PAYNE Package Units(both Units Combined) Manual L0704293
User Manual: PAYNE PAYNE Package Units(both units combined) Manual PAYNE Package Units(both units combined) Owner's Manual, PAYNE Package Units(both units combined) installation guides
Open the PDF directly: View PDF
.
Page Count: 30
| Download | |
| Open PDF In Browser | View PDF |
Installation Instructions
NOTE:
Read
installation.
NOTE:
the entire
Installer:
Instructions
Make
instruction
sure
manual
the Owner's
before
Manual
starting
and
the
Service
are left with the unit after installation.
TABLE
OF CONTENTS
SAFETY CONSIDERATIONS
........................
INTRODUCTION
..................................
Page
1
2
RECEIVING
2-12
AND INSTALLATION
................
Check Equipment
.................................
Identify Unit ...................................
Inspect Shipment ................................
2
2
2
Provide Unit Support
..............................
Roof Curb .....................................
Slab Mount ....................................
2
2
2
Ground Mount
.................................
Field Fabricate Ductwork
...........................
2
2
Provide
................................
6
................................
6
Clearances
Rig and Place Unit
Inspection
.....................................
Use of Rigging Bracket ...........................
Connect Condensate Drain ..........................
Install Flue Hood
6
6
8
................................
8-9
Install Gas Piping
.................................
Install Duct Connections
............................
9
9
Configuring
Units for Downflow
(Vertical)
Discharge
..................................
Install Electrical Connections
.......................
High- Voltage Connections
.......................
Special Procedures
for 208-V Operation .............
Control Voltage Connections
......................
Heat Anticipator Setting
.........................
Transformer
Protection
..........................
PRE-START-UP
..................................
START-UP
AND TROUBLESHOOTING
...........
Check for Refrigerant Leaks .....................
Start-Up Heating & Make Adjustments
...............
Check Heating Control
..........................
Check Gas Input ...............................
Adjust Gas Input ............................
Check Burner Flame ............................
Airflow
and Temperature
9-10
11
11
11
11
12
12
12
12-22
12-13
13
13
Rise .....................
14
14
18
Rollout
18
Switch
................................
...............
...............
Checking & Adjusting Refrigerant Charge
...........
Indoor Airflow and Airflow Adjustments
............
Cooling Sequence of Operation ....................
MAINTENANCE
...............................
18
18
18
19
19
24-26
Air Filter .......................................
Indoor Blower and Motor ..........................
24
24
Flue Gas Passageways
25
.............................
Induced Draft (Combustion
Air) Blower
Limit Switch ....................................
...............
24
24
Burner Ignition
..................................
Main Burners
...................................
Outdoor
Outdoor
Electrical
25
25
Coil, Indoor Coil, & Condensate
Fan ....................................
Controls
and Wiring
Drain Pan
.....
...................
25
26
26-27
Refrigerant
Circuit ................................
Indoor Airflow
..................................
27
27
Metering Devices-AccuRater
_" Piston ................
Liquid Line Strainer
............................
TROUBLESHOOTING
.............................
27
27
27
START-UP
27
CHECKLIST
13
13-14
14
Heating Sequence of Operation
....................
Limit Switches
................................
Start-Up Cooling & Make Adjustments
Checking Cooling Control Operation
A06079
Fig. 1 - Unit PY3P
(Low NOx Model Available)
...........................
SAFETY
CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due to
mechanical and electrical components.
Only trained and qualified
personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance
functions such
as cleaning and replacing air filters. All other operations must be
performed
equipment,
by trained service personnel.
When working on this
observe precautions
in the literature, on tags, and on
labels attached
to or shipped
precautions
that may apply.
Follow
all safety
codes.
with
Installation
local and national building
clothing, and work gloves.
the
unit
and
other
safety
must be in compliance
with
codes. Wear safety glasses, protective
Have fire extinguisher
available. Read
these instructions thoroughly
and follow all warnings
included in literature and attached to the unit.
or cautions
Recognize
safety
information.
Thisisthesafety-alert
symbol
'_'_.
Step 2--Provide
When you see this symbol on the unit and in instructions
For hurricane
or manuals,
be alert to the potential for personal injury. Understand
these signal
words: DANGER,
WARNING,
and CAUTION.
These words are
(Professional
ROOF
Unit Support
tie downs,
Engineering)
contact
distributor
Certificate
for details
and PE
if required.
CURB
used with the safety-alert
symbol. DANGER
identifies the most serious hazards which will result in severe personal injury or death.
Install accessory
WARNING signifies hazards which could result in personal injury
or death. CAUTION
is used to identify unsafe practices which may
with curb (See Fig. 5). Install insulation, cant strips,
flashing. Ductwork must be attached to curb.
result in minor personal injury or product and property damage.
NOTE is used to highlight
suggestions
which will result in enhanced installation, reliability, or operation.
IMPORTANT:
roof curb in accordance
The gasketing
with instructions
applied
and
of the unit to the roof curb is critical
for a water tight seal. Install gasketing
roof curb. Improperly
shipped
roofing,
material
gasketing
supplied
with the
also can result in air leaks
and poor unit performance.
Curb should be level to within
ELECTRICAL
SHOCK
to function
instructions
HAZARD
Failure to follow this warning
or death.
could result in personal
injury
SLAB
Failure to follow this warning
or unit damage.
SHOCK
HAZARD
installation
pad that is a minimum
of 4
in. thick with 2 in. above grade (See Fig. 2). The slab should extend
approximately
2 in. beyond the casing on all 4 sides of the unit. Do
not secure
ELECTRICAL
POISONING
for unit drain
MOUNT
Place the unit on a solid, level concrete
Before installing or servicing system, always turn off main
power to system.
There may be more than one disconnect
switch. Turn off accessory heater power switch if applicable.
FIRE,
EXPLOSION,
CARBON
MONOXIDE
1/4 in. This is necessary
properly.
Refer to accessory
roof curb
for additional information
as required.
the unit to the slab except when required
by local codes.
AND
could result in personal
injury
A
qualified
installer
or
agency
must
use
only
factory-authorized
kits or accessories
when modifying
this
product.
INTRODUCTION
L
EVAR COIL
The PY3P unit (see Fig. 1) is a fully self-contained,
combination
Category I gas heating/electric
cooling unit designed for outdoor
installation
(See Fig. 3 and 4 for unit dimensions).
All unit sizes
have return and discharge
openings
for both horizontal
and
downflow
configurations,
and are factory
shipped
with all
downflow
a rooftop,
duct openings covered. Units may be installed either on
a cement slab, or directly on the ground, if local codes
COND
C99096
Fig. 2 - Slab Mounting
GROUND
The unit may be installed either on a slab or placed directly on the
ground, if local codes permit. Place the unit on level ground
prepared
Models with an N in the thirteenth position of the model number are
dedicated
Low NOx units designed
for California
installations.
Step 3--Field
These models meet the California
maximum
oxides of nitrogen
(NOx) emissions requirements
of 40 nanograms/joule
or less as
shipped from the factory and must be installed in California
Air
discharge units. Do not connect
applications,
unit is provided
NOTE:
Low
installations.
NOx
requirements
regions
only
to
in North
natural
gas
Step 1--Check
AND INSTALLATION
Equipment
UNIT
The unit model number and serial number are stamped on the unit
information
plate. Check this information
against shipping papers.
INSPECT
Secure
with gravel for condensate
SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet. If
unit appears to be damaged or is torn loose from its anchorage, have
it examined by transportation
inspectors before removal. Forward
claim papers directly to transportation
company. Manufacturer
is
not responsible
for any damage incurred in transit. Check all items
against shipping
list. Immediately
notify the nearest equipment
distribution
office if any item is missing. To prevent loss or damage,
leave all parts in original packages until installation.
Fabricate
all ducts
discharge.
Ductwork
to roof
curb
and building
structure
on vertical
ductwork to unit. For horizontal
with flanges
on the horizontal
openings. All ductwork
should be secured to the flanges. Insulate
and weatherproof
all external ductwork, joints, and roof openings
with counter flashing and mastic in accordance
with applicable
codes.
Ducts passing
RECEIVING
IDENTIFY
apply
other
Details
MOUNT
permit (See Fig. 5 for roof curb dimensions).
Quality Management
Districts
or any
America where a Low NOx rule exists.
/
COIL
and covered
through
an unconditioned
space must be insulated
with a vapor barrier.
If a plenum return is used on a vertical
ducted through the roof deck to comply
unit, the return should be
with applicable fire codes.
A minimum
clearance is not required around
return-air
static shall not exceed -.25 in. wc.
duGwork.
Cabinet
810CKOFF
PANE
ON
018
254
0
[10
00]
_5461
254
121
0
gOi
01i1¥_
k
\
\
11600i
COND
[4 63]
88_
[g 4_J
TOP ViEW
[9 83]
[21
67]
[9 83}
REAR ViEW
REQUIRED
CLEARANCE
TO CO_,rBUSTIBLE
MATL
TOP OF UNIT ...................................................................................
DUCT SIDE OF UNIT .........................................................................
SiDE OPPOSITE
DUCTS
................................................................
BOTTOM
OF UNIT .............................................................................
ELECTRIC
HEAT PANEL .................................................................
REQUIRED
INCHES
_4.00
2.00
14.00
0.50
36.00
[mm]
[355.6]
[50.8]
[355.6]
[12_7]
[914.4]
CLEARANCE
FOR OPERATION
AN D SERVICING
INCHES
36.00
36,00
EVAR COIL ACCESS
SIDE ............................................................
POWER
ENTRY SIDE ....................................................................
(EXCEPT
FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................
SIDE OPPOSITE
DUCTS
..............................................................
DUCT PANEL .................................................................................
48.00
36.00
:12.00
[mm]
[914.0]
[914.0]
[1219.2]
[914.0]
[304.8]
*
NEC. REQUIRED CLEARANCES.
INCHES
BETWEEN UNITS, POWER ENTRY SIDE .................................... 42.00
UNiT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 42.00
[mm]
[1066.8]
[914,0]
*MINIMUM DISTANCES: IF UNIT IS PLACED LESSTHAN 12.00 [304.8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
[1066.8]
LEGEND
CG - Center or Gravity
COND - Condensor
EVAP - Evaporator
NEC - National Electrical Code
REQ'D - Required
NOTE: Dimensions are in in, [rnm]
/98
[31
............................
1193 9
[47 00]
44J
116 3
[4 58]
23 0
[0 9i]
\
??
2
[0
88]
DIA
CONTROL
ENTRY
1230
[484]
}90
[0
_5]
NI']
I
i
x 22 0 _P
[I
68]
FLUE
I¢00D
46
8
[I
84J
52
8
12
122
14
LEFT SIDE ViEW
[O ',O] NP
GAS ENIRY
50
[0 20
_
08]
2
81]
FRONT ViEW
RIGHT SiDE ViEW
A06083
UNIT
ELECTRICAL
CHARACTERISTICS
PY3P024
208/230-1-60
CENTER
UNIT HEIGHT
IN. [MM]
UNIT WEIGHT
X
OF GRAVITY
IN. [MM]
Y
Z
Ib
kg
446
202.3
39.02 [991]
20.0 [508]
19.3 [490]
17.6 [447]
PY3P030
208/230-1-60,
208/230-3-60
451
204.6
41.02 [1042]
20.0 [508]
14.0 [356]
13.0 [330]
PY3P036
208/230-1-60,
208/230-3-60,
460-3-60
459
206.2
41.02 [1042]
20.0 [508]
14.0 [356]
13.0 [330]
Fig. 3 - PY3P024-036
Unit Dimensions
3
556 8
[;401]
]
555
[;4
8
01]
i
RETDRN
SUPPLY
4066
&00
[3 i7]
RETURN
DUG1
4020
[i583]
I
I
I1_ 7
14_60/
J
i i
883
[3
I
L30,2-
48]
!/35
[6 83]
v
.......
i...............
7---i
..............
[!3
83]
_341
3
[13
_301
2
67]
[!3
TOP ViEW
83]
REAR VmEW
REQUIRED CLEARANCE TO COMBUSTIBLE MATE
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
INCHES
14.00
2.00
14.00
0,50
36.00
TOP OF UNIT ...................................................................................
DUCT SIDE OF UNIT .........................................................................
SIDE OPPOSITE DUCTS ................................................................
BOTTOM OF UNIT .............................................................................
ELECTRIC HEAT PANEL .................................................................
[mini
[355.6]
[50,8]
[355.6]
[12.7]
[914.4]
iNCHES [mini
36.00 [914.0]
86.00 [914.0]
EVAR COIL ACCESS SIDE ............................................................
POWER ENTRY SIDE ....................................................................
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .....................................................................................
SIDE OPPOSITE DUCTS ..............................................................
DUCT PANEL .................................................................................
48.00 [1219.2]
36.00 [914.0]
12.00 [304.8] *
NEC. REQUIRED CLEARANCES.
INCHES
BETWEEN UNITS, POWER ENTRY SIDE ....................................
42.00
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 42,00
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE
MAYBE COMPROMISE,
[mini
[1066.8]
[914.0]
[1066.8]
LEGEND
CG- Centerof Gravity
COND- Condensor
EVAP- Evaporator
NEC- NationalElectricalCode
REO'D- Required
1959
[47
i0906
_4294]
FIELD
ENTRf_
250
SER¸¸/ICE POI_I¸
_
I
Y
'_
½
7-
i
l
"
........
