PAYNE Package Units(both Units Combined) Manual L0704293

User Manual: PAYNE PAYNE Package Units(both units combined) Manual PAYNE Package Units(both units combined) Owner's Manual, PAYNE Package Units(both units combined) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 30

DownloadPAYNE  Package Units(both Units Combined) Manual L0704293
Open PDF In BrowserView PDF
Installation Instructions
NOTE:
Read
installation.
NOTE:

the entire

Installer:

Instructions

Make

instruction

sure

manual

the Owner's

before

Manual

starting

and

the

Service

are left with the unit after installation.
TABLE

OF CONTENTS

SAFETY CONSIDERATIONS
........................
INTRODUCTION
..................................

Page
1
2

RECEIVING

2-12

AND INSTALLATION

................

Check Equipment
.................................
Identify Unit ...................................
Inspect Shipment ................................

2
2
2

Provide Unit Support
..............................
Roof Curb .....................................
Slab Mount ....................................

2
2
2

Ground Mount
.................................
Field Fabricate Ductwork
...........................

2
2

Provide

................................

6

................................

6

Clearances

Rig and Place Unit

Inspection
.....................................
Use of Rigging Bracket ...........................
Connect Condensate Drain ..........................
Install Flue Hood

6
6
8

................................

8-9

Install Gas Piping
.................................
Install Duct Connections
............................

9
9

Configuring
Units for Downflow
(Vertical)
Discharge
..................................
Install Electrical Connections
.......................
High- Voltage Connections
.......................
Special Procedures
for 208-V Operation .............
Control Voltage Connections
......................
Heat Anticipator Setting
.........................
Transformer
Protection
..........................
PRE-START-UP
..................................
START-UP

AND TROUBLESHOOTING

...........

Check for Refrigerant Leaks .....................
Start-Up Heating & Make Adjustments
...............
Check Heating Control
..........................
Check Gas Input ...............................
Adjust Gas Input ............................
Check Burner Flame ............................
Airflow

and Temperature

9-10
11
11
11
11
12
12
12
12-22
12-13
13
13

Rise .....................

14
14
18

Rollout

18

Switch

................................
...............
...............

Checking & Adjusting Refrigerant Charge
...........
Indoor Airflow and Airflow Adjustments
............
Cooling Sequence of Operation ....................
MAINTENANCE
...............................

18
18
18
19
19
24-26

Air Filter .......................................
Indoor Blower and Motor ..........................

24
24

Flue Gas Passageways

25

.............................

Induced Draft (Combustion
Air) Blower
Limit Switch ....................................

...............

24
24

Burner Ignition
..................................
Main Burners
...................................
Outdoor
Outdoor
Electrical

25
25

Coil, Indoor Coil, & Condensate
Fan ....................................
Controls

and Wiring

Drain Pan

.....

...................

25
26
26-27

Refrigerant
Circuit ................................
Indoor Airflow
..................................

27
27

Metering Devices-AccuRater
_" Piston ................
Liquid Line Strainer
............................
TROUBLESHOOTING
.............................

27
27
27

START-UP

27

CHECKLIST

13
13-14
14

Heating Sequence of Operation
....................
Limit Switches
................................
Start-Up Cooling & Make Adjustments
Checking Cooling Control Operation

A06079

Fig. 1 - Unit PY3P
(Low NOx Model Available)

...........................

SAFETY

CONSIDERATIONS

Installation and servicing of this equipment can be hazardous due to
mechanical and electrical components.
Only trained and qualified
personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance
functions such
as cleaning and replacing air filters. All other operations must be
performed
equipment,

by trained service personnel.
When working on this
observe precautions
in the literature, on tags, and on

labels attached
to or shipped
precautions
that may apply.
Follow

all safety

codes.

with

Installation

local and national building
clothing, and work gloves.

the

unit

and

other

safety

must be in compliance

with

codes. Wear safety glasses, protective
Have fire extinguisher
available. Read

these instructions thoroughly
and follow all warnings
included in literature and attached to the unit.

or cautions

Recognize
safety
information.
Thisisthesafety-alert
symbol
'_'_.

Step 2--Provide

When you see this symbol on the unit and in instructions

For hurricane

or manuals,

be alert to the potential for personal injury. Understand
these signal
words: DANGER,
WARNING,
and CAUTION.
These words are

(Professional
ROOF

Unit Support
tie downs,

Engineering)

contact

distributor

Certificate

for details

and PE

if required.

CURB

used with the safety-alert
symbol. DANGER
identifies the most serious hazards which will result in severe personal injury or death.

Install accessory

WARNING signifies hazards which could result in personal injury
or death. CAUTION
is used to identify unsafe practices which may

with curb (See Fig. 5). Install insulation, cant strips,
flashing. Ductwork must be attached to curb.

result in minor personal injury or product and property damage.
NOTE is used to highlight
suggestions
which will result in enhanced installation, reliability, or operation.

IMPORTANT:

roof curb in accordance

The gasketing

with instructions

applied

and

of the unit to the roof curb is critical

for a water tight seal. Install gasketing
roof curb. Improperly

shipped

roofing,

material

gasketing

supplied

with the

also can result in air leaks

and poor unit performance.
Curb should be level to within
ELECTRICAL

SHOCK

to function
instructions

HAZARD

Failure to follow this warning
or death.

could result in personal

injury

SLAB

Failure to follow this warning
or unit damage.

SHOCK
HAZARD

installation

pad that is a minimum

of 4

in. thick with 2 in. above grade (See Fig. 2). The slab should extend
approximately
2 in. beyond the casing on all 4 sides of the unit. Do
not secure

ELECTRICAL
POISONING

for unit drain

MOUNT

Place the unit on a solid, level concrete

Before installing or servicing system, always turn off main
power to system.
There may be more than one disconnect
switch. Turn off accessory heater power switch if applicable.

FIRE,
EXPLOSION,
CARBON
MONOXIDE

1/4 in. This is necessary

properly.
Refer to accessory
roof curb
for additional information
as required.

the unit to the slab except when required

by local codes.

AND

could result in personal

injury

A
qualified
installer
or
agency
must
use
only
factory-authorized
kits or accessories
when modifying
this
product.
INTRODUCTION

L

EVAR COIL

The PY3P unit (see Fig. 1) is a fully self-contained,
combination
Category I gas heating/electric
cooling unit designed for outdoor
installation
(See Fig. 3 and 4 for unit dimensions).
All unit sizes
have return and discharge
openings
for both horizontal
and
downflow
configurations,
and are factory
shipped
with all
downflow
a rooftop,

duct openings covered. Units may be installed either on
a cement slab, or directly on the ground, if local codes

COND

C99096

Fig. 2 - Slab Mounting
GROUND

The unit may be installed either on a slab or placed directly on the
ground, if local codes permit. Place the unit on level ground
prepared

Models with an N in the thirteenth position of the model number are
dedicated
Low NOx units designed
for California
installations.

Step 3--Field

These models meet the California
maximum
oxides of nitrogen
(NOx) emissions requirements
of 40 nanograms/joule
or less as
shipped from the factory and must be installed in California
Air

discharge units. Do not connect
applications,
unit is provided

NOTE:
Low
installations.

NOx

requirements

regions

only

to

in North

natural

gas

Step 1--Check

AND INSTALLATION

Equipment

UNIT

The unit model number and serial number are stamped on the unit
information
plate. Check this information
against shipping papers.
INSPECT

Secure

with gravel for condensate

SHIPMENT

Inspect for shipping damage while unit is still on shipping pallet. If
unit appears to be damaged or is torn loose from its anchorage, have
it examined by transportation
inspectors before removal. Forward
claim papers directly to transportation
company. Manufacturer
is
not responsible
for any damage incurred in transit. Check all items
against shipping
list. Immediately
notify the nearest equipment
distribution
office if any item is missing. To prevent loss or damage,
leave all parts in original packages until installation.

Fabricate

all ducts

discharge.

Ductwork

to roof

curb

and building

structure

on vertical

ductwork to unit. For horizontal
with flanges
on the horizontal

openings. All ductwork
should be secured to the flanges. Insulate
and weatherproof
all external ductwork, joints, and roof openings
with counter flashing and mastic in accordance
with applicable
codes.
Ducts passing

RECEIVING

IDENTIFY

apply

other

Details

MOUNT

permit (See Fig. 5 for roof curb dimensions).

Quality Management
Districts
or any
America where a Low NOx rule exists.

/

COIL

and covered

through

an unconditioned

space must be insulated

with a vapor barrier.

If a plenum return is used on a vertical
ducted through the roof deck to comply

unit, the return should be
with applicable fire codes.

A minimum
clearance is not required around
return-air
static shall not exceed -.25 in. wc.

duGwork.

Cabinet

810CKOFF

PANE

ON

018

254

0

[10

00]

_5461

254
121

0

gOi

01i1¥_
k

\
\

11600i

COND

[4 63]

88_
[g 4_J

TOP ViEW
[9 83]

[21

67]

[9 83}

REAR ViEW
REQUIRED

CLEARANCE

TO CO_,rBUSTIBLE

MATL

TOP OF UNIT ...................................................................................
DUCT SIDE OF UNIT .........................................................................
SiDE OPPOSITE
DUCTS
................................................................
BOTTOM
OF UNIT .............................................................................
ELECTRIC
HEAT PANEL .................................................................

REQUIRED
INCHES
_4.00
2.00
14.00
0.50
36.00

[mm]
[355.6]
[50.8]
[355.6]
[12_7]
[914.4]

CLEARANCE

FOR OPERATION

AN D SERVICING
INCHES
36.00
36,00

EVAR COIL ACCESS
SIDE ............................................................
POWER
ENTRY SIDE ....................................................................
(EXCEPT
FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................
SIDE OPPOSITE
DUCTS
..............................................................
DUCT PANEL .................................................................................

48.00
36.00
:12.00

[mm]
[914.0]
[914.0]
[1219.2]
[914.0]
[304.8]

*

NEC. REQUIRED CLEARANCES.
INCHES
BETWEEN UNITS, POWER ENTRY SIDE .................................... 42.00
UNiT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 42.00

[mm]
[1066.8]
[914,0]

*MINIMUM DISTANCES: IF UNIT IS PLACED LESSTHAN 12.00 [304.8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.

[1066.8]

LEGEND
CG - Center or Gravity
COND - Condensor
EVAP - Evaporator
NEC - National Electrical Code
REQ'D - Required
NOTE: Dimensions are in in, [rnm]

/98
[31

............................

1193 9
[47 00]

44J

116 3
[4 58]

23 0
[0 9i]

\

??

2

[0

88]

DIA

CONTROL

ENTRY

1230
[484]

}90

[0

_5]

NI']

I
i

x 22 0 _P

[I

68]
FLUE

I¢00D

46

8

[I

84J

52

8

12
122
14

LEFT SIDE ViEW

[O ',O] NP
GAS ENIRY
50
[0 20

_

08]
2
81]

FRONT ViEW

RIGHT SiDE ViEW
A06083

UNIT

ELECTRICAL
CHARACTERISTICS

PY3P024

208/230-1-60

CENTER

UNIT HEIGHT
IN. [MM]

UNIT WEIGHT

X

OF GRAVITY
IN. [MM]
Y

Z

Ib

kg

446

202.3

39.02 [991]

20.0 [508]

19.3 [490]

17.6 [447]

PY3P030

208/230-1-60,

208/230-3-60

451

204.6

41.02 [1042]

20.0 [508]

14.0 [356]

13.0 [330]

PY3P036

208/230-1-60,
208/230-3-60,
460-3-60

459

206.2

41.02 [1042]

20.0 [508]

14.0 [356]

13.0 [330]

Fig. 3 - PY3P024-036

Unit Dimensions
3

556 8
[;401]

]

555
[;4

8
01]

i

RETDRN

SUPPLY

4066

&00
[3 i7]

RETURN
DUG1

4020
[i583]

I

I

I1_ 7
14_60/

J
i i

883
[3

I

L30,2-

48]

!/35
[6 83]

v

.......
i...............
7---i
..............

[!3

83]

_341

3

[13

_301

2

67]

[!3

TOP ViEW

83]

REAR VmEW
REQUIRED CLEARANCE TO COMBUSTIBLE MATE

REQUIRED CLEARANCE FOR OPERATION AND SERVICING
INCHES
14.00
2.00
14.00
0,50
36.00

TOP OF UNIT ...................................................................................
DUCT SIDE OF UNIT .........................................................................
SIDE OPPOSITE DUCTS ................................................................
BOTTOM OF UNIT .............................................................................
ELECTRIC HEAT PANEL .................................................................

[mini
[355.6]
[50,8]
[355.6]
[12.7]
[914.4]

iNCHES [mini
36.00 [914.0]
86.00 [914.0]

EVAR COIL ACCESS SIDE ............................................................
POWER ENTRY SIDE ....................................................................
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .....................................................................................
SIDE OPPOSITE DUCTS ..............................................................
DUCT PANEL .................................................................................

48.00 [1219.2]
36.00 [914.0]
12.00 [304.8] *

NEC. REQUIRED CLEARANCES.
INCHES
BETWEEN UNITS, POWER ENTRY SIDE ....................................
42.00
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 42,00

*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE
MAYBE COMPROMISE,

[mini
[1066.8]
[914.0]
[1066.8]

LEGEND
CG- Centerof Gravity
COND- Condensor
EVAP- Evaporator
NEC- NationalElectricalCode
REO'D- Required
1959
[47

i0906
_4294]
FIELD

ENTRf_

250

SER¸¸/ICE POI_I¸

_

I
Y

'_

½

7-

i

l

"

........

