103066 Catalog
2014-06-03
: Pdf 103066-Catalog 103066-Catalog 785901 Batch4 unilog
Open the PDF directly: View PDF .
Page Count: 200 [warning: Documents this large are best viewed by clicking the View PDF Link!]
- Table of Contents
- Section 1 - Load Centers
- Section 2 - Safety Switches
- Section 3 - Molded Case Circuit Breakers and Enclosures
- Section 4 - Panelboards
- Section 5 - Switchboards
- Section 6 - Transformers
- Section 7 - International Load Centers
- Section 8 - International Safety Switches
- Section 9 - International Circuit Breakers
- Section 10 - International Panelboards
- Section 11 - Obsolescent and Obsolete Circuit Breakers
- Section 12 - Obsolete Motor Control Centers
- Section 13 - Obsolescent Panelboards
- Section 14 - Busway
- Section 15 - Limit Switches
- Section 16 - Medical Products
- Section 17 - NEMA Contactors and Starters
Supplemental and Obsolescence
Digest 176
Process & Machines
Management
Power
Management
Building
Management
Security
Management
IT/Server Room
Management
Global Specialist in Energy Management
Document Number 0100PL1202
© 2012 Schneider Electric. All Rights Reserved. • 998-5626_US_C
Supplemental and Obsolescence Digest 176
2012
2012
Have questions? Need technical
support or on-site service?
Now there’s one toll-free number to get all the
information you need.
1-888-778-2733
Customer Care Center
The Customer Care Center (CCC) is a single point of contact where
qualied personnel answer your customer service and technical
support questions.
Serving all Schneider Electric authorized distributors and customers
anywhere in the United States.
Schneider Electric Services
Schneider Electric Services provides you with power, automation and
control, and energy management services to support the lifecycle of your
system, process or installation. Our solutions help you get the most out of
your investment and keep your facility at peak operational performance.
Any brand. Any industry. Any time.
Schneider Electric USA, Inc.
1415 S. Roselle Road
Palatine, IL 60067
Te l: 847-397-2600
Fax: 847-925-7500
www.schneider-electric.us
This document has been
printed on recycled paper
www.schneider-electric.us
The only good watt
is a negawatt.
©2011 Schneider Electric. All Rights Reserved. Schneider Electric, EcoStruxure, Active Energy Management Architecture from Power Plant to
Plug, and Efficient Enterprise are trademarks owned by Schneider Electric Industries SAS or its affiliated companies. 35 rue Joseph Monier,
CS 30323, 95506 Rueil almaison Cedex (France) • 998-3259_US
*Source: World Energy Outlook 2009, IEA/OECD
What’s a negawatt? The one you didn’t use.
Energy saved is money saved.
Yes, the smart grid is coming and we are actively implementing intelligence and
innovations to help make it a reality. But we need a solution that will save energy and
drive efficiency today as we are building the smarter grids of tomorrow.
Introducing EcoStruxure: Active Energy Management Architecture from
Power Plant to Plug™.
Right now, EcoStruxure™ solutions from Schneider Electric™ can reduce your energy
use by up to 30 while cutting capital and operational costs. End-use efficiency
is where our focus needs to be! The percentage of revenue spent on energy by
companies could reach 30% by 2020. And there is an urgent need to reduce CO2
emissions, especially as energy demand escalates. Energy management is the key
– the fastest and most effective solution to curb greenhouse gas emissions while
improving business performance. In fact, by 2030, energy efficiency and behavior
change will offset more CO2 than all the new wind, solar, and other alternative energy
generation methods combined.*
EcoStruxure solutions cut energy costs today.
As energy prices continue to climb, every unit
of energy you save matters. One unit saved at
the point of use means three units of primary
energy not consumed. Today, only EcoStruxure
Active Energy Management architecture can
deliver up to 30% energy savings across your
buildings, industrial plants, and data centers.
You deserve an Efficient Enterprise™!
30% 30%30%
Visit www.SEreply.com Key Code b653v
Get smarter about energy
Download this White Paper, “Growing a Green
Corporation,” a $199 value, for FREE.
Mining
Due to intrinsic inefficiencies, 33 units of energy consumed at the point of use
require 100 units of primary energy.
100 energy units 35 energy units 33 energy units
Generation Transmission Point of use
i - 1
© 2012 Schneider Electric All Rights Reserved
www.schneider-electric.us
Table of Contents
01 LOAD CENTERS................................................................................... 1-1
Fusible Pullouts .................................................................................................................. 1-2
Circuit Breaker Covers ....................................................................................................... 1-3
02 SAFETY SWITCHES............................................................................. 2-1
General Duty Safety Switches............................................................................................ 2- 4
Accessories .................................................................................................................. 2-4
Heavy Duty Safety Switches .............................................................................................. 2- 3
Accessories .................................................................................................................. 2-3
Key Interlock Systems ................................................................................................. 2-4
Sample Applications .................................................................................................... 2-4
03 MOLDED CASE CIRCUIT BREAKERS AND ENCLOSURES ............. 3-1
PowerPact™ Circuit Breakers ............................................................................................ 3-3
PowerPact™ H- and J-Frame Circuit Breakers ........................................................... 3-3
PowerPact™ L-Frame Circuit Breakers ....................................................................... 3-4
PowerPact™ D-Frame Circuit Breakers ...................................................................... 3-5
PowerPact™ Automatic Switches ....................................................................................... 3-6
Molded Case Circuit Breakers............................................................................................. 3-7
F-Frame Thermal-Magnetic Circuit Breakers ............................................................... 3-7
K- and Q4-Frame Thermal-Magnetic Circuit Breakers ................................................ 3-9
L-Frame Thermal-Magnetic Circuit Breakers ............................................................. 3-11
L-Frame Micrologic™ Series B Trip Circuit Breakers ................................................ 3-13
Molded Case Circuit Breakers........................................................................................... 3-15
Mag-Gard™ Motor Circuit Protector .......................................................................... 3-15
Molded Case Circuit Breakers........................................................................................... 3-16
GJ-Frame MCP Selection .......................................................................................... 3-16
Special Construction Circuit Breakers............................................................................... 3-17
Special Terminal Connectors and Lugs ..................................................................... 3-17
Special Calibration, Rear-Connected Studs, Visi-Blade,
Moisture/Fungus Treatment, and Short LA/LH Handle .............................................. 3-18
Special Magnetic or Thermal Calibration ................................................................... 3-18
Rear-Connected Studs .............................................................................................. 3-18
Visi-BladeTM Circuit Breakers .................................................................................... 3-18
Moisture and Fungus Resistant Treatment for Circuit Breakers ................................ 3-18
Short Handle for LA/LH Circuit Breakers (No Additional Charge) .............................. 3-18
P-Frame Replacement Handles, Key Interlock Adapter Plate and
Exchange Program .................................................................................................... 3-19
Special Terminations ................................................................................................. 3-20
Grounded BØ Systems .............................................................................................. 3-21
Circuit Breakers for Grounded B-Phase (BØ) (Corner-Grounded Delta) Systems
(No Additional Charge) .............................................................................................. 3-21
UL Marine Listed Circuit Breakers ............................................................................. 3-22
UL Naval Listed Circuit Breakers ............................................................................... 3-22
Circuit Breaker Accessories .............................................................................................. 3-23
PowerPact™ Circuit Breakers Electrical Accessories ................................................ 3-23
Factory-Installed Accessories .................................................................................... 3-24
Factory-Installed Electrical Accessories .................................................................... 3-24
Field-Installable Accessories ..................................................................................... 3-25
Field-Installable Electrical Accessories ...................................................................... 3-25
Electrical Operators, Handle Accessories, Cylinder Locks,
and Walking Beam Mechanical Interlocks ................................................................. 3-26
Locks, Installation Accessories, and Rear Connections ............................................ 3-27
Mechanical Lug Information ....................................................................................... 3-28
Compression Lug and Power Distribution Connectors .............................................. 3-29
PowerPact™ Circuit Breakers Miscellaneous Accessories ....................................... 3-30
Electronic Products ........................................................................................................... 3-31
Neutral Current Transformers and
Micrologic™ Series B Trip Unit Accessories .............................................................. 3-31
Restraint Interface Module ......................................................................................... 3-32
Circuit Breaker Dimensions............................................................................................... 3-33
Enclosures......................................................................................................................... 3-34
Industrial Circuit Breaker Enclosures ......................................................................... 3-34
Enclosures......................................................................................................................... 3-35
Enclosed Switches and Enclosure Dimensions ......................................................... 3-35
Accessories ................................................................................................................ 3-36
Key Interlock Systems—Factory Installed Only ......................................................... 3-37
Special Applications ................................................................................................... 3-38
04 PANELBOARDS ................................................................................... 4-1
Panelboards ........................................................................................................................ 4-2
General Information ..................................................................................................... 4-2
General Instructions ..................................................................................................... 4-2
Pricing Instructions ....................................................................................................... 4-2
Metric Conversion ........................................................................................................ 4-2
I-Line™ Panelboards Factory Assembled Pricing ....................................................... 4-2
Special Features ................................................................................................................. 4-3
Mains and Branches .................................................................................................... 4-3
i - 2
© 2012 Schneider Electric All Rights Reserved
www.schneider-electric.us
Mains ........................................................................................................................... 4-3
Branches ...................................................................................................................... 4-3
Cabinets .......................................................................................................................4-4
Increased Enclosure Depth .......................................................................................... 4-4
Increased Side Gutters
(Type 1 Enclosures Only) ............................................................................................ 4-4
Extended Top and Bottom End Gutters ....................................................................... 4-4
Drip Hoods a ................................................................................................................ 4-4
Special Finishes ........................................................................................................... 4-4
Free-standing Enclosures (welded base channels) c .................................................. 4-4
Special Trims ............................................................................................................... 4-4
Cabinets .......................................................................................................................4-5
Padlock Hasp ............................................................................................................... 4-5
Special Locks ............................................................................................................... 4-5
Multi-Section Panels .................................................................................................... 4-5
Cabinets .......................................................................................................................4-6
Panel Skirt for Standard Width Panelboards a ............................................................ 4-6
Wireway a .................................................................................................................... 4-6
Cabinets .......................................................................................................................4-7
Panels to Fit Existing Enclosures ................................................................................. 4-7
Space Heater ............................................................................................................... 4-7
Cabinets .......................................................................................................................4-8
Special Enclosures a ................................................................................................... 4-8
NQ Main Lug and Main Circuit Breaker Interiors with SPD—240 Vac, 48 Vdc .................. 4-9
Ready-to-Install (RTI) Merchandise .................................................................................. 4-10
Miscellaneous Panelboard Accessories .................................................................... 4-10
Copper Equipment Ground Bars ................................................................................ 4-10
Field Installable I-Line™ Door Kits ............................................................................. 4-10
Type 1 Door-in-Door (Hinged) Trim Fronts ................................................................ 4-10
Replacement Parts for Standard Panelboards.................................................................. 4-11
Trim Clamps and Screws ........................................................................................... 4-11
Locks and Keys .......................................................................................................... 4-12
CTC Cabinets....................................................................................................................4-13
Replacement Parts for Standard Panelboards.................................................................. 4-14
Retrofit Existing Enclosure Data Sheet ...................................................................... 4-14
Data Sheet for Panelboards to Retrofit Existing Enclosures ...................................... 4-14
05 SWITCHBOARDS ..................................................................................5-1
Power-Style™ CMM Switchboards ......................................................................................5-2, 5-3
Replacement Parts ...................................................................................................... 5-2
Meter Sockets, Covers, Hardware Kits ........................................................................ 5-2
Tenant Main Disconnects ............................................................................................ 5-3
Class T Fusible Pullouts, CMM Pullout Heads ............................................................ 5-3
Speed-D™ Switchboards..................................................................................................... 5-4
Service Selection ......................................................................................................... 5-4
06 TRANSFORMERS .................................................................................6-1
General Purpose Dry Type 600 Volts and Below................................................................ 6-2
Energy Efficient ............................................................................................................ 6-2
K-Rated ........................................................................................................................6-3
EE NL and NLP Series Transformers .......................................................................... 6-3
Drive Isolation Transformers .......................................................................................... 6-4
Open Core and Coil ..................................................................................................... 6-5
Open Core and Coil Transformers Designed for General Applications
for 600 V and Below ..................................................................................................... 6-5
Industrial Control ................................................................................................................. 6-6
Type EO ....................................................................................................................... 6-6
Type T .......................................................................................................................... 6-7
Type T and MultiTap™ Transformers .......................................................................... 6-7
Selection Guide ............................................................................................................ 6-7
Instrument 600 Volt Class .................................................................................................. 6-8
Voltage Transformers .................................................................................................. 6-8
Current Transformers ................................................................................................... 6-8
Current Transformers: Torroidal .................................................................................. 6-9
Torroidal Current Transformers ..........................................................................6-9, 6-10
Current Transformers: Torroidal, Shorting Terminal Blocks ...................................... 6-10
Shorting Terminal Blocks ........................................................................................... 6-10
Current Transformers: Multi-Ratio, Rectangular, Split-Core ...................................... 6-11
Multi-Ratio Current Transformers .............................................................................. 6-11
Rectangular Window Current Transformers .............................................................. 6-11
Split-Core Current Transformers ................................................................................ 6-11
Current Transformers: Bushing, Auxiliary .................................................................. 6-12
Bushing Current Transformers 50–400 Hz ................................................................ 6-12
Auxiliary Current Transformers .................................................................................. 6-12
07 INTERNATIONAL LOAD CENTERS .....................................................7-1
International Miniature Circuit Breakers ............................................................................. 7-2
QO™ Plug-On and Bolt-On Circuit Breakers and Switches ........................................ 7-2
General Description ..................................................................................................... 7-2
Characteristics ............................................................................................................. 7-2
Accessories .................................................................................................................. 7-2
Plug-On QOXD and Bolt-On QOBXD .......................................................................... 7-3
Load Centers....................................................................................................................... 7-4
IEC Certified QO™ Load Centers, Type 1 (Indoor) ..................................................... 7-4
08 INTERNATIONAL SAFETY SWITCHES ...............................................8-1
i - 3
© 2012 Schneider Electric All Rights Reserved
www.schneider-electric.us
General Duty Safety Switches............................................................................................. 8-2
International ................................................................................................................. 8-2
CSA Certified General Duty—Fusible 240 Vac ............................................................ 8-2
Heavy Duty Safety Switches ............................................................................................... 8-3
International ................................................................................................................. 8-3
CSA Certified Heavy Duty—Fusible 240 Vac .............................................................. 8-3
CSA Certified Heavy Duty—Fusible 600 Vac .............................................................. 8-3
CSA Certified Heavy Duty—Non-Fusible 600 Vac ...................................................... 8-4
CSA Certified Heavy Duty—Special Applications ........................................................ 8-4
Double-Throw Safety Switches ........................................................................................... 8-5
International ................................................................................................................. 8-5
CSA Certified Double-Throw ........................................................................................ 8-5
Accessories .................................................................................................................. 8-6
CSA Certified Switch Accessories ............................................................................... 8-6
09 INTERNATIONAL CIRCUIT BREAKERS ............................................. 9-1
Thermal-Magnetic Circuit Breakers..................................................................................... 9-2
SF and SL Circuit Breakers, IEC Rated 415/240 Vac Max. ......................................... 9-2
Electronic Trip Circuit Breakers........................................................................................... 9-3
P-frame, 3P, Micrologic™ Electronic-Trip Unit, IEC Rated .......................................... 9-3
R-frame, 3P, Micrologic™ Electronic-Trip Unit, IEC Rated .......................................... 9-4
P-frame, 4P, Micrologic™ Electronic-Trip Unit, IEC Rated .......................................... 9-5
R-frame, 4P, Micrologic™ Electronic-Trip Unit, IEC Rated .......................................... 9-6
Breaking Capacities ............................................................................................................ 9-7
Circuit Breaker Dimensions................................................................................................. 9-8
10 INTERNATIONAL PANELBOARDS ................................................... 10-1
Factory Assembled Circuit Breaker Panelboard ........................................................ 10-2
11 OBSOLESCENT AND OBSOLETE CIRCUIT BREAKERS ............... 11-1
Obsolescent and Obsolete Types ..................................................................................... 11-2
Circuit Breaker Availability ......................................................................................... 11-2
Pictorial and Dimensions .................................................................................. 11-4, 11-5
Obsolescent Circuit Breakers............................................................................................ 11-6
F-Frame Thermal-Magnetic Circuit Breakers ............................................................. 11-6
K-Frame Thermal-Magnetic Circuit Breakers ............................................................ 11-7
Automatic Molded-Case Switches ............................................................................. 11-8
Automatic Molded Case Switches ............................................................................. 11-8
Mag-Gard™ Motor Circuit Protector ............................................................... 11-9, 11-10
UL Listed Marine Circuit Breakers ........................................................................... 11-11
Circuit Breakers for NQO, NQOB and NQOD Panelboards, Branch Circuit Breakers
and Mounting Assemblies for ML Panelboards ................................................................ 11-12
Rating Plugs For Obsolete Electronic Trip Circuit Breakers .................................... 11-13
EH/EHB Circuit Breakers ......................................................................................... 11-14
FJA Thermal-Magnetic Circuit Breakers .................................................................. 11-15
QE Metering Circuit Breakers .................................................................................. 11-16
KD/KG Thermal-Magnetic Circuit Breakers ............................................................. 11-17
NHL Thermal-Magnetic Molded Case Circuit Breaker ............................................. 11-18
SE Circuit Breaker with Full-Function Trip Unit ........................................................ 11-19
SE Circuit Breaker Accessories ............................................................................... 11-20
Molded Case Circuit Breakers......................................................................................... 11-21
M-Frame Thermal-Magnetic Circuit Breakers .......................................................... 11-21
Circuit Breaker Accessories ............................................................................................ 11-22
Field-Installable Accessories ................................................................................... 11-22
Field-Installable Electrical Accessories .................................................................... 11-22
Mechanical Lug Information ..................................................................................... 11-23
Electronic Products ......................................................................................................... 11-24
Micrologic™ Series 2/3/A/B Trip Unit Test Sets ...................................................... 11-24
Ground-Fault Protection .................................................................................................. 11-25
Micrologic™ Add-On Ground-Fault Module (GFM) ................................................. 11-25
Obsolescent Circuit Breakers.......................................................................................... 11-26
Masterpact™ M/MP/MC Circuit Breakers, UL 489/1066 Listed ............................... 11-26
Masterpact™ M/MP/MC Circuit Breaker Control Units ............................................ 11-27
For pricing contact your local Schneider Electric distributor. ................................... 11-27
Masterpact™ M/MP/MC Circuit Breaker Accessories ............................................. 11-28
Masterpact™ M/MP/MC Circuit Breaker Spare Parts .............................................. 11-30
12 OBSOLETE MOTOR CONTROL CENTERS...................................... 12-1
Model 4 Branch Feeder Units .................................................................................... 12-2
Model 4 Circuit Breaker Type Combination Starters
1B Wiring and 1 N.O. and 1 N.C. Auxiliary Interlock (Standard) ................................ 12-3
Model 4 Fusible Switch Combination Starter Units
1B Wiring and 1 N.O. and 1 N.C. Auxiliary Interlock (Standard) ................................ 12-4
Series 5600 General Information ............................................................................... 12-5
Telemecanique™ Series 5600 History ....................................................................... 12-5
Transition Sections From Telemecanique Series 5600 To Square D™ Brand Model 6 12-5
Series 5600 Branch Feeder and Circuit Breaker Type
Combination Starter Units .......................................................................................... 12-6
13 OBSOLESCENT PANELBOARDS ..................................................... 13-1
QMB Fusible Panelboards ................................................................................................ 13-2
Ready-to-Install (RTI)—600 Vac, 250 Vdc ................................................................. 13-2
QMB Layout Information ............................................................................................ 13-2
Main Switch Replacement Units ................................................................................ 13-3
Branch Switch Replacement ...................................................................................... 13-4
Obsolescent Branch Switch Replacement Units ........................................................ 13-5
i - 4
© 2012 Schneider Electric All Rights Reserved
www.schneider-electric.us
30–200 A Obsolescent Switch Units—Series D2 ...................................................... 13-5
Series E1 Motor Starter Replacement Units .............................................................. 13-6
Replacement Parts............................................................................................................ 13-7
Trim Clamps and Screws; Circuit I.D. Numbers; Locks ............................................. 13-7
Series Ratings ................................................................................................................... 13-8
NQOD Panelboards ................................................................................................... 13-8
NQOD Panelboards .......................................................................................................... 13-9
Pricing Procedure Examples ...................................................................................... 13-9
NQOD Merchandised Pricing Procedure ................................................................... 13-9
NQOD Merchandised Panelboards................................................................................. 13-10
NQOD 20-inch Wide Enclosures—240 Vac, 48 Vdc ....................................13-10, 13-11
NQOD 14-inch Wide Enclosures—240 Vac, 48 Vdc ............................................... 13-12
For Non-Linear Loads (200% Rated Neutral) .......................................................... 13-13
NQOD Panelboards ........................................................................................................ 13-14
Terminal Data .......................................................................................................... 13-14
14 BUSWAY..............................................................................................14-1
I-Line™ Busway ................................................................................................................ 14-2
Special Purpose Plug-In Units ................................................................................... 14-2
APD and SD Busway Plug-In Units (Not I-Line™ Busway) ....................................... 14-2
Capacitor and Transformer Units ............................................................................... 14-2
Combination Switches and Contactors (For I-Line Busway) ...................................... 14-2
Ground Indicator and Neutralizer Plugs ..................................................................... 14-2
15 LIMIT SWITCHES ................................................................................15-1
Heavy Duty, Industrial Precision and Oiltight .................................................................... 15-1
Type XA ..................................................................................................................... 15-1
Heavy Duty, Industrial Reed Contact ................................................................................ 15-2
Type C ....................................................................................................................... 15-2
16 MEDICAL PRODUCTS ........................................................................16-1
Medical Products............................................................................................................... 16-2
Isolated Power Panels ............................................................................................... 16-2
OR, ICU/CCU, and Controlled Isolation Power Panels—UL Listed ........................... 16-2
Duplex Panels ............................................................................................................ 16-3
Surgical Facility Panels .............................................................................................. 16-4
Dual Output Voltage Panels ....................................................................................... 16-5
Accessories ................................................................................................................ 16-6
17 NEMA CONTACTORS AND STARTERS............................................17-1
IEC Style Disconnect Switches ......................................................................................... 17-2
UL508 Motor Disconnect Switches ................................................................................... 17-8
Vario ........................................................................................................................... 17-8
NEMA Style Disconnect Switches..................................................................................... 17-9
Door-Mounted Operating Mechanisms ........................................................................... 17-10
Approximate Dimensions ................................................................................................ 17-11
Bracket-Mounted Disconnect Devices ............................................................................ 17-13
Flexible Cable Mechanisms ............................................................................................ 17-14
Dual Cable Operating Mechanisms for Square D™ Circuit Breakers ...................... 17-14
Disconnect Switch Accessories....................................................................................... 17-15
Reversing Drum Switches ............................................................................................... 17-17
NEMA Types 1, 3R, 4, and 13 Without Overload .................................................... 17-17
Approximate Dimensions—Class 2601 Reversing Drum Switches ......................... 17-17
Electromechanical Reduced Voltage Starters................................................................. 17-18
Reduced Voltage Starting of Squirrel Cage Motors ................................................. 17-18
Electromechanical Reduced Voltage Starters ......................................................... 17-18
Multispeed Magnetic Starters.......................................................................................... 17-24
Application Data ............................................................................................17-24, 17-25
3-Pole Polyphase, 600 Vac Maximum, 50–60 Hz ..............................17-25, 17-26, 17-27
Two-Speed Combination Starters ............................................................................ 17-26
Reversing Two-Speed Magnetic Starters ................................................................ 17-27
Two-Speed Magnetic Starters ................................................................................. 17-28
Approximate Dimensions ......................................................................................... 17-29
Disconnect Switch or Circuit Breaker Type .............................................................. 17-29
Lighting Contactors ......................................................................................................... 17-30
General Information ................................................................................................. 17-30
Well-Guard™ Pump Panel........................................................................................................ 17-31
Factory Modifications (Forms)......................................................................................... 17-32
Definite Purpose Contactors ........................................................................................... 17-35
Thermal Overload Relays—NEMA Style......................................................................... 17-36
Motor Logic Plus—Class 9065 ................................................................................. 17-36
Example ................................................................................................................... 17-36
1-1
© 2012 Schneider Electric
All Rights Reserved
1LOAD CENTERS
Table of Contents
Section 1
Load Centers
Fusible Pullouts
Class T Fusible Pullouts 1-2
Dimensions 1-2
Circuit Breaker Covers
Circuit Breaker Covers 1-3
Dimensions 1-3
1-2 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
1LOAD CENTERS
Fusible Pullouts
Refer to Catalog 1100CT0501
Class T Fusible Pullouts
•2- or 3-pole fusible pullouts
•200 A maximum 300 V Class T fuses (not included)
•1Ø3W 120/240 V
1Ø2W 240 V
•3Ø3W 240 V delta
3Ø4W 240/120 V delta
3Ø4W 208Y/120 V
•UL Listed 100 kA short circuit current rating
Dimensions
FTL2200 FTL3200
Table 1.1: Fusible Pullouts
Mains Two-pole Three-pole Main Wire Size
AWG/kcmil Fuse Pullout Only $ Price
System Rating Cat. No. $ Price Cat. No. $ Price Al or Cu
1Ø3W 120/240 V
1Ø2W 240 V
100 A FTL2100a380.00 ——
4–250
4050704950a128.00
200 A FTL2200a400.00 —— 4050703850a151.00
3Ø3W 240 V delta
3Ø4W 240/120 V delta
3Ø4W 208Y/120 V
100 A — — FTL3100 1000.00 4050707050a196.00
200 A — — FTL3200 1045.00 4050705950a288.00
aNot stocked in PDS. Order point Lexington.
3.80
97
3.16
80
2.96
75
1.48
38
6.38
162
3.44
87
3.20
81
4.25
108
.63
16
(2) .187 Dia. Hole
.34 Dia. C'bore
1.85
47
2.19
56
2.85
72
3.80
97
3.00
76
2.23
57
1.85
47
Pull
200A
4.00
102
2.98
76
4.46
113
1.48
38
1.50
38
(4) .187 Dia. Mounting Holes
.34 Dia. C'bore, .38 Deep
Pull 200A
6.61
168
.78
20
5.03
128
4.25
108
DE5 Discount
Schedule
www.schneider-electric.us
1LOAD CENTERS
© 2012 Schneider Electric
All Rights Reserved 1-3
Circuit Breaker Covers
Refer to Catalog 1100CT0501
Circuit Breaker Covers
Available now from Square D™ / Schneider Electric™ are two different versions of rainproof circuit breaker covers
which are UL component recognized as being suitable for use as circuit breaker handle covers.
They are constructed of durable impact-resistant material and are intended for use by OEMs where a rainproof cover is
needed (e.g. on heat pumps and air conditioners with built-in disconnects). Both models have a built-in latch with
padlock provisions.
The BCH covers are for use on a horizontally-mounted circuit breaker and fit over Square D two-pole QO™, QOU, Q2,
EH and three-pole Q2 and EH circuit breakers.
The BCV covers are for use on vertically-mounted circuit breakers and will fit over Square D two- and three-pole QO,
QOU, Q2, EH, FA and KA circuit breakers.
