Stock Service Entrance Switchboards
Product Description and Application	

General

Product Description

Individual Product Lines

Siemens stock service entrance switchboards are designed as
stock units to meet the fast delivery needs of the market.

Super Blue Pennant
▪	 Specifically designed to meet EUSERC requirements
▪	 Provision for EUSERC utility metering
▪	 Main fusible switch or circuit breaker
▪	 Optional distribution panel

All of Siemens stock switchboards are suitable for service
entrance. These switchboards combine utility metering
provisions and a main service disconnect that can either be a
Vacu-Break fusible switch or a molded case circuit breaker.

13
SWITCHBOARDS

Stock switchboards have many applications, some of the
most common include:
▪	 Retail stores
▪	 Office buildings
▪	 Small factories
▪	 Commercial stores and shopping centers

BCT Service Cubicle
▪	 Provision for utility metering (non-EUSERC)
▪	 Main molded case circuit breaker
SCT Service Cubicle
▪	 Provision for utility metering (non-EUSERC)
▪	 Main Vacu-Break fusible switches

Additional Information
For complete application and pricing information contact your
local Siemens sales office.
For further information on the product, visit our website at
www.usa.siemens.com/switchboards
For detailed configuration information consult the selection
and application guide on the website.

Super Blue Pennant

BCT Service Cubicle

SCT Service Cubicle

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

13-11

Stock Service Entrance Switchboards

SWITCHBOARDS

13

Super Blue Pennant Switchboards	

General

Product Description

Features & Benefits

Siemens Super Blue Pennant stock service entrance
switchboards are designed as stock units to meet the fast
delivery needs of the market.

Features
▪	 Up to 800 amperes
▪	 Up to 480 volts AC
▪	 Bus bracing up to 200KAIC
▪	 Type 1 or Type 3R enclosures

Super Blue Pennant switchboards are suitable for service
entrance and are specifically designed to meet EUSERC
requirements. They combine utility metering provisions
with either a main Sentron molded case circuit breaker
or Vacu-Break fusible switch. An optional plug-in or bolt
on distribution panel can also added in the field in the
same section.
Super Blue Pennant switchboards have many applications,
some of the most common include:
▪	 Retail stores
▪	 Office buildings
▪	 Small factories
▪	 Commercial stores and shopping centers

Utility Provision
Incoming main lugs are mechanical screw-type, mounted on
studs and accept a wide range of cable sizes. A barriered hot
sequence utility metering compartment is supplied which
meets all EUSERC requirements. The meter and test block
provisions are also built to meet EUSERC requirements.
Main Disconnect
The main service disconnect can be either a Sentron molded
case circuit breaker in 400, 600 or 800 amperes or a VacuBreak fusible switch in 400 or 600 amperes.
Distribution Panel
Super Blue Pennant switchboards can accommodate an
optional distribution panel assembly per unit with ratings of
400, 600 or 800 amperes. The distribution panel can take up
to 40 single pole branch breakers which can be either bolt on
or plug-in.

Standards & Certifications
▪	
▪	
▪	
▪	

Super Blue Pennant

13-12

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

UL891
NEMA PB-2
Seismically qualified
Other equipment is UL listed as applicable

Stock Service Entrance Switchboards
Super Blue Pennant Switchboards 	

Dimensions

Type 1 — Indoor

Type 3R — Outdoor Weatherproof

13
SWITCHBOARDS

	
Description	

Dimensions (inches)
A	
B	
C

	
Description	

Dimensions (inches)
A	
B	
C

Without Lug Landing	

46	

14	

With Lug Landing	

58	

26	

12

Without Lug Landing	

53	

15	

13

24

With Lug Landing	

65	

27	

25

For inches / millimeters conversion, see conversion table
in Application Data section.

