PowerPlus™ Panelboards
Lighting & Heat Tracing Panels
EPL (Div. 1 & 2)
D2L (Div. 2)

Power Panels
EXD (Div. 1 & 2)
D2D (Div. 2)

PowerPlus™ Series
Panelboards provide both
premium factory-sealed and
value non-factory-sealed
solutions for the protection
and distribution of lighting,
power, and heat tracing
circuits.
This panel solution is
designed, engineered, and
manufactured to be the
industry’s safest and most
dependable panelboard for
hazardous area locations.

PowerPlus™ Panelboards

This corrosion-resistant Type 4X
breather and drain comes standard
with all PowerPlus panelboards. This
permits all models to maintain their
Type 4 (Type 4X with suffix S752) rating
while utilizing a breather/drain solution
to drain internal condensation while
protecting against ingress of rain and
hose water.

PowerPlus D2L and EPL panels are available
with GFI and/or EPD breakers. This 21-position
electrical test circuit allows for testing of GFI,
EPD, or a combination of both in one panel.
EPLDN panels are available with up to 42 GFI or
EPD circuits with 225 amp main breaker.

PowerPlus panels come
standard with a high-quality
silver-plated copper buss
system. This provides highefficiency current flow
between the main feed and
branch breakers.

Each branch and main
breaker handle is provided
with lockout/tagout
capability, which complies
with OSHA lockout/tagout
requirements for safety.
This allows for locking in the
ON or OFF position for
standard maintenance
checks.

Spring-loaded, quick-release, captive stainless steel cover bolts
come standard. This design prevents damage to the flat joint
flame path when opening and closing the cover while providing
visual identification of bolt engagement.

PowerPlus panels are
available with an optional
hinged stainless steel
ice/dust shield. This ice
shield solution prevents ice
and snow build-up on
breaker handles to allow for
proper handle function in
cold/wet climate
applications.
Stainless steel hinges are engineered to provide maximum stability and allow
the cover to swing fully open. This avoids misalignment of cover to the body of
the enclosure and prevents the cover from obstructing interior access.
2

EPLCN or
EXDCN*
*Note: D2D / EXD panels are not available with GFI or EPD
circuit breakers or electrical test circuit as standard.
Please contact factory if required.

Integrated steel lifting eye is mounted on
the top side of each PowerPlus panel.
This provides a stable lifting position to
ensure ease of mounting during the
installation process.

PowerPlus cast enclosures are manufactured
with an external flange design. This design
allows for a wide unobstructed cover opening
and provides a completely accessible interior
for ease of maintenance and wiring.
Superior self-aligning breaker operators
are designed for both field and factory
installation. This patent-pending design
guarantees proper handle alignment when
closing the cover.†

All panels with terminal housings
are factory-sealed†† and fully wired
for maximum available circuits. This
allows PowerPlus models the ability
to have additional breakers fieldinstalled while maintaining their
factory seal.

All terminal blocks come fully wired
with each contact numbered for
easy connecting of branch entries.

Heavy gauge 316L stainless
steel terminal housings are
supplied with three removable
gland plates to be used with
Myers® Hubs. This design
allows for the flexibility of
factory- or field-drilled
openings for hubs.

D2LBS (Inverted)
or D2DBS (Inverted)
†Not available in Size F offering. Spring aligning forks are standard on
Size F panels.
††EPL*A and EXD*A conduit entries 2” or larger in Class I, Division 1 must
be sealed within 18” of enclosure. All alternate feed entries to breaker
housing (suffix A) must have an external seal within 18” of enclosure.

PowerPlus panelboards offer an
industrial grade 316L stainless
steel terminal housing as standard.
This design offers an increased
internal volume with a removable
front cover for easy access during
field installation and maintenance.
A cast aluminum terminal housing
is standard on EPL and EXD panels
and available on D2L and D2D
panels.

Stainless steel terminal
housings offer a high-integrity
gasket, providing a watertight
seal to meet enclosure Type
4/CSA ENC. 4/IP65
requirements. This provides
superior protection of enclosed
wiring against water and
corrosion. Cast aluminum
enclosures are also gasketed,
providing a NEMA 4 watertight
seal.

