half duplex. Operates in 10Base-T, full duplex. Operates in 100Base-TX, half duplex. Operates in 100Base-TX, full duplex. Note Adjust the EtherNet/IP Unit’s link settings to match the communications settings of the connected switching hub. If the settings do not match, the link will become unstable and prevent normal communications. The following table shows the allowed settings for each switching hub communications mode. Switching hub setting Autonegotiation Auto-negotiation 10 Mbps Full duplex (fixed) Half duplex 100 Mbps Full duplex (fixed) Half duplex Best --OK --OK EtherNet/IP Unit setting 10 Mbps (fixed) 100 Mbps (fixed) Full Half Full Half duplex duplex duplex duplex --OK --OK OK --------OK --------Best --------OK Note Best = Recommended; OK = Allowed; --- = Not allowed. 3-8-2 Making TCP/IP Settings with the Network Configurator Use the Network Configurator to change IP address settings for any device other than a CS/CJ-series EtherNet/IP Unit or built-in port. You can also use the Network Configurator to change IP address settings for a CS/CJ-series EtherNet/IP Unit or built-in port. 1,2,3... 1. Connect the Network Configurator online. Refer to 6-2-9 Connecting the Network Configurator to the Network for details on connecting the Network Configurator to the EtherNet/IP Unit. 55 TCP/IP and Link Settings Section 3-8 2. Select Tools - Setup TCP/IP Configuration to display the following Setup TCP/IP Configuration Dialog Box, and set the TCP/IP Configuration for the target device. In the following example, the settings are all at their default values. 3. Enter the IP address to set and press the Get from the Device Button. The present setting will be obtained. Change the IP address in the New Configuration Box if required. 4. Press the Set to the Device Button. The IP address will be transferred to the device. The applicable device is the device specified in the Target IP Address Box. The device must be reset to enable the transferred setting. If the device is not reset when the new IP address is transferred, click the Reset the Device Button. When the EtherNet/IP Unit is reset, the IP address will be displayed once in flowing text on the 7-segment display on the front of the Unit. Note 56 (1) The transfer function for IP address settings is defined by ODVA specifications. Target devices that do not support these specifications cannot be set. When setting the IP address of the target device with the Network Section 3-9 Tag Data Link Parameters Configurator, connect the devices one at a time, and download the TCP/ IP Configuration’s IP address parameters. If TCP/IP parameters are set for the EtherNet/IP Unit or built-in EtherNet/IP port from the Network Configurator, the EtherNet/IP Unit may automatically be reset and restarted. Before setting the TCP/IP parameters, make sure that no system problems will occur when the Unit is restarted. If the Unit does not restart automatically, click the Reset the Device Button. (2) If the target node address (IP address) is not set correctly, invalid device parameters may be set in the wrong PLC, so check the connected PLC before downloading parameters. TCP/IP Parameters The following TCP/IP parameters can be set from the Network Configurator. • IP address • Subnet mask • Default gateway • Preferred DNS server • Alternate DNS server • Domain name • Link parameters (baud rate and full/half duplex) 3-9 Tag Data Link Parameters Set the following parameters when using tag data links with an EtherNet/IP Unit or built-in EtherNet/IP port. The parameter settings are saved in flash memory in the EtherNet/IP Unit or CPU Unit. (See note.) Note The CPU Bus Unit Setup Area is not used for tag data link settings for an EtherNet/IP Unit or built-in EtherNet/IP port. This point is different from the operation of Ethernet Units. Refer to SECTION 6 Tag Data Link Functions for details. 3-9-1 Network Configurator Setting Procedure The methods for setting tag data links using the Network Configurator can be roughly divided into the following two. 1. Using the EtherNet/IP Datalink Tool in the Network Configurator to Set the Parameters With this method, there is no flexibility in the settings, but you can easily set the data link parameters using only memory addresses, and the settings will conform to Controller Link data link parameters. 2. Using the Tag Data Link Setting Function in the Network Configurator to Set the Parameters With this method, you can set the connections that comprise the tag data links for each EtherNet/IP node. Tag data links can be set with a high degree of flexibility using both memory addresses and network variables. Refer to SECTION 6 Tag Data Link Functions for details on how to perform these settings. This section presents a setting example using the EtherNet/IP Datalink Tool. Using the EtherNet/IP Datalink Tool The method that is described here is used to set memory addresses in tables to specify data links between EtherNet/IP Units or built-in EtherNet/IP ports on CS/CJ-series PLCs. 57 Section 3-9 Tag Data Link Parameters The following method can be used to easily set the data links shown in the following figure using a wizard in the EtherNet/IP Datalink Tool. Node #1: CJ1H-CPU67H (IP address: 192.168.250.1) Node #2: CJ1H-CPU67H (IP address: 192.168.250.2) Node #3: CJ1H-CPU67H (IP address: 192.168.250.3) EtherNet/IP Area 1 W0 W0 50 words #1 W50 50 words #2 #2 #2 W100 50 words #3 #3 #3 D50 100 words #1 D150 100 words #2 #2 #2 D250 100 words #3 #3 #3 #1 W0 #1 Area 2 1,2,3... D50 #1 D50 #1 1. Start the Network Configurator, select the applicable EtherNet/IP Unit in the Tree View on the left, and then paste it into the Device Configuration Pane on the right. Note If an EtherNet/IP system has already been installed, you can create a similar device configuration by connecting to the EtherNet/IP network and selecting Network − Upload from the menus. Refer to 6-2-9 Connecting the Network Configurator to the Network for information on connecting. 2. Select Network − EtherNet/IP Datalink Tool from the menus to start the EtherNet/IP Datalink Tool. 58 Tag Data Link Parameters Section 3-9 3. Select Datalink − Wizard from the menus in the Datalink Tool when it has started. 4. In the Datalink Wizard Dialog Box, enter 50 words starting from memory address W000 for area 1 and 100 words starting from D00050 for area 2, and then press the OK Button. 5. The data link settings will be automatically created in the window of the EtherNet/IP Datalink Tool. Select File − Save to end. The settings will be saved in the Network Configurator. 59 Tag Data Link Parameters Section 3-9 6. In the Device Configuration Window of the Network Configurator, a mark will be added to each EtherNet/IP Unit to show that data links have been set. 7. Connect the Network Configurator to the EtherNet/IP network and select Network − Download from the menus. The data link settings will be downloaded to the EtherNet/IP Units, and the data links will operate. 60 Section 3-10 Other Parameters 3-10 Other Parameters In addition to the tag data link parameters, the EtherNet/IP Unit and built-in EtherNet/IP port also have the following communications and operation parameters. • FINS/UDP • FINS/TCP • FTP • Auto Adjust Time • Status Area • SNMP • SNMP Trap These parameters are set as Unit Setup from the CX-Programmer. The parameter settings are saved in flash memory in the EtherNet/IP Unit or CPU Unit. (See note.) Note The CPU Bus Unit Setup Area is not used for tag data link settings for an EtherNet/IP Unit or built-in EtherNet/IP port. This point is different from the operation of Ethernet Units. Using FINS/UDP Tab Page in Edit Setting Parameters Dialog Box FINS/UDP FINS/UDP Port Conversion IP Address Table Dynamic change the target IP addresses Function Specifies the local UDP port number to use in the FINS communications service. The UDP uses the UDP port number to distinguish the application layer (FINS communications service in this case). • Default value (9,600) • User-set value (1 to 65,535) Selects one of the following methods to convert from the FINS node address to an IP address (FINS/UDP only). • Automatic generation (dynamic setting) • Automatic generation (static setting) • IP address table • Combined method Sets the IP address table that defines the relationship between FINS node addresses and IP addresses. This table is effective only when FINS/UDP is being used and the IP address conversion method is set to the IP address table. Selects dynamic change of other FINS/UDP nodes’ IP addresses. To disable dynamic changes, deselect this option by removing the check mark. When necessary, set the routing tables using the CX-Integrator. 61 Section 3-10 Other Parameters Using FINS/TCP Tab Page in Edit Setting Parameters Dialog Box FINS/TCP FINS/TCP Port FINS/TCP Connection Setup Protection Setting Function Specifies the local TCP port number to use in the FINS communications service. The TCP uses the TCP port number to distinguish the application layer (FINS communications service in this case). • Default value (9,600) • User-set value (1 to 65,535) This is the network API used when TCP is used for the FINS communications service. Up to 16 APIs can be used at a time, and they are identified by connection numbers 1 to 16. The EtherNet/IP Unit or built-in EtherNet/IP port can thus simultaneously execute the FINS communications service by TCP with up to 16 remote nodes. Select this check box to refuse connection requests from any IP address not set as the target IP address when the server/client setting is set to a server and the target IP address is set to any value other than 0.0.0.0. This check box can be selected to prevent inappropriate operations on the PLC for FINS commands from specific nodes. When necessary, set the routing tables using the CX-Integrator. Using FTP Tab Page in Edit Setting Parameters Dialog Box FTP Not Use FTP or Use FTP Login Password Port No. 62 Function Specifies whether to use FTP. FTP connections from external devices will not be possible if Not Use FTP is specified. Sets the login name for FTP connections to the EtherNet/IP Unit or built-in EtherNet/IP port from external devices Sets the password for FTP connections to the EtherNet/IP Unit or built-in EtherNet/IP port from external devices. Sets the FTP port number of the EtherNet/IP Unit or built-in EtherNet/IP port. It is normally not necessary to change this setting. Two ports are used with the FTP: a control port and a data transfer port. Only the control port can be set. The data transfer port number will be one larger than the control port number. Section 3-10 Other Parameters Using the Automatic Time Adjustment Tab Page in Edit Setting Parameters Dialog Box Auto Adjust Time Not get the time information from the SNTP server or Get the time information from the SNTP server Auto Adjust time Function Specifies whether to set the clock in the CPU Unit to the time on the SNTP server. The time can be set only in CPU Units with an EtherNet/IP Unit or a built-in EtherNet/IP port. Sets the time to access the SNTP server to automatically adjust the CPU Unit clock. When the specified time arrives, the SNTP server will be accessed and the clock in the CPU Unit will be set to the time on the SNTP server. Server Specification Type Specifies whether to use an IP address or a domain name (i.e., host name) to specify the SNTP server to use for automatic time adjustment. IP Address Sets the IP address of the SNTP server to use for automatic time adjustment. This IP address is valid only when the Server Specification Type is set to an IP address. Host Name Sets the host name of the SNTP server to use for automatic time adjustment. This IP address is valid only when the Server Specification Type is set to a host name. Port No. Sets the port number to use to connect to the SNTP server for automatic time adjustment. It is normally not necessary to change this setting. Retry Timer Sets the time to wait before retrying the connection when connecting to the SNTP server fails. It is normally not necessary to change this setting. Adjust Time Sets the time to offset the clock in the CPU Unit when setting the clock in the CPU Unit to the time obtained from the SNTP server. To use the time from the SNTP server as is, enter 0 for the Adjust Time. Using the Status Area Tab Page in Edit Setting Parameters Dialog Box Status Area Layout Type Allocation Area Function Specifies whether to use the default setting or a custom setting for the words allocated to the status area. Sets the first word in the status area when the Layout Type is set for a customer setting. With CS1/CJ1 CPU Units, only an I/O memory address can be set. With CJ2 or NE1S CPU Units, either an I/O memory address or a symbol defined in the CPU Unit can be set. 63 Section 3-10 Other Parameters Using SNMP Tab Page in Edit Setting Function Parameters Dialog Box SNMP Not use SNMP service or Specifies whether to use the SNMP. Use SNMP service If not using the SNMP service is specified, an SNMP manager will not be able to connected from an external device. SNMP Port Sets the port number to use when connecting from an SNMP manager. It is normally not necessary to change this setting. SNMP Contact Informa- Specifies the contact information as text. tion This information can be read from the SNMP manager. SNMP Location Informa- Specifies the location information as text. tion This information can be read from the SNMP manager. Authentication Check 1/2 Specifies the SNMP managers that can access the PLC. To restrict access to only specific SNMP managers, specify the SNMP managers using IP addresses or host names. Community names can also be specified (e.g., public). Ether one or two settings can be made. Using SNMP Trap Tab Page in Edit Setting Parameters Dialog Box SNMP Trap Not use SNMP Trap service or Use SNMP Trap service SNMP Trap Port Trap 1/2 64 Function Specifies whether to use the SNMP trap. If not using the SNMP trap service is specified, SNMP traps cannot be sent to the SNMP manager. Sets the port number to use to connect to the SNMP manager. It is normally not necessary to change this setting. Sets the SNMP manager destinations for SNMP traps. The SNMP managers can be specified using IP addresses or host names. Community names can also be specified (e.g., public). Either one or two trap destinations can be set. Section 3-11 Communications Test 3-11 Communications Test If the basic settings (in particular the IP address and subnet mask) have been made correctly for the EtherNet/IP Unit or built-in EtherNet/IP port, then it should be possible to communicate with nodes on the EtherNet/IP network. This section describes how to use the PING command to test communications with the EtherNet/IP Unit or built-in EtherNet/IP port. 3-11-1 PING Command The PING command sends an echo request packet to a remote node and receives an echo response packet to confirm that the remote node is communicating correctly. The PING command uses the ICMP echo request and responses. The echo response packet is automatically returned in the ICMP. The PING command is normally used to check the connections of remote nodes when configuring a network. The EtherNet/IP Unit or built-in EtherNet/ IP port supports both the ICMP echo request and reply functions. If the remote node returns a normal response to the PING command, then the nodes are physically connected correctly and Ethernet node settings are correct. EtherNet/IP Unit Remote Node (host computer or EtherNet/IP Unit) TCP ICMP UDP IP Ethernet Echo request Echo response 3-11-2 EtherNet/IP Unit or Built-in EtherNet/IP Port Operation The EtherNet/IP Unit or built-in EtherNet/IP port automatically returns the echo response packet in response to an echo request packet sent by another node (host computer, or other EtherNet/IP Unit or built-in EtherNet/IP port). An echo request packet can be sent to another node by issuing the FINS command to execute the PING command from the PLC. 3-11-3 Host Computer Operation The PING command can be executed from the host computer to send an echo request packet to an EtherNet/IP Unit or built-in EtherNet/IP port. The following example shows how to use the PING command in the host computer. Command Method Input the following command at the host computer’s prompt ($): $ ping IP_address(host_name) The destination is specified by its IP address or host name. If the host name is used, the host name must be defined in the /etc/hosts file. Note The PING command is not supported by some host computers. 65 Section 3-11 Communications Test Application Example In this example, a PING command is sent to the node at IP address 130.25.36.8. The “$” in the example represents the host computer prompt. Normal Execution $ ping 130.25.36.8 ← Executes the PING command. PING 130.25.36.8: 56 data bytes 64 bytes from 130.25.36.8: icmp_seq=0. time=0. ms 64 bytes from 130.25.36.8: icmp_seq=0. time=0. ms : : : : : 64 bytes from 130.25.36.8: icmp_seq=0. time=0. ms ← Press the Ctrl+C Keys to cancel execution. ---- 130.25.36.8 PING Statistics ---9 packets transmitted, 9 packets received, 0% packets loss round-trip (ms) min/avg/max = 0/1/16 $ Error Occurred $ png 130.25.36.8 PING 130.25.36.8: 56 data bytes ← Executes the PING command. ← Press the Ctrl+C Keys to cancel execution. ---- 130.25.36.8 PING Statistics ---9 packets transmitted, 9 packets received, 0% packets loss $ Refer to the OS command reference manual for your computer for details on using the PING command. 66 SECTION 4 Memory Allocations This section describes the words allocated in the CIO Area and the DM Area for EtherNet/IP Units or built-in EtherNet/IP ports. 4-1 4-2 4-3 4-4 4-5 Overview of Memory Allocated to the EtherNet/IP Unit . . . . . . . . . . . . . . . . 68 CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 4-2-1 Overview of the Allocated CIO Area Words . . . . . . . . . . . . . . . . . . 70 4-2-2 Details of the Allocated CIO Area Words . . . . . . . . . . . . . . . . . . . . 71 DM Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 4-3-1 Overview of the Allocated DM Area Words . . . . . . . . . . . . . . . . . . 83 4-3-2 Details of the Allocated DM Area Words. . . . . . . . . . . . . . . . . . . . . 83 User Settings Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 4-4-1 Overview of the User Settings Area . . . . . . . . . . . . . . . . . . . . . . . . . 85 4-4-2 User Settings Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Auxiliary Area Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 4-5-1 Read-only Bits/Words. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 4-5-2 Read/Write Bits (User Settings) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 67 Overview of Memory Allocated to the EtherNet/IP Unit 4-1 Section 4-1 Overview of Memory Allocated to the EtherNet/IP Unit The following CPU Unit words are allocated to the EtherNet/IP Unit or built-in EtherNet/IP port. • CPU Unit’s allocated CIO Area words Contains software switch and status information. • CPU Unit’s allocated DM Area words Contains the IP Address Display/Setting Area • CPU Unit’s user settings area Contains status information. (This area can be used only when the allocated CIO Area words are set to user settings.) Note The EtherNet/IP Unit or built-in EtherNet/IP port has the following two data areas in its non-volatile memory. (Unlike the Ethernet Units, settings are not stored in the CPU Unit’s CPU Bus Unit System Setup Area.) • Unit Setup: Settings such as the IP address and FINS/UDP settings. The Unit Setup is set from the CX-Programmer. • Device parameter settings: Settings such as the tag data link setting parameters. The device parameter settings are made from the Network Configurator. 68 Section 4-1 Overview of Memory Allocated to the EtherNet/IP Unit CPU Unit EtherNet/IP Unit ● Allocated CIO Area words (Allocated to the Unit as a CPU Bus Unit.) Unit number 0 Local memory CIO 1500 CIO 1501 Flags and control bits 25 words CIO 1524 CIO 1525 Unit number 1 25 words 25 words Target node PLC's operating and error information, Unit status, communications status, registered/normal target node, and FINS/TCP connection status CIO 1549 CIO 1875 Unit number 15 25 words CIO 1899 ● User Settings Area Local memory Set in Network Configurator. → 64 words 64 words Target node PLC's operating and error information, and registered/normal target node ● Allocated DM Area words (Allocated to the Unit as a CPU Bus Unit.) Local memory D30000 Unit number 0 100 words D30098 D30099 D30100 Unit number 1 IP Address Display/Setting Area 100 words Non-volatile memory in the EtherNet/IP Unit Unit settings D30199 D31500 Unit number 15 100 words 100 words D31599 Settings such as the IP address of the EtherNet/IP Unit and FINS/UDP settings. Refer to 3-8 TCP/IP and Link Settings and 3-10 Other Parameters for details. Device parameter settings (tag data link settings) Refer to Section 6 Tag Data Links for details. Network Configurator 69 Section 4-2 CIO Area Allocations 4-2 CIO Area Allocations 4-2-1 Overview of the Allocated CIO Area Words The various kinds of data are stored in the allocated CIO Area words, which are identified by the offset from the beginning word (n) allocated to each Unit. There are two patterns for the layout of the allocated CIO Area words: the default settings and user settings. The layout can be selected in the Status Area settings in the Edit Parameters Dialog Box from the CX-Programmer. To set a customer areas, select User defined for the Layout Type on the Status Area Tab Page. The beginning word n is calculated by the following equation: Beginning word n = CIO 1500 + (25 × unit number) Default Settings Offset Bit 15 8 0 Data direction CPU Unit → EtherNet/IP Unit 0 n 1 n+1 (Reserved) EtherNet/IP Unit → CPU Unit 2 n+2 Target Node PLC Operating Information EtherNet/IP Unit → CPU Unit 3 n+3 (4 words only) 4 n+4 5 n+5 6 EtherNet/IP Unit → CPU Unit n+6 Target Node PLC Error Information 7 n+7 (4 words only) 8 n+8 9 n+9 10 n+10 Unit status 1 11 n+11 Unit status 2 12 n+12 Communications status 1 13 n+13 Communications status 2 14 n+14 Communications status 3 15 n+15 (Reserved) EtherNet/IP Unit → CPU Unit 16 n+16 Registered Target Node EtherNet/IP Unit → CPU Unit 17 n+17 (4 words only) 18 n+18 19 n+19 20 n+20 Normal Target Node 21 n+21 (4 words only) 22 n+22 23 n+23 24 n+24 FINS/TCP Connection Status Note 70 7 Unit control bits EtherNet/IP Unit → CPU Unit EtherNet/IP Unit → CPU Unit EtherNet/IP Unit → CPU Unit EtherNet/IP Unit → CPU Unit The reserved words are regularly refreshed with all zeroes. Section 4-2 CIO Area Allocations User Settings Offset Bit 15 8 7 0 Data direction Unit control bits CPU Unit → EtherNet/IP Unit (Reserved) EtherNet/IP Unit → CPU Unit n+10 Unit status 1 EtherNet/IP Unit → CPU Unit 11 n+11 Unit status 2 12 n+12 Communications status 1 13 n+13 Communications status 2 14 n+14 Communications status 3 15 n+15 (Reserved) EtherNet/IP Unit → CPU Unit 16 n+16 17 n+17 18 n+18 19 n+19 20 n+20 21 n+21 22 n+22 23 n+23 24 n+24 FINS/TCP Connection Status EtherNet/IP Unit → CPU Unit 0 n 1 n+1 2 n+2 3 n+3 4 n+4 5 n+5 6 n+6 7 n+7 8 n+8 9 n+9 10 Note EtherNet/IP Unit → CPU Unit The reserved words are regularly refreshed with all zeroes. The functions of the allocated CIO Area words are described in the following section. 4-2-2 Details of the Allocated CIO Area Words Unit Control Bits (CPU Unit to EtherNet/IP Unit) (n) 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n Tag Data Link Start Bit Tag Data Link Stop Bit Adjust Clock Bit Bit 0 to 1 2 Switch (Not used.) Tag Data Link Start Bit Status --ON Manipulated by --User OFF Unit Unit operation --The tag data link starts when this bit is switched from OFF to ON. Turned OFF by Unit after the tag data link starts operating. 71 Section 4-2 CIO Area Allocations Bit 3 4 5 6 to 15 Tag Data Link Start Bit (Bit 2) Switch (Not used.) Tag Data Link Stop Bit Adjust Clock Bit (Not used.) Status Manipulated by --ON --User OFF Unit ON User OFF Unit --- --- Unit operation --The tag data link stops when this bit is switched from OFF to ON. Turned OFF by Unit after the tag data link stops operating. The clock time is automatically adjusted when this bit is switched from OFF to ON. Turned OFF by Unit after the clock time has been adjusted. --- Start the tag data links by switching this bit from OFF to ON. If the tag data links are already operating, the signal will be ignored. The tag data link starts operating automatically after the tag data link parameter settings are downloaded from the Network Configurator, the CPU Unit’s power is turned ON, or the Unit is restarted. If the tag data links have been stopped by turning the Tag Data Link Stop Bit (n bit 04) from OFF to ON, the tag data links can be restarted by turning this Tag Data Link Start Bit (n bit 02) from OFF to ON. Once the tag data links start, the EtherNet/IP Unit automatically turns OFF the Tag Data Link Start Bit. Do not force this bit ON or OFF until it is automatically turned OFF by the Unit. Tag Data Link Stop Bit (Bit 4) Stop the tag data links by switching this bit from OFF to ON. Once the tag data links have been stopped, they will remain stopped until the Unit is restarted or the Tag Data Link Start Bit is turned ON. (The tag data links will also start operating automatically when the tag data link parameter settings are downloaded from the Network Configurator.) If the tag data links are already stopped, the signal will be ignored. Message communications can be performed while the tag data links are stopped. Once the tag data links have stopped, the EtherNet/IP Unit automatically turns OFF the Tag Data Link Stop Bit. Do not force this bit ON or OFF until it is automatically turned OFF by the Unit. Adjust Clock Bit (Bit 5) Automatically adjust the time on the clock by switching this bit from OFF to ON. The SNTP server used to adjust the time is set in the Unit Setup. Once the clock time has been adjusted, the EtherNet/IP Unit automatically turns OFF the Adjust Clock Bit. Do not force this bit ON or OFF until it is automatically turned OFF by the Unit. Target Node PLC Operating Information (EtherNet/IP Unit to CPU Unit) (n + 2 to n + 5) These words show the operating status of the target node PLCs that are connected with the EtherNet/IP Unit as the originator. This status information is enabled when the PLC status is included in the communications data in both the originator and target node. These words show the status of nodes 0 to 63 only. If it is necessary to show the status of nodes higher than node 63, select “user settings” as the layout pattern. For details, refer to 4-4 User Settings Area. The flags are valid only when the corresponding Normal Target Node Flag is ON. If the corresponding Normal Target Node Flag is OFF, the Target Node PLC Operating Flag indicates the previous operating status. 72 Section 4-2 CIO Area Allocations 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+2 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+3 n+4 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 n+5 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 Bit --- Target Node PLC Error Information (EtherNet/IP Unit to CPU Unit) (n + 6 to n + 9) Name Status Target Node PLC Operating Flags ON Manipulated by Unit OFF Unit Unit operation The corresponding PLC is operating. (The program is being executed.) The PLC is not operating. These words show the error status (logical OR of fatal and non-fatal errors) of the target node PLCs that are connected with the EtherNet/IP Unit as the originator. This status information is enabled when the PLC status is included in the communications data in both the originator and target node. These words show the error status of nodes 0 to 63 only. If it is necessary to show the error status of nodes higher than node 63, select “user settings” as the layout pattern. For details, refer to 4-4 User Settings Area. The flags are valid only when the corresponding Normal Target Node Flag is ON. If the corresponding Normal Target Node Flag is OFF, the Target Node PLC Error Flag indicates the previous error status. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+6 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+7 n+8 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 n+9 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 Bit --- Name Status Target Node PLC Error Flags ON Manipulated by Unit OFF Unit Unit operation A fatal or non-fatal error occurred in the corresponding PLC. No error occurred in the PLC. Unit Status 1 (EtherNet/IP Unit to CPU Unit) (n + 10) 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+10 Unit Error Occurred Network Error Occurred Unit Memory Error Communications Controller Error IP Address Duplication Error Link OFF Error Status Area Layout Setting Error 73 Section 4-2 CIO Area Allocations Bit 74 Name 0 Unit Error Occurred 1 Network Error Occurred 2 to 3 4 (Not used) Unit Memory Error 5 Communications Controller Error 6 IP Address Duplication Error 7 to 8 9 (Not used) Link OFF Error Status Manipulated Unit operation by ON Unit Indicates that an error occurred that is related to EtherNet/IP Unit operation. This flag is turned ON when any bit in Unit Status 1 is ON. (Bits 1 to 15 are logically ORed.) OFF Unit Indicates that a Unit error did not occur. This flag is turned OFF when the error is cleared. ON Unit One or more networkrelated errors occurred. (The bits in Communications Status 1 and 3 are logically ORed.) OFF Unit Indicates that a network error did not occur. This flag is turned OFF when the error is cleared. ------ON Unit Indicates that an error occurred in accessing the Unit’s internal non-volatile memory (device error). OFF Unit Indicates that a non-volatile memory error did not occur. This flag is not cleared even if it occurs one time. (Flag remains ON.) ON Unit Indicates that an error occurred in the communications controller. OFF Unit Indicates that a communications controller error did not occur. This flag remains ON until the power supply is turned OFF and ON again. ON Unit An ARP was sent with the specified IP address, indicating that an IP address duplication was detected. An address duplication is detected if there is an ARP response. This flag remains ON until the power supply is turned OFF and ON again. (The Ethernet interface will stop.) OFF Unit There was no ARP response. ------ON Unit There was an error establishing a link with the switching hub. OFF Unit A link was established normally with the switching hub. Section 4-2 CIO Area Allocations Bit Name 10 to 13 14 (Not used) Status Area Layout Setting Error 15 Unit Status 2 (EtherNet/IP Unit to CPU Unit) (n + 11) Status Manipulated by ------- (Not used) 15 14 13 12 11 10 9 8 7 ON Unit OFF Unit --- --- 6 5 4 3 Unit operation Indicates that there was an error in the allocated CIO Area’s layout settings. When this error occurs, the allocated CIO Area layout is set to the default pattern. In the following cases, however, the allocated CIO Area layout is set to the user-set pattern. In this case, the user-set area will not be refreshed. • A non-existent area has been specified. There was not an error in the layout settings. --- 2 1 0 n+11 Online Tag Data Link Operating User Settings Area Enabled Operating IP Address Change Multiple Switches ON Error Error Log Stored Bit 0 Name Online Status Manipulated Unit operation by ON Unit Indicates that the Unit is online. (The EtherNet/IP Unit can perform communications processing.) OFF Unit Indicates that the Unit is not online. This bit is turned OFF in the following cases. • IP Address Duplication Error • Ethernet Communications Controller Error (hardware error) • BOOTP Server Error 75 Section 4-2 CIO Area Allocations Bit 1 2 Name Tag Data Link Operating ON Unit OFF Unit ON Unit OFF Unit --ON --Unit OFF Unit (Not used) --- --- Multiple Switches ON Error ON Unit OFF Unit Operating IP Address Change 3 to 10 (Not used) 11 User Setting Area Enabled 12 to 13 14 76 Status Manipulated by Unit operation Indicates that the tag data link is operating. Turned OFF when communications stop in the following cases. • Hardware error • IP Address Duplication Error • BOOTP Server Error • Basic Ethernet Settings Error • Memory Error (MAC Address Error) Indicates that the tag data link is stopped. Turned ON in the following cases. • The Unit is set as the originator and the power supply was turned ON or the Unit was restarted. • The Unit is set as the originator and the Tag Data Link Start Bit was turned ON. ON if the node address setting is different from the setting when the power was turned ON. OFF if the node address setting is the same as the setting when the power was turned ON. --Indicates that the user settings area data is enabled. ON when “user settings” have been specified as the layout of the allocated CIO Area, and refreshing of the user settings area has started. Indicates that the user settings area data is invalid. The bit is turned OFF in the following cases, because communications stop. • The allocated CIO Area layout is set to default settings. • The allocated CIO Area layout is set to user settings, but one of the following problems occurred. • A Layout Setting Error occurred. --ON when two or more control bits are ON simultaneously. (Unused bits are ignored.) Turned OFF when the next control bit operation starts. Section 4-2 CIO Area Allocations Bit Name 15 Communications Status 1 (EtherNet/IP Unit to CPU Unit) (n + 12) Status Manipulated by Error Log Stored ON Unit OFF Unit Unit operation Indicates that an error record is registered in the error log. Indicates that no error records are registered in the error log. Also turned OFF when an error log clear request is received. Word n+12 contains status flags related to the tag data links, as shown in the following diagram. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+12 Verification Error Tag Data Link Error All Tag Data Links Operating Invalid Communications Parameter Tag Refresh Error Tag Database Error Tag Data Links Operating Bit 0 1 2 3 Name Status Manipulated Unit operation by Verification Error ON Unit Indicates that the information registered for a target node in the tag data link parameters is different from the actual node information. Main causes: • The specified target does not exist. • The variable name does not match. • The connection size is different. • Connection resources are insufficient. OFF Unit Indicates that a verification error has not occurred. Also turned OFF when a verification error is cleared. (Not used) ------Tag Data Link Error ON Unit Indicates that there were two or more errors in a connection as an originator. This status does not indicate the following errors. • Connection as a target • Connection timeout due to a Link OFF Error with the switching hub OFF Unit Indicates that the errors listed above did not occur. (Not used) ------- 77 Section 4-2 CIO Area Allocations Bit 4 5 6 Name Invalid Communications Parameter Tag Refresh Error Tag Database Error 7 to 13 (Not used) 14 All Tag Data Links Operating 15 78 Tag Data Links Operating Status Manipulated by ON Unit OFF Unit ON Unit OFF Unit ON Unit OFF Unit --ON --Unit OFF Unit ON Unit OFF Unit Unit operation ON when there was an error in the validation check of tag data link parameters stored in the Unit’s non-volatile memory, and a checksum error occurred. (Includes parameters related to basic Ethernet settings.) The tag data links will stop. OFF when the validation check of parameters in nonvolatile memory was normal. ON when a specified data area or address range is not supported in tag data links. OFF when the specified data areas and addresses are supported in tag data links. ON if a tag database error occurs in the CPU Unit when a symbol name is used incorrectly in a setting for the EtherNet/IP Unit or built-in EtherNet/IP port (tag data link, status area allocations setting, etc.). (CJ2H-CPU6@EIP or CJ2M-CPU3@ only) OFF when a symbol name is not used in a setting for the EtherNet/IP Unit or built-in EtherNet/IP port, when a tag database error has not occurred, or when a previous error has been cleared. --Indicates that tag data links are communicating in all connections as the originator. Indicates that a tag data link failed in on or more connections as the originator. (OFF even if some tag data links are communicating.) Indicates that tag data links are communicating in one or more connections as the originator. Indicates that not even one tag data link is communicating in connections as the originator. (OFF even if the Unit is communicating as a target.) CIO Area Allocations Section 4-2 Communications Status 2 (EtherNet/IP Unit to CPU Unit) (n + 13) Word n+13 contains status flags related to the Ethernet, as shown in the following diagram. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+13 Link Status Bit FTP Status Name 0 Status Manipulated Unit operation by ON Unit ON when the FTP server is operating (i.e., when there is an FTP client connection). OFF Unit OFF when the FTP is on standby (i.e., waiting for a client connection). ------ON Unit ON when a link is established with the switching hub. OFF Unit OFF when the link with the switching hub is stopped. ------- FTP Status 1 to 13 (Not used) 14 Link Status 15 Communications Status 3 (EtherNet/IP Unit to CPU Unit) (n + 14) (Not used) Word n+14 contains status flags related to the Ethernet errors, as shown in the following diagram. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+14 Basic Ethernet Settings Error IP Address Table Error IP Router Table Error Routing Table Error Ethernet Expansion Settings Error BOOTP Server Error Address Mismatch Non-volatile Memory Error Bit 0 to 1 2 3 Name (Not used) Basic Ethernet Settings Error IP Address Table Error Status Manipulated Unit operation by ------ON Unit One of the following parameters is invalid. OFF Unit ON Unit OFF Unit • TCP/IP Configuration settings (IP address, subnet mask, or Link settings) OFF when the parameters above are valid. ON when the IP address table information is incorrect. OFF when the IP address table information is correct. 79 Section 4-2 CIO Area Allocations Bit 4 5 6 7 to 8 9 10 Registered Target Node Table (EtherNet/IP Unit to CPU Unit) (n + 16 to n + 19) 80 Name IP Router Table Error Status Manipulated by ON Unit OFF Unit (Not used) --Routing Table Error ON (Not used) Ethernet Expansion Settings Error BOOTP Server Error 11 to 13 14 (Not used) 15 Non-volatile Memory Error --Unit OFF Unit --ON --Unit OFF Unit ON Unit OFF Unit --- --- Address Mismatch ON Unit OFF Unit ON Unit OFF Unit Unit operation ON when the IP router table information is incorrect. OFF when the IP router table information is correct. --ON when the routing table information is incorrect. OFF when the routing table information is correct. --One of the following parameters is invalid. • FINS settings OFF when the parameters above are valid. One of the following errors occurred when using the BOOTP server. • The IP address received from the BOOTP server is incorrect. • A communications timeout occurred with the server. OFF when the errors listed above did not occur. --ON when the target IP address conversion method is set to Automatic generation, but the local IP address’ host ID does not match the FINS node address. OFF when the values match. ON when an error occurred in the Unit’s internal non-volatile memory. OFF when the Unit’s internal non-volatile memory is operating normally. Words n+16 to n+19 show the registration status of the target nodes that are connected with the EtherNet/IP Unit as the originator. These words show the status of nodes 0 to 63 only. If it is necessary to show the status of nodes higher than node 63, select “user settings” as the layout pattern. For details, refer to 4-4 User Settings Area. Section 4-2 CIO Area Allocations 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+17 n+18 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 n+19 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 Bit --- Normal Target Node Table (EtherNet/IP Unit to CPU Unit) (n+20 to n+23) Name Status Registered Target Node Flags ON Manipulated by Unit OFF Unit Unit operation Indicates that the node’s tag data link is registered. Indicates that the node’s tag data link is not registered. Words n+20 to n+23 show the connection status of the target nodes that are connected with the EtherNet/IP Unit as the originator. With revision 2 or higher, the flag turns ON after all data for multiple connections for individual target devices is refreshed in the CPU Unit. With revision 1, each flag immediately turns ON when all connections are established. These words show the status of nodes 0 to 63 only. If it is necessary to show the status of nodes higher than node 63, select “user settings” as the layout pattern. For details, refer to 4-4 User Settings Area. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+20 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+21 n+22 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 n+23 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 Bit --- Name Status Normal Target Node ON Flags OFF FINS/TCP Connection Status (EtherNet/IP Unit to CPU Unit) (n+24) Manipulated by Unit Unit Unit operation Revision 1: Flags immediately turn ON when all connections are established. Revision 2 or higher: Flags turn ON after all data for multiple connections for the target device is refreshed in the CPU Unit. Indicates that the connection is not established Word n+24 shows the status of FINS/TCP connections. For details, refer to SECTION 8 FINS Communications. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+24 Bit 0 Name FINS/TCP Connection 1 1 FINS/TCP Connection 2 : : Status ON Manipulated by Unit OFF Unit ON Unit OFF Unit : : Unit operation Turned ON by the Unit when a connection is established. Turned OFF by the Unit when the connection is terminated. Turned ON by the Unit when a connection is established. Turned OFF by the Unit when the connection is terminated. : 81 Section 4-2 CIO Area Allocations Bit 14 15 82 Name FINS/TCP Connection 15 FINS/TCP Connection 16 Status ON Manipulated by Unit OFF Unit ON Unit OFF Unit Unit operation Turned ON by the Unit when a connection is established. Turned OFF by the Unit when the connection is terminated. Turned ON by the Unit when a connection is established. Turned OFF by the Unit when the connection is terminated. Section 4-3 DM Area Allocations 4-3 4-3-1 DM Area Allocations Overview of the Allocated DM Area Words The various kinds of data are stored in the offset positions shown in the following diagram, from the beginning word in the area for each Unit. The beginning word m is calculated by the following equation: Beginning word m = D30000 + (100 x unit number) Offset Bit 15 08 07 00 Data direction m (Not used) m+97 m+98 IP Address Display/Setting Area m+99 4-3-2 Ethernet Unit to CPU Unit or CPU Unit to Ethernet Unit Details of the Allocated DM Area Words IP Address Display/Setting Area (m+98 and m+99) 15 m+98 m+99 14 13 12 11 10 9 (1) (2) (5) (6) (1)(2).(3)(4).(5)(6).(7)(8) (Hex) 8 7 6 5 (3) (7) 4 3 2 1 0 (4) (8) IP address: (1)(2).(3)(4).(5)(6).(7)(8) (Hex) If the local IP address is set to a value other than 0.0.0.0 in the TCP/IP Configuration, this area (words m+98 and m+99) will act as an IP Address Display Area and the local IP address set in the TCP/IP Configuration will be read and stored here when the power is turned ON or the Unit restarted. If the local IP address in the TCP/IP Configuration is set to 0.0.0.0, this value is read by the EtherNet/IP Unit when the power is turned ON or the Unit restarted and is used as the local IP address. If the local IP address in these words and the TCP/IP Configuration are both set to 0.0.0.0, the default IP address (192.168.250.Node_address) will be used. For details on the IP address settings, refer to SECTION 5 Determining IP Addresses. Application Simple operation (i.e., The TCP/IP Configuration is left at its default settings. Only the IP address is set.) Setting device Programming Console (CX-Programmer can also be used.) Operation with the desired IP CX-Programmer address set in the TCP/IP Configu- (Unit Setup) ration. Note Setting area Allocated words in the DM Area Remarks • The setting in the allocated DM Area words is enabled only when the IP address is set to 0.0.0.0 in the TCP/IP Configuration. • If the IP address is set to a value other than 00.00.00.00 in the TCP/IP Configuration, this value is stored in the allocated words in the DM Area. Setup TCP/IP Con- The IP address set in the Setup TCP/IP figuration Dialog Box Configuration Dialog Box is stored in the allocated DM Area words. (1) If an IP address other than 00.00.00.00 is set as the local IP address in the TCP/IP Configuration, the IP Address Display/Setting Area words (m+98 and m+99) will be overwritten with the TCP/IP Configuration’s IP 83 Section 4-3 DM Area Allocations address, even if a non-zero IP address was set in the IP Address Display/ Setting Area words beforehand. (2) It is not possible to set the following IP addresses. If any of these values are set, the ERH indicator will flash. • IP addresses where all network number bits are 0 or 1. • IP addresses where all host number bits are 0 or 1. • IP addresses where all subnet number bits are 1. • IP addresses that start with 127 (7F hexadecimal, e.g., 127.35.21.16). 84 Section 4-4 User Settings Area 4-4 4-4-1 User Settings Area Overview of the User Settings Area When the layout of the allocated CIO Area words is set to user settings, the user settings area can be used in addition to the allocated CIO Area words and allocated DM Area words. The beginning word of the user settings area can be set in the Status Area Tab Page in the Edit Parameters Dialog Box of the CX-Programmer. 4-4-2 User Settings Area The user can allocate any available area to contain the registered target node information, normal target node information, target node PLC operating information, and target node PLC error information. Offset Bit 15 00 Data direction 08 07 +0 Registered target node (16 words) EtherNet/IP Unit → CPU Unit Normal target node (16 words) EtherNet/IP Unit → CPU Unit Target node PLC's operating information (16 words) EtherNet/IP Unit → CPU Unit Target node PLC's error information (16 words) EtherNet/IP Unit → CPU Unit +15 +16 +31 +32 +47 +48 +63 Registered Target Node Table (EtherNet/IP Unit to CPU Unit) These flags indicate the registration status of the target nodes, and are valid only when the EtherNet/IP Unit is the originator of the connection. For details on the default settings, refer to 4-2-2 Details of the Allocated CIO Area Words. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 +0 +1 +2 +3 +4 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65 64 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97 96 127 126 125 124 123 122 121 120 119 118 117 116 115 114 113 112 143 142 141 140 139 138 137 136 135 134 133 132 131 130 129 128 159 158 157 156 155 154 153 152 151 150 149 148 147 146 145 144 175 174 173 172 171 170 169 168 167 166 165 164 163 162 161 160 191 190 189 188 187 186 185 184 183 182 181 180 179 178 177 176 207 206 205 204 203 202 201 200 199 198 197 196 195 194 193 192 223 222 221 220 219 218 217 216 215 214 213 212 211 210 209 208 239 238 237 236 235 234 233 232 231 230 229 228 227 226 225 224 255 254 253 252 251 250 249 248 247 246 245 244 243 242 241 240 Bit --- Name Registered Target Node Flags Status ON Manipulated by Unit OFF Unit Unit operation Indicates that the node’s tag data link is registered. Indicates that the node’s tag data link is not registered. 85 Section 4-4 User Settings Area Normal Target Node Table (EtherNet/IP Unit to CPU Unit) These flags indicate the connection status of the target nodes. With revision 2 or higher, the flag turns ON after all data for multiple connections for individual target devices is refreshed in the CPU Unit. With revision 1, each flag immediately turns ON when all connections are established. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 +16 +17 +18 +19 +20 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65 64 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30 +31 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97 96 127 126 125 124 123 122 121 120 119 118 117 116 115 114 113 112 143 142 141 140 139 138 137 136 135 134 133 132 131 130 129 128 159 158 157 156 155 154 153 152 151 150 149 148 147 146 145 144 175 174 173 172 171 170 169 168 167 166 165 164 163 162 161 160 191 190 189 188 187 186 185 184 183 182 181 180 179 178 177 176 207 206 205 204 203 202 201 200 199 198 197 196 195 194 193 192 223 222 221 220 219 218 217 216 215 214 213 212 211 210 209 208 239 238 237 236 235 234 233 232 231 230 229 228 227 226 225 224 255 254 253 252 251 250 249 248 247 246 245 244 243 242 241 240 Bit --- Name Status Normal Target Node ON Flags OFF Target Node PLC Operating Information (EtherNet/IP Unit to CPU Unit) Manipulated by Unit Unit Unit operation Revision 1: Flags immediately turn ON when all connections are established. Revision 2 or higher: Flags turn ON after all data for multiple connections for the target device is refreshed in the CPU Unit. Indicates that all connections are not established These flags indicate the operating status of the target node PLCs, and are valid only when the EtherNet/IP Unit is the originator. The flags are valid only when the corresponding Normal Target Node Flag is ON. If the corresponding Normal Target Node Flag is OFF, the Target Node PLC Operating Flag indicates the previous operating status. For details on the default settings, refer to 4-2-2 Details of the Allocated CIO Area Words. 86 Section 4-4 User Settings Area 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 +32 +33 +34 +35 +36 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65 64 +37 +38 +39 +40 +41 +42 +43 +44 +45 +46 +47 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97 96 127 126 125 124 123 122 121 120 119 118 117 116 115 114 113 112 143 142 141 140 139 138 137 136 135 134 133 132 131 130 129 128 159 158 157 156 155 154 153 152 151 150 149 148 147 146 145 144 175 174 173 172 171 170 169 168 167 166 165 164 163 162 161 160 191 190 189 188 187 186 185 184 183 182 181 180 179 178 177 176 207 206 205 204 203 202 201 200 199 198 197 196 195 194 193 192 223 222 221 220 219 218 217 216 215 214 213 212 211 210 209 208 239 238 237 236 235 234 233 232 231 230 229 228 227 226 225 224 255 254 253 252 251 250 249 248 247 246 245 244 243 242 241 240 Bit --- Target Node PLC Error Information (EtherNet/IP Unit to CPU Unit) Name Status Target Node PLC Operating Flags ON Manipulated by Unit OFF Unit Unit operation The corresponding PLC is operating. (The program is being executed.) The PLC is not operating. These flags indicate the error status (logical OR of fatal and non-fatal errors) of the target node PLCs, and are valid only when the EtherNet/IP Unit is the originator. The flags are valid only when the corresponding Normal Target Node Flag is ON. If the corresponding Normal Target Node Flag is OFF, the Target Node PLC Error Flag indicates the previous error status. For details on the default settings, refer to 4-2-2 Details of the Allocated CIO Area Words. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 +48 +49 +50 +51 +52 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65 64 +53 +54 +55 +56 +57 +58 +59 +60 +61 +62 +63 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97 96 127 126 125 124 123 122 121 120 119 118 117 116 115 114 113 112 143 142 141 140 139 138 137 136 135 134 133 132 131 130 129 128 159 158 157 156 155 154 153 152 151 150 149 148 147 146 145 144 175 174 173 172 171 170 169 168 167 166 165 164 163 162 161 160 191 190 189 188 187 186 185 184 183 182 181 180 179 178 177 176 207 206 205 204 203 202 201 200 199 198 197 196 195 194 193 192 223 222 221 220 219 218 217 216 215 214 213 212 211 210 209 208 239 238 237 236 235 234 233 232 231 230 229 228 227 226 225 224 255 254 253 252 251 250 249 248 247 246 245 244 243 242 241 240 Bit --- Name Target Node PLC Error Flags Status ON Manipulated by Unit OFF Unit Unit operation A fatal or non-fatal error occurred in the corresponding PLC. No error occurred in the PLC. 87 Section 4-5 Auxiliary Area Data 4-5 Auxiliary Area Data The following table and descriptions cover the words and bits in the CPU Unit’s Auxiliary Area that are related to the EtherNet/IP Unit. 4-5-1 Read-only Bits/Words Word(s) Bit(s) A202 A20200 to A20207 Name Communications Port Enabled Flags Function Bits A20200 to A20207 turn ON when a network instruction (SEND, RECV, CMND, or PMCR) can be executed with the corresponding port number. Bits 00 to 07 correspond to communications ports 0 to 7. A203 to A210 --- Communications Port Completion Codes A219 A21900 to A21907 Communications Port Error Flags A302 A30200 to A30215 CPU Bus Unit Initializing Flags These words contain the completion codes for the corresponding port numbers when network instructions (SEND, RECV, CMND, or PMCR) have been executed. Words A203 to A210 correspond to communications ports 0 to 7. Bits A21900 to A21907 turn ON when an error occurred during execution of a network instruction (SEND, RECV, CMND, or PMCR). Bits 00 to 07 correspond to communications ports 0 to 7. Bits A30200 through A30215 turn ON while the corresponding CPU Bus Units (Units #0 through #15, respectively) are initializing. The bits will turn ON either when power is turned ON or when a CPU Bus Unit Restart Bit (A50100 to A50115) is turned ON. A402 A40203 CPU Bus Unit Setting Error Flag (Non-fatal error) A40207 A403 A40300 to A40308 A410 A41000 to A41015 88 Bit A40203 is turned ON when the CPU Bus Units actually installed differ from the Units registered in the I/O tables. The ERR/ALM indicator on the front of the CPU Unit will flash, but CPU operation will continue. The unit number of the CPU Bus Unit involved is stored in word A427. CPU Bus Unit Error Bit A40207 is turned ON when an error occurs Flag during the transmission of data between the CPU (Non-fatal error) and CPU Bus Units. The ERR/ALM indicator on the front of the CPU Unit will flash, but CPU operation will continue. The Unit where the error occurred will stop. The unit number of the CPU Bus Unit involved is stored in word A422. Memory Error When a memory error occurs, the Memory Error Location Flag (A40115) is turned ON and one of the following flags is turned ON to indicate the memory area where the error occurred. A40300: User program A40304: PLC Setup A40305: Registered I/O Tables A40307: Routing Tables The ERR/ALM indicator on the front of the CPU Unit will light and CPU operation will stop. CPU Bus Unit Num- The Duplication Error Flag (A40113) and the ber Duplication corresponding flag in A410 will be turned ON when Flags a CPU Bus Unit’s unit number has been duplicated. Bits 00 to 15 correspond to unit numbers 0 to F. The ERR/ALM indicator on the front of the CPU Unit will light and CPU operation will stop. Settings 0: Network communications running 1: No network communications running 0000: No error Not 0000: Error code 0: Normal end 1: Error end 0: Not initializing 1: Initializing (System will automatically turn the flag OFF when initialization has been completed.) 0: No setting error 1: Setting error 0: No unit number error 1: Unit number error 0: Normal 1: Error 0: No duplication 1: Duplication Section 4-5 Auxiliary Area Data Word(s) Bit(s) A417 A41700 to A41715 A427 A42700 to A42715 4-5-2 Word A501 Name Function CPU Bus Unit Error, When an error occurs in a data exchange between Unit Number Flags the CPU Unit and a CPU Bus Unit, the CPU Bus Unit Error Flag (A40207) and the corresponding flag in A417 are turned ON. Bits 00 to 15 correspond to unit numbers 0 to F. The ERR/ALM indicator on the front of the CPU Unit will flash, but CPU operation will continue. CPU Bus Unit Set- When a CPU Bus Unit Setting Error occurs, A40203 ting Error, Unit and the corresponding flag in A27 are turned ON. Number Flags Bits 00 to 15 correspond to unit numbers 0 to F. The ERR/ALM indicator on the front of the CPU Unit will flash, but CPU operation will continue. Settings 0: No error 1: Error 0: No setting error 1: Setting error Read/Write Bits (User Settings) Bits A50100 to A50115 Name CPU Bus Unit Restart Bits Description Bits A50100 through A50115 can be turned ON to reset CPU Bus Units number #0 through #15, respectively. Settings OFF to ON: Unit restarted. Automatically turned Note The CPU Bus Unit Initializing Flags (A30200 OFF by system after to A30215) will turn ON when initialization of restart processing the Units begins and turn OFF when it is com- has been completed. pleted. Note When turning ON the CPU Bus Unit Restart Bit from a ladder program, use the SET instruction. 89 Auxiliary Area Data 90 Section 4-5 SECTION 5 Determining IP Addresses This section explains how to manage and use IP addresses. 5-1 5-2 5-3 IP Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 5-1-1 IP Address Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 5-1-2 Allocating IP Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 5-1-3 EtherNet/IP Unit IP Address Settings. . . . . . . . . . . . . . . . . . . . . . . . 93 5-1-4 Subnet Masks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 5-1-5 CIDR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 IP Addresses in FINS Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 5-2-1 Specifying Nodes in FINS Communications Services . . . . . . . . . . . 94 5-2-2 Pairing Addresses in Internal Tables . . . . . . . . . . . . . . . . . . . . . . . . 96 5-2-3 Application Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 5-2-4 Related Products and Communications/Setting Methods. . . . . . . . . 103 5-2-5 Pairing IP Addresses and FINS Node Addresses . . . . . . . . . . . . . . . 105 Private and Global Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 5-3-1 Private and Global Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 5-3-2 Using a Private Address for the EtherNet/IP Unit . . . . . . . . . . . . . . 107 5-3-3 EtherNet/IP Unit with a Global Address . . . . . . . . . . . . . . . . . . . . . 109 91 Section 5-1 IP Addresses 5-1 5-1-1 IP Addresses IP Address Configuration IP addresses are made up of 32 bits of binary data divided into four 8-bit fields called octets. These four octets provide the network number (net ID) and host number (host ID). The network number identifies the network, and the host number identifies the node (or host) on the network. The network numbers in an IP address are divided into three classes, A, B, and C, so that the address system can be selected according to the scale of the network. (Classes D and E are not used.) The configuration of the IP address for each of these classes is shown in the following diagram. Class A Bit 31 23 0 Network number (7 bits) 0 Class B Bit 31 1 0 Class C Bit 31 1 1 0 Class D Bit 31 1 1 1 0 Multicast address Class E Bit 31 1 1 1 1 Identification address Host number (24 bits) 15 Network number (14 bits) 0 Host number (16 bits) 7 Network number (21 bits) 0 Host number (8 bits) 0 (Cannot be used.) 0 (Cannot be used.) The number of networks in each class and the number of nodes possible on the network differ according to the class. Class Class A Number of networks Small Class B Medium Class C Large Number of hosts 24−2 max. (16,777,214 max.) 16−2 max. (65,534 max.) 2 2 8−2 2 max. (254 max.) The 32 bits of an IP address are divided into four sections of eight bits each, and expressed as a punctuated number. IP addresses are represented by the decimal equivalent of each of the four octets in the 32-bit address, each separated by a period. For example, the binary address 10000010 00111010 00010001 00100000 would be represented as 130.58.17.32. Note 5-1-2 The same network number must be set for every node on the same Ethernet network. Allocating IP Addresses IP (Internet Protocol) is a standard communications protocol used throughout the world, and is designed to enable communications between any Ethernet nodes regardless of the networks on which they exist. To achieve this, network numbers are allocated by the Network Solutions, InterNIC Registration Services, to ensure that all Ethernet networks have unique numbers regardless of where they exist. The local system administrator is left the responsibility of allocating unique host numbers locally. You therefore should obtain a network number from the InterNIC Registration Services to ensure uniqueness and allow for future network expansions if required. 92 Section 5-1 IP Addresses 5-1-3 EtherNet/IP Unit IP Address Settings An IP address must be set even for the EtherNet/IP Unit or built-in EtherNet/IP port before Ethernet communications can proceed. Use one of the following methods to set the IP address of the EtherNet/IP Unit or built-in EtherNet/IP port. Either use the default IP address setting, use a Programming Device to set a particular IP address in the DM Area words (CS/CJ Series only) allocated to the Unit as a CPU Bus Unit, or set a particular IP address in the EtherNet/IP Unit or built-in EtherNet/IP port. • If you want to connect the EtherNet/IP Unit or built-in EtherNet/IP port immediately, the default IP address is 192.168.250.Node_address. (The node address is set with the Node Address Setting Switches on the front of the EtherNet/IP Unit or CPU Unit.) • If you want to set a particular IP address and store that local IP address in the CPU Unit, set it with the CPU Unit’s allocated DM Area words (CS/CJ Series only). • If you want to set a particular IP address and store that local IP address in the EtherNet/IP Unit or CPU UNit, set the IP address in the TCP/IP settings of the Unit Setup from the CX-Programmer. • If you want to set a particular IP address and obtain the IP address automatically from the BOOTP server, TCP/IP settings of the Unit Setup from the CX-Programmer. For details, refer to 3-8 TCP/IP and Link Settings. 5-1-4 Subnet Masks Operation and management of a network can become very difficult if too many nodes are connected on a single network. In such a case it can be helpful to configure the system so that a single network is divided up into several subnetworks. This can be done by using part of the host number as a subnet number. Internally the network can be treated as a number of subnetworks, but from the outside it acts as a single network and uses only a single Network ID. To establish subnetworks, the Host ID in the IP address is divided into a Subnet ID and a Host ID by using a setting called the Subnet Mask. The Subnet Mask indicates which part of the Host ID is to be used as the Subnet ID. All bits in the Subnet Mask that correspond to the bits in the IP address used either as the Network ID or Subnet ID are set to “1,” and the remaining bits, which correspond to the bits in the IP address actually used for the Host ID, are set to “0.” The following example shows the Subnet Mask for an 8-bit Subnet ID used in a class-B IP address. Bit 31 Class B 1 0 Network ID (14 bits) Subnet mask 15 0 Host ID (16 bits) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 = FF FF FF 00 Network number Subnet number Host number Set the same Subnet Mask value for all of the nodes on that subnetwork. If no subnetworks are used, there is no need to set Subnet Masks. In that case, the following Subnet Mask values will be used depending on the IP address class. Class Class A Class B Class C Subnet Mask value 255.0.0.0 255.255.0.0 255.255.255.0 93 Section 5-2 IP Addresses in FINS Communications 5-1-5 CIDR CIDR, or classless interdomain routing, is used to assign IP addresses that do not use classes. IP addresses that use classes are separated into blocks according to net IDs and host IDs, resulting in inefficient usage of IP address space. CIDR does not use classes, so IP address space can be divided as required to more efficiently use IP address space. For example, using a subnet mask setting with CIDR enables building a horizontally distributed network exceeding 254 nodes even if a class C address block (e.g., 192, 168...). Subnet mask range 192.0.0.0 to 255.255.255.252 CIDR was added for unit version 2.0. 5-2 5-2-1 IP Addresses in FINS Communications Specifying Nodes in FINS Communications Services With FINS communications services on an Ethernet network, IP addresses, UDP port numbers, and TCP port numbers are paired with FINS node addresses to specify nodes on the network. Application level FINS Transport level UDP Internet level IP Node number TCP UDP port number TCP port number Must be allocated. IP address Physical level Automatically allocated Ethernet Ethernet address Note Use the Node Address Setting Switches (NODE NO.) on the front of the EtherNet/IP Unit or, for the built-in EtherNet/IP port, on the front of the CPU Unit to set the FINS node address. Allocating Addresses to EtherNet/IP Units and Built-in EtherNet/IP Ports FINS Message Reception for EtherNet/IP Units or Built-in EtherNet/IP Ports The IP address, FINS/UDP port number, and FINS/TCP port number set for the EtherNet/IP Unit or built-in EtherNet/IP port are mainly used when receiving FINS communications messages. Application level FINS Transport level UDP Internet level IP Physical level Ethernet Node number TCP port number IP address Ethernet address Ethernet V2 94 TCP UDP port number IP UDP Receives communications data conforming to Ethernet address, IP address, UDP port number, and FINS node number. FINS header FINS data Section 5-2 IP Addresses in FINS Communications Pairing IP Addresses with FINS Node Addresses at Local Nodes • Ethernet address: A fixed number is assigned to each EtherNet/IP Unit or built-in EtherNet/IP port and it cannot be changed. • IP address: Use the default IP address (192.168.250.FINS_node number), set the address in the allocated DM Area words, or set the address on the TCP/IP Tab Page of the Edit Parameters Dialog Box from the CX-Programmer. • FINS/UDP port No.: Use the default FINS/UDP port number (9600) or set the number on the FINS/UDP Tab Page of the Edit Parameters Dialog Box from the CX-Programmer. • FINS/TCP port No.: Use the default FINS/TCP port number (9600) or set the number on the FINS/UDP Tab Page of the Edit Parameters Dialog Box from the CX-Programmer. • FINS node address: Set the number using the Node Address Setting Switches (NODE NO.) on the front of the EtherNet/IP Unit or built-in EtherNet/IP port. A particular IP address is allocated to each communications node, including EtherNet/IP Units and built-in EtherNet/IP ports. The IP address must be paired with the FINS node address (1 to 254) by one of the following methods. ■ Automatic Generation Method (Dynamic/Static) Set the relationship between the IP address and the FINS node address setting in the EtherNet/IP Unit or built-in EtherNet/IP port according to the following equation. If the setting does not conform to this equation, a setting error will be generated and the MS Indicator will flash red. FINS node address = IP address host number ■ IP Address Table Method and Combined Method With these methods, the IP address and the FINS node address setting in the EtherNet/IP Unit or built-in EtherNet/IP port have no particular relationship. Set both the FINS node address and the IP address so that they are not duplicated in the network. Sending FINS Messages from EtherNet/IP Units or Built-in EtherNet/IP Ports When the EtherNet/IP Unit or built-in EtherNet/IP port sends a FINS message, it is necessary to determine the remote node's IP address, UDP port number, and TCP port number. The relationships between all addresses, such as remote FINS node addresses and IP addresses, are managed by an internal table at the EtherNet/IP Unit or built-in EtherNet/IP port. Remote FINS node address 1 2 to 254 Remote IP address Connection (Example) 192.168.250.1 UDP 192.168.250.2 UDP Remote port number (Example) 9600 9600 192.168.250.254 9600 UDP When the EtherNet/IP Unit or built-in EtherNet/IP port is turned ON or restarted, the internal table is generated automatically from the various settings that have been made. Depending on the setting method used, data such as remote IP addresses may be changed dynamically. (Dynamic changes can be prohibited.) 95 Section 5-2 IP Addresses in FINS Communications FINS data FINS header Internal table Remote FINS node number 1 2 ! ! ! 254 Remote IP address (Example) Connection Remote port number (Example) 192.168.250.1 192.168.250.2 UDP UDP 9600 9600 192.168.250.254 UDP 9600 Application level Transport level Remote node Application level FINS FINS UDP Internet level IP Physical level Ethernet Node number UDP port number TCP TCP port number Ethernet address 5-2-2 IP UDP UDP Internet level IP Physical level Ethernet TCP UDP port number TCP port number IP address Ethernet address The remote node's IP address, UDP/TCP method, UDP port number, and TCP port number are calculated from the node number in the FINS message, and an Ethernet frame is generated. IP address Ethernet V2 Node number Transport level FINS header FINS data Pairing Addresses in Internal Tables FINS/UDP Communications Methods Automatic Generation (Dynamic) When the EtherNet/IP Unit or built-in EtherNet/IP port is turned ON or restarted, the following values are set for addresses in the internal table. • Remote IP address: Local IP address network number + remote FINS node address • Remote UDP port number: UDP port number set for local Unit • Connection method: FINS/UDP With the dynamic method, data in an internal table that has been generated can be dynamically converted according to FINS messages received from remote nodes. This is enabled when the remote node is a device such as a personal computer and IP addresses are dynamically changed by a method such as DHCP. EtherNet/IP Unit CPU Unit Remote FINS node number Personal computer Must be fixed. Local FINS node number Can be changed. Local IP address Automatic generation (dynamic setting) Internal table Remote IP address IP address FINS command IP address FINS response Local FINS node number Change registration Local IP address Ethernet (EtherNet/IP) For the remote IP address, a response is returned to the changed IP address. 96 Section 5-2 IP Addresses in FINS Communications Automatic Generation (Static) With the static method as well, the following values are set for addresses in the internal table when the EtherNet/IP Unit or built-in EtherNet/IP port is turned ON or restarted. • Remote IP address: Local IP address network number + remote FINS node address • Remote UDP port number: UDP port number set for local Unit • Connection method: FINS/UDP With the static method, however, data in an internal table that has been generated is not freely changed. CPU Unit EtherNet/IP Unit Remote FINS node number Personal computer Local FINS node number Must be fixed. Automatic generation (static setting) Internal table Local FINS node number Must be fixed. Local IP address Remote IP address IP address FINS command Local IP address Ethernet (EtherNet/IP) IP address FINS response IP Address Table Method With this method, FINS node addresses are converted to IP addresses based on a preset correspondence table (IP address table). The IP address table is set on the FINS/UDP Tab Page of the Edit Parameters Dialog Box of the CX-Programmer. Nodes can be registered even if they are in different segments and have different network IDs The internal table will be as follows: • FINS Node Address Registered to IP Address Table The following address is registered to the internal table. • Remote IP address: IP address registered to IP address table • Remote UDP port number: UDP port number set for local Unit • Connection method: FINS/UDP • FINS Node Address Not Registered to IP Address Table The following address is registered to the internal table. • Remote IP address: 0.0.0.0 • Remote UDP port number: UDP port number set for local Unit • Connection method: FINS/UDP With the IP address table method, records of FINS nodes registered to the IP address table are not changed dynamically. When the Unit is turned ON or restarted, the IP addresses of remote FINS nodes registered with an IP address of 0.0.0.0 can be changed dynamically according to FINS messages received from remote nodes. This can be used effectively when the remote node is a device such as a personal computer and IP addresses are dynamically changed by a method such as DHCP. 97 Section 5-2 IP Addresses in FINS Communications Example When FINS Command is Sent FINS node number IP address table Node number in IP address table FINS node number 18 20 153.214.0.62 153.214.0.129 23 153.218.51.8 IP address IP address 153.214.0.129 FINS command sent When FINS Command is Received FINS node number Node number not in IP address table Internal table 25 153.218.51.10 Changed Combined Method IP address 153.218.51.10 FINS response returned The combined method combines the IP address table method and the automatic generation method (dynamic). First the IP address table is referenced. Then, if the applicable FINS node address is found, the corresponding IP address is read. If the FINS node address is not found, the IP address is calculated using the automatic generation method (dynamic). The internal table will be as follows: • FINS Node Address Registered to IP Address Table The following address is registered to the internal table. • Remote IP address: IP address registered in IP address table • Remote UDP port number: UDP port number set for local Unit • Connection method: FINS/UDP • FINS Node Address Not Registered to IP Address Table The following address is registered to the internal table. • Remote IP address: Local IP address network number + FINS node address • Remote UDP port number: UDP port number set for local Unit • Connection method: FINS/UDP With the combined method, records of FINS nodes registered to the IP address table are not dynamically changed. When the Unit is turned ON or restarted and the IP address of a remote FINS node is not registered in the IP table, the IP address can be changed dynamically according to FINS messages received from the remote node. This can be used effectively when the remote node is a device such as a personal computer and IP addresses are dynamically changed by a method such as DHCP. 98 Section 5-2 IP Addresses in FINS Communications Example When FINS Command is Sent FINS node number IP address table FINS node IP address number Node number in 18 153.214.0.62 IP address table 20 153.214.0.129 23 153.218.51.8 Node number not in IP address table Network number: xx.xx.00.00 + FINS node number: xx Automatic generation method IP address FINS command sent IP address (See note.) FINS command sent When FINS Command is Received FINS node number Node number not in IP address table Changed IP address method Automatic generation method (dynamic) Internal table 25 153.218.51.10 IP address 153.218.51.10 FINS response returned Note When an internal table IP address has been changed with the reception of a FINS command, this is sent to the IP address in the internal table. Prohibiting Dynamically Changing Remote IP Addresses With EtherNet/IP Units and built-in EtherNet/IP ports, it is possible to prohibit (protect against) dynamic changes to remote IP addresses by each method (automatic generation, IP address table, or combined method). Use the CXProgrammer to make this setting. When dynamically changing remote (destination) IP addresses is prohibited, the internal table for each method is maintained in the same state it had when the power was turned ON or restarted. Therefore, protection can be provided against access using FINS/UDP from personal computers or other devices that have dynamically changing IP addresses. To prohibit dynamic changes, clear the selection of the Dynamic change the target IP addresses Option on the FINS/UDP Tab Page in the Edit Parameters Dialog Box of the CX-Programmer. Using the ETN11compatible Mode With EtherNet/IP Units and built-in EtherNet/IP ports, operating specifications can be made compatible with the CS1W-ETN11/CJ1W-ETN11 for all methods (automatic generation (dynamic), I/O address table, or combined). (Dynamic changes, however, are prohibited for the destination IP address in ETN11compatible mode.) While in ETN11-compatible mode, the following operations will be performed the same as they are for the CS1W-ETN11/CJ1W-ETN11 for FINS/UDP command data sent from a UDP port number other than the local FINS/UDP port number (default: 9600) set ion the FINS/UDP Tab Page. • If the command data is addressed to an Ethernet Unit, a FINS response will be sent to the source UDP port number. • If the command data is for any other Unit, such as the CPU Unit, a FINS response will be sent to the UDP port number set as the FINS/UDP port number. 