POWER ENTRY
1286 [i 3
'
I
"
i
i
4h2
i'l
.i],l
I
DA K 0
!23 0
484]
i
8
NOTE:Dimensionsare in in. [mm]
1!04
[4
54]
,
[091]
=_e_
_
00]
x
/
1
i
\
_RESSOR
x 22
0 10 671
8P
_
....
329
gOr%R
\
GA_ SECTON
0
[44
_;0_
12263
[48 28]
i2
i [0
50_
,'_
!/ P T
GAS ENTRY
52 8
[208]
[1205]
,,_3,
i
5 0
[0 20]
1424
[5 61]
223
FRONTVIEW
LEFT SIDE VIEW
RIGHT SiDE VIEW
A06084
UNIT
UNIT WEIGHT
ELECTRICAL
CHARACTERISTICS
CENTER
UNIT HEIGHT
IN.[MM]
OF GRAVITY
IN. [MM]
Y
Ib
kg
"A"
X
460-3-60
588
268.7
46.98 [1193]
21.0 [533]
20.5 [520]
17.1 [434]
208/230-3-60,
480-3-60
598
270.3
46.98 [1193]
21.0 [533]
20.0 [508]
17.4 [442]
208/230-3-60,
480-3-60
804
274.0
46.98 [1193]
21.0 [533]
20.0 [508]
17.6 [447]
PY3PO42
208/230-1-60,
2081230-3-60,
PY3PO48
208/230-1-60,
PY3PO6O
208/230-1-60,
Fig. 4 - PY3P042-060
Unit Dimensions
Z
Roof
Curb
for
Small
Cabinet
Roof
Curb for Large
Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used,
Note A: When unit mounting screw is used,
retainer bracket must also be used,
E
R/A
S/A
A
_Gasket
\
\
around
duct
\
_
\
/
\
insulated
deck pan
Support
Gasket
outer
/2
around
edge
\
\
Long
Support
\\,\
A05308
UNIT
ODS CATALOG
NUMBER
A
IN. (MM)
B
IN. (MM)
CPRFCURB008A00
8 (203)
11 (279)
16-1/2
(419)
28-3/4
(730)
30-3/8
(771)
44-5/16
(1126)
45-15/16
(1167)
CPRFCURB00FA00
14 (356)
11 (279)
16-1/2
(419)
28-3/4
(730)
30-3/8
(771)
44-5/16
(1126)
45-15/16
(1167)
CPRFCURB008A00
8 (203)
16-3/16
(411)
17-3/8
(441)
40-1/4
(1022)
41-15/16
(1065)
44-7/16
(1129)
46 - 1/16 (1169)
CPRFCURB009A00
14 (356)
16-3/16
(411)
17-3/8
(441)
40-1/4
(1022)
41-15/16
(1065)
44-7/16
(1129)
46-1/16
SIZE
PY3P024-036
PY3P042-060
D
IN. (MM)
C
IN. (MM)
E
IN. (MM)
F
IN. (MM)
G
IN. (MM)
(1169)
NOTES:
[.
Roof
curb
must
be set up for unit
being
installed.
2. Seat strip must be applied, as required, to unit being installed.
3. Dimensions are in inches.
4. Dimension in ( )are in millimeters.
5. Roof curb is made of 16 gauge steel.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Inadated panels: I in. thick fiberglass 1 lb. density.
S. When unit mounting screw is used (see Note A). a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane
conditions. This bracket is available through Micrometl.
Fig.
5 - Roof
Curb
Dimensions
or seismic
Step 4--Provide
The required
Clearances
minimum
operating
and service clearances
are shown
in Fig. 3 and 4. Adequate combustion,
ventilation and condenser air
must be provided
in accordance
with section
5.3. Air for
Combustion
and Ventilation,
of the National Fuel Gas Code ANSI
(American
provisions
National
Standards
Institute)
Z223.1
or applicable
of local building code. In Canada, follow sections 7.2,
7.3, or 7.4 or Can/CGA.
(Canadian
Gas Association)
Installation
Codes or applicable provisions of local building
IMPORTANT:
Do not restrict outdoor
either the outdoor-air
to compressor
An air restriction
at
may be detrimental
DAMAGE
HAZARD
Failure to follow
this warning
injury/death
or property damage.
could
result
in personal
Rigging brackets
for one unit use only. When removing
unit at the end of its useful life. use a new set of brackets.
USE OF RIGGING
Field Installation
a
BRACKET
of Ri_in_
Bracket
(if not already
installed)
life.
and
1. Remove unit from shipping carton. Leave top shipping skid
on the unit for use as a spreader bar to prevent the rigging
discharges it through the top grille. Be sure that the fan discharge
does not recirculate to the condenser coil. Do not locate the unit in
either a corner or under an overhead obstruction.
The minimum
straps from damaging the unit. If the skid is not available, use
a spreader bar of sufficient length to protect the unit from
The
n
airflow.
inlet or the fan discharge
B149
code.
PROPERTY
condenser
fan
pulls
air
a partial
through
overhang
the condenser
clearance
under
(such
overhang)
extension
is 48-in. above the unit top. The maximum
of a partial overhang must not exceed 48-in.
coil
as a normal
house
horizontal
Do not place the unit where water, ice, or snow from an overhang
damage.
2. Remove
4 screws in unit corner posts.
3. Attach each of the 4 metal rigging brackets under the panel
rain lip (See Fig. 6). Use the screws removed in step 2 above
to secure the brackets to the unit.
or roof will damage or flood the unit. Do not install the unit on
carpeting
or other combustible
materials.
Slab-mounted
units
should be at least 4 in. above the highest expected water and runoff
levels. Do not use unit if it has been under water.
Step 5--Rig
and Place
PROPERTY
Unit
Rigging
and handling
of this equipment
reasons
etc.).
due to the installation
location
can be hazardous
(roofs,
structures,
working
with
this equipment,
and ground
observe
support
to follow
injury/death
precautions
Training for operators of the lifting equipment
not be limited to. the following:
1. Application
Follow
all applicable
safety
PROPERTY
include,
but
of the
codes.
Wear safety
shoes
and work
installed on@ on Small Packaged Products.
used to rig/lift a Small Packaged
Product
elevated structures.
designed
to be
This bracket is to be
onto roofs or other
Prior to initial use, and at monthly intervals, all rigging brackets and
straps should be visually inspected
for any damage, evidence of
wear. structural deformation,
or cracks. Particular attention should
be paid to excessive
wear at hoist hooking
points and load support
areas. Brackets or straps showing any kind of wear in these areas
nmst not be used and should be discarded.
UNIT
FALLING
HAZARD
Failure to follow this warning
or death.
Never stand beneath
rigged
could result in personal
units or lift over people.
DAMAGE
lip to provide
HAZARD
could
result
in personal
be
a
injury
of Unit
1. Bend top of brackets
2. Attach
and
rain
When straps are taut, the clevis should
of 36 inches above the unit top cover.
Ri_,_in_/Liftin_
INSPECTION
is engineered
the
Do not strip screws when re-securing
the unit. If a screw is
stripped, replace the stripped one with a larger diameter screw
the corner
bracket
in personal
of the lifting
gloves.
lifting/rigging
be under
Failure
to follow
this warning
injury/death or property damage.
(included).
minimum
or precaution.
3. Condition of the load as it relates to operation
kit, such as balance, temperature,
etc.
result
and
sizes or kinds of loads.
in any special operation
MUST
could
damage.
in the
of the lifter to the load, and adjustment
lifts to adapt to various
2. Instruction
should
this warning
or property
bracket
lifting.
HAZARD
staff
literature, on tags, stickers, and labels attached to the equipment,
any other safety precautions
that might apply.
The
Failure
Rigging
adequate
Only trained, qualified crane operators
should handle and install this equipment.
When
elevated
for many
DAMAGE
opposite
down approximately
30 degrees from
posts.
straps
of equal
length
to the rigging
brackets
at
ends of the unit. Be sure straps are rated to hold the
weight of the unit (See Fig. 6).
3. Attach a clevis of sufficient strength in the middle of the
straps. Adjust the clevis location to ensure unit is lifted level
with the ground.
4. After unit is securely
corner posts
screws.
screws,
After the unit is placed
the top crating.
in place detach rigging
and rigging
brackets
on the roof curb or mounting
straps. Remove
then
reinstall
pad, remove
UNIT SIZE
Table 1---PhysicalData
024060
030040
024040
- Unit PY3P
030060
NOMINAL CAPACITY (ton)
2
2
2-1/2
2-1/2
OPERATING WEIGHT (lb.)
446
446
451
451
036090
042090
3
3-1/2
3-1/2
459
459
588
588
7.2
7.2
7.8
7.8
1
REFRIGERANT (R-22)
Quantity (lb.)
REFRIGERANT METERING DEVICE
ORIFICE ID (IN.)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
CONDENSER FAN
Nominal Cfm
Diameter (in,)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows_.Fins/in.
Face Area (sq ft)
INDOOR BLOWER
5.9
.070
.070
.080
.080
.084
.084
2,..21
10.2
2._21
10.2
2. _2
11.9
2..,21
11.9
2_.21
13.6
2,.,21
13.6
2_.21
19.4
2...21
19.4
2200
22
2200
22
2800
22
2800
22
3000
22
3000
22
3500
22
3500
22
1/8 (825)
1/8 (825)
1/8 (825)
1/8 (825)
1/8 (825)
1/8 (825)
1/8 (825)
1/8 (825)
3...17
3.7
3.,,17
3.7
3.,.17
3.7
3..,17
3.7
4.,.17
3.7
4..,17
3.7
3...17
4.7
3...17
4.7
800
800
1000
1000
1200
1200
1400
1400
10x10
10x10
10x10
10x10
10x10
10x10
11x10
11x10
1/3 (1050)
1/3 (1050)
1/3 (1050)
1/3 (1050)
1/2 (1000)
1/2 (1000)
1/2 (1075)
1/2 (1075)
2,..44
2...50
2., ,38
2..,46
2,, .44
2.,.50
2.. ,38
2..A6
2., .38
2...46
3,. ,38
3..A6
2., .38
2...46
2,..38
2...46
20x24x1
20x24x1
20x24x1
20x24x1
20x24x1
24x36x1
24x36x1
20x24x1
Table
WEIGHT
6.0
.065
UNIT SiZE
CAPACITY
6.0
.065
Size (in,)
Motor HP (RPM)
FURNACE SECTION*
Burner Orifice No. (Qty..,Drill Size)
Natural Gas
Propane Gas
RETURN-AIR FILTERS (in.)f
Throwaway
5.9
AccuRater
Nominal Airflow (Cfm)
OPERATING
042060
3
Scrofi
COMPRESSORS
Quantity
NOMINAL
036060
1--Physical
Data
('on't
- Unit
PY3P
048090
048115
048130
060090
060115
(ton)
4
4
4
5
5
080130
5
(lb.)
598
596
596
604
604
604
12.0
12,0
12.0
Scroll
COMPRESSORS
Quantity
1
REFRIGERANT
Quantity (lb.)
(R-410A)
REFRIGERANT
METERING
12,4
12.4
12.4
.088
.088
.088
.098
.098
0.098
3500
22
3500
22
3500
22
4200
22
4200
22
4200
22
1/4 (1100)
1/4 (1100)
1/4 (1100)
1/4 (1100)
1/4 (1100)
1/4 (1100)
Face Area (sq ft)
2,.,21
19.4
2.,.21
19.4
2.,.21
19.4
2,.,21
19.4
2,.,21
19.4
2.,.21
19.4
EVAPORATOR
COIL
Rows,.,Fins/in.
Face Area (sq ft)
4..,17
5.7
4.,.17
5.7
4.,.17
5.7
4..,17
5.7
4..,17
5.7
4.,.17
5.7
ORIFICE
DEVIOE
AccuRater
ID (IN,)
CONDENSER
FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
CONDENSER
COIL
Rows,.,Fins/in.
INDOOR
BLOWER
Max
1600
1600
1600
2000
2000
2000
Size (In.)
11X10
11X10
11x10
11x10
11X10
11X10
1/2 (1075)
1/2 (1075)
1/2 (1075)
1.0 (1040)
1.0 (1040)
1.0 (1040)
3,.,38
3...46
3.-33
3...42
3._31
3...41
3,.,38
3...46
3,.,33
3...42
3.-31
3...41
24X36X1
24X36X1
24x36x1
24x36x1
24X36X1
24X36X1
Motor HP (RPM)
FURNACE
SECTION*
Burner Orifice No, (Qty,_DriH
Natural Gas
Propane Gas
Size}
RETURN-AIR
FILTERS (in,)f
Throwaway
Based on altitude of 0 to 8000 ft.
T
Required
mimee
filter
for throwaway
sizes
shown
type
are based
or 450 ft/mimee
on the larger
for high
of the ARI
capacity
(Air
type.
(bnditioning
Air filter
pressure
and Refrigeration
drop
for non
Instielte)
standard
rated
filters
cooling
must
airflow
not exceed
or the heating
0.08
in. wc.
airflow
velocity
of 300 fii
I!
MUNIMUMHEUGHT:36'
Y
DETAIL
A
UNIT HEUGHT
x
Z
SEE DETAIL
3
C00070
I!