Dimensions
Table 1.2: Covers
Quantity Cat. No. $ Price
1BCH 20.50
1BCV 20.50
4.58
116
1.09
28
1.32
34
4.82
122
4.40
112
BCV
Vertical Cover
3.14
80
.30
8
2.50
64
2.11
54
2.33
59
4.62
117
BCH
Horizontal Cover
1.10
28
DE2E Discount
Schedule
www.schneider-electric.us
1LOAD CENTERS
1-4 © 2012 Schneider Electric
All Rights Reserved
2-1
© 2012 Schneider Electric
All Rights Reserved
2SAFETY SWITCHES
Table of Contents
Section 2
Safety Switches
General Duty Safety Switches
Lug Kit 400 or 600 A General Duty Safety Switches 2-2
Heavy Duty Safety Switches
Voltage-Indicating Safety Switches 2-3
Push Button—Pilot Light—Selector Switch 2-3
Electrica Interlock Kits and Contact Ratings
Key Interlock Systems 2-4
Sample Applications 2-4
2SAFETY SWITCHES
2-2 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
General Duty Safety
Switches
Accessories
Class 3130
Field-Installed Lug Kit
Kit consists of three line, three load, and two neutral lugs as required for a three-pole 400 A or 600 A general duty switch.
Kit can be installed in field on 400 or 600 A General Duty switches.
a400 Amp NEMA 1 Series E03 only. 600 Amp NEMA 1 and 3R Series E01, E02 and E03.
Table 2.1: Lug Kit
Switch Rating
(A)
Lug Kit
Cat. No.
Wire Range/NEC
312.6
AWG/kcmil
Lug Wire Range per Lug
AWG/kcmil $ Price
400 or 600 AaGD4060LK
(1) 1/0–600 or
(2) 1/0–500 or
(4) 1/0–250
(2) 1/0–600 or
(4) 1/0–250 404.00
DE1 DE3A Discount
Schedule
2SAFETY SWITCHES
www.schneider-electric.us
© 2012 Schneider Electric
All Rights Reserved 2-3
Heavy Duty Safety
Switches
Accessories
Class 3130
Voltage-Indicating Safety Switches
Voltage-indicating safety switches indicate when voltage
is present, helping to prevent arc-flash hazards and
electric shocks during maintenance work. Voltage
indicators are a factory-installed only option. Order the
indicators by adding the appropriate suffix below to the
switch catalog number. Not available on the following:
NEMA 7 and 9 and NEMA 4 X Fiberglass and Krydon
Enclosures.
Voltage-indicating safety switches can be combined with
other safety features such as visible blades, viewing
windows and color-coded handles.
aAdd an additional $120.00 for 30 and 60 A NEMA TYPE 1, 3R and 12
enclosures.
bAvailable on 30–400 A Double Throw Safety Switches
In addition to the suffix in Table 2.2, a 3 must be added to
the switch catalog number for all 30 and 60 Amp switches,
i.e. H361AWK becomes H3613AWKLI.
Phenolic Legend Plate
Available engraved and mounted on all heavy duty safety
switches, except NEMA 7 and 9. Legend engraved in 1/4
in. high white letters on black background. Customer must
provide legend. UL Listed.
To order, add suffix NP to standard Cat. No.
Example: H363-NP
Price adder per legend plate—$167.00
Push Button—Pilot Light—Selector Switch
Push buttons, pilot lights or selector switches are available
factory-installed in the cover of NEMA 1, 3R, (4-4X-5)
stainless steel or NEMA 12 heavy duty non-fusible safety
switches and all double throw switches. Wiring to contact
blocks is not available. Customer must furnish catalog
number of push button, pilot light or selector switch device
desired. UL Listed.
Contact Schneider Electric for catalog number and
availablility prior to quoting a job.
Factory-installed price adder — $584. for Heavy Duty and
$1168. for Double Throw Switches. Price does not include
cost of buttons/lights. For enclosure sizing, 30 and 60
Amperes switches will be in 100 Ampere enclosures.
Electrical Interlock Kits
Electrical interlocks for heavy duty 30–1200 A safety
switches are available factory-installed or in kit form for
field installation. Each kit contains instructions for proper
field mounting. A pivot arm operates from switch
mechanism, breaking the control circuit before the main
switch blades break. Switches with electrical interlocks
installed are UL Listed. For factory-installed electrical
interlocks add EI (for one contact) or EI2 (for two
contacts) suffix to catalog number.
cSee Digest Section 3 for electrical interlocks on NEMA 4X fiberglass
reinforced polyester and Krydon®.
dElectrical interlock kit catalog numbers with 1 suffix indicates one
normally open and one normally closed contact; 2 indicates two
normally open and two normally closed contacts. Kits are UL Listed.
eHU461AWK uses EK3061 or EK3062.
fThe following series -F5–F7 devices use EIK-1,2: H3612, H3612A,
H3612AWK, H3612RB, H461, H461DS, H461AWK, HU461,
HU461DS, HU661DS, HU661AWK, H361AWA, H361AWC,
HU361AWA and HU361AWC.
gH362WA, HU362WA, H362WC, H362AWA, HU362AWA, H362AWC,
HU362AWC, and H2212AWK use EIK1 or EIK2 electric interlock.
Note: Single pole single throw interlock kits are rated 1•2 hp @ 110 and 220
Vac.
Table 2.2: Voltage Indicators
Suffix Description Heavy Duty
$ Pricea
Double Throw
$ Priceab
SI Line Side Indicator 1208.00 2416.00
LI Load Side Indicator 1208.00 1208.00
LI2 Li ne and Load Side Indicators 2416.00 3624.00
Table 2.3: Electrical Interlock Kit c
Switch
Rating
Series Number
(See Digest Section 3)
Electrical
Interlock Kit
Cat. No.d
$ Price
Factory-
Installed
$ Price
30 A
F1, F5–F7 EIK031e f145.00 359.00
EIK032e f
F3 EIK1 207.00 452.00
EIK2
60 A
F1-F3
F5–F7 (600 V)
EIK1 207.00 452.00
EIK2
F4
F5–F6 (240 V)
EIK031g145.00 359.00
EIK032g
100–200 A F2–F7 EIK1 207.00 452.00
EIK2
400–1200 A E1–E4 EIK40601 355.00 674.00
EIK40602
Table 2.4: Electrical Interlock Contact
RatingsNote:
Interlock
Type
AC - 50 or 60 Hz DC
Volts Make Break Cont. Volts Make &
Break Cont.
Cat. No. ending with a 1 utilize a 9007A01 limit switch.
1 NO/1 NC
Contact
120 40 A 15 A 15 A 115 0.50 A 15 A
240 20 A 10 A 15 A 230 0.25 A 15 A
480 10 A 6 A 15 A ———
600 8 A 5 A 15 A 600 0.05 A 15 A
Cat. No. ending with a 2 utilize a 9007C03 limit switch.
2 NO/2 NC
Contacts
120 30 A 3.0 A 10 A 115 1.0 A 10 A
240 15 A 1.5 A 10 A 230 0.30 A 10 A
480 7.5 A 0.75 A 10 A ———
600 6.0 A 0.60 A 10 A 600 0.10 A 10 A
DE1 DE3A Discount
Schedule
www.schneider-electric.us
2SAFETY SWITCHES
2-4 © 2012 Schneider Electric
All Rights Reserved
Heavy Duty Safety
Switches
Key Interlock Systems
Key Interlock Systems
Factory-installed only on heavy duty and double throw
safety switches.
Interlocks are used to prevent the operator from making
an unauthorized operation. Not available on hazardous
location devices (NEMA 7/9) or fiberglass reinforced
polyester (NEMA 4X).
The key interlock system is a simple and easy method of
applying individual key interlock units and assemblies to
the above equipment so as to require operation in a
predetermined sequence. UL Listed.
Quoting:
Contact Schneider Electric for catalog number, availability
and pricing prior to quoting a job.
Ordering:
Order cannot be released for production until the following
information has been provided:
•End User—Company name, address;
•Function of each lock (e.g., switch to be locked open with key
removed, key held when switch is closed);
•Existing Equipment—if switch is to be interlocked with equipment
already on site, provide brand of existing lock and key number;
•Other New Equipment—if switch is to be interlocked with new
equipment not yet installed at the site, then provide contact
person and phone number so that locks may be coordinated;
•Additional information may be required upon order entry;
•Schneider Electric locks supplied unless otherwise specified.
Use these suffixes on switch catalog numbers:
•KI = 1 lock per switch
•KI2 = 1 lock with 2 cylinders per switch
•KIKI = 2 separate locks per switch
bPrices do not apply when more than three devices are interlocked as these
schemes normally require more than one key assembly per device.
Sample Applications
Sample Application—1
To prevent two devices from being closed simultaneously.
Two devices are shown in Figure 1. In operation they are
not closed at the same time. With the interlocks arranged
as shown only one key is required in the interlocking
system. Both devices are shown open, therefore, the key
is free. To close any one device the key is inserted and
turned in that particular lock, the key is held in this lock
until the device is again locked open. This simple
interlocking sequence lends itself to a multitude of
applications. The procedure is the same for two devices,
neither of which is to be opened at the same time.
Sample Application—2
To prevent opening of switch A when circuit breaker B is
closed.
Switch A and circuit breaker B are in closed position. Key
A-1 is held in circuit breaker B interlock.
1. Open circuit breaker.
2. Turn key A-1 in L-O-R interlock on circuit breaker B to lock
open. Key A-1 is now free.
3. Insert key A-1 in L-C-R interlock on switch A and turn to
unlock.
4. Open switch A. Key A-1 is now held. Reverse sequence to
restore service.
Sample Application—3
To prevent operation of switch A when circuit breaker B is
closed. Permits re-closing of circuit breaker for servicing
when switch is locked open.
Switch A and circuit breaker B are in closed position. Key
A-1 is held in circuit breaker interlock.
5. Open circuit breaker.
6. Turn key A-1 in L-O-R interlock on circuit breaker B to lock
open. Key A-1 is now free.
7. Insert key A-1 in L-O-C-R interlock on switch A and turn to
unlock.
8. Open switch A.
9. Turn key A-1 in L-O-C-R interlock on switch A to lock open.
Key A-1 is now free.
10. Return key A-1 to circuit breaker interlock and unlock for
operation during servicing period.
Reverse sequence to restore service.
Sample Application—4 (Main-Tie-Main)
To prevent paralleling of lines A and B; two loads, fed from
either source.
Circuit breaker A is closed to supply load M. Circuit
breaker B is closed to supply load N. Tie-circuit breaker C
is open. Keys A-1 are held in interlocks on both circuit
breakers A and B. Tie-circuit breaker C cannot be closed
unless either A or B is locked open.
To transfer load N to circuit breaker A, proceed as follows:
1. Open circuit breaker B.
2. Turn key A-1 in L-O-R interlock on circuit breaker B to lock
open. Key A-1 is now free.
3. Insert Key A-1 in L-O-R interlock on tie-circuit breaker C and
turn to unlock. Key A-1 is now held.
4. Close tie-circuit breaker C.
5. Reverse sequence to restore service.
6. Load M can be supplied through circuit breaker B in a similar
manner.
Locking Position—
Designations
L-O-R
L-C-R
L-O-C-R
L-O-H
L-C-H
L-O-C-H
Devices locked open
with key removed
Devices locked closed
with key removed
Devices locked open
or closed with key
removed
Devices locked open
with key held
Devices locked closed
with key held
Devices locked open or
closed with key held
Multi-lock interlock
(More than one key
per lock)
Diagram Symbols
Note:
Device locked open =
switch in OFF (O) position
Device locked closed =
switch in ON (I) position
A-1 A-2 A-3
Device normally
open
Device normally
closed
Direction of key
transfer
Key
interchange
number
Key
Table 2.4: Price Adder Per Lockb
Switch Type $ Price
30–1200 A Heavy Duty 2055.00
30–600 A Double Throw 1988.00
Figure 1
A-1
A 1
L-O-R L-O-R
AB
A-1
Figure 2
A-1
L-C-R L-O-R
A
B
A 1
Figure 3
A-1
L-O-C-R L-O-R
A
B
A 1
Figure 4
L-O-R
C
L-O-R
A
A
N
M
A 1
L-O-R
A 1
A-1
B
B
3-1
© 2012 Schneider Electric
All Rights Reserved
3MOLDED CASE CIRCUIT
BREAKERS
Table of Contents
Section 3
Molded Case Circuit Breakers and Enclosures
PowerPact™ Circuit Breakers 3-3
PowerPact™ H- and J-Frame Circuit Breakers 3-2–3-3
PowerPact™ L-Frame Circuit Breakers 3-4
PowerPact™ D-Frame Circuit Breakers 3-5
PowerPact™ Automatic Switches 3-6
PowerPact™ D-frame Mission Critical Circuit Breakers 3-6
Molded Case Circuit Breakers 3-7
F-Frame Thermal-Magnetic Circuit Breakers 3-7—3-8
K- and Q4-Frame Thermal-Magnetic Circuit Breakers 3-9—3-10
L-Frame Thermal-Magnetic Circuit Breakers 3-11—3-12
L-Frame Micrologic™ Series B Trip Circuit Breakers 3-13—3-14
Mag-Gard™ Motor Circuit Protector 3-15
GJ-Frame MCP Selection 3-16
Special Construction Circuit Breakers 3-17
Special Terminal Connectors and Lugs 3-17
Special Calibration, Rear-Connected Studs, Visi-Blade,
Moisture/Fungus Treatment, and Short LA/LH Handle
3-18
Special Calibration, Rear-Connected Studs, Visi-Blade,
Moisture/Fungus Treatment, and Short LA/LH Handle
3-18
P-Frame Replacement Handles, Key Interlock Adapter Plate and
Exchange Program
3-19
Special Terminations 3-20
Grounded BØ Systems 3-21
UL Marine Listed Circuit Breakers 3-22
Circuit Breaker Accessories 3-23
PowerPact™ Circuit Breakers Electrical Accessories 3-23
Factory-Installed Accessories 3-24
Field-Installable Accessories 3-25
Electrical Operators, Handle Accessories, Cylinder Locks, and
Walking Beam Mechanical Interlocks
3-26
Locks, Installation Accessories, and Rear Connections 3-27
Mechanical Lug Information 3-28
Compression Lug and Power Distribution Connectors 3-29
PowerPact™ Circuit Breakers Miscellaneous Accessories 3-30
Electronic Products 3-31
Neutral Current Transformers and Micrologic™ Series B Trip Unit
Accessories
3-31
Restraint Interface Module 3-32
Circuit Breaker Dimensions 3-33
Enclosures 3-34
Industrial Circuit Breaker Enclosures 3-34
Enclosed Switches and Enclosure Dimensions 3-35
Accessories 3-36
Key Interlock Systems—Factory Installed Only 3-37
Special Applications 3-38
3-2 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
PowerPact™ Circuit
Breakers
PowerPact™ H- and J-Frame Circuit Breakers
Class 611 / Refer to Catalog 0611CT1001
aTo complete catalog number, replace the blank with the appropriate rating (D, G, J, L)
bFor 80% rated use “T” or for 100% rated Use “R” in the 9th character place (for example, HDL36015T or HDL36015R). 100% rated H- and J-frame circuit
breakers have copper lugs and can only be used with copper wire.
cCircuit breakers will be labeled with Line and Load markings and are not suitable for reverse connections.
Only available on standard (80%) rated 3P unit-mount circuit breakers; not available with I-Line™ or Plug-In constructions.
dSee Digest page 7-39–3-41 for lug and termination kits.
eJ and L interrupts are UL Certified as current limiting.
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digest Page 7-35
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digest Page 7-38
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digest Page 7-53
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digest Page 7-54
Table 3.1: H-Frame 150 A UL Current-Limitinge Circuit Breaker Frame with Field-Interchangeable
Thermal-Magnetic Trip Unitsc (600 Vac, 250 Vdc)
Ampere
Rating
Fixed AC
Magnetic Trip Cat.
No.b
D Interrupting G Interrupting Je Interrupting Le Interrupting
Terminal
Wire Range
Hold Trip $ Price
80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated
3P, 600 Vac 50/60 Hz
15 A 350 A 750 A H(a)L36015( ) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
AL150HD
14–3/0 AWG
Al or Cu
20 A 350 A 750 A H(a)L36020( ) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
25 A 350 A 750 A H(a)L36025( ) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
30 A 350 A 750 A H(a)L36030( ) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
35 A 400 A 850 A H(a)L36035( ) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
40 A 400 A 850 A H(a)L36040( ) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
45 A 400 A 850 A H(a)L36045( ) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
50 A 400 A 850 A H(a)L36050( ) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
60 A 800 A 1450 A H(a)L36060( ) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
70 A 800 A 1450 A H(a)L36070( ) 1328.00 1592.00 1701.00 2042.00 2099.00 2519.00 3149.00 3779.00
80 A 800 A 1450 A H(a)L36080( ) 1328.00 1592.00 1701.00 2042.00 2099.00 2519.00 3149.00 3779.00
90 A 800 A 1450 A H(a)L36090( ) 1328.00 1592.00 1701.00 2042.00 2099.00 2519.00 3149.00 3779.00
100 A 900 A 1700 A H(a)L36100( ) 1328.00 1592.00 1701.00 2042.00 2099.00 2519.00 3149.00 3779.00
110 A 900 A 1700 A H(a)L36110( ) 2600.00 3120.00 3599.00 4319.00 5174.00 6209.00 6749.00 8099.00
125 A 900 A 1700 A H(a)L36125( ) 2600.00 3120.00 3599.00 4319.00 5174.00 6209.00 6749.00 8099.00
150 A 900 A 1700 A H(a)L36150( ) 2600.00 3120.00 3599.00 4319.00 5174.00 6209.00 6749.00 8099.00
Table 3.2: J-Frame 250 A UL Current-Limitinge Circuit Breaker Frame with Field-Interchangeable
Thermal-Magnetic Trip Unitsc (600 Vac, 250 Vdc)
Ampere
Rating
Adjustable AC
Magnetic Trip Cat.
No.b
D Interrupting G Interrupting Je Interrupting Le Interrupting
Terminal
Wire Range
$ Price
Low High 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated
3P, 600 Vac 50/60 Hz
150 A 750 A 1500 A J(a)L36150( ) 2730.00 3276.00 3779.00 4535.00 5432.00 6519.00 7086.00 8504.00 AL175JD
4--4/0 AWG Al or Cu
175 A 875 A 1750 A J(a)L36175( ) 2730.00 3276.00 3779.00 4535.00 5432.00 6519.00 7086.00 8504.00
200 A 1000 A 2000 A J(a)L36200( ) 2730.00 3276.00 3779.00 4535.00 5432.00 6519.00 7086.00 8504.00 AL250JD
3/0 AWG–350 kcmil Al
or Cu
225 A 1125 A 2250 A J(a)L36225( ) 2730.00 3276.00 3779.00 4535.00 5432.00 6519.00 7086.00 8504.00
250 A 1250 A 2500 A J(a)L36250( ) 3749.00 4499.00 5001.00 6002.00 7238.00 8685.00 8993.00 10791.00
Table 3.3: H-Frame 150A and J-Frame 250 A 3P Basic UL Current-Limitinge Circuit Breaker Frame Without
Terminationsd or Trip Unit (600 Vac, 250 Vdc)
Circuit Breaker
Frame
Ampere
Rating
D Interrupting G Interrupting Je Interrupting Le Interrupting
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
H-Frame 15–60 A HDF36000F06 525.00 HGF36000F06 930.00 HJF36000F06 1386.00 HLF36000F06 2286.00
70–150 A HDF36000F15 585.00 HGF36000F15 1574.00 HJF36000F15 3149.00 HLF36000F15 4724.00
J-Frame 150–250 A JDF36000F25 1538.00 JGF36000F25 2790.00 JJF36000F25 5027.00 JLF36000F25 6782.00
Table 3.4: H-Frame and J-Frame 3P Field-Installable Thermal-Magnetic Trip Unit
15–60 A H-Frame 70–150 A H-Frame 150–250 A J-Frame
Amperage Cat. No. $ Price Amperage Cat. No. $ Price Amperage Cat. No. $ Price
15 A HT3015 563.00 70 A HT3070 743.00 150 A JT3150 1193.00
20 A HT3020 563.00 80 A HT3080 743.00 175 A JT3175 1193.00
25 A HT3025 563.00 90 A HT3090 743.00 200 A JT3200 1193.00
30 A HT3030 563.00 100 A HT3100 743.00 225 A JT3225 1193.00
35 A HT3035 563.00 110 A HT3110 2025.00 250 A JT3250 2213.00
40 A HT3040 563.00 125 A HT3125 2025.00 — — —
45 A HT3045 563.00 150 A HT3150 2025.00 — — —
50 A HT3050 563.00 — — — — — —
60 A HT3060 563.00 — — — — — —
Table 3.5: H- and J-Frame Interrupting Ratings
Vol tage Interrupting Rating
D G J L
240 Vac 25 KA 65 kA 100 kA 125 kA
480 Vac 18 kA 35 kA 65 kA 100 kA
600 Vac 14 kA 18 kA 25 kA 50 kA
Table 3.6: H- and J-Frame Termination Options
Termination Letter
A - I-Line (See Section 9)
F = No Lugs (includes terminal nut kit on both ends)f
L = Lugs both ends
M = Lugs ON end Terminal Nut Kit OFF end
P = Lugs OFF end Terminal Nut Kit ON end
N = Plug-in g
D = Drawout g
S = Rear Connected g
fAdd TS suffix for circuit breaker without terminal nut kit.
gFor N and D pricing, add termination pricing on Digest page 7-41 to price. For S pricing, add termination pricing
on Digest page 7-37 to price.
H-Frame Trip Unit
H D L 3 6 0 1 5 T
For factory-installed
termination, place termination
letter in the third block of the
circuit breaker catalog number.
Termination Letter
DE2 Discount
Schedule
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
© 2012 Schneider Electric
All Rights Reserved 3-3
PowerPact™ Circuit
Breakers
PowerPact™ H- and J-Frame Circuit Breakers
Class 611 / Refer to Catalog 0611CT1001
fSee Digest page 7-38 for lug and termination kits.
gJ and L interrupts are UL Certified as current limiting.
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digest page 7-36
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digest page 7-39
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digest page 7-55
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digest page 7-56
Table 3.7: H-Frame 150 A and J-Frame 250 A Circuit Breakers with Lugs and Field-Interchangeable Electronic Trip Units cd
(600 Vac, 50/60 Hz, 3P) cd
Electronic Trip Unit
Sensor
Rating
Cat.
No.b
Interrupting Rating (2nd Letter of Catalog Number)
Terminal
Wire Range
Type Function Trip
Unit
D Interrupting G Interrupting J Interrupting L Interrupting
$ Price
80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated
Micrologic
Standard LI 3.2
60 A
100 A
150 A
H(a)L36060( )U31X
H(a)L36100( )U31X
H(a)L36150( )U31X
1247.00
1487.00
2759.00
1455.00
1735.00
3220.00
1652.00
1860.00
3758.00
1928.00
2171.00
4386.00
2108.00
2258.00
5333.00
2460.00
2635.00
6224.00
3008.00
3308.00
6908.00
3510.00
3860.00
8062.00
AL150HD
14–3/0 AWG Al or Cu
250 A J(a)L36250( )U31X 2957.00 3451.00 4006.00 4675.00 5659.00 6604.00 7313.00 8534.00 AL250JD
3/0 AWG–350 kcmil Al or Cue
Micrologic
Standard LSI 3.2S
60 A
100 A
150 A
H(a)L36060( )U33X
H(a)L36100( )U33X
H(a)L36150( )U33X
1433.00
1673.00
2945.00
1641.00
1921.00
3405.00
1838.00
2046.00
3944.00
2113.00
2356.00
4571.00
2294.00
2444.00
5519.00
2646.00
2821.00
6409.00
3194.00
3494.00
7094.00
3696.00
4046.00
8247.00
AL150HD
14–3/0 AWG Al or Cu
250 A J(a)L36250( )U33X 3221.00 3715.00 4270.00 4939.00 5923.00 6868.00 7577.00 8798.00 AL250JD
3/0 AWG–350 kcmil Al or Cue
Micrologic
Ammeter LSI 5.2A
60 A
100 A
150 A
H(a)L36060( )U43X
H(a)L36100( )U43X
H(a)L36150( )U43X
2031.00
2271.00
3543.00
2240.00
2520.00
4004.00
2436.00
2644.00
4542.00
2712.00
2955.00
5170.00
2892.00
3042.00
6117.00
3244.00
3419.00
7008.00
3792.00
4092.00
7692.00
4295.00
4645.00
8846.00
AL150HD
14–3/0 AWG Al or Cu
250 A J(a)L36250( )U43X 4075.00 4569.00 5124.00 5793.00 6777.00 7722.00 8431.00 9653.00 AL250JD
3/0 AWG–350 kcmil Al or Cue
Micrologic
Energy LSI 5.2E
60 A
100 A
150 A
H(a)L36060( )U53X
H(a)L36100( )U53X
H(a)L36150( )U53X
2391.00
2631.00
3903.00
2599.00
2879.00
4363.00
2796.00
3004.00
4902.00
3072.00
3314.00
5529.00
3252.00
3402.00
6477.00
3604.00
3779.00
7367.00
4152.00
4458.00
8052.00
4654.00
5004.00
9205.00
AL150HD
14–3/0 AWG Al or Cu
250 A J(a)L36250( )U53X 4588.00 5082.00 5637.00 6306.00 7290.00 8235.00 8944.00 10165.00 AL250JD
3/0 AWG–350 kcmil Al or Cue
Micrologic
Ammeter LSIG 6.2A
60 A
100 A
150 A
H(a)L36060( )U44X
H(a)L36100( )U44X
H(a)L361504( )U44X
2751.00
2991.00
4263.00
2960.00
3240.00
4724.00
3156.00
3364.00
5262.00
3432.00
3675.00
5890.00
3612.00
3762.00
6837.00
3964.00
4139.00
7728.00
4512.00
4812.00
8412.00
5015.00
5365.00
9566.00
AL150HD
14–3/0 AWG Al or Cu
250 A J(a)L36250( )U44X 5100.00 5594.00 6149.00 6818.00 7802.00 8747.00 9456.00 10678.00 AL250JD
3/0 AWG–350 kcmil Al or Cue
Micrologic
Energy LSIG 6.2E
60 A
100 A
150 A
H(a)L36060( )U54X
H(a)L36100( )U54X
H(a)L36150( )U54X
3111.00
3351.00
4623.00
3319.00
3599.00
5083.00
3516.00
3724.00
5622.00
3792.00
4034.00
6249.00
3972.00
4122.00
7197.00
4324.00
4499.00
8087.00
4872.00
5172.00
8772.00
5374.00
5724.00
9925.00
AL150HD
14–3/0 AWG Al or Cu
250 A J(a)L36250( )U54X 5613.00 6107.00 6662.00 7331.00 8315.00 9260.00 9969.00 11190.00 AL250JD
3/0 AWG–350 kcmil Al or Cue
aTo complete catalog number, replace the blank with the appropriate rating (D, G, J, L)
bFor 80% rated use “T” or for 100% rated Use “R” in the 9th character place (for example, HGL36015TU31X or HGL36015RU31X). 100% rated H- and J-frame circuit breakers have copper
lugs and can only be used with copper wire.
cCircuit breakers will be labeled with Line and Load markings and are not suitable for reverse connections.
dOnly available on 3P unit-mount circuit breakers. Not available with I-Line™ or Plug-in constructions.
eFor smaller wire (4–4/0 AWG Al or Cu), replace the lug wire binding screws with longer binding screws provided.
