Installation Directions
62343-Installationsheet 62343-InstallationSheet 62343-InstallationSheet 078477 Batch10 unilog cesco-content
35023-Installationsheet 35023-InstallationSheet 35023-InstallationSheet 078477 Batch2_1 unilog cesco-content
2016-07-29
: Pdf 1000332179-Installationsheet 1000332179-InstallationSheet B2 unilog
Open the PDF directly: View PDF .
Page Count: 2
RENOIR II
SWITCH & REMOTE DIMMING CONTROL
Cat. Nos. AWRRG, AWSRG, AWSRT, AWWMG, AWWMT, AWWRG & AWWRT
INSTALLATION
WARNINGS AND CAUTIONS:
• TO AVOID FIRE, SHOCK OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!
• TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH ELECTRICAL CODES AND REGULATIONS.
• IF YOU ARE NOT SURE ABOUT ANY PART OF THESE INSTRUCTIONS, CONSULT AN ELECTRICIAN.
• DO NOT GANG VERTICALLY.
• ONLY INSTALL FOR THE ALLOWED LOAD TYPES. INSTALLATION FOR ANY OTHER LOAD TYPE WILL VOID WARRANTY AND POSSIBLY CAUSE DAMAGE TO
THIS DEVICE AND/OR CONNECTED EQUIPMENT.
• USE THIS DEVICE WITH COPPER OR COPPER CLAD WIRE ONLY.
Installation Requirements:
• Thesedevicesaredesignedforinstallationintoametal2"x3"(5.08cmx7.62
cm)singlegangormulti-gangdevicebackbox.2-1/2"(6.35cm)ordeeper
backboxesarerequired.Thesedevicesarenotdesignedforamulti-gangeld
conguredbox.Insomeinstallationswhereconduitentryisfromtheside,or,in
multi-ganginstallationswherenipplesbetweentwoadjacentboxesareused,
deeperbackboxesmaybenecessary.Testtinstallationpriortorough-in.
• Installationofmultipledevicesintoasingleboxmayrequirede-ratingandother
specicinstallationprovisions.ReferenceMulti-Gang Installationsformore
details.
•
Asdevicesventtop/bottom,devicesshouldnotbeinstalledvertically(oneoverthe
other).
• Toavoidickering,ashing,orlightsononedeviceadjustingwhenanother
device’slevelischanged,donotshareneutrals.Runseparateneutralsforeach
loadcircuitbacktothedevice.(See Figure 1).
Installation Instructions:
1. WARNING: TO AVOID FIRE, SHOCK OR DEATH; TURN OFF POWER AT
CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE
WIRING!
2.Removeexistingwallplateandswitch,ifapplicable.
3.Remove5/8"(1.6cm)ofinsulationfromeachcircuitconductor.Makesurethe
endsofwiresarestraight.
4.ConnectwiresperWIRINGDIAGRAMondeviceasfollows:Twiststrandsofeach
leadtightlytogetherand,withcircuitconductors,pushrmlyintoappropriatewire
connector.Screwconnectorsonclockwisemakingsurenobareconductorsshow
belowthewireconnectors.Secureeachconnectorwithelectricaltape.
5.Installationmaynowbecompletedbycarefullypositioningallwirestoprovide
roominoutletboxfordevice.Mountdeviceintoboxwithmountingscrews
supplied.Snapfaceplateintoplace.
6.Installdevicecontrolpushbuttonandcontrolassembly(see Figure 2).
7.Restorepoweratcircuitbreakerorfuse.Installation is complete.
8.TestDeviceoperation.
INPUT - 120 - 277 VAC 60 HZ OUTPUT-AWWMG-00X&AWWMT-00X-15A
Features and Operation:
• TurnDeviceONorOFF–PressingtheswitchwillturnthedeviceONifthe
deviceisOFF.IfthedeviceisON,pressingtheswitchwillturnthedeviceOFF.
• SetDeviceLevel–Adjusttheknoborslidertosetthedesiredoutputlevel.When
thedeviceturnsON,thedevicealwaysturnsONtothelevelsetbytheslideror
knob.
• SetCutoffLevel–Thecutofflevelisthelowestvoltagethedimmerwilloutput
beforeshuttingOFF.Tosetthecutofflevel,adjusttheknoborslidertothe
maximumoutput.Slowlylowertheoutputtothedesiredcutofflevel,thenpush
andholdthepowerbuttonfor5seconds.Thedimmerwilladjusttothenewlevel.
Toresetthecutofflevelto0,adjusttheknoborslidertotheminimumoutput,then
pushandholdthepowerbuttonfor5seconds.Ifyourloadisickering,notturning
ON,orsufferingfromanyothererraticbehaviorattheminimumsetting,raising
thecutofflevelmayeliminatetheproblem.
• PresetOperation–Whiledeviceisoff,setlevelofdevice.Thenpressbutton.The
devicewillturnonatthesetlevel.
• PowerRestore–Uponrestorationofpower,thedeviceturnsONtothestateit
wasinatthetimeofpowerloss.
• 5-WayOperation–Linktogether2,3,4,or5devicesformulti-waydimming.