A06361
CORNER WEIGHTS (SMALL CABINET)
CORNER WEIGHTS
(LARGE CABINET)
Unit
024
030
036
Unit
042
048
060
Total Weight
446
451
459
Total Weight
588
596
604
Corner Weight 1
63
69
66
Corner Weight 1
96
104
97
Corner Weight 2
82
81
87
Corner Weight 2
95
93
102
Corner Weight 3
123
121
122
Corner Weight 3
162
161
163
Corner Weight 4
178
180
184
Corner Weight 4
235
238
242
Rigging Weight
465
470
478
Rigging Weight
610
618
626
Shipping Weight
500
505
513
Shipping Weight
650
658
666
Fig. 6 - PY3P Unit Corner
Step 6--Connect
Condensate
installing
Weights
Drain
condensate
When
comply
with local codes and restrictions.
drain connection
be sure to
Model PY3P disposes of condensate
water through a 3/4 in. NPT
fitting which exits through the base on the evaporator
coil access
side. See Fig. 3 & 4 for location.
water
can be drained
directly
onto the roof in rooftop
installations
(where permitted)
or onto a gravel apron in ground
level installations.
Install a field-supplied
2-in. condensate
trap at
the end of condensate
connection to ensure proper drainage. Make
sure that the outlet of the trap is at least 1 in. lower than the drain-pan
condensate
connection to prevent the pan from overflowing
(See
Fig. 7). Prime the trap with water. When using a gravel apron, make
sure it slopes away from the unit.
Connect
a drain tube using a mininmm
and Suggested
Step 7--Install
NOTE:
Condensate
(in Pounds)
of 3/4-in.
Rigging
Flue Hood
The flue assembly
is secured
and shipped
Remove
duct cover to locate the assembly
NOTE:
Dedicated
low
California Air Quality
rule exists.
These
models
meet
NOx
the California
(NOx) emissions
requirements
shipped from the factory.
NOTE:
Low
installations.
models
Management
NOx
in the return
MUST
Districts
be
where
maximum
installed
apply
oxides
only
in
a Low NOx
of nitrogen
of 40 nanograms/joule
requirements
air duct.
(See Fig. 9 and 10).
to
or less as
natural
gas
PVC or 3/4-in.
copper pipe (all field-supplied)
at the outlet end of the 2-in. trap.
Do not undersize the tube. Pitch the drain tube downward at a slope
of at least l-in. for every 10 ft of horizontal run. Be sure to check
the drain tube for leaks.
CARBON
MONOXIDE
POISONING
Failure to follow this warning
or death.
HAZARD
could result in personal
injury
The venting system is designed to ensure proper venting. The
flue hood assembly mustbe installed as indicted in this section
of the unit installation instructions.
1
In
Install the flue hood
as follows:
1. This installation
2" min.
with the National
must conform
with local building
Fuel Gas (:ode (NFGC),
codes and
ANSI Z223.1 (in
Canada.
CAN/CGA
B149.1.
and B149.2)
or NFPA
(National Fire Protection Association)
latest revision. Refer
to Provincial and local plumbing or wastewater
codes and
C00009
Fig. 7 - Condensate
Trap
other applicable
local codes.
2. Remove flue hood from shipping location (inside the return
section of the blower compartment-see
Fig. 9 & 10). Re-
move
thereturn
ductcover
tolocate
thefluehood.
Place
flue
hoodassembly
overfluepanel.
Orient
screw
holes
influe
hood
withholes
inthefluepanel.
3.Secure
fluehood
tofluepanel
byinserting
asingle
screw
on
therightside
andtheleftside
ofthehood.
Step8--Install Gas Piping
The
gas
supply
pipe
enters
provided. The gas connection
gas inlet on the gas valve.
Install
a gas supply
access
hole
to the unit is made to the 1/2-in.
the
unit
through
the
FPT
line that runs to the heating
section.
IN
OUT_
Refer to
_/
Table 2 and the NFGC for gas pipe sizing. Do not use cast-iron pipe.
It is recommended
that a black iron pipe is used. Check the local
utility for recommendations
concerning
existing lines. Size gas
supply piping for 0.5 in. wc maximum
pressure drop. Never use
pipe smaller than the 1/2-in.
FPT gas inlet on the unit gas valve.
CAP
C99020
NOTE:
piping
Fig. 8 - Sediment Trap
test the gas supply system
Pressure
is connected
disconnected
to the gas valve.
from the gas valve
after the gas supply
The supply
during
piping
the testing
must be
of the piping
For natural gas applications,
the gas pressure at unit gas connection
must not be less than 4.0 in. wc or greater than 13 in. wc while the
systems when test pressure is in excess of 0.5 psig. Pressure test the
gas supply piping system at pressures equal to or less than 0.5 psig.
unit is operating. For propane applications,
the gas pressure must
not be less than 7.0 in. wc or greater than 13 in. wc at the unit
connection.
The unit heating
A 1/8-in.
connection,
supply
NPT
must
plugged
tapping,
accessible
for
be installed immediately
upstream
connection
(in Canada,
CAN/CGA
B149.1).
the state of Massachusetts:
1. Gas supply
connections
MUST be performed
plumber or gas fitter.
2. When flexible connectors
by a licensed
are used. the maximum
shall not exceed 36 inches (915 mm).
3. When lever handle type manual equipment
shutoff
length
valves
are used. they shall be T-handle
valves.
4. The use of copper tubing for gas piping is NOT approved
the state of Massachusetts.
In the absence of local building
pertinent recommendations:
codes,
adhere
by
for every 15 ft of length to prevent traps. Grade all horizontal
runs downward
to risers. Use risers to connect to heating
section and to meter.
2. Protect all segments of piping system against physical and
thermal damage. Support all piping with appropriate straps,
hangers, etc. Use a minimum of one hanger every 6 ft. For
pipe sizes larger than 1/2 in., follow recommendations
of
national codes.
3. Apply joint compound
(pipe dope) sparingly and only to
male threads of joint when making pipe connections.
Use
only pipe dope that is resistant
to action of liquefied
gases as specified
Never use Teflon
by local and/or national
codes.
tape.
4. Install sediment trap in riser leading to heating section (See
Fig. 8). This drip leg functions
as a trap for dirt and
condensate.
5. Install an accessible,
external,
pipe within
manual
6 ft of heating
main shutoff
valve in
valve
and slightly
FIRE
OR EXPLOSION
Failure to follow this warning
death and/or property damage.
-Connect
gas pipe to unit
damaging
gas controls.
plumbing
could result in personal
using
a backup
wrench
injury,
to avoid
-Never purge a gas line into a combustion
chamber. Never test
for gas leaks with an open flame. Use a commercially
available
soap solution made specifically
for the detection of leaks to
check all connections.
-Use proper
manifold.
length
of pipe to avoid
-If a flexible
connector
stress
on gas control
is required
or allowed
by authority
having jurisdiction, black iron pipe shall be installed at furnace
gas valve and extend a minimum of 2 in. outside furnace casing.
-If codes allow a flexible
connector,
always use a new
connector,
do not use a connector
which has previously
serviced another gas appliance.
8. Check
for
gas
factory-installed
leaks
at
the
field-installed
gas lines after all piping
Step 9--Install
and
connections
been completed.
Use soap-and-water
solution
specified by local codes and/or regulations).
have
(or method
Duct Connections
The unit has duct flanges on the supply-
and return-air
openings
in accordance
and gas codes before
with local
connecting
and
piping
on
the side and bottom of the unit. For downshot
applications, the
ductwork connects to the roof curb (See Fig. 3 and 4 for connection
sizes and locations).
CONFIGURING
DISCHARGE
ELECTRICAL
test all gas piping
HAZARD
UNITS
FOR
DOWNFLOW
(VERTICAL)
between
shut-off
valve.
national
to unit.
shutoff
section.
6. Install ground-joint
union close to heating section
unit manual shutoff and external manual main
7. Pressure
manual
union.
to the following
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in.
gas supply
main
the ground-joint
to the gas valve.
NFPA latest edition
petroleum
opening
section must be isolated from the gas piping system
the external
test gauge
of the gas
When installing the gas supply line, observe local codes pertaining
to gas pipe installations.
Refer to the NFGC ANSI Z223.1-2005
NOTE:In
by closing
SHOCK
HAZARD
Failure to follow this warning
or death.
could result in personal
injury
Before installing or servicing system, always turn off main
power to system.
There may be more than one disconnect
switch.
1
!!
Table 2--Maximum
Gas Flow ( apaclty*
NOMINAL
tRON PIPE
SIZE (iN.)
INTERNAL
D_AMETER
(iN.)
10
20
30
40
50
60
70
80
90
100
125
150
1/2
_622
175
120
97
82
73
66
61
57
53
50
44
40
3/4
1
_824
1.049
360
680
250
465
200
375
170
320
151
285
138
260
125
240
118
220
1! 0
205
103
195
93
175
1-1/4
1.380
1400
950
770
600
580
530
490
460
430
400
1-1/2
1.610
2!00
1460
1180
990
900
810
750
690
650
620
Capacity
of pipe
tion Association
This
length
LENGTH OF P_PE (FT)t
in cu ft of gas per hr for gas presalre
NFPA
includes
number
horizontal
(metal)
3. Use a screwdriver
before
starting
duct covers
duct knockouts
and hammer
in, wc (based
on a 0.60
specific
gravity
gas).
72
135
360
325
300
280
550
500
460
430
Refer
to Table,
National
Fire Protec
any service
to access
vertical
in unit base.
to remove
is to be attached
on the unit base (iackstand
time.
PROPERTY
the panels
DAMAGE
to vertical
applications
in the
opening
flanges
only), do so at this
HAZARD
to follow this caution
may result in property
Collect ALL screws that were removed.
on rooftop
of 0,5
77
145
of the unit base (See Fig. 10).
4. If unit ductwork
Failure
drop
84
160
of fittings.
disconnects
(down flow) discharge
bottom
Pressure
200
54.
an ordinary
1. Open all electrical
work.
2. Remove
of 0.5 psig or tess.
175
as permanent
damage
damage.
DUCT
Do not leave screws
COVERS
REMOVED
to the roof may occur.
C99012
Fig. 10 - Vertical Duct Cover
5. It is recommended
perimeter
that
of the vertical
the base
return-air
insulation
opening
around
6. Cover both horizontal
covers. Ensure
7. After completing
duct openings
opening
the
be secured to the
base with aluminum
tape. Applicable
local codes
require aluminum tape to prevent exposed fiberglass.
with the provided
Adhere
may
perform
are
removing
2. Select
all safety checks
criteria
when
shipped
for
horizontal
and
size
ductwork,
grilles according
NFPA
and ventilating
90B;
and/or
systems.
local
codes
duct
sizing,
and
installation
(by
registers,
and
supply-air
to American
Refrigeration
and Air Conditioning
recommendations.
air conditioning
selecting,
duct covers).
return-air
NOTE: The design and installation
of the duct system must be in
accordance
with the standards
of the NFPA for installation
of
90A or residence-type,
ordinances.
following
the duct system:
1. Units
duct
and power up unit.
nonresidence-type
to the
installing
is air- and watertight.
unit conversion,
Removed
Society
Engineers
of Heating,
(ASHRAE)
3. Use flexible transition between rigid ductwork
and unit to
prevent transmission
of vibration.
The transition
may be
NFPA
and
screwed or bolted to duct flanges. Use suitable gaskets
sure weather-tight
and airtight seal.
to en-
4. All units must have field-supplied
filters or accessory
rack
installed
in the return-air
side
of the
filter
unit.
Recommended
sizes for filters are shown
in Table 1.
5. Size all ductwork
for maximum
required
airflow (either
heating or cooling) for unit being installed. Avoid abrupt
duct size increases or decreases or performance
may be
affected.
6. Adequately
insulate and weatherproof
all ductwork located
outdoors.
Insulate
ducts passing through unconditioned
space, and use vapor barrier in accordance with latest issue
of Sheet Metal and Air Conditioning
Association
(SMACNA)
Contractors
and Air Conditioning
National
Contractors
of America (ACCA)
minimum
installation
standards
for
heating and air conditioning
systems. Secure all ducts to
building
SUPPLY
DUCT
OPENING
RETURN
DUCT
OPENING
SHIPPING
LOCATION
7. Flash, weatherproof,
and vibration
isolate all openings
in
building structure in accordance
with local codes and good
A05143
Fig, 9 - Supply
and Return
structure.
building
Duct Opening
10
practices.
Step10--Install
Electrical
Connections
3. Locate the black and yellow wires connected
of the contactor.
4. Connect
field
compressor
ELECTRICAL
SHOCK
HAZARD
Failure to follow this warning
or death.
could result in personal
Three-phase
2. Connect
ground
Electrical
4. Connect
5. Connect
field
6. Connect
HAZARD
SPECIAL
Failure to follow this caution
being installed.
1. Make
all electrical
ANSI/NFPA
governing
connections
codes.
connections
Electrical
copper
field-supplied
electrical
NOT USE ALUMINUM
3. Be sure that high-voltage
voltage range indicated
for connections
disconnect
WIRE.
switch
and unit. DO
FOR 208-V
OPERATION
SHOCK
HAZARD
could result in personal
VOLTAGE
injury
CONNECTIONS
Do not use any type of power-stealing
Consult
voltage
problems
thermostat.
Unit control
may result.
Use no. 18 American Wire Gage (AWG) color-coded,
insulated
(35°C minimum)
wires to make the control voltage connections
between the thermostat and the unit. If the thermostat is located more
than 100 ft from the unit (as measured
wires.
wires), use no. 16 AWG color-coded,
wires.
5. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc.
HIGH-VOLTAGE
13 of the
field wire L3 to blue wire from compressor.
PROCEDURES
CONTROL
power to unit is within operating
on unit rating plate. On 3-phase
phase imbalance.
as high-voltage
11 of the
Before making any wiring changes, make sure the gas supply
is switched off first. Then switch off the power supply to the
unit and install lockout tag.