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

13-13

Stock Service Entrance Switchboards
Super Blue Pennant Switchboards 	

Selection

Main Circuit Breaker

SWITCHBOARDS

13

Main Device
Ampere
Rating

Indoor

Outdoor

Meter Distribution
Socket Kits
Clips
Available

120/240; 1-Phase,
3-Wire

PB224

WPB224

5

 40/120; 3-Phase,
2
4-Wire Delta
240; 3-Phase,
3-Wire
208Y/120; 3-Phase,
4-Wire

PB424

WPB424

 80Y/277; 3-Phase,  
4
4-Wire
PB444
480; 3-Phase,
3-Wire
120/240; 1-Phase,	
3-Wire

Service
Voltage

400 Ampere
Line Lugs 	
(2)—3⁄0-500
kcmil (Copper
or Aluminum)
Breaker Rated
65,000A IR
Symmetrical	
at 240 Volts
35,000A IR
Symmetrical	
at 480 Volts 	
Type JD6

600 Ampere
Line Lugs 	
(2)—3⁄0-500
kcmil (Copper
or Aluminum)
Breaker Rated
65,000A IR
Symmetrical	
at 240 Volts
35,000A IR
Symmetrical	
at 480 Volts 	
Type LD6

800 Ampere
Line Lugs 	
(3)—3⁄0-500
kcmil (Copper
or Aluminum)
Breaker Rated
65,000A IR
Symmetrical	
at 240 Volts
50,000A IR
Symmetrical	
at 480 Volts 	
Type MD6

Catalog Number

Indoor

Outdoor

PQ2630
PQ2612

320

1050

15

PQ4630
PQ4612

335

1060

WPB444

15

PE4630
PF4606

335

1060

PB226

WPB226

5

PQ2630
PQ2612

320

1050

 40/120; 3-Phase,
2
4-Wire Delta
240; 3-Phase,
3-Wire
208Y/120; 3-Phase,
4-Wire

PB426

WPB426

PQ4630
PQ4612

335

1060

 80Y/277; 3-Phase,
4
4-Wire
480; 3-Phase
3-Wire

PB446

WPB446

15

PE4630 	
PF4606

335

1060

120/240; 1-Phase,
3-Wire

PB228

WPB228

5

PQ2840
PQ2816

460

1090

 40/120; 3-Phase,
2
4-Wire Delta
240; 3-Phase,
3-Wire
208Y/120; 3-Phase,
4-Wire

PB428

WPB428

15

PQ4840 	
PQ4818

475

1090

 80Y/277; 3-Phase,
4
4-Wire
480; 3-Phase,
3-Wire

PB448

WPB448

PE4840
PF4809

475

1090

For inches / millimeters conversion, see conversion table
in Application Data section.

13-14

Approximate
Weight (lbs.)

15

15	



a Load

side lugs, distribution panel and subfeed kits are
not included.
6-jaw requirements, order 6th clip kit
from accessories.

= Warehouse Stock



b For

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

Product Category SWBD

Stock Service Entrance Switchboards
Super Blue Pennant Switchboards 	

Selection

Main Fusible Switch
Main Device
Ampere
Rating

120/240; 1-Phase,
3-Wire

PF224

WPF224

5

 40/120; 3-Phase,
2
4-Wire Delta
240; 3-Phase,
3-Wire
208Y/120; 3-Phase,
4-Wire

PF424

WPF424

 80Y/277; 3-Phase,  
4
4-Wire
PF444
480; 3-Phase,
3-Wire
120/240; 1-Phase,	
3-Wire

Approximate
Weight (lbs.)
Indoor

Outdoor

PQ2630
PQ2612

365

1094

15

PQ4630
PQ4612

375

1110

WPF444

15

PE4630
PF4606

375

1110

PF226

WPF226

5

PQ2630
PQ2612

370

1100

 40/120; 3-Phase,
2
4-Wire Delta
240; 3-Phase,
3-Wire
208Y/120; 3-Phase,
4-Wire

PF426

WPF426

PQ4630
PQ4612

390

 80Y/277; 3-Phase,
4
4-Wire
480; 3-Phase
3-Wire

PF446

WPF446

PE4630 	
PF4606

390

For inches / millimeters conversion, see conversion table
in Application Data section.

Product Category SWBD

15

15

a Fuses

1110	

1120

not included.
side lugs, distribution panel and subfeed kits are
not included.

c For 6-jaw requirements, order 6th clip kit
from accessories.
b Load

SWITCHBOARDS

600 Ampere
Line Lugs 	
(2)—3⁄0-500
kcmil (Copper
or Aluminum)
200,000 AIC
maximum at
600 Volts

Outdoor

Catalog Number

13

400 Ampere
Line Lugs 	
(2)—3⁄0-500
kcmil (Copper
or Aluminum)
200,000 AIC
maximum at
600 Volts

Indoor

Meter Distribution
Socket Kits
Clips
Available

Service
Voltage

= Warehouse Stock

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

13-15

Stock Service Entrance Switchboards
Super Blue Pennant Switchboards 	

Selection

SWITCHBOARDS

13

Main Device (Circuit Breaker or Fusible Switch)
Load Side Lugs— Discount Schedule SWBD
Ampere Rating