99 IP Addresses in FINS Communications Section 5-2 Note If the ETN11-compatible mode is used, the internal table will retain the same content from when it was created after the EtherNet/IP Unit was turned ON or restarted. This feature provides protection from access via FINS/UDP from computers that dynamically change their IP address. FINS/TCP Communications Method Pairing in the FINS/TCP Method With the FINS/TCP method, communications are first established for each connection, and then remote FINS node addresses are mutually converted. (See note.) After the FINS node address is converted, FINS message communications are executed. In this way, remote FINS node addresses and remote IP addresses are paired for each connection. Therefore, with the FINS/TCP method, there is no need to set IP address conversions (i.e., pairing FINS node addresses with IP addresses) as with FINS/UDP. On the other hand, it is necessary to set the remote IP address for each connection in the FINS/TCP Tab Page of the Network Configurator’s Edit Parameters Dialog Box. Note The internal table is changed after connections are established. Internal Processing The EtherNet/IP Unit or built-in EtherNet/IP port executes the following processing when the FINS/TCP method is used. ■ 1,2,3... Local Device: FINS/TCP Client 1. Connections are established in TCP/IP protocol with the remote IP addresses set for FINS/TCP connections in the FINS/TCP Tab Page of the CX-Programmer’s Edit Parameters Dialog Box. 2. The remote node (i.e., the server) is notified of the FINS node address for the local device. 3. Notification is received from the remote node (i.e., the server) of the remote node's FINS node address. 4. The EtherNet/IP Unit or built-in EtherNet/IP port changes the internal table (FINS node address, IP address, and TCP port number). 5. FINS messages can then be sent and received. 100 Section 5-2 IP Addresses in FINS Communications ■ 1,2,3... Local Device: FINS/TCP Server 1. A request to open a connection is received in TCP/IP protocol from the remote device (i.e., the client, either a personal computer, an EtherNet/IP Unit or built-in EtherNet/IP port), and the connection is established. 2. Notification is received from the remote node (i.e., the client) of the remote node's FINS node address. 3. The local device provides notification of the local FINS node address. 4. The EtherNet/IP Unit or built-in EtherNet/IP port changes the internal node correspondence table (FINS node address, IP address, and TCP port number). 5. FINS messages can then be sent and received. Personal computer or EtherNet/IP Unit (client) EtherNet/IP Unit (server) (1) The connection is established. Local FINS node number A (2) The local device (such as a personal computer) sends notification that its FINS node number is A. Local IP address T IP address FINS node number transmission CPU Unit Local FINS node number B Local IP address S Ethernet (EtherNet/IP) IP address FINS node number transmission The FINS node number (3) The EtherNet/IP Unit sends notification that is converted for each its FINS node number is B. connection number. (4) The internal node correspondence table is changed. (5) It then becomes possible to send and receive FINS messages. Setting FINS/TCP Connections The procedure for setting FINS/TCP connections involves the items described below. The settings are made individually for each connection (numbers 1 to 16) on the FINS/TCP Tab Page of the Edit Parameters Dialog Box of the CXProgrammer. ■ 1,2,3... Local Device: Server 1. Set the server. 2. Set IP addresses for the devices to be connected. If the option for protection of IP addresses is selected, set the IP addresses for clients where connections are permitted. (This step can be omitted.) 3. Automatic FINS node address allocation: If the client (generally a personal computer) supports FINS/TCP, and if it is to be used without setting a FINS node address, the value set here (from 239 to 254) can be allocated to the client. The default settings should normally be used. ■ 1,2,3... Local Device: Client 1. Set the client. 101 Section 5-2 IP Addresses in FINS Communications 2. Set IP addresses for the devices to be connected. Set the IP address for the remote EtherNet/IP Unit or built-in EtherNet/IP port (i.e., the server) connected by FINS/TCP. This setting must be made if this EtherNet/IP Unit will be used as a FINS/ TCP client. 5-2-3 Application Examples Responding to Computers with Changed IP Addresses FINS/UDP Communications Method With FINS/UDP, whether using the automatic conversion method (dynamic), the IP address table method, or the combined method, remote FINS node addresses and remote IP addresses in the internal table are changed after FINS messages are received. Therefore, even when a FINS command has been received from a personal computer (a DHCP client computer) for which the IP address is dynamically changed, a response can still be sent back to the computer (the DHCP client computer) from which the command originated. Personal computer (client) IP address changed (acquired from DHCP server when connected) FINS command sent IP address FINS command Ethernet (EtherNet/IP) IP address FINS response EtherNet/IP Unit (with fixed IP address) Response sent back to changed IP address FINS/TCP Communications Method With FINS/TCP, FINS node addresses and IP addresses in the internal table are changed with each connection that is established. Therefore, even when a FINS command has been received from a personal computer (a DHCP client computer) for which the IP address is dynamically changed, a response can still be sent back to the computer (the DHCP client computer) from which the command originated. Personal computer (client) IP address changed (acquired from DHCP server when connected) FINS command sent IP address FINS command IP address FINS response Ethernet (EtherNet/IP) EtherNet/IP Unit (FINS/TCP server; with fixed IP address) Response sent back to changed IP address Note 102 Automatic IP Address Setting by DHCP Service DHCP service is a method whereby a DHCP server collectively manages all of the IP address in a network. Nodes that are functioning as clients acquire IP addresses from the DHCP Section 5-2 IP Addresses in FINS Communications server whenever the system is started. Therefore, at a personal computer using the DHCP service, IP addresses may be different with each system startup. DHCP service is mainly used for automatic settings in devices such as personal computers that are used for client applications. Nodes used for server applications, such as mail servers, are normally allocated fixed IP addresses. EtherNet/IP Units and built-in EtherNet/IP ports in PLC systems are also allocated fixed IP addresses. Simultaneously Running Multiple Applications on a Personal Computer In communications involving previous models, multiple communications applications were configured on personal computers according to data accessing uses, and the fact that no more than one UDP port number for FINS communications could be used on any given computer created a problem. This EtherNet/IP Unit provides a practical solution with an internal table that pairs remote nodes (applications) with FINS node addresses, enabling dynamic changes. FINS/UDP Communications Method FINS nodes are allocated individually for each application on the computer, and the respective FINS/UDP port numbers that are used are also allocated individually. When FINS/UDP FINS commands are sent from individual applications to the EtherNet/IP Unit or built-in EtherNet/IP port, the respective remote IP addresses and remote port numbers in the internal table are dynamically changed. FINS/TCP Communications Method With this method as well, FINS nodes are allocated individually for each application on the computer, and the respective FINS/TCP port numbers that are used are also allocated individually. Each application is positioned with a FINS/TCP client, and requests the opening of a connection with the FINS/ TCP server of the EtherNet/IP Unit or built-in EtherNet/IP port. When the connection is established, the respective remote IP address and remote port number in the internal table are dynamically changed. 5-2-4 Related Products and Communications/Setting Methods Models Supporting Automatic Generation Method (Dynamic) Product Model/Series/ Version CS-series Ethernet Unit 100BASE-TX 10BASE-5 10BASE-T CS1W-ETN21 CS1W-ETN01 CS1W-ETN11 CJ-series Ethernet Unit 100BASE-TX 10BASE-T 10BASE-5 CJ1W-ETN21 CJ1W-ETN11 CV500-ETN01 CV/CVM1-series Ethernet Unit FinsGateway Version 4.xx or lower Version 2003 or higher Supports automatic generation method (dynamic)? Yes No: Set by automatic generation method or combined method. Communications are not possible with personal computers with variable IP addresses. Yes No: Set by automatic generation method or combined method. Communications are not possible with personal computers with variable IP addresses. Yes 103 Section 5-2 IP Addresses in FINS Communications Product Programmable Terminal Open Network Controller (ONC) Model/Series/ Version NS Series --- Supports automatic generation method (dynamic)? No: Set manually so that automatic settings can be used with the automatic generation method. Models Supporting Automatic Generation Method (Static) Product Model/Series/ Version CS-series Ethernet Unit 100BASE-TX 10BASE-5 10BASE-T CS1W-ETN21 CS1W-ETN01 CS1W-ETN11 CJ-series Ethernet Unit 100BASE-TX 10BASE-T 10BASE-5 CJ1W-ETN21 CJ1W-ETN11 CV500-ETN01 CV/CVM1-series Ethernet Unit FinsGateway Programmable Terminal Open Network Controller (ONC) Version 4.xx or lower Version 2003 or higher NS Series --- Supports automatic generation method (static)? Yes Yes: Simply called “automatic generation method.” Yes Yes: Simply called “automatic generation method.” Yes No: Set manually so that automatic settings can be used with the automatic generation method. Models Supporting IP Address Table Method Product CS-series Ethernet Unit CJ-series Ethernet Unit CV/CVM1-series Ethernet Unit FinsGateway 100BASE-TX 10BASE-5 10BASE-T 100BASE-TX 10BASE-T 10BASE-5 Programmable Terminal Open Network Controller (ONC) 104 Model/Series/ Version CS1W-ETN21 CS1W-ETN01 CS1W-ETN11 CJ1W-ETN21 CJ1W-ETN11 CV500-ETN01 Version 4.xx or lower Version 2003 or higher NS Series --- Supports IP address table method? Yes No: Set manually. FINS communications are not possible with personal computers set automatically by DHCP. Section 5-2 IP Addresses in FINS Communications Models that Can Use the Combined Method Product CS-series Ethernet Unit CJ-series Ethernet Unit CV/CVM1-series Ethernet Unit FinsGateway 100BASE-TX 10BASE-5 10BASE-T 100BASE-TX 10BASE-T 10BASE-5 Programmable Terminal Open Network Controller (ONC) 5-2-5 Model/Series/ Version CS1W-ETN21 CS1W-ETN01 CS1W-ETN11 CJ1W-ETN21 CJ1W-ETN11 CV500-ETN01 Supports combined method? Yes No No Yes No No Version 4.xx or lower Version 2003 or higher NS Series --- No Yes No: Set manually. FINS communications are not possible with personal computers set automatically by DHCP. Pairing IP Addresses and FINS Node Addresses The following table shows the methods for pairing IP address and FINS node addresses, and the relation between fixed and variable address, for both FINS/UDP and FINS/TCP. Communications method FINS/UDP FINS/TCP Method of pairing of IP addresses and FINS node addresses IP address determination By pairing FINS IP address node addresses with conversion IP addresses in Ethernet By automatic conver- Automatic sion of FINS node addresses at EtherNet/IP Unit and remote node (and then sending and receiving data) Automatic generation method (static) Automatic generation method (dynamic) IP address table method Combined method Connection method (automatic FINS node address conversion) Client (personal Server (PLC) computer of PLC) FINS node IP address FINS node IP address address address Fixed Fixed Fixed Fixed Fixed Fixed or variable Fixed Fixed Fixed or variable Fixed Fixed or variable Fixed or Fixed or can be allo- variable cated automatically when not determined. Fixed Fixed Fixed Fixed Fixed Fixed Fixed 105 Section 5-3 Private and Global Addresses 5-3 5-3-1 Private and Global Addresses Private and Global Addresses There are two kinds of IP addresses, private and global. • Global addresses: These are IP addresses that connect directly to the Internet. Allocated by application to NIC, each address is unique in the world, and as many as 4.3 million can be allocated worldwide. • Private addresses: These are IP addresses for Intranet (LAN) use, and cannot connect directly to the Internet. Frames that include private IP addresses are restricted by the router from being sent outside the LAN. Generally, as shown below, global addresses in the intranet are allocated only to IP routers (such as broadband routers) interfacing with the Internet. All other nodes in the intranet, including the EtherNet/IP Unit or built-in EtherNet/ IP port, are allocated private addresses. Intranet Personal computer, CX-Programmer, etc. Ethernet (EtherNet/IP) Firewall PLC Private address IP router Private address Internet Not output to Internet Global address (required) Not output to Internet Intranet Global address IP router Private address Private address Personal computer, CX-Programmer, etc. Firewall Ethernet (EtherNet/IP) PLC Private address Communications Services That Require Global Addresses for EtherNet/IP Units and built-in EtherNet/IP ports PLC Private address A global address is required for the IP addresses of the EtherNet/IP Units and built-in EtherNet/IP port when the following communications services are used over the Internet. • FINS communications services • Explicit message communications services 106 Section 5-3 Private and Global Addresses 5-3-2 Using a Private Address for the EtherNet/IP Unit Intranet FINS/TCP client computer with CX-Programmer, etc. or CIP client computer with Network Configurator, etc. FINS communications, Explicit messages Ethernet (EtherNet/IP) Communications in intranet Firewall PLC IP router EtherNet/IP Unit: Private address Internet Intranet FINS/TCP client computer with CX-Programmer, etc. or CIP client computer with Network Configurator, etc. IP router FINS communications, Explicit messages Firewall Communications in Intranet Ethernet (EtherNet/IP) PLC PLC Communications in Intranet EtherNet/IP Unit: Private address EtherNet/IP Unit: Private address Conditions for Using Communications Applications When the EtherNet/IP Unit or built-in EtherNet/IP port has a private address, communications applications can be used under the following conditions: ■ FINS Communications Service • The FINS communications service can be executed on the intranet between EtherNet/IP Units and built-in EtherNet/IP ports with private addresses only. A device such as a personal computer (with a FINS application, including the CX-Programmer) cannot connect online and communicate over the Internet with an EtherNet/IP Unit or built-in EtherNet/IP port that has a private address. FINS communications are also not possible over the Internet between EtherNet/IP Units and or built-in EtherNet/IP ports with private addresses. • Either FINS/TCP or FINS/UDP can be used for the FINS communications service. • With FINS/UDP, all of the EtherNet/IP Unit or built-in EtherNet/IP port IP address conversion methods can be used. 107 Section 5-3 Private and Global Addresses • With FINS/UDP, when the IP address (private address) of a computer serving as a DHCP client is changed, the IP address conversion method of the EtherNet/IP Unit or built-in EtherNet/IP port will be the automatic generation method (dynamic), the combined method, or the IP address table method. When FINS/TCP is used, IP addresses can be changed automatically. ■ Explicit Message Communications Service • The explicit message communications service can be executed on the intranet between EtherNet/IP Units and built-in EtherNet/IP ports with private addresses only. • A device such as a personal computer (CIP applications including the Network Configurator) cannot connect online and communicate over the Internet with an EtherNet/IP Unit or built-in EtherNet/IP port that has a private address. Explicit message communications are also not possible over the Internet between EtherNet/IP Units and built-in EtherNet/IP ports with private addresses. Note Network Security and Firewalls Setting up an intranet through a global address involves network security considerations. Before doing so, be sure to consult with a network specialist and consider installing a firewall. Once a firewall has been set up by a communications technician, on the other hand, there may be some applications that cannot be used. Be sure to check first with the communications technician. 108 Section 5-3 Private and Global Addresses 5-3-3 EtherNet/IP Unit with a Global Address Intranet FINS/TCP client computer with CX-Programmer, etc. or CIP client computer with Network Configurator, etc. Ethernet (EtherNet/IP) Communications over Internet Firewall Private address IP router Internet Not output to Internet Global address (required) Not output to Internet Intranet Global address IP router Private address Private address Firewall Ethernet (EtherNet/IP) PLC Communications in intranet EtherNet/IP Unit: Global address Conditions for Using Communications Applications Communications applications can be used over the Internet under the following conditions: ■ FINS Communications Service • A device such as a personal computer (a FINS application, including the CX-Programmer) can connect online and communicate over the Internet with an EtherNet/IP Unit or built-in EtherNet/IP port that has a global address. • FINS/TCP is recommended as the FINS communications service method. FINS/TCP is more reliable than FINS/UDP in terms of communications errors involving IP routers. • The IP address table method is used as the IP address conversion method of the EtherNet/IP Unit or built-in EtherNet/IP port. • The TCP port number to be used for FINS/TCP cannot be used if prohibited by a firewall in the communications path. ■ Explicit Message Communications Service • A device such as a personal computer (a CIP application including the Network Configurator) can connect online and communicate over the Internet with an EtherNet/IP Unit or built-in EtherNet/IP port that has a global address. 109 Private and Global Addresses Section 5-3 • If the TCP port number (44818) or UDP port number (44818) that is used for EtherNet/IP cannot be used if prohibited by a firewall in the communications path. Note Network Security and Firewalls Setting a global IP address for an EtherNet/IP Unit or built-in EtherNet/IP port involves network security considerations. It is recommended that the user contract with a communications company for a dedicated line, rather than using a general line such as a broadband line. Also, be sure to consult with a network specialist and consider security measures such as a firewall. Once a firewall has been set up by a communications technician, on the other hand, there may be some applications that cannot be used. Be sure to check first with the communications technician. 110 SECTION 6 Tag Data Link Functions This section describes tag data link functions and related Network Configurator operations. 6-1 6-2 6-3 Overview of Tag Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 6-1-1 Tag Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 6-1-2 Overview of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 6-1-3 Tag Data Link Functions and Specifications . . . . . . . . . . . . . . . . . . 115 6-1-4 Data Link Data Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Setting Tag Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 6-2-1 Starting the Network Configurator . . . . . . . . . . . . . . . . . . . . . . . . . . 121 6-2-2 Tag Data Link Setting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 6-2-3 Registering Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 6-2-4 Creating Tags and Tag Sets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126 6-2-5 Connection Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 6-2-6 Setting Tags Using Data Link Tool. . . . . . . . . . . . . . . . . . . . . . . . . . 150 6-2-7 Creating Connections Using the Wizard . . . . . . . . . . . . . . . . . . . . . 156 6-2-8 Creating Connections by Device Dragging and Dropping . . . . . . . . 159 6-2-9 Connecting the Network Configurator to the Network . . . . . . . . . . 161 6-2-10 Downloading Tag Data Link Parameters . . . . . . . . . . . . . . . . . . . . . 168 6-2-11 Uploading Tag Data Link Parameters. . . . . . . . . . . . . . . . . . . . . . . . 171 6-2-12 Verifying the Tag Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172 6-2-13 Starting and Stopping Tag Data Links . . . . . . . . . . . . . . . . . . . . . . . 175 6-2-14 Clearing the Device Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176 6-2-15 Saving the Network Configuration File . . . . . . . . . . . . . . . . . . . . . . 177 6-2-16 Reading a Network Configuration File. . . . . . . . . . . . . . . . . . . . . . . 178 6-2-17 Checking Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180 6-2-18 Changing Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181 6-2-19 Displaying Device Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181 Ladder Programming with Tag Data Links. . . . . . . . . . . . . . . . . . . . . . . . . . . 183 6-3-1 Ladder Programming Related to Tag Data Links . . . . . . . . . . . . . . . 183 6-3-2 Status Flags Related to Tag Data Links . . . . . . . . . . . . . . . . . . . . . . 186 111 Section 6-1 Overview of Tag Data Links 6-1 6-1-1 Overview of Tag Data Links Tag Data Links Tag data links enable cyclic data exchanges on an EtherNet/IP network between PLCs or between PLCs and another device. I/O memory addresses (e.g., in the CIO or DM Area) and symbols can be assigned to tags. The settings for tag data links are made using the Network Configurator. Refer to 6-2 Setting Tag Data Links for information on how to make the settings. Note Symbols can be used in tags only for the CJ2H-CPU6@-EIP and CJ2MCPU3@. If you are using a CJ1W-EIP21 or CS1W-EIP21 EtherNet/IP Unit that is mounted to a CJ2H-CPU6@ or any CPU Unit other than the CJ2H-CPU6@EIP, use I/O memory addresses to set the tag data links. With tag data links, one node requests the opening of a communications line called a connection to exchange data with another node. The node that requests opening the connection is called the originator, and the node that receives the request is called the target. CPU Unit EtherNet/IP Unit EtherNet/IP Unit Inputs CPU Unit Outputs Connection Tag set name: ABC DM00100 I/O refreshed. Var-In(WR200) DM00100 Var-In DM20000 Tag set name: OUT1 Input tags Originator Var-Out2(DM100) Target Inputs Outputs DM20100 Var-Out1(DM0) I/O refreshed. Var-Out3(DM200) DM20000 DM00200 Var-Out(WR300) Var-Out1 Var-Out2 Var-Out3 Output tags Connection I/O refreshed. Tag set name: XYZ DM00200 Var-Out DM20100 Tag set name: IN1 Output tags Input tags DM00200 WR300 DM20100 PLC status Target I/O refreshed. DM00200 WR300 DM20100 PLC status Originator Ethernet (EtherNet/IP) For communications between PLCs, the connection information is set in the EtherNet/IP Unit or built-in EtherNet/IP port of the PLC that receives data (i.e., the originator). Note For communications between a PLC and an I/O device, the connection information is set in the EtherNet/IP Unit or built-in EtherNet/IP port that is the originator. If an I/O device is used, the Network Configurator must have an EDS file installed that includes connection information for the I/O device. Refer to Appendix F EDS File Management for the installation procedure. The output words and input words for each node for which data is exchanged must be set in the connection information. These words are called the output tag set and input tag set. A tag set must specify at least one tag. The size of the data for data exchange is the total size of the tags included in the tag set. The size of the output tag set and the size of the input tag set must match. In this manual, set connection information is called tag data link parameters. The following section describes how to set tag data links using the Network Configurator. 112 Section 6-1 Overview of Tag Data Links 6-1-2 Overview of Operation Setting and Downloading Tag Data Link Parameters The tag data link parameters (e.g., connection information) that are described below are created using the Network Configurator, and then the parameters are downloaded to all originator devices on the EtherNet/IP network. Make the following settings using the Network Configurator if tag data link functionality is used with the CJ2B-EIP21 built-in EtherNet/IP port on the CJ2H, CJ2M-EIP21 built-in EtherNet/IP port on the CJ2M, CS1W-EIP21, or CJ1W-EIP21. Tag Settings Create input (reception) tags and output (send) tags for addresses in the CPU Unit's I/O memory areas or for symbols. The following are the limits for tags that can be created with the CJ2B-EIP21 built-in EtherNet/IP port on the CJ2H, CJ2M-EIP21 built-in EtherNet/IP port on the CJ2M, CS1W-EIP21, or CJ1W-EIP21. • A maximum of 32 tags can be created per Unit for the CJ2M-EIP21. A maximum of 256 tags can be created per Unit for other CPU Units. • A maximum data size of 40 bytes (20 words) can be used per tag for the CJ2M-EIP21. A maximum data size of 1,444 bytes (722 words) can be used per tag for other CPU Units. With the CJ2H-CPU6@-EIP or CJ2M-CPU3@, you can create tags by importing network symbols (i.e., I/O allocation settings) that were created using the CX-Programmer into the Network Configurator. Output tags can be defined to clear output data to 0 or to hold the output data when PLC outputs are turned OFF. Setting Tag Sets Create output tag sets and input tag sets and position them. (Up to eight tag sets can be created). The following are the limits on tag sets that can be created with the CJ2B-EIP21 built-in EtherNet/IP port on the CJ2H, CJ2M-EIP21 built-in EtherNet/IP port on the CJ2M, CS1W-EIP21, or CJ1W-EIP21. • A maximum of 32 tag sets can be created per Unit for the CJ2M-EIP21. A maximum of 256 tag sets can be created per Unit for other CPU Units. • A maximum data size of 40 bytes (20 words) can be used per tag set for the CJ2M-EIP21. A maximum data size of 1,444 bytes (722 words) can be used per tag set for other CPU Units. The PLC status can be specified in a tag set to indicate the CPU Unit’s operating status (operating information and error information). Setting Connections The target device output tag set and the originator device input tag set are associated as connections. A maximum of 256 connections can be opened per Unit for the CJ2B-EIP21 built-in EtherNet/IP port on the CJ2H, CS1WEIP21, or CJ1W-EIP21. A maximum of 32 connections can be opened per Unit for the CJ2M-EIP21 built-in EtherNet/IP port on the CJ2M. Counting Connections The number of connections is the total of the number of input tag sets that receive data and the number of nodes that send data for output tag sets. (Refer to the following figure.) One connection is consumed for each connection setting whether the connection is a multicast connection or a unicast (point-to-point) connection. 113 Section 6-1 Overview of Tag Data Links Example of Calculating the Number of Connections • EtherNet/IP Unit or built-in EtherNet/IP port with IP address of 192.168.250.254 in bidirectional connection with 128 nodes 192.168.250.1 192.168.250.254 Tagset _in1 Tagset _in2 Tagset_in128 CN.1 Tagset_out Tagset_in CN.2 CN.129 : 192.168.250.2 Tagset_out CN.128 CN.130 Tagset_out25 4 Tagset_in : : The maximum number of connections for node 192.168.250.254 is 32 for the CJ2M and 256 for other CPU Units. : : 192.168.250.128 Tagset_out CN.256 Tagset_in Another EtherNet/IP Unit must be mounted to the PLC to increase the maximum number of connections. (Refer to the following figure.) Example of Calculating the Number of Connections • The maximum number of connections (32 for the CJ2M and 256 for other CPU Units) per Unit would be exceeded if an EtherNet/IP Unit or built-in EtherNet/IP port with an IP address of 192.168.250.254 is used in a bidirectional connection with 129 nodes. In this case, bidirectional communications can be performed with 129 nodes or more by adding an EtherNet/IP Unit with the IP address of, for example, 192.168.250.253 to the same PLC, creating an output tag set in the new EtherNet/IP Unit, and creating connections. 192.168.250.254 Tagset_in1 Tagset_in2 Tagset _in129 192.168.250.1 CN.1 CN.2 Tagset _out CN.1 : Tagset_in 192.168.250.2 Tagset _out CN.129 CN.2 Tagset _in : : : : 192.168.250.253 Tagset _out 253 192.168.250.129 Tagset _out CN.129 Setting the Packet Interval (RPI) Tagset _in The packet interval is the data I/O refresh cycle in the Ethernet circuit when performing tag data links, and can be set separately for each connection. The packet interval can be set to between 0.5 and 10,000 ms in units of 0.5 ms for the CJ2B-EIP21 (built-in EtherNet/IP port on the CJ2H), CS1W-EIP21, or CJ1W-EIP21. It can be set to between 1 and 10,000 ms in units of 0.5 ms for the CJ2M-EIP21 (built-in EtherNet/IP port on the CJ2M). The default setting is 50 ms. With EtherNet/IP, data is exchanged on the communications line at the packet interval that is set for each connection, regardless of the number of nodes. Using Multicast and Unicast Communications A multicast connection or unicast (point-to-point) connection can be selected as the connection type in the tag data link connection settings. With a multicast connection, you can send an output tag set in one package to multiple nodes and make allocations to the input tag sets. A unicast connection separately sends one output tag set to each node, and so it sends the same number of packets as the number of input tag sets. Therefore, using multicast connections can decrease the communications load if one output tag set is sent to multiple nodes. 114 Section 6-1 Overview of Tag Data Links If multicast connections are used, however, use a switching hub that has multicast filtering, unless the tag set is received by all nodes in the network. If a switching hub that does not have multicast filtering is used, the multicast packets will be broadcast to the entire network, and so packets will be sent to nodes that do not require them, which will cause the communications load on those nodes to increase. This applies only if one output tag set is sent to multiple nodes using a multicast connection with one packet, the connection type of the connections that receive the output tag set is multicast, and the connection I/O types, packet intervals (RPI), and timeout values are all the same. Note The performance of communications devices is limited to some extent by the limitations of each product’s specifications. Consequently, there are limits to the packet interval (RPI) settings. Refer to 10-2 Adjusting the Communications Load and set an appropriate packet interval (RPI). Starting and Stopping Tag Data Links Tag data links are automatically started when the data link parameters are downloaded from the Network Configurator. Thereafter, tag data links can be stopped and started for the entire network or individual devices from the Network Configurator. Starting and stopping tag data links for individual devices must be performed for the originator. Software switches in allocated words can also be used to start and stop tag data links for the entire network. Refer to 6-2-13 Starting and Stopping Tag Data Links for details. 6-1-3 Tag Data Link Functions and Specifications Item Communications type Setting method Tags Tag sets Connections Specification Standard EtherNet/IP implicit communications (connectiontype cyclic communications) After setting tags, tag sets, and connections with the Network Configurator, the tag data link parameters must be downloaded to all devices in the EtherNet/IP network. With a CJ2H-CPU6@-EIP or CJ2M-CPU3@ CPU Unit, a symbol table can be created with the CX- Programmer and then imported into the Network Configurator to allocate tags. After the parameters are downloaded, the EtherNet/IP Units are restarted to start the tag data links. Applicable CPU Unit data: CIO Area, DM Area, EM Area, Holding Area, Work Area, and symbols. (See note.) Number of words per tag: 20 max. (40 bytes) for CJ2M, 722 max. (1,444 bytes) for other CPU Units Number of tags per Unit: 32 max. for CJ2M, 256 max. for other CPU UNits Note With the CJ2H-CPU6@-EIP or CJ2M-CPU3@, network symbols (I/O allocation settings) created using the CXProgrammer can be imported into the Network Configurator. Number of tags per tag set: 8 max. (7 max. if PLC status is included) Number of words per tag set: 20 max. (40 bytes) for CJ2M, 722 max. (1,444 bytes) for other CPU Units Number of tag sets per Unit: 32 max. for CJ2M, 256 max. for other CPU Units Number of connections per Unit: 32 max. for CJ2M, 256 max. for other CPU Units 115 Section 6-1 Overview of Tag Data Links Item Connection type Specification Each connection can be set for 1-to-1 (unicast) or 1-to-N (multicast) communications. (Default: Multicast) Packet interval (RPI) 1 to 10,000 ms for CJ2M and 0.5 to 10,000 ms for other CPU Units (in 0.5-ms units) The packet interval can be set separately for each connection. System Configuration Conditions for Setting Tags Using Symbols or I/O Memory Addresses Local tags for tag data links can be set using I/O memory addresses or network symbols. Support for network symbols, however, depends on the model of CPU Unit, as shown in the following table. Communications with the remote node are possible regardless of whether the remote node tags are set using I/O memory addresses or network symbols. Name in hardware list CPU Unit of Network Configurator CJ2B-EIP21 CJ2H-CPU6@-EIP CJ2M-EIP21 CJ2M-CPU3@ CJ1W-EIP21(CJ2) CJ2H-CPU6@-EIP CJ2H-CPU6@ CJ2M-CPU3@ CJ2M-CPU1@ CJ1W-EIP21 CJ1 CPU Unit CS1W-EIP21 CS1 CPU Unit Note 6-1-4 EtherNet/IP Unit or built-in EtherNet/IP port CJ2H-CPU@@-EIP CJ2M-CPU3@ CJ1W-EIP21 CJ1W-EIP21 CS1W-EIP21 Symbol name specification OK OK OK (CJ2H-CPU6@-EIP and CJ2M-CPU3@ only) (See note.) ----- I/O memory address specification OK OK OK OK OK Symbols cannot be set for tags with CJ2H-CPU6@ and CJ2M-CPU1@ CPU Units. Data Link Data Areas Tags A data link between the local I/O memory and a remote I/O memory is called a tag. A tag can be set using a network symbol name or an I/O memory address. Tag Sets When a connection is established, from 1 to 8 tags (including PLC status) is configured as a tag set. Each tag set represents the data that is linked for a tag data link connection. Tag data links are thus created by connecting one tag set to another tag set. A tag set name must be set for each tag set. Note Example 116 A connection is used to exchange data as a unit within which data concurrency is maintained. Thus, data concurrency is maintained for all the data exchanged for the tags in one data set. In the following example, input tags a to g at the originator are a tag set named SP1_IN and output tags i and ii are a tag set named SP1_OUT). A connection is set between these two tag sets. Section 6-1 Overview of Tag Data Links Target device Originator device IP address: # Connection Information · Target IP address: # · Originator tag set: SP1_IN · Target tag set: SP1_OUT · Packet interval (RPI) Tag Set (Output Tags) Tag Set (Input Tags) Tag set name: SP1_IN Tag set name: SP1_OUT PLC status PLC status Tag a Tag i Connection Tag ii Tag b Tag c Tag g EtherNet/IP There are both input and output tag sets. Each tag set can contain only input tags or only output tags. The same input tag cannot be included in more than one input tag set. Number of Tags in Tag Sets Each tag set can contain one or more tags. ■ Tag Sets with Only One Tag With basic Network Configurator procedures, each tag set contains only one tag. CPU Unit I/O memory CPU Unit Tag set SP1_IN (tag a) Tag set SP1_OUT (tag c) I/O memory Connection One tag each (Each tag is set using a text string of the network symbol or I/O memory address.) c a Tag set SP2_OUT (tag b) Tag set SP2_IN (tag d) Connection d b EtherNet/IP ■ Tag Sets with Multiple Tags As shown below, tags can be created in groups. Each tag set can contain up to 8 tags totaling 20 words for the CJ2M or 722 words for other CPU Units. 117 Section 6-1 Overview of Tag Data Links CPU Unit CPU Unit Tag set SP1_IN (group of tags a, b, and c) I/O memory One tag each (Each tag is set using a text string of the network symbol or I/O memory address.) Tag set SP1_OUT I/O memory a f b g c h Tag set SP2_OUT (group of tags d, e) Tag set SP2_IN Connection d i e j EtherNet/IP Note Specifications CS1W-EIP21 CJ1W-EIP21 CJ2H-CPU@@-EIP Total size of all tags ≤ 184,832 words The I/O memory words used in tags in a tag set do not have continuous addresses. The tags can also be from different I/O memory areas. To enable a connection, however, each tag set must include only input tags or only output tags. (Both input and output tags cannot be included in the same tag set.) The following table shows the tag and tag set specifications. Tags CJ2M-CPU3@ Maximum size of 1 tag ≤ 722 words (The maximum size is 721 words when the tag set includes the PLC status.) Tag sets CS1W-EIP21 CJ2M-CPU3@ CJ1W-EIP21 CJ2H-CPU@@-EIP Maximum size of 1 tag set ≤ Maximum size of 1 tag set ≤ 20 words 722 words (The maximum size is 19 (The maximum size is 721 words when the tag set words when the tag set includes the PLC status.) includes the PLC status.) Total size of all tags ≤ 640 words Maximum size of 1 tag ≤ 20 words (The maximum size is 19 words when the tag set includes the PLC status.) Number of tags per tag set ≤ 8 (7 tags/tag set when the tag set includes the PLC status) Note Input and output variables cannot be combined. Number of registrable tags ≤ Number of registrable tags ≤ Number of registrable tag 256 32 sets ≤ 256 PLC Status Number of registrable tag sets ≤ 32 A characteristic function of the CS1W-EIP21 and CJ1W-EIP21 EtherNet/IP Units and CJ2 built-in EtherNet/IP ports is the ability to specify the PLC status as a member of the tag set. This function reads the operating status (operating and error status) of the CPU Unit of the PLC in which the EtherNet/IP Unit is mounted, and includes the PLC status as status flags in the data transferred by the tag data links. When the PLC status is specified as an output (produce) tag, it is actually transferred as the tag set’s leading data in the following format. 15 14 13 12 11 10 0 0 0 0 0 0 9 8 0 0 7 0 6 0 5 0 4 0 3 0 2 1 0 0 PLC Operating Flag PLC Error Flag 118 Section 6-1 Overview of Tag Data Links To receive the PLC status, specify the PLC status in an input (consume) tag in the reception tag set as well. When the PLC status is specified in an input tag, the PLC status flags will be reflected in the corresponding location in the tag data link’s Target Node PLC Operating Flags and Target Node PLC Error Flags. The following example shows the relationship between the Target Node PLC Operating Flag location and target ID of the target node with 192.168.250.2. IP address = 192.168.250.2 → (Last byte = 2) → Target ID = #002 Target Node PLC Operating Flags: 15 n+2 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+4 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 n+5 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 n+3 CPU Unit PLC status I/O memory a CPU Unit PLC status (when included) Output tag set PLC status Input tag set Connection PLC status (when included) I/O memory f b g c h Target data link status EtherNet/IP Note The target ID may be duplicated depending on the IP addresses of the target nodes. In this case, it is necessary to change the target ID with the Network Configurator. For information on how to change the device number, refer to step 4 under Registering Devices in the Register Device List on page 141. 119 Section 6-1 Overview of Tag Data Links The following table shows the operation of each the bits when multiple connections are used to communicate with a node, and the PLC status is specified in all of the connections. Name (allocated area) Target Node PLC Operating Flag Information Layout set to default settings: Words n+2 to n+5 Layout set to user settings: Words n+32 to n+47 Note Corresponds to the PLC status’s PLC Operating Flag. Target Node PLC Error Flag Information Layout set to default settings: Words n+6 to n+9 Layout set to user settings: Words n+48 to n+63 Note Corresponds to the PLC status’s PLC Error Flag. Normal Target Node Flag Table Layout set to default settings: Words n+20 to n+23 Layout set to user settings: Words n+16 to n+31 Note Does not correspond to the PLC status. Note 120 Contents Each flag indicates the operating status of the corresponding target node PLC of connections in which the EtherNet/IP Unit is the originator. The flag corresponding to the target node’s target ID will be ON when the PLC Operating Flags for all connections with that target node indicate that the PLC is operating. Each node address’s flag location (i.e., target ID) can be changed from the Network Configurator. The PLC status flags are enabled when the PLC status is included in the communications data for both the originator and target. The data in this table is refreshed when necessary. Each flag indicates the error status (logical OR of non-fatal and fatal errors) of the corresponding target node PLC of connections in which the EtherNet/IP Unit is the originator. The flag corresponding to the target node’s target ID will be ON if even one error is indicated in any of the connections with that target node. Each node address’s flag location (i.e., target ID) can be changed from the Network Configurator. The PLC status flags are enabled when the PLC status is included in the communications data for both the originator and target. The data in this table is refreshed when necessary. Each flag indicates the connection status of the corresponding target node PLC of connections in which the EtherNet/IP Unit is the originator. The flag corresponding to the target node’s target ID will be ON when connections are established for all connections with that target node indicate that the PLC is operating. Each node address’s flag location (target ID) can be changed from the Network Configurator. The data in this table is refreshed when necessary. When the PLC status is not selected in the input (consume) tags, the PLC status information (16-bit data) can be used as reception data. Section 6-2 Setting Tag Data Links 6-2 6-2-1 Setting Tag Data Links Starting the Network Configurator Procedure Tag data links are set by using the Network Configurator. Use the following procedure to start the Network Configurator. ■ Starting from the Windows Start Menu To start the Network configurator, select OMRON - CX-One - Network Configurator for EtherNet/IP - Network Configurator from the Windows Start Menu. ■ Starting from the IO Table Dialog Box in CX-Programmer To start the Network configurator, select the Unit in the PLC IO Table Dialog Box and select either of the options for Start Special Application from the pop-up menu. Only operation will be started even if Start with Settings Inherited is selected. 121 Section 6-2 Setting Tag Data Links When the Network Configurator starts, the following window will be displayed. Main Window The Main Window consists of a Hardware List and a Network Configuration Window, as shown in the following diagram. Hardware List: Displays the devices that can be added to the network. 122 Network Configuration Window: Displays the layout and network configuration of devices that are set and monitored. Setting Tag Data Links Section 6-2 When two or more networks are being managed, a new Network Configuration Window can be added by selecting Network - Add. To change the name displayed in the Network Tab Page, select Network Property. The name set in the Comment Field of the Network Property Window can be changed. 123 Section 6-2 Setting Tag Data Links 6-2-2 Tag Data Link Setting Procedure The section describes the procedure for setting tag data links (i.e., connection information). For data links between PLCs, the connection information is set only in the originator, i.e., the node that receives data. 1. Creating a Network Configuration Register all EtherNet/IP Units or built-in EtherNet/IP ports for which connections will be created in the EtherNet/IP Network Configuration Window. (Refer to 6-2-3 Registering Devices.) Note If a system has already been installed, connect online to the EtherNet/IP network and upload the network configuration. (Refer to 6-2-11 Uploading Tag Data Link Parameters.) ↓ 2. Creating Connections Set the connections using one of the following methods. 1) Basic Operation 1-1) Create tags and tag sets for all registered devices (EtherNet/IP Unit or builtin port). (Refer to 6-2-4 Creating Tags and Tag Sets.) 1-2) Create a connection for the originator device (i.e., registered device that receives data as input data). (Refer to 6-2-5 Connection Settings.) 2) Generating a Connection Using the EtherNet/IP Datalink Tool (Refer to 6-2-5 Connection Settings.) The EtherNet/IP Datalink Tool is used to create data links between PLCs by specifying I/O memory addresses in the same manner as for Controller Link. The following functions can be used with Network Configurator version 3.10 or higher. 3) Creating Connections Using the Wizard (Refer to 6-2-7 Creating Connections Using the Wizard.) Create connections between OMRON PLCs following the instructions. Tags and tag sets must be set for all devices before starting the Wizard. (Refer to Basic Operation 1-1.) Note Select Device - Parameters - Wizard from the menus to start operation. 4) Creating Connections by Dragging and Dropping Registered Devices (Refer to 62-8 Creating Connections by Device Dragging and Dropping.) When a target device is dragged and dropped to the originator device, the Edit Connection Dialog Box will be displayed, and a connection can be created. OMRON EtherNet/IP Units or built-in EtherNet/IP ports are the only originator devices for which connections can be created in this way. ↓ Downloading Tag Data Link Parameters (Refer to 6-2-10 Downloading Tag Data Link Parameters.) ↓ Check that tag data links are operating correctly by using the indicators on the EtherNet/IP Unit (refer to 14-2 Using the LED Indicators and Display for Troubleshooting for Troubleshooting) and the Network Configurator monitor function (refer to 14-1 Checking Status with the Network Configurator). ↓ Check that the output tag data is updated in the input tag by using the CX-Programmer's Watch Window or PLC memory function. Note Refer to the CX-Programmer Operation Manual (Cat. No. W446) for the operating procedures. 124 Section 6-2 Setting Tag Data Links 6-2-3 Registering Devices Register all of the devices required in the equipment (such as EtherNet/IP Units performing tag data links) as a network configuration. 1,2,3... 1. Register the devices that will participate in the tag data links by dragging the devices from the Hardware List and dropping them in the Network Configuration Window. (To drag and drop an icon, click and hold the left mouse button over the icon, move the icon to the destination, and release the mouse button.) The icon will be displayed in the Network Configuration Window, as shown in the following diagram. Drag and drop icons from the Hardware List. Hardware List Note Name in hardware list CJ2B-EIP21 CIP revision Rev. 2 CJ2M-EIP21 Rev. 2 CJ1W-EIP21 Rev. 1 or 2 CS1W-EIP21 Rev. 1 or 2 CJ1W-EIP21 (CJ2) Rev. 2 EtherNet/IP Unit Built-in EtherNet/IP port on CJ2H CPU Unit (CJ2H-CPU@@-EIP) Built-in EtherNet/IP port on CJ2M CPU Unit (CJ2M-CPU3@) CJ1W-EIP21 EtherNet/IP Unit connected to CJ1 CPU Unit CS1W-EIP21 EtherNet/IP Unit connected to CJ1 CPU Unit CJ1W-EIP21 EtherNet/IP Unit connected to CJ2 CPU Unit (1) If the revision is unknown, select the newest revision (i.e., the revision with the highest number). The following table shows the relation between the CIP revision and the unit version. Unit version Ver. 1.0 Ver. 2.0 CIP revision Revision 1.01 Revision 2.01 or 2.02 (2) When mounting the CJ1W-EIP21 to a CJ2 CPU Unit, select CJ1W-EIP21 (CJ2) from the Hardware List. 2. Click the right mouse button over the registered device’s icon to display the pop-up menu, and select Change Node Address. 125 Section 6-2 Setting Tag Data Links 3. Set the IP address to match the node address (IP address) actually being used in the device. 4. Repeat steps 1 to 3, and register all of the devices participating in the tag data links. 6-2-4 Creating Tags and Tag Sets Specifying I/O Memory Addresses The tag sets and set member tags required to create connections for a registered EtherNet/IP Unit must be created. The I/O memory addresses or network symbols that are used in the control programs can be set for the tags. (Using network symbols is supported only by the CJ2H-CPU6@-EIP21 and CJ2M-CPU3@.) This section first describes the basic procedure for creating tags and tag sets for using the Network Configurator's device parameter editing function. 1. Creating Tags and Tag Sets Using the Network Configurator's Device Parameter Editing Function Next, the following two procedures, which can be used to effectively use network symbols in tags, are described. 2. Importing Network Symbols Created with the CX-Programmer to the Network Configurator 3. Importing Network Symbols That Were Registered to Tags with the Network Configurator to the CX-Programmer 1. Creating Tags and Tag Sets Using the Network Configurator's Device Parameter Editing Function Note The network symbols described in this section can be used only if you are using a CJ2H-CPU6@-EIP21 or CJ2M-CPU3@ CPU Unit. 1,2,3... 1. Double-click the icon of the device (for which a tag set is being created) to display the Edit Device Parameters Dialog Box. Right-click the icon to display the pop-up menu, and select Parameter - Edit. Creating a Tag Set 126 Setting Tag Data Links Section 6-2 2. Click the Tag Sets Tab at the top of the Edit Device Parameters Dialog Box. There are two kinds of tag sets: input (consume) and output (produce). 127 Section 6-2 Setting Tag Data Links Creating and Adding Tags 3. Click the Edit Tags Button. The Edit Tags Dialog Box will be displayed. Register the input (consume) tags and output (produce) tags separately. 4. Click the In - Consume Tab, and click the New Button. The Edit Tag Dialog Box will be displayed. 5. In the Name Field, enter the character string for the CPU Unit's I/O memory address or a network symbol (e.g., 100, W100, D0, Input_signal). Addresses in the following I/O memory areas can be set. Bank 18 hex Address (Text to input in Name Field.) 0000 to 6143 H000 to H511 W000 to W511 D00000 to D32767 E0_00000 to E0_32767 ··· ··· CPU Unit’s data area CIO Area Holding Area Work Area DM Area EM Area Bank 0 hex E18_00000 to E18_32767 Note (a) The H, W, D, and E characters can also be input in lower case as h, w, d, and e. 128 Section 6-2 Setting Tag Data Links (b) Be sure to directly enter the CPU Unit's I/O memory address (e.g., 100, W100, D0) or a network symbol as a character string. 6. Input the size of the tag in the Size Field, in bytes. 7. Click the Regist Button to register the tag. If an I/O memory address is specified for a tag name, the Edit Tags Dialog Box will be displayed with the next consecutive address as the tag name for editing the next tag. Once you have registered the tags, click the Cancel Button. 8. Click the Out - Produce Tab, and click the New Button. The Edit Tag Dialog Box will be displayed, like the dialog box for input tags, except for the Over Load setting. The Over Load setting determines whether outputs are cleared or continue their previous status when outputs are turned OFF with the PLC’s Output OFF function. Output inhibit settings are not required for input (reception) tag sets. • Follow the output inhibit function: Enabled (default) Output data is cleared to 0 when a PLC output inhibit occurs. • Do not follow the output inhibit function: Disabled Output data maintains its previous status even after a PLC output inhibit occurs. Select Disable or Enable. Note When any of the following errors occurs in the originator PLC while tag data links are in progress, the connection will be forcibly disconnected. • Fatal CPU Unit error • I/O refreshing error • CPU Unit WDT error • I/O bus error 129 Setting Tag Data Links Section 6-2 9. When you are finished registering the required tags, click the OK Button at the bottom of the Edit Tags Dialog Box. 10. At this point, a confirmation dialog box will be displayed to check whether the registered tag names will registered without changes as tag sets. A tag set can contain up to 8 tags, but tag sets will be registered with one tag per tag set if the tags are registered as tag sets. In this case, the Yes Button is clicked to register one tag per tag set. If the No Button is clicked, more tags can be registered at the end of the tag set. Refer to step 18 for details on adding tags to the end of the tag set. 130 Setting Tag Data Links Changing and Registering Tag Sets Section 6-2 11. The following dialog box will be displayed when the tags in the Edit Tags Dialog Box are registered directly as tag sets. 12. If an input tag has already been registered in an input tag set, and you want to change its registration to a different input tag set, it is necessary to delete the tag from the tag set in which it was originally registered. 131 Section 6-2 Setting Tag Data Links Open the Edit Device Parameters Dialog Box, select the tag set containing the tag that you want to delete, and click the Delete Button in the Edit Tag Dialog Box. (If there are other tags registered in that tag set, it is possible to delete just one tag by selecting the tag that you want to delete in the Edit Tag Set Dialog Box and clicking the Button.) At this point, a confirmation dialog box will be displayed to confirm that you want to delete the selected tag set and the tags contained in that tag set. If the No Button is clicked, only the tag set will be deleted. Click the No Button. 132 Section 6-2 Setting Tag Data Links 13. In order to edit a registered tag set and add tags, either double-click the tag set, or select the tag set and click the Edit Button. The Edit Tag Set Dialog Box will be displayed. The Tag List on the left side of the dialog box shows the tags that are already registered, and the Candidate Tag List on the right side of the dialog box shows the other tags that have not been registered yet. To add a tag, select it in the Candidate Tag List and click the Button. 14. When the PLC status is being included in the tag set, select the Include Option at the upper-right corner of the dialog box. 15. If you want to change the tag set’s name, it can be changed in this dialog box. 16. To save the changes, click the OK Button at the bottom of the Edit Tag Set Dialog Box. 17. Click the OK Button at the bottom of the Edit Device Parameters Dialog Box. 133 Setting Tag Data Links Section 6-2 18. If you want to just add new tags and register the tag set, first register the tags with steps 1 to 9. In this example, input tags D00004 and D00005 have been newly added. 19. When you are finished registering the required tags, click the OK Button at the bottom of the Edit Tags Dialog Box. 20. At this point, a confirmation dialog box will be displayed to check whether the registered tag names will be registered without changes as tag sets. Tags are just being added in this case, so click the No Button. Just the tags will be registered, without registering the tags as tag sets. 134 Section 6-2 Setting Tag Data Links 21. To register the newly added tags in a tag set, either double-click the desired tag set, or select the tag set and click the Edit Button. The Tag List on the left side of the dialog box shows the tags that are already registered, and the Candidate Tag List on the right side of the dialog box shows the other tags that have not been registered yet. 22. Select the tags that you want to add from the Candidate Tag List and click the Button. Up to 8 tags can be registered in a tag set, or up to 7 tags can be registered and two byes will be added to the size if the PLC status is included in the tag set. 23. To confirm the changes, click the OK Button at the bottom of the Edit Tag Set Dialog Box. 24. Click the OK Button at the bottom of the Edit Device Parameters Dialog Box. 135 Setting Tag Data Links Section 6-2 2. Importing Network Symbols Created with the CX-Programmer to the Network Configurator If the CJ2H-CPU6@-EIP or CJ2M-CPU3@ is used, you can create network symbols using the CX-Programmer, import them into the Network Configurator, and then create tags and tag sets. Use the following procedure. Creating Global Symbols Create global symbol with the Global Symbol Editor of the CX-Programmer and select Input or Output for the network variable properties. Safe the project when you are finished. Any global symbols with Input or Output set for the network variable property will be imported when the import procedure is performed from the Edit Device Parameters Dialog Box. Importing Symbols to the Network Configurator 1,2,3... Note 1. Start the CX-Programmer and open the project that was saved. When multiple copies of the CX-Programmer are running at the same time, it is possible to import only from the CX-Programmer project that was started first. If the global symbols that are to be imported are stored in multiple CXProgrammer project files, the projects must be started one by one to import the symbols. 2. From the devices registered in the Network Configurator, double-click the icon of the device for which to import the network symbols. The Edit Device Parameter Dialog Box will be displayed. You can also right-click the icon and select Device - Parameters - Edit from the pop-up menu. 3. Click the Import Button on the Tag Sets Tab Page of the Edit Device Parameter Dialog Box. 136 Setting Tag Data Links Section 6-2 A confirmation message will be displayed. Click the Yes Button. The symbols will be imported as shown below on the Tag Sets Tab Page. Each symbol will be imported into a different tag set and the device parameters will be automatically edited. (The symbol name will be used for the tag set name.) 137 Setting Tag Data Links Section 6-2 To place more than one input symbol (input tag) imported from the CXProgrammer into one tag set, you must delete the input tags that were registered to separate input tag sets. Select the tag sets for the symbols that are included in the one tag set and click the Delete Button. A confirmation message will be displayed. Click the No Button to delete only the tag sets. To create a new tag set for more than one tag, click the New Button. To place more than one tag in an existing tag set, double-click the tab set, or select it and click the Edit Button. The Edit Tag Set Dialog Box will be displayed. Imported tags that are not registered in another tag set will be displayed in the Candidate Tag List Area on the right. Click the Right Arrow Button to add tags individually. 138 Section 6-2 Setting Tag Data Links 4. You can change tag set names in this dialog box. To confirm a change, click the OK Button in the dialog box. 5. Perform steps 1 to 3 for all the devices that will perform tag data links. 3. Importing Network Symbols That Were Registered to Tags with the Network Configurator to the CX-Programmer If the CJ2H-CPU6@-EIP or CJ2M-CPU3@ is used, you can specify network symbols for tags using the Network Configurator. The procedure to import network symbols that were created using the Network Configurator into the CXProgrammer is described below. Exporting Tags and Tag Sets with the Network Configurator 1,2,3... 1. Select To/From File - Export to file on the Tag Sets Tab Page in the Edit Device Parameters Dialog Box to export the tag and tag set information to a CSV file. 139 Section 6-2 Setting Tag Data Links Importing the Tag and Tag Set CSV File with the CX-Programmer 1,2,3... 1. In the project global symbol table for the CJ2H-CPU6@-EIP or CJ2MCPU3@, right-click and select Import Network Variable from the pop-up menu. 2. You can add a tag as a network symbol by selecting and executing the CSV file exported using the Network Configurator. Note The following precautions apply when importing. • Tags that have a specified I/O memory address cannot be imported. • Tags are imported as network symbols in a one-dimensional WORD array. To change the data type, use the Symbol Editor of the CX-Programmer. 140 Section 6-2 Setting Tag Data Links 6-2-5 Connection Settings After creating the tag sets, click the Connections Tab at the top of the Edit Device Parameters Dialog Box, and set the following connection information. • The target devices with which connections will be opened • Whether the tag sets are input or output tag sets • The length of the packet intervals (RPI) Make the Connections settings in the originator only. The Connections settings are not necessary in the target device. Note Make the Connections settings after creating tag sets for all of the devices involved in tag data links. Connection Settings (Connections Tab) Registering Devices in the Register Device List 1,2,3... 1. Display the originator device’s Edit Device Parameters Dialog Box by double-clicking the device’s icon in the Network Configuration Window, or right-clicking the device’s icon and selecting Parameter - Edit from the pop-up menu. 2. Click the Connections Tab at the top of the Edit Device Parameters Dialog Box. All of the devices registered in the network (except the local node) will be displayed. 141 Section 6-2 Setting Tag Data Links 3. In the Unregister Device List, select the target device that requires connection settings by clicking the device so its color changes to gray, and click the Button. The selected target device will be displayed in the Register Device List, as shown in the following diagram. 4. Target node IDs are assigned to devices registered in the Register Device List. This target node ID determines the location in the originator node PLC of the Target Node PLC Operating Flag, Target Node PLC Error Flag, Registered Target Node Flag, and Normal Target Node Flag. By default, the target ID is automatically set to the rightmost 8 bits of the IP address. In the example above, the target device’s IP address is 192.168.250.2, so the device number is #002. If a target node ID is duplicated and you want to change the device number, click the Change Target Node ID Button and change the target ID. Editing Settings for Individual Connections Note 142 You can edit each connection separately. Refer to the following page for information on how to perform batch editing in a table format. Section 6-2 Setting Tag Data Links 1,2,3... 1. Select the Connection Tab and then click the New Button. The following Edit Connection Dialog Box will be displayed according to the type of device that is selected. Using an OMRON EtherNet/IP Unit or Built-in EtherNet/IP Port as the Target Using Other EtherNet/IP Devices as the Target 143 Section 6-2 Setting Tag Data Links The settings are as follows: Item Description Connection I/O Type When creating tag data links for a CS1W-EIP21, CJ1W-EIP21, CJ2B-EIP21, or CJ2M-EIP21, select Input Only (Tag Type). When creating tag data links for other target devices, select the connection I/O type specified in that device’s EDS file. Use the Input Only (ID type) setting when another company's node is the originator and does not support connection settings with a Tag type setting. Connection Type Selects whether the data is sent in multicast or unicast (pointto-point). The default setting is multicast. • Multicast connection Select this type when the same data is shared by multiple nodes. This setting is usually used. • Point-to-Point connection Select this type when the same data is not shared by multiple nodes. In a unicast connection, other nodes are not burdened with an unnecessary load. Note Refer to 6-1-2 Overview of Operation for details on using multicast and unicast connection as well as counting the number of connections. The Connection Structure Field and the following items will not be displayed if the Hide Detail Button is pressed. Packet Interval (RPI) Sets the data update cycle (i.e., the packet interval) of each connection between the originator and target. The interval can be set to between 1 and 10,000 ms for the CJ2M and 0.5 and 10,000 ms for other CPU Units in 0.5-ms increments. The default setting is 50 ms (i.e., data updated once every 50 ms). Timeout Value Sets the time until a connection times out. The timeout value is set as a multiple of the packet interval (RPI) and can be set to 4, 8, 16, 32, 64, 128, 256, or 512 times the packet interval. The default setting is 4 times the packet interval (RPI). Connection Name Sets a name for the connection. (32 characters max.) 2. When the settings have been completed, press the Regist Button. Connections Settings (Editing All Connections) 1,2,3... 144 The connection settings between the originator and all of the target devices selected in the Register Device List can be edited together in a table. 1. Select the Connections Tab, and click the Edit All Button. The following Edit All Connections Dialog Box will be displayed. Section 6-2 Setting Tag Data Links The following table describes the various settings in the dialog box. Setting Target Device Connection Name Connection I/O Type In/Out Target Variable Originator Variable Connection Type RPI Timeout Value Function Selects the target device. Any name can be given to the connection (up to 32 characters). If this field is left blank, a default name will be assigned. This Connection Name can be used for comments. When making tag data links in a CS1W-EIP21, CJ1W-EIP21, CJ2B-EIP21, or CJ2M-EIP21, select Input Only (Tag type). When making tag data links in other devices, select the connection I/O type specified in that device’s EDS file. Use the Input Only (ID type) setting when another company’s node is the originator and does not support connection settings with the Tag type setting. The connections I/O is automatically displayed based on the selected connection. • Input Only: Just In is displayed. Selects and allocates the target node’s tag set. • In: Selects the target’s output (produce) tag set. • Out: Selects the target’s input (consume) tag set. Selects and allocates the originator node’s tag set. • In: Selects the originator’s output (produce) tag set. • Out: Selects the originator’s input (consume) tag set. Selects whether the data is sent in a multicast or unicast. The default setting is multicast. • Multicast connection: Select when the same data is shared by multiple nodes. This setting is usually selected. • Point-to-Point connection: Select when the same data is not being shared by multiple nodes. In a unicast transmission, other nodes are not burdened with an unnecessary load. Note Refer to 6-1-2 Overview of Operation for details on using multicast and unicast transmissions, and counting the number of connections. Sets the packet interval (RPI) of each connection between the originator and target. The interval can be set between 1 and 10,000 ms for the CJ2M and 0.5 and 10,000 ms for other CPU Units in 0.5-ms units. The default setting is 50 ms (data refreshed once every 50 ms). Sets the time until a connection timeout is detected. The time out value is set as a multiple of the packet interval (RPI) and can be set to a 4, 8, 16, 32, 64, 128, 256, or 512 multiple. The default setting is 4× the packet interval (RPI). 2. When the settings are completed, click the OK Button. 145 Section 6-2 Setting Tag Data Links Confirming the Connections Settings 1,2,3... 1. An overview of the connections set in the Register Device List is displayed in the Connections Tab Page. 2. Click the OK Button. The following kind of diagram will be displayed. Indicates the IP address of the originator where the connection was set. 3. Repeat the Connections setting procedure until all of the connections have been set. Note 146 After completing the settings, always click the OK Button before closing the Edit Device Parameters Dialog Box and performing another operation. If the Cancel Button is clicked and the dialog box is closed, the new settings will be discarded. Section 6-2 Setting Tag Data Links 4. If the tag set’s size is changed in either the originator or target after the connection was set, the size will not match the other node and a parameter data mismatch will occur. In this case, if the connection settings have been changed, be sure to check the connections. (Refer to 6-2-17 Checking Connections.) Automatically Setting Connections Tag set names set for devices can be automatically detected to automatically set connections between input and output tag sets with the same name (or the same names excluding specified ellipses). Connections are automatically set under the following conditions. Output tag set names Except for specified ellipses, the output tag set name must be the same as the input tag set name. Ellipses can be set for the beginning or end of tag set names. Except for specified ellipses, the input tag set name must be the same as the output tag set name. Ellipses can be set for the beginning or end of tag set names. The connection type must be Input Only. Multicast and single cast connection types can be specified when executing a connection. The default setting is used. The default setting is used. Input tag set names Connection types RPI Timeouts Example 1: Automatic Connections with the Same Tag Set Names The following connections would automatically be set if there is an output tag set named A_Signal at node A and input tag sets named A_Signal at nodes B and C. Node A Output tag set: A_Signal Excluded characters: None Connection Node B Input tag set: A_Signal Node C Input tag set: A_Signal Connection EtherNet/IP 147 Section 6-2 Setting Tag Data Links Example 2: Automatic Connections with the Ellipses The following connections would automatically be set if there is an output tag set named O_Signal at node A and input tag sets named I_Signal at nodes B and C, and “O_” and “I_” were set as ellipses. Node A Output tag set: O_Signal Excluded characters: O_ and I_ Connection Node B Input tag set: I_Signal Node C Input tag set: I_Signal Connection EtherNet/IP 1,2,3... 1. Set the same tag set names for the output and input tag sets for the connection. The tag set names can also include forward and backward ellipses. 2. Select Auto Connection from the Network Menu. The connections will be set automatically. A dialog box will appear to set forward and backward ellipses for both output (product) and input (consume) tag sets as soon as automatic connection setting processing has begun. Input the ellipses and click the OK Button. Automatic setting will be processed. 3. If there are tag sets that meet the conditions for automatic connection setting, they will be displayed. 148 Section 6-2 Setting Tag Data Links Click the OK Button to start processing. 4. A device connection structure tree will be displayed when processing has been completed. 