4. Insulate low-voltage
wires for highest voltage contained
within conduit when low-voltage
control wires are in same
conduit
wire on connection
contactor.
Failure to follow this warning
or death.
local
between
units, ensure phases are balanced within 2 percent.
local power company for correction
of improper
and/or
L1 to black
to the line side
field wire L2 to yellow wire on connection
ELECTRICAL
diagram.
conductor
connection.
with NEC
Code Part 1 and applicable
Refer to unit wiring
only
in accordance
lead to chassis ground
lead into the
to the unit
(latest edition) and local electrical codes
such
wiring.
In Canada,
all electrical
must be in accordance
with CSA standard
C22.1 Canadian
2. Use
may result in damage
23 of the
contactor.
compressor
DAMAGE
(L1, L2, L3) and ground
3. Locate the black and yellow wires connected
of the contactor.
compressor
COMPONENT
11 of the
units:
1. Run the high-voltage
control box.
compartment, or conduit approved for electrical ground when
installed in accordance with NEC, ANSI/NFPA
American
National
Standards
Institute/National
Fire
Protection
UNIT
wire on connection
contactor.
5. Connect field wire L2 to yellow wire on connection
compressor
contactor.
injury
The unit cabinet must have an uninterrupted,
unbroken
electrical ground. This ground may consist of an electrical
wire connected
to the unit ground screw in the control
Association
(latest edition) (in Canada. Canadian
Code CSA C22.1) and local electrical codes.
L1 to black
to the line side
CONNECTIONS
Standard
Connection
Remove
knockout
hole located
along
insulated
the control
(35°C
voltage
minimum)
in the flue panel adjacent
to the
control access panel (See Fig. 3 and 4). Remove the rubber grommet
from the installer's packet (included with unit) and install grommet
in the knockout
opening. Provide a drip loop before running wire
When routing power leads into unit, use only copper wire between
disconnect and unit. The high voltage leads should be in a conduit
until they enter the duct panel; conduit termination
at the duct panel
through
panel.
must be watertight.
The
unit
must
have
a
separate
electrical
service
with
a
field-supplied,
waterproof disconnect switch mounted at, or within
sight from, the unit. Refer to the unit rating plate, NEC and local
codes for maximum
fuse/circuit
breaker size and minimum circuit
amps (ampacity)
for wire sizing.
The field-supplied
disconnect
unit over the high-voltage
low-voltage
entry points
switch box may be mounted
-
-
-
-
-
LABEL)
_
-
-
-
on the
FIELD-SUPPLIED
FUSED DISCONNECT
GR
label and Fig. 11 for reference
follows
when
to
making
high
complete
the
ro[oLOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)
phase units:
1. Run the high-voltage
control box.
2. Connect
-
fc e-
CONTROLBOX
voltage
connections.
Proceed
as
high-voltage
connections
to the unit.
Single
F
POWER
LEADS
(SEE
UNIT
WIRING
inlet hole when the standard power and
are used (See Fig. 3 and 4 for acceptable
location).
See unit wiring
HIGH VOLTAGE
ground
(L1, L2) and ground
lead to chassis
Io-
l
1/
TAT
lead into the
SPLICE
ground
H dih 1/
BOX
connection.
A05144
Fig. 11 - High11
and Control-Voltage
Connections
Run the low-voltage
leads from the thermostat,
hole, and into unit low-voltage
Locate five 18-gage
connection
through
the inlet
a. Inspect
splice box.
wires leaving
control
leads can be identified
box. These low-voltage
c. Leak-test
electronic
side of control box). Route leads through hole in bottom of control
box and make low-voltage
connections
(See Fig. 11). Secure all cut
wires, so that they do not interfere with operation of unit.
heat anticipator
must be properly
adjusted
n
setting.
NOTE:
For thermostat
approximate
required
anticipator
setting.
adjustment
to the occupants
selection
purposes,
Failure
of the conditioned
utilization;
however,
to provide
a greater
the required
degree
TRANSFORMER
to make
a proper
operation,
energy
slightly
for a particular
leak is detected,
Leaks section.
see following
wires do not touch
f. Inspect
coil fins.
handling, carefully
Check
refrigerant
tubing
FIRE,
EXPLOSION
HAZARD
could result in personal
Do not purge gas supply into the combustion
type. It is set to withstand
condition.
injury,
chamber.
Do not
use a match or other open flame to check for gas leaks.
4. Verify the following
UP
ELECTRICAL
SHOCK
HAZARD
Failure to follow this warning
or death.
could result in personal
1. Follow
practices
recognized
NOTE:
conditions:
and wear
chamber,
3. Do
not
compressor
remove
terminal
compressor
cover
terminal
is in place
cover
and
until
electrical sources are disconnected
and tagged.
4. Relieve and recover all refrigerant from system
union.
attempt
to
repair
soldered
all
To remove
a component,
proceed as follows:
a. Shut off electrical
tag.
wear
protective
System
goggles
hnmediately
Never
upon
purge
detection
to purge until the
of gas odor, retighten
to elapse, then light unit.
b. Make
that
sure
fan hub
condenser-fan
blade
is
is positioned
correctly
with
the
correctly
blade
respect
to
(See Fig. 12).
d. Make sure that air filter(s)
is in place.
e. Make sure that condensate
to ensure proper drainage.
drain trap is filled with water
f. Make sure that all tools
have been removed.
and
the
joint
gas lines into a combustion
Allow 5 minutes
motor housing
while
refrigerant system is under pressure.
6. Do not use torch to remove any component.
contains oil and refrigerant under pressure.
and the supply line be allowed
c. Ensure
before
connection
that the ground
positioned in fan orifice. Top 1/3 of condenser-fan
should be within fan orifice venturi.
touching
or disturbing
anything
inside terminal
box if
refrigerant leak is suspected around compressor
terminals.
5. Never
the unit
with the gas valve
If the gas supply pipe was not purged before connecting
odor of gas is detected.
protective
goggles when checking or servicing refrigerant system.
2. Do not operate compressor
or provide any electric power
to unit unless
secured.
the following
unit, it will be full of air. It is recommended
injury
union be loosened,
safety
and
installation.
for the first time, perform
in the OFF position:
EXPLOSION,
Be
or sharp
a. Make sure gas line is free of air. Before lighting
FIRE,
for
If damaged
during
shipping
straighten fins with a fin comb.
Failure to follow this warning
death or property damage.
START-
as
sheet metal edges.
PROTECTION
PRE-
such
etc.
heat
space, and inefficient
The transformer is of the energy-limiting
a 30-sec. overload or shorted secondary
wires,
discomfort
setting may be changed
of comfort
e. Ensure
use 0.18 amp for the
will result in improper
damage,
d. Inspect all field- and factory-wiring
connections.
sure that connections
are completed
and tight.
to
ensure proper heating performance.
Set the heat anticipator, using
an ammeter between the W and R terminals to determine the exact
required
handling
all refrigerant
tubing
connections
using
leak detector,
or liquid-soap
solution.
If a
refrigerant
Refrigerant
SETTING
The room thermostat
and
lines, loose parts, disconnected
b. Inspect for oil at all refrigerant tubing connections
and on
unit base. Detecting oil generally indicates a refrigerant
leak.
by the colors red, green, yellow,
brown, and white (See Fig. 11). Ensure the leads are long enough
to be routed into the low-voltage
splice box (located below right
HEAT ANTICIPATOR
for shipping
broken
MOTOR
and miscellaneous
_
loose
parts
GRILLE
power to unit and install lockout
b. Relieve and reclaim all refrigerant
from system
using both high- and low-pressure
ports.
c. Cut component
connecting
tubing with tubing
cutter and remove component
d. Carefully
unsweat remaining
necessary.
flame.
Oil can ignite
from unit.
tubing stubs
when
exposed
when
1/8"
to torch
MAX
MOTOR
BETWEEN
AND
FAN
HUB
MOTOR
SHAFT
C99009
Fig. 12 - Fan Blade
Use the Start-Up
Checklist supplied at the end of this book and
proceed as follows to inspect and prepare the unit for initial start-up:
Clearance
START-UP
1. Remove
access panel.
Step 1--CHECK
2. Read and follow instructions on all DANGER, WARNING,
CAUTION.
and INFORMATION
labels attached to, or
shipped
Proceed
with unit.
3. Make the following
as follows
FOR
REFRIGERANT
to locate
and repair
LEAKS
a refrigerant
leak and to
charge the unit:
inspections:
1. Locate leak and make sure that refrigerant
has been relieved and reclaimed
from
low-pressure
12
ports.
system pressure
both high- and
CHECK
HEATING
CONTROL
Startandcheck
theunitforproper
heating
control
operation
as
follows
(see
furnace
lighting
instructions
located
inside
burner
or
blower
access
panel):
1.Place
roomthermostat
SYSTEM
switchin theHEAT
position
andthefanswitch
isplaced
inAUTO
position.
2.Settheheating
temperature
control
ofthethermostat
above
room
temperature.
3.Theinduced-draft
motor
willstart.
4.Afteracallforheating,
themain
burner
should
lightwithin
5 sec.
If theburners
donotlight,there
isa22-sec.
delay
before
another
5-sec.
try.Iftheburners
stilldonotlight,this
sequence
isrepeated.
If theburners
donotlightwithin15
minutes
fromtheinitialcallforheat,
there
isalockout.
To
reset
thecontrol,
break
the24-vpower
toW.
5.Theevaporator
fanwillturnon45sec.
after
theflame
has
been
established.
Theevaporator
fanwillturnoff45sec.
after
thethermostat
hasbeen
satisfied.
CHECK
GASINPUT
Check
gas
input
and
manifold
pressure
after
unitstart-up
(See
Table
3).If adjustment
isrequired
proceed
asfollows:
• Therated
gasinputs
shown
inTable
3areforaltitudes
fromsea
levelto2000
ftabove
sea
level.
These
inputs
are
based
onnatural
gas
withaheating
value
of1050
Btu/ft
3
at0.65specific
gravity,
orpropane
gaswithaheating
value
of2500
Btu/ft
3at1.5specific
gravity.
• Forelevations
above
2000
ft,reduce
input4%foreach
1000
ft above
sealevel.
Forexample
at2001ft.a12%
totalderate
isrequired.
• When
thegassupply
being
used
hasadifferent
heating
value
orspecific
gravity,
refer
tonational
andlocal
codes.
orcontact
yourdistributor
todetermine
therequired
orifice
size.
2.Repair
leak
following
accepted
practices.
NOTE:
Install
afilterdrierwhenever
thesystem
hasbeen
opened
forrepair.
3.Addasmall
charge
ofR-22refrigerant
vapor
tosystem
and
leak-test
unit.
4.Recover
refrigerant
fromrefrigerant
system
and
evacuate
to
500microns
ifnoadditional
leaks
arefound.
5.Charge
unitwithR-22refrigerant,
usinga volumetric
charging
cylinder
oraccurate
scale.
Refer
tounitrating
plate
forrequired
charge.
Besuretoaddextrarefrigerant
to
compensate
forinternal
volume
offilterdrier.
STEP
2--START-UP
HEATING
ANDMAKEADJUSTMENTS
Complete
therequired
procedures
givenin thePre-Start-Up
section
before
starting
theunit.Donotjumper
anysafety
devices
when
operating
theunit.Make
sure
thatburner
orifices
areproperly
aligned.
Unstable
operation
myoccur
when
theburner
orifices
in
themanifold
aremisaligned.
Follow
thelighting
instructions
ontheheating
section
operation
label
(located
inside
theburner
orblower
access
door)
tostart
the
heating
section.
NOTE:
Make
sure
thatgassupply
hasbeen
purged,
andthatallgas
piping
hasbeen
checked
forleaks.
/
UNIT
DAMAGE
HAZARD
Failure to follow this caution
component
life.
MANIFOLD
unit and/or
Do Not
redrill
an orifice.
Improper
drilling
(burrs,
out-of-round
holes, etc.) can cause excessive burner noise
and misdirection
of burner flame. If orifice hole appears
damaged or it is suspected to have been redrilled, check orifice
hole with a numbered drill bit of correct size.
PIPE PLUG
C99019
Fig. 13 - Burner
may result in reduced
Assembly
ADJUST
GAS INPUT
BURNER FLAME
The gas input to the unit is determined by measuring the gas flow
at the meter or by measuring the manifold pressure. Measuring the
gas flow at the meter is recommended
for natural gas units. The
manifold
pressure
propane gas units.
Measure
must
be measured
Gas Flow (Natural
to determine
the input
of
Gas Units)
Minor adjustment
to the gas flow can be made by changing the
manifold
pressure.
The manifold
pressure must be maintained
between 3.4 and 3.6 in. wc.
If larger adjustments
are required,
change main burner orifices
following the recommendations
of national and local codes.
IFOLD
NOTE:
All other appliances
off when gas flow is measured
099021
Fig. 14 - Monoport
Burner
13
that use the same meter must be turned
at the meter.
