GE BuyLog — Section 1 1000318537 Catalog

144021-Brochure 144021-Brochure 144021-Brochure B2 unilog cesco-content

2016-07-29

: Pdf 1000318537-Catalog 1000318537-Catalog B2 unilog

Open the PDF directly: View PDF PDF.
Page Count: 42

Q-Line Circuit Breakers– Product Features and Benefits........1-2
PowerMark Gold Load Centers—
Product Features and Benefits ........................................................1-3
PowerMark Gold and Plus Load Centers—
Product Number Guides......................................................................1-4
Q-Line Plug-in Circuit Breakers............................................................1-5
Special Purpose Circuit Breakers........................................................1-6
PowerMark Gold and Plus Single-Phase Load Centers—
Main Lug Convertible to Main Breaker.........................................1-9
Main Breaker Factory Installed .....................................................1-12
PowerMark PlusThree-Phase Load Centers—
Main Circuit Breakers or Main Lugs Factory Installed .......1-14
PowerMark Gold Load Centers—Specialty Panels...................1-17
PowerMark Gold Meter Socket Load Centers ............................1-18
Field Installed Accessories...................................................................1-24
Wiring Diagrams......................................................................................1-30
Load Centers and Meter Socket Load Centers—
Knockouts................................................................................................1-37
Section 1
Rev. 11/13
Data subject to change
without notice
Load Centers and Circuit Breakers
1-1
BuyLogCatalogwww.geindustrial.com
Section Updated 01 / 2016
Special Purpose Circuit Breakers
—PowerMark Gold Main Circuit Breakers
—Arc Fault Circuit Interrupter
—CB3 Ground Fault Circuit Interrupter
—Switching Neutral
—HID Lighting Breaker
—High Magnetic Breaker
—Molded Case Switch
—Surge Arrester
—TQ Breaker
Copper stabs, tin-plated for corrosion resistance,
make the connection reliable and permanent.
Heat-resistant thermoset cases and covers add
stability and structural rigidity.
Trips are easy to spot because handles trip to the
center position.
The dedicated calibration screw is cemented (not
simply papered over) to prevent shifting. The result is
stable calibration for optimum trip performance.
At 1/2”, THQP breakers are half the width of standard breakers, permitting the use of smaller
load centers that save money and space in both new construction and service upgrades. They
feature the same high-performance design, and meet the same stringent standards as other Q-
Line breakers. Our 1” THQL will remain the breaker of choice for many contractors. In applica-
tions where space and cost are not critical, they’re an excellent choice. But when size and money
are driving considerations, THQP breakers are the smart choice.
Enclosed circuit
breakers make it
easy and efficient
to install exterior
main breakers.
THQLSURGE surge
arresters are easy to
install and protect the
whole house comput-
ers, fax machines, televi-
sions, stereos, VCRs and
other sensitive electronic
equipment – from
destructive surges.
Maximum protection
against all-too-common
electrical fires comes
from the new technology
built into GE’s arc fault
circuit interrupters (AFCIs).
With its ability to detect
and interrupt arcing
caused by damaged wire
insulation or a frayed extension cord, the AFCI takes
home and family protection to a new, higher level.
The NEC requires ground fault protection of receptacles outdoors and
in garages, bathrooms and spa areas. These ground fault circuit
interrupters eliminate the need for separate GFCI receptacles, protect
against short circuits and overloads, and prevent shock by detecting
very low levels of current leaks and immediately shutting off power to
the circuit.
Section 1Load Centers and Circuit Breakers
Q-Line Circuit Breakers
Reliability and Economy
1-2 BuyLogCatalog Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
PowerMark Gold load centers lower your costs by making installa-
tion faster and easier, increasing application flexibility and reduc-
ing inventory requirements. At the same time, they deliver obvious
and significant advances in design, function and quality.
—UL Listed (Panelboards No. 67)
—Suitable for Use as Service Entrance Equipment when installed
in accordance with National Electrical Code
—60°C/75°C Conductor Rating
—Single phase, 40-225A, 2-42 circuits
—Main lug models field convertible to main breaker
—Main breaker 22kAIC standard - factory installed
—All load centers top or bottom feed
—Indoor and outdoor rated enclosures
—Indoor fronts combination surface/flush
—Copper bus with tin plating standard1
—Split neutrals extend the full length of the interior for ease of wiring
—Entire main lug line converts easily to main breaker
—Combination surface/flush front with spring-reinforced pan
—Combination slotted/Robertson square-drive screws on neutral,2
ground, front and breaker lugs
—Front packed in inner carton for added protection
—Field installable feed-through lugs up to 200A
—Straight-through main wiring
—Main breaker is clearly marked and circuit numbers are stamped
on front
—Isolated ground bar is available
—Compact box maintains optimum wire-bending space
Safety accessories convenient and easy to install
—THQLSURGE whole house surge protector
—Arc fault circuit interrupter breaker, 1- or 2-pole
—Ground fault circuit interrupter breaker, 5mA and 30mA
—Generator transfer panel – 30A or 60A, indoor or outdoor
—GE AC disconnects
Packaging features comprehensive
selection and application data.
Fronts are packed in inner cartons
for added protection during shipment
and at the job site.
Main lug load centers offer an economical
solution for subpanels and similar applications.
All main lug units 125A and above convert easily
to main breaker.
GE’s residential load centers reach into
commercial applications as well, with riser
panels, auxiliary gutters, three-phase units
with standard 22kAIC ratings, and all the
accessories needed to complete the job.
The PowerMark Gold
line includes a wide
range of outdoor as
well as indoor units.
A complete family of meter socket load centers — ring style
and ringless, wide and narrow, meter mains, farm panels and
more — deliver specialized solutions for special situations.
Combination
slotted/Robertson
square-drive
speeds screw
wiring
All holes rated
for 14-4 wire
100% rated
split neutral
on each side2
Accepts GE Q-Line branch
circuit breakers, including
GE’s exclusive 1/2" THQPs
Main breaker configura-
tion allows top or bottom
feed without modification
Tie bar may be
removed to split
neutral/ground
One-piece interior
removes and
reinstalls easily
Full-length neutrals
are easier to wire,2
reducing installation
time and cost
Minimum 100%
neutral
terminations
Sturdy copper bus
and galvanized box
increase durability
and reliability
Section 1
Rev. 11/13
Data subject to change
without notice
Load Centers and Circuit Breakers
PowerMark Gold Load Centers
Highest Quality and Convenience
1-3
BuyLogCatalogwww.geindustrial.com
1Three-phase PowerMark Plus load centers have aluminum bus with copper breaker
mounting stabs.
216 circuit and above.
Accessories and Options
—Door lock and handle —Hardware kits
—Equipment ground kits —Main breaker retainers
—Sub-feed and feed-thru lugs —Neutral kits
—Front filler plates —Universal raintight hubs
—Handle lock and ties
Product Number Guide for Load Centers
(Product number for illustrative purposes only)
204 C BCU42MT
GE Identification
Type
M = Main breaker
L = Main lug
LM = Convertible
PL = Main lug (Thermoplastic)
Insert for PowerMark Gold
CU = Copper Bus
42 = Copper Bus Full 42 circuit panel
Maximum Number 1" Spaces
2, 4, 6…42
Insert for 3-Phase 4-Wire
Load Centers
Insert for Specials
G or T = Factory installed ground bar
B = Bottom feed main breaker
FL = Factory installed feed-through lugs
D = Optional door for 6-8 circuit panel.
(Doors standard on all units 12
circuits or greater)
W = White Front
Enclosure Type
C = Combination surface/flush
F = Flush
S = Surface
R = Outdoor
Bus Ampere Rating
40 = 40 Amps 20 = 200 Amps
70 = 70 Amps 22 = 225 Amps
10 = 100 Amps 30 = 300 Amps
12 = 125 Amps 40 = 400 Amps
15 = 150 Amps 60 = 600 Amps
Product Number Guide for Q-Line Plug-in Circuit Breakers
(Product number for illustrative purposes only)
1*1 15QLHT
GE Identification
Interrupting Rating
H = 10kAlC
HH = 22kAlC
X = 65kAlC
Ground Fault/Arc Fault Circuit Interrupter
GF = 1-pole Ground Fault Circuit Interrupter–5 mA
GF1= 2-pole Ground Fault Circuit Interrupter–5 mA
AF = 1- & 2-pole Arc Fault Circuit Interrupter
AF2 = 1- & 2-pole Combination Arc Fault
Circuit Interrupter
GFEP = 1- & 2-pole Ground Fault Circuit
Interrupter–30 mA
GFT = 1- & 2-pole self-test Ground Fault Circuit
Interrupter - 5 mA
Poles (1, 2, 3)
Type
QL = 1" plug-in
QP = 1/2" plug-in
QB = 1" bolt-on Ampere Rating
Voltage
1 = 120/240V
2 = 240V
*Omit character for THQP breakers, which are all 120/240V.
GF
Section 1Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Product Number Guides
1-4 BuyLogCatalog Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
Page Updated 01 / 2016
Load Centers and Circuit Breakers
Q-Line Plug-in Circuit Breakers
UL Listed (Molded Case Circuit Breakers No. 489)
Federal Government Specification Qualified (WC-375B)
60°C / 75°C Conductor Rating
Quick Make, Quick Break
Box Type Terminals
Q-Line Plug-in Circuit Breakers
10,000AIC 22,000AIC 65,000AIC
Type THQP 1/2-inch Module Type THQL 1-inch Module Type THHQL 1-inch Module Type TXQL 1-inch Module
120/240 Vac 120/240 Vac 120/240 Vac 240 Vac 120/240 Vac 240 Vac 120/240 Vac
Ampere Product Product Product Product Product Product
Rating Number Number Number Number Number Number
Single Pole1
152THQP115 THQL1115 – THHQL1115 – TXQL1115
202THQP120 THQL1120 – THHQL1120 – TXQL1120
25 THQP125 THQL1125 THHQL1125 TXQL1125
30 THQP130 THQL1130 THHQL1130 TXQL1130
35 THQP135 THQL1135 THHQL1135 ––
40 THQP140 THQL1140 THHQL1140 ––
45 THQP145 THQL1145 THHQL1145 ––
50 THQP150 THQL1150 THHQL1150 ––
Std. Pkg. 5 cartons of 20 5 cartons of 10 5 cartons of 10 5 cartons of 10
Two-Pole3: Incorporates Internal Common Trip Bar
15 THQP215 THQL2115 THQL220154THHQL2115 THHQL220154TXQL2115
20 THQP220 THQL2120 THQL220204THHQL2120 THHQL220204TXQL2120
25 THQP225 THQL2125 THQL220254THHQL2125 THHQL220254TXQL2125
30 THQP230 THQL2130 THQL220304THHQL2130 THHQL220304TXQL2130
35 THQP235 THQL2135 THQL220354THHQL2135 THHQL220354
40 THQP240 THQL2140 THQL220404THHQL2140 THHQL220404
45 THQP245 THQL2145 THQL220454THHQL2145 THHQL220454
50 THQP250 THQL2150 THQL220504THHQL2150 THHQL220504
60 – THQL2160 THQL220604THHQL2160 THHQL220604
70 – THQL2170 THQL220704THHQL2170 THHQL220704
80 – THQL2180 THQL220804THHQL2180 THHQL220804
90 – THQL2190 THQL220904THHQL2190 THHQL220904
100 – THQL21100 THQL221004THHQL21100 THHQL221004
110 – THQL21110 THHQL21110 ––
125 – THQL21125 THHQL21125 ––
Std. Pkg. 5 cartons of 10 5 cartons of 5 5 cartons of 5 5 cartons of 5 5 cartons of 5 5 cartons of 5
Three-Pole3: Incorporates Internal Common Trip Bar
15 ––THQL32015 THHQL32015 TXQL32015
20 ––THQL32020 THHQL32020 TXQL32020
25 ––THQL32025 THHQL32025 TXQL32025
30 ––THQL32030 THHQL32030 TXQL32030
35 ––THQL32035 THHQL32035 –
40 ––THQL32040 THHQL32040 –
45 ––THQL32045 THHQL32045 –
50 ––THQL32050 THHQL32050 –
60 ––THQL32060 THHQL32060 –
70 ––THQL32070 THHQL32070 –
80 ––THQL32080 THHQL32080 –
90 ––THQL32090 THHQL32090 –
100 ––THQL32100 THHQL32100 –
Std. Pkg. 5 cartons of 3 5 cartons of 3 5 cartons of 3
Q-Line Plug-in Circuit Breakers Specifications
Wire Size AWG/kcmil1
Breaker Type Ampere Rating Cu Al
THQP 15-25 14-8 12-8
30-50 8-4 8-4
THQL 15-30 14-8 12-8
THHQL 35-60 8-3 8-3
TXQL 70-100 6-1/0 4-1/0
110-125 2-2/0 2-2/0
1Solid or stranded for 14-10 AWG
THQP130
THQL2140
THQP230
THQL32015
THQL1120
References:
Accessories Pages 1-24 thru 1-29
Auxiliary Switches and Shunt Trips BuyLog pages 6-40 thru 6-42
1UL Listed as HACR (heating, air conditioning and refrigeration).
2UL Listed as SWD (switching duty). Suitable for 120 volts ac fluorescent lighting
loads.
315-100 amp UL Listed as HACR (heating air conditioning and refrigeration).
4Required for three-phase and High Leg Delta Systems only.
Section 1
Rev. 11/13
Data subject to change
without notice
1-5
BuyLogCatalogwww.geindustrial.com
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLogCatalog
1-6
Load Centers and Circuit Breakers
Special Purpose Circuit Breakers
60°C / 75°F Conductor Rating
Box Type Terminals
Quick-Make, Quick-Break
Multi-pole Breakers Incorporate Internal Common Trip
Section 1
Arc Fault2
UL Listed
Arc-Fault Circuit Interrupters No. 1699 1 Pole, 120/240 Volts ac1
Ampere Rating Product Number
10,000 AIC 15 THQL1115AF2
20 THQL1120AF2
22,000 AIC 15 THHQL1115AF2
20 THHQL1120AF2
Std. Pkg. 10 Cartons of 1
As of Jan. 1, 2008, 2005 NECrequires combination AFCI.
1Combination AFCI compliant with 2008 NECand later
2For 2-Pole shared neutral applications use two 1-pole circuit breakers with a handle tie. See DET-719 for more
details on our Arc Fault products.
Dual Function GFCI/AFCI Ground Fault & Combination Arc Fault Circuit Breaker
UL Listed (Available December 2014) 1 Pole, 120 Volts ac
Ampere Rating Product Number
10,000 AIC 15 THQL1115DF
20 THQL1120DF
22,000 AIC 15 THHQL1115DF
20 THHQL1120DF
Std. Pkg. 10 Cartons of 1
Ground Fault
UL Listed
Ground Fault Circuit Interrupters No. 943.
Class A (5 milliamperes ground fault trip level).
