B
B 9
Features/Benefits
Optimized over-load capability for withstanding
elevated levels of current during electronic
motor controller starts
Low I2t (low thermal energy)
Excellent Cycling Ability for frequent starts/stops
without nuisance opening
PROTECT YOUR WIRING AND POWER SEMI-
CONDUCTORS WITH A SINGLE FUSE.
The new High Speed J (HSJ) combines the low
I2t of a semiconductor fuse and the branch circuit
performance of a Class J UL listed fuse. This fuse
was designed for the starting characteristics of solid
state motor controllers. The HSJ can provide branch
circuit protection per NEC requirements, as well as
very low I2t for protection of power semiconductors
such as Diodes, SCR’s, GTO’s and SSR’s.
APPLICATIONS:
Branch Circuits
Control Panels
Electronic Motor
Controllers
Phase Controllers
Drives
Soft-Starters
Solid State Relays
HIGHLIGHTS:
Current-Limiting
AC & DC Ratings
Low l2t
Compact Size
AMP-TRAP®
HSJ
AC: 1-600A 600VAC,
200kA I.R.
300kA I.R. Self Certified
DC: 15-600A 500VDC,
100kA I.R. L/R 10mS
Ratings
HSJ (15 TO 600A)
UL Listed to
Standard 248-8
File E2137
DC Listed to UL248
CSA Certified to
Standard C22.2
No. 248.8
Approvals
HIGH SPEED/CLASS J
Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · sales@grossautomation.com
B 10
AMP-TRAP®
HIGH SPEED/CLASS J HSJ
Fuse Catalog Number
Ampere 600V OR LESS
Rating 1 Pole 3 pole
0-30 US3J1I US3J3I
31-60 US6J1I US6J3I
61-100 61036J 61038J
101-200 62001J 62003J
201-400 64031J 64033J
401-600 6631J 6633J
Recommended Fuse Blocks
With Box Connectors for
Amp-trap® Class J Fuses
A variety of pole configurations and
termination provisions is available.
Standard Fuse Ampere Ratings, Catalog Numbers
15-30 2-1/4 57 13/16 21 - - - - - - - - - - - -
31-60 2-3/8 60 1-1/16 27 - - - - - - - - - - - -
61-100 4-4/8 117 1-1/8 29 1/8 3.2 3/4 19 1 25 3-5/8 92 3/8 10 9/32 7
101-200 5-3/4 146 1-5/8 41 3/16 4.8 1-1/8 29 1-3/8 35 4-3/8 111 3/8 10 9/32 7
201-400 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 13 13/32 10
401-600 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13
AMPERE
RATING A B C D E F G H
In. mm In. mm In. mm In. mm In. mm In. mm In. mm In. mm
Dimensions
Fig 1
AMPERE
RATING
CATALOG
NUMBER
OUTLINE
FIGURE
AMPERE
RATING
CATALOG
NUMBER
OUTLINE
FIGURE
1 HSJ1 1 90 HSJ90 2
3 HSJ3 1 100 HSJ100 2
6 HSJ6 1 110 HSJ110 2
10 HSJ10 1 125 HSJ125 2
15 HSJ15 1 150 HSJ150 2
17-1/2 HSJ17-1/2 1 175 HSJ175 2
20 HSJ20 1 200 HSJ200 2
25 HSJ25 1 225 HSJ225 2
30 HSJ30 1 250 HSJ250 2
35 HSJ35 1 300 HSJ300 2
40 HSJ40 1 350 HSJ350 2
45 HSJ45 1 400 HSJ400 2
50 HSJ50 1 450 HSJ450 2
60 HSJ60 1 500 HSJ500 2
70 HSJ70 2 600 HSJ600 2
80 HSJ80 2
Fig 2
Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · sales@grossautomation.com
B
B 11
AMP-TRAP®
HIGH SPEED/CLASS J
1.0
.8
.6
.4
.2
00 100 200 300 400 500 60
0
110-600 AMP
15-100 AMP
Clearing I
2
t vs Operating Voltage
1.0
.8
.6
.4
.2
50 60 70 80 90 10
0
Watts Loss vs. % Rated Current
Correction Factor for I2t
Operating Voltage (AC RMS Volts) Percent Rated Current
I2t Data - 600 Volts AC, 100kA
Correction Factor for Watts Loss
Max Clearing I2t @ Max Clearing I2t @ Watts
Ampere 600V AC 100kA 480V AC 100kA Loss at
Rating Pre-Arc 1 Fuse 2 in Series 1 Fuse 2 in Series Rated
(A) (A2s x 103) (A2s x 103) (A2s x 103) (A2s x 103) (A2s x 103)Current
15 0.02 0.36 0.15 0.23 0.12 2.6
17.5 0.03 0.45 0.19 0.29 0.15 3.5
20 0.04 0.58 0.24 0.37 0.19 3.7
25 0.08 1.2 0.50 0.77 0.40 4
30 0.16 2 0.84 1.3 0.66 4.1
35 0.16 1.5 0.63 0.96 0.50 5.3
40 0.27 2.3 1.0 1.5 0.76 5.5
45 0.32 3.3 1.4 2.1 1.1 6
50 0.44 5.5 2.3 3.5 1.8 6.8
60 0.72 8.0 3.4 5.1 2.6 8.4
70 1.2 12 5.0 7.7 4.0 10
80 1.6 15 6.3 9.6 5.0 11
90 2.3 21 8.8 13 6.9 13
100 2.7 23 9.7 15 7.6 14
110 2.3 21 10 13.9 8 18
125 3.4 29 14 19 11 19
150 5.1 41 20 27 16 22
175 8.0 60 29 40 23 24
200 14 92 44 61 35 26
225 14 110 53 73 42 30
250 16 130 62 86 49 36
300 26 200 96 132 76 38
350 37 290 139 191 110 40
400 63 450 216 297 171 42
450 67 500 240 330 190 58
500 98 600 288 396 228 59
600 141 900 432 594 342 68
HSJ
Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · sales@grossautomation.com
B 12
Peak Let-Thru Data - HSJ15 to 600, 600Volts AC
Clearing I2t at 500 VDC 100kA, L/R = 10mS DC Voltage vs. Time Constant
DC Voltage Capability
L/R Time Constant (mS)
AMP-TRAP®
HIGH SPEED/CLASS J
AMPERE
RATING CLEARING I2t @ 500 VDC
L/R = 10 ms (A2s X 103)
15 0.12
17.5 0.18
20 0.24
25 0.46
30 0.91
35 0.60
40 0.92
45 1.3
50 2.2
60 3.2
70 4.8
80 6.2
90 8.9
100 10
110 8.8
125 13
150 19
175 28
200 46
225 52
250 59
300 96
350 136
400 230
450 270
500 390
600 560
Maximum Instantaneous Peak Let-Thru Amperes
Available Current in RMS Symmetrical Amperes
HSJ
Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · sales@grossautomation.com
B
B 13
Melting Time - Current Data, HSJ15 to 600, 600Volts AC
Available Current in RMS Symmetrical Amperes
Time in Seconds
Time in Seconds
AMP-TRAP®
HIGH SPEED/CLASS J
Available Current in RMS Symmetrical Amperes
HSJ
Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · sales@grossautomation.com