3--Heating
Table
HEATING BNPUT
Inputs
GAS SUPPLY PRESSURE (iN. WC)
Naturalt
Propane*t
Max
I'din
(BTUH)
NUMBER OF
ORIFICES
40,000
2
4.0
13.0
4.0
13.0
3.5
60,000
2
4.0
13.0
4.0
13.0
3.5
3.5
90,000
115,000
3
3
4.0
4.0
13.0
13.0
3.5
3A
13.0
4.0
4.0
13.0
3.5
3.7
130_000
3
4.0
13.0
4.0
13.0
3.5
3.5
Min
MANIFOLD
Max
PRESSURE
Naturalt
(IN. WC)
Propane*t
3.5
When a unit is converted to propane, different size orifices must be used. See separate, natural to propane conversion kit instructions.
j'Based on altit/des from sea level to 2000 ft above sea level. For altit/des above 2000 ft, reduce 111putrating 4 percellt lot each additioiml 1000 ft above sea level In Canada.
from 2000 ft above sea level to 4500 fl _bove sea level derate tl_e unit 10 percent,
Proceed
as follows:
Measure
1. Turn off gas supply
n
to unit.
2. Remove pipe plug on manifold
manometer. Turn on gas supply
3. Record number
revolution.
EXAMPLE:
(See Fig. 13) and connect
to unit.
in Step 3 into 3600
specified
Assume
3. 112.5 x 1 =112.5
of gas to
size of test dial
5. Adjust
pressure
gas
is 1 cu ft, one
With
Btuh, only a minor change
adjustment
screw on gas
screw to the correct
in Table
3. Turn
manifold
adjusting
screw
manifold pressure, or turn adjusting
to decrease manifold pressure.
cover screw.
BURNER
burner
FLAME
access
panel
removed,
observe
the
unit
heating
operation. Watch the burner flames to see if they are light blue and
soft in appearance,
and that the flames are approximately
the same
in the
as follows
to adjust
gas
adjustment
screw on gas
AIRFLOW
AND TEMPERATURE
The heating
section for each size unit is designed
heating operation
unit rating plate.
screw clockwise
to increase
within
may result.
the approved
Refer to Indoor
heating
for
on the
and Airflow
Adjustments
section
to adjust
OF OPERATION
and unit wiring label.)
On a call for heating,
injury
range.
Airflow
SEQUENCE
(See Fig. 15-17
HAZARD
pressure
and approved
range stamped
airflow when required.
HEATING
Unsafe operation of the unit may result if manifold
outside this range.
the temperature-rise
Table 8 shows the approved temperature rise range for each heating
input, and the air delivery cfm at various temperature
rises. The
heating operation airflow must produce a temperature
rise that falls
and 3.6 in. wc. Unsafe operation
of the unit may result if
manifold pressure is outside this range. Personal injury or
Failure to follow this warning could result in personal
or death and/or property damage.
within
RISE
gas
input, or turn regulator adjustment screw counterclockwise
to decrease input. Manifold pressure must be between 3.4
3. Replace
(See
for each burner. Propane will have blue flame (See Fig. 14). Refer
to the Maintenance
section for information
on burner removal.
and proceed
DAMAGE
manometer
7. Turn off gas to unit. Remove manometer
from pressure tap.
Replace pipe plug on gas valve, then turn on gas to unit.
Check for leaks.
Btuh input.
cover screw over regulator
AND UNIT
adjustment
as specified
6. Replace
value of the gas is 1050
input:
FIRE
regulator
clockwise to increase
screw counterclockwise
CHECK
adjustment
and connect
cover screw over regulator
pressure,
ft 3 of gas flow/hr.
If the desired gas input is 115.000
manifold pressure is required.
unit damage
gas unit:
3. Turn on gas to unit.
one revolution.
4. 112.5 x 1050 = 118,125
2. Turn regulator
to adjust gas input on a propane
pipe plug on manifold
4. Remove
valve.
2. 3600 + 32 = 112.5.
1. Remove
valve.
as follows
2. Remove
of
this value with
in Table 3 (Consult
the local
value of gas is not known).
that the
1. 32 sec. to complete
value
input in Btuh. Compare
input shown
if the heating
(number
of cubic feet (cu ft)
result of Step 5 by Btu heating
manifold
in Table 3.
Proceed
of test dial to obtain cubic feet (cu
revolution takes 32 sec., and the heating
Btu/ft3. Proceed as follows:
Observe
Units)
Fig. 13).
result of Step 4 by the number
obtain total measured
heating
supplier
(Propane
1. Turn off gas to unit.
shown for one revolution
ft) of gas flow per hour.
6. Multiply
Pressure
The main burner orifices on a propane gas unit are sized for the unit
rated input when the manifold pressure reading matches the level
of seconds for gas meter test dial to make one
4. Divide number of seconds
seconds in one hr).
5. Multiply
Manifold
terminal
W of the thermostat
is energized.
starting the induced- draft motor. When the hall-effect sensor on the
induced-draft
motor senses that it has reached the required speed.
is
the burner
integrated
energized
cover screw cap on gas valve.
satisfied
4. Turn off gas supply to unit. Remove
manometer
from
pressure tap and replace pipe plug on gas valve. Turn on gas
to unit and check for leaks.
indoor
delay.
sequence
This
and W is de-energized,
(evaporator)
function
is performed
by the
fan motor
the burners
stop firing
shuts off after a 45-sec.
and the
time-off
An LED (light-emitting
diode) indicator is provided
board to monitor
operation.
The control board
on the control
is located by
removing
operation,
the burner
LED is continuously
14
begins.
gas control (IGC). The indoor (evaporator)-fan
motor is
45 sec. after flame is established.
When the thermostat is
access
panel.
During
normal
on (See Table 4 for error codes).
the
oi
5
L
A07039
Fig, 15 - 208/230-1-60
Wiring
15
Diagram
H
A07040
Fig. 16 - 208/230-3-60
Wiring
]6
Diagram
,c,x_
2J
CD
i
!:_i
ci
j
_J>
,J
,,J
Z,
:7:
A07041
Fig. 17 - 460-3-60
Wiring
17
Diagram
Table
ERROR
Normal
4--LED
Indications
CODE
LED INDICATION
On
IMPORTANT:
Failure
Off
oriented.
1 Flash
3-phase
Fan On/Off Delay Modified
Limit Switch Fault
Four
Sense
Consecutive
Fault
Limit
Switch
Faults
Ignition
Lockout
Fault
Induced-Draft
Motor Fault
Rolloat
Internal
Temporary
Switch
Control
Lock-Out
(1 hr)
scroll
checked
(below
lead orientation.
compressors
to ensure
turning backwards,
the difference
5 Flashes
discharge
may be dramatically
protector
pressures
CHECKING
are
proper
If not corrected
4 Flashes
room
within
will shut off the compressor.
compressor
When
suction and
lower than normal.
REFRIGERANT
CHARGE
9 Flashes
is tested and factory sealed. Allow system to operate a minimum
15 minutes before checking or adjusting charge.
with R-22
NOTE:Adjustment
of the refrigerant
the unit is suspected
of not having the proper
refrigerant
charge is not required
R-22
and
of
unless
charge.
The charging
label and the tables shown
refer to system
temperatures
and pressures
in cooling mode only. A refrigerant
charging label is attached to the outside of the service access door.
The chart includes the required suction line temperature
suction line pressures and outdoor ambient temperatures.
at given
An accurate
superheat,
thermocoupleor thermistor-type
thermometer,
and a gauge manifold are required when using the
superheat charging method for evaluating the unit charge. Do not
use mercury or small dial-type thermometers
adequate for this type of measurement.
When the air temperature at the limit switch drops to the
low-temperature setting of the limit switch, the switch closes and
completes the control circuit. The direct-spark ignition system
cycles and the unit returns to normal heating operation.
ROLLOUT SWITCH
The function of the rollout switch is to close the main gas valve in
the event of flame rollout. The switch is located above the main
burners. When the temperature at the rollout switch reaches the
maximum allowable temperature, the control circuit trips, closing
the gas valve and stopping gas flow to the burners. The indoor
(evaporator) fan motor (IFM) and induced draft motor continue to
run until switch is reset. The IGC LED will display FAULT CODE
7.
MAKE
is fully charged
3-phase
8 Ftashes
in
system
5 minutes,
The
to correct rotation.
between
AND ADJUSTING
direction
compressor
The refrigerant
Normally closed limit switch (LS) completes the control circuit.
Should the leaving-air temperature rise above the maximum
allowable temperature, the limit switch opens and the control circuit
"breaks." Any interruption in the control circuit instantly closes the
gas valve and stops gas flow to the burners and pilot. The blower
motor continues to run until LS resets.
AND
power
be
power leads to the unit must be reversed
LIMIT SWITCHES
COOLING
must
3 Flashes
NOTES:
1. There is a 3 see. pause between error code displays.
2. If more than o*ie error code exists, all applicable error codes will be displayed
numerical sequel*ce.
3. This chart is oil the wiri,lg diagram located inside the burner access panel.
Step 3---START-UP
MENTS
Three-phase,
Unit
the internal
7 Flashes
Fault
is set to call for cooling
2 Flashes
6 Flashes
Fault
control
temperature).
Operation
Hardware
Flame
temperature
UNIT
DAMAGE
HAZARD
Failure
to follow
this caution
When
evaluating
the
because
they are not
may result in unit damage.
refrigerant
charge,
an
indicated
adjustment to the specified factory charge must always be very
minimal. If a substantial adjustment is indicated, an abnormal
condition
exists somewhere
in the cooling system,
insufficient airflow across either coil or both coils.
Proceed
ADJUST-
2. Using
caps from lowhoses
and high-pressure
3. Start unit in Cooling
pressures
4. Measure
and record
and
pressure
Charging
(psig).
Charts,"
(°C) db) with
actual liquid
(°F (°C) db).
(°F (°C)).
(psig) to determine
desired
temperature
(See Table 6).
6. Compare
low-
high-pressure
and let unit run until system
temperature
(high-side)
"Cooling
temperature(°F
2. Place SYSTEM switch in COOL position and FAN switch
in AUTO position. Set cooling control below room
temperature. Observe that compressor, condenser fan, and
evaporator blower motors start. Observe that cooling cycle
shuts down when control setting is satisfied. The evaporator
fan will continue to run for 30 sec.
attach
and
the following:
line temperature
c. Discharge
5. Using
Mode
ambient-air
b. Liquid
1. Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is placed
in ON position and shuts down when FAN switch is placed
in AUTO position.
to low-
fittings.
stabilize.
a. Outdoor
Start and check the unit for proper cooling control operation as
follows:
service
with valve core depressors,
high-pressure
gauge hoses
service fittings, respectively.
CHECKING COOLING CONTROL OPERATION
as
as follows:
1. Remove
Complete the required procedures given in the Pre-Start-Up
section before starting the unit. Do not jumper any safety devices
when operating the unit. Do not operate the compressor when the
outdoor temperature is below 40°F (unless accessory low-ambient
kit is installed). Do not rapid-cycle the compressor. Allow 5
minutes between on cycles to prevent compressor damage.
such
compare
outdoor-air
the discharge
system
line temperature
line pressure
operating
liquid
with desired
line
liquid
line temperature.
Using a tolerance of -+2°K add refrigerant
if actual temperature
is more than 2°F higher than proper
liquid line
temperature
temperature,
or remove refrigerant
is more than 2°F lower than required
if actual
liquid line
temperature.
3. When using an auto-changeover room thermostat, place
both SYSTEM and FAN switches in AUTO positions.
Observe that unit operates in Heating mode when
temperature control is set to call for heating (above room
temperature)
and operates in Cooling mode when
NOTE:
refrigerant
18
If the problem
causing
the
inaccurate
leak, refer to the Check for Refrigerant
readings
is a
Leaks section.
INDOOR
AIRFLOW
ANDAIRFLOW
ADJUSTMENTS
To change the speed of the indoor fan motor (IFM), remove the fan
motor speed leg lead from the blower relay (BR). This wire is
attached to terminal blower motor (BM) of the integrated gas control
(IGC) board for single-phase
units. To change the speed, remove
and replace with lead for desired blower motor speed. Insulate the
UNITOPERATION
HAZARD
Failure
tofollowthiscaution
mayresult
inunitdamage.
Forcooling
operation,
therecommended
airflow
is350to450
cfmforeach12.000
Btuhof rated
cooling
capacity.
For
heating
operation,
theairflow
must
produce
atemperature
rise
thatfallswithintherange
stamped
ontheunitrating
plate.
removed
lead to avoid contact with chassis
COOLING
SEQUENCE
parts.
OF OPERATION
With the room thermostat SYSTEM switch in the COOL position
and the FAN switch in the AUTO position, the cooling sequence of
operation
is as follows:
1. When
above
Table
8shows
thetemperature
riseineach
heating
mode.
Refer
to
these
tables
todetermine
thedesired
heating
airflow
forthesystem
being
installed.
(See
Table
9forwetcoilpressure
drop).
NOTE:
Besure
thatallsupply-and
return-air
grilles
areopen.
free
fromobstructions,
andadjusted
properly.Airflow
canbechanged
using
theUser
Interface.
the room temperature
the cooling control
thermostat
completes
terminal R to terminals
2. The normally
and complete
to condenser
instantly.
(indoor)
NOTE:
the circuit
Y and G.
open contacts
contacmr
((7) close
fan motor (IFM).
Once the compressor
on until
the room
slightly below the cooling
this point,
of energized
thermostat
open contacts of energized relay BM
the circuit through evaporator
blower
has started and then stopped,
not be started again until 5 minutes
remains
between
the circuit through compressor motor (COMP)
(outdoor) fan motor (OFM). Both motors start
3. The set of normally
close and complete
ELECTRICAL
SHOCK
HAZARD
Failure
tofollowthiswarning
could
result
inpersonal
injury
ordeath.
