- GE BuyLog Table of Contents/Introduction
- Section 1: Load Centers and Circuit Breakers
- Section 2: Modular Metering
- Section 3: Electric Vehicle Charging Stations
- Section 4: Safety Switches
- Section 5: Surge Protection Devices (SPD)
- Section 6: Molded Case Circuit Breakers
- Industrial Circuit Breakers
- Q-Line Circuit Breakers
- Thermal Magnetic Trip
- Internal Accessories – Molded Case Circuit Breakers
- Spectra™ RMS
- Spectra™ RMS with microEntelliGuard™ Trip Unit
- Accessories for Spectra™ RMS Circuit Breakers with microEntellGuard™ Trip Units
- Record Plus™
- 15-100A, FB Line……6-69
- FB Internal Accessories……6-73
- FB External Accessories……6-74
- 15-100A, FC Line……6-75
- FC Internal Accessories……6-78
- FC External Accessories……6-79
- 25-250A, FE Line……6-80
- FE Internal Accessories……6-82
- FE External Accessories……6-82
- 100-600A, FG Line……6-84
- FG with PremEon™ S……6-85
- FG with SMR2……6-86
- FG Internal Accessories……6-88
- FG External Accessories……6-89
- Molded Case Switches – 100-1200 A……6-90
- External Accessories
- Cable Operators……6-94
- Flange-Mounted Operators……6-96
- Door Mounted Operators……6-98
- Motor Operators and Plug-in Hardware……6-100
- Mechanical Interlocks and Locking Devices……6-101
- Breaker Mounting Hardware and Kits……6-102
- Lugs and Associated Hardware……6-103
- Neutral Grounds and Sensors……6-104
- Plug-in Hardware……6-106
- Section 7: Circuit Breaker Enclosures
- Section 8: Low Voltage Power & Insulated Case Circuit Breakers
- Section 9: Disconnect Switches and Operating Mechanisms
- Section 10: Dry Type Transformers
- Section 11: Panelboards
- Section 12: Switchboards
- Section 13: Busway
- Section 14: Automatic Transfer Switches
- Section 15: Motor Control Centers—Low Voltage
- Section 16: Switchgear — Low Voltage
- Section 17: Entellisys™ 4.0 Low-Voltage Switchgear
- Section 18: Medium Voltage Equipment
- Section 19: Paralleling Switchgear Critical Power Products
- Section 20: Uninterruptible Power Supplies
- Section 21: Telecommunication Hardware
- Section 22: Relays and Meters
- Section 23: Meters and Instrument Transformers
- Section 24: Capacitors, Arresters and Harmonic Filters
- Section 25: Distribution Transformers–Medium and High Voltage
- Section 26: DC Power Systems
- Section 27: GE Publication Index
- Section 28: Time Current Curves and Outline Drawings
- Section 29: GE Product Index
www.geindustrial.com BuyLog™Catalog 6-1
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Industrial Circuit Breakers
How to Order................................................................................................6-2
Features..........................................................................................................6-4
Quick Reference Guide ............................................................................6-6
Q-Line Circuit Breakers
Plug-In 120/240V Class.........................................................................6-14
Plug-In 240V Class ..................................................................................6-16
Bolt-On 240V Class .................................................................................6-20
Cable-In Cable Out (lug-lug) 240V Class.......................................6-25
DIN-Rail Mount 240V Class .................................................................6-27
Cable-In Cable Out (lug-lug) 240V Class.......................................6-28
Molded Case Switches 240V Class..................................................6-29
Accessories 240V Class ........................................................................6-30
Thermal Magnetic Trip
15-100A Type TEY/TEYF Bolt-On ......................................................6-32
15-125A Type TEYD/TEYH/TEYL........................................................6-33
10-150A E-150 Line Types TEB, TED, THED ................................6-35
125-600A J600 Line Types TJJ, TJK, THJK....................................6-37
Internal Accessories – Molded Case Circuit Breakers
Accessory Devices and Ratings........................................................6-39
Auxiliary Switches....................................................................................6-40
Shunt Trip ....................................................................................................6-41
Undervoltage Release ...........................................................................6-43
Spectra™RMS
15-150A, SE150 Frame .........................................................................6-45
70-250A, SF250 Frame .........................................................................6-47
125-600A, SG600 Frame......................................................................6-49
300-1200A, SK1200 Frame.................................................................6-52
Spectra™RMS with microEntelliGuard™Trip Unit
Features .......................................................................................................6-54
microEntelliGuard™Trip Unit Characteristics .............................6-55
How to Order .............................................................................................6-56
60-600A, SG600 Line..............................................................................6-58
300-1200A, SK1200 Line......................................................................6-60
Accessories for Spectra™RMS Circuit Breakers with
microEntellGuard™Trip Units
Power Management System Accessories....................................6-62
Other Accessories....................................................................................6-66
Internal Accessories ...............................................................................6-67
Record Plus™
15-100A, FB Line ......................................................................................6-69
FB Internal Accessories.........................................................................6-73
FB External Accessories........................................................................6-74
15-100A, FC Line......................................................................................6-75
FC Internal Accessories.........................................................................6-78
FC External Accessories........................................................................6-79
25-250A, FE Line ......................................................................................6-80
FE Internal Accessories.........................................................................6-82
FE External Accessories........................................................................6-82
100-600A, FG Line...................................................................................6-84
FG with PremEon™S................................................................................6-85
FG with SMR2 ...........................................................................................6-86
FG Internal Accessories ........................................................................6-88
FG External Accessories .......................................................................6-89
Molded Case Switches – 100-1200 A ......................................6-90
Motor Circuit Protectors
3-250A Spectra™RMS Mag Break....................................................6-91
125-1200A Spectra™RMS Mag Break............................................6-92
25-600A Record Plus Mag Break......................................................6-93
External Accessories
Cable Operators .......................................................................................6-94
Flange-Mounted Operators ................................................................6-96
Door Mounted Operators.....................................................................6-98
Motor Operators and Plug-in Hardware....................................6-100
Mechanical Interlocks and Locking Devices............................6-101
Breaker Mounting Hardware and Kits ........................................6-102
Lugs and Associated Hardware.....................................................6-103
Neutral Grounds and Sensors.........................................................6-104
Plug-in Hardware..................................................................................6-106
Section Updated 10 / 2014
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-2
Molded Case Circuit Breakers Section 6
How to Order
Q-Line
—Thermal Magnetic Circuit Breakers
—Molded-Case Switches
The product number as shown in the following pages includes the
complete breaker or switch. TQD and TJD breakers are complete
with Cu/Al line and load lugs.
E 150 Line
—Thermal Magnetic Circuit Breakers
—Magnetic Circuit Breakers
—Molded Case Switches
The product numbers as shown in the following pages include the
complete breaker or switch. All devices listed come with Cu/Al line
and load lugs. If line lugs are not required on a breaker, eliminate
“WL” from product number; for molded case switches see page
6-3. Unless otherwise noted, all circuit breakers are UL listed in
File E–11592. Molded case switches are UL listed in File E–57546.
J 600 Line
—Thermal Magnetic Circuit Breakers
—Magnetic Circuit Breakers
—Molded Case Switches
These breakers are available with either noninterchangeable trip
(designated Type TJJ) or interchangeable trip (designated Type
TJK and THJK). Type TJJ product numbers include frame, trip,
Cu/Al line, and load lugs factory assembled. If line lugs are not
required on the breaker, eliminate “WL” from product number, and
subtract price of line lugs from price of complete breaker.