5. Use the device connection structure tree as required to change the RPI and timeout settings. Device Connection Structure Tree Connection settings can be displayed on the network configuration. Select View Device’s Connection Structure Tree from the Network Menu. 149 Section 6-2 Setting Tag Data Links • The Display the detail of Connection Check Box can be used to switch between device-level and connection-level displays of tag data link communications. • An asterisk will be displayed after the device name of the originator set for the connection. • The Edit Device Parameters Dialog Box can be displayed by selecting a connection and clicking the Edit Button. The connections can be edited in this dialog box. 6-2-6 Setting Tags Using Data Link Tool Using the EtherNet/IP Datalink Tool enables easily setting data links similar to those for the Controller Link by using only I/O memory addresses. This method has the following restrictions. • Settings can be made only for tag data links between OMRON EtherNet/ IP Units and built-in EtherNet/IP ports. • Tags must be set using I/O memory addresses. • A maximum of two tags (area 1 and area 2) can be set in one tag set. Select Network - EtherNet/IP Datalink Tool from the menus in the Network Configurator after you have registered all the devices to start the EtherNet/IP Datalink Tool. 150 Section 6-2 Setting Tag Data Links Node List The following items will be displayed in the Node Area on the left side of the window. • IP Address: The IP address of the node. • Device: The name (model number) of the device at the node. Note Data Link Table Information The node list will display the node registered in the Network Configurator. Nodes cannot be added or deleted from this window. The data link table of the node selected on the left will be displayed on the right. Each row specifies word that are allocated for data links for that node. Each row specifies the node settings for the words (area) where a data link has been created. You can set only area 1 or both area 1 and area 2. • IN/OUT: Specifies whether the link inputs data to the node or outputs data from the node. OUT can be selected only once. Once OUT has been selected for one row, IN will automatically be selected for other rows. A asterisk will be displayed if the Over Load function is disabled. (See note.) Note The Over Load function is used to clear output data when all outputs are turned OFF from the CPU Unit of the PLC. This setting is not necessary for inputs. (a) Over Load function enabled: Output data will be cleared to all zeros when all outputs from the PLC are turned OFF from the CPU Unit. (b) Over Load function disabled: Output data will be maintained even when all outputs from the PLC are turned OFF from the CPU Unit. • Area 1, Link CH: The I/O memory address of the first word in link area 1 • Area 1, Size: The number of words in link area 1. (See note.) • Area 2, Link CH: The I/O memory address of the first word in link area 2 • Area 2, Size: The number of words in link area 2. (See note.) Note With the Network Configurator, the PLC status will be shown at the beginning of each area. The PLC status includes the CPU Unit operating status (operating information and error information). 151 Section 6-2 Setting Tag Data Links • Tag Set Name: If the Wizard is used, the names will be automatically assigned using consecutive IP addresses in the following form for both input and output tags: TagSet1_192168.250.1. There is no reason to be concerned with these names. If the Wizard is not used, then names will not be automatically assigned and they must be entered directly into the data link table. • Total Size: The total number of words in areas 1 and 2. This value is automatically displayed after the sizes of areas 1 and 2 are entered. • Node: For an input tag, this is the IP address of the node that provides the output. For an output tag, “-” will be entered automatically. • Target Variable: The target tag set name. For an input tag, this is the name of the target set that provides the output. For an output tag, “-” will be entered automatically. • RPI (ms): The requested packet interval for an input tag. For an output tag, “-” will be entered automatically. Setting Procedure The setting procedure is described here along with setting examples. ■ Setting Example A Area 1 memory area = Work Area (W) Area 1 start address = 0 Area 1 size = 50 words Area 2 memory area = DM Area (D) Area 2 start address = 50 Area 2 size = 100 words ■ Allocations Node 1 (IP address: 192.168.250.1) Node 2 (IP address: 192.168.250.2) Node 3 (IP address: 192.168.250.3) EtherNet/IP Area 1 W0 50 words #1 W50 50 words #2 #2 #2 W100 50 words #3 #3 #3 D50 100 words #1 D150 100 words #2 #2 #2 D250 100 words #3 #3 #3 W0 #1 W0 #1 Area 2 1,2,3... 152 D50 #1 D50 #1 1. Select Wizard from the Data Link Menu. The Datalink Wizard Dialog Box will be displayed. Setting Tag Data Links Section 6-2 2. Select the memory area (here, W) in the Memory Field and enter the starting address (here, 0) and number of words (here, 50) in the Start Address and Size Fields for Area 1. 3. Select the memory area (here, D) in the Memory Field and enter the starting address (here, 50) and number of words (here, 100) in the Start Address and Size Fields for Area 2. 4. Select the Enable Over Load Check Box if the Over Load function is necessary. 5. Click the OK Button. The following dialog box will be displayed. Click the Yes Button to continue creating the data link table, or click the No Button to cancel the operation. 153 Setting Tag Data Links Section 6-2 If the creating the data link table is continued, the data link table will be created with the same size of data link for all registered nodes. Examples are shown below. Automatic Allocation Results for Node 1 (IP Address: 192.168.250.1) Automatic Allocation Results for Node 2 (IP Address: 192.168.250.2) 154 Section 6-2 Setting Tag Data Links Automatic Allocation Results for Node 3 (IP Address: 192.168.250.3) 6. After entering all of the settings in the data link table, select Save from the File Menu. A consistency check will be performed on the table and the results will be displayed. a. Table Inconsistencies The following Check Result Dialog Box will be displayed. Correct the data link table according to the displayed information. To save the check results, click the Copy To Clipboard Button and paste the results to other file, such as the text pad. Click the OK Button. The following message will be displayed. Click the OK Button again to return to the EtherNet/IP Datalink Tool Window. 155 Section 6-2 Setting Tag Data Links b. No Table Inconsistencies The following message will be displayed. Click the OK Button. 7. Select Exit from the File Menu. The EtherNet/IP Datalink Tool will be exited and you’ll return to the Network Configurator. 8. Returning to the Network Configurator Click the icon for each device and check the settings made with the EtherNet/IP Datalink Tool in the Edit Device Parameters Dialog Box. 6-2-7 Creating Connections Using the Wizard You can use the Network Configurator's Wizard to easily create connections between OMRON PLCs following the instructions provided by the Wizard. Network Configurator version 3.10 or higher is required to use the Wizard. Note The Wizard can be used only with the following OMRON EtherNet/IP devices. Device name CJ1W-EIP21 CJ1W-EIP21(CJ2) CJ2B-EIP21 CJ2M-EIP21 CS1W-EIP21 Remarks CJ1W-EIP21 mounted to CJ1 CPU Unit CJ1W-EIP21 mounted to CJ2 CPU Unit Built-in EtherNet/IP port in CJ2H CPU Unit Built-in EtherNet/IP port in CJ2M CPU Unit CJ1W-EIP21 mounted to CS1 CPU Unit Use the following procedure to create connections (i.e., data links) with the Wizard. 1,2,3... 1. Set tags and tag sets for all devices before starting the Wizard. Refer to 62-4 Creating Tags and Tag Sets for the setting procedure. 2. For tag data links between OMRON PLCs, a connection is created in the PLC (i.e., the originator device) that receives data as input data. First, select the registered device for which you want to create a connection in the Network Configuration Window of the Network Configurator, and then select Device - Parameters - Wizard from the menus. 156 Section 6-2 Setting Tag Data Links The following dialog box will be displayed before the Wizard starts. Click the Yes Button to delete the connections that have been set with OMRON PLCs before starting the Wizard. 3. Create the connection following the instructions that are given by the Wizard after the Wizard starts. (See the following figure.) 4. A list of tag sets is displayed on the right side of the Wizard Dialog Box with target devices that support receiving input data. Select the tag sets that you want to receive at the originator device. The following tables describes the meanings of the icons and check marks displayed in the tag set list. Icon Note Display position Status All All output tag sets for all devices are selected. Device All output tag sets for the applicable device are selected. Tag set The applicable output tag sets are selected. These are the tag sets that will be set in the connection. All All or some output tag sets for some devices are selected. Device Some output tag sets for applicable devices are selected. All All output tag sets for all devices are not selected. Device All output tag sets for applicable devices are not selected. Tag set The applicable output tag sets are not selected. The connections for this tag set will be deleted. Device No applicable tag sets. Tag sets that are used in connections that are already set are not displayed. 157 Setting Tag Data Links Section 6-2 The following display will appear when you click the Show Detail Button. The specified values for detailed parameters will be displayed. Change the values as required. The connection name cannot be set. They are automatically created using the following rule. default_N (where N is a 3-digit number (001, 002, etc.) starting from 1) 5. Click the Next Button to switch to the table in the following Wizard Dialog Box. Follow the instructions to select and input from the list box the input tag set of the originator device that receives the output tag set of the target device. • The blank area in the Input Tag Set Column is the connection that you are creating. • The rows in which there are input tag sets are connections that are already set. • To prevent duplicate settings, input tag sets that have been used are not displayed in the list box for input tag sets. • If there is no applicable input tag set, you can edit a tag set or create a new one by using the Edit Tag Sets Button and Edit Tag Button. 6. Once the input tag set settings have been completed, click the Finish Button. You can check the set connection by selecting Network - View Devices Connection Structure Tree from the menus. • The Wizard can be ended even if the input tag set includes a blank row. In that case, a connection is not created for the blank row. • You can delete a connection by deleting the input tag sets that were previously set. 158 Section 6-2 Setting Tag Data Links 6-2-8 Creating Connections by Device Dragging and Dropping You can create a connection to the originator by dragging a target device and dropping it at the originator device. Network Configurator version 3.10 or higher is required to drag and drop devices to make connections. Example: Drag the target device at 192.168.250.1 and drop it at the originator device at 192.168.250.100. Drag & Drop Note The EtherNet/IP originator device (i.e., a device in which connections can be set) must be one of the following OMRON EtherNet/IP devices. Device name CJ1W-EIP21 CJ1W-EIP21(CJ2) CJ2B-EIP21 CJ2M-EIP21 CS1W-EIP21 Remarks CJ1W-EIP21 mounted to CJ1 CPU Unit CJ1W-EIP21 mounted to CJ2 CPU Unit Built-in EtherNet/IP port in CJ2H CPU Unit Built-in EtherNet/IP port in CJ2M CPU Unit CJ1W-EIP21 mounted to CS1 CPU Unit Use the following procedure to create connections (i.e., data links) by dragging and dropping devices. 1,2,3... 1. Set the tags and tag sets for the target device that will be dragged. a. Refer to 6-2-4 Creating Tags and Tag Sets for information on creating the settings if the target is one of the OMRON EtherNet/IP devices given above. b. If the target is another EtherNet/IP device, refer to the manual of that device and perform settings as required. 2. A dialog box as in the following figure for connection allocation will be displayed when you drag the target device and drop it at the OMRON EtherNet/IP device. a. Using One of the Above OMRON EtherNet/IP Devices As Target Select the output tag set from Target Device Area on the right side of the Edit Connection Dialog Box, and then select the input tag set to receive the output tag set in the Originator Device Area on the left. 159 Section 6-2 Setting Tag Data Links • If there is no applicable input tag set at the originator, you can create a new one by using the Edit Tag Sets Button and Edit Tag Button. b. Using Other EtherNet/IP Devices as Target The connection I/O type list box in the upper part of the Connection Settings Dialog Box displays the connection I/O types that can be selected. Select the connection I/O type according to your application. • The connection I/O types that can be selected depend on the target device. • Items that can be selected will depend on the connection I/O type that is selected. • Select the output, input, or both output and input tag sets at the target and specify the corresponding input, output, or both input and output tag sets at the originator. • If there is no applicable tag set at the originator, you can create a new one by using the Edit Tag Sets Button and Edit Tag Button. The following display will appear when you click the Show Detail Button. The specified values for detailed parameters will be displayed. Change the values as required. Connection names are automatically created using the following rule. default_N (where N is a 3-digit number (001, 002, etc.) starting from 1) 160 Section 6-2 Setting Tag Data Links Note The following dialog box will be displayed if a target device that does not have I/O data is dropped. Before dropping again, refer to the manual of the applicable device and create the I/O data (i.e., output tag sets) required to create a connection. 3. After you have set all of the connection, click the Regist Button to create the connection. When creating the connection has been completed, the input tag set and output tag set will be blank. Next, you can continue to create connections by selecting the connection I/O type and setting a tag set. 6-2-9 Connecting the Network Configurator to the Network This section explains how to connect the Network Configurator to the network. Connecting through Ethernet Note The Windows firewall settings must be changed when making this connection for the first time in Windows XP, Vista, or Windows 7. For details on changing the firewall settings, refer to Appendix G Precautions for Using Windows XP, Vista, or Windows 7. Connect to the EtherNet/IP Unit’s Ethernet port via the Ethernet network. 1,2,3... 1. Select Option - Select Interface - Ethernet I/F. 2. Select Network - Connect. If there are multiple Ethernet interfaces on the computer, the Select Connect Network Port Dialog Box will be displayed. Select the interface that is to be connected, and press the OK Button. The following dialog box will be displayed. 3. Click the OK Button. Select the network to be connected. 161 Section 6-2 Setting Tag Data Links The Network Configurator will connect to the EtherNet/IP network. If the Network Configurator is connected online properly, On-line will be displayed in the status bar at the bottom of the window. The network connection icon will be displayed in blue in the Network Tab Page in which the Network Configurator is connected. Network connection icon The connecting network can be switched by selecting Network - Change Connect Network. Connecting through the CPU Unit’s Peripheral or RS-232C Port Connect to the EtherNet/IP Unit’s Ethernet port via the CPU Unit’s peripheral port or RS-232C port. 1,2,3... 1. Select Option - Select Interface - CS/CJ1 Serial Port → EIP Unit I/F. 2. Select Network - Connect. The following dialog box will be displayed. 162 Setting Tag Data Links Section 6-2 3. Input the EtherNet/IP Unit’s unit number in the Unit No. Field, select the connecting COM port number, and click the OK Button. Usually, the Baud Rate is left at this setting. The following dialog box will be displayed. 4. After clicking TCP:2, click the OK Button. The Network Configurator will be connected to the EtherNet/IP network. If the Network Configurator is connected online properly, On-line will be displayed in the status bar at the bottom of the window. Connecting through the CPU Unit’s USB or RS-232C Port (CJ2 CPU Units Only) Connect to the EtherNet/IP Unit’s Ethernet port via the CPU Unit’s USB port or RS-232C port. 1,2,3... 1. Select Option - Select Interface - CJ2 USB/Serial Port to set the communications interface. 163 Section 6-2 Setting Tag Data Links 2. Select Network - Connect. The Setup Interface Dialog Box will be displayed. 3. Set the port type to either USB or serial. 4. Set the port to use and then click the OK Button. (Leave the baud rate at the default setting.) The following dialog box will be displayed. 5. Select the Backplane Icon and click the Refresh Button. The CPU Unit, CPU Bus Units, and Special I/O Units connected in the PLC will be displayed as shown below. 6. Click the + icon to the left of the EtherNet/IP Unit or built-in EtherNet/IP port (CJ1W-EIP21(CJ2) or CJ2B-EIP21). The TCP ports on the EtherNet/IP Unit will be displayed as shown below. 164 Section 6-2 Setting Tag Data Links Select the TCP port of the EtherNet/IP Unit. 7. Select the port for the EtherNet/IP Unit and then click the OK Button. The Network Configurator will be connected to the EtherNet/IP network. If the Network Configurator goes online normally, “On-line” will be displayed in the status bar at the bottom of the window. Connecting to an EtherNet/IP Network via an Ethernet Unit Note (1) Windows firewall settings must be changed when this connection is made for the first time using Windows XP (SP2 or higher), Vista, or Windows 7. Refer to Appendix G Precautions for Using Windows XP, Vista, or Windows 7: Using EtherNet/IP with Windows XP, Vista, or Windows 7 for information on how to make the changes. (2) Use the CX-Integrator to correctly set the FINS routing tables for the CS/ CJ-series CPU Unit that will be the relay node. Network Configurator on Windows computer Ethernet EtherNet/IP Unit Ethernet Unit CS/CJ-series CPU Unit EtherNet/IP EtherNet/IP Unit or built-in EtherNet/IP port CS/CJ-series CJ2 CPU Unit 1,2,3... 1. Select Option - Select Interface - Ethernet → CS/CJ1 ETN-EIP Unit I/F. 165 Section 6-2 Setting Tag Data Links 2. Select Network - Connect. The following Setup Interface Dialog Box will be displayed. 3. Click the Setup Button in the Setup Interface Dialog Box. The Registration of the connection Dialog Box will be displayed. Enter the network information for the connection destination, and then click the Add Button to register the settings. The registration information details are as follows: a. Registration name Enter any name. b. Host (PC) information Enter information for the computer that has the Network Configurator installed. • Network address Same number as the network address of the Ethernet Unit of the PLC that will be the relay node. • Node address Last value in the computer's IP address (e.g., 1 for 192.168.250.1) c. Remote Information - EtherNet/IP Unit Enter the information for the EtherNet/IP Unit of the PLC that will be the relay node. • Network address Network address set in the routing tables 166 Section 6-2 Setting Tag Data Links • Node address Last value in the IP address of the Unit above (e.g., 3 for 192.168.251.3) • Unit number of CPU Bus Unit Unit number of the Unit above d. Remote Information - Ethernet Unit Enter the information for the Ethernet Unit of the PLC that will be the relay node. 4. Once the settings have been registered, the Setup Interface Dialog Box will be displayed again. Check the registered information that has been entered, and then click the OK Button. 5. The following dialog box will be displayed. Select TCP:2, which represents the EtherNet/IP port, and then click the OK Button. The Network Configurator will connect to the EtherNet/IP network, and “On-line” will be displayed in the status bar at the bottom of the window when connection has been properly made online. Note A list of nodes on the EtherNet/IP network you are attempting to connect to will be displayed when the Refresh Button or the icon ( ) at the left of TCP:2 167 Section 6-2 Setting Tag Data Links is clicked in the dialog box above. (Refer to the following figure.) 6-2-10 Downloading Tag Data Link Parameters To make tag data links, you must download tag data link parameters, such as tag set settings and connection settings, to all devices in the EtherNet/IP network. When the download operation is executed, the tag data link parameters will be transferred to the EtherNet/IP Units that require the settings. The following procedure shows how to download the tag data link parameters. Refer to 6-2-9 Connecting the Network Configurator to the Network for information on how to connect the Network Configurator to the network. Note • If the target node IP address is not set correctly, invalid device parameters may be set in the wrong PLC. Check the connected PLC before downloading parameters. • If incorrect tag data link parameters are set, it may cause equipment to operate unpredictably. Even when the correct tag data link parameters are set, make sure that there will be no effect on equipment before transferring the data. • When network symbols are used in tag settings, a connection error will result if the symbols are not also set in the CPU Unit. Before downloading the tag data link parameters, check to confirm that the network symbols have been set in the CPU Unit. On the Connection and Tag Status Tab Pages described in 14-1-1 The Network Configurator’s Device Monitor Function, check whether the network symbol, tag, and connection settings are correct. • When a communications error occurs, the output status depends on the specifications of the Unit being used. When a communications error occurs for a Unit that is used along with output devices, check the operating specifications and implement safety countermeasures. • The EtherNet/IP Unit is automatically restarted after the parameters have been downloaded. This restart is required to enable the tag set and connection information that have been set. Before downloading the parameters, check to confirm that restarting will not cause any problems with the equipment. • Do not disconnect the Ethernet cable or reset or turn OFF the power to the EtherNet/IP Unit while the parameters are being downloaded • For EtherNet/IP Units or built-in EtherNet/IP ports with revision 2 or later, the CPU Unit can download tag data link parameters in either RUN mode or MONITOR mode. (They can also be downloaded in PROGRAM mode.) • For EtherNet/IP Units with revision 1, tag data link parameters can be downloaded only when the CPU Unit is in PROGRAM mode. • Even for Units with revision 2 or later, all CPU Units must be in PROGRAM mode to download the parameters if any Units with revision 1 are included in the network. 168 Section 6-2 Setting Tag Data Links 1,2,3... 1. Connect the Network Configurator online. 2. There are two ways to download the parameters. • Downloading to All Devices in the Network Select Network - Download. The following dialog box will be displayed. • Downloading Individually to Particular Devices Select the icon of the EtherNet/IP Unit to which you want to download. To select multiple nodes, press and hold the Shift Key while selecting additional icons. (In the following example, 2 nodes are selected: 192.168.250.1 and 192.168.250.2.) After selecting the icons, click the right mouse button over the icon to display the pop-up menu, and select Parameter - Download. The following dialog box will be displayed. 3. Click the Yes Button to download the tag data link parameters to the EtherNet/IP Unit. The following dialog box will be displayed if any of the CPU Units is not in PROGRAM mode. • Display When All EtherNet/IP Units and Built-in EtherNet/IP Ports are Revision 2 or Higher 169 Section 6-2 Setting Tag Data Links If the Download after changed to Program mode Button is clicked, all CPU Units will be changed to PROGRAM mode and the parameters will be downloaded. Confirm safety for all controlled equipment if the CPU Units are changed to PROGRAM mode. The operating mode can be returned to the previous setting after the parameters have been downloaded. The Download with Current mode Button can be clicked to download load the parameters even when one or more CPU Units is in RUN or MONITOR mode. • Display When Even One EtherNet/IP Unit Is Revision 1 When the Download after changed to Program mode Button is clicked, all CPU Units will be changed to PROGRAM mode and the parameters will be downloaded. Confirm safety for all controlled equipment if the CPU Units are changed to PROGRAM mode. The operating mode can be returned to the previous setting after the parameters have been downloaded. During the download, the following progress monitor will be displayed to show the progress of the download. 170 Section 6-2 Setting Tag Data Links If the operating mode of one or more CPU Units was changed to download the parameters, the CPU Units can be returned to the previous operating mode. If the No Button is clicked, the CPU Units will remain in PROGRAM mode. 4. The following dialog box will be displayed, indicating that the download was completed. 6-2-11 Uploading Tag Data Link Parameters Tag data link parameters (such as the tag set settings and connection settings) can be uploaded from EtherNet/IP Units in the EtherNet/IP network. The following procedure shows how to upload the parameters. For details on connecting to the network from the Network Configurator, refer to 6-2-9 Connecting the Network Configurator to the Network. 1,2,3... 1. Connect the Network Configurator to the network. 2. There are two ways to upload the parameters. • Uploading from All Devices in the Network Select Network - Upload. The following dialog box will be displayed. • Clicking the Yes Button: Parameters will be uploaded only from the devices registered in the Network Configuration Window. Parameters will not be uploaded from devices that are not registered in the Network Configuration Window. • Clicking the No Button: • If parameters are being uploaded from all devices in the network, the parameters will be newly uploaded from all devices. The current network configuration information will be lost. • If parameters are being uploaded from specified devices only, the upload operation will be cancelled and the upload will not be performed. • Clicking the Cancel Button: The upload operation will be cancelled and the upload will not be performed. • Uploading Individually from Particular Devices 171 Section 6-2 Setting Tag Data Links Select the icon of the EtherNet/IP Unit from which you want to upload. To select multiple nodes, press and hold the Shift Key while selecting additional icons. (In the following example, 2 nodes are selected: 192.168.250.1 and 192.168.250.2.) After selecting the icons, click the right mouse button over the icon to display the pop-up menu, and select Parameter - Upload. The following confirmation dialog box will be displayed. Click the Yes Button or No Button. During the upload, the following progress monitor will be displayed to show the progress of the upload. 3. The following dialog box will be displayed, indicating that the upload was completed. 6-2-12 Verifying the Tag Data Links Tag data link parameters (such as the tag set settings and connection settings) can be compared with the EtherNet/IP Units in the EtherNet/IP network. The following procedure shows how to compare the parameters. For details on connecting to the network from the Network Configurator, refer to 6-2-9 Connecting the Network Configurator to the Network. 172 Section 6-2 Setting Tag Data Links Verifying the Network Configuration 1,2,3... Compare the list of registered devices in the Network Configuration Window with the devices connected on the EtherNet/IP network, and check the IP addresses and device types. This function cannot be used to verify device parameters. 1. Connect the Network Configurator to the network. 2. The following progress monitor will be displayed to show the progress as data is read from the network and compared. 3. The results of the comparison between the network configuration file and data from the network are displayed as follows. • Differences Not Found in the Comparison • Differences Found in the Comparison • Differences Found in the Device Type. 173 Section 6-2 Setting Tag Data Links Click the OK Button or the Close Button. Verifying the Device Parameters 1,2,3... Use the following procedure to compare the device parameters for the devices selected in the Network Configuration Window with those of the devices connected on the EtherNet/IP network. The IP addresses, device types, and device parameters are compared. 1. Connect the Network Configurator to the network. 2. Click the icon of the EtherNet/IP Unit that is to be verified. To select multiple nodes, hold down the Shift Key while clicking the icons. (In the following example, the 192.168.250.1 and 192.168.250.2 nodes are selected.) With the icons selected, right-click and select Parameter - Verify from the pop-up menu. 3. The following dialog box will be displayed. Click the Yes Button or the No Button. 4. One of the following dialog boxes will be displayed. • Differences Not Found in the Comparison • Differences Found in the Comparison 174 Section 6-2 Setting Tag Data Links • Differences Found in the Device Type Click the OK Button or the Close Button. 5. If multiple nodes have been selected, the following message will be displayed. Click the Yes Button. The comparison results will be displayed in order of the selected nodes. 6-2-13 Starting and Stopping Tag Data Links Automatically Starting Tag Data Links Tag data links will start operating automatically immediately after the tag data link parameters are downloaded from the Network Configurator. (They will also start automatically when the power to the PLC is turned ON or the CPU Unit is restarted.) Starting and Stopping All Tag Data Links on the Network Using the Network Configurator All tag data links on the network can be started and stopped by selecting I/O Connection - Start/Stop from the Network Menu. Starting and Stopping Tag Data Links for Individual Devices Using the Network Configurator You can start and stop tag data links for individual devices using the following buttons in the Monitor Device Dialog Box. This applies only to tag data links for which the device is the originator. Access the Monitor Device Dialog Box by selecting Monitor from the Device Menu. 175 Section 6-2 Setting Tag Data Links Start Connection Button: Starts all connections for which the device is the originator. Stop Connection Button: Stops all connections for which the device is the originator. Note Connections will be cut off if any of the following errors occurs in the CPU Unit that is the originator while tag data links are active. • Fatal CPU Unit error • I/O refresh error • CPU Unit WDT error • I/O bus error 6-2-14 Clearing the Device Parameters The device parameters saved in the EtherNet/IP Units in the EtherNet/IP network can be cleared (returned to their default settings). The following procedure shows how to clear the device parameters. For details on connecting to the network from the Network Configurator, refer to 6-2-9 Connecting the Network Configurator to the Network. 1,2,3... 1. Connect the Network Configurator to the network. 2. Select the icon of the EtherNet/IP Unit in which you want to clear the device parameters. In the following example, 2 nodes are selected: 192.168.250.1 and 192.168.250.2. To select multiple nodes, press and hold the Shift Key while selecting additional icons. 176 Section 6-2 Setting Tag Data Links 3. Select Device - Reset. The following dialog box will be displayed. • Clicking the Yes Button: The following dialog box will be displayed. Select one of the following options and click the OK Button. • Emulate cycling power Restarts the Unit. • Return to the out-of-box configuration, and then emulate cycling power Returns the Unit to its factory default settings, and restarts the Unit. • Clicking the No Button: The device parameters are not cleared or reset. 6-2-15 Saving the Network Configuration File Device parameters set in the Network Configurator, or device parameters uploaded from the network can be saved as a network configuration file. 1,2,3... 1. Select File - Save As. The following dialog box will be displayed. The File name Field will contain Untitled.nvf as the default file name. 2. Input the file name, and click the Save Button. 177 Section 6-2 Setting Tag Data Links The network configuration file save operation is complete. 3. When the network configuration is changed later, the existing network configuration file can be overwritten by selecting File - Save or clicking the Button. 4. You can select the Select target network Check Box in the Option Area to save a network configuration file with only the required networks. Select the check boxes of the networks to save and click the OK Button. 6-2-16 Reading a Network Configuration File A previously saved network configuration file can be read into the Network Configurator. 178 Section 6-2 Setting Tag Data Links 1,2,3... 1. Select File - Open or click the be displayed. Button. The following dialog box will If the network configuration file that you want to read is not displayed, change to (Look in) another folder. 2. When you click and select the network configuration file that you want to read, that file name will be displayed in the File name Field. 3. Click the Open Button to read the network configuration file. 4. The Network Configurator’s Title Bar will display the name of the file that was read. 179 Section 6-2 Setting Tag Data Links 5. Select any of the options as necessary. The options are listed below. Option Select target network Add to current document Note Function Allows you to select specific networks from the network configuration and open them. Allows you to add the networks from the network configuration file being opened to the current configuration file. The save format will vary depending on the Network Configurator version. Configuration files (*.ncf) created using the Network Configurator for EtherNet/IP (version 2 or higher) can be imported (opened) by selecting External Data - Import from the File Menu. 6-2-17 Checking Connections Check the consistency of connection parameters for network configuration files with device parameters set using the Network Configurator and device parameters uploaded from the network. 1. Select Check Connections in the Network Menu. The following dialog box will be displayed if parameters are normal. The following dialog box will be displayed if there are parameter errors. Check the displayed details and review the settings. If an inconsistency occurs, open the originator's Edit Device Parameter Dialog Box and click the Connection Tab. The inconsistent connection will be displayed with a icon (instead of the normal icon). To change the connection setting and select a different target variable, select the connection as shown below and click the Edit Button. 180 Section 6-2 Setting Tag Data Links Icon (When normal: ) 6-2-18 Changing Devices Devices that are registered in a network configuration with the Network Configurator can be changed. Select Change Device from the Device Menu to display a list of the devices that can be changed to. Select the desired device. A device can be changed only when there is complete or upward compatibility with the device being changed to. Device Changes Device after change CJ1WEIP21 CS1WEIP21 CJ1WEIP21 CS1WEIP21 CJ1WEIP (CJ2) CJ2BEIP21 CJ2M-EIP21 Device before change Revision 1.01 1.01 2.01 2.01 2.01 2.01 2.01 CJ1W-EIP21 1.01 --- OK OK OK OK OK OK if there are less than 33 tags CS1W-EIP21 1.01 OK --- OK OK OK OK OK if there are less than 33 tags CJ1W-EIP21 2.01 No No --- OK OK OK OK if there are less than 33 tags CS1W-EIP21 2.01 No No OK --- OK OK OK if there are less than 33 tags CJ1W-EIP (CJ2) 2.01 No No OK if no vari- OK if no variables in tags ables in tags --- OK OK if there are less than 33 tags CJ2B-EIP21 2.01 No No OK if no vari- OK if no variables in tags ables in tags OK --- OK if there are less than 33 tags CJ2M-EIP21 2.01 No No OK if no vari- OK if no variables in tags ables in tags OK OK --- 6-2-19 Displaying Device Status Device status is displayed using the following icons in Maintenance Mode. To enter maintenance mode, select Large Icons - Maintenance Mode from the View Menu. 181 Section 6-2 Setting Tag Data Links Icon (gray) Status Offline Default (no configuration) (turquoise edge) (green) Idle (CPU Unit of PLC is in PROGRAM mode.) Communications normal (CPU Unit of PLC is in RUN or MONITOR mode.) Warning (A non-fatal error has occurred in the CPU Unit of the (yellow) PLC.) Alarm (A fatal error has occurred in the CPU Unit of the PLC.) (red) (blue) 182 Ladder Programming with Tag Data Links 6-3 6-3-1 Section 6-3 Ladder Programming with Tag Data Links Ladder Programming Related to Tag Data Links If data in the ladder program is linked by tag data links, add conditions 1 to 4 in the ladder program for that data. If you want to use target node PLC flags as input conditions, add conditions 5 and 6. For details on the various flags, refer to 4-2 CIO Area Allocations. Conditions showing the EtherNet/IP Unit’s Tag Data Links are enabled: 1. The Unit Error Occurred Flag (n+10, bit 00) is OFF, 2. and the Online Flag (n+11, bit 00) is ON, 3. and the Tag Data Link Operating Flag (n+11, bit 01) is ON. Conditions showing that connections are established with the target device, and tag data links are operating: 4. The corresponding Normal Target Node Flag (in words n+20 to n+23) is ON. The location of the Normal Target Node Flags depends on the layout setting. For details on the layout settings, refer to 4-2-2 Details of the Allocated CIO Area Words. Note With revision 2 or higher, the Normal Target Node Flag will turn ON only after the data for all connections for the target device has been refreshed in the CPU Unit. With revision 1, the Normal Target Node Flag will turn ON after the data for only one connection for the target device has been refreshed in the CPU Unit. Condition showing that the Target Node PLC is operating (OMRON PLCs only): 5. The corresponding Target Node PLC Operating Flag (in words n+2 to n+5) is ON. Condition showing the Target Node PLC’s fatal or non-fatal error status (OMRON PLCs only): 6. The corresponding Target Node PLC Error Flag (in words n+6 to n+9) is OFF. When you want to use the Target Node PLC Error Flag, the PLC status must be included in the tag sets for both the originator and target. Include the PLC status by using the Network Configurator to select the Include Options in the Edit Tag Set Dialog Boxes. For details, refer to 6-3-2 Status Flags Related to Tag Data Links. Example of Programming to Detect Normal Status The following programming can be used to confirm that normal communications are being performed for each target node. If the PLC status is included in the tag data, the status of the PLC can also be detected. 183 Section 6-3 Ladder Programming with Tag Data Links Programming for Revision 2 or Higher Tag Data Link Operating Normal Target Node Flag 1 PLC Operating Flag 1 PLC Error Flag 1 Node 1 Data Link Normal Operation Flag n+11 bit 01 n+20 bit 01 n+2 bit 01 n+6 bit 01 Normal Target Node Flag 2 PLC Operating Flag 2 PLC Error Flag 2 Node 2 Data Link Normal Operation Flag n+20 bit 02 n+2 bit 02 n+6 bit 02 Programming for Revision 1 and Revision 2 Tag Data Link Operating All Tag Data Links Operating Normal Operation Flag n+11 bit 01 n+12 bit 14 PLC Operating Flag 1 PLC Error Flag 1 Node 1 Data Link Normal Operation Flag n+2 bit 01 n+6 bit 01 PLC Operating Flag 2 PLC Error Flag 2 Node 2 Data Link Normal Operation Flag n+2 bit 02 Programming to Detect Errors: Example 1 n+6 bit 02 The following programming can be used to check for errors for each target node. This programming is used to detect errors only after the data links for all nodes have started normally. Programming for Revision 2 or Higher Tag Data Link Operating Normal Target Node Flag 1 Node 1 Error output n+11 bit 01 n+20 bit 01 Normal Target Node Flag 1 Node 1 Error output n+20 bit 01 Normal Target Node Flag 2 Node 2 Error output n+20 bit 02 Normal Target Node Flag 2 Node 2 Error output n+20 bit 02 Programming to Detect Errors: Example 2 184 The following programming can be used to detect tag data link errors at the local node. Section 6-3 Ladder Programming with Tag Data Links Programming for Revision 1 or Higher Tag Data Link Operating Unit Error Occurred DIFD 10000 n+11 bit 01 n+10 bit 00 Unit Error Occurred DIFU 10000 n+10 bit 00 10000 Release Flag Local node Error output Local node Error output Example of Programming to Process Data The following type of programming can be used to process data only when the data links are operating normally. Additional part The parts of the ladder program that use the data link area for the relevant node are processed only when the corresponding Normal Operation Flag is ON. Normal Operation Flag Normal Operation Flag Interlocks (IL and ILC instructions) and jumps (JMP and JME instructions) can also be used to process data only when the data links are operating normally as shown below. Node A Data Link Normal Operation Flag IL Node A data processing ILC Node B Data Link Normal Operation Flag IL Node B data processing ILC Node C Data Link Normal Operation Flag IL Node C data processing ILC 185 Ladder Programming with Tag Data Links Note 6-3-2 Section 6-3 Even if an error occurs in communications with a target device, the input data from the target device will remain stored in words allocated in memory to the local node. To prevent malfunctions, write the ladder program so that input data processing will not be performed when the Unit Error Occurred Flag (word n+10 bit 00) is ON. Status Flags Related to Tag Data Links The status of the tag data links is reflected in the following words. Name (allocated area) Target Node PLC Operating Flag Information Layout set to default settings: Words n+2 to n+5 Layout set to user settings: Words n+32 to n+47 Contents Each flag indicates the operating status of the corresponding target node PLC of connections in which the EtherNet/IP Unit is the originator. The flag corresponding to the target node’s target ID will be ON when the PLC Operating Flags for all connections with that target node indicate that the PLC is operating. Note Corresponds to the PLC Each node address’s flag location (i.e., target ID) status’s PLC Operating can be changed from the Network Configurator. Flag. The PLC status flags are enabled when the PLC status is included in the communications data for both the originator and target. The data in this table is refreshed when necessary. Target Node PLC Error Flag Infor- Each flag indicates the error status (logical OR mation of non-fatal and fatal errors) of the corresponding target node PLC of connections in which the EthLayout set to default settings: erNet/IP Unit is the originator. The flag correWords n+6 to n+9 sponding to the target node’s target ID will be Layout set to user settings: ON if even one error is indicated in any of the Words n+48 to n+63 connections with that target node. Note Corresponds to the PLC Each node address’s flag location (i.e., target ID) status’s PLC Error Flag. can be changed from the Network Configurator. The PLC status flags are enabled when the PLC status is included in the communications data for both the originator and target. The data in this table is refreshed when necessary. Normal Target Node Flag Table Each flag indicates the connection status of the corresponding target node PLC of connections Layout set to default settings: in which the EtherNet/IP Unit is the originator. Words n+20 to n+23 The flag corresponding to the target node’s tarLayout set to user settings: get ID will be ON when connections are estabWords n+16 to n+31 lished for all connections with that target node Note Does not correspond to the indicate that the PLC is operating. PLC status. Each node address’s flag location (i.e., target ID) can be changed from the Network Configurator. The data in this table is refreshed when necessary. 186 SECTION 7 Message Communications Functions This section describes message communications using FINS messages and explicit messages. 7-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188 7-2 FINS Message Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 7-3 Explicit Message Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192 7-4 Message Communications Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . 193 7-5 Message Communications Error Indications . . . . . . . . . . . . . . . . . . . . . . . . . 194 7-6 Message Communications Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195 187 Section 7-1 Overview 7-1 Overview The message communications functions send command/response messages between nodes on the Ethernet network. The messages can be sent between a computer and PLC, between two PLCs, between an OMRON PLC and a master made by another company, or between slaves. The messages can be used to send/receive data; read time data, error logs, and other data; or control operation, e.g., by force-setting/resetting bits. There are two types of messages: FINS messages and explicit messages. Item Outline Remote device Features FINS messages Message communications for OMRON products that use the FINS protocol. • Computer with an Ethernet interface • OMRON PLCs (with a CS/CJseries EtherNet/IP Unit, built-in EtherNet/IP port, or Ethernet Unit) Explicit messages Standard ODVA message communications using the CIP protocol. • Computer with an Ethernet interface • Another company’s masters or slaves. • OMRON PLCs (with a CS/CJseries EtherNet/IP Unit or built-in EtherNet/IP port) • Supports message communica• Send and receive the various tions with other companies’ EtherFINS commands to provide an Net/IP devices. even greater range of services than the CIP UCMM messages. CS/CJ Series • Provide transparency in mes• CS1W-EIP21 sage communications with other OMRON networks, such as Con- • CJ1W-EIP21 troller Link, SYSMAC LINK, and • CJ2H-CPU@@-EIP Ethernet. • CJ2M-CPU3@ (CS1/CJ1 CPU Units with unit version 2.0 or later or CJ2 CPU Units: Up to 8 levels, CPU Units with unit version earlier than 2.0: Up to 3 levels) Send FINS communications function Receive Message communications functions Send Explicit message communications function Receive 188 Section 7-1 Overview Overall Structure CPU Unit CMND(490) instruction CMND(490) instruction (2810 Hex) EtherNet/IP Unit FINS message function FINS message FINS Explicit message Explicit message function OMRON special message communications Ethernet (EtherNet/IP) network FINS message EtherNet/IP message communications Explicit message Note With the EtherNet/IP Unit or built-in EtherNet/IP port, message communications are possible even if the I/O link function is disabled. 189 Section 7-2 FINS Message Communications 7-2 FINS Message Communications Messages containing FINS commands can be exchanged over the Ethernet network between nodes that support FINS messages. Note Type of FINS message Network communications instructions PLC to PLC (both must be CS/CJ-series PLCs with a CS/CJ-series EtherNet/IP Unit, built-in EtherNet/IP port, or Ethernet Units) (See note 1.) FINS message communications can be executed without any particular restrictions over the Ethernet network with OMRON Ethernet Units (CS1WETN21 or CJ1W-ETN21), computers (CX-One or Fins Gateway applications), and NS-series Programmable Terminals. Data send/receive commands SEND/RECV instructions CS/CJ-series PLC CS/CJ-series PLC CS/CJ-series PLC CS/CJ-series PLC Command to EtherNet/IP Unit Command Note Inter-network communications are possible with Ethernet networks or other networks, such as Controller Link. (See note 2.) Data length (excluding command code) Any kind of FINS command CMND(490) instructions CS/CJ-series PLC Command to CPU Unit Command SEND instruction: 990 words: RECV instruction: 990 words. Note CMND instruction: 1,990 bytes max. 1. When two or more Communications Units (including the EtherNet/IP Units and built-in EtherNet/IP ports) are mounted to a CS/CJ-series PLC and FINS messages are being used, the EtherNet/IP Units and built-in EtherNet/IP ports must be registered in the CS/CJ-series PLC’s local network routing table. The commands will not be sent if the Unit is not registered in the routing tables. 2. When a CS/CJ-series EtherNet/IP Unit or built-in EtherNet/IP port is connected to an Ethernet network, message communications can be conducted between networks, including other Ethernet networks as well as other networks such as Controller Link and SYSMAC LINK. Up to eight levels of networks can be crossed, provided that routing tables (containing local network tables and relay network tables) have been registered in the CPU Units of each PLC on the network. 3. A Programming Device connected to the CPU Unit of a PLC connected to the network can be used to program and monitor another PLC that is on the network. Up to eight levels of networks can be crossed for CS1/CJ1series CPU Units with unit version 2.0 or later, CJ2 CPU Units, and CXProgrammer version 4.0 or higher. 190 Section 7-2 FINS Message Communications Up to 8 network levels, including the EtherNet/IP network, can be crossed. Controller Link Unit CS/CJ-series EtherNet/IP Unit CS/CJ-series CPU Unit Controller Link Unit Controller Link Remote I/O communications CS/CJ-series EtherNet/IP Unit Ethernet (EtherNet/IP) CS/CJ-series EtherNet/IP Unit Ethernet (EtherNet/IP) Note FINS commands sent and received by the CS/CJ-series EtherNet/IP Unit include commands addressed to the CS/CJ-series CPU Unit and commands addressed to the CS/CJ-series EtherNet/IP Unit. 191 Explicit Message Communications 7-3 Section 7-3 Explicit Message Communications Explicit messages defined in EtherNet/IP can be used to send service requests to other companies’ EtherNet/IP masters/slaves and OMRON PLCs with CS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports. Note Specific FINS commands (commands 2810 and 2801) are used to send explicit messages. Explicit message Network communications instruction Sending CIP UCMM messages can be sent to an EtherNet/IP Unit or built-in EtherNet/IP port by a CMND(490) instruction containing FINS command code 2810 Hex. Functions supported • Masters/slaves made by other manufacturers: in remote devices Supported services determine supported functions. • PLC with a CS/CJ-series EtherNet/IP Unit or built-in EtherNet/IP port: Supports the reading/writing of a remote CPU Unit’s status information and I/O memory data. Receiving Automatically responds to explicit messages from other devices. • Masters made by other manufacturers • PLC with a CS/CJ-series EtherNet/IP Unit or built-in EtherNet/IP port: Supports the reading/writing of the local CPU Unit’s status information and I/O memory data. Note The CS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports (CS1WEIP21, CJ1W-EIP21, CJ2H-CPU@@-EIP, or CJ2M-CPU3@) contain a PLC Object, so that other devices can read/write the I/O memory of the CPU Unit with the built-in EtherNet/IP port or the CPU Unit to which the EtherNet/IP Unit is mounted. 192 Message Communications Specifications 7-4 Section 7-4 Message Communications Specifications CPU Unit function Unit model number Communications Sending/ receiving instructions data FINS commands CS/CJ Series CS1W-EIP21, CJ1W-EIP21, CJ2H-CPU@@-EIP, or CJ2M-CPU3@ SEND and RECV instructions No. of simultaneous instructions One each for 8 ports (ports 0 to 7) Refer to 3-25 Network Instructions in the CS/CJ Series Programmable Controllers Instructions Reference Manual (W340) for information on ports (logical ports). Default setting: 2 s User setting: 0.1 to 6553.5 s 0 to 15 Supports internetwork communications between Ethernet networks connected to CS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports (up to 3 levels). Supports internetwork communications between the EtherNet/IP network connected to a CS/CJ-series EtherNet/IP Unit or built-in EtherNet/IP port and other networks such as Controller Link or SYSMAC LINK (up to 3 levels). CMND(490) instruction There are two kinds of FINS commands: commands addressed to the CPU Unit, and commands addressed to the CS/CJ-series EtherNet/IP Unit or built-in EtherNet/IP port. CMND(490) instruction Sending EtherNet/IP CIP UCMM Sends CIP UCMM messages to other companies’ masters/slaves, or PLCs messages with a CS/CJ-series EtherNet/IP Unit or built-in EtherNet/IP port mounted. Number of destiFINS message com- 1:N communications nation nodes munications Explicit message 1:N communications communications Send functions: CIP unconnected (UCMM) communications only Receive functions: CIP unconnected (UCMM) and CIP connected (Class 3) communications Transmission data FINS message com- • SEND: 990 words (1,980 bytes) max. normally, or 727 words (1,454 bytes) length (not includ- munications max. when broadcasting ing the command • RECV: 990 words (1,980 bytes) max. code) • CMND: 1,990 bytes max. normally, or 1,462 bytes max. when broadcasting (data after the FINS command code) Explicit message CMND: 492 bytes max. communications Response monitoring time Retries Internetwork connections Same network type Different network type 193 Section 7-5 Message Communications Error Indications 7-5 Message Communications Error Indications There are two ways to obtain information on communications errors that occur in message communications: checking the EtherNet/IP Unit’s error log or checking its indicators. 1,2,3... 1. Each time a communications error occurs, an error code is placed in an error record in the error log stored in RAM in the EtherNet/IP Unit or CPU Unit with the built-in EtherNet/IP Port. Up to 64 records can be stored in the error log. The time and date that the error occurred are also recorded together. The error log can be read or cleared from the CPU Unit by sending an FINS command to the EtherNet/IP Unit (Error Log Read/Clear). The contents of the error log can also be monitored from the Configurator. Code Code 64 records Code FINS command Read-out Monitor CPU Unit Configurator 2. When a communications error has occurred, details on the error are indicated by the MS and NS indicators and the 7-segment display on the front panel of the EtherNet/IP Unit or CPU Unit with the built-in EtherNet/IP port. This information can be used for troubleshooting. Example: Routing table error Flashing red Not relevant MS NS Communications status 3 15 EtherNet/IP Unit 194 CPU Unit 00 Section 7-6 Message Communications Errors 7-6 Message Communications Errors The following table shows the main errors that may occur when messages are sent or received. Refer to SECTION 14 Troubleshooting and Error Processing for corrective measures and details on errors that are recorded in error log but not indicated by the LED indicators. Error MS Routing table error IP address duplication error CPU Unit service monitoring error Other CPU error Too many retries, cannot send Node address setting error, cannot send Remote node not part of network, cannot send No Unit with specified unit address, cannot send CPU Unit error occurred, cannot send Destination address not set in routing tables, cannot send Routing tables not registered, cannot send Routing tables error occurred, cannot send Too many relay connections, cannot send Maximum command length exceeded, cannot send Header error; cannot send Reception buffer full, packet discarded Invalid packet discarded Local node busy, cannot send Unexpected routing error Service not supported in present mode, packet discarded Transmission buffer full, packet discarded Maximum frame length exceeded, routing impossible Packet discarded due to response time-out Note Flashing red No change Flashing red No change Indicators NS No change Lit red No change Not lit 7-segment display (See note.) HC F0 HE H7 No change No change Error code (Hex) 021A 0211 0002 0006 0103 0105 0107 0108 010B 010D 010E 010F 0110 0111 0112 0117 0118 0119 0120 0122 0123 0124 0125 The 7-segment display alternately displays the error and the node address of the node where the error occurred. 195 Message Communications Errors 196 Section 7-6 SECTION 8 FINS Communications This section provides information on communicating on EtherNet/IP Systems and interconnected networks using FINS commands. The information provided in the section deals only with FINS communications in reference to EtherNet/IP Units or built-in EtherNet/IP ports. FINS commands issued from a PLC are sent via the SEND(090), RECV(098), and CMND(490) instructions programmed into the user ladder-diagram program. Although an outline of these instructions is provided in this section, refer to the CS/ CJ-series Programmable Controllers Programming Manual (W340) for further details on programming these instructions. 8-1 8-2 8-3 8-4 8-5 8-6 8-7 Overview of FINS Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198 8-1-1 Communications On an Ethernet Network. . . . . . . . . . . . . . . . . . . . 198 8-1-2 Using the FINS/UDP and FINS/TCP Methods . . . . . . . . . . . . . . . . 199 8-1-3 FINS Communications Service Specifications. . . . . . . . . . . . . . . . . 199 FINS/UDP Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 8-2-1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 FINS/TCP Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202 8-3-1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202 Routing Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207 8-4-1 Routing Table Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207 8-4-2 Connecting and Using a Peripheral Device for the PLC . . . . . . . . . 208 8-4-3 Routing Table Setting Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . 209 Using FINS Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211 8-5-1 CX-Programmer (CX-Server) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211 8-5-2 FinsGateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215 Communicating between OMRON PLCs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220 8-6-1 Communications Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220 8-6-2 PLC Communications Data Areas . . . . . . . . . . . . . . . . . . . . . . . . . . 221 8-6-3 Using SEND(090), RECV(098), and CMND(490) . . . . . . . . . . . . . 222 8-6-4 Writing Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226 8-6-5 Program Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230 Precautions on High Traffic in FINS Communications . . . . . . . . . . . . . . . . . 232 197 Section 8-1 Overview of FINS Communications 8-1 8-1-1 Overview of FINS Communications Communications On an Ethernet Network The EtherNet/IP Units and built-in EtherNet/IP ports support the FINS communications service, which can be used simultaneously with the CIP communications service. FINS communications data is sent and received as UDP/IP packets or TCP/IP packets. PLC or host computer EtherNet/IP Unit Packet (FINS command) Ethernet (EtherNet/IP) Packet (FINS response) EtherNet/IP Unit PLC In the FINS communications service, both an IP address for IP (the Internet layer) and a FINS node address for FINS (the application layer) are used for the remote device. Also, 9600 is used as the default setting for the local UDP or TCP port number (i.e., the transport layer) for identifying the application layer, i.e., the FINS communications service. (Another number can be set for the FINS/UDP port from the Setup Tab Page in the Unit Setup.) For details on pairing FINS node addresses with IP addresses and UDP/TCP port numbers, refer to 5-2 IP Addresses in FINS Communications. FINS Application Layer Node Number UDP Transport Layer TCP UDP Port No. TCP Port No. IP Internet Layer IP Address Ethernet Physical Layer Ethernet Address The FINS communications service is a communications method based on UDP/IP, and it is supported by most OMRON Ethernet-related products. (In this manual it is called the FINS/UDP method.) In addition to supporting the FINS/UDP method, the CJ2H-CPU@@-EIP, CJ2M-CPU3@, CS1W-EIP21, and CJ1W-EIP21 support FINS communications using TCP/IP. (In this manual, this is called the FINS/TCP method.) 198 Section 8-1 Overview of FINS Communications 8-1-2 Using the FINS/UDP and FINS/TCP Methods It is recommended that FINS/UDP and FINS/TCP be used as follows: • When remote devices do not support the FINS/TCP method: Use the FINS/UDP method for FINS communications with those devices. • When FINS nodes are connected on the same Ethernet segment: Use the FINS/UDP method between those nodes. Note FINS/UDP offers a slight advantage in performance. • When FINS nodes are connected over multiple IP network layers: Use the FINS/TCP method between those nodes. Note FINS/TCP offers superior communications quality. • When the quality of connections is unreliable, as with wireless LAN: Use the FINS/TCP method between those nodes. Note 8-1-3 FINS/TCP offers superior communications quality. FINS Communications Service Specifications Item Number of nodes Message length Number of buffers Protocol name Protocol used Number of connections Port number Protection Other Internal table Specifications 254 2,012 bytes max. 192 FINS/UDP method UDP/IP --9600 (default) Can be changed. No FINS/TCP method TCP/IP 16 9600 (default) Can be changed. Yes (Specification of client IP addresses when Unit is used as a server) Items set for each connection Items set for each UDP port • Server/client specification • Broadcast • Remote IP address specification • IP Address Conversion When client: Specify the IP address of the remote Unit (server). When server: Specify IP addresses of clients permitted to connect. • Automatic FINS node address allocation: Specify automatic allocation of client FINS node addresses. • Keep-alive: Specify whether remote node keep-alive is to be used. TCP/IP Setting • Remote node keep-alive time This a table of correspondences for remote FINS node addresses, remote IP addresses, TCP/ UDP, and remote port numbers. It is created automatically when power is turned ON to the PLC or when the Ethernet Unit is restarted, and it is automatically changed when a connection is established by means of the FINS/TCP method or when a FINS command received. The following functions are enabled by using this table. • IP address conversion using the FINS/UDP method • Automatic FINS node address conversion after a connection is established using the FINS/ TCP method • Automatic client FINS node address allocation using the FINS/TCP method • Simultaneous connection of multiple FINS applications 199 Section 8-2 FINS/UDP Method 8-2 8-2-1 FINS/UDP Method Overview FINS/UDP Features The FINS/UDP method is a FINS communications method that uses the UDP/ IP protocol. UDP/IP is a connectionless communications protocol. When a message is sent from one node to another, the two nodes have an equal relationship and there is no clear connection. If using TCP is like making a telephone call, then UDP is more like delivering a memo by hand. Although the UDP protocol is fast, data communications are less reliable than with TCP. In particular, when sending large amounts of data involving significant routing, the user must program measures, such as retries, into applications in order to improve reliability. Node Node Data transmission 1 Data transmission 2 Data transmission 3 Data is sent in one direction, with no confirmation of whether the data was received. Because there are few procedures involved, data can be sent at high speed but with less reliability than with TCP. The FINS/UDP method has the following features: • Because FINS/UDP is a connectionless protocol, there is no limit to the number of corrections. • FINS/UDP can be used for broadcasting. • When data is sent via an IP network with multiple layers (such as the Internet), communications reliability drops. FINS/UDP Frame Format The following diagram shows the structure of a UDP packet used for sending and receiving data on an Ethernet network. Ethernet Ver. 2 IP UDP FINS frame FCS UDP packet As the diagram shows, a nested structure is used with the FINS/UDP method, i.e., Ethernet Ver. 2, IP frame, UDP frame, and FINS frame. A UDP data section (FINS frame) that exceeds 1,472 bytes is split into packets for transmission. The split UDP data is then joined automatically at the UDP/IP protocol layer. There is normally no need to pay attention at the application layer to this split, but it may not be possible to send 1,472-byte UDP packets over an IP network with multiple layers. When using the FINS communications service in a system such as this, select the FINS/TCP method. 200 Section 8-2 FINS/UDP Method UDP Port Numbers for FINS/UDP The UDP port number is the number for UDP to identify the application layer (i.e., the FINS communications service in this case). When communications are executed by UDP/IP, this port number must be allocated to the communications service. The default setting for the UDP port number (i.e., the UDP port number of the EtherNet/IP Unit or built-in EtherNet/IP port) is 9600. To set another number, set the number on the FINS/UDP Tab Page of the CX-Programmers Edit Parameters Dialog Box. At the EtherNet/IP Unit or built-in EtherNet/IP port, a UDP/IP frame received with a FINS/UDP port number is recognized as a FINS frame. Procedure for Using FINS/UDP 1,2,3... 1. Make the basic settings. Refer to Initial Settings in 3-1-1 Procedures. 2. Keep the CX-Programmer connected online, right-click the EtherNet/IP Unit or built-in EtherNet/IP port in the PLC IO Table Dialog Box, and select Edit - Unit Setup. Set the following in the CPU Bus Unit Setup Area from the FINS/UDP Tab Page of the Edit Parameters Dialog Box. • IP Address Conversion • FINS/UDP Port No. (Default: 9600) • IP Address List (Set only when the conversion method is set to IP address table.) • Dynamic Change of remote IP addresses 3. Select Transfer to PLC from the PLC Menu and click the Yes Button. The setting data will be transferred to the CPU Bus Unit System Setup Area in the CPU Unit. 4. Make the routing table settings and transfer them to each PLC. (See note.) Set the routing tables with CX-Integrator, and transfer it to each PLC. 5. Create a ladder program that includes the SEND(090), RECV(098), and CMND(490) instructions. Note Routing tables are required in the following situations: • When communicating with a PLC or computer on another network (e.g., remote programming or monitoring using FINS messages or a CX-Programmer). • When multiple Communications Units are mounted to a single PLC (i.e., CPU Unit). • When routing tables are used for one or more other nodes on the same network. It is not necessary to set routing tables if one Communications Unit is mounted to the PLC and the nodes are connected as one network. 201 Section 8-3 FINS/TCP Method 8-3 8-3-1 FINS/TCP Method Overview FINS/TCP Features The FINS/TCP method is a FINS communications method that uses the TCP/ IP protocol. TCP/IP is a connection-type communications protocol. Before a message is sent from one node to another, it is necessary to establish a virtual circuit, i.e., a connection. Once a connection has been established, communications are quite reliable. The arrival of data that is sent via the connection is confirmed by an acknowledgement (ACK) response, and retries are executed automatically as required. When FINS/TCP is used, it must be determined which node is the server and which nodes are the clients. For communications between a personal computer and a PLC, the computer should normally be set as the client and the PLC as the server. For communications between two PLCs, either one can be set as the client and the other as the server. Node (Client) Node (Server) Request to establish a connection Connection established Notification of establishing connection Acknowledgement Data transmission 1 Acknowledgement An acknowledgement is received whenever a connection is established or data is sent, so transmissions are more reliable but somewhat slower. Compared to the FINS/UDP method, the FINS/TCP method has the following characteristics. • Data transmission is more reliable, due to factors such as retry processing at the TCP/IP layer. The FINS/TCP method is thus better suited to dealing with communications errors in an IP network that spans several layers. • Remote clients can be restricted by means of settings at the server (i.e., the server can be protected from access by non-specified IP addresses). • Broadcasting cannot be used. • TCP/IP has various retry procedures, and this tends to lower its performance in comparison with UDP/IP. • There is a limit to the number of connections that can be made (i.e., 16 connections maximum), and any given node can communicate only with up to 16 other nodes at a time. 202 Section 8-3 FINS/TCP Method • After a FINS/TCP connection (connection number, remote IP address) has been set in the FINS/TCP Tab Page of the Network Configurator’s Edit Parameters Dialog Box, it can be dynamically changed from the ladder program using a FINS command (i.e., FINS/TCP CONNECTION REMOTE NODE CHANGE REQUEST). FINS/TCP Frame Format The following diagram shows the structure of a TCP packet sent over an Ethernet network. Ethernet Ver. 2 IP TCP FINS/TCP header FINS frame FCS TCP packet As the diagram shows, a nested structure is used with the FINS/TCP method, i.e., Ethernet Ver. 2, IP frame, TCP frame, FINS/TCP header frame, and FINS frame. A TCP data section (FINS/TCP header + FINS frame) that exceeds the segment size (default setting of 1,024 bytes in the EtherNet/IP Unit or built-in EtherNet/IP port, with automatic adjustment for optimum values between the nodes) is split into TCP packets for transmission. The split TCP data is then joined automatically at the remote node's TCP/IP protocol layer. The TCP/IP protocol layer, however, cannot determine where the data has been split, so the TCP data sections from multiple packets are all joined together. Therefore, when using the FINS/TCP method, FINS/TCP headers must be added at the beginning of FINS frames in order to serve as FINS frame delimiters. The length of the data in the following FINS frame is stored in the header, allowing the frame to be separated out by the remote node. With the EtherNet/IP Unit or built-in EtherNet/IP port and FinsGateway (Ver. 2003 or higher) the appropriate frames are separated out automatically, so there is normally no need to be pay attention to it at the application layer. TCP Port Number for FINS/TCP The TCP port number is the number for TCP to identify the application layer (i.e., the FINS communications service in this case). When communications are executed using TCP/IP, this port number must be allocated for the communications service. The default setting for the TCP port number (i.e., the TCP port number of the EtherNet/IP Unit or built-in EtherNet/IP port) is 9600. To set another number, make the setting for the FINS/TCP port on the FINS/TCP Tab Page of the CXProgrammer’s Edit Parameters Dialog Box. The FINS/TCP port number set in the FINS Configuration Tab Page is used by the FINS/TCP server's TCP socket. The FINS/TCP client's TCP socket uses any TCP port number that can be used at that node. (With the EtherNet/IP Unit or built-in EtherNet/IP port and FinsGateway (Ver. 2003 or higher), an unused TCP port is automatically detected and utilized.) At the EtherNet/IP Unit or built-in EtherNet/IP port, a TCP/IP frame that is received is recognized as a FINS frame, according to the remote TCP port number in the frame. FINS/TCP Connection Numbers FINS/TCP allows up to 16 FINS/TCP connections to be established simultaneously, and these 16 connections are managed at the EtherNet/IP Unit or built-in EtherNet/IP port by connection numbers. When setting FINS/TCP connection settings in the FINS/TCP Tab Page of the Network Configurator’s Edit Parameters Dialog Box, set them individually using these connection numbers. 203 Section 8-3 FINS/TCP Method FINS/TCP Connection Status (Word n+24) While a connection with a remote node is established, the bit corresponding to the FINS/TCP connection status turns ON in the section of the CPU Bus Unit words allocated in the CIO Area. The bit turns OFF if the connection is terminated by a communications error or a FINS command (i.e., FINS/TCP CONNECTION REMOTE NODE CHANGE REQUEST). 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 n+24 *: Bit 15 corresponds to connection No. 16, bit 00 to connection No. 1, etc. Note FINS/TCP Communications Procedure The starting word of the FINS/TCP Connection Status Area is different in the CS1W-ETN21 and CJ1W-ETN21 Ethernet Units; it is n+23 in the Ethernet Units. If a ladder program using FINS/TCP communications was created for Ethernet Units, and is being reused for EtherNet/IP Units and built-in EtherNet/IP ports, change the word starting word address for this area from n+23 to n+24. With FINS/TCP, FINS node addresses are exchanged immediately after a connection is established. This makes it possible to determine the FINS node addresses to which the 16 connection numbers, and to manage them in an internal table. Personal computer (Client) Ethernet/IP Unit (Server) Example: IP address S FINS node number B Example: IP address C FINS node number A Passive open Active open Connection request (C→S) Connection established Connection established Local node No. sent Connection established FINS node number A sent Remote node No. received FINS node numbers exchanged Remote node No. received FINS node number B sent FINS frame sent Local node No. sent FINS frame sent Full duplex communications Normal data communications After a connection has been established as a FINS/TCP server, it is terminated in the following ways. • When the connection is closed by the client. • When a FINS command to close the connection (FINS/TCP CONNECTION REMOTE NODE CHANGE REQUEST) is sent by the client. • When there is no response from the client when the keep-alive function is in effect. 204 Section 8-3 FINS/TCP Method After a connection has been established as a FINS/TCP client, it can be terminated in the following ways. • If the connection is closed by the server. • If there is no response from the client when the keep-alive function is in effect. Even if the connection is closed at the FINS/TCP client, requests continue to be made to the FINS/TCP server every few seconds to open a connection. Note After the EtherNet/IP Unit or built-in EtherNet/IP port is powered up or restarted, the IP address for the connection used as the FINS/TCP client is the remote IP address that was set in the FINS/TCP Tab Page of the CX-Programmer’s Edit Parameters Dialog Box. To dynamically change the remote IP address (i.e., during CPU Unit operation), execute the CMND(490) instruction in the ladder program and send a FINS command (FINS/TCP CONNECTION REMOTE NODE CHANGE REQUEST; command code: 27 30 hexadecimal) to the EtherNet/IP Unit or built-in EtherNet/IP port. Procedure for Using FINS/TCP 1,2,3... 1. Make the basic settings. Refer to Initial Settings in 3-1-1 Procedures. 2. Make the following settings on the FINS/TCP Tab Page of the CX-Programmer's Edit Parameters Dialog Box. • FINS/TCP port (default: 9600) • Server/Client: Specifies whether the connection will operate in FINS/ TCP server mode or client mode. • Target IP address for client: Specifies the IP address of the target FINS/TCP server. • Target IP address for server: Specifies allowed client IP addresses when protection is enabled. • Automatically allocated FINS node address for server: Specifies the address to allocate when automatically allocating a FINS node address to the target FINS/TCP client. • Keep-alive: Specified whether to use the keep-alive function. Note Normally this function is used and the option is selected. • Enable protect via IP address: Note Select this option only when protecting as the server. 