PAYNE Package Units(both Units Combined) Manual L0704293
User Manual: PAYNE PAYNE Package Units(both units combined) Manual PAYNE Package Units(both units combined) Owner's Manual, PAYNE Package Units(both units combined) installation guides
Open the PDF directly: View PDF .
Page Count: 30
Download | |
Open PDF In Browser | View PDF |
Installation Instructions NOTE: Read installation. NOTE: the entire Installer: Instructions Make instruction sure manual the Owner's before Manual starting and the Service are left with the unit after installation. TABLE OF CONTENTS SAFETY CONSIDERATIONS ........................ INTRODUCTION .................................. Page 1 2 RECEIVING 2-12 AND INSTALLATION ................ Check Equipment ................................. Identify Unit ................................... Inspect Shipment ................................ 2 2 2 Provide Unit Support .............................. Roof Curb ..................................... Slab Mount .................................... 2 2 2 Ground Mount ................................. Field Fabricate Ductwork ........................... 2 2 Provide ................................ 6 ................................ 6 Clearances Rig and Place Unit Inspection ..................................... Use of Rigging Bracket ........................... Connect Condensate Drain .......................... Install Flue Hood 6 6 8 ................................ 8-9 Install Gas Piping ................................. Install Duct Connections ............................ 9 9 Configuring Units for Downflow (Vertical) Discharge .................................. Install Electrical Connections ....................... High- Voltage Connections ....................... Special Procedures for 208-V Operation ............. Control Voltage Connections ...................... Heat Anticipator Setting ......................... Transformer Protection .......................... PRE-START-UP .................................. START-UP AND TROUBLESHOOTING ........... Check for Refrigerant Leaks ..................... Start-Up Heating & Make Adjustments ............... Check Heating Control .......................... Check Gas Input ............................... Adjust Gas Input ............................ Check Burner Flame ............................ Airflow and Temperature 9-10 11 11 11 11 12 12 12 12-22 12-13 13 13 Rise ..................... 14 14 18 Rollout 18 Switch ................................ ............... ............... Checking & Adjusting Refrigerant Charge ........... Indoor Airflow and Airflow Adjustments ............ Cooling Sequence of Operation .................... MAINTENANCE ............................... 18 18 18 19 19 24-26 Air Filter ....................................... Indoor Blower and Motor .......................... 24 24 Flue Gas Passageways 25 ............................. Induced Draft (Combustion Air) Blower Limit Switch .................................... ............... 24 24 Burner Ignition .................................. Main Burners ................................... Outdoor Outdoor Electrical 25 25 Coil, Indoor Coil, & Condensate Fan .................................... Controls and Wiring Drain Pan ..... ................... 25 26 26-27 Refrigerant Circuit ................................ Indoor Airflow .................................. 27 27 Metering Devices-AccuRater _" Piston ................ Liquid Line Strainer ............................ TROUBLESHOOTING ............................. 27 27 27 START-UP 27 CHECKLIST 13 13-14 14 Heating Sequence of Operation .................... Limit Switches ................................ Start-Up Cooling & Make Adjustments Checking Cooling Control Operation A06079 Fig. 1 - Unit PY3P (Low NOx Model Available) ........................... SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed equipment, by trained service personnel. When working on this observe precautions in the literature, on tags, and on labels attached to or shipped precautions that may apply. Follow all safety codes. with Installation local and national building clothing, and work gloves. the unit and other safety must be in compliance with codes. Wear safety glasses, protective Have fire extinguisher available. Read these instructions thoroughly and follow all warnings included in literature and attached to the unit. or cautions Recognize safety information. Thisisthesafety-alert symbol '_'_. Step 2--Provide When you see this symbol on the unit and in instructions For hurricane or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are (Professional ROOF Unit Support tie downs, Engineering) contact distributor Certificate for details and PE if required. CURB used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. Install accessory WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may with curb (See Fig. 5). Install insulation, cant strips, flashing. Ductwork must be attached to curb. result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. IMPORTANT: roof curb in accordance The gasketing with instructions applied and of the unit to the roof curb is critical for a water tight seal. Install gasketing roof curb. Improperly shipped roofing, material gasketing supplied with the also can result in air leaks and poor unit performance. Curb should be level to within ELECTRICAL SHOCK to function instructions HAZARD Failure to follow this warning or death. could result in personal injury SLAB Failure to follow this warning or unit damage. SHOCK HAZARD installation pad that is a minimum of 4 in. thick with 2 in. above grade (See Fig. 2). The slab should extend approximately 2 in. beyond the casing on all 4 sides of the unit. Do not secure ELECTRICAL POISONING for unit drain MOUNT Place the unit on a solid, level concrete Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable. FIRE, EXPLOSION, CARBON MONOXIDE 1/4 in. This is necessary properly. Refer to accessory roof curb for additional information as required. the unit to the slab except when required by local codes. AND could result in personal injury A qualified installer or agency must use only factory-authorized kits or accessories when modifying this product. INTRODUCTION L EVAR COIL The PY3P unit (see Fig. 1) is a fully self-contained, combination Category I gas heating/electric cooling unit designed for outdoor installation (See Fig. 3 and 4 for unit dimensions). All unit sizes have return and discharge openings for both horizontal and downflow configurations, and are factory shipped with all downflow a rooftop, duct openings covered. Units may be installed either on a cement slab, or directly on the ground, if local codes COND C99096 Fig. 2 - Slab Mounting GROUND The unit may be installed either on a slab or placed directly on the ground, if local codes permit. Place the unit on level ground prepared Models with an N in the thirteenth position of the model number are dedicated Low NOx units designed for California installations. Step 3--Field These models meet the California maximum oxides of nitrogen (NOx) emissions requirements of 40 nanograms/joule or less as shipped from the factory and must be installed in California Air discharge units. Do not connect applications, unit is provided NOTE: Low installations. NOx requirements regions only to in North natural gas Step 1--Check AND INSTALLATION Equipment UNIT The unit model number and serial number are stamped on the unit information plate. Check this information against shipping papers. INSPECT Secure with gravel for condensate SHIPMENT Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit. Check all items against shipping list. Immediately notify the nearest equipment distribution office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation. Fabricate all ducts discharge. Ductwork to roof curb and building structure on vertical ductwork to unit. For horizontal with flanges on the horizontal openings. All ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing RECEIVING IDENTIFY apply other Details MOUNT permit (See Fig. 5 for roof curb dimensions). Quality Management Districts or any America where a Low NOx rule exists. / COIL and covered through an unconditioned space must be insulated with a vapor barrier. If a plenum return is used on a vertical ducted through the roof deck to comply unit, the return should be with applicable fire codes. A minimum clearance is not required around return-air static shall not exceed -.25 in. wc. duGwork. Cabinet 810CKOFF PANE ON 018 254 0 [10 00] _5461 254 121 0 gOi 01i1¥_ k \ \ 11600i COND [4 63] 88_ [g 4_J TOP ViEW [9 83] [21 67] [9 83} REAR ViEW REQUIRED CLEARANCE TO CO_,rBUSTIBLE MATL TOP OF UNIT ................................................................................... DUCT SIDE OF UNIT ......................................................................... SiDE OPPOSITE DUCTS ................................................................ BOTTOM OF UNIT ............................................................................. ELECTRIC HEAT PANEL ................................................................. REQUIRED INCHES _4.00 2.00 14.00 0.50 36.00 [mm] [355.6] [50.8] [355.6] [12_7] [914.4] CLEARANCE FOR OPERATION AN D SERVICING INCHES 36.00 36,00 EVAR COIL ACCESS SIDE ............................................................ POWER ENTRY SIDE .................................................................... (EXCEPT FOR NEC REQUIREMENTS) UNIT TOP ....................................................................................... SIDE OPPOSITE DUCTS .............................................................. DUCT PANEL ................................................................................. 48.00 36.00 :12.00 [mm] [914.0] [914.0] [1219.2] [914.0] [304.8] * NEC. REQUIRED CLEARANCES. INCHES BETWEEN UNITS, POWER ENTRY SIDE .................................... 42.00 UNiT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES, POWER ENTRY SIDE ......................... 42.00 [mm] [1066.8] [914,0] *MINIMUM DISTANCES: IF UNIT IS PLACED LESSTHAN 12.00 [304.8] FROM WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE. [1066.8] LEGEND CG - Center or Gravity COND - Condensor EVAP - Evaporator NEC - National Electrical Code REQ'D - Required NOTE: Dimensions are in in, [rnm] /98 [31 ............................ 1193 9 [47 00] 44J 116 3 [4 58] 23 0 [0 9i] \ ?? 2 [0 88] DIA CONTROL ENTRY 1230 [484] }90 [0 _5] NI'] I i x 22 0 _P [I 68] FLUE I¢00D 46 8 [I 84J 52 8 12 122 14 LEFT SIDE ViEW [O ',O] NP GAS ENIRY 50 [0 20 _ 08] 2 81] FRONT ViEW RIGHT SiDE ViEW A06083 UNIT ELECTRICAL CHARACTERISTICS PY3P024 208/230-1-60 CENTER UNIT HEIGHT IN. [MM] UNIT WEIGHT X OF GRAVITY IN. [MM] Y Z Ib kg 446 202.3 39.02 [991] 20.0 [508] 19.3 [490] 17.6 [447] PY3P030 208/230-1-60, 208/230-3-60 451 204.6 41.02 [1042] 20.0 [508] 14.0 [356] 13.0 [330] PY3P036 208/230-1-60, 208/230-3-60, 460-3-60 459 206.2 41.02 [1042] 20.0 [508] 14.0 [356] 13.0 [330] Fig. 3 - PY3P024-036 Unit Dimensions 3 556 8 [;401] ] 555 [;4 8 01] i RETDRN SUPPLY 4066 &00 [3 i7] RETURN DUG1 4020 [i583] I I I1_ 7 14_60/ J i i 883 [3 I L30,2- 48] !