340557RevC Installation Directions

2016-06-25

: Pdf 1000308602-Installationsheet 1000308602-InstallationSheet B1 unilog

Open the PDF directly: View PDF PDF.
Page Count: 2

• To prevent severe shock or electro-
cution, always turn the power OFF
at the service panel before working
with wiring.
• Use this GFCI receptacle with
copper or copper-clad wire. Do not
use it with aluminum wire.
• Do not install this GFCI receptacle
on a circuit that powers life support
equipment because if the GFCI
trips, it will shut down the
equipment.
• For installation in wet locations,
protect the GFCI receptacle with a
weatherproof cover that will keep
both the receptacle and any
plugs dry.
• Must be installed in accordance
with national and local electrical
codes.
Please read this leaflet
completely before
getting started.
3. Should you install it?
Installing a GFCI receptacle can be
more complicated than installing a
conventional receptacle.
Make sure that you:
Understand basic wiring principles
and techniques.
Can interpret wiring diagrams.
Have circuit wiring experience.
Are prepared to take a few minutes
to test your work, making sure that
you have wired the GFCI receptacle
correctly.
4. LINE vs. LOAD
A cable consists of 2 or 3 wires.
LINE cable:
Delivers power from the service panel
(breaker panel or fuse box) to the
GFCI. If there is only one cable enter-
ing the electrical box, it is the LINE
cable. This cable should be connected
to the GFCI’s LINE terminals only.
LOAD cable:
Delivers power from the GFCI to
another receptacle/outlet in the circuit.
This cable should be connected to
the GFCI’s LOAD terminals only. The
LOAD terminals are under the yellow
sticker. Do not remove the sticker at
this time.
6. Identify cables/wires
IMPORTANT:
Do not install the GFCI receptacle in an
electrical box containing (a) more than
4 wires (not including the ground wires)
or (b) cables with more than two wires
(not including the ground wire). Contact
a qualified electrician if either (a) or
(b) is true.
If you are replacing an old recepta-
cle, pull it out of the electrical box
without disconnecting the wires.
If you see one cable (2-3 wires), it is
the LINE cable. The receptacle is
probably in position C (see diagram
to the right). Remove the receptacle
and go to step 7A.
If you see two cables (4-6 wires), the
receptacle is probably in position A or
B (see diagram to the right). Follow
steps a-e of the procedure to
the right.
RESET
RESET
TEST
TEST
Procedure: box with two cables
(4-6 wires)
(a) Detach one cable’s white and hot
wires from the receptacle and cap
each one separately with a wire
connector. Make sure that they are
from the same cable.
(b) Reinstall the receptacle in the
electrical box, attach the wall plate,
then turn the power ON at the
service panel.
(c) Determine if power is flowing to the
receptacle. If so, the capped wires
are the LOAD wires. If not, the
capped wires are the LINE wires.
(d) Turn the power OFF at the service
panel, label the LINE and LOAD
wires, then remove the receptacle.
(e) Go to step 7B.
Placement in circuit:
The GFCI’s place in the circuit
determines if it protects other
receptacles/outlets in the circuit.
Sample circuit:
Placing the GFCI in position A will
also provide protection to “load side”
receptacles/outlets B and C. On the
other hand, placing the GFCI in posi-
tion C will not provide protection to
receptacles/outlets A or B. Remember
that receptacles/outlets A, B, and C can
be in different rooms.
1. What is a GFCI?
A GFCI receptacle is different from
conventional receptacles. In the event
of a ground fault, a GFCI will trip and
quickly stop the flow of electricity to
prevent serious injury.
Definition of a ground fault:
Instead of following its normal safe
path, electricity passes through a per-
son’s body to reach the ground.
For example, a defective appliance
can cause a ground fault.
A GFCI receptacle does not protect
against circuit overloads, short circuits,
or shocks. For example, you can still
be shocked if you touch bare wires
while standing on a non-conducting
surface such as a wood floor.
5. Turn the power OFF
Plug an electrical device, such as a
lamp or radio, into the receptacle on
