Commercial Emergency
CTX6 Series
Compac® Thermoplastic
Emergency Unit with Xtest
Project
Type
Model No.
Comments
Specifier’s Reference
CM-22200
rev. 4, 06/29/2012
Options
TD – 15 min. Time Delay
LX – Laser activation of manual test via
handheld remote control transmitter, RLT
(sold separately)
LS – Less Self–Test of lamps
Accessories (Order Separately)
WG5Wire Guard
PCS1 – Polycarbonate Vandal Shield
RLT – Remote Laser Transmitter
Green Product Choice: CTX6
codes and standards
• ETL Listed to UL Standard 924
• NFPA 101 (Life Safety Code)
• NFPA 70 (National Electric Code)
construction
• Flame rated, UV stable ABS thermoplastic white
housing.
• Black is available.
• Low profile test switch comes standard on the unit.
• Contemporary design external square style lamp
heads that utilize an innovative track system that
allows for a full range of adjustment for emergency
illumination.
installation
• Snap together quick mount design.
• Universal J-box mounting pattern.
electronics Xtest
• All units utilize a microprocessor and contain the
Xtest self-diagnostic/self-test circuitry.
• Each unit includes low voltage disconnect, AC
lockout, and brownout protection.
• Each unit with Xtest circuitry will automatically
conduct a self-test once a month with the lamps on
to verify all systems are functioning properly. For
complete details regarding Xtest circuitry see spec
sheet CE-17050.
• 120/277VAC selectable input.
• Power Consumption:
120V= 42 mA Line Amps
= 5.1W input Wattage
277V= 22.6 mA Line Amps
= 6.26W input Wattage
lamps
• Standard unit contains two 6 volt, 5.4W
tungsten lamps.
• Units with the “H” option contain two 6 volt, 6W
halogen lamps.
• The 18 Watt unit comes standard with 9W
tungsten lamps.
battery
• 6V Maintenance free sealed lead acid battery.
• Operating temperature range is 65˚F (19˚C) to
85˚F (30˚C).
• Provides a minimum of 90 minutes emergency
illumination.
options
• Time Delay (TD) – After power failure and power
is restored, the lamp will remain illuminated for
a 15 minute period (provided battery capacity
remains).
• Manual Test Activation (LX) – To operate using a
laser pen: passing laser briefly over the remote
sensor simply duplicates the manual button (1, 2, 3)
pushes.
• Less Self TEST (LS) – Lamps will not come on when
the unit performs its automatic monthly self-test
functions.
warranty
• Five year warranty on unit (lamps not included).
Catalog Number Volts Total Wattage Remote1 Housing Color LampType
Lead Calcium:
CTX6 6 12 None White 5.4W tungsten
CTX6B 6 12 None Black 5.4W tungsten
CTX6H 6 12 None White 6W halogen
CTX6BH 6 12 None Black 6W halogen
CTX618 6 18 None White 9W tungsten
CTX618R 6 18 6W White 5.4W tungsten
CTX618HR 6 18 6W White 6W halogen
Footnote:
1 Refer to CA-51300 for matching remote lamp heads.
Contact Factory for Additional Configurations.
Specifications are subject to change without notice.
CM-22200 rev. 4 06/29/2012
©2012 Philips Chloride
All rights reserved.
776SouthGreenStreet•Tupelo,MS38804
p.800.234.1890•f.662.841.5501
Canadian Division
189BullockDrive•Markham,OntarioL3P1W4
p.905.294.9570•f.905.294.9811
CTX6 Series Compac® Thermoplastic Emergency Unit with Xtest
dimensions
5-11/16"
(128.3mm)
5-1/4"
(133.6mm)
11-1/16"
(280.9mm)
photometry
Meets Life Safety Code standard minimum illuminance of 0.1 FC and average
illuminance of 1.0 FC. Assumes open space with no obstructions, mounting
height: 8', ceiling height: 9', and reflectances: 80/50/20. Analysis based on
independently tested photometrics.
3'
Xtest testing specifications
• Automatic Test: The system charger and lamps are continually being
controlled via pre-determined parameters specific to each model
configuration, automatically. The battery is controlled via a true open circuit
test each hour after initial installation. One each month the Xtest System
illuminates lamps under load for 30 minutes, simulating a power outage
with a true charger off condition, without affecting long term battery life.
This is above and beyond the requirements of the National Fire Protection
Association. This gives you unequaled control and confidence, knowing you
are meeting self-test code requirements each and every month.
• Manual Test: A manual test switch allows for the Xtest system to perform
the following tests at any time:
Press Button
Once–5 second test, charger off, no load
Twice–60 second test, charger off, lamps on
Three–90 minute test, charger off, lamps on
6-Second Hold–Fully reinitializes micro-processor.
Pressing once during any test will cancel/abort testing.
Location of sensor for laser activation
of manual test via handheld remote laser
tester (this is an optional feature, specify
“LX” option)
SELF-TEST / DIAGNOSTIC
CHARGER
BATTERY
LAMPS
CHG-TEST
Xtest Status Indicator Panel
AC/Green Charger/Red Batt/Red Lamp/Red Status/Fault Action
On AC power is on/OK None
F Performing Test None
On F F F Lamp/Battery Disconnected or Charger Fault Check connections; if ok, replace circuit board
On F Charger fault Replace circuit board
On F Battery disconnected/fault Check connection or replace battery
On F Lamp disconnected/bad or remote disconnected Check connection then press manual test once to
determine bad lamp/replace lamp or check remote lamp.*
Fault Indications:
Four LED indicators provide visible indication of system status:
*If unit has remote capacity and remote cable is connected to charger board but not connected to
a remote load, then either connect remote load or disconnect cable from charger board.
On=Steady F=Flashing Blank=Off
lamp spacing avg. fc. max. fc. min. fc.
CTX6 5.4W tungsten 24ft. 1.0 2.00 0.1
CTX618 9W tungsten 39ft. 1.4 2.70 0.1
CTX6H 6W halogen 28ft. 1.00 2.00 0.1
Test Numbers:
CTX6 - CSWA
CTX618 - CSWC
CTX6H - CSWD