POWER ENTRY

1286 [i 3

'
I

"

i

i

4h2

i'l
.i],l

I

DA K 0

!23 0
484]

i

8

NOTE:Dimensionsare in in. [mm]

1!04
[4
54]

,

[091]

=_e_

_
00]

x

/

1

i

\
_RESSOR
x 22

0 10 671

8P

_

....

329

gOr%R

\

GA_ SECTON

0

[44

_;0_

12263
[48 28]

i2

i [0

50_

,'_

!/ P T

GAS ENTRY

52 8
[208]

[1205]

,,_3,

i

5 0
[0 20]

1424
[5 61]

223

FRONTVIEW

LEFT SIDE VIEW

RIGHT SiDE VIEW
A06084

UNIT

UNIT WEIGHT

ELECTRICAL
CHARACTERISTICS

CENTER

UNIT HEIGHT
IN.[MM]

OF GRAVITY
IN. [MM]
Y

Ib

kg

"A"

X

460-3-60

588

268.7

46.98 [1193]

21.0 [533]

20.5 [520]

17.1 [434]

208/230-3-60,

480-3-60

598

270.3

46.98 [1193]

21.0 [533]

20.0 [508]

17.4 [442]

208/230-3-60,

480-3-60

804

274.0

46.98 [1193]

21.0 [533]

20.0 [508]

17.6 [447]

PY3PO42

208/230-1-60,

2081230-3-60,

PY3PO48

208/230-1-60,

PY3PO6O

208/230-1-60,

Fig. 4 - PY3P042-060

Unit Dimensions

Z

Roof

Curb

for

Small

Cabinet

Roof

Curb for Large

Cabinet

Note A: When unit mounting screw is used,
retainer bracket must also be used,

Note A: When unit mounting screw is used,
retainer bracket must also be used,

E

R/A

S/A

A

_Gasket

\
\

around
duct

\

_

\

/

\

insulated
deck pan

Support

Gasket
outer

/2

around
edge

\
\

Long
Support

\\,\

A05308
UNIT

ODS CATALOG
NUMBER

A
IN. (MM)

B
IN. (MM)

CPRFCURB008A00

8 (203)

11 (279)

16-1/2

(419)

28-3/4

(730)

30-3/8

(771)

44-5/16

(1126)

45-15/16

(1167)

CPRFCURB00FA00

14 (356)

11 (279)

16-1/2

(419)

28-3/4

(730)

30-3/8

(771)

44-5/16

(1126)

45-15/16

(1167)

CPRFCURB008A00

8 (203)

16-3/16

(411)

17-3/8

(441)

40-1/4

(1022)

41-15/16

(1065)

44-7/16

(1129)

46 - 1/16 (1169)

CPRFCURB009A00

14 (356)

16-3/16

(411)

17-3/8

(441)

40-1/4

(1022)

41-15/16

(1065)

44-7/16

(1129)

46-1/16

SIZE

PY3P024-036
PY3P042-060

D
IN. (MM)

C
IN. (MM)

E
IN. (MM)

F
IN. (MM)

G
IN. (MM)

(1169)

NOTES:
[.

Roof

curb

must

be set up for unit

being

installed.

2. Seat strip must be applied, as required, to unit being installed.
3. Dimensions are in inches.
4. Dimension in ( )are in millimeters.
5. Roof curb is made of 16 gauge steel.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Inadated panels: I in. thick fiberglass 1 lb. density.
S. When unit mounting screw is used (see Note A). a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane
conditions. This bracket is available through Micrometl.
Fig.

5 - Roof

Curb

Dimensions

or seismic

Step 4--Provide
The required

Clearances

minimum

operating

and service clearances

are shown

in Fig. 3 and 4. Adequate combustion,
ventilation and condenser air
must be provided
in accordance
with section
5.3. Air for
Combustion
and Ventilation,
of the National Fuel Gas Code ANSI
(American
provisions

National
Standards
Institute)
Z223.1
or applicable
of local building code. In Canada, follow sections 7.2,

7.3, or 7.4 or Can/CGA.
(Canadian
Gas Association)
Installation
Codes or applicable provisions of local building
IMPORTANT:

Do not restrict outdoor

either the outdoor-air
to compressor

An air restriction

at

may be detrimental

DAMAGE

HAZARD

Failure to follow
this warning
injury/death
or property damage.

could

result

in personal

Rigging brackets
for one unit use only. When removing
unit at the end of its useful life. use a new set of brackets.
USE OF RIGGING
Field Installation

a

BRACKET

of Ri_in_

Bracket

(if not already

installed)

life.
and

1. Remove unit from shipping carton. Leave top shipping skid
on the unit for use as a spreader bar to prevent the rigging

discharges it through the top grille. Be sure that the fan discharge
does not recirculate to the condenser coil. Do not locate the unit in
either a corner or under an overhead obstruction.
The minimum

straps from damaging the unit. If the skid is not available, use
a spreader bar of sufficient length to protect the unit from

The

n

airflow.

inlet or the fan discharge

B149
code.

PROPERTY

condenser

fan

pulls

air

a partial

through

overhang

the condenser

clearance

under

(such

overhang)
extension

is 48-in. above the unit top. The maximum
of a partial overhang must not exceed 48-in.

coil

as a normal

house

horizontal

Do not place the unit where water, ice, or snow from an overhang

damage.
2. Remove

4 screws in unit corner posts.

3. Attach each of the 4 metal rigging brackets under the panel
rain lip (See Fig. 6). Use the screws removed in step 2 above
to secure the brackets to the unit.

or roof will damage or flood the unit. Do not install the unit on
carpeting
or other combustible
materials.
Slab-mounted
units
should be at least 4 in. above the highest expected water and runoff
levels. Do not use unit if it has been under water.
Step 5--Rig

and Place

PROPERTY

Unit

Rigging

and handling

of this equipment

reasons
etc.).

due to the installation

location

can be hazardous
(roofs,

structures,

working

with

this equipment,

and ground

observe

support

to follow

injury/death

precautions

Training for operators of the lifting equipment
not be limited to. the following:
1. Application

Follow

all applicable

safety

PROPERTY

include,

but

of the

codes.

Wear safety

shoes

and work

installed on@ on Small Packaged Products.
used to rig/lift a Small Packaged
Product
elevated structures.

designed

to be

This bracket is to be
onto roofs or other

Prior to initial use, and at monthly intervals, all rigging brackets and
straps should be visually inspected
for any damage, evidence of
wear. structural deformation,
or cracks. Particular attention should
be paid to excessive

wear at hoist hooking

points and load support

areas. Brackets or straps showing any kind of wear in these areas
nmst not be used and should be discarded.

UNIT

FALLING

HAZARD

Failure to follow this warning
or death.
Never stand beneath

rigged

could result in personal

units or lift over people.

DAMAGE

lip to provide

HAZARD
could

result

in personal

be

a

injury

of Unit

1. Bend top of brackets

2. Attach
and

rain

When straps are taut, the clevis should
of 36 inches above the unit top cover.

Ri_,_in_/Liftin_

INSPECTION
is engineered

the

Do not strip screws when re-securing
the unit. If a screw is
stripped, replace the stripped one with a larger diameter screw

the corner

bracket

in personal

of the lifting

gloves.

lifting/rigging

be under

Failure
to follow
this warning
injury/death or property damage.

(included).
minimum

or precaution.

3. Condition of the load as it relates to operation
kit, such as balance, temperature,
etc.

result

and

sizes or kinds of loads.

in any special operation

MUST

could

damage.

in the

of the lifter to the load, and adjustment

lifts to adapt to various
2. Instruction

should

this warning

or property

bracket
lifting.

HAZARD

staff

literature, on tags, stickers, and labels attached to the equipment,
any other safety precautions
that might apply.

The

Failure

Rigging
adequate

Only trained, qualified crane operators
should handle and install this equipment.
When

elevated

for many

DAMAGE

opposite

down approximately

30 degrees from

posts.
straps

of equal

length

to the rigging

brackets

at

ends of the unit. Be sure straps are rated to hold the

weight of the unit (See Fig. 6).
3. Attach a clevis of sufficient strength in the middle of the
straps. Adjust the clevis location to ensure unit is lifted level
with the ground.
4. After unit is securely
corner posts
screws.

screws,

After the unit is placed
the top crating.

in place detach rigging
and rigging

brackets

on the roof curb or mounting

straps. Remove
then

reinstall

pad, remove

UNIT SIZE

Table 1---PhysicalData
024060
030040

024040

- Unit PY3P
030060

NOMINAL CAPACITY (ton)

2

2

2-1/2

2-1/2

OPERATING WEIGHT (lb.)

446

446

451

451

036090

042090

3

3-1/2

3-1/2

459

459

588

588

7.2

7.2

7.8

7.8

1

REFRIGERANT (R-22)
Quantity (lb.)
REFRIGERANT METERING DEVICE
ORIFICE ID (IN.)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
CONDENSER FAN
Nominal Cfm
Diameter (in,)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows_.Fins/in.
Face Area (sq ft)
INDOOR BLOWER

5.9

.070

.070

.080

.080

.084

.084

2,..21
10.2

2._21
10.2

2. _2
11.9

2..,21
11.9

2_.21
13.6

2,.,21
13.6

2_.21
19.4

2...21
19.4

2200
22

2200
22

2800
22

2800
22

3000
22

3000
22

3500
22

3500
22

1/8 (825)

1/8 (825)

1/8 (825)

1/8 (825)

1/8 (825)

1/8 (825)

1/8 (825)

1/8 (825)

3...17
3.7

3.,,17
3.7

3.,.17
3.7

3..,17
3.7

4.,.17
3.7

4..,17
3.7

3...17
4.7

3...17
4.7

800

800

1000

1000

1200

1200

1400

1400

10x10

10x10

10x10

10x10

10x10

10x10

11x10

11x10

1/3 (1050)

1/3 (1050)

1/3 (1050)

1/3 (1050)

1/2 (1000)

1/2 (1000)

1/2 (1075)

1/2 (1075)

2,..44
2...50

2., ,38
2..,46

2,, .44
2.,.50

2.. ,38
2..A6

2., .38
2...46

3,. ,38
3..A6

2., .38
2...46

2,..38
2...46

20x24x1

20x24x1

20x24x1

20x24x1

20x24x1

24x36x1

24x36x1

20x24x1

Table

WEIGHT

6.0

.065

UNIT SiZE
CAPACITY

6.0

.065

Size (in,)
Motor HP (RPM)
FURNACE SECTION*
Burner Orifice No. (Qty..,Drill Size)
Natural Gas
Propane Gas
RETURN-AIR FILTERS (in.)f
Throwaway

5.9

AccuRater

Nominal Airflow (Cfm)

OPERATING

042060

3

Scrofi

COMPRESSORS
Quantity

NOMINAL

036060

1--Physical

Data

('on't

- Unit

PY3P

048090

048115

048130

060090

060115

(ton)

4

4

4

5

5

080130
5

(lb.)

598

596

596

604

604

604

12.0

12,0

12.0

Scroll

COMPRESSORS
Quantity

1

REFRIGERANT
Quantity (lb.)

(R-410A)

REFRIGERANT

METERING

12,4

12.4

12.4

.088

.088

.088

.098

.098

0.098

3500
22

3500
22

3500
22

4200
22

4200
22

4200
22

1/4 (1100)

1/4 (1100)

1/4 (1100)

1/4 (1100)

1/4 (1100)

1/4 (1100)

Face Area (sq ft)

2,.,21
19.4

2.,.21
19.4

2.,.21
19.4

2,.,21
19.4

2,.,21
19.4

2.,.21
19.4

EVAPORATOR
COIL
Rows,.,Fins/in.
Face Area (sq ft)

4..,17
5.7

4.,.17
5.7

4.,.17
5.7

4..,17
5.7

4..,17
5.7

4.,.17
5.7

ORIFICE

DEVIOE

AccuRater

ID (IN,)

CONDENSER
FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
CONDENSER
COIL
Rows,.,Fins/in.

INDOOR

BLOWER

Max

1600

1600

1600

2000

2000

2000

Size (In.)

11X10

11X10

11x10

11x10

11X10

11X10

1/2 (1075)

1/2 (1075)

1/2 (1075)

1.0 (1040)

1.0 (1040)

1.0 (1040)

3,.,38
3...46

3.-33
3...42

3._31
3...41

3,.,38
3...46

3,.,33
3...42

3.-31
3...41

24X36X1

24X36X1

24x36x1

24x36x1

24X36X1

24X36X1

Motor HP (RPM)
FURNACE
SECTION*
Burner Orifice No, (Qty,_DriH
Natural Gas
Propane Gas

Size}

RETURN-AIR
FILTERS (in,)f
Throwaway
Based on altitude of 0 to 8000 ft.
T

Required

mimee

filter

for throwaway

sizes

shown
type

are based

or 450 ft/mimee

on the larger
for high

of the ARI
capacity

(Air

type.

(bnditioning

Air filter

pressure

and Refrigeration
drop

for non

Instielte)
standard

rated
filters

cooling
must

airflow

not exceed

or the heating
0.08

in. wc.

airflow

velocity

of 300 fii

I!

MUNIMUMHEUGHT:36'

Y

DETAIL

A

UNIT HEUGHT

x

Z

SEE DETAIL

3
C00070

I!