TJK breakers are available in two frames, 400 ampere frame
(125 to 400 amperes) and 600 ampere frame (250 to 600
amperes). Trip units are not interchangeable between frames.
“Complete Circuit Breaker” price includes frame, trip unit, Cu/Al
line, and load lugs. Unit will be shipped unassembled unless order
specifies “must be factory assembled.” If line lugs are not
required, eliminate “WL” from product number and subtract price
of line lugs from price of complete breaker.
To order the frame, trip, and lugs separately, select the required
components from table. Magnetic breakers must be ordered as
components. A complete breaker consists of frame, trip, and one
line and one load lug per pole.
Price of ordering “Complete Circuit Breaker” vs. frame, trip, and
line and load lugs separately is the same.
Molded case switches can also be ordered as complete units
(designated Type TJK---Y) or as separate components. They are
UL listed only as complete units. To indicate required lugs, see
page 6-3.
Unless otherwise noted, all circuit breakers are UL listed in File
E–11592. Molded case switches are UL listed in File E–57546.
Tri-Break™Line
—Integrally Fused Thermal Magnetic Circuit Breakers
—Integrally Fused Magnetic Circuit Breakers
—Integrally Fused Molded Case Switches
These breakers are available in three types. Type TB1 (15-100
amperes) product numbers include frame, trip, line and load
lugs, and current limiters all factory assembled. TB6 (300 to 600
amperes) and TB8 (600 to 800 amperes) include frame, trip and
limiters, factory assembled, but do not include line or load lugs.
If line and load lugs are required, order
separately. Unless other-
wise noted, TB1, TB6, and TB8 breaker components are UL
listed in File E–42263. Fused molded case switches are UL
listed in File E–57546.
Mag-Break Line
—Magnetic only circuit breakers (motor circuit protectors)
These breakers are available only with noninterchangeable
adjustable magnetic trip, in frame Types E, F, J, K, and Tri-Break™.
All breakers are shipped factory assembled, complete with Cu/Al
line and load lugs.
All magnetic only circuit breakers and limiters are UL Component
Recognized in Files E–11592 and E–66390, respectively, unless
otherwise noted.
Industrial Circuit Breakers
Q-Line Thermal Magnetic Circuit Breakers
and Molded-Case Switches
www.geindustrial.com BuyLog™Catalog 6-3
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
www.geindustrial.com
Spectra™RMS
—Circuit Breakers
Determine the required breaker frame, IC rating, and load
requirements. Select frame, trip unit (rating plug), and lug,
if required, product numbers from the tables on pages 6-45
to 6-53. For Spectra™breakers with microEntelliGuard™Trip
Units refer to pages 6-54 through 6-61. Select field-mounted
internal accessory product numbers, if required, on pages 6-67
and 6-68. Select field-mounted external accessory product
numbers, if required, on pages 6-95 through 6-106 and pages
6-62 to 6-66 for Spectra™breakers with microEntelliGuard™
Trip Units. Order as separate items.
—Mag-Break Motor Circuit Protectors
Determine the required frame and ampere requirements.
Select frame, trip unit (rating plug), and lug, if required,
product numbers from the table on pages 6-91 through 6-92.
Select accessories as noted above for circuit breakers. The
same accessories are used with both circuit breakers and
motor circuit protectors. Order as separate items.
—Molded Case Switches
Determine the required frame and ampere requirements.
Select frame and lug, if required, product numbers from
the table on page 6-90. Rating plugs are not used. Select
accessories as noted above for circuit breakers. Internal
accessories do not require dummy trips. The same
accessories are used with both circuit breakers and molded
case switches. Order as separate items.
Unless otherwise noted, all circuit breakers are UL listed in File
E–11592. Molded case switches are UL listed in File E–57546.
Field-Installable Internal Accessories are UL listed in File E–57253.
Distribution Cable Accessories for microEntelliGuard™Trip
Units are UL listed in File E–57253.
Accessories
Order accessories from the appropriate table:
—Thermal Magnetic Circuit Breakers, Magnetic Circuit Breakers,
and Molded Case Switches1—pages 6-39 to 6-44 and 6-94
to 6-106.
—Spectra™RMS Breakers—pages 6-66 to 6-67 and 6-94 to
6-106.
—Spectra™RMS Breakers with microEntelliGuard™Trip Units—
pages 6-62 to 6-68, and 6-94 to 6-106.
1Installation of accessories in molded case switches requires dummy trip; see page
6-44 for information. Dummy trip not required for Tri-Break™or Q-Line molded
case switches.
Blank WL XL X2 LL
TQD/TJD Load Lugs
Only
Line and
Load Lugs —Line Lugs
Only No Lugs
Molded Case
Breakers, Thermal
Magnetic
Load Lugs
Only
Line and
Load Lugs —Load Lugs
Only No Lugs
Molded Case
Switch
Line and
Load Lugs No Lugs— Line Lugs
Only
Load Lugs
Only
Spectra RMS™
Breakers No Lugs
Mine Duty™
Breakers No Lugs
Mag-Break™
Breakers
Line and
Load Lugs ————
Order Lugs Separately
Breaker/Switch
Type
Suffix
Order Lugs Separately
Industrial Circuit Breakers
Molded Case Circuit Breaker and Switch Terminal
Configuration Code
Order standard Cu/Al lugs by using suffix codes presented. Order
lugs separately if special lugs are required. For optional lugs, see
pages 6-103 and 6-104.
Spectra Circuit Breakers
and Molded Case Switches
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-4
Molded Case Circuit Breakers Section 6
www.geindustrial.com
Features
Spectra™RMS Molded Case Circuit Breakers
SE150, SF250, SG600, and SK1200 circuit breaker frames have a
digital, solid-state, rms sensing trip system with field installable,
front-mounted rating plugs to establish or change the breaker
ampere rating. Adjustable instantaneous with tracking short-time
is standard on all frames including SE150. The trip system uses
digital sampling to determine the rms value of sinusoidal and
nonsinusoidal currents.
microEntelliGuard™Trip Units
Spectra™SG600 and SK1200 breakers are now available with
microEntelliGuard™trip units - the newest and most advanced trip
unit available in the Spectra™line of molded case circuit breakers.
Based on the EntelliGuard™TU trip unit platform, the
microEntelliGuard™trip unit has the same HMI interface and
incorporates the advanced features and protective functions for
improved system protection, coordination, selectivity, perform-
ance, and diagnostic capabilities. New features offered with the
microEntelliGuard™trip unit include enhanced time-current curve
shaping capability, ground fault alarm, direct Modbus communi-
cations, reduced energy let-through setting, zone selective inter-
lock, neutral protection, waveform capture, and programmable
output contacts. The microEntelliGuard™trip unit utilizes the same
power management accessories offered for the Spectra™
MicroVersaTrip™with the addition of a new advanced junction
box and interconnect cables. The breakers have the same foot-
print and interrupt ratings as their SG/SK counterparts and are
backwards compatible with existing equipment and installations.
The microEntelliGuard™trip unit uses the same universal rating
plugs and test kit offered for the EntelliGuard TU™trip unit.
