FEATURES & SPECIFICATIONS
INTENDED USE — Ideal for applications requiring attractive steel exit signage. Meets city of Chicago
requirements.

Type

CONSTRUCTION — 20-gauge steel housing with glass panel face.
Uniform graphical illumination without shadows or hot spots.

Steel Exits

Letters are 6” high with 100 ft viewing distance rating based upon UL924 standard (meets UL924 requirements however models with the city of Chicago required full stroke arrow cannot bear any UL mark). Full
stroke arrow. City of Chicago approved.

LXC

OPTICS — White LED technology provides uniform illumination to meet city of Chicago requirements.
The typical life of exit LED lamp is 10 years. Unique LED lamp platform accommodates both single-face
and double-face exits.
Low energy consumption; fewer than five watts.
ELECTRICAL — Dual-voltage input capacity (120/277). Battery (for EL option only): Sealed, maintenance-free nickel-cadmium battery delivers 90 minutes capacity to lamp. Charger maximizes battery life
and automatically recharges after battery discharge.

LED LAMPS

INSTALLATION — Universal mounting (top, end or back). Canopy provided.
Full stroke arrow option available.
LISTINGS — UL listed damp location 32°F to 122°F (0°C to 50°C). Meets UL 924 (meets UL924 requirements however models with the city of Chicago required full stroke arrow cannot bear any UL mark),
NFPA 101 (current Life Safety Code), NEC and OSHA illumination standards. City of Chicago approved.
WARRANTY — 5-year limited warranty. Complete warranty terms located at
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx

Specifications
LXC EXIT
LXC STAIRS
Length: 12-3/8 (31.5)
Length: 13-7/8(35.3)
Depth: 4-1/2 (11.5)
Depth: 4-1/2 (11.5)
Height: 11-1/4 (28.6)
Height: 13-7/8 (35.3)
Shipping Weight : 7.8 lbs Shipping Weight : 7.8 lbs

Note: Actual performance may differ as a result of end-user environment and application.
All values are design or typical values, measured under laboratory conditions at 25 °C.
Specifications subject to change without notice.

ORDERING INFORMATION
LXC

RW

Family
LXC

Example: LXC W 1 RW CH2 EL

Lead times will vary depending on options selected. Consult with your sales representative.

LED exit

Housing color

Number of faces

Letter color

Directional indicators1

W
B

1

Single face
Double face

RW Red on white
background

Single face

2

White
Black

Accessories: Order as separate catalog number.
ELA US12
ELA WG1

EMERGENCY

CH3

EXIT with no arrow

CH6

EXIT with right arrow

CH9

EXIT with left arrow

CH12

EXIT with double arrow

CH2

STAIRS with no arrow

CH5
CH8
CH11

STAIRS with right arrow
STAIRS with left arrow
STAIRS with double arrow

Operation
Double face
CH18 EXIT with no arrow
CH21 EXIT with right/left arrow
CH24 EXIT with double arrow
CH17 STAIRS with no arrow
CH20 STAIRS with right/left arrow
CH23 STAIRS with double arrow

(blank)
EL

Standard non-emergency
Emergency operation with
nickel-cadmium battery

Notes
1 See charts on page 2 for more information.
2 See spec sheet ELA-Stemkit.
3 See spec sheet ELA WG.

12” stem kit 2
Wireguard 3 (back mount only)

LXC

LXC Steel Exits
MOUNTING

SPECIFICATIONS

All dimensions are inches (centimeters).

ELECTRICAL
Primary Circuit
Type

Typical
LED life1

EXIT/STAIRS AC only

10 years

EXIT/STAIRS emergency

10 years

Supply
voltage
120

Input
watts
5

Max.
amps
0.10

277
120
277

5
5
5

0.05
0.10
0.05

6-7/8
(17.5)

4-1/2
(11.5)

11-1/4
(28.6)

10-3/8
(26.4)

BATTERY
Sealed Nickel-Cadmium (EL option)
Shelf
life2
3 years

Typical
life2
5-7 years

Maintenance3
none

Optimum
temperature4
32°–122°F (0°–50°C)

12-3/8 (31.5)

Notes
1 Based on continuous operation. The typical life of the exit LED lamp is 10 years.
2 At 77°F (25°C).
3 All life safety equipment, including emergency lighting path of egress, must be maintained, serviced and tested
in accordance with all National Fire Protection Association and local codes. Failure to perform the required
maintenance, service or testing could jeopardize the safety of occupants and will void all warranties.
4 Optimum ambient temperature range where unit will provide capacity for 90 minutes. Higher and lower
temperatures affect life and capacity. Consult factory for detailed information.

2-3/8
(6.1)

10-3/8 11-1/4
(26.4) (28.6)

13-7/8 (35.3)

Directional Indicators (Exit)

*Models with the city of Chicago required full stroke arrow cannot
bear any UL mark. Excludes: CH3, CH18

Directional Indicators (Stairs)

*Models with the city of Chicago required full stroke arrow cannot
bear any UL mark. Excludes: CH2, CH17

LXC

EMERGENCY: One Lithonia Way Conyers, GA 30012

Phone: 800.334.8694

Fax: 770-981-8141 www.lithonia.com

© 2010-2016 Acuity Brands Lighting, Inc. All rights reserved. Rev. 10/18/16



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.7
Linearized                      : Yes
Has XFA                         : No
Language                        : en-US
XMP Toolkit                     : Adobe XMP Core 5.6-c123 79.158978, 2016/02/13-01:11:19
Create Date                     : 2016:10:18 12:25:37-05:00
Metadata Date                   : 2016:10:18 12:25:52-05:00
Modify Date                     : 2016:10:18 12:25:52-05:00
Creator Tool                    : Adobe InDesign CC 2015 (Macintosh)
Instance ID                     : uuid:e7608fee-fa57-8b40-9c52-0c62e261fbf8
Original Document ID            : xmp.did:0DD70B77235AE011B7B89995924C2DAB
Document ID                     : xmp.id:f71d3ea9-9a61-45b6-9023-6bc38263d94b
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:2e01343b-449b-416a-a4ed-2defae6656b5
Derived From Document ID        : xmp.did:C8F73FB98A6CE111A76DA5F0BB67C5F2
Derived From Original Document ID: xmp.did:0DD70B77235AE011B7B89995924C2DAB
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CC 2015 (Macintosh)
History Changed                 : /
History When                    : 2016:10:18 12:25:37-05:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 15.0
Trapped                         : False
Slug Family                     : Myriad Pro
Slug Version                    : 1.006
Slug Outline File Size          : 0
Slug Kerning Checksum           : 0
Slug Foundry                    : Adobe Systems
Slug Font Kind                  : OpenType - PS
Slug Checksum                   : 3932508134
Slug Post Script Name           : MyriadPro-Cond
Slug Font Sense 12 Checksum     : 3932508134
Page Count                      : 2
Creator                         : Adobe InDesign CC 2015 (Macintosh)
EXIF Metadata provided by EXIF.tools

Navigation menu