/35 [6 83] v ....... i............... 7---i .............. [!3 83] _341 3 [13 _301 2 67] [!3 TOP ViEW 83] REAR VmEW REQUIRED CLEARANCE TO COMBUSTIBLE MATE REQUIRED CLEARANCE FOR OPERATION AND SERVICING INCHES 14.00 2.00 14.00 0,50 36.00 TOP OF UNIT ................................................................................... DUCT SIDE OF UNIT ......................................................................... SIDE OPPOSITE DUCTS ................................................................ BOTTOM OF UNIT ............................................................................. ELECTRIC HEAT PANEL ................................................................. [mini [355.6] [50,8] [355.6] [12.7] [914.4] iNCHES [mini 36.00 [914.0] 86.00 [914.0] EVAR COIL ACCESS SIDE ............................................................ POWER ENTRY SIDE .................................................................... (EXCEPT FOR NEC REQUIREMENTS) UNIT TOP ..................................................................................... SIDE OPPOSITE DUCTS .............................................................. DUCT PANEL ................................................................................. 48.00 [1219.2] 36.00 [914.0] 12.00 [304.8] * NEC. REQUIRED CLEARANCES. INCHES BETWEEN UNITS, POWER ENTRY SIDE .................................... 42.00 UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES, POWER ENTRY SIDE ......................... 42,00 *MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE, [mini [1066.8] [914.0] [1066.8] LEGEND CG- Centerof Gravity COND- Condensor EVAP- Evaporator NEC- NationalElectricalCode REO'D- Required 1959 [47 i0906 _4294] FIELD ENTRf_ 250 SER¸¸/ICE POI_I¸ _ I Y '_ ½ 7- i l " ........ POWER ENTRY 1286 [i 3 ' I " i i 4h2 i'l .i],l I DA K 0 !23 0 484] i 8 NOTE:Dimensionsare in in. [mm] 1!04 [4 54] , [091] =_e_ _ 00] x / 1 i \ _RESSOR x 22 0 10 671 8P _ .... 329 gOr%R \ GA_ SECTON 0 [44 _;0_ 12263 [48 28] i2 i [0 50_ ,'_ !/ P T GAS ENTRY 52 8 [208] [1205] ,,_3, i 5 0 [0 20] 1424 [5 61] 223 FRONTVIEW LEFT SIDE VIEW RIGHT SiDE VIEW A06084 UNIT UNIT WEIGHT ELECTRICAL CHARACTERISTICS CENTER UNIT HEIGHT IN.[MM] OF GRAVITY IN. [MM] Y Ib kg "A" X 460-3-60 588 268.7 46.98 [1193] 21.0 [533] 20.5 [520] 17.1 [434] 208/230-3-60, 480-3-60 598 270.3 46.98 [1193] 21.0 [533] 20.0 [508] 17.4 [442] 208/230-3-60, 480-3-60 804 274.0 46.98 [1193] 21.0 [533] 20.0 [508] 17.6 [447] PY3PO42 208/230-1-60, 2081230-3-60, PY3PO48 208/230-1-60, PY3PO6O 208/230-1-60, Fig. 4 - PY3P042-060 Unit Dimensions Z Roof Curb for Small Cabinet Roof Curb for Large Cabinet Note A: When unit mounting screw is used, retainer bracket must also be used, Note A: When unit mounting screw is used, retainer bracket must also be used, E R/A S/A A _Gasket \ \ around duct \ _ \ / \ insulated deck pan Support Gasket outer /2 around edge \ \ Long Support \\,\ A05308 UNIT ODS CATALOG NUMBER A IN. (MM) B IN. (MM) CPRFCURB008A00 8 (203) 11 (279) 16-1/2 (419) 28-3/4 (730) 30-3/8 (771) 44-5/16 (1126) 45-15/16 (1167) CPRFCURB00FA00 14 (356) 11 (279) 16-1/2 (419) 28-3/4 (730) 30-3/8 (771) 44-5/16 (1126) 45-15/16 (1167) CPRFCURB008A00 8 (203) 16-3/16 (411) 17-3/8 (441) 40-1/4 (1022) 41-15/16 (1065) 44-7/16 (1129) 46 - 1/16 (1169) CPRFCURB009A00 14 (356) 16-3/16 (411) 17-3/8 (441) 40-1/4 (1022) 41-15/16 (1065) 44-7/16 (1129) 46-1/16 SIZE PY3P024-036 PY3P042-060 D IN. (MM) C IN. (MM) E IN. (MM) F IN. (MM) G IN. (MM) (1169) NOTES: [. Roof curb must be set up for unit being installed. 2. Seat strip must be applied, as required, to unit being installed. 3. Dimensions are in inches. 4. Dimension in ( )are in millimeters. 5. Roof curb is made of 16 gauge steel. 6. Attach ductwork to curb (flanges of duct rest on curb). 7. Inadated panels: I in. thick fiberglass 1 lb. density. S. When unit mounting screw is used (see Note A). a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane conditions. This bracket is available through Micrometl. Fig. 5 - Roof Curb Dimensions or seismic Step 4--Provide The required Clearances minimum operating and service clearances are shown in Fig. 3 and 4. Adequate combustion, ventilation and condenser air must be provided in accordance with section 5.3. Air for Combustion and Ventilation, of the National Fuel Gas Code ANSI (American provisions National Standards Institute) Z223.1 or applicable of local building code. In Canada, follow sections 7.2, 7.3, or 7.4 or Can/CGA. (Canadian Gas Association) Installation Codes or applicable provisions of local building IMPORTANT: Do not restrict outdoor either the outdoor-air to compressor An air restriction at may be detrimental DAMAGE HAZARD Failure to follow this warning injury/death or property damage. could result in personal Rigging brackets for one unit use only. When removing unit at the end of its useful life. use a new set of brackets. USE OF RIGGING Field Installation a BRACKET of Ri_in_ Bracket (if not already installed) life. and 1. Remove unit from shipping carton. Leave top shipping skid on the unit for use as a spreader bar to prevent the rigging discharges it through the top grille. Be sure that the fan discharge does not recirculate to the condenser coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum straps from damaging the unit. If the skid is not available, use a spreader bar of sufficient length to protect the unit from The n airflow. inlet or the fan discharge B149 code. PROPERTY condenser fan pulls air a partial through overhang the condenser clearance under (such overhang) extension is 48-in. above the unit top. The maximum of a partial overhang must not exceed 48-in. coil as a normal house horizontal Do not place the unit where water, ice, or snow from an overhang damage. 2. Remove 4 screws in unit corner posts. 3. Attach each of the 4 metal rigging brackets under the panel rain lip (See Fig. 6). Use the screws removed in step 2 above to secure the brackets to the unit. or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab-mounted units should be at least 4 in. above the highest expected water and runoff levels. Do not use unit if it has been under water. Step 5--Rig and Place PROPERTY Unit Rigging and handling of this equipment reasons etc.). due to the installation location can be hazardous (roofs, structures, working with this equipment, and ground observe support to follow injury/death precautions Training for operators of the lifting equipment not be limited to. the following: 1. Application Follow all applicable safety PROPERTY include, but of the codes. Wear safety shoes and work installed on@ on Small Packaged Products. used to rig/lift a Small Packaged Product elevated structures. designed to be This bracket is to be onto roofs or other Prior to initial use, and at monthly intervals, all rigging brackets and straps should be visually inspected for any damage, evidence of wear. structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Brackets or straps showing any kind of wear in these areas nmst not be used and should be discarded. UNIT FALLING HAZARD Failure to follow this warning or death. Never stand beneath rigged could result in personal units or lift over people. DAMAGE lip to provide HAZARD could result in personal be a injury of Unit 1. Bend top of brackets 2. Attach and rain When straps are taut, the clevis should of 36 inches above the unit top cover. Ri_,_in_/Liftin_ INSPECTION is engineered the Do not strip screws when re-securing the unit. If a screw is stripped, replace the stripped one with a larger diameter screw the corner bracket in personal of the lifting gloves. lifting/rigging be under Failure to follow this warning injury/death or property damage. (included). minimum or precaution. 3. Condition of the load as it relates to operation kit, such as balance, temperature, etc. result and sizes or kinds of loads. in any special operation MUST could damage. in the of the lifter to the load, and adjustment lifts to adapt to various 2. Instruction should this warning or property bracket lifting. HAZARD staff literature, on tags, stickers, and labels attached to the equipment, any other safety precautions that might apply. The Failure Rigging adequate Only trained, qualified crane operators should handle and install this equipment. When elevated for many DAMAGE opposite down approximately 30 degrees from posts. straps of equal length to the rigging brackets at ends of the unit. Be sure straps are rated to hold the weight of the unit (See Fig. 6). 3. Attach a clevis of sufficient strength in the middle of the straps. Adjust the clevis location to ensure unit is lifted level with the ground. 4. After unit is securely corner posts screws. screws, After the unit is placed the top crating. in place detach rigging and rigging brackets on the roof curb or mounting straps. Remove then reinstall pad, remove UNIT SIZE Table 1---PhysicalData 024060 030040 024040 - Unit PY3P 030060 NOMINAL CAPACITY (ton) 2 2 2-1/2 2-1/2 OPERATING WEIGHT (lb.) 446 446 451 451 036090 042090 3 3-1/2 3-1/2 459 459 588 588 7.2 7.2 7.8 7.8 1 REFRIGERANT (R-22) Quantity (lb.) REFRIGERANT METERING DEVICE ORIFICE ID (IN.) CONDENSER COIL Rows...Fins/in. Face Area (sq ft) CONDENSER FAN Nominal Cfm Diameter (in,) Motor Hp (Rpm) EVAPORATOR COIL Rows_.Fins/in. Face Area (sq ft) INDOOR BLOWER 5.9 .070 .070 .080 .080 .084 .084 2,..21 10.2 2._21 10.2 2. _2 11.9 2..,21 11.9 2_.21 13.6 2,.,21 13.6 2_.21 19.4 2...21 19.4 2200 22 2200 22 2800 22 2800 22 3000 22 3000 22 3500 22 3500 22 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 3...17 3.7 3.,,17 3.7 3.,.17 3.7 3..,17 3.7 4.,.17 3.7 4..,17 3.7 3...17 4.7 3...17 4.7 800 800 1000 1000 1200 1200 1400 1400 10x10 10x10 10x10 10x10 10x10 10x10 11x10 11x10 1/3 (1050) 1/3 (1050) 1/3 (1050) 1/3 (1050) 1/2 (1000) 1/2 (1000) 1/2 (1075) 1/2 (1075) 2,..44 2...50 2., ,38 2..,46 2,, .44 2.,.50 2.. ,38 2..A6 2., .38 2...46 3,. ,38 3..A6 2., .38 2...46 2,..38 2...46 20x24x1 20x24x1 20x24x1 20x24x1 20x24x1 24x36x1 24x36x1 20x24x1 Table WEIGHT 6.0 .065 UNIT SiZE CAPACITY 6.0 .065 Size (in,) Motor HP (RPM) FURNACE SECTION* Burner Orifice No. (Qty..,Drill Size) Natural Gas Propane Gas RETURN-AIR FILTERS (in.)f Throwaway 5.9 AccuRater Nominal Airflow (Cfm) OPERATING 042060 3 Scrofi COMPRESSORS Quantity NOMINAL 036060 1--Physical Data ('on't - Unit PY3P 048090 048115 048130 060090 060115 (ton) 4 4 4 5 5 080130 5 (lb.) 598 596 596 604 604 604 12.0 12,0 12.0 Scroll COMPRESSORS Quantity 1 REFRIGERANT Quantity (lb.) (R-410A) REFRIGERANT METERING 12,4 12.4 12.4 .088 .088 .088 .098 .098 0.098 3500 22 3500 22 3500 22 4200 22 4200 22 4200 22 1/4 (1100) 1/4 (1100) 1/4 (1100) 1/4 (1100) 1/4 (1100) 1/4 (1100) Face Area (sq ft) 2,.,21 19.4 2.,.21 19.4 2.,.21 19.4 2,.,21 19.4 2,.,21 19.4 2.,.21 19.4 EVAPORATOR COIL Rows,.,Fins/in. Face Area (sq ft) 4..,17 5.7 4.,.17 5.7 4.,.17 5.7 4..,17 5.7 4..,17 5.7 4.,.17 5.7 ORIFICE DEVIOE AccuRater ID (IN,) CONDENSER FAN Nominal Cfm Diameter (in.) Motor Hp (Rpm) CONDENSER COIL Rows,.,Fins/in. INDOOR BLOWER Max 1600 1600 1600 2000 2000 2000 Size (In.) 11X10 11X10 11x10 11x10 11X10 11X10 1/2 (1075) 1/2 (1075) 1/2 (1075) 1.0 (1040) 1.0 (1040) 1.0 (1040) 3,.,38 3...46 3.-33 3...42 3._31 3...41 3,.,38 3...46 3,.,33 3...42 3.