Spectra™SG600 and SK1200 Breakers
with microEntelliGuard™Trip Units
www.geindustrial.com BuyLog™Catalog 6-5
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
www.geindustrial.com
Record Plus™Molded Case Circuit Breakers
Record Plus™represents the very latest in molded case circuit
breaker design. Utilizing design features such as double-break
rotary contact structures and advanced ablative materials to
enhance interruption, Record Plus™is capable of interrupting
ratings up to 200kA. High kAIC ratings, selective coordination,
reduced arc flash energy, and current limitation embody the
core design principles of Record Plus™.
FC 100 and FB 100 circuit breakers are supplied with factory
installed non-user interchangeable thermal-magnetic trip units
and can be supplied with or without lugs. FB breakers are avail-
able in 1-, 2- and 3-pole versions. FC is available in 2- and 3-pole
versions, both in a 3-pole footprint.
FE 250 circuit breakers are supplied with factory installed, non-user
interchangeable PremEon S electronic trip units that feature the
use of front accessible, user adjustable dials to establish or change
the breaker’s amp rating.Adjustable instantaneous with tracking
short-time is standard.Ground fault protection is optional. FE is
available in 2- or 3-pole versions, both in a 3-pole footprint.
FG 600 circuit breakers are supplied with factory installed, non-
user interchangeable electronic trip units.Customers can select
from the PremEon S or SMR2 electronic trip units.PremEon S
features the use of front accessible, user adjustable dials to
establish or change the breaker’s amp rating.Adjustable
instantaneous with tracking short-time is standard.Ground fault
protection is optional.
SMR2 uses rating plugs to establish or change the breaker’s amp
rating. Rating plugs are user specified and ordered under separate
product number. SMR2 allows individual adjustment of Long-Time
delay, Short-Time pickup and Delay, and Ground Fault Pickup and
Delay (if so equipped). Zone Selective Interlocking (ZSI), Ground
Fault Alarm, and Modbus Communications are also available via
the SMR2’s interface. FG is available in 2- and 3-pole versions,
both in a 3-pole footprint.
All frames use common internal accessories (auxiliary switches, UV
releases, shunt trips, and bell alarms) UL listed for field installation.
UL listed maximum short circuit ratings at 480VAC are 150kA for
the 100A frames, 100kA for the 250A frame and 200kA for the
600A frames.
Unless noted otherwise, all circuit breakers and accessories are
listed in UL file number E11592.
Record Plus™Molded Case Circuit Breakers
Other MCCB Features
—UL489/cUL489 Listed
—Broad product line to meet virtually any application need.
—Reduced downtime. A tripped breaker is easily spotted and can
be immediately reset after the fault has been corrected.
—Eliminates single phasing. A common trip bar disconnects all
poles simultaneously on both overloads and short circuits.
—Offers application flexibility through the use of a wide variety of
accessory devices and special attachments.
—Repetitive operation—no fuses to replace.
—Breakers can be repetitively tested. Fuses must be destroyed to
confirm calibration accuracy.
For more information on these products, order publications listed
in Sections 27 and 28.
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-6
Molded Case Circuit Breakers Section 6
www.geindustrial.com
ac dc 120 120/240 240 277 480 600 125 250 H W D A B C E
1 1/2 100
2 1 50
1—1 50
2 2 25
3 240 —3 15
15-70 1 —1 50
15-125 2 2 25
15-100 3 240 —3 15
15-70 1 —1 50
2 2 25
3 240 —3 15
15-70 1 —1 50
15-125 2 2 25
15-100 3 240 —3 15
1—1 50
2 2 25
3240 —3 15
100-225 2 240 10 10 2 3/4 —1
100-225 3 240 —10 4 1/8 11/16 1
100-225 2 240 22 22 2 3/4 —1
100-225 3 240 —22 4 1/8 11/16 1
2240 22 22 10 1
3240 —22 1
—
—
—
—
———TJD 250-400 — — 3 13/168 1/410 1/8—
2 7/16 2 7/16 27/32
1 3/161 3/83 13/163 15/16
— — 6 9/16 2 5/8— — — —
2 7/16 27/32
THQD1
— 6 9/16 2 5/8 2 7/16
— —15-30
TQD1— — — — —
3 9/32 2 3/8 — —— — — —
TXQL1
TXQB1
TXQC1
120/240 —— 65
65 —
—
—
3 9/32 2 3/8
THHQL1120/240 —22
22 ——
22
22 3 9/32 2 3/8
— — — —
—
———
— —
THHQB1
THHQC115-100
120/240
—
—
—
———
— — —
THQL1
THQB1
THQC1
120/240 10
10
—
52
52
— — — ———
— —
— — —
3 9/32 2 3/8
2 3/8 — —— — — 3 9/32
—
TQL/TQB/
TQC 10 120/240 —
—2 3/8 — —
—— — —
— — — 3 9/32
Std.
Pack
THQP115-50 120/240 — — 10 — — —
UL Listed Interrupting Ratings—
rms Symmetrical kA
Vac Vdc Dimensions (in.)
Circuit
Breaker
Type
Ampere
Rating
No.
Poles
Maximum
Voltage Rating
15-50 1 120/240 10 3/4
—
—10
15-60 2 120/240 10 —1 1/2 5
2 3/8
TQ — — — — ——3
10
1120
10
10 —1
1
10
2120/240 10
THHQL
THHQB
...GF
15-30 1120 22 — — — — — — 3 9/32 — — — — 10
—
—
— —
———
1UL listed as HACR (heating, air conditioning and refrigeration).
2Not UL listed.
— — —— 3 9/32 2 3/8
2 3/8
—
THQL
THQC
THQB
...GF, GFEP
15-30 ——
2
CB3 Ground Fault, Equipment Ground Fault and Arc Fault (UL File E-51075; Fixed Thermal Magnetic Trip Unit)
1 101 120/240 — — — — — — — —— 3 9/32 2 3/8
22 1120/24015-20 1 — — — — — — 3 9/32 — — — — 10—— 2 3/8
—
THQB
THQC
THQL
...AF
THHQB
...AF
THHQL
15-20 ——
Quick Reference Guide
Ratings do not apply to molded case switches.
The interruption ratings and voltages shown in the table are
maximum ratings. A circuit breaker of the type given in the left-
hand column may be applied at the given circuit voltage in any
electrical distribution system where the available fault current at
the load terminals of the breaker does not exceed the value in the
table. That circuit breaker type may also be applied at intermedi-
ate values of circuit voltage provided the available fault current at
the load terminals of the breaker does not exceed the value in the
table for the higher value of voltage.
Q-Line (UL file E-11592; Fixed Thermal Magnetic Trip Unit)
THQL 32015
www.geindustrial.com BuyLog™Catalog 6-7
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
www.geindustrial.com
Industrial Circuit Breakers
Quick Reference Guide
10-1200A Circuit Breakers
Thermal Magnetic Trip
TEYD, TEYH, TEYL
TEY and TEYF (UL File E-11592; CSA LR 57114), TEYD/H/L (UL/cUL File E-11592)
Circuit
Breaker
Type
Ampere
Rating
No.
Poles
Maximum
Voltage Rating
UL Listed Interrupting Rating—kA
Approx.
Ship
Wt./Std.
Pack
Vac Vdc Dimensions (in)
ac dc 120 120/
240 240 277 480/277 480 600 125 250 500 H W D A B C E
TEY2,3 15-100
127712565
—
14 14 — —
—
10 — —
5 1/4
1
3 1/16 — — — — —
2
480/277
250
—
—10— 2
65 14 14 —
3— ———3
TEYF2,3
15-60 1 277 125 65
—
14 18 — —
—
10 — —
5 1/4
1
3 1/16 — — — — —
15-125
2
480/277
250
65 18 18 —
—10— 2
3—— ———3
TEYD
15-70 1 277 — 65 65 — 25 — — — — — —
5 1/4
1
3 1/16 — — — —
1 lb
15-125
2
480/277 — — 65 65 — 25 — — — — —
2 2 lb
3 3 2.7 lb
TEYH
15-70 1 277 — 65 65 — 35 — — — — — —
5 1/4
1
3 1/16 — — — —
1 lb
15-125
2
480/277 — — 65 65 — 35 — — — — —
2 2 lb
3 3 2.7 lb
TEYL
15-70 1 277 125 100 100 — 65 — — — 15 — —
5 1/4
1
3 1/16 — — — —
1 lb
15-125
2
480/277 250 — 100 100 — 65 — —
42 20 — 2 2 lb
3 42 35 — 3 2.7 lb
E150 (UL File E-11592; CSA LR 57114)
TEB2,3 10-1004
112012510
—
—
—— ——
5——
6 5/16
1 3/8
3 3/8 2 41/64 2 15/64
—
23/32
26 lb/24
2
240
250
—
10 — 5 — 2 3/4 24 lb/12
3 — 10 — — — 4 1/8 11/16 28 lb/8
TED2,3
10-10041 277, 3475125
——
—14 — 10 —10— —
6 5/16
1 3/8
3 3/8 2 41/64 2 15/64 —23/32
26 lb/24
2480250 18 — — 18 — — 10 — 2 3/4 24 lb/12
10-1504
3 480, 600 500 14 — — 1014 1/8 11/16 28 lb/8
THED2,3
15-30 1 277, 3475125
——
—65 — — —10
6——
6 5/16
1 3/8
3 3/8 2 41/64 2 15/64
—
23/32
26 lb/24
15-100 2480250 65
—25
—10
6—
4 1/8 11/16
24 lb/12
15-100 65 — 18 ——10
1
3600500 28 lb/8
110-150 42
1UL listed with poles in series for 500 Vdc ungrounded battery applications.
2UL listed as HACR (heating, air conditioning, and refrigeration).
315-50A UL listed as HID (high intensity discharge).
410 amp not UL listed, rated 5kA @ 120V, 240V and 480V
5UL listed/CSA Certified for 10kA @ 347 Vac (TED) and 18kA @ 347V (THED). Also rated 10kA @ 480V but not UL listed.
6UL listed 10kA, GE tested to 20kA.
Ratings do not apply to molded case switches. The interruption ratings
and voltages shown in the table are maximum ratings. A circuit breaker
of the type given in the left-hand column may be applied at the given
circuit voltage in any electrical distribution system where the available
fault current at the load terminals of the breaker does not exceed the
value in the table. That circuit breaker type may also be applied at inter-
mediate values of circuit voltage provided the available fault current at
the load terminals of the breaker does not exceed the value in the table
for the higher value of voltage.
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-8
Molded Case Circuit Breakers Section 6
www.geindustrial.com
Industrial Circuit Breakers
Quick Reference Guide
15-1200A Circuit Breakers
Thermal Magnetic Trip
Ratings do not apply to molded case switches. The interruption ratings and voltages shown in
the table are maximum ratings. A circuit breaker of the type given in the left-hand column may
be applied at the given circuit voltage in any electrical distribution system where the available
fault current at the load terminals of the breaker does not exceed the value in the table. That
circuit breaker type may also be applied at intermediate values of circuit voltage provided the
available fault current at the load terminals of the breaker does not exceed the value in the table
for the higher value of voltage.
TFJ2, 9 70-225 2 480 250
——25—22
—
—
10 — —
10 1/8 4 1/8 3 13/16 3 7/8 3 7/8 11/16 1 3/16
10 lb/1
70-250 3 600 500 18 10 101— 12 lb/1
TFK2, 9 70-225
2 480 250
——25—22
—
—
10— —
10 1/8 4 1/8 3 13/16 3 7/8 3 7/8 11/16 1 3/16
10 lb/1
3600500 18 1010
1— 12 lb/1
THFK2, 9 70-225
2 480 250
——65—25
—
—
10— —
10 1/8 4 1/8 3 13/16 3 7/8 3 7/8 11/16 1 3/16
10 lb/1
3600500 18 1010
1— 12 lb/1
TFL8, 9 70-225 3 600 — — 100 100 — 65 25 — — — — 10 1/8 4 1/8 3 13/16 3 7/8 3 7/8 11/16 1 3/16 —
J600 (UL File E-11592; TJJ, Fixed Thermal Magnetic Trip Unit; TJK, THJK: Interchangeable Thermal Mag. Trip Unit; CSA LR 40350)
TJJ,
TJK4 200-400
2
600
250
——42—3022—
20 — —
10 1/8 8 1/4 3 13/16 3 15/16 3 13/16 1 3/8 1 3/16
16 lb/1
3500 2020
1— 17 1/2 lb/1
TJK6 250-600
2
600
250
——42—3022—
20 — —
10 1/8 8 1/4 3 13/16 3 15/16 3 13/16 1 3/8 1 3/16
18 lb/1
3 500 20 201— 20 lb/1
THJK4 200-400
2
600
250
——65—3525—
40 — —
10 1/8 8 1/4 3 13/16 3 15/16 3 13/16 1 3/8 1 3/16
16 lb/1
3500 4020
1— 17 1/2 lb/1
THJK6 250-600
2
600
250
——65—3525—
40 —
— 10 1/8 8 1/4 3 13/16 3 15/16 3 13/16 1 3/8 1 3/16
18 lb/1
3500 4020
120 lb/1
THJK4 D9125-400 3 — 600 — — — — — — — 40 50 25 10 1/8 8 1/4 3 13/16 3 15/16 3 13/16 1 3/8 1 3/16 17 1/2 lb/1
THJK6 D9250-400 3 — 600 — — — — — — — 40 50 25 10 1/8 8 1/4 3 13/16 3 15/16 3 13/16 1 3/8 1 3/16 20 lb/1
K1200 (UL File E-11592; Interchangeable Thermal Magnetic Trip Unit; CSA LR 40350)
TKM89300-800
2
600
250
——42—3022—
20 — —
15 1/2 8 1/4 5 1/2 8 9/16 5 11/16 1 3/8 5/8
33 lb/1
3500 2022
1— 39 lb/1
TKM129600-1200
2
600 — — — 42 — 30 22 — — — — 15 1/2 8 1/4 5 1/2 8 9/16 5 11/16 1 3/8 5/8
38 lb/1
3 41 1/2 lb/1
THKM89300-800
2
600
250
——65—3525—
40 — —
15 1/2 8 1/4 5 1/2 8 9/16 5 11/16 1 3/8 5/8
33 lb/1
3500 4022
1— 39 lb/1
THKM129600-1200
2
600 — — — 65 — 35 25 — — — — 15 1/2 8 1/4 5 1/2 8 9/16 5 11/16 1 3/8 5/8
38 lb/1
3 41 1/2 lb/1
F225 (UL File E-11592; TFJ, Fixed Thermal Magnetic Trip Unit; TFK, THFK: Interchangeable Thermal Mag. Trip Unit; CSA LR 40350)
Circuit
Breaker
Type
Ampere
Rating
No.
