Bussmann Series REN And RES Renewable Fuse Data Sheet No. 1028 Brochure
2016-07-04
: Pdf 157040-Brochure 157040-Brochure B1 unilog
Open the PDF directly: View PDF .
Page Count: 5
Description:
Non-current limiting, renewable 250V (REN)
and 600V (RES) Class H size fuses and fuse
links (250V LKN and 600V LKS) for use in
electrical systems where the available fault
current is less than 10,000 amps and
frequent outages dictate the economy of
these renewable type fuses.
NOTE: The 70-600 amp ratings of the REN
and RES fuses are now discontinued.
Suggested replacements are:
• REN; Use 250V FRN-R Class RK5 fuses
(see data sheet No. 1020)
• RES; Use 600V FRS-R Class RK5 fuses
(see data sheet No. 1018)
Replacement fuse links for all 1-600A
ratings (250V LKN and 600V LKS) will
continue to be available to service the
installed base of REN and RES fuses.
Specifications:
Ratings
• Volts
• REN 250Vac
• RES 600Vac
• Amps
• 1-60A
• Interrupting Rating
• 10kA RMS Sym.
REN (250V) and RES (600V) Renewable
Class H size fuses
Technical Data 1028
250V REN Catalog numbers (1-60 Amps)
REN-1 REN-6 REN-15 REN-40
REN-2 REN-7 REN-20 REN-45
REN-3 REN-8 REN-25 REN-50
REN-4 REN-10 REN-30 REN-60
REN-5 REN-12 REN-35 -
250V REN Carton quantity and weight
Catalog
number
Carton
qty
Weight
lbs (kg)*
REN 1–30 10 0.55 (0.249)
REN 35–60 10 1.40 (0.634)
*Weight per carton.
600V RES Catalog numbers (1-60 Amps)
RES-1 RES-6 RES-20 RES-45
RES-2 RES-8 RES-25 RES-50
RES-3 RES-10 RES-30 RES-60
RES-4 RES-12 RES-35 -
RES-5 RES-15 RES-40 -
600V RES Carton quantity and weight
Catalog
number
Carton
qty
Weight
lbs (kg)*
RES 1–30 10 0.18 (0.082)
RES 35–60 10 0.36 (0.163)
*Weight per carton.
Features
• These fuses are generally sized at the amp
rating of non-inductive circuits and 300% for
motor circuits.
Recommended fuse blocks
Part number Description
HM250 250V, 30 and 60A 1-, 2- and
3-pole open fuse blocks
HM600 600V, 30 and 60A 1-, 2 and
3-pole open fuse blocks
For details, see data sheet No. 10289.
Effective December 2015
Supersedes March 2014
BUSSMANN
SERIES
2
Technical Data 1028
Effective December 2015
REN (250V) and RES (600V)
Renewable Class H fuses
Eaton.com/bussmannseries
Dimensions - in
Replacement 250V REN and 600V RES fuse links
250V LKN Fuse link catalog numbers (amps)
LKN-1 LKN-10 LKN-60 LKN-200
LKN-1-1/2 LKN-12 LKN-70 LKN-225
LKN-2 LKN-15 LKN-75 LKN-250
LKN-3 LKN-20 LKN-80 LKN-300
LKN-4 LKN-25 LKN-90 LKN-350
LKN-5 LKN-30 LKN-100 LKN-400
LKN-6 LKN-35 LKN-110 LKN-450
LKN-7 LKN-40 LKN-125 LKN-500
LKN-8 LKN-45 LKN-150 LKN-600
LKN-9 LKN-50 LKN-175 -—
250V LKN Fuse link carton quantity and weight
Catalog
number
Carton
qty
Weight
lbs (kg)*
LKN 1–30 20 0.05 (0.02)
LKN 35–60 20 0.20 (0.09)
LKN 70–100 10 0.20 (0.09)
LKN 110–200 50.25 (0.11)
LKN 225–400 50.55 (0.25)
LKN 450–600 20.32 (0.15)
*Weightpercarton.
600V LKS Fuse link catalog numbers (amps)
LKS-1 LKS-10 LKS-50 LKS-200
LKS-2 LKS-12 LKS-60 LKS-225
LKS-2-1/2 LKS-15 LKS-70 LKS-250
LKS-3 LKS-17-1/2 LKS-80 LKS-300
LKS-4 LKS-20 LKS-90 LKS-350
LKS-5 LKS-25 LKS-100 LKS-400
LKS-6 LKS-30 LKS-110 LKS-450
LKS-7 LKS-35 LKS-125 LKS-500
LKS-8 LKS-40 LKS-150 LKS-600
LKS-9 LKS-45 LKS-175 —
600V RES Fuse link carton quantity and weight
Catalog
number
Carton
qty
Weight
lbs (kg)*
LKS 1–30 20 0.05 (0.02)
LKS 35–60 20 0.02 (0.09)
LKS 65–100 10 0.02 (0.09)
LKS 110–200 50.25 (0.11)
LKS 225–400 50.55 (0.25)
LKS 450–600 20.32 (0.15)
*Weightpercarton.
1A to 30A
0.56"
2"
35A to 60A
0.81"
3"
1.06"
5.5"
35A to 60A
1A to 30A
0.81"
5"
250V REN 600V RES
3
REN (250V) and RES (600V)
Renewable Class H fuses
Technical Data 1028
Effective December 2015
Eaton.com/bussmannseries
Time-current characteristic curves – average melt
250V REN (LKN Fuse links)
Current in amperes
Current in amperes
Time in seconds
4
REN (250V) and RES (600V)
Renewable Class H fuses
Technical Data 1028
Effective December 2015
Time-currentcharacteristiccurves–averagemelt
600V RES (LKS Fuse links)
Eaton.com/bussmannseries
Current in amperes
Time in seconds
Current in amperes
5
REN (250V) and RES (600V)
Renewable Class H fuses
Technical Data 1028
Effective December 2015
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this
document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical
information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of
any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any
technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Eaton and Bussmann are valuable
trademarks of Eaton in the US and other
countries. You are not permitted to use the
Eaton trademarks without prior written
consent of Eaton.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. 1028 – BU-SB14109
December 2015
For Eaton’s Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton.com/bussmannseries
Follow us on social media to get the
latest product and support information.