-31 3...41 24X36X1 24X36X1 24x36x1 24x36x1 24X36X1 24X36X1 Motor HP (RPM) FURNACE SECTION* Burner Orifice No, (Qty,_DriH Natural Gas Propane Gas Size} RETURN-AIR FILTERS (in,)f Throwaway Based on altitude of 0 to 8000 ft. T Required mimee filter for throwaway sizes shown type are based or 450 ft/mimee on the larger for high of the ARI capacity (Air type. (bnditioning Air filter pressure and Refrigeration drop for non Instielte) standard rated filters cooling must airflow not exceed or the heating 0.08 in. wc. airflow velocity of 300 fii I! MUNIMUMHEUGHT:36' Y DETAIL A UNIT HEUGHT x Z SEE DETAIL 3 C00070 I! A06361 CORNER WEIGHTS (SMALL CABINET) CORNER WEIGHTS (LARGE CABINET) Unit 024 030 036 Unit 042 048 060 Total Weight 446 451 459 Total Weight 588 596 604 Corner Weight 1 63 69 66 Corner Weight 1 96 104 97 Corner Weight 2 82 81 87 Corner Weight 2 95 93 102 Corner Weight 3 123 121 122 Corner Weight 3 162 161 163 Corner Weight 4 178 180 184 Corner Weight 4 235 238 242 Rigging Weight 465 470 478 Rigging Weight 610 618 626 Shipping Weight 500 505 513 Shipping Weight 650 658 666 Fig. 6 - PY3P Unit Corner Step 6--Connect Condensate installing Weights Drain condensate When comply with local codes and restrictions. drain connection be sure to Model PY3P disposes of condensate water through a 3/4 in. NPT fitting which exits through the base on the evaporator coil access side. See Fig. 3 & 4 for location. water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field-supplied 2-in. condensate trap at the end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the drain-pan condensate connection to prevent the pan from overflowing (See Fig. 7). Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit. Connect a drain tube using a mininmm and Suggested Step 7--Install NOTE: Condensate (in Pounds) of 3/4-in. Rigging Flue Hood The flue assembly is secured and shipped Remove duct cover to locate the assembly NOTE: Dedicated low California Air Quality rule exists. These models meet NOx the California (NOx) emissions requirements shipped from the factory. NOTE: Low installations. models Management NOx in the return MUST Districts be where maximum installed apply oxides only in a Low NOx of nitrogen of 40 nanograms/joule requirements air duct. (See Fig. 9 and 10). to or less as natural gas PVC or 3/4-in. copper pipe (all field-supplied) at the outlet end of the 2-in. trap. Do not undersize the tube. Pitch the drain tube downward at a slope of at least l-in. for every 10 ft of horizontal run. Be sure to check the drain tube for leaks. CARBON MONOXIDE POISONING Failure to follow this warning or death. HAZARD could result in personal injury The venting system is designed to ensure proper venting. The flue hood assembly mustbe installed as indicted in this section of the unit installation instructions. 1 In Install the flue hood as follows: 1. This installation 2" min. with the National must conform with local building Fuel Gas (:ode (NFGC), codes and ANSI Z223.1 (in Canada. CAN/CGA B149.1. and B149.2) or NFPA (National Fire Protection Association) latest revision. Refer to Provincial and local plumbing or wastewater codes and C00009 Fig. 7 - Condensate Trap other applicable local codes. 2. Remove flue hood from shipping location (inside the return section of the blower compartment-see Fig. 9 & 10). Re- move thereturn ductcover tolocate thefluehood. Place flue hoodassembly overfluepanel. Orient screw holes influe hood withholes inthefluepanel. 3.Secure fluehood tofluepanel byinserting asingle screw on therightside andtheleftside ofthehood. Step8--Install Gas Piping The gas supply pipe enters provided. The gas connection gas inlet on the gas valve. Install a gas supply access hole to the unit is made to the 1/2-in. the unit through the FPT line that runs to the heating section. IN OUT_ Refer to _/ Table 2 and the NFGC for gas pipe sizing. Do not use cast-iron pipe. It is recommended that a black iron pipe is used. Check the local utility for recommendations concerning existing lines. Size gas supply piping for 0.5 in. wc maximum pressure drop. Never use pipe smaller than the 1/2-in. FPT gas inlet on the unit gas valve. CAP C99020 NOTE: piping Fig. 8 - Sediment Trap test the gas supply system Pressure is connected disconnected to the gas valve. from the gas valve after the gas supply The supply during piping the testing must be of the piping For natural gas applications, the gas pressure at unit gas connection must not be less than 4.0 in. wc or greater than 13 in. wc while the systems when test pressure is in excess of 0.5 psig. Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig. unit is operating. For propane applications, the gas pressure must not be less than 7.0 in. wc or greater than 13 in. wc at the unit connection. The unit heating A 1/8-in. connection, supply NPT must plugged tapping, accessible for be installed immediately upstream connection (in Canada, CAN/CGA B149.1). the state of Massachusetts: 1. Gas supply connections MUST be performed plumber or gas fitter. 2. When flexible connectors by a licensed are used. the maximum shall not exceed 36 inches (915 mm). 3. When lever handle type manual equipment shutoff length valves are used. they shall be T-handle valves. 4. The use of copper tubing for gas piping is NOT approved the state of Massachusetts. In the absence of local building pertinent recommendations: codes, adhere by for every 15 ft of length to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter. 2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 ft. For pipe sizes larger than 1/2 in., follow recommendations of national codes. 3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of liquefied gases as specified Never use Teflon by local and/or national codes. tape. 4. Install sediment trap in riser leading to heating section (See Fig. 8). This drip leg functions as a trap for dirt and condensate. 5. Install an accessible, external, pipe within manual 6 ft of heating main shutoff valve in valve and slightly FIRE OR EXPLOSION Failure to follow this warning death and/or property damage. -Connect gas pipe to unit damaging gas controls. plumbing could result in personal using a backup wrench injury, to avoid -Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. -Use proper manifold. length of pipe to avoid -If a flexible connector stress on gas control is required or allowed by authority having jurisdiction, black iron pipe shall be installed at furnace gas valve and extend a minimum of 2 in. outside furnace casing. -If codes allow a flexible connector, always use a new connector, do not use a connector which has previously serviced another gas appliance. 8. Check for gas factory-installed leaks at the field-installed gas lines after all piping Step 9--Install and connections been completed. Use soap-and-water solution specified by local codes and/or regulations). have (or method Duct Connections The unit has duct flanges on the supply- and return-air openings in accordance and gas codes before with local connecting and piping on the side and bottom of the unit. For downshot applications, the ductwork connects to the roof curb (See Fig. 3 and 4 for connection sizes and locations). CONFIGURING DISCHARGE ELECTRICAL test all gas piping HAZARD UNITS FOR DOWNFLOW (VERTICAL) between shut-off valve. national to unit. shutoff section. 6. Install ground-joint union close to heating section unit manual shutoff and external manual main 7. Pressure manual union. to the following 1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in. gas supply main the ground-joint to the gas valve. NFPA latest edition petroleum opening section must be isolated from the gas piping system the external test gauge of the gas When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFGC ANSI Z223.1-2005 NOTE:In by closing SHOCK HAZARD Failure to follow this warning or death. could result in personal injury Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. 1 !! Table 2--Maximum Gas Flow ( apaclty* NOMINAL tRON PIPE SIZE (iN.) INTERNAL D_AMETER (iN.) 10 20 30 40 50 60 70 80 90 100 125 150 1/2 _622 175 120 97 82 73 66 61 57 53 50 44 40 3/4 1 _824 1.049 360 680 250 465 200 375 170 320 151 285 138 260 125 240 118 220 1! 0 205 103 195 93 175 1-1/4 1.380 1400 950 770 600 580 530 490 460 430 400 1-1/2 1.610 2!00 1460 1180 990 900 810 750 690 650 620 Capacity of pipe tion Association This length LENGTH OF P_PE (FT)t in cu ft of gas per hr for gas presalre NFPA includes number horizontal (metal) 3. Use a screwdriver before starting duct covers duct knockouts and hammer in, wc (based on a 0.60 specific gravity gas). 72 135 360 325 300 280 550 500 460 430 Refer to Table, National Fire Protec any service to access vertical in unit base. to remove is to be attached on the unit base (iackstand time. PROPERTY the panels DAMAGE to vertical applications in the opening flanges only), do so at this HAZARD to follow this caution may result in property Collect ALL screws that were removed. on rooftop of 0,5 77 145 of the unit base (See Fig. 10). 4. If unit ductwork Failure drop 84 160 of fittings. disconnects (down flow) discharge bottom Pressure 200 54. an ordinary 1. Open all electrical work. 2. Remove of 0.5 psig or tess. 175 as permanent damage damage. DUCT Do not leave screws COVERS REMOVED to the roof may occur. C99012 Fig. 10 - Vertical Duct Cover 5. It is recommended perimeter that of the vertical the base return-air insulation opening around 6. Cover both horizontal covers. Ensure 7. After completing duct openings opening the be secured to the base with aluminum tape. Applicable local codes require aluminum tape to prevent exposed fiberglass. with the provided Adhere may perform are removing 2. Select all safety checks criteria when shipped for horizontal and size ductwork, grilles according NFPA and ventilating 90B; and/or systems. local codes duct sizing, and installation (by registers, and supply-air to American Refrigeration and Air Conditioning recommendations. air conditioning selecting, duct covers). return-air NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of 90A or residence-type, ordinances. following the duct system: 1. Units duct and power up unit. nonresidence-type to the installing is air- and watertight. unit conversion, Removed Society Engineers of Heating, (ASHRAE) 3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be NFPA and screwed or bolted to duct flanges. Use suitable gaskets sure weather-tight and airtight seal. to en- 4. All units must have field-supplied filters or accessory rack installed in the return-air side of the filter unit. Recommended sizes for filters are shown in Table 1. 5. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected. 6. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Association (SMACNA) Contractors and Air Conditioning National Contractors of America (ACCA) minimum installation standards for heating and air conditioning systems. Secure all ducts to building SUPPLY DUCT OPENING RETURN DUCT OPENING SHIPPING LOCATION 7. Flash, weatherproof, and vibration isolate all openings in building structure in accordance with local codes and good A05143 Fig, 9 - Supply and Return structure. building Duct Opening 10 practices. Step10--Install Electrical Connections 3. Locate the black and yellow wires connected of the contactor. 4. Connect field compressor ELECTRICAL SHOCK HAZARD Failure to follow this warning or death. could result in personal Three-phase 2. Connect ground Electrical 4. Connect 5. Connect field 6. Connect HAZARD SPECIAL Failure to follow this caution being installed. 