3. Select Transfer to PLC from the PLC Menu and click the Yes Button. The setting data will be transferred to the CPU Bus Unit System Setup Area in the CPU Unit. 4. Make the routing table settings and transfer them to each PLC. (See note 1.) Set the routing tables with CX-Integrator, and transfer it to each PLC. 5. Create a ladder program that includes the SEND(090), RECV(098), and CMND(490) instructions. Note (1) Routing tables are required in the following situations: • When communicating with a PLC or computer on another network (e.g., remote programming or monitoring using FINS messages or a CX-Programmer) • When multiple Communications Units are mounted to a single PLC (i.e., CPU Unit) 205 FINS/TCP Method Section 8-3 • When routing tables are used for one or more other nodes on the same network It is not necessary to set routing tables if one Communications Unit is mounted to the PLC and the nodes are connected as one network. (2) If EtherNet/IP is selected for CX-Programmer communications, FINS message communications and remote programming/monitoring from the CX-Programmer will be possible as long as CIP routing is possible for the entire communications path. Routing tables do not need to be set. If FINS messages are sent from a PLC, however, then routing tables must be set. 206 Section 8-4 Routing Tables 8-4 Routing Tables When the FINS communications service is used, routing tables must be created in advance. Routing tables are required in the following circumstances. • When communicating with a PLC or computer on another network (e.g., remote programming or monitoring using FINS messages or a CX-Programmer) • When multiple Communications Units are mounted to a single PLC (i.e., CPU Unit). • When routing tables are used for one or more other nodes on the same network. It is not necessary to set routing tables if one Communications Unit is mounted to the PLC and the nodes are connected as one network. The routing tables are required not only for nodes communicating via the FINS communications service but also for all relay nodes on the network. 8-4-1 Routing Table Overview The routing tables describe the transmission path for FINS messages when the FINS communications are used. It consists of two tables: A local network table and a relay network table. Local Network Table The local network table is a table describing the correspondences among unit numbers of the Communications Units and Boards mounted to each node. Example Unit #04 Unit #05 Unit #06 Unit #07 Local Network Table Local network Unit number address Network #1 Network #2 Network #3 Network #4 Note 1 2 3 4 04 05 06 07 1. The unit number is set (0 to F: 1 to 15) using the rotary switch on the front of the EtherNet/IP Unit (built-in port). 2. The network address is the number of the network (1 to 127) to which the Communications Unit or Board is connected. It is set when the local network table is created. Relay Network Table A relay table is a table that shows the nodes to which data should be sent first in order to send data to a network that is not connected to the local node. It shows the correspondence between the address of the final destination network, and the network address and node address of the first relay point of the path to reach there. When internetwork communications are carried out, the end network can be reached by following the relay points. 207 Section 8-4 Routing Tables The following example shows routing tables for sending data from PLC #1 (the local node: network address 1, node address 1) to PLC #4 (the destination node: network address 3, node address 2). PLC #3 (relay node) PLC #2 (relay node) PLC #1 (local node) Node #1 Node #2 Unit #0 Node #1 Unit #1 Node #3 Node #2 PLC #4 (destination node) Node #2 Node #1 PLC #1 relay network table PLC #2 relay network table End Relay Relay network network node End Relay Relay network network node 2 1 3 3 1 3 3 Note 8-4-2 2 2 To go to network #3, first go to node #2 at network #2. To go to network #3, first go to node #3 at network #1. Network #3 Network #2 Network #1 End network PLC #3 local network table Local network address Unit number 2 0 3 1 (To go to network #3 (The network is the same, according to the local so go to node #2 at network #3.) network table, go through unit number 1 of the local CPU Rack.) In the above example, the routing tables required for a message to reach PLC #4 from PLC #1 are shown. Additional settings would be required in the routing tables for a message to reach PLC #1 from PLC #4. Refer to 8-4-3 Routing Table Setting Examples for routing table setting examples. Connecting and Using a Peripheral Device for the PLC Routing tables must be created by a CX-Integrator connected to the PLC. (They cannot be created using a Programming Console.) For details on how to connect and use the CX-Integrator, refer to the CX-Integrator Operation Manual (W445). (CX-Integrator is automatically installed when CX-One is installed.) Note 1. When routing tables are transferred from the CX-Integrator to the PLC, all of the CPU Bus Unit are reset so that the routing tables that have been created can be read and enabled. Before transferring the routing tables, confirm that there will be no problems in the system when the CPU Bus Units are reset. 2. To transfer routing tables for multiple nodes to a PLC in one batch, connect the CX-Integrator to a PLC with only one Communications Unit mounted. Routing tables cannot be transferred to other nodes from a PLC with multiple Communications Units mounted. 3. Routing tables can only be transferred as a batch to multiple nodes within the same network as the PLC to which the CX-Integrator is connected. 208 Section 8-4 Routing Tables 8-4-3 Routing Table Setting Examples ■ Example 1: Local Network Table for a PLC With Multiple Units Mounted This example shows the local network table settings for a PLC to which multiple CPU Bus Units are mounted. Ethernet (EtherNet/IP) network Controller Link network (Network #A) (Network #B) PS: CPU: EIP: CLK: E C C P I L P S P K U Power Supply Unit CPU Unit EtherNet/IP Unit Controller Link Unit Unit #a Unit #b Local Network Table No. 1 2 ■ Local network A B CPU Bus Unit a b Example 2: Three Interconnected Networks This example shows the relay network table settings for three different interconnected networks. Relay Network Table PLC #1 Node #a Network #A PLC #2 Node #b Node #c PLC #3 Network #B Node #d PLC #4 Node #e Node #f Network #C PLC #5 No. End network Relay network 1 2 B C A A b b 1 C B e 1 2 A C B B c e 1 A B c 1 2 A B C C f f Node Node #g In the table for PLC #3, for example, if network #A is taken as the end network, then network #B becomes the relay network and node #c becomes the relay node. If network #C is taken as the end network, then network #B still becomes the relay network and node #e becomes the relay node. 209 Section 8-4 Routing Tables ■ Example 3: All Nodes This example uses the following configuration to show the routing tables for all nodes. Unit #5 Node #6 Unit #3 Node #4 Unit #2 Node #3 Network #20 C L K E I P CE L I PLC KP 2 PLC 4 Unit #0 Node #1 C L K CPU Bus Unit No. 05 CPU Bus Unit No. 03 02 PLC #3 Routing Table (Local network table) Local No. network 1 010 2 030 3 CPU Bus Unit No. 04 07 PLC #4 Routing Table (Local network table) Local No. network 1 020 2 3 CPU Bus Unit No. 00 PLC #5 Routing Table (Local network table) Local No. network 1 020 2 3 CPU Bus Unit No. 01 PLC #6 Routing Table (Local network table) Local No. network 1 030 2 3 CPU Bus Unit No. 05 PLC #7 Routing Table (Local network table) Local No. network 1 030 2 3 210 CPU Bus Unit No. 06 S L K Unit #1 Node #2 PLC #2 Routing Table (Local network table) Local No. network 1 010 2 020 3 ES I L PK PLC 5 PLC #1 Routing Table (Local network table) Local No. network 1 010 2 3 PLC 1 Network #10 Unit #4 PLC Node #5 Unit #7 3 Node #15 Network #30 S L K PLC 6 Unit #5 Node #5 PLC 7 Unit #6 Node #10 (Relay network table) End No. network 1 020 030 2 3 Relay network 010 010 Relay node 004 005 (Relay network table) End No. network 1 030 2 3 Relay network 010 Relay node 005 (Relay network table) End No. network 1 020 2 3 Relay network 010 Relay node 004 (Relay network table) End No. network 1 010 030 2 3 Relay network 020 020 Relay node 003 003 (Relay network table) End No. network 1 010 2 030 3 Relay network 020 020 Relay node 003 003 (Relay network table) End No. network 1 010 020 2 3 Relay network 030 030 Relay node 015 015 (Relay network table) End No. network 1 010 020 2 3 Relay network 030 030 Relay node 015 015 Section 8-5 Using FINS Applications 8-5 Using FINS Applications 8-5-1 CX-Programmer (CX-Server) The following examples show how to connect online from a CX-Programmer on an Ethernet network to a PLC on the Ethernet network. ■ System Configuration Example 1: No Routing In this example, an online connection is made by FINS/UDP to a PLC on an Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CXIntegrator connected to the Ethernet network. Conditions • FINS/UDP method • IP Address Conversion: Automatic (Dynamic) generation method CX-Programmer/CX-Integrator Node number: 1 IP address: 192.168.250.1 EtherNet/IP Unit IP address conversion: Automatic generation method (dynamic) EtherNet/IP Unit node number: 2 EtherNet/IP Unit IP address: 192.168.250.2 Ethernet port Target: PLC1 Ethernet or EtherNet/IP (Network address: None) FINS/UDP method CX-Programmer's Change PLC Dialog Box Settings for target PLC (PLC1)'s Change PLC Dialog Box PLC name Network classification Network Tab Page FINS transmission source address FINS destination Network number Node address Frame length Response monitor time Driver Tab Page Workstation node address Automatic generation method IP address Port number Setting PLC1 Ethernet 0 0 2 2,000 bytes 2 seconds 1 Not selected 192.168.250.2 (EtherNet/IP Unit or built-in EtherNet/IP port IP address) 9600 CX-Programmer's FINS/UDP Tab Page in Edit Parameters Dialog Box Item FINS/UDP Port IP Address Conversion IP Router Table Setting Default (9600) Automatic (Dynamic) generation method None 211 Section 8-5 Using FINS Applications Example: Inputs to the CX-Programmer's Setup Window Example: Change PLC Settings Example: Network Settings (Network Tab Page) Note 212 When FinsGateway is selected as the network type, make sure that the frame length is set to 2,000 bytes max. Section 8-5 Using FINS Applications Example: Network Settings (Driver Tab Page) ■ System Configuration Example 2: Using Routing Tables In this example, an online connection is made via the Ethernet to a PLC on a Controller Link network (PLC 3 below) from a CX-Programmer/CX-Integrator connected to the Ethernet network. Conditions • FINS/UDP method • IP address conversion: Automatic generation method (dynamic) Controller Link Unit Node address: 1 IP address: 192.168.250.1 CX-Programmer/CX-Integrator EtherNet/IP Unit IP address conversion: Automatic generation method (dynamic) Gateway between networks PLC1 EtherNet/IP Unit node address: 2 EtherNet/IP Unit IP address: 192.168.250.2 EtherNet/IP Unit unit number: 0 Controller Link Unit node address: 1 Controller Link Unit unit number: 1 Ethernet port Controller Link Unit Ethernet or EtherNet/IP (network address 1) Target PLC PLC2 Routing according to routing table Routing to final network address 2 requires relaying through node address 2 of relay network address 1 (EtherNet/IP Unit). Node address 2 Controller Link Unit PLC3 Node address 3 Controller Link (network address 2) CX-Programmer's Change PLC Dialog Box Settings for target PLC (PLC3)'s Change PLC Dialog Box PLC name Network classification Network Tab FINS destination FINS transmission Page source address Network number Node address Frame length Response monitor time Setting PLC3 Ethernet 1 2 3 2,000 bytes 2 seconds 213 Section 8-5 Using FINS Applications Settings for target PLC (PLC3)'s Change PLC Dialog Box Driver Tab Page Workstation node address Automatic generation method IP address Setting 1 Not selected 192.168.250.2 (EtherNet/IP Unit or built-in EtherNet/IP port IP address) 9600 Port number CX-Programmer's FINS/UDP Tab Page in Edit Parameters Dialog Box Same as for System Configuration Example 1. Routing Table Settings and Transfer to Each PLC Set the routing tables with CX-Integrator, and transfer them. 1. Using CX-Integrator, connect online, and select Routing table − Settings. Then create FINS local routing tables (a local network table and a relay network table). Example: PLC 1 Routing Table Settings • Local Network Table Unit number 0 1 Local network number 1 2 • Relay Network Table None Example: PLC 2 and PLC 3 Routing Table Settings • Local Network Table Unit number 0 Local network number 2 • Relay Network Table In order to relay from PLC2/3 to the final network number 1, it is necessary to relay via node address 1 (i.e., the Controller Link Unit) on relay network number 2. Final network number 1 Relay network number 2 Relay node address 1 2. Save the routing table file (File - Save local routing table file). 3. Next, to connect online, select Communication Settings from the Network Menu. For each PLC, register a PLC with a direct serial connection (node address: 0), and select it. 4. With the CX-Integrator, select Work Online from the Network Menu. 5. Select Tools - Start Routing table, read the saved file, and select Options - Transfer to PLC. Click Yes to transfer the routing tables to the connected PLC. 214 Section 8-5 Using FINS Applications 8-5-2 FinsGateway FinsGateway Ver. 2003 must be used to communicate using FINS/TCP between applications serving as communications drivers and CS1W-EIP21, CJ1W-EIP21, CJ2H-CPU@@-EIP, or CJ2M-CPU3@ EtherNet/IP Units. FinsGateway Ver. 3.@ or lower versions can be used, however, when communicating by the FINS/UDP method only. ■ Overview of Setup Methods 1. Starting FinsGateway Settings Select FinsGateway − FinsGateway Setup to start the FinsGateway Setup. 2. ETN_UNIT Driver Setup 1. Double-click on ETN_UNIT in the settings for the network and Unit. The following ETN_UNIT Properties Window will be displayed. • Network Tab Page • Network number • Local node address • Communication unit number Set the network number for the personal computer (Ethernet port). Set the personal computer (Ethernet port) node address (1 to 254) on the Ethernet network. Set the unit number in decimal (16 to 31) for the personal computer (Ethernet port). 215 Section 8-5 Using FINS Applications • Communication Unit Tab Page • UDP port number Set the local UDP port number for the personal computer (Ethernet port). The default is 9600. • Priority Network Card If multiple Network Cards are mounted at the personal computer, select the Network Card that is to be given priority. • FINS - IP address conver- Set the IP address conversion method. sion • UDP Nodes Tab Page: Automatic Generation Method (Dynamic or Passive) 216 Section 8-5 Using FINS Applications • UDP Nodes Tab Page: IP Address Table Method or Combined Method Click the Add Button, and then set the IP address table in the following Ethernet Node Definition Dialog Box. • Node address: • IP address: Set the remote FINS node address. Set the remote IP address. 217 Section 8-5 Using FINS Applications • TCP Nodes Tab Page Click the Add Button, and then set the IP address table in the following Ethernet Node Definition Dialog Box. • Node address: • IP address: • Destination port number: • Keep-alive setting: Set the remote FINS node address. Set the remote IP address. Set the FINS/TCP port number for the remote node. Normally the PLC's default setting of 9600 should be specified. Sets the keep-alive function. Normally this should be selected. 3. Starting FinsGateway ETN_UNIT Service Select ETN_UNIT from Services under the Basic Tab in the FinsGateway Setup Window, and then click the Start Button. 218 Section 8-5 Using FINS Applications ■ System Configuration Example 3: Connecting the CX-Programmer Online Using the FINS/TCP Method In this example, an online connection is made by FINS/TCP to a PLC on an Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CXIntegrator connected to the Ethernet network. Conditions • FINS/TCP method CX-Programmer/CX-Integrator Node number: 1 IP address: 192.168.250.1 EtherNet/IP Unit IP address conversion: Automatic generation method (dynamic) EtherNet/IP Unit node number: 2 EtherNet/IP Unit IP address: 192.168.250.2 FinsGateWay Version 2003 Ethernet port Target: PLC1 Ethernet or EtherNet/IP (Network number: none) FINS/TCP method CX-Programmer's Change PLC Dialog Box Settings for target PLC (PLC1)'s Change PLC Dialog Box PLC name Network classification Network Tab FINS destination Network number Page Node address Frame length Response monitor time Setting PLC1 FinsGateway 0 2 2,000 bytes 2 seconds CX-Programmer's FINS/TCP Tab Page in Edit Parameters Dialog Box Item FINS/TCP Port IP Router Table Setting Default (9600) None Not set. (All defaults are used.) FinsGateway ETN_UNIT Setup TCP Nodes Tab Page: Ethernet Node Definition Dialog Box Item Node address IP address Destination port number Keep-alive setting Setting 2 192.168.250.2 9600 Selected (yes) 219 Section 8-6 Communicating between OMRON PLCs 8-6 Communicating between OMRON PLCs FINS commands can be sent from the CPU Unit of a PLC by using the SEND(090), RECV(098), and CMND(490) instructions. SEND(090): Writes I/O data from the local node to another node. RECV(098): Reads I/O data from another node to the local node. CMND(490): Issues FINS commands for controlling operations such as sending and receiving I/O memory data to and from other nodes, reading information regarding other nodes, and so on. 8-6-1 Communications Specifications The following table shows the specifications for PLC communications using the SEND(090), RECV(098), and CMND(490) instructions. Item Destination Data length Data contents Communications port number Response monitor time Number of retries Note Specifications 1:1 SEND(090), RECV(098), CMND(490) instructions 1:N SEND(090), CMND(490) instructions (broadcasting) SEND(090): 990 words (1,980 bytes) max.; broadcasting: 727 words (1,454 bytes) RECV(098): 990 words (1,980 bytes) max. CMND(490): 1,990 bytes max.; broadcasting: 1,462 bytes (after FINS command code) The following data is sent and received with the execution of each instruction. SEND(090): Sends request for remote node to receive data, and receives response data. RECV(098): Sends request for remote node to send data, and receives response data. CMND(490): Sends any FINS command and receives response data. Ports 0 to 7 (Eight transmissions can occur simultaneously.) 0000: 2 s (default) 0001 to FFFF: 0.1 to 6,553.5 s in 0.1-s increments (specified by user) 0 to 15 retries 1. The maximum data length is limited to 512 bytes for data exchange between the PLC and SYSMAC LINK Systems or the PLC and SYSMAC BUS/2 Remote I/O Systems. 2. When broadcasting, do not require a response. Use the FINS/UDP method for broadcasting. 220 Section 8-6 Communicating between OMRON PLCs 8-6-2 PLC Communications Data Areas The following table shows the I/O data areas involved when SEND(090) and RECV(098) are used. Area CIO Area Work Area Holding Area Auxiliary Area Timer Area Counter Area DM Area EM Area Note Range CIO 0000 to CIO 6143 W000 to W511 H000 to H1535 A000 to A959 (See note 1.) TIM0000 to 4095 CNT0000 to 4095 D00000 to D32767 E00000 to E32767 (See note 2.) 1. Data cannot be written to words A000 to A447 in the Auxiliary Area. 2. A maximum of 13 banks in the EM Area can be used for a CS1/CJ1 CPU Unit. A maximum of 25 banks in the EM Area can be used for a CJ2H CPU Unit. A maximum of 4 banks in the EM Area can be used for a CJ2M CPU Unit. For details regarding the EM Area, refer to the operation manual for the PLC that is used. Refer to the operation manual for your CPU Unit to confirm EM Area support. 221 Section 8-6 Communicating between OMRON PLCs 8-6-3 Using SEND(090), RECV(098), and CMND(490) Make the settings shown below when using the SEND(090), RECV(098), and CMND(490) instructions in the user’s ladder-diagram program in the PC. SEND(090) The SEND(090) instruction sends the data in n number of words, starting from the beginning word S at the local node, to the words starting from the beginning word D at the remote destination node (node address N). 15 S→ Destination node number N 0 15 D→ n Local node 0 Number of words (n) (@)SEND(90) S D C S: Local node beginning word D: Destination beginning word C: First word of control data (below) 15 15 0 C+3 C 10 0 15 11 0 8 7 11 8 7 0 0 0 Response 0: Required. 1: Not required. Destination network number 00 (Hex): Local network 01 to 7F (Hex): 1 to 127 15 3 0 Number of retries 0 to F (Hex): 0 to 15 retries Communications port number: 0 to 7 Number of words (n) 0001 to 03DE (Hex): 1 to 990 words C+1 8 7 0 C+2 C+4 Destination unit address 00 (Hex): 10 to 1F: (Hex): E1 (Hex): FE (Hex): CPU Unit Unit #0 to #15 Inner Board Unit connected to network Response monitor time 0000 (Hex): 2 s 0001 to FFFF (Hex): 0.1 to 6,553.5 s (in units of 0.1 s) Destination node number N 00 to FE (Hex): 0 to 254 The same data can be broadcast to all nodes on the network by setting the destination node number to FF (Hex). The range of node addresses is different for networks other than Ethernet. Note 222 The message service does not guarantee that a message will reach the destination node. A message may be lost during transmission due to factors such as noise. To prevent this from occurring when using message services, it is common to set up retry processing at the node from which instructions are issued. With the SEND(090), RECV(098), and CMND(490) instructions, retry processing is executed automatically by specifying the number of retries, so specify a number other than 0. Section 8-6 Communicating between OMRON PLCs RECV(098) With the RECV(098) instruction, the data in m number of words, starting from the beginning word S at the remote node (node address M) is received at the words starting from the beginning word D at the local node. Local node 15 D→ Remote node number N 0 0 15 S→ Number of words (m) m (@)RECV(98) S D C S: Remote node beginning word D: Local beginning word C: First word of control data (below) 15 15 0 C+3 C 10 0 15 11 0 8 7 15 11 8 7 0 0 0 Response 0: Required. 1: Not required. Destination network number 00 (Hex): Local network 01 to 7F (Hex): 1 to 127 C+2 3 0 Number of retries 0 to F (Hex): 0 to 15 retries Communications port number: 0 to 7 Number of reception words (m) 0001 to 03DE (Hex): 1 to 990 words C+1 8 7 0 C+ 4 Destination Unit address 00 (Hex): CPU Unit 10 to 1F: (Hex): Unit #0 to #15 E1 (Hex): Inner Board FE (Hex): Unit connected to network Response monitor time 0000 (Hex): 2 s 0001 to FFFF (Hex): 0.1 to 6,553.5 s (in units of 0.1 s) Remote node number M (send source) 00 to FE (Hex): 0 to 254 The range of node addresses is different for networks other than Ethernet. Note The message services function does not guarantee that a message will reach the destination node. A message may be lost during transmission due to factors such as noise. In order to prevent this from occurring when using message services, it is common to set up retry processing at the node from which instructions are issued. With the SEND(090), RECV(098), and CMND(490) instructions, retry processing is executed automatically by specifying the number of retries, so specify a number other than 0. 223 Section 8-6 Communicating between OMRON PLCs CMND(490) The CMND(490) instruction sends n bytes of command data, starting from the beginning word S at the local node, to the node at node address N. the data in m number of words, starting from the beginning word S at the remote node (node address M) is received at the words starting from the beginning word D at the local node. 15 Local node 0 Destination node number N S Command (S−1) n +− 2 Command data: n bytes Interpretation Response D (D−1) m +− 2 Execution Response data: m bytes (@)CMND(490) S S: Beginning command storage word D D: Beginning response storage word C C: First word of control data (below) 15 0 C Number of bytes of command data (n) 0000 to 07C6 (Hex): 1 to 1,990 bytes 15 0 C+1 Number of bytes of response data (m) 0000 to 07C6 (Hex): 1 to 1,990 bytes 15 C+2 11 0 8 7 15 0 0 C+4 10 15 8 7 0 3 0 0 Number of retries 0 to F (Hex): 0 to 15 retries Communications port number: 0 to 7 Destination network number 00 (Hex): Local network 01 to 7F (Hex): 1 to 127 C+3 8 7 0 Response 0: Required. 1: Not required. Destination Unit address 00 (Hex): CPU Unit 15 10 to 1F: (Hex): Unit #0 to #15 C+5 E1 (Hex): Inner Board FE (Hex): Unit connected to network Destination node number N 00 to FE (Hex): 0 to 254 The same data can be broadcast to all nodes on the network by setting the destination node number to FF (Hex). 10 8 7 3 0 Response monitor time 0000 (Hex): 2 s 0001 to FFFF (Hex): 0.1 to 6,553.5 s (in units of 0.1 s) The range of node addresses is different for networks other than Ethernet. Note 224 The message services function does not guarantee that a message will reach the destination node. A message may be lost during transmission due to factors such as noise. In order to prevent this from occurring when using message services, it is common to set up retry processing at the node from which instructions are issued. With the SEND(090), RECV(098), and CMND(490) instructions, retry processing is executed automatically by specifying the number of retries, so specify a number other than 0. Section 8-6 Communicating between OMRON PLCs Commands Addressed to CS/CJ-series CPU Units The following table provides a list of FINS commands that can be processed by a CS/CJ-series CPU Unit. For details, refer to the CS/CJ-series Programmable Controllers Communications Commands Reference Manual (W342). For details on FINS commands that can be processed by the EtherNet/IP Unit or built-in EtherNet/IP port, refer to Appendix E FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports. Usage Command code MR SR 01 01 MEMORY AREA READ 01 02 MEMORY AREA WRITE 01 03 MEMORY AREA FILL 01 04 MULTIPLE MEMORY AREA READ 01 05 MEMORY AREA TRANSFER 02 01 PARAMETER AREA READ 02 02 PARAMETER AREA WRITE 02 03 PARAMETER AREA FILL (CLEAR) 03 03 03 04 06 07 08 01 PROGRAM AREA READ PROGRAM AREA WRITE PROGRAM AREA CLEAR RUN 04 02 STOP Machine configura- 05 tion reading 05 01 02 CPU UNIT DATA READ CONNECTION DATA READ Status reading 06 06 01 20 CPU UNIT STATUS READ CYCLE TIME READ Time data access 07 01 CLOCK READ 07 02 CLOCK WRITE Message display 09 20 MESSAGE READ/CLEAR Access rights 0C 01 ACCESS RIGHT ACQUIRE 0C 02 ACCESS RIGHT FORCED ACQUIRE 0C 03 ACCESS RIGHT RELEASE 21 21 21 01 02 03 ERROR CLEAR ERROR LOG READ ERROR LOG POINTER CLEAR I/O memory area access Parameter access (registered I/O tables, routing tables, etc.) Program area access Operating mode changes Error log Name Function Reads the contents of consecutive I/O memory area words. Writes the contents of consecutive I/O memory area words. Writes the same data to the specified range of I/O memory area words. Reads the contents of specified nonconsecutive I/O memory area words. Copies the contents of consecutive I/O memory area words to another I/O memory area. Reads the contents of consecutive parameter area words. Writes the contents of consecutive parameter area words. Writes the same data to the specified range of parameter area words. Reads the UM (User Memory) area. Writes to the UM (User Memory) area. Clears the UM (User Memory) area. Changes the CPU Unit’s operating mode to RUN or MONITOR. Changes the CPU Unit’s operating mode to PROGRAM. Reads CPU Unit data. Reads the model numbers of the device corresponding to addresses. Reads the status of the CPU Unit. Reads the maximum, minimum, and average cycle time. Reads the present year, month, date, minute, second, and day of the week. Changes the present year, month, date, minute, second, or day of the week. Reads and clears messages, and reads FAL/FALS messages. Acquires the access right as long as no other device holds it. Acquires the access right even if another device already holds it. Releases the access right that has been acquired. Clears errors or error messages. Reads the error log. Clears the error log pointer. 225 Section 8-6 Communicating between OMRON PLCs Usage File memory Debugging 8-6-4 Command code MR SR 22 22 01 02 22 03 22 22 04 05 22 07 22 22 08 0A 22 0B 22 0C 22 23 15 01 23 02 Name Function FILE NAME READ SINGLE FILE READ Reads file memory data. Reads a specified length of file data from a specified position within a single file. SINGLE FILE WRITE Writes a specified length of file data from a specified position within a single file. FILE MEMORY FORMAT Formats (initializes) the file memory. FILE DELETE Deletes specified files stored in the file memory. FILE COPY Copies files from one file memory to another file memory in the same system. FILE NAME CHANGE Changes a file name. MEMORY AREA–FILE TRANSFER Transfers or compares data between the I/O memory area and the file memory. PARAMETER AREA–FILE TRANSFER Transfers or compares data between the parameter area and the file memory. PROGRAM AREA–FILE TRANSFER Transfers or compares data between the UM (User Memory) area and the file memory. CREATE/DELETE DIRECTORY Creates or deletes a directory. FORCED SET/RESET Force-sets or force-resets bits, or releases force-set status. FORCED SET/RESET CANCEL Cancels all bits that have been force-set or force-reset. Writing Programs Programs incorporating the SEND(090), RECV(098), and CMND(490) instructions are generally created using the Communications Port Enabled Flag and the Communications Port Error Flag as input conditions. CS/CJseries CPU Units have eight communications ports. Only one instruction can be executed at any given port at one time, however, so the program must not overlap the use of any of the ports. A program example is provided below. Communications port EtherNet/IP Unit CPU Unit Instruction 1 Instruction 2 Instruction 3 Instruction 4 Instruction 5 Instruction 6 Instruction 7 Instruction 8 There are eight communications ports, so up to eight communications instructions can be executed at a time. The number of messages that can be sent or received with a single CPU Bus Unit service, though, is not more than two each for the CPU Unit to the EtherNet/IP Unit and for the EtherNet/IP Unit to the CPU Unit. 226 Section 8-6 Communicating between OMRON PLCs Communications Port Enabled Flag Execution condition C KEEP(011) A Input A remains ON from start to completion of communications instruction. Operand, control data created with @MOV and @XFER. Creates operand and control data in a given area. Reset B A Communications instructions @SEND @RECV @CMND Executes communications instructions. Communications Port Enabled Flag A DIFU(013) B Creates reset input. (Turns reset B ON after execution of communications instruction.) Communications Port Error Flag A Send Error Flag display (Retry can be executed.) Execution condition Communications Port Enabled Flag Exclusive control so execution is not simultaneous. A KEEP(011) C Use exclusive control so that no other communications instructions are started before execution of the above communications instruction is complete. Reset D (Continued in same way.) The execution status of the SEND(090), RECV(098), and CMND(490) instructions is always reflected by the communications flags (i.e., the Communications Port Enabled Flag and the Communications Port Error Flag). The CS/ CJ-series CPU Unit’s communications flags are allocated in the Auxiliary Area as shown in the following table. Flag name Word Communications Port A202 Enabled Flag Communications Port A219 Error Flag Note Address Bits Bit 7: Port 7 Bit 6: Port 6 Bit 5: Port 5 Bit 4: Port 4 Bit 3: Port 3 Bit 2: Port 2 Bit 1: Port 1 Bit 0: Port 0 Bit 7: Port 7 Bit 6: Port 6 Bit 5: Port 5 Bit 4: Port 4 Bit 3: Port 3 Bit 2: Port 2 Bit 1: Port 1 Bit 0: Port 0 Contents OFF: Execution enabled (being executed) ON: Execution disabled (not being executed) 0: Normal completion 1: Abnormal completion In CS/CJ-series PLCs, communications ports 0 to 7 are also used when executing the PCMR(260) (PROTOCOL MACRO), TXDU(256), and RXDU(255) instructions, so these flags are shared by SEND(090), RECV(098), CMND(490), PCMR(260), TXDU(256), and RXDU(255). SEND(090), RECV(098), and CMND(490) cannot be executed at a communications port if PCMR(260) TXDU(256), or RXDU(255) is being executed at that port. 227 Communicating between OMRON PLCs Communications Port Completion Codes Section 8-6 The status of a SEND(090), RECV(098), and CMND(490) instruction after execution is reflected as a communications port completion code, in one word (two bytes) of data as shown in the following table. (The value is 0000 during instruction execution.) The recorded status is saved until execution of the next instruction. Word A203 A204 A205 A206 A207 A208 A209 A210 Contents Communications Port 0 Completion Code Communications Port 1 Completion Code Communications Port 2 Completion Code Communications Port 3 Completion Code Communications Port 4 Completion Code Communications Port 5 Completion Code Communications Port 6 Completion Code Communications Port 7 Completion Code The meanings of the communications port completion codes are the same as those for FINS commands and responses. Bits 08 to 15 in the communications port completion code correspond to the first byte of the response code, and bits 00 to 07 correspond to the second byte. For details, refer to 14-6 Troubleshooting with FINS Response Codes. Communications Port Error Flag and Completion Codes CMND(490) Errors that occur when CMND(490) is used generate a Communications Port Error Flag and are recorded in a communications port completion code only in the following cases: • When a response timeout error has occurred. • When the number of communications data bytes exceeds the maximum value for the Unit (i.e., 2,000 bytes for the EtherNet/IP Unit or built-in EtherNet/IP port). • When the actual number of response bytes is greater than the number of reception bytes that has been set. (The response is not stored in this case.) Errors other than these are recorded in the response codes of the responses stored from the beginning response storage word onwards. Be careful of these, because there are no Communications Port Error Flags and they are not recorded in a communications port completion code. Timing of Communications Flag Changes • The Communications Port Enabled Flag remains OFF during communications and turns ON when they are completed (regardless of whether or not an error occurs). • The Communications Port Error Flag retains its status until the next transmission or reception. • The Communications Port Error Flag turns OFF with the execution of the next communications instruction even if there was an abnormal completion. 228 Section 8-6 Communicating between OMRON PLCs Example 1 0 Communications Port Enabled Flag Communications instruction: SEND(090), RECV(098), CMND(490) Communications Port Error Flag Communications Port Completion Code Instruction 1 being executed. Instruction 2 being executed. Instruction 3 being executed. 0000 0000 0000 1 0 Completion 0000 (Normal completion) 0000 (Normal completion) 0202 (Unit address setting error) 229 Section 8-6 Communicating between OMRON PLCs 8-6-5 Program Example Execution condition A20207 000000 (See note 1.) 120002 S KEEP 120000 R When the Communications Port Enabled Flag for port 7 is ON, and RECV(098) is not being executed, the send execution program will start when execution condition CIO 000000 turns ON. 120001 120000 @MOV(21) #000A D00000 Input CIO 120000 remains ON from the start of SEND(090) execution until completion. Control Data Creation Word @MOV(21) #0002 D00001 @MOV(21) Contents D0000 00 0A Number of send words = 10 D0001 00 02 Destination network number = 2 D0002 04 00 Destination node number = 4 D0003 07 05 Response required. #0400 D00002 Meaning Destination unit address = 0 Communications port No. used = 7 @MOV(21) #0705 D00003 Number of retries = 5 D0004 00 64 Response monitor time = 10 s @MOV(21) #0064 D00004 Send Data Creation @XFER(70) #000A Ten words of data from word CIO 0000 is stored from D00010 onwards. 0000 D00010 @SEND(90) D00010 D00020 Ten words of data from D00010 at the local node is sent to D00020 onwards at network number 2, node number 4, unit address 0 (the PLC). D00000 120000 A20207 (See note 1.) DIFU(13) 120001 120000 A21907 121000 (Continued on next page.) 230 Reset Input Creation Send Error Display Section 8-6 Communicating between OMRON PLCs (Continued from previous page.) Execution condition A20207 000001 (See note 1.) 120000 S KEEP 120002 When the Communications Port Enabled Flag for port 7 is ON, and SEND(090) is not being executed, the transmission execution program will start when execution condition CIO 000001 turns ON. R 120003 120002 @MOV(21) #0010 D00005 Input CIO 120002 remains ON from the start of RECV(098) execution until completion. Control Data Creation Word @MOV(21) Contents Meaning #0003 D0005 00 10 Number of reception words = 16 D00006 D0006 00 03 Source network number = 3 D0007 20 00 Source node number = 32 Source unit address = 0 D0008 07 05 Response required. Communications port No. used = 7 @MOV(21) #2000 D00007 @MOV(21) Number of retries = 5 #0705 D00008 D0009 00 00 Response monitor time = Default @MOV(21) #0000 D00009 @RECV(98) A100 A total of 16 words of data beginning from word A100 at network number 3, node number 32, unit address 0 (the PLC) is received at word CIO 2000 onwards of the local node. 2000 D00005 120002 A20207 (See note 1.) Reset Input Creation DIFU(13) 120003 120002 A21907 121001 120002 120003 A21907 Reception Error Display Reception Data Processing @XFER(70) #0016 2000 If there is no reception processing completion error, the 16 words of data received from word CIO 2000 onwards is stored at D00040 onwards. D00040 Note 1. With CS/CJ-series PLCs, the Communications Port Enabled Flags at bits 0 to 7 in word A202 turn OFF even when the PCMR(260) instruction is being executed using the ports corresponding to those flags. 2. Before using the sample program as is, confirm that the memory areas (words and bits) used in the sample program are not already being used in the user program o r by Special I/O Units. 231 Precautions on High Traffic in FINS Communications 8-7 Section 8-7 Precautions on High Traffic in FINS Communications When applications are constructed using FINS communications services, communications errors (from multiple response timeouts) may occasionally occur due to high traffic, depending on the system configuration and the application programs. This section describes precautions for systems with high traffic in FINS communications. ■ Conditions for High Traffic A heavy communications load may occur at an EtherNet/IP Unit or built-in EtherNet/IP port if FINS messages and CIP messages from multiple nodes are concentrated on that EtherNet/IP Unit or built-in EtherNet/IP port. The EtherNet/IP Unit or built-in EtherNet/IP port and the CPU Unit may have insufficient processing capacity for the volume of FINS messages (commands) that are coming from the network. For example, suppose that approximately 20 ms are required to process a single FINS frame (i.e., 20 ms from the time that the command is received at the EtherNet/IP Unit or built-in EtherNet/IP port until a response is sent). If 100 or more FINS frames (commands) are received at once from multiple communicating nodes, it will take approximately 2 seconds to send a response to the last command. If a timeout is set at the remote node for 2 seconds or less, then a timeout will be generated. A retry will begin due to the timeout, and the traffic to the EtherNet/IP Unit or built-in EtherNet/IP port will thus be increased even further, until ultimately the responses to all the nodes will be too slow. At this point, the system is overloaded. ■ Avoiding Errors due to High Traffic To avoid high traffic from FINS communications, the communications load must be kept down to a reasonable level. To accomplish this, follow the procedure below. 1. Specify the node where FINS frames seem to be concentrated. 2. Estimate the total processing time for all of the FINS frames processed at that node. (For details, refer to 10-5-1 Maximum Transmission Delays (Excluding Delays in the Network).) 3. Set the timeout value for all of the SEND(090), RECV(098), and CMND(490) FINS commands at all the remote nodes to at least 1.5 times the total processing time for all of the FINS frames. 4. As much as possible, implement communications traffic testing up to the point of actual system operation. If any problem occurs, adjust the traffic. 5. If a commercially-available protocol analyzer can be used, then the actual FINS frame processing time (i.e., the time from when a command is received at the EtherNet/IP Unit or built-in EtherNet/IP port until a response is sent) can be measured under high traffic conditions and the communications traffic can be further adjusted as required. 232 SECTION 9 Message Communications This section describes message communications using FINS commands sent from the ladder program in the CPU Unit of the PLC. 9-1 Sending Explicit Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sending Explicit Messages Using CMND(490). . . . . . . . . . . . . . . . 243 9-2 Receiving Explicit Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248 9-2-1 249 9-1-1 List of PLC Object Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234 233 Section 9-1 Sending Explicit Messages 9-1 Sending Explicit Messages CS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports can send explicit messages. Only CIP unconnected message (UCMM) communications can be used to send explicit messages. Explicit messages can be sent to the following destinations. • EtherNet/IP Units made by other manufacturers • Other PLCs with a CS/CJ-series EtherNet/IP Unit or built-in EtherNet/IP port Example CS/CJ-series EtherNet/IP Unit Other manufacturer's EtherNet/IP node CS/CJ-series CPU Unit Explicit messages can be sent Explicit message Ethernet (EtherNet/IP) CS/CJ-series EtherNet/IP Unit CS/CJ-series CPU Unit When the destination is another company’s EtherNet/IP node, an explicit message can be sent to the EtherNet/IP Unit or built-in EtherNet/IP port using FINS command code 28 01 or 28 10, through the Connection Manager class’s Unconnected Send service, as shown in the following diagram. CPU Unit Explicit message CMND (490) Other company's EtherNet/IP node EtherNet/IP Unit FINS header FINS header EtherNet/IP network Note: Use 28 01 for the FINS command code. FINS header Response Explicit message FINS header Response When sending an explicit message, set the local node’s EtherNet/IP Unit or built-in EtherNet/IP port as the destination of the FINS command, and not the actual destination (other company’s EtherNet/IP node). Specify the node address of the actual destination in the command data of the explicit message send command. There are two ways to send an explicit message send command: 1,2,3... 1. CIP UCMM MESSAGE SEND command (28 10) Messages can be routed through multiple CIP network layers. (Messages can be routed through 16 network levels. The explicit message send command may time out if routing is attempted for more than 16 networks. 2. EXPLICIT MESSAGE SEND command for DeviceNet Units (28 01) This command is compatible with the DeviceNet Unit’s explicit message send command (28 01) in the ladder program. The message must be sent 234 Section 9-1 Sending Explicit Messages in the same network layer and the remote node’s IP address range is limited. The following diagram shows an example of actual node address specifications. EtherNet/IP Unit with unit number 2 PLC's CPU Unit FINS command CMND S D C The node address of the non-OMRON node is set as the destination node address in the FINS command data. 15 8 7 2 0 S S+1 8 6 0 0 Command code 1 Node 05 Explicit command block Node address of the nonOMRON node: 06 Hex 15 C+3 8 7 0 5 0 F E Explicit message Other company's EtherNet/IP node Destination node address: Destination unit address: Local node address: 05 FE or 12 (Hex) Note Depending on conditions, the destination slave may not always accept an explicit message. Always perform retry processing when sending explicit messages. 235 Section 9-1 Sending Explicit Messages CIP UCMM MESSAGE SEND (28 10) This command sends an explicit message for CIP routing to another node’s specified class and receives a response. There are two command formats: one with a specified route path (path to the target device), and the other without the route path. Command Block • Relay Hop Format The following format includes the route path (routing service data). Specify the entire routing path in the command’s request path. 502 bytes max. Request path 52 28 10 Command code Transport ID 02 20 06 24 Message monitoring time 01 Instance ID: 01 Hex 8-bit instance ID: 24 Hex Class ID Connection Manager: 06 Hex 8-bit class ID: 20 Hex Request path size = 2 words: 02 Hex Service code Unconnected Send service: 52 Hex Routing service data 502 bytes max. 00 Message request size Time Out Ticks Priority/Time Tick Request path (variable length) Request path size Service code Request data (variable length) Route path (variable length) Padding data (when necessary) Routing service data Last hop data Routing service data Route path size • Last Hop Format The following format does not include the route path. 2810 Hex Command code Transport Message ID monitoring time 502 bytes max. Request path size (variable length) Request path size Service code 236 Request data (variable length) Section 9-1 Sending Explicit Messages Response Block The following normal response is returned to a transmitted CIP UCMM MESSAGE SEND command if it was completed normally. 2810 Hex 0000 Hex Command code Response code 00 Hex Transport No. of bytes ID received 502 bytes max. 00 00 Hex Hex Service response data (variable length) Reserved General status Reserved Service code (response) The following response is returned if an error occurs in a transmitted CIP UCMM MESSAGE SEND command. 2810 Hex 0000 Hex Command code Response code Transport No. of bytes ID received 502 bytes max. 00 Hex Additional status Service (variable length) response data Additional status size (variable length) General status Reserved Service code (response) The following response is returned if the CIP UCMM MESSAGE SEND command could not be sent or timed out. 2810 Hex Command code Response code (See note.) Note: There may be additional data depending on the response code, e.g., for a relay error. Parameters Transport ID (command, response): When multiple CIP UCMM MESSAGE SEND commands are being sent, the Transport ID identifies the commands. This Transport ID is returned unchanged in the response. Message monitoring time (command): Specifies the monitoring time in 10-ms units, in order to monitor the time from the point that the EtherNet/IP Unit or built-in EtherNet/IP port extracts the CIP explicit message from this command until a response is received. The monitoring time can be set between 0.01 and 655.35 s. Service code (command, response): In the command, this code is the service code defined for EtherNet/IP. In the response, bit 15 of the service code specified in the command is turned ON and the resulting value is returned. 237 Section 9-1 Sending Explicit Messages In the routing format for rely hops, the first service code (in the routing service data) is 52 Hex, which is the Unconnected Send service. Request path size (command): Specifies the number of words of data that are specified in the request path field. In the routing format for relay hops, the first request path size (in the routing service data) is 02 Hex. Request path (command): Specifies the request path (class ID, instance ID, etc.) in bytes. If there is an odd number of bytes, pad the last byte with a 0 so that the data is in full word units. In the routing format for relay hops, the first request path (in the routing service data) is 20 06 24 01 Hex (Connection Manager). For details, refer to the description of the Route Path in Appendix D CIP Message Communications. Request data (command): In the command, specify the data determined by the service code. In the response, the reception data determined by the service code will be returned. Priority/Time tick (command): The timeout time specified by the Priority Time Tick is used as a base value to specify the actual timeout value. For details, refer to the description of the Priority/Time Ticks and Time Out Ticks at the end of Appendix D CIP Message Communications. Time Out Ticks (command): Specifies the base value of the timeout time. For details, refer to the description of the Priority/Time Ticks and Time Out Ticks at the end of Appendix D CIP Message Communications. Message request size (command): Specifies the number of bytes of data from the second service code to the request data. The data size is specified in LSB, MSB order. For example, if there are 400 bytes, the data size is 0190 hex bytes, which is entered as 90 01 hex. Padding data (command): If the message request size specifies an odd number of bytes, use 00 hex as padding in the last byte. The padding data is not required if there is an even number of bytes. Route path size (command): Specifies the number of words of data that are specified in the route path field. Route path (command): Specifies the path (route path) to the target device. For details, refer to the description of the Route Path in Appendix D CIP Message Communications. No. of bytes received (response): This hexadecimal value is returned to indicate the number of bytes of data received after the service code (response). General status (response): The general status defined in EtherNet/IP is returned. The normal response is 00 hex. For details, refer to the description of the Response Codes in Appendix D CIP Message Communications. Additional status size (response): 238 Section 9-1 Sending Explicit Messages This hexadecimal value is returned to indicate the number of words of data in the additional status field. Additional status (response): The additional status defined in EtherNet/IP is returned. For details, refer to the description of the Response Codes in Appendix D CIP Message Communications. Service response data (response): The reception data determined by the service code is returned. Description • The CIP UCMM MESSAGE SEND command is used to send an EtherNet/IP-defined explicit message to another company’s node and receive a response. • Unlike other FINS commands, the destination of a CIP UCMM MESSAGE SEND command’s control data is the local node’s EtherNet/IP Unit or built-in EtherNet/IP port, and the actual destination node is specified in the command’s route path. • When an EtherNet/IP Unit or built-in EtherNet/IP port receives an explicit message, it automatically returns a response to the message. • When specifying the timeout time, the proper values are different for lasthop and relay-hop methods. With the last-hop method, set the timeout time for the actual request service processing. With the relay-hop method, the timeout for the relay path must be added to the timeout time for the actual request service processing. In CIP routing, the node/Unit performing the routing subtracts the timeout time for 1 hop, deletes its own address from the routing information, and relays the message to the next node/Unit. Set the following timeout values for command processing. The maximum number of relay nodes (Units) is 16. If the number is more than 16, the explicit message send command may time out even if the conditions of network and each node (Unit) are normal. If more than 16 relay nodes (Units) have been set, a constant time must be specified for the request service processing timeout time (normally 0000 hex). • Priority Time Tick and Time Out Ticks = (5 s × Number of relay nodes/Units) + Request processing timeout • Message monitoring time ≥ Priority Time Tick and Time Out Ticks • CMND(490) timeout set value = Message monitoring time A timeout may occur sooner than the actual set value, depending on the point where the timeout occurs in the path. • General status = 01 hex, and Additional status = 0204 hex A FINS timeout error response (0205 hex) may occur if the CMND(490) timeout set value or message monitoring time is less than the Priority Time Tick and Time Out Ticks. Note 1. For details on the parameters of explicit messages, refer to the EtherNet/ IP and CIP specifications. 2. The Open DeviceNet Vendor Association, Inc. (ODVA) can be contacted at the following address to obtain copies of the EtherNet/IP and CIP specifications. ODVA Headquarters 4220 Varsity Drive, Suite A 239 Section 9-1 Sending Explicit Messages Ann Arbor, Michigan 48108-5006 USA TEL: 1 734-975-8840 FAX: 1 734-922-0027 Email odva@odva.org WEB www.odva.org 240 Section 9-1 Sending Explicit Messages EXPLICIT MESSAGE SEND (28 01) EXPLICIT MESSAGE SEND will send a DeviceNet Unit-compatible explicit message to the specified class of another node and receive a response. The other node is specified with the destination node address in the command. The actual destination IP address is as follows. Destination IP address = (Local IP address & Subnet mask) + Destination node address Command Block 28 01 468 bytes max. Command code Class ID Service code Instance ID Service data Destination node address Response Block Normal Response 28 01 00 00 Command Response No. of bytes code code received 498 bytes max. Service data Service code Destination node address (remote node) Error Responses The following response is returned if an error occurs for the explicit message. 28 01 00 00 Command Response No. of bytes code code received 94 Error code Service code 94 (Hex) Destination node address (remote node) The following response is returned if the explicit message cannot be sent or times out. 28 01 Command code Parameters Response code Destination node address (command): The node address of the destination of the explicit message. The node address of the local EtherNet/IP Unit or built-in EtherNet/IP port is specified in the control data for the CMND(490), but the node address of the actual destination is specified here in the FINS command. The destination node address cannot be set to 00 hex or FF hex. Service code (command, response): A service code defined for EtherNet/IP. In a normal response, bit 15 of the service code specified in the command will be turned ON and returned. In an error response, 94 Hex will always be returned. 241 Section 9-1 Sending Explicit Messages Class ID (command): The class ID of the destination of the explicit message. Instance ID (command): The instance ID of the destination of the explicit message. Service data (command, response): The data defined for the services codes. No. of bytes received (response): The number of bytes received from the destination node address (remote node). Destination node address (remote node): The node address of the OMRON Special I/O Slave Unit or Slave manufactured by another company to which the explicit message was sent is returned. Error code (response): An error code defined in EtherNet/IP (1-byte general status and 2-byte additional status) is returned. The data format is DeviceNet-compatible (2 bytes total), so the returned Error Code is converted to the 1-byte general status and a 1-byte additional status (high byte only). Description • The EXPLICIT MESSAGE SEND command is used to send an EtherNet/ IP-defined explicit message to another company’s node and receive a response. • Unlike other FINS commands, the destination of a EXPLICIT MESSAGE SEND command’s control data is the local node’s EtherNet/IP Unit or built-in EtherNet/IP port, and the actual destination node is specified in the command’s route path. Always specify the local node’s EtherNet/IP Unit or built-in EtherNet/IP port in the CMND(490) instruction’s control data. An error will occur if another node’s Master Unit is specified as the destination. • When an EtherNet/IP Unit or built-in EtherNet/IP port receives an explicit message, it automatically returns a response to the message. • A time of 2 s is used for request service processing timeouts. Set the CMND(490) instruction’s timeout set value to 2 s or longer. When there is a timeout, the error code will be 0102 hex. When the CMND(490) instruction’s timeout set value is less than 2 s, a FINS timeout error response of 0205 hex may occur. Note 1. For details on the parameters of explicit messages, refer to the EtherNet/ IP specifications. 2. The Open DeviceNet Vendor Association, Inc. (ODVA) can be contacted at the following address to obtain copies of the EtherNet/IP and CIP specifications. ODVA Headquarters 4220 Varsity Drive, Suite A Ann Arbor, Michigan 48108-5006 USA TEL: 1 734-975-8840 FAX: 1 734-922-0027 Email odva@odva.org WEB www.odva.org 242 Section 9-1 Sending Explicit Messages 9-1-1 Sending Explicit Messages Using CMND(490) With a CS/CJ-series EtherNet/IP Unit or built-in EtherNet/IP port, a CMND(490) in the CPU Unit’s ladder program can send CIP UCMM explicit messages. Send the CIP UCMM explicit message’s command data in a FINS command following the 2810 hex FINS command code. The CIP UCMM explicit message’s response is received following the 2810 hex FINS command code and the FINS completion code. The following command is used: [ CMND S D C] S: First command word D: First response word C: First control data word Command data is set in order starting with the word specified for the CMND(490) operand S (first command word) and continuing with words with higher addresses in I/O memory in the command block format. Command Format Example: Get_Attribute_All Service to Identity Object Request path 28 10 Command code 00 05 00 DC 52 02 20 06 24 01 0A 0C 06 00 Message request size Transport ID Time Out Ticks Service code Unconnected Send service: 52 Hex Priority/Time Tick Instance ID Request path size = 2 words: 02 Hex 8-bit class ID: 20 Hex 8-bit instance ID: 24 Hex Class ID Connection Manager: 06 Hex Routing service data Route path Request path 01 02 20 24 01 01 08 00 12 Route path size (8 words) Instance ID 0D 31 39 32 2E 31 36 1 9 2 . 1 6 Route path size (13 bytes) Ethernet port: 12 Hex 8-bit instance ID: 24 Hex Class ID identity object 8-bit class ID Request path size (2 words) Service code Get_Attribute_All service Last hop data Routing service data Route path 38 2E 32 35 30 2E 32 8 . 2 5 0 . 2 00 Padding data Routing service data 243 Section 9-1 Sending Explicit Messages Setting the Command Data for CMND(490) Bit 15 08 07 00 S+0 28 10 S+1 00 00 FINS command code Transport ID S+2 05 DC Message monitoring time S+3 52 02 S+4 20 06 S+5 24 01 S+6 0A 0C Service code = 52 hex, Request path size = 02 hex 8-bit class ID = 20 hex, Class ID = 06 hex (Connection Manager) 8-bit instance ID = 24 hex (request path), Instance ID = 01 hex Priority/Time Tick = 0A hex, Time Out Ticks = 0C hex S+7 06 00 Message request size S+8 01 02 S+9 20 01 S+10 24 01 S+11 08 00 S+12 12 0D S+13 31 39 S+14 32 2E S+15 31 36 S+16 38 2E S+17 32 35 S+18 30 2E S+19 32 00 Service code = 01 hex (Get_Attribute_All service), Request path size = 02 hex 8-bit class ID = 20 hex, Class ID = 01 hex (Identity Object) Link path 8-bit instance ID = 24 hex, Instance ID = 01 hex Route path size = 8 words Ethernet port = 12 hex (Extended Link Address Size = 1 hex, Ethernet port number = 2 hex), Route path size = 13 bytes 1 9 2 . 1 6 Route path IP address 8 . 192.168.250.2 2 5 0 . 2 The response data is set in the same way, starting from the word specified for CMND(490) operand D (first response word) and continuing with words with higher addresses in I/O memory in the response block format. Note Request path data or request data that is in word (2-byte) or double-word (4byte) units, such as word data and ERROR CLEAR codes, is specified from low to high (U) bytes in command block format. For example, to specify word data 1234 hex, specify 34 hex and then 12 hex. To specify the double word data 12345678 hex, specify 78 hex, 56 hex, 34 hex, and then 12 hex. The command blocks are shown in the following diagram. Command Block Example: 1234 hex Example: 12345678 hex Service Data Service Data The format from CMND(490) operand S onwards will be set as follows: Example: 1234 hex From higher byte Bit Example: 12345678 hex From higher byte Bit From lower byte Bit From lower byte Bit Similarly, when the additional status data and service response data in the response block is in word (2-byte) or double-word (4-byte) units, such as word 244 Section 9-1 Sending Explicit Messages data and ERROR CLEAR codes, is also returned in the same order from low to high bytes in the response block. Example: Sending Explicit Messages Using CMND(490) EtherNet/IP Unit with unit number 0 PLC's CPU Unit CMND(490) instruction Network address: 01 hex Node address: 05 hex Unit address: 10 hex Explicit message EtherNet/IP node of other manufacturer Operation The identity object information (class ID = 01 hex) is read from the other company’s EtherNet/IP node at IP address 192.168.250.2, using the CIP UCMM MESSAGE SEND command, 28 10. The command data is stored in the DM Area starting at DM01000, and the response data is stored in the DM Area starting at D02000. If the command ends with an error, the end code is stored in D00006 and command transmission is retried. Command Details [CMND S D C] S = D01000: First command word D01000 = 2810 hex D01001 = 0000 hex D01002 = 05DC hex D01003 = 5202 hex D01004 = 2006 hex D01005 = 2401 hex Command Code Transport ID: 0000 hex Message monitoring time: 15.00 s Slave code: 52 hex (Unconnected Send) Request path size: 2 words Request path: 20 06 24 01 hex (Connection Manager) Class ID: 06 hex Instance ID: 01 hex Words S+6 to S+19 contain the request data. D01006 = 0A0C hex Priority/Time_Tick: 0A hex Time Out Ticks: 0C hex D01007 = 0600 hex Message request size: 6 bytes Words S+8 to S+10 contain the request message request. D01008 = 0102 hex Service: 01 hex (Get_Attribute_All) Request path size: 2 words Words S+9 and S+10 contain the request path. D01009 = 2001 hex 8-bit class ID: 20 hex Class ID: 01 hex D01010 = 2401 hex 8-bit instance ID: 24 hex Instance ID: 01 hex (Identity object) Words S+11to S+19 contain the root path. D01011 = 0800 hex Route path size: 8 words D01012 = 120D hex Extended link address size = 1 hex Route path size: 13 bytes (characters) = 0D hex D01013 = 3139 hex IP address: “19” D01014 = 322E hex IP address: “2.” D01015 = 3136 hex IP address: “16” 245 Section 9-1 Sending Explicit Messages D01016 = 382E hex D01017 = 3235 hex D01018 = 302E hex D01019 = 3200 hex D = D02000: C = D00000: First response word at local node First control word D00000 = 0028 hex D00001 = 0064 hex D00002 = 0001 hex D00003 = 0510 hex D00004 = 0000 hex D00005 = 00A0 hex Response IP address: “8.” IP address: “25” IP address: “0.” IP address: “2” Padding data: 00 hex D02000 = 2801 hex D02001 = 0000 hex D02002 = 0000 hex D02003 = 001D hex D02004 = 8100 hex D02005 = 0000 hex Number of command bytes: 40 bytes Number of response bytes: 100 bytes Destination network address: 1 Destination node address: 5 Destination unit address: FE hex (or 10 hex) Response, communications port 0, no retries Response monitoring time: 16.0 s Command code FINS completion code Transport ID Number of bytes received: 29 bytes Service code (response): 81 hex Reserved: 00 hex General status: 00 hex Reserved: 00 hex Words C+6 to C+18 contain the service response data. D02006: 2F00 hex D02007: 0C00 hex D02008: 0C00 hex D02009: 0101 hex D020010: 3000 hex D020011: 5303 hex D020012: 0011 hex D020013: 0A43 hex D020014: 5331 hex D020015: 572D hex D020016: 4549 hex D020017: 5032 hex D020018: 3100 hex 246 Section 9-1 Sending Explicit Messages Program Example A20011 (071) BSET #0000 D00000 D02999 000000 First Cycle Flag Sets 0000 in D00000 to D02999. (021) MOV #0028 D00000 Sets 0028 in D00000. (Number of send data bytes: 40) (021) MOV #0064 D00001 Sets 0064 in D00001. (Number of receive data bytes: 100). (021) MOV #0001 D00002 Sets 0001 in D00002. (Destination network address: 01). (021) MOV #0510 D00003 Sets 0510 in D00003. (Destination node address: 05, destination unit address: 10) (021) MOV #0000 D00004 (021) MOV #00A0 D00005 Sets 0000 in D00004. (Response required, port number 0, number of retries = 0) Sets 00A0 in D00005. (Response monitoring time: 16.0 s) (021) MOV #2810 D1000 (021) MOV #0000 D1001 (021) MOV #05DC D1002 (021) MOV #5202 D1003 (021) MOV #2006 D1004 (021) MOV #2401 D1005 (021) MOV #0A0C D1006 (021) MOV #0600 D1007 (021) MOV #0102 D1008 (021) MOV #2001 D1009 (021) MOV #2401 D1010 (021) MOV #0800 D1011 Command data Set the CIP UCMM MESSAGE SEND command's command data in words D01000 to D01019 in routing data format. (021) MOV #120D D1012 (021) MOV #3139 D1013 (021) MOV #322E D1014 (021) MOV #3136 D1015 (021) MOV #382E D1016 (021) MOV #3235 D1017 (021) MOV #302E D1018 (021) MOV #3200 D1019 Execution condition 000000 (021) MOV #0001 0000 A20200 151100 Communications Enabled Flag Online Flag (n+11, bit 00) A20200 A21900 000013 000001 (490) CMND D01000 D02000 D00000 000018 Communications Enabled Flag 000024 Network Communication Execution Error Flag (025) ASL 0000 (021) MOV A203 D00006 (026) ASR 0000 (001) END Moves 0001 into CIO 0000. Sends 8 bytes of command data to destination node address 06, receives 14 bytes of response data, and stores it in the local node starting at D02000. (D00000 is control data.) Shifts the contents of CIO 0000 one bit to the left. Copies the completion code (network communications error response code) from A203 to D00006. Shifts the contents of CIO 0000 one bit to the right and retries in the next cycle (CIO 000000 ON). 247 Section 9-2 Receiving Explicit Messages 9-2 Receiving Explicit Messages The CS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports are equipped with a PLC Object that is functionally compatible with CS/CJ-series DeviceNet Units. The Unit will receive messages addressed to the PLC Object, process service requests addressed to the CPU Unit, and return responses. The CS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports support CIP unconnected message (UCMM) communications and CIP connected (Class 3) communications as reception functions. The following services are provided by the PLC Object. • CPU Unit status read/write • CPU Unit I/O memory read/write • CPU Unit error log read/clear Explicit messages can be received from the following sources: • EtherNet/IP nodes made by other manufacturers • OMRON PLCs with a CS/CJ-series EtherNet/IP Unit or a CPU Unit with a built-in EtherNet/IP port. (Messages from CS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports must be CIP unconnected messages (UCMM).)* * Messages from CS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports must be CIP unconnected messages (UCMM). Example CS/CJ-series CS/CJ-series EtherNet/IP Unit EtherNet/IP Unit CS/CJ-series CPU Unit Explicit messages can be sent. CS/CJ-series CPU Unit Other company's Ethernet node Explicit message Ethernet (EtherNet/IP) Note For an EtherNet/IP Unit or built-in EtherNet/IP port with version 2.0 or higher, change the class ID of the PLC Object from 2F hex to C4 hex. When using a PLC Object with a DeviceNet Unit or EtherNet/IP Unit with version 1.0, and converting to EtherNet/IP Unit or built-in EtherNet/IP port with a version 2.0 or higher, the class ID must be changed according to the communications application. 248 Section 9-2 Receiving Explicit Messages 9-2-1 List of PLC Object Services PLC Objects provide the following services. Status Read/Write for CPU Units Services CPU Unit Information Read CPU Unit Write CPU Unit Status Read Service code 0E Hex 10 Hex 40 Hex Class ID C4 Hex (2F Hex) (See note.) Instance ID 00 Hex Request service data Attribute ID = 64 Hex Attribute ID = 65 Hex Attribute ID = 66 Hex Attribute ID = 64 Hex, Attribute Value Attribute ID = 65 Hex Attribute Value None Contents Reads the operating mode of the CPU Unit. Reads if there is a fatal or non-fatal error in the CPU Unit. Reads CPU Unit model. Changes the operating mode of the CPU Unit. Clears errors. Reads the detailed status of the CPU Unit. Operation status: Stop, run, CPU standby Operating modes: PROGRAM, MONITOR, RUN Fatal error information: Error flags, including memory errors, I/O bus errors, system errors Messages: Message No. when MSB instruction executed by CPU Unit Error codes: Error code for the most serious errors Error messages: Messages stored in CPU Unit when FAL/FALS instruction executed 249 Section 9-2 Receiving Explicit Messages I/O Memory Read/Write for CPU Units Service Service code Byte Data Read 1C Hex Word Data Read 1D Hex Byte Data Write 1E Hex Word Data Write 1F Hex Class ID Instance ID C4 Hex (2F Hex) (See note.) Specifies area (01 Hex to 14 Hex) Request Contents service data Address, No. Reads the specified node data in byte units. of read bytes The word data is read in order, from high to low bytes. Read data: 200 bytes max. Address, No. Reads the specified node data in word of read units. The word data is read in order, from words high to low bytes. Read data: 200 bytes max. Address, Writes the specified node data in byte units. byte data The word data is specified in order, from high to low bytes. Write data: 200 bytes max. Address Writes the specified node data in word word data units. The word data is specified in order, from high to low bytes. Write data: 200 bytes max. Note With a EtherNet/IP Unit or built-in EtherNet/IP port with unit version 2.0 or later, the PLC object class ID is C4 hex. (With unit version 1.0, the PLC object class ID is F2 hex.) The commands and responses for the explicit messages that can be sent and received are described on the following pages. In the following command and response formats, all boxes represent 1 byte each. 250 Section 9-2 Receiving Explicit Messages CPU Information Read (Service Code: 0E Hex) Reads CPU Unit information, including operating mode, fatal/non-fatal errors, and the CPU Unit model. Command Block 0E C4 (2F) (*) 00 (*) The class ID depends on the unit version. Version 2.0: The class ID is C4. Version 1.0: The class ID is 2F. Attribute ID Class ID Instance ID Service Code Note A body format of either 8 bits or 16 bits is possible. Response Block 8E Service Code Attribute Value Parameters Service code (command, response): 0E Hex is specified for commands. For responses, the highest bit be ON and 8E Hex will be returned. Class ID (command): Always C4 (2F). The class ID depends on the unit version. The class ID is C4 for unit version 2.0, and 2F for unit version 1.0. Instance ID (command): Always 00 Hex. Attribute ID (command): The read information is specified by the attribute ID. The attribute IDs are listed in the following table. Attribute ID (Hex) 64 65 66 Contents CPU Unit operating mode CPU Unit errors CPU Unit model Attribute value size 1 word (2 bytes) 1 word (2 bytes) 22 bytes • CPU Operating Mode (when Attribute ID = 64 Hex) Reads the CPU Unit operating mode. • CPU Unit Errors (when Attribute ID = 65 Hex) Reads if there are any fatal or non-fatal errors in the CPU Unit. • CPU Unit Model (when Attribute ID = 66 Hex) Reads the CPU Unit model. Read data (response): The specified information is returned in order. • CPU Unit operating mode (attribute ID = 64 Hex). The CPU Unit operating mode is returned in 1-word (2-byte) hexadecimal format, as follows: 0001 Hex: PROGRAM mode; 0002 Hex: MONITOR mode; 0004 Hex: RUN mode PROGRAM mode MONITOR mode RUN mode 251 Section 9-2 Receiving Explicit Messages Note The codes for the above modes are 1-word (2-byte) data and are returned in low byte first. For example, for PROGRAM mode, the code is returned as 01 Hex followed by 00 Hex. • CPU Unit Errors (when Attribute ID = 65 Hex) The CPU Unit fatal/non-fatal error data is returned in 1-word (2-byte) hexadecimal format, as follows: 01 Hex: Error; 00 Hex: No error. 1: Error • CPU Unit Model (when Attribute ID = 66 Hex) The CPU Unit model is returned in ASCII. Size: 2 bytes (Always 1400 Hex) + Model: 20 bytes (fixed). Unused area is filled with 20 Hex (spaces) and returned. 20 bytes Byte Byte Byte Byte Byte Unit name CPU Unit Write (Service Code: 10 Hex) This PLC Object service writes CPU Unit information, including the operating mode and clearing errors. Command Block 10 C4 (2F) (*) 00 The class ID depends on the unit version. Version 2.0: The class ID is C4. Version 1.0: The class ID is 2F. (*) Attribute ID Class ID Service Code Attribute Value Instance ID Note A body format of either 8 bits or 16 bits is possible. Response Block 90 Service Code Parameters Service code (command, response): 10 Hex is specified for commands. For responses, the highest bit will turn ON and 90E Hex will be returned. Class ID (command): Always C4 (2F). The class ID depends on the unit version. The class ID is C4 for unit version 2.0, and 2F for unit version 1.0. Instance ID (command): Always 00 Hex. Attribute ID (command): Information to write is specified by the attribute ID. The attribute IDs are listed in the following table. Attribute ID (Hex) 64 65 252 Contents CPU Unit operating mode CPU Unit errors Attribute value size 1 word (2 bytes) 1 word (2 bytes) Section 9-2 Receiving Explicit Messages • CPU Operating Mode (Attribute ID = 64 Hex) Changes the CPU Unit operating mode. The Attribute Values are as follows: 0001 Hex: PROGRAM mode; 0002 Hex: MONITOR mode; 0004 Hex: RUN mode Note The specified code for the above operating modes are 1-word (2-byte data, and are specified with the low byte first. For example, for PROGRAM mode, the code is specified as 01 Hex followed by 00 Hex. Accordingly, the low to high bytes for the above codes are set as high to low bytes in I/O memory, when setting the codes as data for operand S of CMND(490). • Clearing CPU Unit Errors (when Attribute ID = 65 Hex) Clears any fatal or non-fatal errors in the CPU Unit. Sets the error clear code to Attribute Value. The error clear codes are listed in the following table. Error code (Hex) FFFE 0008B 009A 009B 02F0 0300 to 035F 00A0 to 00A1 0500 to 055F 00E7 Data cleared Current error (clears the highest priority error) Interrupt task error Basic I/O error PLC Setup error Inner Board non-fatal error Special I/O Unit error SYSMAC BUS error Special I/O Unit settings error I/O verification error When registered and actual I/O tables are different When disconnecting or connecting I/O Units Battery error CS/CJ-series CPU Bus Unit error (last 2 digits are binary code for the Unit No.) For parity errors generated when data transferred between CS/CJseries CPU Bus Unit and CPU Unit For watchdog timer errors in CS/CJ-series CPU Bus Unit CPU Bus settings error (last 2 digits are binary code for the Unit No.) System error (FAL): FAL instruction executed 00F7 0200 to 020F 0400 to 040F 4101 to 42FF Note Error clear codes are 1-word (2-byte) data, so the above codes are specified with the low byte first. The low to high bytes for the above codes are set as high to low bytes in I/O memory, when setting the codes as data for operand S of CMND(490). For example, to specify battery error 00F7 Hex, specify the error code as F7 Hex followed by 00 Hex, as shown in the following diagram. 