Poles
Maximum
Voltage
Rating
UL Listed Interrupting Rating—kA
Approx.
Ship
Wt./Std.
Pack
Vac Vdc Dimensions (in)
acdc120
120/
240 240 277 480 600 125 250 500 600 H W D A B C E
1UL listed with poles in series for 500 Vdc ungrounded battery applications.
2UL listed as HACR (heating, air conditioning, and refrigeration).
315-50A UL listed as HID (high intensity discharge).
410 amp not UL listed, rated 5kA @ 120V, 240V and 480V
5UL listed/CSA Certified for 10kA @ 347 Vac (TED) and 18kA @ 347V (THED). Also rated 10kA @ 480V but not UL listed.
6480Y/277 Vac.
7UL listed 10kA, GE tested to 20kA.
8Not CSA listed
9Obsolete as of 12/13.
TJJ, TJK, THJK
www.geindustrial.com BuyLog™Catalog 6-9
Rev. 11/13
Data subject to change
without notice
Molded Case Circuit Breakers Section 6
Industrial Circuit Breakers
TF and TK Cross Reference Table
Transition guide – Obsoleted TF and TK Molded Case Circuit Breakers, switches and Motor Circuit Protectors to Spectra RMS equivalents.
Spectra RMS products are not DC rated. For DC applications, continue use of TJ frame Molded Case Circuit Breakers.
Molded Case Circuit Breakers
Obsoleted Frame Rating Plug Lugs
Frame Product Product Product Product
F225 AIC Rating Trip Unit Poles Voltage Number Spectra AIC Poles Voltage Number Number Number
TFJ 22kA 225A noninterchangeable 2 480V TFJ224XXX SFH 35kA 2 480V SFHA24AT0250 SRPF250AXXX (2) TCAL29
22kA 225A noninterchangeable 3 600V TFJ236XXX SFH 35kA 3 600V SFHA36AT0250 SRPF250AXXX (3) TCAL29
TFK 22kA 225A interchangable 2 480V TFK224XXX SFH 35kA 2 480V SFHA24AT0250 SRPF250AXXX (2) TCAL29
22kA 225A interchangable 3 600V TFK236XXX SFH 35kA 3 600V SFHA36AT0250 SRPF250AXXX (3) TCAL29
THFK 25kA 225A interchangable 2 480V THFK224XXX SFH 35kA 2 480V SFHA24AT0250 SRPF250AXXX (2) TCAL29
25kA 225A interchangable 3 600V THFK236XXX SFH 35kA 3 600V SFHA36AT0250 SRPF250AXXX (3) TCAL29
Molded Case Circuit Breakers
Obsoleted Frame Rating Plug Lugs
Frame Product Product Product Product
K1200 AIC Rating Trip Unit Poles Voltage Number Spectra AIC Poles Voltage Number Number Number
TKMA 30kA 800A interchangeable 2 600V TKMA826XXX SKHA 50kA 2 600V SKHA26AT0800 SRPK800AXXX (2) TCAL81
30kA 800A interchangeable 3 600V TKMA836XXX SKHA 50kA 3 600V SKHA36AT0800 SRPK800AXXX (3) TCAL81
THKMA 35kA 800A interchangeable 2 600V THKMA826XXX SKHA 50kA 2 600V SKHA26AT0800 SRPK800AXXX (2) TCAL81
35kA 800A interchangeable 3 600V THKMA836XXX SKHA 50kA 3 600V SKHA36AT0800 SRPK800AXXX (3) TCAL81
TKMA 30kA 1200A interchangeable 2 600V TKMA2XXXX SKHA 50kA 2 600V SKHA26AT1200 SRPK1200AXXX (2) TCAL125
30kA 1200A interchangeable 3 600V TKMA3XXXX SKHA 50kA 3 600V SKHA36AT1200 SRPK1200AXXX (3) TCAL125
THKMA 35kA 1200A interchangeable 2 600V THKMA2XXXX SKHA 50kA 2 600V SKHA26AT1200 SRPK1200AXXX (2) TCAL125
35kA 1200A interchangeable 3 600V THKMA3XXXX SKHA 50kA 3 600V SKHA36AT1200 SRPK1200AXXX (3) TCAL125
Molded Case Switches
Obsoleted Rating Plug Lugs
Frame Product Product Product Product
Type AIC Rating Trip Unit Poles Voltage Number Spectra AIC Poles Amps Number Number Number
TFK N/A 225A N/A 2 600V TFK226Y225 SF250 N/A 3 250A SFDA36AN0250 N/A (3) TCAL29
TFK N/A 225A N/A 3 600V TFK236Y225 SF250 N/A 3 250A SFDA36AN0250 N/A (3) TCAL29
TKM N/A 800A N/A 2 600V TKMA826Y800 SK1200 N/A 3 800A SKDA36AN0800 N/A (3) TCAL81
TKM N/A 800A N/A 3 600V TKMA836Y800 SK1201 N/A 3 800A SKDA36AN0800 N/A (3) TCAL81
TKM N/A 1000A N/A 2 600V TKMA2Y1000 SK1202 N/A 3 1000A SKDA36AN1000 N/A (3) TCAL125
TKM N/A 1000A N/A 3 600V TKMA3Y1000 SK1203 N/A 3 1000A SKDA36AN1000 N/A (3) TCAL125
TKM N/A 1200A N/A 2 600V TKMA2Y1200 SK1204 N/A 3 1200A SKDA36AN1200 N/A (3) TCAL125
TKM N/A 1200A N/A 3 600V TKMA3Y1200 SK1205 N/A 3 1200A SKDA36AN1200 N/A (3) TCAL125
Motor Circuit Protectors
Obsoleted Rating Plug Lugs
Frame Inst Trip Product Product Product Product
Type AIC Rating Amp Rating Poles Voltage Number Spectra AIC Poles Amps Number Number Number
TF 30kA 225A 600 - 1400 3 N/A TFC36225 SFLA 65kA 3 250A SFLA36AI0250 SRPF250AXXX (3) TCAL29
TF 30kA 225A 100 - 2250 3 N/A TFC36225A SFPA 100kA 3 250A SFPA36AI0250 SRPF250AXXX (3) TCAL29
TK 30kA 800A 3000 - 6000 3 N/A TKC36800L SKLA 65kA 3 800A SKLA36AI0800 SRPK800AXXX (3) TCAL81
TK 30kA 800A 5000 - 10000 3 N/A TKC36800M SKLA 65kA 3 800A SKLA36AI0800 SRPK800AXXX (3) TCAL81
TK 30kA 1200A 3000 - 6000 3 N/A TKC361200L SKLA 65kA 3 1200A SKLA36AI1200 SRPK1200AXXX (3) TCAL125
TK 30kA 1200A 5000 - 10000 3 N/A TKC361200M SKLA 65kA 3 1200A SKLA36AI1200 SRPK1200AXXX (3) TCAL125
Legend
XXX = Variable in Product Number changes per application
Spectra RMS Accessories
Description Product Number
Shunt Trip SASTX
Auxiliary Switch SAUXPABX
UV Release SAUVX
Bell Alarm SABAP1
Actuator SACTUATOR
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-10
Molded Case Circuit Breakers Section 6
Spectra™RMS Circuit Breakers UL/CSA Ratings
Industrial Circuit Breakers
Quick Reference Guide
15-1200A Circuit Breakers
Electronic Trip
Ratings do not apply to molded case switches. The interruption ratings and voltages shown in
the table are maximum ratings. A circuit breaker of the type given in the left-hand column may
be applied at the given circuit voltage in any electrical distribution system where the available
fault current at the load terminals of the breaker does not exceed the value in the table. That
circuit breaker type may also be applied at intermediate values of circuit voltage provided the
available fault current at the load terminals of the breaker does not exceed the value in the table
for the higher value of voltage. SE 150
Solid-State with Interchangeable Trip Unit (Rating Plug)
Circuit
Breaker
Type
Ampere
Rating
No.
Poles
Maximum
Vac
UL Listed Interrupting Rating—kA Dimensions Inches (mm) Approx.
Ship Wt./
Std. Pack
240 Vac 480 Vac 600 Vac H W D A B C E
SE150 Current Limiting (UL File No. E-11592; CSA LR 40350)1
SED2,3
15-150
2480
18 18 —
6.31
(160)
4.12
(105)
3.38
(86)
2.41
(61)
2.47
(63)
.69
(18)
.72
(18) 5.65 lb/1
3600 14
SEH22 480 65 25 —
3600 18
SEL
15-150
2480
100 65 —
3600 25
SEP 2 480 200 100 —
3 600 25
SF-250 Current Limiting (UL File No. E-11592; CSA LR 40350)1
SFH270-250 2480
6535 —
10.12
(257)
4.12
(105)
3.81
(97)
3.87
(98)
3.87
(98)
.69
(18)
1.19
(30) 9.15 lb/1
3600 22
SFL
70-250
2480
100 65 —
3600 25
SFP 2480
200 100 —
3 600 25
SG600 Current Limiting (UL File No. E-11592; CSA LR 40350)1,4
SGH12,5 6-150 3 600 65 35 25
10.096
(256)
5.50
(140)
3.81
(97)
4.45
(113)
3.30
(84)
.91
(23)
1.186
(30) 15.85 lb/1
SGD2
125-400
2240 65 — —
3
SGH422600 65 35 25
3
SGH62250-600 2600 65 35 25
3
SGL15
60-150 36001006565
SGP15360020010065
SGL4
125-400
2600 100 65 65
3
SGP4 2600 200 100 65
3
SGL6
250-600
2600 100 65 65
3
SGP6 2600 200 100 65
3
SK1200 (UL File No. E-11592; CSA LR 40350)1,4
SKH8
300-800
2600 65 50 25
15.507
(394)
8.25
(210)
5.50
(140)
8.56
(217)
5.69
(145)
1.38
(35)
.627
(16) 47.6 lb/1
3
SKL8 2600 100 65 42
3
SKP8 2600 200 100 65
3
SKH12
600-1200
2600 65 50 25
3
SKL12 2600 100 65 42
3
SKP12 2600 200 100 65
3
SKS8 800-1200 3480 200 100 —
SKT8 3 100 65
SKS12 800-1200 3480 200 100 —
SKT12 3 100 65
1
5microEntelliGuard™, MicroVersaTrip™Plus and MicroVersaTrip™PM Trip Units only.
6Add 1.76 inches (45 mm) to each end with lugs and lug cover installed.
7Add 4.00 inches (101 mm) to upper end for SKP (100 kAIC-480V) lug cover.
1UL listed as HACR (heating, air conditioning and refrigeration).
2Not current-limiting circuit breaker.
3UL listed as HID (high intensity discharge).
4Includes microEntelliGuard™ Trip Units.
www.geindustrial.com BuyLog™Catalog 6-11
Rev. 11/13
Data subject to change
without notice
Molded Case Circuit Breakers Section 6
Industrial Circuit Breakers
Quick Reference Guide
15-1200A Circuit Breakers
Electronic Trip
Ratings do not apply to molded case switches
IEC/JIS Ratings
Icu Ics Icu Ics Icu Ics Icu Ics 220-240 380-415 500 690
2—
3444
2—
3666
2—
3 8 8 3 383
2—
—
—
310 10 5 5 10 5
2—
3 14 7 14
2—
3 25 12 18
2—
3 40 20 555 25
2—
—
—
3550 25 10 65 10
2—
3 25 12 18
2——
3740 20 14 25 14
2——
3 965 33 18 65 18
2
3
2
3
2
3
2
3
2
3
2
3
Vac
SE150 Current Limiting, 15-32A
Solid-State with Interchangeable Trip Unit (Rating Plug)
Circuit
Breaker
Type
Ampere
Rating
No.
Poles
IEC 947-2 Interruption Capacity — kA
220-240 Vac 380-415 Vac 500 Vac 690 Vac
Japanese Industry Standard
Interruption Capacity kA
SED
SEH
5
10
9
15-32
15-32
10
65 33 15
18
100
20
SEL
SEP 100
40-160
SED
SEH
SEL
SEP
40-160
20
20
100 50
17353365
18
18
65
100
200
10 —
15 —
20
20
14
SE150 Current Limiting, 40-160A
9 14 7
50 15
200
18
65 25
—
—
100
200
65
100
SF250 Current Limiting
100200
65 33
50100
SFH
SFL
SFP
70-250
70-250
65 33 35 17
100 50 65 33
200 100 100 50
65 25
100 65
200 100
—
SG600 Current Limiting
SK1200
SKH8 65 50 25 65
SKL8
SKP8
SKH12
300-800 100
140
16
25
35
65
85
13
16
25
42
50
13
21
25
14
18
14
18
100
140
50
65
85
—
14
18
SKL12
SKP12
600-1250
65
100
140
16
25
35
50
65
70
13
21
25
25
42
50
13
16
25
—
14
18
—
——
——
——
——
——
——
——— —
—— ——
——— —
—— ——
—— ——
——— —
— —
— —
——
——
— —
14
18
65
100
140
—
14
18
1microEntelliGuard™, MicroVersaTrip™ Plus, and MicroVersaTrip™ PM Trip Units only.
50
65
85
25
42
50
25
42
50
SGH11 65 33 25 13 18 9 — — 65 25 18 —
SGL11 60-150 3 100 50 65 33 35 18 14 7 100 65 35 22
SGP11 200 100 100 50 50 25 18 9 200 100 65 35
SGH4 2 65 33 25 13 — —
— — 65 25 — —
3 18 9 18 —
SGL4 125-400 2 100 50 65 33 — — — — 100 65 — —
3 35 18 14 7 35 22
SGP4 2 200 100 100 50 — — — — 200 100 — —
3 50 25 18 9 65 35
SGH6 2 65 33 25 13 — —
— — 65 25 — —
3 18 9 18 —
SGL6 250-600 2 100 50 65 33 — — — — 100 65 — —
3 35 18 14 7 35 22
SGP6 2 200 100 100 50 — — — — 200 100 — —
3 50 25 18 9 65 35
SE
SF
SG
SK
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-12
Molded Case Circuit Breakers Section 6
Industrial Circuit Breakers
Quick Reference Guide
Ratings do not apply to molded case switches. The interruption
ratings and voltages shown in the table are maximum ratings. A
circuit breaker of the type given in the left-hand column may be
applied at the given circuit voltage in any electrical distribution
system where the available fault current at the load terminals of
the breaker does not exceed the value in the table. That circuit
breaker type may also be applied at intermediate values of circuit
voltage provided the available fault current at the load terminals
of the breaker does not exceed the value in the table for the
higher value of voltage.