• LEDLocator–AtthebottomoftheswitchisanLEDlocator.Thislocator
illuminateswhenthedeviceisOFFsoyoucanndthedeviceinthedark.
• RemoteControl–Ifyouareusingaremote,theoperationattheremoteis
identicaltotheoperationatthemaster.Aslightreactiondelaymaybenoticedif
operatinglevelchangesveryquickly.
ForTechnicalAssistanceCall:1-800-824-3005(U.S.A.Only)www.leviton.com
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
LevitonwarrantstotheoriginalconsumerpurchaserandnotforthebenetofanyoneelsethatthisproductatthetimeofitssalebyLevitonisfreeofdefectsinmaterialsandworkmanshipundernormalandproperuseforveyearsfromthepurchasedate.Leviton’sonlyobligation
istocorrectsuchdefectsbyrepairorreplacement,atitsoption,ifwithinsuchveyearperiodtheproductisreturnedprepaid,withproofofpurchasedate,andadescriptionoftheproblemtoLevitonManufacturingCo.,Inc.,Att:QualityAssuranceDepartment,201North
ServiceRoad,Melville,NewYork11747.Thiswarrantyexcludesandthereisdisclaimedliabilityforlaborforremovalofthisproductorreinstallation.Thiswarrantyisvoidifthisproductisinstalledimproperlyorinanimproperenvironment,overloaded,misused,opened,
abused,oralteredinanymanner,orisnotusedundernormaloperatingconditionsornotinaccordancewithanylabelsorinstructions.Therearenootherorimpliedwarrantiesofanykind,includingmerchantabilityandtnessforaparticularpurpose,butifanyimplied
warrantyisrequiredbytheapplicablejurisdiction,thedurationofanysuchimpliedwarranty,includingmerchantabilityandtnessforaparticularpurpose,islimitedtoveyears.Levitonisnotliableforincidental,indirect,special,orconsequentialdamages,including
withoutlimitation,damageto,orlossofuseof,anyequipment,lostsalesorprotsordelayorfailuretoperformthiswarrantyobligation.Theremediesprovidedhereinaretheexclusiveremediesunderthiswarranty,whetherbasedoncontract,tortorotherwise.
PK-93969-10-00-2A
Align flats when
installing knob
Center tab in opening
Figure2-RemoteDimmerAssembly
RotaryDevice SlideDevice
Wiring Diagram
Switch Control
LOAD
Black
Blue
Neutral (White)
Hot (Black)
White
White Yellow
For use in multi-way
control (remote)
applications.
Cap wire if not used.
Ground (Green)
Line
120-277VAC
60 Hz
Figure1-DONOTshareneutralwires
Blue
Hot (Black)
Neutral (White)
White
White
Load
Blue
Black
Black
White
Yellow
Yellow
Green
Ground
White
Hot (Black)
Neutral (White)
–
Load
X
–
Run a separate neutral wire
for each control circuit
–
Run a separate neutral wire
for each control circuit
DO NOT
share
neutral
wires
Green
Ground
PK-93969-10-00-2A
©2012LevitonMfg.Co.,Inc.
Multi-WayControl:
TheRenoirIIproductlinesupportsupto5-waycontrol.Anycombinationof
Dimmers,
FanControls,Switches,orRemotesaresupportedwithaMAXIMUM OF
5 DEVICES.TotalrunlengthfromendtoendisMAXIMUM 250 FEET.Remotes
requireUncontrolledHot,Neutral,&Groundforproperoperation.Onetravelerwireis
toruninbetweenallmastersandremotes.Remotesdraw15mApower(ea)fromthe
Controltowhichtheyareconnected.
NOTE:RemoteHot/NeutralshouldideallybefedfromthesamecircuitastheMaster.If
thisisnotpossible,ensurethatthemasterandremotearebothfedfromthesamephase.
Backbox - # Gangs
Wallplate Part #
Device Configuration
Backbox - # Gangs
Wallplate Part #
Device Configuration
Backbox - # Gangs
Wallplate Part #
Device Configuration
Backbox - # Gangs
Wallplate Part #
Device Configuration
Number & Type of NARROW
Number & Type of WIDE
0
1
2
3
0
4**
N+N+N
AWP00-30x
2
N*+*N
AWP00-20x
1
N
AWP0F-10x
1
6**
W+N+N+N
AWP00-31x
4
W+N*+*N
AWP00-21x
3
W+N
AWP0F-11x
1
W
AWP0F-01x
2
7
W+N*+N*+*N+W
AWP00-32x
6
W+N*+*N+W
AWP00-22x
5 or 6
W+N+W
AWP0F-12x
4
W+W
AWP0F-02x
3
9
W*+*W+N*+N*+*N+W
AWP00-33x
8
W*+*W+N*+*N+W
AWP00-23x
8
W+W+N+W
AWP0F-13x
6**
W+W+W
AWP0F-03x
Basic Configurations
Multi-Gang Installations:
Amulti-gangedinstallationexistswhenmultipledevicesareinstalledinthesame
backbox.Inmulti-ganginstallations,thefollowingmayberequired:
- Devicede-rating -Finremoval
- Useofjoinerbarsforadjacentdevices. - Backboxsize
NOTE: TEST FIT DEVICE INSTALLATION WITH THE WALL PLATE PRIOR TO
BREAKING FINS OR INSTALLING DEVICES TO ENSURE YOU UNDERSTAND ALL
REQUIREMENTS.