3

PowerPlus™ Panelboards

•

P re m i u m S o l u t i o n : PowerPlus factory-sealed panelboards are premium panelboards that provide maximum circuit
flexibility with labor savings during installation, operation, and maintenance, and are accommodating for future changes in the
field (order with either “S” or “A” in base part number). Panels are pre-wired to maximum circuit capacity, allowing for easy and
safe replacement or installation of components in the field, while maintaining factory-sealed integrity.

•

Va l u e S o l u t i o n : PowerPlus non-factory-sealed panelboards are value panelboards that offer maximum circuit flexibility
and many of the same features and benefits of the PowerPlus premium line. This value solution is provided without terminal
housing and factory wiring of circuits (order with “N” in base part number). The non-factory-sealed solution reduces initial
panelboard material costs and requires field wiring to circuit breakers and external seals to be field-installed during installation.

APPLICATIONS
PowerPlus panelboards are used:
•

in areas made hazardous by the continuous or abnormal presence of flammable gases, vapors, and combustible dusts

•

in areas subject to weather, dampness, and corrosion

•

for branch power distribution and circuit protection to motors,
valves, pumps, lighting, heat tracing, receptacles, etc.

•

for indoor and outdoor applications in petroleum refineries,
chemical and petrochemical plants, and other process industry
facilities where similar hazards exist

•

to accommodate up to 100 amp branch loads (only 3 circuits),
balance is up to 50 amps

CERTIFICATIONS & COMPLIANCES (EXD/EPL)

CERTIFICATIONS & COMPLIANCES (D2D/D2L)

EXD & EPL Series (Division 1):

D2D & D2L Series (Division 2):

•

•

NEC/CEC:

NEC/CEC:

Class I, Division 1 & 2, Groups B†, C, D

Class I, Division 2, Groups B†, C, D

Class I, Zone 1 & 2, IIB + H2†
Class II, Division 1, Groups E, F, G

Class I, Zone 2, IIB + H2†

Class II, Division 2, Groups F, G

Class III

Class II, Division 2, Groups F, G

Class III

•

NEMA/EEMAC: 3, 4, 4X††, 7B†, C, D, 12

•

NEMA/EEMAC: 3, 4, 4X*, 7B†CD, 9EFG, 12

•

CSA Enc. 3, 4, 5

•

CSA Enc. 3, 4, 5

•

UL Standard: 67, 877, 1077

•

UL Standard: 67, 877, 1203

•

cUL (to CSA Standard C22.2 Nos. 29 & 30)

•

cUL (to CSA Standard C22 Nos. 29 & 30)

•

IP65

•

IP65

†Group B and IIB + H2 is standard on all PowerPlus panels, but requires special brackets to be installed on breakers to ensure long-term operability of circuit breakers. To order with
brackets installed at factory, add suffix -GB. For field installable kit, order EPL-GB-KIT for D2L/EPL or EXD-GB-KIT for D2D/EXD Sizes B, C, and D separately.
††NEMA 4X rating is available when ordered with suffix S752 or S753.

4

PowerPlus™ Panelboards

ELECTRICAL RATINGS (D2D/EXD Series)

ELECTRICAL RATINGS (D2L/EPL Series)
Branch Breakers (120/240VAC Quicklag® Bolt-on) Trip Ratings:

Branch Breakers Trip Ratings:
Panel
Size

B
C
D

F

Voltage

Phase/Wire

Main Breaker
Amperage

Branch
Breaker

•

1-, 2-, and 3-pole

480Y/277
480Δ†††
480Y/277
480Δ†††
480Y/277
480Δ†††

3P 4W
3P 3W
3P 4W
3P 3W
3P 4W
3P 3W

up to 100
up to 100
up to 100
up to 100
up to 225
up to 225

G-frame
G-frame
G-frame
G-frame
G-frame
G-frame

•

10, 15, 20, 25, 30, 35, 40, 45, 50 amp (available in all breaker
spaces in panel) 55, 60, 70, 80, 90, 100 amp (only 3 breaker
spaces available for 55 to 100 amp branch breakers)

•

GFI Type, 1- and 2-pole (5mA sensitivity) 15, 20, 25, 30, 40
(50 amp - available 2-pole only)

•

EPD Type, 1- and 2-pole (30mA sensitivity) 15, 20, 25, 30, 40
(50 amp - available 2-pole only)

