Effective May 2010
Technical Data TD01005018E
Submittal specification for
120 kA SPD Series sidemount versions
Eaton’s SPD Series Surge Protective Devices (SPD) are used
to protect equipment from damage caused by surge events.
This submittal specification represents sidemount versions
of the SPD Series units with a catalog number beginning
with “SPD120.” These versions are designed to be mounted
external to electrical distribution assemblies and interfaced via
conduit and wires.
Table 1. Surge Current Capacity
Configuration Per
Phase L-N
Mode L-G
Mode N-G
Mode L-L
Mode
Single split phase (3W+G) 120 60 60 60
Three-phase wye (4W+G) 120 60 60 60
Three-phase delta (3W+G) 120 60 60
Three-phase high-leg delta (4W+G) 120 60 60 60
Table 2. Catalog Numbering System
SPD120 240S 1 K
Voltage Code
q 240S = 120/240 single split-phase
q 208Y = 120/208 wye (4W+G)
q 220Y = 127/220 wye (4W+G)
q 400Y = 230/400 wye (4W+G)
q 480Y = 277/480 wye (4W+G)
q 600Y = 347/600 wye (4W+G)
q 240D = 240 delta (3W+G)
q 480D = 480 delta (3W+G)
q 600D = 600 delta (3W+G)
q 240H = 240 high-leg delta
(4W+G) on ‘B’ phase
Feature Package
q 1 = Basic a b
q 2 = Standard a b c
q 3 = Standard +
surge counter
a b c d
Enclosure Options
q K = NEMAT 1 enclosure
q L = NEMA 1 flushmount enclosure
q M = NEMA 1 with internal disconnect
q N = NEMA 4
q O = NEMA 4 with internal disconnect
q P = NEMA 4X e
q Q = NEMA 4X with internal disconnect e
Performance Specifications
and Features
A. ANSI/ULT 1449 3rd Edition Voltage Protection Rating (VPR)
a. VPR for units containing the basic feature package in
a NEMA 1 enclosure without an internal disconnect
(catalog number ends with 1K or 1L). For all other VPR
values, please refer to Technical Data TD01005025E
or insert Voltage Code and VPR Value in the fields
below Table 3.
Table 3. Voltage Code and VPR
Voltage
Code
VPR for Each Protection Mode
L-N L-G N-G L-L
240S 700 700 700 1200
208Y and 220Y 700 700 700 1200
400Y and 480Y 1200 1200 1200 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2500
600D N/A 2500 N/A 2500
240H 700 700 700 1200
Enter VPR if not listed
Voltage
Code
VPR for Each Protection Mode
L-N L-G N-G L-L
b. VPR for units containing the standard or standard with
surge counter feature package in a NEMA 1 enclo-
sure without an internal disconnect (catalog number
ends with 2K, 2L, 3K, or 3L). For all other VPR values,
please refer to Technical Data TD01005025E or
insert Voltage Code and VPR Value in the fields
below Table 4.
a Dual-colored LED per phase to indicate protection status.
b Dual-colored LED to indicate protection status of the N-G mode on units with a
neutral wire.
c Audible alarm with silence button, Form C relay contact, EMI/RFI filtering providing up to
50 dB of noise attenuation from 10 kHz to 100 MHz.
d Surge counter with Reset button.
e Constructed of 304 stainless steel.
Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2010 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. TD01005018E / Z9922
May 2010
PowerChain Management is a registered
trademark of Eaton Corporation.
All other trademarks are property of their
respective owners.
Technical Data TD01005018E
Effective May 2010
Submittal specification for
120 kA SPD Series sidemount versions
Table 4. Voltage Code and VPR
Voltage
Code
VPR for Each Protection Mode
L-N L-G N-G L-L
240S 600 800 600 1000
208Y and 220Y 600 800 600 1000
400Y and 480Y 1200 1200 1200 1800
600Y 1500 1500 1500 2500
240D N/A 1000 N/A 1000
480D N/A 2500 N/A 2500
600D N/A 2500 N/A 2500
240H 700 800 700 1200
Enter VPR if not listed
Voltage
Code
VPR for Each Protection Mode
L-N L-G N-G L-L
B. Internal overcurrent protection
a. All units contain thermally protected metal-oxide varistors.
Each of these devices is internally fused by a thermal
element that safely removes them from the circuit under
abnormal conditions, such as temporary overvoltage or
high fault current conditions.
C. Monitoring and features (refer to Table 2 for a listing of the
individual features contained in each feature package)
D. General features
a. Units with catalog numbers ending in K, L, or M contain a
factory-installed ¾-inch trade size chase nipple
b. Units with catalog numbers ending in N, O, P, or Q contain
a factory-installed ¾-inch trade size hub connector
c. All units are prewired at the factory. Phase, neutral, and
ground connections are made via 10 AWG wires. Form C
relay contact connections are made via 14 AWG wires a
d. All units are factory sealed. No user intervention or internal
connections are required
e. Units with an internal disconnect (catalog numbers ending
in M, O, or Q) contain a three-pole, 30A thermal-magnetic
circuit breaker, Eaton catalog number FDC3030
f. NEMA 1 and NEMA 4 enclosures are constructed of
powder-coated steel
g. NEMA 4X enclosures are constructed of 304 stainless steel
E. Enclosure dimensions and weights
a. NEMA 1 (catalog number ends with K):
10.50L x 7.50W x 3.50D inches, 6.8 lbs
b. NEMA 1 flushmount (catalog number ends with L):
10.50L x 7.50W x 3.50D inches, 6.8 lbs; flushmount plate
dimensions are 14.00L x 11.00W inches
c. NEMA 1 with disconnect (catalog number ends with M):
10.70L x 11.10W x 5.80D inches, 14.7 lbs
d. NEMA 4 and 4X (catalog number ends with N or P):
11.30L x 8.70W x 5.40D inches, 14.6 lbs
e. NEMA 4 and 4X with disconnect (catalog number ends
with O or Q): 12.30L x 12.50W x 7.70D inches, 27.5 lbs
Table 5. Specifications
Description Specification
Surge capacity ratings available 50, 80, 100, 120, 160, 200, 250, 300, 400 kA
per phase
Nominal discharge current (In) 20 kA
Short circuit current rating (SCCR) 200 kA
SPD type Basic feature package = Type 1
(can also be used in Type 2 applications)
Standard and Standard with Surge Counter
feature packages = Type 2
Single split phase voltages
available
120/240
Three-phase wye system
voltages available
120/208, 127/220, 230/400, 277/480, 347/600
Three-phase delta system
voltages available
240, 480, 600
Input power frequency 50/60 Hz
Power consumption (basic units)—
voltage codes
208Y, 220Y, 240S, 240D, and 240H 0.5W
400Y, 480Y, and 480D 1.1W
600Y and 600D 1.3W
Power consumption—voltage codes a
208Y, 220Y, 240S, 240D, and 240H 0.6W
400Y, 480Y, and 480D basic 1.7W
600Y and 600D 2.1W
Protection modes Single split phase . . . . . . . . . . . L-N, L-G, N-G, L-L
Three-phase wye . . . . . . . . . . . L-N, L-G, N-G, L-L
Three-phase delta . . . . . . . . . . . L-G, L-L
Three-phase high-leg delta . . . . L-N, L-G, N-G, L-L
Maximum continuous operating
voltage (MCOV)
240S, 208Y, 220Y, and 240H
400Y and 480Y
600Y
240D
480D
600D
150 L-N, 150 L-G, 150 N-G, 300 L-L
320 L-N, 320 L-G, 320 N-G, 640 L-L
420 L-N, 420 L-G, 420 N-G, 840 L-L
320 L-G, 320 L-L
640 L-G, 640 L-L
840 L-G, 840 L-L
Ports 1
Operating temperature –40°C–50°C (–40°F–122°F)
Operating humidity 5%–95%, noncondensing
Operating altitude Up to 16,000 ft (5000m)
Seismic withstand capability Meets or exceeds the requirements specified in
IBCT 2006, CBC 2007, and UBCT Zone 4
Form C relay contact ratings 150 Vdc or 125 Vac, 1A maximum
Form C relay contact logic Power ON, normal state—NO contact = open,
NC contact = closed
Power OFF or fault state—NO contact = closed,
NC contact = open
EMI/RFI filtering attenuation aUp to 50 dB from 10 kHz–100 MHz
Agency certifications
and approvals
UL 1449 3rd Edition listed, CSAT, UL 1283
(Type 2 SPDs only)
Warranty 10 years
a Standard and standard with surge counter units.