Disconnect
electrical
power
totheunitandinstall
lockout
tag
before
changing
blower
speed.
rises to a point that is slightly
setting of the thermostat,
the
have elapsed.
temperature
drops
it should
The cooling
to a point
cycle
that is
control setting of the room thermostat.
the thermostat
breaks
the circuit
between
At
thermostat
terminal R to terminals Y and G. These open circuits deenergize
contactor coil C. The condenser and compressor
motors stop. After
Airflowcanbechanged
bychanging
theleadconnections
ofthe
blower
motor.
AllPY3Punitsarefactory
wiredforlowspeed
except
the030
through
the048sizes.
FOR208/230V
Forcolorcoding
onthe208/230V
motor
leads,
see
Table
5.
Table
5--Color
( odlng for 208/230V
Motor Leads
a 30-sec.
condition,
thermostat.
BLACK = HIGH SPEED
Blue = Medium Speed
Red = Low Speed
19
delay, the blower
waiting
motor
stops. The unit is in a standby
for the next call for cooling
from
the room
n
Table
6--Coollng
( harglng
Chart
Suctien
Line
femperature
{°F
!
ODTemp,
(°F) 52 54 56 59 6t 64 67 70 73 76 79
45
5I 55 60 64
53 57 62 66 70
55
53 57 62 66 71 75
65
56 61 66 71
75
53 58 63
85
50 54
95
50
105
49
115
125
0DTemp,
__ m ______
(°C) 361 370 387 405
11 13 15 18
7
12 14
13
18
24
29
35
41
46
52
Suction
Line
Temperature
!°C)
Suction
Line
Press_
423 442 462 482 502 523 544
21
16 19 2!
12 14 17 19 21 24
13 16 19
12 14 17
10 12
10
9
82 85 89 92
76
67
58
53
52
50
72
62 66
60 64
55 58 6I
53 56 59
566 589 612 636
24
20
14
12
11
10
17
14
13
11
19
16 18
14 16
13 15
AO5109
20
Table
FILTER
SIZE
20X20X1
7iFilter
Pressure
500
600
700
800
900
1000
1100
1200
0,05
0,07
0.08
0.1
0.12
0.13
0,14
0.15
0.09
0.1
0.11
0.13
0.07
20X24X1
24X30X1
Table
8--Dry
Coil Air Delivery*
Unit PY3P024-060
Unit
Heating Rise
Range OF
(°C)
LOW1
20 -
50
(11 -
28)
Medium
High
PYSP024060
35 -
65
(19 -
36)
Medium
High
20 (11 -
50
28)
65
36)
55
31)
70
39)
55
31)
2300
0.14
0.08
0.15
0.09
0.16
0.1
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18
- Horizontal
(Deduct
and Downflow
Discharge
-
10% for 208 Volts)
External
Static Pressure
(in. wc)
0,2
309
0.3
304
0,4
301
0.5
288
0,6
290
0.7
288
0,8
280
0.9
CFM
Heating Rise OF
(°c)
Watts
CFM
985
82
(18)
411
1195
885
34
(19)
405
1155
820
37
(20)
398
1100
757
40
(22)
390
1028
686
44
(24)
379
957
583
NA
423
NA
263
NA
NA
357
868
357
769
345
647
327
365
Heating Rise °F
(°c)
Watts
CFM
Heating Rise OF
25
(14)
528
1484
20
26
(14)
518
1421
21
27
(15)
509
1868
22
29
(16)
492
1279
23
31
(17)
477
1185
25
35
(19)
467
1088
28
39
(22)
447
970
81
46
(26)
485
853
35
421
712
42
(11)
311
(12)
309
(12)
304
(13)
301
(14)
288
(15)
290
(17)
288
(20)
280
CFM
Heating Rise OF
(°C)
Watts
CFM
985
48
(27)
411
1195
885
51
(28)
405
1155
820
55
(30)
398
1100
757
59
(33)
390
1028
686
NA
583
NA
423
NA
263
NA
NA
379
957
357
868
357
769
345
647
327
365
Heating Rise °F
(°c)
Watts
CFM
Heating Rise OF
(°c)
38
(21)
528
1484
39
(22)
518
1421
41
(23)
509
1868
44
(24)
492
1279
35
47
(26)
477
1185
38
52
(29)
467
1088
41
59
(33)
447
970
46
NA
NA
485
853
53
421
712
63
(28)
288
428
(29)
280
263
(35)
NA
(23)
(21)
288
686
(23)
290
583
Heating Rise OF
(°C)
Watts
82
(18)
411
34
(19)
405
37
(20)
898
40
(22)
390
44
(24)
879
NA
NA
NA
NA
357
857
345
827
CFM
Heating Rise °F
(°C)
Watts
CFM
Heating Rise OF
1195
25
(14)
528
1484
20
1155
26
(14)
518
1421
21
1100
27
(15)
509
1868
22
1028
29
(16)
492
1279
23
957
31
(17)
477
1185
25
868
35
(19)
467
1088
28
769
39
(22)
447
970
81
647
46
(26)
485
853
35
365
NA
(C)
Watts
CFM
Heating Rise °F
(°c)
Watts
(11)
311
935
48
(27)
411
(12)
809
885
51
(28)
405
(12)
304
820
55
(30)
398
(13)
801
757
59
(33)
390
(14)
286
686
(15)
290
583
(17)
286
428
(20)
280
263
(23)
NA
NA
NA
NA
NA
379
357
357
345
327
CFM
Heating Rise °F
(°c)
Watts
CFM
1195
38
(21)
528
1484
1155
39
(22)
518
1421
1100
41
(23)
509
1368
1028
44
(24)
492
1279
957
47
(26)
477
1185
868
52
(29)
467
1088
769
59
(33)
447
970
647
NA
335
NA
435
853
421
712
Heating Rise OF
(°c)
Watts
CFM
Heating Rise °F
(°C)
Watts
NA
NA
NA
439
1242
36
(20)
503
429
1170
38
(21)
491
415
1089
41
(23)
479
35
(20)
401
994
45
(25)
461
38
(21)
395
917
49
(27)
450
41
(23)
380
837
54
(30)
486
46
(28)
356
702
53
(29)
339
570
63
(35)
329
442
NA
NA
NA
418
404
389
CFM
Heating Rise OF
(°C)
Watts
CFM
1320
34
(19)
641
1332
1244
36
(20)
627
1288
1162
39
(22)
623
1205
1081
42
(23)
609
1119
1005
45
(25)
601
1033
897
50
(28)
588
933
767
NA
662
NA
541
NA
571
826
559
714
548
580
Heating Rise OF
(°c)
Watts
CFM
33
(18)
439
1242
35
(19)
429
1170
37
(21)
415
1089
40
(22)
401
994
44
(24)
395
917
48
(27)
380
837
54
(30)
356
702
NA
NA
339
570
329
442
Heating Rise °F
(°c)
Watts
54
(30)
503
58
(32)
491
62
(34)
479
68
(38)
461
NA
NA
NA
NA
NA
450
486
418
404
389
CFM
Heating Rise °F
(°C)
Watts
CFM
1820
51
(28)
641
1332
1244
54
(30)
627
1288
1162
58
(32)
623
1205
1081
62
(35)
609
1119
1005
67
(37)
601
1033
897
NA
767
NA
662
NA
541
NA
588
933
571
826
559
714
548
580
Heating Rise OF
(°c)
Watts
CFM
Heating Rise °F
(°c)
Watts
50
(28)
434
1282
35
(20)
560
52
(29)
428
1241
36
(20)
548
58
(31)
422
1206
37
(21)
535
60
(34)
403
1160
39
(22)
526
65
(36)
404
1109
41
(23)
511
NA
NA
NA
NA
390
1040
43
(24)
496
375
967
47
(26)
478
360
890
51
(28)
460
344
813
55
(31)
439
Medium I
CFM
Heating Rise °F
(°c)
Watts
CFM
1526
29
(16)
785
1860
1482
30
(17)
746
1805
1437
81
(17)
780
1751
1398
32
(18)
709
1685
1344
83
(19)
690
1620
1281
35
(20)
864
1541
1205
87
(21)
642
1468
1125
40
(22)
824
1870
1029
44
(24)
600
1265
High
Heating Rise OF
(°c)
NA
25
(14)
28
(14)
27
(15)
28
(15)
29
(16)
81
(17)
33
(18)
36
(20)
Medium I
Medium I
Medium I
Medium I
Low
25 (14 -
2200
(20)
301
757
High
PYSPO42060
2100
NA
Low
40 (22 -
2000
304
820
High
PYSPO36090
1900
NA
Low
25 (14 -
1800
309
885
High
PYSPO36060
1700
NA
Low
35 (19 -
1600
311
935
High
PYSPO3O06O
1500
Watts
CFM
LOW
PYSP03O04O
1400
0.1
311
(°c)
Watts
Low1
(in_ wc)
1300
Motor
Speed
Watts
PYSP024040
D_-op Table
CFM
21
421
712
42
/
Table
8 - ('ont'd
Dry ('oil
Air Delivery*
Unit PY3P024-060
Heating Rise
Range OF
(°C)
Unit
40 -
70
(22 -
59)
External
Medium 1
High
Low
25 (14 -
PYSP048090
I
55
51)
Medium 1
High
Low
PYSP048115
35 -
65
(19 -
56)
Medium 1
High
Low
PYSP048130
40 -
70
(22 -
39)
Medium 1
High
Low1
25 (14 -
PYSP080090
55
31)
Medium
High
Low1
35 - 65
(19- 36)
PYSP080115
Medium
High
Low1
40 (22 -
PYSP080130
70
39)
Medium
High
ail delively vah_es ale without
iFae{oly shipped heating_coolill
"NA" = Not allowed fol heatii_g
Note: De&ict field supplied aii
and Downflow
-
Static Pressure
(in. wc)
Watts
CFM
0.1
434
1282
0,2
428
1241
0.3
422
1206
0,4
403
1160
0.5
404
1109
0,6
390
1040
0.7
375
967
0,8
380
890
Heating Rise °F
(°C)
Watts
CFM
53
(29)
560
1526
54
(30)
548
1482
58
(31)
535
1437
58
(32)
526
1398
61
(34)
511
1344
85
(38)
496
1281
70
(39)
478
1205
NA
NA
460
1125
439
1029
Heating Rise OF
(°C)
Watts
CFM
44
(25)
785
1860
46
(25)
746
1805
47
(28)
730
1751
48
(27)
709
1885
50
(28)
690
1620
53
(29)
664
1541
56
(31)
642
1488
80
(33)
624
1370
66
(36)
600
1265
Heating
(°C)
Watts
CFM
Heating
(°C)
Watts
CFM
Heating
(°c)
Watts
CFM
Heating
(°C)
Watts
CFM
NA
NA
NA
627
1550
44
(24)
771
1798
38
(21)
969
2124
32
(18)
627
1550
617
1530
44
(24)
755
1771
38
(21)
941
2071
33
(18)
617
1530
607
1493
45
(25)
734
1734
39
(22)
908
2000
84
(19)
607
1493
40
(22)
584
1461
46
(26)
711
1887
40
(22)
887
1944
35
(19)
584
1461
42
(23)
567
1414
48
(27)
690
1645
41
(23)
858
1876
56
(20)
567
1414
44
(24)
548
1361
50
(28)
865
1595
42
(24)
827
1811
37
(21)
548
1361
46
(28)
528
1320
51
(28)
639
1530
44
(25)
804
1735
59
(22)
528
1320
49
(27)
505
1250
54
(30)
807
1449
47
(26)
767
1847
41
(23)
505
1250
53
(30)
480
1177
Heating Rise
oF (°C)
Watts
CFM
58
(31)
771
1798
56
(31)
755
1771
58
(32)
734
1734
59
(33)
711
1887
61
(34)
690
1645
83
(35)
865
1595
65
(38)
639
1530
NA
NA
807
1449
572
1355
Heating Rise OF
(°C)
Watts
CFM
Heating Rise OF
(°C)
Watts
CFM
48
(27)
969
2124
41
(23)
627
1550
49
(27)
941
2071
42
(23)
617
1530
50
(28)
908
2000
43
(24)
607
1493
51
(28)
887
1944
44
(25)
584
1461
52
(29)
858
1876
46
(26)
567
1414
54
(30)
827
1811
48
(28)
548
1361
56
(31)
804
1735
50
(28)
528
1320
80
(33)
767
1847
52
(29)
505
1250
64
(35)
748
1555
55
(31)
480
1177
Heating Rise °F
(°C)
Watts
CFM
63
(35)
771
1798
84
(35)
755
1771
65
(38)
734
1734
87
(37)
711
1887
69
(38)
690
1645
NA
NA
NA
NA
865
1595
639
1530
807
1449
572
1355
Heating Rise OF
(°c)
Watts
CFM
Heating Rise OF
(°C)
Watts
54
(30)
969
2124
46
(26)
786
55
(31)
941
2071
47
(26)
769
56
(31)
908
2000
49
(27)
754
58
(32)
887
1944
50
(28)
736
59
(33)
858
1876
52
(29)
722
81
(34)
827
1811
54
(30)
705
64
(35)
804
1735
58
(31)
684
87
(37)
767
1847
59
(33)
658
748
1555
63
(35)
618
CFM
Heating Rise °F
(°c)
Watts
CFM
Heating Rise OF
2027
33
(19)
873
2095
32
1960
34
(19)
849
2026
33
1901
36
(20)
833
1962
84
1821
37
(21)
815
1887
36
1759
38
(21)
798
1817
57
1893
40
(22)
782
1748
39
1616
42
(23)
783
1679
40
1513
45
(25)
748
1583
43
1354
50
(28)
704
1439
47
(°c)
Watts
CFM
Heating Rise °F
(°C)
Watts
(18)
1012
2184
31
(17)
786
(19)
993
2109
32
(18)
769
(19)
981
2036
33
(18)
754
(20)
965
1963
34
(19)
736
(21)
948
1886
36
(20)
722
(21)
927
1812
37
(21)
705
(22)
904
1729
39
(22)
684
(24)
886
1847
41
(23)
858
(28)
848
1496
45
(25)
618
CFM
Heating Rise °F
(°c)
Watts
CFM
Heating Rise OF
(°c)
Watts
CFM
Heating Rise °F
(°c)
Watts
2027
43
(24)
873
2095
41
(23)
1012
2184
39
(22)
786
1960
44
(24)
849
2026
43
(24)
993
2109
41
(23)
769
1901
45
(25)
833
1962
44
(24)
981
2036
42
(24)
754
1821
47
(26)
815
1887
46
(25)
963
1963
44
(24)
736
1759
49
(27)
798
1817
47
(28)
948
1886
46
(25)
722
1893
51
(28)
782
1748
49
(27)
927
1812
48
(26)
705
1616
53
(30)
783
1679
51
(29)
904
1729
50
(28)
684
1513
57
(32)
748
1583
54
(30)
886
1847
52
(29)
858
1354
64
(35)
704
1439
60
(33)
848
1496
58
(32)
618
CFM
Heating Rise °F
(°C)
Watts
CFM
Heating Rise OF
(°c)
Watts
CFM
Heating Rise °F
2027
48
(27)
873
2095
47
(28)
1012
2184
45
1960
50
(28)
849
2026
48
(27)
993
2109
46
1901
51
(28)
833
1962
50
(28)
981
2036
48
1821
54
(30)
815
1887
52
(29)
965
1963
50
1759
55
(31)
798
1817
54
(30)
948
1886
52
1893
58
(32)
782
1748
56
(31)
927
1812
54
1616
60
(34)
783
1679
58
(32)
904
1729
58
1513
84
(38)
748
1583
82
(34)
886
1847
59
1354
NA
(28)
(27)
(28)
(29)
(30)
(31)
(33)
(38)
Rise OF
Rise °F
Rise OF
Rise OF
(°C)
(25)
ail filtel and aIe fol chy coil (see Wet Coil ?Iessule D_op table)
8 speed
speed
filtei plessme dlop ai_d wet coil pzessule dzop to obtain extelnal
Table
9--PY3P
1100
UNIT SIZE
static piessule
Wet
0.9
344
813
NA
572
1355
50
(28)
748
1555
43
(24)
480
1177
NA
704
1439
68
(38)
848
1496
65
available fol ductin 8
Coil
Pressure
Drop
STANDARD CFM (S.C.F,M,)
1200
1300
1400
600
700
800
900
1000
0.030
0.037
0.044
0.053
0.063
030
036
0.037
-
0.044
-
0.053
0.05
0.063
0.061
0.072
0.072
0.081
0,08
0.105
0,09
.....