1-Pole, 120 Volts ac 2-Pole, 120/240 Volts ac
Ampere Rating Product Number Product Number
10,000 AIC 15 THQL1115GF THQL2115GF1
20 THQL1120GF THQL2120GF1
30 THQL1130GF THQL2130GF1
40 – THQL2140GF1
50 – THQL2150GF1
22,000 AIC 15 THHQL1115GF
20 THHQL1120GF
30 THHQL1130GF
Std. Pkg. 10 cartons of 1 10 cartons of 1
Ground Fault with Self-Test Feature
cULus
Ground Fault Circuit Interrupters UL943 ed5 (5 milliamperes)
1-Pole, 120 Volts ac 2-Pole, 120/240 Volts ac
Ampere Rating Product Number Product Number
10,000 AIC 15 THQL1115GFT THQL2115GFT
20 THQL1120GFT THQL2120GFT
25 THQL1125GFT THQL2125GFT
30 THQL1130GFT THQL2130GFT
40 – THQL2140GFT3
50 – THQL2150GFT3
22,000 AIC 15 THHQL1115GFT
20 THHQL1120GFT
25 THHQL1125GFT
30 THHQL1130GFT
3UL & CSA
PowerMark Gold Main Circuit Breakers for use with 150A-225A PowerMark Gold Load
Centers (Includes mounting base)
UL Listed.
Description Ampere Rating Product Number Lug Size
100 THQMV100D
125 THQMV125D
Main Circuit Breaker Kits 150 THQMV150D 1-300 (cu),
22,000 AIC 175 THQMV175D 2/0-300
200 THQMV200D
225 THQMV225D
Note: Wire bending rules affect allowed wire sizes when THQMV breakers are installed in an enclosure. For load
centers, the wire range will be on the rating label. In addition, refer to the specifications for the main breaker
versions of the load center you are considering to review allowed wire ranges when a TLMXX20 load center is
converted to main breaker.
THQMV100D with filler plates
Arc Fault
THQL2120GFT
THQL1115DF
THQL1120GF
Page Updated 01 / 2016
PowerMark Gold Main Circuit Breaker Kit
For use with 125A PowerMark Gold load Centers; 22kAIC RMS symmetrical.
Description Product Number
Main Circuit Breaker Kit - Order appropriate THQL TQMH0001
10kAIC or THHQL 22kAIC breakers separately
1Please review the footnotes listed with the individual Load Center product numbers for proper parts needed to
convert to a main circuit breaker. This main breaker base is only applicable for 16 circuit and larger 125 amp load
centers, 12 circuit load centers with A C24 suffix, and the TLM812RCU2.
Ground Fault with Equipment Protection
cULus
Ground Fault Circuit Interrupters No. 943 30 milliampere ground fault trip level
1-Pole, 120 Volts ac 2-Pole, 120/240 Volts ac
Ampere Rating Product Number Product Number
10,000 AIC
15 THQL1115GFEP THQL2115GFEP
20 THQL1120GFEP THQL2120GFEP
30 THQL1130GFEP THQL2130GFEP
Std. Pkg. 10 Cartons of 1 10 Cartons of 1
www.geindustrial.com BuyLogCatalog 1-7
Load Centers and Circuit Breakers
Special Purpose Circuit Breakers
60°C / 75°F Conductor Rating
Box Type Terminals
Quick-Make, Quick-Break
Multi-pole Breakers Incorporate Internal Common Trip
Rev. 11/13
Prices and data subject
to change without notice
Section 1
Switching Neutral
UL Listed. 10kAIC RMS symmetrical.
Standard 1- or 2-pole automatic breaker plus one fully-rated, non-automatic pole.
1-Pole Plus Switching Neutral 2-Pole Plus Switching Neutral
120/240 Volts ac 120/240 Volts ac
Ampere Rating Product Number Product Number
15 THQL21WY15 THQL31WY15
20 THQL21WY20 THQL31WY20
25 THQL21WY25 THQL31WY25
30 THQL21WY30 THQL31WY30
Std. Pkg. 5 cartons of 5 5 cartons of 3
"HID" Lighting
UL Listed as HID. HID breakers have been designed to handle the current and voltage
spikes that result when gaseous discharge lamps, including fluorescent and HID lamps,
are switched on and off.
1-Pole, 120/240 Volts ac 2-Pole, 120/240 Volts ac
Ampere Rating Product Number Product Number
10,000 AIC
15 THQL1115HID2THQL2115HID
20 THQL1120HID2THQL2120HID
30 THQL1130HID THQL2130HID
22,000 AIC
15 THHQL1115HID2THHQL2115HID
20 THHQL1120HID2THHQL2120HID
30 THHQL1130HID THHQL2130HID
Std. Pkg. 5 cartons of 10 5 cartons of 5
2UL Listed as SWD (switching duty). Suitable for 120 volts ac fluorescent lighting loads.
High Magnetic
UL Listed. 10kAIC RMS symmetrical
High short circuit setting suitable for circuits with inherent high-inrush load currents.
1-Pole, 120/240 Volts ac
Ampere Rating Product Number
15 THQL1115HM
20 THQL1120HM
25 THQL1125HM
30 THQL1130HM
40 THQL1140HM
50 THQL1150HM
Std. Pkg. 5 cartons of 10
TQMH000
THQL2120HID
THQL21WY30
THQL1140HM
Page Updated 01 / 2016
TQ Circuit Breakers
3/4" UL Classified Circuit Breakers for use in *Square D **QO Load Centers.
10 kAIC RMS symmetrical 1-Pole 2-Pole
Ampere Rating Product Number Product Number
15 TQ1115 TQ2115
20 TQ1120 TQ2120
30 TQ1130 TQ2130
40 TQ1140 TQ2140
50 TQ1150 TQ2150
60 – TQ2160
Std. Pkg. 1 carton of 10 1 carton of 5
THQL 120/240 Vac, with Factory Installed Shunt1
# of Ampere 120/240 Vac
Poles Rating Wire Range2Interrupting Rating Product Number
1 15 (1) 14-8 Cu/12-8 Al 10kA THQL1115ST1
1 20 (1) 14-8 Cu/12-8 Al 10kA THQL1120ST1
1 30 (1) 14-8 Cu/12-8 Al 10kA THQL1130ST1
1 35 (1) 8-3 Cu/8-3 Al 10kA THQL1135ST1
1 40 (1) 8-3 Cu/8-3 Al 10kA THQL1140ST1
1 45 (1) 8-3 Cu/8-3 Al 10kA THQL1145ST1
1 50 (1) 8-3 Cu/8-3 Al 10kA THQL1150ST1
1Shunt trip requires one additional pole of space.
THQL 120/240 Vac, Internal Common Trip with Factory Installed Shunt1
# of Ampere 240 Vac
Poles Rating Wire Range2Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 10kA THQL2115ST1
2 20 14-8 Cu/12-8 Al 10kA THQL2120ST1
2 30 14-8 Cu/12-8 Al 10kA THQL2130ST1
2 35 8-3 Cu/8-3 Al 10kA THQL2135ST1
2 40 8-3 Cu/8-3 Al 10kA THQL2140ST1
2 45 8-3 Cu/8-3 Al 10kA THQL2145ST1
2 50 8-3 Cu/8-3 Al 10kA THQL2150ST1
2 60 8-3 Cu/8-3 Al 10kA THQL2160ST1
2 70 6-1/0 Cu/4-1/0 Al 10kA THQL2170ST1
2 80 6-1/0 Cu/4-1/0 Al 10kA THQL2180ST1
2 90 6-1/0 Cu/4-1/0 Al 10kA THQL2190ST1
2 100 6-1/0 Cu/4-1/0 Al 10kA THQL21100ST1
3 20 14-8 Cu/12-8 Al 10kA THQL32020ST1
3 30 14-8 Cu/12-8 Al 10kA THQL32030ST1
3 40 8-3 Cu/8-3 Al 10kA THQL32040ST1
3 50 8-3 Cu/8-3 Al 10kA THQL32050ST1
3 60 8-3 Cu/8-3 Al 10kA THQL32060ST1
3 70 6-1/0 Cu/4-1/0 Al 10kA THQL32070ST1
3 80 6-1/0 Cu/4-1/0 Al 10kA THQL32080ST1
3 90 6-1/0 Cu/4-1/0 Al 10kA THQL32090ST1
3 100 6-1/0 Cu/4-1/0 Al 10kA THQL32100ST1
2Solid or stranded for 14-10 AWG.
*Square D is a registered trademark of SNA Holdings, Inc. **QO is a registered trademark of the Square D Company.
TQ1120
THQL1130ST1
THQL2120ST1
THQL32020ST1
Section 1Load Centers and Circuit Breakers
Special Purpose Circuit Breakers
60°C / 75°F Conductor Rating
Box Type Terminals
Quick-Make, Quick-Break
Multi-pole Breakers Incorporate Internal Common Trip
1-8 BuyLogCatalog Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
Molded Case Switches
UL Listed
Without overload or short circuit protection.
2-Pole 3-Pole
Ampere Rating Product Number Product Number
120/240 Volts ac
60 TQL21Y60 –
100 TQL21Y100 –
240 Volts ac
60 TQL22Y60 TQL32Y60
100 TQL22Y100 TQL32Y100
Std. Pkg. 5 cartons of 5 5 cartons of 3
Interlocking Circuit Breakers for use in PowerMark Gold Generator Panels
Two breakers required for interlocking.
Poles Ampere Rating Product Number
2 30 THQL2130GEN
2 60 THQL2160GEN
TQL21Y100
TQ2120
Page Updated 01 / 2016
Product Features
—UL Listed (Panelboards No. 67)
—60°/75°C Conductor Rating
—Suitable for Use as Service Entrance Equipment when Installed
in Accordance with the National Electrical Code
—22kAIC RMS symmetrical, Except Where Noted
—6-42 circuit devices UL Listed for bottom mounted lugs by
installing complete unit (box, interior and front) upside down.
—For a listing of CSA Listed load centers, visit geindustrial.com.
Main Lugs Factory Installed (TLM units convertible to main breaker),
Indoor (NEMA 1) Enclosure
Main 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total Main Wire Size
Ampere 1” 1” 1/2” 1/2” 1-pole Front Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Spaces Type Feed Type1 Number Cu-Al Ground Kit Number
40 2 1 4 1 4 Surface Top 1A 14-4 TGK4 (order separately) TL240SCU1,8
Bottom
70 2 1 4 1 4 Surface Top 1A 6-3 TGK4 (order separately) TL270SCU1,8
Bottom
125 4 2 8 3 8 Combination Top 2A 1-2/0 TGL1 (order separately) TL412C1,2,8
Flush/Surface Bottom
125 4 2 8 3 8 Combination Top 2A 1-2/0 TGL1 installed TL412CT1,2,3,8
Flush/Surface Bottom
125 4 2 8 3 8 Thermoplastic Top 2 1-2/0 TGL1 (order separately) TPL412C1,2,3,8
Bottom
125 4 2 8 3 8 Thermoplastic Top 2 1-2/0 TGL1 installed TPL412CT1,2,3,8
Bottom
125 6 3 12 4 12 Flush Top 3A 6-1 TGL2 (order separately) TLM612FCU4,8
Bottom
125 6 3 12 4 12 Flush Top 3A 6-1 TGL2 (order separately) TLM612FCUD4,8
Bottom
125 6 3 12 4 12 Flush Top 3A 6-1 TGL2 installed TLM612FCUDG4,8
Bottom
125 6 3 12 4 12 Surface Top 3A 6-1 TGL2 (order separately) TLM612SCU4,8
Bottom
125 6 3 12 4 12 Surface Top 3A 6-1 TGL2 (order separately) TLM612SCUD4,8
Bottom
125 6 3 12 4 12 Surface Top 3A 6-1 TGL2 installed TLM612SCUDG4,8
Bottom
125 8 4 16 8 16 Flush Top 3A 6-1 TGL2 (order separately) TLM812FCU4,8
Bottom
125 8 4 16 8 16 Flush Top 3A 6-1 TGL2 (order separately) TLM812FCUD4,8
Bottom
125 8 4 16 8 16 Flush Top 3A 6-1 TGL2 (order separately) TLM812FCUDG4,8
Bottom
125 8 4 16 8 16 Surface Top 3A 6-1 TGL2 (order separately) TLM812SCU4,8
Bottom
125 8 4 16 8 16 Surface Top 3A 6-1 TGL2 (order separately) TLM812SCUD4,8
Bottom
125 8 4 16 8 16 Surface Top 3A 6-1 TGL2 installed TLM812SCUDG4,8
Bottom
125 14 6 20 8 24 Combination Top 18 6-2/0 Included10 TLM1212CCU7,8
Flush/Surface Bottom
125 14 6 20 8 24 White Combo Top 18 6-2/0 Included10 TLM1212CCUW7,8,9
Flush/Surface Bottom
This table continued on next page
TLM2020CCU TPL412R
Section 1
Load Center
1PH
Main Lug
Indoor NEMA 1
Rev. 11/13
Data subject to change
without notice
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Single-Phase, Three-Wire, 120/240 Vac
Main Lugs Convertible to Main Breaker
1-9
BuyLogCatalogwww.geindustrial.com
Main Lugs Factory Installed (TLM units convertible to main breaker),
Indoor (NEMA 1) Enclosure
Main 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total Main Wire Size
Ampere 1” 1” 1/2” 1/2” 1-pole Front Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Spaces Type Feed Type Number Cu-Al Ground Kit Number
125 16 8 16 6 24 Combination Top 4 6-2/0 TGK12 and TGK24 TLM1612CCU5
Flush/Surface Bottom (order separately)
125 16 8 16 6 24 Combination Top 4 6-2/0 TGK12 and TLK20 TLM1612CCUG7
Flush/Surface Bottom installed
125 24 12 0 0 24 Combination Top 7 6-2/0 TGK24 and TGK32 TLM2412CCU5
Flush/Surface Bottom (order separately)
125 24 12 0 0 24 White Combo Top 7 6-2/0 TGK24 and TGK32 TLM2412CCUW5,9
Flush/Surface Bottom (order separately)
125 24 12 0 0 24 Combination Top 7 6-2/0 TGK24 and TLK20 TLM2412CCUG7
Flush/Surface Bottom installed
200 16 8 32 14 32 Combination Top 7 6-250 TGK32 TLM1620CCU6
Flush/Surface Bottom (order separately)
200 16 8 32 14 32 White Combo Top 7 6-250 TGK32 TLM1620CCUW6,9
Flush/Surface Bottom (order separately)
200 16 8 32 14 32 Combination Top 7 6-250 TGK32 TLM1620CCUG6
Flush/Surface Bottom installed
200 20 10 40 18 40 Combination Top 8 6-250 TGK32 TLM2020CCU6
Flush/Surface Bottom (order separately)
200 20 10 40 18 40 White Combo Top 8 6-250 TGK32 TLM2020CCUW6,9
Flush/Surface Bottom (order separately)
200 20 10 40 18 40 Combination Top 8 6-250 TGK42 TLM2020CCUG6
Flush/Surface Bottom installed
200 24 12 36 18 42 Combination Top 9 1-3/0 (Cu), TGK24 and TLK32 TLM2420C426
Flush/Surface Bottom 2/0-3/0 (Al) (order separately)
200 32 16 20 8 42 Combination Top 11 1-250 (Cu), TGK32 and TLK20 TLM3220C426
Flush/Surface Bottom 2/0-250 (Al) (order separately)
200 32 16 16 6 40 Combination Top 11 6-250 TGK32 TLM3220CCU6
Flush/Surface Bottom (order separately)
200 32 16 16 6 40 White Combo Top 11 6-250 TGK32 TLM3220CCUW6,9
Flush/Surface Bottom (order separately)
200 40 20 0 0 40 Combination Top 13 6-250 TGK42 TLM4020CCU6
Flush/Surface Bottom (order separately)
200 40 20 0 0 40 White Combo Top 13 6-250 TGK42 TLM4020CCUW6,9
Flush/Surface Bottom (order separately)
200 42 20 0 0 42 Combination Top 14 1-300 (Cu), TGK42 TLM4220CCU6
Flush/Surface Bottom 2/0-300 (Al) (order separately)
225 42 20 0 0 42 Combination Top 14 1-300 (Cu), TGK42 TLM4222CCU6
Flush/Surface Bottom 2/0-300 (Al) (order separately)
1No door
210 kAIC
3125 amp maximum branch capacity.