1. Make all electrical ANSI/NFPA governing connections codes. connections Electrical copper field-supplied electrical NOT USE ALUMINUM 3. Be sure that high-voltage voltage range indicated for connections disconnect WIRE. switch and unit. DO FOR 208-V OPERATION SHOCK HAZARD could result in personal VOLTAGE injury CONNECTIONS Do not use any type of power-stealing Consult voltage problems thermostat. Unit control may result. Use no. 18 American Wire Gage (AWG) color-coded, insulated (35°C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft from the unit (as measured wires. wires), use no. 16 AWG color-coded, wires. 5. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc. HIGH-VOLTAGE 13 of the field wire L3 to blue wire from compressor. PROCEDURES CONTROL power to unit is within operating on unit rating plate. On 3-phase phase imbalance. as high-voltage 11 of the Before making any wiring changes, make sure the gas supply is switched off first. Then switch off the power supply to the unit and install lockout tag. 4. Insulate low-voltage wires for highest voltage contained within conduit when low-voltage control wires are in same conduit wire on connection contactor. Failure to follow this warning or death. local between units, ensure phases are balanced within 2 percent. local power company for correction of improper and/or L1 to black to the line side field wire L2 to yellow wire on connection ELECTRICAL diagram. conductor connection. with NEC Code Part 1 and applicable Refer to unit wiring only in accordance lead to chassis ground lead into the to the unit (latest edition) and local electrical codes such wiring. In Canada, all electrical must be in accordance with CSA standard C22.1 Canadian 2. Use may result in damage 23 of the contactor. compressor DAMAGE (L1, L2, L3) and ground 3. Locate the black and yellow wires connected of the contactor. compressor COMPONENT 11 of the units: 1. Run the high-voltage control box. compartment, or conduit approved for electrical ground when installed in accordance with NEC, ANSI/NFPA American National Standards Institute/National Fire Protection UNIT wire on connection contactor. 5. Connect field wire L2 to yellow wire on connection compressor contactor. injury The unit cabinet must have an uninterrupted, unbroken electrical ground. This ground may consist of an electrical wire connected to the unit ground screw in the control Association (latest edition) (in Canada. Canadian Code CSA C22.1) and local electrical codes. L1 to black to the line side CONNECTIONS Standard Connection Remove knockout hole located along insulated the control (35°C voltage minimum) in the flue panel adjacent to the control access panel (See Fig. 3 and 4). Remove the rubber grommet from the installer's packet (included with unit) and install grommet in the knockout opening. Provide a drip loop before running wire When routing power leads into unit, use only copper wire between disconnect and unit. The high voltage leads should be in a conduit until they enter the duct panel; conduit termination at the duct panel through panel. must be watertight. The unit must have a separate electrical service with a field-supplied, waterproof disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing. The field-supplied disconnect unit over the high-voltage low-voltage entry points switch box may be mounted - - - - - LABEL) _ - - - on the FIELD-SUPPLIED FUSED DISCONNECT GR label and Fig. 11 for reference follows when to making high complete the ro[oLOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL) phase units: 1. Run the high-voltage control box. 2. Connect - fc e- CONTROLBOX voltage connections. Proceed as high-voltage connections to the unit. Single F POWER LEADS (SEE UNIT WIRING inlet hole when the standard power and are used (See Fig. 3 and 4 for acceptable location). See unit wiring HIGH VOLTAGE ground (L1, L2) and ground lead to chassis Io- l 1/ TAT lead into the SPLICE ground H dih 1/ BOX connection. A05144 Fig. 11 - High11 and Control-Voltage Connections Run the low-voltage leads from the thermostat, hole, and into unit low-voltage Locate five 18-gage connection through the inlet a. Inspect splice box. wires leaving control leads can be identified box. These low-voltage c. Leak-test electronic side of control box). Route leads through hole in bottom of control box and make low-voltage connections (See Fig. 11). Secure all cut wires, so that they do not interfere with operation of unit. heat anticipator must be properly adjusted n setting. NOTE: For thermostat approximate required anticipator setting. adjustment to the occupants selection purposes, Failure of the conditioned utilization; however, to provide a greater the required degree TRANSFORMER to make a proper operation, energy slightly for a particular leak is detected, Leaks section. see following wires do not touch f. Inspect coil fins. handling, carefully Check refrigerant tubing FIRE, EXPLOSION HAZARD could result in personal Do not purge gas supply into the combustion type. It is set to withstand condition. injury, chamber. Do not use a match or other open flame to check for gas leaks. 4. Verify the following UP ELECTRICAL SHOCK HAZARD Failure to follow this warning or death. could result in personal 1. Follow practices recognized NOTE: conditions: and wear chamber, 3. Do not compressor remove terminal compressor cover terminal is in place cover and until electrical sources are disconnected and tagged. 4. Relieve and recover all refrigerant from system union. attempt to repair soldered all To remove a component, proceed as follows: a. Shut off electrical tag. wear protective System goggles hnmediately Never upon purge detection to purge until the of gas odor, retighten to elapse, then light unit. b. Make that sure fan hub condenser-fan blade is is positioned correctly with the correctly blade respect to (See Fig. 12). d. Make sure that air filter(s) is in place. e. Make sure that condensate to ensure proper drainage. drain trap is filled with water f. Make sure that all tools have been removed. and the joint gas lines into a combustion Allow 5 minutes motor housing while refrigerant system is under pressure. 6. Do not use torch to remove any component. contains oil and refrigerant under pressure. and the supply line be allowed c. Ensure before connection that the ground positioned in fan orifice. Top 1/3 of condenser-fan should be within fan orifice venturi. touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals. 5. Never the unit with the gas valve If the gas supply pipe was not purged before connecting odor of gas is detected. protective goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any electric power to unit unless secured. the following unit, it will be full of air. It is recommended injury union be loosened, safety and installation. for the first time, perform in the OFF position: EXPLOSION, Be or sharp a. Make sure gas line is free of air. Before lighting FIRE, for If damaged during shipping straighten fins with a fin comb. Failure to follow this warning death or property damage. START- as sheet metal edges. PROTECTION PRE- such etc. heat space, and inefficient The transformer is of the energy-limiting a 30-sec. overload or shorted secondary wires, discomfort setting may be changed of comfort e. Ensure use 0.18 amp for the will result in improper damage, d. Inspect all field- and factory-wiring connections. sure that connections are completed and tight. to ensure proper heating performance. Set the heat anticipator, using an ammeter between the W and R terminals to determine the exact required handling all refrigerant tubing connections using leak detector, or liquid-soap solution. If a refrigerant Refrigerant SETTING The room thermostat and lines, loose parts, disconnected b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak. by the colors red, green, yellow, brown, and white (See Fig. 11). Ensure the leads are long enough to be routed into the low-voltage splice box (located below right HEAT ANTICIPATOR for shipping broken MOTOR and miscellaneous _ loose parts GRILLE power to unit and install lockout b. Relieve and reclaim all refrigerant from system using both high- and low-pressure ports. c. Cut component connecting tubing with tubing cutter and remove component d. Carefully unsweat remaining necessary. flame. Oil can ignite from unit. tubing stubs when exposed when 1/8" to torch MAX MOTOR BETWEEN AND FAN HUB MOTOR SHAFT C99009 Fig. 12 - Fan Blade Use the Start-Up Checklist supplied at the end of this book and proceed as follows to inspect and prepare the unit for initial start-up: Clearance START-UP 1. Remove access panel. Step 1--CHECK 2. Read and follow instructions on all DANGER, WARNING, CAUTION. and INFORMATION labels attached to, or shipped Proceed with unit. 3. Make the following as follows FOR REFRIGERANT to locate and repair LEAKS a refrigerant leak and to charge the unit: inspections: 1. Locate leak and make sure that refrigerant has been relieved and reclaimed from low-pressure 12 ports. system pressure both high- and CHECK HEATING CONTROL Startandcheck theunitforproper heating control operation as follows (see furnace lighting instructions located inside burner or blower access panel): 1.Place roomthermostat SYSTEM switchin theHEAT position andthefanswitch isplaced inAUTO position. 2.Settheheating temperature control ofthethermostat above room temperature. 3.Theinduced-draft motor willstart. 4.Afteracallforheating, themain burner should lightwithin 5 sec. If theburners donotlight,there isa22-sec. delay before another 5-sec. try.Iftheburners stilldonotlight,this sequence isrepeated. If theburners donotlightwithin15 minutes fromtheinitialcallforheat, there isalockout. To reset thecontrol, break the24-vpower toW. 5.Theevaporator fanwillturnon45sec. after theflame has been established. Theevaporator fanwillturnoff45sec. after thethermostat hasbeen satisfied. CHECK GASINPUT Check gas input and manifold pressure after unitstart-up (See Table 3).If adjustment isrequired proceed asfollows: • Therated gasinputs shown inTable 3areforaltitudes fromsea levelto2000 ftabove sea level. These inputs are based onnatural gas withaheating value of1050 Btu/ft 3 at0.65specific gravity, orpropane gaswithaheating value of2500 Btu/ft 3at1.5specific gravity. • Forelevations above 2000 ft,reduce input4%foreach 1000 ft above sealevel. Forexample at2001ft.a12% totalderate isrequired. • When thegassupply being used hasadifferent heating value orspecific gravity, refer tonational andlocal codes. orcontact yourdistributor todetermine therequired orifice size. 2.Repair leak following accepted practices. NOTE: Install afilterdrierwhenever thesystem hasbeen opened forrepair. 3.Addasmall charge ofR-22refrigerant vapor tosystem and leak-test unit. 4.Recover refrigerant fromrefrigerant system and evacuate to 500microns ifnoadditional leaks arefound. 