Description

Catalog Number

Wire Range

400
600
400
600
800

For Fusible
Switch
For Circuit
Breaker

LKF4
LKF6
LKB4
LKB6
LKB8

(1)—3/0-750 kcmil (Cu or Al)
(2)—3/0-500 kcmil (Cu or Al)
(1)—600-750 kcmil (Cu or Al)
(2)—3/0-350 kcmil (Cu or Al)
(2)—600-750 kcmil (Cu or Al)

Distribution Panel Kits — Discount Schedule SWBD
Ampere
Rating

400
and
600

Number and Type of Breaker Poles
Voltage

QP or HQ 

ED4 

QJ2 or QJH2 

FXD6 

Catalog
Number

120/240V; 1-Phase, 3-Wire

30
12

—
—

—
12

—
—

PQ2630
PQ2612

30

—

—

—

PQ4630

12

—

12

—

PQ4612

—
—
40
12

30
12
—
—

—
—
—
16

—
6
—
—

PE4630
PF4606
PQ2840
PQ2816

240/120V; 3-Phase, 4-Wire Delta 
240V; 3-Phase, 3-Wire 
208Y/120V; 3-Phase, 4-Wire
480Y/277V; 3-Phase, 4-Wire
480V; 3-Phase, 3-Wire
120/240V; 1-Phase, 3-Wire

800

240/120V; 3-Phase, 4-Wire Delta 
240V; 3-Phase, 3-Wire
208Y/120V; 3-Phase, 4-Wire
480V; 3-Phase, 3-Wire

40

—

—

—

PQ4840

12

—

18

—

PQ4818

—
—

40
12

—
—

—
9

PE4840
PF4809

Weight
39
42
42
65
65
70
65
70

Circuit Breaker Subfeed Kits: (Breakers Not Included) — Discount Schedule SWBD
Description

Catalog Number

For FXD6-225A 2 or 3-pole
For JXD6, JD6, HJD6 400A 2 or 3-pole

PSFFJ6
PSFJL6

For inches / millimeters conversion, see conversion table
in Application Data section.
Includes

phase and neutral load lugs and neutral link
assembly.
FXD6 requires 3-pole space.

Includes

branch neutral and disconnect link assembly.
breakers must not be connectedto “B” phase.
breakers must be rated 240V.
FXD6 circuit breakers are limited to 225A maximum.
Price from Molded Case Circuit Breaker section.
1-pole

= Warehouse Stock

2-pole

2-pole

13-16

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

Product Category SWBD

Stock Service Entrance Switchboards
Super Blue Pennant Switchboards 	

Accessories

Description	

Catalog Number

Underground Pull Section or Full Height Section For Load Wiring — Discount Schedule SWBD
14.5" Deep 90" High	
14" Wide (12" opening) — indoor	
15" Wide (12" opening) — outdoor	

	
PUG14
WPUG14

26" Wide (24" opening) — indoor	
27" Wide (24" opening) — outdoor	

PUG26
WPUG26

10" Wide (load wiring)	

PLW10

Lug Landing Kits — Discount Schedule SWBD (Requires Catalog Number PUG26 or WPUG26)
1-Phase, 3-Wire or 3-Phase, 4-Wire	

PLL44 a

600A	

1-Phase, 3-Wire or 3-Phase, 4-Wire	

PLL46 a

800A	

1-Phase, 3-Wire or 3-Phase, 4-Wire	

PLL48 a

13

400A	

SWITCHBOARDS

“R” Fuse Clip Adapter Kit (Set of 3) — Discount Schedule VBSS
400A 250/600V	

SSRK35

600A 250/600V	

SSRK36

“J” Fuse Clip Adapter Kit (Set of 3) — Discount Schedule VBSS
400A 250V	

W49814

400A 600V	

W49816

600A 240V	

W49813

600A 600V	

W49815

“T” Fuse Clip Adapter Kit (One Pole Kit) — Discount Schedule VBSS
400A 240V	

TFAK52

400A 600V	

TFAK55

600A 240V	

TFAK62

600A 600V	

TFAK65

Optional Meter Sockets and Doors — Discount Schedule SWBD
Meter Compartment Door (32" Wide x 15" High for “S” base socket with	
test block cutout (order necessary meter base from items below)	