10 lb/1
12 lb/1
31 lb/1
33 lb/1
16 lb/1
17 1/2/1
53 lb/1
55 lb/1
38 lb/1
41 1/2/1
53 lb/1
55 lb/1
TJ4V2,3,4 42 42 30 22
THJ4V2,3,4 65 65 35 25
TJL4V2100 100 65 30
TK4V2,4 800-1200 3 600 — — 42 42 —30 22 15 1/2 8 1/4 5 1/2 8 9/16 5 11/16 1 3/8 5/8 —
TKL4V2,4 800-1200 3 600 — — 100 100 —65 42 15 1/2 8 1/4 5 1/2 8 9/16 5 11/16 1 3/8 5/8 —
TJH1S-6S 60-600 3 600 — — 65 65 —35 25 16 1/8 8 1/4 3 13/16 3 15/16 9 13/16 1 3/8 1 3/16 —
TJL1S-6S 60-600 3 600 — — 100 100 —65 30 16 1/8 8 1/4 3 13/16 3 15/16 9 13/16 1 3/8 1 3/16 —
TKH8S4, 12S4300-1200 3 600 — — 65 65 —50 25 21 7/8 8 1/4 5 1/2 8 9/16 12 11/16 1 3/8 5/8 —
TKL8S4, 12S4300-1200 3 600 — — 100 100 —65 42 21 7/8 8 1/4 5 1/2 8 9/16 12 11/16 1 3/8 5/8 —
6003— 1 3/8 1 3/168 1/4 3 13/16 3 15/16 3 13/16
5/8
150-600 — — —10 1/8
5 7/8 8 9/16 12 1/16 1 3/821 7/8 8 1/4100 — 100 100
15 1/2800-1200TKC
TBC8 800 3 600 — — —
8 1/4 5 1/2 8 9/16 5/81 3/85 11/163042 223 600 — —
3600600TBC6 — — —100100100 —
——
5/821 7/8 8 1/4 5 7/8 8 9/16 12 1/16 1 3/8
1 3/163042600 — — 3 13/16 3 13/16 3 13/16 1 3/810 1/8 8 1/4
TBC45
223
3
400-600TJC
600225-400 — 100 100100
TFC5
1 3/161 3/89 13/163 15/164 1/28 1/416 1/8
—
—
3600225 — 22 1825 3 7/83 13/164 1/810 1/8 1 3/1611/163 7/8
Mag-Break (UL Files E-11592, E-66390; Magnetic Trip Unit)1
——
—
—
—
—
——
——
——
——
——
——
——
——
——
——
——
——
——
1Per UL 489, interrupting capacities are not shown on product label.
Contact GE Sales Office for availability of 200 kAIC ratings with internal accessories.
4Obsolete as of 12/13.
3Suitable for single-phase, use outer two poles.
2With Power+ 4 trip unit.
TJC TJL6S
Molded Case Circuit Breakers Section 6
www.geindustrial.com BuyLog™Catalog 6-13
Rev. 11/13
Data subject to change
without notice
Ratings
FC 100 Amp Frame; Current Limiting (UL/cUL File No. E-11592)
Maximum UL Listed Interrupting Ratings - IEC Listed Interrupting Ratings, Approx.
Circuit Voltage rms Symmetrical Amperes (in Thousands) Icu, Amperes (in Thousands) Ship
Breaker Ampere No. Rating Vac Vdc Vac Vdc Dimensions in. (mm.) Wt./Std.
Type Rating Poles AC DC 240 480 600/347 250 (2p) 500 (3p) 220-240 400-415 500 250 (2p) 500 (3p) HWDPack
FCS 15-100 2, 3 600 500 42 25 18 22 30 36 22 14 22 30 6.4 (162.6) 3.0 (76.2) 3.2 (81.3) 2.5 lb/1
FCV 15-100 2, 3 600 500 65 35 22 25 35 50 30 18 25 35 6.4 (162.6) 3.0 (76.2) 3.2 (81.3) 2.5 lb/1
FCN 15-100 2, 3 600 500 150 65 25 30 42 85 50 22 30 42 6.4 (162.6) 3.0 (76.2) 3.2 (81.3) 2.5 lb/1
FCH 15-100 2, 3 600 500 200 100 35 42 65 100 80 36 42 65 6.4 (162.6) 3.0 (76.2) 3.2 (81.3) 2.5 lb/1
FCL 15-100 2, 3 600 500 200 150 42 65 80 200 150 50 65 80 6.4 (162.6) 3.0 (76.2) 3.2 (81.3) 2.5 lb/1
FB 100 Amp Frame; Current Limiting (UL/cUL File No. E-11592)
Maximum UL Listed Interrupting Ratings - Approx.
Circuit Voltage rms Symmetrical Amperes (in Thousands) Ship
Breaker Ampere No. Rating Vac Dimensions in. (mm.) Wt./Std.
Type Rating Poles AC DC 240 277 347 480 600/347 HWDPack
1 600/347 — 35 35 22 ——6.45 (163.8) 1.36 (34.5) 3.28 (83.3) 1.1 lb/1
FBV 15-100 2 600/347 — 65 ——35 22 6.45 (163.8) 2.74 (69.6) 3.28 (83.3) 2.6 lb/1
3 600/347 — 65 ——35 22 6.45 (163.8) 4.11 (104.4) 3.28 (83.3) 3.3 lb/1
1 600/347 — 65 65 25 ——6.45 (163.8) 1.36 (34.5) 3.28 (83.3) 1.1 lb/1
FBN 15-100 2 600/347 — 150 ——65 25 6.45 (163.8) 2.74 (69.6) 3.28 (83.3) 2.6 lb/1
3 600/347 — 150 ——65 25 6.45 (163.8) 4.11 (104.4) 3.28 (83.3) 3.3 lb/1
1 600/347 — 100 100 35 ——6.45 (163.8) 1.36 (34.5) 3.28 (83.3) 1.1 lb/1
FBH 15-100 2 600/347 — 200 ——100 35 6.45 (163.8) 2.74 (69.6) 3.28 (83.3) 2.6 lb/1
3 600/347 — 200 ——100 35 6.45 (163.8) 4.11 (104.4) 3.28 (83.3) 3.3 lb/1
1 600/347 — 100 100 42 ——6.45 (163.8) 1.36 (34.5) 3.28 (83.3) 1.1 lb/1
FBL 15-100 2 600/347 — 200 ——150 42 6.45 (163.8) 2.74 (69.6) 3.28 (83.3) 2.6 lb/1
3 600/347 — 200 ——150 42 6.45 (163.8) 4.11 (104.4) 3.28 (83.3) 3.3 lb/1
FE 250 Amp Frame; Current Limiting (UL/cUL File No. E-11592)
Maximum UL Listed Interrupting Ratings - Approx.
