Fire alarm system
EBL512
1548, 1549 and 1550

•
•

EBL512 -- an intelligent analog addressable fire alarm system
Up to 512 addresses per control and indicating equipment (c.i.e.)

•

TLON network for up to 30 c.i.e.:s

Analog addressable system

Up to 512 addresses

EBL512 is an intelligent analog addressable
fire alarm system, conforming to the EN54-2
and –4 standards.

EBL512 has the capacity of connecting 512
addresses. Basic configurations 128, 256 or
512 addresses. Can be upgraded on site.
Each c.i.e. has four COM loops for
connection of up to 512 loop units. Each
addressable loop unit uses one address.
Some loop units that can be connected:
• Analog detectors (sensors)
• Addressable manual call points
• Addressable short circuit isolators
• Addressable input and output units
• Addressable sirens & sounder bases
• Addressable external power supply units
• Conventional detectors and manual call
points

Features / functions
The fire alarm system EBL512 meets the
most stringent requirements relating to fire
detection and alarm.
A user-friendly PC software Win512 is used
for site specific data editing, download,
backup and SW download.
Some features / functions:
• Adaptation of each analog detector's
alarm level in relation to its contamination. Service signal when required.
• Algorithms for filtering and alarm, to
reduce nuisance alarms. Algorithm for
faster detection of smouldering fires.
• Functions, customer related: Test mode,
alert annunciation, disablements, etc.
• Functions: Fire door closing, interlocking combinations of outputs &
inputs, time channels, alarm delay, twounit dependence, user definable text
message for each alarm point, etc.
• Programmable inputs and outputs and
a large number of trigger conditions.
• Expansion boards (options) with zone
line inputs or relay outputs.
• Interface (option) for ext. Fire brigade
panels, alert annunciation units, data
converters, etc.

TLON Network
Up to 30 EBL512 c.i.e.:s can be connected
to a TLON network. A TLON connection
board 1590 is then required in each c.i.e.

Miscellaneous
EBL512 has space in the cabinet for two
sealed Lead Acid 24 (27) Ah batteries.
In each c.i.e. can be mounted up to six
expansion boards 1580-1587. The ext. FBPs
182x and the Alert Annunciation units 173x,
shall be connected via a 1587 board.
One Web-server II 1598 (option) connects
the EBL512 system to Internet / an Intranet
(LAN).

Panasonic Electric Works Fire & Security Technology Europe AB
Citadellsvägen 23, SE-211 18 Malmö, Sweden
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99
info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com

Type numbers

1548
1549
1550

EBL512 c.i.e., excl. printer, configured for 128, 256 or 512 addresses.
EBL512 c.i.e., incl. printer, configured for 128, 256 or 512 addresses.
EBL512 c.i.e., excl. front panel, excl. printer, configured for 128, 256 or 512
addresses.
Printer board (option for 1548).
Cabinet for drawings.
8 zones expansion board (8 zone line inputs for conventional detectors).
8 relays expansion board (8 programmable relay outputs).
External FBP interface board (for connection of data converters and the "older"
types of ext. FBPs).
German FBP interface board (for connection of a "Feuerwehr-Bedienfeld", incl.
a VdS Standardschnittstelle "Löschen").
Autronica interface board (for connection of Autronica, BS100 units).
Connection cable (male-male) for the 1580-1587 boards (no. 1->2 and no. 5->6).
Connection cable (female-female) for the 1580-1587 boards (no. 3->4).
External FBP / DU interface board (for connection of the newest types of display
units, e.g. ext. FBPs (1826 / 1828) and Alert Annunciation units (1735 /1736).
TLON connection board (for TLON network). One board in each c.i.e.

1558
1572
1580
1581
1582
1583
1584
1585
1586
1587
1590

Technical data
Voltage
primary (V AC)
secondary system (V DC)
Current consumption (mA)
Ambient temperature (°C)
operating
storage

230
24
Depending on type (1548-1550), expansion board(s), etc. See EBL512
Planning Instructions.
0 to +40
-40 to +70

Ambient humidity (% RH)

max. 90, non-condensing

Ingress Protection rating (estimated)

IP32

Inputs

4 COM loops for 128, 256 or 512 addresses
4 programmable

Outputs

4 programmable supervised voltage outputs
2 programmable relay outputs
Relay outputs for routing equipment (Fire brigade tx and Fault tx)
Power supply (24 V DC) for routing equipment and external equipment

Size W x H x D (mm)

400 x 610 x 175

Weight (kg)

1548: 17.6 / 1549: 18 / 1550: 17.4

Colour (metal cabinet)

Light grey (NCS S1500-N, PMS Cool Grey 2)

Approvals

CE; Conforms with EN54-2 and -4. The front conforms with SS3654.

Note! All voltages are nominal.

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.

Product Leaflet

Date of issue

Revision / Date of revision

MEW00006

2000-05-12

6 / 2008-01-24



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Page Count                      : 2
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:a9e50b72-cb56-447d-809a-5ca08de24818
Producer                        : Acrobat Distiller 6.0.1 (Windows)
Creator Tool                    : PScript5.dll Version 5.2
Modify Date                     : 2008:01:24 09:31:10+01:00
Create Date                     : 2008:01:24 09:31:10+01:00
Document ID                     : uuid:cd2d8df2-e13e-4309-9e0d-ac3aa9ea95ba
Format                          : application/pdf
Title                           : Microsoft Word - MEW00006rev6.doc
Creator                         : PetterssonJ
Author                          : PetterssonJ
EXIF Metadata provided by EXIF.tools

Navigation menu