ENCLOSED SWITCHES LAYOUT

2014-07-05

: Pdf 107354-Attachment 107354-Attachment 093045 Batch5 unilog

Open the PDF directly: View PDF PDF.
Page Count: 2

• Compact size
Visible blade, double break switching action
• Quick make, quick break operating mechanism
• Indoor and galvanized steel outdoor enclosures
• Highly visible “ON” / “OFF” indications
• Bondable Neutral (where indicated)
• Cover interlock on indoor enclosures
• Padlocking provisions to lock cover
closed or to lock switch in the “OFF”position
30 Amp General Duty
Enclosed Switches
• UL listed under file #E4776
• All fusible switches suitable for use as service
entrance equipment
• Fused switches rated 10,000 AlC with either
plug or Class H fuses or 100,000 AlC with
Class R fuses
• Meets federal spec WS865C
(type LD or type NDS)
Indoor - Type 1 Outdoor - Type 3R
Horsepower Ratings 120/240V AC HP Rating
Ampere Fuse Catalog List Ship Wt Catalog List Ship Wt 1 Phase 2W 3 Phase 3W 250 Volt
Rating Type Number Price $ (Std Pkg) Number Price $ (Std Pkg) Std Max Std Max DC
30 Plug LF111N 46.50 35 (10) LF111NR 96.00 35 (10) ¹⁄₂ 2— —
30 Cartridge GF321N 117.00 24 (5) GF321NR 182.00 24 (5) 1¹⁄₂ 3 3 7¹⁄₂
30 GNF321 96.00 24 (5) GNF321R 182.00 24 (5) 3 7¹⁄₂ 5 (Std)
60 Use Outoor LNF222R103.00 35 (10) 10
30 Plug LF211N 57.00 35 (10) LF211NR 117.00 35 (10) 1¹⁄₂ 3—
30 Cartridge GF221N74.00 35 (10) GF221NR 117.00 35 (10) 1¹⁄₂ 33 7¹⁄₂ 5 (Std)
120 Volt Fusible - 1 Pole and Neutral
Features Ratings
Ordering Information
120/240 Volt Fusible - 2 Pole and Neutral
240 Volt Max Fusible - 3 Pole and Neutral (Also use for 240V, 3P, 3W Applications)
240 Volt Max Non-Fusible - 3 Pole(Also use for 240V, 2P Applications)
240 Volt Max Non-Fusible - 2 Pole Special Application (Bottom Cable Entry and Exit Only)
Dual horsepower ratings standard applies when non-
time delay fuses are installed Max - applies when time
delay fuses are installed.
Use neutral kit catalog number W410190 for 1 Phase,
3W or 3 Phase, 4W applications.
Bottom cable entry & exit only No hub provisions
supplied.
Suitable for 3 Pole motor loads.
These switches can also be used for 240V 2P, 2W
applications and are UL listed for application on a
grounded B system.
Ratings shown are 120V - 1 Phase, 2W.
New Switch Catalog Numbering System
PART 1 PART 2 PART 3 PART 4 PART 5 PART 6 PART 7
Switch Fused or Number Voltage Ampere With or Enclosure
Type Non Fused of Poles Rating Rating Without Neutral Type
L = Gen. Duty F = Fused 1 = 1 1 = 120V 1 = 30A Omit = Less Omit = Type 1
10k AIC Max. or Neutral Indoor
(Plug Fused and NF=Non-Fused 2 = 2 120/240V 2 = 60A
60A Special N = with R = Type 3R
Application) 3 = 3 2 = 240V Neutral Outdoor
G = Gen. Duty
100k AIC Max.
LF211
GF321
GNF321R
LNF222R
BACK
B
C
A
D
1 5/8"
Embossed 0.25 in.
Mounting Hole
(4 Places)
2 K. O.'s for
0.5, 0.75 in.
Conduit
10 K. O.'s for
0.5, 0.75, 1 in.
Conduit
Embossed 0.25 in.
Mounting Hole
(3 Places)
2 K. O.'s for
0.5, 0.75 in.
Conduit
3 K. O.'s for
0.5, 0.75, 1 in.
Conduit
Removable Plate
Covering HA Type
Hub Opening
(Max. 1" Conduit)
Embossed 0.25 in.
Mounting Hole
(3 Places)
2 K. O.'s for
0.5, 0.75 in.
Conduit
4 K. O.'s for
0.5, 0.75, 1 in.
Conduit
Removable Plate
Covering HA Type
Hub Opening
(Max. 1" Conduit)
Embossed 0.25 in.
Mounting Hole
(3 Places)
2 K. O.'s for
0.5, 0.75 in.
Conduit
3 K. O.'s for
0.5, 0.75, 1 in.
Conduit
Outline Drawings and Knockout Diagrams
© 1999 Siemens Energy & Automation, Inc. Bulletin RPFL-1014AS (Revised)
Siemens is a registered trademark of Siemens AG 5M0399SP Printed in U.S.A.
Description Wire Range Cu/Al
30A Switch Line #14 - 6 AWG
30A Switch Load #14 - 8 AWG
60A Switch Line & Load #14 - 3 AWG
30A Neutral Kit (W410190) #14 - 8 AWG
30 - 60A Ground Kit (GSGK60) #14 - 2 AWG
Catalog Number Description List Price $
HA075S ³⁄₄” Type “HA” Outdoor Hub 21.50
HA100S 1” Type “HA” Outdoor Hub 21.50
HA125S 1 ¹⁄₄” Type “HA” Outdoor Hub 21.50
GSRK321 30A Class R Fuse Clip Kit 15.00
GSGK60 30-60A Equipment Ground Kit 14.20
W410190 30A Neutral Kit 41.00
Accessories
Catalog Number Description List Price $
W410472 A Replacement Interior 2P Fusible37.00
W410473 A Replacement Interior 3P Fusible 53.00
W410473 B Replacement Interior Non-Fusible 43.00
Replacement Interiors
Dimensions & Old to New Cross Reference
Lug Wire Ranges (60/75°C)
Siemens Energy & Automation, Inc.
Distribution Products Division
5400 Triangle Parkway
Norcross, GA 30082
For information, call Siemens at:
1-800-964-4114
or visit our web site at:
http:/www.sea.siemens.com
Embossed 0.25 in.
Mounting Hole
(4 Places)
4 K. O.'s for
0.5, 0.75 in.
Conduit
7 K. O.'s for
0.5, 0.75, 1 in.
Conduit
For cartridge type fusible switches only.
New Old New Switch Dimensions (Inches) New
Switch Vacu-Break Width Switch
Catalog Cat. No. Height Box Rain Shed With Handle Depth Knockout
Number (for ref. only) A B E C D Diagram
LF111N CFN211 8 1/4 5 1/2 — 5 13/16 3 S1N
LF111NR CFNR211 8 1/4 5 3/8 5 9/16 5 13/16 3 1/8 S3N
LF211N CFN311 8 1/4 5 1/2 — 5 13/16 3 S1N
LF211NR CFNR311 8 1/4 5 3/8 5 9/16 5 13/16 3 1/8 S3N
LNF222R CNFR222 8 1/4 5 3/8 5 9/16 5 13/16 3 1/8 S5N
GF221N JN321 8 1/4 5 1/2 — 5 13/16 3 S1N
GF221N + GSRK321 JN321R 8 1/4 5 1/2 — 5 13/16 3 S1N
GF221NR NR321 8 1/4 5 3/8 5 9/16 5 13/16 3 1/8 S3N
GF221NR + GSRK321 NR321R 8 1/4 5 3/8 5 9/16 5 13/16 3 1/8 S3N
GF321N JN421 8 1/4 7 3/8 — 7 11/16 3 S2N
GF321N + GSRK321 JN421R 8 1/4 7 3/8 — 7 11/16 3 S2N
GF321NR NR421 8 1/4 7 3/16 7 3/8 7 11/16 3 1/8 S4N
GF321NR + GSRK321 NR421R 8 1/4 7 3/16 7 3/8 7 11/16 3 1/8 S4N
GNF321 JU321 8 1/4 7 3/8 — 7 11/16 3 S2N
GNF321R NFR321 8 1/4 7 3/16 7 3/8 7 11/16 3 1/8 S4N

Navigation menu