A06361

CORNER WEIGHTS (SMALL CABINET)

CORNER WEIGHTS

(LARGE CABINET)

Unit

024

030

036

Unit

042

048

060

Total Weight

446

451

459

Total Weight

588

596

604

Corner Weight 1

63

69

66

Corner Weight 1

96

104

97

Corner Weight 2

82

81

87

Corner Weight 2

95

93

102

Corner Weight 3

123

121

122

Corner Weight 3

162

161

163

Corner Weight 4

178

180

184

Corner Weight 4

235

238

242

Rigging Weight

465

470

478

Rigging Weight

610

618

626

Shipping Weight

500

505

513

Shipping Weight

650

658

666

Fig. 6 - PY3P Unit Corner

Step 6--Connect

Condensate
installing

Weights

Drain

condensate

When

comply

with local codes and restrictions.

drain connection

be sure to

Model PY3P disposes of condensate
water through a 3/4 in. NPT
fitting which exits through the base on the evaporator
coil access
side. See Fig. 3 & 4 for location.
water

can be drained

directly

onto the roof in rooftop

installations
(where permitted)
or onto a gravel apron in ground
level installations.
Install a field-supplied
2-in. condensate
trap at
the end of condensate
connection to ensure proper drainage. Make
sure that the outlet of the trap is at least 1 in. lower than the drain-pan
condensate
connection to prevent the pan from overflowing
(See
Fig. 7). Prime the trap with water. When using a gravel apron, make
sure it slopes away from the unit.
Connect

a drain tube using a mininmm

and Suggested

Step 7--Install

NOTE:

Condensate

(in Pounds)

of 3/4-in.

Rigging

Flue Hood

The flue assembly

is secured

and shipped

Remove

duct cover to locate the assembly

NOTE:

Dedicated

low

California Air Quality
rule exists.
These

models

meet

NOx

the California

(NOx) emissions
requirements
shipped from the factory.
NOTE:
Low
installations.

models

Management

NOx

in the return

MUST

Districts

be

where

maximum

installed

apply

oxides

only

in

a Low NOx

of nitrogen

of 40 nanograms/joule

requirements

air duct.

(See Fig. 9 and 10).

to

or less as

natural

gas

PVC or 3/4-in.

copper pipe (all field-supplied)
at the outlet end of the 2-in. trap.
Do not undersize the tube. Pitch the drain tube downward at a slope
of at least l-in. for every 10 ft of horizontal run. Be sure to check
the drain tube for leaks.

CARBON

MONOXIDE

POISONING

Failure to follow this warning
or death.

HAZARD

could result in personal

injury

The venting system is designed to ensure proper venting. The
flue hood assembly mustbe installed as indicted in this section
of the unit installation instructions.
1

In

Install the flue hood

as follows:

1. This installation
2" min.

with the National

must conform

with local building

Fuel Gas (:ode (NFGC),

codes and

ANSI Z223.1 (in

Canada.
CAN/CGA
B149.1.
and B149.2)
or NFPA
(National Fire Protection Association)
latest revision. Refer
to Provincial and local plumbing or wastewater
codes and
C00009

Fig. 7 - Condensate

Trap

other applicable

local codes.

2. Remove flue hood from shipping location (inside the return
section of the blower compartment-see
Fig. 9 & 10). Re-

move
thereturn
ductcover
tolocate
thefluehood.
Place
flue
hoodassembly
overfluepanel.
Orient
screw
holes
influe
hood
withholes
inthefluepanel.
3.Secure
fluehood
tofluepanel
byinserting
asingle
screw
on
therightside
andtheleftside
ofthehood.
Step8--Install Gas Piping
The

gas

supply

pipe

enters

provided. The gas connection
gas inlet on the gas valve.
Install

a gas supply

access

hole

to the unit is made to the 1/2-in.

the

unit

through

the

FPT

line that runs to the heating

section.

IN

OUT_

Refer to

_/

Table 2 and the NFGC for gas pipe sizing. Do not use cast-iron pipe.
It is recommended
that a black iron pipe is used. Check the local
utility for recommendations
concerning
existing lines. Size gas
supply piping for 0.5 in. wc maximum
pressure drop. Never use
pipe smaller than the 1/2-in.

FPT gas inlet on the unit gas valve.

CAP

C99020

NOTE:
piping

Fig. 8 - Sediment Trap
test the gas supply system

Pressure
is connected

disconnected

to the gas valve.

from the gas valve

after the gas supply

The supply

during

piping

the testing

must be

of the piping

For natural gas applications,
the gas pressure at unit gas connection
must not be less than 4.0 in. wc or greater than 13 in. wc while the

systems when test pressure is in excess of 0.5 psig. Pressure test the
gas supply piping system at pressures equal to or less than 0.5 psig.

unit is operating. For propane applications,
the gas pressure must
not be less than 7.0 in. wc or greater than 13 in. wc at the unit
connection.

The unit heating

A 1/8-in.
connection,
supply

NPT
must

plugged
tapping,
accessible
for
be installed immediately
upstream

connection

(in Canada,

CAN/CGA

B149.1).

the state of Massachusetts:

1. Gas supply

connections

MUST be performed

plumber or gas fitter.
2. When flexible connectors

by a licensed

are used. the maximum

shall not exceed 36 inches (915 mm).
3. When lever handle type manual equipment

shutoff

length
valves

are used. they shall be T-handle
valves.
4. The use of copper tubing for gas piping is NOT approved
the state of Massachusetts.
In the absence of local building
pertinent recommendations:

codes,

adhere

by

for every 15 ft of length to prevent traps. Grade all horizontal
runs downward
to risers. Use risers to connect to heating
section and to meter.
2. Protect all segments of piping system against physical and
thermal damage. Support all piping with appropriate straps,
hangers, etc. Use a minimum of one hanger every 6 ft. For
pipe sizes larger than 1/2 in., follow recommendations
of
national codes.
3. Apply joint compound
(pipe dope) sparingly and only to
male threads of joint when making pipe connections.
Use
only pipe dope that is resistant
to action of liquefied
gases as specified

Never use Teflon

by local and/or national

codes.

tape.

4. Install sediment trap in riser leading to heating section (See
Fig. 8). This drip leg functions
as a trap for dirt and
condensate.
5. Install an accessible,

external,

pipe within

manual

6 ft of heating

main shutoff

valve in

valve

and slightly

FIRE

OR EXPLOSION

Failure to follow this warning
death and/or property damage.
-Connect

gas pipe to unit

damaging

gas controls.

plumbing

could result in personal

using

a backup

wrench

injury,
to avoid

-Never purge a gas line into a combustion
chamber. Never test
for gas leaks with an open flame. Use a commercially
available
soap solution made specifically
for the detection of leaks to
check all connections.
-Use proper
manifold.

length

of pipe to avoid

-If a flexible

connector

stress

on gas control

is required

or allowed

by authority

having jurisdiction, black iron pipe shall be installed at furnace
gas valve and extend a minimum of 2 in. outside furnace casing.
-If codes allow a flexible
connector,
always use a new
connector,
do not use a connector
which has previously
serviced another gas appliance.
8. Check

for

gas

factory-installed

leaks

at

the

field-installed

gas lines after all piping

Step 9--Install

and

connections

been completed.
Use soap-and-water
solution
specified by local codes and/or regulations).

have

(or method

Duct Connections

The unit has duct flanges on the supply-

and return-air

openings

in accordance

and gas codes before

with local

connecting

and

piping

on

the side and bottom of the unit. For downshot
applications, the
ductwork connects to the roof curb (See Fig. 3 and 4 for connection
sizes and locations).
CONFIGURING
DISCHARGE

ELECTRICAL
test all gas piping

HAZARD

UNITS

FOR

DOWNFLOW

(VERTICAL)

between
shut-off

valve.

national
to unit.

shutoff

section.

6. Install ground-joint
union close to heating section
unit manual shutoff and external manual main

7. Pressure

manual

union.

to the following

1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in.

gas supply

main

the ground-joint

to the gas valve.

NFPA latest edition

petroleum

opening

section must be isolated from the gas piping system

the external

test gauge
of the gas

When installing the gas supply line, observe local codes pertaining
to gas pipe installations.
Refer to the NFGC ANSI Z223.1-2005

NOTE:In

by closing

SHOCK

HAZARD

Failure to follow this warning
or death.

could result in personal

injury

Before installing or servicing system, always turn off main
power to system.
There may be more than one disconnect
switch.

1

!!

Table 2--Maximum

Gas Flow ( apaclty*

NOMINAL
tRON PIPE
SIZE (iN.)

INTERNAL
D_AMETER
(iN.)

10

20

30

40

50

60

70

80

90

100

125

150

1/2

_622

175

120

97

82

73

66

61

57

53

50

44

40

3/4
1

_824
1.049

360
680

250
465

200
375

170
320

151
285

138
260

125
240

118
220

1! 0
205

103
195

93
175

1-1/4

1.380

1400

950

770

600

580

530

490

460

430

400

1-1/2

1.610

2!00

1460

1180

990

900

810

750

690

650

620

Capacity

of pipe

tion Association
This

length

LENGTH OF P_PE (FT)t

in cu ft of gas per hr for gas presalre
NFPA

includes

number

horizontal

(metal)

3. Use a screwdriver

before

starting

duct covers

duct knockouts

and hammer

in, wc (based

on a 0.60

specific

gravity

gas).

72
135

360

325

300

280

550

500

460

430

Refer

to Table,

National

Fire Protec

any service

to access

vertical

in unit base.

to remove

is to be attached

on the unit base (iackstand
time.

PROPERTY

the panels

DAMAGE

to vertical

applications

in the

opening

flanges

only), do so at this

HAZARD

to follow this caution

may result in property

Collect ALL screws that were removed.
on rooftop

of 0,5

77
145

of the unit base (See Fig. 10).

4. If unit ductwork

Failure

drop

84
160

of fittings.

disconnects

(down flow) discharge

bottom

Pressure

200

54.
an ordinary

1. Open all electrical
work.
2. Remove

of 0.5 psig or tess.

175

as permanent

damage

damage.
DUCT

Do not leave screws

COVERS

REMOVED

to the roof may occur.

C99012

Fig. 10 - Vertical Duct Cover
5. It is recommended
perimeter

that

of the vertical

the base

return-air

insulation
opening

around

6. Cover both horizontal
covers. Ensure
7. After completing

duct openings

opening

the

be secured to the

base with aluminum
tape. Applicable
local codes
require aluminum tape to prevent exposed fiberglass.
with the provided

Adhere

may

perform

are

removing
2. Select

all safety checks

criteria

when

shipped

for

horizontal

and

size

ductwork,

grilles according

NFPA

and ventilating
90B;

and/or

systems.
local

codes

duct

sizing,

and

installation

(by

registers,

and

supply-air

to American

Refrigeration
and Air Conditioning
recommendations.

air conditioning

selecting,

duct covers).

return-air

NOTE: The design and installation
of the duct system must be in
accordance
with the standards
of the NFPA for installation
of

90A or residence-type,
ordinances.

following

the duct system:

1. Units
duct

and power up unit.

nonresidence-type

to the

installing

is air- and watertight.

unit conversion,

Removed

Society

Engineers

of Heating,
(ASHRAE)

3. Use flexible transition between rigid ductwork
and unit to
prevent transmission
of vibration.
The transition
may be

NFPA
and

screwed or bolted to duct flanges. Use suitable gaskets
sure weather-tight
and airtight seal.

to en-

4. All units must have field-supplied
filters or accessory
rack
installed
in the return-air
side
of the

filter
unit.

Recommended

sizes for filters are shown

in Table 1.

5. Size all ductwork
for maximum
required
airflow (either
heating or cooling) for unit being installed. Avoid abrupt
duct size increases or decreases or performance
may be
affected.
6. Adequately
insulate and weatherproof
all ductwork located
outdoors.
Insulate
ducts passing through unconditioned
space, and use vapor barrier in accordance with latest issue
of Sheet Metal and Air Conditioning
Association

(SMACNA)

Contractors

and Air Conditioning

National
Contractors

of America (ACCA)
minimum
installation
standards
for
heating and air conditioning
systems. Secure all ducts to
building
SUPPLY
DUCT
OPENING

RETURN
DUCT
OPENING

SHIPPING
LOCATION

7. Flash, weatherproof,
and vibration
isolate all openings
in
building structure in accordance
with local codes and good

A05143

Fig, 9 - Supply

and Return

structure.

building

Duct Opening

10

practices.

Step10--Install

Electrical

Connections

3. Locate the black and yellow wires connected
of the contactor.
4. Connect

field

compressor
ELECTRICAL

SHOCK

HAZARD

Failure to follow this warning
or death.

could result in personal

Three-phase

2. Connect

ground

Electrical

4. Connect

5. Connect

field

6. Connect

HAZARD

SPECIAL
Failure to follow this caution
being installed.
1. Make

all electrical

ANSI/NFPA
governing
connections
codes.

connections

Electrical

copper

field-supplied
electrical
NOT USE ALUMINUM
3. Be sure that high-voltage
voltage range indicated

for connections

disconnect
WIRE.

switch

and unit. DO

FOR 208-V

OPERATION

SHOCK

HAZARD
could result in personal

VOLTAGE

injury

CONNECTIONS

Do not use any type of power-stealing

Consult
voltage

problems

thermostat.

Unit control

may result.

Use no. 18 American Wire Gage (AWG) color-coded,
insulated
(35°C minimum)
wires to make the control voltage connections
between the thermostat and the unit. If the thermostat is located more
than 100 ft from the unit (as measured

wires.

wires), use no. 16 AWG color-coded,
wires.

5. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc.
HIGH-VOLTAGE

13 of the

field wire L3 to blue wire from compressor.

