Molded case circuit breakers

Tmax

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Tmax
Molded case circuit breakers

Introduction

ABB is once again demonstrating its
commitment to new product development
and its superiority in product technology.
Never before has the industry seen such high
performance, versatility and standardization
in a range of molded case circuit breakers.
The ABB Tmax line of circuit breakers, with a
range up to 3000A, has several key features
that go along with its very small size:
•	Double insulation – this construction
characteristic allows for the UL Listed
field installation of internal accessories
without exposure to energized parts.
•	Complete range of electrical and
mechanical accessories
•	Positive operation – breakers from ABB
ensure that the toggle indicates the
precise position of the moving contacts.
This guarantees safe and reliable
signaling by the device.
•	Installation – Tmax molded case circuit
breakers can be installed in panels and
switchboards in either the horizontal
or vertical planes while being fed from
either end without any derating of their
performance characteristics.
•	Interrupting ratings at 480VAC up to
150kAIC.
•	Compact size
•	All Tmax molded case circuit breakers
are UL Listed and IEC rated for global
application and acceptance.
•	All versions of the Tmax family are
suitable for reverse feed applications.

15
T
M ma
CC x
Bs

The ABB Tmax product line has the
performance and accessories to satisfy all
industry requirements in the 600VAC to 600VDC
ranges.

Frame sizes — Eight basic sizes

The ABB Tmax series includes eight basic frame
sizes as well as the T1 single pole with the
range rated from 15A to 1200A at 480VAC. The
various versions carry the following interrupting
capacities:
	 •	 B Basic breaking capacity
	 •	 N Normal breaking capacity
	 •	 S Standard breaking capacity
	 •	 H High breaking capacity
	 •	 L Extra high breaking capacity
	 •	 V Very high breaking capacity

Derived versions
	
	
	
	
	

•	
•	
•	
•	
•	

16

Thermal magnetic
Electronic
Molded case switches
Motor circuit protectors (MCPs)
Direct current (DC) rated

ABB Tmax versions

	 •	 Fixed: all models
	 •	 Drawout or plug-in: T2, T3, Ts3, T4, T5, T6
and T7
	 •	 UL File #E93565 (breakers and MCPs)
		 #E116596 (Accessories)
		 #E116595 (Molded case switches)

16.1
1SXU000023C0202

15

Selection Guide
Circuit breakers for power distribution
T1 – Ts3

ax s
Tm CB
C
M

T1 1P	

T1	

Type

T3	

Ts3

Tmax T1 1p

Tmax T1

Tmax T2

Tmax T3

Tmax Ts3

[A]

100

100

100

225

150

225

[Nr]

1

3-4

3-4

3-4

2-3-4

2-3-4

AC (50-60Hz)

[V]

347

600Y/347

480

600Y/347

600

480

DC

[V]

500

600

Frame size
Number of poles
Rated voltage

T2	

500

Interrupting ratings

B

Tmax Ts3

500

N

S

H

N

S

N

H

L

N

H

L

50 2

65

150

50

65

65

100

150

65

100

150

35

65

25

50

85 5

25

50

65

14

14

25

20

35

50

240V AC

[kA rms]

277V AC

[kA rms]

18 1

347V AC

[kA rms]

14 1

480V AC

[kA rms]

22 2

25

35

600Y/347V AC

[kA rms]

10

10

10

600V AC

[kA rms]

250V DC (2 poles in series)

[kA rms]

25

25

35

500V DC (3 poles in series)

[kA rms]

25

25

35

500V DC (2 poles in series)

[kA rms]

35

50

65

600V DC (3 poles in series)

[kA rms]

20

35

50

Trip units

TMF

■

■

■

■

■

■

■

■

■

TMD/TMA

Dimensions

ELT

■

MA

■

Electronic

■

H

[in/mm]

5.12/130

5.12/130

5.12/130

5.9/150

6.7/170

6.7/170

W 3p

[in/mm]

1/25.4

3/76

3.54/90

4.13/105

4.13/105

4.13/105

[in/mm]

2.76/70

2.76/70

2.76/70

2.76/70

4.07/103.5

4.07/103.5

25000

25000

25000

25000

25000

25000

D

16

Mechanical life

1	
2	
3	
4	
5	

[No. operations]

In15A = 10kA@277VAC 10kA@347VAC
In15A = 35kA@240VAC 14kA@480Y/277 VAC
T5 600 with electronic trip units only and in three pole version
2p breakers: available only in N interrupting rating
In from 15A up to 30A=65kA@480V AC

16.2	
1SXU000023C0202	

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

15

Selection Guide
Circuit breakers for power distribution
T4 – T8

	

T4	

T5	

Type
Frame size
Number of poles
Rated voltage

T6	

T7	

T8

Tmax T4

Tmax T5

Tmax T6

Tmax T7

[A]

250

400-600 3

800

1000-1200

[Nr]

2-3-4 4

2-3-4 4

3-4

3-4

AC (50-60Hz)

[V]

600

600

600

600

DC

[V]

Interrupting ratings

600
N

S

600

H

L

V

N

S

L

V

N

S

H

L

[kA rms] 65 100 150 200 200 65 100 150 200 200 65 100 200 200

277V AC

[kA rms]

347V AC

[kA rms]

480V AC

[kA rms] 25

600Y/347V AC

[kA rms]

600V AC

[kA rms] 18

250V DC (2 poles in series)

[kA rms]

500V DC (3 poles in series)

[kA rms]

Insulated case
T8 / S8
1600, 2000,
2500 & 3000
3
600
T8

S8

S

H

L

T8V

S8V

65

100

150

125

125

600

H

240V AC

35

65 100 150 25

35

65 100 150 35

50

65 100

50

65

100

125

100

25

35

65 100 18

25

35

65 100 20

25

35

42

25

50

65

100

85

500V DC (2 poles in series)

[kA rms] 25

35

50

65 100 25

35

50

65 100 35

35

50

65

600V DC (3 poles in series)

[kA rms] 16

25

35

50

25

35

50

20

35

50

Trip units

T
M ma
CC x
Bs

TMF

■

TMD/TMA

■

65

16

■

65

20

25 6

■

ELT
MA
Electronic
Dimensions

Mechanical life

1	
2	
3	
4	
5	
6	

■

■

■

■

H

[in/mm]

8.07/205

8.07/205

10.55/268

10.55/268

W 3p

[in/mm]

4.13/105

5.51/140

8.26/210

D

[in/mm]

4.07/103.5

4.07/103.5

4.07/103.5

20,000

20,000

20,000

8.26/210
6.06/154 (toggle)
7/178 (motor)
10,000

[No. operations]

15 / 382

15.75 / 400

16.8 / 427 15.98 / 406
11.2 / 282

9.53 / 242

15,000

10,000

In15A = 10kA@277 VAC 10kA@347 VAC
In15A = 35kA@240 VAC 14kA@480Y/277 VAC
T5 600 with electronic trip units only and in three pole version2p T4N250 and T5N400 available only in N interrupting capacity.
In from 15A up to 30A=65kA@480 VAC
Applies to MCS only.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

16.3
1SXU000023C0202

16

15

General information
Catalog number explanation

ax s
Tm CB
C
M

T3  S  080 T W  - 4   xxx
Accessories (added in alpha-numeric order) 1
A =	 Auxiliary Switch
S_ = 	 Shunt trip with voltage code
U_ =	 Undervoltage release with voltage code

Number of poles
-1 =1 pole (T1 only)
-2 = 2 pole
-4 = 4 pole
None	= 3 pole

Type connectors
W = None
L = Lugs included

Trip unit function

B 	 =	 LS/I (AC only)
D 	 = 	Molded Case Switch (MCS)
T 	 =	 Thermal-magnetic
M	 =	 Magnetic only (MCP)
E5	 =	 Electronic MCP (AC only)
C	 =	 LSI (AC only)
E	 =	 LSIG (AC only)

Current rating
015 = 	15A
080 = 	80A
100 = 	100A
225 = 	225A
250 = 	250A
400 =	 400A
600 = 	600A
800 =	 800A
1200 = 1200A

Interrupting rating class

16

B	 =	 Basic	
N	 = 	Normal
S	 = 	Standard
H	 = 	High
L	 =	 Extra High
V	 =	 Very high

Frame size
T1 	
T2 	
T3 	
Ts3
T4 	
T5 	
T6 	
T7 	

= 100A
= 100A
= 225A
= 225A
= 250A
= 400A, 600A
= 600A, 800A
= 1000A, 1200A

1 Consult ABB for factory installed accessories.

16.4	
1SXU000023C0202	

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

15

T1
100A, 600Y/347V, 480V ∆
Thermal-magnetic

T
M ma
CC x
Bs

Dimensions	 3P Fixed Version 	 5.12H x 3.00W x 2.76D
Weight		

2.34 (Ibs)

T1

General

The T1 breaker family ranges from 15 through 100 amperes. The T1 trip units
are non-interchangeable and use the very latest technology in electromagnetic
relays for overcurrent trip protection. Thermal overload protection is provided by
heat sensitive bimetals. Short circuit protection for the breaker is accomplished
using a precise magnetic coil. State of the art construction in contacts and arcing
chambers aid in limiting damaging fault currents through the protected circuits.

Standards

The UL489/CSA 22.2 version of T1 also carries an IEC-60947-2 rating.

Versions

The T1 frame is available in two versions:
	 T = Thermal-magnetic, fixed
	 D = Molded case switch

UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage

Continuous rating

B (1 pole)

N

240VAC

15 – 100A

—

50 1

347VAC

15A
20 – 100A

10
14

—
—

480VAC ∆

15A 2
20 – 100A

—
—

14
22

600Y/347VAC

15 – 100A

—

10

250VDC 2 pole series

15 – 100A

—

25

500VDC 3 pole series

15 – 100A

—

25

Performance levels

The T1 breaker has two performance levels available:
	 B = Basic single pole
	 N = Normal three pole

IEC 60947-2 Interrupting capacity (kA RMS)
Voltage

Continuous rating

B (1 pole)

N

Number of poles

230VAC

15 – 100A

25 3

50

The T1 molded case circuit breaker is available in single, three and four pole
versions. Estimate 4 pole pricing by adding 35% to the 3 pole price and contact
your ABB sales person for details.

415VAC

15 – 100A

—

36

690VAC

15 – 100A

—

6

500VDC 2 pole series

15 – 100A

—

36

Molded case switches

UL489 switches include no overcurrent protection except for a high instantaneous
trip mechanism for self protection.

16

1 In 15A 35kA @ 240VAC.
2 15A available in 480/277 VAC only.
3	 Interrupting capacity for 16-20A is 16kA

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

16.5
1SXU000023C0202

15

T1
100A, 600Y/347V, 480V ∆
Thermal-magnetic/Molded Case Switch

ax s
Tm CB
C
M

T1B TMF — Single pole thermal magnetic fixed
	
Breaker	
		

	

IC at	
Rating	
277VAC		

Magnetic	
trip	

1 pole, 277VAC 	
catalog number	

10kA	

15A	

1000A	

T1B015TL-1	

		
		
		
		
T1B	
18kA	
		

20A	
25A	
30A	
40A	
50A	
60A	

1000A	
1000A	
1000A	
1000A	
1500A	
1500A	

T1B020TL-1	
T1B025TL-1	
T1B030TL-1	
T1B040TL-1	
T1B050TL-1	
T1B060TL-1	

		
		
		
		

70A	
80A	
90A	
100A	

1500A	
1500A	
1500A	
1500A	

T1B070TL-1	
T1B080TL-1	
T1B090TL-1	
T1B100TL-1	

Magnetic	
trip	

3 pole, 600Y/347VAC/500VDC	
catalog number	

List
price

$ 230

262

T1N TMF — 3 pole thermal magnetic fixed
	
Breaker	
		

	

IC at	
Rating	
480VAC		

14kA	

15A	

1000A	

T1N015TL1	

		
		
		
		
T1N	
22kA	
		

20A	
25A	
30A	
40A	
50A	
60A	

1000A	
1000A	
1000A	
1000A	
1500A	
1500A	

T1N020TL	
T1N025TL	
T1N030TL	
T1N040TL	
T1N050TL	
T1N060TL	

		
		
		
		

70A	
80A	
90A	
100A	

1500A	
1500A	
1500A	
1500A	

T1N070TL	
T1N080TL	
T1N090TL	
T1N100TL	

List
price

$ 402

479

T1N TMF — 100% Rated thermal-magnetic
Breaker

IC at
480VAC

14kA

T1N

22kA

Rating

15 1
20
25
30
40
50
60
70
80
90
100

16

Magnetic
trip

3 pole 600Y/347 500VDC
catalog number

1000A
1000A
1000A
1000A
1000A
1500A
1500A
1500A
1500A
1500A
1500A

T1NQ015TL
T1NQ020TL
T1NQ025TL
T1NQ030TL
T1NQ040TL
T1NQ050TL
T1NQ060TL
T1NQ070TL
T1NQ080TL
T1NQ090TL
T1NQ100TL

Magnetic	
trip	

480VAC/500VDC 	
catalog number	

List
price

$ 442

527

T1N-D — Molded case switch
	
Breaker	
		

T1-D	

Interrupting	
Rating	
capacity 2		

240V, 50kA	

100A	

1000A	

T1N100DL	

List
price

$ 431

1	 Rated 480V/277 VAC for 15A.
2	 When protected by a OCPD with appropriate ratings.

16.6	
1SXU000023C0202	

Discount schedule S1T

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

T2
100A, 480V ∆
Thermal-magnetic/electronic/current limiting

15
T
M ma
CC x
Bs

Dimensions	 3P Fixed Version 	 5.12H x 3.54W x 2.76D
Weight		

2.84 (Ibs)

T2

General

The T2 breaker family ranges from 15 through 100 amperes. The T2 trip units are
non-interchangeable and use the very latest technology in electromagnetic relays
for overcurrent trip protection as well as a version with microprocessor-based
electronic trip unit. Thermal overload protection is provided by heat sensitive
bimetals. State of the art construction in contacts and arcing chambers aid in
limiting damaging fault currents through the protected circuits.

Standards

The UL489/CSA 22.2 version of T2 also carries an IEC-60947-2 rating.