4For main breaker, order THQLRK2 retainer kit plus 2-pole circuit breaker. See page 1-28, 100 amp max.
5For main breaker, order TQMH000. See page 1-24. Also order 2-pole THQL, THHQL, or TXQL circuit breaker. See page 1-5.
6For main breaker, order THQMVXXXD circuit breaker from page 1-6.
7For main breaker applications, use reverse feed THQL breaker or THHQL circuit breaker (see page 1-5) and THQLRK3 breaker retainer (see page 1-28).
8No lock provision available. Use next size larger load center such as TLM1612CCU with a TDL106 accessory if locking provision is required.
9Minimum order QTY is 40 for below 24 circuits; QTY 24 for 24 circuits and above. (See DEE-590)
10Load center includes a factory installed ground bar and add-a-lug. See wiring diagram on page 1-30. A separate TGL2 can be added in the unlikey event
that another ground bar is required.
Note: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers.
1-10 BuyLogCatalog Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
Section 1
Load Center
1PH
Main Lug
Indoor NEMA 1
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Single-Phase, Three-Wire, 120/240 Vac
Main Lugs Convertible to Main Breaker
Main Lugs Factory Installed (TLM units convertible to main breaker),
Outdoor (NEMA 3R) Enclosure1
Main 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total Main Wire Size
Ampere 1” 1” 1/2” 1/2” 1-pole Front Feed1 Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Spaces Type Type Number Cu-Al Ground Kit Number
40 2 1 4 1 4 Top R1A 14-4 TGK4 (order separately) TL240RCU
70 2 1 4 1 4 Top R1A 6-3 TGK4 (order separately) TL270RCU
100 5 0 0 0 5 Flush Top R41 6-3 TGL1 installed TL510RT2,8
125 4 2 8 3 8 Top R1A 1-2/0 TGL1 (order separately) TL412R12
125 4 2 8 3 8 Top R1A 1-2/0 TGL1 installed TL412RT12
125 4 2 8 3 8 Top R41 1-2/0 TGL1 (order separately) TL412R22
125 4 2 8 3 8 Thermoplastic Top R1 1-2/0 TGL1 (order separately) TPL412R2,3
Front
125 4 2 8 3 8 Thermoplastic Top R1 1-2/0 TGL1 installed TPL412RT2,3
Front
125 4 3 12 4 12 Top R2A 6-1 TGK12 (order separately) TLM612RCU4
125 8 4 16 8 16 Top R2A 6-1 TGK12 (order separately) TLM812RCU4
125 8 4 16 8 16 Top R3A 6-1 TGK12 (order separately) TLM812RCU25
125 14 6 20 8 24 Top R3A 6-2/0 Included TLM1212RCU7,9
125 24 12 0 0 24 Top R4A 6-2/0 TGK24 (order separately) TLM2412RCU5
Bottom TGK32 (order separately)
150 24 12 12 4 30 Top R6A 1-3/0 (Cu), TGK24 (order separately) TLM2415RCU6
Bottom 2/0-3/0 (Al) TGK32 (order separately)
200 12 6 24 10 24 Top R5A 6-250 TGK24 (order separately) TLM1220RCU6
200 16 8 32 14 32 Top R5A 6-250 TGK32 (order separately) TLM1620RCU6
200 20 10 40 18 40 Top R6A 6-250 TGK24 (order separately) TLM2020RCU6
TGK42 (order separately)
200 24 12 36 18 42 Top R39 1-250 (Cu), TGK24 (order separately) TLM2420R42
Bottom 2/0-250 (Al)
200 32 16 16 6 40 Top R7A 1-250 (Cu), 2/0-250 (Al) TGK32 (order separately) TLM3220RCU6
Bottom
200 40 20 0 0 40 Top R8A 6-250 TGK42 (order separately) TLM4020RCU6
Bottom
225 42 20 0 0 42 Top R8A 1-300 (Cu), TGK42 (order separately) TLM4222RCU6
Bottom 2/0-300 (Al)
140-225 amp single-phase devices have removable closing caps. Larger ampere devices require field-cut openings. Order hubs separately. See page 1-27.
210 kAIC.
3125 amp maximum branch capacity.
4For main breaker, order THQLRK2 retainer kit plus 2-pole circuit breaker. See page 1-28, 100 amp maximum due to wire bending requirements.
5For main breaker, order TQMH000. See page 1-24. Also order 2-pole THQL or THHQL circuit breaker. See page 1-5.
6For main breaker, order THQMVXXXD circuit breaker from page 1-6.
7For main breaker applications, use reverse feed THQL or THHQL circuit breaker (see page 1-5) and THQLRK3 breaker retainer (see page 1-28).
8Main and branch breakers are limited to 70 amps.
9Load center includes a factory installed ground bar and add-a-lug. See wiring diagram on page 1-30. A separate TGL2 can be added in the unlikey event
that another ground bar is required.
Note: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers.
Rev. 11/13
Data subject to change
without notice
1-11
BuyLogCatalogwww.geindustrial.com
Section 1
Load Center
1PH
Main Lug
Outdoor NEMA 3R
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Single-Phase, Three-Wire, 120/240 Vac
Main Lugs Convertible to Main Breaker
Page Updated 01 / 2016
Product Features
—UL Listed (Panelboards No. 67)
—60°C/75°C Conductor Rating
—Suitable for Use as Service Entrance Equipment when Installed
in Accordance with the National Electrical Code
—22kAIC RMS symmetrical, Except Where Noted
—6-42 circuit devices UL Listed for bottom mounted lugs by
installing complete unit (box, interior and front) upside down.
—For a listing of CSA Listed load centers, visit geindustrial.com.
Indoor (NEMA 1) Enclosure
Main 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total Main Wire Size
Ampere 1” 1” 1/2” 1/2” 1-pole Front Feed Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Spaces Type Type Number Cu-Al Ground Kit Number
100 12 5 20 8 22 Combination Top 18 4-1/0 Included1 TM1210CCU2
Flush/Surface Bottom
Front
100 24 12 0 0 24 Combination Top 7 1-2/0 TGK24, TGK32 and TM2410CCU
Flush/Surface Bottom TLK20 (order separately)
Front
100 20 10 0 0 20 Combination Top 6 4-1/0 TGK24 (order separately) TM2010CCU
Flush/Surface Bottom
Front
100 32 16 0 0 32 Combination Top 11 4-1/0 TGK32 (order separately) TM3210CCU
Flush/Surface Bottom
Front
125 12 5 20 8 22 Combination Top 18 1-2/0 Included1 TM1212CCU2
Flush/Surface Bottom
Front
125 24 12 0 0 24 Combination Top 7 1-2/0 TGK24 (order separately) TM2412CCU
Flush/Surface Bottom
Front
125 16 8 16 6 24 Combination Top 4 1-2/0 TGK12 (order separately) TM1612CCU
Flush/Surface Bottom TGK24 (order separately)
Front
125 16 8 16 6 24 Combination Top 4 1-2/0 TGK24 installed TM1612CCUG
Flush/Surface Bottom
Front
150 16 8 32 14 32 Combination Top 7 1-3/0 (Cu), TGK24 (order separately) TM1615CCU
Flush/Surface Bottom 2/0-3/0 (Al) TGK32 (order separately)
Front
150 16 8 32 14 32 Combination Top 7 1-3/0 (Cu), TGK32 installed TM1615CCUG
Flush/Surface Bottom 2/0-3/0 (Al)
Front
This table continued on next page
TM820RCUFLTM2020CCU
Section 1
Load Center
1PH
Main Breaker
Indoor NEMA 1
Load Centers and Circuit Breakers
PowerMark Gold and Plus Main Breaker Load Centers
Single-Phase, Three-Wire, 120/240 Vac
Main Breaker Factory Installed
1-12 BuyLogCatalog Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
Indoor (NEMA 1) Enclosure
Main 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total Main Wire Size
Ampere 1” 1” 1/2” 1/2” 1-pole Front Feed Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Spaces Type Type Number Cu-Al Ground Kit Number
150 32 16 0 0 32 Combination Top 11 1-3/0 (Cu), TGK32 (order separately) TM3215CCU
Flush/Surface Bottom 2/0-3/0 (Al)
150 24 12 36 18 42 Combination Top 9 1-3/0 (Cu), TGK24 (order separately) TM2415C42
Flush/Surface Bottom 2/0-3/0 (Al) TLK32 (order separately)
150 32 16 20 10 42 Combination Top 11 1-3/0 (Cu), TGK32 and TLK20 TM3215C42
Flush/Surface Bottom 2/0-3/0 (Al) (order separately)
200 16 8 32 14 32 Combination Top 7 1-250 (Cu), TGK32 (order separately) TM1620CCU
Flush/Surface Bottom 2/0-250 (Al)
200 16 8 32 14 32 Combination Top 8 1-250 (Cu), TGK32 installed TM1620CCUG
Flush/Surface Bottom 2/0-250 (Al)
200 20 10 40 18 40 Combination Top 8 1-250 (Cu), TGK32 (order separately) TM2020CCU
Flush/Surface Bottom 2/0-250 (Al)
200 20 10 40 18 40 White Combo Top 8 1-250 (Cu), TGK24 (order separately) TM2020CCUW3
Flush/Surface Bottom 2/0-250 (Al) TGK42 (order separately)
200 20 10 40 18 40 Combination Top 8 1-250 (Cu), TGK32 (order separately) TM2020CCUG
Flush/Surface Bottom 2/0-250 (Al)
200 20 10 40 18 40 White Combo Top 8 1-250 (Cu), TGK32 (order separately) TM2020CCUGW3
Flush/Surface Bottom 2/0-250 (Al)
200 32 16 16 6 40 Combination Top 11 1-250 (Cu), TGK32 (order separately) TM3220CCU
Flush/Surface Bottom 2/0-250 (Al)
200 40 20 0 0 40 Combination Top 13 1-250 (Cu), TGK42 (order separately) TM4020CCU
Flush/Surface Bottom 2/0-250 (Al)
200 32 16 20 8 42 Combination Top 11 1-250 (Cu), TGK32 and TLK20 TM3220C42
Flush/Surface Bottom 2/0-250 (Al) (order separately)
200 42 20 0 0 42 Combination Top 14 1-300 (Cu), TGK42 (order separately) TM4220CCU
Flush/Surface Bottom 2/0-300 (Al)
225 42 20 0 0 42 Combination Top 14 1-300 (Cu), TGK42 (order separately) TM4222CCU
Flush/Surface Bottom 2/0-300 (Al)
1Load center includes a factory installed ground bar and add-a-lug. See wiring diagram on page 1-30. A separate TGL2 can be added in the unlikey event
that another ground bar is required.
2No lock provision available. Use next size larger load center such as TLM1612CCU with a TDL106 accessory if locking provision is required.
3Minimum order QTY is 40 for below 24 circuits; QTY 24 for 24 circuits and above. (See DEE-590)
Section 1
Load Center
1PH
Main Breaker
Indoor NEMA 1
Rev. 11/13
Data subject to change
without notice
Load Centers and Circuit Breakers
PowerMark Gold and Plus Main Breaker Load Centers
Single-Phase, Three-Wire, 120/240 Vac
Main Breaker Factory Installed
1-13
BuyLogCatalogwww.geindustrial.com
Load Center
1PH
Main Breaker
Outdoor NEMA 3R
Outdoor (NEMA 3R) Enclosure4
Main 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total Main Wire Size
Ampere 1” 1” 1/2” 1/2” 1-pole Feed Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Spaces Type Number Cu-Al Ground Kit Number
100 12 5 20 8 22 Top R3A 4-1/0 TGK12 (order separately) TM1210RCU
TGK24 (order separately)
100 20 10 0 0 30 Top R4 4-1/0 TGK24 (order separately) TM2010RCU
125 12 5 20 8 22 Top R3A 1-2/0 TGK12 (order separately) TM1212RCU
TGK24 (order separately)
125 24 12 0 0 24 Top R4 1-2/0 TGK24 (order separately) TM2412RCU
150 8 4 16 6 16 Top R5 1-250 (Cu), 2/0-250 (Al) TGK24 (order separately) TM815RCUFL
150 16 8 32 14 32 Top R5 1-3/0 (Cu), 2/0-3/0 (Al) TGK24 (order separately) TM1615RCU
TGK32 (order separately)
150 24 12 12 4 30 Top R6 1-3/0 (Cu), 2/0-3/0 (Al) TGK24 (order separately) TM2415RCU
TGK32 (order separately)
150 24 12 36 18 42 Top R39 1-250 (Cu), 2/0-250 (Al) TGK24 (order separately) TM2415R42
Bottom
150 32 16 0 0 32 Top R7 1-3/0 (Cu), 2/0-3/0 (Al) TGK32 (order separately) TM3215RCU
200 8 4 16 6 16 Top R5 1-250 (Cu), 2/0-250 (Al) TGK32 (order separately) TM820RCUFL
200 20 10 40 18 40 Top R6 1-250 (Cu), 2/0-250 (Al) TGK24 (order separately) TM2020RCU
TGK42 (order separately)
200 24 12 36 18 42 Top R39 1-250 (Cu), 2/0-250 (Al) TGK24 (order separately) TM2420R42
Bottom
200 32 16 16 6 40 Top R7 1-250 (Cu), 2/0-250 (Al) TGK32 (order separately) TM3220RCU
200 40 20 0 0 40 Top R8 1-250 (Cu), 2/0-250 (Al) TGK42 (order separately) TM4020RCU
225 8 4 16 6 16 Top R5 1-250 (Cu), 2/0-250 (Al) TGK24 (order separately) TM822RCUFL
225 42 20 0 0 42 Top R8 1-300 (Cu), 2/0-300 (Al) TGK42 (order separately) TM4222RCU
4100-225 amp devices have removable closing caps. Larger ampere devices require field-cut openings. Order hubs separately. See page 1-27.
Note: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers.
Product Features
—UL Listed (Panelboards No. 67)
—60°/75°C Conductor Rating
—Suitable for Use as Service Entrance Equipment when Installed
in Accordance with the National Electrical Code
—22kAIC RMS symmetrical Short-circuit Rating Standard
—Bottom feed models available where noted with a “B” suffix.
—For a listing of CSA Listed load centers, visit geindustrial.com.