10 C4 (2F) 00 65 F7 00 The class ID depends on the unit version. Version 2.0: The class ID is C4. Version 1.0: The class ID is 2F. Class ID Attribute ID Attribute Value Service Code Instance ID 253 Section 9-2 Receiving Explicit Messages CPU Unit Status Read (Service Code: 40 Hex) This PLC Object service reads status details (operation status, operating mode, fatal and non-fatal errors, etc.) from the CPU Unit. Command Block 40 C4 00 (2F) (*) (*) The class ID depends on the unit version. Version 2.0: The class ID is C4. Version 1.0: The class ID is 2F. Class ID Service Code Instance ID Note A body format of either 8 bits or 16 bits is possible. Response Block C0 Service Code Detailed status Parameters Service code (command, response): 40 Hex is specified for commands. For responses, the highest bit will turn ON and C0 Hex will be returned. Class ID (command): Always C4 (2F). The class ID depends on the unit version. The class ID is C4 for unit version 2.0, and 2F for unit version 1.0. Instance ID (command): Always 00 Hex. Read data (response): The read data is given in the following table. The data is returned after the service code in the order shown in the table (high to low). Operation Status RUN mode Fatal error information (L) Fatal error information (H) Non-fatal error information (L) Non-fatal error information (H) Message exists/does not exist (L) Message exists/does not exist (H) Error code (L) Error code (H) Error message (16 bytes) • Operation status: Returns the operation status of the CPU Unit in 1-byte (2-digit) hexadecimal. The values of bits 3 to 6 are not fixed. Always mask them when addressing the status data. 254 Section 9-2 Receiving Explicit Messages Bit 7 6 - 5 - 4 - 3 - 2 1 0 Operation status 0: Stopped (User program is not being executed.) 1: Operating (User program is being executed.) Flash memory access status (CS1H, CJ1-H, CJ1M, and CS1D only) 0: Memory is not being written. 1: Memory is being written. Battery status (CS1H, CJ1-H, CJ1M, and CS1D only) 0: No battery 1: Battery installed CPU status 0: Normal 1: CPU standby (waiting for SYSMAC Bus Remote I/O or other event) Unspecified • Operating mode: Returns the operating mode of the CPU Unit in 1-byte (2-digit) hexadecimal. 0001 Hex: PROGRAM mode; 0002 Hex: MONITOR mode; 0004 Hex: RUN mode • Fatal error information: Returns the fatal error information for the CPU Unit in 2 bytes (low to high). 1: System error (FALS) 1: Cycle time over 1: Program error 1: I/O setting error 1: No. of I/O points exceeded 1: Inner Board fatal error 1: Number duplicate use error 1: I/O Bus error 1: Memory error • Non-fatal error information: Returns the non-fatal error information for the CPU Unit in 2 bytes (low to high). Unspecified (reserved for system use) 1: Special I/O Unit error 1: CPU Bus settings error 1: Battery error 1: SYSMAC BUS error 1: Special I/O Unit 1: CS1-series CPU Bus Unit error 1: Inner Board error 1: I/O verification error 1: PLC system error 1: Unspecified (reserved for system use) 1: Basic I/O Unit error 1: Interrupt task error 1: Unspecified (reserved for system use) 1: System error (FAL) 255 Section 9-2 Receiving Explicit Messages • Message Exists/Does Not Exist: When the MSG instruction is executed by the CPU Unit, the bit corresponding to the message number will turn ON and be returned in 2 bytes (from low to high bytes). Message No. 0 (1: exists; 0: does not exist) Message No. 1 (1: exists; 0: does not exist) Message No. 2 (1: exists; 0: does not exist) Message No. 3 (1: exists; 0: does not exist) Message No. 4 (1: exists; 0: does not exist) Message No. 5 (1: exists; 0: does not exist) Message No. 6 (1: exists; 0: does not exist) Message No. 7 (1: exists; 0: does not exist) • Error Code: The highest priority error code of the errors existing when the command is executed will be returned in 2-byte decimal (from low to high bytes). If there are no errors, the error code will be 0000. Note For information on the severity of error codes, refer to the CS1 Series CPU Unit Operation Manual (W339) or the CJ Series CPU Unit Operation Manual (W393). • Error Messages: If the above error codes have occurred when FAL/FALS instructions are executed with registered messages, those messages are returned in 16-byte ASCII. If there are no registered messages or if the error codes have not occurred due to execution of FAL/FALS instructions, the code is returned in ASCII with 20 Hex (space) in 16 bytes. Byte Data Read (Service Code: 1C Hex) Byte Data Read reads any I/O memory area data in a CPU Unit. The read word data is in byte units. The response block data is returned in low-to-high byte order. Command Block 1C C4 (2F) (*) The class ID depends on the unit version. Version 2.0: The class ID is C4. Version 1.0: The class ID is 2F. (*) Class ID Address L No. of bytes read Address H Service Code Instance ID Note A body format of either 8 bits or 16 bits is possible. Response Block 9C Service Code Word data L Word data H Word data L Word data H Read data (200 bytes max.) Parameters 256 Service code (command, response): 1C Hex is specified for commands. For responses, the highest bit will turn ON and 9C Hex will be returned. Section 9-2 Receiving Explicit Messages Class ID (command): Always C4 (2F). The class ID depends on the unit version. The class ID is C4 for unit version 2.0, and 2F for unit version 1.0. Instance ID (command): The memory area that will read the data is specified as shown in the following table. Instance ID (Hex) 01 03 04 05 08 to 20 CPU Unit memory area for read CIO DM WR HR EM, banks 0 to 18 Word range 0000 to 6143 D00000 to D32767 W000 to W511 H000 to H1535 En_00000 to En_32767 (n: 0 to 18) Address L, Address H (command): The address of the first word from which to read the data is specified in hexadecimal as shown below. Address L: The lower 2 digits when the first word address is given in 4-digit hexadecimal. Address H: The higher 2 digits when the first word address is given in 4-digit hexadecimal. No of Read Bytes (command): The number of bytes of read data is specified in 1-byte (2-digit) hexadecimal. The range is 01 to C8 Hex (1 to 200 decimal). No. of bytes received (response): The number of bytes received from the destination node address (remote node) is returned in hexadecimal. Destination node address (response): The node address of the CS/CJseries EtherNet/IP Unit or built-in EtherNet/IP port that returned the response is returned in hexadecimal. Read data (response): The specified area, word, and byte data is returned in order from word H (high byte: bits 8 to 15) to word L (low byte: bits 0 to 7). If an odd number is specified for the number of read bytes, the last 1 byte of data will be read to the high word. Important Points The actual address L, address H, and number of read bytes that can be specified depends on the model of the CPU Unit, and the data area being read. Do not exceed the boundary of the data areas for the PLC you are using. Word Data Read (Service Code: 1D Hex) Word Data Read reads I/O memory area data in a CPU Unit. The read word data is in word units. The response block data is returned in low-to-high byte order. Command Block C4 1D (2F) (*) Class ID Service Code (*) The class ID depends on the unit version. Version 2.0: The class ID is C4. Version 1.0: The class ID is 2F. Address L No. of words read Instance ID Address H Note A body format of either 8 bits or 16 bits is possible. 257 Section 9-2 Receiving Explicit Messages Response Block 9D Service Code Word data H Word data L Word data H Word data L Read data (200 bytes max.) Parameters Service code (command, response): ID Hex is specified for commands. For responses, the highest bit will turn ON and 9D Hex will be returned. Class ID (command): Always C4 (2F). The class ID depends on the unit version. The class ID is C4 for unit version 2.0, and 2F for unit version 1.0. Instance ID (command): The type of memory area that will read the data is specified as shown in the following table. Instance ID (Hex) 01 03 04 05 08 to 20 CPU Unit memory area for read CIO DM WR HR EM, banks 0 to 18 Word range 0000 to 6143 D00000 to D32767 W000 to W511 H000 to H1535 En_00000 to En_32767 (n: 0 to 18) Address L, Address H (command): The address of the first word to read the data from is specified in hexadecimal as shown below. Address L: The lower 2 digits when the first word address is given in 4-digit hexadecimal. Address H: The higher 2 digits when the first word address is given in 4-digit hexadecimal. No of Read Words (command): The number of words of read data is specified in 1-byte (2-digit) hexadecimal. The range is 01 to 64 Hex (1 to 100 decimal). Read data (response): The specified area, word, and byte data is returned in order from word L (low byte: bits 0 to 7) to word H (high byte: bits 8 to 15). Important Points The actual address L, address H, and number of write data bytes that can be specified depends on the model of the CPU Unit, and the data area being written. Do not exceed the boundary of the data areas for the PLC you are using. Byte Data Write (Service Code: 1E Hex) Byte Data Write writes data to an I/O memory area in a CPU Unit. The write word data is in byte units. The command block is specified in high-to-low byte order, as shown in the following diagram. 258 Section 9-2 Receiving Explicit Messages Command Block 1E C4 (2F) (*) Class ID The class ID depends on the unit version. Version 2.0: The class ID is C4. Version 1.0: The class ID is 2F. (*) Address L Word data L Address H Service Instance ID Code Word data H Word data L Word data H Write data (200 bytes max.) Note A body format of either 8 bits or 16 bits is possible. Response Block 9E Service Code Parameters Service code (command, response): IE Hex is specified for commands. For responses, the highest bit will turn ON and 9E Hex will be returned. Class ID (command): Always C4 (2F). The class ID depends on the unit version. The class ID is C4 for unit version 2.0, and 2F for unit version 1.0. Instance ID (command): The type of memory area to which the data will be written is specified as shown in the following table. Instance ID (Hex) 01 03 04 05 08 to 20 CPU Unit memory area for write CIO DM WR HR EM, banks 0 to 18 Word range 0000 to 6143 D00000 to D32767 W000 to W511 H000 to H1535 En_00000 to En_32767 (n: 0 to 18) Address L, Address H (command): The address of the first word to which the data will be written is specified in hexadecimal as shown below. Address L: The lower 2 digits when the first word address is displayed in 4digit hexadecimal. Address H: The higher 2 digits when the first word address is displayed in 4digit hexadecimal. Write data (response): The specified area and write data is returned in order from word H (higher byte: bits 8 to 15) to word L (lower byte: bits 0 to 7). For byte data write, specify an even number. Important Points The actual address L, address H, and number of write data bytes that can be specified depends on the model of the CPU Unit, and the data area being written. Do not exceed the boundary of the data areas for the PLC you are using. Word Data Write (Service Code: 1F Hex) Word Data Write writes data to any I/O memory area in a CPU Unit. The write word data is in word units. The response block data is returned in low-to-high byte order. 259 Section 9-2 Receiving Explicit Messages Command Block 1F C4 (2F) (*) Class ID Service Code The class ID depends on the unit version. Version 2.0: The class ID is C4. Version 1.0: The class ID is 2F. (*) Address L Instance ID Word data H Address H Word data L Word data H Word data L Write data (200 bytes max.) Note A body format of either 8 bits or 16 bits is possible. Response Block 9F Service Code Parameters Service code (command, response): IF Hex is specified for commands. For responses, the highest bit will turn ON and 9F Hex will be returned. Class ID (command): Always C4 (2F). The class ID depends on the unit version. The class ID is C4 for unit version 2.0, and 2F for unit version 1.0. Instance ID (command): The memory area to which the data is written is specified as shown in the following table. Instance ID (Hex) 01 03 04 05 08 to 20 CPU Unit memory area for write CIO DM WR HR EM, banks 0 to 18 Word range 0000 to 6143 D00000 to D32767 W000 to W511 H000 to H1535 En_00000 to En_32767 (n: 0 to 18) Address L, Address H (command): The address of the first word to which the data is written is specified in hexadecimal as shown below. Address L: The lower 2 digits when the first word address is displayed in 4digit hexadecimal. Address H: The higher 2 digits when the first word address is displayed in 4digit hexadecimal. Write data (response): The specified area and write data is returned in order from word L (lower byte: bits 0 to 7) to word H (higher byte: bits 8 to 15). Important Points 260 The actual address L, address H, and number of write data bytes that can be specified depends on the model of the CPU Unit, and the data area being written. Do not exceed the boundary of the data areas for the PLC you are using. SECTION 10 Communications Performance and Communications Load This section describes the communications performance in an EtherNet/IP network, and shows how to estimate the I/O response times and transmission delays. 10-1 Communications System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262 10-1-1 Tag Data Link Communications Method . . . . . . . . . . . . . . . . . . . . . 262 10-1-2 Calculating the Number of Connections. . . . . . . . . . . . . . . . . . . . . . 264 10-1-3 Network Transmission Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . 265 10-2 Adjusting the Communications Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268 10-2-1 Checking Bandwidth Usage for Tag Data Links . . . . . . . . . . . . . . . 269 10-2-2 Tag Data Link Bandwidth Usage and RPI . . . . . . . . . . . . . . . . . . . . 270 10-2-3 Adjusting Device Bandwidth Usage. . . . . . . . . . . . . . . . . . . . . . . . . 271 10-2-4 Changing the RPI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272 10-2-5 RPI Setting Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276 10-3 I/O Response Time in Tag Data Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283 10-3-1 Timing of Data Transmissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283 10-3-2 EtherNet/IP Unit or CJ2H Built-in Port Data Processing Time . . . . 283 10-3-3 Effect on the CPU Unit’s Cycle Time. . . . . . . . . . . . . . . . . . . . . . . . 284 10-3-4 Tag Data Link I/O Response Time Calculation Example. . . . . . . . . 285 10-4 Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports . . . . . . . . . 291 10-4-1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291 10-4-2 Tag Data Link I/O Response Time . . . . . . . . . . . . . . . . . . . . . . . . . . 292 10-5 Message Service Transmission Delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294 10-5-1 Maximum Transmission Delays (Excluding Delays in the Network) 294 261 Section 10-1 Communications System 10-1 Communications System 10-1-1 Tag Data Link Communications Method Packet Interval (RPI) Settings In EtherNet/IP tag data links, the data transmission period is set for each connection as the packet interval (RPI). The target device will send data (i.e., output tags) once each packet interval (RPI), regardless of the number of nodes. Also, the heartbeat frame is sent from the originator to the target for each connection. The target uses the heartbeat to check to see if errors have occurred in the connection with the originator. The data transmission period of the heartbeat frame depends on the packet interval (RPI) settings. ■ Heartbeat Frame Transmission Period • Packet interval < 100 ms The heartbeat frame transmission period is 100 ms. • Packet interval ≥ 100 ms The heartbeat frame transmission period is the same as the RPI. Example In this example, 2 tag data link connections are set for node 2 (the originator) and node 1 (the target). The packet interval (RPI) for output data 1 is set to 10 ms. The packet interval (RPI) for output data 2 is set to 15 ms. In this case, output data 1 is sent from node 1 to node 2 every 10 ms, and output data 2 is sent from node 1 to node 2 every 15 ms, as shown in the following diagram. Also, data is sent from node 2 (the originator) to node 1 (the target) with a heartbeat of 100 ms for connection 1 and a heartbeat of 100 ms for connection 2. Node 1 Target Node 2 Output data 1 Originator Connection 1 heartbeat 100-ms interval Output data 2 10 ms Connection 2 heartbeat Output data 1 15 ms 10 ms Output data 2 Output data 1 262 100-ms interval Communications System Section 10-1 Packet Interval (RPI) and Bandwidth Usage (PPS) In a tag data link, the number of packets transferred each second is called the bandwidth used or PPS (packets per second). The PPS is calculated from the RPI and heartbeat as follows for each connection: PPS used in a connection (pps) = (1,000 ÷ RPI (ms)) + (1,000 ÷ Heartbeat transmission period (ms)) The following equation is used to calculate the total number of packets transferred by each EtherNet/IP Unit or built-in EtherNet/IP port in 1 second. Unit’s total PPS = Total PPS of originator connections + Total PPS of target connections (See note.) Note Connections set as target connections must be added, too. The maximum number of packets that the Unit can transfer in 1 second (called the allowed Unit bandwidth) is 6,000 pps (CJ2M: 3,000 pps), so set the connection below this maximum value. Example Node 1 has both originator and target connections, with send RPI of 200 ms and 2 ms, and receive RPI of 1 ms. Node 2 has originator connections only, with receive RPI of 200 ms, 2 ms, and 5 ms. Node 3 has target connections only, with send RPI of 5 ms and 1 ms. T Node 1 T O: Originator T: Target HB: Heartbeat O RPI: 200 ms HB: 200 ms RPI: 1 ms HB: 100 ms RPI: 2 ms HB: 100 ms T O O Node 2 Node 3 O RPI:5ms HB:100ms T Each node’s total PPS is calculated as follows. • Total PPS of node 1 Unit = 1,000 / 200 ms + 1,000 / 2 ms + 1,000 / 1 ms (for data) +1,000 / 200 ms + 1,000 / 100 ms + 1,000 / 100 ms (for heartbeat) = 1,530 pps • Total PPS of node 2 Unit = 1,000 / 200 ms + 1,000 / 2 ms + 1,000 / 5 ms (for data) +1,000 / 200 ms + 1,000 / 100 ms + 1,000 / 100 ms (for heartbeat) = 730 pps • Total PPS of node 3 Unit = 1,000 / 5 ms + 1,000 / 1 ms (for data) +1,000 / 100 ms + 1,000 / 100 ms (for heartbeat) = 1,220 pps All of the Units are within the allowed Unit bandwidth of 6,000 pps (CJ2M: 3,000 pps), so they can transfer data. 263 Section 10-1 Communications System 10-1-2 Calculating the Number of Connections The maximum number of connections for the Unit is 32 for the CJ2M and 256 for other CPU Units. The number of connections must be set to 32 or less for the CJ2M and 256 or less for other CPU Units combining both connections that the Unit opens as the originator and connections that are opened from an originator with the Unit as the target. Example Node 1 opens two connections as the target with node 2 and one connection as the originator with node 3. Therefore, the total is three connections. Node 2 opens two connections as the originator with node 1 and one connection as the target with node 3. Therefore, the total is three connections. Node 3 opens one connection as the target with node 1 and one connection as the target with node 2. Therefore, the total is two connections. In either case, the connections can be opened because the maximum number of connections for the Unit is less than 32 for the CJ2M and less than 256 for other CPU Units. T O Node 1 T O: Originator T: Target O T O Node 2 Node 3 O T Also, if multicast is set, one packet will be sent, but the number of connections will be consumed. Example Node 3 sends one multicast packet to node 1 and node 2. At that time, node 3 opens one connection as the target with node 1 and one connection as the target with node 2 for a total of two connections. Caution is required because the number of connections consumed is the same as for unicast connections even when multicast connections are set. O: Originator T: Target Node 1 O Multicast T Multicast Node 2 Node 3 O 264 T Section 10-1 Communications System 10-1-3 Network Transmission Delay Time In an EtherNet/IP network, the tag data link packets are sent once each packet interval (RPI), but several delays occur between the transmission of packets from each node and the arrival of the packets at the destination nodes. The following diagram shows the 4 major delay sources. Total network transmission delay = (1) Send processing delay + (2) Cable delays + (3) Switching hub delay + (4) Receive processing delay (1) Send processing delay EtherNet/IP Unit EtherNet/IP Unit (4) Receive processing delay Data Switching hub (2) Cable delay (3) Switching hub delay (2) Cable delay The lengths of these delays depend on many factors, such as the tag data link connection settings (number of connections and data sizes), number of nodes, the switching hub being used, and cable lengths. Each delay is described in detail below. 1. Send Processing Delay The send processing delay is the delay that occurs within the EtherNet/IP Unit or built-in EtherNet/IP port when data packets are sent once each packet interval. This delay varies with the RPI error shown in the following graph, so the send processing time is the maximum value for each RPI. Packet interval (RPI) 0.5 to 1,000 ms 1,000 ms to 10,000 ms RPI error (±) (%) 15 − (RPI (ms) ÷ 100) 5% of the RPI 16 14 RPI error (±)[%] 12 10 8 6 4 2 0 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 RPI [ms] 2. Cable Delay The cable delay is the time required for the data signal to pass through the cable and reach the destination. When an STP (shielded twisted-pair) cable of category 5, 5e, or higher is being used, the maximum cable delay is 545 ns/ 100 m. The cable delay represents a very small percentage of the total tag data link delay. 265 Section 10-1 Communications System 3. Switching Hub Delay The switching hub delay is the delay time between the arrival of the packet at the switching hub and the output of the packet from the hub’s transmission port. This delay depends on the total number of connections used for reception and data sizes used in the tag data links. In addition, this delay depends on the switching hub maker and model, but the delay can be approximated with the following table. (For a precise estimate, contact the switching hub manufacturer.) The following values are the delays when cascade connections are not being used. If cascade connections are used, more nodes can be connected, but the switching hub delays will increase. Words per connection 2 words 200 words 400 words 600 words 722 words 4. Receive Processing Delay Number of connections used for reception 16 32 64 128 256 0.2 ms 0.3 ms 0.5 ms 1.0 ms 1.9 ms 0.7 ms 1.3 ms 2.5 ms 5.0 ms 10.0 ms 1.2 ms 2.3 ms 4.6 ms 9.1 ms 18.2 ms 1.7 ms 3.3 ms 6.6 ms 13.2 ms 26.4 ms 2.0 ms 4.0 ms 7.9 ms 15.7 ms 31.4 ms The receive processing delay is the delay that occurs within the EtherNet/IP Unit or built-in EtherNet/IP port from the reception of the data packet at the Unit until the completion of reception processing in the Unit. This delay depends on the size of the connections used in the tag data links and the number of connections. In practice, the delay depends on the number of connections used in tag data links with less than 200 words. If the number of connections is “n”, the maximum delay can be calculated with the following equation. Maximum reception processing delay = 1 + (n × 0.043) ms The size of the connections may cause a delay when the data sizes are smaller and a large number of packets may be received in a fixed interval, because the data may wait for receive processing. Example Calculation of the Tag Data Link Delay This example shows how to calculate the tag data link delay when the following tag data link connection settings have been made. In this case, 17 EtherNet/IP Units or built-in EtherNet/IP ports are being used, and one Unit is receiving 200 words of data from each of the other Units at a packet interval (RPI) of 5 ms. Thus, 16 tag data link connections are used. The length of the cables between the Units is 50 m for all connections. Send processing delay = 5 ms × (15 − 5/100)% = 0.7475 ms Cable delay = 545 ns × 50 m/100 = 272.5 ns Switching hub delay = 0.7 ms Receive processing delay = 1 + (16 × 0.043) ms = 1.688 ms Tag data link delay 266 = 0.7475 ms + 0.0002725 ms + 0.7 ms + 1.688 ms ≈ 3.14 ms Section 10-1 Communications System PLC #1 PLC #2 PLC #3 PLC #17 5 ms #2 #3 200 words 5 ms 200 words 200 words × 16 #17 5 ms 200 words 267 Section 10-2 Adjusting the Communications Load 10-2 Adjusting the Communications Load In an Ethernet network using a switching hub, the network bandwidth is not shared by all of the nodes; independent transmission paths are established between individual nodes through the switching hub. A dedicated communications buffer is established in the switching hub for communications between the nodes and full-duplex communications (simultaneous transmission and reception) are performed asynchronously with other transmission paths. The communications load in other transmission paths does not affect communications, so packet collisions do not occur and stable, high-speed communications can be performed. The switching hub functions shown in the following table determine the performance of tag data links. Item Buffer capacity Multicast filtering QoS function Description This is the amount of data that can be buffered when packets accumulate at the switching hub. This function transfers multicast packets to specific nodes only. This function performs priority control on packet transfers. The following table shows the tag data link settings that can be made for individual EtherNet/IP Units as well as the setting ranges. Item Network bandwidth Allowed tag data link communications bandwidth Connection resources Contents Physical Ethernet baud rate Maximum number of tag data link packets that can be processed in 1 second (pps: packets per second) Number of connections that can be established Packet interval Refresh cycle for tag data (RPI: Requested Packet Interval) Settings 100 Mbps or 10 Mbps CJ2M: 3,000 pps max. Other CPU Units: 6,000 pps max. CJ2M: 32 max. Other CPU Units: 256 max. CJ2M: 1 to 1,000 ms Other CPU Units: 0.5 to 10,000 ms (in 0.5 ms units) When the tag data link settings exceed the capabilities of the switching hub being used, increase the RPI value. Particularly when using a switching hub that does not support multicast filtering, the settings must be made considering that multicast packets will be sent even to nodes without connection settings. In addition, if the required tag data link performance cannot be achieved with the switching hub’s capabilities, reevaluate the overall network configuration and correct it by taking steps such as selecting a different switching hub or splitting the network. The following sections show how to check the device bandwidth being used by the tag data links in the designed network, and how to set the appropriate values. Note 268 If the Network Configurator is used to set the connection type in the connection settings to a multicast connection, multicast packets will be used. If the connection type is set to a point-to-point connection, multicast packets will not be used. Section 10-2 Adjusting the Communications Load 10-2-1 Checking Bandwidth Usage for Tag Data Links The Network Configurator can display the bandwidth actually used for tag data links at each EtherNet/IP Unit, based on the connections set in the network configuration. The device bandwidth used by tag data links can be checked by clicking the Detail Button in the Usage of Device Bandwidth Area at the bottom of the Network Configuration Window. Item # Comment Usage of Capacity Mbit/s Usage of IP Multicast Addresses Description The IP address of the device. A description of the device. The comment is displayed below the device icon. The model number of the device is displayed by default. The percentage of the allowable communications bandwidth used for tag data links for the device is displayed. Bandwidth used ÷ Allowable tag data link bandwidth The values outside parentheses are for when multicast filtering is used. The values inside parentheses are for when multicast filtering is not used. The bandwidth used for communications by the device of the 100-Mbps network bandwidth is shown. The values outside parentheses are for when multicast filtering is used. The values inside parentheses are for when multicast filtering is not used. The number of multicast IP addresses actually used for communications by the device is shown. 269 Adjusting the Communications Load Section 10-2 Item Description Total usage of IP The number of multicast IP addresses used in the entire netmulticast addresses work is shown. This value is used to estimate the number of multicast filters for switching. Network Total of The total network bandwidth used for tag data link communicaMax. Mbit/s tions in the entire network is shown. Tag data links will not operate normally if 100 Mbps is exceeded for the network bandwidth. Checking the Usage of Capacity and Network Bandwidth for Tag Data Links The percentage of the allowable communications bandwidth for tag data links for each EtherNet/IP Unit is displayed as the Usage of Capacity and the bandwidth used for tag data link communications in the entire network is displayed as the Mbit/s. The usage of capacity and used network bandwidth that are displayed in parentheses are for a switching hub that does not use multicast filtering. In this case, multicast packets will be sent to even the nodes without connection settings, so the displayed values will include these packets as well. These values can be adjusted according to instructions in 10-2-4 Changing the RPI. Checking the Total Number of Multicast IP Addresses in the Network When using a switching hub that provides multicast filtering, there must be enough multicast filters for the network being used. The number of multicast IP address used in the entire network that is displayed by the Network Configurator as the Network Total of Max. Mbit/s is based on connection settings. Make sure that the number of multicast IP addresses used in the entire network does not exceed the number of multicast filters supported by the switching hub. If necessary, change to a switching hub with enough multicast filters, or adjust the usage of capacity and network bandwidth for tag data links (Mbit/ s) values given for a switching hub without multicast filtering (i.e., the values in parentheses). Adjust these values according to instructions in 10-2-4 Changing the RPI. Checking the Total Maximum Network Bandwidth The Network Configurator displays the total maximum bandwidth that can be used for the entire network as the Network Total of Max. Mbit/s. This value indicates the maximum bandwidth that can be used on the transmission paths when switching hubs are cascaded. If the value exceeds the bandwidth of a cascade connection in the actual network, the maximum bandwidth for part of the communications path may be exceeded, depending on how the network is wired. If this occurs, either calculate the bandwidth usage for each communications path and be sure that the maximum bandwidth is not exceeded for any cascade connection, or adjust the bandwidth for all cascade connections so that the total maximum network bandwidth is not exceeded. Adjust the bandwidth according to instructions in 10-2-4 Changing the RPI. 10-2-2 Tag Data Link Bandwidth Usage and RPI The usage of capacity can be adjusted using the RPI setting. If the RPI is made shorter, the usage of capacity will increase. If the RPI is made longer, the usage of capacity will decrease. The RPI can be set in any one of the following ways. • Setting the same interval for all connections • Setting a particular device’s connection • Setting a particular connection When the same RPI is set for all connections, the usage of capacity will basically increase proportionally as the RPI is made shorter. 270 Adjusting the Communications Load Section 10-2 Example: If the RPI is set to 50 ms for all connections and the usage of capacity is 40%, the usage of capacity may increase to 80% when the RPI is reduced to 25 ms for all connections. Note Performing message communications or other network operations from the Network Configurator (such as monitoring or other operations that place a load on the network) or from the user application when the tag data link bandwidth usage of capacity is between 80% and 100% can create an excessive load on the network and result in timeouts. If timeouts occur, increase one or all of the RPI settings or reduce the usage of capacity. 10-2-3 Adjusting Device Bandwidth Usage Switching Hubs without Multicast Filtering (100Mbps Hubs) • Is the network bandwidth without multicast filtering usage under 100 Mbps for each node? (This appears as “Mbit/s” in the dialog box shown on page 269.) → If any node exceeds 100 Mbps, change the connections settings, such as the RPI. • Is the usage of capacity without multicast filtering under 100% for each node? (This appears as “Usage of Capacity” in the dialog box shown on page 269.) → If any node exceeds 100%, change the connections settings, such as the RPI. • Is the total network bandwidth usage under 100 Mbps? (This appears as “Network Total of Max. Mbit/s” in the dialog box shown on page 269.) → If the total bandwidth usage exceeds 100 Mbps, the bandwidth of part of the transmission path (e.g., a switching hub or media converter) had been exceeded as the result of how the network was wired (e.g., switch hub or cascade connection), causing a tag data link to operate abnormally. Check the bandwidth of the transmission path for all cascade connections. If the bandwidth is exceeded, rewire the network or increase the bandwidth between switching hubs (e.g., to 1 Gbps). If these countermeasures are not possible, change the connection settings, e.g., the RPI settings, and adjust the bandwidth for all cascade connections until the total network bandwidth is not exceeded. Switching Hubs with Multicast Filtering (100Mbps Hubs) • Is the network bandwidth usage under 100 Mbps for each node? → If any node exceeds 100 Mbps, change the connections settings, such as the RPI. • Is the usage of capacity under 100% for each node? → If any node exceeds 100%, change the connections settings, such as the RPI. • Is the total network bandwidth usage under 100 Mbps? (This appears as “Network Total of Max. Mbit/s” in the dialog box shown on page 269.) → If the total bandwidth usage exceeds 100 Mbps, the bandwidth of part of the transmission path (e.g., a switching hub or media converter) had been exceeded as the result of how the network was wired (e.g., switch hub or cascade connection), causing a tag data link to operate abnormally. Check the bandwidth of the transmission path for all cascade connections. If the bandwidth is exceeded, rewire the network or increase the bandwidth between switching hubs (e.g., to 1 Gbps). If these countermeasures are not possible, change the connection settings, e.g., the RPI settings, and adjust the bandwidth for all cascade connections until the total network bandwidth is not exceeded. 271 Adjusting the Communications Load Section 10-2 • Is the network bandwidth usage without multicast filtering under 100 Mbps for each node or the usage of capacity without multicast filtering under 100% for each node? (These appear as “Mbit/s” and “Usage of Capacity” in the dialog box shown on page 269.) → If the total bandwidth usage exceeds 100 Mbps, the bandwidth of part of the transmission path (e.g., a switching hub or media converter) had been exceeded as the result of how the network was wired (e.g., switch hub or cascade connection), causing a tag data link to operate abnormally. Check the bandwidth of the transmission path for all cascade connections. If the bandwidth is exceeded, rewire the network or increase the bandwidth between switching hubs (e.g., to 1 Gbps). If these countermeasures are not possible, change the connection settings, e.g., the RPI settings, and adjust the bandwidth for all cascade connections until the total network bandwidth is not exceeded. 10-2-4 Changing the RPI You can check the usage of capacity offline without multicast filtering against the tag data link's allowable bandwidth by following the procedures in 10-2-1 Checking Bandwidth Usage for Tag Data Links. The usage of capacity without multicast filtering can be adjusted against the tag data link's allowable bandwidth by changing the packet interval (RPI). If the required communications performance cannot be achieved by changing the settings, reevaluate the network starting with the network configuration. 1,2,3... 1. Make the required settings in the Network Configurator’s Network Configuration Window. 2. Click the Detail Button in the Usage of Device Bandwidth Area at the bottom of the Network Configuration Window. The Usage of Device Bandwidth Dialog Box will be displayed. 272 Adjusting the Communications Load Section 10-2 The Usage of Capacity column will show the percentage of the allowed tag data link bandwidth being used, and the Mbit/s column will show the network bandwidth being used. 3. The usage of capacity can be adjusted by changing the associated devices’ RPI settings. The RPI settings can be changed with the following three methods. Method 1: Same Packet Interval Set for all Connections The usage of capacity can be adjusted by changing the RPI for all of the connections at the same time. a. Click the Set Packet Interval (RPI) Button at the bottom of the Usage of Device Bandwidth Dialog Box. b. The Set Packet Interval (RPI) Dialog Box will be displayed. Input a new RPI value, and click the OK Button. 273 Adjusting the Communications Load Section 10-2 Method 2: Changing a Particular Device’s RPI Setting The usage of capacity can be adjusted for only a particular device by changing the packet intervals (RPI) for all of the device’s connections together. In this case, the usage of capacity will also change for the devices that are the target devices of the connection which was adjusted. a. Click the Set Packet Interval (RPI) Button at the bottom of the Usage of Device Bandwidth Dialog Box. b. The Set Packet Interval (RPI) Dialog Box will be displayed. In the Target Device Area, deselect the target devices that are not being adjusted by removing the check marks. c. Input a new RPI value, and click the OK Button. Method 3: Changing a Particular Connection’s RPI Setting The usage of capacity can be adjusted by individually changing the packet intervals (RPI) setting for a particular connection. In this case, the usage of capacity will also change for the device that is the target device of the connection which was adjusted. 274 Adjusting the Communications Load Section 10-2 a. Click the Close Button at the bottom of the Usage of Device Bandwidth Dialog Box. b. Double-click the device that is set as the originator of the desired connection. The Edit Device Parameters Dialog Box will be displayed. c. In the Register Device List, select the connection for which you want to change the RPI, and click the Edit Button. d. The device’s Edit Connections Dialog Box will be displayed. Input a new RPI value, and click the OK Button. 275 Adjusting the Communications Load Section 10-2 4. If the usage of capacity cannot be adjusted to the desired level when the setting described above has been performed, reconsider the network configuration considering the following points. Refer to 10-2-3 Adjusting Device Bandwidth Usage. • Reduce the number of nodes and number of connections. • Split the network. 5. Check the bandwidth usage again. If the connection settings have been changed, click the Detail Button in the Usage of Device Bandwidth Area at the bottom of the Network Configuration Window and check bandwidth usage according to the instructions in 10-2-1 Checking Bandwidth Usage for Tag Data Links. It is particularly important to check the usage of capacity when an individual connection’s RPI setting was changed without using the Set Packet Interval (RPI) Button at the bottom of the Usage of Device Bandwidth Dialog Box. 6. Run user tests to verify that there are no problems with the new settings. 10-2-5 RPI Setting Examples The following examples explain how to calculate the packet intervals (RPI) in the following network configuration. 276 Section 10-2 Adjusting the Communications Load Example Conditions Connections In this example, there are 10 CS1W-EIP21 Units and 10 CJ1W-EIP21 Units for a total of 20 devices connected in the network. Each device has one 100word tag for transmission and nineteen 100-word tags for reception, so that the Units exchange data mutually. By default, the packet intervals (RPI) are set to 10 ms for all of the connections. The devices’ IP addresses range from 192.168.250.1 to 192.168.250.20. IP address: 192.168.250.1 CS1W-EIP21 100 words 100 words 100 words 192.168.250.2 CS1W-EIP21 192.168.250.3 192.168.250.20 CS1W-EIP21 CJ1W-EIP21 Transmit Transmit Tag data link area with 100 words × 20 Units Transmit 100 words Transmit 10 CS1W-EIP21 Units + 10 CJ1W-EIP21 Units = 20 Units total The RPI is 10 ms (ethernet default) for all connections. Checking the Device Bandwidth Usage When the Detail Button is clicked in the Usage of Device Bandwidth Area, it is apparent that the percentage of the allowed tag data link bandwidth being used by each device’s tag data link (Usage of Capacity) is 39.67%, as shown in the following dialog box. 277 Adjusting the Communications Load Changing the Settings Section 10-2 Method 1: Same Packet Interval Setting for All Connections The percentage of the allowed tag data link bandwidth being used (Usage of Capacity) was 39.67% with the RPI set to 10.0 ms for all of the connections, so the RPI will be set to 5.0 ms, with a target of 80% or less of the allowable bandwidth. Click the Set Packet Interval (RPI) Button at the bottom of the Usage of Device Bandwidth Dialog Box. The Set Packet Interval (RPI) Dialog Box will be displayed. Input 5.0 ms as the new RPI value, and click the OK Button. 278 Adjusting the Communications Load Section 10-2 If the packet interval for all connections has been set to the same setting, the dialog box will show that the usage of capacity for the tag data link's allowable communications bandwidth is 73.00% and the fastest set value is 5.0 ms. Method 2: Changing the Packet Interval (RPI) of Only Specific Devices In this example, we want faster tag data links for devices 192.168.250.1 and 192.168.250.10 only. Click the Set Packet Interval (RPI) Button at the bottom of the Usage of Device Bandwidth Dialog Box to display the Set Packet Interval (RPI) Dialog Box. In the Target Device Area, deselect all devices other than 192.168.250.1 and 192.168.250.10 by removing the corresponding check marks. Input 5.0 ms as the new RPI value, and click the OK Button. The percentage of the allowed tag data link bandwidth being used (Usage of Capacity) increases to 74.67% for devices 192.168.250.1 and 192.168.250.10, which indicates that the RPI is set to a higher speed for these devices’ connections. 279 Adjusting the Communications Load Section 10-2 The Usage of Capacity values also indicate that the Usage of Capacity has increased (from 39.67% to 43.00%) for all of the other devices, which connect with devices 192.168.250.1 and 192.168.250.10. In this case, if there is no multicast filter, the value becomes 106.33%. If there is no multicast filter for a switching hub, communications errors may occur depending on the communications load of the EtherNet/IP Unit or built-in EtherNet/IP Unit port. 280 Adjusting the Communications Load Section 10-2 Method 3: Changing the Packet Interval (RPI) of Only Specific Connections In this example, we want a faster tag data links for just a particular connection of device 192.168.250.1. Double-click device 192.168.250.1 in the Network Configuration Window. Information about the connection with device 192.168.250.20 is registered in the Register Device List. Double-click this connection to edit the settings. 281 Adjusting the Communications Load Section 10-2 In the Edit Connection Dialog Box, input 1.0 ms as the new RPI value, and click the OK Button. The tag data link bandwidth being used by device 192.168.250.1 (Usage of Capacity) increases to 54.67%, which indicates that a RPI is set to a higher speed for this device. In this case, the tag data link bandwidth being used by device 192.168.250.20 (Usage of Capacity) also increases (from 39.67% to 56.33%). 282 Section 10-3 I/O Response Time in Tag Data Links 10-3 I/O Response Time in Tag Data Links Note This section describes the data processing time for an EtherNet/IP Unit or a built-in EtherNet/IP port on a CJ2H-CPU6@-EIP CPU Unit. The data processing time for a built-in EtherNet/IP port on the CJ2M-CPU3@ CPU Unit is different. For details, refer to 10-4 Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports. 10-3-1 Timing of Data Transmissions The following diagram shows the timing of tag data link transmissions between the EtherNet/IP Unit or CJ2H built-in port and the CPU Unit. The data transmission is processed during the I/O refresh period. Send data is processed with transmission at regular intervals, and received data is processed together with the send data when new data has been received from other nodes. The following diagram shows the timing of data transmissions. Data received EtherNet/IP Unit processing EtherNet/IP Unit data processing time (Refer to 10-3-2.) CPU Unit processing Basic processes Program execution I/O refreshing Peripheral servicing Basic processes Data exchange processing CPU Unit’s cycle time If there is an interrupt for data transmission processing, the CPU Unit’s cycle time is extended by that interrupt processing time. Refer to 10-3-2 EtherNet/IP Unit or CJ2H Built-in Port Data Processing Time for details. 10-3-2 EtherNet/IP Unit or CJ2H Built-in Port Data Processing Time The following formula approximates the time required for the EtherNet/IP Unit or CJ2H built-in port to process data transmissions with the CPU Unit (i.e., the data processing time). Approximation of the data processing time for an EtherNet/IP Unit or CJ2H Built-in Port (0.0008 × Number of data transmission words) + 1.0 ms 283 Section 10-3 I/O Response Time in Tag Data Links The maximum number of tag data link words that can be transferred by one EtherNet/IP Unit or CJ2H built-in port is 184,832 words. However, if the number of tag data link words exceeds the number of words that can be exchanged with the CPU Unit at one time, the data will be divided and transferred in multiple data exchanges. The following table shows the number of words that each CPU Unit can exchange at one time. CPU Unit CS/CJ Series SYSMAC CJ2 Series Number of words per data transmission Output/Send: About 7,405 words max. (If there are more words, the data will be divided.) Input/Receive: About 7,405 words max. (If there are more words, the data will be divided.) Note The total amount of send data and receive data that can be exchanged at one time is about 14,810 words maximum. Output/send: About 6,432 words max. (If there are more words, the data will be separated into multiple transmissions.) Input/receive: About 6,432 words max. (If there are more words, the data will be separated into multiple transmissions.) Note The total amount of send data and receive data that can be transferred at one time is about 12,864 words maximum. The number of data exchanges may double as given in the following table according to the relation with the CPU Unit’s cycle time and the data processing time of the EtherNet/IP Unit or CJ2H built-in port. Condition CPU Unit’s cycle time > EtherNet/IP Unit or CJ2H built-in port data processing time CPU Unit’s cycle time ≤ EtherNet/IP Unit or CJ2H built-in port data processing time Note Number of data transmissions Number of data transmissions based on the data size Number of data transmissions × 2 based on the data size (1) With CS/CJ-series PLCs, consecutive data area words specified in the tag set will be transferred together if possible. Up to 19 send data blocks can be processed in one data transmission; up to 20 receive data blocks can be processed in one data transmission. If there are more blocks, the data will be divided and transferred in separate data transmissions. (2) The preceding data processing time approximation is the standard formula when a higher priority processing event does not occur in peripheral servicing. For example, if an instruction such as SEND, RECV, or FAL is executed, the instruction’s processing will have higher priority, so the data processing time may be longer. 10-3-3 Effect on the CPU Unit’s Cycle Time The CPU Unit’s cycle time is affected when the EtherNet/IP Unit or CJ2H builtin port refreshes tag data and status data with the CPU Unit. This effect depends on the size of the tag data links, and can be approximated with the values in the following table. When there are multiple EtherNet/IP Units or CJ2H built-in ports, the effect is cumulative. 284 Section 10-3 I/O Response Time in Tag Data Links CPU Unit CJ2H Effect of EtherNet/IP Unit or CJ2H built-in port only CPU Rack: 0.1 ms Expansion Rack: 0.13 ms CJ2M CPU Rack: 0.14 ms Expansion Rack: 0.16 ms CJ1 CJ1M CJ1-H CS1 CS1-H Long-distance Rack 0.25 ms 0.17 ms 0.1 ms 0.2 ms 0.1 ms 0.2 ms × Coefficient 2 Note Total effect when tag data links are being used CPU Rack: Value from left column + 0.1 ms + No. of words transferred × 0.33 µs (See note 2.) Expansion Rack: Value from left column + 0.1 ms + No. of words transferred × 0.45 µs CPU Rack: Value from left column + 0.02 ms + No. of words transferred × 0.78 µs Expansion Rack: Value from left column + 0.02 ms + No. of words transferred × 0.92 µs 0.25 ms + 1.5 ms + (Number of words × 1 µs) 0.17 ms + 0.1 ms + (Number of words × 0.7 µs) 0.1 ms + 0.1 ms + (Number of words × 0.7 µs) 0.2 ms + 1.5 ms + (Number of words × 1 µs) 0.1 ms + 0.1 ms + (Number of words × 0.7 µs) (0.2 ms × Coefficient 2) + 1.5 ms + (Number of words × 1 µs × Coefficient 3) (1) When one of the listed CPU Bus Units is mounted in a CS-series Longdistance Rack, the I/O refreshing time is extended by the distance to the Rack in which the Unit is mounted, regardless of the model of the CPU Unit. The following graph shows the coefficients (2 and 3) required to calculate this effect. Coefficient Distance to Long-distance Rack (m) (2) The additional time for CJ2H CPU Units with unit version 1.1 or later will be as follows if high-speed interrupts are enabled. 0.1 ms + Number of words transferred × 0.87 µs 10-3-4 Tag Data Link I/O Response Time Calculation Example When using the tag data link functions of the EtherNet/IP Unit or CJ2H built-in port, there is a time lag between the point when the data link area’s data changes due to an input at a node and the point when the change is output at another node’s data link area. This time lag is called the tag data link I/O response time. This example shows how to calculate the minimum and maximum I/O response times in the following configuration for connection 1 opened between node 1 and node 2. 285 Section 10-3 I/O Response Time in Tag Data Links EtherNet/IP PLC#1 PLC#2 Node 3 Node 2 Node 1 Input switch (external input device) Input PLC#3 Output relay (external output device) W000.01 W000.01 Output Tag Data Link Table PLC#2 PLC#1 Connection 1 PLC#3 RPI = 10 ms W000 W000 Outputs RPI = 10 ms 256 words x 16 connections Total: 4,096 words Inputs Inputs 722 words x 16 connections Total: 11,552 words RPI = 100 ms Outputs The following table gives the items required to find the I/O response time and values used in calculations for this system configuration. Item Value used in calculation example PLC#1 PLC#2 External I/O device delay time Input device delay: Output device delay: 1.5 ms 2.0 ms Cable length 50 m CPU Unit model CJ2H CPU Unit CJ2H CPU Unit RPI 10 msec --Number of receive connections 0 32 CPU Unit cycle time 10 msec 15 msec Total number tag Number of send 11,552 None data link words words Number of None 15,648 receive words Maximum Tag Data Link I/O Response Time You can find the maximum I/O response time from the total of (1) to (6) in the following figure. 286 Section 10-3 I/O Response Time in Tag Data Links : I/O processing : Data exchange Tag data link I/O response time Input device (4) Network transmission delay time (1) Input ON (2) Send data (6) Output ON processing response (5) Receive data (3) RPI response time time time processing time Input PLC #1 processing Send data processing time Cycle time x 2 Tag data link refresh cycle Receive data processing time Calculation PLC #2 processing Output device PLC #2 Transmission path PLC #1 Calculation Cycle time x 4 Output (1) Node 1 (PLC #1) Input ON Response Time This is the delay time for the external input device from when the input occurs until the switch actually turns ON and the time until the input data is stored in the memory area of the CPU Unit for PLC #1. In this system, the input switch delay time is 1.5 ms. Also, one CPU cycle time is required until the data is stored in the memory area of the CPU Unit. Therefore, the input ON response time is 1.5 ms + 10 ms, or 11.5 ms. (2) Node 1 (PLC #1) Send Data Processing Time This is the time until memory data in the CPU Unit is transferred to the EtherNet/IP Unit. If the amount of data that can be processed in one data transmission with the CPU Unit is exceeded, data transmission will be performed over multiple cycles of the CPU Unit, and so time is calculated for the number of transmissions times the CPU Unit cycle times. The following table gives the send data processing times and breakdown for node 1 (PLC #1) in this system configuration. Refer to 10-3-2 EtherNet/IP Unit or CJ2H Built-in Port Data Processing Time for details on the calculation formula for each item. Item A CPU Unit cycle time for PLC #1 B Number of transmissions based on the data size C EtherNet/IP Unit data processing time Calculation formula Time 10 m sec Number of data transmission words (11,552 2 words) ÷ 6,432 words (using a CJ2 CPU Unit) 0.0008 × 6,432 + 1.0 (Maximum number of 6.15 m sec transmission words per cycle) 287 Section 10-3 I/O Response Time in Tag Data Links Item Calculation formula Time D Number of data trans- A 10 m sec > C 6.15 m sec 2 missions To meet the conditions, the number of transmissions is the same as B. Total: CPU Unit cycle time of A PLC #1 × D Num- 20 m sec ber of data transmissions (2) Send data processing time (3) Packet Interval (RPI) This is the communications refresh cycle set for each connection using the Network Configurator. In this system, it is the refresh cycle for connection 1 (10 ms), which includes W000.01. (4) Network Transmission Delay Time This is the total of the send processing delay, receive processing delay, switching hub delay, and cable delay. Refer to 10-1-3 Network Transmission Delay Time for details on the calculation formula for network delay time. In this system, it is 5.2 ms. Delay item A Send processing delay Calculation formula 10 m sec × (15-10 msec/100)% Max. delay time 1.49 msec B Cable delay C Switching hub delay D Receive processing delay Total: (4) Network Transmission Delay Time 545 nsec + 50 m/100 2 msec + Approx. 0.7 msec 1 + (0 connection × 0.043) 272.5 nsec 2.7 msec 1.0 msec A+B+C+D 5.2 msec (5) Node 2 (PLC #2) Receive Data Processing Time This is the time to transfer the data received by the EtherNet/IP Unit or CJ2H built-in port to the memory area in the CPU Unit. Receive data is transferred in the order that it is received, but if the amount of data that can be processed in one transmission is exceeded, multiple cycles are required to transfer the data. Also, data transmission is performed only once per CPU Unit cycle. Therefore, if data transfer has ended in the cycle in which data is received, the start of transmission for received data will be delayed by one CPU Unit cycle time. In this system configuration, data transfer is performed a maximum of three times based on the data size of node 2 (PLC #2) to transfer received data for node 1 (PLC #1) and node address 3 (PLC #3). Also, the cycle time of PLC #2 is 15 ms, the effect on the CPU Unit cycle time is 2.3 ms, and the data processing time for the EtherNet/IP Unit or CJ2H built-in port is 6.15 ms. The number of data transmissions is thus calculated as 3. In addition, the number of data transmissions is calculated as a maximum of 4 (3 + 1) because it is necessary to consider a delay of one CPU Unit cycle time in transferring received data. Item A CPU Unit cycle time B Number of transmissions based on the data size C EtherNet/IP Unit data processing time 288 Calculation formula Time --15 msec Number of data transmission words (15,648 3 words) ÷ 6,432 words (using a CJ2 CPU Unit) 0.0008 × 6,432 + 1.0 (Maximum number of 6.15 msec transmission words per cycle) Section 10-3 I/O Response Time in Tag Data Links Item Calculation formula Time D Number of data transmissions A 10 m sec > C 6.15 m sec 4 To meet the condition to enable processing in one data transmission, the number of transmissions is the same as B plus 1. (Delay of one CPU Unit cycle time) A Cycle time × D Number of data trans60 msec Total: (5) Receive data process- missions ing time (6) Output ON response time This is the delay time for the external output device from when the output bit turns ON in the memory of the CPU Unit until the output is actually performed. In this system configuration, the delay time for an output relay is 2.0 ms. Also, one CPU cycle time is required until the data is stored in the memory area of the CPU Unit. Item A CPU Unit cycle time of PLC #2 B Output relay delay time Total: (6) Node 2 (PLC #2) output ON response time Time 15 msec 2.0 msec 17.0 msec The maximum tag data link I/O response time for this system configuration found from the total of (1) to (6) is 124 ms. Note (1) Node 1 (PLC #1) input ON response time (2) Node 1 (PLC #1) send data processing time (3) Packet Interval (RPI) 11.5 msec 20 msec 10 msec (4) Network Transmission Delay Time (5) Node 2 (PLC #2) receive data processing time (6) Output ON response time Maximum I/O response performance (total of (1) to (6)) 5.5 msec 60 msec 17 msec 124 msec The I/O response time may be longer due to noise, or other events. 289 Section 10-3 I/O Response Time in Tag Data Links Minimum Tag Data Link I/O Response Time : I/O processing : Data exchange Tag data link I/O response time (2) Network transmission delay time Input device (1) Input ON response time (3) Output ON response time Input Calculation Transmission path PLC #1 PLC #1 processing PLC #2 Tag data link refresh cycle Output device Calculation PLC #2 processing Output The minimum tag data link I/O response time, which occurs when there are no processing delays, is calculated as follows. (1) Node 1 (PLC #1) input ON response time Input switch delay time CPU Unit cycle time of PLC #1 (2) Transmission time (722 send data words) (3) Node 2 CPU Unit cycle time of PLC #2 (PLC #1) output ON response time Output relay delay time 1.5 ms 10.0 ms 0.121 msec 15.0 ms 2.0 ms Total (tag data link I/O response time) 28.6 ms When the baud rate is 100 Mbps, the transmission time can be calculated with the following equation. If a network delay does not occur, just this transmission time is added. Transmission time = (Number of send data words × 2 + 74) × 8 × 0.00001 ms Note 290 The I/O response time may be longer due to noise, or other events. Section 10-4 Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports 10-4 Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports 10-4-1 Overview The built-in EtherNet/IP port on a CJ2M CPU Unit (CJ2M-CPU3@) supports tag data links for up to 32 connections, with a data size of 20 words per connection. These specifications are different from those of CJ2H built-in ports and EtherNet/IP Units. The maximum number of words that can be transmitted for tag data links is 640 words. This 640 words is the amount of data that is processed for one data transmissions between the CPU Unit and the CJ2M built-in port. The tag data link specifications of CJ2M built-in ports are provided in the following table. If these specifications are insufficient for the required system configuration, use a CJ2H built-in port on a CJ2H-CPU6@-EIP CPU Unit or a CJ1W-EIP21 EtherNet/IP Unit. Tag Data Link Specifications for CJ2M Built-in EtherNet/IP Ports CJ2M built-in port (CJ2M-CPU3@) Number of connections Packet interval (RPI) Allowed communications bandwidth per Unit (PPS) Number of tags that can be registered Tag types Number of registrable tag sets Number of tags per connection Maximum size of 1 tag set Maximum data size per connection Maximum link data size per node Maximum number of tags that can be refreshed per CPU Unit cycle Reference: CJ2H built-in port (CJ2H-CPU6@-EIP) 32 1 to 10,000 ms (in 0.5-ms units) 3,000 pps 256 0.5 to 10,000 ms (in 0.5-ms units) 6,000 pps 32 256 CIO Area, DM Area, EM Area, Holding Area, Work Area, and network symbols 32 256 8 (7 tags when the tag set contains the PLC status) 20 words (The PLC status uses 1 word when the tag set contains the PLC status.) 20 words 722 words (The PLC status uses 1 word when the tag set contains the PLC status.) 722 words 640 words 184,832 words Output/Transmission (CPU → EtherNet/IP): 32 Input/Reception (EtherNet/IP → CPU): 32 Output/Transmission (CPU → EtherNet/IP): 256 Input/Reception (EtherNet/IP → CPU): 256 Data that can be refreshed per Output/Transmission (CPU → EtherNet/IP): CPU Unit cycle 640 words Input/Reception (EtherNet/IP → CPU): 640 words Output/Transmission (CPU → EtherNet/IP): 6,432 words Input/Reception (EtherNet/IP → CPU): 6,432 words Note The total for output/transmission and Note The total for output/transmission and input/reception is 640 words. input/reception is 12,864 words. Tag Data Link System Configuration Example This example configuration is based on the maximum specifications for CJ2M built-in ports where all nodes send and receive data to the other nodes. In this case, the maximum send area for each node in a 17-node configuration is 20 words. For example, node 1 establishes 16 send connections and 16 receive connections to the other 16 nodes, for a total of 32 connections. The maximum data size per connection is 20 words, so the send area in node 1 is 20 words and the receive areas in node 1 are each 20 words. 291 Section 10-4 Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports If the same RPI is set for all connections, 12 ms is the lowest setting that can be used. ■ Calculation Example (1,000 ÷ 12 [ms] (RPI) + 1,000 ÷ 100 [ms] (heartbeat transmission period)) × 32 (connections) = 2,987 pps < 3,000 pps Send connections = 16 (20 words × 16 = 320 words) Node 3 Node 16 Node 17 Receive 20 words Receive 20 words Receive 20 words Receive 20 words Receive 20 words Receive 20 words Send 20 words Receive 20 words Receive 20 words Receive 20 words Receive 20 words Send 20 words Receive 20 words Receive 20 words Receive 20 words Receive 20 words Send 20 words Node 2 Node 1 Receive 20 words Send 20 words Receive 20 words Receive 20 words Receive 20 words Receive 20 words *All nodes use CJ2M built-in ports. Send 20 words Receive 20 words Receive connections = 16 (20 words × 16 = 320 words) 10-4-2 Tag Data Link I/O Response Time With tag data links, if the data in the data link area for a node changes due to an input to that node, a certain amount of time is required for the data in data link area at another node to be updated and output. The I/O response time for tag data links can be calculated for a CJ2M built-in port in the same was as it can for a CJ2H built-in port (refer to 10-2-4 Changing the RPI). Here, formulas to calculate guideline I/O response times are provided. (Tag data link delays are ignored because the data link size handled by the built-in CJ2M port is small.) Maximum I/O Response Time Input ON delay + Cycle time of sending PLC × 2 + RPI + Cycle time of receiving PLC × 2 + Output ON delay Minimum I/O Response Time Input ON delay + Cycle time of sending PLC + Cycle time of receiving PLC + Output ON delay PLC #1 Node 1 Cycle time: 5 ms Connection RPI: 12 ms 20 words PLC #2 Node 2 20 words Cycle time: 10 ms Output ON response time: 2.0 ms Input ON response time: 1.5 ms All connections EtherNet/IP Input Output Data link 292 Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports Section 10-4 For example, the maximum and minimum I/O response times would be as follows for the above system. Maximum response time: 1.5 ms + 5 ms × 2 + 12 ms + 10 ms × 2 + 2.0 ms = 45.5 ms Minimum response time: 1.5 ms + 5 ms + 10 ms + 2.0 ms = 18.5 ms Note If the message service is used at the same time on the CJ2M built-in port, the tag data link I/O response time will change. 293 Section 10-5 Message Service Transmission Delay 10-5 Message Service Transmission Delay This section explains the maximum transmission delay that can occur between the execution of a SEND(090), RECV(098), or CMND(490) instruction in the ladder program until completion of the instruction. This delay does not include the time required for the tag data link or the execution time of the ladder program itself. 10-5-1 Maximum Transmission Delays (Excluding Delays in the Network) Use the following equation to calculate the maximum transmission delay that can occur between the execution of a SEND(090) or RECV(098) instruction in the ladder program until completion of the instruction. SEND(090) Instruction Execution of SEND(090) in user program CPU Bus Unit service cycle (Local node) CPU Bus Unit service processing time (Local node) Send processing Transmission delay Receive processing CPU Bus Unit service cycle (Remote node) CPU Bus Unit service processing time (Remote node) CPU data set processing Maximum transmission delay Maximum transmission delay = CPU Bus Unit service cycle (local node) + CPU Bus Unit service processing time (local node) + Send processing + Transmission delay + Receive processing + CPU Bus Unit service cycle (remote node) + CPU Bus Unit service processing time (remote node) CPU Bus Unit Service Cycle (Local Node) The following table shows the service cycle, which depends on the CPU Unit’s CPU processing mode setting. CPU execution mode Processing time details Normal Mode (See note.) One CPU Unit cycle time Priority peripheral servicing Parallel processing with synchronous memory access Parallel processing with asyn- 0.2 ms + peripheral servicing time (1 ms max. for chronous memory access peripheral servicing of each Special I/O Unit, CPU Bus Unit, peripheral port, RS-232C port, and Inner Board) Note 294 CJ2 CPU Units support only Normal Mode. Section 10-5 Message Service Transmission Delay For details, refer to the CPU Unit’s Operation Manual. CPU Bus Unit Service Processing Time (Local Node) The following table shows the CPU Bus Unit service processing time, which depends on the CPU Unit’s CPU processing mode setting. CPU execution mode Normal Mode (See note.) Processing time details Set peripheral servicing time Default: 4% of CPU Unit cycle time (10% for CJ2 CPU Units) Priority peripheral servicing Parallel processing with synchronous memory access Parallel processing with asyn- 1 ms max. chronous memory access Note CJ2 CPU Units support only Normal Mode. For details, refer to the CPU Unit’s Operation Manual. Send Processing (Number of words being transferred × 0.002) + 0.550 ms Transmission Delay The transmission delay time depends on the baud rate set for the EtherNet/IP Unit or built-in EtherNet/IP port, as shown in the following table. (There may be additional delays due to the other devices in the network, such as switching hubs.) Baud rate 100Base-TX 10Base-T Delay time (Number of words being transferred × 0.0013) + 0.0118 ms (Number of words being transferred × 0.0019) + 0.0157 ms Receive Processing (Number of words being transferred × 0.003) + 0.704 ms CPU Bus Unit Service Cycle (Remote Node) The following table shows the CPU Bus Unit service cycle, which depends on the CPU Unit’s CPU processing mode setting. CPU execution mode Normal Mode (See note.) Priority peripheral servicing Parallel processing with synchronous memory access Processing time details One CPU Unit cycle time EtherNet/IP Unit or Time slice instruction execution built-in EtherNet/IP time port is given priority. EtherNet/IP Unit or One CPU Unit cycle time built-in EtherNet/IP port is not given priority. One CPU Unit cycle time Parallel processing with asyn- 0.2 ms + peripheral servicing time (1 ms max. for chronous memory access peripheral servicing of each Special I/O Unit, CPU Bus Unit, peripheral port, RS-232C port, and Inner Board) Note CJ2 CPU Units support only Normal Mode. For details, refer to the CPU Unit’s Operation Manual. 295 Section 10-5 Message Service Transmission Delay CPU Bus Unit Service Processing Time (Remote Node) The following table shows the CPU Bus Unit service processing time, which depends on the CPU Unit’s CPU processing mode setting. CPU execution mode Normal Mode (See note.) Priority peripheral servicing Processing time details Set peripheral servicing time Default: 4% of CPU Unit cycle time (10% for CJ2 CPU Units) EtherNet/IP Unit or Time slice peripheral servicing built-in EtherNet/IP execution time port is given priority. EtherNet/IP Unit or Set peripheral servicing time built-in EtherNet/IP (Default: 4% of CPU Unit cycle port is not given time) priority. Parallel processing with synSet peripheral servicing time chronous memory access Default: 4% of CPU Unit cycle time (10% for CJ2 CPU Units) Parallel processing with asyn- 1 ms max. chronous memory access Note CJ2 CPU Units support only Normal Mode. For details, refer to the CPU Unit’s Operation Manual. Note Example Calculation Depending on the actual operating environment, the transmission time may be longer than the one calculated with the equations given here. The following factors can cause longer transmission times: other traffic on the network, window sizes of network nodes, other traffic at the EtherNet/IP Unit or built-in EtherNet/IP port itself (e.g., simultaneous tag data link communications), and the system configuration. In this example, SEND(090) is used to send 256 words of data between two PLCs. The maximum transmission delay is calculated based on the following operating conditions. • Local node’s CPU cycle time: 10 ms • Local node’s CPU execution mode: Normal • Local node’s CPU peripheral servicing time: Default (4%) • Remote node’s CPU cycle time: 5 ms • Remote node’s CPU execution mode: Normal • Remote node’s CPU peripheral servicing time: Default (4%) • Baud rate: 100Base-TX Item CPU Bus Unit service cycle (local node) CPU Bus Unit service processing time (local node) Send processing Transmission delay Receive processing CPU Bus Unit service cycle (remote node) CPU Bus Unit service processing time (remote node) Maximum transmission delay 296 Calculated value 10 ms 0.4 ms (256 × 0.002) + 0.550 = 1.062 ≅ 1.1 ms (256 × 0.0013) + 0.0118 = 0.3446 ≅ 0.3 ms (256 × 0.003) + 0.704 = 1.472 ≅ 1.5 ms 5 ms 0.2 ms 10 + 0.4 + 1.1 + 0.3 + 1.5 + 5 + 0.2 = 18.5 ms Section 10-5 Message Service Transmission Delay RECV(098) Instruction Execution of RECV(099) in user program CPU Bus Unit service cycle (Local node, 1) CPU Bus Unit service cycle (Local node, 2) CPU Bus Unit service processing time (Local node, 2) CPU Bus Unit service processing time (Local node, 1) Send processing (Command) Transmission delay (Response) Transmission delay (Command) CPU data set processing Transmission delay (Response) Receive processing (Command) Send processing (Response) CPU Bus Unit service processing time (Remote node) CPU Bus Unit service cycle (Remote node) Maximum transmission delay Maximum transmission delay = CPU Bus Unit service cycle (Local node, 1) + CPU Bus Unit service processing time (Local node, 1) + Send processing (Command) + Transmission delay (Command) + Receive processing (Command) + CPU Bus Unit service cycle (remote node) + CPU Bus Unit service processing time (remote node) + Send processing (Response) + Transmission delay (Response) + Receive processing (Response) + CPU Bus Unit service cycle (Local node, 2) + CPU Bus Unit service processing time (Local node, 2) CPU Bus Unit Service Cycle (Local Node, 1) The following table shows the service cycle, which depends on the CPU Unit’s CPU processing mode setting. CPU execution mode Normal Mode (See note.) Priority peripheral servicing Parallel processing with synchronous memory access Parallel processing with asynchronous memory access Note Processing time details One CPU Unit cycle time 0.2 ms + peripheral servicing time (1 ms max. for peripheral servicing of each Special I/O Unit, CPU Bus Unit, peripheral port, RS-232C port, and Inner Board) CJ2 CPU Units support only Normal Mode. For details, refer to the CPU Unit’s Operation Manual. CPU Bus Unit Service Processing Time (Local Node, 1) The following table shows the CPU Bus Unit service processing time, which depends on the CPU Unit’s CPU processing mode setting. CPU execution mode Normal Mode (See note.) Priority peripheral servicing Parallel processing with synchronous memory access Parallel processing with asynchronous memory access Note Processing time details Set peripheral servicing time Default: 4% of CPU Unit cycle time (10% for CJ2 CPU Units) 1 ms max. CJ2 CPU Units support only Normal Mode. 297 Section 10-5 Message Service Transmission Delay For details, refer to the CPU Unit’s Operation Manual. Send Processing Command Response Transmission Delay 0.550 ms (Number of words being transferred × 0.002) + 0.550 ms The transmission delay time depends on the baud rate set for the EtherNet/IP Unit or built-in EtherNet/IP port, as shown in the following table. (There may be additional delays due to the other devices in the network, such as switching hubs.) Baud rate Delay time 100Base-TX Command 0.0118 ms Response (Number of words transferred × 0.0013) + 0.0118 ms 10Base-T Command 0.0157 ms Response (Number of words transferred × 0.0019) + 0.0157 ms Receive Processing Command Response CPU Bus Unit Service Cycle (Remote Node) 0.704 ms (Number of words being transferred × 0.003) + 0.704 ms The following table shows the CPU Bus Unit service cycle, which depends on the CPU Unit’s CPU processing mode setting. CPU execution mode Normal Mode (See note.) Priority peripheral servicing Parallel processing with synchronous memory access Processing time details One CPU Unit cycle time EtherNet/IP Unit or Time slice instruction execution built-in EtherNet/IP time port is given priority. EtherNet/IP Unit or One CPU Unit cycle time built-in EtherNet/IP port is not given priority. One CPU Unit cycle time Parallel processing with asyn- 0.2 ms + peripheral servicing time (1 ms max. for chronous memory access peripheral servicing of each Special I/O Unit, CPU Bus Unit, peripheral port, RS-232C port, and Inner Board) Note CJ2 CPU Units support only Normal Mode. For details, refer to the CPU Unit’s Operation Manual. CPU Bus Unit Service Processing Time (Remote Node) The following table shows the CPU Bus Unit service processing time, which depends on the CPU Unit’s CPU processing mode setting. CPU execution mode Normal Mode (See note.) Priority peripheral servicing 298 Processing time details 4% of CPU Unit cycle time (10% for CJ2 CPU Units) EtherNet/IP Unit or Time slice peripheral servicing built-in EtherNet/IP execution time port is given priority. EtherNet/IP Unit or Set peripheral servicing time built-in EtherNet/IP (Default: 4% of CPU Unit cycle port is not given time) priority. Section 10-5 Message Service Transmission Delay CPU execution mode Processing time details Parallel processing with syn4% of CPU Unit cycle time chronous memory access Parallel processing with asyn- 1 ms max. chronous memory access Note CJ2 CPU Units support only Normal Mode. For details, refer to the CPU Unit’s Operation Manual. CPU Bus Unit Service Cycle (Local Node, 2) The following table shows the CPU Bus Unit service cycle, which depends on the CPU Unit’s CPU processing mode setting. CPU execution mode Normal Mode (See note.) Priority peripheral servicing Processing time details One CPU Unit cycle time EtherNet/IP Unit or Time slice instruction execution built-in EtherNet/IP time port is given priority. EtherNet/IP Unit or One CPU Unit cycle time built-in EtherNet/IP port is not given priority. One CPU Unit cycle time Parallel processing with synchronous memory access Parallel processing with asyn- 0.2 ms + peripheral servicing time (1 ms max. for chronous memory access peripheral servicing of each Special I/O Unit, CPU Bus Unit, peripheral port, RS-232C port, and Inner Board) Note CJ2 CPU Units support only Normal Mode. For details, refer to the CPU Unit’s Operation Manual. CPU Bus Unit Service Processing Time (Local Node, 2) The following table shows the CPU Bus Unit service processing time, which depends on the CPU Unit’s CPU processing mode setting. CPU execution mode Normal Mode (See note.) Priority peripheral servicing Parallel processing with synchronous memory access Processing time details 4% of CPU Unit cycle time (10% for CJ2 CPU Units) EtherNet/IP Unit or Time slice peripheral servicing built-in EtherNet/IP execution time port is given priority. EtherNet/IP Unit or Set peripheral servicing time built-in EtherNet/IP (Default: 4% of CPU Unit cycle port is not given time) priority. 