Catalog Number
Notes Type
FEATURES & SPECIFICATIONS
INTENDED USE
The Quick-Flex Starter Fixture Cable is a combination of the QC and QFC. This product wires
directly into a home-run junction box, a switch box or a junction box located above a switch
location; it provides power to the rst xture from the above mentioned locations.
ELECTRICAL
•Rated for use on 20-amp branch circuits.
•All conductors are No. 12 AWG copper with -20°C to +90°C thermoplastic insulation rated
600V.
•All components provide a fully rated No. 12 AWG grounding conductor.
•Fixture leads are No. 18 AWG solid copper with -20°C to +90°C thermoplastic insulation
rated 600V. Prestripped, solid-color leads for easy installation into side, back or push-in-
type terminals. 10 amp max.
•RRL option includes 18 AWG conductors; 3-amp max.
•Safety-keying prevents accidental mating of components with dierent voltages.
SYSTEM FEATURES
•Pin and socket contacts.
•Color-coded labels for quick voltage identication.
•No xture ground lead to connect. Snap-in tting provides ground connection for US only.
•Auto-latching springs for easy male/female connections.
•Available in varying lengths to suit most common xture spacing requirements.
•Cast snap-in connector provided on whip-end for fast, easy installation into a 1/2" trade
size knockout.
•Dustcover available for unused ports: QUICK FLEX DUST COVER J50.
•Green armor standard for easy identication in healthcare facilities.
•Plenum rated.
LISTINGS
•UL Listed to US and Canadian Saftey Standards.
•Built to UL Standard 183 for Manufactured Wiring Systems and suitable for air-handling
spaces above grid ceiling as described in NEC 300.22(C).
•Meets NEC requirements for redundant ground paths for patient care areas in healthcare
1 of 2One Lithonia Way Conyers, GA 30012 Phone: 800-241-4750 Fax: 770-808-8650 www.relocwiring.com © 1996-2014 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/20/14
facilities (HCF option).
•U.S Patent Nos. 6,083,053; 6,102,733; 6,113,435; 6,126,490; 7,021,961.
WARRANTY
•5-year limited warranty. Complete warranty terms located at
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Actual performance may dier as a result of end-user environment and application.
Note: Specications subject to change without notice.
Quick-Flex® Starter Fixture Cable
QSFC
RECESSED CEILING LIGHTING SYSTEM
NOTES
1. Standard lengths listed. Consult factory for customer lengths up to 50ft .
2. G option required for Canada, HCF, and RRL option.
3. If RRL selected, xture must have RRL and wiring instruction. See xture
spec sheet for details. See RRL spec sheet for connector details.
4. RRL option avaiable in lengths up to 35ft.
Example: QSFC120 12/2G09
ORDERING LOGIC
For shortest lead times, congure product using bolded options.
QFSC
Series Voltage Lengths1
Conductors Options
120 120V
277 277V
347 347V
12/2G Two 12 AWG conductors,
plus 12 AWG ground
12/3G Three 12 AWG conductors,
plus 12 AWG ground
09 9 ft.
11 11 ft.
13 13 ft.
15 15 ft.
G18 AWG ground lead dropped to xture2
HCF Meets healthcare facility requirements
RRL RELOC®-ready luminaire3,4
QSFC
QSFC Quick-Flex® Starter Fixture Cable
2 of 2
A – Connector body
B – 18-gauge galvanized steel cover, zinc alloy casting
C – Tin-plated brass contacts
D – No. 18 AWG solid copper wires
E – MC cable standard and HCF MC optional
F – Cast snap-in tting ts 1/2” trade size K.O. and provides ground
connection for US only. G option required for Canada
G – 6" leads prestripped 5/8"; No. 12 AWG with 90°C, 600V insulation
One Lithonia Way Conyers, GA 30012 Phone: 800-241-4750 Fax: 770-808-8650 www.relocwiring.com © 1996-2014 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/20/14
QFSC
Connection above the wall
QFC
QFC
QSFC
QSFC
MC CABLE
(BY OTHERS)
MC CABLE
(BY OTHERS)
MC CABLE
(BY OTHERS)
Connection inside the wall
QFC
QFC
QSFC
QSFC
MC CABLE
(BY OTHERS)
MC CABLE
(BY OTHERS)
MC CABLE
(BY OTHERS)
SYSTEM VIEW
System View designs are for illustrative purposes only.
DIMENSIONS
Dimensions are shown in inches (millimeters)
C
A B
4-1/4
(108)
2-3/4
(70)
1
(25.5)
3/4
(19)
E
DF G
Pin Position / Wire Color
Position 120V 277V 347V
1 Black Brown Black
N White Gray White
G Green Green Green
2 Red Orange Red