0,11
042
-
-
-
0.044
0.051
0.059
0.065
048
-
-
-
0.044
0.050
060
......
024
Discharge
10% for 208 Volts)
Motor
Speed
Low
PYSP042090
- Horizontal
(Deduct
1500
1600
1700
1800
0.072
0.060
0.053
1900
2000
0.088
0.095
0.105
0.059
0.066
0.072
0.077
0.086
-
0.079
0.087
0.095
0.102
0.113
0.123
.......
22
....
-
MAINTENANCE
To ensure
possibility
dimensional
size and type as originally
recommended
filter sizes.
continuing
high performance
and to minimize
the
of premature equipment
failure, periodic maintenance
10, Troubleshooting
Chart.
NOTE TO EQUIPMENT
OWNER:
about the availability
of a maintenance
PERSONAL
INJURY
Consult
contract.
AND UNIT
your
INDOOR
local dealer
in the Owner's
AND MOTOR
are pre-lubricated.
Do not attempt
to lubricate
annually.
injury
The ability
to properly
perform
maintenance
on this
equipment requires certain expertise, mechanical
skills, tools
and equipment.
If you do not possess these, do not attempt to
perform any maintenance
on this equipment, other than those
recommended
1 for
For longer life, operating economy, and continuing efficiency, clean
accumulated
dirt and grease from the blower wheel and motor
HAZARD
Failure to follow this warning could result in personal
or death and unit component
damage.
procedures
BLOWER
NOTE: All motors
these motors.
DAMAGE
See Table
Inspect
air filter(s)
at least once each month
and replace
(throwaway-type)
or clean (cleanable-type)
at least mqce during
each cooling season and twice during the heating season, or
whenever the filter becomes clogged with dust and lint.
must be performed on this equipment.
This unit should be inspected
at least once each year by a qualified service person. To troubleshoot
unit, refer to Table
installed.
ELECTRICAL
SHOCK
HAZARD
Failure to follow this warning
or death.
Manual.
could result in personal
injury
Disconnect
and tag electrical power to the unit before cleaning
and lubricating the blower motor and wheeL
ELECTRICAL
SHOCK
Failure to follow
injury or death:
these
To clean the blower
HAZARD
warnings
could
result
and disassemble
a. Remove
1. Turn off electrical power to the unit before performing
maintenance
or service on this unit.
2. Use extreme
1. Remove
in personal
motor and wheeh
caution
when removing
3. Never place anything
with the unit.
combustible
panels
b. Disconnect
Disconnect
contactor.
any
and parts.
motor
ytellow
c. On all units remove
either on or in contact
blower
assembly
as follows:
unit access panel.
lead from
lead from
blower
blower
relay
terminal
L2
assembly
(BM).
of the
from unit. Remove
screws securing blower
to blower partition
assembly out. Be careful not to tear insulation
and slide
in blower
compartment.
d. Ensure proper reassembly by marking blower wheel and
motor in relation to blower housing before disassembly.
UNIT
OPERATION
Failure
to follow
operation.
HAZARD
this
caution
may
result
e. Loosen
remove
in improper
housing,
maintenance
1. Inspect
air filter(s)
requirements
for this equipment
are as
each
Clean
when
month.
or replace
2. Remove
indoor
coil, drain pan, and condensate
cooling
season
for cleanliness.
drain each
d. Reassemble
tightened
shaft.
season.
7. Check
and
inspect
heating
before
refrigerant
each
heating
Never operate
any obstructions,
the unit without
in the return- air duct system. Always
of
as follows:
by marking
wheel orientation.
vanes.
into housing.
unit access
electrical
Be sure setscrews
shaft flats and not on round
are
part of
panel.
power
and check
for
and motor speeds during heating
to unit.
Start unit
and
the flue
collector
box
and upper
areas
of the heat
exchanger:
if necessary.
1. Remove
AIR FILTER
IMPORTANT:
out
GAS PASSAGEWAYS
To inspect
Clean and adjust when necessary.
flue hood and remove
motor
proper blower rotation
cooling cycles.
FLUE
section
wheel
on motor
f. Reinstall
3. Restore
when necessary.
6. Check
mount
wheel into housing.
e. Reassemble
connections
for tightness and controls for
each heating and cooling season. Service
with
motor
and housing
with vacuum
cleaner, using soft brush
attachment.
Remove grease and oil with mild solvent.
season, inspect
proper cleaning
in contact
and clean blower wheel
(clips) on blower
frequency.
5. Ensure electric wires are not
tubing or sharp metal edges.
and
c. Remove caked-on
dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations
from wheel
3. Inspect blower
motor and wheel for cleanliness
at the
beginning of each heating and cooling season. Clean when
4. Check electrical
proper operation
motor
a. Ensure proper reassembly
Clean when necessary.
necessa U. For first heating and cooling
blower wheel bi-monthly
to determine
slide
b. Lift wheel from housing. When handling and/or cleaning
blower wheel, be sure not to disturb balance weights
necessary.
2. Inspect
and
housing.
Errors made when reconnecting
wires may cause improper
and
dangerous
operation.
Label
all wires
prior
to
disconnecting
when servicing.
The minimum
follows:
setscrew(s)
that secures wheel to motor shaft.
screws that secure motor mount brackets
to
a suitable
according
section.
air filter
replace the filter with the same
23
the combustion
to directions
blower wheel
in the
and motor
Combustion-Air
assembly
Blower
2.Remove
the3screws
holding
theblower
housing
totheflue
collector
boxcover
(See
Fig.18-21).
3.Remove
the12screws
holding
thefluecollector
boxcover
(See
Fig.20-21)
totheheat
exchanger
assembly.
Inspect
the
heat
exchangers.
4.Clean
allsurfaces,
asrequired,
using
awirebrush.
INDUCED
DRAFT
(COMBUSTION
AIR)BLOWER
Clean
periodically
toassure
proper
airflow
andheating
efficiency.
Inspect
blower
wheel
every
fallandperiodically
during
theheating
season.
Forthefirstheating
season,
inspect
blower
wheel
bimonthly
todetermine
proper
cleaning
frequency.
Toinspect
blower
wheel,
remove
drafthoodassembly.
Shine
a
flashlight
intoopening
toinspect
wheel.
If cleaning
isrequired,
remove
motor
andwheel
asfollows:
1.Remove
unitaccess
panel
(See
Fig.19).
2.Remove
the7 screws
thatattach
induced-draft
motor
mounting
plate
toblower
housing
(See
Fig.20).
3.Slide
themotor
and
blower
wheel
assembly
outoftheblower
housing
(See
Fig.20).Clean
theblower
wheel.
Ifadditional
cleaning
isrequired,
continue
withSteps
4and5.
4.Toremove
blower,
remove
2setscrews.
5.Toremove
motorandcooling
fanassembly,
remove
4
screws
thatholdblower
housing
tomounting
plate.
6.Toreinstall,
reverse
theprocedure
outlined
above.
obstructions,
including
airflow through
Straighten
weeds
the condenser
and shrubs,
that interfere
with the
coil.
bent fins with a fin comb. If coated with dirt or lint, clean
the coils with a vacuum cleaner, using the soft brush attachment. Be
careful not to bend the fins. If coated with oil or grease, clean the
coils with a mild detergent and water solution. Rinse coils with clear
water, using a garden hose. Be careful not to splash water on motors,
insulation, wiring, or air filter(s). For best results, spray condenser
coil fins from inside to outside the unit. On units with an outer and
inner condenser coil, be sure to clean between
flush all dirt and debris from the unit base.
the coils.
Be sure to
Inspect the drain pan and condensate drain line when inspecting
coils. Clean the drain pan and condensate
drain by removing
the
all
foreign matter from the pan. Flush the pan and drain trough with
clear water. Do not splash water on the insulation, motor, wiring, or
air filter(s). If the drain trough is restricted,
snake" or similar probe device.
IGNITION
MODULE
\
clear it with a "plumbers
INDUCED
DRAFT
!
MOTOR
MOUNT
\\\\
¢3
LIMITSWITCH
Remove
unitaccess
panel.
Limitswitch
islocated
ontheblower
partition.
BURNER
IGNITION
Unitisequipped
withadirect
spark
ignition
100percent
lockout
system.
Ignition
module
islocated
inthecontrol
box(See
Fig.
18).Module
contains
aself-diagnostic
LED.During
servicing,
refer
tolabel
diagram
forLEDinterpretation.
If lockout
occurs,
unitmayberesetby eithermomentarily
interrupting
power
supply
tounitorbyturning
selector
switch
to
OFFposition
atthethermostat.
MAINBURNERS
Atthebeginning
ofeach
heating
season,
inspect
fordeterioration
or
blockage
due
tocorrosion
orother
causes.
Observe
themain
burner
flames
andadjust,
ifnecessary.
Removal
COLLECTOR
BOX
the gas train for servicing:
1. Shut off main gas valve.
2. Shut off power to unit and install lockout
3. Remove
tag.
unit access panel (See Fig. 19).
4. Disconnect
gas piping
at unit gas valve.
5. Remove
wires connected
6. Remove
ignitor
7. Remove
the mounting
to gas valve.
Mark each wire.
and sensor wires at the ignitor
screw that attaches
module.
the burner rack to
the unit base (See Fig. 18).
8. Slide the burner
9. To reinstall,
rack out of the unit (See Fig. 18 and 21).
reverse the procedure
OUTDOOR
COIL,
DRAIN PAN
INDOOR
Inspect
coil. evaporator
the condenser
COIL,
outlined
AND
above.
CONDENSATE
coil, and condensate
BLOWER
HOUSING
BURNER
RACK
MOUNTING
SCREW
A05119
Fig. 18 - Blower
of Gas Train
To remove
ROLLOUT
SWITCH
i
drain
pan at least once each year.
The coils are easily cleaned when dry: therefore, inspect and clean
the coils either before or after each cooling season. Remove all
24
Housing
and Flue Collector
Box
FRONT
ACCESS
RANEL
A05127
Fig. 19 - Unit Access
Panel
C99086
Fig. 21 - Burner
OUTDOOR
Rack
Removed
FAN
HOUSING
UNIT
OPERATION
Failure to follow
components.
(HIDDEN)
1. Remove
cover.
2. Turn
6 screws
to unit
4.
C99085
Wheel
5.
the fan
If fan needs
shaft.