Table 3.8: H-Frame 150A and J-Frame 250 A 3P Basic UL Current-Limitingg Circuit Breaker Frame Without
Terminationsf or Trip Unit (600 Vac, 250 Vdc)
Circuit Breaker
Frame
Ampere
Rating
D Interrupting G Interrupting Jg Interrupting Lg Interrupting
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
H-Frame 15–60 A HDF36000F06 525.00 HGF36000F06 930.00 HJF36000F06 1386.00 HLF36000F06 2286.00
70–150 A HDF36000F15 585.00 HGF36000F15 1574.00 HJF36000F15 3149.00 HLF36000F15 4724.00
J-Frame 150–250 A JDF36000F25 1538.00 JGF36000F25 2790.00 JJF36000F25 5027.00 JLF36000F25 6782.00
Table 3.9: Micrologic Field-Installable Trip Unit
Model Trip
Function
Trip
Unit Contiuous Current Trip Unit
Cat. No. $ Price Termination Letter
Micrologic
Standard
LI 3.2
15-20-25-30-35-40-45-50-60 HE3060U31X 722.00 A - I-Line (See Section 9)
35-40-45-50-60-70-80-90-100 HE3100U31X 902.00 F = No Lugs (includes terminal nut kit on both ends)h
50-60-70-80-90-100-110-125-150 HE3150U31X 2184.00 L = Lugs both ends
70-80-100-125-150-175-200-225-250 JE3250U31X 1216.00 M = Lugs ON end Terminal Nut Kit OFF end
LSI 3.2S
15-20-25-30-35-40-45-50-60 HE3060U33X 908.00 P = Lugs OFF end Terminal Nut Kit ON end
35-40-45-50-60-70-80-90-100 HE3100U33X 1088.00 N = Plug-in i
50-60-70-80-90-100-110-125-150 HE3150U33X 2370.00 D = Drawout i
70-80-100-125-150-175-200-225-250 JE3250U33X 1480.00 S = Rear Connected i
Micrologic
Ammeter
LSI 5.2A
15–60 HE3060U43X 1506.00
35–100 HE3100U43X 1686.00
50–150 HE3150U43X 2968.00
70–250 JE3250U43X 2334.00
LSIG 6.2A
15–60 HE3060U44X 1866.00
35–100 HE3100U44X 2046.00
50–150 HE3150U44X 3318.00 hAdd TS suffix for circuit breaker without
terminal nut kit.
iFor N and D pricing, add termination pricing on
Digest page 7-42 to price. For S pricing, add
termination pricing on Digest page 7-38 to
price.
70–250 JE3250U44X 2847.00
Micrologic
Energy
LSI 5.2E
15–60 HE3060U53X 2226.00
35–100 HE3100U53X 2406.00
50–150 HE3150U53X 4038.00
70–250 JE3250U53X 3359.00
LSIG 6.2E
15–60 HE3060U54X 2586.00
35–100 HE3100U54X 2766.00
50–150 HE3150U54X 4038.00
70–250 JE3250U54X 3872.00
Table 3.10: H- and J-Frame Interrupting Ratings
Voltage Interrupting Rating
D G J L
240 Vac 25 KA 65 kA 100 kA 125 kA
480 Vac 18 kA 35 kA 65 kA 100 kA
600 Vac 14 kA 18 kA 25 kA 50 kA
H D L 3 6 0 1 5 T
For factory-installed termination, place
termination letter in the third block of the
circuit breaker catalog number.
DE2 Discount
Schedule
www.schneider-electric.us
3-4 © 2012 Schneider Electric
All Rights Reserved
3MOLDED CASE CIRCUIT
BREAKERS
PowerPact™ Circuit
Breakers
PowerPact™ L-Frame Circuit Breakers
Class 612, 615 / Refer to Catalogs: 0612CT0101, 0616CT0801
eFor N, D, and S pricing, add termination pricing to price. See Digest
page 7-42.
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Digest pages 7-36–7-45
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Digest pages 7-39–7-40
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digest page 7-55
Table 3.11: L-Frame 3 Pole, 600 A Circuit Breakers with Lugs and Field-Interchangeable Electronic Trip Units (600 Vac, 50/60 Hz)ad
Electronic Trip Unit Sensor
Rating
Cat.
No.b
D Interrupting G Interrupting J Interrupting L Interrupting
Terminal
Wire Range
$ Price
Type Function Trip
Unit 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated
Micrologic
Standard LI 3.3
250 A L(a)L36250( )U31 4287.00 5648.00 5081.00 5945.00 8487.00 9919.00 9918.00 11604.00
AL400L61K3D
(1) 2 AWG–600 kcmil Cu
(1) 2 AWG–500 kcmil Al
400 A
600 A
L(a)L36400( )U31X
L(a)L36600( )U31X
4827.00
7109.00
5648.00
—
5081.00
7484.00
5945.00
—
8487.00
10541.00
9919.00
—
9918.00
11837.00
11604.00
—
AL600S52K3
(2) 2/0 AWG–500 kcmil Al/Cu
Micrologic
Standard LSI 3.3S
250 A L(a)L36250( )U33X 5391.00 6211.00 5674.00 6538.00 9071.00 10513.00 10511.00 12198.00
AL400L61K3D
(1) 2 AWG–600 kcmil Cu
(1) 2 AWG–500 kcmil Al
400 A
600 A
L(a)L36400( )U33X
L(a)L36600( )U33X
5391.00
7673.00
6211.00
—
5674.00
8077.00
6538.00
—
9071.00
11134.00
10513.00
—
10511.00
12430.00
12198.00
—
AL600S52K3
(2) 2/0 AWG–500 kcmil Al/Cu
Micrologic
Ammeter LSI 5.3A 400 A
600 A
L(a)L36400( )U43X
L(a)L36600( )U43X
6253.00
8535.00
7073.00
—
6582.00
8984.00
7445.00
—
9979.00
12041.00
11420.00
—
11419.00
13337.00
13105.00
—
AL600S52K3
(2) 2/0 AWG–500 kcmil Al/Cu
Micrologic
Energy LSI 5.3E 400 A
600 A
L(a)L36400( )U53X
L(a)L36600( )U53X
7200.00
9483.00
8021.00
—
7579.00
9982.00
8443.00
—
10976.00
13039.00
12418.00
—
12416.00
14335.00
14103.00
—
Micrologic
Ammeter LSIG 6.3A 400 A
600 A
L(a)L36400( )U44X
L(a)L36600( )U44X
8149.00
10431.00
8969.00
—
8578.00
10980.00
9441.00
—
11975.00
14037.00
13416.00
—
13415.00
15333.00
15101.00
—
Micrologic
Energy LSIG 6.3E 400 A
600 A
L(a)L36400( )U54X
L(a)L36600( )U54X
9097.00
11379.00
9917.00
—
9575.00
11978.00
10439.00
—
12972.00
15035.00
14414.00
—
14412.00
16331.00
16099.00
—
aTo complete catalog number, replace the blank with the appropriate rating (D, G, J, L)
bFor 80% rated use “T” or for 100% rated Use “R” in the 9th character place (for example, LGL36400TU31X or LGL36400RU31X). 100% rated H- and J-frame circuit breakers have copper
lugs and can only be used with copper wire.
cCircuit breakers will be labeled with Line and Load markings and are not suitable for reverse connections.
dOnly available on 3P unit-mount circuit breakers.
Table 3.12: L-Frame 3 Pole, 600 A Circuit Breaker Breaker Frame without Trip Units (600 Vac, 50/60 Hz)
Ampere
Rating
D Interrupting G Interrupting J Interrupting L Interrupting
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
250 A (70–250 A) LDF36000F25 1328.00 LGF36000F25 1480.00 LJF36000F25 4616.00 LLF36000F25 6069.00
400 A (125–400 A LDF36000F40 2628.00 LGF36000F40 2766.00 LJF36000F40 6164.00 LLF36000F40 7602.00
600 A (200–600 A) LDF36000F60 5199.00 LGF36000F60 5472.00 LJF36000F60 8226.00 LLF36000F60 9522.00
Table 3.13: L-Frame 3P Field-Installable Micrologic Electronic Trip Units
Electronic Trip Unit Continuous Current Trip Unit
Cat. No. $ Price
Type Function Code
Micrologic
Standard
LI 3.3
70-80-100-125-150-175-200-225-250 LE3250U31X 2315.00
125-150-175-200-225-250-300-350-400 LE3400U31X 2315.00
200-225-250-300-350-400-450-500-600 LE3600U31X 2315.00
LSI 3.3S
70-80-100-125-150-175-200-225-250 LE3250U33X 2908.00
125-150-175-200-225-250-300-350-400 LE3400U33X 2908.00
200-225-250-300-350-400-450-500-600 LE3600U33X 2908.00
Micrologic
Ammeter
LSI 5.3A 125–400 LE3400U43X 3816.00
200–600 LE3600U43X 3816.00
LSIG 6.3A 125–400 LE3400U44X 4813.00
200–600 LE3600U44X 4813.00
Micrologic Energy
LSI 5.3E 125–400 LE3400U53X 5812.00
200–600 LE3600U53X 5812.00
LSIG 6.3E 125–400 LE3400U54X 6809.00
200–600 LE3600U54X 6809.00
Table 3.14: Termination Options
Termination Letter Termination Option
A I-Line (See Section 9)
F No lugs (includes terminal nut kit on both ends)
L Lugs both ends
M Lugs ON end, terminal nut kit OFF end
P Lugs OFF end, terminal nut kit ON end
NePlug In
DeDrawout
SeRear Connected
M G L 3 6 4 0 0 or
For factory-installed termination, place termination letter in
the third block of the circuit breaker catalog number.
Termination Letter
L G L 3 6 6 0 0 U 4 4 X
Table 3.15: L-Frame Interrupting Ratings
Voltage Interrupting Rating
D G J L
240 Vac 25 kA 65 kA 100 kA 125 kA
480 Vac 18 kA 35 kA 65 kA 100 kA
600 Vac 14 kA 18 kA 25 kA 50 kA
DE2 Discount
Schedule
www.schneider-electric.us
© 2012 Schneider Electric
All Rights Reserved 3-5
3MOLDED CASE CIRCUIT
BREAKERS
PowerPact™ Circuit
Breakers
PowerPact™ D-Frame Circuit Breakers
Class 612, 615 / Refer to Catalogs: 0612CT0101, 0616CT0801
aPrice shown is for quantity of 1.
bFor N, D, and S pricing, add termination pricing to price.
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-24—3-27
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-28—3-29
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 3-33
Enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Digest Page 7-56
Table 3.16: D-Frame (600 A 600 Vac) 3P 50/60 Hz Circuit Breaker with Lugs and Electronic Trip Unitsa
Electronic Trip
Unit Type Trip Function Trip Unit Continuous
Current
G Interrupting J Interrupting L Interrupting Terminal Wire Range
(AWG/kcmil)
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
Standard
LS STR23SP
150 A DGL36150E20 5081.00 DJL36150E20 8478.00 DLL36150E20 9918.00
(1) 2–600 Cu or (1) 2–500 Al250 A DGL36250E20 5081.00 DJL36250E20 8478.00 DLL36250E20 9918.00
400 A DGL36400E20 5081.00 DJL36400E20 8478.00 DLL36400E20 9918.00
600 A DGL36600E20 8315.00 DJL36600E20 11712.00 DLL36600E20 13152.00 (2) 2/0–350 Cu or (2) 2/0–500 Al
LSI SR53UP-Fb
150 A DGL36150E53 6200.00 DJL36150E53 9597.00 DLL36150E53 11037.00
(1) 2–600 Cu or (1) 2–500 Al250 A DGL36250E53 6200.00 DJL36250E53 9597.00 DLL36250E53 11037.00
400 A DGL36400E53 6200.00 DJL36400E53 9597.00 DLL36400E53 11037.00
600 A DGL36600E53 9429.00 DJL36600E53 12813.00 DLL36600E53 14721.00 (2) 2/0–350 Cu or (2) 2/0–500 Al
LSIG STR53UP-FTb
150 A DGL36150E54 7527.00 DJL36150E54 10925.00 DLL36150E54 12365.00
(1) 2–600 Cu or (1) 2–500 Al250 A DGL36250E54 7527.00 DJL36250E54 10925.00 DLL36250E54 12365.00
400 A DGL36400E54 7527.00 DJL36400E54 10925.00 DLL36400E54 12365.00
600 A DGL36600E54 10761.00 DJL36600E54 14159.00 DLL36600E54 15599.00 (2) 2/0–350 Cu or (2) 2/0–500 Al
Ammeter
LSI STR53UP-FIb
150 A DGL36150E58 7661.00 DJL36150E58 11058.00 DLL36150E58 12498.00
(1) 2–600 Cu or (1) 2–500 Al250 A DGL36250E58 7661.00 DJL36250E58 11058.00 DLL36250E58 12498.00
400 A DGL36400E58 7661.00 DJL36400E58 11058.00 DLL36400E58 12498.00
600 A DGL36600E58 10895.00 DJL36600E58 14292.00 DLL36600E58 15732.00 (2) 2/0–350 Cu or (2) 2/0–500 Al
LSIG STR53UP-FTIb
150 A DGL36150E59 8990.00 DJL36150E59 12387.00 DLL36150E59 13827.00
(1) 2–600 Cu or (1) 2–500 Al250 A DGL36250E59 8990.00 DJL36250E59 12387.00 DLL36250E59 13827.00
400 A DGL36400E59 8990.00 DJL36400E59 12387.00 DLL36400E59 13827.00
600 A DGL36600E59 9434.00 DJL36600E59 15621.00 DLL36600E59 17061.00 (2) 2/0–350 Cu or (2) 2/0 –
500 Al
aD-frame circuit breakers 400 A and below are 100% rated. 600 A is standard (80%) rated only.
bF = Fault indicator; T = Residual-type ground-fault protection; I = Ammeter
cAvailable with lugs (L) or bus (F) connections only.
Table 3.17: D-Frame 3P 600 A Circuit Breaker, Frame Only, and Field-Installable Trip Units
Basic Frame Only (600 Vac)d Field Installable D-Frame Electronic Trip Unit
Ampere
Rating
G Interrupting J Interrupting L Interrupting Long-time, Short-time and Instantaneous Protection
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Description Factory Code Trip Function Cat. No. $ Price
150 A DGL36150F40 2766.00 DJL36150F40 6164.00 DLL36150F40 7602.00 STR23SP E20 LS 36940 2033.00
250 A DGL36250F40 2766.00 DJL36250F40 6164.00 DLL36250F60 7602.00 STR53UP-F E53 LSI 36942 3152.00
400 A DGL36400F40 2766.00 DJL36400F40 6164.00 DLL36400F40 7602.00 STR53UP-FT E54 LSIG 36943 4479.00
600 A DGL36600F60 5904.00 DJL36600F60 9302.00 DLL36600F60 10740.00 STR53UP-FI E58 LSI 36944 4613.00
dAvailable with lugs (L) or bus (F) connections only. STR53UP-FTI E59 LSIG 36945 5942.00
Table 3.18: Plug-In and Drawout Mountings for D-Frame Circuit Breakers
Description Poles
Plug-in Mounting Drawout Mounting
Factory
Installed
Cat. No.
Field-
Installed
Cat. No.
$ Price
Factory
Installed
Cat. No.
Field-
Installed
Cat. No.
$ Price
Kit (stationary and moving parts) 3N 32546 1542.00 D32548 2466.00
4N M32547 2082.00 DM32549 3281.00
Stationary Part Plug-in base 332514 1065.00 32514 1065.00
4M32515 1439.00 M32515 1439.00
Fixed part of chassis 32532 693.00
Moving Part
HJ00 710.00 HJ00 710.00
Moving part of chassis 32533 231.00
Short terminal covers 332562 149.00 32562 149.00
432563 161.00 32563 161.00
Power connections 33x32518a95.00 3x 32518a95.00
44x32518a95.00 4x 32518a95.00
Table 3.19: Plug-In and Drawout Accessories for D-Frame Circuit Breakers
Description Field-Installed Cat. No. $ Price
Secondary Disconnecting Blocks
Fixed Part 9-wire connector 29273 95.00
Moving Part 9-wire connector 32523 60.00
Support for 3 moving connectors 32525 42.60
Shutters Two shutters for plug-in base 32521 81.00
Chassis Accessories
Extended escutcheon for toggle 32534 104.00
Locking device (key lock is not included) 29286 164.00
Two position indicating switches (connected/disconnected) 29287 207.00
Table 3.20: Termination Options
Frame Termination
Letter Termination Option
D-Frame
F No Lugs (Includes terminal nut kit on both ends)
L Lugs both ends
M Lugs ON end Terminal Nut Kit Off end
P Lugs OFF end Terminal Nut Kit On end
N bPlug-in
D bDrawout
S bRear Connected
M G L 3 6 4 0 0 or
For factory-installed termination, place termination letter in
the third block of the circuit breaker catalog number.
Termination Letter
D G L 3 6 4 0 0 E 2 0
Table 3.21: D-Frame Interrupting Ratings
Voltage Interrupting Rating
G J L
240 Vac 65 kA 100 kA 125 kA
480 Vac 35 kA 65 kA 100 kA
600 Vac 18 kA 25 kA 25 kA
DE2 Discount
Schedule
3-6 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
PowerPact™ Automatic
Switches Class 600 / Refer to Catalog 0612CT0101
Automatic molded case switches open instantaneously at a factory preset magnetic trip point, calibrated to protect only
the molded case switch itself, when it is subjected to high fault currents. The trip point is nonadjustable and provides no
overload or low level fault protection.
Molded case switches open when the handle is switched to the OFF position or in response to an auxiliary tripping
device such as a shunt trip.
All molded case switches will accept the same lugs and accessories as equivalent thermal-magnetic circuit breakers,
with the exception of Q-frame switches which do not have electrical accessories available.
Automatic molded case switches are UL Listed per UL 489 and are CSA Certified.
cWithstand rating of 10 kA at 240 Vac.
dDE2A discount schedule.
eP-frame L-interrupting is available in 480 Vac only.
fUL magnetic trip tolerances are -20% / +30% from the nominal values shown.
gThe withstand rating is the fault current at rated voltage that the molded case switch will withstand without damage when protected by a circuit breaker
with an equal continuous current rating.
PowerPact™ D-frame Mission Critical Circuit Breakers
When the D-frame Mission Critical circuit breaker is used as a main circuit breaker with QO branch circuit breakers, the
D-frame MC will remain closed during any fault that occurs downstream of the QO circuit breaker up to 30kA at
208Y/120 Vac.
Ratings:
•UL 489 Listed
•CSA Certified
•Voltage: 208Y/120 V
•Handle ratings: 60–600 A
•AIR: 65 kA
Available Configurations:
•Four sizes: 150 A, 250 A, 400 A, and 600 A
•Main circuit breaker in NQ panelboards
•Unit mount for OEM users
•Plug-in base for OEM users
•Drawout base for OEM users
aD-Frame circuit breakers 400 A and below are 100% rated.
For N, D, and S pricing, add termination pricing to price. See page 7-45
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-24—3-27
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-28—3-29
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-33
Table 3.22: D-Frame (600 Vac) and Q-Frame (240 Vac) PowerPact™ Automatic Molded Case Switches
Circuit
Breaker Poles Ampere
Rating
J Interrupting Terminal Wire Range
Cat. No. $ Price Trip Point
D-Frame 3 400 A DJL36000S40 4572.00 6000 A S32508 2 AWG–500 kcmil Al or 2 AWG–600 kcmil Cu
600 A DJL36000S60 7484.00 6000 A S32510 (2) 2/0 AWG–500 kcmil Al or (2) 2/0 AWG–350 kcmil Cu
Q-Framec2225 AQBL22000S22d440.00 4500 A 4 AWG–300 kcmil
3225 AQBL32000S22d1193.00 4500 A
Table 3.23: D-Frame Withstand Ratingsg
Voltage Interrupting
J
240 Vac 150 kA
480 Vac 100 kA
600 Vac 25 kA
Table 3.24: D-Frame Mission Critical Circuit Breakers
Circuit Breaker
Cat. No.a
Continuous Current
Rating $ Price
Terminal
Cat. No. Wire Range
(AWG/kcmil)
DJL32150W 150 A 10317.00
32508 #2-600 Cu or #2-500 AlDJL32250W 250 A 10317.00
DJL32400W 400 A 10317.00
DJL32600W 600 A 13551.00 32510 (2) 2/0-350 Cu or (2) 2/0-500Al
Table 3.25: Termination Options
Frame Termination
Letter Termination Option
D-Frame
F No Lugs (Includes terminal nut kit on both ends)
L Lugs both ends
M Lugs ON end Terminal Nut Kit Off end
P Lugs OFF end Terminal Nut Kit On end
N Plug-in
D Drawout
S Rear Connected
D-Frame Switch
For factory-installed termination, place termination letter in
the third block of the circuit breaker catalog number.
Termination Letter
D G L 3 6 4 0 0 E 2 0
DE2 DE2A Discount
Schedule
www.schneider-electric.us
© 2012 Schneider Electric
All Rights Reserved 3-7
3MOLDED CASE CIRCUIT
BREAKERS
Molded Case Circuit
Breakers
F-Frame Thermal-Magnetic Circuit Breakers
Class 650
Thermal-magnetic molded case circuit breakers shown on
pages 3-7 through 3-18 are permanent trip UL Listed,
CSA® Certified, IEC rated, and also meet the requirements
of Federal Specification W–C–375B/GEN as indicated on
Digest pages 7-4 through 7-7.
NOTE: Consider using PowerPact™ circuit breakers for
situations requiring circuit breaker accessories.
See Digest Section 7 for more information.
aSee Section 11
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-24—3-27
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-28—3-29
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 3-33
Enclosures: see Digest Section 7
FAL 1P
15–100 A
FAL/FHL 2P
15–100 A
FAL/FHL 3P
15–100 A
Table 3.26: F-Frame—100 A, Thermal-Magnetic, Individually-Mounted, Standard Interrupting, 240 Vac
Ampere
Rating
Fixed AC Magnetic
Trip
1 P 2 P 3 P
Terminal Wire Range
(AWG)
120 Vac 240 Vac 240 Vac
Hold Trip Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
15 A 275 A 600 A FAL12015 198.00 FAL22015 333.00 FAL32015 495.00
AL50FA
14–4 Cu or 12–4 Al
20 A 275 A 600 A FAL12020 198.00 FAL22020 333.00 FAL32020 495.00
25 A 275 A 600 A FAL12025 198.00 FAL22025 333.00 FAL32025 495.00
30 A 275 A 600 A FAL12030 198.00 FAL22030 333.00 FAL32030 495.00
35 A 400 A 850 A FAL12035 198.00 FAL22035 333.00 FAL32035 495.00
AL100FA
14–1/0 Cu or 12–1/0 Al
40 A 400 A 850 A FAL12040 198.00 FAL22040 333.00 FAL32040 495.00
45 A 400 A 850 A FAL12045 198.00 FAL22045 333.00 FAL32045 495.00
50 A 400 A 850 A FAL12050 198.00 FAL22050 333.00 FAL32050 495.00
60 A 800 A 1450 A FAL12060 198.00 FAL22060 333.00 FAL32060 495.00
70 A 800 A 1450 A FAL12070 261.00 FAL22070 543.00 FAL32070 704.00
80 A 800 A 1450 A FAL12080 261.00 FAL22080 543.00 FAL32080 704.00
90 A 900 A 1700 A FAL12090 261.00 FAL22090 543.00 FAL32090 704.00
100 A 900 A 1700 A FAL12100 261.00 FAL22100 543.00 FAL32100 704.00
Table 3.27: F-Frame—100 A, Thermal-Magnetic, Individually-Mounted, 480 Vac
Standard Interrupting
Ampere
Rating
Fixed AC Magnetic
Trip
1P 2P 3P Terminal
Wire Range
(AWG)
277 Vac, 125 Vdc 480 Vac, 250 Vdc 480 Vac, 250 Vdc
Hold Trip Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
15 A 275 A 600 A FAL14015 251.00 FAL24015 609.00 FAL34015 782.00
AL50FA
(1) 14–4 Cu or
(1) 12–4 Al
20 A 275 A 600 A FAL14020 251.00 FAL24020 609.00 FAL34020 782.00
25 A 275 A 600 A FAL14025 251.00 FAL24025 609.00 FAL34025 782.00
30 A 275 A 600 A FAL14030 251.00 FAL24030 609.00 FAL34030 782.00
35 A 400 A 850 A FAL14035 251.00 FAL24035 609.00 FAL34035 782.00
AL100FA
(1) 14–1/0 Cu
or (1) 12–1/0 Al
40 A 400 A 850 A FAL14040 251.00 FAL24040 609.00 FAL34040 782.00
45 A 400 A 850 A FAL14045 251.00 FAL24045 609.00 FAL34045 782.00
50 A 400 A 850 A FAL14050 251.00 FAL24050 609.00 FAL34050 782.00
60 A 800 A 1450 A FAL14060 251.00 FAL24060 609.00 FAL34060 782.00
70 A 800 A 1450 A FAL14070 312.00 FAL24070 788.00 FAL34070 924.00
80 A 800 A 1450 A FAL14080 312.00 FAL24080 788.00 FAL34080 924.00
90 A 900 A 1700 A FAL14090 312.00 FAL24090 788.00 FAL34090 924.00
100 A 900 A 1700 A FAL14100 312.00 FAL24100 788.00 FAL34100 924.00
Table 3.28: F-Frame—100 A, Thermal-Magnetic, Individually-Mounted, 600 Vac
Ampere
Rating
Fixed AC
Magnetic
Trip
Standard Interrupting High Interrupting Current Limiting
Terminal
Wire Range
(AWG)
2P 3P 1P 2P 3P 2P 3P
600 Vac, 250 Vdc 600 Vac, 250 Vdc 277 Vac, 125 Vdc 600 Vac, 250 Vdc 600 Vac, 250 Vdc 600 Vac, 250 Vdc 600 Vac, 250 Vdc
Hold Trip Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
15 A 275 A 600 A FAL26015 704.00 FAL36015 906.00 FHL16015 452.00 FHL26015 1163.00 FHL36015 1358.00 ——
AL50FA
14–4 Cu or
12–4 Al
20 A 275 A 600 A FAL26020 704.00 FAL36020 906.00 FHL16020 452.00 FHL26020 1163.00 FHL36020 1358.00 FIL26020 2633.00 FIL36020 3296.00
25 A 275 A 600 A FAL26025 704.00 FAL36025 906.00 FHL16025 452.00 FHL26025 1163.00 FHL36025 1358.00 FIL26025 2633.00 FIL36025 3296.00
30 A 275 A 600 A FAL26030 704.00 FAL36030 906.00 FHL16030 452.00 FHL26030 1163.00 FHL36030 1358.00 FIL26030 2633.00 FIL36030 3296.00
35 A 400 A 850 A FAL26035 704.00 FAL36035 906.00 FHL16035 452.00 FHL26035 1163.00 FHL36035 1358.00 FIL26035 2633.00 FIL36035 3296.00
AL100FA
14–1/0 Cu
or 12–1/0 Al
40 A 400 A 850 A FAL26040 704.00 FAL36040 906.00 FHL16040 452.00 FHL26040 1163.00 FHL36040 1358.00 FIL26040 2633.00 FIL36040 3296.00
45 A 400 A 850 A FAL26045 704.00 FAL36045 906.00 FHL16045 452.00 FHL26045 1163.00 FHL36045 1358.00 FIL26045 2633.00 FIL36045 3296.00
50 A 400 A 850 A FAL26050 704.00 FAL36050 906.00 FHL16050 452.00 FHL26050 1163.00 FHL36050 1358.00 FIL26050 2633.00 FIL36050 3296.00
60 A 800 A 1450 A FAL26060 704.00 FAL36060 906.00 FHL16060 452.00 FHL26060 1163.00 FHL36060 1358.00 FIL26060 2633.00 FIL36060 3296.00
70 A 800 A 1450 A FAL26070 890.00 FAL36070 1115.00 FHL16070 509.00 FHL26070 1353.00 FHL36070 1541.00 FIL26070 2633.00 FIL36070 3296.00
80 A 800 A 1450 A FAL26080 890.00 FAL36080 1115.00 FHL16080 509.00 FHL26080 1353.00 FHL36080 1541.00 FIL26080 2633.00 FIL36080 3296.00
90 A 900 A 1700 A FAL26090 890.00 FAL36090 1115.00 FHL16090 509.00 FHL26090 1353.00 FHL36090 1541.00 FIL26090 2633.00 FIL36090 3296.00
100 A 900 A 1700 A FAL26100 890.00 FAL36100 1115.00 FHL16100 509.00 FHL26100 1353.00 FHL36100 1541.00 FIL26100 2633.00 FIL36100 3296.00
Table 3.29: Interrupting Ratings
Vol tage FA L FHL FCLa FIL
240 Vac 480 Vac 600 Vac
240 Vac 10 kA 18 kA (1P), 25 kA (2P, 3P) 25 kA 25 kA (1P) 65 kA (2P, 3P) 100 kA 200 kA
480 Vac — 18 kA 18 kA 25 kA (2P, 3P) 65 kA 200 kA
600 Vac — — 14 kA 18 kA (2P, 3P) — 100 kA
Table 3.30: Termination Option
Termination Letter
F = No Lugs
L = Lugs both ends
P with MT Suffix = Lugs ON end
P = Lugs OFF end
F A L 3 6 1 0 0
For factory-installed termination, place
termination letter in the third block of the
circuit breaker catalog number.
Termination Letter
DE2 Discount
Schedule
www.schneider-electric.us
3-8 © 2012 Schneider Electric
All Rights Reserved
3MOLDED CASE CIRCUIT
BREAKERS
Molded Case Circuit
Breakers
F-Frame Thermal-Magnetic Circuit Breakers
Class 650
NOTE: Consider using PowerPact™ circuit breakers for situations requiring circuit breaker
accessories. See Digest Section 7 for more information.
.
eSee Section 11.
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 3-24—3-27
Optional Lugs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 3-28—3-29
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-33
Enclosures: see Digest Section 7
Table 3.31: F-Frame—100 A, Thermal-Magnetic, I-Line™ Construction, 240 Vac,
Standard Interrupting
Ampere
Rating
Fixed AC Magnetic
Trip
2 Pa3 P Terminal
Wire Range
(AWG)
240 Vac 240 Vac
Hold Trip Cat. No. $ Price Cat. No. $ Price
15 A 275 A 600 A FA22015( ) 398.00 FA32015 572.00
AL50FA
14–4 Cu or
12–4 Al
20 A 275 A 600 A FA22020( ) 398.00 FA32020 572.00
25 A 275 A 600 A FA22025( ) 398.00 FA32025 572.00
30 A 275 A 600 A FA22030( ) 398.00 FA32030 572.00
35 A 400 A 850 A FA22035( ) 398.00 FA32035 572.00
AL100FA
14–1/0 Cu
or 12–1/0 Al
40 A 400 A 850 A FA22040( ) 398.00 FA32040 572.00
45 A 400 A 850 A FA22045( ) 398.00 FA32045 572.00
50 A 400 A 850 A FA22050( ) 398.00 FA32050 572.00
60 A 800 A 1450 A FA22060( ) 398.00 FA32060 572.00
70 A 800 A 1450 A FA22070( ) 617.00 FA32070 780.00
80 A 800 A 1450 A FA22080( ) 617.00 FA32080) 780.00
90 A 900 A 1700 A FA22090( ) 617.00 FA32090 780.00
100 A 900 A 1700 A FA22100( ) 617.00 FA32100 780.00
Table 3.32: F-Frame—100 A, Thermal-Magnetic, I-Line™ Construction, 480 Vac
Ampere
Rating
Fixed AC Magnetic
Trip
Standard Interrupting
1Pad 2Pa3P Terminal
Wire Range
(AWG)
277 Vac, 125 Vdc 480 Vac, 250 Vdc 480 Vac, 250 Vdc
Hold Trip Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
15 A 275 A 600 A — — FA24015( ) 651.00 FA34015 833.00
AL50FA
(1) 14–4 Cu or
(1) 12–4 Al
20 A 275 A 600 A — — FA24020( ) 651.00 FA34020 833.00
25 A 275 A 600 A — — FA24025( ) 651.00 FA34025 833.00
30 A 275 A 600 A — — FA24030( ) 651.00 FA34030 833.00
35 A 400 A 850 A FA14035( ) 302.00 FA24035( ) 651.00 FA34035 833.00
AL100FA
(1) 14–1/0 Cu
or (1) 12–1/0 Al
40 A 400 A 850 A FA14040( ) 302.00 FA24040( ) 651.00 FA34040 833.00
45 A 400 A 850 A FA14045( ) 302.00 FA24045( ) 651.00 FA34045 833.00
50 A 400 A 850 A FA14050( ) 302.00 FA24050( ) 651.00 FA34050 833.00
60 A 800 A 1450 A FA14060( ) 302.00 FA24060( ) 651.00 FA34060 833.00
70 A 800 A 1450 A FA14070( ) 332.00 FA24070( ) 833.00 FA34070 996.00
80 A 800 A 1450 A FA14080( ) 332.00 FA24080( ) 833.00 FA34080 996.00
90 A 900 A 1700 A FA14090( ) 332.00 FA24090( ) 833.00 FA34090 996.00
100 A 900 A 1700 A FA14100( ) 332.00 FA24100( ) 833.00 FA34100 996.00
FA 1P
1.5 in. (38 mm)
Mounting Height
FA 2P
3 in. (76 mm)
Mounting Height
FA 3P
4.5 in. (114 mm)
Mounting Height
Table 3.33: F-Frame—100 A, Thermal-Magnetic, I-Line™ Construction, 600 Vac
Ampere
Rating
Fixed AC
Magnetic
Trip
Standard Interrupting High Interrupting Current Limiting
2Pa3 P 1Pad 2Pa3P 2Pa3P Terminal
Wire Range
(AWG)
600 Vac. 250 Vdc 600 Vac. 250 Vdc 277 Vac, 125 Vdc 600 Vac. 250 Vdc 600 Vac. 250 Vdc 600 Vac. 250 Vdc 600 Vac. 250 Vdc
Hold Trip Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
15 A 275 A 600 A FA26015( ) 780.00 FA36015 971.00 FH16015( ) 507.00 FH26015( ) 1214.00 FH36015 1446.00 ————
AL50FA
14–4 Cu or
12–4 Al
20 A 275 A 600 A FA26020( ) 780.00 FA36020 971.00 FH16020( ) 507.00 FH26020( ) 1214.00 FH36020 1446.00 FI26020( ) 2763.00 FI36020 3296.00
25 A 275 A 600 A FA26025( ) 780.00 FA36025 971.00 FH16025( ) 507.00 FH26025( ) 1214.00 FH36025 1446.00 ————
30 A 275 A 600 A FA26030( ) 780.00 FA36030 971.00 FH16030( ) 507.00 FH26030( ) 1214.00 FH36030 1446.00 FI26030( ) 2763.00 FI36030 3296.00
35 A 400 A 850 A FA26035( ) 780.00 FA36035 971.00 FH16035( ) 507.00 FH26035( ) 1214.00 FH36035 1446.00 ————
AL100FA
14–1/0 Cu
or 12–1/0 Al
40 A 400 A 850 A FA26040( ) 780.00 FA36040 971.00 FH16040( ) 507.00 FH26040( ) 1214.00 FH36040 1446.00 FI26040( ) 2763.00 FI36040 3296.00
45 A 400 A 850 A FA26045( ) 780.00 FA36045 971.00 FH16045( ) 507.00 FH26045( ) 1214.00 FH36045 1446.00 ————
50 A 400 A 850 A FA26050( ) 780.00 FA36050 971.00 FH16050( ) 507.00 FH26050( ) 1214.00 FH36050 1446.00 FI26050( ) 2763.00 FI36050 3296.00
60 A 800 A 1450 A FA26060( ) 780.00 FA36060 971.00 FH16060( ) 507.00 FH26060( ) 1214.00 FH36060 1446.00 FI26060( ) 2763.00 FI36060 3296.00
70 A 800 A 1450 A FA26070( ) 947.00 FA36070 1163.00 FH16070( ) 563.00 FH26070( ) 1452.00 FH36070 1632.00 FI26070( ) 2763.00 FI36070 3296.00
80 A 800 A 1450 A FA26080( ) 947.00 FA36080 1163.00 FH16080( ) 563.00 FH26080( ) 1452.00 FH36080 1632.00 FI26080( ) 2763.00 FI36080 3296.00
90 A 900 A 1700 A FA26090( ) 947.00 FA36090 1163.00 FH16090( ) 563.00 FH26090( ) 1452.00 FH36090 1632.00 FI26090( ) 2763.00 FI36090 3296.00
100 A 900 A 1700 A FA26100( ) 947.00 FAL6100 1163.00 FH16100( ) 563.00 FH26100( ) 1452.00 FH36100 1632.00 FI26100( ) 2763.00 FI36100 3296.00
a1P and 2P circuit breaker catalog numbers are completed by adding the required phase connection letters as a suffix. See Phase Option Table.
bFCL 2P circuit breakers are built using 3P module.
cFCL circuit breakers are not rated for 250 Vdc.
dRated 277 Vac, 125 Vdc. 15–30 A circuit breaker suitable for use with 60°C or 75 °C conductors. 35–100 A circuit breakers are suitable for use with 75°C conductors.
Table 3.34: Phase Options
Phase Option
Letter 1P 2P 3P
A
B
C
FA14035A
FA14035B
FA14035C
AB
AC
BC
FA24030AB
FA24030AC
FA24030BC
ABC
CBA
FA34030
FA34030CBA
Table 3.35: Interrupting Ratings
Voltage FA FH FCeFI
240 Vac 480 Vac 600 Vac
240 Vac 10 kA 18 kA (1P), 25 kA (2P, 3P) 25 kA 25 kA (1P) 65 kA (2P, 3P) 100 kA 200 kA
277 Vac — 18 kA — — 65 kA —
480 Vac — 18 kA 18 kA 25 kA (2P, 3P) 65 kA 200 kA
600 Vac — — 14 kA 18 kA (2P, 3P) — 100 kA
DE2 Discount
Schedule
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
© 2012 Schneider Electric
All Rights Reserved 3-9
Molded Case Circuit
Breakers
K- and Q4-Frame Thermal-Magnetic Circuit Breakers
Class 655, 825, 660
NOTE: Consider using PowerPact™ circuit breakers for situations requiring circuit breaker accessories. See Digest
Section 7 for more information.
aUL magnetic trip setting tolerances are ±25% for low and ±20% for high from nominal value shown.
bKC circuit breakers are 480 Vac
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-25
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-28
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-33
Enclosures: see Digest Section 7
Table 3.36: K-Frame—250 A, Thermal-Magnetic, Individually-Mounted, 600 Vac
Ampere
Rating
Adjustable AC Magnetic TripaCurrent Limiting Terminal
Wire Range
Low High Cat. No. $ Price
2P, 600 Vac, 250 Vdc
110 550 A 1100 A KIL26110 6177.00
AL250KA
(1) 4 AWG–350 kcmil Al
125 625 A 1250 A KIL26125 6177.00
150 750 A 1500 A KIL26150 6177.00
175 875 A 1750 A KIL26175 6177.00
200 1000 A 2000 A KIL26200 6177.00 AL250KI
(1) 1/0 AWG–350 kcmil Al
225 1125 A 2250 A KIL26225 6177.00
250 1250 A 2500 A KIL26250 7223.00
3P, 600 Vac, 250 Vdc
110 550 A 1100 A KIL36110 7754.00
AL250KA
(1) 4 AWG–350 kcmil Al
125 625 A 1250 A KIL36125 7754.00
150 750 A 1500 A KIL36150 7754.00
175 875 A 1750 A KIL36175 7754.00
200 1000 A 2000 A KIL36200 7754.00 AL250KI
(1) 1/0 AWG–350 kcmil Al
225 1125 A 2250 A KIL36225 7754.00
250 1250 A 2500 A KIL36250 9081.00
Table 3.37: Q4-Frame—400 A, Thermal-Magnetic, Individually-Mounted, 240 Vac
Ampere
Rating
Adjustable AC Magnetic TripaStandard Interrupting Terminal
Wire Range
Low High Cat. No. $ Price
2P, 240 Vac
250 1250 A 2500 A Q4L2250 3171.00 AL400LA
(1) 1 AWG–600 kcmil Al
or
(2) 1 AWG–250 kcmil Al
300 1500 A 3000 A Q4L2300 3171.00
350 1750 A 3500 A Q4L2350 3171.00
400 2000 A 4000 A Q4L2400 3171.00
3P, 240 Vac
250 1250 A 2500 A Q4L3250 3831.00 AL400LA
(1) 1 AWG–600 kcmil Al
or
(2) 1 AWG–250 kcmil Al
300 1500 A 3000 A Q4L3300 3831.00
350 1750 A 3500 A Q4L3350 3831.00
400 2000 A 4000 A Q4L3400 3831.00
Table 3.38: Interrupting Ratings
Vol tage KIL Q4
240 Vac 200 kA 25 kA
480 Vac 200 kA —
600 Vac 100 kA —
KAL/KHL
2P and 3P
70–250 A
KIL36250
Q4L
2P and 3P
250–400 A
DE2 Discount
Schedule
3-10 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
Molded Case Circuit
Breakers
K- and Q4-Frame Thermal-Magnetic Circuit Breakers
Class 655, 825, 660
NOTE: Consider using PowerPact™ circuit breakers for situations requiring circuit breaker accessories. See Digest
Section 7 for more information.
aUL magnetic trip setting tolerances are ±25% for low and ±20% for high from nominal value shown.
bKC circuit breakers are 480 Vac
c2P and 3P circuit breaker catalog numbers are completed by adding the required phase connection letters as a suffix. See Phase Option Table.
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-25
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-28
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-33
Enclosures: see Digest Section 7
Table 3.39: K-Frame—250A, Thermal-Magnetic, I-Line™ Construction, 600 Vac
Ampere
Rating
Adjustable AC Magnetic TripaCurrent
Limiting Terminal
Wire Range
Low High Cat. No. $ Price
2P, 600 Vac, 250 Vdcc
110 550 A 1100 A KI26110( ) 6633.00
AL250KA
(1) 4 AWG–350 kcmil Al
125 625 A 1250 A KI26125( ) 6633.00
150 750 A 1500 A KI26150( ) 6633.00
175 875 A 1750 A KI26175( ) 6633.00
200 1000 A 2000 A KI26200( ) 6633.00 AL250KI
(1) 1/0 AWG–350 kcmil Al
225 1125 A 2250 A KI26225( ) 6633.00
250 1250 A 2500 A KI26250( ) 7704.00
3P, 600 Vac, 250 Vdc
110 550 A 1100 A KI36110 8375.00
AL250KA
(1) 4 AWG–350 kcmil Al
125 625 A 1250 A KI36125 8375.00
150 750 A 1500 A KI36150 8375.00
175 875 A 1750 A KI36175 8375.00
200 1000 A 2000 A KI36200 8375.00 AL250KI
(1) 1/0 AWG–350 kcmil Al
225 1125 A 2250 A KI36225 8375.00
250 1250 A 2500 A KI36250 9267.00
Table 3.40: Q4-Frame—400 A, Thermal-Magnetic, I-Line™ Construction, 240 Vac
Ampere
Rating
Adjustable AC Magnetic TripaStandard Interrupting Terminal
Wire Range
Low High Cat. No. $ Price
2P, 240 Vacc
250 1250 A 2500 A Q422250( ) 3435.00 AL400LA
(1) 1 AWG–600 kcmil Al
or
(2) 1 AWG–250 kcmil Al
300 1500 A 3000 A Q422300( ) 3435.00
350 1750 A 3500 A Q422350( ) 3435.00
400 2000 A 4000 A Q422400( ) 3435.00
3P, 240 Vac
250 1250 A 2500 A Q43250 4313.00 AL400LA
(1) 1 AWG–600 kcmil Al
or
(2) 1 AWG–250 kcmil Al
300 1500 A 3000 A Q43300 4313.00
350 1750 A 3500 A Q43350 4313.00
400 2000 A 4000 A Q43400 4313.00
Table 3.41: Interrupting Ratings
Voltage KI Q4
240 Vac 200 kA 25 kA
480 Vac 200 kA —
600 Vac 100 kA —
Table 3.42: Phase Options
Phase Option Letter 2P 3P
AB
AC
BC
KA26250AB
KA26250AC
KA26250BC
ABC
CBA
KA36250
KA36250CBA
Q4 2P and 3P
6 in. (152 mm)
Mounting Height
KI 2P and 3P
4.5 in. (114 mm)
Mounting Height
DE2 Discount
Schedule
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
© 2012 Schneider Electric
All Rights Reserved 3-11
Molded Case Circuit
Breakers
L-Frame Thermal-Magnetic Circuit Breakers
Class 600, 665, 736, 830
NOTE: Consider using PowerPact™ circuit breakers for situations requiring circuit breaker accessories. See Digest
Section 7 for more information.
aAC magnetic setting tolerances are +0–25% from max. value shown.
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-24—3-27
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-28—3-29
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-33
Enclosures: see Digest Section 7
Table 3.43: L-Frame—400 A, Thermal-Magnetic, Individually-Mounted, High Magnetic Withstand Circuit
Breakers For Mission Critical Loads
Ampere
Rating
AC Magnetic Level
Factory Seta
Standard Interrupting High Interrupting Terminal
Wire Range
Cat. No. $ Price Cat. No. $ Price
LA/LH MC Circuit Breaker, 3P, 480 Vac
200 A 4000 A LAL34200MC 4962.00 LHL34200MC 7941.00 AL250LA
(1) 4 AWG–350 kcmil Al
225 A 4500 A LAL34225MC 4962.00 LHL34225MC 7941.00
250 A 5000 A LAL34250MC 5355.00 LHL34250MC 8336.00
400 A 8000 A LAL34400MC 6615.00 LHL34400MC 9596.00
AL400LA
(1) 1 AWG–600 kcmil Al or
(2) 1 AWG–250 kcmil Al
Table 3.44: L-Frame—600 A, Thermal-Magnetic, Individually-Mounted Circuit Breakers, 600 Vac
Ampere
Rating
Adjustable AC
Magnetic Trip Standard Interrupting High Interrupting Terminal
Wire Range
Low High Cat. No. $ Price Cat. No. $ Price
2P, 600 Vac, 250 Vdc
125 A
150 A
175 A
200 A
225 A
250 A
625 A
750 A
875 A
1000 A
1125 A
1250 A
1250 A
1500 A
1750 A
2000 A
2250 A
2500 A
LAL26125
LAL26150
LAL26175
LAL26200
LAL26225
LAL26250
3807.00
3807.00
3807.00
3807.00
3807.00
3807.00
LHL26125
LHL26150
LHL26175
LHL26200
LHL26225
LHL26250
6362.00
6362.00
6362.00
6362.00
6362.00
6362.00
AL400LA
(1) 1 AWG–600 kcmil Al
or
(2) 1 AWG–250 kcmil Al
300 A
350 A
400 A
1500 A
1750 A
2000 A
3000 A
3500 A
4000 A
LAL26300
LAL26350
LAL26400
3807.00
3807.00
3807.00
LHL26300
LHL26350
LHL26400
6362.00
6362.00
6362.00
3P, 600 Vac, 250 Vdc
125 A
150 A
175 A
200 A
225 A
250 A
625 A
750 A
875 A
1000 A
1125 A
1250 A
1250 A
1500 A
1750 A
2000 A
2250 A
2500 A
LAL36125
LAL36150
LAL36175
LAL36200
LAL36225
LAL36250
4619.00
4619.00
4619.00
4619.00
4619.00
4619.00
LHL36125
LHL36150
LHL36175
LHL36200
LHL36225
LHL36250
7598.00
7598.00
7598.00
7598.00
7598.00
7598.00
AL400LA
(1) 1 AWG–600 kcmil Al
or
(2) 1 AWG–250 kcmil Al
300 A
350 A
400 A
1500 A
1750 A
2000 A
3000 A
3500 A
4000 A
LAL36300
LAL36350
LAL36400
4619.00
4619.00
4619.00
LHL36300
LHL36350
LHL36400
7598.00
7598.00
7598.00
Table 3.45: L-Frame—600 A, Current-Limiting, Individually-Mounted Circuit Breakers, 600 Vac
Ampere
Rating
Adjustable AC
Magnetic Trip Extra-High Interrupting Current Limiting Terminal
Wire Range
Low High Cat. No. $ Price Cat. No. $ Price
2P, 600 Vac
300 A
350 A
400 A
1500 A
1750 A
2000 A
3200 A
3200 A
3200 A
LCL26300
LCL26350
LCL26400
7479.00
7479.00
7479.00
LIL26300
LIL26350
LIL26400
8604.00
8604.00
8604.00 AL600LI5
(2) 4/0 AWG–500 kcmil Al
450 A
500 A
600 A
2250 A
2500 A
3000 A
4200 A
4200 A
4200 A
LCL26450
LCL26500
LCL26600
7823.00
7823.00
7823.00
LIL26450
LIL26500
LIL26600
12551.00
12551.00
12551.00
3P, 600 Vac
300 A
350 A
400 A
1500 A
1750 A
2000 A
3200 A
3200 A
3200 A
LCL36300
LCL36350
LCL36400
8312.00
8312.00
8312.00
LIL36300
LIL36350
LIL36400
9563.00
9563.00
9563.00 AL600LI5
(2) 4/0 AWG–500 kcmil Al
450 A
500 A
600 A
2250 A
2500 A
3000 A
4200 A
4200 A
4200 A
LCL36450
LCL36500
LCL36600
8691.00
8691.00
8691.00
LIL36450
LIL36500
LIL36600
13949.00
13949.00
13949.00
Table 3.46: Interrupting Ratings
Voltage LAL LHL LCL LIL
240 Vac 42 kA 65 kA 100 kA 200 kA
480 Vac 30 kA 35 kA 65 kA 200 kA
600 Vac 22 kA 25 kA 35 kA 100 kA
LAL/LHL MC
For Mission Critical
Power Loads
available in 200, 225, 250,
and 400 A @ 480 Vac
LIL36600
2P and 3P 300–600 A
LAL/LHL
2P and 3P
125–400 A
DE2 Discount
Schedule
3-12 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
Molded Case Circuit
Breakers
L-Frame Thermal-Magnetic Circuit Breakers
Class 600, 665, 736, 830
NOTE: Consider using PowerPact™ circuit breakers for situations requiring circuit breaker accessories. See Digest
Section 7 for more information.
aFactory set AC magnetic setting tolerances are +0–25% from max. value shown.
a2P and 3P circuit breaker catalog numbers are completed by adding the required phase connection letters as a suffix. See Phase Option Table.
bUL magnetic trip setting tolerances are ±25% for low and ±20% for high from nominal value.
ccessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-24—3-27
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-28—3-29
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-33
Enclosures: see Digest Section 7
Table 3.47: L-Frame—400 A, Thermal-Magnetic, I-Line™ Construction, High Magnetic Withstand Circuit
Breakers For Mission Critical Loads
Ampere
Rating
AC Magnetic Level
Factory Seta
Standard Interrupting High Interrupting Terminal
Wire Range
Cat. No. $ Price Cat. No. $ Price
LA/LH MC Circuit Breaker, 3P, 480 Vac
200 A 4000 A LA34200MC 5571.00 LH34200MC 8771.00 AL250LA
(1) 4 AWG–350 kcmil Al
225 A 4500 A LA34225MC 5571.00 LH34225MC 8771.00
250 A 5000 A LA34250MC 5681.00 LH34250MC 8882.00
400 A 8000 A LA34400MC 7241.00 LH34400MC 10142.00
AL400LA
(1) 1 AWG–600 kcmil Al or
(2) 1 AWG–250 kcmil Al
Table 3.48: L-Frame—600 A, Thermal-Magnetic I-Line™ Construction Circuit Breakers, 600 Vac
Ampere
Rating
Adjustable AC
Magnetic TripbStandard Interrupting High Interrupting Terminal
Wire Range
Low High Cat. No. $ Price Cat. No. $ Price
2P, 600 Vac, 250 Vdca
125 A
150 A
175 A
200 A
225 A
250 A
625 A
750 A
875 A
1000 A
1125 A
1250 A
1250 A
1500 A
1750 A
2000 A
2250 A
2500 A
LA26125( )
LA26150( )
LA26175( )
LA26200( )
LA26225( )
LA26250( )
4053.00
4053.00
4053.00
4053.00
4053.00
4053.00
LH26125( )
LH26150( )
LH26175( )
LH26200( )
LH26225( )
LH26250( )
6762.00
6762.00
6762.00
6762.00
6762.00
6762.00
AL400LA
(1) 1 AWG–600 kcmil Al
or
(2) 1 AWG–250 kcmil Al
300 A
350 A
400 A
1500 A
1750 A
2000 A
3000 A
3500 A
4000 A
LA26300( )
LA26350( )
LA26400( )
4053.00
4053.00
4053.00
LH26300( )
LH26350( )
LH26400( )
6762.00
6762.00
6762.00
3P, 600 Vac, 250 Vdc
125 A
150 A
175 A
200 A
225 A
250 A
625 A
750 A
875 A
1000 A
1125 A
1250 A
1250 A
1500 A
1750 A
2000 A
2250 A
2500 A
LA36125
LA36150
LA36175
LA36200
LA36225
LA36250
4944.00
4944.00
4944.00
4944.00
4944.00
4944.00
LH36125
LH36150
LH36175
LH36200
LH26225
LH36250
8145.00
8145.00
8145.00
8145.00
8145.00
8145.00
AL400LA
(1) 1 AWG–600 kcmil Al
or
(2) 1 AWG–250 kcmil Al
300 A
350 A
400 A
1500 A
1750 A
2000 A
3000 A
3500 A
4000 A
LA36300
LA36350
LA36400
4944.00
4944.00
4944.00
LH36300
LH36350
LH36400
8145.00
8145.00
8145.00
Table 3.49: L-Frame—600 A, Current-Limiting, I-Line™ Construction, Circuit Breakers, 600 Vac
Ampere
Rating
Adjustable AC
Magnetic TripbExtra-High Interrupting Current Limiting Terminal
Wire Range
Low High Cat. No. $ Price Cat. No. $ Price
2P, 600 Vaca
300 A
350 A
400 A
1500 A
1750 A
2000 A
3200 A
3200 A
3200 A
LC26300( )
LC26350( )
LC26400( )
8312.00
8312.00
8312.00
LI26300( )
LI26350( )
LI26400( )
9563.00
9563.00
9563.00 AL600LI5
(2) 4/0 AWG–500 kcmil Al
450 A
500 A
600 A
2250 A
2500 A
3000 A
4200 A
4200 A
4200 A
LC26450( )
LC26500( )
LC26600( )
8691.00
8691.00
8691.00
LI26450( )
LI26500( )
LI26600( )
13949.00
13949.00
13949.00
3P, 600 Vac
300 A
350 A
400 A
1500 A
1750 A
2000 A
3200 A
3200 A
3200 A
LC36300
LC36350
LC36400
9234.00
9234.00
9234.00
LI36300
LI36350
LI36400
10673.00
10673.00
10673.00 AL600LI5
(2) 4/0 AWG–500 kcmil Al
450 A
500 A
600 A
2250 A
2500 A
3000 A
4200 A
4200 A
4200 A
LC36450
LC36500
LC36600
9657.00
9657.00
9657.00
LI36450
LI36500
LI36600
15498.00
15498.00
15498.00
Table 3.50: Interrupting Ratings
Voltage LA LH LC LI
240 Vac 42 kA 65 kA 100 kA 200 kA
480 Vac 30 kA 35 kA 65 kA 200 kA
600 Vac 22 kA 25 kA 35 kA 100 kA
Table 3.51: Phase Options
Phase Option Letter 2P 3P
AB
AC
BC
LA26400AB
LA26400AC
LA26400BC
ABC
CBA
LA36400
LA36400CBA
LA / LH 2P and 3P
6 in. (152 mm)
Mounting Height
LC 2P and 3P
7.5 in. (190 mm)
Mounting Height
LI 2P and 3P
7.5 in. (190 mm)
Mounting Height
DE2 Discount
Schedule
www.schneider-electric.us
© 2012 Schneider Electric
All Rights Reserved 3-13
3MOLDED CASE CIRCUIT
BREAKERS
Molded Case Circuit
Breakers
L-Frame Micrologic™ Series B Trip Circuit Breakers
NOTE: Consider using PowerPact™ circuit breakers for situations
requiring circuit breaker accessories. See Digest Section 7 for
more information.
Standard-Function Features:
•80% rated
•True RMS sensing
•Interchangeable rating plugs
•LSI, LS(I)G, trip configurations
•Short-time delay = I2t IN and ground-fault delay = I2t OUT
•Integral ground-fault testing
•LED long-time pickup indication
•Thermal & magnetic backup protection
•Long-time & ground-fault memory
•Optional local trip indicators—overload, short circuit, ground-fault
•Optional local ammeter/trip indicator
•Universal test set available
•Optional I-Line™ mounting (LX, LXI)
•Optional neutral current transformer for 4-wire systems
Full-Function Features:
•100% rated (600 sensor LE/LEL) circuit breakers are 80% rated)
•True RMS sensing
•Interchangeable rating plugs
•PowerLogic™ compatible
•LI, LIG, LS(I), LS(I)G (instantaneous OFF) configurations
•Short-time delay = I2t IN & I2t OUT and ground-fault delay = I2t IN & I2t OUT
•Short-time withstand rating
•Integral ground-fault testing
•Optional ground-fault alarm (no trip) (Requires CIM3F with PowerLogic, see
Bulletin 0502DB0001.)
•LED long-time pickup indication
•Zone-selective interlocking (short-time & ground-fault)
•Long-time & ground-fault memory
•Local Trip Indicators—overload, short circuit, ground-fault
•Local ammeter/trip indicator
•Universal test set available
•Optional I-Line™ mounting (LE)
•Optional neutral current transformer for 4-wire systems
Table 3.52: L-Frame—600 A, Micrologic Series B Trip System, Individually-Mounted, 3P, 600 Vac
Sensor
Size
Ampere
Rating
Trip
Function
Standard Function Standard Function
Current Limiting
100% Rated
Full FunctionbInstalled
Rating
Plug
Terminal
Wire Range
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
250
100
LI — — — — LEL36100LI 7692.00
ARP040
AL600LI35
(2) 1 AWG–350 kcmil
Al/Cu
LSI LXL36100 5616.00 LXIL36100 11262.00 LEL36100LS 13035.00
LIG — — — — LEL36100LIG 9768.00
LSIG LXL36100G 7692.00 LXIL36100G 13338.00 LEL36100LSG 15111.00
125
LI — — — — LEL36125LI 7692.00
ARP050
LSI LXL36125 5616.00 LXIL36125 11262.00 LEL36125LS 13035.00
LIG — — — — LEL36125LIG 9768.00
LSIG LXL36125G 7692.00 LXIL36125G 13338.00 LEL36125LSG 15111.00
150
LI — — — — LEL36150LI 7692.00
ARP060
LSI LXL36150 5616.00 LXIL36150 11262.00 LEL36150LS 13035.00
LIG — — — — LEL36150LIG 9768.00
LSIG LXL36150G 7692.00 LXIL36150G 13338.00 LEL36150LSG 15111.00
175
LI — — — — LEL36175LI 7692.00
ARP070
LSI LXL36175 5616.00 LXIL36175 11262.00 LEL36175LS 13035.00
LIG — — — — LEL36175LIG 9768.00
LSIG LXL36175G 7692.00 LXIL36175G 13338.00 LEL36175LSG 15111.00
200
LI — — — — LEL36200LI 7692.00
ARP080
LSI LXL36200 5616.00 LXIL36200 11262.00 LEL36200LS 13035.00
LIG — — — — LEL36200LIG 9768.00
LSIG LXL36200G 7692.00 LXIL36200G 13338.00 LEL36200LSG 15111.00
225
LI — — — — LEL36225LI 7692.00
ARP090
LSI LXL36225 5616.00 LXIL36225 11262.00 LEL36225LS 13035.00
LIG — — — — LEL36225LIG 9768.00
LSIG LXL36225G 7692.00 LXIL36225G 13338.00 LEL36225LSG 15111.00
250
LI — — — — LEL36250LI 7692.00
ARP100
LSI LXL36250 5616.00 LXIL36250 11262.00 LEL36250LS 13035.00
LIG — — — — LEL36250LIG 9768.00
LSIG LXL36250G 7692.00 LXIL36250G 13338.00 LEL36250LSG 15111.00
400
300
LI — — — — LEL36300LI 10691.00
ARP075
AL600LI5
(2) 4/0 AWG– 500 kcmil
Al/Cu
LSI LXL36300 8618.00 LXIL36300 16400.00 LEL36300LS 16034.00
LIG — — — — LEL36300LIG 12767.00
LSIG LXL36300G 10694.00 LXIL36300G 18476.00 LEL36300LSG 18110.00
350
LI — — — — LEL36350LI 10691.00
ARP088
LSI LXL36350 8618.00 LXIL36350 16400.00 LEL36350LS 16034.00
LIG — — — — LEL36350LIG 12767.00
LSIG LXL36350G 10694.00 LXIL36350G 18476.00 LEL36350LSG 18110.00
400
LI — — — — LEL36400LI 10691.00
ARP100
LSI LXL36400 8618.00 LXIL36400 16400.00 LEL36400LS 16034.00
LIG — — — — LEL36400LIG 12767.00
LSIG LXL36400G 10694.00 LXIL36400G 18476.00 LEL36400LSG 18110.00
600
450
LI — — — — LEL36450LI 14688.00
ARP075
LSI LXL36450 12611.00 LXIL36450 23250.00 LEL36450LS 20031.00
LIG — — — — LEL36450LIG 16764.00
LSIG LXL36450G 14687.00 LXIL36450G 25326.00 LEL36450LSG 22107.00
500
LI — — — — LEL36500LI 14688.00
ARP083
LSI LXL36500 12611.00 LXIL36500 23250.00 LEL36500LS 20031.00
LIG — — — — LEL36500LIG 16764.00
LSIG LXL36500G 14687.00 LXIL36500G 25326.00 LEL36500LSG 22107.00
600
LI — — — — LEL36600LI 14688.00
ARP100
LSI LXL36600 12611.00 LXIL36600 23250.00 LEL36600LS 20031.00
LIG — — — — LEL36600LIG 16764.00
LSIG LXL36600G 14687.00 LXIL36600G 25326.00 LEL36600LSG 22107.00
a600 A sensor is 80% rated
bSubstitute (A) in place of (G) for ground-fault alarm (pickup indication only).
Requires CIM3F and Powerlogic, or see Data Bulletin 0502DB0001. No
instantaneous OFF position for LI or LIG trip function type circuit breakers.
NOTE: Consider using PowerPact™ circuit breakers for situations
requiring circuit breaker accessories.
Table 3.53: Interrupting Ratings
Voltage LXL LEL LXIL
240 V 100 kA 100 kA 200 kA Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-24—3-27
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-28—3-29
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 3-33
480 V 65 kA 65 kA 200 kA
600 V 35 kA 35 kA 100 kA
DE2 Discount
Schedule
Micrologic Standard-Function
Trip Systems (LXL, LXIL)
Micrologic Full-Function Trip
Systems (LEL)
3-14 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
Molded Case Circuit
Breakers
L-Frame Micrologic™ Series B Trip Circuit Breakers
NOTE: Consider using PowerPact™ circuit breakers for situations requiring circuit breaker accessories. See Digest
Section 7 for more information.
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-25
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-28
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3-33
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digest Page 7-56
Table 3.54: L-Frame—600 A, Micrologic Series B Trip System, I-Line™ Construction, 3P, 600 Vacc
Ampere
Rating
Trip
Function
Standard Function Standard Function Current
Limiting
100% Rated
Full FunctionbInstalled
Rating
Plug
Terminal
Wire Range
Cat. No. $ Price Catalog No. $ Price Cat. No. $ Price
100
LI — — — —LE36100LI 8078.00
ARP040
AL600LI35
(2) 1 AWG–350 kcmil
Al/Cu
LSI LX36100 5898.00 LXI36100 11825. LE36100LS 13421.00
LIG — — — —LE36100LIG 10154.00
LSIG LX36100G 7974.00 LXI36100G 13901. LE36100LSG 15497.00
125
LI — — — —LE36125LI 8078.00
ARP050
LSI LX36125 5898.00 LXI36125 11825. LE36125LS 13421.00
LIG — — — —LE36125LIG 10154.00
LSIG LX36125G 7974.00 LXI36125G 13901. LE36125LSG 15497.00
150
LI — — — —LE36150LI 8078.00
ARP060
LSI LX36150 5898.00 LXI36150 11825. LE36150LS 13421.00
LIG — — — —LE36150LIG 10154.00
LSIG LX36150G 7974.00 LXI36150G 13901. LE36150LSG 15497.00
175
LI — — — —LE36175LI 8078.00
ARP070
LSI LX36175 5898.00 LXI36175 11825. LE36175LS 13421.00
LIG — — — —LE36175LIG 10154.00
LSIG LXL36175G 7974.00 LXI36175G 13901. LE36175LSG 15497.00
200
LI — — — —LE36200LI 8078.00
ARP080
LSI LX36200 5898.00 LXI36200 11825. LE36200LS 13421.00
LIG — — — —LE36200LIG 10154.00
LSIG LX36200G 7974.00 LXI36200G 13901. LE36200LSG 15497.00
225
LI — — — —LE36225LI 8078.00
ARP090
LSI LX36225 5898.00 LXI36225 11825. LE36225LS 13421.00
LIG — — — —LE36225LIG 10154.00
LSIG LX36225G 7974.00 LXI36225G 13901. LE36225LSG 15497.00
250
LI — — — —LE36250LI 8078.00
ARP100
LSI LX36250 5898.00 LXI36250 11825. LE36250LS 13421.00
LIG — — — —LE36250LIG 10154.00
LSIG LX36250G 7974.00 LXI36250G 13901. LE36250LSG 15497.00
300
LI — — — —LE36300LI 11223.00
ARP075
AL600LI5
(2) 4/0 AWG– 500 kcmil
Al/Cu
LSI LX36300 9047.00 LXI36300 17222. LE36300LS 16566.00
LIG — — — —LE36300LIG 13299.00
LSIG LX36300G 11123.00 LXI36300G 19298. LE36300LSG 18642.00
350
LI — — — —LE36350LI 11223.00
ARP088
LSI LX36350 9047.00 LXI36350 17222. LE36350LS 16566.00
LIG — — — —LE36350LIG 13299.00
LSIG LX36350G 11123.00 LXI36350G 19298. LE36350LSG 18642.00
400
LI — — — —LE36400LI 11223.00
ARP100
LSI LX36400 9047.00 LXI36400 17222. LE36400LS 16566.00
LIG — — — —LE36400LIG 13299.00
LSIG LX36400G 11123.00 LXI36400G 19298. LE36400LSG 18642.00
450
LI — — — —LE36450LI 15422.00
ARP075
LSI LX36450 13241.00 LXI36450 24413. LE36450LS 20765.00
LIG — — — —LE36450LIG 17498.00
LSIG LX36450G 15317.00 LXI36450G 26489. LE36450LSG 22841.00
500
LI — — — —LE36500LI 15422.00
ARP083
LSI LX36500 13241.00 LXI36500 9413. LE36500LS 20765.00
LIG — — — —LE36500LIG 17498.00
LSIG LX36500G 15317.00 LXI36500G 26489. LE36500LSG 22841.00
600a
LI — — — —LE36600LI 15422.00
ARP100
LSI LX36600 13241.00 LXI36600 24413. LE36600LS 20765.00
LIG — — — —LE36600LIG 17498.00
LSIG LX36600G 15317.00 LXI36600G 26489. LE36600LSG 22841.00
a600 A Sensor is 80% rated.
bSubstitute (A) in place of (G) for ground-fault alarm (pickup indication only). Requires CIM3F and Powerlogic, or see Data Bulletin 0502DB0001. No
instantaneous OFF position for LI or LIG trip function type circuti breakers.
cType LX, LXI and LE circuit breakers are NOT recommended for use on single motor branch circuits.
Table 3.55: Interrupting Ratings
Voltage LX LE LXI
240 Vac 100 kA 100 kA 200 kA
480 Vac 65 kA 65 kA 200 kA
600 Vac 35 kA 35 kA 100 kA
DE2 Discount
Schedule
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
© 2012 Schneider Electric
All Rights Reserved 3-15
Molded Case Circuit
Breakers
Mag-Gard™ Motor Circuit Protector
Class 680, 685
Mag-Gard™ Motor Circuit Protector
Instantaneous trip magnetic only circuit breakers have a single adjustment which simultaneously sets the magnetic trip
level of each individual pole. Mag-Gard circuit breakers comply with NEC® requirements for providing motor circuit
protection when installed as part of a UL Listed combination controller having motor overload protection. Interrupting
ratings are established for these UL Recognized Components only when they are used in combination with motor
starters with properly sized overload relays and contactors.
Mag-Gard circuit breakers will accept the same lugs and accessories as equivalent thermal-magnetic circuit breakers.
aUL magnetic trip setting tolerances are -20%/+30% from the nominal values shown.
bNo GJL I-Line available.
c250 Vdc ratings are available . No UL component recognition.
dEach ampere rating can be ordered with any designated trip range for the frame by adding the proper suffix to the catalog numbers.
eHold and Trip indicate fixed magnetic trip levels
fLow and High refer to adjustable mag level setting.
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 11-30
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 11-25
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 11-4
Table 3.56: Magnetic Only LAL Mag-Gard, 400 A,
600 Vac, 50/60 Hzc
Ampere
Rating
Adjustablea
Trip Range
3P only
Cat. No. $ Price
GJLb
3
7
15
30
50
75
9–33 A
21–77 A
45–165 A
90–330 A
150–550 A
225–825 A
GJL36003M01
GJL36007M02
GJL36015M03
GJL36030M04
GJL36050M05
GJL36075M06
1089.00
1089.00
1089.00
1089.00
1380.00
1643.00
Table 3.57: Special Magnetic Trip Settings for PowerPact H- and J-Frame Thermal Magnetic Circuit Breakers
Amps Special Low Mags Ii on
Label Mag Suffix
Interrupting Rating
D G J L
HoldeTripeCat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
70 400 850 625 H83 HDL36070H83 1594.00 HGL36070H83 2041.00 HJL36070H83 2519.00 HLL36070H83 3779.00
80 400 850 625 H83 HDL36080H83 1594.00 HGL36080H83 2041.00 HJL36080H83 2519.00 HLL36080H83 3779.00
90 400 850 625 H83 HDL36090H83 1594.00 HGL36090H83 2041.00 HJL36090H83 2519.00 HLL36090H83 3779.00
100 400 850 625 H83 HDL36100H83 1594.00 HGL36100H83 2041.00 HJL36100H83 2519.00 HLL36100H83 3779.00
110 400 850 625 H83 HDL36110H83 3120.00 HGL36110H83 4319.00 HJL36110H83 6209.00 HLL36110H83 8099.00
125 800 1450 1125 H84 HDL36125H84 3120.00 HGL36125H84 4319.00 HJL36125H84 6209.00 HLL36125H84 8099.00
Amps Special High Mags Ii on
Label Mag Suffix D G J L
HoldeTripeCat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
90 900 1700 1300 H85 HDL36090H85 1594.00 HGL36090H85 2041.00 HJL36090H85 2519.00 HLL36090H85 3779.00
Amps Special Low Mags Ii on
Label Mag Suffix D G J L
LowfHighfCat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
150 875L 1750H H29 JDL36150H29 3276.00 JGL36150H29 4535.00 JJL36150H29 6518.00 JLL36150H29 8503.00
200 1250L 2500H H32 JDL36200H32 3276.00 JGL36200H32 4535.00 JJL36200H32 6518.00 JLL36200H32 8503.00
Table 3.58: H- and J-Frame Interrupting Ratings
Vol tage Interrupting Rating
D G J L
240 Vac 25 KA 65 kA 100 kA 125 kA
480 Vac 18 kA 35 kA 65 kA 100 kA
600 Vac 14 kA 18 kA 25 kA 50 kA
DE2 Discount
Schedule
www.schneider-electric.us
3-16 © 2012 Schneider Electric
All Rights Reserved
3MOLDED CASE CIRCUIT
BREAKERS
Molded Case Circuit
Breakers
GJ-Frame MCP Selection
Class 680
Adjustable instantaneous-trip circuit breakers are intended
for use in combination with motor starters with overload
relays for the protection of motor circuits from short circuits.
Other specific applications include rectifiers and resistance
welders. These circuit breakers contain a magnetic trip
element in each pole with the trip point adjustable from the
front. Interrupting ratings are determined by testing the
instantaneous-trip circuit breakers in combination with a
contactor and overload relay.
Select instantaneous-trip circuit breakers as follows:
This selection table is suitable for motors, other than
NEMA Design E, with locked-rotor indicating code letters
per NEC® Table 430.7 (b) as follows:
1. For other motors order a special thermal-magnetic circuit
breaker with magnetic trip settings for the specific motor—
specify motor horsepower, voltage, frequency, full-load
current and code letter or locked rotor current.
2. Determine motor hp rating from the motor nameplate.
3. Refer to the tables and select an instantaneous-trip circuit
breaker with an ampere rating recommended for the hp and
voltage involved.
4. Select an adjustable trip setting of at least 800%, not to
exceed 1300%, of the motor full-load amperes (FLA) for other
than Design E motors. For Design E motors, select an
adjustable trip setting of at least 1100% not to exceed 1700%
of FLA.
5. The NEC 1300% maximum setting may be inadequate for
instantaneous-trip circuit breakers to withstand current surges
typical of the magnetization current of autotransformer type
reduced voltage starters, or open transition wye-delta starters
during transfer from “start” to “run,” constant hp multi-speed
motors, and motors labeled “high efficiency.” Select thermal-
magnetic circuit breakers from Digest page 7-32 for those
applications.
6. Part-winding motors, per NEC 430.3, should have two circuit
breakers selected from the above at not more than one half
the allowable trip setting for the horsepower rating. The two
circuit breakers should operate simultaneously as a
disconnecting means per NEC 430.103.
7. Based on NEC 430.52 and NEC Table 430.150. See
Digest page 7-30 for a available Adjustable Instantaneous-
Trip Circuit Breakers.
Table 3.59: Locked-Rotor Indicating Codes
Horsepower Motor Code letter
1/2 or less
3/4 to 1-1/2
2 to 3
5 to 25
30 to 125
150 or more
A–L
A–K
A–J
A–H
A–G
A–F
Table 3.60: GJL Adjustable Instantaneous-Trip Circuit Breakers for Single Motor Circuit Protection
Hp Ratings of Induction Type
Squirrel-Cage and
Wound Rotor Motors Full
Load
Amperesa
GJL Family
Mag-Gard
Circuit Breaker
Cat. No.
Magnetic Trip
Settingsb
Hp Ratings of Induction Type
Squirrel-Cage and
Wound Rotor Motors Full
Load
Amperesa
GJL Family
Mag-Gard
Circuit Breaker
Cat. No.
Magnetic Trip
Settingsb
3Ø 60 Hz 3Ø 60 Hz
200
Vac
230
Vac
460
Vac
575
Vac MIN MAX 200
Vac
230
Vac
460
Vac
575
Vac MIN MAX
1/2 0.8 GJL36003M01c1100% 4100% 7-1/2 9 GJL36015M03 500% 1800%
1/2 1 GJL36003M01c900% 3300% 3 9.6 GJL36015M03 500% 1700%
3/4 1.1 GJL36003M01c800% 3000% 3 7-1/2 10 11 GJL36015M03 400% 1500%
3/4 1.4 GJL36003M01 600% 2400% 10 14 GJL36030M04 600% 2400%
1 1.8 GJL36003M01 500% 1800% 5 15.2 GJL36030M04 600% 2200%
1/2 2 GJL36003M01 500% 1700% 15 17 GJL36030M04 500% 1900%
1-1/2 2.1 GJL36003M01 400% 1600% 5 17.5 GJL36030M04 500% 1900%
1/2 2.3 GJL36003M01 400% 1400% 15 21 GJL36030M04 400% 1600%
1-1/2 2.6 GJL36003M01 300% 1300% 7-1/2 20 22 GJL36030M04 400% 1500%
2 2.7 GJL36003M01d300% 1200% 7-1/2 25.3 GJL36030M04 400% 1300%
3/4 2.8 GJL36003M01d300% 1200% 20 25 27 GJL36050M05 600% 2000%
3/4 3.2 GJL36007M02 700% 2400% 10 28 GJL36050M05 500% 2000%
2 3.4 GJL36007M02 600% 2300% 30 32 GJL36050M05 500% 1700%
1 3.6 GJL36007M02 600% 2100% 10 32.2 GJL36050M05 500% 1700%
3 3.9 GJL36007M02 500% 2000% 25 34 GJL36050M05 400% 1600%
1 4.1 GJL36007M02 500% 1900% 30 40 GJL36050M05 400% 1400%
3 4.8 GJL36007M02 400% 1600% 40 41 GJL36050M05 400% 1300%
1-1/2 5.2 GJL36007M02 400% 1500% 15 42 GJL36075M06 400% 1300%
1-1/2 6 GJL36007M02 400% 1300% 15 48.3 GJL36075M06 500% 1700%
5 6.1 GJL36015M03 700% 2700% 40 50 52 GJL36075M06 400% 1600%
2 6.8 GJL36015M03 700% 2400% 20 54 GJL36075M06 400% 1500%
5 7.6 GJL36015M03 600% 2200% 20 60 62 GJL36075M06 400% 1300%
2 7.8 GJL36015M03 600% 2100% 50 65 GJL36075M06 300% 1300%
aMotor full-load currents are taken from NEC Table 430.150. Select wire and circuit breakers on basis of horsepower rather than nameplate full-load current
per NEC 430.6 (A) for general motor applications. Do not use these values to select overload relay thermal units. See Digest pages 14-129–14-152 for
selection of thermal units when actual full load current is not known. The voltages listed are rated motor voltages. Corresponding nominal system voltages
are 200–208, 220–240, 440–480 and 550–600 V.
bOnly MIN and MAX settings are shown, intermediate settings are available on all circuit breakers.
cSee NEC 430.52(A) for circuit breaker settings above 800%.
dIf due to motor starting characteristics, trip settings at the 1300% maximum permitted level are needed, the next size Mag-Gard circuit breaker should be
chosen.
www.schneider-electric.us
© 2012 Schneider Electric
All Rights Reserved 3-17
3MOLDED CASE CIRCUIT
BREAKERS
Special Construction
Circuit Breakers
Special Terminal Connectors and Lugs
Class 600
Bolt-On I-Line™
(20% Price Adder)
The standard I-Line circuit breaker is designed to provide a high quality, secure connection
between the distribution bus and circuit breaker. I-Line circuit breakers use plug-on type
line-side connectors. The parallel line-side connectors “clamp’’ around the bus bars. In case
of a short circuit, the increased magnetic flux causes the connectors to grasp the bus bars
even tighter. I-Line circuit breakers with bolted connections have clamp-on jaws that are
bolted around the main bus, as shown. The bolt-on I-Line design is offered as an alternative
in order to meet specifications requiring a bolted connection. Bolt-on I-Line construction is
available on FY, QB, QD, QG, QJ, Q4, FA, FH, FI, KI, LA, and LH frame circuit breakers
and molded case switches, and SL100, SL225 and SL400 sub-feed lugs.
To order on all products except QB, QD, QG and QJ, simply add the letter “B’’ in the catalog
number prefix of the circuit breaker, e.g., FA36100 becomes FAB36100. For QB, QD, QG
and QJ, insert the letter “E” in the third position, e.g., QBE, QDE, etc.
NOTE: Not available on Powerpact™ circuit breakers.
Top-Feed I-Line
(No Additional Charge)
I-Line panelboards may require the use of a top-feed I-Line circuit breaker in applications
where a top-feed main circuit breaker is required. This involves having the I-Line jaw
connectors on the OFF end of the circuit breaker, as opposed to the standard location on
the ON end of the circuit breaker. To designate this construction, simply place the suffix
“MT” at the end of the circuit breaker catalog number, e.g., FA36100 becomes FA36100MT.
On LA or LH top-feed I-Line circuit breakers, accessories must be factory installed. This
option is available in PowerPact™ H and J-frame by placing a “K” in the 4th position
(termination indicator) of the circuit breaker catalog number, e.g., HGA36125 becomes
HGK36125. This option is not available on L-frame (600 A only), M-frame,
N-Frame or Powerpact M-, P- and R-frame.
“CBA” I-Line Jaw Configuration (Non-PowerPact Circuit Breaker)
(No Additional Charge)
Standard 1-pole and 2-pole I-Line circuit breakers are ordered by designating the required
phase connection letters as a suffix to the circuit breaker catalog number. 3-pole circuit
breakers do not require this phase designation and are supplied with an “ABC” phase jaw
configuration as standard. In most applications this is acceptable since the phase loading is
evenly distributed. In applications where the phases must be reversed it is possible to order
a “CBA” jaw configuration by simply placing the letters “CBA” at the end of the standard
catalog number, e.g., FA36100 becomes FA36100CBA.
Control Wire Tap Lugs
(No Additional Charge if Field Installed; 20% Price Adder if Factory Installed)
Control wire tap lugs are used in applications requiring connection to a small wire (22-14
AWG) for control circuits. This is accomplished by crimping the wire to a standard wire
crimp terminal (not included) and fastening the terminal to the circuit breaker lug. On LA
lugs, the lug is drilled to accept a 6-32 screw (included) to secure the crimp connector. On
FA lugs, a flat slip-on crimp connector is used to attach to a shim-like connector placed
under the circuit breaker lug.
Note: To order as a factory-installed device on FA, FH, FI, KI, Q4, LA, LH, LC, LI, LXI, LX or
LC circuit breakers, add suffix number 8041 to circuit breaker catalog number, e.g.,
KIL362258041. To order as a factory-installed device on MG, MJ, PG, PJ, PL RG, RJ and
RL use the product selector or the respective PowerPact catalog. Tapped lugs will be
installed on the “ON” and “OFF” ends of the circuit breaker.
aUse fully-insulated 0.250 in slip-on connectors.
bI-Line Only.
Table 3.61: Control Wire Terminations for Circuit Breakers
Circuit Breaker
Control Wire Termination Kits
Cat. No.
Standard
Package
Quantity
$ Price
Per Lug
Factory
Installed $ Price
(Suffix 8041)
FA, FH, FI FATa18.40
Add 20%
to price of
circuit breaker
KI AL250KIT 1113.00
Q4, LA, LH AL400LAT 140.80
LC, LI, LXI,
LX, LE
AL600LI35T 153.00
AL600LI5T 144.60
MA, MH, MX, ME AL900MAT 1111.00
AL1000MAT 1111.00
NA, NC, NX, NE AL1200NE6T 1228.00
Table 3.62: Tapped Lugs for PowerPact™ Circuit Breakers
Circuit Breaker Amperes
Max. Kit Cat. No. Standard
Package Qty. $ Price Per Kit
MG, MJ,
PG, PJ, PL 800 A AL800M23TK 3312.00
AL800P6TK 3458.00
PG, PJ, PL
800 A AL800M23TK4 4414.00
AL800P6TK4 4608.00
1200 A
AL1200P24TK 1138.00
AL1200P25TK 3416.00
AL1200P25TK4 4555.00
RG, RJ, RL 1200 A AL1200R53TKb1237.00
Plug-on Connector
Bolted Connector
Control Wire
Mounting Screw
Circuit Breaker
Terminal
Control Wire
AL250KAT Lug
ASKC 809
Lug
BSKC 394
Lug Mounting Screw
Circuit Breaker Lug
Circuit Breaker Terminal
Control Wire Terminal
(Catalog Number FAT)
DE2 Discount
Schedule
3-18 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
Special Construction
Circuit Breakers
Special Calibration, Rear-Connected Studs, Visi-Blade,
Moisture/Fungus Treatment, and Short LA/LH Handle
Special Magnetic or Thermal Calibration
(20% Price Adder)
Magnetic
The magnetic trip ranges for standard circuit breakers are listed in the Square D Digest. Requirements outside this
range are best accommodated by selecting another standard circuit breaker. In some cases where this is not practical,
a circuit breaker may be ordered with special magnetic calibration. Special magnetic calibration is not possible in all
cases. Circuit breakers with special magnetic calibration and an adjustable magnetic trip range are not UL Listed;
those with a fixed magnetic trip setting are UL Listed. Consult Schneider Electric local sales office for more information.
50 Degrees C
UL 489 Listed molded case circuit breakers are calibrated for 40 degree C ambient temperature. To meet requirements
of higher ambient conditions, circuit breakers can be factory calibrated for a 50 degree C ambient temperature. Circuit
breakers with special thermal calibration are not UL Listed. To order 50° calibration, add “35” suffix to FA/FH/LA/LH or
CA to H or J thermal magnetic breakers and add 20% to the List price of the breaker. Consult local sales office for more
information.
Rear-Connected Studs
Rear-connected studs are designed to allow rear termination in applications such as control panels where wire gutter
space may be limited. The studs may be bolted directly to the bus or lugs may be attached to the studs.
NOTE: Long and short studs must be alternated on adjacent poles to assure proper electrical clearance
Note: Use alternate size studs on adjacent poles to obtain proper electrical clearance.
Visi-BladeTM Circuit Breakers
(20% Price Adder)
Visi-blade construction is a modification to the cover of a thermal-magnetic circuit breaker, a molded case switch, or a
Mag-Gard™ circuit breaker which provides a “window” through which the position of the movable contacts can be
verified. Luminescent paint is applied to the movable contact arms to clearly indicate their position. Gases produced
during high level interruption may cause clouding of the Visi-blade window. Visi-Blade circuit breakers listed below are
UL Listed except for FH circuit breakers. Visi-Blade construction is not available on circuit breakers not included in table
below.
Add suffix letter “V” to the circuit breaker catalog number, i.e., FAL 36100V.
aFH circuit breaker is not UL Listed.
bNot available on 1P FA/FH circuit breakers.
Moisture and Fungus Resistant Treatment for Circuit Breakers
(20% Price Adder)
This treatment covers the application of moisture and fungus resistant varnish to circuit breakers and molded case
switches.
•The varnish meets Military Specification MIL-V-173C VARNISH, MOISTURE AND FUNGUS RESISTANT.
•The treatment meets military Specification MIL-T-152E TREATMENT, MOISTURE AND FUNGUS-RESISTANT,
OF COMMUNICATIONS, ELECTRONIC, AND ASSOCIATED ELECTRICAL EQUIPMENT.
The treatment of circuit breakers in accordance with said specifications is intended to protect them against the moisture
and fungus condition encountered in service by retarding the absorption of moisture and inhibiting the growth of fungi.
To order for F- and L-frame circuit breakers, place the suffix “FT” at the end of the circuit breaker catalog number, e.g.,
FAL36100 becomes FAL36100FT. To order for QB, QD, and QG circuit breakers, place the suffix “YF” at the end of the
circuit breaker catalog number, e.g., QDL32150 becomes QDL32150YF. ED, EG, EF, GJL, PowerPact™ D-, H-, J-, M-
, P- and R-frame circuit breakers are inherently fungus resistant and need no further treatment.
Short Handle for LA/LH Circuit Breakers (No Additional Charge)
Certain applications of the LA/LH circuit breakers (as mains in particular panelboards) require the use of a slightly
shorter operating handle. For ordering information refer to the chart below.
Rear- Connected Studs
Table 3.63: Rear-Connected Studs—Not UL Listed
Circuit Breaker
Cat. No.
Prefix
Ampere
Ratings
Stud
Cat. No.
Dimensions
$ Price Per Stud
Overall
Length
To Back of
Circuit Breaker Diameter Threads/Inch
FAL, FHL 15–100 A FAS20 2-1/4 in. 2 in. 3/8 in. 16 70.00
FAL, FHL 15–100 A FAS42 4-7/8 in. 4-1/4 in. 3/8 in. 16 92.00
LAL, LHL 125–400 A LAS54 6-3/16 in. 5-1/2 in. 3/4 in. 16 243.00
LAL, LHL 125–400 A LAS114 12-3/16 in. 11-1/2 in. 3/4 in. 16 360.00
Visi-Blade Circuit Breaker
Table 3.64: Available Visi-Blade Circuit Breakers
Circuit Breaker Prefix Amperes $ Price
FA, FHab 15–100 A 20% Price Adder
LA, LH 125–400 A
Table 3.65: Catalog Numbers for Short Handle LA/LH CIrcuit Breakers
Lug Configuration Desired Catalog
“Prefix Indication”
Catalog
“Suffix Indication”
Circuit Breaker
Cat. No.
ON End OFF End
Lugs Lugs “L” “MB” LAL36400MB
No Lugs Lugs “P” “MB” LAP36400MB
Lugs No Lugs “P” “MT” LAP36400MT
No Lugs No Lugs “F” “MB” LAF36400MB
DE2 Discount
Schedule
www.schneider-electric.us
© 2012 Schneider Electric
All Rights Reserved 3-19
3MOLDED CASE CIRCUIT
BREAKERS
Special Construction
Circuit Breakers
P-Frame Replacement Handles, Key Interlock Adapter Plate
and Exchange Program
P-Frame Replacement Handle
Replacement handle assemblies for PA, PC, PE, PX and PH circuit
breakers (produced after March 1975) are available.
Exchange Guarantee Prices, Permanent Trip Molded
Case Circuit Breakers
When a Square D permanent trip circuit breaker is supplied to
meet a specification requiring an interchangeable trip unit, it may
be exchanged for another circuit breaker of the same type with a
different trip setting.
When entering an order for the replacement circuit breaker:
1. Reference “Exchange Price Guarantee” as a line item marking on the
replacement order. The replacement order will be billed at normal
authorized selling net price.
2. Request Return Material Authorization referencing “Exchange Price
Guarantee” and the replacement exchange price guarantee invoice
number.
When the circuit breaker is returned to Cedar Rapids, credit will
be issued for the difference between the replacement net price
billed and the exchange list price (from the table below) times the
same multiplier used on the replacement order. The list price
used to determine credit will be based on the highest trip setting
of the circuit breakers involved in the exchange.
Only those circuit breaker types below are eligible for this
exchange guarantee program.
Table 3.66: P-Frame Replacement Handle
Circuit Breaker
Cat. No. Prefix
Replacement Handle
Cat. No. $ Price
PAF, PAE, PHF, PHE, PCF, PEC, PEF, PXF HRPA 111.00
P-Frame Key Interlock Adapter Plate
PAKK Kit – An adapter plate that is added under the circuit breaker
handle to allow mechanical interlocking with a key interlock (not
included). The kit includes all the necessary hardware to mount onto the
circuit breaker handle.
Table 3.67: P-Frame Key Interlock Adapter Plate
Cat. No. $ Price
PAKK 185.00
Table 3.68: Exchange Guarantee Circuit Breakers
Circuit Breaker Type Trip Range Exchange List $ Price
LA All 2465.00
LH All 4055.00
LC All 4434.00
Replacement
Handle
Assembly
Optional
PAKK
Assembly
Circuit Breaker with Handle Removed
Hub q
Washers are to remain with Circuit Breaker
aThe “hub” under normal conditions is insulated. When the phenolic handle is removed,
a label is exposed warning of the hub being energized. That can only happen if a short
circuit or severe overload occurs. The ionized gasses inside the circuit breaker could
momentarily (1-2 cycles) put a high voltage potential on the hub.
DE2 Discount
Schedule
www.schneider-electric.us
3-20 © 2012 Schneider Electric
All Rights Reserved
3MOLDED CASE CIRCUIT
BREAKERS
Special Construction
Circuit Breakers
Special Terminations
Class 690
Lug Deletion (No Additional Charge)
In some applications, the circuit breaker does not require
lugs on one or both ends. To meet this requirement, the
circuit breaker should be ordered with the desired lug
configuration as indicated below. If necessary, lugs may
be removed in the field. However, if lugs are removed in
the field, circuit breaker Types FH, FC, Q4 LA and LH
must be secured with pan-mounting screws, or have “P”
screws (cover screws and nuts) installed securing the
base to the cover.
Termination Insert Kits
The standard lugs supplied with EDB, EGB, EJB, and FJA
circuit breakers and molded case switches are secured by
means of a screw fastened through the circuit breaker
terminal into the lug body. If the standard lug is removed
and a bolted connection to the circuit breaker terminal pad
is desired, a threaded insert kit is required. The insert is
installed below the terminal pad. For ordering information
see chart below.
LC, LI, LE, LX and LXI Circuit Breaker
Termination Clip Kit
The standard
lugs supplied
with LC, LI, LE,
LX and LXI
circuit breakers
are secured by
means of a
screw fastened
through the
circuit breaker
terminal into the
lug body. If the
standard lug is
removed and a
bolted
connection to the circuit breaker terminal is desired, the
AL600IN threaded terminal clip kit is required to make this
connection. The AL600IN clip snaps onto the bottom of
the terminal. For ordering information, see chart below.
Electric Joint Compound
I-Line™ circuit
breakers, I-Line
busway plug-on units,
I-Line panelboards
and switchboards,
QMB plug-on switches
and motor control
center plug-on units
are supplied with
factory applied joint
compound on the
plug-on connectors.
The compound should
not be removed
because it contributes
to the overall
performance of the
connection.
Whenever one of
these units is removed
and reinstalled, the
joint compound should
be reapplied. Catalog
number PJC 7201 is a
two-ounce container of
compound specially formulated for the I-Line, QMB and
motor control center connections.
No other type of commercially available joint compound
should be used.
Table 3.69: Lug Configurationa
ON End OFF End Circuit Breaker Prefix – Suffix
Lugs Lugs “L”
(e.g., FAL36100)
No Lugs No Lugs “F”
(e.g., FAF36100)
No Lugs Lugs “P”
(e.g., FAP36100)
Lugs No Lugs “P – MT”b
(e.g., FAP36100MT)
aSee information on termination kits below
bMT suffix also required (except for PowerPact™).
Table 3.70: Termination Kit Inserts
Kit Cat. No. Inserts Per Kit Circuit Breakers $ Price Per Kit
TIKFD 3 EDB, EGB, EJB, FJA 17.40
EDB, EGB, EJB,
FJA
Table 3.71: Termination Clip Kit
Kit Cat. No. Clips Per Kit Circuit Breakers $ Price Per Kit
AL600IN 3 LC, LI, LE, LX, LXI 65.00
Table 3.72: Electric Joint Compound
Use With Cat. No. $ Price
I-Line Circuit Breakers, QMB Plug-On Units, or
Model-V MCC Units PJC7201 19.80
SED Drawout Circuit Breakers PJC8311 42.80
Terminal Clip
LC, LI, LE, LX and LXI Circuit Breakers
Terminal
DE2 Discount
Schedule
www.schneider-electric.us
© 2012 Schneider Electric
All Rights Reserved 3-21
3MOLDED CASE CIRCUIT
BREAKERS
Special Construction
Circuit Breakers
Grounded BØ Systems
Class 600
Circuit Breakers for Grounded B-Phase (BØ)
(Corner-Grounded Delta) Systems (No Additional
Charge)
Ordering Information For Grounded BØ Circuit Breakers
1. There is no additional charge for grounded BØ circuit breakers.
2. For use on 480 V systems, FH and LH type circuit breakers must be ordered
as 600 V versions and with a 5861 suffiix (i.e. FHL361005861).
3. For use on 240 V systems, FH type circuit breakers may be ordered as 480 V
versions with a 5861 suffix (i.e. FHL341005861).
4. FA and LA type circuit breakers are not available with grounded B phase
markings.
5. Two-pole 240 V grounded B-phase circuit breakers (except EDB, EGB, EJB,
QB, QD, QG, and QJ) will be built using three-pole modules.
6. Two-pole grounded BØ circuit breakers will be labeled with 240 Vac
interrupting ratings.
7. No self-certification is available for interrupting ratings greater than shown in
the tables below.
NOTE: Three-pole circuit breakers must be used on three-phase
480 V corner-grounded delta systems. The outside poles
are to be connected to the ungrounded phase and the
grounded conductor connected to the center pole.
Connecting the circuit breaker in a manner other than that
described or shown may result in an unsafe application of
the circuit breaker.
Table 3.73: 480 Vac 3Ø Corner-Grounded Delta System
Cat. No. Prefix Polesc
UL Listed Interrupting Ratingc
Ampere Rating 480 Vac Interrupting
Rating
HD, HG, HJ, HL 3 15–150 A 18 kA, 35 kA, 65 kA, 100 kA
JD, JG, JJ, JL 3 150–250 A
FH, FHL 3 15–100 A 10 kA
LH, LHL 3 125–400 A 14 kA
LD, LG, LJ, LL Electronic Trip Unit 3 250–600 A 18 kA, 35 kA, 65 kA, 100 kA
MG, MJ Electronic Trip Unit 3d300–800 A 35 kA
PG, PK Electronic Trip Unit 3d600–1200 A 35 kA, 50 kA
PG, PK Micrologic Trip Unit 3d250–1200 A
PJ, PL Electronic Trip Unit 3d600–1200 A 65 kA, 100 kA
PJ, PL Micrologic Trip Unit 3d250–1200 A
RG, RJ, RK RL Electronic Trip Unit 3d1200–2500 A 35 kA, 65 kA, 65 kA,100 kA
Table 3.74: Application Data for 240 Vac 3Ø Corner-Grounded
Delta System RG, RJ, RK, RL Micrologic Trip Unit 3d600–2500 A
NT 3 800–1200 100 kA
Cat. No. Prefix Poles
UL Listed Interrupting Rating NW 3 800–6000 150 kA
Ampere Rating 240 Vac Interrupting
Rating
cThe grounded phase should be connected through the center pole only.
dElectronic = ET1.0 Electronic Trip System
Micrologic = 3.0, 5.0, 3.0A, 5.0A, 6.0A, 5.0P, 6.0P, 5.0H and 6.0 H Micrologic Trip
System.
QO-H, QOB-H 2 15–100 A 5 kA
QB, QD, QG, QJ 2a70–250 A 10 kA
EDB, EGB, EJB 2a15–125 A 18 kA, 35 kA, 65 kA
HD, HG, HJ, HL 2a15–150 A 42 kA, 42 kA,
65 kA, 100 kA
JD, JG, JJ, JL 2b150–250 A
FH, FHL 2b15–100 A 42 kA
LH, LHL 2b125–400 A 30 kA
MG, MJ Electronic Trip Unit 2cb 300–800 A 65 kA
PG, PJ, PK, PL Electronic Trip Unit 2bc 600–1200 A 65 kA
RG, RK Electronic Trip Unit 2bc 1200–2500 A 35 kA, 65 kA
RJ Electronic Trip Unit 2bc 1200–2500 A 100 kA
RL Electronic Trip Unit 2bc 1200–2500 A 125 kA
aStandard labeling includes grounded B phase.
bBuilt using 3P module.
cElectronic = ET1.0 Electronic Trip System
Micrologic = 3.0, 5.0, 3.0A, 5.0A, 6.0A, 5.0P, 6.0P, 5.0H and 6.0 H Micrologic Trip
System.
Load
2-pole
Circuit Breaker
3Ø 240 Vac Corner-Grounded Delta System
Load
3-pole
Circuit Breaker
3Ø 480 Vac Corner-Grounded Delta System
3-22 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
Special Construction
Circuit Breakers
UL Marine Listed Circuit Breakers
Class 600
UL Marine Listed/CSA Certified Circuit Breakers (UL 489 Supplement SA)
PowerPact H and J circuit breakers with thermal magnetic trip units meet the UL 489 SA requirements on vessels of
any length under or over 65 ft. (19.8m). PowerPact H, J, and L circuit breakers with Micrologic trip units meet the
UL 489 Supplement SA requirements for use on vessels over 65 ft. (19.8m) in length. Marine circuit breakers must not
use aluminum or aluminum alloys for terminal connections and must be calibrated at an ambient temperature of 104°F
(40°C). Standard circuit breakers should not be specified or used in place of marine rated circuit breakers.
Circuit breakers can be ordered with the Marine SA listing by adding the suffixes of “LC” (copper lugs) and “YA”
(marine) to the catalog number.
aThermal-Magnetic trip units only.
bMicrologic trip units only.
UL Naval Listed/CSA Certified Circuit Breakers (UL 489 Supplement SB)
PowerPact H, J, and L circuit breakers with Micrologic trip units meet the UL 489 Supplement SB requirements for
naval vessels. These circuit breakers are subject to various vibration testing as described in UL 489 Supplement SB.
Naval circuit breakers must not use aluminum or aluminum alloys for terminal connections and are calibrated at an
ambient temperature of 122°F (50°C). Standard circuit breakers should not be specified or used in the place of naval
rated circuit breakers.
Circuit breakers can be ordered with the Naval SB listing by adding the suffixes of “LC” (copper lugs) and “YA1” (naval)
to the catalog number.
aWith Micrologic trip units only thermal-magnetic breakers not approved.
Table 3.75: Circuit Breakers for Marine Applications
Cat. No. Prefix Poles Ampere
Rating Application Cat. No. $ Price
FA, FAL 2 15–100 A
For use only on
vessels over 65 feet
(19.8 m) in length.
Add the number “9’’ after the catalog
number prefix of the standard circuit
breaker catalog number.
Example:
Standard FAL36100
Marine FAL936100
There is a 20%
adder to the price of
the equivalent standard
circuit breaker. All
marine
circuit breakers are
supplied with copper
lugs.
3 15–100 A
FH, FHL 2, 3 15–100 A
FI, FIL 2, 3 20–100 A
KI, KIL 2, 3 110–250 A
LA, LAL 2, 3 125–400 A
LH, LHL 2, 3 125–400 A
PowerPact™ HD, HG, HJ, HLa2, 3 15–150 A For use on vessels over and under
65 feet (19.8 m) in length. Add suffix for Copper Lugs (LC) and
“YA’’ after the standard circuit
breaker catalog number.
Example:
Standard HGL36100
Marine HGL36100LCYA
PowerPact JD, JG, JJ, JLa2, 3 150–250 A
PowerPact HD, HG, HJ, HL, HRb2, 3 15–150 A For use on vessels over 65 feet
(19.8m) in length.
PowerPact JD, JG, JJ, JL, JRb2, 3 150–250 A
PowerPact LD, LG, LJ, LL, LR 3, 4 250–600 A
PowerPact MG, MJ 2, 3 300–800 A For use only on
vessels over 65 feet
(19.8 m) in length.
PowerPact PG, PJ, PL 2, 3, 4 100–1200 A
PowerPact RG, RJ, RL 2, 3, 4 600–2500 A
Table 3.76: Circuit Breakers for Navel Applications
Cat. No. Prefix Poles Ampere
Rating Application Cat. No. $ Price
HD, HG, HJ, HLa2, 3 15–150 A
For use on non-combat and
auxiliary naval
ships of any length.
Add suffix for Copper Lugs (LC) and
“YA1’’ after the standard circuit
breaker catalog number.
Example:
Standard HGL36100
Marine HGL36100LCYA1
There is a 20%
adder to the price of
the equivalent standard
circuit breaker. All marine
circuit breakers are
supplied with copper lugs.
JD, JG, JJ, JLa2, 3 150–250 A
LD, LG, LH, LL 3,4 250–600 A
For use on vessels over 65 ft.
(19,8 m) in length
DE2 Discount
Schedule
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
© 2012 Schneider Electric
All Rights Reserved 3-23
Circuit Breaker
Accessories
PowerPact™ Circuit Breakers Electrical Accessories
Class 612 / Refer to Catalog 0616CT0801
Table 3.77: Electrical Accessories
Accessory Description Rated Voltage
G-Frame D-Frame
Field-
Installable
Cat. No.
$ Price
Factory-
Installed
Cat. Suffix
Field-
Installable
Cat. No.
$ Price $ Price
Auxiliary and Alarm Switches
(OF, SD, SDE)
Provides circuit
breaker contact
status.
Note: The location of
the accessory in the
circuit breaker
determines its
function.
Standard Min
Load =
10mA with 24V
1 auxiliary switch (OF) 1a1b AAC 297.00 AA S29450 297.00 297.00
2 auxiliary switch (OF) 2a2b — — AB 2x S29450 594.00 594.00
3 auxiliary switch (OF) 3a3b — — AC 3x S29450 891.00 891.00
Alarm Switch (SD) 1a1b AAC 297.00 BC S29450 297.00 297.00
Overcurrent trip switch (SDE) 1a1b — — BD S29450 297.00 297.00
Consisting of: OF Switch — — — — — —
SDE Adapter — — — — — —
Alarm switch and Overcurrent trip switch — — BE 2x S29450 594.00 594.00
Consisting of: OF Switch — — — — — —
SDE Adapter — — — — — —
Auxiliary Switch/Alarm Switch/Adapter
(OF/SD/SDE) Kit —— — ——297.00
Low Level
Min Load =
1mA with 24V
One auxiliary switch (OF) 1a1b — — AE S29452 372.00 372.00
Two auxiliary switches (OF) 2a2b — — AF 2x S29452 744.00 744.00
3 auxiliary switches (OF) 3a3b — — AG 3x S29452 1116.00 1116.00
Alarm Switch (SD) 1a1b — — BH S29452 372.00 372.00
Overcurrent trip switch (SDE) 1a1b — — BJ S29452 372.00 372.00
Consisting of: OF Switch — — — — — —
SDE Adapter — — — — — —
Alarm switch and Overcurrent trip switch — — BK 2x S29452 744.00 744.00
Consisting of: OF Switch — — — — — —
SDE Adapterd—— — ———
Shunt Trip (MX)
Trips the circuit breaker from a remote
location by means of a trip coil energized
from a separate supply voltage circuit.
AC
24 —
717.00
SK S29384
717.00 755.00
48 — SL S29385
120 GSA ——
110/130 — SA S29386
208 GSB ——
240 GSC ——
200/250 — — —
277 GSD ——
208/277 — SD S29387
480 GSH ——
380/480 — SH S29388
525/600 — SJ S29389
DC
12 —
717.00
SN S29382
717.00 755.00
24 GSO SO S29390
30 — SU S29391
48 GSP SP S29392
60 — SV S29383
125 GSR SR S29393
250 GSS SS S29394
Undervoltage Trip
Instantaneously opens the circuit breaker
when the under-voltage trip supply voltage
drops to a value between 35% and 70% of
its rated voltage. Closing is allowed when
the supply voltage of the undervoltage trip
reaches 85% of rated voltage.
AC
24 —
717.00
UK S29404
717.00 755.00
48 — UL S29405
120 GUA ——
110/130 — UA S29406
208 GUB ——
240 GUC ——
200/250 — — —
277 GUD ——
208/277 — UD S29407
480 GUH ——
380/480 — UH S29408
525/600 — UJ S29409
DC
12 —
717.00
UN S29402
717.00 755.00
24 GUO UO S29410
30 — UU S29411
48 GUP UP S29412
60 — UV S29403
125 GUR UR S29413
250 GUS US S29414
aField-installable kit includes time delay module only. Order undervoltage trip separately.
bDiscount schedule DE2F.
cP-frame drawout circuit breaker only.
dSDE Adapter used for H- and J-frame only.
G-Frame
D-Frame
G-Frame
D-Frame
G-Frame
D-Frame
DE2 DE2F Discount
Schedule
3-24 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
Circuit Breaker
Accessories
Factory-Installed Accessories
Factory-Installed Electrical Accessories
Electrical accessories are available on all molded case circuit breakers except FY and QOM1 circuit breakers.
•Alarm switch is the only accessory available for the 1-pole FA circuit breaker.
•Combination accessories may be ordered by description, i.e., 1021 and 1212.
•All AC electrical accessories shown below are rated for 50/60 Hz.
•Add 20% to accessory price for each field-installable accessory that is factory-installed.
•See page 3-25 for field-installable accessories. See Digest page 7-35 for PowerPact™ circuit breaker accessories.
Table 3.78: Factory-Installed Accessories for Thermal-Magnetic Circuit Breakers
Accessory Description Rated
Voltage
Coil
BurdenaSuffix $ Price
Adder
Shunt Trip
Trips the circuit breaker from a remote location by means of a trip coil energized from a separate circuit.
A 120 V shunt trip will operate at 55% or more of rated voltage. All other shunt trips will operate at 75%
or more of rated voltage.
Application
•For use with momentary or maintained push button.
•Sure Trip Capacitor Unit requires 48 Vdc shunt trip.
•Leads: (2) Black.18 AWG Cu.
24 Vac 21 VA -1042b755.00
120 Vac 24 VA -1021c755.00
208 Vac 107 VA -1021 755.00
240 Vac 154 VA -1021 755.00
277 Vac 14 VA -1037b755.00
480 Vac 45 VA -1037b755.00
24 Vdc 36 VA -1027 755.00
48 Vdc 36 VA -1028 755.00
125 Vdc 44 VA -1029 755.00
250 Vdc 15 VA -1030d755.00
Ground-
Fault
Shunt Trip
Trips the circuit breaker electrically using the signal from a Micrologic™ Ground-Fault Module.
Application
•For use only with obsolete GP Ground-Censor™ system or add on ground-fault module.
•Leads: (2) Orange 18 AWG Cu.
——-Gd755.00
Undervoltage
Tr ip ( U VR)
Trips the circuit breaker electrically when a control circuit falls below 35 to 70% of nominal (not field
adjustable). Picks up at 35–85% of nominal voltage.
Application
•UVR must be energized in order to close the circuit breaker.
•Leads: (2) Brown 18 AWG Cu leads.
24 Vac
120 Vac
240 Vac
24 Vdc
48 Vdc
5 VA
8 VA
8 VA
2 VA
3 VA
-1143d
-1121
-1124
-1127
-1128
755.00
755.00
755.00
755.00
755.00
Time Delay
Unit
Provides adjustable time delay for UVR of 0.1 to 0.6 second before circuit breaker trips.
Application
•For use only with -1121 UV trip.
•Adjustable time delay (0.1 to 0.6 second).
•I-Line unit requires 1.5 in. (38 mm) of mounting space.
•Leads: (2) Brown 18 AWG Cu and (2) Black/White 18 AWG Cu.
120 Vac
Cat. No.
Unit Mt. I-Line™
690UVTD 690UVTDI 1941.00
Auxiliary
Switches
Monitors circuit breaker contact status and provides a remote signal indicating
the circuit breaker contacts are OPEN or CLOSED.
Application
•Max. Load = FA, FH, FI, LC, LE, LI, LX, LXI.
10 A @ 125–250 Vac, ¼ hp @ 125–250 Vac, 5 A @ 30 Vdc
•Leads: Yellow for “A’’, Blue for “B’’, Striped for common 18 AWG Cu.
See load
info. in
App. text
at left
See load
info. in
App. text
at left
1A/1B -1212 312.00
2A/2B -1352 623.00
3A/3B -1364e800.00
Alarm
Switches
Used with control circuits and actuated only when the circuit breaker has tripped.
Standard construction includes a normally-open contact.
Application
•Max. Load = 10 A @ 125–250 Vac
•Max. Load = 15 A @ 30 Vdc
•Leads: (2) Red 18 AWG Cu.
1A
1A
1B
1B
250 Vac
28 Vdc
250 Vac
48 Vdc
See
load
info. in
App.
text
at left
-2100
-2100
-2103
-2103
312.00
312.00
312.00
312.00
aCoil burden values do not apply to LC, LE, LI, LX and LXI. Consult Field Sales office for more information.
bNot available on FI or KI circuit breakers.
cLC, LE, LI, LX, and LXI circuit breakers operate at 75% or more of rated voltage.
dNot available on LC, LE, LI, LX, LXI circuit breakers.
eNot available in FA, FC, FH, FI and KI circuit breakers.
Circuit Breaker Open or Closed
1A Alarm Switch
Configuration
Color Code: Red Leads
Circuit Breaker Tripped
Circuit Breaker Tripped
1B Alarm Switch
Configuration
Color Code: Red Leads
Circuit Breaker Open or Closed
1A/1B
Circuit Breaker Closed
AB
Circuit Breaker Open or Tripped
AB
Auxiliary Switch
Contact Configuration
Color Code:
"A" Contact - Yellow Leads
"B" Contact - Blue Leads
Common-Striped Leads
Undervoltage Trip
Wiring Diagram
Brown
Brown
Brown Wires To Be
Connected To
Control Power
UVR
Shunt Trip
Wiring Diagram
Black
Black
Black Wires To Be
Connected To
Control Power
Shunt
Tr i p
690UVTD Wiring Diagram
DE2 Discount
Schedule
www.schneider-electric.us
© 2012 Schneider Electric
All Rights Reserved 3-25
3MOLDED CASE CIRCUIT
BREAKERS
Circuit Breaker
Accessories
Field-Installable Accessories
Field-Installable Electrical Accessories
Complete field-installable accessory catalog number by inserting suffix from 3-24 between
the parentheses in the catalog numbers shown in the table below. (Example: LA11212) See
3-24 for accessory pricing; add 20% to factory-install field-installable devices.
Table 3.79: Field-Installable Accessories for Thermal-Magnetic and Electronic Trip
Circuit Breakers
Circuit Breaker Shunt Trip Ground-Fault
Shunt TripaUndervoltage Trip Auxiliary Switches Alarm Switch
Miniature Circuit Breakers,
EH and EH-PL
Factory-Installed
Only Not Available Not Available Factory-Installed
Only
Factory-Installed
Only
FA, FH, FI, KI Factory-Installed
Only
Factory-Installed
Only
Factory-Installed
Only
Factory-Installed
Only
Factory-Installed
Only
LA, LH
Series 4bLA1( ) LA1G LA1 ( ) LA1( ) Factory-Installed
Only Right Pole
Q4 LA1( ) LA1G LA1 ( ) LA1( ) Factory-Installed
Only Right Pole
LC, LE, LI, LX, LXI LC1( ) LC1G LC1 ( ) LC1( ) Factory-Installed
Only
aUsed with obsolete GP Ground-Censor™ system or add-on ground-fault modules.
bWith LA and LH top-feed circuit breakers (suffix MT, I-Line jaws on OFF end) all accessories must be factory
installed.
Table 3.80: Accessory Mounting Locations
LA, LH, Q4 Series 4 circuit breakers or newer =
Field-installable accessories
LC, LI, LX, LXI circuit breakers = Field-installable
accessories
Both accessory ports will accept shunt trips, UVRs
and auxiliary switches. Alarm switches are factory
installable only (right pole). Maximum of one device
per port.
1A/1B
Circuit Breaker Closed
AB
Circuit Breaker Open or Tripped
AB
Auxiliary Switch
Contact Configuration
Color Code:
"A" Contact - Yellow Leads
"B" Contact - Blue Leads
Common-Striped Leads
Circuit Breaker Open or Closed
1A Alarm Switch
Configuration
Color Code: Red Leads
Circuit Breaker Tripped
Circuit Breaker Tripped
1B Alarm Switch
Configuration
Color Code: Red Leads
Circuit Breaker Open or Closed
Undervoltage Trip
Wiring Diagram
Brown
Brown
Brown Wires To Be
Connected To
Control Power
UVR
Shunt Trip
Wiring Diagram
Black
Black
Black Wires To Be
Connected To
Control Power
Shunt
Tr i p
L
R
3-26 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
Circuit Breaker
Accessories
Electrical Operators, Handle Accessories, Cylinder Locks, and
Walking Beam Mechanical Interlocks
Electrical Operators
Provides remote ON, OFF/RESET control of molded case circuit breakers.
•A complete line of field-installable electrical operators.
•Not applicable on LC/LI/LE/LX/LXI circuit breakers.
•Installing side mounted motor operators on non I-Line™ circuit breakers requires the use of a separate mounting pan.
•Side mounted electrical operators require an additional 4-1/2 in. (114 mm) of mounting space in I-Line installations.
When remote indication of circuit breaker status is required, order circuit breaker with 1A-1B auxilliary switch for ON-
OFF Indication and alarm switch for TRIP Indication. Electrical operators require SPDT maintained contact switch.
Refer to Class 9001 control unit listing for operators and pilot lights.
NOTE: Not available on Mag-Gard™ circuit breakers and molded case switches.
Handle Accessories
aLocks OFF only.
Cylinder Lock
Used to lock the circuit breaker in the OFF position. Circuit breaker cannot be reset when locked OFF.
Interlocks
Table 3.81: Electrical Operators
Circuit
Breaker
Prefix
Top Mount Side Mount Mounting Pan
Voltage Cat. No. $ Price Voltage Cat. No. $ Price Cat. No. $ Price
FA, FH — — — 120 Vac FAMO1 1304.00 ——
FAL, FHL — — — 120 Vac FAMO1 1304.00 FAMOP 108.00
FI, KI — — — 120 Vac KAMO1 3506.00 ——
FIL, KIL
120 Vac KAMO2120AC 3642.00
120 Vac KAMO1 3506.00 KAMOP 134.00
240 Vac KAMO2240AC 3642.00
24 Vdc KAMO224DC 3642.00
125 Vdc KAMO2125DC 3642.00
LA, LH, Q4 — — — 120 Vac LAMO1 4518.00 ——
LAL, LHL,
Q4L
120 Vac LAMO2120AC 4704.00
120 Vac LAMO1 4518.00 LAMOP 185.00
240 Vac LAMO2240AC 4704.00
24 Vdc LAMO224DC 4704.00
125 Vdc LAMO2125DC 4704.00
MAL, MHL
120 Vac MAMO2120AC 4704.00
120 Vac MAMO1 4518.00 MAMOP 1856.00
240 Vac MAMO2240AC 4704.00
24 Vdc MAMO224DC 4704.00
125 Vdc MAMO2125DC 4704.00
PA, PH, PC, PE, PX 120 Vac PA M O2 5544.00 —————
Table 3.82: Handle Accessories
Circuit Breaker Prefix Poles Cat. No. $ Price Circuit Breaker Prefix Poles Cat. No. $ Price
Handle Tie Handle Padlock Attachment (locks ON or OFF)
(2)FA 3 FKHT 215.00 FY Series 1 1 HPAFYQ 19.80
(2)FI,(2)KI, or (1)FI + (1)KI 2,3 FKHT 215.00 FA, FH, FC, FI 1,2,3 HPAFK 24.20
(2)LA or (2)Q4 2,3 LAHT 497.00 FY Series 2, 2,3 HPAFK 24.20
California Title 24 Comb. Handle Tie and Lock Off KI 2,3 HPAFKFa32.60
FY
FA
(3)1P
(3)1P
FY3HT
FA3HT
53.00
53.00 LA, LH, Q4 2,3 HPALM
HPAXLM
26.00
27.60
Handle Extension LC, LE, LI, LX, LXI 2,3 AHPALI 25.20
LA, LH, LE, LI, LX, LXI, Q4 2,3 AHEXLI 95.00
Table 3.83: Cylinder Lock
Circuit Breaker
Prefix
Factory Installed
Suffix
Field Installable
Cat. No. $ Price
FA, FAL, FH, FHLb—CL Factory-installed
only 315.00
LA, LAL, LH, LHL, Q4 Field-installable
only LA1CL 315.00
bNot available on Mag-Gard circuit breakers and molded case
switches.
KAMO2120AC
With KAL Circuit Breaker
FAMO1 and FAMOP
With FAL Circuit Breaker
Table 3.84: Walking Beam Mechanical Interlock Componentsc
Circuit
Breaker
Prefix
Manually Operated Electrically Operated
Operator
Suffix
$ Price
Adder
Walking Beam
Ass'y. Mounting Pan Operator
Suffix
$ Price
Adder
Walking Beam
Ass'y. Mounting Pan
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
FAL, FHL
LAL, LHL
WB
WB
246.00
246.00
FA4WB
LA6WB
134.00
179.00
FAWBP4
LAWBP6
177.00
242.00
WBMO
WBMO
246.00
246.00
FA9WB
LA10WB
200.00
213.00
FAWBP9
LAWBP10
242.00
309.00
cFully enclosed interlocked units are available in Type 1 and Type 3R enclosures, with two neutrals provided in each enclosure. The
completely enclosed assembly is not UL Listed. Please consult your nearest Schneider Electric local sales office for more information.
Walking Beam Mechanical Interlock
Requires 2 circuit breakers with WB suffix,
1 walking beam assembly and 1 mounting pan.
DE2 Discount
Schedule
www.schneider-electric.us
© 2012 Schneider Electric
All Rights Reserved 3-27
3MOLDED CASE CIRCUIT
BREAKERS
Circuit Breaker
Accessories
Locks, Installation Accessories, and Rear Connections
Class 612 / Refer to Catalog 0612CT0101
Table 3.85: Locks, Interlocking
G-Frame D-Frame
Device Description
Field-
Installed
Cat. No.
$ Price
Field-
Installed
Cat. No.
$ Price
Handle
Padlocking
Device
Removable (lock OFF only) AHP 19.70 S29370 50.00
Fixed (lock OFF or ON) — — S32631 122.00
Fixed (lock OFF only) — — NJPAF 122.00
Interlocking
(Not UL listed)
Mechanical for circuit breakers with rotary handles — — 32621 494.00
Mechanical for circuit breakers with toggles — — 32614 494.00
Key Locking Provision and 2 locks keyed
alike
Ronis — — 41950 183.00
Profalux — — 42878 183.00
Table 3.86: Installation Accessories for G- and D-Frame Circuit Breakers
Description
G-Frame D-Frame
Field-
Installed
Cat. No.
$ Price
Field-
Installed
Cat. No.
$ Price
Front Panel Escutcheon for Toggle Breakers — — 32556 55.00
Front Panel Escutcheon for Rotary Handle, Motor Operator, or
extended escutcheon ——32558 74.00
Phase Barriers (set of 6) — — 32570 72.00
Handle Rubber Boot — — 32560 171.00
Sealing Accessories ACS 18.50 29375 42.00
DIN rail adapter GYR 93.00 — —
Toggle Extensions (set of 10) — — 32553 33.20
Table 3.87: Rear Connections
Device Description
D-Frame
Poles Factory-Installed
Termination No.
Field-Installed
Cat. No. $ Price
Mixed Rear
Connection Kit
3S 32477 848.00
4S 32478 1122.00
Consisting of:
Short rear connections (set of 2) 3—2x32475d219.00
Long rear connections (set of 2) — 32476 261.00
Short terminal cover (3P) 3 — 32562 149.00
dPrice shown is for quantity one.
Handle Rubber Boot
Door Escutcheon
Terminal Covers
Removable Padlock
Attachment
Fixed Padlock
Attachment
Key Locking
DE2 DE2F Discount
Schedule
3-28 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
Circuit Breaker
Accessories
Mechanical Lug Information
aUnless otherwise specified, wire sizes apply to both aluminum and copper conductors.
bFor use in the OFF end only, when the OFF end is the load end.
cUse suffix 8002 for factory-installed Cu lugs. (20% adder.)
Table 3.88: Mechanical Lug Kit Information
Circuit Breaker Application (Number of Wires Per Lug )
Wire RangeaCat. No.
Lugs
Per
Kit
$ Price
Per Kit
Standard Ampere
Rating Optional Ampere
Rating
Al Lugs for Use with Al or Cu Wire
FA, FH
FI 15–30 A FA, FH
FI 35–100 A (1) 14–4 AWG Cu or
(1) 12–4 AWG Al AL50FA 337.20
FC 35–100 A FC 15–30 A (1) 14–3 AWG Cu or
(1) 12–1 AWG Al AL100FA4 337.20
FA, FH
FI 35–100 A FA, FH
FI 15–30 A (1) 14–1/0 AWG Cu or
(1) 12–1/0 AWG Al AL100FA 337.20
— — FA, FH, FC 15–100 A (1) 12–3 AWG Cu AL100TFb337.20
——FA 150 A
(only) (1) 2–3/0 AWG AL150FA 337.20
KI 110–175 A — — (1) 4 AWG–350 kcmil AL250KA 3113.00
KI 200–250 A KI 110–175 A (1) 1/0 AWG–350 kcmil AL250KI 3107.00
Q4, LA, LH 125–400 A — — (1) 1 AWG–600 kcmil or
(2) 1 AWG–250 kcmil AL400LA 135.70
— — Q4, LA, LH 125–400 A (1) 350–750 kcmil AL400LH7 147.10
LE, LX, LXI 100–250 A LC, LI, LE, LX, LXI 300–600 A (2) 1 AWG–350 kcmil AL600LI35 149.60
LI, LE,
LX, LXI 300–600 A LE, LX, LXI 100–250 A (2) 4/0 AWG–500 kcmil AL600LI5 147.10
— — LC, LI, LE, LX, LXI — (1) 500–750 kcmil AL600LI7 153.00
Cu Lugs for Use with Cu Wire Only c
FC 15–30 A — — (1) 14–10 AWG Cu CU30FA4 337.20
— — FA, FH, FC, FI 15–100 A (1) 14–1 AWG Cu CU100FA 337.20
— — FA, FH, FC 15–100 A (1) 12–3 AWG Cu CU100TFb362.00
— — KI 110–250 A (1) 4 AWG–250 kcmil Cu CU250KA 3113.00
— — Q4, LA, LH 125–400 A (1) 1 AWG–600 kcmil Cu or
(2) 1 AWG–250 kcmil Cu CU400LA 170.00
— — LI, LE, LX, LXI — (2) 1 AWG–350 kcmil Cu CU600LI35 1230.00
— — LI, LE, LX, LXI — (2) .4/0 AWG–500 kcmil Cu CU600LI5 1230.00
— — LI, LE, LX, LXI — (1) 500–750 kcmil Cu CU600LI7 1230.00
Table 3.89: Mechanical Lug Kits for D-Frame Circuit Breakers
Description Poles 400 A Lugs 600 A Lugs
Cat. No. $ Price Cat. No. $ Price
Field-Installable Lug Kit, Terminal Cover Included 3 32508 191.00 32510 347.00
Voltage Takeoffs (set of two) 29348 28.40 29348 28.40
Wire Range (1) 2 AWG-600 kcmil stranded CU cable
(1) 2 AWG-500 kcmil stranded AL cable
(2) 2/0 AWG-350 kcmil stranded CU cable
(2) 2/0 AWG-500 kcmil stranded AL cable
Table 3.90: Terminal Shields and Phase Barriers
Used With Description Cat. No. Qty Per
Kit $ Price
D-Frame Terminal Shield
(3P)
PDC5DG2
PDC12DG2 36965 1108.00
AL50FA
AL250KI
AL250KA
AL100FA
AL400LA AL600LI5
AL400LH7
D-Frame Lugs
DE2 Discount
Schedule
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
© 2012 Schneider Electric
All Rights Reserved 3-29
Circuit Breaker
Accessories
Compression Lug and Power Distribution Connectors
Compression Lug Kits
aSee instruction bulletins for recommended tools.
bThese lug kits cannot be used on I-Line™ circuit breakers.
cUnless otherwise specified, wire sizes apply to both aluminum and copper conductors.
dAll P-frame circuit breakers require terminal pads for mounting lugs of any type.
Power Distribution Connectors (PDC) for Circuit Breakers—for Field Replacement of Mechanical
Lugs
Can be used for multiple load connections on one circuit breaker. Use in place of standard distribution blocks to save
space and time.
Field-installable kits, including tin-plated aluminum connectors and all necessary mounting hardware are available for
Square D FA, LA and Q4-frame molded case circuit breakers.
Connectors are UL Listed:
•For use on load end of circuit breaker only
•For use in UL508 Industrial Control applications only
•For use in UL 1995/CSA C22.2 No. 236 heating and cooling equipment
•For copper wire only
eNot for use with I-Line circuit breakers.
fWhen using fine stranded wire, increased cross sectional area may cause maximum wire size to be reduced.
gOFF end only when OFF end is the load end.
hKit includes long terminal shield, which adds 1.65 inches to standard lug with short terminal shield.
Table 3.91: Field-installable Compression Lug Kitsa
Circuit Breaker
Type Wire RangecDimension A
(In)
Max. Lugs
Per Terminal Cat. No. Lug Qty.
Per Kit
$ Price Per
Kit
Aluminum Compression Lug Kits
FA, FH, FC, FI 8–1/0 AWG 1.3 1 VC100FA 3175.00
KI 4 AWG–300 kcmil 1.5 1 VC250KA3 3255.00
250–350 kcmil 1.5 1 VC250KA35 3194.00
LA, LH, Q4
250–350 kcmil 1.25 2 VC400LA35 2194.00
4 AWG–300 kcmil 1.0 2 VC400LA3 2202.00
2/0 AWG–500 kcmil 2.2 1 VC400LA5 1166.00
500–750 kcmil 2.5 1 VC400LA7 1198.00
LI, LE, LX, LXI b
4 AWG–300 kcmil 1.05 2 VC600LI3 2295.00
2/0 AWG–500 kcmil 3.20 2 VC600LI5 2308.00
500–750 kcmil 3.45 1 VC600LI7 1311.00
Copper Compression Lug Kits
FA, FH, FC, FI 6–1/0 AWG Cu 1.4 1 CVC100FA 3156.00
KI 2/0 AWG–300 kcmil Cu 1.5 1 CVC250KA3 3301.00
LA, LH, Q4 2/0 AWG–300 kcmil Cu 1.3 2 CVC400LA3 2271.00
250–500 kcmil Cu 2.3 1 CVC400LA5 1118.00
LI, LE, LX, LXI b250–500 kcmil Cu 3.20 2 CVC600LI5 2491.00
Compression Lug Kits for D-Frame Circuit Breakers
Not Available
Table 3.92: PDC Lugs
Use With Circuit
Breakere
Circuit Breaker
Ampere Rating
Wires Per Terminal
& Wire Rangef
Cu
Cat. No. Lug Quantity Per Kit Dimension
A (i.)
$ Price Per
Kit
FAL, FHL, FCLg15–100 A (6) 14–6 AWG PDC6FA6 31.092.00
(3) 14–2 AWG PDC3FA2 31.292.00
LAL, LHL, Q4L 125–400 A
(6) 12–2/0 AWG PDC6LA20 12.25182.00
(12) 14–4 AWG PDC12LA4 11.25129.00
(3) 14–2 AWG
(1) 2 AWG–250 kcmil PDC4LA250 12.0129.00
Table 3.93: Power Distribution Connectors for D-Frame Circuit Breakers
Use with Circuit
Breaker Type
Circuit Breaker
Ampere Rating
Wires Per Terminal &
Wire Range Dimension A (in.) Cat. No. Quantity Per Kit $ Price Per Kit
DG, DJ, DL 150–600 (3) 14–2 AWG and (2) 14–2/0 AWG 1.28hPDC5DG20 3387.00
150–600 (12) 14–4 AWG 1.31hPDC12DG4 3387.00
Extremity
of
Molded Case
w/Mechanical
Lugs
“A” See Table
Crimp lug or
power distribution connectors
extension past end of
circuit breaker “A” See Table
CVC100FA VC250KA3
VC400LA7
VC1200NE5
VC400LA7
CVC600MA5
PDC12LA4
DE2 Discount
Schedule
www.schneider-electric.us
3-30 © 2012 Schneider Electric
All Rights Reserved
3MOLDED CASE CIRCUIT
BREAKERS
Circuit Breaker
Accessories
PowerPact™ Circuit Breakers Miscellaneous Accessories
Class 612 / Refer to Catalog 0612CT0101
aShort lug shields provide IP20 protection for mechanical lugs and are compatible with control wire terminals.
bJ-frame terminal shield is not compatible with the YA250J35 compression terminal.
cDE5A Discount Schedule
Table 3.94: Bus Bar Connections Hardware for D-Frame Circuit Breakers
Frame Description Term. No. Poles Cat. No. $ Price
D-Frame Set of 3 terminal screws and washers for one side F336966 23.70
Set of 4 terminal screws and washers for one side 4 36967 31.50
Table 3.95: Terminal Shields and Phase Barriers
Used With Description Dimension B
(in.) Cat. No. Qty Per
Kit $ Price
G-Frame Terminal Shield
(3P) —— — GYT 175.00
D-Frame Terminal Shield
(3P)
PDC5DG2
PDC12DG2 —— 36965 1108.00
Table 3.96: Miscellaneous D-Frame Circuit Breaker Accessories
Accessory Description Field-Installed
Cat. No, $ Price
External Neutral Sensor
150 A Neutral Sensor 36950 806.00
250 A Neutral Sensor 36951 806.00
400 A Neutral Sensor 36952 806.00
600 A Neutral Sensor 36953 806.00
Spare Parts 100 Identification Labels 29314 119.00
Te st K i t s Mini test kit (battery not included) 43362 884.00
Portable test kit 55391c16365.00
Table 3.97: Motor Operators for D-Frame Circuit Breakers
Description Rated
Voltage
Factory Installed
Cat. No. Suffix
Field-Installed
Cat. No, $ Price
Standard motor for
electrically-operated circuit
breakers
AC
48/60 ML 32839
3395.00
110/130 MA 32840
208/277 MD 22841
220/240 MC —
380/415 MF 32842
380/485 MH —
440/480 MH 32847
DC
24/30 MO 32843
3545.00
48/60 MP 32844
110/130 MR 32845
250 MS 32846
Locking Device
Mounting Hardware — 32649 58.00
Ronis lock — 41940 146.00
Profalux lock — 42888 146.00
Operations Counter — 32648 225.00
Mini Test Kit Portable Test Kit
Motor Operator
DE2 Discount
Schedule
www.schneider-electric.us
© 2012 Schneider Electric
All Rights Reserved 3-31
3MOLDED CASE CIRCUIT
BREAKERS
Electronic Products Neutral Current Transformers and
Micrologic™ Series B Trip Unit Accessories
Complying with NEC®
The National Electrical Code, Section 240-6(c) exception allows conductor ampere ratings
equal to the selected long-time pick-up setting. Square D offers the seals below to restrict
access to trip unit once settings are selected.
aRequired for Micrologic to communicate with PowerLogic™ system.
Table 3.98: Neutral Current Transformers
Cat. No. $ Price Sensor Where Used
LE25CT2
LE4CT2
LE6CT2
588.00
588.00
588.00
250 A
400 A
600 A
LXL, LEL, LXIL
Table 3.99: Electronic Trip Indicator and Current Meter Field-installable Kits
Device Cat. No. Included With
Circuit Breaker Optional $ Price
Local Trip Indicator Kit ALTI —LXL, LXIL1461.00
Local Current Meter Kit/Trip Indicator ALAM LEL LXL, LXIL 2286.00
Table 3.100: Interchangeable Rating Plug Kits for all Circuit Breakers with
Micrologic Series B Trip System
Cat. No. Sensor Multiplier Value $ Price
ARP040 0.400 297.00
ARP050 0.500 297.00
ARP056 0.563 297.00
ARP058 0.583 297.00
ARP060 0.600 297.00
ARP063 0.625 297.00
ARP067 0.667 297.00
ARP070 0.700 297.00
ARP075 0.750 297.00
ARP080 0.800 297.00
ARP083 0.833 297.00
ARP088 0.875 297.00
ARP090 0.900 297.00
ARP100 1.000 297.00
Table 3.101: Trip Unit Seals
Description Cat. No. Package Quantity $ Price
Trip Unit Seal TUSEAL 100 102.00
Table 3.102: Communication Adapter
Description Cat. No. $ Price
Communication Adapter CIM3Fa465.00
Table 3.103: Test Equipment for Circuit Breakers with Micrologic Series B Trip
Systems
Description Cat. No. $ Price
Universal Test Set (includes test module for Full-function and Standard-function LEL, LXL, LXIL) UTS3 14022.00
Test Module for Full-function and Standard-function LEL, LXL, LXIL. (For use with existing CBTU1
or UTS3 test set.) CBTMB 2349.00
Replacement ribbon cable and rating plug adapter for CBTMB CBTMBRK 627.00
Long-time and ground-fault Memory Reset Module (Series B Electronics) MTMB 381.00
Combination Local Current Meter
and Trip Indicator
Electronic Trip Unit with Seals Installed
to Restrict Access
CIM3F Communication Adapter
Universal Test Set
DE2 Discount
Schedule
www.schneider-electric.us
3-32 © 2012 Schneider Electric
All Rights Reserved
3MOLDED CASE CIRCUIT
BREAKERS
Electronic Products Restraint Interface Module
S48890 and S48895 Restraint Interface Modules
The Restraint Interface Module (RIM) is used to allow
zone-selective Interlocking communications between
circuit breakers with Micrologic™ Series B trip units or
Micrologic™ #.Ox trip units, Compact™ STR53 trip units,
Masterpact™ STR58 trip units, Federal Pioneer USRC
and USRCM trip units, and Square D GC series ground-
fault relays.
Upstream circuit breakers with Micrologic 3.0A, 5.0A 5.0P,
5.0H, 6.0A, 6.0P, and 6.0H trip units can receive up to 15
input signals without requiring a restraint interface
module. If the number of input signals exceeds 15, then a
RIM is required. Contact your local Sales Office for RIM
requirements.
The restraint interface module operates on either 120
Vac/24 Vdc, or 240 Vac/24 Vdc, 50/50 Hz.
NOTE: The maximum distance between devices is
1000 ft. (305 m)
Table 3.104: RIM Requirements
Note: R=RIM module is required to restrain any devices.
Numerical References=Maximum number of upstream circuit breakers which can be
restrained without requiring a RIM module.
Micrologic
#.0x Trip Units
Square D Micrologic
Series B Trip Units
Square D GC-100 Ground-Fault
Relay for Equipment Protection
Square DGC-200 Ground-Fault
Relay for Equipment Protection
Merin Gerin
STR58 Trip Units
Federal Pioneer
USRC and USRCM Trip Units
Micrologic #.0x Trip Units 15 R R 15 15 R
Square D Micrologic Series B Trip Units R26R R R15
Square D GC-100 Ground-Fault
Relay for Equipment Protection RR7RRR
Square D GC-200 Ground-Fault
Relay for Equipment Protection 15 R R 15 15 R
Merlin Gerin STR58 Trip Units 15 R R 15 15 R
Merlin Gerin STR53 Trip Units 15 R R 15 15 R
Federal Pioneer USRC
and USRCM Trip Units R15R R R15
Square D Add-on Ground-Fault Module
for Equipment Protection R5RRRR
Upstream Device
(receives input
from RIM)
Downstream Device
(sends output to RIM))
Table 3.105: Restrain Interface Module (RIM)
Cat. No. Voltage $ Price
S48890 120 Vac/24 Vdc 1860.00
S48895 240 Vac/24 Vdc 1860.00
DE2 Discount
Schedule
www.schneider-electric.us
© 2012 Schneider Electric
All Rights Reserved 3-33
3MOLDED CASE CIRCUIT
BREAKERS
Circuit Breaker
Dimensions
Table 3.106: Circuit Breakers Dimensions
Circuit Breaker
Catalog No.
Prefix
No.
Poles
Fig.
No.
Dimensions—Inches
A B C D E F G H
FAL, FHL
1 21 6.00 1.50 3.16 4.13 0.44 5.13 1.50 —
2 22 6.00 3.00 3.16 4.13 0.44 5.13 — —
3 23 6.00 4.50 3.16 4.13 0.44 5.13 1.50 0.75
KAL, KCL, KHL 2 & 3 23 8.00 4.50 3.66 4.75 0.44 7.13 1.50 0.75
FIL, KIL 2 & 3 23 8.00 4.50 3.66 4.75 0.44 7.13 1.50 0.75
GJ 3 32 3.54 4.72 2.76 3.94 2.20 — — —
DG, DJ, DL 3 28 13.38 5.51 3.75 6.61 2.22 8.93 1.77 —
LC, LI, LE, LX, LXI 2 & 3 23 11.86 7.50 5.48 6.74 0.55 10.75 2.50 —
Q4L, LAL, LHL 2 & 3 23 11.00 6.00 4.06 5.84 0.88 9.25 2.00 1.00
MAL, MHL 2 & 3 23 14.00 9.00 4.53 6.50 1.66 10.69 3.00 1.50
Table 3.107: Shipping Weights
Frame Size Approx. Shipping Weight
(Lbs.)
FAL
FHL 2-pole
FCL
3
FAL
FHL 3-pole 5
FIL 8
KAL, KHL 7
KIL 9
Q4L 15
DG, DJ, DL 14
GJ 3
LAL
LHL 15
LXL
LEL
LIL
25
MAL, MHL 34
Figure 21
A
G
B
E
F
E
C/L
Figure 22
B
E
E
FA
Figure 23
C/L
B
D
C
G
HH
E
E
FA
Figure 32
A
EB
C
D
A
C
D
B
G
F
Figure 28
3-34 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
Enclosures Industrial Circuit Breaker Enclosures
Class 610
Circuit breaker enclosures are UL Listed, CSA Certified and are suitable for use as service equipment except as
footnoted.
•The short circuit rating of an enclosed circuit breaker is equal to the rating of the circuit breaker installed, except as footnoted.
•Circuit breakers are ordered and shipped separately for field installation.
•For enclosure accessories refer to page 3-36 . For enclosure dimensions refer to page 3-35.
aEnclosures with NRB or RB suffix have provisions for 3/4 in. through 2-1/2 in. bolt-on hubs in top endwall. Enclosures with R suffix have blank endwalls
and require field cut opening. For details and hub catalog numbers see Digest Section 3.
bNEMA 7—Indoor Hazardous Locations—Division 1 and 2, Class I, Groups C and D; Class II, Groups E, F and G; Class III.
cSuitable for rainproof NEMA 3R application by removing drain screw from bottom endwall.
dShort circuit rating is 100 k AIR at 480 Vac maximum.
eNEMA 9—Indoor Hazardous Locations–Division 1 and 2, Class II, Groups E, F and G; Class III
fUse 75oC Copper conductors only.
gSuitable for rainproof applications—includes PKDB1 breather and drain kit.
hcULus listed.
Enclosed Motor-Operated Molded Case Circuit Breakers
NOTE: Contact local Field Office for catalog number prior to quoting or placing an order.
Motor-operated enclosed circuit breakers are utilized whenever it is desired to control the operation of an individually
mounted circuit breaker from a remote location. Enclosed motor operated circuit breakers are available in either NEMA
1 or 3R construction. 120 Vac control circuit required for operation of motor operator. Sufficient space is included for
field-installation of a terminal block for convenient end-user control circuit wiring. Not UL Listed.
Enclosed motor-operated circuit breaker with neutral
•Specify circuit breaker catalog number (ex: FAL36060)
•Specify side mounted operator only.
•Specify enclosure type (ex: NEMA 1, 3R, 12)
•Specify if neutrals are required (Same price)
aPrice includes 3P circuit breaker, motor operator, and neutral assembly
factory assembled in specified enclosure.
Table 3.108: Circuit Breaker Enclosures
Circuit Breaker Enclosure
Cat. No. Prefix Rating Poles Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
NEMA 4, 4X, 5, 3, 3R Stainless
Steel (Hubs—See page 3-9)
NEMA 12/3R, 12K (Hubs—See page 3-9)
With Knockouts (NEMA 12K) Without Knockoutsc (NEMA 12/3R, 5)
KILd110–250 A 2, 3 IK250DS 5238.00 ——IK250AWK 878.00
NEMA 7b Cast Aluminum NEMA 9e Cast Aluminum
FALf15–60 A 1, 2, 3 FA060Xgh 1620.00 FA060Yh1227.00
15–100 A 1, 2, 3 FA100Xgh 2006.00 FA100Yh1389.00
Table 3.109: Enclosed Motor-Operated Circuit Breakers
Circuit Breaker Type $ Price a
NEMA 1 NEMA 3R
FAL—240 V 2915.00 3149.00
FAL—480 V 3131.00 3369.00
FAL—600 V 3308.00 3525.00
FHL—600 V 3725.00 3950.00
LAL—600 V 11187.00 11477.00
LHL—600 V 14147.00 14429.00
FA100X
FA100Y
DE1 DE2A Discount
Schedule
www.schneider-electric.us
3MOLDED CASE CIRCUIT
BREAKERS
© 2012 Schneider Electric
All Rights Reserved 3-35
Enclosures Enclosed Switches and Enclosure Dimensions
Class 610
Enclosed Molded Case Switches
Enclosed molded case switches are UL Listed devices supplied with factory-installed automatic molded case switch.
Use the Cat. No. listed below and add the enclosure style suffix. An insulated groundable neutral, if required, must be
ordered separately from Digest page 7-58. Enclosed molded case switches are manufactured on order only.
aFHE and KHE devices accept bolt-on hubs and have a suffix RB. LHE, MHE and NCE devices have blank endwalls and have a suffix R. For details and
hub catalog numbers see page 3-9.
Dimensions: Refer to enclosed circuit breaker dimensions by NEMA type.
Table 3.110: Enclosed Molded Case Switches
System Ampere
Rating
Cat. No.
Add Suffix
600 Vac
Short Circuit
Withstand Ratings
$ Price
NEMA 1 NEMA 3RaNEMA 4,4X,5 NEMA 12
(F) or (S) (RB) or (R) (DS) (AWK)
FH—100 A Frame, 3P, 600 Vac Max.
2P 100 FHE26000( ) 18 kA 963.00 1277.00 2273.00 1083.00
3P 100 FHE36000( ) 18 kA 1187.00 1499.00 2432.00 1310.00
LH—400 A Frame, 3P, 600 Vac Max.
2P 400 LHE26000( ) 25 kA 3915.00 5174.00 9264.00 4497.00
3P 400 LHE36000( ) 25 kA 4653.00 5982.00 9999.00 5232.00
Table 3.111: Enclosure Dimensions
Cat. No.
Approximate Dimension
Series H W D
in. mm in. mm in. mm
FA060XaE1 16.00 406 9.88 251 7.00 178
FA060YaE1 16.00 406 9.88 251 7.00 178
FA100Xa
FA100Ya
E1
E1
16.00
16.00
406
406
9.88
9.88
251
251
7.00
7.00
178
178
IK250DS
IK250AWK
E2
E2
42.25
42.25
1073
1073
13.88
13.88
353
353
7.50
7.50
191
191
aTapped conduit opening, top and bottom endwall: FA060X/Y– 3/4", FA100X/Y–1-1/4"
W
H
D
Enclosures FA060X, FA100X,
FA060Y and FA100Y
Enclosures for IK250DS
and IK250AWK
W
H
D
DE1 Discount
Schedule
www.schneider-electric.us
3-36 © 2012 Schneider Electric
All Rights Reserved
3MOLDED CASE CIRCUIT
BREAKERS
Enclosures
Accessories
Lock-On Provisions
Lock-off provisions are standard on all NEMA Type 4-4X-5 stainless steel
and NEMA Type 12, 12K circuit breaker enclosures. Provision for one inch
hasp padlock is available factory installed. This modification will allow the
circuit breaker to be locked in the ON position. When locked in the ON
position, the external operator will not indicate if circuit breaker is tripped. UL
Listed.
Pilot Light—Selector Switch—Push Button
Pilot lights, push buttons or selector switches are available factory
installed in the cover of NEMA Type 3R, (4-4X-5) stainless steel or 12
enclosures. Wiring to contact blocks is not available. Customer must
furnish catalog number of device desired. Price = circuit breaker +
enclosure + neutral + ground + pilot light, push button and/or selector
switch + factory-installed adder. Order by description. Not UL Listed.
Phenolic Legend Plate
Available engraved and mounted on most circuit breaker enclosures.
Legend engraved in 1/4-inch high white letters on black background.
Customer must provide legend. UL Listed. Not available on NEMA Type
7 or 9 enclosures.
To order, add suffix NP to standard catalog number (i.e. LA400SNP).
Price adder per legend plate: $167.00
Special Paint
UL Listed circuit breaker enclosures are available painted with special
safety colors. To order safety colored enclosures add suffixes as noted
in Table 3.115 to the standard enclosure commercial reference number.
All colors comply with OSHA Standard 1910.144 and ANSI Specification
Z535.1 for marking physical hazards.
A minimum quantity of ten is required. Order by description. Not
available for NEMA Type 7/9 or stainless steel enclosures.
Shipment: 6 weeks
aStandard Square D ANSI 49 grey paint, when selecting this suffix, switches will receive
additional coat of paint.
Stainless Steel Front
The FA100F NEMA Type 1, flush-mount circuit breaker enclosure is
available with a stainless steel front. This modification is desirable in
food handling areas such as cafeterias and restaurants.
Enclosed Ground-Fault Modules (GFM)
Ground-fault modules (GFM) can be factory installed on FAL and FHL
circuit breakers and enclosed in the next larger size NEMA 1 or 3R
enclosure.
Enclosed circuit breaker with ground-fault module
•Specify circuit breaker catalog number
•Specify enclosure type (NEMA 1 or 3R)
•Ground-fault modules are available factory installed. See table below for
pricing and availability.
bPrice includes 3P circuit breaker, GFM, neutral assembly and neutral CT factory
assembled in specified enclosure
cNot UL Listed
Equipment Ground Kit
Price adder includes price of ground bar kit.
Table 3.112: Price Adder Each Enclosure
Enclosure Prefix Suffix for Lock-On Provision $ Price
FA, J SPLO 155.00
LA, M, P 234.00
Table 3.113: Price Adder
Quantity $ Price Adder
For Each Device Installed 297.00
Lock-on Provision
Table 3.114: Price Adder Each Enclosure
Enclosure Prefix
FA $ Price J $ Price LA $ Price P $ Price
113.00 180.00 327.00 513.00
Table 3.115: Safety Colors
Safety Color Suffix
Black SP0
Red SP2
Orange SP3
Yellow SP4
Green SP5
Blue SP6
Purple SP7
Gray SP8
Gray ANSI61 SP861a
White SP9
Table 3.116: Price Each Enclosure
Cat. No. $ Price
FA100FSS 1659.00
Table 3.117: Enclosed Circuit Breaker with Ground Fault Modulec
Circuit Breaker
Prefix
$ Price b
NEMA 1 NEMA 3R
FAL, 600 V, 15–60 A 6585.00 7091.00
FAL, 600 V, 70–100 A 6797.00 7307.00
Table 3.118: Insulated Groundable Neutral Assembly
Circuit Breaker Neutral Assembly For Use With Terminal Lug Data—Total Available
(Line plus Load)
AWG/kcmil
Cat. No. Prefix Ampere
Rating
NEMA 1 & 3R NEMA 4, 4X, 5, 12 & 12K NEMA 7 & 9
Cat. No. $ Price Cat. No. Price Cat. No. $ Price
KIL
KIL
225
250
—
—
—
—
SN225KA
SN400LA
201.00
251.00
—
—
—
—
(2) 4–300 Al/Cu, plus (2) 14–1/0 Al/Cu
(2) 1–600 or (4) 1–250 Al/Cu, plus (2) 4–300 Al/Cu
Table 3.119: Ground Kit Price Adder
Enclosure Number of
Terminals per
Kit
Conductors
Per Terminal
Wire Range
AWG/kcmil
Field-Installable Factory-Installedd
Enclosure Type Circuit Breaker Cat. No. Prefix Ground Bar
Kit Cat. No. $ Price Suffix $ Price
NEMA Type 1 and 3R
FAL, FHL, FIL
KIL
LAL, LHL 21 10–2/0 Cu or
6–2/0 Al PKOGTA2f263.00 GL 191.00
NEMA Type 4-4X-5 stainless steel
and NEMA Type 12
FAL, FHL, FIL
KIL
LAL, LHL, Q4L
M, Pe2 1 10–2/0 Cu or 6–2/0 Al 263.00 263.00
dFor factory installation of equipment ground lugs in these or any other enclosures, add suffix GL.
eUse of PKOGTA2 with M, and P enclosure prefix not UL Listed
fQuantity (2) may be required for some wire installation.
DE1 Discount
Schedule
www.schneider-electric.us
© 2012 Schneider Electric
All Rights Reserved 3-37
3MOLDED CASE CIRCUIT
BREAKERS
Enclosures Key Interlock Systems—Factory Installed Only
Class 736, 1130
Key Interlock Systems
(Factory installed only)
Interlocks are used to prevent the authorized operator from making an unauthorized
operation. Not available on hazardous location devices (NEMA 7/9.)
The key interlock system is a simple and easy method of applying individual key interlock
units and assemblies to the above equipment so as to require operation in a predetermined
sequence. UL Listed.
Quoting:
Contact local Field Sales office for catalog number, availability and pricing prior to quoting a
job.
Ordering:
•Order cannot be released for production until the following information has been provided.
•End User—Company name, address
•Function of each lock (e.g., circuit breaker to be locked open with key removed, key held when
circuit breaker is closed)
•Existing Equipment—if circuit breaker is to be interlocked with equipment already on site, provide
brand of existing lock and key number
•Other New Equipment—if circuit breaker is to be interlocked with new equipment not yet installed at
the site, then provide contact person and phone number so that locks may be coordinated
•Additional information may be required upon order entry
•Federal Pioneer locks supplied unless otherwise specified
aPrices do not apply when more than three devices are interlocked as these schemes
normally require more than one key assembly per device.
Table 3.120: Locking Position Designations
Locking
Position Designation
Device locked open with key removed.
Device locked closed with key removed.
Device locked open or closed with key removed.
Device locked open with key held.
Device locked closed with key held.
Device locked open or closed with key held.
Multi-lock interlock.
(More than one key per lock.)
NOTE: 1. Device locked open (circuit
breaker in OFF position).
2. Device locked closed (circuit
breaker in ON position).
L-O-R
L-C-R
L-O-C-R
L-O-H
L-C-H
L-O-C-H
Table 3.121: Price Adder Per Lock, Each Complete Enclosed Devicea
Device $ Price
Enclosed industrial circuit breaker 2055.00
DE1 Discount
Schedule
www.schneider-electric.us
3-38 © 2012 Schneider Electric
All Rights Reserved
3MOLDED CASE CIRCUIT
BREAKERS
Enclosures Special Applications
Class 610
Sample Application—1
To prevent two devices from being closed simultaneously.
Two devices are shown in Figure 1. In operation they are not closed at
the same time. With the interlocks arranged as shown only one key is
required in the interlocking system. Both devices are shown open,
therefore, the key is free. To close any one device the key is inserted
and turned in that particular lock, the key is held in this lock until the
device is again locked open. This simple interlocking sequence lends
itself to a multitude of applications. The procedure is the same for two
devices, neither of which is to be opened at the same time.
Sample Application—2
To prevent opening of switch A when circuit breaker B is closed.
Switch A and circuit breaker B are in closed position. Key A-1 is held in
circuit breaker B interlock.
1. Open circuit breaker.
2. Turn key A-1 in L-O-R interlock on circuit breaker B to lock open. Key A-1 is
now free.
3. Insert key A-1 in L-C-R interlock on switch A and turn to unlock.
4. Open switch A. Key A-1 is now held. Reverse sequence to restore service.
Sample Application—3
To prevent operation of switch A when circuit breaker B is closed.
Permits reclosing of circuit breaker for servicing when switch is locked
open.
Switch A and circuit breaker B are in closed position. Key A-1 is held in
circuit breaker interlock.
1. Open circuit breaker.
2. Turn key A-1 in L-O-R interlock on circuit breaker B to lock open. Key A-1 is
now free.
3. Insert key A-1 in L-O-C-R interlock on switch A and turn to unlock.
4. Open switch A.
5. Turn key A-1 in L-O-C-R interlock on switch A to lock open. Key A-1 is now
free.
6. Return key A-1 to circuit breaker interlock and unlock for operation during
servicing period.
Reverse sequence to restore service.
Sample Application—4 (Main-Tie-Main)
To prevent paralleling of lines A and B.—Two loads, fed from either
source.
Circuit breaker A is closed to supply load M. Circuit breaker B is closed
to supply load N. Tie-circuit breaker C is open. Keys A-1 are held in
interlocks on both circuit breakers A and B. Tie-circuit breaker C cannot
be closed unless either A or B is locked open.
To transfer load N to circuit breaker A, proceed as follows:
1. Open circuit breaker B.
2. Turn key A-1 in L-O-R interlock on circuit breaker B to lock open. Key A-1 is
now free.
3. Insert Key A-1 in L-O-R interlock on tie-circuit breaker C and turn to unlock.
Key A-1 is now held.
4. Close tie-circuit breaker C.
Reverse sequence to restore service.
Load M can be supplied through circuit breaker B in a similar manner.
. . . . . . . . Device normally open
. . . . . . . . Device normally closed
. . . . . . . . Direction of key transfer
. . . . . . . . Key interchange number
. . . . . . . . Key
Diagram Symbols
A-1 A-2 A-3
Figure 1
A-1
A 1
L-O-R L-O-R
AB
A-1
Figure 2
A-1
L-C-R L-O-R
A
B
A 1
Figure 3
A-1
L-O-C-R L-O-R
A
B
A 1
Figure 4
L-O-R
C
L-O-R
A
A
NM
A 1
L-O-R
A 1
A-1
B
B
4-1
© 2012 Schneider Electric
All Rights Reserved
4PANELBOARDS
Table of Contents
Section 4
Panelboards
NQ Panelboard with
Door-in-Door (Hinged) Trim
MH38 Enclosure with 12-inch Wireway and
Mono-Flat™ Trim with 12-inch Wireway Cover
Factory Assembled Panelboard Special Features
General Instructions 4-2
Pricing Instructions 4-2
Metric Conversion 4-2
I-Line Panelboards Factory Assembled Pricing 4-2
Metering 4-3
Current Transformers 4-3
Customer Equipment Space 4-3
Keyed Interlocks 4-3
Motor Operators 4-3
Increased Enclosure Depth 4-4
Increased Side Gutters 4-4
Extended Top and Bottom End Gutters 4-4
Drip Hoods 4-4
Special Finishes
(non-standard paint color, painted enclosures, etc.)
4-4
Free Standing Enclosures 4-4
Special Trims (hinged, stainless steel, etc.) 4-4
Padlock Hasp 4-5
Special Locks 4-5
Multi-section Panels
(equal-height enclosures, common trims, etc.)
4-5
Panel Skirts 4-6
Wireway 4-6
Panels to Fit Existing Enclosures 4-7
Space Heater 4-7
Special Enclosures
(Type 1, 3R-12, 4, 4X, etc.)
4-8
NQ Merchandised Panelboards
NQ Main Lug and Main Circuit Breaker Panelboard
with SPD
4-9
Ready-to-Install (RTI) Merchandise
Copper Equipment Ground Bars 4-10
Field Installable I-Line™ Door Kits 4-10
Type 1 Door-in-Door (Hinged) Trim Fronts 4-10
Replacement Parts for Standard Panelboards
Trim Clamps and Screws 4-11
Locks and Keys 4-12
CTC Cabinets 4-13
Datasheet for the Retrofit of an Existing
Enclosure
4-14
4-2 © 2012 Schneider Electric
All Rights Reserved
www.schneider-electric.us
4PANELBOARDS
Panelboards General Information
cRefer to Table 4.3 for LE, LX and LXI Micrologic Trip Unit price adders.
General Instructions
The special feature options covered in this Panelboard estimating
procedure are applicable to factory-assembled panelboards only. Do
not apply this pricing to ready-to-assemble panelboards.
Special features are listed in three major categories:
• Mains
• Branches
• Cabinets
Pricing Instructions
All special feature entry prices are list prices.
Price the panelboard in the standard manner, then add for any special
features required to obtain the total price.
Certain features already appear in the Q2C or EQM panelboard
quotation system. For those features not listed in the quotation system,
enter the information as it appears in this publication with the
appropriate price in the “Other Special Features” screen in Q2C or
EQM. Follow the example below:
Metric Conversion
Inches (in.) x 25.4 = millimeters (mm).
I-Line™ Panelboards Factory Assembled Pricing
Table 4.1: Basic $ Price – Main Circuit Breaker
Panel Type No.
Poles
Main Circuit Breakera
400 A 600 A
LXbLEbLXIbLXbLEbLXIb
HCP, HCP-SU 210976.00 15232.00 19944.00 14312.00 17078.00 29878.00
312132.00 17944.00 22734.00 17822.00 20590.00 33390.
aWhen required, add the $ Price of a solid neutral from Digest Table 9.125.
bStd. construction back-fed main.
Quantity Description $ Price
1 Corbin Locks 704.00
Table 4.2: Micrologic LE, LX and LXI Branch Circuit Breakers (See Digest pages 7-7 for interrupting rating,
voltage rating, Fed. Specs. etc.)
Circuit
Breaker
Ampere
Circuit
Breaker
3 pole 2 pole 1 pole
240 V 480 Vac
250 Vdc 600 V Space
only H240 V 480 Vac
250 Vdc
480 Vac
250 Vdc
Space
only H120 V 277 V 277 Vac
125 Vdc
Space
only H
Micrologic™ Circuit Breakers (% Rated)
100–250 A
LX (80%)c
— — 10100.00
456.00 7.5
— — 7580.00
456.00 7.5
——— ——
300–400 A — — 10400.00 — — 9240.00 — — — — —
450–600 A — — 15566.00 — — 12056.00 — — — — —
100–250 A
LXI (80%)c
— — 16556.00
456.00 7.5
— — 13666.00
456.00 7.5
——— ——
300–400 A — — 21002.00 — — 18212.00 — — — — —
450–600 A — — 31134.00 — — 27622.00 — — — — —
100–250 A LE
(100%)c
— — 14544.00 456.00 7.5 — — 10740.00 456.00 7.5 ——— ——
300–400 A — — 16212.00 — — 13500.00 — — — — —
450–600 A LE (80%)c— — 18334.00 456.00 7.5 — — 14820.00 456.00 7.5 ——— ——
Table 4.3: LE, LX & LXI Micrologic Trip Units
LE LX and LXI
LI - Std —
LSI - $4670.00 Standard
LIG - $4670.00 —
LSIG - $9340.00 $12,880.00
Table 4.4: D-Frame (600 A 480 Vac) 3P 50/60 Hz circuit Breaker with Electronic Trip Units
Electronic
Trip Unit
Type
Trip
Function Trip Unit Continuous
Currenta
G Interrupting J Interrupting L Interrupting
Terminal Wire Ratings
Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price
Standard
LS STR23SP
150 A DGA34150E20
5631.00
DJA34150E20
9028.00
DLA34150E20
10468.00 (1) 2–600 Cu or (1) 2– 500 Al250 A DGA34250E20 DJA34250E20 DLA34250E20
400 A DGA34400E20 DJA34400E20 DLA34400E20
600 A DGA34600E20 8865.00 DJA34600E20 12262.00 DLA34600E20 13702.00 (2) 2/0–350 Cu or (2) 2/0–500 Al
LSI STR53UP-b
150 A DGA34150E53
6750.00
DJA34150E53
10147.00
DLA34150E53
11587.00 (1) 2–600 Cu or (1) 2– 500 Al250 A DGA34250E53 DJA34250E53 DLA34250E53
400 A DGA34400E53 DJA34400E53 DLA34400E53
600 A DGA34600E53 9984.00 DJA34600E53 13381.00 DLA34600E53 14821.00 (2) 2/0–350 Cu or (2) 2/0–500 Al