Product Detail Manual
2016-08-17
: Pdf 1000431796-Attachment 1000431796-Attachment B3 unilog
Open the PDF directly: View PDF .
Page Count: 2
68966 - UltraStart(R) T8 Step Dimming Program Start Dimming
Ballast
GE132-MVPS-N-S30
Bi-level Switching 100 to 30%☞
Program Start Bi-level Dimming☞
Anti-Striation Control for better light quality, with no striations.☞
2 or 1 F32T8 120-277V N .88 BF UltraStart (R) 100/30% Bi-level
Switching
☞
UL 55C (131F) Ambient rating - High Temparature Protection
Circuit
☞
Multi-Voltage Technology handles voltage from 120 to 277V☞
Parallel Lamp Operation - reliable deep dimming performance☞
UL Type CC Rating provides protection against arcing in electrical
devices.
☞
Product Photo
GENERAL CHARACTERISTICS
Ambient Temp [Max] 55 °C
Ballast Factor Normal
Ballast Type Dimming
Case Temperature (Max) 70 °C
Dimming Type Step dimming
Enclosure Type Metal
Line Voltage Regulation (+/-) 10
Classification (Regulations) ANSI - C82.11
ANSI - C62.41
UL Type HL
UL Type 1 Outdoor
Product is compliant with
material restriction
requirements of RoHS
cUL Listed
UL Type CC
FCC Part 18 (Class A) for EMI
and RFI Non-Consumer Limits
High Temperature Rated:
Suitable for high temperature
applications
70C max case temp 5 yr
warranty or 90C max case
temp 3 yr warranty
NEMA Premium®
Sound Rating A (20-24 decibels)
Starting Method Programmed start
Product Technology Linear Fluorescent
Lamp Wiring Parallel
Power Factor Correction Active
PRODUCT INFORMATION
Product Code 68966
Description GE132-MVPS-N-S30
Alternative Unit Of Measure EACH
Standard Package Quantity 10
Ean UPC 043168689663
Standard Package GTIN 00043168689663
No Of Items Per Sales Unit 1
No Of Items Per Standard Package 10
Sales Unit Each
UCC 043168689663
Alternative Unit Of Measure CASE
DIMENSIONS
Weight 1.47 lb
Exit Type
Remote Mount Distance 8.0 ft
Case Dimensions
Length 9.5in
Width 1.7in
Height 1.2in
Mounting Dimensions
Mount Length 8.9in
Mount Slot 0.25in
Lead Color Qty Exit Length ( 1 in.)
Black 1 Left 25in
Yellow 1 Right 47in
Blue 1 Left 33in
White 1 Right 25in
Red 1 Right 33in
SAFETY & PERFORMANCE
Jul 4, 2016 9:17:15 AM For additional information, visit www.gelighting.com
ANSI_C82☞ANSI_C62☞UL_Type_HL☞UL_Type1_Out☞Pro_comp_res_req☞cUL_Listed☞UL_Type_CC☞FCC_Part_18_Limits☞High_Temp_App☞
SPECIFICATIONS BY LAMP & WATTAGE
Lamp # of Lamps Line Volts System
Watts Nom. Line
Current System
Ballast
Factor
Ballast
Efficacy
Factor
Power
Factor% (>=) Crest Factor
(<=) THD% (<=) Min. Starting
Temp (F/ C)
F17T8 1 120 18 0.16 0.95 5 0.99 1.7 10 0
F17T8 1 277 18 0.08 0.95 5 0.87 1.7 14 0
F25T8 1 277 24 0.1 0.9 4 0.92 1.7 11 0
F25T8 1 120 25 0.21 0.9 4 0.99 1.7 5 0
FE15T8 1 120 15 0.13 0.92 6 0.99 1.7 10 32
FE15T8 1 277 15 0.07 0.92 6 0.99 1.7 17 32
F32T8/25W 1 120 25 0.22 0.84 3 0.99 1.7 5 32
F32T8/25W 1 277 24 0.1 0.84 4 0.91 1.7 11 32
F36T8 1 120 25 0.22 0.88 4 0.99 1.7 5 32
F36T8 1 277 25 0.1 0.88 4 0.92 1.7 11 32
F28T8 1 120 25 0.22 0.87 3 0.99 1.7 5 32
F28T8 1 277 26 0.1 0.87 3 0.92 1.7 11 32
F32T8/WM 1 120 28 0.25 0.88 4 0.99 1.7 5 32
F32T8/WM 1 120 12 0.11 0.18 2 0.99 1.7 10 32
F32T8/U 1 120 30 0.26 0.88 3 0.99 1.7 5 0
F32T8/U 1 120 12 0.11 0.25 2 0.99 1.7 10 32
F32T8/U 1 277 29 0.12 0.88 3 0.94 1.7 10 0
F32T8/U 1 277 13 0.06 0.25 2 0.93 1.7 20 32
F32T8/WM 1 277 13 0.06 0.18 1 0.83 1.7 21 32
F28T8 1 120 12 0.11 0.22 2 0.99 1.7 5 32
F28T8 1 277 13 0.06 0.22 2 0.83 1.7 21 32
F32T8/25W 1 120 12 0.11 0.23 2 0.99 1.7 10 32
F32T8/25W 1 277 13 0.06 0.23 2 0.83 1.7 21 32
F25T8 1 120 9 0.08 0.17 2 0.98 1.7 10 32
F25T8 1 277 10 0.05 0.17 2 0.77 1.7 25 32
F17T8 1 120 10 0.09 0.21 2 0.98 1.7 10 32
F17T8 1 277 10 0.05 0.21 2 0.78 1.7 25 32
F36T8 1 120 14 0.11 0.18 1 0.99 1.7 10 32
FE15T8 1 277 8 0.04 0.38 5 0.68 1.7 32 32
F36T8 1 277 13 0.06 0.18 1 0.94 1.7 20 32
FE15T8 1 120 7 0.06 0.38 5 0.97 1.7 12 32