PROCEDURES

CONTROL

power to unit is within operating
on unit rating plate. On 3-phase

phase imbalance.

as high-voltage

11 of the

Before making any wiring changes, make sure the gas supply
is switched off first. Then switch off the power supply to the
unit and install lockout tag.

4. Insulate low-voltage
wires for highest voltage contained
within conduit when low-voltage
control wires are in same
conduit

wire on connection

contactor.

Failure to follow this warning
or death.

local

between

units, ensure phases are balanced within 2 percent.
local power company for correction
of improper
and/or

L1 to black

to the line side

field wire L2 to yellow wire on connection

ELECTRICAL

diagram.

conductor

connection.

with NEC

Code Part 1 and applicable

Refer to unit wiring
only

in accordance

lead to chassis ground

lead into the

to the unit

(latest edition) and local electrical codes
such
wiring.
In Canada,
all electrical
must be in accordance
with CSA standard

C22.1 Canadian

2. Use

may result in damage

23 of the

contactor.

compressor
DAMAGE

(L1, L2, L3) and ground

3. Locate the black and yellow wires connected
of the contactor.

compressor

COMPONENT

11 of the

units:

1. Run the high-voltage
control box.

compartment, or conduit approved for electrical ground when
installed in accordance with NEC, ANSI/NFPA
American
National
Standards
Institute/National
Fire
Protection

UNIT

wire on connection

contactor.

5. Connect field wire L2 to yellow wire on connection
compressor
contactor.

injury

The unit cabinet must have an uninterrupted,
unbroken
electrical ground. This ground may consist of an electrical
wire connected
to the unit ground screw in the control

Association
(latest edition) (in Canada. Canadian
Code CSA C22.1) and local electrical codes.

L1 to black

to the line side

CONNECTIONS

Standard

Connection

Remove

knockout

hole located

along
insulated

the control
(35°C

voltage

minimum)

in the flue panel adjacent

to the

control access panel (See Fig. 3 and 4). Remove the rubber grommet
from the installer's packet (included with unit) and install grommet
in the knockout
opening. Provide a drip loop before running wire

When routing power leads into unit, use only copper wire between
disconnect and unit. The high voltage leads should be in a conduit
until they enter the duct panel; conduit termination
at the duct panel

through

panel.

must be watertight.
The

unit

must

have

a

separate

electrical

service

with

a

field-supplied,
waterproof disconnect switch mounted at, or within
sight from, the unit. Refer to the unit rating plate, NEC and local
codes for maximum
fuse/circuit
breaker size and minimum circuit
amps (ampacity)

for wire sizing.

The field-supplied

disconnect

unit over the high-voltage
low-voltage
entry points

switch box may be mounted

-

-

-

-

-

LABEL)

_

-

-

-

on the
FIELD-SUPPLIED
FUSED DISCONNECT
GR

label and Fig. 11 for reference
follows

when
to

making

high

complete

the

ro[oLOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)

phase units:

1. Run the high-voltage
control box.
2. Connect

-

fc e-

CONTROLBOX

voltage
connections.
Proceed
as
high-voltage
connections
to the unit.
Single

F

POWER
LEADS
(SEE
UNIT
WIRING

inlet hole when the standard power and
are used (See Fig. 3 and 4 for acceptable

location).
See unit wiring

HIGH VOLTAGE

ground

(L1, L2) and ground

lead to chassis

Io-

l

1/

TAT

lead into the
SPLICE

ground

H dih 1/

BOX

connection.

A05144

Fig. 11 - High11

and Control-Voltage

Connections

Run the low-voltage

leads from the thermostat,

hole, and into unit low-voltage
Locate five 18-gage
connection

through

the inlet

a. Inspect

splice box.

wires leaving

control

leads can be identified

box. These low-voltage

c. Leak-test
electronic

side of control box). Route leads through hole in bottom of control
box and make low-voltage
connections
(See Fig. 11). Secure all cut
wires, so that they do not interfere with operation of unit.

heat anticipator

must be properly

adjusted

n

setting.

NOTE:

For thermostat

approximate

required

anticipator

setting.

adjustment

to the occupants

selection

purposes,
Failure

of the conditioned

utilization;

however,

to provide

a greater

the required
degree

TRANSFORMER

to make

a proper

operation,

energy
slightly

for a particular

leak is detected,
Leaks section.

see following

wires do not touch

f. Inspect
coil fins.
handling, carefully

Check

refrigerant

tubing

FIRE,

EXPLOSION

HAZARD
could result in personal

Do not purge gas supply into the combustion

type. It is set to withstand
condition.

injury,

chamber.

Do not

use a match or other open flame to check for gas leaks.
4. Verify the following

UP

ELECTRICAL

SHOCK

HAZARD

Failure to follow this warning
or death.

could result in personal

1. Follow

practices

recognized

NOTE:

conditions:

and wear

chamber,

3. Do

not

compressor

remove

terminal

compressor

cover

terminal

is in place
cover

and

until

electrical sources are disconnected
and tagged.
4. Relieve and recover all refrigerant from system

union.

attempt

to

repair

soldered

all

To remove

a component,

proceed as follows:
a. Shut off electrical
tag.

wear

protective

System

goggles

hnmediately

Never
upon

purge
detection

to purge until the

of gas odor, retighten

to elapse, then light unit.

b. Make

that

sure

fan hub

condenser-fan

blade

is

is positioned

correctly

with

the

correctly
blade

respect

to

(See Fig. 12).

d. Make sure that air filter(s)

is in place.

e. Make sure that condensate
to ensure proper drainage.

drain trap is filled with water

f. Make sure that all tools
have been removed.

and

the
joint

gas lines into a combustion

Allow 5 minutes

motor housing

while

refrigerant system is under pressure.
6. Do not use torch to remove any component.
contains oil and refrigerant under pressure.

and the supply line be allowed

c. Ensure

before

connection

that the ground

positioned in fan orifice. Top 1/3 of condenser-fan
should be within fan orifice venturi.

touching
or disturbing
anything
inside terminal
box if
refrigerant leak is suspected around compressor
terminals.
5. Never

the unit

with the gas valve

If the gas supply pipe was not purged before connecting

odor of gas is detected.

protective

goggles when checking or servicing refrigerant system.
2. Do not operate compressor
or provide any electric power
to unit unless
secured.

the following

unit, it will be full of air. It is recommended

injury

union be loosened,

safety

and

installation.

for the first time, perform
in the OFF position:
EXPLOSION,

Be

or sharp

a. Make sure gas line is free of air. Before lighting

FIRE,

for

If damaged
during
shipping
straighten fins with a fin comb.

Failure to follow this warning
death or property damage.

START-

as

sheet metal edges.

PROTECTION

PRE-

such
etc.

heat

space, and inefficient

The transformer is of the energy-limiting
a 30-sec. overload or shorted secondary

wires,

discomfort

setting may be changed

of comfort

e. Ensure

use 0.18 amp for the

will result in improper

damage,

d. Inspect all field- and factory-wiring
connections.
sure that connections
are completed
and tight.

to

ensure proper heating performance.
Set the heat anticipator, using
an ammeter between the W and R terminals to determine the exact
required

handling

all refrigerant
tubing
connections
using
leak detector,
or liquid-soap
solution.
If a

refrigerant
Refrigerant

SETTING

The room thermostat

and

lines, loose parts, disconnected

b. Inspect for oil at all refrigerant tubing connections
and on
unit base. Detecting oil generally indicates a refrigerant
leak.

by the colors red, green, yellow,

brown, and white (See Fig. 11). Ensure the leads are long enough
to be routed into the low-voltage
splice box (located below right

HEAT ANTICIPATOR

for shipping

broken

MOTOR

and miscellaneous

_

loose

parts

GRILLE

power to unit and install lockout

b. Relieve and reclaim all refrigerant
from system
using both high- and low-pressure
ports.
c. Cut component
connecting
tubing with tubing
cutter and remove component
d. Carefully
unsweat remaining
necessary.
flame.

Oil can ignite

from unit.
tubing stubs

when

exposed

when

1/8"

to torch

MAX

MOTOR

BETWEEN
AND

FAN

HUB

MOTOR

SHAFT
C99009

Fig. 12 - Fan Blade

Use the Start-Up
Checklist supplied at the end of this book and
proceed as follows to inspect and prepare the unit for initial start-up:

Clearance

START-UP
1. Remove

access panel.
Step 1--CHECK

2. Read and follow instructions on all DANGER, WARNING,
CAUTION.
and INFORMATION
labels attached to, or
shipped

Proceed

with unit.

3. Make the following

as follows

FOR

REFRIGERANT

to locate

and repair

LEAKS
a refrigerant

leak and to

charge the unit:
inspections:

1. Locate leak and make sure that refrigerant
has been relieved and reclaimed
from
low-pressure
12

ports.

system pressure
both high- and

CHECK
HEATING
CONTROL
Startandcheck
theunitforproper
heating
control
operation
as
follows
(see
furnace
lighting
instructions
located
inside
burner
or
blower
access
panel):
1.Place
roomthermostat
SYSTEM
switchin theHEAT
position
andthefanswitch
isplaced
inAUTO
position.
2.Settheheating
temperature
control
ofthethermostat
above
room
temperature.
3.Theinduced-draft
motor
willstart.
4.Afteracallforheating,
themain
burner
should
lightwithin
5 sec.
If theburners
donotlight,there
isa22-sec.
delay
before
another
5-sec.
try.Iftheburners
stilldonotlight,this
sequence
isrepeated.
If theburners
donotlightwithin15
minutes
fromtheinitialcallforheat,
there
isalockout.
To
reset
thecontrol,
break
the24-vpower
toW.
5.Theevaporator
fanwillturnon45sec.
after
theflame
has
been
established.
Theevaporator
fanwillturnoff45sec.
after
thethermostat
hasbeen
satisfied.
CHECK
GASINPUT
Check
gas
input
and
manifold
pressure
after
unitstart-up
(See
Table
3).If adjustment
isrequired
proceed
asfollows:
• Therated
gasinputs
shown
inTable
3areforaltitudes
fromsea
levelto2000
ftabove
sea
level.
These
inputs
are
based
onnatural
gas
withaheating
value
of1050
Btu/ft
3
at0.65specific
gravity,
orpropane
gaswithaheating
value
of2500
Btu/ft
3at1.5specific
gravity.
• Forelevations
above
2000
ft,reduce
input4%foreach
1000
ft above
sealevel.
Forexample
at2001ft.a12%
totalderate
isrequired.
• When
thegassupply
being
used
hasadifferent
heating
value
orspecific
gravity,
refer
tonational
andlocal
codes.
orcontact
yourdistributor
todetermine
therequired
orifice
size.

2.Repair
leak
following
accepted
practices.
NOTE:
Install
afilterdrierwhenever
thesystem
hasbeen
opened
forrepair.
3.Addasmall
charge
ofR-22refrigerant
vapor
tosystem
and
leak-test
unit.
4.Recover
refrigerant
fromrefrigerant
system
and
evacuate
to
500microns
ifnoadditional
leaks
arefound.
5.Charge
unitwithR-22refrigerant,
usinga volumetric
charging
cylinder
oraccurate
scale.
Refer
tounitrating
plate
forrequired
charge.
Besuretoaddextrarefrigerant
to
compensate
forinternal
volume
offilterdrier.
STEP
2--START-UP
HEATING
ANDMAKEADJUSTMENTS
Complete
therequired
procedures
givenin thePre-Start-Up
section
before
starting
theunit.Donotjumper
anysafety
devices
when
operating
theunit.Make
sure
thatburner
orifices
areproperly
aligned.
Unstable
operation
myoccur
when
theburner
orifices
in
themanifold
aremisaligned.
Follow
thelighting
instructions
ontheheating
section
operation
label
(located
inside
theburner
orblower
access
door)
tostart
the
heating
section.
NOTE:
Make
sure
thatgassupply
hasbeen
purged,
andthatallgas
piping
hasbeen
checked
forleaks.

/

UNIT

DAMAGE

HAZARD

Failure to follow this caution
component
life.

MANIFOLD

unit and/or

Do Not
redrill
an orifice.
Improper
drilling
(burrs,
out-of-round
holes, etc.) can cause excessive burner noise
and misdirection
of burner flame. If orifice hole appears
damaged or it is suspected to have been redrilled, check orifice
hole with a numbered drill bit of correct size.

PIPE PLUG
C99019

Fig. 13 - Burner

may result in reduced

Assembly
ADJUST

GAS INPUT

BURNER FLAME
The gas input to the unit is determined by measuring the gas flow
at the meter or by measuring the manifold pressure. Measuring the
gas flow at the meter is recommended
for natural gas units. The
manifold
pressure
propane gas units.
Measure

must

be measured

Gas Flow (Natural

to determine

the input

of

Gas Units)

Minor adjustment
to the gas flow can be made by changing the
manifold
pressure.
The manifold
pressure must be maintained
between 3.4 and 3.6 in. wc.
If larger adjustments
are required,
change main burner orifices
following the recommendations
of national and local codes.

IFOLD

NOTE:

All other appliances

off when gas flow is measured
099021

Fig. 14 - Monoport

Burner

13

that use the same meter must be turned
at the meter.