4% of CPU Unit cycle time Parallel processing with asyn- 1 ms max. chronous memory access Note CJ2 CPU Units support only Normal Mode. For details, refer to the CPU Unit’s Operation Manual. Note Depending on the actual operating environment, the transmission time may be longer than the one calculated with the equations given here. The following factors can cause longer transmission times: other traffic on the network, window sizes of network nodes, other traffic at the EtherNet/IP Unit or built-in EtherNet/IP port itself (e.g., simultaneous tag data link communications), and the system configuration. 299 Section 10-5 Message Service Transmission Delay Example Calculation In this example, RECV(098) is used to receive 256 words of data from another PLC. The maximum transmission delay is calculated based on the following operating conditions. • Local node’s CPU cycle time: 10 ms • Local node’s CPU execution mode: Normal • Local node’s CPU peripheral servicing time: Default (4%) • Remote node’s CPU cycle time: 15 ms • Remote node’s CPU execution mode: Normal • Remote node’s CPU peripheral servicing time: Default (4%) • Baud rate: 100Base-TX Item CPU Bus Unit service cycle (local node, 1) CPU Bus Unit service processing time (local node, 1) Send processing (command) Transmission delay (command) Receive processing (command) CPU Bus Unit service cycle (remote node) CPU Bus Unit service processing time (remote node) Send processing (command) Transmission delay (command) Receive processing (command) CPU Bus Unit service cycle (local node, 2) CPU Bus Unit service processing time (local node, 2) Maximum transmission delay 300 Calculated value 10 ms 0.4 ms 0.550 ms ≅ 0.5 ms 0.0118 ms ≅ 0.1 ms 0.704 ms ≅ 0.7 ms 15 ms 0.6 ms (256 × 0.002) + 0.550 = 1.062 ≅ 1.1 ms (256 × 0.0013) + 0.0118 = 0.3446 ≅ 0.3 ms (256 × 0.003) + 0.704 = 1.472 ≅ 1.5 ms 10 ms 0.4 ms 10 + 0.4 + 0.5 + 0.1 + 0.7 + 15 + 0.6 + 1.1 + 0.3 + 1.5 + 10 + 0.4 = 40.6 ms SECTION 11 FTP Server This section describes the functions provided by the FTP server. 11-1 Overview and Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302 11-1-1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302 11-1-2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303 11-2 FTP Server Function Details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303 11-2-1 File Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303 11-2-2 Connecting to the FTP Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304 11-3 Using the FTP Server Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305 11-3-1 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305 11-3-2 List of Settings Required for the FTP Server Function . . . . . . . . . . 305 11-3-3 FTP Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306 11-4 FTP Server Application Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307 11-5 Using FTP Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308 11-5-1 Table of Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308 11-5-2 Using the Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308 11-5-3 Error Messages and FTP Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313 11-6 Checking FTP Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314 11-6-1 FTP Status Flag. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314 11-7 Using File Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315 11-7-1 File Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315 11-7-2 File Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315 11-7-3 Initializing File Memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317 11-7-4 I/O Memory Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317 11-8 FTP File Transfer Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 11-9 Host Computer Application Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321 301 Section 11-1 Overview and Specifications 11-1 Overview and Specifications 11-1-1 Overview The EtherNet/IP Unit or built-in EtherNet/IP port has a built-in FTP (File Transfer Protocol) server function, so other computers on the Ethernet can read or write (upload/download) large files in the EM file memory by executing FTP commands from the FTP client software. FTP can be used for EtherNet/IP Units with unit version 2.0. FTP client Intranet Specify the file and upload or download using FTP commands such as get and put. Ethernet Download EtherNet/IP Unit or built-in EtherNet/IP port Upload Large file Files in the EM File Memory or the Memory Card mounted to the CPU Unit. Note 302 Only one FTP client can connect at the same time. Section 11-2 FTP Server Function Details 11-1-2 Specifications Item Executable commands Protection Protocol Number of connections Specification open: Connects the specified host FTP server. user: Specifies user name for the remote FTP server. ls: Displays the Memory Card file names. dir: Display the Memory Card file names and details. rename: Changes a file name. mkdir: Creates a new directory in the working directory in the remote host. rmdir: Deletes a new directory from the working directory in the remote host. cd: Changes the Ethernet Unit work directory to the specified directory. cdup: Changes the working directory at the remote host to the parent directory. pwd: Displays the Ethernet Unit work directory. type: Specifies the data type of transferred files. get: Transfers the specified file from the Memory Card to the local host. mget: Transfers multiple files from the Memory Card to the local host. put: Transfers the specified local file to the Memory Card. mput: Transfers multiple local files to the Memory Card. delete: Deletes the specified file from the Memory Card. mdelete: Deletes multiple files from the Memory Card. close: Disconnects the FTP server. bye: Closes the FTP (client). quit: Closes the FTP (client). FTP login name consists of 12 letters max. CONFIDENTIAL is the default login name. Password consists of 8 characters max. FTP (port number: 20/TCP, 21/TCP) 1 Note The PLC, however, is unable to read or write files at other nodes using FTP because the EtherNet/IP Unit or built-in EtherNet/IP port does not support FTP client functions. 11-2 FTP Server Function Details 11-2-1 File Types The file system in the CPU Unit that can be accessed by the EtherNet/IP Unit or built-in EtherNet/IP port includes files in any Memory Card mounted in the CPU Unit and files in the EM file memory. The directory tree is shown below. /: root MEMCARD: Memory card directory EM: EM file memory directory A connection will be initially made to the root directory. Note 1. The date of the MEMCARD directory displayed for ls or dir commands in the root directory will be the date of the file system volume label. 2. The login date will be displayed for EM files and for MEMCARD if a volume label has not been created. 303 Section 11-2 FTP Server Function Details 11-2-2 Connecting to the FTP Server The host computer must connect to the FTP server before the FTP server functions can be used. The login name and password set in the Unit Setup will be used when connecting. The default FTP login name is “CONFIDENTIAL” and no password is required. The FTP server in the EtherNet/IP Unit or built-in EtherNet/IP port can connect to only one client at a time. If a client attempts to connect when the FTP server is in use, a message will be returned and connection will be refused. Note When general-purpose FTP software is used, files can be transferred and read using a graphical user interface similar to Explorer. Login Name and Password Setting The default login name for FTP is “CONFIDENTIAL” and no password is set for the default login, so login is possible by simply entering “CONFIDENTIAL” as the login name. A user-set login name and password can also be set in the User Setup (CPU Bus Unit System Setup). Login Messages Status Normal connection FTP server busy Message 220 xxx.xx.xx.xx yyyyyyyyyy FTP server (FTP Version z.zz) ready. xxx.xx.xx.xx: IP address of EtherNet/IP Unit or built-in EtherNet/IP port yyyyyyyyyy: EtherNet/IP Unit or built-in EtherNet/IP port model number (e.g., CS1W-EIP21) z.zz: Firmware version of EtherNet/IP Unit or built-in EtherNet/ IP port 221 FTP server busy, Goodbye. Setting Restrictions The following restrictions apply to login names and passwords. • The login name and password must consist of alphanumeric characters, hyphens, and/or underscores. They are not case sensitive. • A login name consists of 12 characters. • A password consists of 8 characters. • Always set a password when setting a new login name. The login name will not be valid unless a password is set for it. • If a login name is not set or contains illegal characters, the default login name, CONFIDENTIAL, must be used. No password is required and any password that is set will be ignored. FTP File Transfer Mode FTP has two file transfer modes: ASCII mode and binary mode. Before starting to transfer files, use the type command (specifies the data type of transferred files) to select the required mode. Always select binary mode for binary files (extensions .IOM, .STD, or .OBJ) in the CS/CJ-series file memory and other program files (with extensions such as .CXP). 304 Section 11-3 Using the FTP Server Function 11-3 Using the FTP Server Function 11-3-1 Procedure 1,2,3... 1. Make the basic settings. Refer to Initial Settings on page 34. 2. When using a user-set FTP login name and password: With the CX-Programmer online, right-click the EtherNet/IP Unit or built-in EtherNet/IP port in the IO Table Dialog Box of the CX-Programmer, and select Edit - Unit Setup. Set the following on the FTP Tab Page of the Edit Parameters Dialog Box. • FTP login name • FTP password. 3. Select Transfer to PLC from the PLC Menu and click the Yes Button. The setting data will be transferred to the CPU Bus Unit System Setup Area in the CPU Unit. 4. When reading from and writing to the Memory Card: Mount the Memory Card into the CPU Unit. 5. Connect the EtherNet/IP Unit or built-in EtherNet/IP port using the FTP client software. 6. Enter the FTP login name and password set in the Unit Setup and log into the EtherNet/IP Unit or built-in EtherNet/IP port. Note Once logged in, the ftp commands can be used, such as cd (Change Directory), and get (Obtain File). 7. Search in the following directories for the required file in the Memory Card mounted to the CPU Unit or the EM File Memory. File memory type Memory Card EM File Memory Directory \MEMCARD \EM 8. Download the files. 9. Exit the connection. Note The EtherNet/IP Unit or built-in EtherNet/IP port will be restarted when the settings data is transferred to the CPU Bus Unit System Setup Area, so that the new settings are read and become effective. Verify that it is safe for the EtherNet/IP Unit or built-in EtherNet/IP port to restart before transferring the settings data. 11-3-2 List of Settings Required for the FTP Server Function Make the following settings for the unit setup when the server function is used. CX-Programmer tab FTP Settings Login Password Port No. Setting conditions Page User-set (when the default, CON- 306 FIDENTIAL, is not used) User-set Rarely required (when the default, 21, is not used) 305 Section 11-3 Using the FTP Server Function 11-3-3 FTP Tab The CPU Bus Unit System Setup, which is set when using the FTP server function, is shown in the CX-Programmer's Edit Parameters Dialog Box. ■ Settings Setting Login Password Port No. 306 Details Set the login name to externally connect to the EtherNet/IP Unit or built-in EtherNet/IP port via FTP. Default value None (CONFIDENTIAL is used.) Set the password to externally connect to the None EtherNet/IP Unit or built-in EtherNet/IP port via FTP. FTP port number of the EtherNet/IP Unit or built-in EtherNet/IP port. This setting does not normally need to be changed. FTP uses two ports: a port for control and a port for data transfer. Set the control port only. The data transfer port uses the value set for the control port –1. 0 (21 is used.) Section 11-4 FTP Server Application Example 11-4 FTP Server Application Example The following procedure shows how to use the FTP server by connection with the default login name, CONFIDENTIAL. No password is required. Note The login name and a password must be set in the CPU Bus Setup for the Ethernet Unit in the CPU Unit to use any login name other than CONFIDENTIAL. Note When general-purpose FTP software is used, files can be transferred and read using a graphical user interface similar to Explorer. 1,2,3... 1. Make sure that a Memory Card is inserted in the CPU Unit and turn ON the power supply to the PLC. If EM File Memory is to be used, create the EM File Memory. 2. Connect to the FTP server from a computer on the Ethernet by entering the text that is underlined in the following diagram. IP address of the Ethernet/IP Unit or built-in EtherNet/IP port $ ftp 150.31.2.83 connected to 150.31.2.83 220 **IPaddress** CJ1W-EIP21 FTP server(FTP**version**)ready Name:CONFIDENTIAL Results Login name 230 Guest logged in. 3. Enter FTP commands (underlined in the following diagram) to read and write files. The following directory tree is used in this example. /: root EM MEMCARD ABC (subdirectory) DEF.IOM (file) ftp> ls File names read 200 PORT command successful. 150 opening data connection for ls(**IPaddress**port#**)(0bytes). MEMCARD EM Results 226 Transfer complete. ** bytes received in 0 seconds(**bytes/s) ftp> cd MEMCARD Change to MEMCARD directory 250 CWD command successful. Results ftp> get ABC/DEF.IOM Transfer DEF.IOM from ABC directory 200 PORT command successful. 150 opening data connection for abc/def.iom(**IPaddress**port#**)(**bytes). Results 226 Transfer complete **bytes received in *.*** seconds(**bytes/s) 307 Section 11-5 Using FTP Commands 11-5 Using FTP Commands This section describes the FTP commands which the host computer (FTP client) can send to the FTP server of the EtherNet/IP Unit or built-in EtherNet/IP port. The descriptions should also apply to most UNIX workstations, but slight differences may arise. Refer to your workstation’s operation manuals for details. 11-5-1 Table of Commands The FTP commands which can be sent to the EtherNet/IP Unit or built-in EtherNet/IP port are listed in the following table. Command open user ls dir rename mkdir rmdir cd cdup pwd type get mget put mput delete mdelete close bye quit Description Connects the specified host FTP server. Specifies user name for the remote FTP server. Displays the Memory Card file names. Display the Memory Card file names and details. Changes a file name. Creates a new directory in the working directory in the remote host. Deletes a new directory from the working directory in the remote host. Changes the Ethernet Unit work directory to the specified directory. Changes the working directory at the remote host to the parent directory. Displays the Ethernet Unit work directory. Specifies the data type of transferred files. Transfers the specified file from the Memory Card to the local host. Transfers multiple files from the Memory Card to the local host. Transfers the specified local file to the Memory Card. Transfers multiple local files to the Memory Card. Deletes the specified file from the Memory Card. Deletes multiple files from the Memory Card. Disconnects the FTP server. Closes the FTP (client). Closes the FTP (client). • The EtherNet/IP Unit or built-in EtherNet/IP port is considered to be the remote host and the host computer (FTP client) is considered to be the local host. • A remote file is a file on the Memory Card or in EM File Memory in the CPU Unit. A local file is one in the host computer (FTP client). • The parent directory is the directory one above the working directory. 11-5-2 Using the Commands open Format open [IP_address or host_name_of_FTP_server] Function Connects the FTP server. Normally when the FTP client is booted, the FTP server IP address is specified to execute this command automatically. 308 Section 11-5 Using FTP Commands user Format user [user_name] Function Specifies the user name. Specify the FTP login name set in the EtherNet/IP Unit or built-in EtherNet/IP port system setup. The default FTP login name is “CONFIDENTIAL.” If a non-default login name is used, it must be followed by the password. In this case, enter the FTP password set in the system setup. The user name is automatically requested immediately after connection to the FTP server. ls Format ls [-l] [REMOTE_FILE_NAME [local_file_name]] Function Displays the remote host (Memory Card or EM File Memory) file names. Set the switch [-l] to display not only the file names but the creation date and size as well. If the switch is not set, only the file names will be displayed. You can specify a file name in the Memory Card or EM File Memory if desired. If a local file name is specified, the file information will be stored in the specified file in the host computer. dir Format dir [REMOTE_FILE_NAME [local_file_name]] Function Displays the file names, date created, and size of the files in the remote host (Memory Card or EM File Memory). It displays the same information as command [ls -l]. Specify a file name in the Memory Card or EM File Memory as the remote file name. If a local file name is specified, the file information is stored in the specified file in the host computer. rename Format rename CURRENT_FILE_NAME NEW_FILE_NAME Function Changes the specified current file name to the specified new file name. rename can be used only to change the file name. It cannot be used to move the file to a different directory. 309 Section 11-5 Using FTP Commands mkdir Format mkdir DIRECTORY_NAME Function Creates a directory of the specified name at the remote host (Memory Card or EM File Memory). An error will occur if a file or directory of the same name already exists in the working directory. rmdir Format rmdir DIRECTORY_NAME Function Deletes the directory of the specified name from the remote host (Memory Card or EM File Memory). The directory must be empty to delete it. An error will occur if the specified directory does not exist or is empty. pwd Format pwd Function Displays the remote host’s (Ethernet Unit) current work directory. cd Format cd [directory_name] Function Changes the remote host (Ethernet Unit) work directory to the specified remote directory. The files in the Memory Card are contained in the MEMCARD directory under the root directory (/). The files in EM File Memory are contained in the EM directory under the root directory (/). The root directory (/) is the directory used when logging into the EtherNet/IP Unit or built-in EtherNet/IP port. No MEMCARD directory will exist if a Memory Card is not inserted in the PLC or if the Memory Card power indicator is not lit. No EM directory will exist if EM File Memory does not exist. cdup Format cdup Function Changes the working directory at the remote host to the parent directory (one directory above the current working directory). 310 Section 11-5 Using FTP Commands type Format type data_type Function Specifies the file data type. The following data types are supported: ascii: Files are transferred as ASCII data binary (image): Files are transferred as binary data. All files are treated by the PLC as binary files. Before reading or writing any files, always use the type command to set the file type to binary. File contents cannot be guaranteed if transferred as ASCII data. The default file type is ASCII. get Format get FILE_NAME [receive_file_name] Function Transfers the specified remote file from the Memory Card or EM File Memory to the local host. A receive file name can be used to specify the name of the file in the local host. mget Format mget FILE_NAME Function Allows the use of a wildcard character (*) to transfer multiple remote files from the Memory Card or EM File Memory to the local host. put Format put file_name [DESTINATION_FILE_NAME] Function Transfers the specified local file to the remote host (Memory Card or EM File Memory). A destination file name can be used to specify the name the file is stored under in the Memory Card or EM File Memory. Any existing file with the same name in the remote host (Memory Card or EM File Memory) will be overwritten by the contents of the transferred file. If an error occurs during file transfer, the file being transferred will be deleted and the transmission will end in an error. mput Format mput FILE_NAME Function Allows the use of a wildcard character (*) to transfer multiple local files to the remote host (Memory Card or EM File Memory). 311 Section 11-5 Using FTP Commands Any existing file with the same name in the remote host (Memory Card or EM File Memory) will be overwritten by the contents of the transferred file. If an error occurs during file transfer, the file being transferred will be deleted and the transmission of that file will end in an error. However, mput execution will continue and remaining files will be transferred. delete Format delete FILE_NAME Function Deletes the specified remote file from the Memory Card or EM File Memory. mdelete Format mdelete FILE_NAME Function Allows the use of a wildcard character (*) to delete multiple remote files from the Memory Card or EM File Memory. close Format close Function Disconnects the FTP server of the EtherNet/IP Unit or built-in EtherNet/IP port. bye Format bye Function Ends the FTP (client). quit Format quit Function Ends the FTP (client). 312 Section 11-5 Using FTP Commands 11-5-3 Error Messages and FTP Status Error Messages The error messages returned by the EtherNet/IP Unit or built-in EtherNet/IP port are listed in the following table. Message PPP is a directory. PPP is not a directory. Another unit has access authority (FINS error 0 x 3001). Bad sequence of commands. Can't create data socket (X.X.X.X, YY). Cannot access to device (FINS error 0 x 250F). Cannot get memory blocks. Command format error (FINS error 0 x 1003). Connect error. Directories of old and new paths are not same. Directory name length exceeded max. size. Directory not empty (FINS error 0 x 2108). Fatal error (FINS error 0 x 1101). Fatal error (FINS error 0 x 1103). File or directory already exists. File or directory already exists (FINS error 0 x 2107). File or directory name illegal. File or directory name illegal (FINS error 0 x 110C). File read error (FINS error 0 x 1104). File read error (FINS error 0 x 110B). File write error (FINS error 0 x 2106). File write error (FINS error 0 x 2107). FINS error MRES 0 x XX: SRES 0 x XX. Length of directory name too long. No space to create entry (FINS error 0 x 2103). No such device (FINS error 0 x 2301). No such file or directory. No such file or directory (FINS error 0 x 2006). No such file or directory (FINS error 0 x 2106). Not enough memory. Not enough space in the system. (FINS error 1104). PLC communication error (timeout). Socket canceled. Socket error NN. Socket receive error NN. Socket send error NN. Timeout (900 seconds): closing control connection. Too many open files. Write access denied. Write access denied. (FINS error 0 x 2101). Meaning The path name indicated at PPP is a directory. The path name indicated at PPP is not a directory. Another Unit currently has the access right. The RNFR command has not been executed. A socket cannot be created. A file device error has occurred. A message memory block cannot be allocated. The command format is incorrect. A connection error has occurred. The directories before and after changing the name are different. The directory name is too long. The directory must be empty to delete it. A parameter error has occurred. The specified file or directory name already exists. The file or directory name is incorrect. An error occurs when reading the file. An error occurs when reading the file. Some other FINS error has occurred. The path name of the directory is too long. There are too many files to create a new one. The file device cannot be found. The specified file or directory does not exist. The communications buffers are full. The file device is full. File access timed out. The socket was canceled. A socket bind error occurred. The error code will be given at NN. A data reception error occurred. The error code will be given at NN. A data send error occurred. The error code will be given at NN. The connection was closed because the client did not respond for 15 minutes. Too many sockets have been created. Writing is not possible. 313 Section 11-6 Checking FTP Status PPP: XXX: YY: MM: NN: Path name IP address Port number FINS error code Socket error code 11-6 Checking FTP Status 11-6-1 FTP Status Flag The current status of the FTP server can be obtained from the service status in the words allocated to the EtherNet/IP Unit in the CPU Bus Unit Area in the CIO Area. The word containing the FTP Status Flag can be computed as follows: CIO 1500 + (25 x unit number) + 13 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 n+13 FTP Status Flag Status of bit 00 1 0 Note Meaning FTP server busy (a user is connected) FTP server free 1. File operations for files on the Memory Card are performed during FTP communications. Do not remove the Memory Card or turn OFF power to the PLC while FTP is being used. 2. When using File Memory Instruction from the program in the CPU Unit, program exclusive control using the FTP Status Flag so that the same data is not manipulated simultaneously by more than one instruction. 314 Section 11-7 Using File Memory 11-7 Using File Memory There are two media that can be used to store files in memory for CS/CJseries PLCs: • Memory Cards • EM File Memory CPU Unit File Memory Card File File EM File Memory File 11-7-1 File Memory Media CS/CJseries Memory Cards EM File Memory Memory type Capacity Flash memory 8 MB 15 MB 30 MB RAM Model HMC-EF861 HMC-EF171 HMC-EF371 File data recognized by CPU Unit • Complete user program • Specified portions of I/O Memory • Parameter area data (e.g. PLC Setup) Max. capacity of EM Area All EM Area banks in CPU Unit from specified bank in I/O Memory (specified in PLC Setup) 11-7-2 File Types ■ File Names Files are distinguished by assigning file names and extensions. The following characters can be used in file names and extensions: Alphanumeric characters: A to Z and 0 to 9. (Names converted to all-caps) !&$#’[]-^()_ The following characters cannot be used in files names and extensions: , . / ? * ” : ; < > = + (spaces) File names are not case sensitive and will be converted to all-caps in the PLC file system. File names can be up to 8 character long with 3-character extensions. An error will occur if a file name or extension is too long. The first period (.) in a file name will be taken as the delimiter between the file name and extension. Extensions are determined by the file type. ■ Directories Up to five levels of directories (including root as the first level) can be created as file storage locations. A maximum of 65 characters can be used in directory names. 315 Section 11-7 Using File Memory File Names Handled by CPU Unit The files described in the following table can be read or written by the CPU Unit. File type Data file File name ******** Extension Contents .IOM Specified ranges of I/O Memory Program file ******** .OBJ Parameter area file ******** .STD Files transferred at startup Data files AUTOEXEC .IOM Program files AUTOEXEC .OBJ Parameter area file AUTOEXEC .STD Note Description • Contains word (16-bit) data from a starting word through an end word in one memory area. • The following areas can be used: CIO, HR, WR, AR, DM, and EM. Complete user pro• Contains all the programs for cyclic tasks gram and interrupt tasks, as well as task information for one CPU Unit. • Contains all of the parameter data for one • PLC Setup CPU Unit. • Registered I/O • There is no need for the user to distinguish tables the various types of data contained in the • Routing tables file. • CPU Bus Unit • The file can be automatically read to or Setup and other written from the CPU Unit simply by specisetup data fying the extension (.STD) I/O Memory data for • There does not necessarily need to be a the specified number data file in the Memory Card when the of words starting from automatic file transfer function is used at D20000 startup. • The AUTOEXEC.IOM file always contains DM Area data starting at D20000. • All data in the file will be transferred to memory starting at D20000 at startup. Complete user pro• There must be a program file in the Memgram ory Card when the automatic file transfer function is used at startup. • Contains all the programs for cyclic tasks and interrupt tasks, as well as task information for one CPU Unit. • There must be a parameter file in the • PLC Setup Memory Card when the automatic file • Registered I/O transfer function is used at startup. tables • Contains all of the parameter data for one • Routing tables CPU Unit. • CPU Bus Unit • There is no need for the user to distinguish Setup and other the various types of data contained in the setup data file. • All parameters in the file will be automatically transferred to specified locations in memory at startup. 1. Refer to information on file memory in the CS/CJ-series Programmable Controllers Operation Manual (W339). 2. All files transferred automatically at startup must have the name AUTOEXEC. 316 Section 11-7 Using File Memory 11-7-3 Initializing File Memory Memory Memory Cards Initialization method 1. Insert the Memory Card into the CPU Unit. 2. Initialize the Memory Card from a Programming Device (Programming Consoles included). EM File Mem- 1. Specify in the PLC Setup the first bank to convert to file memory. ory 2. Initialize EM File Memory from the CX-Programmer. 11-7-4 I/O Memory Data Format ■ IOM Format The IOM format is a data format used for binary data specified by the ladder instructions, READ DATA FILE (FREAD(700)) and WRITE DATA FILE (FWRIT(701)), in the CPU Unit. If five words of data from the I/O memory (1234 hexadecimal, 5678 hexadecimal, 9ABC hexadecimal, etc.) is contained in an attached file in IOM format, the data will be stored in the attached file as shown in the following diagram. Example: Binary data format with a delimiter after every 10 fields. I/O memory +0 +10 +0 +1 1234 5678 9ABC DEF0 +2 +3 9ABC DEF0 1234 +4 +5 1234 5678 5678 9ABC DEF0 +6 +7 9ABC DEF0 1234 +8 +9 1234 5678 5678 9ABC DEF0 .IOM file contents XX XX XX 12 34 56 78 9A BC DE F0 12 34 48 bytes (Reserved by the system.) ■ TXT Format The TXT format is a data format (using tab delimiters) specified by the ladder instructions, READ DATA FILE (FREAD(700)) and WRITE DATA FILE (FWRIT(701)), in the CPU Unit. The format is configured according to the specified FREAD(700) and FWRIT(701) parameters, as follows: Data format • Words without delimiters • Double words without delimiters • Words delimited by tabs. • Double words delimited by tabs Use of CRs and CR position • No CRs • CR after every 10 fields. • CR after each field. • CR after every 2 fields. • CR after every 4 fields. • CR after every 5 fields. • CR after every 16 fields. If data from the I/O memory (1234 hexadecimal, 5678 hexadecimal, 9ABC hexadecimal, etc.) is contained in an attached file in TXT format, the data will be converted into ASCII format in words or double-words. The words are delimited by inserting tabs ([HT]: 09), and carriage returns (CR) after specified fields ([CR][LF]: 0D0A). 317 Section 11-7 Using File Memory Example: Data format using words delimited by tabs and CRs after every 10 fields. I/O memory +0 +0 +10 +1 1234 5678 9ABC DEF0 +2 +3 9ABC DEF0 1234 +4 +5 1234 5678 +6 +7 9ABC DEF0 5678 9ABC DEF0 1234 +8 +9 1234 5678 5678 9ABC DEF0 .TXT file contents 31 32 33 34 09 35 36 37 38 09 39 41 42 43 09 1 2 3 4 [HT] 5 6 7 8 [HT] 9 A B C [HT] 35 36 37 38 0D 0A 39 41 42 43 09 5 6 7 8 [CR][LF] 9 A B C [HT] .TXT file displayed as text 1234@5678@9ABC@DEF0@1234@5678@9ABC@DEF0@1234@5678 9ABC@DEF0@1234@5678@9ABC@DEF0@1234@5678@9ABC@DEF0 @...[HT]: Used to display tab space when displayed as text. ■ CSV Format The CSV format is a data format (using comma delimiters) that is specified by ladder instructions, READ DATA FILE (FREAD(700)) and WRITE DATA FILE (FWRIT(701)), in the CPU Unit. The CSV format is configured according to the specified FREAD(700) and FWRIT(701) parameters, as follows: Data format Words delimited by commas. Double words delimited by commas. Use of CRs and CR position • No CRs • CR after every 10 fields. • CR after each field. • CR after every 2 fields. • CR after every 4 fields. • CR after every 5 fields. • CR after every 16 fields. If word data from the I/O memory (1234 hexadecimal, 5678 hexadecimal, up to DEF0 hexadecimal) is contained in an attached file in CSV format, the word data will be converted into ASCII format in word or double-word units. The words are delimited by inserting comma delimiters (',':2C), and CRs after specified fields ([CR][LF]: 0D0A). 318 Section 11-7 Using File Memory Example: Data format using words delimited by commas with CRs after every 10 fields. I/O memory +0 +0 +10 +1 1234 +2 5678 +3 9ABC DEF0 9ABC DEF0 1234 +4 +5 1234 5678 +6 +7 9ABC DEF0 5678 9ABC DEF0 1234 +8 +9 1234 5678 5678 9ABC DEF0 .CSV file contents 31 32 33 34 2C 35 36 37 38 2C 39 41 42 43 2C 1 2 3 4 , 5 6 7 8 , 9 A B C , 35 36 37 38 0D 0A 39 41 42 43 2C 5 6 7 8 [CR] [LF] 9 A B C , .TXT file displayed as text 1234,5678,9ABC,DEF0,1234,5678,9ABC,DEF0,1234,5678 9ABC,DEF0,1234,5678,9ABC,DEF0,1234,5678,9ABC,DEF0 Note FREAD(700) will not be able to read the last byte in a file that has been written to the Memory Card if the file contains an odd number of bytes. Add 00 hexadecimal to the end of the file if necessary to write an even number of bytes to the Memory Card. Note The UM and DM Areas contain binary data. Set the data type to binary using the type command before reading or writing files using FTP. (Refer to type on page 311.) Note For details on how to use File Memory Instructions, refer to the CS/CJ Series Instructions Reference Manual (W340). 319 Section 11-8 FTP File Transfer Time 11-8 FTP File Transfer Time File transfers using FTP can require 30 or 40 minutes depending on the capacity of the file. Approximate file transfer time are provided in the following table for reference. All times are in seconds unless otherwise specified. ■ CS1 CPU Units and CJ1 CPU Units File system CPU Unit status Operating mode Cycle time Transfers using 1 KB put 30 KB 60 KB 120 KB Transfers using 1 KB get 30 KB 60 KB 120 KB Memory Card PROGRAM RUN --20 ms 0.7 s 6.0 s 4.5 s 38.3 s 7.4 s 72.1 s 14.4 s 141.4 s 0.3 s 1.4 s 2.8 s 19.3 s 4.9 s 37.6 s 9.6 s 75.7 s EM File Memory PROGRAM RUN --20 ms 0.4 s 2.9 s 2.5 s 21.5 s 5.0 s 44.7 s 11.0 s 120.8 s 0.2 s 0.8 s 1.9 s 11.4 s 3.8 s 26.7 s 8.6 s 68.2 s ■ CS1-H CPU Units, CJ1-H CPU Units, CJ1-R CPU Units, CJ2-H CPU Units, and CJ2M CPU Units File system CPU Unit status Operating mode Cycle time Transfers using 1 KB put 30 KB 60 KB 120 KB Transfers using 1 KB get 30 KB 60 KB 120 KB Note Memory Card PROGRAM RUN --20 ms 0.5 s 2.7 s 1.8 s 11.6 s 3.2 s 21.1 s 6.2 s 40.2 s 0.2 s 0.3 s 1.7 s 4.8 s 2.5 s 9.4 s 4.9 s 18.8 s EM File Memory PROGRAM RUN --20 ms 0.2 s 0.6 s 0.7 s 6.6 s 1.5 s 14.0 s 3.6 s 32.5 s 0.2 s 0.2 s 1.0 s 4.1 s 2.3 s 9.7 s 4.9 s 27.0 s 1. The above times assume that the Fixed Peripheral Servicing Time in the PLC Setup is set to the default value of 4%. 2. If the Fixed Peripheral Servicing Time in the PLC Setup is increased, FTP files will be transferred faster. 320 Host Computer Application Example Section 11-9 11-9 Host Computer Application Example The following procedure provides an example of FTP operations from a host computer. In this example, the following assumptions are made. • The IP address of the EtherNet/IP Unit or built-in EtherNet/IP port is registered in /etc/hosts on the host name as [cs1]. • The default FTP login name is being used (CONFIDENTIAL). • A processing results data file called RESULT.IOM already exists on the Memory Card in the CPU Unit. • A processing instructions data file called PLAN.IOM already exists on the workstation. The following procedure transfers the processing results file RESULT.IOM from the Memory Card in the CPU Unit to the workstation and then the processing instructions file PLAN.IOM is transferred from the workstation to the Memory Card in the CPU Unit. Underlined text is keyed in from the FTP client. The workstation prompt is indicated as $ and the cursor is indicated as ■. 1,2,3... 1. Start FTP and connect to the EtherNet/IP Unit or built-in EtherNet/IP port. $ ftp cs1 ··· FTP started. connected to cs1 220 **IPaddress** CS1W-ETN21 FTP server(FTP**version**)ready Name(cs1:root): ■ 2. Enter the login name. Name(cs1:root):CONFIDENTIAL ··· Login name 230 Guest logged in. ftp> ■ 3. Make sure the Memory Card is inserted. The MEMCARD directory will be displayed if there is a Memory Card in the CPU Unit. ftp> ls ··· Make sure the Memory Card is inserted. 200 PORT command successful. 150 opening data connection for ls(**IPaddress**port#**)(0 bytes). MEMCARD 226 Transfer complete. 15 bytes received in 0 seconds(**bytes/s) ftp> ■ 321 Host Computer Application Example 4. Change to the MEMCARD directory. ftp> cd MEMCARD ··· Change to MEMCARD directory. 250 CWD command successful. ftp> ■ 5. Change data type to binary. ftp> type binary ··· Binary data type set. 200 Type set to I. ftp> ■ 6. Transfer the file RESULT.IOM to the workstation. ftp> get RESULT.IOM ··· File read. 200 PORT command successful. 150 opening data connection for result.iom (**IPaddress**port#**) (**bytes). 226 Transfer complete. ** bytes received in *.*** seconds (**bytes/s) ftp> ■ 7. Write the file PLAN.IOM to the Memory Card. ftp> put PLAN.IOM ··· File written 200 PORT command successful. 150 opening data connection for plan.iom (**IPaddress**port#**). 226 Transfer complete. ** bytes received in *.** seconds (**bytes/s) ftp> ■ 8. End FTP. ftp> bye ··· FTP ended. 221 Goodbye. $ ■ 322 Section 11-9 SECTION 12 Automatic Clock Adjustment Function This section provides an overview of the automatic clock adjustment function, including details on specifications, required settings, operations from CX-Programmer, and troubleshooting. 12-1 Automatic Clock Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 324 12-1-1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 324 12-1-2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325 12-2 Using the Automatic Clock Adjustment Function . . . . . . . . . . . . . . . . . . . . . 325 12-2-1 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325 12-2-2 Settings Required for Automatic Clock Adjustment Function. . . . . 326 12-2-3 Auto Adjust Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327 12-3 Automatic Clock Adjustment Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328 12-4 Automatic Clock Adjustment Error Processing . . . . . . . . . . . . . . . . . . . . . . . 328 12-4-1 Automatic Clock Adjustment (SNTP) Errors. . . . . . . . . . . . . . . . . . 328 12-4-2 Error Log Error Codes for the Automatic Clock Adjustment Function 328 323 Section 12-1 Automatic Clock Adjustment 12-1 Automatic Clock Adjustment 12-1-1 Overview The EtherNet/IP Unit or built-in EtherNet/IP port can obtain the clock information from the SNTP server (see note 1) at a particular time or when a designated bit turns ON and then refresh the internal clock information of the CPU Unit to which it is mounted (referred to as the local CPU Unit). Intranet SNTP server Automatic clock adjustment The clock information can be broadcast to other CPU Units on the same Network. Ethernet 24: 00: 00 24: 00: 00 EtherNet/IP Unit or built-in EtherNet/IP port Clock data is obtained from the SNTP server and written at a particular time or when a designated bit turns ON. Note (1) The SNTP (Simple Network Time Protocol) server is used to control the time on the LAN. (2) An error will occur in the following CPU Units when the automatic clock adjustment function is executed under the conditions shown in the table. CPU Unit CPU Units manufactured on or before January 31, 2003 (lot numbers 030131 or earlier): CJ1G-CPU@@H CJ1H-CPU@@H CS1G-CPU@@H CS1H-CPU@@H Conditions When the CPU execution mode is set to other than normal mode (priority peripheral servicing mode, parallel processing with synchronous memory access mode, or parallel processing with asynchronous memory access mode). AND When the CPU Unit operating mode is set to RUN or MONITOR mode. (3) The manufacturing date can be determined from the lot number on the side or top corner of the CPU Unit. (4) The lot numbers are as follows: YYMMDDnnnn, in which YY indicates the last two digits of the year, MM the month, DD the day, and nnnn the serial number. (5) In accordance with SNTP protocol specifications, automatic adjustment will not be possible from February 7, 2036. In EtherNet/IP Units or builtin EtherNet/IP ports, this function will no longer operate from February 7, 2036 (an error message will not be displayed). 324 Using the Automatic Clock Adjustment Function Section 12-2 12-1-2 Specifications Item Protocol Port number Adjustment timing Access to SNTP server Refresh timing Specification SNTP 123 (UDP) Can also be set from the CX-Programmer in the Unit Setup. Automatic (fixed time) and manual (manual only cannot be set) Obtains the clock information Writes the clock information from the SNTP server set up from the SNTP server to the on the Network, and applies local CPU Unit. the information obtained to the local CPU Unit. When the automatic clock adjustment switch is turned from OFF to ON and at a specified time. 12-2 Using the Automatic Clock Adjustment Function 12-2-1 Procedure 1,2,3... 1. Make the basic settings. Refer to Initial Settings on page 34. 2. With the CX-Programmer online, right-click the EtherNet/IP Unit or built-in EtherNet/IP port in the IO Table Dialog Box of the CX-Programmer, and select Edit - Unit Setup Set the following on the Auto Adjust Time Tab Page of the Edit Parameters Dialog Box. • SNTP server specification (required) • Access to the SNTP server is enabled when writing clock information from the SNTP server to the local CPU Unit when the Automatic Clock Adjustment Switch is turned from OFF to ON and at a set automatic adjustment time. • Automatic clock adjustment setting. 3. To perform automatic clock adjustment manually, turn the Automatic Clock Adjustment Switch from OFF to ON. (The Automatic Clock Adjustment Switch is word n bit 05 in the words allocated in the CPU Bus Unit Area, where n = CIO 1500 + (25 × unit number.) 4. Select Transfer to PLC from the PLC Menu and click the Yes Button. The Unit Setup (CPU Bus System Setup) will be transferred to the CPU Unit (the setting data will be transferred to the CPU Bus Unit System Setup Area). 325 Section 12-2 Using the Automatic Clock Adjustment Function 12-2-2 Settings Required for Automatic Clock Adjustment Function The following settings must be set in the Unit Setup when using the automatic clock adjustment function. CXProgrammer tab Auto Adjust Time Settings Setting conditions Reference Server specification type IP Address Host name Required. 12-2-3 Auto Adjust Time on page 327 Auto Adjust Time Retry timer Optional Optional (Change when the default setting of 10 seconds is unacceptable.) Optional Required. 3-8 TCP/IP and Link Settings on page 52 Rarely required. (Change when a setting other than the default setting of 53 is required.) Optional (Change when the default setting of 10 seconds is unacceptable.) One or the other is required, depending on the Server specification type setting. Port No. Rarely required. (Change when a setting other than the default setting of 123 is required.) Get the time informa- Required. tion from the SNTP server DNS (See note.) Adjust Time IP Address Port No. Retry timer Note 326 When the Server specification type field in Auto Adjust Time Tab is set to Host name. Using the Automatic Clock Adjustment Function Section 12-2 12-2-3 Auto Adjust Time The contents in the CPU Bus Unit System Setup that are set for using mail send and receive functions are shown in the CX-Programmer’s Edit Parameters Dialog Box. Item Get the time information from the SNTP server Auto Adjust Time Server specification type IP Address Host name Port No. Contents Enable to set the CPU Unit's clock to the time at the SNTP server's clock. The clock can be changed only for the CPU Unit to which the EtherNet/IP Unit or built-in EtherNet/IP port is mounted. Set the time at which the SNTP server is to be accessed to synchronize the clocks. When the time that is set here arrives, the SNTP server is accessed and the CPU Unit clock is adjusted to match the SNTP server clock. Select whether the SNTP server used for automatic clock adjustment is to be specified by IP address or by host domain name (i.e., by host name). Set the IP address for the SNTP server that is to be used for automatic clock adjustment. This setting is enabled only when server specification by IP address has been selected. Set the host domain name (i.e., the host name) for the SNTP server that is to be used for automatic clock adjustment. This setting is enabled only when server specification by host name has been selected. Set the port number for connecting to the SNTP server that is to be used for automatic clock adjustment. This setting does not normally need to be changed. Default Not selected (disabled) 0:0:0 IP Address 0.0.0.0 None 0 (Number 123 is used.) 327 Section 12-3 Automatic Clock Adjustment Switch Item Contents Retry timer Default Set the time to elapse before retrying when a connec- 0 tion to the SNTP server fails. This setting does not (10 s) normally need to be changed. This sets in the CPU Unit's clock data the time differ- +0:0 ence made up from the SNTP server's clock data. To use the clock data from the SNTP server just as it is, input 0. Adjust Time 12-3 Automatic Clock Adjustment Switch The Automatic Clock Adjustment Switch is allocated in the CIO Area as shown below. The first word n of the CIO Area is calculated using the following equation. n = CIO 1500 + (25 × unit number) Automatic Clock Adjustment Switch (Bit 05 of n) The Unit control bit is shown in the following diagram. 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 n Automatic Clock Adjustment Switch When the Automatic Clock Adjustment Switch turns from OFF to ON, the EtherNet/IP Unit or built-in EtherNet/IP port obtains the clock data from the SNTP server on the network, and applies it to the local CPU Unit. After applying the data, the switch automatically turns OFF again. 12-4 Automatic Clock Adjustment Error Processing 12-4-1 Automatic Clock Adjustment (SNTP) Errors The following table shows the main causes and remedies for errors that occur in the automatic clock adjustment function (SNTP). Cause SNTP, DNS server address not set Correction Reset each server address (IP address or host name). SNTP, DNS server communications time- Inspect the communications path (Etherout Net/IP Unit or built-in EtherNet/IP port, cable connections, hub, router, server), and correct the situation that is causing the error. CPU Unit internal clock could not be set The automatic clock adjustment function is not supported by certain CPU Units (models, lot numbers) if they are in RUN or MONITOR mode. 12-4-2 Error Log Error Codes for the Automatic Clock Adjustment Function When an error occurs while the EtherNet/IP Unit or built-in EtherNet/IP port is operating, the error code, detailed error code, and time the error occurred are saved in the error log. The following table provides a list of the error codes. 328 Section 12-4 Automatic Clock Adjustment Error Processing The error log can be read by sending FINS commands to the EtherNet/IP Unit or built-in EtherNet/IP port or by using the mail receive function and specifying the ErrorLogRead command. Error code 03C1 03C4 03C6 Meaning Detailed error code 1st byte 2nd byte Server set- 00H: DNS 01: IP address ting error 03H: 02: Host name SNTP 04H: FTP 03: Port number 04: Other 06H: parameters BOOTP 07H: SNMP 08H: SNMP Trap 09H: FINS/ UDP 0AH: FINS/ TCP Server 00H: DNS 01: Specified host does not connection 03H: exist error SNTP 04H: FTP 02: No service 06H: at specified host BOOTP 03: Timeout 07H: 04: Closed uniSNMP laterally by host 08H: SNMP 05: Cannot conTrap nect because account information does not match 06: Host name resolution error 07: Transmission error 08: Reception error 09: Other error 0AH: Error in obtained IP address Clock data 0001: Clock data could not write error be refreshed because of a CPU Unit error. 0002: Clock data could not be refreshed because the CPU Unit could not write clock data in that operation mode. Correction Set the server settings correctly based on the information in the detailed error code. EEPROM --- Take either of the --following measures. • Correct the settings for each server. • Inspect the communications path (EtherNet/ IP Unit or built-in EtherNet/IP port), cable connections, hub, router, server), and correct the situation that is causing the error. Clear the CPU Unit error. --- --The automatic clock adjustment function is not supported by certain CPU Units (models, lot numbers) if they are in RUN or MONITOR mode. (See note.) 329 Section 12-4 Automatic Clock Adjustment Error Processing Note (1) For details on other error log information, refer to the Operation Manual, Construction of Networks: SECTION 14 Troubleshooting and Error Processing. (2) An error will occur in the following CPU Units when the automatic clock adjustment function is executed under the conditions shown in the table. CPU Unit CPU Units manufactured on or before January 31, 2003 (lot numbers 030131 or earlier): CJ1G-CPU@@H CJ1H-CPU@@H CS1G-CPU@@H CS1H-CPU@@H Conditions When the CPU execution mode is set to other than normal mode (priority peripheral servicing mode, parallel processing with synchronous memory access mode, or parallel processing with asynchronous memory access mode). AND When the CPU Unit operating mode is set to RUN or MONITOR mode. (3) The manufacturing date can be determined from the lot number on the side or top corner of the CPU Unit. (4) The lot numbers are as follows: YYMMDDnnnn, in which YY indicates the last two digits of the year, MM the month, DD the day, and nnnn the serial number. 330 SECTION 13 Maintenance and Unit Replacement This section describes cleaning, inspection, and Unit replacement procedures, as well as the Simple Backup Function. 13-1 Maintenance and Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332 13-1-1 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332 13-1-2 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332 13-1-3 Unit Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332 13-2 Simple Backup Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333 13-3 Using the Backup Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336 331 Section 13-1 Maintenance and Replacement 13-1 Maintenance and Replacement This section describes the routine cleaning and inspection recommended as regular maintenance, as well as the Unit replacement procedure required if an EtherNet/IP Unit needs to be replaced. 13-1-1 Cleaning Clean the EtherNet/IP Unit regularly as described below in order to keep the network in its optimal operating condition. • Wipe the Unit daily with a dry, soft cloth. • When a spot can’t be removed with a dry cloth, dampen the cloth with a neutral cleanser (2% solution), wring out the cloth, and wipe the Unit. • A smudge may remain on the Unit from gum, vinyl, or tape that was left on for a long time. Remove the smudge when cleaning. !Caution Never use volatile solvents such as paint thinner, benzene, or chemical wipes. These substances could damage the surface of the Unit. 13-1-2 Inspection Be sure to inspect the system periodically to keep it in its optimal operating condition. In general, inspect the system once every 6 to 12 months, but inspect more frequently if the system is used with high temperature or humidity or under dirty/dusty conditions. Inspection Equipment Prepare the following equipment before inspecting the system. Normally Required Equipment Have a standard and Phillips-head screwdriver, multimeter, alcohol, and a clean cloth. Occasionally Required Equipment Depending on the system conditions, a synchroscope, oscilloscope, thermometer, or hygrometer (to measure humidity) might be needed. Inspection Procedure Check the items in the following table and correct any items that are below standard. Environmental conditions Installation Item Ambient and cabinet temperature Ambient and cabinet humidity Standard Inspection 0 to 55°C Thermometer 10 to 90% (with no condensa- Hygrometer tion or icing) Dust/dirt accumulation None Visual Are the Units installed securely? No looseness Phillips-head screwdriver Are the Ethernet cable connectors No looseness Visual fully inserted and locked? 13-1-3 Unit Replacement Procedure Replace a faulty EtherNet/IP Unit as soon as possible. If the built-in EtherNet/ IP port is faulty, replace the CPU Unit as soon as possible. We recommend having spare Units available to restore network operation as quickly as possible. Precautions Observe the following precautions when replacing a faulty Unit. • After replacement, verify that there are no errors with the new Unit. • When a Unit is being returned for repair, attach a sheet of paper detailing the problem and return the Unit to your OMRON dealer. 332 Section 13-2 Simple Backup Function • If there is a faulty contact, try wiping the contact with a clean, lint-free cloth dampened with alcohol. Note Settings Required after Unit Replacement To prevent electric shock when replacing a Unit, always stop communications in the network and turn OFF the power supplies to all of the nodes before removing the faulty Unit. After a Unit has been replaced, verify that the following steps have been made correctly. • Set the node address and unit number. • Connect the Ethernet cable. • Set the configuration data (parameter settings) again and download them. 13-2 Simple Backup Function Overview The simple backup function can be used to back up not only all of the data in the CPU Unit, but also all of the data stored in memory in the EtherNet/IP Unit or data for the built-in EtherNet/IP port. All of this data will automatically be backed up to the Memory Card. The simple backup function can be used for the following EtherNet/IP Units and built-in EtherNet/IP port. • CS-series EtherNet/IP Unit (CS1W-EIP21) mounted to a CS1D/CS1H CPU Unit • CJ-series EtherNet/IP Unit (CJ1W-EIP21) mounted to a CJ1-H/CJ1M/ CJ2H-CPU@@-EIP CPU Unit • A built-in EtherNet/IP port on a CJ2H-CPU@@-EIP/CJ2M-CPU3@ CPU Unit When the EtherNet/IP Unit’s setup data is written to the Memory Card using a simple backup operation, it is stored in the Memory Card as a Unit/Board backup file with the file name BACKUP@@.PRM. (The @@ digits in the backup file name indicate the unit address of the EtherNet/IP Unit or built-in EtherNet/IP port, which is the unit number + 10 hex.) This backup file is also used when reading data from the Memory Card or comparing data with a file in the Memory Card. EtherNet/IP Unit CPU Unit Memory Card Power Supply Switch All data All setup data Note • Backup • Restore • Compare Memory Card The following table shows the Units that support the simple backup function. Confirm that the Units being used support the function. CPU Unit EtherNet/IP Unit CS1W-EIP21 CS1D CS1-H Yes Yes CJ1W-EIP21 ----- 333 Section 13-2 Simple Backup Function CPU Unit EtherNet/IP Unit CS1W-EIP21 CS1 CJ1-H CJ1 CJ1M CJ2H CJ2M CJ1W-EIP21 No ----------- --Yes No Yes Yes Yes Applications Use the simple backup function when creating a backup data file for the entire PLC (including the CPU Unit, EtherNet/IP Units, built-in EtherNet/IP port, and Serial Communications Units/Boards), or when replacing all the Units. Backup Sources and Restore Targets The data that was backed up with the simple backup function can be restored to Units or built-in ports as shown in the following table. Network Configuration designations are given for the model numbers and versions of the backup sources and restore targets. The model number must be the same for both the backup source and restore target. The CIP revision must be the same or higher. Restore target Backup source CS1W-EIP21, CJ1W-EIP21 Rev. 1.1 CS1W-EIP21, CJ1W-EIP21 Rev. 2.1 CJ2B-EIP21 Rev. 2.1 CJ2M-EIP21 Rev. 2.1 CJ1W-EIP21 (CJ2) Rev. 2.1 Note CS1W-EIP21 CJ1W-EIP21 Rev. 1.1 Rev. 2.1 Yes Yes (See note 1.) No Yes CJ2B-EIP21 CJ2M-EIP21 Rev. 2.1 No Rev. 2.1 No CJ1W-EIP21 (CJ2) Rev. 2.1 No No No No No No Yes No No No No No Yes No No No No No Yes (1) Functions added for revision 2.1 will be set to their default settings. The number of settings will be increased, so an error will occur in the comparison after data is restored. (2) Data backed up for revision 1.1 using a simple backup can be restored to an EtherNet/IP Unit or built-in EtherNet/IP port with revision 2.1, but an error will occur in the comparison. When changing the unit version, refer to 6-2-18 Changing Devices for information on the Network Configurator device change function. Operating Methods Backing Up EtherNet/IP Unit or Built-in EtherNet/IP Port Setup Files to the Memory Card Set pins 7 and 8 of the DIP switch on the front panel of the CPU Unit as shown in the following table, and press the Memory Card Power Supply Switch for 3 seconds with the Memory Card inserted into the slot. Release the switch when the BUSY indicator lights. SW7 SW8 334 DIP switch settings ON OFF Section 13-2 Simple Backup Function EtherNet/IP Unit CPU Unit Memory Card Power Supply Switch All data Memory Card All setup data Backup This operation will create an EtherNet/IP Unit or built-in EtherNet/IP port settings file, and write that file to the Memory Card along with the other backup files. When the Memory Card Power Supply Switch is pressed, the MCPWR indicator on the front of the CPU Unit will flash once and then remain lit while data is being written. If the data is written normally, the MCPWR indicator will turn OFF. The BUSY indicator will flash while the data is being written. Note The backup operation will fail if it is performed after the device parameters were not downloaded successfully from the Network Configurator or CX-Programmer. Perform the backup operation only if the device parameters were downloaded normally. Restoring the EtherNet/IP Unit or Built-in EtherNet/IP Port Setup File from the Memory Card (Reading and Setting the Data in the Unit) Set pins 7 and 8 of the DIP switch on the front panel of the CPU Unit, as shown in the following table, and turn the power to the CPU Unit OFF and then ON again with the Memory Card inserted into the slot. SW7 SW8 DIP switch settings ON OFF EtherNet/IP Unit CPU Unit Power ON All data Memory Card All setup data Restore This operation will read the EtherNet/IP Unit or built-in EtherNet/IP port setup data file from the Memory Card and restore the data in the EtherNet/IP Unit or built-in EtherNet/IP port. When the power supply is ON, the MCPWR indicator on the front of the CPU Unit will turn ON, flash once, and then remain lit while data is being read. The BUSY indicator will flash while data is being read. After the data has been read correctly, the MCPWR and BUSY indicators will turn OFF. If the MCPWR indicator flashes five times or if only the BUSY indicator turns OFF, it means that an error has occurred. Note If the restoration from the Memory Card fails, an “H8” error will be displayed on the 7-segment display on the front panel. If this happens, the data on the Memory Card may not be correct. Confirm that the backup operation was completed normally before performing the restore operation. 335 Section 13-3 Using the Backup Tool Comparing EtherNet/IP Unit or Built-in EtherNet/IP Port Data with the Setup File in the Memory Card Set pins 7 and 8 of the DIP switch on the front panel of the CPU Unit, as shown in the following table, and press down the Memory Card Power Supply Switch for 3 seconds. SW7 SW8 DIP switch settings OFF OFF EtherNet/IP Unit Memory Card Power Supply Switch CPU Unit All data Memory Card All setup data Compare This operation will compare the data in the EtherNet/IP Unit or built-in EtherNet/IP port setup file in the Memory Card with the device parameters in the EtherNet/IP Unit or built-in EtherNet/IP port. When the Memory Card Power Supply Switch is pressed, the MCPWR indicator on the front of the CPU Unit will flash once, and then remain lit while data is being compared. The BUSY indicator will flash while data is being compared. If the data matches, the MCPWR and BUSY indicators will turn OFF. If the MCPWR and BUSY indicators both flash, it means that the data does not match or that an error has occurred. Note Data backed up for revision 1.1 using a simple backup can be restored to an EtherNet/IP Unit or built-in EtherNet/IP port with revision 2.1, but an error will occur in the comparison. When changing the unit version, refer to 6-2-18 Changing Devices for information on the Network Configurator device change function. 13-3 Using the Backup Tool Overview The PLC Backup Tool of the CX-Programmer can be used to back up, compare, and restore data for all Units or only specified Units in the PLC that is connected online. Specified backup folder PLC Backup Tool Default folder: C:\Backup\yymmdd_hhmmss CJ2 CPU Unit with Configuration Units (CPU Bus Units and Special I/O Units) Restore/compare Back up 336 Section 13-3 Using the Backup Tool Usage The PLC Backup Tool can be used for the following: • Backing up all data in a PLC • Comparing all of the data in a PLC with data that was previously backed up in the computer • Using the restore function to transfer all of the PLC data to a system with the same configuration • Transferring data to a new Unit after replacing a faulty Unit Procedure Select PLC Backup Tool from the CX-Programmer's Tool Menu. You can also select OMRON - CX-One - CX-Programmer - PLC Backup Tool from the Windows Start Menu. Backup Menu Button Backup from PLC Compare Restore to PLC Function Click this button to back up data. All of the data in the target PLC will be backed up to the computer. Click this button to compare data. The data in the PLC can be compared to the data in a backup file or the data in two backup files can be compared. Any differences will be displayed. Click this button to restore data. The data in a backup file will be transferred to the PLC to restore the status that existed when the data was backed up. Communications Settings Button Communications Settings Function Click this button to set communications conditions for the target PLC. The current PLC model and network type will be displayed. Refer to the CX-Programmer Operation Manual for detailed procedures. 337 Using the Backup Tool 338 Section 13-3 SECTION 14 Troubleshooting and Error Processing This section describes error processing, periodic maintenance operations, and troubleshooting procedures needed to keep the EtherNet/IP network operating properly. We recommend reading through the error processing procedures before operation so that operating errors can be identified and corrected more quickly. 14-1 Checking Status with the Network Configurator . . . . . . . . . . . . . . . . . . . . . . 340 14-1-1 The Network Configurator’s Device Monitor Function . . . . . . . . . . 340 14-2 Using the LED Indicators and Display for Troubleshooting . . . . . . . . . . . . . 347 14-2-1 Errors Occurring at the EtherNet/IP Unit or Built-in EtherNet/IP Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347 14-3 Connection Status Codes and Error Processing . . . . . . . . . . . . . . . . . . . . . . . 358 14-4 Error Log Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 14-4-1 Error Log Data Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 14-4-2 Error Log Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 14-4-3 FINS Commands for Error Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 14-4-4 Error Log Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365 14-5 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368 14-5-1 CPU Unit's ERR/ALM Indicator Lit or Flashing . . . . . . . . . . . . . . . 368 14-5-2 General Ethernet Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369 14-5-3 Tag Data Links Fail to Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369 14-5-4 Tag Data Link Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 14-5-5 Message Timeout Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 371 14-6 Troubleshooting with FINS Response Codes . . . . . . . . . . . . . . . . . . . . . . . . . 371 339 Checking Status with the Network Configurator Section 14-1 14-1 Checking Status with the Network Configurator 14-1-1 The Network Configurator’s Device Monitor Function Connect the Network Configurator online, select the device to be checked, right-click to display the pop-up menu, and select Monitor. The Monitor Device Dialog Box will be displayed. Note Status 1 Tab Page If a communications error occurs during monitoring, the dialog box will continue to show the last information that was collected. To start monitoring again, close the Monitor Device Dialog Box, and then open the dialog box again. The information displayed on the Status 1 Tab Page shows the status of the flags in the following allocated CIO Area words: Unit status 1, Unit status 2, Communications status 1, Communications status 2, and Communications status 3. There will be a check mark in the box when the corresponding flag is ON. In addition, the Target Node Status Field shows the connection status of the target nodes that are connected with the EtherNet/IP Unit as the tag data link originator. The icon will be blue if the connection is normal, or red if an error occurred. 340 Checking Status with the Network Configurator Status 2 Tab Page Section 14-1 The Status 2 Tab Page’s Target PLC Status Field shows the status of the target node PLCs that are connected with the EtherNet/IP Unit as the tag data link originator. The icon will be blue if the CPU Unit is in RUN mode or MONITOR mode, gray if it is in PROGRAM mode, or red if an error occurred. The Connected Status of FINS/TCP Connections Field shows the status of FINS/TCP connections. There will be a check mark in the box when the corresponding connection is established (connected). 341 Checking Status with the Network Configurator Note 342 Section 14-1 The target PLC status is can be used when the PLC status is selected for all the target sets for both originator and target connections. For those that are not selected, the status will be grayed-out. Checking Status with the Network Configurator Connection Tab Page Section 14-1 The Connection Tab Page’s Target Node Status Field shows the connection status of the target nodes that are connected with the EtherNet/IP Unit as the tag data link originator. The icon will be blue if the connection is normal, or red if an error occurred. In addition, the Connection Status Area shows the current status each connection that is set as the originator. This information can be used to identify the cause of tag data link errors. For details on the connection status, refer to 14-3 Connection Status Codes and Error Processing. 343 Checking Status with the Network Configurator Error History Tab Page Section 14-1 The Error History Tab Page displays the error log stored in the EtherNet/IP Unit or built-in EtherNet/IP port. Errors that occurred in the past are recorded, and can be cleared or saved in a computer file as required. In some cases, error records are cleared when the power is turned OFF, and in other cases the records are retained. For details on the error log, refer to 14-4 Error Log Function. Controller Error History Tab Page 344 The error history of the CPU Unit for the EtherNet/IP Unit or built-in EtherNet/ IP port is displayed on this tab page. The error history shows errors that have occurred. It can be cleared or saved in a file in the computer. Section 14-1 Checking Status with the Network Configurator Refer to the operation manual of the CPU Unit for details on error information. Tag Status Tab Page This tab page shows if the tag settings for each tag for tag data links is set so that data can be exchanged with the CPU Unit. The following status is displayed. Ok: Data was exchanged normally. Processing to solve: The symbol or I/O memory address for the tag is being resolved. When the resolution is completed normally, a connection will be established and the data exchange will start. Area type error: The area (e.g., EM bank) specified by the tag setting does not exist in the CPU Unit. A connection will not be established for a tag for which this error occurs. Out of address range: The area specified by the tag setting is outside of the area address range in the CPU Unit. A connection will not be established for a tag for which this error occurs. Size error: Different sizes are set for the network symbol and the tag settings. Connections will not be opened for tags with this error. Not exist: A network symbol is not set in the symbol table in the CPU Unit for the specified tag setting. A connection will not be established for a tag for which this error occurs. PLC I/F error: There is a problem in the bus interface with the CPU Unit. Determine the cause based on the indicators and the error log. 345 Checking Status with the Network Configurator Section 14-1 If the status is not “OK,” check the tag data link settings or the network symbol settings in the symbol table in the CJ2 CPU Unit. 346 Using the LED Indicators and Display for Troubleshooting Ethernet Information Tab Page Section 14-2 The Ethernet Information Tab Page shows the communications status at the communications driver level. The error counter information can be used to confirm whether communications problems have occurred. The tag data link information can be used to confirm characteristics such as the bandwidth usage (pps). 14-2 Using the LED Indicators and Display for Troubleshooting 14-2-1 Errors Occurring at the EtherNet/IP Unit or Built-in EtherNet/IP Port Errors Related to CPU Unit Data Exchange MS Indicator NS 7-segment The 7-segment display alternates between the node address and error code. Error Cause Unit operation (Flag status) Flashing red Not lit H1 Duplicate unit number Operation stops. The same unit number is set on another Unit. Flashing red Not lit H2 CPU Unit faulty --- Operation stops. Error Countermeasure log (hex) --Set the unit numbers correctly and restart the EtherNet/IP Unit or builtin EtherNet/IP port. --Replace the CPU Unit if the error recurs when the CPU Unit is restarted. 347 Section 14-2 Using the LED Indicators and Display for Troubleshooting MS Indicator NS 7-segment Error Cause Error log (hex) Countermeasure Operation stops. --- Replace the EtherNet/IP Unit or (for a built-in EtherNet/IP port) the CPU Unit if the error recurs when the Unit is restarted. Set the node address correctly and restart the EtherNet/IP Unit or built-in EtherNet/IP port. Replace the CPU Unit if the error recurs when the CPU Unit is restarted. Create the I/O table. Lit red Not lit H3 EtherNet/IP Unit or built-in EtherNet/IP port faulty Flashing red Not lit H4 Node address The node setting error address set on the switches is invalid (00 or FF.) Operation stops. --- Flashing red Not lit H6 CPU Unit faulty Records the error in the error log (time/ date all zeroes). Operation stops. 