PSP32

Meter Compartment Door (32" Wide x 30" High) for 2 “S” base	
meters with mounting provisions for test block and printing	
demand meter (order meter base from table below)	
Left Hand Hinge or Right Hand Hinge	

PSDP32

Blank Meter Compartment Door (32" Wide x 15" High)	

PBP32

5 Clip Meter Socket with ring	

PMS5

6 Clip Meter Socket with ring	

PMS6

8 Clip Meter Socket with ring	

PMS8

13 Clip Meter Socket with ring	

PMS13

15 Clip Meter Socket with ring	

PMS15

Filler Plates — Discount Schedule MCCB
QP, BL, BQD, NGB, ED	

QF3

EB	

EBF1

Handle Blocking and Padlock Devices — Discount Schedule MCCB
Blocking (QP-HQP 1, 2 and 3-pole)	

ECQL1

Blocking (QJ2, QJ2-H, QJH2)	

QJHS1

Blocking (ED2, ED4, ED6)	

E2HBL

Padlock (QP-HQP)	

ECQLD3

Padlock (QJ2, QJ2-H, QJH2)	

HL9419

Padlock (ED2, ED4, ED6)	

ED2HPL

Equipment Ground Bus –– Discount Schedule SWBD
PEGB42

	

For inches / millimeters conversion, see conversion table
in Application Data section.

Product Category SWBD

a A

PUG26 or WPUG26 Underground pull section is
required when using these lug landing kits.

= Warehouse Stock

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

13-17

Stock Service Entrance Switchboards
BCT Service Cubicle 	

Selection

Product Description

Features & Benefits

Siemens BCT stock service entrance switchboards are
designed as stock units to meet the fast delivery needs of the
market.

Features
▪	 Up to 1200 amperes
▪	 Up to 600 volts AC
▪	 Bus bracing up to 100KAIC
▪	 Type 1 enclosures only

SWITCHBOARDS

13

Siemens BCT switchboards incorporate a utility current
transformer compartment and a Sentron molded case circuit
breaker in a single section.

Utility Provision

BCT switchboards have many applications, some of the most
common include:
▪	 Retail stores
▪	 Office buildings
▪	 Small factories
▪	 Commercial stores and shopping centers

The provision can be adjusted for use with 12” or 14.5”
primary bar type current transformers. All switchboards
are supplied as top feed cold sequence metering only.
Switchboards can be field modified for other configurations
per the available configurations table below.
Main Disconnect
The main service disconnect is a Sentron molded case circuit
breaker available from 400 to 1200 amperes.
Enclosure
The enclosure is tamperproof with a hinged door over the
utility provision compartment with a latch for the utility to
be able to seal off the compartment. Enclosures are only
available as type 1 indoor.

Standards & Certifications

Utility metering provsion

▪	 UL891
▪	 NEMA PB-2
▪	 Other equipment is UL listed as applicable

Connectors (Per Phase & Neutral)

BCT Service Cubicle

Ampere
Rating

Connectors Suitable
For Cu or Al

400

(1)
(2)
(2)
(2)
(4)
(4)

600
800
1000
1200

Neutral disconnect link

4/0-500 kcmil
250 kcmil  
4/0-500 kcmil
250-500 kcmil
250-500 kcmil
250-500 kcmil

BCT Catalog Numbers & Application Data
Catalog
Number

Symmetrical Amperes
Interrupting Capacity
240V

BCT436JXD6
BCT436HJD6
BCT636LXD6
BCT636HLD6
BCT836MXD6
BCT836HMD6
BCT1036NXD6
BCT1036HND6
BCT1236NXD6
BCT1236HND6
PTE

13-18

480V

65,000  
35,000  
100,000   65,000  
65,000  
35,000  
100,000   65,000  
65,000  
50,000  
100,000   65,000  
65,000  
—  
100,000   —  
65,000  
—  
100,000   —  
Potential Transformer

Ampere
Rating
600V
25,000  
35,000  
25,000  
35,000  
25,000  
50,000  
—  
—  
—  
—  
Enclosure  

Dimensions
(inches)
System Voltage

400
600
800
1000
1200
—  

Height

120/240V	
208Y/120V	
240V	
480Y/277V	
480V	
600V

1-Phase,
3-Phase,
3-Phase,
3-Phase,
3-Phase,
3-Phase,

208Y/120V	
240V

3-Phase, 4-Wire	
3-Phase, 4-Wire

3-Wire	
4-Wire	
3-Wire	
4-Wire	
3-Wire	
3-Wire

Width

Depth

70

32

13.75

Available
Configurations
Top Feed
Top Feed
Cold Seq. Hot Seq.