Versions

The T2 frame is available in four versions:
T = Thermal-magnetic, fixed
B = Adjustable LS/I electronic
M = Magnetic only (MCP)
E5 = Electronic instantaneous only (MCP)

UL489 / CSA C22.2 Interrupting capacity (kA RMS)
	

Voltage	

Continuous rating	

S	

H

	

240VAC	

15 – 100A	

65	

100

	

480VAC ∆	

15 – 100A	

35	

65

IEC 60947-2 Interrupting capacity (kA RMS)
Voltage

Continuous rating

B (1 pole)

N

230VAC

15 – 100A

85

100

415VAC

15 – 100A

50

70

690VAC

15 – 100A

7

8

500VDC 2 pole series

15 – 100A

50

70

Trip functions

These tripping functions are available:
L = Long time
S = Short time
I - Instantaneous

Performance levels

The T2 breaker has two performance levels available:
S = Standard
H = High - UL Current Limiting

16

Number of poles

The T2 is available in three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

16.7
1SXU000023C0202

15

T2
100A, 480V ∆
Thermal-magnetic/current limiting

ax s
Tm CB
C
M

T2 —
­ 100A TMF thermal magnetic fixed
	
Breaker	
		

IC at	
Rating	
480VAC		

Magnetic	
trip	

3 pole, 480VAC	
catalog number	

List
price

			
			
			
			
			
	
T2S	
35kA	
			

15A	
20A	
25A	
30A	
40A	
50A	
60A	

500A		
500A		
500A		
500A		
500A		
500A		
600A		

T2S015TW	
T2S020TW	
T2S025TW	
T2S030TW	
T2S040TW	
T2S050TW	
T2S060TW	

$ 690

			
			
			
			

70A	
80A	
90A	
100A	

700A		
800A		
900A		
1000A		

T2S070TW	
T2S080TW	
T2S090TW	
T2S100TW	

793

3 pole, 480VAC	
catalog number	

List
price

	
Breaker	
		

IC at	
Rating	
480VAC		

Magnetic		
trip		

			
			
			
			
			
	
T2H	
65kA	
	 UL Current		

15A	
20A	
25A	
30A	
40A	
50A	
60A	

500A		
500A		
500A		
500A		
500A		
500A		
600A		

T2H015TW	
T2H020TW	
T2H025TW	
T2H030TW	
T2H040TW	
T2H050TW	
T2H060TW	

	
Limiting		
			
			
			

70A	
80A	
90A	
100A	

700A		
800A		
900A		
1000A		

T2H070TW	
T2H080TW	
T2H090TW	
T2H100TW	

$ 942

1,153

T2 ­– 100A TMF, 100% rated thermal magnetic fixed
	
Breaker	
		

16

IC at	
Rating	
480VAC		

Magnetic	
trip	

3 pole, 480VAC	
catalog number	

List
price

			
			
			
			
			
	
T2S	
35kA	
			

15A	
20A	
25A	
30A	
40A	
50A	
60A	

500A	
500A	
500A	
500A	
500A	
500A	
600A	

T2SQ015TW	
T2SQ020TW	
T2SQ025TW
T2SQ030TW	
T2SQ040TW	
T2SQ050TW	
T2SQ060TW	

$ 760

			
			
			
			

70A	
80A	
90A	
100A	

700A	
800A	
900A	
1000A	

T2SQ070TW	
T2SQ080TW	
T2SQ090TW	
T2SQ100TW	

872

	
Breaker	
		

IC at	
Rating	
480VAC		

Magnetic	
trip	

3 pole, 480VAC	
catalog number	

List
price

			
			
			
			
	
T2H		
	
UL Current	
65kA	
	
Limiting		

15A	
20A	
25A	
30A	
40A	
50A	
60A	

500A	
500A	
500A	
500A	
500A	
500A	
600A	

T2HQ015TW	
T2HQ020TW	
T2HQ025TW	
T2HQ030TW	
T2HQ040TW	
T2HQ050TW	
T2HQ060TW	

$ 1,025

			
			
			
			

70A	
80A	
90A	
100A	

700A	
800A	
900A	
1000A	

T2HQ070TW	
T2HQ080TW	
T2HQ090TW	
T2HQ100TW	

1,268

16.8	
1SXU000023C0202	

Discount schedule S2T

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

15

T2
100A, 480V ∆, 100% rated
Electronic/Current limiting/MCP

T
M ma
CC x
Bs

T2 — 100A Frame, electronic trip unit (AC only)
	
Breaker	
		

IC at	
480VAC	

Trip unit	
type	

CT	
rating	

3 pole, 480VAC	
catalog number	

	
			
	
T2S	
35kA	
PR221DS-LS/I	
				

25A	
60A	
100A	

T2S025BW	
T2S060BW	
T2S100BW	

$ 1,240
1,240
1,343

	
	
	

25A	
60A	
100A	

T2H025BW	
T2H060BW	
T2H100BW	

1,492
1,492
1,703

3 pole, 480VAC	
catalog number	

List
price

T2H
	
		
UL Current	
65kA	
PR221DS-LS/I	
Limiting			

List
price

T2 – 100A Frame 100% rated, electronic trip unit (AC only)
	
Breaker	
		

	
	

IC at	
480VAC	

Trip unit	
type	

25A	
60A	

T2SQ025BW	
T2SQ060BW

$ 1,363

				

100A	

T2SQ100BW	

1,477

	
	

25A	
60A	

T2HQ025BW	
T2HQ060BW

1,640

100A	

T2HQ100BW	

1,873

	

			
T2S	
35kA	
PR221DS-LS/I	

CT	
rating	

	
PR221DS-LS/I	

T2H		
65kA	
UL Current	
Limiting			

T2 — 100A Frame, instantaneous only (MCP)
	
Breaker	
		

IC at	
480VAC	

Trip unit	
Rating	
type		

Adjustment 	
range	

3 pole, 480VAC	
catalog number	

List
price

				
	
T2S	
35kA	
Mag only
	
				

20A	
50A	
100A	

120 - 240		
300 - 600		
600 – 1200	
	

T2S020MW	
T2S050MW	
T2S100MW	

$ 598
670
804

				
	
T2H	
65kA	
Mag only	
				

20A	
50A	
100A	

120 - 240		
300 - 600		
600 – 1200	
	

T2H020MW	
T2H050MW	
T2H100MW	

673
754
904

3 pole, 480VAC	
catalog number	

List
price

T2 — 100A Frame, instantaneous only, electronic (MCP - AC only)
	
Breaker	
		

IC at	
480VAC	

Trip unit	
Rating	
type		

Adjustment 	
range	

	
Instantaneous	
	
	
35kA
	
T2S		
only	
				

25A	
60A	
100A	

25 - 250		
60 - 600		
100 - 1000		

T2S025E5W	
T2S060E5W	
T2S100E5W	

$ 1,178
1,178
1,276

	
Instantaneous	
	
	
65kA
	
T2H		
only	
				

25A	
60A	
100A	

25 - 250		
60 - 600		
100 - 1000		

T2H025E5W	
T2H060E5W	
T2H100E5W	

1,417
1,417
1,618

16

Note: For terminal connection options see page 16.43

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Discount schedule S2T

16.9
1SXU000023C0202

15
ax s
Tm CB
C
M

T3
225A, 600Y/347V, 480V ∆
Thermal-magnetic
Dimensions	 3P Fixed Version 	 5.9H x 4.13W x 2.76D
Weight		

5.45 (Ibs)

T3

General

The T3 breaker family ranges from 60 through 225 amperes. The T3 trip units are
non-interchangeable and use the very latest technology in electromagnetic relays
for overcurrent trip protection. Thermal overload protection is provided by heat
sensitive bimetals. Short circuit protection begins at 10 times the thermal rating of
the breaker using a precise magnetic coil. State of the art construction in contacts
and arcing chambers aid in limiting damaging fault currents through the protected
circuits.

Standards

UL489 / CSA C22.2 Interrupting capacity (kA RMS)
	

Voltage	

Continuous rating	

N	

S

	

240VAC	

60 – 225A	

50	

65

	

480VAC ∆	

60 – 225A	

25	

35

	

600Y/347VAC	

60 – 225A	

10	

10

	

250VDC 2 pole series	

60 – 225A	

25	

35

	

500VDC 3 pole series	

60 – 225A	

25	

35

The UL489/CSA 22.2 version of T3 also carries an IEC-60947-2 rating.

Versions

The T3 frame is available in three versions:
T = Thermal-magnetic, fixed
M = Magnetic only (MCP)
D = Molded case switch

Performance levels

The T3 breaker has two performance levels available:
N = Normal
S = Standard

IEC 60947-2 Interrupting capacity (kA RMS)
Voltage

Continuous rating

B (1 pole)

N

230VAC

60 – 225A

50

85

415VAC

60 – 225A

36

50

690VAC

60 – 225A

5

8

750VDC 3 pole series

60 – 225A

36

50

Number of poles

The T3 molded case circuit breaker is available in three and four pole versions.
Estimate 4 pole pricing by adding 35% to the 3 pole price and contact your ABB
sales person for details.

16

Molded case switches

UL489 switches include no overcurrent protection except for a high instantaneous
trip mechanism for self protection.

16.10	
1SXU000023C0202	

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

15

T3
225A, 600Y/347V, 480V ∆
Thermal-magnetic

T
M ma
CC x
Bs

T3 ­— 225A Frame TMF, thermal magnetic fixed
	
Breaker	
		

IC at	
Rating	
480VAC		

Magnetic	
trip	

3 pole, 480VAC/500VDC	
catalog number	

List
price

			

60A	

600A	

T3N060TW	

$ 615

			
			
			
			

70A	
80A	
90A	
100A	

700A	
800A	
900A	
1000A	

T3N070TW	
T3N080TW	
T3N090TW	
T3N100TW	

740

	
T3N	
25kA	
			
			

125A	
150A	
175A	

1250A	
1500A	
1750A	

T3N125TW	
T3N150TW	
T3N175TW	

1,560

			
			

200A	
225A	

2000A	
2250A	

T3N200TW	
T3N225TW	

1,560

Magnetic	
trip	

3 pole, 480VAC/500VDC	
catalog number	

	
Breaker	
		

IC at	
Rating	
480VAC		

List
price

			

60A	

600A	

T3S060TW	

$ 790

			
			
			
			

70A	
80A	
90A	
100A	

700A	
800A	
900A	
1000A	

T3S070TW	
T3S080TW	
T3S090TW	
T3S100TW	

970

	
T3S	
35kA	
			
			

125A	
150A	
175A	

1250A	
1500A	
1750A	

T3S125TW	
T3S150TW	
T3S175TW	

2,160

			
			

200A	
225A	

2000A	
2250A	

T3S200TW	
T3S225TW	

2,160

T3 ­– 225A Frame TMF, 100% rated thermal magnetic fixed
	
Breaker	
		

IC at	
Rating	
480VAC		

Magnetic	
trip	

3 pole, 600/347V VAC/500VDC	
catalog number	

List
price

			

60A	

600A	

T3NQ060TW	

$ 656

			
			
			
			

70A	
80A	
90A	
100A	

700A	
800A	
900A	
1000A	

T3NQ070TW	
T3NQ080TW	
T3NQ090TW	
T3NQ100TW	

812

	
T3N	
25kA	
			
			

125A	
150A	
175A	

1250A	
1500A	
1750A	

T3NQ125TW	
T3NQ150TW	
T3NQ175TW	

1,717

			
			

200A	
225A	

2000A	
2250A	

T3NQ200TW	
T3NQ225TW	

1,717

Magnetic	
trip	

3 pole, 600/347V VAC/500VDC	
catalog number	

	
Breaker	
		

IC at	
Rating	
480VAC		

List
price

			

60A	

600A	

T3SQ060TW	

$ 778

			
			
			
			

70A	
80A	
90A	
100A	

700A	
800A	
900A	
1000A	

T3SQ070TW	
T3SQ080TW	
T3SQ090TW	
T3SQ100TW	

1,065

	
T3S	
35kA	
			
			

125A	
150A	
175A	

1250A	
1500A	
1750A	

T3SQ125TW	
T3SQ150TW	
T3SQ175TW	

2,399

			
			

200A	
225A	

2000A	
2250A	

T3SQ200TW	
T3SQ225TW	

2,399

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Discount schedule S3T

16

16.11
1SXU000023C0202

15

T3
225A, 600Y/347V, 480V ∆
MCP/Molded case switch

ax s
Tm CB
C
M

T3 — 225A Frame instantaneous only, (MCP)
	
Breaker	
		

IC at	
480VAC	

Trip unit	
Rating	
type		

Adjustment 	
range	

3 pole, 480VAC	
catalog number	

List
price

				

100A	

600 – 1200	

	

T3S100MW	

$ 1,074

	
	
	
T3S	
35kA
Mag only
				
				

125A	
150A	
200A	

750 - 1500		
900 - 1800		
1200 - 2400		

T3S125MW	
T3S150MW	
T3S200MW	

1,108
1,299
1,382

T3S-D ­— Molded case switch
	
Breaker	
		

Interrupting 1	
Rating	
capacity		

	
	
T3S-D
		

240V, 65kA		
480V, 35kA	

150A	
225A	

Magnetic	
trip	

1500A	
2250A	

3 pole, 480VAC/500VDC	
catalog number	

T3S150DW	
T3S225DW	

List
price

$ 1,078
1,515

Note: For terminal connection options see page 16.43

16

1 When protected by a OCPD with appropriate ratings.

16.12	
1SXU000023C0202	

Discount schedule S3T

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

15

Ts3
150A, 600V ∆, 225A, 480V ∆
Thermal magnetic

T
M ma
CC x
Bs

Dimensions	 3P Fixed Version 	 6.7H x 4.13W x 4.07D
Weight		

6.75 (Ibs)

Ts3

General

The Ts3 breaker family ranges from 15 through 225 amperes. The Ts3 trip
mechanisms are non-interchangeable and use sensitive electromagnetic relays
for overcurrent trip protection. Heat sensitive bimetals are used for thermal
overcurrent protection. Short circuit current protection begins at 10 times the
thermal rating of the breaker and uses a magnetic coil principle.

Standards

The UL489/CSA 22.2 version of Ts3 also carries an IEC-60947-2 rating.

Versions

To meet all application needs, the Ts3 is available in various versions:
	 T =Thermal-magnetic
	 D = Molded case switch
	 M = Magnetic only (MCP)

Performance level

Each version is also available in different maximum fault interrupting levels	
	 N = Normal
	 H = High
	 L = Extra high

UL/CSA Interrupting capacity (kA RMS)
UL489 / CSA C22.2
Voltage

N

150AF, 15A-150A
240 VAC
65
480 VAC
25
600 VAC
14
500 VDC
35
600 VDC
20
225AF, 175A-225A
240 VAC
65
480 VAC
25
600 VAC
–
500 VDC
20
600 VDC
–
IEC-60947-2 Interrupting capacity (kA RMS)
230 VAC
65
415 VAC
35
690 VAC
14
20
750 VDC 2

H

L

100
50
14
50
35

150
85 1
25
65
50

100
50
–
35
–

150
65
–
50
–

100
65
18
35

170
85
20
50

Number of poles

The Ts3 is available in two, three and four pole versions. Estimate 4 pole pricing
by adding 35% to the 3 pole price and contact your ABB sales person for details.

Molded case switches

UL489 switches include no overcurrent protection except for a high instantaneous
trip mechanism for self protection.

