APPLICATION: Quadcast luminaires are designed for outdoor, wet location use
not to exceed 40˚C ambient. Approved for ceiling/surface, parking garage, canopy,
stairwell, low bay and rigid and free swing pendant applications.
NOTE: DO NOT REMOVE LED OPTICAL PANELS, WET LOCATION GROMMETS, OR
FLEXIBLE CORD GLANDS.
TOOLS REQUIRED:
Phillips tip screwdriver, electrical wiring tools, 9/64" Allen® Head Key, wet location
UL Listed wiring connectors, UL Listed wet location junction box (For pendant mount
applications).
ALIGNMENT GUIDE (PARKING GARAGE INSTALLATION):
Align quick mount plate to junction box by aligning arrows with parking garage
driving lanes (FIG. 3). Direction of arrows should be in line with direction of traffic.
CEILING/JUNCTION BOX INSTALLATION:
1. Loosen (do not remove) the two locking screws (FIG. 1). Pivot both locking hinges
out to the left/right sides until they stop.
2. Slide quick mount plate forward until the plate disengages from the housing
(FIG. 2).
3. Unhook quick mount plate from the wire hinge (FIG. 3).
4. Install the quick mount plate onto a wet location junction box (SUPPLIED BY
OTHERS) using the hardware supplied (#8-32x3/4" or #6-32x3/4" screws).
See alignment guide above and the alignment arrows on the quick mount
plate label. (FIG. 3).
5. Hang the luminaire to the quick mount plate by the wire hinge (FIG. 3A).
CAUTION: PLEASE ENSURE WIRE HINGE IS SEATED WITHIN BOTH OF THE
QUICK MOUNT PLATE RETENTION HOOKS. FAILURE TO DO SO MAY RESULT IN
PERSONAL INJURY OR PROPERTY DAMAGE.
ADH120932
Customer First Center
1121 Highway 74 South
Peachtree City, GA 30269
P: 770.486.4800 F: 770.486.4801
www.cooperlighting.com
QuadcastTM LED
Parking Garage/Canopy
Luminaire
Sheet 1 of 2
7/6/2012 IMI-775
SAFETY: This fixture must be wired in accordance with the National Electrical Code
and applicable local codes and ordinances. Proper grounding is required to insure
personal safety. Carefully observe grounding procedure under installation section.
WARNING: Make certain power is OFF before starting installation or attempting any
maintenance. Risk of fire/electric shock. If not qualified, consult an electrician.
RISK OF ELECTRIC SHOCK—Disconnect power at fuse or circuit breaker before
installing or servicing.
• RISK OF BURN—Disconnect power and allow xture to cool before servicing.
RISK OF PERSONAL INJURY—Fixture may become damaged and/or unstable if
not installed properly. Tighten all fixture components to their recommended torque
values.
INSTALLATION INSTRUCTIONS
IMPORTANT: READ BEFORE INSTALLING FIXTURE.
RETAIN FOR FUTURE REFERENCE.
WARNING: Make certain power is OFF before starting installation or attempting any maintenance.
These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every possible
contingency during installation, operation or maintenance. When additional information is desired to satisfy a problem not covered sufciently for user’s purpose, please contact
your nearest representative. NOTE: Specications and dimensions subject to change without notice.
—continued
FIG. 1
Locking
Screw
Locking
Screw
Locking
Hinge
Locking
Hinge
Quick Mount Plate
FIG. 2
Slide Quick
Mount Plate
FIG. 3
Locking
Screw
Locking
Screw
Locking
Hinge
Locking
Hinge
Wire Hinge
Quick Mount Plate
Wet Location
Junction Box
(Supplied by Others)
Housing
Plate
Align Arrows with
Driving Lane
Alignment Guide Label
FIG. 3A
Wire Hinge
Retention Hooks
Make electrical connections (FIG. 4).
NOTE: ENSURE WIRING IS CENTERED THROUGH WIRE HINGE.
a. Connect supply side line voltage wire to black lead.
b. Connect supply side neutral wire to white lead.
c. Connect supply side ground wire to green lead.
NOTE: INSTALLER MUST USE UL LISTED WET LOCATION APPROVED WIRING
CONNECTIONS INSIDE UL LISTED WET LOCATION JUNCTION BOX (SUPPLIED BY
OTHERS).
6. After electrical connections are made, push the wire splices through the center
hole of the quick mount plate. Swing and lift the luminaire into position while
maintaining tension on wire hinge. FAILURE TO MAINTAIN TENSION MAY RESULT
IN THE WIRE HINGE BECOMING DISLODGED. The metal tabs on the quick mount
plate will align with openings in the housing plate. With luminaire lifted in place,
slide the luminaire in the direction of the locking hinges. A “click” sound will
occur when the luminaire is fully seated.
7. Pivot both locking hinges back into place and tighten locking screws to
10 inch-pounds (FIG. 5).
RIGID OR FREE-SWING PENDANT INSTALLATION:
1. Install UL Listed wet location junction box (SUPPLIED BY OTHERS) to pendant pipe
(SUPPLIED BY OTHERS) and run supply wires down through pendant pipe and into
wet location junction box (Per NEC Guidelines).
2. Refer to CEILING/JUNCTION BOX INSTALLATION steps above to install.
LED OPTICAL ROTATION (FIG. 6)
The LED optical panels can be rotated to provide a range of lighting distributions.
1. Loosen the 9/64" Allen Head set screw to allow rotation of the LED optical
panel to the desired position.
2. Tighten set screw to 15 inch-pounds once desired angle is achieved.
MAINTENANCE
A regular maintenance schedule should be followed to retain optimal
light output and thermal performance. Optical lens cleaning should
be performed with a clean dry cloth to remove any dust or other
contaminants. Additional cleaning can be performed with
non-abrasive acrylic cleaning solution.
OPTIONAL FIELD INSTALLED ACCESSORIES (ORDER SEPARATELY)
ADH120932
Customer First Center
1121 Highway 74 South
Peachtree City, GA 30269
P: 770.486.4800 F: 770.486.4801
www.cooperlighting.com
QuadcastTM LED
Parking Garage/Canopy
Luminaire
Sheet 2 of 2
7/6/2012 IMI-775
INSTALLATION INSTRUCTIONS
IMPORTANT: READ BEFORE INSTALLING FIXTURE.
RETAIN FOR FUTURE REFERENCE.
WARNING: Make certain power is OFF before starting installation or attempting any maintenance.
These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every possible
contingency during installation, operation or maintenance. When additional information is desired to satisfy a problem not covered sufciently for user’s purpose, please contact
your nearest representative. NOTE: Specications and dimensions subject to change without notice.
FIG. 4
FIG. 5
Locking
Screws
FIG. 6
Set Screw
Angle
Indicator
11
10
9
8
765
4
3
2*
1
Set Screw
Location Angle
of Degrees Location Angle
of Degrees
Factory
Pre-set* 15° 6 75°
1 7 90°
215° 8 105°
3 30° 9 120°
4 45° 10 135°
5 60° 11 150°
PENDANT BIRD GUARD (QDPBG)
Pendant
(Supplied by
Others) Bird Guard
OCCUPANCY SENSOR (QDOCC)
Occupancy
Sensor

Navigation menu