3--Heating

Table
HEATING BNPUT

Inputs

GAS SUPPLY PRESSURE (iN. WC)
Naturalt
Propane*t
Max
I'din

(BTUH)

NUMBER OF
ORIFICES

40,000

2

4.0

13.0

4.0

13.0

3.5

60,000

2

4.0

13.0

4.0

13.0

3.5

3.5

90,000
115,000

3
3

4.0
4.0

13.0

13.0

3.5

3A

13.0

4.0
4.0

13.0

3.5

3.7

130_000

3

4.0

13.0

4.0

13.0

3.5

3.5

Min

MANIFOLD
Max

PRESSURE

Naturalt

(IN. WC)

Propane*t
3.5

When a unit is converted to propane, different size orifices must be used. See separate, natural to propane conversion kit instructions.
j'Based on altit/des from sea level to 2000 ft above sea level. For altit/des above 2000 ft, reduce 111putrating 4 percellt lot each additioiml 1000 ft above sea level In Canada.
from 2000 ft above sea level to 4500 fl _bove sea level derate tl_e unit 10 percent,

Proceed

as follows:

Measure

1. Turn off gas supply

n

to unit.

2. Remove pipe plug on manifold
manometer. Turn on gas supply
3. Record number
revolution.

EXAMPLE:

(See Fig. 13) and connect
to unit.

in Step 3 into 3600

specified

Assume

3. 112.5 x 1 =112.5

of gas to

size of test dial

5. Adjust

pressure

gas

is 1 cu ft, one

With

Btuh, only a minor change

adjustment

screw on gas

screw to the correct

in Table

3. Turn

manifold

adjusting

screw

manifold pressure, or turn adjusting
to decrease manifold pressure.

cover screw.

BURNER

burner

FLAME

access

panel

removed,

observe

the

unit

heating

operation. Watch the burner flames to see if they are light blue and
soft in appearance,
and that the flames are approximately
the same

in the

as follows

to adjust

gas

adjustment

screw on gas

AIRFLOW

AND TEMPERATURE

The heating

section for each size unit is designed

heating operation
unit rating plate.
screw clockwise

to increase

within

may result.

the approved

Refer to Indoor
heating

for

on the

and Airflow

Adjustments

section

to adjust

OF OPERATION

and unit wiring label.)

On a call for heating,

injury

range.

Airflow

SEQUENCE

(See Fig. 15-17

HAZARD

pressure

and approved

range stamped

airflow when required.

HEATING

Unsafe operation of the unit may result if manifold
outside this range.

the temperature-rise

Table 8 shows the approved temperature rise range for each heating
input, and the air delivery cfm at various temperature
rises. The
heating operation airflow must produce a temperature
rise that falls

and 3.6 in. wc. Unsafe operation
of the unit may result if
manifold pressure is outside this range. Personal injury or

Failure to follow this warning could result in personal
or death and/or property damage.

within

RISE

gas

input, or turn regulator adjustment screw counterclockwise
to decrease input. Manifold pressure must be between 3.4

3. Replace

(See

for each burner. Propane will have blue flame (See Fig. 14). Refer
to the Maintenance
section for information
on burner removal.

and proceed

DAMAGE

manometer

7. Turn off gas to unit. Remove manometer
from pressure tap.
Replace pipe plug on gas valve, then turn on gas to unit.
Check for leaks.

Btuh input.

cover screw over regulator

AND UNIT

adjustment

as specified

6. Replace

value of the gas is 1050

input:

FIRE

regulator

clockwise to increase
screw counterclockwise

CHECK

adjustment

and connect

cover screw over regulator

pressure,

ft 3 of gas flow/hr.

If the desired gas input is 115.000
manifold pressure is required.

unit damage

gas unit:

3. Turn on gas to unit.

one revolution.

4. 112.5 x 1050 = 118,125

2. Turn regulator

to adjust gas input on a propane

pipe plug on manifold

4. Remove
valve.

2. 3600 + 32 = 112.5.

1. Remove
valve.

as follows

2. Remove

of

this value with

in Table 3 (Consult
the local
value of gas is not known).

that the

1. 32 sec. to complete

value

input in Btuh. Compare

input shown
if the heating

(number

of cubic feet (cu ft)

result of Step 5 by Btu heating

manifold

in Table 3.

Proceed

of test dial to obtain cubic feet (cu

revolution takes 32 sec., and the heating
Btu/ft3. Proceed as follows:

Observe

Units)

Fig. 13).

result of Step 4 by the number

obtain total measured
heating
supplier

(Propane

1. Turn off gas to unit.

shown for one revolution
ft) of gas flow per hour.
6. Multiply

Pressure

The main burner orifices on a propane gas unit are sized for the unit
rated input when the manifold pressure reading matches the level

of seconds for gas meter test dial to make one

4. Divide number of seconds
seconds in one hr).
5. Multiply

Manifold

terminal

W of the thermostat

is energized.

starting the induced- draft motor. When the hall-effect sensor on the
induced-draft
motor senses that it has reached the required speed.

is

the burner
integrated
energized

cover screw cap on gas valve.

satisfied

4. Turn off gas supply to unit. Remove
manometer
from
pressure tap and replace pipe plug on gas valve. Turn on gas
to unit and check for leaks.

indoor
delay.

sequence

This

and W is de-energized,
(evaporator)

function

is performed

by the

fan motor

the burners

stop firing

shuts off after a 45-sec.

and the
time-off

An LED (light-emitting
diode) indicator is provided
board to monitor
operation.
The control board

on the control
is located by

removing

operation,

the burner

LED is continuously
14

begins.

gas control (IGC). The indoor (evaporator)-fan
motor is
45 sec. after flame is established.
When the thermostat is

access

panel.

During

normal

on (See Table 4 for error codes).

the

oi

5

L

A07039

Fig, 15 - 208/230-1-60

Wiring

15

Diagram

H

A07040

Fig. 16 - 208/230-3-60

Wiring

]6

Diagram

,c,x_

2J

CD

i

!:_i
ci

j

_J>

,J
,,J

Z,

:7:

A07041

Fig. 17 - 460-3-60

Wiring
17

Diagram

Table
ERROR
Normal

4--LED

Indications

CODE

LED INDICATION
On

IMPORTANT:

Failure

Off

oriented.

1 Flash

3-phase

Fan On/Off Delay Modified
Limit Switch Fault

Four

Sense

Consecutive

Fault

Limit

Switch

Faults

Ignition
Lockout
Fault
Induced-Draft
Motor Fault
Rolloat
Internal
Temporary

Switch
Control
Lock-Out

(1 hr)

scroll

checked

(below

lead orientation.

compressors

to ensure

turning backwards,

the difference

5 Flashes

discharge

may be dramatically

protector

pressures

CHECKING

are

proper

If not corrected

4 Flashes

room

within

will shut off the compressor.
compressor

When

suction and

lower than normal.

REFRIGERANT

CHARGE

9 Flashes

is tested and factory sealed. Allow system to operate a minimum
15 minutes before checking or adjusting charge.

with R-22

NOTE:Adjustment

of the refrigerant

the unit is suspected

of not having the proper

refrigerant

charge is not required
R-22

and
of

unless

charge.

The charging
label and the tables shown
refer to system
temperatures
and pressures
in cooling mode only. A refrigerant
charging label is attached to the outside of the service access door.
The chart includes the required suction line temperature
suction line pressures and outdoor ambient temperatures.

at given

An accurate
superheat,
thermocoupleor thermistor-type
thermometer,
and a gauge manifold are required when using the
superheat charging method for evaluating the unit charge. Do not
use mercury or small dial-type thermometers
adequate for this type of measurement.

When the air temperature at the limit switch drops to the
low-temperature setting of the limit switch, the switch closes and
completes the control circuit. The direct-spark ignition system
cycles and the unit returns to normal heating operation.
ROLLOUT SWITCH
The function of the rollout switch is to close the main gas valve in
the event of flame rollout. The switch is located above the main
burners. When the temperature at the rollout switch reaches the
maximum allowable temperature, the control circuit trips, closing
the gas valve and stopping gas flow to the burners. The indoor
(evaporator) fan motor (IFM) and induced draft motor continue to
run until switch is reset. The IGC LED will display FAULT CODE
7.
MAKE

is fully charged

3-phase

8 Ftashes

in

system

5 minutes,

The

to correct rotation.

between

AND ADJUSTING

direction

compressor

The refrigerant

Normally closed limit switch (LS) completes the control circuit.
Should the leaving-air temperature rise above the maximum
allowable temperature, the limit switch opens and the control circuit
"breaks." Any interruption in the control circuit instantly closes the
gas valve and stops gas flow to the burners and pilot. The blower
motor continues to run until LS resets.

AND

power

be

power leads to the unit must be reversed

LIMIT SWITCHES

COOLING

must

3 Flashes

NOTES:
1. There is a 3 see. pause between error code displays.
2. If more than o*ie error code exists, all applicable error codes will be displayed
numerical sequel*ce.
3. This chart is oil the wiri,lg diagram located inside the burner access panel.

Step 3---START-UP
MENTS

Three-phase,

Unit

the internal

7 Flashes

Fault

is set to call for cooling

2 Flashes

6 Flashes

Fault

control

temperature).

Operation

Hardware

Flame

temperature

UNIT

DAMAGE

HAZARD

Failure

to follow

this caution

When

evaluating

the

because

they are not

may result in unit damage.

refrigerant

charge,

an

indicated

adjustment to the specified factory charge must always be very
minimal. If a substantial adjustment is indicated, an abnormal
condition
exists somewhere
in the cooling system,
insufficient airflow across either coil or both coils.
Proceed

ADJUST-

2. Using

caps from lowhoses

and high-pressure

3. Start unit in Cooling
pressures
4. Measure

and record

and

pressure

Charging

(psig).

Charts,"

(°C) db) with

actual liquid

(°F (°C) db).

(°F (°C)).

(psig) to determine
desired
temperature
(See Table 6).
6. Compare

low-

high-pressure

and let unit run until system

temperature

(high-side)

"Cooling

temperature(°F

2. Place SYSTEM switch in COOL position and FAN switch
in AUTO position. Set cooling control below room
temperature. Observe that compressor, condenser fan, and
evaporator blower motors start. Observe that cooling cycle
shuts down when control setting is satisfied. The evaporator
fan will continue to run for 30 sec.

attach
and

the following:

line temperature

c. Discharge
5. Using

Mode

ambient-air

b. Liquid

1. Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is placed
in ON position and shuts down when FAN switch is placed
in AUTO position.

to low-

fittings.

stabilize.

a. Outdoor

Start and check the unit for proper cooling control operation as
follows:

service

with valve core depressors,

high-pressure
gauge hoses
service fittings, respectively.

CHECKING COOLING CONTROL OPERATION

as

as follows:

1. Remove

Complete the required procedures given in the Pre-Start-Up
section before starting the unit. Do not jumper any safety devices
when operating the unit. Do not operate the compressor when the
outdoor temperature is below 40°F (unless accessory low-ambient
kit is installed). Do not rapid-cycle the compressor. Allow 5
minutes between on cycles to prevent compressor damage.

such

compare

outdoor-air

the discharge
system

line temperature

line pressure

operating

liquid

with desired

line
liquid

line temperature.
Using a tolerance of -+2°K add refrigerant
if actual temperature
is more than 2°F higher than proper
liquid line
temperature

temperature,
or remove refrigerant
is more than 2°F lower than required

if actual
liquid line

temperature.

3. When using an auto-changeover room thermostat, place
both SYSTEM and FAN switches in AUTO positions.
Observe that unit operates in Heating mode when
temperature control is set to call for heating (above room
temperature)
and operates in Cooling mode when

NOTE:
refrigerant

18

If the problem

causing

the

inaccurate

leak, refer to the Check for Refrigerant

readings

is a

Leaks section.

INDOOR
AIRFLOW
ANDAIRFLOW
ADJUSTMENTS

To change the speed of the indoor fan motor (IFM), remove the fan
motor speed leg lead from the blower relay (BR). This wire is
attached to terminal blower motor (BM) of the integrated gas control
(IGC) board for single-phase
units. To change the speed, remove
and replace with lead for desired blower motor speed. Insulate the

UNITOPERATION
HAZARD
Failure
tofollowthiscaution
mayresult
inunitdamage.
Forcooling
operation,
therecommended
airflow
is350to450
cfmforeach12.000
Btuhof rated
cooling
capacity.
For
heating
operation,
theairflow
must
produce
atemperature
rise
thatfallswithintherange
stamped
ontheunitrating
plate.

removed

lead to avoid contact with chassis

COOLING

SEQUENCE

parts.

OF OPERATION

With the room thermostat SYSTEM switch in the COOL position
and the FAN switch in the AUTO position, the cooling sequence of
operation

is as follows:

1. When
above

Table
8shows
thetemperature
riseineach
heating
mode.
Refer
to
these
tables
todetermine
thedesired
heating
airflow
forthesystem
being
installed.
(See
Table
9forwetcoilpressure
drop).
NOTE:
Besure
thatallsupply-and
return-air
grilles
areopen.
free
fromobstructions,
andadjusted
properly.Airflow
canbechanged
using
theUser
Interface.

the room temperature
the cooling control

thermostat
completes
terminal R to terminals
2. The normally
and complete
to condenser
instantly.

(indoor)
NOTE:

the circuit
Y and G.

open contacts

contacmr

((7) close

fan motor (IFM).