16

1 15-30A are 65kA at 480VAC

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Discount schedule S3T

16.13
1SXU000023C0202

15

Ts3
150A, 600V ∆, 225A, 480V ∆
Thermal magnetic

ax s
Tm CB
C
M

Ts3
150A 600VAC/225A 480VAC
Thermal Magnetic Trip Units
Breaker

Ts3N

Breaker

Ts3H

IC at 480VAC

kA

25

IC at 480VAC

kA

50

Rating

Magnetic
trip

2 pole,
600VAC/500VDC
catalog number

15A

500A

Ts3N015TW-2

Ts3N015TW

20A
25A
30A
35A
40A
50A
60A
70A
80A
90A
100A
125A
150A

500A
500A
500A
500A
500A
500A
600A
700A
800A
900A
1000A
1250A
1500A

Ts3N020TW-2
Ts3N025TW-2
Ts3N030TW-2
Ts3N035TW-2
Ts3N040TW-2
Ts3N050TW-2
Ts3N060TW-2
Ts3N070TW-2
Ts3N080TW-2
Ts3N090TW-2
Ts3N100TW-2
Ts3N125TW-2
Ts3N150TW-2

Ts3N020TW
Ts3N025TW
Ts3N030TW
Ts3N035TW
Ts3N040TW
Ts3N050TW
Ts3N060TW
Ts3N070TW
Ts3N080TW
Ts3N090TW
Ts3N100TW
Ts3N125TW
Ts3N150TW

Rating

Magnetic
trip

2 pole,
600VAC/500VDC
catalog number

15A

500A

Ts3H015TW-2

Ts3H015TW

20A
25A
30A
35A
40A
50A
60A
70A
80A
90A
100A
125A
150A

500A
500A
500A
500A
500A
500A
600A
700A
800A
900A
1000A
1250A
1500A

Ts3H020TW-2
Ts3H025TW-2
Ts3H030TW-2
Ts3H035TW-2
Ts3H040TW-2
Ts3H050TW-2
Ts3H060TW-2
Ts3H070TW-2
Ts3H080TW-2
Ts3H090TW-2
Ts3H100TW-2
Ts3H125TW-2
Ts3H150TW-2

Ts3H020TW
Ts3H025TW
Ts3H030TW
Ts3H035TW
Ts3H040TW
Ts3H050TW
Ts3H060TW
Ts3H070TW
Ts3H080TW
Ts3H090TW
Ts3H100TW
Ts3H125TW
Ts3H150TW

Rating

Magnetic
trip

2 pole,
600VAC/500VDC
catalog number

15A

500A

Ts3L015TW-2

20A
25A
30A
35A
40A
50A
60A
70A
80A
90A
100A
125A
150A

500A
500A
500A
500A
500A
500A
600A
700A
800A
900A
1000A
1250A
1500A

Ts3L020TW-2
Ts3L025TW-2
Ts3L030TW-2
Ts3L035TW-2
Ts3L040TW-2
Ts3L050TW-2
Ts3L060TW-2
Ts3L070TW-2
Ts3L080TW-2
Ts3L090TW-2
Ts3L100TW-2
Ts3L125TW-2
Ts3L150TW-2

List price

$ 814

948

1,471

List price

$ 939

1,071

2,323

3 pole, 600VAC/DC
catalog number

3 pole, 600VAC/DC
catalog number

List price

$ 958

1,115

1,610

List price

$ 1,105

1,260

2,733

16
Breaker

IC at 480VAC

65

Ts3L
85

16.14	
1SXU000023C0202	

kA

List price

3 pole, 600VAC/DC
catalog number

List price

Ts3L015TW
$ 1,518

1,518

1,692

3,636

Discount schedule S3T

Ts3L020TW
Ts3L025TW
Ts3L030TW
Ts3L035TW
Ts3L040TW
Ts3L050TW
Ts3L060TW
Ts3L070TW
Ts3L080TW
Ts3L090TW
Ts3L100TW
Ts3L125TW
Ts3L150TW

$ 1,786

1,786

1,990

4,278

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Ts3
150A, 600V ∆, 225A, 480V ∆, 100% rated
Thermal magnetic

15
T
M ma
CC x
Bs

Ts3
150A 600VAC/225A 480VAC
Thermal Magnetic Trip Units 100% Rated
Breaker

Ts3NQ

Breaker

Ts3HQ

Breaker

IC at
480VAC

25

IC at
480VAC

50kA

IC at
480VAC
65kA

Ts3LQ
85kA

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Magnetic
trip

3 pole 600VAC/DC
catalog number

15A

500A

Ts3NQ015TW

20A
25A
30A
35A
40A
50A
60A
70A
80A
90A
100A
125A
150A

500A
500A
500A
500A
500A
500A
600A
700A
800A
900A
1000A
1250A
1500A

Ts3NQ020TW
Ts3NQ025TW
Ts3NQ030TW
Ts3NQ035TW
Ts3NQ040TW
Ts3NQ050TW
Ts3NQ060TW
Ts3NQ070TW
Ts3NQ080TW
Ts3NQ090TW
Ts3NQ100TW
Ts3NQ125TW
Ts3NQ150TW

Rating

Magnetic
trip

3 pole
catalog number

15A

500A

Ts3HQ015TW

20A
25A
30A
35A
40A
50A
60A
70A
80A
90A
100A
125A
150A

500A
500A
500A
500A
500A
500A
600A
700A
800A
900A
1000A
1250A
1500A

Ts3HQ020TW
Ts3HQ025TW
Ts3HQ030TW
Ts3HQ035TW
Ts3HQ040TW
Ts3HQ050TW
Ts3HQ060TW
Ts3HQ070TW
Ts3HQ080TW
Ts3HQ090TW
Ts3HQ100TW
Ts3HQ125TW
Ts3HQ150TW

Rating

Rating
15A
20A
25A
30A
35A
40A
50A
60A
70A
80A
90A
100A
125A
150A

Magnetic
trip
500A
500A
500A
500A
500A
500A
500A
600A
700A
800A
900A
1000A
1250A
1500A

3 pole
catalog number
Ts3LQ015TW
Ts3LQ020TW
Ts3LQ025TW
Ts3LQ030TW
Ts3LQ035TW
Ts3LQ040TW
Ts3LQ050TW
Ts3LQ060TW
Ts3LQ070TW
Ts3LQ080TW
Ts3LQ090TW
Ts3LQ100TW
Ts3LQ125TW
Ts3LQ150TW

List price

$ 1,054

1,227

1,771

List price

$ 1,216

1,386

3,006

16

List price

$ 1,965

2,189

4,706

Discount schedule S3T

16.15
1SXU000023C0202

15

Ts3
150/225A 600VAC
MCP/Molded case switch

ax s
Tm CB
C
M

Magnetic only (MCP)
Breaker

Ts3L

Ts3L

IC at 480VAC

Trip unit type

25
25
25
25
85
85
85
85
65
65

Magnetic only
Magnetic only
Magnetic only
Magnetic only
Magnetic only
Magnetic only
Magnetic only
Magnetic only
Magnetic only
Magnetic only

Rating

3
5
10
25
50
100
125
150
175 1
200 1

Adjustment
range

3 pole 600VAC
Catalog number

List
Price

12-36
20-60
40-120
100-300
200-600
400-1200
500-1500
600-1500
700-2100
800-2400

Ts3L003MW
Ts3L005MW
Ts3L010MW
Ts3L025MW
Ts3L050MW
Ts3L100MW
Ts3L125MW
Ts3L150MW
Ts3L175MW
Ts3L200MW

$ 726
726
726
726
920
1,095
1,448
1,448
1,448
1,517

3 pole 600V
catalog number

List
price

Ts3H150DW
Ts3H225DW

$ 1,060
1,188

Molded Case Switch 2
Type

IC at 480V (2)

Magnetic trip

Ts3H

50
50

1500
2250

Amps

150
225 1

Note: For terminal connection options see page 16.43

16

1 When protected by a OCPD with appropriate ratings.
2 480 VAC maximum

16.16	
1SXU000023C0202	

Discount schedule S3T

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

15

T4
250A, 600V ∆
Electronic and thermal magnetic

T
M ma
CC x
Bs

Dimensions	 3P Fixed Version 	 8.07H x 4.13W x 4.07D
Weight		

6.18 (Ibs)

T4

General

The T4 breaker is a 250 amp frame with either a microprocessor based over
current protective trip system or a thermal magnetic trip unit.

Standards

The UL489/CSA 22.2 version of T4 also carries an IEC-60947-2 rating.

Versions

To meet all application requirements, the T4 is available in the following versions:
T = Thermal-magnetic
B = Selectable & adjustable LI or LS
C = Adjustable LSI
E = Adjustable LSIG
D = Molded Case Switch
E5 = Electronic instantaneous only (MCP)

Trip functions

These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault

UL489 / CSA C22.2 Interrupting capacity (kA RMS)
	

Voltage	

N	

S	

H	

L	

V

	

240VAC	

65	

100	

150	

200	

200

	

480VAC	

25	

35	

65	

100	

150

	

600VAC	

18	

25	

35	

65	

100

	

500VDC 1	

25	

35	

50	

65	

100

	

600VDC 2	

16	

25	

35	

50	

65

IEC 60947-2 Interrupting capacity (kA RMS)
	

Voltage	

N	

S	

H	

L	

V

	

230VAC	

70	

85	

100	

200	

200

	

415VAC	

36	

50	

70	

120	

200

	

690VAC	

20	

25	

40	

70	

80

	

750VDC 2	

16	

25	

36	

50	

70

Performance levels

Each version is also available in different maximum fault interrupting levels:
N = Normal
S = Standard
H = High - UL Current Limiting
L = Extra high
V = Very high - UL Current Limiting

16

Number of poles 3

The T4 is available in two, three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.

1	 2 poles in series.
2	 3 poles in series.
3	 2 pole breakers available in N version only. 4 pole breakers available in N and H version only.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

16.17
1SXU000023C0202

15

T4
250A, 600V ∆
Adjustable thermal magnetic

ax s
Tm CB
C
M

20A - 250A Frame
Breaker

IC at
480VAC

T4N

25

T4S

T4H
UL Current
Limiting

T4L

T4V
UL Current
Limiting

35

65

100

150

Rating

Magnetic
trip

2 pole, 600VAC/600VDC
catalog number

125A
150A
200A
250A
125A
150A
200A
250A
125A
150A
200A
250A
125A
150A
200A
250A
125A
150A
200A
250A

625-1250
750-1500
1000-2000
1250-2500
625-1250
750-1500
1000-2000
1250-2500
625-1250
750-1500
1000-2000
1250-2500
625-1250
750-1500
1000-2000
1250-2500
625-1250
750-1500
1000-2000
1250-2500

T4N125TW-2
T4N150TW-2
T4N200TW-2
T4N250TW-2

List
price

$ 1,584
1,631

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

–

3 pole, 600VAC/600VDC
catalog number

T4N125TW
T4N150TW
T4N200TW
T4N250TW
T4S125TW
T4S150TW
T4S200TW
T4S250TW
T4H125TW
T4H150TW
T4H200TW
T4H250TW
T4L125TW
T4L150TW
T4L200TW
T4L250TW
T4V125TW
T4V150TW
T4V200TW
T4V250TW

List
price

$ 1,667
1,717
2,067
2,092
3,767
3,832
5,995
6,110
6,847
6,887

16

16.18	
1SXU000023C0202	

Discount schedule S4T

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

15

T4
250A, 600V ∆ 100% rated
Adjustable thermal magnetic

T
M ma
CC x
Bs

30A - 250A Frame 100% rated
Breaker

T4N

T4S

IC at 480 VAC
kA

25

35

T4H
UL Current
Limiting

65

T4L

100

T4V
UL Current
Limiting

150

Rating

125A
150A
200A
250A
125A
150A
200A
250A
125A
150A
200A
250A
125A
150A
200A
250A
125A
150A
200A
250A

Magnetic
trip

625-1250
750-1500
1000-2000
1250-2500
625-1250
750-1500
1000-2000
1250-2500
625-1250
750-1500
1000-2000
1250-2500
625-1250
750-1500
1000-2000
1250-2500
625-1250
750-1500
1000-2000
1250-2500

3 pole,
600VAC/600VDC
Catalog number

T4NQ125TW
T4NQ150TW
T4NQ200TW
T4NQ250TW
T4SQ125TW
T4SQ150TW
T4SQ200TW
T4SQ250TW
T4HQ125TW
T4HQ150TW
T4HQ200TW
T4HQ250TW
T4LQ125TW
T4LQ150TW
T4LQ200TW
T4LQ250TW
T4VQ125TW
T4VQ150TW
T4VQ200TW
T4VQ250TW

List
price

$ 1,839
1,894
2,280
2,307
4,155
4,227
6,612
6,739
7,552
7,569

16

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Discount schedule S4T

16.19
1SXU000023C0202

15

T4
250A, 600V ∆
Electronic (AC only)

ax s
Tm CB
C
M

100A Frame, electronic trip unit (AC only)
Breaker

IC at 480VAC
kA

T4N

25

T4S

35

T4H
UL Current
Limiting

65

T4L

100

T4V
UL Current
Limiting

150

Trip
Unit

2 pole, 600V
catalog number

List
price

3 pole, 600V
catalog number

List
price

PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG

T4N100BW-2
T4N100CW-2
T4N100EW-2
-

$ 1,808
2,413
3,164
-

T4N100BW
T4N100CW
T4N100EW
T4S100BW
T4S100CW
T4S100EW
T4H100BW
T4H100CW
T4H100EW
T4L100BW
T4L100CW
T4L100EW
T4V100BW
T4V100CW
T4V100EW

Trip
Unit

2 pole, 600V
catalog number

List
price

3 pole, 600V
catalog number

PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG

T4N150BW-2
T4N150CW-2
T4N150EW-2
-

$ 1,948
2,600
3,409
-

T4N150BW
T4N150CW
T4N150EW
T4S150BW
T4S150CW
T4S150EW
T4H150BW
T4H150CW
T4H150EW
T4L150BW
T4L150CW
T4L150EW
T4V150BW
T4V150CW
T4V150EW

$ 2,050
2,737
3,588
2,542
3,394
4,449
4,633
5,024
6,094
6,174
6,288
7,354
8,872
9,555
10,326

Trip
Unit

2 pole, 600V
catalog number

List
price

3 pole, 600V
catalog number

List
price

PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG

T4N250BW-2
T4N250CW-2
T4N250EW-2
-

$ 1,903
2,540
3,330
2,370
3,164
4,148
4,498
4,845
5,877
5,954
6,063
7,091
8,555
9,213
9,957

150A Frame, electronic trip unit (AC only)
Breaker

IC at 480VAC
kA

T4N

25

T4S

35

T4H
UL Current
Limiting

65

T4L

100

T4V
UL Current
Limiting

150

List
price

250A Frame, electronic trip unit (AC only)
Breaker

IC at 480VAC
kA

T4N

25

T4S

35

T4H
UL Current
Limiting

65

T4L

100

T4V
UL Current
Limiting

150

16

16.20	
1SXU000023C0202	

$ 2,006
2,678
3,511
-

Discount schedule S4T

T4N250BW
T4N250CW
T4N250EW
T4S250BW
T4S250CW
T4S250EW
T4H250BW
T4H250CW
T4H250EW
T4L250BW
T4L250CW
T4L250EW
T4V250BW
T4V250CW
T4V250EW

$ 2,112
2,819
3,696
2,573
3,435
4,503
4,713
5,127
6,219
6,300
6,416
7,504
9,053
9,750
10,537

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

T4
250A, 600V ∆, 100% Rated
Electronic (AC only)

15
T
M ma
CC x
Bs

100A Frame - 100% rated, electronic trip unit (AC only)
Breaker

IC at 480VAC
kA

T4N

25

T4S

35

T4H
UL Current
Limiting

65

T4L

100

T4V
UL Current
Limiting

150

Trip
Unit

3 pole, 600V
catalog number

PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG

T4NQ100BW
T4NQ100CW
T4NQ100EW
T4SQ100BW
T4SQ100CW
T4SQ100EW
T4HQ100BW
T4HQ100CW
T4HQ100EW
T4LQ100BW
T4LQ100CW
T4LQ100EW
T4VQ100BW
T4VQ100CW
T4VQ100EW

List
price

$ 2,124
2,835
3,716
2,645
3,531
4,629
5,020
5,383
6,530
6,616
6,737
7,879
9,506
10,237
11,063

150A Frame - 100% rated, electronic trip unit (AC only)
Breaker

IC at 480VAC
kA

T4N

25

T4S

35

T4H
UL Current
Limiting

65

T4L

100

T4V
UL Current
Limiting

150

Trip
Unit

3 pole, 600V
catalog number

PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG

T4NQ150BW
T4NQ150CW
T4NQ150EW
T4SQ150BW
T4SQ150CW
T4SQ150EW
T4HQ150BW
T4HQ150CW
T4HQ150EW
T4LQ150BW
T4LQ150CW
T4LQ150EW
T4VQ150BW
T4VQ150CW
T4VQ150EW

List
price

$ 2,288
3,055
4,004
2,837
3,788
4,965
5,171
5,582
6,771
6,860
6,987
8,171
9,858
10,616
11,473

250A Frame - 100% rated, electronic trip unit (AC only)
Breaker

IC at 480VAC
kA

T4N

25

T4S

35

T4H
UL Current
Limiting

65

T4L

100

T4V
UL Current
Limiting

150

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Trip
Unit

3 pole, 600V
catalog number

PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG

T4NQ250BW
T4NQ250CW
T4NQ250EW
T4SQ250BW
T4SQ250CW
T4SQ250EW
T4HQ250BW
T4HQ250CW
T4HQ250EW
T4LQ250BW
T4LQ250CW
T4LQ250EW
T4VQ250BW
T4VQ250CW
T4VQ250EW

List
price

$ 2,357
3,146
4,125
2,872
3,788
5,025
5,260
5,697
6,910
7,000
7,129
8,338
10,058
10,833
11,708

Discount schedule S4T

16

16.21
1SXU000023C0202

15

T4
250A, 600V ∆
Instantaneous only, MCP/Molded case switch

ax s
Tm CB
C
M

Instantaneous only MCPs
T4 - 250A Frame magnetic only (MCP - AC only)
Breaker

IC at 480VAC

Trip unit type

Rating

Adjustment range

3 pole, 600VAC
Catalog number

List
price

T4N

25kA

Instantaneous
only

100A
150A
250A
100A
150A
250A

100-1000
150-1500
250-2500
100-1000
150-1500
250-2500

T4N100E5W
T4N150E5W
T4N250E5W
T4S100E5W
T4S150E5W
T4S250E5W

$ 1,808
1,948
2,006
2,252
2,415
2,444

T4S

35kA

Instantaneous
only

T4H

65kA

Instantaneous
only

100A
150A
250A

100-1000
150-1500
250-2500

T4H100E5W
T4H150E5W
T4H250E5W

4,273
4,401
4,477

T4L

100kA

Instantaneous
only

100A
150A
250A

100-1000
150-1500
250-2500

T4L100E5W
T4L150E5W
T4L250E5W

5,656
5,865
5,985

Molded case switch 1
Type

IC at 480VAC

Amps

Magnetic
trip

3 pole 600V
catalog number

List
price

T4N-D
T4S-D
T4H-D
T4L-D
T4V-D

25kA
35kA
65kA
100kA
150kA

250
250
250
250
250

3000
3000
3000
3000
3000

T4N250DW
T4S250DW
T4H250DW
T4L250DW
T4V250DW

$ 1,354
1,510
2,154
3,419
3,842

NOTE: For terminal connection options, see page 16.43.

16

1 When protected by a OCPD with appropriate ratings.

16.22	
1SXU000023C0202	

Discount schedule S4T

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

15

T5
400/600A, 600V ∆
Electronic and thermal magnetic

T
M ma
CC x
Bs

Dimensions	 3P Fixed Version 	 8.07H x 5.51W x 4.07D
Weight		

8.55 (Ibs)

T5

General

The T5 breaker is a 400/600 amp frame with either a microprocessor based over
current protective trip system or a thermal magnetic trip unit. 3

Standards

The UL489/CSA 22.2 version of T5 also carries an IEC-60947-2 rating.

Versions

To meet all application requirements, the T5 is available in the following versions:
T = Thermal-magnetic
B = Selectable & adjustable LI or LS
C = Adjustable LSI
E = Adjustable LSIG
D = Molded Case Switch
E5 = Electronic instantaneous only (MCP)

Trip functions

These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault

UL489 / CSA C22.2 Interrupting capacity (kA RMS)
	

Voltage	

N	

S	

H	

L	

V

	

240VAC	

65	

100	

150	

200	

200

	

480VAC	

25	

35	

65	

100	

150

	

600VAC	

18	

25	

35	

65	

100

	

500VDC 1	

25	

35	

50	

65	

100

	

600VDC 2	

16	

25	

35	

50	

65

IEC 60947-2 Interrupting capacity (kA RMS)
	

Voltage	

N	

S	

H	

L	

V

	

230VAC	

70	

85	

100	

200	

200

	

415VAC	

36	

50	

70	

120	

200

	

690VAC	

20	

25	

40	

70	

80

	

750VDC	

16	

25	

36	

50	

70

Performance levels

Each version is also available in different maximum fault interrupting levels:
N = Normal
S = Standard
H = High - UL Current Limiting
L = Extra high
V = Very high - UL Current Limiting

16

Number of poles 4

The T5 is available in two, three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.

1	 2 poles in series.
2	 3 poles in series.
3	 T5 600A not available with thermal magnetic trip unit.
4	 2 pole available in N version only. 4 pole available in N and H version only.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

16.23
1SXU000023C0202

15

T5
400/600A, 600V ∆
Thermal magnetic 1

ax s
Tm CB
C
M

300A - 400A Frames - thermal-magnetic trip units
Breaker

IC at 480VAC
kA

T5N

25

T5S

35

T5H
UL Current Limiting

65

T5L

100

T5V
UL Current Limiting

150

Rating

Magnetic
trip

2 pole, 600VAC/600VDC
catalog number

List
price

300A
400A
300A
400A
300A
400A
300A
400A
300A
400A

1500-3000
2000-4000
1500-3000
2000-4000
1500-3000
2000-4000
1500-3000
2000-4000
1500-3000
2000-4000

T5N300TW-2
T5N400TW-2

$ 2,481

–

–

–

–

–

–

–

–

List
price

3 pole, 600VAC/600VDC
catalog number

T5N300TW
T5N400TW
T5S300TW
T5S400TW
T5H300TW
T5H400TW
T5L300TW
T5L400TW
T5V300TW
T5V400TW

List
price

$ 2,612
2,880
4,950
6,400
9,873

300A - 400A Frames - 100% rated, thermal-magnetic
Breaker

IC at 480VAC

T5N

25

T5S

35

T5H
UL Current Limiting

65

T5L

100

T5V
UL Current Limiting

150

Rating

Magnetic
trip

3 pole,
600VAC/600VDC
Catalog number

300A
400A
300A
400A
300A
400A
300A
400A
300A
400A

1500-3000
2000-4000
1500-3000
2000-4000
1500-3000
2000-4000
1500-3000
2000-4000
1500-3000
2000-4000

T5NQ300TW
T5NQ400TW
T5SQ300TW
T5SQ400TW
T5HQ300TW
T5HQ400TW
T5LQ300TW
T5LQ400TW
T5VQ300TW
T5VQ400TW

$ 2,888
3,185
5,475
7,078
10,920

16

1	 T5 600A not available with Thermal Magnetic trip unit.

16.24	
1SXU000023C0202	

Discount schedule S5T

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

15

T5
400/600A, 600V ∆
Electronic (AC only)

T
M ma
CC x
Bs

300A Frame, electronic trip unit (AC only)
Breaker

IC at 480VAC
kA

T5N

25

T5S

35

T5H
UL Current
Limiting

65

T5L

100

T5V
UL Current
Limiting

150

Trip
Unit

2 pole, 600V
catalog number

List
price

3 pole, 600V
catalog number

PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG

T5N300BW-2
T5N300CW-2
T5N300EW-2
-

$ 3,097
3,672
4,717
-

T5N300BW
T5N300CW
T5N300EW
T5S300BW
T5S300CW
T5S300EW
T5H300BW
T5H300CW
T5H300EW
T5L300BW
T5L300CW
T5L300EW
T5V300BW
T5V300CW
T5V300EW

Trip
Unit

2 pole, 600V
catalog number

List
price

3 pole, 600V
catalog number

PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG

T5N400BW-2
T5N400CW-2
T5N400EW-2
-

$ 3,097
3,672
4,717
-

Trip
Unit

3 pole, 600V
catalog number

List
price

PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG

T5N600BW
T5N600CW
T5N600EW
T5S600BW
T5S600CW
T5S600EW
T5H600BW
T5H600CW
T5H600EW
T5L600BW
T5L600CW
T5L600EW
T5V600BW
T5V600CW
T5V600EW

List
price

$ 3,260
3,865
4,965
3,350
3,945
5,138
5,395
5,893
7,148
6,860
7,375
8,625
10,406
11,206
12,111

400A Frame, electronic trip unit (AC only)
Breaker

IC at 480VAC
kA

T5N

25

T5S

35

T5H
UL Current
Limiting

65

T5L

100

T5V
UL Current
Limiting

150

600A Frame, electronic trip unit (AC only) 1
Breaker

IC at 480VAC
kA

T5N

25

T5S

35

T5H

65

T5L

100

T5V

150

T5N400BW
T5N400CW
T5N400EW
T5S400BW
T5S400CW
T5S400EW
T5H400BW
T5H400CW
T5H400EW
T5L400BW
T5L400CW
T5L400EW
T5V400BW
T5V400CW
T5V400EW

List
price

$ 3,260
3,865
4,965
3,350
3,945
5,138
5,395
5,893
7,148
6,860
7,375
8,625
10,406
11,206
12,111

$ 5,750
6,460
8,360
5,910
6,595
8,645
8,170
8,805
10,890
9,860
10,440
12,630
13,550
14,375
16,350

16

1 T5 600A not available in 2 pole version.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Discount schedule S5T

16.25
1SXU000023C0202

15

T5
400/600A, 600V ∆, 100% Rated 1
Electronic (AC only)

ax s
Tm CB
C
M

300A Frame – 100% rated, electronic trip units (AC only)
Breaker

IC at 480VAC
kA

T5N

25

T5S

35

T5H
UL Current

65

limiting

T5L

100

T5V
UL Current

150

limiting

Trip
Unit

PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG

3 pole, 600V
catalog number

List
price

T5NQ300BW
T5NQ300CW
T5NQ300EW
T5SQ300BW
T5SQ300CW
T5SQ300EW
T5HQ300BW
T5HQ300CW
T5HQ300EW
T5LQ300BW
T5LQ300CW
T5LQ300EW
T5VQ300BW
T5VQ300CW
T5VQ300EW

$ 3,628
4,302
5,526
3,729
4,391
5,719
6,005
6,559
7,956
7,635
8,208
9,600
11,582
12,473
13,480

400A Frame – 100% rated, electronic trip units (AC only)
Breaker

IC at 480VAC
kA

T5N

25

T5S

35

T5H
UL Current

65

limiting

T5L

100

T5V
UL Current

150

limiting

Trip
Unit

PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG
PR221 LS/I
PR222 LSI
PR222 LSIG

3 pole, 600V
catalog number

T5NQ400BW
T5NQ400CW
T5NQ400EW
T5SQ400BW
T5SQ400CW
T5SQ400EW
T5HQ400BW
T5HQ400CW
T5HQ400EW
T5LQ400BW
T5LQ400CW
T5LQ400EW
T5VQ400BW
T5VQ400CW
T5VQ400EW

List
price

$ 3,628
4,302
5,526
3,729
4,391
5,719
6,005
6,559
7,956
7,635
8,208
9,600
11,582
12,473
13,480

16

1 T5 600A not available in 100% rated frame.

16.26	
1SXU000023C0202	

Discount schedule S5T

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

T5
400/600A, 600V ∆
Instantaneous only, MCP/Molded case switch

15
T
M ma
CC x
Bs

T5 - 400A Frame, magnetic only (MCP - AC only)
Breaker

IC at 480VAC

Trip unit type

Rating

Adjustment
range

3 pole, 600VAC
Catalog number

List
price

T5N

25kA

Instantaneous
only

$ 3,097

35kA

Instantaneous
only

300-3000
400-4000
300-3000
400-4000

T5N300E5W
T5N400E5W

T5S

300A
400A
300A
400A

T5S300E5W
T5S400E5W

3,183

T5H

65kA

Instantaneous
only

300A
400A

300-3000
400-4000

T5H300E5W
T5H400E5W

5,125

Instantaneous
only

300A
400A

300-3000
400-4000

T5L300E5W
T5L400E5W

6,517

Rating

Adjustment
range

3 pole, 600VAC
Catalog number

List
price

600A

600-6000

T5N600E5W

$ 5,615

600A

600-6000

T5S600E5W

5,770

600A

600-6000

T5H600E5W

7,761

600A

600-6000

T5L600E5W

9,370

T5L

100kA

T5 - 600A Frame, magnetic only (MCP - AC only)
Breaker

IC at 480VAC

T5N

25kA

T5S

35kA

T5H

65kA

T5L

100kA

Trip unit type

Instantaneous
only
Instantaneous
only
Instantaneous
only
Instantaneous
only

Molded case switch 1
Type

IC at 480VAC

Amps

T5N-D
25kA
400
T5S-D
35kA
400
T5H-D
65kA
400
T5L-D
100kA
400
T5V-D
150kA
400
T5N-D
25kA
600
T5S-D
35kA
600
T5H-D
65kA
600
T5L-D
100kA
600
T5V-D
150kA
600
Note: For terminal connection options see page 16.43.

Magnetic
trip

3 pole 600V
catalog number

5000
5000
5000
5000
5000
6000
6000
6000
6000
6000

T5N400DW
T5S400DW
T5H400DW
T5L400DW
T5V400DW
T5N600DW
T5S600DW
T5H600DW
T5L600DW
T5V600DW

List
price

$ 2,393
2,659
4,585
5,878
7,536
3,419
3,799
6,550
8,350
11,575

16

1 When protected by a OCPD with appropriate ratings.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Discount schedule S5T

16.27
1SXU000023C0202

15
ax s
Tm CB
C
M

T6
600A, 800A, 600V ∆
Thermal magnetic and electronic
Dimensions	 3P Fixed Version 	 10.55H x 8.26W x 4.07D
Weight		

20.9 (Ibs)

T6

General

The T6 breaker is an 800 amp frame with either a microprocessor based over
current protective trip system or a thermal magnetic trip unit. The T6 is available
as a 600 or 800A frame.

Standards

The UL489/CSA 22.2 version of T6 also carries an IEC-60947-2 rating.

Versions

To meet all application requirements, the T6 is available in the following versions:
T = Thermal-magnetic, fixed
B = Selectable & adjustable LI or LS
C = Adjustable LSI
E = Adjustable LSIG
D = Molded Case Switch
E5 = Electronic instantaneous only (MCP)

Trip functions

These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault

UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage

N

S

H

L

240VAC

65

100

200

200

480VAC

35

50

65

100

600VAC

20

25

35

42

500VDC 1

35

35

50

65

600VDC 2

20

20

35

50

IEC 60947-2 Interrupting capacity (kA RMS)
Voltage

N

S

H

L

230VAC

70

85

100

200

415VAC

36

50

70

100

600VAC

20

22

25

30

750VDC 2

16

20

36

50

Performance levels

16

Each version is also available in different maximum fault interrupting levels:
N = Normal
S = Standard
H = High
L = Extra high

Number of poles 3

The T6 is available as a 3 and 4 pole breaker. Estimate 4 pole pricing by adding
35% to the 3 pole price and contact your ABB sales person for details.

1	 2 poles in series.
2	 3 poles in series.
3	 4 pole available N and H version only.

16.28	
1SXU000023C0202	

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

T6
600A, 800A, 600V ∆
Thermal magnetic and electronic

15
T
M ma
CC x
Bs

T6
600A, 800A, 600V
Thermal Magnetic Trip Units
Breaker IC at 480 VAC kA
T6N

35

T6S

50

T6H

65

T6L

100

Rating

Magnetic trip

3 pole, 600VAC/600VDC
catalog number

600A
800A
600A
800A
600A
800A
600A
800A

3000 - 6000A
4000 - 8000A
3000 - 6000A
4000 - 8000A
3000 - 6000A
4000 - 8000A
3000 - 6000A
4000 - 8000A

T6N600TW
T6N800TW
T6S600TW
T6S800TW
T6H600TW
T6H800TW
T6L600TW
T6L800TW

T6
600A, 800A, 600V
Thermal Magnetic Trip Units 100% rated
Breaker IC at 480 VAC kA
T6N

35

T6S

50

T6H

65

T6L

100

Rating

Magnetic trip

600A
800A
600A
800A
600A
800A
600A
800A

3000 - 6000A
4000 - 8000A
3000 - 6000A
4000 - 8000A
3000 - 6000A
4000 - 8000A
3000 - 6000A
4000 - 8000A

Trip type

Adjustment

PR221
PR222
PR222
PR221
PR222
PR222
PR221
PR222
PR222
PR221
PR222
PR222

LS/I
LSI
LSIG
LS/I
LSI
LSIG
LS/I
LSI
LSIG
LS/I
LSI
LSIG

Trip type

Adjustment

PR221
PR222
PR222
PR221
PR222
PR222
PR221
PR222
PR222
PR221
PR222
PR222

LS/I
LSI
LSIG
LS/I
LSI
LSIG
LS/I
LSI
LSIG
LS/I
LSI
LSIG

T6
600A, 600V
Electronic Trip Units
Breaker

IC at 480VAC

T6N

35

T6S

50

T6H

65

T6L

100

T6
800A, 600V
Electronic Trip Units
Breaker

IC at 480VAC

T6N

35

T6S

50

T6H

65

T6L

100

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

3 pole, 600VAC/600VDC
catalog number
T6NQ600TW
T6NQ800TW
T6SQ600TW
T6SQ800TW
T6HQ600TW
T6HQ800TW
T6LQ600TW
T6LQ800TW

3 pole, 600VAC catalog
number
T6N600BW
T6N600CW
T6N600EW
T6S600BW
T6S600CW
T6S600EW
T6H600BW
T6H600CW
T6H600EW
T6L600BW
T6L600CW
T6L600EW

3 pole, 600VAC catalog
number
T6N800BW
T6N800CW
T6N800EW
T6S800BW
T6S800CW
T6S800EW
T6H800BW
T6H800CW
T6H800EW
T6L800BW
T6L800CW
T6L800EW

List price
$ 6,700
7,400
7,100
7,800
7,300
8,050
9,300
9,968

List price
$ 7,370
8,140
7,810
8,580
8,030
8,855
10,230
10,965

List price
$ 6,900
6,560
8,400
7,300
7,800
8,800
7,550
8,050
9,050
9,550
10,425
11,557

16

List price
$ 8,100
8,600
10,600
9,100
9,600
11,600
9,300
9,800
11,800
10,965
11,465
13,465

Discount schedule S6T

16.29
1SXU000023C0202

15

T6
600A, 800A, 600V ∆
Thermal magnetic and electronic

ax s
Tm CB
C
M

T6
600A, 600V ∆
Electronic Trip Units 100% Rated
Breaker

IC at 480VAC

T6N

35

T6S

50

T6H

65

T6L

100

Trip type
PR221
PR222
PR222
PR221
PR222
PR222
PR221
PR222
PR222
PR221
PR222
PR222

3 pole, 600VAC
catalog number
T6NQ600BW
T6NQ600CW
T6NQ600EW
T6SQ600BW
T6SQ600CW
T6SQ600EW
T6HQ600BW
T6HQ600CW
T6HQ600EW
T6LQ600BW
T6LQ600CW
T6LQ600EW

Adjustment
LS/I
LSI
LSIG
LS/I
LSI
LSIG
LS/I
LSI
LSIG
LS/I
LSI
LSIG

T6
800A, 600V
Electronic Trip Units 100% Rated
Breaker

IC at 480VAC

T6N

35

T6S

50

T6H

65

T6L

100

Trip type
PR221
PR222
PR222
PR221
PR222
PR222
PR221
PR222
PR222
PR221
PR222
PR222

3 pole, 600VAC
catalog number
T6NQ800BW
T6NQ800CW
T6NQ800EW
T6SQ800BW
T6SQ800CW
T6SQ800EW
T6HQ800BW
T6HQ800CW
T6HQ800EW
T6LQ800BW
T6LQ800CW
T6LQ800EW

Adjustment
LS/I
LSI
LSIG
LS/I
LSI
LSIG
LS/I
LSI
LSIG
LS/I
LSI
LSIG

T6
600A, 600V ∆
Electronic Trip Units Instantaneous Only
Breaker

IC at 480VAC

T6N
T6S
T6H
T6L

16

kA

35
50
65
100

Trip type

Adjustment Range

PR221
PR221
PR221
PR221

600-6000
600-6000
600-6000
600-6000

T6
800A, 600V
Electronic Trip Units Instantaneous Only
Breaker

IC at 480VAC

T6N
T6S
T6H
T6L

kA

35
50
65
100

Trip type

Adjustment Range

PR221
PR221
PR221
PR221

800-8000
800-8000
800-8000
800-8000

T6
800A, 600V
Molded Case Switch

3 pole, 600VAC
catalog number
T6N600E5W
T6S600E5W
T6H600E5W
T6L600E5W

3 pole, 600VAC
catalog number
T6N800E5W
T6S800E5W
T6H800E5W
T6L800E5W

List price
$ 6,496
7,216
9,240
8,030
8,580
9,680
10,230
10,780
12,980
10,505
11,605
12,713

List price
$ 8,910
9,460
11,660
10,010
10,560
12,760
8,305
10,667
11,667
12,062
12,612
14,812

List price
$ 5,929
6,407
6,623
8,635

List price
$ 6,254
6,733
6,948
8,961

Breaker

IC at 480VAC 1

Amp

Magnetic Trip

3 pole, 600VAC
catalog number

List price

T6H

65

800

10,000

T6H800DW

$ 4,824

Note: For terminal connection options see page 16.43

1 When protected by a OCPD with appropriate ratings.

16.30	
1SXU000023C0202	

Discount schedule S6T

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

15

T7
1000A, 1200A, 600V ∆
Electronic

T
M ma
CC x
Bs

Dimensions	 3P Fixed Version 	 10.55H x 8.26W x 6.06D
Weight		

21.4 (Ibs)

T7

General

The T7 breaker is a 1200 amp frame with a microprocessor based over current
protective trip system.

Standards

The UL489/CSA 22.2 version of T7 also carries an IEC-60947-2 rating.

Versions

To meet all application requirements, the T7 is available in the following versions:
B = Selectable & adjustable LI or LS
C = Adjustable LSI
E = Adjustable LSIG
D = Molded Case Switch
P = LI
R = LSI
S = LSIG

Trip functions

UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage

S

H

L

240VAC

65

100

150

480VAC

50

65

100

600VAC

25

50

65

IEC 60947-2 Interrupting capacity (kA RMS)
Voltage

S

H

L

230VAC

85

100

200

415VAC

50

70

120

690VAC

30

42

50

These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault

Performance levels

Each version is also available in different maximum fault interrupting levels:
S = Standard
H = High
L = Extra high

16

Number of poles 1

The T7 is available as a 3 and 4 pole breaker. Estimate 4 pole pricing by adding
35% to the 3 pole price and contact your ABB sales person for details.

1 4 Pole available S, H and L version.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

16.31
1SXU000023C0202

T7
1000A, 1200A, 600V ∆
Electronic

ax s
Tm CB
C
M
T7S, 1000A, 600V
Electronic
Breaker

IC at 480VAC    kA

Trip type

Adjustment

50

PR231/P
PR232/P
PR331/P
PR332/P
PR332/P
PR332/P

LS/I
LSI
LSIG
LI
LSI
LSIG

IC at 480VAC    kA

Trip type

Adjustment

50

PR231/P
PR232/P
PR331/P
PR332/P
PR332/P
PR332/P

LS/I
LSI
LSIG
LI
LSI
LSIG

IC at 480VAC    kA

Trip type

Adjustment

65

PR231/P
PR232/P
PR331/P
PR332/P
PR332/P
PR332/P

T7S

T7S, 1200A, 600V
Electronic
Breaker

T7S

T7H, 1000A, 600V
Electronic
Breaker

T7H

LS/I
LSI
LSIG
LI
LSI
LSIG

T7H, 1200A, 600V
Electronic
Breaker

IC at 480VAC    kA

Trip type

65

PR231/P
PR232/P
PR331/P
PR332/P
PR332/P
PR332/P

T7H

16

Adjustment
LS/I
LSI
LSIG
LI
LSI
LSIG

T7L, 1000A, 600V
Electronic
Breaker

IC at 480VAC    kA

Trip type

100

PR231/P
PR232/P
PR331/P
PR332/P
PR332/P
PR332/P

T7L

Adjustment
LS/I
LSI
LSIG
LI
LSI
LSIG

T7L, 1200A, 600V
Electronic
Breaker

IC at 480VAC    kA

Trip type

100

PR231/P
PR232/P
PR331/P
PR332/P
PR332/P
PR332/P

T7L

16.32	
1SXU000023C0202	

Adjustment
LS/I
LSI
LSIG
LI
LSI
LSIG

3 pole, 600VAC catalog
number
T7S1000BW
T7S1000CW
T7S1000EW
T7S1000PW
T7S1000RW
T7S1000SW

3 pole, 600VAC catalog
number
T7S1200BW
T7S1200CW
T7S1200EW
T7S1200PW
T7S1200RW
T7S1200SW

3 pole, 600VAC catalog
number
T7H1000BW
T7H1000CW
T7H1000EW
T7H1000PW
T7H1000RW
T7H1000SW

3 pole, 600VAC catalog
number
T7H1200BW
T7H1200CW
T7H1200EW
T7H1200PW
T7H1200RW
T7H1200SW

3 pole, 600VAC catalog
number
T7L1000BW
T7L1000CW
T7L1000EW
T7L1000PW
T7L1000RW
T7L1000SW

3 pole, 600VAC catalog
number
T7L1200BW
T7L1200CW
T7L1200EW
T7L1200PW
T7L1200RW
T7L1200SW

Discount schedule S7T

List price
$ 9,803
10,303
12,303
10,362
11,362
12,606

List price
$ 13,235
13,451
14,063
13,792
14,790
16,036

List price
$ 11,937
12,197
19,120
12,589
13,739
15,170

List price
$ 14,025
14,252
15,924
14,593
15,591
16,837

List price
$ 10,965
11,191
12,863
11,532
12,532
13,776

List price
$ 14,826
15,053
16,725
15,394
16,393
17,638

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

T7
1000A, 1200A, 600V ∆
Electronic, 100% rated
T7S, 1000A, 600V
Electronic, 100% rated
Breaker

T7S

IC at 480VAC    kA

Trip type

50

PR231/P
PR232/P
PR331/P
PR332/P
PR332/P
PR332/P

Adjustment
LS/I
LSI
LSIG
LI
LSI
LSIG

T7S, 1200A, 600V
Electronic, 100% rated
Breaker

T7S

IC at 480VAC    kA

Trip type

50

PR231/P
PR232/P
PR331/P
PR332/P
PR332/P
PR332/P

Adjustment
LS/I
LSI
LSIG
LI
LSI
LSIG

T7H, 1000A, 600V
Electronic, 100% rated
Breaker

T7H

IC at 480VAC    kA

Trip type

Adjustment

65

PR231/P
PR232/P
PR331/P
PR332/P
PR332/P
PR332/P

LS/I
LSI
LSIG
LI
LSI
LSIG

IC at 480VAC    kA

Trip type

Adjustment

65

PR231/P
PR232/P
PR331/P
PR332/P
PR332/P
PR332/P

LS/I
LSI
LSIG
LI
LSI
LSIG

T7H, 1200A, 600V
Electronic, 100% rated
Breaker

T7H

T7L

IC at 480VAC    kA

Trip type

100

PR231/P
PR232/P
PR331/P
PR332/P
PR332/P
PR332/P

Adjustment
LS/I
LSI
LSIG
LI
LSI
LSIG

T7L, 1200A, 600V
Electronic, 100% rated
Breaker

T7L

IC at 480VAC    kA

Trip type

100

PR231/P
PR232/P
PR331/P
PR332/P
PR332/P
PR332/P

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

3 pole, 600VAC catalog
number
T7SQ1000BW
T7SQ1000CW
T7SQ1000EW
T7SQ1000PW
T7SQ1000RW
T7SQ1000SW

$ 10,783
11,333
13,533
11,398
12,498
13,867

3 pole, 600VAC catalog
number
T7SQ1200BW
T7SQ1200CW
T7SQ1200EW
T7SQ1200PW
T7SQ1200RW
T7SQ1200SW

$ 14,559
14,769
15,469
15,171
16,269
17,640

3 pole, 600VAC catalog
number
T7HQ1000BW
T7HQ1000CW
T7HQ1000EW
T7HQ1000PW
T7HQ1000RW
T7HQ1000SW

$ 13,131
13,417
15,532
13,848
15,113
16,687

3 pole, 600VAC catalog
number
T7HQ1200BW
T7HQ1200CW
T7HQ1200EW
T7HQ1200PW
T7HQ1200RW
T7HQ1200SW

$ 15,428
15,677
17,516
16,052
17,150
18,521

List price

List price

List price

List price

16

T7L, 1000A, 600V
Electronic, 100% rated
Breaker

T
M ma
CC x
Bs

Adjustment
LS/I
LSI
LSIG
LI
LSI
LSIG

3 pole, 600VAC catalog
number
T7LQ1000BW
T7LQ1000CW
T7LQ1000EW
T7LQ1000PW
T7LQ1000RW
T7LQ1000SW

$ 12,062
12,310
14,149
12,685
12,785
15,154

3 pole, 600VAC catalog
number
T7LQ1200BW
T7LQ1200CW
T7LQ1200EW
T7LQ1200PW
T7LQ1200RW
T7LQ1200SW

$ 16,309
16,558
18,398
16,933
18,032
19,402

List price

Discount schedule S7T

List price

16.33
1SXU000023C0202

T7
1200A, 600V ∆
Electronic/Molded case switch

ax s
Tm CB
C
M
T7
1200A, 600V
Molded case switch
Breaker

IC at 480VAC    kA
1

Amp

Magnetic
trip

3 pole, 600VAC catalog
number

T7H

-

1200

12,000

T7H1200DW

List price
Consult
factory

Call for availability!

Note: For terminal connection options see page 16.43

16

1 When protected by a OCPD with appropriate ratings.

16.34	
1SXU000023C0202	

Discount schedule S7T

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

T8V & S8V
1600 / 2000 / 2500 / 3000A
Insulated case circuit breaker

	

T8V	

T
M ma
CC x
Bs

S8V

T8V (1600A / 2000A / 2500A / 3000A)

S8V (1600A / 2000A / 2500A)

•	 Dimensions 3P Version:  15.00” H x 16.8”W x 11.2”D	

•	 Dimensions 3P Version:  15.75” H x 15.98”W x 9.25”D	

•	 Weight: 161 (lbs) 1600A/2000A/2500A
                 236 (lbs) 3000A	
	
Voltage	
Interrupting capacity
240 VAC	
125
480 VAC	
125
600 VAC	
100
600 VDC	
—

•	 Weight: 135 (lbs) 	
	
Voltage	
Interrupting capacity
240 VAC	
125
480 VAC	
100
600 VAC	
85
600 VDC 1	
25
•	 Three different frame ratings, 1600, 2000 and 2500 Amps 	

•	 Four different frame ratings, 1600, 2000, 2500 & 3000 Amps 	

•	 Available 100% rated version up to 2000A 	

•	 Available 100% rated version up to 3000A 	

•	 Standard interrupting capacity 100kA @ 480V 	

•	 Standard interrupting capacity 125kA @ 480V 	

•	 Installation vertical position only	

•	 Installation vertical position only	

•	 Internal accessories include electric charging motor,	
	 combination auxiliary /bell alarm switch, and undervoltage release	

•	 Wide range of UL field-installable accessories	
•	 Solid state trip unit available in three different versions:
	 PR232/P-LSI
	 PR331/P-LSIG
	 PR332/P-LI
	 PR332/P-LSI
	 PR332-LSIG
	 The ability to add internal modules for flexible and precise
	 configuration:
	 Optional modules include:
	 Voltage module
	 Signaling module
	 Communications module

•	 Solid state trip unit available in three different versions:
	 PR212/P-LSI	
	 PR212/P-LSIG	

16

Coming 2009
Call for Availability!

1 Applies to MCS only.
Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

16.35
1SXU000023C0202

Accessories
Electrical
T1 - T7

ax s
Tm CB
C
M

Shunt trips -(Standard) 1
For remote opening of circuit breaker. Guaranteed operation for a voltage of between 75-110%
of the rated power supply voltage. T1-T6 mounts in the left hand cavity cannot be used with UVR on 2-3P breakers
Factory Installation 1
Frame Size

T1-T3
KT3S4

Ts3

T4, T5, T6
3

T1 with KT3S4

T7

Voltage

Catalog number
suffix

480 - 500VAC
220-250VAC/DC
380 - 440VAC
110 - 125VAC/DC
48 - 60VAC/DC
24 - 30VAC/DC
12VDC
480VAC/250VDC
240 VAC
120VAC/125VDC
48VDC
24VAC/VDC
12VDC
480-500VAC
220/250VAC/DC
380-440VAC
110-125VAC/DC
48-60VAC/DC
24VAC/DC
12VDC
415-440VAC
380-400VAC
240-250VAC/DC
220-240VAC/DC
120-127VAC/DC
110-120VAC/DC
60VAC/DC
48VAC/DC
30VAC/DC
24VAC/DC

S1
S2
S3
S4
S7
S8
S9
S1
S2
S4
S7
S8
S9
S1
S2
S3
S4
S7
S8
S9
S1
S2
S3
S4
S5
S6
S7
S8
S9
S0

List price
adder

$ 535

535

535

535

Shunt trip connector (REQUIRED for Ts3) 2
Ts3
Ts3

Fixed Mount 2
Draw-out 2

Field Installation
List
Price

Catalog number

KT3S1
KT3S2
KT3S3
KT3S4
KT3S7
KT3S8
KT3S9
KTS3S1
KTS3S2
KTS3S4
KTS3S7
KTS3S8
KTS3S9
KT5S1
KT5S2
KT5S3
KT5S4
KT5S7
KT5S8
KT5S9
KT7XS1
KT7XS2
KT7XS3
KT7XS4
KT7XS5
KT7XS6
KT7XS7
KT7XS8
KT7XS9
KT7XS0

$ 490

490

490

490

Field Kit

Included when shunt trip factory installed
Included when shunt trip factory installed

KTS3C-SU
KTS3C-SUP

$ 45

Shunt trips (Permanent Supply) 1
T7 X1 Shunt trip - UVR

For remote opening of circuit breaker. Guaranteed operation for a voltage of between 75-110% of the rated power supply
voltage. These shunt trips have much lower power consumption.
Factory Installation 1
Frame Size

16

Ts3
T4, T5, T6 3

Voltage

Catalog number
suffix

24VDC
120VAC
24-30VDC
110/120/VAC

SA
SB
SA
SB

List price
adder

$ 535
535

Shunt trip connector (REQUIRED for Ts3) 2
Ts3

Fixed Mount 2
Draw-out 2

Included when shunt trip factory installed
Included when shunt trip factory installed

Field Installation
Catalog number

KTS3SA
KTS3SB
KT5SA
KT5SB

List
Price

$ 490
490
Field Kit

KTS3C-SU
KTS3C-SUP

$ 45

1 For factory installation add suffix given to end of circuit breaker catalog number per accessory format.
2 Must be ordered separately for field installation.
3 SAT5 Discount schedule.

16.36	
1SXU000023C0202	

Discount schedule SAT — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 — T4-T5 Accessories

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Accessories
Electrical
T1 - T7

T
M ma
CC x
Bs

Undervoltage release - UVR

Will trip circuit breaker when connected voltage drops to 35-70% of the undervoltage release
voltage rating.  Will allow circuit breaker to close when voltage is approximately 85% of the
rated voltage. T1-T6 mounts in the left hand cavity cannot be used with shunt trip on 2-3P breakers
Field Installation

Factory Installation 1
Frame Size

T1-T3

KT3U2

Ts3

T4, T5, T6
3

T7 X1 Shunt trip - UVR

T7

Voltage

Catalog number
suffix

480 - 500VAC
220-250VAC/DC
380 - 440VAC
110 - 125VAC/DC
60VAC/DC
48VAC/DC
24 - 30VAC/DC
480VAC
240VAC
24VAC
120VAC
250VDC
125VDC
48VDC
24VDC
480-500VAC
220/250VAC/DC
380-440VAC
110-125VAC/DC
60VAC/DC
48VAC/DC
24VAC/DC
415-440VAC
380-400VAC
240-250VAC/DC
220-240VAC/DC
120-127VAC/DC
110-120VAC/DC
60VAC/DC
48VAC/DC
30VAC/DC
24VAC/DC

U1
U2
U3
U4
U5
U7
U8
U1
U2
U3
U4
U5
U6
U7
U8
U1
U2
U3
U4
U5
U7
U8
U1
U2
U3
U4
U5
U6
U7
U8
U9
U0

List price
adder

Ts3

Fixed Mount 2
Plug-In/Draw-out 2

KT3U1
KT3U2
KT3U3
KT3U4
KT3U5
KT3U7
KT3U8
KTS3U1
KTS3U2
KTS3U3
KTS3U4
KTS3U5
KTS3U6
KTS3U7
KTS3U8
KT5U1
KT5U2
KT5U3
KT5U4
KT5U5
KT5U7
KT5U8
KT7XU1
KT7XU2
KT7XU3
KT7XU4
KT7XU5
KT7XU6
KT7XU7
KT7XU8
KT7XU9
KT7XU0

$ 535

535

535

535

Undervoltage trip connector (REQUIRED for Ts3) 2

Included when under voltage factory installed
Included when under voltage factory installed

List
Price

Catalog number

$ 490

490

490

490

Field Kit

KTS3C-SU
KTS3C-SUP

$ 45

16

1 For factory installation add suffix given to end of circuit breaker catalog number per accessory format.
2 Must be ordered separately for field installation.
3 SAT5 Discount schedule.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Discount schedule SAT — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 — T4-T5 Accessories

16.37
1SXU000023C0202

Accessories
Electrical
T1 - T7

ax s
Tm CB
C
M

Auxiliary contacts - AUX 1
Auxiliary contacts are for indication of the circuit breaker open-closed.  Bell alarm contacts (BA) can be
used to indicate circuit breaker tripped.
Factory Installation 1
Frame Size

T1-T3 2
T2
Ts3
T4, T5, T6 4

T7

1 Form C + 1BA
3 Form C + 1BA
3 Form C + 1BA 24VDC
T2 PR221DS 1 Form C + 1BA
2 Form C
1 Form C+ 1 BA
1 Form C + 1BA 250VAC/VDC
3 Form C + 1BA 250VAC/VDC
3 Form C + 1BA 24VDC
1 Form C + 1BA 400VAC/250VDC
2 Form C 400VAC/250VDC
1 Form C + 1BA 24VDC
2 Form C 24VDC

Catalog number
suffix

T1 with K3TAS

Ts3

Fixed Mount 3
Plug-In /Drawout 3

$ 433
770
770
433

A
A3
A3AU
A
A
BA
A
A3
A3AU
A
A2
AAU
A2AU

Auxiliary contact connector (REQUIRED for Ts3) 3

List price
adder

430
433
770
770
446

Field Installation
Catalog number

KT3AS
KT3AS3
KT3AS3-AU
KT2AS-E
KTS3AS
KTS3BA
KT5AS
KT5AS3
KT5AS3-AU
KT7AS
KT7XAS2
KT7AS-AU
KT7XAS2-AU

List
Price

$ 380
725
725
380
275
380
388
725
725
396

Field Kit

Included
Included

KTS3C-AB
KTS3C-ABP

$ 45

KTS3AS

16

1 For factory installation add suffix to end of breaker part number per accessory format .
2 Not compatible for T2 with PR221DS trip unit.
3 Must be ordered separately for field installation.
4 SAT5 Discount schedule.

16.38	
1SXU000023C0202	

Discount schedule SAT — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 — T4-T5 Accessories

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Accessories
Motor operators
T1 - T7

T
M ma
CC x
Bs

Electrical operators
Allows remote opening and closing of circuit breaker
Frame size

Voltage

Catalog
number

List
price

Solenoid operator
T1-T3

48 - 60VDC
110 - 250VAC/DC

KT3M1
KT3M2

$ 850

KTS3M2
KTS3M4
KTS3M7
KTS3M8

1,799

Direct action motor operator
Ts3

240VAC/250VDC
120VAC/125VDC
48VDC
24VDC

Motor operator connector (REQUIRED for Ts3) 1
KT3M1

Ts3

Fixed Mount 1
Plug-In / Draw-out 1

KTS3C-M
KTS3C-MP

45

Stored energy motor operator
T4, T5

220-250VAC/DC
110--125-VAC/DC
48-60VDC
24VDC

KT5M2
KT5M4
KT5M7
KT5M8

2,385

Contact for remote/manual operation (stored energy operator)
-

KT5MA

220

220-250VAC/DC
110--125-VAC/DC
48-60VDC
24VDC
380VAC

KT6M2
KT6M4
KT6M7
KT6M8
KT6M3

4,990

T4, T5, T6 2

Stored energy motor operator
T6

KT5M2

16

KTS3M2

1 Must be ordered separately for field installation
2 SAT5 Discount schedule.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Discount schedule SAT — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 — T4-T5 Accessories

16.39
1SXU000023C0202

ax s
Tm CB
C
M

Accessories
Trip units

Frame Size

Catalog
number

List
Price

KT7X0400RP
KT7X0600RP
KT7X0800RP
KT7X1000RP
KT7X1200RP

$ 125

PR330/D-M
PR030/B

4,500
275

Rating plugs
400A Rating plug
600A Rating plug
800 Rating plug
1000A Rating plug
1200 Rating plug

T7

Modules for T7 PR332 electronic trip units
Communication module (Modbus RTU)
Battery power supply unit 1

T7

Neutral current transformers (required for 4 wire ground fault systems)
100A
150A
250A
300A
400A
600A
800A

T4
T5
T6

KT4NCT-100
KT4NCT-150
KT4NCT-250
KT5NCT-300
KT5NCT-400
KT6NCT-600
KT6NCT-800

300
300
770

Test sets
Test and configuration unit 3
Trip coil test-all Tmax electronic trip unit except PR33*
External Bluetooth communication module 1
Includes diagnostic software for Modbus / Bluetooth networks

PR010/T
K7TUT
BT030

12,500
210
3,335

Actuator module
T7

Actuator module 2

PR330/R-T7

700

16

1 Always supplied with PR332/P trip unit.
2 Must be ordered when using PR330/D-M.
3 Discount schedule EDX.

16.40	
1SXU000023C0202	

Discount schedule SAT — T6, T7 Accessories
Discount schedule SAT5 — T4-T5 Accessories

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Technical data
Shunt trips/Undervoltages

T
M ma
CC x
Bs

Standard shunt trip
Voltage

12 VDC
24 VAC/DC
24…30 VAC/DC
30 VAC/DC
48 VAC/DC
48…60 VAC/DC
60 VAC/DC
100…120 VAC/DC
120…127 VAC/DC
110…127 VAC 110…125 VDC
220…240 VAC/DC
220…240 VAC 220…250 VDC
240…250 VAC/DC
380…400 VAC
380…440 VAC
415…440 VAC
480 VAC
480…525 VAC
Opening Time (ms)

T1,T2,T3
AC (VA)
DC (W)

50
60
50
50
55
55
15

50
50
60
50
50
15

Inrush Power Consumption
Ts3
T4,T5,T6
AC (VA)
DC (W)
AC (VA)
DC (W)

120
100
100 or 4 1
120
100 or 4 1
120
100
120
100
≤15
≤15

150
150
150
150
150
150
15

150
150
150
150
150
15

T7
AC (VA)

DC (W)

300
300
300
300
300
300
300
300
300
300
20

300
300
300
300
300
300
300
300
20

Permanent supply shunt trip
Voltage
24 VAC/DC
100…120 VAC

T4,T5,T6
AC (VA)
DC (W)
4
4
4
-

Undervoltage
Voltage

24 VAC/DC
24…30 VAC/DC
30 VAC/DC
48 VAC/DC
60 VAV/DC
110…120 VAC/DC
120…127 VAC/DC
110…127 VAC 110…125 VDC
220…240 VAC/DC
220…240 VAC 220…250 VDC
220…250 VAC
240…250 VAC/DC
380…400 VAC
380…440 VAC
415 - 440 VAC
480…525 VAC
480 VAC
Opening Time (ms)

T1,T2,T3
AC (VA)
DC (W)

1.5
1
1
2
2.5
3
4
15

1.5
1
1
2
2.5
15

Power consumption during permanent operation
Ts3
T4, T5, T6
AC (VA)
DC (W)
AC (VA)
DC (W)

6
6
6
6
6
≤18

3
3
3
≤18

6
6
6
6
6
6
6
≤25

3
3
3
3
3
≤25

T7
AC (VA)

DC (W)

3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
≤25

3.5
3.5
3.5
3.5
3.5
3.5
≤25

1 Shunt trip permanent supply

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

16.41
1SXU000023C0202

16

ax s
Tm CB
C
M

Technical data
Electrical operators
Electrical operator, T1-T3
Rated Voltage
Operating Voltage
Inrush power absorption during operation
Power on stand by
opening (s)
Time
closing  (s)
Minimum control impulse time on
opening and closing (ms)      

AC
DC
48…60
110...250
110...250
85…110% Un
1800 (VA)
1000 (W)
< 100 (mW)
< 0.1
< 0.1
>100

This unit is permanently supplied on stand by, a control is applied by means of
external contact in a low power circuit.
Contact characteristics:
                                Voltage  AC/DC=24V
                                Current 50 mA

Electrical operator, Ts3
Rated Voltage

Operating Voltage
Inrush power absorption
Service power absorption
Time constant (ms)
opening (s)
Duration
closing  (s)
Minimum duration of the opening and closing
command impulse (ms)

AC
DC
24
48…60
120
125
240
250
440
85…110 % Un
500 (VA)
500 (W)
350 (VA)
350 (W)
18
0.1
0.1
≥150

Electrical operator, T4-T5
Voltage

Operating Voltage
Inrush power consumption
In service power consumption
opening  (s)
Duration
closing   (s)
resetting (s)
Minimum duration of the opening and closing
command impulse (ms)

16

AC
DC
24
48…60
110…125 110…125
220-250
220-250
380
85…110%
≤ 300VA
≤ 300W
≤150VA
≤150W
1.5
< 0.1
3
≥100

Electrical operator, T6
Voltage

Operating Voltage
Inrush power consumption
In service power consumption
opening  (s)
Duration
closing   (s)
resetting (s)
Minimum duration of the opening and closing
command impulse (ms)

16.42	
1SXU000023C0202	

AC
DC
24
48…60
110-125
110-125
220-250
220-250
380
85…110%
≤ 400VA
≤ 400W
≤150VA
≤150W
3
< 0.1
5
≥100

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Accessories
Mechanical
T1 - T7

T
M ma
CC x
Bs

Standard cable terminal
Frame

T1
T2
T3
Ts3
T4
KT3100-3

T5
T5 1
T5 2
T6
T6 1
T7 1

Wire Size

14 AWG-1/0
14 AWG-1/0
14 AWG - 1/0
4 AWG - 300 kcmil
14-2
14-1/0
2-4/0
4-300 kcmil
14 AWG-1/0
6 AWG-350 kcmil
250 kcmil-500 kcmil
(2) 3/0-250 kcmil
(2) 3/0-500 kcmil
(2) 250-500 kcmil 3
(3) 2/0-400 kcmil 3
(4) 4/0-500 kcmil

Catalog number
(set of 3)

Integral
KT2100-3
KT3100-3
KT3225-3
K3TA 3
K4TB 3
K4TC 3
K4TD 3
KT4100-3
KT4250-3
KT5300-3
KT5400-3
KT5600-3
K6TH 3
K6TJ 3
KT7X1200-3

List
Price

Catalog number
(set of 4)

List
Price

—
$9
9
18
6
6
6
15
9
30
45
45
225
75
135
560

Integral
KT2100-4
KT3100-4
KT3225-4
K3TA-4 3
K4TB-4 3
K4TC-4 3
K4TD-4 3
KT4100-4
KT4250-4
KT5300-4
KT5400-4
—
K6TH-4 3
K6TJ-4 3
KT7X1200-4

—
$ 12
12
24
8
8
8
20
12
40
60
60
—
100
180
747

Standard cable lug kits with power control taps
Frame

T3
Ts3
T4
T5
T5 1
T6
T6 2

Wire Size

14 AWG - 1/0
4 AWG - 300 kcmil
14 AWG-1/0
2 AWG-4/0
4 AWG-300 kcmil
14 AWG-1/0
6 AWG-350 kcmil
250 kcmil-500 kcmil
(2) 3/0-250 kcmil
(2) 250-500 kcmil
(3) 2/0-400 kcmil

Catalog number
(set of 3)

List
Price

Catalog number
(set of 4)

List
Price

KT3100-3C
KT3225-3C
K4TBC
K4TCC
K4TDC
KT4100-3C
KT4250-3C
KT5300-3C
KT5400-3C
K6THC 3
K6TJC 3

$ 16
18
12
12
21
15
36
51
51
81
141

KT3100-4C
KT3225-4C
K4TBC-4
K4TCC-4
K4TDC-4
KT4100-4C
KT4250-4C
KT5300-4C
KT5400-4C
K6THC-4 3
K6TJC-4 3

$ 19
31
20
20
31
20
48
68
68
109
190

KT1HTC-3

Terminal covers for fixed breakers - Low profile-kit includes two pieces
Frame

T1
T2
T3
Ts3
T4
T5
T6
T7

Catalog number
(3 pole)

KT1LTC-3
KT2LTC-3
KT3LTC-3
KTS3LTC-3
KT4LTC-3
KT5LTC-3
KT6LTC-3
KT7XLTC-3

List
Price

$ 35
40
50
55
55
60
75
80

Catalog number
(4 pole)

KT1LTC-4
KT2LTC-4
KT3LTC-4
KTS3LTC-4
KT4LTC-4
KT5LTC-4
KT6LTC-4
KT7XLTC-4

List
Price

$ 47
54
68
74
74
81
101
108

16

Terminal covers for fixed breakers - High profile-kit includes two pieces
Frame

KT4LTC-3

T1
T2
T3
Ts3
T4
T5
T6
T7

Catalog number
(3 pole )

KT1HTC-3
KT2HTC-3
KT3HTC-3
KTS3HTC-3
KT4HTC-3
KT5HTC-3
KT6HTC-3
KT7XHTC-3

List
Price

$ 37
43
53
58
58
63
85
90

Catalog number
(4 pole)

KT1HTC-4
KT2HTC-4
KT3HTC-4
KTS3HTC-4
KT4HTC-4
KT5HTC-4
KT6HTC-4
KT7XHTC-4

List
price

$ 50
58
72
78
78
85
108
115

1 Comes standard with high profile terminal covers.
2 Uses front extended spreaded terminals... refer to technical catalog.
3 Discount schedule SA.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Discount schedule SAT — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 — T4-T5 Accessories

16.43
1SXU000023C0202

Accessories
Mechanical
T1 - T7

ax s
Tm CB
C
M

Phase barriers - Low profile 100mm-3.93 in
Frame

T1-T3
T4-T5
T6
T7

4 pcs (3p)

KT3PBL-3
KT5PBL-3
KT6PBL-3
KT7PBL-3

List
Price

$ 28
28
42
50

6 pcs (4p)

KT3PBL-4
KT5PBL-4
KT6PBL-4
KT7PBL-4

List
Price

$ 42
42
57
68

Phase barriers - High profile 200mm-7.87 in

KT2EF-3

Frame

4 pcs (3p)

List
Price

6 pcs (4p)

List
Price

T1-T3
T4-T5
T7

KT3PBH-3
KT5PBH-3
KT7PBH-3

$ 42
42
67

KT3PBH-4
KT5PBH-4
KT7PBH-4

$ 63
63
90

Saddle terminals for Copper Cables - IEC
Frame

Catalog number
( Set of 3 )

List
Price

Catalog number
(Set of 4)

List
Price

T2
T3
Ts3
T4
T5

KT2100S-3
KT3225S-3
K4TES 3
KT4250S-3
KT5300S-3

$ 34
52
30
41
270

KT2100S-4
KT3225S-4
K4TES-4 4
KT4250S-4
KT5300S-4

$ 46
70
40
55
365

Extended front terminals

KT4EF-_

16

KT2R-3

Frame

Catalog number
(set of 3)

List
Price

Catalog number
(set of 4)

List
Price

T2
T3
Ts3
T4
T5   

KT2EF-3
KT3EF-3
KTS3EF-3
KT4EF-3
KT5EF-3

$ 26
33
65
55
115

KT2EF-4
KT3EF-4
KTS3EF-4
KT4EF-4
KT5EF-4

$ 35
44
88
73
155

Frame

Catalog number
(set of 3)

List
Price

Catalog number
(set of 4)

List
Price

T2
T3
T4
T5
T6
T7

KT2R-3
KT3R-3
KT4R-3
KT5R-3
KT6R-3
KT7R-3

$ 78
98
60
122
350
407

KT2R-4
KT3R-4
KT4R-4
KT5R-4
KT6R-4
KT7R-4

Rear terminals 1
$ 105
131
80
163
473
550

Distribution cable lug kit 2
Frame

T3
Ts3
T4
T5

Wire Size

(6) #14-6
(6) #14-6
(6) #14-6
(6 )#14-1/0

Catalog number
(set of 3)

KT3TN
KTS3TN
KT4TN
KT5TGD

List
Price

$ 125
125
125
240

Catalog number
(set of 4)

KT3TN-4
KTS3TN-4
KT4TN-4
KT5TGD-4

List
Price

$ 167
169
167
320

1 Includes low profile terminal cover.
2 Includes high profile terminal cover.
3 Set of six, Discount schedule SA.
4 Set of eight, Discount schedule SA.

16.44	
1SXU000023C0202	

Discount schedule SAT — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 — T4-T5 Accessories

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Accessories
Mechanical, T1 - T7
Locking devices and handle operators

T
M ma
CC x
Bs

Padlock locking device
Frame

Style

Locking Position

T1,T2,T3

PLL

OPEN/CLOSED
OPEN

Ts3

FLD

OPEN

T4-T5

FLD

OPEN

T6

FLD

OPEN

T7

PLL

OPEN

Breaker
Mounting

Catalog number

KT3LD
KT3LDO
KTS3FLD
KTS3FLDW
KT5FLD
KT5FLDW
KT6FLD
KT6FLDW
KT7LDO

Fixed
Fixed, Plug-In
Draw-0ut
Fixed, Plug-In
Draw-out
Fixed, Plug-In
Draw-out
Fixed, Drawout

List
Price

$ 35
87
125
40
55
220
240
260

Keylocks-rotary handle mechanism
Frame
KT3LD

T1,T2,T3
Ts3
T4-T5
T6
T7

Style

Locking Position

Keys

Catalog number

RHL
KLF-D
KLF-D
KLF-D

OPEN/CLOSED
OPEN
OPEN
OPEN
OPEN

Different
Different
Different
Different
Different

KT3RHL3
KTS3KLFD
KT5KLFD
KT6KLFD
KT7KLFD

List
Price

$ 94
58
58
68
79

Direct mount rotary operator handle
Breaker
Mounting

Frame

KT5RH

T1,T2,T3
Ts3
Ts3
T5
T5
T6
T6
T7

Catalog number

List
Price

KT3RH
KTS3RH
KTS3RHW
KT5RH
KT5RHW
KT6RH
KT6RHW
KT7RH

$ 146
150
150
135
135
450
450
450

Fixed, Plug-In
Fixed, Plug-In
Draw-out
Fixed, Plug-In
Draw-0ut
Fixed, Plug-In
Draw-out
Fixed, Plug-In

Variable depth handle operators
Frame

NEMA rating

Mechanism
catalog number

List
Price

Shaft catalog number

List
Price

1,3R,12

—

—

—

—

4, 4X

KT3VD-M

$ 72

T1—T3

Ts3

OHB65J6

T4-T5

T6

OHB125J10

T7

OXP6X430 (16.9”) 2

$ 28

1

—

—

KT3VD-S (11.8”)

35

1,3R,12

—

—

OXP10X148 (5.8") 2

24

4,4X

KTS3VD-M

72

OXP10X225 (8.9") 1

26

—
1

—
—

—
—

OXP10X500 (19.7") 1
KT3VD-S (20")

32
35

1,3R,12

—

—

OXP10X148 (5.8") 1

24

4,4X

KT5VD-M

65

OXP10X225 (8.9") 1

26

—
—
1

—
—
—

—
—
—

OXP10X500 (19.7") 1
—
KT5VD-S (19.7")

32
—
36

1,3R,12

—

—

OXP10X148 (5.8") 1

24

4,4X
—
1

KT6VD-M
—
—

370
—
—

OXP10X225 (8.9") 1
OXP10X500 (19.7") 1
KT5VD-S (19.7)

26
32
36

1,3R,12

—

—

OXP10X148 (5.8") 1

24

—
—
1

KT7VD-M
—
—

370
—
—

OXP10X225 (8.9") 1
OXP10X500 (19.7") 1
KT7VD-S (19.7")

26
32
130

Handle catalog
number

OHB65J6 1
OHY65J6 1
OHB80L6 1
OHY80L6 1
KT3VD-H
OHB95J10 1
OHY95J10 1
OHB95L10 1
OHY95L10 1
—
KTS3VD-H
OHB95J10 1
OHY95J10
OHB95L10 1
OHY95L10 1
—
—
KT5VD-H
OHB125J10 1
OHY125J10 1
OHB125L10 1
—
KT6VD-H
OHB175J10 1
OHY175J10 1
OHB175L10 1
—
KT7VD-H

List
Price

$ 80
130
87
80
120
—
87
80
120
—
—
87
90
130
—
210
100
140
—
231

1 Discount schedule SH.
2 Discount schedule H6.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Discount schedule SAT — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 — T4-T5 Accessories

16.45
1SXU000023C0202

16

Accessories
Mechanical, T1 - T7

ax s
Tm CB
C
M

Plug-in kits 1
Frame

Catalog number
Adapter moving part    

List
Price

Catalog number
fixed part     

T2 - 3 pole with front terminals
KT2PMK
$ 171
KT2PFF
T3 - 3 pole with front terminals
KT3PMK
190
KT3PFF
     T2-T3 Fixed parts accept the same cable and rear terminal kits as the circuit breakers
Ts3 3 pole with front terminals
KTS3PFF
KTS3PMK
250
Ts3 3 pole with rear terminals
KTS3PFR
T4 3 pole with extended front terminal
KT4PFEF
T4 3 pole with rear horizontal terminals
KT4PMK
250
KT4PFHR
T4 3 pole with rear vertical terminals
KT4PFVR
400A
T5 400A 3 pole with extended front terminal
T5 400A 3 pole with rear horizontal terminal
T5 400A 3 pole with rear vertical terminal    

KT2PFF + KT2PMK (on back of breaker) +
breaker

600A
T5 600A 3 pole with extended front terminal
T5 600A 3 pole with rear horizontal terminal
T5 600A 3 pole with rear vertical terminal    

KT5PMK

350

KT5PFEF
KT5PFHR
KT5PFVR

KT56PMK

501

KT56PFEF
KT56PFHR
KT56PFVR

List
Price

$ 238
264
305
710
766
766
810
866
866
1,158
1,238
1,238

Plug connectors, T1-T3
Required when adding accessories to plug-in breakers
Plug Connector

Catalog
number

Shunt trip or UVR
1 form C plus 1 BA
3 form C plus 1 BA

KT3PC-3
KT3PC-6
KT3PC-12

List
price

$ 18
21
24

Adaptors, T4-T6 2

Required when adding accessories to plug-in or drawout breakers
Catalog
number

Adaptors

KT4PFVR

1 form C plus 1 BA
Shunt trip/UVR
Stored energy operator
Stored energy operator plus shunt trip/UVR
3 form C plus 1BA

KT5ADP-6
KT5ADP-6
KT5ADP-10
KT5ADP-10
KT5ADP-12

List
price

$ 24
24
30
30
35

KT4PMK (on back of
breaker)

16

1 Plug connectors (T2-T3), Adaptors (T4-T5), required when adding accessories to plug-in breakers.
2 SAT5 Discount schedule.

16.46	
1SXU000023C0202	

Discount schedule SAT — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 — T4-T5 Accessories

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Accessories
T1 - T7

T
M ma
CC x
Bs

Draw-out kits 1
Catalog number
Adaptor moving part

Item

Ts3 3 pole with front terminals
Ts3 3 pole with rear terminals
T4 3 pole with extended front terminal
T4 3 pole with rear horizontal terminals
T4 3 pole with rear vertical terminals

KTS3WMK

400A
T5 3 pole with extended front terminal
T5 3 pole with rear horizontal terminal
T5 3 pole with rear vertical terminal     

KT5WFVR

KT4WMK (on back of
breaker)

600A
T5 3 pole with extended front terminal
T5 3 pole with rear horizontal terminal
T5 3 pole with rear vertical terminal    
T6 3 pole with extended front terminal
T6 3 pole with rear horizontal terminal
T6 3 pole with rear vertical terminal     
T7 3 pole with horizontal/vertical terminals

List
Price

Catalog Number
Fixed part

List
Price

$ 290

KTS3WFF 3
KTS3WFR 3
KT4WFEF
KT4WFHR
KT4WFVR

$ 790

KT5WFEF
KT5WFHR
KT5WFVR

931
1,154
1,154

KT56WFEF
KT56WFHR
KT56WFVR
KT6WFEF 3
KT6WFHR 3
KT6WFVR
KT7WFHR 2

1,331
1,650
1,650
1,844
1,844
2,144
2,567

KT4WMK

290

KT5WMK

407

KT56WMK

582

KT6WMK

670

KT7XWMK

755

816
1,021
1,021

Adaptors — T4-T6 4

Required when adding accessories to plug-in or drawout breakers
Catalog
number

Adaptors

1 form C plus 1 BA
Shunt trip/UVR
Stored energy operator
Stored energy operator plus shunt trip/UVR
3 form C plus 1BA

KT5ADP-6
KT5ADP-6
KT5ADP-10
KT5ADP-10
KT5ADP-12

List
price

$ 24
24
30
30
35

Sliding contact blocks — T7-Draw-out
Moving Part
Breaker

Item

Left Block
Spring charging motor
Spring charged contact
Ready to close contact
Early auxiliary contact
Contact for trip coil release trip
Trip rest
Center Block
PR331
PR332
Right Block
Auxiliary contacts
Shunt trip
Closing Coil
Undervoltage release

List
Price

Fixed Part
Cradle

List
Price

KT7XSCMP-L

$ 160

KT7XSCMP-C

160

KT7XSCFP-C

310

KT7XSCMP-R

160

KT7XSCFP-R

310

KT7SCFP-L

$ 185

16

If at least one of the accessories in table is installed on the breaker - respective pair of contact blocks must be installed on the
fixed part (cradle) and the moving part. (breaker)

Position key lock — T7 - T7M-X1
Item

Key #20005
Different key

Catalog
number

KT7XPL2
KT7XPL1

List
Price

$ 202

Locks drawout breaker in racked-in / test isolation / racked-out position.

Position key lock accessory — T7 - T7M-X1
Item

Key lock accessory

Catalog
number

List
Price

KT7XPLA

$ 35

Accessory added to position key lock allows breaker to be locked in racked-out position only.

1	 Adaptors (T4-T6), Sliding contact blocks (T7) required when adding accessories to draw-out breakers.
2 Comes standard with horizontal terminals field convertible to vertical
3 IEC
4 SAT5 Discount schedule.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Discount schedule SAT — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 — T4-T5 Accessories

16.47
1SXU000023C0202

Accessories
T1 - T7

ax s
Tm CB
C
M

DIN rail adapters
Item

T1/T2 (mounts on 35 mm DIN rail 15mm high)   
T3 (mounts on 35mm DIN rail 15mm high)
Ts3 (mounts on 75 mm DIN rail)

Catalog Number

KT2DIN
KT3DIN
KTS3DIN

List Price

$ 33
41
51

Mechanical interlocks
T1-T3
Sliding bar interlock-front mounted (2 Breakers)
Sliding bar interlock-front mounted (3 Breakers)
T3
Rear Interlock-horizontal
Rear Interlock-vertical

Catalog Number

$ 625
844

KT3MI-H
KT3MI-V

896
985

KTS3MI-H
KTS3MI-V

798
798

KT5MIR-HB
KT5MIR-VB

490
588

TS3

KT3MIF2

Horizontal
Vertical
T4-T5 1
Interlock frame
Mechanical Interlock frame-horizontal
Mechanical Interlock frame-vertical
Plate type
A    T4 (F-P-W)     T4 (F-P-W)          
B    T4 (F-P-W)     T5 400 (F-P-W) OR T5 600 (F)
C    T4 (F-P-W)     T5 600 (P-W)
D    T5 (F-P-W)     T5 400 (F-P-W) OR 630 (F)     
E    T4 (F-P-W)     T5 600 (P-W)
F    T4 (F-P-W)     T5 600 (P-W)
T6
Horizontal
Vertical
T7 2
Cable T7-X1
Mech. interlock plate-fixed
Mech. interlock plate-draw-out

List Price

KT3MIF2
KT3MIF3

KT5MIR-PA
KT5MIR-PB
KT5MIR-PC
KT5MIR-PD
KT5MIR-PE
KT5MIR-PF

210

KT6MI-H
KT6MI-V

620

KT7XMLC
KT7XMLPW
KT7XMLPF

270
670
670

16

1 T4-T5 Complete assembly consists of one interlock frame and one plate.
2 To interlock two circuit breakers, you have to order a cable kit and two plates.

16.48	
1SXU000023C0202	

Discount schedule SAT — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 — T4-T5 Accessories

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Enclosures
Type 1 & 3R/12

T
M ma
CC x
Bs

T3E-1

T4E-3R12 3

Enclosures (Price does not include circuit breaker; order as a separate item.) 4
NEMA  
designation

Breaker  
type

Enclosure maximum rating
AL cables
CU cables

Approximate dimensions1
H x W x D (inches)

  
  
Type 1 1
  
  

T1
T2
T3
T4
T5

100A
100A
175A
200A
325A

100A
100A
225A
250A
400A

15 x 8.5 x 4
15 x 8.5 x 4
20 x 11 x 4
26 x 15 x 6.25
26 x 15 x 6.25

  
  
Type 3R/123
  
  

T1
T2  
T3
T4
T5

100A
100A
175A
200A
325A

100A
100A
225A
250A
400A

15 x 8.5 x 7
15 x 8.5 x 7
20 x 11 x 7
26 x 15 x 9
26 x 15 x 9

Catalog
number

T1E-1
T2E-1
T3E-1
T4E-1 2
T5E-1 2
T1E-3R12
T2E-3R12
T3E-3R12
T4E-3R12
T5E-3R12

List
price

$ 267
267
315
407
435
407
407
527
625
767

Neutral kits
Breaker
type

Neutral cable capacity
and wire range

Neutral kit
catalog number

List
price

T1 – T2
  

Neutral #14-1/0
Bonding Lug #14-1/0

T2NK125

$ 140

T3
  

Neutral #6-250 kcmil
Bonding Lug #14-1/0

T3NK225

150

T4
  

Neutral #6-250 kcmil
Bonding Lug #14-1/0 kcmil

T4NK250

155

T5
  

Neutral (2) #6-250 kcmil
Bonding Lug #14-1/0 kcmil

T5NK400

295

NOTE:  The list price adder for factory installation of an enclosed circuit breaker is 50% of the enclosure list price.

Description
Type 1

16

•	General purpose indoor enclosure intended for use in normal
environments to provide a degree of protection against contact with
enclosed equipment.
•	Sheet steel, surface mount.
•	Breaker is front-operable and can be padlocked via a separately
ordered padlock device.
•	Available through 400A, 600VAC
•	(SUSE) suitable for use as service equipment.

Type 3R/12

•	Type 3R is intended for outdoor use providing protection against
rain, sleet or snow.
•	Type 12 is for use in indoor atmospheres to provide a degree of
protection against circulating dust, lint, sawdust, falling dirt and
dripping non-corrosive liquids.
•	Surface-mounted, sheet steel enclosure.
•	Breaker can be operated via separately ordered handle
mechanism; door is interlocked with mechanism.
•	Available through 400A, 600VAC.
•	(SUSE) suitable for use as service equipment.

1	 Padlocking provision must be ordered separately.
2	 Must order KT5FLD (padlock device) separately.
3	 Variable depth rotary handle must be ordered separately.
4	 Consult ABB for breakers installed in enclosures.

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Discount schedule SET

16.49
1SXU000023C0202

Enclosures
Approximate dimensions, T1 – T5
NEMA 1, 3R & 12

ax s
Tm CB
C
M
NEMA 1

JJ

JH

JJ

SHOWN WITH BREAKER, PADLOCK DEVICE AND NEUTRAL KIT ORDERED SEPARATELY

F MTG HOLES
4 PLACES

Cat. #

B

C
G

E

FRONT VIEW

SIDE VIEW

SECTION

B

C

D

E

T1E-1 15.00
381

A

8.50
216

4.00
102

13.00
330

6.50
165

0.281 4.93 1, 1-1/4 3/4, 1
7
125 25, 32 19, 25

F

G

H

J

T2E-1 15.00
381

8.50
216

4.00
102

13.00
330

6.50
165

0.281 4.93 1, 1-1/4 3/4, 1
7
125 25, 32 19, 25

11.00
T3E-1 20.00
508
279

4.00
102

18.00
457

9.00
229

0.281 4.93 1, 1-1/4 3/4, 1
7
125 25, 32 19, 25

15.00
T4E-1 26.00
660
381

6.25
159

24.00 13.00 0.281 7.01 1, 1-1/4 3/4, 1
610
330
7
178 25, 32 19, 25

15.00
T5E-1 26.00
660
381

6.25
159

24.00 13.00 0.281 7.01 1, 1-1/4 3/4, 1
610
330
7
178 25, 32 19, 25

NEMA 3R, 12

SHOWN WITH BREAKER, VARI-DEPTH MECHANISM, HANDLE, SHAFT AND NEUTRAL KIT, ORDERED SEPARATELY

F MTG HOLES
4 PLACES

16
B

C

D

E

F

G

T1E-3R12 15.00
381

Cat. #

A

8.50
216

7.00
178

15.75
400

5.00
127

0.313
8

9.06
230

T2E-3R12 15.00
381

8.50
216

7.00
178

15.75
400

5.00
127

0.313
8

9.06
230

11.00
T3E-3R12 20.00
508
279

7.00
178

20.75
527

7.50
191

0.313
8

9.06
230

15.00
T4E-3R12 26.00
660
381

9.00
229

26.75 11.50 0.313 11.06
679
292
8
281

15.00
T5E-3R12 26.00
660
381

9.00
229

26.75 11.50 0.313 11.06
679
292
8
281

C
B
FRONT VIEW

16.50	
1SXU000023C0202	

G
SIDE VIEW

E
SECTION

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Approximate dimensions
T1 & T2

T
M ma
CC x
Bs

T1 — 3 pole

T1 — Single pole

16
83
78

90
30

70

30

¯9.38

Y

17

X

X

45

130

181

65

53.25

76.2

106.5

T2 — 2 & 3 pole

Y
>3

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

103

<2

16.51
1SXU000023C0202

ax s
Tm CB
C
M

Approximate dimensions
T3

T3 — 2 & 3 pole

Door cut-out for Tmax without faceplate

16

16.52	
1SXU000023C0202	

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Approximate dimensions
Ts3

T
M ma
CC x
Bs

16

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

16.53
1SXU000023C0202

ax s
Tm CB
C
M

Approximate dimensions
T4

Fixed circuit breaker

Caption
1

Overall dimensions with
cabled accessories mounted
(SOR-C, UVR-C,
RC221-222)

2

Overall dimensions with
cabled auxiliary contacts
mounted
(only 3Q 1SY)

Flange for
compartment door

16

Drilling templates of the compartment door

3-4 POLES

3-4 POLES

With flange

Without flange

Drilling templates for support sheet
For front terminals

3 POLES

16.54	
1SXU000023C0202	

For rear terminals

4 POLES

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Approximate dimensions
T5

T
M ma
CC x
Bs

Fixed circuit breaker
Fixing on sheet
Caption
1

Overall dimensions with
cabled accessories mounted
(SOR-C, UVR-C,
RC221-222)

2

Overall dimensions with
cabled auxiliary contacts
mounted
(only 3Q 1SY)

Flange for
compartment door

Drilling templates of the compartment door

With flange (3-4 POLES)

Without flange (3-4 POLES)

16

Drilling templates for support sheet
For front terminals

3 POLES

For rear terminals

4 POLES
3 POLES

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

4 POLES

16.55
1SXU000023C0202

ax s
Tm CB
C
M

Approximate dimensions
T6

16

16.56	
1SXU000023C0202	

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Approximate dimensions
T7

T
M ma
CC x
Bs

16

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

16.57
1SXU000023C0202

ax s
Tm CB
C
M

Approximate dimensions
Variable depth mechanism with OHB handle
T1 - T3

16

16.58	
1SXU000023C0202	

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Approximate dimensions
Variable depth mechanism with OHB handle
T4 - T5

T
M ma
CC x
Bs

16

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

16.59
1SXU000023C0202

ax s
Tm CB
C
M

Approximate dimensions
Variable depth mechanism
T6

16

16.60	
1SXU000023C0202	

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Approximate dimensions
Variable depth mechanism
T7

T
M ma
CC x
Bs

16

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

16.61
1SXU000023C0202

ax s
Tm CB
C
M

Notes

16

16.62	
1SXU000023C0202	

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Create Date                     : 2009:02:02 10:07:31-06:00
Metadata Date                   : 2009:02:10 15:42:56-06:00
Modify Date                     : 2009:02:10 15:42:56-06:00
Creator Tool                    : Adobe InDesign CS3 (5.0.4)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 10456 bytes, use -b option to extract)
Instance ID                     : uuid:a066d27c-f39c-40d8-bd7f-5e2ed5788d5d
Document ID                     : adobe:docid:indd:9bb05ac2-8bb3-11dd-8fa4-fa56efc83f89
Rendition Class                 : proof:pdf
Derived From Instance ID        : 9090192a-85a0-11dd-b9e0-fd13a4fdaa04
Derived From Document ID        : adobe:docid:indd:d1db77fc-84cf-11dd-b9e0-fd13a4fdaa04
Derived From Version ID         : 1
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 72.00, 72.00, 280.00, 72.00, 72.00, 304.57, 304.57, 304.57, 300.00, 72.00, 280.00, 280.00, 300.00, 300.00, 300.00, 72.00, 304.47, 72.00, 304.57, 72.00, 72.00, 300.00, 72.00, 72.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 260.00, 72.00, 72.00, 72.00, 72.00, 72.00, 300.00, 72.00, 72.00, 72.00, 300.00
Manifest Placed Y Resolution    : 72.00, 72.00, 280.00, 72.00, 72.00, 304.57, 304.57, 304.57, 300.00, 72.00, 280.00, 280.00, 300.00, 300.00, 300.00, 72.00, 304.47, 72.00, 304.57, 72.00, 72.00, 300.00, 72.00, 72.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 260.00, 72.00, 72.00, 72.00, 72.00, 72.00, 300.00, 72.00, 72.00, 72.00, 300.00
Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches
Manifest Reference Instance ID  : uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:7683d199-c1cf-11db-b318-000a95b46cce, uuid:382d2cf2-54e7-11d9-a91a-d1e977fe5aeb, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:C3D06F0B1C1C11DDB43F9F82DD8687F5, uuid:ce7d0eb3-e284-11d6-9741-8cccbcad6335, uuid:42e63f2a-e283-11d6-9741-8cccbcad6335, uuid:e8d0e9bf-e1ef-11d6-a7f3-d78ee86306f3, uuid:216EEF1842CD11DD98A7FCC0FD192A5D, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:9d19a081-54ed-11d9-a91a-d1e977fe5aeb, uuid:5dfb6034-54ed-11d9-a91a-d1e977fe5aeb, uuid:40DA185AF1DE11DC8820B2E94100FA4F, uuid:7797B77DF5B611DC96CAB9BAD14BB9D2, uuid:584C3362A74E11DDB22289F0EA8A0147, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:75c8b092-e350-11d6-ad2a-dcc7ce849814, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:e8d0e9bf-e1ef-11d6-a7f3-d78ee86306f3, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:5125C40DF1D311DC8820B2E94100FA4F, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:2162001EF1D611DC8820B2E94100FA4F, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:C3D06F0B1C1C11DDB43F9F82DD8687F5, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:C2325E22F1D811DC8820B2E94100FA4F, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:26fd621a-54ea-11d9-a91a-d1e977fe5aeb, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:40DA185AF1DE11DC8820B2E94100FA4F, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:b176cdfd-c284-11db-b318-000a95b46cce, uuid:7797B77DF5B611DC96CAB9BAD14BB9D2
Manifest Reference Document ID  : uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608BC26311DBA751A3570BA5E701, adobe:docid:photoshop:382d2cee-54e7-11d9-a91a-d1e977fe5aeb, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:85F664B0182F11DDB43F9F82DD8687F5, adobe:docid:photoshop:42e63f2b-e283-11d6-9741-8cccbcad6335, adobe:docid:photoshop:e8d0e9c0-e1ef-11d6-a7f3-d78ee86306f3, adobe:docid:photoshop:190ae302-e1bd-11d6-a7f3-d78ee86306f3, uuid:F496672542CC11DD98A7FCC0FD192A5D, uuid:27A1608EC26311DBA751A3570BA5E701, adobe:docid:photoshop:443ff929-54ec-11d9-a91a-d1e977fe5aeb, adobe:docid:photoshop:443ff920-54ec-11d9-a91a-d1e977fe5aeb, uuid:40DA1854F1DE11DC8820B2E94100FA4F, uuid:7186A376F5B611DC96CAB9BAD14BB9D2, uuid:7ACBB25DA5D711DDB22289F0EA8A0147, uuid:27A1608EC26311DBA751A3570BA5E701, adobe:docid:photoshop:75c8b08c-e350-11d6-ad2a-dcc7ce849814, uuid:27A1608EC26311DBA751A3570BA5E701, adobe:docid:photoshop:190ae302-e1bd-11d6-a7f3-d78ee86306f3, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:5125C40CF1D311DC8820B2E94100FA4F, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:0EF05F57F1D611DC8820B2E94100FA4F, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:85F664B0182F11DDB43F9F82DD8687F5, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:C2325E1CF1D811DC8820B2E94100FA4F, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, adobe:docid:photoshop:67230c68-54e6-11d9-a91a-d1e977fe5aeb, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:40DA1854F1DE11DC8820B2E94100FA4F, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:27A1608EC26311DBA751A3570BA5E701, uuid:7186A376F5B611DC96CAB9BAD14BB9D2
Format                          : application/pdf
Producer                        : Adobe PDF Library 8.0
Trapped                         : False
Page Count                      : 62
Creator                         : Adobe InDesign CS3 (5.0.4)
EXIF Metadata provided by EXIF.tools

Navigation menu