5.Charge unitwithR-22refrigerant, usinga volumetric charging cylinder oraccurate scale. Refer tounitrating plate forrequired charge. Besuretoaddextrarefrigerant to compensate forinternal volume offilterdrier. STEP 2--START-UP HEATING ANDMAKEADJUSTMENTS Complete therequired procedures givenin thePre-Start-Up section before starting theunit.Donotjumper anysafety devices when operating theunit.Make sure thatburner orifices areproperly aligned. Unstable operation myoccur when theburner orifices in themanifold aremisaligned. Follow thelighting instructions ontheheating section operation label (located inside theburner orblower access door) tostart the heating section. NOTE: Make sure thatgassupply hasbeen purged, andthatallgas piping hasbeen checked forleaks. / UNIT DAMAGE HAZARD Failure to follow this caution component life. MANIFOLD unit and/or Do Not redrill an orifice. Improper drilling (burrs, out-of-round holes, etc.) can cause excessive burner noise and misdirection of burner flame. If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. PIPE PLUG C99019 Fig. 13 - Burner may result in reduced Assembly ADJUST GAS INPUT BURNER FLAME The gas input to the unit is determined by measuring the gas flow at the meter or by measuring the manifold pressure. Measuring the gas flow at the meter is recommended for natural gas units. The manifold pressure propane gas units. Measure must be measured Gas Flow (Natural to determine the input of Gas Units) Minor adjustment to the gas flow can be made by changing the manifold pressure. The manifold pressure must be maintained between 3.4 and 3.6 in. wc. If larger adjustments are required, change main burner orifices following the recommendations of national and local codes. IFOLD NOTE: All other appliances off when gas flow is measured 099021 Fig. 14 - Monoport Burner 13 that use the same meter must be turned at the meter. 3--Heating Table HEATING BNPUT Inputs GAS SUPPLY PRESSURE (iN. WC) Naturalt Propane*t Max I'din (BTUH) NUMBER OF ORIFICES 40,000 2 4.0 13.0 4.0 13.0 3.5 60,000 2 4.0 13.0 4.0 13.0 3.5 3.5 90,000 115,000 3 3 4.0 4.0 13.0 13.0 3.5 3A 13.0 4.0 4.0 13.0 3.5 3.7 130_000 3 4.0 13.0 4.0 13.0 3.5 3.5 Min MANIFOLD Max PRESSURE Naturalt (IN. WC) Propane*t 3.5 When a unit is converted to propane, different size orifices must be used. See separate, natural to propane conversion kit instructions. j'Based on altit/des from sea level to 2000 ft above sea level. For altit/des above 2000 ft, reduce 111putrating 4 percellt lot each additioiml 1000 ft above sea level In Canada. from 2000 ft above sea level to 4500 fl _bove sea level derate tl_e unit 10 percent, Proceed as follows: Measure 1. Turn off gas supply n to unit. 2. Remove pipe plug on manifold manometer. Turn on gas supply 3. Record number revolution. EXAMPLE: (See Fig. 13) and connect to unit. in Step 3 into 3600 specified Assume 3. 112.5 x 1 =112.5 of gas to size of test dial 5. Adjust pressure gas is 1 cu ft, one With Btuh, only a minor change adjustment screw on gas screw to the correct in Table 3. Turn manifold adjusting screw manifold pressure, or turn adjusting to decrease manifold pressure. cover screw. BURNER burner FLAME access panel removed, observe the unit heating operation. Watch the burner flames to see if they are light blue and soft in appearance, and that the flames are approximately the same in the as follows to adjust gas adjustment screw on gas AIRFLOW AND TEMPERATURE The heating section for each size unit is designed heating operation unit rating plate. screw clockwise to increase within may result. the approved Refer to Indoor heating for on the and Airflow Adjustments section to adjust OF OPERATION and unit wiring label.) On a call for heating, injury range. Airflow SEQUENCE (See Fig. 15-17 HAZARD pressure and approved range stamped airflow when required. HEATING Unsafe operation of the unit may result if manifold outside this range. the temperature-rise Table 8 shows the approved temperature rise range for each heating input, and the air delivery cfm at various temperature rises. The heating operation airflow must produce a temperature rise that falls and 3.6 in. wc. Unsafe operation of the unit may result if manifold pressure is outside this range. Personal injury or Failure to follow this warning could result in personal or death and/or property damage. within RISE gas input, or turn regulator adjustment screw counterclockwise to decrease input. Manifold pressure must be between 3.4 3. Replace (See for each burner. Propane will have blue flame (See Fig. 14). Refer to the Maintenance section for information on burner removal. and proceed DAMAGE manometer 7. Turn off gas to unit. Remove manometer from pressure tap. Replace pipe plug on gas valve, then turn on gas to unit. Check for leaks. Btuh input. cover screw over regulator AND UNIT adjustment as specified 6. Replace value of the gas is 1050 input: FIRE regulator clockwise to increase screw counterclockwise CHECK adjustment and connect cover screw over regulator pressure, ft 3 of gas flow/hr. If the desired gas input is 115.000 manifold pressure is required. unit damage gas unit: 3. Turn on gas to unit. one revolution. 4. 112.5 x 1050 = 118,125 2. Turn regulator to adjust gas input on a propane pipe plug on manifold 4. Remove valve. 2. 3600 + 32 = 112.5. 1. Remove valve. as follows 2. Remove of this value with in Table 3 (Consult the local value of gas is not known). that the 1. 32 sec. to complete value input in Btuh. Compare input shown if the heating (number of cubic feet (cu ft) result of Step 5 by Btu heating manifold in Table 3. Proceed of test dial to obtain cubic feet (cu revolution takes 32 sec., and the heating Btu/ft3. Proceed as follows: Observe Units) Fig. 13). result of Step 4 by the number obtain total measured heating supplier (Propane 1. Turn off gas to unit. shown for one revolution ft) of gas flow per hour. 6. Multiply Pressure The main burner orifices on a propane gas unit are sized for the unit rated input when the manifold pressure reading matches the level of seconds for gas meter test dial to make one 4. Divide number of seconds seconds in one hr). 5. Multiply Manifold terminal W of the thermostat is energized. starting the induced- draft motor. When the hall-effect sensor on the induced-draft motor senses that it has reached the required speed. is the burner integrated energized cover screw cap on gas valve. satisfied 4. Turn off gas supply to unit. Remove manometer from pressure tap and replace pipe plug on gas valve. Turn on gas to unit and check for leaks. indoor delay. sequence This and W is de-energized, (evaporator) function is performed by the fan motor the burners stop firing shuts off after a 45-sec. and the time-off An LED (light-emitting diode) indicator is provided board to monitor operation. The control board on the control is located by removing operation, the burner LED is continuously 14 begins. gas control (IGC). The indoor (evaporator)-fan motor is 45 sec. after flame is established. When the thermostat is access panel. During normal on (See Table 4 for error codes). the oi 5 L A07039 Fig, 15 - 208/230-1-60 Wiring 15 Diagram H A07040 Fig. 16 - 208/230-3-60 Wiring ]6 Diagram ,c,x_ 2J CD i !:_i ci j _J> ,J ,,J Z, :7: A07041 Fig. 17 - 460-3-60 Wiring 17 Diagram Table ERROR Normal 4--LED Indications CODE LED INDICATION On IMPORTANT: Failure Off oriented. 1 Flash 3-phase Fan On/Off Delay Modified Limit Switch Fault Four Sense Consecutive Fault Limit Switch Faults Ignition Lockout Fault Induced-Draft Motor Fault Rolloat Internal Temporary Switch Control Lock-Out (1 hr) scroll checked (below lead orientation. compressors to ensure turning backwards, the difference 5 Flashes discharge may be dramatically protector pressures CHECKING are proper If not corrected 4 Flashes room within will shut off the compressor. compressor When suction and lower than normal. REFRIGERANT CHARGE 9 Flashes is tested and factory sealed. Allow system to operate a minimum 15 minutes before checking or adjusting charge. with R-22 NOTE:Adjustment of the refrigerant the unit is suspected of not having the proper refrigerant charge is not required R-22 and of unless charge. The charging label and the tables shown refer to system temperatures and pressures in cooling mode only. A refrigerant charging label is attached to the outside of the service access door. The chart includes the required suction line temperature suction line pressures and outdoor ambient temperatures. at given An accurate superheat, thermocoupleor thermistor-type thermometer, and a gauge manifold are required when using the superheat charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers adequate for this type of measurement. When the air temperature at the limit switch drops to the low-temperature setting of the limit switch, the switch closes and completes the control circuit. The direct-spark ignition system cycles and the unit returns to normal heating operation. ROLLOUT SWITCH The function of the rollout switch is to close the main gas valve in the event of flame rollout. The switch is located above the main burners. When the temperature at the rollout switch reaches the maximum allowable temperature, the control circuit trips, closing the gas valve and stopping gas flow to the burners. The indoor (evaporator) fan motor (IFM) and induced draft motor continue to run until switch is reset. The IGC LED will display FAULT CODE 7. MAKE is fully charged 3-phase 8 Ftashes in system 5 minutes, The to correct rotation. between AND ADJUSTING direction compressor The refrigerant Normally closed limit switch (LS) completes the control circuit. Should the leaving-air temperature rise above the maximum allowable temperature, the limit switch opens and the control circuit "breaks." Any interruption in the control circuit instantly closes the gas valve and stops gas flow to the burners and pilot. The blower motor continues to run until LS resets. AND power be power leads to the unit must be reversed LIMIT SWITCHES COOLING must 3 Flashes NOTES: 1. There is a 3 see. pause between error code displays. 2. If more than o*ie error code exists, all applicable error codes will be displayed numerical sequel*ce. 3. This chart is oil the wiri,lg diagram located inside the burner access panel. Step 3---START-UP MENTS Three-phase, Unit the internal 7 Flashes Fault is set to call for cooling 2 Flashes 6 Flashes Fault control temperature). Operation Hardware Flame temperature UNIT DAMAGE HAZARD Failure to follow this caution When evaluating the because they are not may result in unit damage. refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, insufficient airflow across either coil or both coils. Proceed ADJUST- 2. Using caps from lowhoses and high-pressure 3. Start unit in Cooling pressures 4. Measure and record and pressure Charging (psig). Charts," (°C) db) with actual liquid (°F (°C) db). (°F (°C)). (psig) to determine desired temperature (See Table 6). 6. Compare low- high-pressure and let unit run until system temperature (high-side) "Cooling temperature(°F 2. Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set cooling control below room temperature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The evaporator fan will continue to run for 30 sec. attach and the following: line temperature c. Discharge 5. Using Mode ambient-air b. Liquid 1. Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position. to low- fittings. stabilize. a. Outdoor Start and check the unit for proper cooling control operation as follows: service with valve core depressors, high-pressure gauge hoses service fittings, respectively. CHECKING COOLING CONTROL OPERATION as as follows: 1. Remove Complete the required procedures given in the Pre-Start-Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the compressor when the outdoor temperature is below 40°F (unless accessory low-ambient kit is installed). Do not rapid-cycle the compressor. Allow 5 minutes between on cycles to prevent compressor damage. such compare outdoor-air the discharge system line temperature line pressure operating liquid with desired line liquid line temperature. Using a tolerance of -+2°K add refrigerant if actual temperature is more than 2°F higher than proper liquid line temperature temperature, or remove refrigerant is more than 2°F lower than required if actual liquid line temperature. 3. When using an auto-changeover room thermostat, place both SYSTEM and FAN switches in AUTO positions. Observe that unit operates in Heating mode when temperature control is set to call for heating (above room temperature) and operates in Cooling mode when NOTE: refrigerant 18 If the problem causing the inaccurate leak, refer to the Check for Refrigerant readings is a Leaks section. INDOOR AIRFLOW ANDAIRFLOW ADJUSTMENTS To change the speed of the indoor fan motor (IFM), remove the fan motor speed leg lead from the blower relay (BR). This wire is attached to terminal blower motor (BM) of the integrated gas control (IGC) board for single-phase units. To change the speed, remove and replace with lead for desired blower motor speed. Insulate the UNITOPERATION HAZARD Failure tofollowthiscaution mayresult inunitdamage. Forcooling operation, therecommended airflow is350to450 cfmforeach12.000 Btuhof rated cooling capacity. For heating operation, theairflow must produce atemperature rise thatfallswithintherange stamped ontheunitrating plate. removed lead to avoid contact with chassis COOLING SEQUENCE parts. OF OPERATION With the room thermostat SYSTEM switch in the COOL position and the FAN switch in the AUTO position, the cooling sequence of operation is as follows: 1. When above Table 8shows thetemperature riseineach heating mode. Refer to these tables todetermine thedesired heating airflow forthesystem being installed. (See Table 9forwetcoilpressure drop). NOTE: Besure thatallsupply-and return-air grilles areopen. free fromobstructions, andadjusted properly.Airflow canbechanged using theUser Interface. the room temperature the cooling control thermostat completes terminal R to terminals 2. The normally and complete to condenser instantly. (indoor) NOTE: the circuit Y and G. open contacts contacmr ((7) close fan motor (IFM). Once the compressor on until the room slightly below the cooling this point, of energized thermostat open contacts of energized relay BM the circuit through evaporator blower has started and then stopped, not be started again until 5 minutes remains between the circuit through compressor motor (COMP) (outdoor) fan motor (OFM). Both motors start 3. The set of normally close and complete ELECTRICAL SHOCK HAZARD Failure tofollowthiswarning could result inpersonal injury ordeath. Disconnect electrical power totheunitandinstall lockout tag before changing blower speed. rises to a point that is slightly setting of the thermostat, the have elapsed. temperature drops it should The cooling to a point cycle that is control setting of the room thermostat. the thermostat breaks the circuit between At thermostat terminal R to terminals Y and G. These open circuits deenergize contactor coil C. The condenser and compressor motors stop. After Airflowcanbechanged bychanging theleadconnections ofthe blower motor. AllPY3Punitsarefactory wiredforlowspeed except the030 through the048sizes. FOR208/230V Forcolorcoding onthe208/230V motor leads, see Table 5. Table 5--Color ( odlng for 208/230V Motor Leads a 30-sec. condition, thermostat. BLACK = HIGH SPEED Blue = Medium Speed Red = Low Speed 19 delay, the blower waiting motor stops. The unit is in a standby for the next call for cooling from the room n Table 6--Coollng ( harglng Chart Suctien Line femperature {°F ! ODTemp, (°F) 52 54 56 59 6t 64 67 70 73 76 79 45 5I 55 60 64 53 57 62 66 70 55 53 57 62 66 71 75 65 56 61 66 71 75 53 58 63 85 50 54 95 50 105 49 115 125 0DTemp, __ m ______ (°C) 361 370 387 405 11 13 15 18 7 12 14 13 18 24 29 35 41 46 52 Suction Line Temperature !°C) Suction Line Press_ 423 442 462 482 502 523 544 21 16 19 2! 12 14 17 19 21 24 13 16 19 12 14 17 10 12 10 9 82 85 89 92 76 67 58 53 52 50 72 62 66 60 64 55 58 6I 53 56 59 566 589 612 636 24 20 14 12 11 10 17 14 13 11 19 16 18 14 16 13 15 AO5109 20 Table FILTER SIZE 20X20X1 7iFilter Pressure 500 600 700 800 900 1000 1100 1200 0,05 0,07 0.08 0.1 0.12 0.13 0,14 0.15 0.09 0.1 0.11 0.13 0.07 20X24X1 24X30X1 Table 8--Dry Coil Air Delivery* Unit PY3P024-060 Unit Heating Rise Range OF (°C) LOW1 20 - 50 (11 - 28) Medium High PYSP024060 35 - 65 (19 - 36) Medium High 20 (11 - 50 28) 65 36) 55 31) 70 39) 55 31) 2300 0.14 0.08 0.15 0.09 0.16 0.1 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18 - Horizontal (Deduct and Downflow Discharge - 10% for 208 Volts) External Static Pressure (in. wc) 0,2 309 0.3 304 0,4 301 0.5 288 0,6 290 0.7 288 0,8 280 0.9 CFM Heating Rise OF (°c) Watts CFM 985 82 (18) 411 1195 885 34 (19) 405 1155 820 37 (20) 398 1100 757 40 (22) 390 1028 686 44 (24) 379 957 583 NA 423 NA 263 NA NA 357 868 357 769 345 647 327 365 Heating Rise °F (°c) Watts CFM Heating Rise OF 25 (14) 528 1484 20 26 (14) 518 1421 21 27 (15) 509 1868 22 29 (16) 492 1279 23 31 (17) 477 1185 25 35 (19) 467 1088 28 39 (22) 447 970 81 46 (26) 485 853 35 421 712 42 (11) 311 (12) 309 (12) 304 (13) 301 (14) 288 (15) 290 (17) 288 (20) 280 CFM Heating Rise OF (°C) Watts CFM 985 48 (27) 411 1195 885 51 (28) 405 1155 820 55 (30) 398 1100 757 59 (33) 390 1028 686 NA 583 NA 423 NA 263 NA NA 379 957 357 868 357 769 345 647 327 365 Heating Rise °F (°c) Watts CFM Heating Rise OF (°c) 38 (21) 528 1484 39 (22) 518 1421 41 (23) 509 1868 44 (24) 492 1279 35 47 (26) 477 1185 38 52 (29) 467 1088 41 59 (33) 447 970 46 NA NA 485 853 53 421 712 63 (28) 288 428 (29) 280 263 (35) NA (23) (21) 288 686 (23) 290 583 Heating Rise OF (°C) Watts 82 (18) 411 34 (19) 405 37 (20) 898 40 (22) 390 44 (24) 879 NA NA NA NA 357 857 345 827 CFM Heating Rise °F (°C) Watts CFM Heating Rise OF 1195 25 (14) 528 1484 20 1155 26 (14) 518 1421 21 1100 27 (15) 509 1868 22 1028 29 (16) 492 1279 23 957 31 (17) 477 1185 25 868 35 (19) 467 1088 28 769 39 (22) 447 970 81 647 46 (26) 485 853 35 365 NA (C) Watts CFM Heating Rise °F (°c) Watts (11) 311 935 48 (27) 411 (12) 809 885 51 (28) 405 (12) 304 820 55 (30) 398 (13) 801 757 59 (33) 390 (14) 286 686 (15) 290 583 (17) 286 428 (20) 280 263 (23) NA NA NA NA NA 379 357 357 345 327 CFM Heating Rise °F (°c) Watts CFM 1195 38 (21) 528 1484 1155 39 (22) 518 1421 1100 41 (23) 509 1368 1028 44 (24) 492 1279 957 47 (26) 477 1185 868 52 (29) 467 1088 769 59 (33) 447 970 647 NA 335 NA 435 853 421 712 Heating Rise OF (°c) Watts CFM Heating Rise °F (°C) Watts NA NA NA 439 1242 36 (20) 503 429 1170 38 (21) 491 415 1089 41 (23) 479 35 (20) 401 994 45 (25) 461 38 (21) 395 917 49 (27) 450 41 (23) 380 837 54 (30) 486 46 (28) 356 702 53 (29) 339 570 63 (35) 329 442 NA NA NA 418 404 389 CFM Heating Rise OF (°C) Watts CFM 1320 34 (19) 641 1332 1244 36 (20) 627 1288 1162 39 (22) 623 1205 1081 42 (23) 609 1119 1005 45 (25) 601 1033 897 50 (28) 588 933 767 NA 662 NA 541 NA 571 826 559 714 548 580 Heating Rise OF (°c) Watts CFM 33 (18) 439 1242 35 (19) 429 1170 37 (21) 415 1089 40 (22) 401 994 44 (24) 395 917 48 (27) 380 837 54 (30) 356 702 NA NA 339 570 329 442 Heating Rise °F (°c) Watts 54 (30) 503 58 (32) 491 62 (34) 479 68 (38) 461 NA NA NA NA NA 450 486 418 404 389 CFM Heating Rise °F (°C) Watts CFM 1820 51 (28) 641 1332 1244 54 (30) 627 1288 1162 58 (32) 623 1205 1081 62 (35) 609 1119 1005 67 (37) 601 1033 897 NA 767 NA 662 NA 541 NA 588 933 571 826 559 714 548 580 Heating Rise OF (°c) Watts CFM Heating Rise °F (°c) Watts 50 (28) 434 1282 35 (20) 560 52 (29) 428 1241 36 (20) 548 58 (31) 422 1206 37 (21) 535 60 (34) 403 1160 39 (22) 526 65 (36) 404 1109 41 (23) 511 NA NA NA NA 390 1040 43 (24) 496 375 967 47 (26) 478 360 890 51 (28) 460 344 813 55 (31) 439 Medium I CFM Heating Rise °F (°c) Watts CFM 1526 29 (16) 785 1860 1482 30 (17) 746 1805 1437 81 (17) 780 1751 1398 32 (18) 709 1685 1344 83 (19) 690 1620 1281 35 (20) 864 1541 1205 87 (21) 642 1468 1125 40 (22) 824 1870 1029 44 (24) 600 1265 High Heating Rise OF (°c) NA 25 (14) 28 (14) 27 (15) 28 (15) 29 (16) 81 (17) 33 (18) 36 (20) Medium I Medium I Medium I Medium I Low 25 (14 - 2200 (20) 301 757 High PYSPO42060 2100 NA Low 40 (22 - 2000 304 820 High PYSPO36090 1900 NA Low 25 (14 - 1800 309 885 High PYSPO36060 1700 NA Low 35 (19 - 1600 311 935 High PYSPO3O06O 1500 Watts CFM LOW PYSP03O04O 1400 0.1 311 (°c) Watts Low1 (in_ wc) 1300 Motor Speed Watts PYSP024040 D_-op Table CFM 21 421 712 42 / Table 8 - ('ont'd Dry ('oil Air Delivery* Unit PY3P024-060 Heating Rise Range OF (°C) Unit 40 - 70 (22 - 59) External Medium 1 High Low 25 (14 - PYSP048090 I 55 51) Medium 1 High Low PYSP048115 35 - 65 (19 - 56) Medium 1 High Low PYSP048130 40 - 70 (22 - 39) Medium 1 High Low1 25 (14 - PYSP080090 55 31) Medium High Low1 35 - 65 (19- 36) PYSP080115 Medium High Low1 40 (22 - PYSP080130 70 39) Medium High ail delively vah_es ale without iFae{oly shipped heating_coolill "NA" = Not allowed fol heatii_g Note: De&ict field supplied aii and Downflow - Static Pressure (in. wc) Watts CFM 0.1 434 1282 0,2 428 1241 0.3 422 1206 0,4 403 1160 0.5 404 1109 0,6 390 1040 0.7 375 967 0,8 380 890 Heating Rise °F (°C) Watts CFM 53 (29) 560 1526 54 (30) 548 1482 58 (31) 535 1437 58 (32) 526 1398 61 (34) 511 1344 85 (38) 496 1281 70 (39) 478 1205 NA NA 460 1125 439 1029 Heating Rise OF (°C) Watts CFM 44 (25) 785 1860 46 (25) 746 1805 47 (28) 730 1751 48 (27) 709 1885 50 (28) 690 1620 53 (29) 664 1541 56 (31) 642 1488 80 (33) 624 1370 66 (36) 600 1265 Heating (°C) Watts CFM Heating (°C) Watts CFM Heating (°c) Watts CFM Heating (°C) Watts CFM NA NA NA 627 1550 44 (24) 771 1798 38 (21) 969 2124 32 (18) 627 1550 617 1530 44 (24) 755 1771 38 (21) 941 2071 33 (18) 617 1530 607 1493 45 (25) 734 1734 39 (22) 908 2000 84 (19) 607 1493 40 (22) 584 1461 46 (26) 711 1887 40 (22) 887 1944 35 (19) 584 1461 42 (23) 567 1414 48 (27) 690 1645 41 (23) 858 1876 56 (20) 567 1414 44 (24) 548 1361 50 (28) 865 1595 42 (24) 827 1811 37 (21) 548 1361 46 (28) 528 1320 51 (28) 639 1530 44 (25) 804 1735 59 (22) 528 1320 49 (27) 505 1250 54 (30) 807 1449 47 (26) 767 1847 41 (23) 505 1250 53 (30) 480 1177 Heating Rise oF (°C) Watts CFM 58 (31) 771 1798 56 (31) 755 1771 58 (32) 734 1734 59 (33) 711 1887 61 (34) 690 1645 83 (35) 865 1595 65 (38) 639 1530 NA NA 807 1449 572 1355 Heating Rise OF (°C) Watts CFM Heating Rise OF (°C) Watts CFM 48 (27) 969 2124 41 (23) 627 1550 49 (27) 941 2071 42 (23) 617 1530 50 (28) 908 2000 43 (24) 607 1493 51 (28) 887 1944 44 (25) 584 1461 52 (29) 858 1876 46 (26) 567 1414 54 (30) 827 1811 48 (28) 548 1361 56 (31) 804 1735 50 (28) 528 1320 80 (33) 767 1847 52 (29) 505 1250 64 (35) 748 1555 55 (31) 480 1177 Heating Rise °F (°C) Watts CFM 63 (35) 771 1798 84 (35) 755 1771 65 (38) 734 1734 87 (37) 711 1887 69 (38) 690 1645 NA NA NA NA 865 1595 639 1530 807 1449 572 1355 Heating Rise OF (°c) Watts CFM Heating Rise OF (°C) Watts 54 (30) 969 2124 46 (26) 786 55 (31) 941 2071 47 (26) 769 56 (31) 908 2000 49 (27) 754 58 (32) 887 1944 50 (28) 736 59 (33) 858 1876 52 (29) 722 81 (34) 827 1811 54 (30) 705 64 (35) 804 1735 58 (31) 684 87 (37) 767 1847 59 (33) 658 748 1555 63 (35) 618 CFM Heating Rise °F (°c) Watts CFM Heating Rise OF 2027 33 (19) 873 2095 32 1960 34 (19) 849 2026 33 1901 36 (20) 833 1962 84 1821 37 (21) 815 1887 36 1759 38 (21) 798 1817 57 1893 40 (22) 782 1748 39 1616 42 (23) 783 1679 40 1513 45 (25) 748 1583 43 1354 50 (28) 704 1439 47 (°c) Watts CFM Heating Rise °F (°C) Watts (18) 1012 2184 31 (17) 786 (19) 993 2109 32 (18) 769 (19) 981 2036 33 (18) 754 (20) 965 1963 34 (19) 736 (21) 948 1886 36 (20) 722 (21) 927 1812 37 (21) 705 (22) 904 1729 39 (22) 684 (24) 886 1847 41 (23) 858 (28) 848 1496 45 (25) 618 CFM Heating Rise °F (°c) Watts CFM Heating Rise OF (°c) Watts CFM Heating Rise °F (°c) Watts 2027 43 (24) 873 2095 41 (23) 1012 2184 39 (22) 786 1960 44 (24) 849 2026 43 (24) 993 2109 41 (23) 769 1901 45 (25) 833 1962 44 (24) 981 2036 42 (24) 754 1821 47 (26) 815 1887 46 (25) 963 1963 44 (24) 736 1759 49 (27) 798 1817 47 (28) 948 1886 46 (25) 722 1893 51 (28) 782 1748 49 (27) 927 1812 48 (26) 705 1616 53 (30) 783 1679 51 (29) 904 1729 50 (28) 684 1513 57 (32) 748 1583 54 (30) 886 1847 52 (29) 858 1354 64 (35) 704 1439 60 (33) 848 1496 58 (32) 618 CFM Heating Rise °F (°C) Watts CFM Heating Rise OF (°c) Watts CFM Heating Rise °F 2027 48 (27) 873 2095 47 (28) 1012 2184 45 1960 50 (28) 849 2026 48 (27) 993 2109 46 1901 51 (28) 833 1962 50 (28) 981 2036 48 1821 54 (30) 815 1887 52 (29) 965 1963 50 1759 55 (31) 798 1817 54 (30) 948 1886 52 1893 58 (32) 782 1748 56 (31) 927 1812 54 1616 60 (34) 783 1679 58 (32) 904 1729 58 1513 84 (38) 748 1583 82 (34) 886 1847 59 1354 NA (28) (27) (28) (29) (30) (31) (33) (38) Rise OF Rise °F Rise OF Rise OF (°C) (25) ail filtel and aIe fol chy coil (see Wet Coil ?Iessule D_op table) 8 speed speed filtei plessme dlop ai_d wet coil pzessule dzop to obtain extelnal Table 9--PY3P 1100 UNIT SIZE static piessule Wet 0.9 344 813 NA 572 1355 50 (28) 748 1555 43 (24) 480 1177 NA 704 1439 68 (38) 848 1496 65 available fol ductin 8 Coil Pressure Drop STANDARD CFM (S.C.F,M,) 1200 1300 1400 600 700 800 900 1000 0.030 0.037 0.044 0.053 0.063 030 036 0.037 - 0.044 - 0.053 0.05 0.063 0.061 0.072 0.072 0.081 0,08 0.105 0,09 ..... 0,11 042 - - - 0.044 0.051 0.059 0.065 048 - - - 0.044 0.050 060 ...... 024 Discharge 10% for 208 Volts) Motor Speed Low PYSP042090 - Horizontal (Deduct 1500 1600 1700 1800 0.072 0.060 0.053 1900 2000 0.088 0.095 0.105 0.059 0.066 0.072 0.077 0.086 - 0.079 0.087 0.095 0.102 0.113 0.123 ....... 22 .... - MAINTENANCE To ensure possibility dimensional size and type as originally recommended filter sizes. continuing high performance and to minimize the of premature equipment failure, periodic maintenance 10, Troubleshooting Chart. NOTE TO EQUIPMENT OWNER: about the availability of a maintenance PERSONAL INJURY Consult contract. AND UNIT your INDOOR local dealer in the Owner's AND MOTOR are pre-lubricated. Do not attempt to lubricate annually. injury The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment, other than those recommended 1 for For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor HAZARD Failure to follow this warning could result in personal or death and unit component damage. procedures BLOWER NOTE: All motors these motors. DAMAGE See Table Inspect air filter(s) at least once each month and replace (throwaway-type) or clean (cleanable-type) at least mqce during each cooling season and twice during the heating season, or whenever the filter becomes clogged with dust and lint. must be performed on this equipment. This unit should be inspected at least once each year by a qualified service person. To troubleshoot unit, refer to Table installed. ELECTRICAL SHOCK HAZARD Failure to follow this warning or death. Manual. could result in personal injury Disconnect and tag electrical power to the unit before cleaning and lubricating the blower motor and wheeL ELECTRICAL SHOCK Failure to follow injury or death: these To clean the blower HAZARD warnings could result and disassemble a. Remove 1. Turn off electrical power to the unit before performing maintenance or service on this unit. 2. Use extreme 1. Remove in personal motor and wheeh caution when removing 3. Never place anything with the unit. combustible panels b. Disconnect Disconnect contactor. any and parts. motor ytellow c. On all units remove either on or in contact blower assembly as follows: unit access panel. lead from lead from blower blower relay terminal L2 assembly (BM). of the from unit. Remove screws securing blower to blower partition assembly out. Be careful not to tear insulation and slide in blower compartment. d. Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly. UNIT OPERATION Failure to follow operation. HAZARD this caution may result e. Loosen remove in improper housing, maintenance 1. Inspect air filter(s) requirements for this equipment are as each Clean when month. or replace 2. Remove indoor coil, drain pan, and condensate cooling season for cleanliness. drain each d. Reassemble tightened shaft. season. 7. Check and inspect heating before refrigerant each heating Never operate any obstructions, the unit without in the return- air duct system. Always of as follows: by marking wheel orientation. vanes. into housing. unit access electrical Be sure setscrews shaft flats and not on round are part of panel. power and check for and motor speeds during heating to unit. Start unit and the flue collector box and upper areas of the heat exchanger: if necessary. 1. Remove AIR FILTER IMPORTANT: out GAS PASSAGEWAYS To inspect Clean and adjust when necessary. flue hood and remove motor proper blower rotation cooling cycles. FLUE section wheel on motor f. Reinstall 3. Restore when necessary. 6. Check mount wheel into housing. e. Reassemble connections for tightness and controls for each heating and cooling season. Service with motor and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild solvent. season, inspect proper cleaning in contact and clean blower wheel (clips) on blower frequency. 5. Ensure electric wires are not tubing or sharp metal edges. and c. Remove caked-on dirt from wheel and housing with a brush. Remove lint and/or dirt accumulations from wheel 3. Inspect blower motor and wheel for cleanliness at the beginning of each heating and cooling season. Clean when 4. Check electrical proper operation motor a. Ensure proper reassembly Clean when necessary. necessa U. For first heating and cooling blower wheel bi-monthly to determine slide b. Lift wheel from housing. When handling and/or cleaning blower wheel, be sure not to disturb balance weights necessary. 2. Inspect and housing. Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnecting when servicing. The minimum follows: setscrew(s) that secures wheel to motor shaft. screws that secure motor mount brackets to a suitable according section. air filter replace the filter with the same 23 the combustion to directions blower wheel in the and motor Combustion-Air assembly Blower 2.Remove the3screws holding theblower housing totheflue collector boxcover (See Fig.18-21). 3.Remove the12screws holding thefluecollector boxcover (See Fig.20-21) totheheat exchanger assembly. Inspect the heat exchangers. 4.Clean allsurfaces, asrequired, using awirebrush. INDUCED DRAFT (COMBUSTION AIR)BLOWER Clean periodically toassure proper airflow andheating efficiency. Inspect blower wheel every fallandperiodically during theheating season. Forthefirstheating season, inspect blower wheel bimonthly todetermine proper cleaning frequency. Toinspect blower wheel, remove drafthoodassembly. Shine a flashlight intoopening toinspect wheel. If cleaning isrequired, remove motor andwheel asfollows: 1.Remove unitaccess panel (See Fig.19). 2.Remove the7 screws thatattach induced-draft motor mounting plate toblower housing (See Fig.20). 3.Slide themotor and blower wheel assembly outoftheblower housing (See Fig.20).Clean theblower wheel. Ifadditional cleaning isrequired, continue withSteps 4and5. 4.Toremove blower, remove 2setscrews. 5.Toremove motorandcooling fanassembly, remove 4 screws thatholdblower housing tomounting plate. 6.Toreinstall, reverse theprocedure outlined above. obstructions, including airflow through Straighten weeds the condenser and shrubs, that interfere with the coil. bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent and water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between flush all dirt and debris from the unit base. the coils. Be sure to Inspect the drain pan and condensate drain line when inspecting coils. Clean the drain pan and condensate drain by removing the all foreign matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain trough is restricted, snake" or similar probe device. IGNITION MODULE \ clear it with a "plumbers INDUCED DRAFT ! MOTOR MOUNT \\\\ ¢3 LIMITSWITCH Remove unitaccess panel. Limitswitch islocated ontheblower partition. BURNER IGNITION Unitisequipped withadirect spark ignition 100percent lockout system. Ignition module islocated inthecontrol box(See Fig. 18).Module contains aself-diagnostic LED.During servicing, refer tolabel diagram forLEDinterpretation. If lockout occurs, unitmayberesetby eithermomentarily interrupting power supply tounitorbyturning selector switch to OFFposition atthethermostat. MAINBURNERS Atthebeginning ofeach heating season, inspect fordeterioration or blockage due tocorrosion orother causes. Observe themain burner flames andadjust, ifnecessary. Removal COLLECTOR BOX the gas train for servicing: 1. Shut off main gas valve. 2. Shut off power to unit and install lockout 3. Remove tag. unit access panel (See Fig. 19). 4. Disconnect gas piping at unit gas valve. 5. Remove wires connected 6. Remove ignitor 7. Remove the mounting to gas valve. Mark each wire. and sensor wires at the ignitor screw that attaches module. the burner rack to the unit base (See Fig. 18). 8. Slide the burner 9. To reinstall, rack out of the unit (See Fig. 18 and 21). reverse the procedure OUTDOOR COIL, DRAIN PAN INDOOR Inspect coil. evaporator the condenser COIL, outlined AND above. CONDENSATE coil, and condensate BLOWER HOUSING BURNER RACK MOUNTING SCREW A05119 Fig. 18 - Blower of Gas Train To remove ROLLOUT SWITCH i drain pan at least once each year. The coils are easily cleaned when dry: therefore, inspect and clean the coils either before or after each cooling season. Remove all 24 Housing and Flue Collector Box FRONT ACCESS RANEL A05127 Fig. 19 - Unit Access Panel C99086 Fig. 21 - Burner OUTDOOR Rack Removed FAN HOUSING UNIT OPERATION Failure to follow components. (HIDDEN) 1. Remove cover. 2. Turn 6 screws to unit 4. C99085 Wheel 5. the fan If fan needs shaft. When replacing be visible) 6. Ensure 7. Replace 25 and grille upside down and on motor top to top cover to for cracks loosen fan blade, setscrew setscrew position the motor Fig. or bends. end blade (1/8 and slide so that in. of motor fan off the hub shaft is will 12). engages the fiat area on the motor shaft tightening. ELECTRICAL to turn blades from (See that when sure assembly to be removed, motor 1/8 in. away Inspect outdoor fan blade. 