Once the compressor
on until

the room

slightly below the cooling
this point,

of energized

thermostat

open contacts of energized relay BM
the circuit through evaporator
blower

has started and then stopped,

not be started again until 5 minutes
remains

between

the circuit through compressor motor (COMP)
(outdoor) fan motor (OFM). Both motors start

3. The set of normally
close and complete

ELECTRICAL
SHOCK
HAZARD
Failure
tofollowthiswarning
could
result
inpersonal
injury
ordeath.
Disconnect
electrical
power
totheunitandinstall
lockout
tag
before
changing
blower
speed.

rises to a point that is slightly
setting of the thermostat,
the

have elapsed.

temperature

drops

it should

The cooling
to a point

cycle
that is

control setting of the room thermostat.

the thermostat

breaks

the circuit

between

At

thermostat

terminal R to terminals Y and G. These open circuits deenergize
contactor coil C. The condenser and compressor
motors stop. After

Airflowcanbechanged
bychanging
theleadconnections
ofthe
blower
motor.
AllPY3Punitsarefactory
wiredforlowspeed
except
the030
through
the048sizes.
FOR208/230V
Forcolorcoding
onthe208/230V
motor
leads,
see
Table
5.
Table
5--Color
( odlng for 208/230V
Motor Leads

a 30-sec.
condition,
thermostat.

BLACK = HIGH SPEED
Blue = Medium Speed
Red = Low Speed

19

delay, the blower
waiting

motor

stops. The unit is in a standby

for the next call for cooling

from

the room

n

Table
6--Coollng
( harglng
Chart
Suctien
Line
femperature
{°F
!
ODTemp,
(°F) 52 54 56 59 6t 64 67 70 73 76 79
45
5I 55 60 64
53 57 62 66 70
55
53 57 62 66 71 75
65
56 61 66 71
75
53 58 63
85
50 54
95
50
105
49
115
125

0DTemp,
__ m ______
(°C) 361 370 387 405
11 13 15 18
7
12 14
13
18
24
29
35
41
46
52

Suction
Line
Temperature
!°C)
Suction
Line
Press_
423 442 462 482 502 523 544
21
16 19 2!
12 14 17 19 21 24
13 16 19
12 14 17
10 12
10
9

82 85 89 92

76
67
58
53
52
50

72
62 66
60 64
55 58 6I
53 56 59

566 589 612 636

24
20
14
12
11
10

17
14
13
11

19
16 18
14 16
13 15
AO5109

20

Table
FILTER

SIZE

20X20X1

7iFilter

Pressure

500

600

700

800

900

1000

1100

1200

0,05

0,07

0.08

0.1

0.12

0.13

0,14

0.15

0.09

0.1

0.11

0.13
0.07

20X24X1
24X30X1

Table

8--Dry

Coil Air Delivery*
Unit PY3P024-060

Unit

Heating Rise
Range OF
(°C)

LOW1

20 -

50

(11 -

28)

Medium

High

PYSP024060

35 -

65

(19 -

36)

Medium

High

20 (11 -

50
28)

65
36)

55
31)

70
39)

55
31)

2300

0.14
0.08

0.15
0.09

0.16
0.1

0.11

0.12

0.13

0.14

0.15

0.16

0.17

0.18

- Horizontal
(Deduct

and Downflow

Discharge

-

10% for 208 Volts)
External

Static Pressure

(in. wc)

0,2
309

0.3
304

0,4
301

0.5
288

0,6
290

0.7
288

0,8
280

0.9

CFM
Heating Rise OF
(°c)
Watts
CFM

985
82
(18)
411
1195

885
34
(19)
405
1155

820
37
(20)
398
1100

757
40
(22)
390
1028

686
44
(24)
379
957

583
NA

423
NA

263
NA

NA

357
868

357
769

345
647

327
365

Heating Rise °F
(°c)
Watts
CFM
Heating Rise OF

25
(14)
528
1484
20

26
(14)
518
1421
21

27
(15)
509
1868
22

29
(16)
492
1279
23

31
(17)
477
1185
25

35
(19)
467
1088
28

39
(22)
447
970
81

46
(26)
485
853
35

421
712
42

(11)
311

(12)
309

(12)
304

(13)
301

(14)
288

(15)
290

(17)
288

(20)
280

CFM
Heating Rise OF
(°C)
Watts
CFM

985
48
(27)
411
1195

885
51
(28)
405
1155

820
55
(30)
398
1100

757
59
(33)
390
1028

686
NA

583
NA

423
NA

263
NA

NA

379
957

357
868

357
769

345
647

327
365

Heating Rise °F
(°c)
Watts
CFM
Heating Rise OF
(°c)

38
(21)
528
1484

39
(22)
518
1421

41
(23)
509
1868

44
(24)
492
1279
35

47
(26)
477
1185
38

52
(29)
467
1088
41

59
(33)
447
970
46

NA

NA

485
853
53

421
712
63

(28)
288
428

(29)
280
263

(35)

NA

(23)

(21)
288
686

(23)
290
583

Heating Rise OF
(°C)
Watts

82
(18)
411

34
(19)
405

37
(20)
898

40
(22)
390

44
(24)
879

NA

NA

NA

NA

357

857

345

827

CFM
Heating Rise °F
(°C)
Watts
CFM
Heating Rise OF

1195
25
(14)
528
1484
20

1155
26
(14)
518
1421
21

1100
27
(15)
509
1868
22

1028
29
(16)
492
1279
23

957
31
(17)
477
1185
25

868
35
(19)
467
1088
28

769
39
(22)
447
970
81

647
46
(26)
485
853
35

365
NA

(C)
Watts
CFM
Heating Rise °F
(°c)
Watts

(11)
311
935
48
(27)
411

(12)
809
885
51
(28)
405

(12)
304
820
55
(30)
398

(13)
801
757
59
(33)
390

(14)
286
686

(15)
290
583

(17)
286
428

(20)
280
263

(23)

NA

NA

NA

NA

NA

379

357

357

345

327

CFM
Heating Rise °F
(°c)
Watts
CFM

1195
38
(21)
528
1484

1155
39
(22)
518
1421

1100
41
(23)
509
1368

1028
44
(24)
492
1279

957
47
(26)
477
1185

868
52
(29)
467
1088

769
59
(33)
447
970

647
NA

335
NA

435
853

421
712

Heating Rise OF
(°c)
Watts
CFM
Heating Rise °F
(°C)
Watts

NA

NA

NA

439
1242
36
(20)
503

429
1170
38
(21)
491

415
1089
41
(23)
479

35
(20)
401
994
45
(25)
461

38
(21)
395
917
49
(27)
450

41
(23)
380
837
54
(30)
486

46
(28)
356
702

53
(29)
339
570

63
(35)
329
442

NA

NA

NA

418

404

389

CFM
Heating Rise OF
(°C)
Watts
CFM

1320
34
(19)
641
1332

1244
36
(20)
627
1288

1162
39
(22)
623
1205

1081
42
(23)
609
1119

1005
45
(25)
601
1033

897
50
(28)
588
933

767
NA

662
NA

541
NA

571
826

559
714

548
580

Heating Rise OF
(°c)
Watts
CFM

33
(18)
439
1242

35
(19)
429
1170

37
(21)
415
1089

40
(22)
401
994

44
(24)
395
917

48
(27)
380
837

54
(30)
356
702

NA

NA

339
570

329
442

Heating Rise °F
(°c)
Watts

54
(30)
503

58
(32)
491

62
(34)
479

68
(38)
461

NA

NA

NA

NA

NA

450

486

418

404

389

CFM
Heating Rise °F
(°C)
Watts
CFM

1820
51
(28)
641
1332

1244
54
(30)
627
1288

1162
58
(32)
623
1205

1081
62
(35)
609
1119

1005
67
(37)
601
1033

897
NA

767
NA

662
NA

541
NA

588
933

571
826

559
714

548
580

Heating Rise OF
(°c)
Watts
CFM
Heating Rise °F
(°c)
Watts

50
(28)
434
1282
35
(20)
560

52
(29)
428
1241
36
(20)
548

58
(31)
422
1206
37
(21)
535

60
(34)
403
1160
39
(22)
526

65
(36)
404
1109
41
(23)
511

NA

NA

NA

NA

390
1040
43
(24)
496

375
967
47
(26)
478

360
890
51
(28)
460

344
813
55
(31)
439

Medium I

CFM
Heating Rise °F
(°c)
Watts
CFM

1526
29
(16)
785
1860

1482
30
(17)
746
1805

1437
81
(17)
780
1751

1398
32
(18)
709
1685

1344
83
(19)
690
1620

1281
35
(20)
864
1541

1205
87
(21)
642
1468

1125
40
(22)
824
1870

1029
44
(24)
600
1265

High

Heating Rise OF
(°c)

NA

25
(14)

28
(14)

27
(15)

28
(15)

29
(16)

81
(17)

33
(18)

36
(20)

Medium I

Medium I

Medium I

Medium I

Low

25 (14 -

2200

(20)
301
757

High

PYSPO42060

2100

NA

Low

40 (22 -

2000

304
820

High

PYSPO36090

1900

NA

Low

25 (14 -

1800

309
885

High

PYSPO36060

1700

NA

Low

35 (19 -

1600

311
935

High

PYSPO3O06O

1500

Watts
CFM
LOW

PYSP03O04O

1400

0.1
311

(°c)
Watts
Low1

(in_ wc)

1300

Motor
Speed
Watts

PYSP024040

D_-op Table
CFM

21

421
712
42

/

Table

8 - ('ont'd

Dry ('oil

Air Delivery*

Unit PY3P024-060
Heating Rise
Range OF
(°C)

Unit

40 -

70

(22 -

59)

External

Medium 1

High

Low

25 (14 -

PYSP048090

I

55
51)

Medium 1

High

Low

PYSP048115

35 -

65

(19 -

56)

Medium 1

High

Low

PYSP048130

40 -

70

(22 -

39)

Medium 1

High

Low1

25 (14 -

PYSP080090

55
31)

Medium

High

Low1

35 - 65
(19- 36)

PYSP080115

Medium

High

Low1

40 (22 -

PYSP080130

70
39)

Medium

High
ail delively vah_es ale without
iFae{oly shipped heating_coolill
"NA" = Not allowed fol heatii_g
Note: De&ict field supplied aii

and Downflow

-

Static Pressure

(in. wc)

Watts
CFM

0.1
434
1282

0,2
428
1241

0.3
422
1206

0,4
403
1160

0.5
404
1109

0,6
390
1040

0.7
375
967

0,8
380
890

Heating Rise °F
(°C)
Watts
CFM

53
(29)
560
1526

54
(30)
548
1482

58
(31)
535
1437

58
(32)
526
1398

61
(34)
511
1344

85
(38)
496
1281

70
(39)
478
1205

NA

NA

460
1125

439
1029

Heating Rise OF
(°C)
Watts
CFM

44
(25)
785
1860

46
(25)
746
1805

47
(28)
730
1751

48
(27)
709
1885

50
(28)
690
1620

53
(29)
664
1541

56
(31)
642
1488

80
(33)
624
1370

66
(36)
600
1265

Heating
(°C)
Watts
CFM
Heating
(°C)
Watts
CFM
Heating
(°c)
Watts
CFM
Heating
(°C)
Watts
CFM

NA

NA

NA

627
1550
44
(24)
771
1798
38
(21)
969
2124
32
(18)
627
1550

617
1530
44
(24)
755
1771
38
(21)
941
2071
33
(18)
617
1530

607
1493
45
(25)
734
1734
39
(22)
908
2000
84
(19)
607
1493

40
(22)
584
1461
46
(26)
711
1887
40
(22)
887
1944
35
(19)
584
1461

42
(23)
567
1414
48
(27)
690
1645
41
(23)
858
1876
56
(20)
567
1414

44
(24)
548
1361
50
(28)
865
1595
42
(24)
827
1811
37
(21)
548
1361

46
(28)
528
1320
51
(28)
639
1530
44
(25)
804
1735
59
(22)
528
1320

49
(27)
505
1250
54
(30)
807
1449
47
(26)
767
1847
41
(23)
505
1250

53
(30)
480
1177

Heating Rise
oF (°C)
Watts
CFM

58
(31)
771
1798

56
(31)
755
1771

58
(32)
734
1734

59
(33)
711
1887

61
(34)
690
1645

83
(35)
865
1595

65
(38)
639
1530

NA

NA

807
1449

572
1355

Heating Rise OF
(°C)
Watts
CFM
Heating Rise OF
(°C)
Watts
CFM

48
(27)
969
2124
41
(23)
627
1550

49
(27)
941
2071
42
(23)
617
1530

50
(28)
908
2000
43
(24)
607
1493

51
(28)
887
1944
44
(25)
584
1461

52
(29)
858
1876
46
(26)
567
1414

54
(30)
827
1811
48
(28)
548
1361

56
(31)
804
1735
50
(28)
528
1320

80
(33)
767
1847
52
(29)
505
1250

64
(35)
748
1555
55
(31)
480
1177

Heating Rise °F
(°C)
Watts
CFM

63
(35)
771
1798

84
(35)
755
1771

65
(38)
734
1734

87
(37)
711
1887

69
(38)
690
1645

NA

NA

NA

NA

865
1595

639
1530

807
1449

572
1355

Heating Rise OF
(°c)
Watts
CFM
Heating Rise OF
(°C)
Watts

54
(30)
969
2124
46
(26)
786

55
(31)
941
2071
47
(26)
769

56
(31)
908
2000
49
(27)
754

58
(32)
887
1944
50
(28)
736

59
(33)
858
1876
52
(29)
722

81
(34)
827
1811
54
(30)
705

64
(35)
804
1735
58
(31)
684

87
(37)
767
1847
59
(33)
658

748
1555
63
(35)
618

CFM
Heating Rise °F
(°c)
Watts
CFM
Heating Rise OF

2027
33
(19)
873
2095
32

1960
34
(19)
849
2026
33

1901
36
(20)
833
1962
84

1821
37
(21)
815
1887
36

1759
38
(21)
798
1817
57

1893
40
(22)
782
1748
39

1616
42
(23)
783
1679
40

1513
45
(25)
748
1583
43

1354
50
(28)
704
1439
47

(°c)
Watts
CFM
Heating Rise °F
(°C)
Watts

(18)
1012
2184
31
(17)
786

(19)
993
2109
32
(18)
769

(19)
981
2036
33
(18)
754

(20)
965
1963
34
(19)
736

(21)
948
1886
36
(20)
722

(21)
927
1812
37
(21)
705

(22)
904
1729
39
(22)
684

(24)
886
1847
41
(23)
858

(28)
848
1496
45
(25)
618

CFM
Heating Rise °F
(°c)
Watts
CFM
Heating Rise OF
(°c)
Watts
CFM
Heating Rise °F
(°c)
Watts

2027
43
(24)
873
2095
41
(23)
1012
2184
39
(22)
786

1960
44
(24)
849
2026
43
(24)
993
2109
41
(23)
769

1901
45
(25)
833
1962
44
(24)
981
2036
42
(24)
754

1821
47
(26)
815
1887
46
(25)
963
1963
44
(24)
736

1759
49
(27)
798
1817
47
(28)
948
1886
46
(25)
722

1893
51
(28)
782
1748
49
(27)
927
1812
48
(26)
705

1616
53
(30)
783
1679
51
(29)
904
1729
50
(28)
684

1513
57
(32)
748
1583
54
(30)
886
1847
52
(29)
858

1354
64
(35)
704
1439
60
(33)
848
1496
58
(32)
618

CFM
Heating Rise °F
(°C)
Watts
CFM
Heating Rise OF
(°c)
Watts
CFM
Heating Rise °F

2027
48
(27)
873
2095
47
(28)
1012
2184
45

1960
50
(28)
849
2026
48
(27)
993
2109
46

1901
51
(28)
833
1962
50
(28)
981
2036
48

1821
54
(30)
815
1887
52
(29)
965
1963
50

1759
55
(31)
798
1817
54
(30)
948
1886
52

1893
58
(32)
782
1748
56
(31)
927
1812
54

1616
60
(34)
783
1679
58
(32)
904
1729
58

1513
84
(38)
748
1583
82
(34)
886
1847
59

1354
NA

(28)

(27)

(28)

(29)

(30)

(31)

(33)

(38)

Rise OF

Rise °F

Rise OF

Rise OF

(°C)
(25)
ail filtel and aIe fol chy coil (see Wet Coil ?Iessule D_op table)
8 speed
speed
filtei plessme dlop ai_d wet coil pzessule dzop to obtain extelnal

Table

9--PY3P
1100

UNIT SIZE

static piessule

Wet

0.9
344
813

NA
572
1355
50
(28)
748
1555
43
(24)
480
1177

NA

704
1439
68
(38)
848
1496
65

available fol ductin 8

Coil

Pressure

Drop

STANDARD CFM (S.C.F,M,)
1200
1300
1400

600

700

800

900

1000

0.030

0.037

0.044

0.053

0.063

030
036

0.037
-

0.044
-

0.053
0.05

0.063
0.061

0.072
0.072

0.081
0,08

0.105
0,09

.....
0,11

042

-

-

-

0.044

0.051

0.059

0.065

048

-

-

-

0.044

0.050

060

......

024

Discharge

10% for 208 Volts)

Motor
Speed

Low

PYSP042090

- Horizontal

(Deduct

1500

1600

1700

1800

0.072

0.060

0.053

1900

2000

0.088

0.095

0.105

0.059

0.066

0.072

0.077

0.086

-

0.079

0.087

0.095

0.102

0.113

0.123

.......

22

....
-

MAINTENANCE
To ensure
possibility

dimensional
size and type as originally
recommended
filter sizes.

continuing
high performance
and to minimize
the
of premature equipment
failure, periodic maintenance

10, Troubleshooting

Chart.

NOTE TO EQUIPMENT
OWNER:
about the availability
of a maintenance

PERSONAL

INJURY

Consult
contract.

AND UNIT

your

INDOOR

local dealer

in the Owner's

AND MOTOR
are pre-lubricated.

Do not attempt

to lubricate

annually.

injury

The ability
to properly
perform
maintenance
on this
equipment requires certain expertise, mechanical
skills, tools
and equipment.
If you do not possess these, do not attempt to
perform any maintenance
on this equipment, other than those
recommended

1 for

For longer life, operating economy, and continuing efficiency, clean
accumulated
dirt and grease from the blower wheel and motor

HAZARD

Failure to follow this warning could result in personal
or death and unit component
damage.

procedures

BLOWER

NOTE: All motors
these motors.

DAMAGE

See Table

Inspect
air filter(s)
at least once each month
and replace
(throwaway-type)
or clean (cleanable-type)
at least mqce during
each cooling season and twice during the heating season, or
whenever the filter becomes clogged with dust and lint.

must be performed on this equipment.
This unit should be inspected
at least once each year by a qualified service person. To troubleshoot
unit, refer to Table

installed.

ELECTRICAL

SHOCK

HAZARD

Failure to follow this warning
or death.

Manual.

could result in personal

injury

Disconnect
and tag electrical power to the unit before cleaning
and lubricating the blower motor and wheeL
ELECTRICAL

SHOCK

Failure to follow
injury or death:

these

To clean the blower

HAZARD
warnings

could

result

and disassemble

a. Remove

1. Turn off electrical power to the unit before performing
maintenance
or service on this unit.
2. Use extreme

1. Remove

in personal

motor and wheeh

caution

when removing

3. Never place anything
with the unit.

combustible

panels

b. Disconnect
Disconnect
contactor.

any

and parts.

motor
ytellow

c. On all units remove

either on or in contact

blower

assembly

as follows:

unit access panel.
lead from
lead from

blower

blower
relay
terminal
L2

assembly

(BM).
of the

from unit. Remove

screws securing blower
to blower partition
assembly out. Be careful not to tear insulation

and slide
in blower

compartment.
d. Ensure proper reassembly by marking blower wheel and
motor in relation to blower housing before disassembly.
UNIT

OPERATION

Failure
to follow
operation.

HAZARD
this

caution

may

result

e. Loosen
remove

in improper

housing,

maintenance

1. Inspect

air filter(s)

requirements

for this equipment

are as

each

Clean

when

month.

or replace

2. Remove

indoor

coil, drain pan, and condensate

cooling

season

for cleanliness.

drain each

d. Reassemble

tightened
shaft.

season.
7. Check

and

inspect

heating

before

refrigerant

each

heating

Never operate

any obstructions,

the unit without

in the return- air duct system. Always

of

as follows:

by marking

wheel orientation.

vanes.

into housing.

unit access

electrical

Be sure setscrews

shaft flats and not on round

are

part of

panel.

power

and check

for

and motor speeds during heating

to unit.

Start unit

and

the flue

collector

box

and upper

areas

of the heat

exchanger:
if necessary.

1. Remove

AIR FILTER
IMPORTANT:

out

GAS PASSAGEWAYS

To inspect

Clean and adjust when necessary.
flue hood and remove

motor

proper blower rotation
cooling cycles.
FLUE

section

wheel

on motor

f. Reinstall
3. Restore

when necessary.

6. Check

mount

wheel into housing.

e. Reassemble

connections
for tightness and controls for
each heating and cooling season. Service

with

motor

and housing
with vacuum
cleaner, using soft brush
attachment.
Remove grease and oil with mild solvent.

season, inspect
proper cleaning

in contact

and clean blower wheel

(clips) on blower

frequency.

5. Ensure electric wires are not
tubing or sharp metal edges.

and

c. Remove caked-on
dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations
from wheel

3. Inspect blower
motor and wheel for cleanliness
at the
beginning of each heating and cooling season. Clean when

4. Check electrical
proper operation

motor

a. Ensure proper reassembly

Clean when necessary.

necessa U. For first heating and cooling
blower wheel bi-monthly
to determine

slide

b. Lift wheel from housing. When handling and/or cleaning
blower wheel, be sure not to disturb balance weights

necessary.
2. Inspect

and

housing.

Errors made when reconnecting
wires may cause improper
and
dangerous
operation.
Label
all wires
prior
to
disconnecting
when servicing.
The minimum
follows:

setscrew(s)
that secures wheel to motor shaft.
screws that secure motor mount brackets
to

a suitable

according
section.

air filter

replace the filter with the same
23

the combustion
to directions

blower wheel
in the

and motor

Combustion-Air

assembly
Blower

2.Remove
the3screws
holding
theblower
housing
totheflue
collector
boxcover
(See
Fig.18-21).
3.Remove
the12screws
holding
thefluecollector
boxcover
(See
Fig.20-21)
totheheat
exchanger
assembly.
Inspect
the
heat
exchangers.
4.Clean
allsurfaces,
asrequired,
using
awirebrush.
INDUCED
DRAFT
(COMBUSTION
AIR)BLOWER
Clean
periodically
toassure
proper
airflow
andheating
efficiency.
Inspect
blower
wheel
every
fallandperiodically
during
theheating
season.
Forthefirstheating
season,
inspect
blower
wheel
bimonthly
todetermine
proper
cleaning
frequency.
Toinspect
blower
wheel,
remove
drafthoodassembly.
Shine
a
flashlight
intoopening
toinspect
wheel.
If cleaning
isrequired,
remove
motor
andwheel
asfollows:
1.Remove
unitaccess
panel
(See
Fig.19).
2.Remove
the7 screws
thatattach
induced-draft
motor
mounting
plate
toblower
housing
(See
Fig.20).
3.Slide
themotor
and
blower
wheel
assembly
outoftheblower
housing
(See
Fig.20).Clean
theblower
wheel.
Ifadditional
cleaning
isrequired,
continue
withSteps
4and5.
4.Toremove
blower,
remove
2setscrews.
5.Toremove
motorandcooling
fanassembly,
remove
4
screws
thatholdblower
housing
tomounting
plate.
6.Toreinstall,
reverse
theprocedure
outlined
above.

obstructions,

including

airflow through
Straighten

weeds

the condenser

and shrubs,

that interfere

with the

coil.

bent fins with a fin comb. If coated with dirt or lint, clean

the coils with a vacuum cleaner, using the soft brush attachment. Be
careful not to bend the fins. If coated with oil or grease, clean the
coils with a mild detergent and water solution. Rinse coils with clear
water, using a garden hose. Be careful not to splash water on motors,
insulation, wiring, or air filter(s). For best results, spray condenser
coil fins from inside to outside the unit. On units with an outer and
inner condenser coil, be sure to clean between
flush all dirt and debris from the unit base.

the coils.

Be sure to

Inspect the drain pan and condensate drain line when inspecting
coils. Clean the drain pan and condensate
drain by removing

the
all

foreign matter from the pan. Flush the pan and drain trough with
clear water. Do not splash water on the insulation, motor, wiring, or
air filter(s). If the drain trough is restricted,
snake" or similar probe device.
IGNITION

MODULE

\

clear it with a "plumbers

INDUCED

DRAFT

!

MOTOR

MOUNT

\\\\

¢3

LIMITSWITCH
Remove
unitaccess
panel.
Limitswitch
islocated
ontheblower
partition.
BURNER
IGNITION
Unitisequipped
withadirect
spark
ignition
100percent
lockout
system.
Ignition
module
islocated
inthecontrol
box(See
Fig.
18).Module
contains
aself-diagnostic
LED.During
servicing,
refer
tolabel
diagram
forLEDinterpretation.
If lockout
occurs,
unitmayberesetby eithermomentarily
interrupting
power
supply
tounitorbyturning
selector
switch
to
OFFposition
atthethermostat.
MAINBURNERS
Atthebeginning
ofeach
heating
season,
inspect
fordeterioration
or
blockage
due
tocorrosion
orother
causes.
Observe
themain
burner
flames
andadjust,
ifnecessary.
Removal

COLLECTOR
BOX

the gas train for servicing:

1. Shut off main gas valve.
2. Shut off power to unit and install lockout
3. Remove

tag.

unit access panel (See Fig. 19).

4. Disconnect

gas piping

at unit gas valve.

5. Remove

wires connected

6. Remove

ignitor

7. Remove

the mounting

to gas valve.

Mark each wire.

and sensor wires at the ignitor
screw that attaches

module.

the burner rack to

the unit base (See Fig. 18).
8. Slide the burner
9. To reinstall,

rack out of the unit (See Fig. 18 and 21).

reverse the procedure

OUTDOOR
COIL,
DRAIN PAN

INDOOR

Inspect

coil. evaporator

the condenser

COIL,

outlined
AND

above.
CONDENSATE

coil, and condensate

BLOWER
HOUSING

BURNER
RACK

MOUNTING
SCREW
A05119

Fig. 18 - Blower

of Gas Train

To remove

ROLLOUT
SWITCH

i

drain

pan at least once each year.
The coils are easily cleaned when dry: therefore, inspect and clean
the coils either before or after each cooling season. Remove all
24

Housing

and Flue Collector

Box

FRONT
ACCESS

RANEL

A05127

Fig. 19 - Unit Access

Panel

C99086

Fig. 21 - Burner
OUTDOOR

Rack

Removed

FAN

HOUSING

UNIT

OPERATION

Failure to follow
components.

(HIDDEN)

1. Remove
cover.
2. Turn

6 screws

to unit

4.

C99085

Wheel
5.

the fan

If fan needs
shaft.

When

replacing

be visible)
6. Ensure

7. Replace

25

and

grille

upside

down

and

on

motor

top

to top

cover

to

for cracks
loosen

fan blade,

setscrew

setscrew

position

the motor
Fig.

or bends.

end

blade
(1/8

and slide

so that

in. of motor

fan off

the hub
shaft

is

will

12).
engages

the fiat area

on the motor

shaft

tightening.

ELECTRICAL

to turn

blades

from
(See

that

when

sure

assembly

to be removed,

motor

1/8 in. away

Inspect

outdoor

fan blade.

3. Inspect

and Blower

may result in damage

holding

motor/grille

expose

of Motor

this caution

Keep the condenser fan free from all obstructions
to ensure
proper cooling operation. Never place articles on top of the
unit.

2 SETSCREWS

Fig. 20 - Removal

HAZARD

grille.
CONTROLS

check
off

the

AND

electrical

the electrical

power

WIRING

controls

and

to the unit.

wiring

annually.

Be

Remove

access panel to locate all the electrical

and wiring.

If oil is detected

or if low performance

is suspected,

refrigerant tubing using an electronic leak detector,
solution.
If a refrigerant
leak is detected,
refer

disassemble the connection,
clean all the parts, re-strip
and reassemble the connection properly and securely.

Refrigerant

After inspecting

n

controls

Check all electrical connections
for tightness. Tighten all screw
connections.
If any smoky or burned cnnnections
are noticed,

the electrical

controls

and wiring,

the wire end

replace

Leaks

leak test all
or liquid-soap
to Check for

section.

If no refrigerant leaks are found and low performance
is suspected,
refer to Checking
and Adjusting
Refrigerant
Charge section.

all the

panels. Start the unit, and observe at least one complete cooling
cycle to ensure proper operation.
If discrepancies
are observed in

INDOOR

operating cycle, or if a suspected malfunction
has occurred, check
each
electrical
component
with
the
proper
electrical
instrumentation.
Refer to the unit wiring label when making these
checks.

The heating

REFRIGERANT

METERING

AIRFLOW
and/or cooling airflow does not require checking

unless

improper performance
is suspected. If a problem exists, be sure that
all supplyand return-air
grilles are open and free from
obstructions,
and that the air filter is clean.

CIRCUIT

Refrigerant
distributor

Inspect all refrigerant tubing connections
and the unit base for oil
accumulation
annually.
Detecting
oil generally
indicates
a
refrigerant leak.

LIQUID

DEVICES-ACCURATER
metering
assembly

PISTON

device is a fixed orifice and is located
to the indoor coil.

in the

LINE STRAINER

The liquid line strainer (to protect metering device) is made of wire
mesh and is located in the liquid line on the inlet side of the metering
device.
EXPLOSION,

PERSONAL

INJURY

Failure to follow
this warning
damage, personal injury or death.

could

HAZARD
result

TROUBLESHOOTING

in property

Refer
to
the Troubleshooting
troubleshooting
information.

System under pressure.
Relieve
pressure
and recover all
refrigerant before system repair or final unit disposal. Use all
service ports and open all flow-control
devices, including
solenoid valves.

START-UP
Use the Start-Up

26

Checklist

Chart

(Table

CHECKLIST

at the back of this manual.

10-12)

for

Table

lO--T_oubleshooting

SYMPTOM

Chart

CAUSE

REMEDY

Power failure

Call power company
Replace fuse or reset circuit breaker

Fuse blown or circuit breaker tripped

Compreeeor

and

eoadeneer

fan

wiiI not

Defective eontactor, transformer, or high-pressure,
loss-of-charge
or low-pressure switch

Replace component

Insufficient

Determine cause and correct

etart,

line voltage

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

U! setting too high

Lower Ut temperature
perature

Faulty wiring or loose connections
cuit

Compreeeor
rune

will

not

start

but

eoadeneer

fan

in compressor

Determine cause

Defective run/start capacitor, overload, start relay

Determine cause and replace
Replace fuse or reset circuit breaker
Determine cause

power dead

low

Correct the direction of rotation by reversing the

eeroll eompraeaor

exeeeaive

preaaara

aoiae_

and

thera

may

be a

Scroll compressor

is rotating in the wrong direction

differential

Refrigerant

overcharge

or undercharge

Defective compressor
Compreeeor
isfying UI)

Compreeeor

cycles

(other than

operates

normally

aontinuouely

sat-

Defective run/start capacitor

Determine cause and replace

Faulty outdoor fan motor or capacitor
Restriction in refrigerant system

Replace
Locate restriction and remove

Dirty air filter
Unit undersized for load

Replace filter
Decrease load or increase

U! temperature

set too low

Reset UI

Low refrigerant

charge

Locate leak, repair, and recharge
Recover refrigerant, evacuate system, and recharge
Clean coil or remove restriction

coil dirty or restricted

Dirty air filter

Condenser

Exceaeive

eLfCtion

praaaura

air restricted

Recover excess

or air short-cycting

Check for leaks, repair, end recharge,
Remove restriction

High heat load
Compressor valves leaking

Cheek for source and eliminate

Refrigerant

Recover excess refrigerant

Replace compressor

overcharged

Metering device or low side restricted
praeeLfra

tOO

lOW

refrigerant

Recover refrigerant, evacuate system, and recharge
Determine cause and correct

Low refrigerant charge
Restriction in liquid tube

Dirty air filter
Low refrigerant charge

Suction

unit size

Replace filter
Clean coil

Dirty condenser coil
Refrigerant overcharged
Air in system

too low

Recover refrigerant, evacuate system, and recharge to capacities shown on rating plate
Replace and determine cause
Determine cause end correct
Determine cause and correct

Outdoor

Head praeeura

3-phase power leads to the unit, Shut down unit
to allow pressures to equalize,

Insufficient line voltage
Blocked outdoor coil

Air in system

Exceaeive head praeeura

Replace compressor

Determine cause and correct

Low input voltage (20% low)
Feakee

Check wiring and repair or replace

Compressor motor burned out, seized, or
internal overload open

One leg of 3-phase

Thrae-phaee

cir-

setting below room tem-

Insufficient

evaporator

airflow

Temperature too low in conditioned
Outdoor ambient below 55"F
Filter drier restricted

area

Replace filter
Check for leaks, repair and recharge
Remove source of restriction
Increase air quantity
Check filte_replace
if necessary
Reset UI
Install low-ambient kit
Replace filter

27

I!

Table

11

Troubleshooting

SYMPTOM

Gulde=Heating

CAUSE

REMEDY

Water in gas line

Drain, Install drip leg.
Check power supply fuses, wiring or circuit
breaker,

No power to furnace

No 20-v

Burners

will not ignite

Check transformer.
NOTE: Some transformers have internal overcurrent protection that requires a cool-down peg
od to reset.

power suppmy to contr@ circuit

Mis-wired

or loose connections

Check all widng and wire nut connections
Check flame ignition and sense electrode positioning.
Adiust as necessary,
1. Check gas line for air, Purge as necessary.
NOTE: After purging gas line of air, wait at least 5
minutes for any gas to dissipate before attempting to light unit.
2. Check gas valve.

Misaligned spark electrodes

No gas at main burners

Dirty air filter

Clean or replace filter as necessary
Check gas pressure at manifold match with that
on unit namepmate

Gas input to furnace too low
Inadequate

Poor flame

heating

Unit undersized for application
Restricted airflow

Replace with proper unit or add additional unit
Clean or replace filter, Remove any restriction,

Limit switch cycles main burners

Check rotation of blower, temperature
Adiust as necessary,

1. Tighten all screws around burner compartment
2. Cracked heat exchanger. Replace,
3. Unit over-fired. Reduce input (change orifices
or ad}ust gas line or manifold pressure),
4. Check burner alignment,
5. Inspect heat exchanger for bbckage. Clean
as necessary,

Incomplete combustion results in: Aldehyde odors,
carbon monoxide, sooting flame, floating flame

characteristics

Table

12

SYMPTOM

Xi_ubleshooting
CAUSE

Guide--LED

En-or

rise of unit.

Codes
REMEDY

Loss of power to control module (IGO)*.

Check 5-amp fuse son IGC*, power to unit, 24-v circuit
breaker, and transformer. Units without a 24-v circuit
breaker have an internal overload in the 24-v transformer.
If the overload trips, allow 10 minutes for automatic reset.

High limit switch opens during heat exchanger
warm-up period before fan-on delay expires.
Limit switch opens within three minutes after
blower-off delay timing in heating mode,

Ensure unit is fired on rate; ensure temperature rise is correct, Ensure unit's external static pressure is within application guidelines,

Limit switch faults
(LED 2 flashes)

High temperature

Check the operation of the indoor (evaporator) fan motor,
Ensure that the supply-air temperature rise is in accordance with the range on the unit nameplate, Clean or replace filters,

Flame sense fault
(LED 3 flashes)

The IGC* sensed flame that should not be present.

Hardware failure
(LED OFF)

Fan ON/OFF

delay modified

(LED/FLASH)

4 consecutive
limit switch
(LED 4 flashes)

limit switch is open.

faults

Ignition lockout
(LED 5 flashes)

Inadequate

Induced-draft
motor
(LED 6 flashes)

fault

Check the operation of the indoor (evaporator) fan motor
and that supply-air temperature rise agrees with range on
unit nameplate information,

airflow to unit.

Unit unsuccessfully
utes,

Reset unit. If problem persists, replace control board.

attempted ignition for 15 min-

IGC does not sense that induced-draft
operating,*

motor is

Check ignitor and flame sensor electrode spacing, gaps,
etc, Ensure that fame sense and ignition wires are propedy
terminated. Verify that unit is obtaining proper amount of
gas.
Check for proper voltage. If motor is operating, check the
speed sensor plug/IGC Terminal J2 connection, Proper
connection:
PIN 1 - White
PIN 2 - Red
PIN 8 - Black
Rollout switch will automatically

reset, but IGC* will contin-

Rollout switch fault
(LED 7 flashes)

Rollout switch has opened,

ue to lockout unit, Check gas valve operation. Ensure that
induced-draft blower wheel is properly secured to motor
shaft. Inspect heat exchanger, Reset unit at unit disconnect,

Internal control
(LED 8 flashes)

Microprocessor has sensed an error in the software or hardware,

If error code is not cleared by resetting unit power, repmace
the IGC*,

Electrical interference

Reset 24-v, to control board or turn thermostat off, then on
again. Fault will automatically reset itself in one (1) hour.

fault

Temporary software
(LED 9 flashes)
WARNING

_

lockout
impeding IGC software

: If the IGC must be replaced, be sure to ground yoreself to dissipate any electrical charge that my be present before handling

sensitive to static electricity and my be damaged if the necessary precautions are not taken.
IMPORTANT:
Refer to Table 12 Troubleshooting
Guide Heating for additional troubleshooting
LEGEND
IGC--tntegrated
LED

Gas Unit Controller

Light Emitting Diode

28

analysis.

new control board. The IGC is

START-U P CHECKLIST
(Remove and Store in Job File)

I.Preliminary

mnformation

MODEL

NO.:

SERIAL

NO.:

DATE:
TECHNICIAN:
II, PRE=START-UP
(mnsert ¢heckmark
in box as each item ia completed)
() VERIFY THAT ALL PACKING MATERIALS
HAVE BEEN REMOVED
FROM
( ) REMOVE

ALL SHIPPING

HOLD

DOWN

BOLTS

CONNECTIONS

AND

BRACKETS

( ) CHECK

ALL ELECTRICAL

( ) CHECK
( ) CHECK

GAS PIPING FOR LEAKS (WHERE APPLICABLE)
THAT INDOOR
(EVAPORATOR)
AIR FILTER IS CLEAN

( ) VERIFY

THAT

( ) CHECK

FAN WHEEL,

UNIT INSTALLATION
AND

AND TERMINALS

AND

FOR LOCATION

IN HOUSING/ORIFICE

ELECTRICAL
SUPPLY VOLTAGE
COMPRESSOR
AMPS
FAN AMPS

OUTDOOR
(CONDENSER)
AIR TEMPERATURE
RETURN-AIR
TEMPERATURE
DB

REFRIGERANT
REFRIGERANT

TEMPERATURE
MEASURED
*Measured
tMeasured

RISE

IN.WG
PSIG SUCTION
PSIG
CHARGE
RISE

(See Literature)

TEMPERATURE

WB

IN.WG

SUCTION
DISCHARGE

( ) VERIFY
REFRIGERANT
GAS HEAT TEMPERATURE

DB
WB

DB

PRESSURES
GAS iNLET PRESSURE
GAS MANIFOLD
PRESSURE

IN PLACE

IS LEVEL

PROPELLER

COOLING
SUPPLY AIR
GAS HEAT SUPPUY' AIR

INSTRUCTIONS

FOR TIGHTNESS

III, START-UP

INDOOR (EVAPORATOR)
TEMPERATURES

UNIT

PER INSTALLATION

USING

LINE TEMP*

DISCHARGE

CHARGING

TEMPt

CHARTS

RANGE

RISE

at suction inlet to compressor
at liquid line leaving condenser.

2g

AND

SETSCREW

TIGHTNESS

g

Payne

Heating & Cooling

Manufacturer

reserves

Systems * 7310 W. Morris St. * indianapolis,

the right to change_ at any time_ specifications

IN 46231
and designs

Printed in U.S.A
without

notice

and without

3O

Edition
obligations,

Date: 03/07

Catalog No: IM-PY3P-05
Replaces:

IM-PY3P-O4



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 30
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Fri Jun 29 00:43:28 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu