DF-52418:E1 • 1/27/12 — Page 1 of 4
MS-9050UD(E)
Fire Alarm Control Panel
with DACT
Addressable
DF-52418:E1 • A1-20
52418cov.jpg
General
The Fire•Lite MS-9050UD(E) is a Fire Alarm Control Panel
(FACP) and Digital Alarm Communicator/Transmitter (DACT)
combined into one circuit board. This compact, intelligent
addressable control panel supports up to 50 addressable
devices of any type of detectors and modules. With an exten-
sive list of powerful features, the MS-9050UD programs just like
Fire•Lite’s larger products, yet
fits into applications previously
served only by conventional panels.
The MS-9050UD’s integral DACT transmits system status
(alarms, troubles, AC loss, etc.) to a Central Station via the pub-
lic switched telephone network. It also allows remote and local
programming of the control panel using the PK-CD Upload/
Download utility. In addition, the control panel may be pro-
grammed or interrogated off-site via the public switched tele-
phone network. Any personal computer with Windows 95 or
greater, and compatible modem with a speed of 14.4 kbps or
faster and Fire•Lite Upload/Download software kit PK-CD, may
serve as a Service Terminal. This allows download of the entire
program or upload of the entire program, history file, walk-test
data, current status and system voltages.
The power supply and all electronics are contained on a single
circuit board supported on a new quick install chassis and
housed in a metal cabinet. Available accessories include local
and remote upload/download software, remote annunciators,
and reverse polarity/city box transmitter. (4XTMF)
New options include a UL listed printer, PRN-6F and the new
IPDACT Internet Monitoring module.The FireWatch Series inter-
net monitoring modules IPDACT-2 and IPDACT-2UD permit
monitoring of alarm signals over the Internet, saving the monthly
cost of two telephone lines. Although not required, the second-
ary telephone line may be retained providing backup communi-
cation over the public switched telephone line.
NOTE: Unless otherwise specified, the term MS-9050UD is used
in this data sheet to refer to both the MS-9050UD and the MS-
9050UDE FACPs. For MS-9050UDC, refer to DF-60445.
Features
Listed to UL Standard 864, 9th edition.
Auto-program (learn mode) reduces installation time.
Reports two devices set to the same address.
On-board DACT.
Two independently programmable Style Z (Class A) or Style
Y (Class B) NAC circuits.
Selectable strobe synchronization for System Sensor, Whee-
lock, and Gentex devices.
Remote Acknowledge, Silence, Reset and Drill via address-
able monitor modules.
Two programmable relays and one fixed trouble relay.
Built-in Programmer.
Telephone Line Active LEDs.
EIA-232 PC interface.
Integral 80-character LCD display with backlighting.
Real-time clock/calendar with automatic daylight savings
control.
History file with 500 event capacity.
Automatic detector sensitivity testing (NFPA 72 compliant).
Automatic device type-code verification.
Point trouble identification.
Waterflow selection per module point.
Alarm verification selection per detector point.
Maintenance alert warns when smoke detector dust accumu-
lation is excessive.
One-person audible or silent walk test with walk-test log and
printout.
System alarm verification selection per detector point.
PAS (Positive Alarm Sequence) and Pre-signal per point
(NFPA 72 compliant).
Up to eight ANN-BUS annunciators
Remote Acknowledge, Alarm Silence, Reset and Drill via
addressable modules or remote annunciator.
Upload/Download (local or remote) of program and data via
integral DACT.
SLC COMMUNICATION LOOP
Single addressable SLC loop which meets NFPA Style 4, 6
and 7 requirements.
50 addressable device capacity (any combination of address-
able detectors and modules).
Compatible with Fire•Lite’s addressable devices (refer to SLC
Wiring Manual).
NOTIFICATION APPLIANCE CIRCUITS (NACS)
Two independently programmable output circuits. Circuits
can be configured for the following outputs:
Style Y (Class B)
Style Z (Class A)
Door Holder Service (cannot be used for notification appliances)
Aux Power Source (cannot be used for notification appliances)
Silence Inhibit and Autosilence timer options.
Continuous, March Time, Temporal or California code for
main circuit board NACs with two-stage capability.
Selectable strobe synchronization per NAC.
2.5 A total power for NACs.
NOTE: Maximum or total 24VDC system power shared between
all NAC circuits and the ANN-BUS is 2.7 A.
Page 2 of 4 — DF-52418:E1 • 1/27/12
PROGRAMMING AND SOFTWARE
Autoprogram (learn mode) reduces installation time.
Custom English labels (per point) may be manually entered
or selected from an internal library file.
Two programmable Form-C relay outputs.
20 software zones.
Continuous fire protection during online programming at the
front panel.
Program Check automatically catches common errors not
linked to any zone or input point.
OFFLINE PROGRAMMING: Create the entire program in
your office using a Windows®-based software package(order
programming kit PK-CD, containing PS-Tools, separately).
Upload/download system programming locally.
User interface
LED INDICATORS
AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
Alarm Silenced signals (yellow)
KEYPAD
16 key alpha-numeric pad
• Acknowledge/Step
Alarm Silenced
Drill (Manual Evacuate)
Reset (lamp test)
Product Line Information
MS-9050UD(E): Combination DACT/Fire Alarm Control Panel
with one SLC loop. Includes main circuit board with display,
chassis with transformer, backbox with door, plastic bag contain-
ing screws, cables, key, etc., manual. (For MS-9050UDC, refer
to DF-60445.)
PK-CD: Contains PS-Tools programming software for Win-
dows®-based PC computer (cable not included).
DP-51050: Optional dress panel for the MS-9050UD.
TR-CE: Optional trim ring for semi-flush mounting.
BB-2F: Optional cabinet for one or two modules.
BB-6F: Optional cabinet for up to six modules mounted on
CHS-6 chassis.
BB-26: Battery backbox, holds up to two 25 AH batteries and
CHG-75.
BB-55F: Battery box, houses two 55 AH batteries
CHS-6: Chassis, mounts up to six multi-modules in a BB-6F
cabinet.
CHG-75: Battery charger for lead-acid batteries with a rating of
25 to 75 AH.
CHG-120F: Remote battery charging system for lead-acid bat-
teries with a rating of 55 to 120 AH. Requires additional BB-55F
for mounting.
BAT Series: Batteries, see data sheet DF-52397.
PRT/PK-CABLE: Cable printer/personal computer interface
cable.
PRN-6F: UL listed compatible event printer. Uses tractor-fed
paper.
IPDACT, IPDACT-2/2UD Internet Monitoring Module: Mounts
in bottom of enclosure with optional mounting kit (PN IPBRKT).
Connects to primary and secondary DACT telephone output
ports for internet communications over customer provided ether-
ADDRESSABLE FIRE ALARM
CONTROL PANEL
MS-9050UD
MS-9050UD
Fire Alarm
Control Panel
pooL CLS
SD355
Photo Detector
AD355
Adapt Detector
MMF-300
Monitor Module
P2R
Strobe
P2R
Strobe
MMF-302
2-Wire Detector
Monitor Module
BG-12LX Addressable
Manual Pull Station
Power Supply
FCPS-24FS6
FCPS-24FS8
SD355T
Photo/Thermal
ANN-80
MDF-300
Dual Monitor Module
H355/H355R/H355HT
Heat Detector
D355PL
Duct Detector
Multi-Modules
CRF-300-6 Six-Relay Control Module
CMF-300-6 Six-Circuit Supervised Control Module
MMF-302-6 Six-Zone Interface Module
MMF-300-10 Ten-Input Monitor Module
P2R
Strobe
Beam Detector
BEAM-335/(S)
Printer
Gateway
ANN-S/PG
Graphic LED Module
Relay Module
ANN-RLY
ANN-I/O
DF-52418:E1 • 1/27/12 — Page 3 of 4
net internet connection. Requires compatible Teldat Visoralarm
Central Station Receiver. Can use DHCP or static IP. (See data
sheet df-52424 for more information.)
IPBRKT:
Mounting kit for IPDACT-2/2UD in common enclosure.
IPSPLT: Y-adaptor option allows connection of both panel dialer
outputs to one IPDACT-2/2UD cable input.
AC-TRMBLK: AC Terminal Block mounts to a metal bracket, in
turn, mounts to the FACP chassis. Use AC-TRMBLK when wire
nuts are not allowed for AC connections to the transformer.
OPTIONAL MODULES
4XTMF Reverse Polarity Transmitter Module: Provides a
supervised output for local energy municipal box transmitter,
alarm and trouble. Includes a disable switch and disable trouble
LED.
ANN-SEC: Optional secondary ANN-BUS interface module.
Note: Used only with firmware 3.0 or higher.
COMPATIBLE ANNUNCIATORS
ANN-80(-W): Remote LCD annunciator mimics the information
displayed on the FACP LCD display. Recommended wire type is
un-shielded. (Basic model is red; order -W version for white; see
DF-52417.)
ANN-I/O: LED Driver Module provides connections to a user
supplied graphic annunciator. (See DF-52430.)
ANN-LED: Annunciator Module provides three LEDs for each
zone: Alarm, Trouble, and Supervisory. Ships with red enclo-
sure. (See DF-60241.)
ANN-RLED: Provides alarm (red) indicators for up to 30 input
zones or addressable points. (See DF-60241.)
ANN-RLY: Relay Module provides 10 programmable Form-C
relays. Can be mounted inside the cabinet. (See DF-52431.)
ANN-S/PG: Serial/Parallel Printer Gateway module provides a
connection for a serial or parallel printer. (See DF-52429.)
ADDRESSABLE DEVICES
All feature a polling LED and rotary switches for addressing.
CP355: Addressable low-profile ionization smoke detector.
SD355: Addressable low-profile photoelectric smoke detector.
SD355T: Addressable low-profile photoelectric smoke detector
with thermal sensor.
SD355R: Remote test capable addressable photoelectric
smoke detector for use with DNR(W) duct detector housing.
H355: Fast-response, low-profile heat detector.
H355R: Fast-response, low-profile heat detector with rate-of-
rise option.
H355HT: Fast-response, low-profile heat detector that activates
at 190°F/88°C.
AD355: Low-profile, intelligent, “Adapt” multi-sensor detector
(B350LP base included).
BEAM355: Intelligent beam smoke detector.
BEAM355S: Intelligent beam smoke detector with integral sen-
sitivity test.
D355PL: InnovairFlex low-flow non-relay duct-detector housing;
includes SD355R.
DNR: InnovairFlex low-flow non-relay duct-detector housing.
(Order SD355R separately.)
DNRW: InnovairFlex low-flow non-relay duct-detector housing,
with NEMA-4 rating. Watertight. (Order SD355R separately.)
MMF-300: Addressable Monitor Module for one zone of nor-
mally-open dry-contact initiating devices. Mounts in standard
4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-line
resistor. Module may be configured for either a Style B (Class B)
or Style D (Class A) IDC.
MDF-300: Dual Monitor Module. Same as MMF-300 except it
provides two Style B (Class B) only IDCs.
MMF-301: Miniature version of MMF-300. Excludes LED and
Style D option. Connects with wire pigtails. May mount in device
backbox.
MMF-302A: Similar to MMF-300A. Addressable Monitor Module
for one zone of conventional two-wire detectors. Requires reset-
table 24 VDC power. Refer to the Device Compatibility Docu-
ment for listed compatible devices and quantity limitation.
CMF-300: Addressable Control Module for one Style Y/Z (Class
B/A) zone of supervised polarized Notification Appliances.
Mounts directly to a 4.0" (10.16 cm.) electrical box. Notification
Appliance Circuit option requires external 24 VDC to power noti-
fication appliances.
CRF-300: Addressable relay module containing two isolated
sets of Form-C contacts, which operate as a DPDT switch.
Mounts directly to a 4.0" (10.16 cm.) box, surface mount using
the SMB500.
BG-12LX: Addressable manual pull station with interface mod-
ule mounted inside.
I300: This module isolates the SLC loop from short circuit condi-
tions (required for Style 6 or 7 operation).
SMB500: Used to mount all modules except the MMF-301 and
M301.
MMF-300-10: Ten-input monitor module. Mount one or two mod-
ules in a BB-2F cabinet (optional). Mount up to six modules on a
CHS-6 chassis in a BB-6F cabinet.
MMF-302-6: Six-zone interface module. Mount one or two mod-
ules in a BB-2F cabinet (optional). Mount up to six modules on a
CHS-6 chassis in a BB-6F cabinet.
CMF-300-6: Six-circuit supervised control module. Mount one or
two modules in a BB-2F cabinet (optional). Mount up to six mod-
ules on a CHS-6 chassis in a BB-6F cabinet.
CRF-300-6: Six-relay control module (Form-C relays). Mount
one or two modules in a BB-2F cabinet (optional). Mount up to
six modules on a CHS-6 chassis in a BB-6F cabinet.