480Y/277, 480Δ,
or 600Δ†††

3P 3W or
3P 4W

up to 225

F-frame

•

HID Type, 1- and 2-pole, 15, 20, 25, 30, 35, 40, 50, 60

•

Available with GFI, EPD, or a combination of both in one panel
with a 21-position electrical test circuit
Ambient compensated breakers available to +50ºC

Panel Sizes B, C, and D (GHB Series Cutler-Hammer™)
•

1-, 2-, & 3-pole: GHB 480/277Y (standard offering)

•

•

2- & 3-pole: GDB 480Δ (requires suffix -GDB)

Main Breaker Trip Ratings:

•

15, 20, 25, 30, 35, 40, 45, 50 amp (avail. in all breaker spaces in
panel) 60, 70, 80, 90, 100 amp (only 3 breaker spaces avail.)†††††

•

2- or 3-pole

•

Size B: 10 to 100 amps

•

Ambient compensated breakers are optional to +50ºC (suffix V)

•

Size C and D: 10 to 225 amps

Panel Size F (F-frame Breaker: EHD Cutler-Hammer™ standard)
•

15, 20, 25, 30, 35, 40, 45, 50, 60, 70 amp (avail. in all breaker
spaces in panel) 80, 90, 100 amp (only 3 breaker spaces avail.)

•

Breaker types available†††† (refer to Options on page 6 to specify breaker type)
- FDB: 1-, 2-, and 3-pole 600V
- FD: 1-, 2-, and 3-pole 600V
- HFD: 1-, 2-, and 3-pole 600V
- EHD: 1-, 2-, and 3-pole 480V

Main Lugs:
•

Size B, C, and D: 225 amp

Main Breaker Trip Ratings:
• 2- and 3-pole
• Size B: 15 to 100 amps
• Size C, D, and F: 15 to 225 amps
Main Lugs:
• Size B, C, and F: 225 amps
• Size D: not available; main breaker only
Ampere Interrupting Capacity:
•

All size panels are certified to 10kAIC

•

Breaker AIC Ratings:
- GHB Breaker: 14kAIC at 480Y/277
- EHD Breaker: 14kAIC at 480V
Breaker types optional with Sizes B, C, and D panel only:
- GDB Breaker: 14kAIC at 480V
Breaker types optional with Size F panel only:
- FDB Breaker: 14kAIC at 480V and 600V
- FD Breaker: 18kAIC at 600V and 35kAIC at 480V
- HFD Breaker: 25kAIC at 600V and 65kAIC at 480V

D2DDS

†††For 480Δ 3P 3W system or for 600VAC, a suffix is required. See page 6 for suffix options. For 480Δ system, please contact factory. Note: for single-pole 480Δ, GHB
breakers will be furnished for Sizes B, C, and D.
††††F-frame breakers are only available in Size F panel with up to a maximum of 30 circuit spaces.
†††††2-pole GDB breakers are only available up to 50 Amps.

5

PowerPlus™ Panelboards

STANDARD MATERIALS AND FINISHES
•

Circuit breaker enclosure body and cover - copper-free
aluminum

•

Terminal housing - Type 316L stainless steel (“S”) or copperfree aluminum (“A”)

Incoming Lug Terminals
Panel Size B,C,D D2D/EXD Size F
Line (A,B,C) wire range
4-4/0
6-350MCM
Branch circuit (1,3,5) wire range
10-0
10-0
Branch circuit (balance) wire range
24-8
18-4
Neutral line wire range
6-350MCM
6-250MCM
Neutral circuit wire range
14-4
14-1/0
Ground line wire range
6-350MCM
6-250MCM
Ground circuit wire range
14-4
14-1/0

•

Gasket - neoprene (cast aluminum enclosures), foam-in-place
(stainless steel enclosure)

ACCESSORIES
Field-installable gland plates with factory-provided aluminum
Myers Hubs for the D2L and D2D stainless steel terminal
housing (one 3-inch hub and 12 branch entry hubs - size dependent
upon suffix, each kit includes 3 gland plates, 1 for the top or bottom
and 1 for each side):
D2L

D2D

⁄4” branch entry hub

D2L HUB2 KIT

D2D HUB2 KIT

1” branch entry hub

D2L HUB3 KIT

D2D HUB3 KIT

1 1⁄2” branch entry hub

D2L HUB5 KIT

D2D HUB5 KIT

Replacement gland plate (no hubs)

D2L HUB0 KIT

D2D HUB0 KIT

3

Circuit Breaker Operator Assemblies
Operator Assemblies

Part Number

D2L/EPL 1-pole or 3-pole breakers

EPL HDL13

D2L/EPL 2-pole breakers

EPL HDL2

D2D/EXD All Breakers Panel Sizes B, C, D

EXD HDL 123

D2D/EXD All Breakers Panel Size F

EXD K1

•

Operating handles - copper-free aluminum

•

Operating shafts and bushings, cover bolts, washers,
hinges, breather/drain, retractile springs - stainless steel

•

Circuit breaker operators - D2D/EXD Size F: copper-free
aluminum; all other types: non-metallic

•

Lifting bracket - electrogalvanized cold rolled steel

•

Chassis - silver-plated copper

•

Breather cap - Delrin® non-metallic material

D2L/EPL Sizes B, C, D

EPL OP PLG

•

Neutral and ground bar - tin-plated aluminum

D2D/EXD Sizes B, C, D

EXD OP PLG

D2D/EXD Size F

EXD K2

Replacement cover plugs for both D2L/EPL and D2D/EXD for
unused circuit breaker positions (qty. 5):
Plug Kits

Part Number

OPTIONS
To add the following features to the panelboard, add a dash and then
the suffix to the catalog number. Multiple suffixes should be added in
alpha-numeric order.
Space Heater (D2L/EPL). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R22
Space Heater (D2D/EXD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R44
Square-head plugs on all conduit openings . . . . . . . . . . . . . . . . . . SP
Epoxy powder coat finish, external . . . . . . . . . . . . . . . . . . . . . . . S752
Epoxy powder coat finish, internal and external . . . . . . . . . . . . . S753
Recess-head plugs on all conduit openings. . . . . . . . . . . . . . . . . . RP
Stainless steel breaker operator cover (ice shield) . . . . . . . . . . . . . HG
Group B Kit factory installed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GB
GFI breakers* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G
EPD breakers* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
HID breakers* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H
Ambient compensated breakers (50ºC) . . . . . . . . . . . . . . . . . . . . . . . V
GDB 480Δ 3P 3W System***** . . . . . . . . . . . . . . . . . . . . . . . . . . GDB
FDB 600V breakers** . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FDB600
FD 600V breakers**. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FD600
HFD 600V breakers** . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HFD600
Lamacoid Nameplate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LID
A standard panelboard has conduit openings for power and
branch circuits on top.
•
To order a panelboard with main power feed
from the bottom of breaker housing, and branch
entries on top (Alternate), add . . . . . . . . . . . . . . . . . . . . . . . . -A***
•
To order an inverted panelboard with all conduit
openings for power and branch circuits on the
bottom (Inverted), add . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -I
•
To order an inverted panelboard with main power
feed on top and bottom (Alternate Inverted), add . . . . . . . -A-I***
6

Kit for Group B, standard panels less GB suffix are good for Group
B, but it is required to install brackets on breakers. To order brackets
factory-installed, add suffix -GB. For field installable kit, order:
D2L / EPL Kit: EPL GB KIT
D2D / EXD Sizes B, C, D Kit: EXD GB KIT
D2L/EPL stainless steel breaker operator cover to protect operators
from ice build-up for all D2L/EPL PowerPlus panels. For D2D/EXD
styles, please contact factory.
- Kit for Size B panel: EPL-HG24-KIT
- Kit for Size C and D panel: EPL-HG42-KIT
Space heater kits:
D2L / EPL: EPL R22 KIT
D2D / EXD: EXD R44 KIT
Terminal housing mounting plate kit to adapt depth of terminal
housing to same depth as breaker enclosure: EPLA-MTG-KIT****
Panel Types / Sizes

Part Number

Terminal Housing

D2L/EPL Sizes B, C, D

EPLA-MTG-KIT

Aluminum

D2D/EXD Sizes B, C, D

EXDA-MTG-KIT

Aluminum

D2L Sizes B, C, D

D2LS-MTG-KIT

Stainless

D2D Sizes B, C, D

D2DS-MTG-KIT

Stainless

*Available with D2L and EPL panels only. For D2D / EXD, please contact factory.
**Available with D2D and EXD Size F panels only.
***Not available in D2L/EPL Size D panels. D2D/EXD Sizes C and D are only available
with up to 36 circuits.
****The weight of the panel is sufficiently supported by mounting of breaker enclosure.
*****Available in D2D and EXD Sizes B, C, and D only.
Delrin® is a registered trademark of DuPont.