which you are working. Turn the lamp
or radio on. Then, go to the service
panel. Find the breaker or fuse that
protects that receptacle. Place the
breaker in the OFF position or com-
pletely remove the fuse. The lamp or
radio should turn OFF.
Next, plug in and turn ON the lamp or
radio at the receptacle’s other outlet to
make sure the power is OFF at both
outlets. If the power is not OFF, stop
work and call an electrician to com-
plete the installation.
2. The GFCI’s features
Cable Wires
ABC
LINE
LOAD
Service
Panel
LOAD
LINE LINE
LINE
LOAD
WHITE
HOT
WHITE
HOT
FRONT VIEW BACK VIEW
Receptacle
Outlet
TEST button:
See step 8
Trip Indicator
Light (optional)
Reset button:
See step 8
Outlet
Mounting
bracket
Screw (terminal) colors:
Green = ground terminals
Silver = white terminals
Brass = hot terminals
LINE
Hot terminal (Brass):
Connection for the LINE
cable’s black wire
LOAD
Hot terminal (Brass):
Connection for the LOAD
cable’s black wire
A yellow sticker covers
the LOAD terminals.
Do not remove the sticker
at this time.
Ground terminal (Green):
Connection for bare
copper or green wire
LINE
White terminal (Silver):
Connection for the
LINE cable’s white wire
LOAD
White terminal (Silver):
Connection for the
LOAD cable’s white wire
Installing and
Testing a
GFCI Receptacle
15A 120V 60Hz
20A 120V 60Hz
CAUTION
If you do not fully understand
these instructions, you should
seek the assistance of a
qualified electrician.
P.O. Box 4822
Syracuse, NY 13221 (800) 223-4185
Part No. 340557 Rev. C
!
LIMITED ONE YEAR WARRANTY
Pass & Seymour will remedy any defect in workmanship or material in Pass & Seymour products which may develop under proper and nor-
mal use within one year from date of purchase by a consumer:
(1) by repair or replacement, or, at Pass & Seymour’s option, (2) by return of an amount equal to consumer’s purchase price. Such remedy
is IN LIEU OF ANY AND ALL EXPRESSED OR IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PUR-
POSE. Such remedy by Pass & Seymour does not include or cover cost of labor for removal or reinstallation of the product. ALL OTHER
FURTHER ELEMENTS OF DAMAGE (INCIDENTAL OR CONSEQUENTIAL DAMAGES) FOR BREACH OF ANY AND ALL EXPRESSED
OR IMPLIED WARRANTIES INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE
EXCLUDED HEREBY. (Some states do not allow disclaimers or exclusion or limitation of incidental or consequential damages, so the above
disclaimer and limitation or exclusion may not apply to you.) ANY IMPLIED WARRANTIES INCLUDING WHERE REQUIRED WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE SHALL BE LIMITED TO THE ONE YEAR PERIOD SET FORTH
ABOVE. (Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.)
To insure safety, all repairs to Pass & Seymour products must be made by Pass & Seymour, or under its specific direction. Procedure to obtain
performance of any warranty obligation is as follows: (1) Contact Pass & Seymour, Syracuse, New York 13221, for instructions concerning
return or repair; (2) return the product to Pass & Seymour, postage paid, with your name and address and a written description of the instal-
lation or use of the Pass & Seymour product, and the observed defects or failure to operate, or other claimed basis for dissatisfaction.
This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
LINE
LOAD
WHITE
HOT
WHITE
HOT
About wire connections:
Connect the LINE cable wires to the LINE terminals:
The white wire connects to the White terminal (Silver)
The black wire connects to the Hot terminal (Brass)
Connect the ground wire (only if there is a ground wire):
For a box with no ground terminal (diagram not shown): Connect the LINE
cable’s bare copper (or green) wire directly to the ground terminal on the GFCI
receptacle.
For a box with a ground terminal (diagram shown above): Connect a 6-inch bare
copper (or green) 12 or 14 AWG wire to the ground terminal on the GFCI. Also
connect a similar wire to the ground terminal on the box. Connect the ends of
these wires to the LINE cable’s bare copper (or green) wire using a wire
connector. If these wires are already in place, check the connections.
Complete the installation:
Fold the wires into the box, keeping the ground wire away from the White and