3. Inspect and Blower may result in damage holding motor/grille expose of Motor this caution Keep the condenser fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit. 2 SETSCREWS Fig. 20 - Removal HAZARD grille. CONTROLS check off the AND electrical the electrical power WIRING controls and to the unit. wiring annually. Be Remove access panel to locate all the electrical and wiring. If oil is detected or if low performance is suspected, refrigerant tubing using an electronic leak detector, solution. If a refrigerant leak is detected, refer disassemble the connection, clean all the parts, re-strip and reassemble the connection properly and securely. Refrigerant After inspecting n controls Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned cnnnections are noticed, the electrical controls and wiring, the wire end replace Leaks leak test all or liquid-soap to Check for section. If no refrigerant leaks are found and low performance is suspected, refer to Checking and Adjusting Refrigerant Charge section. all the panels. Start the unit, and observe at least one complete cooling cycle to ensure proper operation. If discrepancies are observed in INDOOR operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checks. The heating REFRIGERANT METERING AIRFLOW and/or cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supplyand return-air grilles are open and free from obstructions, and that the air filter is clean. CIRCUIT Refrigerant distributor Inspect all refrigerant tubing connections and the unit base for oil accumulation annually. Detecting oil generally indicates a refrigerant leak. LIQUID DEVICES-ACCURATER metering assembly PISTON device is a fixed orifice and is located to the indoor coil. in the LINE STRAINER The liquid line strainer (to protect metering device) is made of wire mesh and is located in the liquid line on the inlet side of the metering device. EXPLOSION, PERSONAL INJURY Failure to follow this warning damage, personal injury or death. could HAZARD result TROUBLESHOOTING in property Refer to the Troubleshooting troubleshooting information. System under pressure. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flow-control devices, including solenoid valves. START-UP Use the Start-Up 26 Checklist Chart (Table CHECKLIST at the back of this manual. 10-12) for Table lO--T_oubleshooting SYMPTOM Chart CAUSE REMEDY Power failure Call power company Replace fuse or reset circuit breaker Fuse blown or circuit breaker tripped Compreeeor and eoadeneer fan wiiI not Defective eontactor, transformer, or high-pressure, loss-of-charge or low-pressure switch Replace component Insufficient Determine cause and correct etart, line voltage Incorrect or faulty wiring Check wiring diagram and rewire correctly U! setting too high Lower Ut temperature perature Faulty wiring or loose connections cuit Compreeeor rune will not start but eoadeneer fan in compressor Determine cause Defective run/start capacitor, overload, start relay Determine cause and replace Replace fuse or reset circuit breaker Determine cause power dead low Correct the direction of rotation by reversing the eeroll eompraeaor exeeeaive preaaara aoiae_ and thera may be a Scroll compressor is rotating in the wrong direction differential Refrigerant overcharge or undercharge Defective compressor Compreeeor isfying UI) Compreeeor cycles (other than operates normally aontinuouely sat- Defective run/start capacitor Determine cause and replace Faulty outdoor fan motor or capacitor Restriction in refrigerant system Replace Locate restriction and remove Dirty air filter Unit undersized for load Replace filter Decrease load or increase U! temperature set too low Reset UI Low refrigerant charge Locate leak, repair, and recharge Recover refrigerant, evacuate system, and recharge Clean coil or remove restriction coil dirty or restricted Dirty air filter Condenser Exceaeive eLfCtion praaaura air restricted Recover excess or air short-cycting Check for leaks, repair, end recharge, Remove restriction High heat load Compressor valves leaking Cheek for source and eliminate Refrigerant Recover excess refrigerant Replace compressor overcharged Metering device or low side restricted praeeLfra tOO lOW refrigerant Recover refrigerant, evacuate system, and recharge Determine cause and correct Low refrigerant charge Restriction in liquid tube Dirty air filter Low refrigerant charge Suction unit size Replace filter Clean coil Dirty condenser coil Refrigerant overcharged Air in system too low Recover refrigerant, evacuate system, and recharge to capacities shown on rating plate Replace and determine cause Determine cause end correct Determine cause and correct Outdoor Head praeeura 3-phase power leads to the unit, Shut down unit to allow pressures to equalize, Insufficient line voltage Blocked outdoor coil Air in system Exceaeive head praeeura Replace compressor Determine cause and correct Low input voltage (20% low) Feakee Check wiring and repair or replace Compressor motor burned out, seized, or internal overload open One leg of 3-phase Thrae-phaee cir- setting below room tem- Insufficient evaporator airflow Temperature too low in conditioned Outdoor ambient below 55"F Filter drier restricted area Replace filter Check for leaks, repair and recharge Remove source of restriction Increase air quantity Check filte_replace if necessary Reset UI Install low-ambient kit Replace filter 27 I! Table 11 Troubleshooting SYMPTOM Gulde=Heating CAUSE REMEDY Water in gas line Drain, Install drip leg. Check power supply fuses, wiring or circuit breaker, No power to furnace No 20-v Burners will not ignite Check transformer. NOTE: Some transformers have internal overcurrent protection that requires a cool-down peg od to reset. power suppmy to contr@ circuit Mis-wired or loose connections Check all widng and wire nut connections Check flame ignition and sense electrode positioning. Adiust as necessary, 1. Check gas line for air, Purge as necessary. NOTE: After purging gas line of air, wait at least 5 minutes for any gas to dissipate before attempting to light unit. 2. Check gas valve. Misaligned spark electrodes No gas at main burners Dirty air filter Clean or replace filter as necessary Check gas pressure at manifold match with that on unit namepmate Gas input to furnace too low Inadequate Poor flame heating Unit undersized for application Restricted airflow Replace with proper unit or add additional unit Clean or replace filter, Remove any restriction, Limit switch cycles main burners Check rotation of blower, temperature Adiust as necessary, 1. Tighten all screws around burner compartment 2. Cracked heat exchanger. Replace, 3. Unit over-fired. Reduce input (change orifices or ad}ust gas line or manifold pressure), 4. Check burner alignment, 5. Inspect heat exchanger for bbckage. Clean as necessary, Incomplete combustion results in: Aldehyde odors, carbon monoxide, sooting flame, floating flame characteristics Table 12 SYMPTOM Xi_ubleshooting CAUSE Guide--LED En-or rise of unit. Codes REMEDY Loss of power to control module (IGO)*. Check 5-amp fuse son IGC*, power to unit, 24-v circuit breaker, and transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the overload trips, allow 10 minutes for automatic reset. High limit switch opens during heat exchanger warm-up period before fan-on delay expires. Limit switch opens within three minutes after blower-off delay timing in heating mode, Ensure unit is fired on rate; ensure temperature rise is correct, Ensure unit's external static pressure is within application guidelines, Limit switch faults (LED 2 flashes) High temperature Check the operation of the indoor (evaporator) fan motor, Ensure that the supply-air temperature rise is in accordance with the range on the unit nameplate, Clean or replace filters, Flame sense fault (LED 3 flashes) The IGC* sensed flame that should not be present. Hardware failure (LED OFF) Fan ON/OFF delay modified (LED/FLASH) 4 consecutive limit switch (LED 4 flashes) limit switch is open. faults Ignition lockout (LED 5 flashes) Inadequate Induced-draft motor (LED 6 flashes) fault Check the operation of the indoor (evaporator) fan motor and that supply-air temperature rise agrees with range on unit nameplate information, airflow to unit. Unit unsuccessfully utes, Reset unit. If problem persists, replace control board. attempted ignition for 15 min- IGC does not sense that induced-draft operating,* motor is Check ignitor and flame sensor electrode spacing, gaps, etc, Ensure that fame sense and ignition wires are propedy terminated. Verify that unit is obtaining proper amount of gas. Check for proper voltage. If motor is operating, check the speed sensor plug/IGC Terminal J2 connection, Proper connection: PIN 1 - White PIN 2 - Red PIN 8 - Black Rollout switch will automatically reset, but IGC* will contin- Rollout switch fault (LED 7 flashes) Rollout switch has opened, ue to lockout unit, Check gas valve operation. Ensure that induced-draft blower wheel is properly secured to motor shaft. Inspect heat exchanger, Reset unit at unit disconnect, Internal control (LED 8 flashes) Microprocessor has sensed an error in the software or hardware, If error code is not cleared by resetting unit power, repmace the IGC*, Electrical interference Reset 24-v, to control board or turn thermostat off, then on again. Fault will automatically reset itself in one (1) hour. fault Temporary software (LED 9 flashes) WARNING _ lockout impeding IGC software : If the IGC must be replaced, be sure to ground yoreself to dissipate any electrical charge that my be present before handling sensitive to static electricity and my be damaged if the necessary precautions are not taken. IMPORTANT: Refer to Table 12 Troubleshooting Guide Heating for additional troubleshooting LEGEND IGC--tntegrated LED Gas Unit Controller Light Emitting Diode 28 analysis. new control board. The IGC is START-U P CHECKLIST (Remove and Store in Job File) I.Preliminary mnformation MODEL NO.: SERIAL NO.: DATE: TECHNICIAN: II, PRE=START-UP (mnsert ¢heckmark in box as each item ia completed) () VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM ( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS CONNECTIONS AND BRACKETS ( ) CHECK ALL ELECTRICAL ( ) CHECK ( ) CHECK GAS PIPING FOR LEAKS (WHERE APPLICABLE) THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN ( ) VERIFY THAT ( ) CHECK FAN WHEEL, UNIT INSTALLATION AND AND TERMINALS AND FOR LOCATION IN HOUSING/ORIFICE ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS FAN AMPS OUTDOOR (CONDENSER) AIR TEMPERATURE RETURN-AIR TEMPERATURE DB REFRIGERANT REFRIGERANT TEMPERATURE MEASURED *Measured tMeasured RISE IN.WG PSIG SUCTION PSIG CHARGE RISE (See Literature) TEMPERATURE WB IN.WG SUCTION DISCHARGE ( ) VERIFY REFRIGERANT GAS HEAT TEMPERATURE DB WB DB PRESSURES GAS iNLET PRESSURE GAS MANIFOLD PRESSURE IN PLACE IS LEVEL PROPELLER COOLING SUPPLY AIR GAS HEAT SUPPUY' AIR INSTRUCTIONS FOR TIGHTNESS III, START-UP INDOOR (EVAPORATOR) TEMPERATURES UNIT PER INSTALLATION USING LINE TEMP* DISCHARGE CHARGING TEMPt CHARTS RANGE RISE at suction inlet to compressor at liquid line leaving condenser. 2g AND SETSCREW TIGHTNESS g Payne Heating & Cooling Manufacturer reserves Systems * 7310 W. Morris St. * indianapolis, the right to change_ at any time_ specifications IN 46231 and designs Printed in U.S.A without notice and without 3O Edition obligations, Date: 03/07 Catalog No: IM-PY3P-05 Replaces: IM-PY3P-O4
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 30 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Jun 29 00:43:28 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools