IF 1635 Revision 3 Installation Directions

2014-10-23

: Pdf 133193-Installationsheet 133193-InstallationSheet Batch9 unilog

Open the PDF directly: View PDF PDF.
Page Count: 4

IF 1635 • 09/12 Copyright © 2012, Cooper Industries, Inc. Page 1
EVLL HAZARD•GARD®
LED LUMINAIRE
Installation & Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
IF 1635
APPLICATION
EVLL HAZARD•GARD®LED Luminaires are suitable for use in the following
hazardous (classified) areas as defined by the National Electrical Code (NEC®) and
Canadian Electrical Code (CEC):
• Class I, Division 1, Groups B, C, D
• Class II, Groups E, F, G
• Wet locations (UL1598), Marine locations (UL1598A), NEMA 4X, IP66
Refer to the luminaire nameplate for specific classification information, maximum
ambient temperature suitability and corresponding operating temperature (T-Code).
EVLL HAZARD•GARD®LED Luminaire is designed for use indoors and outdoors in
marine and wet locations, where moisture, dirt, corrosion, vibration, and rough
usage may be present. FIGURE 1
WARNING
To avoid the risk of fire, explosion, or electric shock, this product should
be installed, inspected, and maintained by a qualified electrician only, in
accordance with all applicable electrical codes.
WARNING
To avoid electric shock:
Be certain electrical power is OFF before and during installation and
maintenance.
Luminaire must be supplied by a wiring system with an equipment grounding
conductor.
WARNING
To avoid explosion:
Make sure that the supply voltage is the same as the luminaire voltage.
Do not install where the marked operating temperatures exceed the ignition
temperature of the hazardous atmosphere.
Do not operate in ambient temperatures above those indicated on the luminaire
nameplate.
All gasket seals must be clean and undamaged.
Use proper supply wiring as specified on the luminaire nameplate.
Before dismounting, electrical power to the luminaire must be turned off. Keep
tightly closed when in operation.
EVLL HAZARD•GARD®LED Luminaires are
supplied for use with a choice of voltages:
• 100VAC - 277VAC, 50/60Hz, 108-250VDC
• NEMA 4X • UL IP66
DIMENSIONS
406.4
Ø 16.0
296.9
11.7
339.7
Ø 13.4
322.4
12.7
Driver Housing Bolt (Qty. 8)
Upper Driver Housing
Lower Driver Housing
LED Housing
Set Screw
IF 1635 • 09/12 Copyright © 2012, Cooper Industries, Inc. Page 2
INSTALLATION
Mounting Modules
1. To prevent galling, lightly lubricate all mounting module threads using Cooper
Crouse-Hinds HTL lubricant.
2. Refer to the mounting module nameplate for the supply wire temperature
rating.
Pendant mounting module installation:
Lightly lubricate hub threads with Cooper Crouse-Hinds HTL lubricant. Thread the
pendant mount onto the conduit until wrench-tight.
Tighten hub locking screw to conduit to 40 lb.-in. (4.5 N-m).
Figure 2 - Pendant Mounting Module Installation
Stanchion mounting module installation: Hub mounting thread is 1-1/2 NPT.
Lightly lubricate hub thread using Cooper Crouse-Hinds HTL lubricant. Thread
stanchion mounting module on conduit and torque until wrench-tight.
Tighten hub locking screw to conduit to 40 lb.-in. (4.5 N-m).
Figure 3 - Stanchion Mounting Module Installation
TABLE 1
WARNING
To avoid explosion, seal luminaire conduit within the distance given in Table
1, local electrical code requirements, and NEC Article 501 (CEC Section 18).
WARNING
To prevent electric shock, isolating fixture hangers must not be used in
installations where the conduit system is used as the grounding connection.
Mounting module
locking screw
Hub locking screw
Mounting module locking
screw
Hub locking screw
EXTERNAL SEALING REQUIREMENTS
Module Group C & D Group B
EVSP Pendant
EVSC Ceiling
EVSJ Stanchion 10 ft. (3 m.)
EVSW Wall
EVSA Adapter + EVMP Pendant 18 in. (45 cm.)
EVSA + EV Ceiling 5 ft. (1.5m) 18 in. (45 cm.)
EVSA + EVMJ Stanchion 18 in. (45 cm.)
EVSA + EV Wall Bracket 18 in. (45 cm.)
Ceiling mounting module
installation:
Secure the ceiling mount to the
structure using four 5/16"
fasteners (not supplied).
Lightly lubricate hub threads
using Cooper Crouse-Hinds HTL
lubricant. Thread conduit into
the mounting module hubs until
wrench-tight. Install pipe plugs
(supplied) into unused conduit
openings and torque firmly.
Wall mounting module:
Secure the wall mounting module
to the structure using two 3/8"
fasteners (not supplied).
Lightly lubricate hub threads
using Cooper Crouse-Hinds HTL
lubricant. Thread conduit into
the mounting module until
wrench-tight. Install pipe plugs
(supplied) into unused conduit
openings and torque firmly.
Wiring must be made prior to
mounting fixture. Access
opening may be used while
pulling wires into the wall
mounting module. Ensure that
the cap o-ring is clean and
undamaged and that the cap is
completely threaded into the mounting module before power is restored.
Wiring
1. Remove connection block from mounting
module by removing two chrome-colored
screws. Pull field wiring into the mounting
module.
2. Connect connection block wires to supply
wires per the attached wiring diagrams using
methods that comply with all applicable codes.
3. Attach circuit ground wire to GREEN ground
wire in the mounting module. If separate
ground conductor is not used in wiring system,
ground wire in mounting module must be
capped or removed.
4. Attach ungrounded primary supply wire to
BLACK connection block conductor and other
supply wire to RED connection block
conductor.
5. Tighten all electrical connections securely.
6. Insert connection block into mounting module,
and install the two mounting screws. See
Figure 7. Figure 6 -
Wiring Connections
Connection Block
Figure 4 -
Ceiling Mounting Module Installation
MOUNTING DETAIL
CEILING MOUNT
4.00
4.00
4 HOLES
5/16 DIA.
4.00 2 HOLES
13/32 DIA
MOUNTING DETAIL
WALL MOUNT
Figure 5 -
Wall Mounting Module Installation
Mounting
Screws
IF 1635 • 09/12 Copyright © 2012, Cooper Industries, Inc. Page 3
Mounting
Screws
(chrome
colored)
Figure 7 - Connection Block Installation
WARNING
To maintain explosionproof integrity, make sure all threads are fully
engaged.
7. Apply a small amount of HTL®lubricant to threads. Thread luminaire
assembly completely into the mounting module. Tighten locking screw on
mounting module head to 40 lb.-in. (4.5 N-m).
8. Turn power on.
GUARD INSTALLATION
Optional guards:
Wire P71
1. Slip wire guard on the LED housing (see diagram below).
2. Tighten the screw.
MAINTENANCE
1. Perform visual, electrical, and mechanical inspections on a regular basis. The
environment and frequency of use should determine this. However, it is
recommended that checks be made at least once a year. We recommend an
Electrical Preventive Maintenance Program as described in the National Fire
Protection Association Bulletin NFPA No. 70B: Recommended Practice For
Electrical Equipment Maintenance (www.nfpa.org).
2. The lens should be cleaned periodically to ensure continued lighting
performance. To clean, wipe the lens with a clean, damp cloth. If this is not
sufficient, use a mild soap or a liquid cleaner such as Collinite NCF or Duco
#7. Do not use an abrasive, strong alkaline, or acid cleaner. Damage may
result.
3. Visually check for undue heating evidenced by discoloration of wires or other
components, damaged parts, or leakage evidenced by water or corrosion in
the interior. Replace all worn, damaged, or malfunctioning components, and
clean gasket seals before putting the luminaire back into service.
4. Electrically check to make sure that all connections are clean and tight.
5. Mechanically check that all parts are properly assembled.
6. To prevent heat build-up, remove dust from the fins on the LED housing, using
a soft brush or air pressure.
REPLACEMENT PARTS
Cooper Crouse-Hinds EVLL HAZARD•GARD®LED Luminaires are designed to
provide years of reliable lighting performance. However, should the need for
replacement parts arise, they are available through your authorized Cooper
Crouse-Hinds distributor. Assistance may also be obtained through your local
Cooper Crouse-Hinds representative.
Cooper Crouse-Hinds Sales Service Department, P.O. Box 4999, Syracuse, New
York 13221, Phone (315) 477-7000.
LED Housing
Screw
Guard
TRUNNION MOUNT INSTALLATION
LENS DOWN LENS HORIZONTAL
AIMING RANGE
YOKE
PIVOT BOLT (2)
(SEE NOTES 3, 4, 5)
LOCKING BOLT (2)
(SEE NOTES 3, 4, 6)
TRUNNION MOUNTING SHOWN
(SUFFIX -S812)
1. Using yoke as a template, mark and drill desired location on mounting
surface.
2. Secure yoke to surface using 1/2” bolts or lag screws (not provided).
3. To make final adjustment, loosen the pivot and locking bolts to position at the
desired angle*.
4. Rotate fixture to the desired position.
5. Tighten the two (2) 1/2-13 pivot bolts to 45±1.7 lbs.-ft. [61.23±0.23 N-m].
6. Tighten the two (2) 5/16-18 locking bolts to 11.45±1.2 lbs.-ft. [15.6±1.6 N-m].
*For Class II installations only. Fixture mounting range is limited to lens down to horizontal.
All statements, technical information and recommendations contained herein are based on information and tests we believe to be
reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Crouse-Hinds "Terms and Conditions of Sale",
and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use
and assumes all risk and liability whatsoever in connection therewith.
Cooper Industries Inc. IF 1635
Crouse-Hinds Division Revision 3
PO Box 4999, Syracuse, New York 13221 • U.S.A. Revised 09/12
Copyright © 2012, Cooper Industries, Inc.Supercedes 04/12
WIRING DIAGRAMS
FIELD ASSEMBLED LUMINAIRE - EVLL HAZARD•GARD®LED SERIES LUMINAIRE
A complete EVLL luminaire consists of: an EVLL driver-led enclosure, a mounting module, with or without guard and/or reflector
EVJ2
EV22
EV33
EVMP2
EVMP3
EV22
EV33
EV87 EVMJ4
EVSP2
EVSP3
EVSP25
EVSP32
EVSC2 EVSC25
EVSC3 EVSC32
EVSA
EVSW2
EVSW3
EVSW25
EVSW32
EVSJ5
(1 14”)
(1 12”)
100V TO 277VAC (BLK)
NEUTRAL (WHT)
100V TO 277VAC 50 OR 60HZ OR 108V TO 250VDC INPUT
EVLL13LC
LINE IN (BLK) DRIVER
NEUTRAL (WHT) V- (BLK)
V+ (RED)
INPUT OUTPUT
V- (BLK)
OUTPUT
V+ (RED)
DRIVER
NEUTRAL (WHT)
LINE IN (BLK)
INPUT
V- (BLK)
V+ (RED)
OUTPUT
DRIVER
NEUTRAL (WHT)
LINE IN (BLK)
INPUT
V- (BLK)
V+ (RED)
OUTPUT
DRIVER
NEUTRAL (WHT)
INPUT
LINE IN (BLK)
LED SUBARRAY
LED SUBARRAY
LED SUBARRAY
LED SUBARRAY
GROUND (GND)
FOR DC WIRING, ATTACH POSITIVE (+) LEAD TO LINE OUT (BLK) AND ATTACH NEGATIVE (-) LEAD TO NEUTRAL (WHT) WIRE
LINE IN (BLK)
NEUTRAL (WHT)
V+ (RED)
V- (BLK)
INPUT OUTPUT
DRIVER
INPUT
NEUTRAL (WHT)
LINE IN (BLK) OUTPUT
V- (BLK)
V+ (RED)
DRIVER
INPUT
NEUTRAL (WHT)
LINE IN (BLK)
OUTPUT
V- (BLK)
V+ (RED)
DRIVER
INPUT
NEUTRAL (WHT)
LINE IN (BLK)
OUTPUT
V- (BLK)
V+ (RED)
DRIVER
LED SUBARRAY
LED SUBARRAY
LED SUBARRAY
LED SUBARRAY
LED ARRAY
TRANSFORMER
347V OR 480V
(BLU OR RED)
NEUTRAL (WHT)
LINE OUT (BLK)
NEUTRAL (WHT)
347V OR 480V 60HZ INPUT
EVLL
GROUND (GRN)
NOT USED FOR NEVLL
• Not for IEC units

Navigation menu