Hot terminals. Screw the receptacle to the box and attach the wall plate.
Go to step 8.
About wire connections:
Connect the LINE cable wires to the LINE terminals:
The white wire connects to the White terminal (Silver)
The black wire connects to the Hot terminal (Brass)
Connect the LOAD cable wires to the LOAD terminals:
Remove the yellow sticker to reveal the LOAD terminals
The white wire connects to the White terminal (Silver)
The back wire connects to the Hot terminal (Brass)
Connect the ground wires as shown above (only if there is a ground wire):
Connect a 6-inch bare copper (or green) 12 or 14 AWG wire to the ground
terminal on the GFCI. If the box has a ground terminal, also connect a similar
wire to the ground terminal on the box. Connect the ends of these wires to the
LINE and LOAD cable’s bare copper (or green) wire using a wire connector. If
these wires are already in place, check the connections.
Complete the installation:
Fold the wires into the box, keeping the ground wire away from the White and
Hot terminals. Screw the receptacle to the box and attach the wall plate.
Go to step 8.
8. Test your work
Why perform this test?
If you miswired the GFCI, it may not prevent personal injury or death due to a
ground fault (electrical shock).
If you mistakenly connect the LINE wires to the LOAD terminals, the GFCI will
still operate like an ordinary receptacle, but it will not interrupt a ground fault.
Procedure:
(a) Turn the power ON at the service panel. Press the RESET but-
ton fully. The RESET button should stay in. If the RESET button
does not stay in, go to Troubleshooting. If the RESET button
stays in, plug a lamp or radio into the GFCI (and leave it
plugged in) to verify that the power is ON. If there is no power,
go to Troubleshooting.
(b) Press the TEST button in order to trip the device. This should
stop the flow of electricity, making the radio or lamp shut OFF
and the GFCI’s red Trip Indicator Light (if present) come on.
Note that the RESET button will pop-out. If the power stays ON,
go to Troubleshooting. If the power goes OFF, you have installed
the GFCI receptacle correctly. To restore power, press the
RESET button.
(c) If you installed your GFCI using step 7B, plug a lamp or radio into
surrounding receptacles to see which one(s), in addition to the
GFCI, lost power when you pressed the TEST button. Do not plug
life saving devices into any receptacles that lost power. Place a
“GFCI Protected” sticker on every receptacle that lost power.
(d) Press the TEST button (then RESET button) every month to
assure proper operation.
7. Connect the wires (choose A or B)…only after reading other side completely
B: Two cables (4 or 6 wires) entering the box
LINE
LOAD
WHITE
HOT
WHITE
HOT
Screw Terminal
Wire 1 inch
Side Wire
Clockwise, 2/3
of the way
around screw
LINE
WHITE
HOT
Back Wire
LINE cable brings
power to the GFCI
Ground connection
to box (if box has a
ground terminal)
Wire
connector
Electrical
box Yellow sticker
remains in place
to cover the
LOAD terminals
LINE cable brings
power to the GFCI
Ground connection
to box (if box has a
ground terminal)
Wire
connector
Electrical
box
LOAD cable feeds power to
other receptacles/outlets
Back Wire Holes
Wire .6 inch
Back Wire Holes
Wire .6 inch
A: One cable (2 or 3 wires) entering the box OR
TROUBLESHOOTING
Turn the power OFF and check the wire connections against the appropriate
wiring diagram in step 7A or 7B. Make sure that there are no loose wires or
loose connections. Also, it is possible that you reversed the LINE and LOAD
connections. LINE/LOAD reversal will be indicated by power remaining ON at
the GFCI and by the RESET button not staying in when pressed. Reverse the
LINE and LOAD connections if necessary. Start the test from the beginning of
step 8 if you rewired any connections to the GFCI.
TEST
TEST
RESET
RESET
TEST
TEST
RESET
RESET
TEST
TEST
RESET
RESET
1. Insert wire
to bottom
of hole.
2. Securely
tighten screw
beneath wire
hole to retain
inserted wire.
Side Wire
Clockwise, 2/3
of the way
around screw
LINE
WHITE
HOT
Back Wire
1. Insert wire
to bottom
of hole.
2. Securely
tighten screw
beneath wire
hole to retain
inserted wire.

Navigation menu