—Copper breaker mounting stabs with aluminum bus1
Indoor (NEMA 1) Enclosure
Main 1 Pole, 2 Pole, 3 Pole, Total Main Wire Size
Ampere 1” 1” 1” 1-pole Feed Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Front Type Type Number Cu-Al Ground Kit Number
125 12 6 4 12 Combination Top 4 6-2/0 TGK12 (order separately) TL12412C3
Flush/Surface Bottom TGK24 (order separately)
Front
150 18 8 6 18 Combination Top 7 1-3/0 (Cu), TGK24 (order separately) TL18415C3
Flush/Surface Bottom 2/0-3/0 (Al) TGK32 (order separately)
Front
150 24 12 8 24 Combination Top 7 1-3/0 (Cu), TGK24 (order separately) TL24415C3
Flush/Surface Bottom 2/0-3/0 (Al) TGK32 (order separately)
Front
200 18 8 6 18 Combination Top 8 1-250 (Cu), TGK32 (order separately) TL18420C3
Flush/Surface Bottom 2/0-250 (Al)
Front
200 30 14 10 30 Combination Top 11 1-250 (Cu), TGK32 (order separately) TL30420C3
Flush/Surface Bottom 2/0-250 (Al)
Front
200 42 20 14 42 Combination Top 13 1-250 (Cu), TGK42 (order separately) TL42420C
Flush/Surface Bottom 2/0-250 (Al)
Front
225 30 14 10 30 Combination Top 15 1-300 (Cu), (2) TGL2 (order separately) TL30422C4
Flush/Surface Bottom 2/0-300 (Al)
Front
225 42 20 14 42 Combination Top 15 1-300 (Cu), (2) TGL2 (order separately) TL42422C4
Flush/Surface Bottom 2/0-300 (Al)
Front
1Three-phase PowerMark Plus load centers have aluminum bus with copper breaker mounting stabs, providing copper-to-copper contact at breaker stabs.
2Also UL Listed for three-phase, four-wire 240/120 Volts ac delta and three-phase, three-wire 240 Volts ac branch breakers installed.
3Alternate main breaker: 100 Amp max. THQL three-pole, use retainer THQLRK. See page 1-28.
4Not suitable for use as service entrance equipment.
Note: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers.
Section 1
Load Center
3PH
Main Lugs
Indoor NEMA 1
Load Centers and Circuit Breakers
PowerMark PlusLoad Centers
Three-Phase, Four-Wire, 208Y/120 Vac2
Main Lugs Factory Installed
1-14 BuyLogCatalog Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
Main Lugs Factory Installed
Outdoor (NEMA 3R) Enclosure
Main 1 Pole, 2 Pole, 3 Pole, Total Main Wire Size
Ampere 1” 1” 1” 1-pole Feed Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Type Number Cu-Al Ground Kit Number
125 12 6 4 12 Top R3 6-2/0 TGK12 (order separately) TL12412R2,4
TGK24 (order separately)
150 18 8 6 18 Top R4 1-3/0 (Cu), TGK24 (order separately) TL18415R2,4
2/0-3/0 (Al) TGK32 (order separately)
150 24 12 8 24 Top R4 1-3/0 (Cu), TGK24 (order separately) TL24415R2,4
2/0-3/0 (Al) TGK32 (order separately)
200 18 8 6 18 Top R4 1-250 (Cu), TGK32 (order separately) TL18420R2,4
2/0-250 (Al)
200 30 14 10 30 Top R6 1-250 (Cu), TGK32 (order separately) TL30420R2,4
2/0-250 (Al)
200 42 20 14 42 Top R8 1-250 (Cu), TGK42 (order separately) TL42420R2,3
2/0-250 (Al)
225 42 20 14 42 Top R8 1-300 (Cu), TGK42 (order separately) TL42422R2,3
2/0-300 (Al)
1Also UL Listed for three-phase, four-wire 240/120 Volts ac delta and three-phase, three-wire 240 Volts ac branch breakers installed.
2100-200 Amp three-phase devices have removable closing cap. Larger Ampere devices require field cut openings. Order hubs separately. See page 1-27.
3Not suitable for use as service entrance equipment.
4Alternate main breaker: 100 Amp max. THQL three-pole, use retainer THQLRK. See page 1-28.
Main Breaker Factory Installed
Indoor (NEMA 1) Enclosure
Main 1 Pole, 2 Pole, 3 Pole, Total Main Wire Size
Ampere 1” 1” 1” 1-pole Feed2 Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Front Type Type Number Cu-Al Ground Kit Number
100 12 6 4 12 Combination Top 6 6-1/0 (Cu), TGK12 (order separately) TM12410C6
Flush/Surface Bottom 4-1/0 (Al) TGK24 (order separately)
Front
100 18 8 6 18 Combination Top 6 6-1/0 (Cu), TGK24 (order separately) TM18410C6
Flush/Surface Bottom 4-1/0 (Al) TGK32 (order separately)
Front
125 30 14 10 30 Combination Top 11 1-3/0 (Cu), TGK32 (order separately) TM30412C
Flush/Surface 2/0-3/0 (Al)
Front
125 30 14 10 30 Combination Bottom 11 1-3/0 (Cu), TGK32 (order separately) TM30412CB
Flush/Surface 2/0-3/0 (Al)
Front
150 24 12 8 24 Combination Top 11 1-3/0 (Cu), TGL1, TGL2, TGL20,TNG3, TM24415C
Flush/Surface 2/0-3/0 (Al TGN6 (order separately)
Front
150 24 12 8 24 Combination Bottom 11 1-3/0 (Cu), TGK32 (order separately) TM24415CB
Flush/Surface 2/0-3/0 (Al)
Front
150 30 14 10 30 Combination Top 11 1-3/0 (Cu), TGK32 (order separately) TM30415C
Flush/Surface 2/0-3/0 (Al)
Front
150 30 14 10 30 Combination Bottom 11 1-3/0 (Cu), TGK32 (order separately) TM30415CB
Flush/Surface 2/0-3/0 (Al)
Front
150 42 20 14 42 Combination Top 13 1-3/0 (Cu), TGK42 (order separately) TM42415C
Flush/Surface 2/0-3/0 (Al)
Front
150 42 20 14 42 Combination Bottom 13 1-3/0 (Cu), TGK42 (order separately) TM42415CB
Flush/Surface 2/0-3/0 (Al)
Front
200 24 12 8 24 Combination Top 11 1-300 (Cu), TGK32 (order separately) TM24420C
Flush/Surface 2/0-300 (Al)
Front
200 24 12 8 24 Combination Bottom 11 1-300 (Cu), TGK32 (order separately) TM24420CB
Flush/Surface 2/0-300 (Al)
Front
5Also UL Listed for three-phase, four-wire 240/120 Volts ac delta and three-phase, three-wire 240 Volts ac branch breakers installed.
6100 Amp indoor devices UL listed for bottom-feed by installing complete unit upside-down.
Note: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers. This table continued on next page
Section 1
Load Center
3PH
Main Lugs
Outdoor NEMA 3R
Rev. 11/13
Data subject to change
without notice
Load Centers and Circuit Breakers
PowerMark PlusLoad Centers
Three-Phase, Four-Wire, 208Y/120Vac1
Main Circuit Breaker or Main Lugs Factory Installed
1-15
BuyLogCatalogwww.geindustrial.com
Load Center
3PH
Main Breaker
Indoor NEMA 1
TM24420CB
Indoor (NEMA 1) Enclosure
Main 1 Pole, 2 Pole, 3 Pole, Total Main Wire Size
Ampere 1” 1” 1” 1-pole Feed2 Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Front Type Type Number Cu-Al Ground Kit Number
200 30 14 10 30 Combination Top 12 1-250 (Cu), TGK32 (order separately) TM30420C
Flush/Surface 2/0-250 (Al)
Front
200 30 14 10 30 Combination Bottom 12 1-250 (Cu), TGK32 (order separately) TM30420CB
Flush/Surface 2/0-250 (Al)
Front
200 42 20 14 42 Combination Top 14 1-250 (Cu), TGK42 (order separately) TM42420C
Flush/Surface 2/0-250 (Al)
Front
200 42 20 14 42 Combination Bottom 14 1-250 (Cu), TGK42 (order separately) TM42420CB
Flush/Surface 2/0-250 (Al)
Front
225 42 20 14 42 Combination Top 15 1-300 (Cu), (2) TGL2 (order separately) TM42422C
Flush/Surface 2/0-300 (Al)
Front
225 42 20 14 42 Combination Bottom 15 1-300 (Cu), (2) TGL2 (order separately) TM42422CB
Flush/Surface 2/0-300 (Al)
Front
1Also UL Listed for three-phase, four-wire 240/120 Volts ac delta and three-phase, three-wire 240 Volts ac branch breakers installed.
Outdoor (NEMA 3R) Enclosure
Main 1 Pole, 2 Pole, 3 Pole, Total Main Wire Size
Ampere 1” 1” 1” 1-pole Feed2 Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Type Number Cu-Al Ground Kit Number
100 18 8 6 18 Top R4 6-1/0 (Cu), TGK24 (order separately) TM18410R2
4-1/0 (Al) TGK32 (order separately)
125 30 14 10 30 Top R7 1-3/0 (Cu), TGK32 (order separately) TM30412R2
2/0-3/0 (Al)
150 24 12 8 24 Top R6 1-3/0 (Cu), TGK32 (order separately) TM24415R2
2/0-3/0 (Al)
150 30 14 10 30 Top R7 1-3/0 (Cu), TGK32 (order separately) TM30415R2
2/0-3/0 (Al)
200 30 14 10 30 Top R7 1-250 (Cu), TGK32 (order separately) TM30420R2
2/0-250 (Al)
200 42 20 14 42 Top R8 1-250 (Cu), TGK42 (order separately) TM42420R2
2/0-250 (Al)
225 42 20 14 42 Top R8 1-300 (Cu), TGK42 (order separately) TM42422R2
2/0-300 (Al)
2100-200 Amp three-phase devices have removable closing cap. Larger Ampere devices require field cut openings. Order hubs separately. See page 1-27.
Note: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers.
Section 1
Load Center
3PH
Main Breaker
Indoor NEMA 1
Load Centers and Circuit Breakers
PowerMark PlusLoad Centers
Three-Phase, Four-Wire, 208Y/120 Vac1
Main Circuit Breaker Factory Installed
1-16 BuyLogCatalog Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
Load Center
3PH
Main Breaker
Outdoor NEMA 3R
Product Features - Generator Panels
—Suitable for use in accordance with Article 702 of the National
Electrical Code, ANSI/NFPA 70
—Single-phase, 2 interlock 60A or 30A main breakers, 8 circuits
max.
—Safety and convenience when using a generator - 14,000 peak
wattage, 11,520 continuous load, 48 amps at 240 volts.
—Maintains power to such critical circuits as those for furnace,
pump, refrigerator, lights.
—Connected dual breaker mechanism ensures that only one
source is active at a time.
Generator Panels, Two Interlocked Main Breakers Factory Installed
Indoor (NEMA 1) Enclosure
Main 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total Main Wire Size
Ampere 1” 1” 1/2” 1/2” 1-pole Feed Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Spaces Front Type Type Number Cu-Al Ground Kit Number
30 4 2 8 4 8 Flush Front Top 3A 6-1 TGK12 included TM830FCUGEN
Bottom
30 4 2 8 4 8 Surface Front Top 3A 6-1 TGK12 included TM830SCUGEN
Bottom
60 4 2 8 4 8 Flush Front Top 3A 6-1 TGK12 included TM860FCUGEN
Bottom
60 4 2 8 4 8 Surface Front Top 3A 6-1 TGK12 included TM860SCUGEN
Bottom
Generator Panels, Two Interlocked Main Breakers Factory Installed
Outdoor (NEMA 3R) Enclosure
Main 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total Main Wire Size
Ampere 1” 1” 1/2” 1/2” 1-pole Feed Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Spaces Type Number Cu-Al Ground Kit Number
30 4 2 8 4 8 Top R2A 6-1 TGK12 included TM830RCUGEN
60 4 2 8 4 8 Top R2A 6-1 TGK12 included TM860RCUGEN
Riser Panels
Indoor (NEMA 1) Enclosure
Main 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total Main Wire Size
Ampere 1” 1” 1/2” 1/2” 1-pole Feed Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Spaces Front Type Type Number Cu-Al Ground Kit Number
125 20 10 40 20 40 Combination Top 9A 6-2/0 TGK12 (order TLM2012CCURP
Flush/Surface Front separately)
Tap kits required, order separately. See page 1-29.
Auxiliary gutters available. See page 1-29.
Spa Panels
Outdoor (NEMA 3R) Enclosure
Main 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total Main Wire Size
Ampere 1” 1” 1/2” 1/2” 1-pole Load Center Feed Box (AWG/kcmil) Equipment Product
Rating Spaces Spaces Spaces Spaces Spaces Type Type Number Cu-Al Ground Kit Number
125 4 2 8 4 8 Factory Included Top 1-2/0 TGL1 installed TL412R250GF
50A GFCI Bottom
125 4 2 8 4 8 Factory Included Top 1-2/0 TGL1 installed TL412R260GF
60A GFCI Bottom
Twist Lock Power Inlets
Product
Receptacles Amps Volts UL Number
L14-20 20 120/240 Canada, US T020N
L14-30 30 120/240 Canada, US T030N
CS637 50 120/240 Canada, US T050N
TL412R250GF TM830FCUGEN
Section 1
Load Center
Generator Panels
Riser Panels
Spa Panels
Rev. 11/13
Data subject to change
without notice
Load Centers and Circuit Breakers
PowerMark Gold Load Centers
Single-Phase, Three-Wire, 120/240 Vac
1-17
BuyLogCatalogwww.geindustrial.com
Single-Phase, Three-Wire, 120/240 Vac
With Bonded Neutrals
Main
Ampere 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total 1-pole Enclosure Bypass UL Agency Product
Rating 1” Spaces 1” Spaces 1/2” Spaces 1/2” Spaces Spaces Type Front Type Type Incoming Certification Number
Meter Main - Ring Type, Field Installed Mains
100 2 1 4 1 4 Outdoor Semi-Flush None OH/UG UL TSL210CFCU1
(NEMA 3R) EUSERC
100 2 1 4 1 4 Outdoor Surface2 None OH/UG UL TSL210CSCU1,2,3
(NEMA 3R) EUSERC
125 4 2 6 3 6 Outdoor Surface2 None OH/UG UL TSL412CSCU1,2,3
(NEMA 3R) EUSERC
200 4 2 6 3 6 Outdoor Semi-Flush None OH/UG UL TSL420CFCU1,4,5
(NEMA 3R) EUSERC
200 4 2 6 3 6 Outdoor Surface2 None OH/UG UL TSL420CSCU1,2,3,4
(NEMA 3R) EUSERC
Meter Main - Factory Installed Mains
100 0 0 0 0 0 Outdoor Surface2 None OH/UG UL TM10RMC2
(NEMA 3R)
125 0 0 0 0 0 Outdoor Surface2 None OH/UG UL TM12RMC2
(NEMA 3R)
150 0 0 0 0 0 Outdoor Surface2 None OH/UG UL TM15RMC2
(NEMA 3R)
200 0 0 0 0 0 Outdoor Surface2 None OH/UG UL TM20RMC2
(NEMA 3R)
1Accepts field installed fifth jaw terminal in the 3 or 9 o’clock position. Product number TJAW53; order separately.
2Devices include removable closing cap. Order hub separately. See page 1-27.
3Surface mounted units have two hub provisions on top end wall.
4THQL and THHQL only, 125 amp max. TQDL is obsolete.
5Restricted
Application Data
Main Wire Size
Product Box Unit Width Unit Height Depth Factory Inst. Field Inst. (AWG/kcmil) Equipment
Number Number (in inches) (in inches) (in inches) Svcs Disc Svcs Disc Cu-Al Ground Kit
TSL210CFCU R12 14 23-1/2 4-7/8 THQP/THQL 6-2/0 TGL1 installed
TSL210CSCU R12 14 23-1/2 4-7/8 THQP/THQL 6-2/0 TGL1 installed
TSL412CSCU R12 14 23-1/2 4-7/8 THQP/THQL 6-2/0 TGL1 installed
TSL420CFCU R14 14 30-3/4 5-3/4 THQP/THQL 1-250 TGL1 installed
TSL420CSCU R14 14 30-3/4 5-3/4 THQP/THQL 1-250 TGL1 installed
TM10RMC R32 16 17 5 TQD Field Installed4 2-250
TM12RMC R32 16 17 5 TQD Field Installed4 2-250
TM15RMC R32 16 17 5 TQD Field Installed4 2-250
TM20RMC R32 16 17 5 TQD Field Installed4 2-250
TSM2020CFCU
Section 1
Meter Socket LC
1PH
Ring Type
Meter Main
NEMA 3R
Load Centers and Circuit Breakers
PowerMark Gold Meter Socket Load Centers
1-18 BuyLogCatalog Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
Designed and manufactured for quality applications, these
PowerMark Gold Meter Socket Load Centers are a superior
solution to specific applications. Increased durability and
reliability, maximum circuit layout flexibility and ease of
installation add up to lower total installed cost.
The Ringless UL Style meter socket load centers (Florida Meter
Group, Georgia Power, Others) are specifically designed to meet
UL requirements as well as some special features required by spe-
cific utilities. If your local utility does not require specific approval
and you need a ringless meter socket load center, use the Florida
Meter Group style.
Ring Type - Farm Panel - Main Breaker
Main
Ampere 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total 1-pole Enclosure Front Bypass UL Agency Product
Rating 1” Spaces 1” Spaces 1/2” Spaces 1/2” Spaces Spaces Type Front Type Type Incoming Certification Number
200 4 2 8 3 8 Outdoor Surface None OH/UG UL TSF420CSCU1,2
(NEMA 3R) EUSERC
1Devices include removable closing cap. Order hub separately. See page 1-27.
2Separate field mounted service disconnect can be added, THQL/THHQL. See wiring diagram on page 1-35.
Application Data
Main Wire Size
Product Box Unit Width Unit Height Depth Factory Inst. Field Inst. (AWG/kcmil) Equipment
Number Number (in inches) (in inches) (in inches) Svcs Disc Svcs Disc Cu-Al Ground Kit
TSF420CSCU R16 16-3/4 33 6-3/16 THQMV THQL/THHQL 1-300 TGK12 (order separately)
Ring Type Feed-Thru - Main Breaker
Main
Ampere 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total 1-pole Enclosure Front Bypass UL Agency Product
Rating 1” Spaces 1” Spaces 1/2” Spaces 1/2” Spaces Spaces Type Type Type Incoming Certification Number
150 4 2 8 3 8 Outdoor Surface None OH/UG UL TSM415CSCU1
(NEMA 3R
150 8 4 16 6 16 Outdoor Surface None OH/UG UL TSM815CSCU1
(NEMA 3R)
150 8 4 16 6 16 Outdoor Surface None OH/UG UL TSM815CSFL1
(NEMA 3R)
200 4 2 8 3 8 Outdoor Surface None OH/UG UL TSM420CSCU1
(NEMA 3R)
200 8 4 16 6 16 Outdoor Surface None OH/UG UL TSM820CSCU1
(NEMA 3R
200 8 4 16 6 16 Outdoor Surface None OH/UG UL TSM820CSFL1
(NEMA 3R)
1Devices include removable closing cap. Order hub separately. See page 1-27.
Application Data
Main Wire Size
Product Box Unit Width Unit Height Depth Factory Inst. (AWG/kcmil) Equipment
Number Number (in inches) (in inches) (in inches) Svcs Disc Cu-Al Ground Kit
TSM415CSCU R36 14 28-1/2 4-1/2 THQMV 6-350 TGL2 included
TSM815CSCU R16 16-3/4 33 6-3/16 THQMV 1-300 TGK12 (order separately)
TSM815CSFL R37B 14 31-3/4 4-1/2 THQMV 6-350 TGK24 included
TSM420CSCU R36 14 28-1/2 4-1/2 THQMV 6-350 TGL2 included
TSM820CSCU R16 16-3/4 33 6-3/16 THQMV 6-350 TGK12 (order separately)
TSM820CSFL R37B 14 31-3/4 4-1/2 THQMV 6-350 TGK24 included
Section 1
Meter Socket LC
1PH
Ring Type
Farm Panel
Main Breaker
NEMA 3R
Rev. 11/13
Data subject to change
without notice
Load Centers and Circuit Breakers
PowerMark Gold Meter Socket Load Centers
Single-Phase, Three-Wire, 120/240 Vac
With Bonded Neutrals
1-19
BuyLogCatalogwww.geindustrial.com
Single-Phase, Three-Wire, 120/240 Vac
With Bonded Neutrals
Ring Type - Side by Side - Main Breaker - OH/UG
Main
Ampere 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total 1-pole Enclosure Bypass UL Agency Product
Rating 1” Spaces 1” Spaces 1/2” Spaces 1/2” Spaces Spaces Type Front Type Type Incoming Certification Number
100 16 8 32 14 32 Outdoor Semi-Flush None OH/UG UL/EUSERC TSM1610CFCU1
125 12 6 24 12 24 Outdoor Semi-Flush None OH/UG UL/EUSERC TSM1212CFCU1
125 16 8 32 14 32 Outdoor Semi-Flush None OH/UG UL/EUSERC TSM1612CFCU1
200 20 10 40 18 40 Outdoor Semi-Flush None OH/UG UL/EUSERC TSM2020CFCU1
100 16 8 32 14 32 Outdoor Surface None OH/UG UL/EUSERC TSM1610CSCU1,2,3
125 12 6 24 12 24 Outdoor Surface None OH/UG UL/EUSERC TSM1212CSCU1,2,3
125 16 8 32 14 32 Outdoor Surface None OH/UG UL/EUSERC TSM1612CSCU1,2,3
200 20 10 40 18 40 Outdoor Surface None OH/UG UL/EUSERC TSM2020CSCU1,2,3
1Accepts field installed fifth jaw terminal in the 3 or 9 o’clock position. Product number TJAW53; order separately.
2Devices include removable closing cap. Order hub separately. See page 1-27.
3Surface mounted units have two hub provisions on top end wall.
Application Data
Main Wire Size
Box Unit Width Unit Height Depth Factory Inst. (AWG/kcmil) Equipment
Product Number Number (in inches) (in inches) (in inches) Svcs Disc Cu-Al Ground Kit
TSM1610CFCU R19 14-3/4 28-1/2 7-5/16 THHQL 12-2/0 TGK12 (order separately)
TSM1212CFCU R19 14-3/4 28-1/2 7-5/16 THHQL 12-2/0 TGK12 (order separately)
TSM1612CFCU R19 14-3/4 28-1/2 7-5/16 THHQL 12-2/0 TGK12 (order separately)
TSM2020CFCU R17 16-3/4 34-1/4 7-5/16 THQMV 1-300 TGK12 (order separately)
TSM1610CSCU R20 14-3/4 27-5/16 5-7/16 THHQL 12-2/0 TGK12 (order separately)
TSM1212CSCU R20 14-3/4 27-5/16 5-7/16 THHQL 12-2/0 TGK12 (order separately)
TSM1612CSCU R20 14-3/4 27-5/16 5-7/16 THHQL 12-2/0 TGK12 (order separately)
TSM2020CSCU R18 14-3/4 33 6-5/16 THQMV 1-300 TGK12 (order separately)
Ring Type - Extra Wide - Main Breaker
Main
Ampere 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total 1-pole Enclosure Bypass UL Agency Product
Rating 1” Spaces 1” Spaces 1/2” Spaces 1/2” Spaces Spaces Type Front Type Type Incoming Certification Number
200 32 16 16 6 40 Outdoor Surface None UG UL/EUSERC TSM3220UWCU2
200 40 20 0 0 40 Outdoor Surface None UG UL/EUSERC TSM4020UWCU2
2Devices include removable closing cap. Order hub separately. See page 1-27.
Application Data
Main Wire Size
Box Unit Width Unit Height Depth Factory Inst. (AWG/kcmil) Equipment
Product Number Number (in inches) (in inches) (in inches) Svcs Disc Cu-Al Ground Kit
TSM3220UWCU R28 22-1/2 27-7/8 6-1/4 THQMV 1-300 TGK12 (order separately)
TSM4020UWCU R29 22-1/2 34-7/8 6-1/4 THQMV 1-300 TGK12 (order separately)
Ring Type - Top/Bottom - Main Breaker
Main
Ampere 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total 1-pole Enclosure Bypass UL Agency Product
Rating 1” Spaces 1” Spaces 1/2” Spaces 1/2” Spaces Spaces Type Front Type Type Incoming Certification Number
200 24 12 36 18 42 Outdoor Semi-Flush None UG UL/EUSERC TSM2420UF421
200 32 14 16 6 40 Outdoor Semi-Flush None UG UL/EUSERC TSM3220UFCU
225 20 10 40 18 40 Outdoor Semi-Flush None UG UL/EUSERC TSM2022UFCU
225 32 14 16 6 40 Outdoor Semi-Flush None UG UL/EUSERC TSM3222UFCU
200 24 12 36 18 42 Outdoor Surface None UG UL/EUSERC TSM2420US421,2,3
200 32 14 16 6 40 Outdoor Surface None UG UL/EUSERC TSM3220USCU1
225 20 10 40 18 40 Outdoor Surface None UG UL/EUSERC TSM2022USCU1
225 32 14 16 6 40 Outdoor Surface None UG UL/EUSERC TSM3222USCU1
1Accepts field installed fifth jaw terminal in the 3 or 9 o’clock position. Product number TJAW53; order separately.
2Devices include removable closing cap. Order hub separately. See page 1-27.
3Surface mounted units have two hub provisions on top end wall.
Application Data
Main Wire Size
Box Unit Width Unit Height Depth Factory Inst. (AWG/kcmil) Equipment
Product Number Number (in inches) (in inches) (in inches) Svcs Disc Cu-Al Ground Kit
TSM2420UF42 R17 16-3/4 34-1/4 7-5/16 THQMV 1-4/0 TGK12 (order separately)
TSM3220UFCU R27 14-9/16 43-5/8 7-3/16 THQMV 1-300 TGK12 (order separately)
TSM2022UFCU R21 14-9/16 43-5/8 7-3/16 THQMV 1-300 TGK12 (order separately)
TSM3222UFCU R22 16-3/16 48-1/8 7-3/16 THQMV 1-300 TGK12 (order separately)
TSM2420US42 R17 16-3/4 34-1/4 7-5/16 THQMV 1-4/0 TGK12 (order separately)
TSM3220USCU R27 14-9/16 48-1/8 6-3/16 THQMV 1-300 TGK12 (order separately)
TSM2022USCU R26 14-9/16 43-5/8 6-3/16 THQMV 1-300 TGK12 (order separately)
TSM3222USCU R27 14-9/16 48-1/8 6-3/16 THQMV 1-300 TGK12 (order separately)
Section 1
Meter Socket LC
1PH
Ring Type
Narrow, Wide, Over/Under
Main Breaker
NEMA 3R
Load Centers and Circuit Breakers
PowerMark Gold Meter Socket Load Centers
1-20 BuyLogCatalog Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
Single-Phase, Three-Wire, 120/240 Vac
With Bonded Neutrals
Ringless with Bypass - Xcel Energy
Main
Ampere 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total 1-pole Enclosure Main Bypass UL Agency Product
Rating 1” Spaces 1” Spaces 1/2” Spaces 1/2” Spaces Spaces Type Type Front Type Type Incoming Certification Number
125 4 2 8 3 8 Outdoor MLO Surface Horn Bypass OH/UG Xcel/UL TSLR412CSCU1
(NEMA 3R)
125 4 2 6 3 6 Outdoor MLO Surface1 Lever OH/UG Xcel/UL TSLB412CSCU1
(NEMA 3R) Bypass
125 12 6 24 10 24 Outdoor MB Surface Horn Bypass OH/UG Xcel/UL TSMR1212CSCU1
(NEMA 3R)
125 12 6 24 12 24 Outdoor MB Surface Lever OH/UG Xcel/UL TSMB1212CSCU1
(NEMA 3R) Bypass
150 4 2 8 3 8 Outdoor MB Surface Horn Bypass OH/UG Xcel/UL TSMR415CSCU
(NEMA 3R)
150 20 10 40 18 40 Outdoor MB Surface Horn Bypass OH/UG Xcel/UL TSMR2015CSCU1
(NEMA 3R)
150 20 10 40 18 40 Outdoor MB Surface Lever OH/UG Xcel/UL TSMB2015CSCU1
(NEMA 3R) Bypass
200 4 2 6 3 6 Outdoor MLO Surface1 Lever OH/UG Xcel/UL TSLB420CSCU1
(NEMA 3R) Bypass
200 4 2 8 3 8 Outdoor MLO Surface Horn Bypass OH/UG Xcel/UL TSLR420CSCU1
(NEMA 3R)
200 4 2 8 3 8 Outdoor MB Surface Horn Bypass OH/UG Xcel/UL TSMR420CSCU
(NEMA 3R)
200 20 10 40 18 40 Outdoor MB Surface Horn Bypass OH/UG Xcel/UL TSMR2020CSCU1
(NEMA 3R)
200 20 10 40 18 40 Outdoor MB Surface Lever OH/UG Xcel/UL TSMB2020CSCU1
(NEMA 3R) Bypass
1Devices include removable closing cap. Order hub separately. See page 1-27.
Application Data
Main Wire Size
Box Unit Width Unit Height Depth Factory Inst. (AWG/kcmil) Equipment
Product Number Number (in inches) (in inches) (in inches) Svcs Disc Cu-Al Ground Kit
TSLR412CSCU R31 14-9/16 33-9/16 6-3/16 Field Installed2 6-350 TGK12 (order separately)
TSLB412CSCU R12 14 23-1/2 4-7/8 Field Installed2
6-350 TGL1 installed
TSMR1212CSCU R30 14-9/16 40-1/2 6-3/16 THHQL 6-350 TGK12 (order separately)
TSMB1212CSCU R20 14-3/4 27-5/16 5-7/16 THHQL 12-2/0 TGK12 (order separately)
TSMR415CSCU R31 14-9/16 33-9/16 6-3/16 THQMV 6-350 TGK12 installed
TSMR2015CSCU R30 14-9/16 40-1/2 6-3/16 THQMV 6-350 TGK12 (order separately)
TSMB2015CSCU R18 14-3/4 33 6-5/16 THQMV 1-300 TGK12 (order separately)
TSLB420CSCU R14 14 30-3/4 5-3/4 Field Installed2 6-350 TGL1 installed
TSLR420CSCU R31 14-9/16 33-9/16 6-3/16 Field Installed2 6-350 TGK12 (order separately)
TSMR420CSCU R31 14-9/16 33-9/16 6-3/16 THQMV 6-350 TGK12 installed
TSMR2020CSCU R30 14-9/16 40-1/2 6-3/16 THQMV 6-350 TGK12 (order separately)
TSMB2020CSCU R18 14-3/4 33 6-5/16 THQMV 1-300 TGK12 (order separately)
2THQL and THHQL only. 125 amp max. TQDL is obsolete.