When
replacing
be visible)
6. Ensure
7. Replace
25
and
grille
upside
down
and
on
motor
top
to top
cover
to
for cracks
loosen
fan blade,
setscrew
setscrew
position
the motor
Fig.
or bends.
end
blade
(1/8
and slide
so that
in. of motor
fan off
the hub
shaft
is
will
12).
engages
the fiat area
on the motor
shaft
tightening.
ELECTRICAL
to turn
blades
from
(See
that
when
sure
assembly
to be removed,
motor
1/8 in. away
Inspect
outdoor
fan blade.
3. Inspect
and Blower
may result in damage
holding
motor/grille
expose
of Motor
this caution
Keep the condenser fan free from all obstructions
to ensure
proper cooling operation. Never place articles on top of the
unit.
2 SETSCREWS
Fig. 20 - Removal
HAZARD
grille.
CONTROLS
check
off
the
AND
electrical
the electrical
power
WIRING
controls
and
to the unit.
wiring
annually.
Be
Remove
access panel to locate all the electrical
and wiring.
If oil is detected
or if low performance
is suspected,
refrigerant tubing using an electronic leak detector,
solution.
If a refrigerant
leak is detected,
refer
disassemble the connection,
clean all the parts, re-strip
and reassemble the connection properly and securely.
Refrigerant
After inspecting
n
controls
Check all electrical connections
for tightness. Tighten all screw
connections.
If any smoky or burned cnnnections
are noticed,
the electrical
controls
and wiring,
the wire end
replace
Leaks
leak test all
or liquid-soap
to Check for
section.
If no refrigerant leaks are found and low performance
is suspected,
refer to Checking
and Adjusting
Refrigerant
Charge section.
all the
panels. Start the unit, and observe at least one complete cooling
cycle to ensure proper operation.
If discrepancies
are observed in
INDOOR
operating cycle, or if a suspected malfunction
has occurred, check
each
electrical
component
with
the
proper
electrical
instrumentation.
Refer to the unit wiring label when making these
checks.
The heating
REFRIGERANT
METERING
AIRFLOW
and/or cooling airflow does not require checking
unless
improper performance
is suspected. If a problem exists, be sure that
all supplyand return-air
grilles are open and free from
obstructions,
and that the air filter is clean.
CIRCUIT
Refrigerant
distributor
Inspect all refrigerant tubing connections
and the unit base for oil
accumulation
annually.
Detecting
oil generally
indicates
a
refrigerant leak.
LIQUID
DEVICES-ACCURATER
metering
assembly
PISTON
device is a fixed orifice and is located
to the indoor coil.
in the
LINE STRAINER
The liquid line strainer (to protect metering device) is made of wire
mesh and is located in the liquid line on the inlet side of the metering
device.
EXPLOSION,
PERSONAL
INJURY
Failure to follow
this warning
damage, personal injury or death.
could
HAZARD
result
TROUBLESHOOTING
in property
Refer
to
the Troubleshooting
troubleshooting
information.
System under pressure.
Relieve
pressure
and recover all
refrigerant before system repair or final unit disposal. Use all
service ports and open all flow-control
devices, including
solenoid valves.
START-UP
Use the Start-Up
26
Checklist
Chart
(Table
CHECKLIST
at the back of this manual.
10-12)
for
Table
lO--T_oubleshooting
SYMPTOM
Chart
CAUSE
REMEDY
Power failure
Call power company
Replace fuse or reset circuit breaker
Fuse blown or circuit breaker tripped
Compreeeor
and
eoadeneer
fan
wiiI not
Defective eontactor, transformer, or high-pressure,
loss-of-charge
or low-pressure switch
Replace component
Insufficient
Determine cause and correct
etart,
line voltage
Incorrect or faulty wiring
Check wiring diagram and rewire correctly
U! setting too high
Lower Ut temperature
perature
Faulty wiring or loose connections
cuit
Compreeeor
rune
will
not
start
but
eoadeneer
fan
in compressor
Determine cause
Defective run/start capacitor, overload, start relay
Determine cause and replace
Replace fuse or reset circuit breaker
Determine cause
power dead
low
Correct the direction of rotation by reversing the
eeroll eompraeaor
exeeeaive
preaaara
aoiae_
and
thera
may
be a
Scroll compressor
is rotating in the wrong direction
differential
Refrigerant
overcharge
or undercharge
Defective compressor
Compreeeor
isfying UI)
Compreeeor
cycles
(other than
operates
normally
aontinuouely
sat-
Defective run/start capacitor
Determine cause and replace
Faulty outdoor fan motor or capacitor
Restriction in refrigerant system
Replace
Locate restriction and remove
Dirty air filter
Unit undersized for load
Replace filter
Decrease load or increase
U! temperature
set too low
Reset UI
Low refrigerant
charge
Locate leak, repair, and recharge
Recover refrigerant, evacuate system, and recharge
Clean coil or remove restriction
coil dirty or restricted
Dirty air filter
Condenser
Exceaeive
eLfCtion
praaaura
air restricted
Recover excess
or air short-cycting
Check for leaks, repair, end recharge,
Remove restriction
High heat load
Compressor valves leaking
Cheek for source and eliminate
Refrigerant
Recover excess refrigerant
Replace compressor
overcharged
Metering device or low side restricted
praeeLfra
tOO
lOW
refrigerant
Recover refrigerant, evacuate system, and recharge
Determine cause and correct
Low refrigerant charge
Restriction in liquid tube
Dirty air filter
Low refrigerant charge
Suction
unit size
Replace filter
Clean coil
Dirty condenser coil
Refrigerant overcharged
Air in system
too low
Recover refrigerant, evacuate system, and recharge to capacities shown on rating plate
Replace and determine cause
Determine cause end correct
Determine cause and correct
Outdoor
Head praeeura
3-phase power leads to the unit, Shut down unit
to allow pressures to equalize,
Insufficient line voltage
Blocked outdoor coil
Air in system
Exceaeive head praeeura
Replace compressor
Determine cause and correct
Low input voltage (20% low)
Feakee
Check wiring and repair or replace
Compressor motor burned out, seized, or
internal overload open
One leg of 3-phase
Thrae-phaee
cir-
setting below room tem-
Insufficient
evaporator
airflow
Temperature too low in conditioned
Outdoor ambient below 55"F
Filter drier restricted
area
Replace filter
Check for leaks, repair and recharge
Remove source of restriction
Increase air quantity
Check filte_replace
if necessary
Reset UI
Install low-ambient kit
Replace filter
27
I!
Table
11
Troubleshooting
SYMPTOM
Gulde=Heating
CAUSE
REMEDY
Water in gas line
Drain, Install drip leg.
Check power supply fuses, wiring or circuit
breaker,
No power to furnace
No 20-v
Burners
will not ignite
Check transformer.
NOTE: Some transformers have internal overcurrent protection that requires a cool-down peg
od to reset.
power suppmy to contr@ circuit
Mis-wired
or loose connections
Check all widng and wire nut connections
Check flame ignition and sense electrode positioning.
Adiust as necessary,
1. Check gas line for air, Purge as necessary.
NOTE: After purging gas line of air, wait at least 5
minutes for any gas to dissipate before attempting to light unit.
2. Check gas valve.
Misaligned spark electrodes
No gas at main burners
Dirty air filter
Clean or replace filter as necessary
Check gas pressure at manifold match with that
on unit namepmate
Gas input to furnace too low
Inadequate
Poor flame
heating
Unit undersized for application
Restricted airflow
Replace with proper unit or add additional unit
Clean or replace filter, Remove any restriction,
Limit switch cycles main burners
Check rotation of blower, temperature
Adiust as necessary,
1. Tighten all screws around burner compartment
2. Cracked heat exchanger. Replace,
3. Unit over-fired. Reduce input (change orifices
or ad}ust gas line or manifold pressure),
4. Check burner alignment,
5. Inspect heat exchanger for bbckage. Clean
as necessary,
Incomplete combustion results in: Aldehyde odors,
carbon monoxide, sooting flame, floating flame
characteristics
Table
12
SYMPTOM
Xi_ubleshooting
CAUSE
Guide--LED
En-or
rise of unit.
Codes
REMEDY
Loss of power to control module (IGO)*.
Check 5-amp fuse son IGC*, power to unit, 24-v circuit
breaker, and transformer. Units without a 24-v circuit
breaker have an internal overload in the 24-v transformer.
If the overload trips, allow 10 minutes for automatic reset.
High limit switch opens during heat exchanger
warm-up period before fan-on delay expires.
Limit switch opens within three minutes after
blower-off delay timing in heating mode,
Ensure unit is fired on rate; ensure temperature rise is correct, Ensure unit's external static pressure is within application guidelines,
Limit switch faults
(LED 2 flashes)
High temperature
Check the operation of the indoor (evaporator) fan motor,
Ensure that the supply-air temperature rise is in accordance with the range on the unit nameplate, Clean or replace filters,
Flame sense fault
(LED 3 flashes)
The IGC* sensed flame that should not be present.
Hardware failure
(LED OFF)
Fan ON/OFF
delay modified
(LED/FLASH)
4 consecutive
limit switch
(LED 4 flashes)
limit switch is open.
faults
Ignition lockout
(LED 5 flashes)
Inadequate
Induced-draft
motor
(LED 6 flashes)
fault
Check the operation of the indoor (evaporator) fan motor
and that supply-air temperature rise agrees with range on
unit nameplate information,
airflow to unit.
Unit unsuccessfully
utes,
Reset unit. If problem persists, replace control board.
attempted ignition for 15 min-
IGC does not sense that induced-draft
operating,*
motor is
Check ignitor and flame sensor electrode spacing, gaps,
etc, Ensure that fame sense and ignition wires are propedy
terminated. Verify that unit is obtaining proper amount of
gas.
Check for proper voltage. If motor is operating, check the
speed sensor plug/IGC Terminal J2 connection, Proper
connection:
PIN 1 - White
PIN 2 - Red
PIN 8 - Black
Rollout switch will automatically
reset, but IGC* will contin-
Rollout switch fault
(LED 7 flashes)
Rollout switch has opened,
ue to lockout unit, Check gas valve operation. Ensure that
induced-draft blower wheel is properly secured to motor
shaft. Inspect heat exchanger, Reset unit at unit disconnect,
Internal control
(LED 8 flashes)
Microprocessor has sensed an error in the software or hardware,
If error code is not cleared by resetting unit power, repmace
the IGC*,
Electrical interference
Reset 24-v, to control board or turn thermostat off, then on
again. Fault will automatically reset itself in one (1) hour.
fault
Temporary software
(LED 9 flashes)
WARNING
_
lockout
impeding IGC software
: If the IGC must be replaced, be sure to ground yoreself to dissipate any electrical charge that my be present before handling
sensitive to static electricity and my be damaged if the necessary precautions are not taken.
IMPORTANT:
Refer to Table 12 Troubleshooting
Guide Heating for additional troubleshooting
LEGEND
IGC--tntegrated
LED
Gas Unit Controller
Light Emitting Diode
28
analysis.
new control board. The IGC is
START-U P CHECKLIST
(Remove and Store in Job File)
I.Preliminary
mnformation
MODEL
NO.:
SERIAL
NO.:
DATE:
TECHNICIAN:
II, PRE=START-UP
(mnsert ¢heckmark
in box as each item ia completed)
() VERIFY THAT ALL PACKING MATERIALS
HAVE BEEN REMOVED
FROM
( ) REMOVE
ALL SHIPPING
HOLD
DOWN
BOLTS
CONNECTIONS
AND
BRACKETS
( ) CHECK
ALL ELECTRICAL
( ) CHECK
( ) CHECK
GAS PIPING FOR LEAKS (WHERE APPLICABLE)
THAT INDOOR
(EVAPORATOR)
AIR FILTER IS CLEAN
( ) VERIFY
THAT
( ) CHECK
FAN WHEEL,
UNIT INSTALLATION
AND
AND TERMINALS
AND
FOR LOCATION
IN HOUSING/ORIFICE
ELECTRICAL
SUPPLY VOLTAGE
COMPRESSOR
AMPS
FAN AMPS
OUTDOOR
(CONDENSER)
AIR TEMPERATURE
RETURN-AIR
TEMPERATURE
DB
REFRIGERANT
REFRIGERANT
TEMPERATURE
MEASURED
*Measured
tMeasured
RISE
IN.WG
PSIG SUCTION
PSIG
CHARGE
RISE
(See Literature)
TEMPERATURE
WB
IN.WG
SUCTION
DISCHARGE
( ) VERIFY
REFRIGERANT
GAS HEAT TEMPERATURE
DB
WB
DB
PRESSURES
GAS iNLET PRESSURE
GAS MANIFOLD
PRESSURE
IN PLACE
IS LEVEL
PROPELLER
COOLING
SUPPLY AIR
GAS HEAT SUPPUY' AIR
INSTRUCTIONS
FOR TIGHTNESS
III, START-UP
INDOOR (EVAPORATOR)
TEMPERATURES
UNIT
PER INSTALLATION
USING
LINE TEMP*
DISCHARGE
CHARGING
TEMPt
CHARTS
RANGE
RISE
at suction inlet to compressor
at liquid line leaving condenser.
2g
AND
SETSCREW
TIGHTNESS
g
Payne
Heating & Cooling
Manufacturer
reserves
Systems * 7310 W. Morris St. * indianapolis,
the right to change_ at any time_ specifications
IN 46231
and designs
Printed in U.S.A
without
notice
and without
3O
Edition
obligations,
Date: 03/07
Catalog No: IM-PY3P-05
Replaces:
IM-PY3P-O4
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 30 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Jun 29 00:43:28 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools