Surge Protective Device Transient Voltage Suppressor (TVSS) MULTI 9 SPD Series

2014-07-05

: Pdf 107630-Attachment 107630-Attachment 785901 Batch5 unilog

Open the PDF directly: View PDF PDF.
Page Count: 8

Schneider Electric Brand
s
Surge Protective Device
Transient Voltage Surge Suppressor (TVSS)
MULTI 9™ SPD Series
Class 1312
CONTENTS
Description Page
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Selection and Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MULTI 9™ SPD Series
Product Description
© 2001 Schneider Electric All Rights Reserved
211/01
PRODUCT DESCRIPTION
The MULTI 9™ Surge Protective Device (SPD), also referred to as Transient Voltage Surge Suppressor
(TVSS), manufactured by Square D provides high-quality surge protection for electronic equipment. These
devices can be mounted on a 35 mm rail on the load side of the incoming power to protect from transient
voltage surges. This product is ideal for control-panel manufacturers and electrical installers requiring
integral power protection.
The SPD provides protection for single- and multi-pole circuits and is ideal for manufacturers and integrators
of industrial, medical, and commercial instrumentation equipment. These devices provide protection up to
80 kA (refer to the “Performance Features” table on page 3) from voltage surges generated by lightning,
power supplier network switching, motors, frequency converters, etc.
The MULTI 9 circuit breakers and the SPDs mount quickly and easily to 35 mm mounting rails. The
connectors provide easy parallel connection and greater installation flexibility. The plug-in module of the
single-pole device allows replacement of a damaged SPD while still connected to the mounting rail
and circuits.
Design Features
Thermally fused suppression mode(s).
Solid state bi-directional.
Status indicator shows proper operation of the device.
Optional dry contacts for remote monitoring (on many models).
NOTE: The SPD must be used with C60N Merlin Gerin Supplementary Protectors (MGSP) of proper
rating according to the “Selection” table on page 5.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MULTI 9™ SPD Series
Product Description
3
11/01 © 2001 Schneider Electric All Rights Reserved
Performance Features
Catalog
Number
Service Voltage Poles
Maximum Surge
Current/Phase
UL®
MCOVq
IEC
Protection
Modes
Suppressed Voltage Rating (SVR) Nominal
Discharge Current
Voltage
Protection Level
LNNG
UNIMAX NPE UCINUP (LN)
12710 120 V 1 20 kA 500 V 150 V 5 kA 600 V
L–N
12711 230 V 1 20 kA 700 V 270 V 5 kA 960 V
12712 400 V 1 20 kA 1500 V 480 V 5 kA 1580 V
12713 120 V 1 45 kA 500 V 150 V 10 kA 750 V
12714 120 V 1 45 kA 500 V 150 V 10 kA 750 V
12715 230 V 1 45 kA 700 V 270 V 10 kA 1000 V
12716 230 V 1 45 kA 700 V 270 V 10 kA 1000 V
12717 400 V 1 45 kA 1500 V 480 V 10 kA 1450 V
12718 400 V 1 45 kA 1500 V 480 V 10 kA 1450 V
12719 120 V 1 65 kA 400 V 150 V 20 kA 920 V
12720 120 V 1 65 kA 400 V 150 V 20 kA 920 V
12721 230 V 1 65 kA 700 V 270 V 20 kA 1200 V
12722 230 V 1 65 kA 700 V 270 V 20 kA 1200 V
12723 400 V 1 65 kA 1200 V 480 V 20 kA 1950 V
12724 400 V 1 65 kA 1200 V 480 V 20 kA 1950 V
12725 120 V 2 20 kA 400 V 500 V 150 V 5 kA 575 V
L–N, N–G (N–PE)
12726 230 V 2 20 kA 700 V 600 V 270 V 5 kA 900 V
12727 120 V 2 45 kA 400 V 500 V 150 V 10 kA 775 V
12728 230 V 2 45 kA 700 V 600 V 270 V 10 kA 1080 V
12729 208Y/120 V 4 20 kA 400 V 500 V 300/150 V 5 kA 560 V
12730 208Y/120 V 4 20 kA 400 V 500 V 300/150 V 5 kA 560 V
12731 400Y/230 V 4 20 kA 700 V 600 V 540/270 V 5 kA 900 V
12732 400Y/230 V 4 20 kA 700 V 600 V 540/270 V 5 kA 900 V
12733 208Y/120 V 4 45 kA 400 V 500 V 300/150 V 10 kA 760 V
12734 208Y/120 V 4 45 kA 400 V 500 V 300/150 V 10 kA 760 V
12735 400Y/230 V 4 45 kA 700 V 600 V 540/270 V 10 kA 1080 V
12736 400Y/230 V 4 45 kA 700 V 600 V 540/270 V 10 kA 1080 V
12737 208Y/120 V 4 80 kA 400 V 500 V 300/150 V 20 kA 1040 V
12738 208Y/120 V 4 80 kA 400 V 500 V 300/150 V 20 kA 1040 V
12739 400Y/230 V 4 80 kA 700 V 600 V 540/270 V 20 kA 1420 V
12740 400Y/230 V 4 80 kA 700 V 600 V 540/270 V 20 kA 1420 V
qMCOV=Maximum Continuous Operating Voltage
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MULTI 9™ SPD Series
Application Information
© 2001 Schneider Electric All Rights Reserved
411/01
APPLICATION INFORMATION
The effects of lightning and the damage caused by lightning-generated transients are well known.
The failure of sensitive electronic equipment can be attributed directly to lightning-generated transients
and lower magnitude transients generated within a facility.
Transient voltages generated from inductive motors, pumps, electric welders, etc., may not always be
large enough to cause immediate damage, but they can cause sensitive equipment to malfunction.
As a result of these transient disturbances, it is beneficial for a manufacturer to install protection within
their equipment. The DIN rail products shown in this catalog provide a convenient means of
incorporating transient voltage protection within a new or existing cabinet using DIN rail mounting
configurations. The combination of MULTI 9 supplementary protectors and the DIN rail SPD Series
TVSS provides a compact way of incorporating transient voltage protection.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MULTI 9™ SPD Series
Selection and Specifications
5
11/01 © 2001 Schneider Electric All Rights Reserved
SELECTION
SPD Series Voltage Specifications
Poles Dry Contacts
Maximum Surge C60N Merlin Gerin Supplementary Protectors
Catalog
Number
Service Voltage Current/Phase
UNIMAX Rating 1 Pole 2 Pole 3 Pole 4 Pole
12710 120 V 1 No 20 kA 10 A, Curve B MG24116 MG24131
12711 230 V 1 No 20 kA 10 A, Curve B MG24116 MG24131
12712 400 V 1 No 20 kA 10 A, Curve B MG24116 MG24131
12713 120 V 1 No 45 kA 20 A, Curve B MG24119 MG24134
10 A, Curve C MG24432 MG24449
12714 120 V 1 Yes 45 kA 20 A, Curve B MG24119 MG24134
10 A, Curve C MG24432 MG24449
12715 230 V 1 No 45 kA 20 A, Curve B MG24119 MG24134
10 A, Curve C MG24432 MG24449
12716 230 V 1 Yes 45 kA 20 A, Curve B MG24119 MG24134
10 A, Curve C MG24432 MG24449
12717 400 V 1 No 45 kA 20 A, Curve B MG24119 MG24134
10 A, Curve C MG24432 MG24449
12718 400 V 1 Yes 45 kA 20 A, Curve B MG24119 MG24134
10 A, Curve C MG24432 MG24449
12719 120 V 1 No 65 kA 25 A, Curve B MG24120 MG24135
20 A, Curve C MG24435 MG24452
12720 120 V 1 Yes 65 kA 25 A, Curve B MG24120 MG24135
20 A, Curve C MG24435 MG24452
12721 230 V 1 No 65 kA 25 A, Curve B MG24120 MG24135
20 A, Curve C MG24435 MG24452
12722 230 V 1 Yes 65 kA 25 A, Curve B MG24120 MG24135
20 A, Curve C MG24435 MG24452
12723 400 V 1 No 65 kA 25 A, Curve B MG24120 MG24135
20 A, Curve C MG24435 MG24452
12724 400 V 1 Yes 65 kA 25 A, Curve B MG24120 MG24135
20 A, Curve C MG24435 MG24452
12725 120 V 2 No 20 kA 10 A, Curve B MG24116 MG24131
12726 230 V 2 No 20 kA 10 A, Curve B MG24116 MG24131
12727 120 V 2 No 45 kA 20 A, Curve B MG24119 MG24134
10 A, Curve C MG24432 MG24449
12728 230 V 2 No 45 kA 20 A, Curve B MG24119 MG24134
10 A, Curve C MG24432 MG24449
12729 208Y/120 V 4 No 20 kA 10 A, Curve B MG24146 MG24161
12730 208Y/120 V 4 Yes 20 kA 10 A, Curve B MG24146 MG24161
12731 400Y/230 V 4 No 20 kA 10 A, Curve B MG24146 MG24161
12732 400Y/230 V 4 Yes 20 kA 10 A, Curve B MG24146 MG24161
12733 208Y/120 V 4 No 45 kA 20 A, Curve B MG24149 MG24164
10 A, Curve C MG24466 MG24483
12734 208Y/120 V 4 Yes 45 kA 20 A, Curve B MG24149 MG24164
10 A, Curve C MG24466 MG24483
12735 400Y/230 V 4 No 45 kA 20 A, Curve B MG24149 MG24164
10 A, Curve C MG24466 MG24483
12736 400Y/230 V 4 Yes 45 kA 20 A, Curve B MG24149 MG24164
10 A, Curve C MG24466 MG24483
12737 208Y/120 V 4 No 80 kA 25 A, Curve C MG24470 MG24487
12738 208Y/120 V 4 Yes 80 kA 25 A, Curve C MG24470 MG24487
12739 400Y/230 V 4 No 80 kA 25 A, Curve C MG24470 MG24487
12740 400Y/230 V 4 Yes 80 kA 25 A, Curve C MG24470 MG24487
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MULTI 9™ SPD Series
Selection and Specifications
© 2001 Schneider Electric All Rights Reserved
611/01
GENERAL SPECIFICATIONS
1-Pole Replacement Modules
Catalog Number Service Voltage Maximum Surge
Dry ContactsCurrent/Phase
UNIMAX
12710M 120 V 20 kA No
12711M 230 V 20 kA No
12712M 400 V 20 kA No
12713M 120 V 45 kA No
12714M 120 V 45 kA Yes
12715M 230 V 45 kA No
12716M 230 V 45 kA Yes
12717M 400 V 45 kA No
12718M 400 V 45 kA Yes
12719M 120 V 65 kA No
12720M 120 V 65 kA Yes
12721M 230 V 65 kA No
12722M 230 V 65 kA Yes
12723M 400 V 65 kA No
12724M 400 V 65 kA Yes
Maximum Surge Current Refer to the IMAX column in the table on page 5.
Housing Rating Type 1 (IP20)
Connection Method Parallel
Termination #12 to #4 AWG (3-25 mm2)
Terminal Torque 45 lb-in (5 N•m)
Thermal Fusing Yes
Operating Temperature -22° to +160°F (-30° to +70°C)
Operating Frequency 50/60/400 Hz
Diagnostics 1 Pole, Status indicator; 2 and 4 Pole, Status LED
Product Standards to UL 1449–Second Edition and CSA C22.2
No. 0-M91, IEC 61643-1.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MULTI 9™ SPD Series
Wiring Diagrams
7
11/01 © 2001 Schneider Electric All Rights Reserved
WIRING DIAGRAMS
L/N
G
Load
Breakers
MGSP
L
N
L/N
G
LN
G
Load
Breakers
MGSP
L
N
1-phase, 2-wire 120 Vac or
230 Vac using a 2-pole SPD
MGSP
Load
Breakers
L3
N
L2
L1
G
L1 L2 L3
N
3-phase, 4-wire 208Y/120 Vac or 400Y/230 Vac using a 4-pole SPD
1-phase, 2-wire 120 Vac, 230 Vac, or 400 Vac
using 1-pole surge protective devices (SPDs)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MULTI 9™ SPD Series
Dimensions and Weights
Square D Company
8001 Highway 64 East
Knightdale, N.C. USA
1-888-SquareD
(1-888-778-2733)
www.SquareD.com Catalog No. 1312CT0101 November 2001 © 2001 Schneider Electric All Rights Reserved
DIMENSIONS
WEIGHTS
Poles Weight
lb (grams)
1 .22 (100)
2 .24 (109)
4 .56 (255)
2.56
(65)
1.42
(36)
3.39
(86) 1.77
(45)
3.62
(92)
2.57
(67)
2.56
(65)
0.71
(18)
2.80
(71) 1.77
(45)
3.39
(86)
3.62
(92)
2-Pole Front 2- and 4-Pole Side
1-Pole Side
1-Pole Front
1.77
(45)
3.50
(89)
2.57
(67)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com