Section 1
Meter Socket LC
1PH
Ringless with Bypass
Xcel Energy
NEMA 3R
Rev. 11/13
Data subject to change
without notice
Load Centers and Circuit Breakers
PowerMark Gold Meter Socket Load Centers
1-21
BuyLogCatalogwww.geindustrial.com
Single-Phase, Three-Wire, 120/240 Vac
With Bonded Neutrals
Georgia Power Ringless - Main Breaker
Main
Ampere 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total 1-pole Enclosure Bypass UL Agency Product
Rating 1” Spaces 1” Spaces 1/2” Spaces 1/2” Spaces Spaces Type Front Type Type Incoming Certification Number
150 – – – Outdoor Surface None OH/UG UL/GP TSMR015CSGP1,4
(NEMA 3R)
200 – – – Outdoor Surface None OH/UG UL/GP TSMR020CSGP1,4
(NEMA 3R)
150 4 2 8 3 8 Outdoor Surface None OH/UG UL/GP TSMR415CSCUGP1,4
(NEMA 3R)
200 4 2 8 3 8 Outdoor Surface None OH/UG UL/GP TSMR420CSCUGP1,4
(NEMA 3R)
Application Data
Main Wire Size
Box Unit Width Unit Height Depth Factory Inst. (AWG/kcmil) Equipment
Product Number Number (in inches) (in inches) (in inches) Svcs Disc Cu-Al Ground Kit
TSMR015CSGP R32A 18-7/8 18-9/16 5 THQD 2-250 –
TSMR020CSGP R32A 18-7/8 18-9/16 5 THQD 2-250 –
TSMR415CSCUGP R40 14 32 4-1/2 THQMV 6-350 TGL2 included
TSMR420CSCUGP R40 14 32 4-1/2 THQMV 6-350 TGL2 included
Florida Meter Group MSLC Ringless - Main Breaker
Main
Ampere 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total 1-pole Enclosure Bypass UL Agency Product
Rating 1” Spaces 1” Spaces 1/2” Spaces 1/2” Spaces Spaces Type Front Type Type Incoming Certification Number
150 4 2 8 3 8 Outdoor Surface None OH/UG UL/FMG TSMR415CSFLFMG
(NEMA 3R)
200 4 2 8 3 8 Outdoor Surface None OH/UG UL/FMG TSMR420CSFLFMG
(NEMA 3R)
150 8 4 16 6 16 Outdoor Surface None OH/UG UL/FMG TSMR815CSFLFMG4
(NEMA 3R)
200 8 4 16 6 16 Outdoor Surface None OH/UG UL/FMG TSMR820CSFLFMG4
(NEMA 3R)
200 20 4 40 18 40 Outdoor Surface None OH/UG UL/FMG TSMR2020CSCUFMG2
(NEMA 3R)
Application Data
Main Wire Size
Box Unit Width Unit Height Depth Factory Inst. (AWG/kcmil) Equipment
Product Number Number (in inches) (in inches) (in inches) Svcs Disc Cu-Al Ground Kit
TSMR415CSFLFMG R36A 14 28-1/2 4-1/2 THQMV 6-350 TGL2 included
TSMR420CSFLFMG R36A 14 28-1/2 4-1/2 THQMV 6-350 TGL2 included
TSMR815CSFLFMG R37A 14 31-3/4 4-1/2 THQMV 6-350 TGK24 included
TSMR820CSFLFMG R37A 14 31-3/4 4-1/2 THQMV 6-350 TGK24 included
TSMR2020CSCUFMG R403 14 34-1/2 4-1/2 THQMV 6-350 TGK24 included
1Use FMG unit if Ringless standard UL design is required by your local utility.
2No feed through lugs.
3Knock outs are the same as R36A.
4Feed-thru lugs provided.
Section 1
Meter Socket LC
1PH
Ringless
Georgia Power
Florida Meter Group
Main Breaker
NEMA 3R
Load Centers and Circuit Breakers
PowerMark Gold Meter Socket Load Centers
1-22 BuyLogCatalog Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
Class 320
Main 1 Pole, 2 Pole, 1 Pole, 2 Pole, Total
Ampere 1” 1” 1/2” 1/2” 1-pole Enclosure Bypass UL Agency Product
Rating Spaces Spaces Spaces Spaces Spaces Type Front Type Type Incoming Certification Number
320 24 12 32 14 40 Outdoor Surf/Semi None UG UL TM2432RMS1,2,3
(NEMA 3R)
400 0 0 0 0 0 Outdoor Surf/Semi Lever Bypass UG UL TSDR040UFCU4
(NEMA 3R)
300 8 4 16 6 16 Outdoor Surface Lever Bypass UG UL TSDR830USCU4
(NEMA 3R) FMG
400 8 4 16 6 16 Outdoor Surface Lever Bypass UG UL TSDR840UFCU4
(NEMA 3R) FMG
400 24 12 32 14 40 Outdoor Surf/Semi K-4 Bolt-In UG UL TM2440RMKS1,2,3
(NEMA 3R) Meter Provision
400 24 12 32 14 40 Outdoor Surf/Semi Lever Bypass UG UL TM2440RMRS1,2,3
(NEMA 3R)
400 24 12 32 14 40 Outdoor Surf/Semi None UG UL TM2440RMS1,2,3
(NEMA 3R) EUSERC
400 24 12 32 14 40 Outdoor Surf/Semi Lever Bypass UG UL TMH2440RMRS1,2,3,4
(NEMA 3R) Xcel
400 24 12 32 14 40 Outdoor Surf/Semi None UG UL TMH2440RMS1,2,3,4
(NEMA 3R)
320 0 0 0 0 0 Outdoor Surf/Semi Lever Bypass UG UL TSD032UFCU4
(NEMA 3R)
320 24 12 32 14 42 Outdoor Surf/Semi Link Bypass UG UL TSDA2432UC424
(NEMA 3R) EUSERC
400 24 12 32 14 42 Outdoor Surf/Semi Link Bypass UG UL TSDA2440UC424
(NEMA 3R) EUSERC
1200A main breaker factory installed. Space provided for field mounted TQD-WL sub feed.
2For semi-flush applications, order surface enclosure load center and field installed kit, Product number SF400.
3Stud provisions only provided.
422 kAIC.
Application Data
Main Wire Size
Product Box Unit Width Unit Height Depth Factory Inst. Field Inst. (AWG/kcmil) Equipment
Number Ringless Number (in inches) (in inches) (in inches) Main Breaker Main Breaker Cu-Al Ground Kit
TM2432RMS No R24 30-1/4 40 6 TQD THQL (1) 800 or (2) 400 compression type; (2) TGL2
(1) 1000 or (2) compression type; (order separately)
(1) 1000 or (2) 350 pressure type
TM2440RMS No R24 30-1/4 40 6 TQD TQD (1) 800 or (2) 400 compression type; (2) TGL2
(1) 1000 or (2) 350 pressure type (order separately)
TMH2440RMS No R24 30-1/4 40 6 THQD THQD (1) 800 or (2) 400 compression type; (2) TGL2
(1) 1000 or (2) 350 pressure type (order separately)
TSDA2432UC42 No R24 30-1/4 40 6 THQD THQL/THHQL (1) 800 or (2) 400 compression type (2) TGL2
(order separately)
TSDA2440UC42 No R24 30-1/4 40 6 THQD TQD/THQD (1) 800 or (2) 400 compression type (2) TGL2
(order separately)
TSD032UFCU No R33 30-1/4 33 6-3/32 THQD THQL/THHQL (1) 800 or (2) 400 compression type (2) TGL2
(order separately)
TM2440RMKS Yes R23 30-1/4 40 6 TQD TQD (1) 800 or (2) 400 compression type; (2) TGL2
(1) 1000 or (2) 350 pressure type (order separately)
TM2440RMRS Yes R24 30-1/4 40 6 TQD TQD (1) 800 or (2) 400 compression type; (2) TGL2
(1) 1000 or (2) 350 pressure type (order separately)
TMH2440RMRS Yes R24 30-1/4 40 6 THQD THQD (1) 800 or (2) 400 compression type; (2) TGL2
(1) 1000 or (2) 350 pressure type (order separately)
TSDR040UFCU Yes R33 30-1/4 33 6-3/32 THQD TQD/THQD (1) 800 or (2) 400 compression type (2) TGL2
(order separately)
TSDR840UFCU Yes R33 30-1/4 33 6-3/32 THQD TQD/THQD (1) 800 or (2) 400 compression type (2) TGL2
(order separately)
Section 1
Meter Socket LC
1PH
Class 320
NEMA 3R
Rev. 11/13
Data subject to change
without notice
Load Centers and Circuit Breakers
PowerMark Gold Meter Socket Load Centers
Single-Phase, Three-Wire, 120/240 Vac
With Bonded Neutrals
1-23
BuyLogCatalogwww.geindustrial.com
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLogCatalog
1-24
Section 1Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Field Installed Accessories
PowerMark Gold Main Circuit Breaker Kit
For use with 125A PowerMark Gold load Centers; 22kAIC RMS symmetrical.
Product
Description Number
Main Circuit Breaker Kit - Order appropriate THQL TQMH0001
10kAIC or THHQL 22kAIC breakers separately
1Please review the footnotes listed with the individual Load Center product numbers for proper parts needed to
convert to a main circuit breaker. This main breaker base is only applicable for 16 circuit and larger 125 amp load
centers, 12 circuit load centers with A C24 suffix, and the TLM812RCU2.
PowerMark PlusEquipment Ground Kits
Product
Description Standard Package Quantity Number
(4) 14-8Cu/12-8AL, 20 TGL1
(3) 14-4Cu/6-4AL
(8) 14-8Cu/12-8AL, 20 TGL21
(6) 14-4Cu/6-4AL
(7) 14-8Cu/12-8AL, (3) 14-4Cu/6-4AL, 20 TGL81
(2) 14-4Cu/12-4AL, (1) 14-2Cu/AL
(1) 6-2/0Cu/Al Number of Terminals, 20 TGL202
Equipment Ground Kits
(3) 10-1/0 Cu/Al Number of Terminals 1 TNG33
for 400 and 600 Amp
(6) 10-1/0 Cu/Al Number of Terminals 1 TNG64
for 400 and 600 Amp
1TGL2, TGL4 and TGL8 mount interchangeably
2Add-on Equipment Ground Lug (for use on any TGL Kit)
3Suitable for use with up to six TPLUG108 lugs or six crimp lugs per pole
PowerMark Gold Equipment Ground and Isolated Ground Bar Kits4,5
Product
Description Standard Package Quantity Number
4-hole Ground 1 TGK4
12-hole Ground 1 TGK12
24-hole Ground 1 TGK24
32-hole Ground 1 TGK32
42-hole Ground 1 TGK42
46-12 circuit indoor load centers use PowerMark Plus style neutrals and grounds
5Add TGKIS for isolated ground and mount to ground kit.
TQMH000
TGL2
TGL20 combined with TGL1
TGK12
TGK12 with TGKIS
www.geindustrial.com BuyLogCatalog 1-25
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Field Installed Accessories
Rev. 11/13
Data subject to change
without notice
Section 1
PowerMark PlusNeutral Kits
Wire Standard Product
Description Range Package Quantity Number
400 & 600 Amp PowerMark PlusNeutral Kit (5) 14-1/0 1 TNLK11
400 & 600 Amp PowerMark PlusNeutral Kit (3) 1-300 1 TNLK21
Add-on neutral lug for 100-200 Amp PowerMark 6-2/0 1 286A8894G1
Plus load centers
Add-on neutral lug for 100-200 Amp PowerMark 1-300 Cu or 1 192A7663G13
Plus load centers 2/0-300 Al
1Suitable for use with up to six TPLUG108 lugs or six crimp lugs per pole
PowerMark Gold Neutral Kits
Wire Standard Product
Description Range Package Quantity Number
PowerMark Gold Neutral Kit - 6-2/0 1 TNLK20
Mounted on top of neutral only
PowerMark Gold Neutral Kit - 6-250 1 TNLK250
Mounted on top of neutral only
PowerMark Gold Neutral/Ground Lug Kits
Mounted on any neutral or ground position by removing the termination screw
Wire Standard Product
Description Range Package Quantity Number
Neutral/Ground Lug Kit 6-2/0 1 TLK20
Neutral/Ground Lug Kit 6-250 1 TLK250
Neutral/Ground Lug Kit 6-300 1 TLK300
Isolated Ground Bus Bars Equipment Ground Kit
Standard Product
Description Package Quantity Number
Isolated Ground Bar Kit (order with 1 TGKIS
TGK Equipment Ground Kits)
Isolated Ground Bar Feet (Order with TGK8) 1 TGKIS2
Subfeed Lug Kits
Standard Product
Description Package Quantity Number
125A 2 Pole Plug-in 1 THLK2125
150A 2 Pole Plug-in - For use with PowerMark Gold only 1 THLK2150
200A 2 Pole Plug-in - For use with PowerMark Gold only 1 THLK2200
125A 3 Pole Plug-in 1 THLK3125
225A 3 Pole Plug-in - For use with 3 phase only 1 THLK3225
TNLK250
TLK20 TLK250
TGK12 with TGKIS
192A7663G13 286A8894G1
Sub-feed and Feed-thru Lugs
UL Listed
For use in load centers to economically supply power to a subpanel.
Product
Poles Ampere Rating Number
2 125 THLK2125
3 125 THLK3125
2 150 THLK21501
2 200 THLK22001
3 225 THLK32252
1For use with PowerMark Gold load centers only
2For use with three-phase load centers only. Includes mounting base.
THLK2125
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLogCatalog
1-26
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Field Installed Accessories
Section 1
PowerMark PlusMain Lug Kits
Product
Description Wire Range (Cu/Al) Number
150 Amp PowerMark PlusReplacement Main Lug kit 2-3/0 THLK150
200 Amp PowerMark PlusReplacement Main Lug kit 1-250 THLK200
PowerMark Gold Main Lug Kits
Product
Description Wire Range (Cu/Al) Number
125 Amp PowerMark Gold Replacement Main Lug kit 6-2/0 TMLK125
200 Amp PowerMark Gold Replacement Main Lug kit 6-250 TMLK200
225 Amp PowerMark Gold Replacement Main Lug kit 6-300 TMLK225
For replacement of main lugs on 125 amp load centers; TLM load centers include main lugs.
Door Lock
Standard Product
Description Package Quantity Number
For indoor load centers larger than 12 circuits (Does not fit TPL412) 10 TDL106
Circuit Directory
Standard Product
Description Package Quantity Number
Card and holder with pressure-sensitive backing. 1 TD42
Mounts inside the door.