000F Flashing red Not lit H7 I/O table not registered Operation stops. 0006 Flashing red --- H8 The CPU Unit’s I/O table is not registered. Simple backup The simple backup funcfunction tion’s data restorestore error ration failed. Flashing red --- H9 I/O bus error 348 --- Unit operation (Flag status) --- --The settings of the EtherNet/IP Unit or built-in EtherNet/IP port are all cleared, unless the backup file does not exist, a Memory Card is not mounted, or the PLC model does not match. An error • If the Unit is the orig- 000E occurred while inator of the tag data exchanging data link connection, it with the CPU stops communicaUnit. tions. • If the Unit is the target of the tag data link connection and the PLC status is included in the communications data, the corresponding Target Node PLC Error Flag will be turned ON. Perform the simple backup operation again. If the error recurs, replace the Memory Card, or EtherNet/IP Unit, or (for a built-in EtherNet/IP port) the CPU Unit. Check and correct the CPU Unit’s operating environment. Section 14-2 Using the LED Indicators and Display for Troubleshooting MS Flashing red Indicator NS 7-segment --- HA Error Cause Unit operation (Flag status) Error log (hex) Countermeasure CPU Unit memory error A parity error occurred during an operation such as reading the routing tables. Records the error in the error log. If the routing tables were being read, the routing tables are treated as missing. 0012 Register the routing tables in the CPU Unit again and restart the CPU Unit. Replace the CPU Unit if the error recurs. Download the tag data to the CPU Unit again. Replace the CPU Unit if the error recurs. 0017 A memory error • If a symbol (tag has occurred for name) is specified in the tag data link or the tag database in the CPU Unit Status Area, refreshing the userUnit (CJ2H/ specified status area CJ2M CPU Unit is stopped and tag only). data links will operate as follows: • Tag data link communications will be stopped for originator connections. • Communications will continue for target connection. If PLC status is included in the communications data, the target node PLC error flag for the relevant target node will be turned ON. Note Recovery is possible from this error. If recovery is achieved, the tag data links will be restarted to return to normal status. Flashing red Not lit Hb CPU Unit event servicing timeout Flashing red --- HC Routing table error Flashing red --- Hd I/O refresh error A timeout occurred during an operation such as reading the routing tables to the CPU Unit. There is a logic error in the routing table settings. The EM Area bank in which the device parameters were set was converted to file memory while the tag data link was operating. Operation stops. 0011 The Unit continues operating without the routing tables. 021A Tag data is not refreshed if it is assigned to a nonexistent area. Note: Recovery is possible for this error. 0347 Replace the EtherNet/IP Unit or (for a built-in EtherNet/IP port) the CPU Unit. if the error recurs when the Unit is restarted. Create the routing tables again. Stop using the EM Area bank (in which the device parameters were set) as file memory, or correct the device parameters. 349 Section 14-2 Using the LED Indicators and Display for Troubleshooting MS Indicator NS 7-segment Error Flashing red --- HE CPU Unit service monitoring error Flashing red --- HF CPU Unit watchdog timer error 350 Cause Unit operation (Flag status) Error log (hex) • If the Unit is the orig- 0002 Servicing from inator of the tag data the CPU Unit link connection, it was not completed within the stops communications. fixed interval. The monitoring • If the Unit is the tartime is normally get of the tag data 11 s. link connection and the PLC status is included in the communications data, the corresponding Target Node PLC Error Flag will be turned ON. Note: Recovery is possible for this error. When operation is restored, tag data link startup processing will be performed and operations will return to normal. An error • If the Unit is the orig- 0001 occurred in the inator of the tag data CPU Unit. link connection, it stops communications. • If the Unit is the target of the tag data link connection and the PLC status is included in the communications data, the corresponding Target Node PLC Error Flag will be turned ON. Countermeasure Check and correct the CPU Unit’s operating environment. Replace the CPU Unit. Using the LED Indicators and Display for Troubleshooting Errors Related to the CPU Unit MS Indicator NS 7-segment The 7-segment display alternates between the node address and error code. Error Cause Flashing red --- HH CPU Unit Fatal Error A fatal error occurred in the CPU Unit. --- --- --- Output OFF Error An Output OFF (output inhibit) condition occurred in the CPU Unit. Errors Related to the Control Bits MS --- Indicator NS 7-segment --- C6 Section 14-2 Error Countermeasure log (hex) • If the Unit is the orig- 0015 Eliminate the cause of the error inator of the tag data in the CPU Unit. link connection, it stops communicaThe tag data link tions. will restart auto• If the Unit is the tarmatically when the get of the tag data cause of the error link connection and is eliminated. the PLC status is included in the communications data, the corresponding Target Node PLC Error Flag will be turned ON. --Turn OFF the CPU The tag data link’s Unit’s Output OFF send data will be Bit (A50015). The cleared to 0 in accortag data link’s send dance with the Output data will be OFF settings, and restored automatidata transfer will concally when this bit tinue with that data. is turned OFF. Unit operation (Flag status) The 7-segment display alternates between the node address and error code. Error Multiple Switches ON Cause Unit operation (Flag status) Error Countermeasure log (hex) Execute control bit The error code will be --Two or more displayed on the 7operations one at a software segment display for time. switches were 30 seconds, and the ON simultaMultiple Switches ON neously, or a Error Flag (n+11, bit second software switch was 14) will go ON. turned ON The error display will before a prior be cleared the next operation was time that a settings completed. operation is completed normally. 351 Section 14-2 Using the LED Indicators and Display for Troubleshooting Errors Related to the Tag Data Links MS Indicator NS 7-segment The 7-segment display alternates between the node address and error code. Error Cause Unit operation (Flag status) Error log (hex) --Not record ed for version 2.0 or higher --- --- d5 Verification Error (target non-existent) The target registered in the device parameters does not exist. The Unit will periodically attempt to reconnect to the target. The Verification Error Flag (n+12, bit 00), Unit Error Occurred Flag (n+10, bit 00), and Network Error Occurred Flag (n+10, bit 01) will go ON. --- --- d6 Connection Failed The Unit will periodi- 03D4 cally attempt to reconnect to the target. The Verification Error Flag (n+12, bit 00) and Unit Error Occurred Flag (n+10, bit 00) will go ON. --- --- d9 Tag Data Link Error The connection could not be established because device parameters (such as the variable name and size) did not match in the originator and target, or connection resources are insufficient. A timeout occurred in the tag data link. (Tag data was not received from the target within the specified timeout time.) 352 The Unit will periodi- 03D5 cally attempt to reconnect to the target where the error occurred. The Tag Data Link Error Flag (n+12, bit 02), Unit Error Occurred Flag (n+10, bit 00), and Network Error Occurred Flag (n+10, bit 01) will go ON. Countermeasure Check the following items: • Is the registered node’s power supply ON? • Is the cable connected? • Is the cable damaged or loose? • Is there excessive noise? Correct the device parameter settings, and download the device parameters again from the Network Configurator. Check the following items: • Is the registered node’s power supply ON? • Is the cable connected? • Is the cable damaged or loose? • Is there excessive noise? Using the LED Indicators and Display for Troubleshooting Errors Related to Memory Access MS Flashing red Indicator NS 7-segment --- E9 Section 14-2 The 7-segment display alternates between the node address and error code. Error Memory Access Error Error Countermeasure log (hex) 0602 Download the Unit Case 1: An error Setup from the tab occurred in the The error record pages of the Edit Unit's non-vola- remains in RAM only. Parameters Dialog Subsequent writes to tile memory Box of the CX-Proitself. This error non-volatile memory grammer and will occur in the are all ignored. Other download the following cases. than that, normal device parameters operation continues. 1. An error ocfrom the Network curred while (Error records conConfigurator. If the tinue to be written to writing the ererror recurs, RAM.) ror log. replace the EtherCase 2: 2. An error ocNet/IP Unit or (for a curred while Tag data links and built-in EtherNet/IP message communicawriting the port) the CPU Unit. tions will continue device paoperating. rameters. The Unit Error Note: This error does Occurred Flag (n+10, bit 00), Unit Memory not indicate checksum errors Error Flag (n+10, bit 04), and Non-volatile detected when Memory Error Flag reading data. (n+14, bit 15) will turn ON. Cause Unit operation (Flag status) 353 Section 14-2 Using the LED Indicators and Display for Troubleshooting MS Indicator NS 7-segment Error Cause Unit operation (Flag status) Error log (hex) 021A There is an error in the parameter settings stored in the Unit’s non-volatile memory. (An error can occur when power is interrupted while data is being written to non-volatile memory.) The Unit Error Occurred Flag (n+10, bit 00) and Invalid Communications Parameter Flag (n+12, bit 04) will go ON. Flashing red --- E8 Device Param- The I/O Area set eters Error in the device parameters does not exist in the CPU Unit, or the EM Area was converted to file memory. A checksum error or logic error was detected in the parameters. The Unit was mounted to a different PLC (e.g., from CJ1 to CJ2) after the Unit settings were made. Flashing red --- EA IP Advanced Settings Error 03D1 Flashing red --- F2 Ethernet Basic Settings Error 03D0 354 Countermeasure Download the Unit Setup from the tab pages of the Edit Parameters Dialog Box of the CX-Programmer and download the device parameters from the Network Configurator. If the error recurs, replace the EtherNet/IP Unit or (for a built-in EtherNet/IP port) the CPU Unit. If the ladder program uses the OUT instruction to turn ON the CPU Bus Unit Restart Bit, change the OUT instruction to the SET instruction and download the parameters again. Identify the error log data, correct the settings, and then download the Unit Setup from the tab pages of the Edit Parameters Dialog Box of the CX-Programmer Download the settings from the TCP/ IP or Ethernet Tab Pages of the Edit Parameters Dialog Box of the CX-Programmer or download the TCP/IP settings from the Network Configurator. Using the LED Indicators and Display for Troubleshooting Errors Related to the Network MS --- Indicator NS 7-segment --- E1 Section 14-2 The 7-segment display alternates between the node address and error code. Error Ethernet Link Not Detected Cause Unit operation (Flag status) The link with the • The Unit will be offline and unable to switching hub communicate. Errors could not be will be returned to all detected. Note This error communications requests. will not • Data exchanges occur (refreshing) will conwhen tinue with the CPU data links Unit. are not set for The Unit Error version Occurred Flag (n+10, 2.0 or bit 00), Network Error higher. Occurred Flag (n+10, bit 01), and Link OFF Error Flag (n+10, bit 09) will go ON. The Link Status Flag (n+13, bit 14) will go OFF. Error Countermeasure log (hex) 03D3 Check the following items: • Is the cable connected? • Is the cable damaged or loose? • Is there excessive noise? 355 Section 14-2 Using the LED Indicators and Display for Troubleshooting MS --- Indicator NS 7-segment --- E3 Error Server Connection Error Cause Unit operation (Flag status) Error log (hex) Countermeasure An error occurred in communications with the DNS server. The DNS Server Error Flag (n+14, bit 05) will turn ON. 03C4 Details: 00xx An error occurred with the BOOTP server. 1. There was no response from the BOOTP server. 2. The BOOTP server attempted to set an invalid IP address in the EtherNet/ IP Unit or built-in EtherNet/IP port. Case 1: The Unit will continue sending requests to the BOOTP server until there is a response. In the meantime, the Unit will be offline and unable to communicate. Errors will be returned to all communications requests. Data exchanges (refreshing) will continue with the CPU Unit. Case 2: The Unit will operate with the default IP address (192.168.250.node_ address). The Unit Error Occurred Flag (n+10, bit 00), Network Error Occurred Flag (n+10, bit 01), and BOOTP Server Error Flag (n+14, bit 10) will go ON. The SNTP Server Error Flag (n+14, bit 11) will turn ON. 03C4 Details: 06xx Perform one of the following: • Correct the DNS server settings. • Check the communications path (EtherNet/IP Unit or built-in EtherNet/IP port, cable connections, hubs, routers, and servers) and correct any problems. Perform one of the following: • Correct the BOOTP server settings. • Check the communications path (EtherNet/IP Unit or built-in EtherNet/IP port, cable connections, hubs, routers, and servers) and correct any problems. An error occurred in communications with the STNP server. 356 03C4 Details: 03xx Perform one of the following: • Correct the SNTP server settings. • Check the communications path (EtherNet/IP Unit or built-in EtherNet/IP port, cable connections, hubs, routers, and servers) and correct any problems. Section 14-2 Using the LED Indicators and Display for Troubleshooting MS Indicator NS 7-segment Error Cause Unit operation (Flag status) Error log (hex) Countermeasure --- 03C4 Details: 07xx Perform one of the following: • Correct the SNMP trap settings. • Check the communications path (EtherNet/IP Unit or built-in EtherNet/IP port, cable connections, hubs, routers, and servers) and correct any problems. Check the IP addresses set on other nodes. Restart the EtherNet/IP Unit or builtin EtherNet/IP port after correcting the IP address settings to eliminate duplications. --- --- E3 Server Connection Error An error occurred in transmission to the SNMP trap. --- Lit red F0 IP Address Duplication Flashing red --- F3 Address mismatch 0211 The IP address • The Unit will be offline and unable to of the EtherNet/ IP Unit or built-in communicate. Errors EtherNet/IP port will be returned to all is the same as communications requests. the IP address set for another • Data exchanges node. (refreshing) will continue with the CPU Unit. The Unit Error Occurred Flag (n+10, bit 00), Network Error Occurred Flag (n+10, bit 01), and IP Address Duplication Error Flag (n+10, bit 06) will go ON. --• Operation will conThe target IP address conver- tinue with the set IP address as the local sion method is set to Automatic IP address. The Address Misgeneration, but match Flag (n+14, the last byte of bit 14) will turn ON. the local IP address does not match the value set on the Node Address Setting Switch. Check the IP address and the Node Address Setting Switch setting. 357 Section 14-3 Connection Status Codes and Error Processing MS Indicator NS 7-segment Flashing red Not lit F4 Flashing red --- C8 Lit red Unit operation (Flag status) Error log (hex) 020F • The Unit will be An error offline and unable to occurred in the communicate. Errors Communicawill be returned to all tions Controller communications in the EtherNet/ IP Unit or built-in requests. EtherNet/IP • Data exchanges port. (refreshing) will continue with the CPU Unit. The Unit Error Occurred Flag (n+10, bit 00), Network Error Occurred Flag (n+10, bit 01), and Communications Controller Error Flag (n+10, bit 05) will go ON. Node Address The Node Operation will con--Setting Address Setting tinue. The IP Address Changed Dur- Switch was ing Operation changed during Changed During Operation Flag (n+11, operation. bit 02) will turn ON. Indicator NS 7-segment Not lit Cause Communications Controller Error Errors Related to the Unit MS Error --- Countermeasure Replace the EtherNet/IP Unit or (for the built-in EtherNet/IP port) the CPU Unit if the error recurs when the Unit is restarted. Restart the EtherNet/IP Unit or builtin EtherNet/IP port after setting the correct node address. The 7-segment display alternates between the node address and error code. Error Special Unit Error Cause An error occurred in a Special I/O Unit or CPU Bus Unit. Unit operation (Flag status) Records the error in the error log. Operation stops. Error Countermeasure log (hex) 0601 Restart the CPU Unit. Replace the EtherNet/IP Unit or (for the built-in EtherNet/IP port) the CPU Unit if the error recurs. 14-3 Connection Status Codes and Error Processing This section explains how to identify and correct errors based on the tag data link’s connection status. The connection status can be read using the Connection Tab Page of the Network Configurator’s Monitor Device Window. For details, refer to 14-1-1 The Network Configurator’s Device Monitor Function. Note 1. The connection status has the same meaning as the Connection Manager’s General and Additional error response codes, as defined in the CIP specifications. 2. The Open DeviceNet Vendor Association, Inc. (ODVA) can be contacted at the following address to obtain a copy of the CIP specifications. ODVA Headquarters 4220 Varsity Drive, Suite A Ann Arbor, Michigan 48108-5006 USA TEL: 1 734-975-8840 FAX: 1 734-922-0027 358 Section 14-3 Connection Status Codes and Error Processing Email odva@odva.org WEB www.odva.org The following table shows the possible originator/target configurations. Configuration Configuration 1 Configuration 2 Configuration 3 Originator CS1W-EIP21, CJ1W-EIP21, CJ2H-CPU@@-EIP, CJ2MCPU3@ CS1W-EIP21, CJ1W-EIP21, CJ2H-CPU@@-EIP, CJ2MCPU3@ Other company’s device Target CS1W-EIP21, CJ1W-EIP21, CJ2H-CPU@@-EIP, CJ2MCPU3@ Other company’s device CS1W-EIP21, CJ1W-EIP21, CJ2H-CPU@@-EIP, CJ2MCPU3@ The following table shows the likely causes of the errors causes for each configuration and connection status (code). Connection status Source of error General Additional Configuration 1 Status Status (hex) (hex) 00 0000 Normal status code: --The connection has been opened and the tag data link is communicating normally. 01 0100 Error code returned from target: This error does Attempted to open multiple con- not occur. nections at the same connection. 01 0103 01 0106 01 0107 01 0108 Handling Configuration 2 Configuration 3 --- --- Depends on the target’s specifications. (Contact the target device’s manufacturer for details on preventing the error from occurring in the future.) Depends on the originator’s specifications. (Contact the originator device’s manufacturer for details on preventing the error from occurring in the future.) Confirm that the originator supports Class 1. Error code returned from target: Attempted to open a connection with an unsupported transport class. Duplicate consumers: Attempted to open multiple connections for single-consumer data. This error does not occur. Confirm that the target supports Class 1. If the tag data link is stopped or started, this error may occur according to the timing, but the system will recover automatically. Depends on the target’s specifications. (Contact the target device’s manufacturer.) If the tag data link is stopped or started, this error may occur according to the timing, but the system will recover automatically. Error code returned from target: Attempted to close a connection, but that connection was already closed. Error code returned from target: Attempted to open a connection with an unsupported connection type. This error does not occur. This error does not occur. This is not an error because the connection is already closed. This error does not occur. Check which connection types can be used by the target. (Contact the manufacturer.) Only multicast and point-to-point can be set. Check which connection types can be used by the originator. (An error will occur if a connection other than multicast or point-to-point is set.) 359 Section 14-3 Connection Status Codes and Error Processing Connection status General Additional Status Status (hex) (hex) 01 0109 01 0110 01 0111 01 0113 01 0114 01 0115 01 0116 01 0117 360 Source of error Configuration 1 Error code returned from target: The connection size settings are different in the originator and target. Error code returned from target: The target was unable to open the connection, because of its operating status, such as downloading settings. Handling Configuration 2 Configuration 3 Check the connection sizes set in the originator and target. Check whether the tag data link is stopped at the target. (Restart the tag data link communications with the control bit.) Error code returned from target: This error does The RPI was set to a value that not occur. exceeds the specifications. Error code generated by origiCheck the connection settings nator or returned from target: (number of conAttempted to open more connections) at the nections than allowed by the specifications (CJ2M: 32, other originator and target. CPU Units: 256). Depends on the target’s specifications. (Contact the target device’s manufacturer.) Check whether the tag data link is stopped at the originator. (Restart the tag data link communications with the control bit.) Check the target’s Set the originator’s RPI setting specifica- RPI setting to 10 tions. seconds or less. Check the connection settings (number of connections) at the originator and target. Check the connection specifications for another company’s devices. Depends on the tarError code returned from target: This error does not occur. get’s specifications. The Vendor ID and Product (Contact the target Code did not match when opendevice’s manufacing connection. turer.) Confirm that the target device’s EDS file is correct. Error code returned from target: This error does Depends on the tarnot occur. get’s specifications. The Product Type did not match (Contact the target when opening connection. device’s manufacturer.) Confirm that the target device’s EDS file is correct. Depends on the tarError code returned from target: Check the major get’s specifications. The Major/Minor Revisions did and minor revi(Contact the target sions set for the not match when opening contarget device and device’s manufacnection. connection. If nec- turer.) essary, obtain the Confirm that the tarEDS file and set it get device’s EDS file again. is correct. Depends on the tarError code returned from target: Check whether The tag set specified in the con- the originator and get’s specifications. (Contact the target nection’s target variables does target tag sets device’s manufacand tags are set not exist. turer.) correctly. CJ2 CPU Units Only: Check symbol settings in the CPU Unit. Check the connection settings (number of connections) at the originator and target. Check the connection specifications for another company’s devices. Check the originator’s connection settings. Check the originator’s connection settings. Check the originator’s connection settings. Check the originator’s connection settings. Check whether the target’s tag sets and tags are set correctly. CJ2 CPU Units Only: Check symbol settings in the CPU Unit. Section 14-3 Connection Status Codes and Error Processing Connection status General Additional Status Status (hex) (hex) Source of error Configuration 1 An unexpected network load may have been received. Use the Network Configurator Device Monitor or the Ethernet Tab Page to check the bandwidth usage, and correct the load. If there are places where broadcast storms occur, such as loop connections in the network connection format, then correct them. Error code returned from target: This error does The RPI was set to a value that not occur. is below the specifications. Handling Configuration 2 An unexpected network load may have been received. Use the Network Configurator Device Monitor or the Ethernet Tab Page to check the bandwidth usage, and correct the load. If there are places where broadcast storms occur, such as loop connections in the network connection format, then correct them. Configuration 3 Follow the operating specifications for the originator. (Consult the originator manufacturer.) 01 011A Error code returned from originator: Connection could not be established because the buffer was full due to high traffic. 01 011B 01 0203 01 0204 Depends on the tar- Set the originator’s get’s specifications. RPI setting to 0.5 ms or greater. (Contact the target device’s manufacturer.) Error code returned from target: Tag data link communications from the target timed out. Check the power supply and cable wiring of the devices in the commuThe connection timed out. nications path, including the target and switches. If performance has dropped due to heavy load, change the performance settings. For example, increase the timeout time or RPI setting. Error code returned from target: There was no response from the target. Check the power supply and cable wiring of the devices in the communications path, The connection-opening proincluding the target and switches. cess timed out. 01 0205 Error code returned from target: This error does There was a parameter error in not occur. the frame used to open the connection. 01 0302 Error occurred at originator or error code returned from target: The tag data link’s allowable bandwidth (pps) was exceeded. 01 0311 Error code returned from target: There was a parameter error in the frame used to open the connection. 01 0312 Error code returned from target: There was a parameter error in the frame used to open the connection. 01 0315 Error code returned from target: This error does There was a parameter error in not occur. the frame used to open the connection. Depends on the target’s specifications. (Contact the target device’s manufacturer.) Check the origina- Check the target’s tor and target con- connection settings nection settings (number of connec(number of contions and RPI). nections and RPI). This error does Depends on the tarnot occur. get’s specifications. (Contact the target device’s manufacturer.) This error does Depends on the tarnot occur. get’s specifications. (Contact the target device’s manufacturer.) Depends on the target’s specifications. (Contact the target device’s manufacturer.) Depends on the originator’s specifications. (Contact the originator device’s manufacturer.) Check the originator and target connection settings (number of connections and RPI). Depends on the originator’s specifications. (Contact the originator device’s manufacturer.) Depends on the originator’s specifications. (Contact the originator device’s manufacturer.) Depends on the originator’s specifications. (Contact the originator device’s manufacturer.) 361 Section 14-3 Connection Status Codes and Error Processing Connection status General Additional Status Status (hex) (hex) Source of error Configuration 1 Handling Configuration 2 Configuration 3 01 0316 Error code returned from target: This error does There was a parameter error in not occur. the frame used to close the connection. Depends on the originator’s specifications. (Contact the originator device’s manufacturer.) 01 031C Error code generated in originator: Some other error occurred. Depends on the originator’s specifications. (Contact the originator device’s manufacturer.) 08 --- Error code returned from target: There is no Forward Open or Large Forward Open service in the target device. D0 0001 Error code generated in originator: The connection operation is stopped. D0 0002 Error code generated in originator: The connection is being opened (opening processing in progress). 362 Depends on the target’s specifications. (Contact the target device’s manufacturer.) This error does The originator genernot occur. ates this code when an unsupported response code is returned from the target in reply to a connection-opening request. This error does Depends on the tarnot occur. get’s specifications. (Contact the target device’s manufacturer.) The meaning of this The connection error code is defined was stopped because the Tag by each vendor, so it Data Link Stop Bit depends on the tarwas turned ON, or get’s specifications. the settings data (Contact the target device’s manufacis being downturer.) loaded. Either turn ON the Tag Data Link Start Bit, or wait until the settings data has been downloaded. Includes Controller stop errors, Unit failure, and EM bank files at the refresh destination. To handle these errors, refer to 14-2-1Errors Occurring at the EtherNet/IP Unit or built-in EtherNet/IP port. Wait until the The meaning of this opening process- error code is defined ing is completed. by each vendor, so it depends on the target’s specifications. (Contact the target device’s manufacturer.) Depends on the originator’s specifications. (Contact the originator device’s manufacturer.) Depends on the originator’s specifications. (Contact the originator device’s manufacturer.) Depends on the originator’s specifications. (Contact the originator device’s manufacturer.) Section 14-3 Connection Status Codes and Error Processing Connection status General Additional Status Status (hex) (hex) Source of error Configuration 1 Unique OMRON Error Codes 01 0810 Error code returned from target: New data could not be obtained from the CPU Unit when opening connection. (The Unit will automatically retry, and attempt to open the connection again.) 01 0811 This error may occur if the CPU Unit’s cycle time was long when opening the connection, the specified EM bank was converted to file memory, or some problem in the PLC caused the PLC to stop. If the cycle time was too long, the problem will be resolved automatically. If the EM bank is set as file memory, change the storage location for the tag data. If the PLC has stopped, identify and correct the error. If the PLC system is stopped, identify the cause of the error from the CPU Unit error data. Error code generated in origina- This error may tor: occur if the CPU New data could not be obtained Unit’s cycle time from the CPU Unit when open- was long when opening the coning connection. (The Unit will automatically retry, and attempt nection, or the to open the connection again.) specified EM bank was converted to file memory. If the cycle time was too long, the problem will be resolved automatically. If the EM bank is set as file memory, change the storage location for the tag data. Handling Configuration 2 Configuration 3 The meaning of this error code is defined by each vendor, so it depends on the target’s specifications. (Contact the target device’s manufacturer.) The meaning of this error code is defined by each vendor, so it depends on the originator’s specifications. (Contact the originator device’s manufacturer.) The meaning of this error code is defined by each vendor, so it depends on the target’s specifications. (Contact the target device’s manufacturer.) The meaning of this error code is defined by each vendor, so it depends on the originator’s specifications. (Contact the originator device’s manufacturer.) 363 Section 14-4 Error Log Function 14-4 Error Log Function Errors detected by the EtherNet/IP Unit or built-in EtherNet/IP port are stored in the error log along with the date and time of their occurrence. The error log can be read and cleared from the Network Configurator. Some error log records are cleared when the CPU Unit’s power goes OFF, and other records are not cleared. 14-4-1 Error Log Data Specifications Each error is recorded as one record in the error log. Item Record length Number of records Data type Specifications 10 bytes/record 64 records max. Binary (time information: BCD) Structure of Each Record Bit 15 Minutes Day of month Year Bit 00 Error code Detail code Seconds Hour Month 14-4-2 Error Log Registration Error Log Storage Area When an error occurs, information on the error and the time stamp are stored in the Unit’s internal RAM as an error log record. Serious errors are recorded in non-volatile EEPROM as well as RAM. The time read from the CPU Unit during cyclic servicing is used for the time stamp. The error log records stored in EEPROM are copied to RAM when the Unit starts operating, so these records are retained even when the Unit’s power is turned OFF or the Unit is restarted. When the error log is read, the error log records in RAM are read. When the error log is cleared, the error log records in both RAM and EEPROM are erased. Error Log Overflows The error log can record up to 64 records. If another error occurs when the log is full, the oldest record will be erased to make room for the new error record. Power Interruptions when Saving to EEPROM If the power supply is interrupted or the Unit is restarted while the error log is being written to EEPROM, the error log may be corrupted. When the Unit starts, it performs a checksum test on the error log data read from EEPROM to detect corrupted data. 14-4-3 FINS Commands for Error Logs The following FINS commands can be sent to the EtherNet/IP Unit or built-in EtherNet/IP port to read or clear the error log. Command code MRC SRC 21 02 03 Function name ERROR LOG READ ERROR LOG CLEAR For details, refer to Appendix E FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports. 364 Section 14-4 Error Log Function 14-4-4 Error Log Error Codes Error code (hex) 0001 0002 0006 CPU Unit watchdog timer error CPU Unit service monitoring error Other CPU error 000E 000F 0011 0012 I/O bus error CPU Unit initialization error Event timed out CPU Unit memory error 0015 0017 0103 0105 0107 0108 CPU Unit fatal error Tag database error Resend count exceeded (send failed) Node address setting error (send failed) Remote node not in network (send failed) No Unit with specified unit address (send failed) CPU Unit error (send failed) Destination address not in routing tables (send failed) Not registered in routing tables (send failed) Routing table error (send failed) Too many relay points (send failed) Command too long (send failed) Header error (send failed) Internal buffers full; packet discarded Illegal packet discarded Local node busy (send failed) Unexpected routing error Service not supported in current mode; packet discarded Internal send buffer full; packet discarded Maximum frame size exceeded; routing failed Response timeout; packet discarded Communications controller error 00 hex IP address duplication Port number (always 02) Logic error in setting table 00 hex 010B 010D 010E 010F 0110 0111 0112 0117 0118 0119 0120 0122 0123 0124 0125 020F 0211 021A Error Detail code First byte Second byte 00 hex 00 hex Monitoring time (ms) Bit D11: Unit not in Registered I/O Tables (Other bits are reserved for system use.) 00 hex 00 hex 00 hex 00 hex MRC (main command) SRC (subcommand) 01 hex: Read error 03 hex: Routing tables 02 hex: Write error 50 hex: CPU Bus Unit Area (CIO or DM) 00 hex 00 hex 00 hex 00 hex FINS Command: Bit 15: OFF Bits 08 to 14: Source network address Bits 00 to 07: Source node address FINS Response: Bit 15: ON Bits 08 to 14: Destination network address Bits 00 to 07: Destination node address CIP Frame: FFFF Saved in EEPROM Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No No No No No No 01 hex Yes Lower byte of IP address Yes 02 hex: Network parame- Yes ters 03 hex: Routing tables 04 hex: Unit Setup 0E hex: Unit name 12 hex: Status area layout setting error 13 hex: Status area layout setting verification error 15 hex: Installation in a PLC of another series (e.g., from CJ1 to CJ2) after setting the Unit. 365 Section 14-4 Error Log Function Error code (hex) 0300 Parameter error; packet discarded 0347 03C0 I/O refreshing error FINS/TCP setting error 03C1 Server settings error 03C2 FINS/TCP packet discarded 03C3 FINS/UDP packet discarded 366 Error Detail code First byte Second byte FINS Command: Bit 15: OFF Bits 08 to 14: Source network address Bits 00 to 07: Source node address FINS Response: Bit 15: ON Bits 08 to 14: Destination network address Bits 00 to 07: Destination node address CIP Frame: FFFF 00 hex 00 hex 01 to 10 hex: 01: Automatically alloConnection number cated FINS node address duplication 02: Destination IP address error 03: Destination port number error 00 hex: DNS 01: IP address 02: Host name 03 hex: SNTP 03: Port number 04 hex: FTP 04: Other parameter 06 hex: BOOTP 07 hex: SNMP 08 hex: SNMP Trap 09 hex: FINS/UDP 0A hex: FINS/TCP 01 to 10 hex: 02 hex: Reopening Connection number because remote node closed 03 hex: Reopening because of reception error 04 hex: Reopening because of transmission error 05 hex: Reopening because RST received from remote node 06 hex: Reopening because of no keep-alive response 07 hex: Illegal FINS/TCP procedure 08 hex: Insufficient memory during server processing 09 hex: Insufficient memory during client processing 0A hex: Insufficient memory during node switching 00 hex 01 to FE hex: Source node address Saved in EEPROM No Yes No No No No Section 14-4 Error Log Function Error code (hex) 03C4 Server connection error 00 hex: DNS 03 hex: SNTP 04 hex: FTP 06 hex: BOOTP 07 hex: SNMP 08 hex: SNMP Trap 03C6 Clock write error 0001: The clock time could not be updated because a error occurred in the CPU Unit. 0002: The clock time could not be updated because the CPU Unit or operating mode does not support this function. 01 hex: Ethernet setting error 03D0 Error Detail code First byte Ethernet basic setting error 02 hex: TCP/IP basic setting error 03D1 Ethernet advanced setting error 02 hex: FINS setting error 03D2 Packet discarded. 01 hex Second byte Saved in EEPROM 01 hex: Specified host No does not exist 02 hex: No such service at specified host 03 hex: Timeout 06 hex: Host name resolution error 07 hex: Transmission error 08 hex: Reception error 09 hex: Other error 0A hex: Obtaining IP address error Clear the error from the No CPU Unit. Refer to SECTION 12 Automatic Clock Adjustment Function and check the application conditions. 01 hex: Checksum error Yes 11 hex: Inconsistent settings 12 hex: Specified baud rate is not supported. 01 hex: Checksum error 11 hex: Invalid IP address 12 hex: Invalid subnet mask 13 hex: Invalid default gateway address 14 hex: Invalid primary name server 15 hex: Invalid secondary name server 16 hex: Invalid domain name 17 hex: Invalid host name 01 hex: Checksum error Yes 10 hex: Invalid IP router table 11 hex: Invalid FINS/UDP setting 12 hex: Invalid FINS/TCP setting 13 hex: Invalid FTP setting 14 hex: Invalid SNTP setting 15 hex: Invalid SNMP setting 16 hex: Invalid SNMP trap setting 00 hex No 367 Section 14-5 Troubleshooting Error code (hex) 03D3 03D4 03D5 0601 0602 Error Detail code First byte Second byte Link OFF error Verification error (Tag data link only) 00 hex 00 hex Connection instance num- Lower byte of IP address Note For details on identifying the cause of ber (0 to 255) the verification error, refer to 14-3 Connection Status Codes and Error Processing. This error will not be stored when a target node is missing for version 2.0 or higher. Tag data link error 00 hex Lower byte of IP address CPU Bus Unit error Variable CPU Bus Unit memory error 01: Read error 02 hex: Network parameter 02: Write error 06 hex: Error log 09 hex: Identity data 0E hex: Unit name 0F hex: Ethernet basic setting 10 hex: Ethernet advanced setting 11 hex: MAC address 12 hex: Status area layout setting 14 hex: Term Tag address resolution memory write error Note Saved in EEPROM No No No Yes Yes (See note.) If a memory error occurs in the error log area of EEPROM, the record will not be stored in EEPROM. 14-5 Troubleshooting 14-5-1 CPU Unit's ERR/ALM Indicator Lit or Flashing Use the following table to troubleshoot the system when the CPU Unit’s ERR/ ALM indicator is lit or flashing when the EtherNet/IP Unit or built-in EtherNet/ IP port is mounted. An I/O verification error occurred. A CPU Bus Unit setting error occurred. A CPU Bus error occurred. An I/O Bus error occurred. • Confirm that the Unit is connected properly. • Check the I/O table with the I/O Table Verification operation and correct it if necessary. After correcting it, perform the I/O Table Create operation. • The CPU Bus Unit model registered in the I/O tables does not match the model of CPU Bus Unit actually mounted. Check the I/O tables with the I/O Table Verification operation and correct it if necessary. After correcting the I/O tables, perform the I/O Table Create operation. • Confirm that the Unit is connected properly. • Restart the Unit. Replace the Unit if it doesn’t restart. • Confirm that the Unit is connected properly. • Restart the Unit. Replace the Unit if it doesn’t restart. For details, refer to the CPU Unit’s Operation Manual. 368 Section 14-5 Troubleshooting 14-5-2 General Ethernet Problems The 100M and 10M Indicators on the EtherNet/IP Unit or CPU Unit are both OFF. The NS Indicator on the EtherNet/IP Unit or CPU Unit is lit red. • Confirm that the cable being used has the correct ratings. • Confirm that the cable is properly connected to the switching hub, and the hub’s power supply is ON. (The 7-segment display will indicate error E1.) • If the switching hub’s settings can be changed, confirm that the Ethernet link settings are the same as the settings for the EtherNet/IP Unit or built-in EtherNet/IP port. (For details, refer to 3-4 Network Installation.) • Check whether the same IP address is set on another node. (The 7-segment display will indicate error F0.) 14-5-3 Tag Data Links Fail to Start Use the following table to troubleshoot tag data links when the Tag Data Links Operating Flag (bit 15 in Communications Status 1) does not go ON. The indicators on • Check whether power is being supplied to the PLC. the EtherNet/IP Unit • Check whether the EtherNet/IP Unit or built-in EtherNet/IP or CPU Unit are all port is mounted in the Backplane correctly. OFF. • If a watchdog timer (WDT) error has occurred in the PLC, follow the procedures described in the PLC’s Operation Manual to correct the problem. • All of the indicators for the EtherNet/IP Unit or built-in EtherNet/IP port will be OFF if a CPU Bus Unit error has occurred. Check for a CPU Bus Unit error. • Restart the Unit. Replace the Unit if it doesn’t restart. • If the EtherNet/IP Unit's 7-segment display is displaying an The MS indicator error code, refer to the tables in 14-2 Using the LED Indicaon the EtherNet/IP tors and Display for Troubleshooting. Unit or CPU Unit is lit green, but the NS • Confirm that the cables are properly connected to the indicator remains switching hub and the power supply to the switching hub is OFF. ON. • If data is being restored by the simple backup function, wait until the restore operation is completed. • If the EtherNet/IP Unit's 7-segment display is displaying an The MS indicator on the EtherNet/IP error code, refer to the tables in 14-2 Using the LED Indicators and Display for Troubleshooting. Unit or CPU Unit is lit green, but the NS • The NS indicator will continue to flash green if the tag data indicator continlink settings have not been set in the Unit. Use the Network ues to flash green. Configurator to set the tag data link settings in the Unit, and then restart the Unit. The MS indicators • Identify the error code shown on the 7-segment display is lit green on the based on the tables in 14-2 Using the LED Indicators and EtherNet/IP Unit or Display for Troubleshooting, and eliminate the cause of the CPU Unit, but the error. NS indicator continues to flash red. 369 Section 14-5 Troubleshooting 14-5-4 Tag Data Link Problems The tag data isn't simultaneous. Observe the following precautions when writing application programs: • Maintain the simultaneity of data in connection-units between the PLC and EtherNet/IP Unit or built-in EtherNet/IP port. • If another company's device is being used, refer to that device's user's manual for details. • When received data is used in the ladder program, use the At startup, the received data is All Tag Data Links Operating Flag in Communications Status OFF unexpectedly. 1, or the Target Node PLC Operating Flag as a condition. If the Target Node PLC Operating Flag is used, the PLC status must be included in tag sets of both the sending and receiving nodes. • If the Output OFF function (Output Inhibit) is enabled in the output (produce) tag settings, all of the output data will be OFF if a fatal error occurs in the CPU Unit or the Output OFF Bit is turned ON. Check the status of the output (producer) PLC. The tag data links • Check whether the baud rate is set to 10 Mbps, or a 10M or start and stop com- 100M repeater hub is being used. The tag data link performunicating intermance is based on the use of switching hubs. The bandwidth mittently. listed in the specifications (CJ2M: 3,000 pps, other CPU Units: 6,000 pps) is achieved when the Unit auto-negotiates to full-duplex at 100 Mbps. • Refer to 14-1 Checking Status with the Network Configurator for details on checking the error counters on the Monitor Device Window’s Ethernet Information Tab Page. The error and discarded packet counters indicate problems such as noise in the communications path, the use of substandard cables, damaged cables/connectors, loose connectors, abnormally high communications load, or incorrect wiring (loops) in the switching hub wiring. • Contact the switching hub manufacturer to determine whether there are any problems with the transfer capacity of the switching hubs in the communications path. If switching hubs are arranged in a cascade connection, there may be a heavy load concentrated at a mid-level switching hub. In the EtherNet/IP Unit or built-in EtherNet/IP port itself, processing is performed with a higher priority than message communications, so specifications provide for a 3,000 pps bandwidth for the CJ2M and a 6,000 pps bandwidth for other CPU Units in tag data link performance only. • Refer to 14-1 Checking Status with the Network Configurator for details on checking the connection status on the Monitor Device Window’s Connection Tab Page. Eliminate any errors, which can be identified in the tables in 14-3 Connection Status Codes and Error Processing. 370 Section 14-6 Troubleshooting with FINS Response Codes 14-5-5 Message Timeout Problems Timeout errors occur frequently in message services (CIP UCMM, CIP Class 3, or FINS). • When there is a high load in the tag data link, and the CPU Unit’s cycle time is relatively long or there are messages coming in from many nodes, the message service response time may be delayed and messages may be discarded occasionally. • In this case, the communications load must be reduced by increasing (slowing) the tag data link’s RPI, reducing the message load, or increasing the timeout value. • The tag data link’s bandwidth usage can be checked on the Monitor Device Window’s Ethernet Information Tab Page. Refer to 14-1 Checking Status with the Network Configurator for details. • The error log error codes that indicate discarded messages (insufficient memory) due to heavy communications loads are 0117, 0119, 0123, 0125, 03C2 (detail code @@08, @@09, or @@0A), 03C3, and 03D2. Refer to 14-1 Checking Status with the Network Configurator for details on reading the error codes on the Error History Tab Page. • For information on preventing high loads in FINS communications, refer to 8-7 Precautions on High Traffic in FINS Communications. 14-6 Troubleshooting with FINS Response Codes The cause of errors that occur when using the SEND(090), RECV(098), or CMND(490) instructions can be identified from the response codes. (Refer to the description of Communications Port Completion Codes in 8-6-4 Writing Programs for the storage locations of response codes generated by the SEND(090), RECV(098), or CMND(490) instructions.) This section describes the completion codes produced by EtherNet/IP Units. For details on completion codes produced by CPU Units, other CPU Bus Units, or computers equipped with FINS services, refer to the device’s operation manual. The 6th, 7th, and 15th bits of the response codes have specific functions. The 6th bit will be ON when a non-fatal error has occurred in the PLC at the remote node; the 7th bit will be ON when a fatal error has occurred in the PLC at the remote node; and the 15th bit will be ON when a network relay error has occurred. The following table explains the meaning of the completion codes. Bit 7 6 5 First byte 4 3 2 1 0 7 6 Main response code (RES) 5 Second byte 4 3 2 1 0 Sub response code (SRES) PLC Fatal Error Flag PLC Non-fatal Error Flag Relay Error Flag Main response code Value and meaning 00 Normal completion Sub response code Item to check Likely cause Corrective action Value and meaning 00 --- --- --- --- 371 Section 14-6 Troubleshooting with FINS Response Codes Main response code Value and meaning 01 Local node error Sub response code 03 07 Remote node error 01 02 05 03 Unit error (Controller error) 01 02 04 04 Service not 01 supported 05 Routing error 01 02 03 04 372 Likely cause Corrective action Value and meaning 05 02 Item to check Local node send error --- Lack of available space in The load (traffic) on the Etherinternal buffers net Unit is too heavy. Check your user applications. Node address setLocal IP The network cannot be Correct the local IP address. ting error address used because the IP address setting is incorrect. Local node busy System load Lack of available space in The load (traffic) on the Ether(send failed) internal buffers net Unit is too heavy. Check your user applications. Remote node not in IP address IP address of remote Set IP address of remote node not set correctly. node into IP address table network table and IP router table and, if internetwork transmission is required, into the IP router table. No Unit with speciInstruction’s There is no Unit with the Check the remote node's unit fied unit address control data specified unit address. address. Response timeout Transfer condi- Message packet was cor- Increase the number of transrupted by transmission mit retry attempts. tions error. (Use FINS status read commands.) Instruction’s The response monitoring Set a longer response monicontrol data time is too short. toring time. Read out the error log and Read the error The transmission frame log. may be corrupted or the correct the system as required. internal reception buffer full. Communications Affected con- Error occurred in the Take corrective action, refercontroller error troller’s ERC communications control- ring to troubleshooting proceindicator ler. dures in this section. PLC error Affected CPU Unit error occurred Clear the error in the CPU node’s LED in the PLC at the remote Unit. (Refer to the PLC's operindicators node. ation manuals.) Unit number setting Unit number The unit number setting Confirm that the unit number error is incorrect. set on the switch is within the specified range and that the same unit number is not used twice in the same network. Unsupported comCommand The specified command Check the command code. mand code code is not supported by the destination Unit. FINS header A short frame (4 bytes) is The EtherNet/IP Unit does not frame length being used for the FINS support short headers. header frame. Routing table setting Routing tables Remote node is not set in Set the destination address in error the routing tables. the routing tables. Set routing tables at the local Routing tables not Routing tables Destination is unknown node, remote node, and any registered because there are no relay nodes. routing tables. Routing table error Routing tables Routing table error Set the routing tables correctly. Too many relay Network con- The maximum number of Redesign the network, or points figuration network levels (3) was reconsider the routing tables exceeded in the comto reduce the number of relay mand. nodes in the command. Section 14-6 Troubleshooting with FINS Response Codes Main response code Value and meaning 10 Sub response code Command 01 format error 21 Parameter error Cannot write Likely cause Corrective action The command is too long. The command exceeded 1,473 bytes when broadcasting. The command is too short. The specified number of items does not match the amount of write data. Data for another node on the same network was received from the network. Attempted to send response data for a broadcast address. The specified parameters are incorrect. The UDP/TCP socket number was not within the proper range. The local UDP port number might be set to 0. A correct memory area code has not been used or EM Area is not available. The first word is in an inaccessible area. Check the command format of the command and set it correctly. A FINS message was received from an IP address that differed from the ones in the Unit Setup with FINS node addresses that could not be dynamically changed. Correct the relationships between IP addresses and FINS node addresses. Refer to SECTION 5 Determining IP Addresses for details. Value and meaning Command too long Command data 02 Command too short 03 Number of items does not match amount of data Header parameter error Command data Command data 05 11 Item to check 00 Parameter error Command data Parameters in command data 01 No data area code Variable type in command data 03 Address out-ofrange error First word address in command data 04 Address range overflow Command data 0B Response too long Command data 0C Parameter error 08 Cannot change Parameters in command data IP address conversion method Check the number of items and amount of data, and make them agree. Check the command format of the command and set it correctly. Check the command data and set the parameters correctly. Be sure the socket number is between 1 and 8. Set the local UDP port number correctly. Check the command’s data area code in the Results Storage Area and set the appropriate code. Check the data area range, and set a first word that is in an accessible area. The specified bit number Check the command’s data is not 00. area code in the Results Storage Area. The bit address must be 00 for EtherNet/IP Units. The address range speci- Set the address in the command data so that the start fied in the command is address plus the number of not correct. words does not exceed accessible memory. The response frame is Correct the number of data longer than allowed. elements or other parameters in the command data for which the response is being returned. The specified parameCheck the command data and ters are incorrect. set the parameters correctly. 373 Section 14-6 Troubleshooting with FINS Response Codes Main response code Value and meaning 22 Sub response code Item to check Likely cause Cannot execute because service is being processed. Socket status area The same socket service is already in progress at the specified socket number. 10 Socket not open Socket status area 11 Local node busy (send failed) System load 20 FINS/TCP not connected Unit Setup Value and meaning Status error 0F (operating mode disagreement) 21 22 23 24 25 26 23 374 No such Unit (Environment error) Corrective action 30 Establishing connec- Command tion data 31 Cannot change connection 32 Cannot execute Command because service was data interrupted 05 Parameters Unit Setup 07 Configuration error IP address conversion in Unit Setup Unit Setup and command data Use the corresponding socket status flag in PLC memory to be sure that socket service has finished before starting services again. The specified socket is Open the socket. (For TCP not open. sockets, wait until the connection is made.) Lack of available space in The load (traffic) on the Etherinternal buffers net Unit is too heavy. Check your user applications. Not opened due to sysCorrectly set the Unit Setup, tem settings. FINS/TCP connection number, remote IP address, and Not opened due to a remote port number. change command from the FINS/TCP connection’s remote node. Closed by remote node; opening again. Opening again because of a reception error. Opening again because of a send error. Opening again because of an RST response in keep-alive. Opening again because there was no response in keep-alive. A connection is already Correct the settings for the established with the FINS/TCP connection numspecified remote node. ber, the remote IP address, and the remote port number. The specified connection Correct the settings for the number is not set as a Unit Setup, the FINS/TCP FINS/TCP client in the connection number, the Unit Setup. remote IP address, and the remote port number. Correct the settings for the While a remote node FINS/TCP connection numchange was being prober, the remote IP address, cessed for the specified and the remote port number. connection number, a request for a change was received and the processing was stopped. IP address conversion Check the IP address and failed. subnet mask in the Unit Setup, and correct if necessary. IP address conversion is Check the IP address converset for automatic conver- sion setting in the Unit Setup. sion only. This error will be generated for the READ IP ADDRESS TABLE command only. Appendix A CS/CJ-series Ethernet Unit Function Comparison Item Ethernet Unit Tag data link communications service CIP message communications service FINS/UDP service FINS/TCP service Socket service File transfer (FTP) Mail send/receive Web functions No No Yes Yes Yes Yes Yes Yes Automatic adjustment of PLC’s internal clock Simple backup function Error log Response to PING command SNMP/SNMP trap CIDR function for IP addresses Online connection by EtherNet/IP using CX-One Online connection by Ethernet (FINS) using CX-One Online connection by EtherNet/IP using Network Configurator Yes Yes Yes Yes No No No Yes No Support for function EtherNet/IP Unit or built-in EtherNet/ IP port Unit version 1.0 Unit version 2.0 Yes Yes Yes Yes Yes Yes Yes Yes No No No Yes No No No No No Yes Yes Yes No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 375 CS/CJ-series Ethernet Unit Function Comparison 376 Appendix A Appendix B Ethernet Network Parameters Parameter TCP send buffer TCP receive buffer UDP send buffer UDP receive buffer FINS receive buffer RAW send buffer RAW receive buffer Hold timer Value 4,096 bytes 4,096 bytes 9,000 bytes 9,016 bytes 16,383 bytes 2,048 bytes 2,048 bytes 75 s (See note.) Description Maximum capacity of the TCP send buffer Maximum capacity of the TCP receive buffer Maximum capacity of the UDP send buffer Maximum capacity of the UDP receive buffer Maximum capacity of the FINS receive buffer Maximum capacity of the RAW send buffer Maximum capacity of the RAW receive buffer The hold timer is used for active open processing of TCP sockets. An ETIMEDOUT error will occur if connection is not completed within 75 s. Resend timer Initial value: 250 ms The resend timer is used to monitor completion of reception of arrival confirmations when transferring data via TCP sockets. If the timer setting Maximum value: 64 s is exceeded before arrival confirmation is received, data is resent. Resends are performed from the first timeout (1 s) through the 12th timeout (64 s). An ETIMEDOUT error will occur after the 12th timeout. Continue timer Initial value: 1s The continue timer starts if preparations have been completed to send Maximum value: 60 s data but the send window is too small (either 0 or too small) to send the data and the remote node has not requested that communications be restarted. Confirmation of the window size is requested from the remote node when the continue timer times out. The initial value of the timer is 5 s and confirmation processing will continue consecutively with increasingly longer times until the maximum time of 60 s is reached. 2MSL timer 60 s The 2MSL timer starts at the TCP socket that first closes the socket and will run for 60 s in the TIME_WAIT status. IP reassemble timer 12 s A fragmented IP packet is discarded if it cannot be reassembled within 12 seconds. ARP timer 20 min/3 min If a complete ARP table entry (with an Ethernet address) is not referred to for 20 minutes, it is removed from the table. An incomplete ARP table entry (no response yet returned to the ARP request) is removed from the table after 3 minutes. 4,096 bytes The initial value of the maximum capacity used to control the converWindow size gence of TCP sockets. Actually, the node negotiates with the remote (initial value of maxnode and uses the smaller of the values for the two nodes. The window imum window size) size will fluctuate with the available space in the TCP reception buffers of the remote node when processing communications. Fragment size 1,500 bytes Data packets are fragmented into 1,500-byte IP packets. UDP data is separated into 1,472-byte fragments before sending. Segment size 1,024 bytes TCP data is separated into 1,024-byte units, unless the segments are different, in which case it will be separated into 536-byte units. TTL (Time to Live) 30 Decremented each time an IP router is passed. Keep-alive timer First time: 5 min The keep-alive timer is used for the keep-alive function with TCP connecResend: 5 s × 5 times tions. It must be used with UCMM, Class 3. Note The hold time is 3 s for the UCMM service, Class 3 service, and tag data link open/close processing. 377 Ethernet Network Parameters 378 Appendix B Appendix C TCP Status Transitions The TCP socket status can be confirmed using the socket status data returned for the FINS command SOCKET STATUS READ (27 64). CLOSED ACTIVE OPEN snd SYN CLOSE Passive OPEN LISTEN rcv SYN snd SYN, ACK CLOSE SEND snd SYN rcv SYN SYN RECEIVED SYN SENT snd ACK rcv ACK of SYN CLOSE snd FIN rcv SYN, ACK snd ACK ESTABLISHED rcv FIN snd ACK CLOSE snd FIN CLOSED WAIT FIN WAIT-1 rcv ACK of FIN FIN WAIT-2 rcv FIN snd ACK rcv FIN snd ACK CLOSE snd FIN CLOSING LAST-ACK rcv ACK of FIN rcv ACK of FIN Timeout=2MSL TIME WAIT Status CLOSED Connection closed. LISTEN SYN SENT SYN RECEIVED ESTABLISHED CLOSE WAIT FIN WAIT 1 CLOSING LAST ACK FIN WAIT 2 TIME WAIT Waiting for connection. SYN sent in active status. SYN received and sent. Already established. FIN received and waiting for completion. Completed and FIN sent. Completed and exchanged FIN. Awaiting ACK. FIN sent and completed. Awaiting ACK. Completed and ACK received. Awaiting FIN. After closing, pauses twice the maximum segment life (2MSL). CLOSED Meaning 379 TCP Status Transitions 380 Appendix C Appendix D CIP Message Communications This appendix describes CIP message communications. The basic concepts of CIP message communications are described in this appendix from CIP Object on page 381 through Example of CIP Message Creation on page 386. Read these sections to improve your understanding of CIP message communications. CIP Object Object Model In the CIP (Common Industrial Protocol) system, each device is modeled as a group of “Objects.” An Object abstractly represents a related group of the device’s data values. Object Object Object Device When accessing the device from the outside, access an Object. An Object represents the abstracted device function, processing, and the resulting data. A request from the outside of Object, such as Read Data, is called “Service.” Data belonging to the Object is called “Attribute.” The actual entity of Object is called “Instance” or “Object Instance.” When Object is generalized, it is called “Class.” For example, “Japan” is one of Instances (Object Instances) of Class “Nation.” External request (Example. Read, Write) Attribute Service Data Data Data Processing Data Object Instance 381 Appendix D CIP Message Communications Terminology In CIP specifications, “Object,” “Class,” “Instance,” “Attribute” and “Service” are defined as follows: Term Object Class Instance Attribute Service Meaning An abstract representation of a particular component within a product. A set of objects that all represent the same kind of system component. A class is a generalization of an object. All objects in a class are identical in form and behavior, but may contain different attribute values. A specific and real (physical) occurrence of an object. For example: New Zealand is an instance of the object class Country. The terms Object, Instance, and Object Instance all refer to a specific Instance. A description of an externally visible characteristic or feature of an object. Typically, attributes provide status information or govern the operation of an Object. For example: the ASCII name of an object; and the repetition rate of a cyclic object. A function supported by an object and/or object class. CIP defines a set of common services and provides for the definition of Object Class and/or Vendor Specific services. Specifying an Object Address (Request Path) This is the basic concept involved in accessing an Object or Attribute. Each Object Class has a “Class ID”. There are two types of “Class ID”; one is standardized by ODVA and the other is decided independently by each device vendor. Each Object Instance also has ID. This is called “Instance ID.” Different Instance ID is assigned to each Object. As for Object Class standardized by ODVA, Instance ID is given to it according to the ODVA method. On the other hand, vendor's own Instance ID is decided independently by the vendor. Each Attribute also has “Attribute ID.” Each Object is accessed to by using “Class ID,” “Instance ID,” and “Attribute ID.” In the device, you can designate Object by specifying these three IDs. When requesting “Service,” you should specify “Class ID,” “Instance ID,” and “Attribute ID.” (Instance ID and Attribute ID may not be required, depending on the Service.) The “Class ID,” “Instance ID,” and “Attribute ID” identify a location in the device and are known as the request path. Class ID = 2 Attribute 1 Attribute = 3 Attribute 2 Attribute 3 Attribute 4 Instance ID = 1 Class ID = 1 Device 382 Instance ID = 1 Appendix D CIP Message Communications Route Path Route Path In the CIP, unlike the internet protocol, the transmission frame contains a complete relay route from the transmission node to the reception node. The described route is called the “route path.” The route path is described as “EPATH type.” The basic concept of the route path is as follows: First of all, specify a network port of the transmission node with the destination network, and specify a node address (called the Link Address) on that network. For the relay node, similarly, specify a network port with the destination network and node address on that network. Then, repeat the same procedure to the final destination. X Y Object A Z Port-A Object B #2 #1 #1 #3 Port-B Port-C Port-D When sending data from X to Z. Route Path = Port A: #3, Port C: #1 Send data from the network port of X (Port-A) to #3 on that circuit, and the data reaches Y. Then, send it from the network port of Y (Port-C) to #1 on that circuit. Through this procedure, the destination node Z can be designated. Description by EPATH Type In CIP, the EPATH type is used to describe the route path and request path. With this method, the route path and request path are divided into segments and a value is assigned to each segment, so the route path description shows the path to the final destination when the data segments are joined together. The segment includes the segment type information and the segment data. Segment 1 Segment 2 Segment 3 Segment 4 ···· Details of Segment Type The interpretation method of a segment is included in the first 1 byte, which consists of two parts; a 3-bit “Segment Type” and a 5-bit “Segment Format.” Segment Type 7 6 5 Segment Format 4 3 2 1 0 383 Appendix D CIP Message Communications According to CIP Specifications, the Segment Type specifications are decided as follows: 7 0 0 0 0 1 1 1 1 Segment Type 6 5 0 0 0 1 1 0 1 1 0 0 0 1 1 0 1 1 Description Port Segment Logical Segment Network Segment Symbolic Segment Data Segment Data Type Data Type Reserved The specifications of Segment Format are different for each Segment Type. The following sections describe Port Segment, Logical Segment, and Data Segment which are needed to use the CIP message communications instructions. Port Segment The Port Segment is used to specify the path described above. Segment Type 7 6 5 0 0 0 Extended Link Address Size 4 Port Identifier 3 2 1 0 Set the ID of the port in Port Identifier. The Port Identifier is 4 bits, so it can have a value between 0 and 15. A port identifier of “0” is reserved and not available. A port identifier of “1” indicates the backplane port. A port identifier of “15” has a special meaning, which indicates that the size of Port Identifier is larger than 1 byte, and the 4-bit port identifier (15) is followed by 2-byte Port Identifier. The port identifier does not exceed 1 byte when using the EtherNet/IP Unit or built-in EtherNet/IP port, so this special case is not explained here. Set the Extended Link Address Size to “1” when that port’s Link Address is larger than 1 byte. The following diagram shows the Port Segment value when the Extended Link Address Size is set to “0.” Segment Type 384 Extended Link Address Size 7 6 5 4 0 0 0 0 Port Identifier 3 2 1 0 Link Address 7 6 5 4 3 2 1 0 Appendix D CIP Message Communications Specify the size of Link Address when the Extended Link Address Size is set to “1.” The following diagram shows the Port Segment value in this case. Extended Link Address Size Segment Type 7 6 5 4 0 0 0 1 Port Identifier 3 6 5 4 3 1 0 7 6 5 4 3 2 1 0 → · · · · · · · · · · · · Link Address 7 2 Link Address Size 2 1 0 7 Link Address 6 5 4 3 2 1 0 · · · · · · → Always set the Link Address to an even number of bytes. If there is an odd number of bytes, pad the Link Address with “00” so that it has an even number of bytes. Logical Segment The Logical Segment is used to specify the request path. Segment Format Bits Segment Type 7 6 5 0 0 1 4 0 0 0 0 1 1 1 1 0 0 1 1 Logical Type 3 2 0 0 0 1 1 0 1 1 0 0 0 1 1 0 1 1 Logical Format 1 0 0 1 0 1 Logical Type 4 3 2 Logical Format 1 0 Description Class ID Instance ID Member ID Connection Point Attribute ID Special (Do not use the logical addressing definition for the Logical Format.) Service ID (Do not use the logical addressing definition for the Logical Format.) Reserved Description 8-bit logical address 16-bit logical address 32-bit logical address Reserved The 32-bit logical address format is reserved and cannot be used. The 8-bit and 16-bit logical address can be used for the Class ID and Instance ID, which specify the request path. 385 CIP Message Communications Appendix D The 8-bit logical address can be used for the Attribute ID. Use the Attribute ID when requesting a Service of a particular Object of a particular device. Example of CIP Message Creation Setting the Route Path Port Number The following description explains the network port, which is used to specify the route path. In the CJ2 Series, the Backplane is also considered part of the network when specifying the Link Address. CPU Unit CJ2 (Not supported by CS1/CJ1 CPU Units.) Each CPU Unit has one backplane port. By convention, the built-in port on a CJ2H-CPU6@-EIP or a CJ2M-CPU3@ CPU Unit functions as a CPU Bus Unit. Port Backplane Port Number 1 The Backplane port is the Backplane. CPU Unit communications routed through CPU Bus Units always travel through the backplane. EtherNet/IP Unit or CJ2 Built-in EtherNet/IP Port The EtherNet/IP Unit has two ports. A CJ2 CPU Unit also has two built-in EtherNet/IP ports. One is a Backplane port and the other is an Ethernet port. The Backplane port is the Backplane. Communications routed through the CPU Unit, a Special I/O Unit, or another CPU Bus Unit always travel through the backplane. Port Backplane Ethernet Port Number 1 2 Link Address The Link Address is a node address on the network, which is used to specify the route path. The method to set the Link Address is different for each network. In the CS/CJ Series, the Backplane is also considered part of the network when specifying the Link Address. Backplane • CPU Bus Unit or Special I/O Unit In the CS/CJ Series, the base unit is recognized as a backplane port. CPU Bus Units, such as the EtherNet/IP Unit, are also recognized as nodes on the backplane port. The Link Address of a CPU Bus Unit on the Backplane is the “unit number + 10 hex.” For example, when the unit number is 0, the Link Address is 10 hex. When the unit number is F, the Link Address is 1F hex. The Link Address of a Special I/O Unit on the Backplane is the “unit number + 20 hex.” For example, when the unit number is 0, the Link Address is 20 hex. Network • EtherNet/IP The Ethernet port’s Link Address is described by the IP address. The IP address must be described entirely in ASCII. For example, IP address of 192.168.200.200 will be [31] [39] [32] [2E] [31] [36] [38] [2E] [32] [30] [30] [2E] [32] [30] [30]. 386 Appendix D CIP Message Communications Response Codes General Status Code The General Status Code is stored in the response data after execution of the CMND instruction has been completed. General Status Status Name Code (hex) 00 Success 01 Connection failure 02 Resource unavailable Description of Status 06 Service was successfully performed by the object specified. A connection related service failed along the connection path. Resources needed for the object to perform the requested service were unavailable. Invalid parameter value See Status Code 20 hex, which is the preferred value to use for this condition. Path segment error The path segment identifier or the segment syntax was not understood by the processing node. Path processing shall stop when a path segment error is encountered. Path destination The path is referencing an object class, instance or structure element that is unknown not known or is not contained in the processing node. Path processing shall stop when a path destination unknown error is encountered. Partial transfer Only part of the expected data was transferred. 