Bottom Feed
Cold / Hot Seq.

●

●

●

●

●

●

●

●

●

●

●

●

●

●

●

●

●
●

90

●
●
●

—  

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

—  

20

●

20

10

Stock Service Entrance Switchboards
SCT Service Cubicle 	

Selection

Product Description

Features & Benefits

Siemens SCT stock service entrance switchboards are
designed as stock units to meet the fast delivery needs of the
market.

Features
▪	 Up to 1200 amperes
▪	 Up to 600 volts AC
▪	 Bus bracing up to 200KAIC
▪	 Type 1 enclosures only

Siemens SCT switchboards incorporate a utility current
transformer compartment and a Vacu-Break fusible switch.

Utility Provision
The provision can be adjusted for use with 12” or 14.5”
primary bar type current transformers. All switchboards are
supplied as top feed cold sequence metering only..

The main service disconnect is a Vacu-Break fusible switch
available from 400 to 1200 amperes.
Enclosure
The enclosure is tamperproof with a hinged door over the
utility provision compartment with a latch for the utility to
be able to seal off the compartment. Enclosures are only
available as type 1 indoor.

Standards & Certifications
▪	 UL891
▪	 NEMA PB-2
▪	 Other equipment is UL listed as applicable

Connectors (Per Phase & Neutral)
Ampere
Rating

Connectors Suitable
For Cu or Al

400

(1)
(2)
(2)
(2)
(4)
(4)

600
800
1000
1200

4/0-500 kcmil
250 kcmil  
4/0-500 kcmil
250-500 kcmil
250-500 kcmil
250-500 kcmil

Vacu-Break Main Switch

Fuse Clips
SCT Service Cubicle

Ampere
Rating

Fuse
Clip

Symmetrical Amperes
Interrupting Capacity

400 - 600  
800 - 1200  

R  
L  

200,000  
100,000

SCT Catalog Numbers & Application Data
Catalog Number

Dimensions (inches)

Cold Sequence

Hot Sequence

Ampere
Rating

System Voltage

SCT432
SCT632
SCT436
SCT636
SCT836
SCT1236

LSCT432
LSCT632
LSCT436
LSCT636
LSCT836
LSCT1236

400  
600  
400  
600  
800  
1200  

120/240V  
208Y/120V 240V  
480Y/277V  
480 or 600V  
All  
208Y/120V 240V  

1-Phase,
3-Phase,
3-Phase,
3-Phase,
—  
3-Phase,

3-Wire  
4-Wire 3-Phase, 3-Wire  
4-Wire  
3-Wire  

Height

Width

Depth

90  

32  

20  

4-Wire 3-Phase, 3-Wire  

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

13-19

SWITCHBOARDS

Main Disconnect

13

SCT switchboards have many applications, some of the most
common include:
▪	 Retail stores
▪	 Office buildings
▪	 Small factories
▪	 Commercial stores and shopping centers

Switchboard Replacement Parts and Modification Kits
Replacement Information, Accessories & Modifications	

Selection

Connection Strap Kits - Circuit Breaker	

Connection Strap Kits - Vacu-Break & HCP

For use with SB1, SB2, SB3, FC20, FCI, FCII, CDP-6 & VB-6
switchboards or series 5 or 6 CDP circuit breaker panelboards.
Includes straps, cover plates and necessary hardware for
switchboards manufactured since 1974. For replacement
strap kits for RCIII switchboards, contact your local sales
office.

For use with SB1, SB2, SB3, FC20, FCI, FCII, VB-5 & VB-6
switchboards. Includes straps, cover plates and necessary
hardware for switchboards manufactured since 1974. For
replacement strap kits for RCIII switchboards, contact your
local sales office.