1.
Findthecellsthatcorrespondtoyourapplicationbyidentifyingtherowwiththe
numberofwideheatsinkdevicesyouhave,andthecolumnsthatcorrespond
tothenumberofnarrowheatsinkdevicesyouhave.Inthecellyou’llndthe
following:
2.
Thenumberindicatesthenumberof“Gangs”required.
3.
Thelettersunderthenumberindicatetheorderdevicesshouldbeinstalled,
N=narrow,W=wide.
4.-W*=rightnbreak-offonwidedevice,N*=rightnbreak-offonnarrowdevice.
-*W=leftnbreak-offonwidedevice,*N=leftnbreak-offonnarrowdevice.
-*W*=nbreak-offonbothsidesofwidedevice,*N*=nbreak-offonbothsidesof
narrowdevice.
5.**indicatesthatuseofjumperbarsisrequired.Jumperbarscanbefoundinthekit
withthefaceplate.
6. Replace'x'inthefaceplatepartnumberwiththedesiredcolor:W=White,I=Ivory,
A=Almond,T=LightAlmond,E=Black,G=Gray,K=24KGold,L=SatinStainless,
R=AntiqueBronze,B=BrushedBrass.
NOTE:Metalnishesarenotavailableoncustomfaceplates.
BasicWIDE/NARROWcongurations,foradditionalcongurationssee:
www.leviton.com/RENOIRII
BackBoxSize&JoinerBars:
Todeterminetherequiredback-boxsizeinmulti-ganginstallations,reference
tablebelow.Inapplicationswherethedevicesdonotlineupwithbackboxdevice
mountingholes,usejoinerbarstojointhecontrolstogether.ReferenceFigure 5.
De-ratings:
Whennsarebroken,somedevicesmustbede-rated.Referencetablebelowto
determinethedeviceratingswhen0,1,or2nsareremoved.
Switches-120-277VAC/VCA,60Hz
Useonlyforresistive,incandescent,inductive,ballastormotorload.
Switches
AWWMG-0D_
AWWMT-0D_
Amps
VA @ 120V
FLA
VA @ 120V
VA @ 230V
VA @ 277V
VA @ 230V
VA @ 277V
0, 1 or 2 fins
removed
1HP
15.0
1.5HP
1.5HP
1800
12.0
4150
3450
FinRemoval:
Whenitisdesiredtoinstalldevicesinassmallaspaceaspossible,allinsidensoflike
sized,adjacentdevicescanbebrokenoff.Figure 4showhowtobreakoffnsandthe
specicorderinwhichmultipledevicesmustbeinstalledinmulti-ganginstallations.
MULTI-GANGINSTALLATIONREQUIREMENTS
Additional-SingleGangBox
Multi-WayControlWiringDiagram
Maximum 5 Devices, Dimmers, Remotes or Fan Controls
Maximum 250 feet
Device/Switch
Maximum 5 Devices, Dimmers, Remotes or Fan Controls
Maximum 250 feet
Remote
Device/Switch Remote
Device/Switch Remote
Device/Switch
Multiple Device/Switches and Remote Device/Switches
Master
Device/Switch Remote
Device/Switch Remote
Device/Switch Remote
Device/Switch Remote
Device/Switch
Hot
Neutral
Ground
Traveler
Hot
Neutral
Ground
Hot
Neutral
Ground
Traveler
Hot
Neutral
Ground
Traveler
Hot
Neutral
Ground
Traveler
Dimmed Hot
Neutral
Ground
LOAD
Hot
Neutral
Ground
Traveler
Hot
Neutral
Ground
Hot
Neutral
Ground
Traveler
Hot
Neutral
Ground
Traveler
Hot
Neutral
Ground
Traveler
Dimmed Hot
Neutral
Ground
LOAD
Dimmed Hot
Neutral
Ground
LOAD
Multiple Remote Device/Switches
Load in between Master Device/Switch and Remote Device/Switch
Master Device/Switch Remote Device/Switch
Dimmed Hot
Neutral
Ground
Hot
Neutral
Ground
Traveler
Hot
Neutral
Ground
LOAD
Load after Remote Device/Switch and Master Device/Switch
Master Device/SwitchRemote Device/Switch
Hot
Neutral
Ground
Hot
Neutral
Ground
Dimmed Hot
Neutral
Ground
Traveler
LOAD
Master
Device/Switch
Figure4-FinRemoval
Back view of devices shown
Break off these fins
DO NOT Break off these fins
Break off these fins
Fin break off points
Figure5-JoinerBar
Narrow/Narrow
Wide/NarrowWide/Wide
Joiner Bar
Joiner Bar
3/4" space (use chase nipple)
3-1/2" deep
back box is
required
Four-gang wallbox Single-gang
wallbox