07 08 Connection lost Service not supported 09 0A Invalid attribute value Attribute list error 0B Already in requested mode/state Object state conflict Object already exists Attribute not settable Privilege violation Device state conflict 03 04 05 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C The messaging connection was lost. The requested service was not implemented or was not defined for this Object Class/Instance. Invalid attribute data detected. An attribute in the Get_Attribute_List or Set_Attribute_List response has a non-zero status. The object is already in the mode/state being requested by the service. The object cannot perform the requested service in its current mode/state. The requested instance of object to be created already exists. A request to modify a non-modifiable attribute was received. A permission/privilege check failed. The device's current mode/state prohibits the execution of the requested service. Reply data too large The data to be transmitted in the response buffer is larger than the allocated response buffer Fragmentation of a The service specified an operation that is going to fragment a primitive data primitive value value, i.e. half a REAL data type. Not enough data The service did not supply enough data to perform the specified operation. Attribute not supported The attribute specified in the request is not supported. Too much data The service supplied more data than was expected. Object does not exist The object specified does not exist in the device. Service fragmentation The fragmentation sequence for this service is not currently active for this data. sequence not in progress No stored attribute data The attribute data of this object was not saved prior to the requested service. Store operation failure The attribute data of this object was not saved due to a failure during the attempt. Routing failure (request The service request packet was too large for transmission on a network in the packet too large) path to the destination. The routing device was forced to abort the service. The service response packet was too large for transmission on a network in Routing failure the path from the destination. The routing device was forced to abort the ser(response packet too vice. large) Missing attribute list The service did not supply an attribute in a list of attributes that was needed by entry data the service to perform the requested behavior. 387 Appendix D CIP Message Communications General Status Code (hex) 1D 1E 1F 20 21 22 23-24 25 26 27 28 29 2A 2B-CF D0-FF 388 Status Name Invalid attribute value list Embedded service error Vendor specific error Description of Status The service is returning the list of attributes supplied with status information for those attributes that were invalid. An embedded service resulted in an error. A vendor specific error has been encountered. The Additional Code Field of the Error Response defines the particular error encountered. Use of this General Error Code should only be performed when none of the Error Codes presented in this table or within an Object Class definition accurately reflect the error. Invalid parameter A parameter associated with the request was invalid. This code is used when a parameter does not meet the requirements of this specification and/or the requirements defined in an Application Object Specification. Write-once value or An attempt was made to write to a write-once medium (e.g. WORM drive, medium already written PROM) that has already been written, or to modify a value that cannot be changed once established. Invalid Reply Received An invalid reply is received (e.g. reply service code does not match the request service code, or reply message is shorter than the minimum expected reply size). This status code can serve for other causes of invalid replies. Reserved by CIP for future extensions Key Failure in path The Key Segment that was included as the first segment in the path does not match the destination module. The object specific status shall indicate which part of the key check failed. Path Size Invalid The size of the path which was sent with the Service Request is either not large enough to allow the Request to be routed to an object or too much routing data was included. Unexpected attribute in An attempt was made to set an attribute that is not able to be set at this time. list Invalid Member ID The Member ID specified in the request does not exist in the specified Class/ Instance/Attribute. Member not settable A request to modify a non-modifiable member was received. Group 2 only server This error code may only be reported by DeviceNet group 2 only servers with general failure 4K or less code space and only in place of Service not supported, Attribute not supported and Attribute not settable. --Reserved by CIP for future extensions Reserved for Object This range of error codes is to be used to indicate Object Class specific errors. Class and service Use of this range should only be performed when none of the Error Codes preerrors sented in this table accurately reflect the error that was encountered. Appendix D CIP Message Communications Example of Additional Status in case that General Status Is 01 Hex. (Status of Connection Manager Object) General Status (hex) 01 01 01 01 01 Additional Status (hex) 0100 0103 0106 0107 0108 Explanation 01 01 01 0109 0110 0111 01 01 01 01 01 01 01 01 01 01 01 0113 0114 0115 0116 0117 0118 0119 011A 011B 0203 0204 Connection in Use or Duplicate Forward Open. Transport Class and Trigger combination not supported Ownership Conflict Connection not found at target application. Invalid Connection Type. Indicates a problem with either the Connection Type or Priority of the Connection. Invalid Connection Size Device not configured RPI not supported. May also indicate problem with connection time-out multiplier, or production inhibit time. Connection Manager cannot support any more connections Either the Vendor Id or the Product Code in the key segment did not match the device Product Type in the key segment did not match the device Major or Minor Revision information in the key segment did not match the device Invalid Connection Point Invalid Configuration Format Connection request fails since there is no controlling connection currently open. Target Application cannot support any more connections RPI is smaller than the Production Inhibit Time. Connection cannot be closed since the connection has timed out Unconnected Send timed out waiting for a response. 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 0205 0206 0207 0301 0302 0303 0304 0311 0312 0315 0316 0317 0318 0319 031A 031B 031C 031D 031F 0320-07FF Parameter Error in Unconnected Send Service Message too large for Unconnected message service Unconnected acknowledge without reply No buffer memory available Network Bandwidth not available for data No Tag filters available Not Configured to send real-time data Port specified in Port Segment Not Available Link Address specified in Port Segment Not Available Invalid Segment Type or Segment Value in Path Path and Connection not equal in close Either Segment not present or Encoded Value in Network Segment is invalid. Link Address to Self Invalid Resources on Secondary Unavailable Connection already established Direct connection already established Miscellaneous Redundant connection mismatch No connection resources exist for target path Vendor specific 389 Appendix D CIP Message Communications Priority/Time Ticks and Time Out Ticks Format of the Priority/Time Tick Time tick 0000 hex 0001 hex 0010 hex 0011 hex 0100 hex 0101 hex 0110 hex 0111 hex 1000 hex 1001 hex 1010 hex 1 2 4 8 16 32 64 128 256 512 1,024 Maximum time-out time (ms) that can be set in the time out ticks 255 510 1,020 2,040 4,080 8,160 16,320 32,640 65,280 130,560 261,120 1011 hex 2,048 522,240 1100 hex 1101 hex 1110 hex 1111 hex 4,096 8,192 16,389 32,768 1,044,480 2,088,960 4,177,920 8,355,840 390 Base value (ms) Appendix E FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports 04 05 06 08 21 27 Command code MRC SRC 03 01 01 01 02 03 02 03 20 30 31 50 57 60 61 62 63 64 65 67 01 10 28 Function name RESET CONTROLLER DATA READ CONTROLLER STATUS READ INTERNODE ECHO TEST BROADCAST TEST RESULTS READ BROADCAST DATA SEND ERROR LOG READ ERROR LOG CLEAR PING FINS/TCP CONNECTION REMOTE NODE CHANGE REQUEST FINS/TCP CONNECTION STATUS READ IP ADDRESS TABLE WRITE IP ADDRESS WRITE IP ADDRESS TABLE READ IP ROUTER TABLE READ PROTOCOL STATUS READ MEMORY STATUS READ SOCKET STATUS READ ADDRESS INFORMATION READ IP ADDRESS READ EXPLICIT MESSAGE SEND CIP UCMM MESSAGE SEND Remarks --------------------------------------------- RESET Resets the EtherNet/IP Unit or built-in EtherNet/IP port. Command Block 04 03 Command code Response Block 04 03 Command code Response code 391 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Precautions • No response will be returned if the command ends normally. A response will be returned only if an error occurs. • In some cases, send requests (SEND(192)/RECV(193) instructions) made from the PLC to the EtherNet/ IP Unit or built-in EtherNet/IP port just before execution of the RESET command may not be executed. • Applications that use TCP/IP, such as FINS/TCP communications services, are closed immediately before resetting. Response Codes Response code 1001 Description Command too large CONTROLLER DATA READ Reads the following data from the EtherNet/IP Unit or built-in EtherNet/IP port: Model number, version, IP address, subnet mask, FINS UDP port number, mode settings, Ethernet address. Command Block 05 01 Command code Response Block 05 01 Command code Response code 20 byte 20 byte 4 byte 4 byte Model number Version IP address Subnet mask 6 byte FINS UDP port number Mode setting Ethernet address Parameters Model number, Version (Response) The model number and version of the EtherNet/IP Unit or built-in EtherNet/IP port are returned as ASCII characters occupying 20 bytes each (i.e., 20 characters each). If all bytes are not used, the remaining bytes will be all spaces (ASCII 20 Hex). Example Model: CS1W-EIP21, CJ1W-EIP21, CJ2B-EIP21, or CJ2M-EIP21 Example Version: V2.00 By convention, the model number of the built-in EtherNet/IP port on a CJ2H-CPU@@-EIP CPU Unit is CJ2BEIP21. By convention, the model number of the built-in EtherNet/IP port on a CJ2M-CPU3@ CPU Unit is CJ2M-EIP21. IP Address, Subnet Mask (Response) The IP address and subnet mask of the EtherNet/IP Unit or built-in EtherNet/IP port are returned as 4 bytes each. FINS UDP Port Number (Response) The UDP port number of the EtherNet/IP Unit or built-in EtherNet/IP port for FINS is returned as 2 bytes. 392 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Mode Setting (Response) The mode setting in the system setup is returned. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit 1: Broadcast setting Bits 2 and 3: IP address conversion method Bit 4: UDP port number setting for FINS Bit 5: TCP port number setting for FINS/TCP Bit 8: Transmission speed (baud rate) Bit 9: SNTP server specification method Broadcast Address Setting Bit 1 Meaning 0 Broadcast with host number set to all ones (4.3BSD specifications) 1 Broadcast with host number set to all zeroes (4.2BSD specifications) Communications Partner IP Address Conversion Method Setting Bit 3 0 0 1 1 Bit 2 0 1 0 1 Meaning Automatic generation method (dynamic) Automatic generation method (static) IP address table reference method Combined method (IP address table reference + automatic generation (dynamic)) FINS/UDP Port Number Setting Bit 4 0 Default (9600) 1 Unit Setup value Meaning FINS/TCP Port Number Setting Bit 5 0 Default (9600) 1 Unit Setup value Meaning Baud Rate Setting Bit 8 0 Automatic detection 1 Fixed Meaning SNTP Server Specification Method Bit 9 0 IP address 1 Host name Meaning Ethernet Address (Response) The Ethernet address of the EtherNet/IP Unit or built-in EtherNet/IP port is returned. Note This Ethernet address is listed on the label on the side of the EtherNet/IP Unit or (for a built-in EtherNet/ IP port), on the CPU Unit. 393 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Response Codes Response code 0000 1001 Description Normal end Command too large CONTROLLER STATUS READ Reads the controller status. Command Block 06 01 Command code Response Block 06 01 2 byte Command code Response Communications Total number of status 3 code 4 byte 4 byte 4 byte 4 byte 4 byte Total number Total number Total number Total number of of of of packets received receive errors packets sent send errors send collisions Parameters Communications Status 3 (Response) 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit 2: EtherNet/IP basic setting error Bit 3: IP address table error Bit 4: IP router table error Bit 6: Routing table error Bit 9: EtherNet/IP advanced setting error Bit 10: BOOTP server error Bit 11: SNTP server error Bit 14: Address mismatch Bit 15: Non-volatile memory error Ethernet Basic Setting Error Bit 2 Meaning 0 No error 1 An error (such as an invalid IP address) was detected during the validity check of parameters related to the TCP/IP Interface Object and Ether Link Object. IP Address Table Error Bit 3 Meaning 0 No error 1 Error detected (More than 32 records, invalid IP address, or invalid FINS node address). 394 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E IP Router Table Error Bit 3 Meaning 0 No error 1 Error detected (More than 8 records, or invalid IP address). Routing Table Error Bit 6 0 No error 1 Error detected in routing table check. Meaning Ethernet Advanced Setting Error Bit 9 Meaning 0 No error 1 An error was detected during the validity check of vendor-specific parameters for the TCP/IP Interface Object and Ether Link Object. BOOTP Server Error Bit 10 Meaning 0 No error 1 Error detected. (A time-out occurred during communications with the BOOTP server). SNTP Server Error Bit 10 Meaning 0 No error 1 Error detected. (The setting of the host specification (IP address or host name) of the SNTP server is not correct, or communications with the SNTP server timed out.) Address Mismatch Bit 14 Meaning 0 No error 1 Error detected. (The address conversion method was set for automatic generation, but the last eight bits of the local IP address does not match the local node address (FINS node address), or the host section other than the last byte of the local IP address is non-zero.) Non-volatile Memory Error Bit 15 Meaning 0 No error 1 Error detected. (The non-volatile memory’s service life has expired, or the memory has failed). Total Number of Packets Received (Response) The total number of packets received by the EtherNet/IP Unit or built-in EtherNet/IP port is returned. Total Number of Receive Errors (Response) The total number of packet errors detected while the EtherNet/IP Unit or built-in EtherNet/IP port was receiving is returned. The following types of error are detected: • Short packet errors • Alignment errors • CRC errors • Frame length errors (received frame: 1,515 bytes or more) • Communications controller overflow errors 395 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Total Number of Packets Sent (Response) The total number of packets sent by the EtherNet/IP Unit or built-in EtherNet/IP port is returned. Total Number of Errors Sent (Response) The total number of packet errors detected while the EtherNet/IP Unit or built-in EtherNet/IP port was sending is returned. Total Number of Send Collisions (Response) Returns the number of packets damaged by 16 collisions with data from other nodes during EtherNet/IP Unit or built-in EtherNet/IP port transmissions. Precautions Counting of the total number of packets received, total number of receive errors, total number of packets sent, total number of errors sent, and total number of send collisions is discontinued when the counted value reaches the maximum value. Response Codes Response code 0000 1001 Description Normal end Command too large INTERNODE ECHO TEST Performs an echoback test (internode communications test) between specified nodes. Command Block 08 01 1,998 bytes max. Command code Test data Response Block 1,998 bytes max. 08 01 Command code Response code Test data Parameters Test Data (Command, Response) This command specifies the data to be sent to the specified nodes. Up to 1,998 bytes can be specified. The response sends back data identical to the data specified in the command. An abnormality is assumed if the data returned in the response differs from the test data sent. Precautions • The test destination node is the destination node specified in the CMND(194) instruction operands. • Always specify the unit address of the EtherNet/IP Unit or built-in EtherNet/IP port in the CMND(194) instruction. 396 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Response Codes Response code 0000 1001 1002 Description Normal end Command too large Command too small (No test data) BROADCAST TEST RESULTS READ Reads the results (number of times data received) of the broadcast test. Command Block 08 02 Command code Response Block 08 02 Command code Response code Times received Parameters Times Received (Response) The number of times the data has been received normally during the broadcast send test is returned as a hexadecimal number. The number of times received is cleared each time the result is read. Response Codes Response code 0000 1001 Description Normal end Command too large BROADCAST DATA SEND Sends test data simultaneously to all nodes on the network. Command Block 08 03 Command code 1,460 bytes max. Test data Parameters Test Data (Command) This command specifies the data to be sent to the specified nodes. Up to 1,460 bytes can be specified. 397 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Precautions • No response is made to this command. • When using this command, set the FINS header parameters (or the control data for the CMND(194) instruction) as follows: Destination node address: FF (broadcast data) Destination unit address: FE (EtherNet/IP Unit or built-in EtherNet/IP port) Response/no response flag: 1 (no response) ERROR LOG READ Reads the error log. Command Block 21 02 Command code Beginning record number Number of records Response Block 21 02 Command code Response code Maximum number of stored records Number of stored records Number of records 10 bytes 10 bytes Error log data Error log data Parameters Beginning Record Number (Command) The first record to be read. The first record number can be specified in the range between 0000 and 003F (0 to 63 decimal) where 0000 is the oldest record. Number of Records (Command, Response) The number of records to read is specified between 0001 and 0040 (1 to 64 decimal) in the command. The response returns the actual number of records read. Maximum Number of Stored Records (Response) Indicates the maximum number of records that can be stored in the error log. The maximum number of error log records depends on the model of CPU Unit or CPU Bus Unit being used. In an EtherNet/IP Unit or built-in EtherNet/IP port, the maximum number of stored records is fixed at 40 (64 decimal). Number of Stored Records (Response) The number of records stored at the time the command is executed is returned. Error Log Data (Response) The specified number of error log records from the beginning record number is returned sequentially. The total number of bytes in the error log is calculated as the number of records x 10 bytes/record. Each error log record thus comprises 10 bytes, configured as follows: 398 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports 1st byte Appendix E 10th byte Error code Detailed Minutes Second Day Hour Year Month information Error Code, Detailed Information Details of the error stored in the record. Refer to 14-4-4 Error Log Error Codes for details. Minute, Second, Day, Hour, Year, Month Indicate the time at which the error stored in the record occurred. Precautions • If the error log contains fewer records than the number specified in the number of records parameter, all records stored in the error log at the time the command is executed will be returned and the command executed will end normally. Response Codes Response code 0000 1001 1002 1103 110C Description Normal end Command too large Command too small Beginning record number is out of range The number of read records is 0. ERROR LOG CLEAR Clears the error log for the EtherNet/IP Unit or built-in EtherNet/IP ports, and resets the number of stored records to 0. Command Block 21 03 Command code Response Block 21 03 Command code Response code Response Codes Response code 0000 1001 Description Normal end Command too large PING Performs processing equivalent to a UNIX computer’s PING command (see below). 399 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Command Block 27 20 Command code Destination IP address Timeout value Response Block 27 20 Command code Response code Parameters Destination IP Address (Command) The IP address (in hexadecimal) of the destination node for the PING command echo request packet. Timeout Value (Command) The wait time for the echo reply packet. The value is set in seconds. The timeout time is set at 20 seconds if the value is specified as 0. If the echo reply packet is not received within the set time limit, the code for a timeout error will be set as the results storage response code. Remarks PING Command The PING command runs the echoback test using the ICMP protocol. When the PING command is executed, an echo request packet is sent to the remote node ICMP. Correct communications are confirmed when the returned response packet is received normally. The echo reply packet is automatically returned by the remote node ICMP. Response Codes Response code 0000 0205 1001 1002 1100 220F 2211 Description Normal end (echo reply received from the remote node) Timeout error Command too large Command too small Zero destination address PING command currently being executed High traffic at Unit; cannot execute service. FINS/TCP CONNECTION REMOTE NODE CHANGE REQUEST Requests a remote node change for the FINS/TCP connection. The default destination IP address in a connection in which the EtherNet/IP Unit or built-in EtherNet/IP port is used as a client is the destination IP address set under the FINS/TCP Tab Page in the Unit Setup. By sending this command to the EtherNet/IP Unit or built-in EtherNet/IP port, the destination IP address for the specified connection can be changed to another IP address. Remote node changes can be made only for connection numbers specified as FINS/TCP clients in the Unit Setup. 400 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Command Block 27 30 Command FINS/TCP connection No. code Remote IP address Remote TCP port number Response Block 27 30 Command code Response code Parameters FINS/TCP Connection No. (Command) Specifies, in two bytes, the FINS/TCP connection number (1 to 16) for which the change is to be made. Remote IP Address (Command) Specifies the remote node’s IP address (must be non-zero) in hexadecimal. Remote Port Number (Command) Specifies the remote TCP port number (must be non-zero) with this command. Response Codes Response code 0000 0105 0302 1001 1002 1100 2230 2231 2232 Description Normal end Node address setting error Local IP address setting error CPU Unit error; execution not possible. Command too large Command too small Connection number not set from 1 to 16 Remote IP address set to 0 Remote TCP port number set to 0 Connection already established with specified remote node Specified connection number not set as FINS/TCP client in Unit Setup Remote node change processing for specified connection number aborted because change request received during processing FINS/TCP CONNECTION STATUS READ Reads the FINS/TCP connection status. Command Block 27 31 Command FINS/TCP code connection No. 401 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Response Block 27 31 Command code Response code FINS/TCP Connection connection service No. Local IP address Local TCP port number Remote IP address Remote TCP TCP transition port number Parameters FINS/TCP Connection No. (Command, Response) Command: Specifies, in two bytes, the FINS/TCP connection number (1 to 16) for which the status is to be read. Response: Specifies the FINS/TCP connection number (1 to 16) for which the status was read. Connection Service (Response) Specifies the service that is being used for the FINS/TCP connection as a number. 0003: FINS/TCP server 0004: FINS/TCP client Local IP Address (Response) Specifies the IP address for the local node in hexadecimal. Local TCP Port Number (Response) Specifies the TCP port number for the local node. Remote IP Address (Response) Specifies the IP address for the remote node in hexadecimal. Remote TCP Port Number (Response) Specifies the TCP port number for the remote node. TCP Transitions (Response) Specifies the TCP connection status using the following numbers. For details on TCP status changes, refer to Appendix C TCP Status Transitions. Number 00000000 00000001 00000002 00000003 00000004 00000005 00000006 00000007 00000008 00000009 0000000A 402 Status CLOSED LISTEN SYN SENT SYN RECEIVED ESTABLISHED CLOSE WAIT FIN WAIT 1 CLOSING LAST ACK FIN WAIT 2 TIME WAIT Meaning Connection closed. Waiting for connection. SYN sent in active status. SYN received and sent. Already established. FIN received and waiting for completion. Completed and FIN sent. Completed and exchanged FIN. Awaiting ACK. FIN sent and completed. Awaiting ACK. Completed and ACK received. Awaiting FIN. After closing, pauses twice the maximum segment life (2MSL). FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Response Codes Response code Description 0000 Normal end 0105 Node address setting error Local IP address setting error 0302 CPU Unit error; execution not possible. 1001 Command too large 1002 Command too small 1100 Connection number not set from 1 to 16 IP ADDRESS TABLE WRITE Writes the IP address table. Command Block 27 50 Command code Number of records 6 bytes 6 bytes IP address table records IP address table records Response Block 27 50 Command Response code code Parameters Number of Records (Command) The number of records to write is specified in hexadecimal between 0000 and 0020 (0 to 32 decimal) in the command. If this value is set to 0, the IP address table will be cleared so that no records are registered. IP Address Table Records (Command) Specify the IP address table records. The number of records specified must be provided. The total number of bytes in the IP address table records is calculated as the number of records × 6 bytes/record. The configuration of the 6 bytes of data in each record is as shown in the following diagram. 1 6 bytes 00 FINS node number IP address FINS Node Address Node address for communications via the FINS command (hexadecimal). IP Address IP address used by TCP/IP protocol (hexadecimal). Precautions • The registered IP address table will not be effective until the PLC or EtherNet/IP Unit or built-in EtherNet/IP port is restarted. 403 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E • An error response will be returned if the IP address conversion method in the system mode settings is set for automatic generation on the FINS/UDP Tab Page of the Unit. Response Codes Response code 0000 1001 1002 1003 110C 2307 Description Normal end (echo reply received from the remote node) Command too large Command too small The number of records specified does not match the sent data length. The number of records is not between 0 and 32. The FINS node address is not between 1 and 126 The IP address is 0. IP address conversion method is set for automatic generation. IP ADDRESS WRITE Write the local IP address and the subnet mask in the CPU Bus Unit System Setup. Command Block 27 57 Command code IP address Subnet mask Response Block 27 57 Command code Response code Parameters IP Address (Command) Specify the local IP address of the EtherNet/IP Unit or built-in EtherNet/IP port using 4 pairs of 2-digit hexadecimal numbers in the range 00.00.00.00 to FF.FF.FF.FF (0.0.0.0 to 255.255.255.255 decimal). Specify 0.0.0.0 to enable the local IP address set in the allocated DM Area words. Example: 150.31.2.83 96 1F 02 53 Subnet Mask (Command) Specify the local IP address of the EtherNet/IP Unit or built-in EtherNet/IP port using 4 pairs of hexadecimal numbers in the range 00.00.00.00 to FF.FF.FF.FF (0.0.0.0. to 255.255.255.255 decimal). Example: 255.255.255.255 FF FF FF 00 404 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Response Codes Response code 0000 1001 1002 Description Normal end Command too large Command too small Precautions • The local IP address and subnet mask set by this command are written to the CPU Bus Unit System Setup for the EtherNet/IP Unit or built-in EtherNet/IP port. • The new local IP address and subnet mask settings will become effective when the PLC or EtherNet/IP Unit or built-in EtherNet/IP port is restarted. IP ADDRESS TABLE READ Reads the IP address table. Command Block 27 60 Command code Number of records Response Block 27 60 Command code Response code Maximum number of stored records Number of stored records Number of records 6 bytes 6 bytes IP address table records IP address table records Parameters Number of Records (Command, Response) The number of records to read is specified between 0000 and 0020 (0 to 32 decimal) in the command. If this value is set to 0, the number of stored records is returned but the IP address table records are not returned. The response returns the actual number of records read. Maximum Number of Stored Records (Response) The maximum number of records that can be stored in the IP address table is returned. The maximum number of stored records is fixed at 0020 (32 records). Number of Stored Records (Response) The number of IP address table records stored at the time the command is executed is returned as a hexadecimal number. IP Address Table Records (Response) The number of IP address table records specified in the number of records parameter is returned. The total number of bytes in the IP address table records is calculated as the number of records × 6 bytes/record. The configuration of the 6 bytes of data in each record is as shown in the following diagram. 405 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports 1 Appendix E 6 bytes 00 IP address FINS node number FINS Node Address Node address for communications via the FINS command (in hexadecimal). IP Address IP number used by TCP/IP protocol (in hexadecimal). Precautions • If the IP address table contains fewer records than the number specified in the number of records parameter, all the records contained in the IP address table when the command is executed will be returned and the command execution will end normally. • An error response will be returned if the IP address conversion method in the system mode settings is set to the automatic generation method on the FINS/UDP Tab Page of the Unit. Response Codes Response code 0000 1001 1002 2307 Description Normal end Command too large Command too small IP address conversion method is set to the automatic generation method. IP ROUTER TABLE READ Reads the IP router table. Command Block 27 61 Command code Number of records Response Block 27 61 Command code Response code Maximum number of stored records Number of stored records Number of records 8 bytes 8 bytes IP router table records IP router table records Parameters Number of Records (Command, Response) The number of records to read is specified between 0000 and 0008 (0 to 8 decimal) in the command. If this value is set to 0, the number of stored records will be returned but the IP router table records will not be returned. The response returns the actual number of records read. 406 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Maximum Number of Stored Records (Response) The maximum number of records that can be stored in the IP router table is returned. The maximum number of stored records is fixed at 0008 (8 records). Number of Stored Records (Response) The number of IP router table records stored at the time the command is executed is returned in hexadecimal. IP Router table Records (Response) The number of IP router table records specified in the number of records parameter is returned. The total number of bytes in the IP router table records is calculated as the number of records × 8 bytes/record. The configuration of the 8 bytes of data in each record is shown below. 8 bytes 1 Router IP address IP Network address (Network ID) IP Network Address The network ID from the IP address in hexadecimal. The network ID part corresponding to the address class (determined by the leftmost 3 bits) set here, is enabled. Router IP Address The IP address (in hexadecimal) of a router connected to a network specified with IP addresses. Precautions If the IP router table contains fewer records than the number specified in the number of records parameter, all the records contained in the IP router table when the command is executed will be returned and the command execution will end normally. Response Codes Response code 0000 1001 1002 Description Normal end Command too large Command too small PROTOCOL STATUS READ Reads the protocol status or the EtherNet/IP Unit or built-in EtherNet/IP port. Command Block 27 62 Command code Response Block 27 62 Command code Response code 48 bytes 184 bytes IP status ICMP status 184 bytes 12 bytes TCP status UDP status 407 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Parameters IP Status (Response) Twelve types of IP status information occupying 4 bytes each are returned in the following sequence. Each value is returned as an 8-digit hexadecimal value. 1. Total number of IP packets received. 2. The number of IP packets discarded due to an error with the checksum in the packet header. 3. The number of IP packets discarded because the received packet was larger than the overall packet length value in the packet header. 4. The number of IP packets discarded because the minimum size of the IP header data could not be stored in the first short buffer (See note.) when an attempt was made to store the packet. 5. The number of packets discarded for one of the following reasons: • The IP header length value in the IP header was smaller than the smallest size of the IP header. • The size of the first short buffer (See note.) was smaller than the IP header length value in the IP header when storing the packet. 6. The number of IP packets discarded because the IP header length was larger than the overall packet length value in the packet header. 7. The number of fragmented packets received. 8. The number of received fragmented IP packets discarded because a queue for reassembly could not be secured. 9. The number of fragmented IP packets discarded because they could not be reassembled within 12 seconds after being received. 10. Always 0. 11. The number of packets addressed to other networks that have been discarded. 12. Always 0. Note Refer to MEMORY STATUS READ on page 411 for details on the short buffer. ICMP Status (Response) Ten types (46 items) of ICMP status information occupying 4 bytes each are returned in the following sequence. Each value is returned as an 8-digit hexadecimal value. 1. The number of times the ICMP error routine was called. The ICMP error routine uses ICMP packets to inform the source about errors. The routine is called when an illegal packet is received (error in IP option processing or error in relay processing) or if the object port does not exist when using UDP. 2. Always 0. 3. Always 0. 4. Total number of outputs of each packet type during ICMP output. The 19 statistical values are returned in the order shown below. Contents are defined for 13 types only; all other types contain 0. Only #0, #3, #14, #16, and #18 are counted by the EtherNet/IP Unit or built-in EtherNet/IP port. #0 #1 #2 #3 #4 #5 #15 4 bytes Type number #0 #1, #2 #3 #4 #5 408 Description Echo reply Undefined, always 0 Destination unreachable Source quench Routing redirect #16 #17 #18 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Type number #6, #7 #8 #9, #10 #11 #12 #13 #14 #15 #16 #17 #18 Appendix E Description Undefined, always 0 Echo Undefined, always 0 Time exceeded Parameter problem Time stamp Time stamp reply Information request Information request reply Address mask request Address mask reply 5. The number of received ICMP packets discarded because the type-indication code was out of range. 6. The number of received ICMP packets discarded because the overall packet length value in the packet header was smaller than the minimum ICMP packet length. 7. The number of received ICMP packets discarded because of an incorrect checksum value in the packet header. 8. The number of received ICMP packets discarded because the ICMP header length value in the packet header did not match the lengths of individual header types. 9. The number of responses returned to received ICMP packets requiring a response. 10. Total number of inputs of each packet type during ICMP input. The 19 statistical values are returned in the order shown below. Contents are defined for 13 types only; all other types contain 0. #0 #1 #2 #3 #4 #5 #15 #16 #17 #18 4 bytes Type number #0 #1, #2 #3 #4 #5 #6, #7 #8 #9, #10 #11 #12 #13 #14 #15 #16 #17 #18 Description Echo reply Undefined, always 0 Destination unreachable Source quench Routing redirect Undefined, always 0 Echo Undefined, always 0 Time exceeded Parameter problem Time stamp Time stamp reply Information request Information request reply Address mask request Address mask reply TCP Status (Response) Three types (46 items) of TCP status information occupying 4 bytes each are returned in the following sequence. Each value is returned as an 8-digit hexadecimal value. 1) Connection Information (60 Bytes) Fifteen items are returned in the following sequence: 409 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E 1. The number of times active connections were correctly established. 2. The number of times a SYN packet was received while waiting to establish a passive connection. 3. The number of times active or passive connections were correctly established. 4. The number of times an established connection was cut off. 5. The number of times the connection wait status was cut off. 6. The number of times protocol control blocks or other actively allocated structures were released. 7. The number of segments for the round-trip time (time from segment transmission to ACK). 8. The number of times the round-trip time was changed. 9. The number of times a delayed acknowledgement (ACK) was sent. If the order of the received segments is reversed, ACK is sent with a packet of data separate from ACK (response to input data, etc.) or is immediately sent with the ACK for other data. 10. The number of times the connection was cut off because no ACK was returned after several resend attempts. 11. The number of times no ACK was returned within the resend timer set time. (The resend timer sets the maximum time limit between the data being output and ACK being returned.) 12. The number of times no window advertisement is received within the time set on the duration timer. (The duration timer sets the maximum time limit for a window advertisement to be received if the transmission window is smaller than necessary and the resend timer is not set. If no window advertisement is received within the time limit, the number of segments permitted by the transmission window are sent. If the transmission window is set to 0, a window probe (1 octet of data) is sent before the timer restarts.) 13. The number of times no segment was sent or received within the time set on the hold timer. 14. The number of times the hold packet is resent. (Always 0.) 15. The number of times the hold packet is sent without response before the connection is cut off. 2) Send Information (40 Bytes) Ten information items are returned in the following sequence: 1. The total number of packets sent. 2. The number of data packets sent. 3. The number of data bytes sent. 4. The number of data packets resent. 5. The number of data bytes resent. 6. The number of ACK packets sent. 7. The number of window probes (1 octet of data) sent. 8. The number of emergency data packets sent. (Always 0.) 9. The number of window advertisement packets sent. 10. The number of control packets (SYN, FIN, RST) sent. 3) Receive Information (84 Bytes) Twenty-one information items are returned in the following sequence: 1. The total number of packets received. 2. The number of packets received continuously. 3. The number of bytes received continuously. 4. The number of received packets discarded due to an incorrect checksum. 5. The number of packets discarded because the TCP header was smaller than the minimum size for a TCP header or was larger than the IP packet. 6. The number of packets discarded because the TCP header and IP header could not be stored in the first short buffer. 7. The number of resent packets received. 410 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E 8. The number of bytes in the resend packets. 9. The number of duplicated resend packets received. 10. The number of bytes in the duplicated resend packets received. 11. The number of out-of-range data packets received. (Always 0.) 12. The number of bytes in the out-of-range data packets received. (Always 0.) 13. The number of packets where the data was larger than the window. 14. The number of bytes in the packets where the data was larger than the window. 15. The number of packets received after closing. 16. The number of window probe packets received. 17. The number of resent ACK packets received. 18. The number of ACK packets received with no data set. 19. The number of ACK packets received. 20. The number of ACK packets received for received transmission acknowledgements (ACK). 21. The number of window advertisement packets received. UDP Status (Response) Three items of UDP information occupying 4 bytes each are returned in the following sequence. Each value is returned as an 8-digit hexadecimal value. 1. The number of packets discarded because the size of the first short buffer was smaller than the minimum size (28) of the IP header and UDP header when the packet was stored. 2. The number of packets discarded due to an incorrect checksum in the UDP header. 3. The number of packets discarded because the IP overall length in the IP header was shorter than the UDP overall length in the UDP header. Precautions All the above values are set to 0 if network operation stops due to incorrect settings in the system setup. Counting will be stopped when a count reaches the maximum value. The maximum values are as follows: IP, ICMP, or UDP status: 7FFFFFFF (2,147,483,647 decimal) TC status: FFFFFFFF (4,294,967,295 decimal) Response Codes Response code 0000 1001 Description Normal end Command too large MEMORY STATUS READ Reads the status of the network memory for the EtherNet/IP Unit or built-in EtherNet/IP port. The network memory contains 2,991 bytes that are used as required as for communications buffers for communications servicing. The network memory consists of 23,928 short buffers (128 bytes each) and 64 long buffers (1,024 bytes each). Command Block 27 63 Command code 411 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Response Block 27 63 Command code 92 bytes Response code Memory status Parameters Memory Status (Response) A total of 23 data items in six areas are returned in the following order. Each item consists of 4 bytes. 1) Short Buffer Application: Two items are returned (8 bytes). 1. The number of short buffers currently being used. 2. The number of short buffers in the system (fixed at 23,928 decimal). 2) Short Buffer Application by Type: Thirteen items are returned (52 bytes). 1. The number of short buffers used for storing communications data 2. The number of short buffers used for protocol headers (TCP, UDP, IP, ICMP, ARP) 3. The number of short buffers used in socket structures 4. The number of short buffers used as protocol control blocks 5. The number of short buffers used for routing tables 6. Not used (always 0) 7. Not used (always 0) 8. The number of short buffers used for IP fragment re-assembly queue headers 9. The number of short buffers used for storing socket addresses 10. Not used (always 0) 11. The number of short buffers used for storing socket options 12. The number of short buffers used for storing access rights 13. The number of short buffers used for storing interface addresses 3) Long Buffer Application: Two items are returned (8 bytes). 1. The number of long buffers currently being used. 2. The number of long buffers in the system (fixed at 64 decimal). 4) Not Used: Always 0. (4 bytes) 5) Network Memory Application: Two items are returned (8 bytes). 1. The number of bytes used (in K bytes) 2. The percentage used 6) Memory Exhaustion Log (12 bytes) Counts for the following values indicate a high load on the EtherNet/IP Unit or built-in EtherNet/IP port. These high loads may be caused by problems in communications, particularly FINS communications and UDP sockets. If these values are consistently high, check your applications. 1. The number of times an attempt was made to secure a short buffer without WAIT when there were no short buffers available. 2. The number of times an attempt was made to secure a short buffer with WAIT when there were no short buffers available. 3. The number of times an attempt was made to release and secure a short buffer already being used by another socket when there were no short buffers available. 412 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Precautions All the above values are set to 0 if Ethernet communications functions are stopped due to improper settings in the system setup. These values are cleared when the EtherNet/IP Unit or built-in EtherNet/IP port is started or reset. Values will be counted only until the maximum values are reached. Response Codes Response code 0000 1001 Description Normal end Command too large SOCKET STATUS READ Reads the network socket status of the EtherNet/IP Unit or built-in EtherNet/IP port. Command Block 27 64 Command code Response Block 27 64 Command code Response code 32 bytes 32 bytes Socket status Socket status Parameters Socket Status (Response) Returns eight types of information in records of 32 bytes each. A maximum of 62 records can be returned. The format of each record is shown below. Protocol (4 bytes) The protocol used for the socket is returned as a number. 00 00 00 06: TCP; 00 00 00 11: UDP Receive Queue (4 bytes) The number of bytes in the reception queue. Send Queue (4 bytes) The number of bytes in the send queue. Local IP Address (4 bytes) The local IP address allocated to the socket. Local Port Number (4 bytes) The local port number allocated to the socket. Remote IP Address (4 bytes) The remote IP address allocated to the socket. 413 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Remote Port Number (4 bytes) The remote port number allocated to the socket. TCP Transitions (4 bytes) The TCP connection status is returned as one of the numbers shown in the following table. Refer to Appendix C TCP Status Transitions for a diagram of transitions. Number 00 00 00 00 00 00 00 01 00 00 00 02 00 00 00 03 00 00 00 04 00 00 00 05 00 00 00 06 00 00 00 07 00 00 00 08 00 00 00 09 00 00 00 0A Stage CLOSED LISTEN SYN SENT SYN RECEIVED ESTABLISHED CLOSE WAIT FIN WAIT 1 CLOSING LAST ACK FIN WAIT 2 TIME WAIT Status Closed. Waiting for connection. SYN sent in active status. SYN received and sent. Already established. Received FIN, waiting to close. Completed and FIN sent. Completed and exchanged FIN. Awaiting ACK. FIN sent and completed. Awaiting ACK. Close completed and ACK received. Awaiting FIN. After closing, pauses twice the maximum segment life (2MSL). Precautions All the above values are set to 0 if Ethernet communications functions are stopped due to improper settings in the system setup. Response Codes Response code 0000 1001 Description Normal end Command too large ADDRESS INFORMATION READ Reads FINS node addresses and IP addresses Command Block 27 65 Command code Response Block 27 65 Command code 6 bytes Response Number code of addresses Address information Parameters Number of Addresses (Response) Returns the number of pairs of FINS node addresses and IP addresses. With the EtherNet/IP Unit or built-in EtherNet/IP port, this value is always 0001 (1 decimal). 414 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E Address Information Returns the FINS node addresses and IP addresses. Each pair requires 6 bytes and has the following configuration. 1 6 bytes 00 FINS node number IP address FINS Node Address Node address set in the EtherNet/IP Unit or built-in EtherNet/IP port (hexadecimal). IP Address IP address set in the EtherNet/IP Unit or built-in EtherNet/IP port (hexadecimal). Response Codes Response code 0000 1001 Description Normal end Command too large IP ADDRESS READ Reads the local IP address and subnet mask in the CPU Bus Unit System Setup and the FINS node address. The values read with this command, however, are not necessarily the settings actually used for operation. The settings that are actually used for operation can be confirmed using CONTROLLER DATA READ (page 392) and ADDRESS INFORMATION READ (page 414). This command is supported for CJ-series EtherNet/IP Units only. Command Block 27 67 Command code Response Block 27 67 Command code 00 Response code Number of addresses IP address FINS node number Subnet mask Parameters Number of Addresses (Response) The number of sets of FINS node addresses, IP addresses, and subnet masks being returned. The EtherNet/ IP Unit or built-in EtherNet/IP port is always 0001 (1 decimal). FINS Node Address (Response) Node address set on the EtherNet/IP Unit or built-in EtherNet/IP port (hexadecimal). 415 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E IP Address (Response) The local IP address set in the CPU Bus Unit System Setup for the EtherNet/IP Unit or built-in EtherNet/IP port is returned in order starting from the leftmost bytes in hexadecimal. If the local IP address set in the allocated words in the DM Area is enabled, 0.0.0.0 is returned. Subnet Mask (Response) The subnet mask set in the CPU Bus Unit System Setup for the EtherNet/IP Unit or built-in EtherNet/IP port is returned in order starting from the leftmost bytes in hexadecimal. Response Codes Response code 0000 1001 Description Normal end Command too large EXPLICIT MESSAGE SEND Sends a explicit request message to the specified object, and receives a response. The rightmost 8 bits of the remote (destination) IP address are used as the remote MAC ID, and the remote IP address is the network ID of the local IP address + the rightmost 8 bits of the remote IP address. Command Block 28 01 468 bytes max. Command code Class ID Service Code Destination node address Instance ID Service Data Response Block 28 01 Command code 00 00 498 bytes max. Service Data Service Code Destination node address (remote node) End code Number of bytes received Response Codes Response code 0000 0101 0105 0106 0201 0204 0205 1001 1002 1004 1005 416 Description Normal end The local node’s network has not started up. Local node setting error (A BOOTP errors occurs, and the IP address is undetermined.) Duplicate address error The remote node’s network has not started up. Remote node busy, cannot send. No response returned from remote node. Monitoring timer timed out. Command length exceeds maximum command length. Command length is less than minimum command length. Command block format does not match. Header error FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Response code 110B 2211 Appendix E Description Response length exceeds maximum response length. Unit is busy. Description For details, refer to EXPLICIT MESSAGE SEND (28 01) on page 241 in 9-1-1 Sending Explicit Messages Using CMND(490). CIP UCMM MESSAGE SEND Sends a message in the CIP message (UCMM) format. Command Block 2810 hex Command code Transport Message monitoring ID timer 502 bytes max. Request bus size (variable length) Request bus size Service code Request data (variable length) Response Block 2810 hex 0000 hex Command code End code 00 hex Transport Number of ID bytes received 502 bytes max. 00 hex 00 hex Service response data (variable length) Reserved General status Reserved Service code (response) Response Codes Response code 0000 0101 0106 0201 0204 0205 1001 1002 1004 Description Normal end The local node’s network has not started up. Duplicate address error The remote node’s network has not started up. Remote node busy, cannot send. No response returned from remote node. Monitoring timer timed out. Command length exceeds maximum command length. Command length is less than minimum command length. Command block format does not match. 417 FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Response code 1005 110B 2211 Appendix E Description Header error Response length exceeds maximum response length. Unit is busy. Description For details, refer to CIP UCMM MESSAGE SEND (28 10) on page 236 in 9-1-1 Sending Explicit Messages Using CMND(490). 418 Appendix F EDS File Management This section explains the EDS file management functions used in the Network Configurator. Installing EDS Files Note Using Windows Vista or Windows 7 Is recommended that you start the Network Configurator from Run as administrator when you install an EDS file in the Network Configurator. If the EDS file is installed on a Network Configurator that is started in any other way, Windows security user management will cause the installed EDS file to not be recognized when you log in using a different user account. You can run the Network Configurator as the administrator by using the following procedure. 1. Select the Network Configurator from the Start Menu, and then right-click. 2. Select Run as administrator from the pop-up menu that is displayed. EDS File - Install The Network Configurator can support new devices if the proper EDS files are installed. To install the EDS file, use the following procedure. 1. Select EDS File and Install. The following window will be displayed. 2. The device information will be displayed on the bottom of the window when the EDS file is selected. 419 EDS File Management Appendix F 3. Select the EDS file to be installed and click the Open Button. Next, select the icon file (*.ico), and the EDS file will be added to the Hardware List. If the EDS file already exists, the new EDS file will overwrite the previous one. If the hardware versions are different, an EDS file will be added to the Hardware List for each version. Creating EDS Files EDS File - Create The EDS files are required by the Network Configurator in order to create a network configuration. To create an EDS file, use the following procedure. 1. Select EDS File - Create. 2. Set the device information and I/O information. The device information can be obtained from the device on the network if the network is online. 3. The device can be added to the Hardware List as a new device, just like installing an EDS file. Note Device parameters cannot be set with the Network Configurator’s EDS file creation function. Obtain a proper EDS file from the manufacturer of the device to make device parameter settings for the device. Deleting EDS Files EDS File - Delete To delete an EDS file, use the following procedure. 1. Select the device from the Hardware List. 2. Select EDS File - Delete. The following confirmation window will be displayed. 3. Click the Yes Button. The selected device will be deleted from the Hardware List together with the EDS file. Saving EDS Files EDS File - Save To save the EDS file, use the following procedure. 1. Select the device from the Hardware List. 2. Select EDS file - Save As. The following window will be displayed to specify the name of the folder where the EDS file will be saved and the name of the EDS file. 420 EDS File Management Appendix F 3. Input the folder and file names and click the Save Button The EDS file will be saved. Searching EDS Files EDS File - Search To search the devices (EDS files) displayed in the Hardware List, use the following procedure. 1. Select EDS file - Find. The following window will be displayed. 2. Input the character string and click the Find Next Button. 3. When there is a matching device found, the cursor will move to that position. 4. To quit the search operation, click the Cancel Button. Note (1) The device will be found if it is located below the present cursor position. (2) To search all the devices, select Hardware in the Hardware List before performing the search procedure. Displaying EDS File Properties EDS File - Property To display the properties of the EDS file, use the following procedure. 1. Select the desired hardware (device) from the Hardware List. 421 EDS File Management Appendix F 2. Select EDS File - Property. The following window will be displayed. The time and date that the EDS file was created will be displayed, along with the device information. 422 Appendix G Precautions for Using Windows XP, Vista, or Windows 7 Changing Windows Firewall Settings Better firewall security for Windows XP (SP2 or higher), Windows Vista, and Windows 7 has increased the restrictions for data communications on Ethernet ports. When using an EtherNet/IP connection*1 to one of the following PLCs from an Ethernet port on a computer, you must change the settings of the Windows Firewall to enable using CX-Programmer or Network Configurator communications. Applicable PLCs: • CJ2H-CPU@@-EIP/CJ2M-CPU3@ • CS1W/CJ1W-EIP@@ *1 CX-Programmer • An EtherNet/IP connection includes the following cases: • An online connection with the network type set to EtherNet/IP • An automatic online connection to a PLC on an EtherNet/IP network when Auto Online - EtherNet/IP Node Online is selected from the PLC Menu Network Configurator • A connection made by selecting Option - Select Interface - Ethernet I/F Note Windows Firewall is mainly designed to prevent inappropriate access from external devices (e.g., via the Internet). The changes to the Windows Firewall settings described in this document enable EtherNet/IP connections to be used by the CX-Programmer. If the same computer is being used on a company network or other network, confirm that the changes will not create security problems before proceeding with the changes. The changes described in this document are required only when you connect using EtherNet/IP through an Ethernet port. No changes are necessary if you are connecting through any other port, such as a USB port. Changing Windows Firewall Settings Windows XP 1. When you attempt to connect the CX-Programmer or Network Configurator to a PLC on an EtherNet/IP network through an Ethernet port, the Windows Security Alert Dialog Box will be displayed. 2. Click the Unblock Button. An EtherNet/IP connection will be accepted from CX-Programmer or Network Configurator and EtherNet/ IP connections will be enabled in the future as well. Windows Vista or Windows 7 Use the following procedure to change the settings before attempting to connect from the CX-Programmer or Network Configurator. 423 Precautions for Using Windows XP, Vista, or Windows 7 Appendix G The User Account Control Dialog Box may be displayed during this procedure. If it appears, click the Continue Button and continue with the procedure. 1. Select Control Panel from the Windows Start Menu and change the display to Classic View. 2. Open the Administrative Tools and select Windows Firewall with Advanced Security from the dialog box that is displayed. 3. Select Inbound Rules under Windows Firewall with Advanced Security on Local Computer on the left side of the Windows Firewall with Advanced Security Dialog Box. 4. Select New Rule under Inbound Rules in the Actions Area on the right side of the dialog box. 5. Make the following settings for each step in the New Inbound Rule Wizard Dialog Box, clicking the Next Button to move between steps. Rule Type Program Protocol and Ports Select Custom. Select All Programs. Select ICMPv4 as the protocol type. Scope Action Profile Name Select Any IP address for everything. Select Allow the connection. Select Domain, Private, and Public. Enter any name, e.g., Omron_EIP. 6. Click the Finish Button. The rule that you defined will be registered in the Inbound Rules (e.g., Omron_EIP). Close the Windows Firewall with Advanced Security Dialog Box. 7. When you attempt to connect the CX-Programmer or Network Configurator to a PLC on an EtherNet/IP network through an Ethernet port, the Windows Security Alert Dialog Box will be displayed. 8. Click the Unblock Button. 424 Precautions for Using Windows XP, Vista, or Windows 7 Appendix G An EtherNet/IP connection will be accepted from CX-Programmer or Network Configurator and EtherNet/ IP connections will be enabled in the future as well. 425 Precautions for Using Windows XP, Vista, or Windows 7 426 Appendix G Index Numerics 7-segment display, 24 A Adjust Time field, 326, 328 alternate DNS server, 54 applications precautions, xxiv Auto Adjust Time field, 326, 327 Auto Adjust Time Tab, 326, 327 automatic clock adjustment Automatic Clock Adjustment Switch, 328 errors error codes, 328 error log, 328 SNTP, 328 overview, 324 procedure, 325 requirements, 324 settings, 326 specifications, 325 Auxiliary Area related data, 88 B C cables connections, 44 installation, 43 precautions, 41 cd command, 303, 308, 310 cdup command, 303, 308 CIDR, 3, 94 CIO Area allocations, 70 CIP, 3, 381 CIP communications services, 6 CIP message communications., 381 cleaning, 332 close command, 303, 308, 312 CMND(490) instruction, 190, 220, 224 commands FTP commands, 308 communications high traffic conditions, 232 message communications, 187, 233 message communications errors, 195 communications cables, xxv Communications Port Enabled Flags, 226 Communications Port Error Flags, 226 communications specifications, 17 Backup Tool, 336 Communications Status 1 Flags, 77 bandwidth usage relationship to packet interval (RPI), 263 Communications Status 3 Flags, 79 Communications Status 2 Flags, 79 communications test, 65 baud rate, 55, 268 CJ-series, 15, 16 CS-series, 14 component names, 21 bits Automatic Clock Adjustment Switch, 328 connection setting, 141 boots recommended models, 28 Connections Tab, 141 BROADCAST DATA SEND, 397 connecting to the FTP server, 304 Connections settings (Edit All Connections), 144 connectors (modular plug) recommended models, 28 broadcast test command, 397 reading results, 397 Contact Output Units precautions, 43 BROADCAST TEST RESULTS READ, 397 control bits, 71 buffers, 377, 411 CONTROLLER DATA READ, 392 bye command, 303, 308, 312 CONTROLLER STATUS READ, 394 CPU Bus Units precautions, xxvi 427 Index creating a tag set, 126 creating tag sets, 126 E creating tags, 128 EC Directives, xxvi crimp terminals, xxv Edit Parameters, 52, 61 current consumption CJ-series, 15, 16 CS-series, 14 CX-Integrator, 46 creating routing tables, 208 CX-Programmer, 8, 46 connecting to PLC, 211 cyclic communications required settings, 35 EDS file management, 419 EDS files, 10, 419 creating, 420 installing, 419 saving, 420 searching, 421 electromagnetic fields, xxiv EM File Memory, 315 using, 315 EMC Directives, xxvi D EMI Standard, xxvi EMS Standard, xxvi Datalink Tool, 57 EPATH type, 383 default gateway, 54 error codes table of error codes, 365 delays message service delays, 294 delete command, 303, 308, 312 Device Monitor function, 340 device parameters clearing, 176 editing, 127 devices registering, 125 DHCP client computer, 102 DHCP service automatic IP address setting by DHCP service, 102 dimensions CJ-series, 15, 16, 19 CS-series, 14, 19 dir command, 303, 308, 309 distance CJ-series transmission distance, 15, 16 transmission distance, 14 DM Area allocations, 83 DNS server, 54 automatic clock adjustment errors, 328 error flags Target Node PLC Error Flags, 73, 87 error log clearing, 364 codes, 365 overflow, 364 specifications, 364 ERROR LOG CLEAR, 399 error log function, 364 ERROR LOG READ, 398 error processing, 339 errors automatic clock adjustment, 328 controller status, 394 error log clearing, 399 reading, 398 error messages, 313 flags FINS communications, 394 message communications, 194, 195 domain name, 55 Ethernet communications addresses reading from Unit, 392 network parameters, 375 parameters, 375, 377 downloading tag data link parameters, 168 Ethernet Connectors, 44 dynamic changes of remote IP address prohibiting, 99 Ethernet Units reading status, 411 DNS Tab, 326 EtherNet/IP Datalink Tool, 57 428 Index EtherNet/IP Unit Features, 2 EtherNet/IP Units resetting, 391 ETN11-compatible mode, 99 explicit message communications, 187, 233 explicit message communications service, 106, 108 explicit messages list of PLC object services, 249 receiving, 248 sending, 234 sending using CMND(490), 243 F FALS instruction, xxiii FINS communications, 233 overview, 8 specifications, 199, 220 testing, 399 FINS communications service, 106, 107 FINS communications services, 94 FINS message communications, 187, 190 FINS node address relationship to IP address, 94, 105 FINS response codes troubleshooting with response codes, 371 FINS/TCP, 202 communications, 204 connection numbers, 203 connection status, 204 features, 202 frame format, 203 procedure, 205 TCP port number, 203 FINS/TCP communications method, 100 FINS/TCP Connection Status Flags, 81 FINS/UDP, 200 frame format, 200 procedure, 201 UDP port numbers, 201 FINS/UDP and FINS/TCP comparison, 199 FINS/UDP communications methods, 96 FinsGateway, 215 flags Error Flags, 394 FTP Status Flag, 314 FTP, 3, 62, 302 FTP server application examples, 307 commands, 308 bye, 312 cd, 310 close, 312 delete, 312 dir, 309 get, 311 ls, 309 mdelete, 312 mget, 311 mput, 311 open, 308 put, 311 pwd, 310 quitting, 312 type, 311 user, 309 connecting, 304, 308 data type, 311 displaying current directory, 310 file types, 303 protection, 303 protocol, 303 quitting, 312 See also Memory Cards specifications, 303 status, 314 FTP Status Flag, 314 full duplex, 55 G gateway default gateway, 54 general specifications, 14 get command, 303, 308, 311, 320 Get the time information from the SNTP server field, 326, 327 global address, 106 GMRP, 29 H half duplex, 55 high communications traffic preventing, 232 host name, 54 429 Index Host name field, 326, 327 I I/O allocations CIO Area, 70 DM Area, 83 I/O memory address, 116 reading tables, 405 IP router tables reading, 406 status, 408 IP ROUTER TABLE READ, 406 L I/O response time, 283 ladder programming for tag data links, 183 I/O tables creating, 46 overview, 46 LED indicators, 23 using for troubleshooting, 347 ICMP communications status, 408 link setting (baud rate), 55 local network table, 207 IGMP snooping, 29 locking devices precautions, xxv importing, 136 Login field, 306 indicators, 23 using LED indicators for troubleshooting, 347 Low Voltage Directive, xxvi ls command, 303, 308, 309 initial settings, 34 installation, 33 cable connections, 44 location, xxiv mounting Unit to PLC, 38 precautions, 41 INTERNODE ECHO TEST, 396 internode test command, 396 IP address, 54, 92 automatic generation, 95 automatic generation (dynamic), 96 automatic generation (static), 97 automatic IP address setting by DHCP service, 102 combined method, 98 determining IP addresses, 92 global address, 106 IP address table method, 95, 97 private address, 106 prohibiting dynamic changes of remote IP address, 99 relationship to FINS node address, 94, 105 responding to computers with changed IP address, 102 M maintenance, 332 maximum tag data link I/O response time, 286 mdelete command, 303, 308, 312 memory allocation, 68 Memory Card, 334 restoring data, 335 Memory Cards, 303, 315 deleting files, 312 displaying directories, 309 See also FTP server transferring files from host, 311 transferring files to host, 311 MEMORY STATUS READ, 411 message communications, 7, 233 errors, 194 specifications, 193 message communications functions, 187 IP Address Display/Setting Area, 83 message communications service required settings, 35 IP Address field, 326, 327 mget command, 303, 308, 311 IP ADDRESS TABLE READ, 405 mkdir command, 303, 308 IP addresses allocating, 92 configuration, 92 mode settings reading from Unit, 392 IP communications IP addresses reading from Units, 392 mput command, 303, 308, 311 430 mounting procedure, 39 MS indicator, 23 Index multicast communications, 114 multicast filter, 29 PING, 399 PING command, 65 PLC object services, 249 N n beginning word of allocated CIO Area, 70 Port No. field, 306, 326, 327 port numbers UDP port reading from Unit, 392 network devices required for constructing a network, 4 power supply, xxiv precautions, xxv network configuration file reading, 178 saving, 177 precautions, xxi applications, xxiv Contact Output Units, 43 general, xxii handling, 40 installation, 41 operating environment, xxiv power supply, xxv safety, xxii wiring, 44 Network Configurator, 121 connecting to the network, 161 Device Monitor function, 340 requirements, 10 starting, 121 TCP/IP settings, 55 Network Configurator overview, 10 network devices recommended devices, 28 networks network memory, 411 network parameters, 375 Node Address Setting Switch, 27 node addresses setting, 36, 37 noise, xxiv Contact Output Units, 43 reducing, 41 nomenclature and functions, 21 Normal Target Node Flags, 81, 86 NS indicator, 23 O online editing, xxiii open command, 303, 308 operating environment precautions, xxiv P packet interval (RPI) relationship to bandwidth usage, 263 setting, 262 Password field, 306 PCMR(260) instruction, 227 preferred DNS server, 54 private address, 106 Programming Console, 46 Programming Devices connecting, 46 CX-Net, 46 CX-Programmer, 46 Programming Console, 46 PROTOCOL STATUS READ, 407 protocols FTP server, 303 reading status, 407 put command, 303, 308, 311, 320 pwd command, 303, 308, 310 Q QoS, 29 quit command, 303, 308, 312 R radioactivity, xxiv receiving explicit messages, 248 recommended network devices, 28 recommended products, 41 RECV(098) instruction, 190, 220, 223 accessible data areas, 221 delays, 297 431 Index refresh cycle, 268 Register Device List, 141 Registered Target Node Flags, 81, 85 registering devices, 125, 141 relay tables, 207 rename command, 303, 308 CJ-series general specifications, 15, 16 communications specifications, 17 CS-series general specifications, 14 FINS communications, 220 FTP server, 303 message communications, 193 Network Configurator, 10 replacing a Unit, 332 startup procedure, 34 replacing Units precautions, xxv static electricity, xxiv precautions, xxv restoring data from the Memory Card, 335 Retry timer field, 326, 328 rmdir command, 303, 308 route path, 383 routing tables, 207 precautions, xxvi relay network table, 207 setting examples, 209 S safety precautions, xxii SEND(090) instruction, 190, 220, 222 accessible data areas, 221 delays, 294 sending explicit messages, 243 Server specification type field, 326, 327 Setup Tab, 306 seven-segment Display, 24 seven-segment display error status, 347, 351, 353, 355, 358 short-circuits precautions, xxv status flags for tag data links, 186 subnet mask, 93 subnet masks, 54 reading from Unit, 392 switch Node Address Setting Switch, 27 switching hub connection methods, 42 environment precautions, 42 functions, 29 precautions when selecting, 29 recommended models, 28 switching hub types, 28 SYSMAC BUS/2, 220 SYSMAC LINK, 220 T SNMP trap, 64 tag data link parameters downloading, 113, 168 setting, 113 uploading, 171 verifying, 172 SNTP, 3, 63, 324 Tag Data Link Start Bit, 72 Simple Backup Function, 333 SNMP, 3, 64 SNTP server automatic clock adjustment errors, 328 obtaining clock information, 324 SOCKET STATUS READ, 379, 413 sockets reading status, 413 TCP sockets status, 379 testing communications, 399 specifications, 14 432 status reading memory status, 411 reading protocol status, 407 reading socket status, 413 Tag Data Link Stop Bit, 72 tag data links checking bandwidth usage, 269 data areas, 116 delay time, 265 functions, 115 I/O response time, 283 ladder programming, 183 maximum I/O response time, 286 overview, 112 required settings, 35 Index specifications, 115 status flags, 186 tag data links (cyclic communications), 6 tag set, 116 W wiring precautions, 44 tag sets creating, 126 Target Node PLC Error Flags, 73, 87 Target Node PLC Operating Flags, 73, 87 TCP communications sockets status, 379 status, 409 TCP status transitions, 379 TCP/IP, 52 terminal blocks, xxiii timeout errors, 371 timers, 377 to, 61 troubleshooting, 368 twisted-pair cable recommended models, 28 twisted-pair cables precautions, 41 type command, 303, 308, 311 U unicast communications, 114 unit numbers setting, 36, 37 Unit replacement, 332 unit setup, 4, 61 Unit Status 1 Flags, 73 Unit Status 2 Flags, 75 Unregister Device List, 142 uploading tag data link parameters, 171 user command, 303, 308, 309 user name specifying, 309 User Settings Area, 85 using FTP commands, 308 V verifying tag data link parameters, 172 433 Index 434 Revision History A manual revision code appears as a suffix to the catalog number on the front cover of the manual. Cat. No. W465-E1-05 Revision code The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version. Revision code 01 02 03 04 05 Date June 2007 July 2008 Revised content Original production Added information for CJ-series CJ2 CPU Units and for new unit version 2.0 functions. December 2008 Added the CJ-series CJ2 CPU Units (CJ2H-CPU@@). December 2009 Added information on methods to create connections and heartbeats. Greatly changed the structure of sections 1 and 2. Added and improved information on communications performance and communications load in section 10. Made changes accompanying a new version of the Network Configurator (V3.10). February 2010 Added the CJ-series CJ2M CPU Units (CJ2M-CPU3@). 435 Revision History 436 OMRON Corporation Industrial Automation Company Authorized Distributor: Tokyo, JAPAN Contact: www.ia.omron.com Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69-2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC One Commerce Drive Schaumburg, IL 60173-5302 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 OMRON ASIA PACIFIC PTE. LTD. No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711 OMRON (CHINA) CO., LTD. Room 2211, Bank of China Tower, 200 Yin Cheng Zhong Road, PuDong New Area, Shanghai, 200120, China Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 © OMRON Corporation 2007 All Rights Reserved. In the interest of product improvement, specifications are subject to change without notice. Printed in Japan Cat. No. W465-E1-05 0210
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Encryption : Standard V2.3 (128-bit) User Access : Print, Copy, Extract, Print high-res Page Mode : UseOutlines XMP Toolkit : 3.1-702 Producer : Acrobat Distiller 5.0 (Windows) Keywords : W465-E1-05 0210 Create Date : 2010:02:10 10:43:24Z Modify Date : 2010:03:22 14:12:51+01:00 Metadata Date : 2010:03:22 14:12:51+01:00 Creator Tool : FrameMaker 6.0 Format : application/pdf Creator : OMRON Title : SYSMAC CS and CJ Series .CS1W-EIP21 (100Base-TX) .CJ1W-EIP21 (100Base-TX) .CJ2H-CPU6_-EIP (100Base-TX) .CJ2M-CPU3_ (100Base-TX/10Base-T) .EtherNet/IP Units Document ID : uuid:1556e157-fa04-458b-b8da-2f277f65a066 Instance ID : uuid:62886e1e-7551-4c73-b0bf-18ec3ae1a84f Page Count : 464 Author : OMRONEXIF Metadata provided by EXIF.tools