Table A. Panel Capacity - D2L / EPL
Maximum Number of Breaker Spaces:
D2L / EPL Panels
Maximum Number of Branch Circuit Breaker Spaces
Panel Size

With Main Breaker
With Main Lug Only

B

Three-pole

22

21

Up to 100‡

Yes

40

39

Up to 100‡

Yes

36

36

110 to 225##

Yes

42

42

Up to 225##

Yes

42

D

Available with
GFI, EPD
Branch Protection

Two-pole
24

C#

Available Main
Breaker Ampacity

42

#All Size B and Size C panels with main breaker rated up to 100 amps use a back-fed branch breaker. All Size D and Size C panels with main breaker rated from 110 amps
to 225 amps have a dedicated location for main breaker. Size C ordered with suffix 2M00 or 3M00 are provided with 36 branch circuits for maximum breaker ampacity.

Table B. Panel Capacity - D2D / EXD
Maximum Number of Breaker Spaces:
D2D / EXD Panels
Maximum Number of Branch Circuit Breaker Spaces
Panel Size

With Main Breaker
With Main Lug Only
Two-pole

Three-pole

Available Main
Breaker Ampacity

Available with
GFI, EPD
Branch Protection‡‡

B

24

22

21

Up to 100‡

No

C

42

40

39

Up to 100‡

No

D

N/A

42

42

Up to 225##

No

F

30

30

30

Up to 225##

No

Table C. To Size Panels with GFI or EPD Branch Breakers
Maximum Number of GFI or EPD Breakers
Panel Size
With Main Lug
or Main Breaker

B

C
D

Single-pole

Two-pole

Each factory-sealed panel is equipped with 42 load wires for GFI/EPD
breakers and any combination with standard branch breakers.
Determine the total number of load wires required to complete your
panel. You may not exceed 42 load wires.

Load Wires
Required
Single-pole breaker
=
1
Single-pole GFI (or EPD) breaker =
2
21
12
Two-pole breaker
=
2
(10 with 3-pole MCB,
Two-pole GFI (or EPD) breaker
=
3
11 with 2-pole MCB)
Three-pole breaker
=
3
Maximum Total: 42 load wires
(factory-sealed)
EPLDN Panels
Maximum Total: 82 load wires
21
14
(non-factory-sealed)
EPLDN only - can go up to 42 GFI or EPD circuits. EPLDN will accommodate up to 225 amp main breaker.

‡Main breakers are chassis mounted and back fed.
##Main breakers are mounted external to chassis.
‡‡GFI, EPD, for D2D / EXD are not standard options. If required, please contact factory.

7

PowerPlus™ Panelboards

Lighting Panelboard Catalog Number Example - D2L and EPL
Example: A Class I, Division 2 / Zone 2, Group B panel with:
• 240VAC Lighting Panelboard
• (28) single-pole 20 amp branch breakers
• (1) single-pole 15 amp branch GFI breaker
• 225 amp 3-pole main circuit breaker
Example would be ordered as:

D2L C S 3 30G * 28 1 20 * 01 1 15G - 3 M 225 -GB
1. Select panel type
D2L = Div. 2 / Zone 2 Panelboard
EPL = Div. 1 & 2 / Zone 1 & 2 Panelboard
2. Select size of enclosure
B = 24 circuit panel
C = 42 circuit panel (36 circuit panel with main breaker
greater than 100 amps)
D = 42 circuit panel
3. Select terminal enclosure material type
Premium Solution
S = stainless steel terminal housing (Div. 2 / Zone 2 panels only)
A = cast aluminum terminal housing
Value Solution
N = no terminal housing (non-factory-sealed - Div. 1 & 2 /
Zone 1 & 2)
4. Select panel phase
1 = single-phase electrical system
3 = three-phase electrical system
5. Select breaker spaces and options (combined # of circuits
required)†
1-pole breaker = 1 circuit
2-pole breaker = 2 circuit
3-pole breaker = 3 circuits
GFI = 1 additional circuit per breaker (suffix “G”)
EPD = 1 additional circuit per breaker (suffix “E”)
Example:
(28) 1-pole 20 amp breakers
= 28 circuits
+ (1) 1-pole 15 amp GFI breaker
= 2 circuits
Total number circuits
= 30 (with “G” for GFI
circuit option)
6. Insert asterisk (*) before each branch breaker series
7. Quantity of alike branch breakers
8. Branch breaker pole rating
1 = single-pole breaker
2 = 2-pole breaker
3 = 3-pole breaker
9. Branch breaker ampere rating (numerical value represents
ampere rating)
20 = 20 amps
10. Insert asterisk (*) before each branch breaker series
11. Quantity of alike branch breakers
12. Branch breaker pole rating (see #8 above)
13. Branch breaker ampere rating
15 = 15 amps
G = GFI breakers
15G = GFI with 15 amps
14. Dash indicates that main breaker follows
15. Main breaker number of poles
†Even number of breaker spaces is required. For odd number of spaces, round up to next even number.

8

18. Group
B
Option
17. Indicates
main
breaker
amperage
rating
16. M indicates
main breaker

Power Panelboard Catalog Number Example - D2D and EXD
Example: A Class I, Division 2 / Zone 2, Group B panel with:
• 480ΔVAC Power Panelboard with 3 Phase 3 Wire
• (42) single-pole 20 amp branch breakers
• 225 amp 3-pole main circuit breaker

Example would be ordered as:

D2D D S 3 42 V * 42 1 20 - 3 M 225 -GB -GDB
1. Select panel type
D2D - Division 2 / Zone 2 Panel
EXD - Division 1 / Zone 1 Panel
2. Select size of enclosure (refer to Electrical Ratings Chart on page 5)
B = 24 circuit panel
C = 36 circuit panel
D = 42 circuit panel
F = 30 circuit panel
3. Select terminal enclosure material type
Premium Solution
S = stainless steel terminal housing (Sizes B, C, D only)
A = cast aluminum terminal housing
Value Solution
N = no terminal housing included (non-factory-sealed)
4. Select panel phase
1 = single-phase electrical system
3 = three-phase electrical system
5. Select breaker spaces (combined # of circuits required)†
Example:
Single-pole breaker
= 1 circuit
2-pole breaker
= 2 circuits
3-pole breaker
= 3 circuits
6. Select breaker options
V = ambient compensated
7. Asterisk (*) denotes breaker characteristics follow
8. Quantity of alike branch breakers
9. Branch breaker pole rating
1 = single-pole breaker
2 = 2-pole breaker
3 = 3-pole breaker
10. Branch breaker ampere rating (numerical value
represents ampere rating)

15 = 15 Amps
20 = 20 Amps
25 = 25 Amps
30 = 30 Amps
35 = 35 Amps

40 = 40 Amps
50 = 50 Amps
60 = 60 Amps
70 = 70 Amps

11. Dash indicates that main breaker follows
12. Main breaker number of poles
13. M indicates main breaker
14. Indicates main breaker amperage rating
Size B: 15 to 100 amps
Sizes C, D, and F: 15 to 225 amp
15. Options††
GB = Group B Kit factory-installed
GDB = GDB frame breakers with 480Δ 3P 3W System
†Even number of breaker spaces is required. For odd number of spaces, round up to next even number.
††See all available options on page 6.

9

PowerPlus™ Panelboards

Dimensions - D2L and EPL

6.50 (165.1)
4.66 (118.4)
2.81 (71.4)

6.50
(165.1)
1-1/2" NPT
12 PLACES

4.66
(118.4)
2.81
(71.4)

5.10
3.51
(129.5) (89.2)
TYP.
TYP.
.92 (23.4)

3 1/2" NPT

1/2" BOLT (M12)

1.31 (33.3)TYP.
.50 (12.7)

5.50 (139.7)

1.83 (46.5)

20.12
(511.0)

12.93 (328.4)
APPROXIMATE

CL

3/8"
BOLT (M9)

11.16 (283.5)
4.00 (101.6)

11.52 (292.6)
APPROXIMATE

61.75
(1568.5)

3 1/2" NPT
ALTERNATE FEED OPTION
(SUFFIX 'A') ONLY

48.63
(1235.2)

29.50 (749.3)
17.50 (444.5)

6.00 (152.4)

14.88 (377.8)
TYP.

5.75 (146.0)

14.88 (377.8) TYP.