NOTE: For more information on Compatible Addressable Devices
for use with the MS-9050UD, see the following data sheets (docu-
ment numbers): AD355 (DF-52386), BG-12LX (DF-52013), CMF-
300-6 (DF-52365), CRF-300-6 (DF-52374), CMF/CRF Series (DF-
52130), CP355 (DF-52383), H355 Series (DF-52385), I300 (DF-
52389), MMF-300 Series/MDF-300 (DF-52121), MMF-300-10
(DF-52347), MMF-302-6 (DF-52356), SD355/SD355T (DF-
52384).
ADDRESSABLE DEVICE ACCESSORIES
End-of-Line Resistor Assembly (R-47K and R-3.9K): The
47k ohm assembly supervises the MMF-300, MDF-300, MMF-
301, and CMF-300 module circuits. The 3.9k ohm assembly
supervises the MMF-302 module circuit. These resistors are
included with each module.
Power Supervision Relay: Supervises the power to 4-wire
smoke detectors and notification appliances.
Wiring Requirements
While shielded wire is not required, it is recommended that all
SLC wiring be twisted-pair to minimize the effects of electrical
interference. Refer to the panel manual for wiring details.
Page 4 of 4 — DF-52418:E1 • 1/27/12
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
www.firelite.com
Made in the U.S. A.
System Capacity
Intelligent Signalling Line Circuits......................................... 1
Addressable device capacity .............................................. 50
Programmable software zones ........................................... 20
Annunciators......................................................................... 8
Electrical Specifications
AC Power: MS-9050UD 120 VAC, 60 Hz, 3.0 A. MS-9050UDE:
240 VAC, 50 Hz, 1.5 A. Wire size: minimum 14 AWG (2.00 mm2)
with 600 V insulation. Nonpower-limited, supervised.
Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger
Capacity: 7-18 AH (MS-9050UD cabinet holds maximum of two
18 AH batteries.)
Communication Loop: Supervised and power-limited.
Notification Appliance Circuits: Terminal Block provides con-
nections for two NACs, Style Y (Class B) or Style Z (Class A).
Special Application power. Power-limited, supervised circuitry.
Maximum signaling current per circuit: 2.5 A. End-of-Line Resis-
tor: 4.7k ohm, ½ watt (P/N 71252 UL listed) for Style Y (Class B)
NAC. Refer to the Fire•Lite Device Compatibility Document for
listed compatible devices.
Two Programmable Relays and One Fixed Trouble Relay:
Contact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC
(resistive). Form-C relays, nonpower-limited, nonsupervised.
Cabinet Specifications
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72"
(1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65"
(42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (TR-CE):
22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.
Shipping Specifications
Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00” (50.80 cm.)
high x 22.5” (57.15 cm.) wide x 8.5” (21.59 cm.) deep.
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (non-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic compo-
nents may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system and
its peripherals be installed in an environment with a normal room
temperature of 15 – 27°C/60 – 80°F.
NFPA Standards
The MS-9050UD(E) complies with the following NFPA 72 Fire
Alarm Systems requirements:
–LOCAL (Automatic, Manual, Waterflow and Sprinkler
Supervisory).
– AUXILIARY (Automatic, Manual and Waterflow) (requires
4XTMF).
REMOTE STATION (Automatic, Manual and Waterflow)
(Where a DACT is not accepted, the alarm, trouble and
supervisory relays may be connected to UL 864 listed
transmitters. For reverse polarity signaling of alarm and
trouble, 4XTMF is required.)
–PROPRIETARY (Automatic, Manual and Waterflow).
CENTRAL STATION (Automatic, Manual and Waterflow,
and Sprinkler Supervised).
–OT, PSDN (Other Technologies, Packet-switched Data Net-
work)
Agency Listings and Approvals
The listings and approvals below apply to the basic MS-
9050UD(E) control panel. In some cases, certain modules may
not be listed by certain approval agencies, or listing may be in
process. Consult factory for latest listing status.
UL: S624
FM approved
CSFM: 7165-0075:210
MEA: 442-06-E
NOTE: See DF-60445 for ULC-listed model.
FireLite® Alarms® and System Sensor® are registered trademarks of
Honeywell International Inc. Microsoft® and Windows® are registered
trademarks of the Microsoft Corporation.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
SYSTEM SPECIFICATIONS