Touch-up Paint
Standard Product
Description Package Quantity Number
12 3/4 oz. spray can of light gray enamel 1 TSP61
THLK200
PowerMark Gold main lug kits - TMLK200
TDL106
TD42
TSP61
www.geindustrial.com BuyLogCatalog 1-27
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Field Installed Accessories
Rev. 11/13
Data subject to change
without notice
Section 1
Front Filler Plates
Standard Product
Description Package Quantity Number
1/2” Front Filler Plate 100 TFH
1” Front Filler Plate 50 TQLFP1
Covers 1/2” rectangular breaker knockouts
Covers 1” rectangular breaker knockouts
Universal Raintight Hubs
Standard Product
Description Base Size (in.) Package Quantity Number
3/4” Diameter 3 10 TC75
1” Diameter 3 10 TC100
1-1/4” Diameter 3 10 TC125
1-1/2” Diameter 3 10 TC150
2” Diameter 3 10 TC200
2-1/2” Diameter 3 10 TC250
3” Diameter 3 5 TC300
Closing Cap 3 10 TCCP
2” Diameter 4 TCU27
2-1/2” Diameter 4 TCU28
3” Diameter 4 TCU30
3-1/2” Diameter 4 TCU35
4” Diameter 4 TCU401
4” Cover Plate 4 TCUP
1For 40 and 42 circuit units in R8 boxes only.
Door Handle
Standard Product
Description Package Quantity Number
Replacement Door Handle Universal 1 TRL22
PowerMark Gold Cross Arm
Standard Product
Description Package Quantity Number
Replacement cross arm for
PowerMark Gold load centers 1 LCCROSSARM
TFH
TRL22
TC150
LCCROSSARM
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLogCatalog
1-28
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Field Installed Accessories
Section 1
PowerMark Gold Main Breaker Retainers
Product
Description Breaker Type Number
Travel Trailer Main Breaker Retainer Kit THQP THQPSBK
for THQP Breakers
For use on PowerMark Plusload centers with THQL THQLRK
THQL Breakers 225A max
For use with 12 - 42 circuit PowerMark Gold THQL THQLRK1
load centers with THQL Breakers
For use with 6 - 8 circuit PowerMark Gold THQL THQLRK2
load centers with THQL Breakers
For use with TM/TLM1212CCU Mod 2 current model THQL THQLRK3
For use with 6 - 42 circuit PowerMark Gold THQL THQLRK4
load centers with THQL Breakers. Similar to
THQLRK1 but it does not take up a breaker space.
For main lug load centers utilizing a back fed branch breaker as a main
Handle Locks - Padlocking
Product
Description Breaker Type Number
THQP Padlocking Handle Lock THQP TQPPL
THQL Padlocking Handle Lock THQL THP100
TQD Padlocking Handle Lock TQD TQDPLD1
Snap on handle lock
Padlock not included
Handle Locks - Non Padlocking
Product
Description Breaker Type Number
THQP Non Padlocking Handle Lock THQP TQPL
THQL Non Padlocking Handle Lock THQL THL103
Snap on handle lock
Handle Ties
Product
Description Breaker Type Number
Handle Ties for THQP Breakers - Solid Snap-on THQP THT11
Trip Indicating
Handle Ties for THQP Breakers - For 2 THQPs THQP THT21
separated by 2 side-by-side THQPs
TQB
Snap-on Handle Tie - Trip Indicating TQC TQHT11
TQL
TQB
Snap-on Handle Tie - Solid TQC THT1041
TQL
Multiwire Branch Breaker TQB TQ3HTK2
TQC
Handle Tie Kits TQL TQ4HTK3
All multi-pole breakers have internal common trip
Handle ties provide manual on-off capability only between one-pole devices
1For two single-pole breakers
2For three single-pole breakers - kit includes (10) pcs.
3For four single-pole breakers - kit includes (10) pcs.
THQLRK
THQLRK1
THL103
THT1
THT104
THT2
TQHT1
www.geindustrial.com BuyLogCatalog 1-29
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Field Installed Accessories
Rev. 11/13
Data subject to change
without notice
Section 1
Load Center Hardware Kits Hardware
Standard Product
Description Package Quantity Number
PowerMark Plushardware kit: TQD THQD Main or 1 LCHDKIT
THLK main lug kit in a TLM load center, installation
instructions and front mounting screws
Powermark Gold Bond Screw Kit Screw 100 - 200A 1 TBS
Powermark Gold Bond Screw Kit 225A 1 TBS22
Powermark Gold Hardware kit 1 THDWRKIT
containing 20 front mounting screws
Powermark Gold Hardware kit 1 THDWRKIT2
containing 10 interior mounting screws
Generator Interlock Kit
Standard Product
Description Package Quantity Number
Load Center Generator Interlock Kit 1 THQLLX1
MSLC Generator Interlock Kit 1 THQLLX4
MSLC Generator Interlock Kit 1 THQLLX8CU
MSLC Generator Interlock Kit 1 THQLLX8DR
MSLC Generator Interlock Kit 1 THQLLX8FL
PowerMark Gold Auxiliary Gutter Enclosures
Product
Description Number
24” Auxiliary Gutter Enclosure TMAGB24
28” Auxiliary Gutter Enclosure TMAGB28
28” Auxiliary Gutter Enclosure Flush TMAGB28F
33” Auxiliary Gutter Enclosure TMAGB33
39” Auxiliary Gutter Enclosure TMAGB39
43” Auxiliary Gutter Enclosure TMAGB43
43” Deep Auxiliary Gutter Enclosure TMAGB43D
PowerMark Gold Gutter Tap Kits
Product
Description Number
250 kcmil Lugs Gutter Tap Kit - one kit per phase required TMGT250
500 kcmil Lugs Gutter Tap Kit - one kit per phase required TMGT500
750 kcmil Lugs Gutter Tap Kit - one kit per phase required - TMGT750
Not for use with riser panels
Meter Socket Load Center Flange Kits
Product
Description Number
Semi-Flush Kit 400A for MSLC SF400
Semi-Flush Kit 400A for MSLC Adjustable SF400A
Semi-Flush Kit 200A for MSLC Adjustable SF200A
Surge Protectors
Product
Description Number
SurgePro AC 27KA Panel-Mount Surge Protector THQLSURGE
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLogCatalog
1-30
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Wiring Diagrams
Section 1
Breaker Fill
Breaker Symbol 1” THQL 1/2” THQP
1
1 2
Wire Range (AWG/kcmil)
Terminal Symbol Cu Al
o 14-8 12-8
14-4 12-4
A 6-2 6-2
B 14-1/0 12-1/0
C 6-2/0 6-2/0
D 1-300 2/0-300
E 1-300 1-300
F 6-1 6-1
G 6-3 6-3
G G G
TL240SCU, RCU
TL270SCU, RCU
C
C
MAIN LUGS
TPL412CT, TL412CT
TPL412RT, TL412RT1
TLM612FCU, SCU
FCUD, SCUD, RCU
C
MAIN
TLM1612CCU, TM1612CCU, TM1612RCU
C E
E
MAIN
BREAKER
SUB−FEED
LUGS
TM815RCUFL
TM820RCUFL
C
MAIN LUGS
TPL412C, TL412C, TPL412R, TL412R1,
TL412R2, TL412R250GF, TL412R260GF
FMAIN
BREAKER MAIN
BREAKER
TM860FCUGEN, TLM830FCUGEN,
TM860SCUGEN, TLM830SCUGEN,
TM860RCUGEN, TLM830RCUGEN
EC MAIN
TM1615CCU, TM1615RCU, TM1620CCU,
TLM1620CCU, TLM1620RCU
F F
C
TLM812RCU2
MAIN
CC
TM2420R42B
E
MAIN
TLM2012CCURP
C
MAIN
C C C C
TM1210CCU, TM1212CCU, TLM1212CCU
E
AA
T
TL510RT
TM1210RCU, TM1212RCU, TLM1212RCU
F F
F
TLM812FCU, SCU,
FCUD, SCUD, RCU
www.geindustrial.com BuyLogCatalog 1-31
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Wiring Diagrams
Rev. 11/13
Data subject to change
without notice
Section 1
Breaker Fill
Breaker Symbol 1” THQL 1/2” THQP
1
1 2
Wire Range (AWG/kcmil)
Terminal Symbol Cu Al
o 14-8 12-8
14-4 12-4
A 6-2 6-2
B 14-1/0 12-1/0
C 6-2/0 6-2/0
D 1-300 2/0-300
E 1-300 1-300
F 6-1 6-1
G 6-3 6-3
MAIN EC
TM2020CCU, TM2020RCU
TLM2020CCU, TLM2020RCU
MAIN
C E
TM4222RCU, TLM4222CCU
TLM4222RCU, TM4222CCU
MAIN
CE
TM4020CCU, TM4020RCU
TLM4020CCU, TLM4020RCU
MAIN
EC
TM3215C42, TLM3220C42, TM3220C42
MAIN
EC
TM3220CCU, TM3220RCU, TLM3220CCU
MAIN
CE
TM2415RCU, TLM2415RCU
MAIN C
TM2410CCU, TM2412CCU
TM2412RCU, TLM2412CCU, TLM2412RCU
MAIN C
TL12412
MAIN
C
TM3210CCU
MAIN
EC
TM3215CCU, TM3215RCU
C
MAIN
TM12410
MAIN
C
TM2010CCU, TM2010RCU
MAIN
C E
TLM2420C42, TM2415C42
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLogCatalog
1-32
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Wiring Diagrams
Section 1
Breaker Fill
Breaker Symbol 1” THQL 1/2” THQP
1
1 2
Wire Range (AWG/kcmil)
Terminal Symbol Cu Al
o 14-8 12-8
14-4 12-4
A 6-2 6-2
B 14-1/0 12-1/0
C 6-2/0 6-2/0
D 1-300 2/0-300
E 1-300 1-300
F 6-1 6-1
G 6-3 6-3
MAIN
CCD
TL24415, TM24415
MAIN
MAIN
D D D CCCCCCC
TL24440, TM24420
MAIN
CCD
TM30412
MAIN
CC CD
TM30415, TL30420, TM30240, TL30422
C
MAIN
TM18410
MAIN
CCD
TL18415, TL18420
www.geindustrial.com BuyLogCatalog 1-33
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Wiring Diagrams
Rev. 11/13
Data subject to change
without notice
Section 1
Breaker Fill
Breaker Symbol 1” THQL 1/2” THQP
1
1 2
Wire Range (AWG/kcmil)
Terminal Symbol Cu Al
o 14-8 12-8
14-4 12-4
A 6-2 6-2
B 14-1/0 12-1/0
C 6-2/0 6-2/0
D 1-300 2/0-300
E 1-300 1-300
F 6-1 6-1
G 6-3 6-3
MAIN
CCD
TL42420, TM42415C, TM42420
MAIN
CC CD
TL42422
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLogCatalog
1-34
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Wiring Diagrams
Section 1
WHM
A
A
A
TSL412CSCU
C
C
WHM
C
MAIN
BREAKER
SPACE PROVIDED
FOR 110A PARALLEL
MAIN BREAKER
TSF420CSCU
WHM
A
B
A
A
TSL420CSCU, TSL420CFCU
C
C
WHM
C
MAIN
BREAKER
TSM815CSCU, TSM820CSCU
WHM
MAIN
B
C
A
DDC
E
ALoad
Load
TSM415CSCU, TSM420CSCU, TSMF415CSFL,
TSMF420CSFL, TSMR415CSCUGP, TSMR420CSCUGP,
TSMR415CSFLFMG, TSMR420CSFLFMG
C
C
WHM
MAIN
BREAKER
TSM1212CSCU, TSM1212CFCU
WHM
A
A
A
TSL210CSCU, TSL210CFCU
WHM
MAIN
CB
AB C
TM10RMC, TM12RMC, TM15RMC, TM20RMC,
TSMR015CSGP, TSMR020CSGP
Breaker Fill
Breaker Symbol 1” THQL 1/2” THQP
1
1 2
Wire Range (AWG/kcmil)
Terminal Symbol Cu Al
o 14-8 12-8
14-4 12-4
A 6-2 6-2
B 14-1/0 12-1/0
C 6-2/0 6-2/0
D 1-300 2/0-300
E 1-300 1-300
F 6-1 6-1
G 6-3 6-3
www.geindustrial.com BuyLogCatalog 1-35
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Wiring Diagrams
Rev. 11/13
Data subject to change
without notice
Section 1
C
C
WHM
MAIN
BREAKER
TSM1610CSCU, TSM1610CFCU, TSM1612CFCU, TSM1612CSCU
MAIN
BREAKER
C
C
WHM
TSM2020CSCU, TSM2020CFCU
MAIN
CC
WHM
A
B
N
TSM2420UF42
WHM
MAIN
BREAKER
B PHA PH
CE
NEUTRAL
TSM3220USCU, TSM3220UFCU, TSM3222USCU,
TSM3222UFCU
MAIN
BREAKER
WHM
TSMR2020CSCU, TSMR2015CSCU,
TSMB2020CSCU, TSMB2015CSCU
MAIN
BREAKER
WHM
CE
TSM4020UWCU
WHM
TSLR420CSCU, TSLR412CSCU,
TSLB412CSCU, TSLB420CSCU
WHM
MAIN
BREAKER
TSMR1212CSCU, TSMB1212CSCU
MAIN
BREAKER
WHM
CE
TSM3220UWCU
WHM
MAIN
DDC
C
D
E
A
Sub feed lugs
TSM815CSFL, TSM820CSFL, TSMF815CSFL,
TSMF820CSFL, TSMR815CSFLFMG,
TSMR820CSFLFMG
Breaker Fill
Breaker Symbol 1” THQL 1/2” THQP
1
1 2
Wire Range (AWG/kcmil)
Terminal Symbol Cu Al
o 14-8 12-8
14-4 12-4
A 6-2 6-2
B 14-1/0 12-1/0
C 6-2/0 6-2/0
D 1-300 2/0-300
E 1-300 1-300
F 6-1 6-1
G 6-3 6-3
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLogCatalog
1-36
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Wiring Diagrams
Section 1
Breaker Fill