Size C and D Panel*
(with cast terminal housing)

Size B Panel*
(with stainless steel terminal housing)

*Stainless steel terminal housing for Sizes B, C, D, and F are the same. Cast aluminum terminal housing for Sizes B, C, and D are the same.

10

Dimensions - D2D and EXD

6.50
4.66 [165.1]
2.81 [118.4]
71.4

1-1/2" NPT
12 PLACES

6.50
[165.1]
4.66
[118.4]
2.81
71.4

3.51
[89.2]
TYP.

5.10
[129.5]
TYP.
.92
[23.4]

3 1/2" NPT

20.12
[511.2]

1.83
[46.5]

1.31
[33.3]
5.50
[139.7]

.50
[12.7]

11.16
[283.4]
13.49
[342.7]
APPROXIMATE

4.00
[101.5]

62.15
[1578.5]

11.37
[288.9]
APPROXIMATE

48.36
[1228.3]

3 1/2" NPT
ALTERNATE FEED OPTION
(SUFFIX 'A') ONLY

17.25
[438.2]

28.25
[717.6]

6.17
[156.7]
6.82
[173.3]

21.88
[555.6]

21.88
[555.6]

Size C and D Panel†
(with cast aluminum
terminal housing)

Size B Panel†
(with stainless steel
terminal housing)

Size F Panel
†Stainless steel and cast aluminum terminal housing for sizes B, C 7 D panels have same dimensions.

11

For more information:
If further assistance is required, please contact an authorized Cooper Crouse-Hinds Distributor,
Sales Office, or Customer Service Department.

U.S. (Global Headquarters):
Cooper Crouse-Hinds
Wolf & Seventh North Streets
Syracuse, NY 13221
(866) 764-5454
FAX: (315) 477-5179
FAX Orders Only: (866) 653-0640
crouse.customerctr@cooperindustries.com

Canada:
Cooper Crouse-Hinds Canada
Toll Free: 800-265-0502
FAX: (800) 263-9504
FAX Orders only: (866) 653-0645

Mexico/Latin America/Caribbean:
Cooper Crouse-Hinds, S.A. de C.V.
52-555-804-4000
FAX: 52-555-804-4020
mxmercadotecnia@cooperindustries.com

Europe (Germany):
Cooper Crouse-Hinds GmbH
49 (0) 6271 806-500
49 (0) 6271 806-476
info-ex@ceag.de

Middle East (Dubai):
Cooper Crouse-Hinds LLC
971 4 4272500
FAX: 971 4 4298521

Singapore:
Cooper Crouse-Hinds Pte. Ltd.
65-6297-4849
FAX: 65-6297-4819
sales@cchspore.com.sg

China:
Cooper Crouse-Hinds Pte. Ltd.
86-21-2899-3600
FAX: 86-21-2899-4055
cchsales@cooperindustries.com

Korea:
Cooper Crouse-Hinds Korea
82-2-3484-6783
82-2-3484-6778

Australia:
Cooper Electrical Australia
61-2-8787-2777
FAX: 61-2-9609-2342
sales@cooperelectrical.com.au

India:
Cooper India Pvt. Ltd.
91-124-4683888
FAX: 91-124-4683899
cchindia@cooperindustries.com

www.crouse-hinds.com
Cooper Crouse-Hinds is a registered trademark of Cooper Industries, Inc.
©2009 Cooper Industries, Inc.

Your Authorized Cooper Crouse-Hinds Distributor is:

Cooper Industries, Ltd.
600 Travis, Ste. 5800
Houston, TX 77002-1001
P: 713-209-8400
www.cooperindustries.com

4886-0409

Printed in USA



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Author                          : e3a4a
Create Date                     : 2016:10:22 15:48:57+05:30
Modify Date                     : 2016:10:22 15:48:57+05:30
XMP Toolkit                     : Adobe XMP Core 5.4-c005 78.147326, 2012/08/23-13:03:03
Producer                        : Acrobat Distiller 11.0 (Windows)
Creator Tool                    : PScript5.dll Version 5.2
Format                          : application/pdf
Title                           : PowerPlus Brochure:Layout 1.qxd
Creator                         : e3a4a
Document ID                     : uuid:81b0c98e-d225-48d5-930d-40ff9adb32d5
Instance ID                     : uuid:80d875af-474a-47c4-9fb7-3ddad9dcfca7
Page Count                      : 12
EXIF Metadata provided by EXIF.tools

Navigation menu