13

100

SWITCHBOARDS

Max
Amp
Rating

125
150
225
250

400

600

800

1200

Breaker
Family

Breaker
Type

Catalog
Number

Unit
Height
(inches)

General
General
General
General
General
VL
General
VL
Sentron
Sentron
VL
VL
Sentron
Sentron
Sentron
Sentron
Sentron
VL
Sentron
Sentron
Sentron
Sentron
VL
Sentron
Sentron
Sentron
VL
Sentron
Sentron

BL, BQD
EB
NGB  
ED
CED
DG
QJ
FG
FD
CFD
JG
JG
JD
JD
CJD
SJD
SCJD
LG
LD
CLD
SLD
SCLD
MG
LMD
MD
SMD
NG
ND
SND

SBLBD
SEBD
SNBD
6E62
6CLE2
SDGD
6QJ2
SFGD
6F62
6CLF1
SJG2De
SJG1D
6JJ61
6JJ62
6CLJ1
6SJL1
6SCJ1
SLGD
6LL61
6CLL1
6SLL1
6SCL1
MG1D
SLM1D
SMND
SSMND
NG1D
SMND
SSMND

3.75  
3.75  
3.75  
3.75  
3.75  
5  
5  
5  
5  
5  
6.25  
6.25  
8.75  
8.75  
8.75  
8.75  
8.75  
6.25  
8.75  
8.75  
8.75  
8.75  
8.75  
8.75  
10  
10  
10  
10  
10  

Mounting
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Single
Twin
Single
Single
Twin
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single

Switch
Type

Ampere
Rating

Unit Height
(inches)

Catalog
Number

Vacu-Break

30-30
30-60
60-60
60-100
100-100
100
200
200-200
400-600
800-1200

5, 7.5
5, 7.5
5, 7.5
7.5
7.5
7.5
7.5, 10
10
15
16.25

VB657

HCP

VB671
VB610
VB6150
F6162D

Blank Plates - Circuit Breaker & Fusible Switch
For use with SB1, SB2, SB3, FC20, FCI, FCII switchboards or
series 5 or 6 VB and CDP panelboards.
Unit Height (Inches)

Catalog Number

1.25
2.5
3.75
5
10

6FPB01
6FPB02
6FPB03
6FPB05
6FPB10

Replacement Meter Socket Kits
For use with SMM and SMD metering switchboards
Type

Catalog Number

1-Phase
3-Phase

MSK2001
MSK2003

Connecting Kits

Filler Plates
For use with SB1, SB2, SB3, FC20, FCI, FCII, CDP-6 & VB-6
switchboards or series 5 or 6 CDP circuit breaker panelboards.
Includes straps, cover plates and necessary hardware for
switchboards manufactured since 1974. For replacement
strap kits for RCIII switchboards, contact your local sales
office.
Breaker Frame

Filler Plate Catalog Number

Notes

BL, BQD, ED

QF3

Per Pole

EB

EBF1

Per Pole

For use with SMM and SMD metering switchboards
Disconnect Device

Catalog Number

NGG
EG
BQ
QJ
ED
FD
CED
T-Fuse Pullout  

SMMNGMK
SMMHEMK
SMMBQMK
SMMQJMK
SMMEDMK
SMMFDMK
SMMCEMK
SMMTFMK

Note: When a front filler plate is not completely filled with
breakers, the openings in the unused space must be closed
with 1-pole filler plates from table.
For inches / millimeters conversion, see conversion table
	 Consult

sales office for availability
strap kit includes front filler plate after 1/91.

	 Connecting

13-20

	 Siemens

meter socks used in SMM switchboards
Type WMS263 Meter Sockets are rated 200A in
application Data Section

	 Siemens

Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog

e	 Twin

mounted VL JG breakers places the trip unit under
the gutters preventing the trip unit from being visible by
the customer.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c041 52.342996, 2008/05/07-21:37:19
Modify Date                     : 2011:09:01 12:09:48-04:00
Create Date                     : 2011:09:01 10:42:31-04:00
Metadata Date                   : 2011:09:01 12:09:48-04:00
Creator Tool                    : Adobe InDesign CS4 (6.0.6)
Format                          : application/pdf
Document ID                     : uuid:c8d909e5-aa5e-f846-8414-c28479deaeb8
Instance ID                     : uuid:b358c380-decd-9a41-875b-d6279e82c35f
Producer                        : Adobe PDF Library 9.0
Page Count                      : 10
Creator                         : Adobe InDesign CS4 (6.0.6)
EXIF Metadata provided by EXIF.tools

Navigation menu