Breaker Symbol 1” THQL 1/2” THQP
1
1 2
Wire Range (AWG/kcmil)
Terminal Symbol Cu Al
o 14-8 12-8
14-4 12-4
A 6-2 6-2
B 14-1/0 12-1/0
C 6-2/0 6-2/0
D 1-300 2/0-300
E 1-300 1-300
F 6-1 6-1
G 6-3 6-3
MAIN
C
C
C
WHM
Line
Neutral
CE
TSM2015URCU
WHM
MAIN
Space for Field Installed
Second Main Breaker
T
TSD032UFCU
Space for Field Installed
Second Main Breaker
WHM
MAIN
TSDR040UFCU
Space for Field Installed
Second Main Breaker
WHM
MAIN
CE
TSDR840UFCU
CC C D
Space for
Field-installed
TQD Breaker
200A
Main
Breaker
WHM
L1 NL2
TM2440RMKS, RMRS, RMS,
TMH2440RMS, TMH2440RMRS
Space for
Field-installed
Breaker
WHM
L1 L2
MAIN
CE
N
C
TSDA2432UC42, TSDA2440UC42
B PHA PH
CE
NEUTRAL
WHM
MAIN
BREAKER
TSM2022USCU, TSM2022UFCUTSMR2020CSCUFMG
WHM
MAIN
D
Ground
termination
DC
C
D
E
www.geindustrial.com BuyLogCatalog 1-37
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Indoor Enclosures
Rev. 11/13
Data subject to change
without notice
Section 1
Symbol A B C D E F G H J K L M N P Q R S T U V W X Y Z
5/16 – – – – – – – – – – – – – – –
3/8 3/8 – 3/8 – – – – – – – – – –
1/2 1/2 1/2 1/2 1/2 1/2 1/2 – – – – – – – 1/2
3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 – – – 3/4 – 3/4 3/4 3/4
Conduit – – – – 1 1 1 1 1 1 1 – 1 1 – 1 – 1 – 1 1
Size – – – – – 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 – – – 1 1/4 1 1/4 –
in – – – – – 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 – – 1 1/2 1 1/2 1 1/2
inches – – – – – – – – 2 2 2 2 2 2 – 2 2 – – 2 2
– – – – – – 2 1/2 2 1/2 2 1/2 2 1/2 – 2 1/2 2 1/2 – 2 1/2 2 1/2
– – – – – – – – – 3 – 3 3 – –
– – – – – – – – – – 3 1/2 3 1/2 3 1/2 –
– – – – – – – – – – – – 4
Box No. Width Height Depth
1A 5 11/16 10 1/4 3 3/8
2 7 1/2 9 7/32 3 5/16
2A 7 1/4 9 3
3A 11 9/16 11 3/8 3 3/8
4 14 19 3 3/4
4A 14 19 3 3/4
6 14 23 3 3/4
7 14 24 11/16 3 3/4
8 14 26 7/16 3 3/4
9 14 28 7/16 3 3/4
9A 14 28 7/16 3 3/4
11 14 33 3/16 3 3/4
12 14 35 7/16 3 3/4
13 14 39 3/16 3 3/4
14 14 43 7/16 3 3/4
15 14 43 7/16 4 5/8
16 16 45 1/8 5 13/16
17 20 59 7/8 6 3/32
18 14 16 3 3/8
Knockouts
Dimensions (in inches)
C
C
B
BG
GZ
Z
Box 4A, 9A
AA
A
AB
D
D
D
D
X
W
W
WX
X
X
Box 2
C
CCC
C
S
S
S
S
S
H
HA
A
A
A
A
B
B
B
B
B
B
B
B
C
C
C
C
KK
K
N
N
Box 15
K
K
G
G
B
Box 2A
A
A
AA
A
A
B
B
B
B
B
B
P
P
P
P
P
C
C
T
T
J
J
Box 16
A
DD
D
D
K
KH
H
AA
A
Box 3A
B
B
B
B
B
B
JJ
JJ
GG
G
UV
C
CC
R
A
P
Box 17
H
H
H
H
H
Q Q
Y
Y
Y
Y M
M
A
A
A
A
A
A F D
D
D
D
D
D
Q
Box 4, 6, 7, 8, 9, 11, 12, 13, 14
A
A
A
A
A
A
H
HH
H
J
JD
D
G
G
Box 1A
BB B
BBB
D
D
AK
D
B
B
D
D
K
K
D
D
D
D
D
D
B
B
B
B
B
D
D
D
D
D
B
B
B
B
B
D
AA
D
A
BB
K
AA
K
BDD K
B
Box 18
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLogCatalog
1-38
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Outdoor Enclosures
Section 1
Symbol A B C D E F G H J K L M N P Q R S T U V W X Y Z AA BB CC DD
9/16 – – – – – – – – – – – – – – – – – – – – – – – –
3/8 – 3/8 – – – – – – – – – – – – – – – – – – – –
1/2 1/2 1/2 1/2 1/2 1/2 1/2 – – – – – – – 1/2 – – – – – – 1/2 – 1/2 1/2
– 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 – – 3/4 – 3/4 – 3/4 – – – 3/4 – – 3/4 – 3/4 3/4
Conduit – – – – 1 1 1 1 1 1 1 – 1 1 – 1 – 1 – 1 – – 1 1
Size – – – – 1 1/4 – 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 – – – 1 1/4 1 1/4 1 1/4 – 1 1/4 1 1/4
in – – – – – 1 1/2 – – – 1 1/2 1 1/2 1 1/2 1 1/2 – 1 1/2 1 1/2 1 1/2 – – – – 1 1/2 1 1/2 1 1/2 – 1 1/2 1 1/2 1 1/2
Inches – – – – – – – – – – – 2 2 2 2 2 2 2 2 – – 2 2 – 2 2 2
– – – – – – – – – – 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 – 2 1/2
– – – – – – – – – – – – – – 3 3 – – – – 3
– – – – – – – – – – – – – – 3 1/2 3 1/2 3 1/2 – – – 3 1/2 –
– – – – – – – – – – – – – – – 4 – – – 4
Knockouts
Box No. Width Height Depth
R1 7 1/2 9 7/32 3 5/16
R1A 7 1/4 10 3 3/4
R1B 7 3/8 13 3 3/4
R2A 11 1/4 11 1/8 3 1/4
R3A 13 21 1/2 5
R3 12 1/2 21 3/16 4 5/8
R4A 14 11/16 30 3/16 5 1/4
R4 14 33 3/16 4 5/8
R5A 13 29 5
R5 12 1/2 28 11/16 4 5/8
R6A 13 33 5
R6 14 35 7/16 4 5/8
R7A 14 11/16 34 3/16 5 1/4
R7 14 39 3/16 4 5/8
R8A 14 21/32 43 1/4 6 13/32
R8 14 43 11/16 5 3/4
R9 16 45 15/16 5 27/32
R10 20 48 15/16 6 7/8
R11 20 59 15/16 6 7/8
R41 7 1/2 13 1/4 4
Dimensions (in inches)
X
XX
D
D
D
A
A
W
W
W
B
A
X
Box R1
Q
Q
QD
DH
A
Q
Box R3, R4, R5, R6, R7
B
C
C
CC
C
CC
J
J
R
B
GVU
B
Box R10, R11
HUB
G
B
K
Box R1A
B
BB
P
P
R
RLL
C
TJ
Box R9
DD
D
Box R2A
U
R
B
D
J
U
RAKD
Box R8
Mounting provided
for universal hubs
K
B
B
K
K
K
K
Box R41
Box R4A, R7A
Box R3A, R5A, R6A
R8A
www.geindustrial.com BuyLogCatalog 1-39
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Meter Socket Load Centers
Rev. 11/13
Data subject to change
without notice
Section 1
Symbol A B C D E F G H J K L M N P Q R S T U V W X Y Z AA BB CC DD EE FF
5/32 – – – – – – – – – – – – – – – – – – – – –
3/8 3/8 – 3/8 – – – – – – – – – – – – – – – – –
1/2 1/2 1/2 1/2 – 1/2 1/2 1/2 – – – – 1/2 – – – – – 1/2 1/2 1/2 1/2
3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 – 3/4 3/4 – – 3/4 – 3/4 3/4 3/4 3/4 – 3/4
Conduit – 1 1 1 1 1 1 1 1 1 – 1 1 – 1 – – 1 1 – 1
Size – – 1 1/4 – 1 1/4 1 1/4 1/1/4 1/1/4 1 1/4 1 1/4 1 1/4 1 1/4 – 1 1/4 1 1/4 – – – 1 1/4 1 1/4 1 1/4 – 1 1/4 1 1/4 1 1/4 1 1/4
in – – – 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 – 1 1/2 1 1/2 1 1/2 – – – – 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2
inches – – – – – – – – – – 2 2 2 2 2 2 – 2 2 – 2 2 2 2 2 2 2
– – – – – –– – – – 2 1/2 2 1/2 2 1/2 2 1/2 – 2 1/2 2 1/2 – – 2 1/2 2 1/2 – 2 1/2 2 1/2 2 1/2
– – – – – – – – – – – 3 3 – – – – 3 – – –
– – – – – – – – – 3 1/2 3 1/2 3 1/2 – – – 3 1/2 – – – –
– – – – – – – – – – – – 4 – – – 4 – – –
Knockouts
Box No. Width Height Depth
R12 14 23 1/2 4 7/8
R14 14 30 3/4 5 3/4
R15 16 3/4 33 6 3/16
R16 16 3/4 33 6 3/16
R17 16 3/4 34 1/4 7 5/16
R18 14 3/4 33 6 5/16
R19 16 3/4 28 1/2 7 5/16
R20 14 3/4 27 5/16 5 7/16
R21 14 9/16 43 5/8 7 3/16
R22 16 3/16 48 1/8 7 3/16
R23 30 1/4 40 6
R24 30 1/4 40 6
Dimensions (in inches)
B
B
C
K
B
B
B
BB
BB
CCG
C
C
CC CC
BBB
Box R21, R22
HUB
PUNCHING HUB
PUNCHING
B
B
B
B
BB
B
BB
B
B
A
CC
C
A
Box R16
AA
D
D
R
K
S
S
Z
R
G
D
Box R23
B
B
B
B
B
BB
BB
CCG
C
C
CC CC
BBB
BB
B
B
B
C
C
C
B
B
A
K
B
B
B
B
Box R17, R18
S
Z
R
K
AA
D
D
R
K
S
Z
G
Box R24
B
B
BB
BB
C
C
C
C
C
A
G
B
B
BB
C
CC
B
C
CG
C
C
CCCC
BBB
BBBB
Q
Box R19, R20
Semi-Flush Only
Y
FF
A
W
B
BB
FF
F
EE BB
B
A
C
Box R12
Semi-Flush Only
EE
EE
AK
E
B
Q
A
C
B
F
Box R14
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLogCatalog
1-40
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Meter Socket Load Centers
Section 1
Symbol A B C D E F G H J K L M N P Q R S T U V W X Y Z AA BB CC DD EE FF
5/32 – – – – – – – – – – – – – – – – – – – – –
3/8 3/8 – 3/8 – – – – – – – – – – – – – – – – –
1/2 1/2 1/2 1/2 – 1/2 1/2 1/2 – – – – 1/2 – – – – – 1/2 1/2 1/2 1/2
3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 – 3/4 3/4 – – 3/4 – 3/4 3/4 3/4 3/4 – 3/4
Conduit – 1 1 1 1 1 1 1 1 1 – 1 1 – 1 – – 1 1 – 1
Size – – 1 1/4 – 1 1/4 1 1/4 1/1/4 1/1/4 1 1/4 1 1/4 1 1/4 1 1/4 – 1 1/4 1 1/4 – – – 1 1/4 1 1/4 1 1/4 – 1 1/4 1 1/4 1 1/4 1 1/4
in – – – 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 – 1 1/2 1 1/2 1 1/2 – – – – 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2
inches – – – – – – – – – – 2 2 2 2 2 2 – 2 2 – 2 2 2 2 2 2 2
– – – – – –– – – – 2 1/2 2 1/2 2 1/2 2 1/2 – 2 1/2 2 1/2 – – 2 1/2 2 1/2 – 2 1/2 2 1/2 2 1/2
– – – – – – – – – – – 3 3 – – – – 3 – – –
– – – – – – – – – 3 1/2 3 1/2 3 1/2 – – – 3 1/2 – – – –
– – – – – – – – – – – – 4 – – – 4 – – –
Knockouts
Box No. Width Height Depth
R25 14 26 4 1/2
R26 14 9/16 43 5/8 6 3/16
R27 14 9/16 48 1/8 6 3/16
R28 22 1/2 27 7/8 6 1/4
R29 22 1/2 34 7/8 6 1/4
R30 14 9/16 40 1/2 6 3/16
R31 14 9/16 33 9/16 6 3/16
R32 16 17 5
R32A 18 7/8 18 9/16 5
R40 14 32 4 1/2
Dimensions (in inches)
B
B
B
B
L
R
B
B
A
BC
C
Box R30
HUB
PUNCHING HUB
PUNCHING
BB
BB
BBBB
BB
C
K
B
Box R26, R27
L
R
A
B
B
BC
C
GG EE EE
E
CC CC CC
9/32
HUB
Box R31
Box R40
EE
G
CCB BB
B
EE
BB
BB
B
Box R28
HUB
PUNCHING
FF
FF
ABB
P
G G
HUB
PUNCHING
FF
FF
ABB
P
Box R32 Box R32A
BB
G
CCBBB
B
BB
BB
BB
B
Box R29
Z
Z
Z Z
S
SB
1/4"
S
HUB
PUNCHING HUB
PUNCHING
Box R25
www.geindustrial.com BuyLogCatalog 1-41
Load Centers and Circuit Breakers
PowerMark Gold and Plus Load Centers
Circuit Breakers
Meter Socket Load Centers
Rev. 11/13
Data subject to change
without notice
Section 1
Knockouts
Symbol A B C D E F G H J K L M N P Q R S T U V W X Y Z AA BB CC DD EE FF GG
5/32 – – – – – – – – – – – – – – – – – – – – – – –
3/8 – 3/8 – – 3/8 – – – – – – – – – – – – – – – – –
1/2 1/2 1/2 1/2 – 1/2 1/2 1/2 – – – – – 1/2 – – – – 1/2 – – 1/2 1/2 1/2 –
– – 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 – – 3/4 – 3/4 – 3/4 – – – 3/4 3/4 3/4 3/4 3/4 – 3/4 –
Conduit – – – – – – 1 1 1 1 1 1 1 – 1 1 – – 1 – – 1 1 – – 1 1 – 1 –
Size – – – – – – 1 1/4 – 1 1/4 1 1/4 1/1/4 1/1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 – – 1 1/4 1 1/4 1 1/4 – 1 1/4 1 1/4 – 1 1/4 1 1/4 1 1/4
in – – – – – – 1 1/2 – 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 – – – – 1 1/2 1 1/2 1 1/2 – 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2
inches – – – – – – – – – 2 2 2 2 2 2 – 2 2 – 2 2 2 2 2 2 2 2
– – – – – –– – – – – – 2 1/2 2 1/2 2 1/2 2 1/2 – 2 1/2 2 1/2 – 2 1/2 – 2 1/2 – 2 1/2 2 1/2 2 1/2 2 1/2
– – – – – – – – – – – – – – 3 3 3 – – – 3
– – – – – – – – – – – – – 3 1/2 3 1/2 3 1/2 – 3 1/2 – – – –
– – – – – – – – – – – – – – – 4 – 4 – – – –
Box No. Width Height Depth
R33 30 1/4 33 6 3/32
R34 30 1/4 40 6 3/32
R35 30 1/4 47 6 3/32
R36 14 28 1/2 4 1/2
R37 14 31 3/4 4 1/2
R38 14 49 1/2 10
R39 14 31 11/16 4 5/8
R40 14 32 4 1/2
Dimensions (in inches)
DDD
D
DK
AA AA
KRR
K
DG
DDDDD
SSSSZZSS
3/32 3/323/32
Box R33
GG EE EE
E
CC CC CC
9/32
HUB HUB
Box R36B, R37B
DDD
D
DKK RR
K
DG
DDDDD
SSSSZZSS
3/323/32
Box R34, R35
CC
C
C
C
C
C
C
C
C
C
CCC
C
C
CC
9/32
K
EE
EE
EE
EE
EE
Box R39 Box R40
D D D D D
D D
BDB
B B
LL
W
Box R38
GG EE GG
E
CC CC CC
9/32
HUB HUB
d
Box R36A, R37A
GG EE EE
E
CC CC CC
9/32
HUB
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLogCatalog
1-42
Load Centers and Circuit Breakers Section 1
NOTES:

Navigation menu