Circuit Voltage rms Symmetrical Amperes (in Thousands) Ship
Breaker Ampere No. Rating Vac Dimensions in. (mm.) Wt./Std.
Type Rating Poles AC DC 240 480 600 HWDPack
FEN 250 2 480 - 150 65 - 6.70 (170.1) 4.11 (104.4) 3.52 (89.5) 4.5 lb/1
FEN 250 3 480 - 150 65 - 6.70 (170.1) 4.11 (104.4) 3.52 (89.5) 4.5 lb/1
FEH 250 2 480 - 200 100 - 6.70 (170.1) 4.11 (104.4) 3.52 (89.5) 4.5 lb/1
FEH 250 3 480 - 200 100 - 6.70 (170.1) 4.11 (104.4) 3.52 (89.5) 4.5 lb/1
FG 600 Amp Frame; Current Limiting (UL/cUL File No. E-11592)
Maximum UL Listed Interrupting Ratings - EN 60947-2 Interrupting Ratings, Approx.
Circuit Voltage rms Symmetrical Amperes (in Thousands) Icu, Amperes (in Thousands) Ship
Breaker Ampere No. Rating Vac Vac Dimensions in. (mm.) Wt./Std.
Type Rating Poles AC DC 240 480 600 240 400-415 690 HWDPack
FGN 250-600 2 600 — 150 65 25 ———10.31 (262.0) 5.46 (138.7) 4.53 (115.0) 22 lb/1
3 600 — 150 65 25 85 50 10 10.31 (262.0) 5.46 (138.7) 4.53 (115.0) 22 lb/1
FGH 250-600 2 600 — 200 100 35 ———10.31 (262.0) 5.46 (138.7) 4.53 (115.0) 22 lb/1
3 600 — 200 100 35 100 80 22 10.31 (262.0) 5.46 (138.7) 4.53 (115.0) 22 lb/1
FGL 250-600 2 600 — 200 150 42 ———10.31 (262.0) 5.46 (138.7) 4.53 (115.0) 22 lb/1
3 600 — 200 150 42 200 150 40 10.31 (262.0) 5.46 (138.7) 4.53 (115.0) 22 lb/1
FGP 250-600 2 600 — 200 200 65 ———10.31 (262.0) 5.46 (138.7) 4.53 (115.0) 22 lb/1
3 600 — 200 200 65 ———10.31 (262.0) 5.46 (138.7) 4.53 (115.0) 22 lb/1
FG 600
Industrial Circuit Breakers
Quick Reference Guide
15-600A Record Plus™Circuit Breakers
The interruption ratings and voltages shown in the table are maximum ratings. A circuit breaker
of the type given in the left-hand column may be applied at the given circuit voltage in any
electrical distribution system where the available fault current at the load terminals of the
breaker does not exceed the value in the table. That circuit breaker type may also be applied at
intermediate values of circuit voltage provided the available fault current at the load terminals of
the breaker does not exceed the value in the table for the higher value of voltage.
www.geindustrial.com
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-14
Molded Case Circuit Breakers Section 6
TQL and THQL 120/240 Vac
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 1045kA TQL1110
1 152(1) 14-8 Cu/12-8 Al 10kA THQL1115
1 202(1) 14-8 Cu/12-8 Al 10kA THQL1120
1 25 (1) 14-8 Cu/12-8 Al 10kA THQL1125
1 30 (1) 14-8 Cu/12-8 Al 10kA THQL1130
1 35 (1) 8-3 Cu/8-3 Al 10kA THQL1135
1 40 (1) 8-3 Cu/8-3 Al 10kA THQL1140
1 45 (1) 8-3 Cu/8-3 Al 10kA THQL1145
1 50 (1) 8-3 Cu/8-3 Al 10kA THQL1150
1 60 (1) 8-3 Cu/8-3 Al 10kA THQL1160
1 70 (1) 6-1/0 Cu/4-1/0 Al 10kA THQL1170
THQL 120/240 Vac, with Factory Installed Shunt
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 (1) 14-8 Cu/12-8 Al 10kA THQL1115ST1
1 20 (1) 14-8 Cu/12-8 Al 10kA THQL1120ST1
1 30 (1) 14-8 Cu/12-8 Al 10kA THQL1130ST1
1 35 (1) 8-3 Cu/8-3 Al 10kA THQL1135ST1
1 40 (1) 8-3 Cu/8-3 Al 10kA THQL1140ST1
1 45 (1) 8-3 Cu/8-3 Al 10kA THQL1145ST1
1 50 (1) 8-3 Cu/8-3 Al 10kA THQL1150ST1
TQL and THQL 120/240 Vac, Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 1045kA TQL2110
2 15 (1) 14-8 Cu/12-8 Al 10kA THQL2115
2 20 (1) 14-8 Cu/12-8 Al 10kA THQL2120
2 25 (1) 14-8 Cu/12-8 Al 10kA THQL2125
2 30 (1) 14-8 Cu/12-8 Al 10kA THQL2130
2 35 (1) 8-3 Cu/8-3 Al 10kA THQL2135
2 40 (1) 8-3 Cu/8-3 Al 10kA THQL2140
2 45 (1) 8-3 Cu/8-3 Al 10kA THQL2145
2 50 (1) 8-3 Cu/8-3 Al 10kA THQL2150
2 60 (1) 8-3 Cu/8-3 Al 10kA THQL2160
2 70 (1) 6-1/0 Cu/4-1/0 Al 10kA THQL2170
2 80 (1) 6-1/0 Cu/4-1/0 Al 10kA THQL2180
2 90 (1) 6-1/0 Cu/4-1/0 Al 10kA THQL2190
2 100 (1) 6-1/0 Cu/4-1/0 Al 10kA THQL21100
2 110 (1) 2-2/0 Cu/2-2/0 Al 10kA THQL21110
2 125 (1) 2-2/0 Cu/2-2/0 Al 10kA THQL211253
THQP 120/240 Vac
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 10kA THQP115
1 20 14-8 Cu/12-8 Al 10kA THQP120
1 25 14-8 Cu/12-8 Al 10kA THQP125
1 30 8-4 Cu/8-4 Al 10kA THQP130
1 35 8-4 Cu/8-4 Al 10kA THQP135
1 40 8-4 Cu/8-4 Al 10kA THQP140
1 45 8-4 Cu/8-4 Al 10kA THQP145
1 50 8-4 Cu/8-4 Al 10kA THQP150
THQP 120/240 Vac, Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 10kA THQP215
2 20 14-8 Cu/12-8 Al 10kA THQP220
2 25 14-8 Cu/12-8 Al 10kA THQP225
2 30 8-4 Cu/8-4 Al 10kA THQP230
2 35 8-4 Cu/8-4 Al 10kA THQP235
2 40 8-4 Cu/8-4 Al 10kA THQP240
2 45 8-4 Cu/8-4 Al 10kA THQP245
2 50 8-4 Cu/8-4 Al 10kA THQP250
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (Switching Duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
3Recommended for use as main or submain breaker only.
4Not UL listed.
UL listed as HACR (heating, air conditioning and refrigeration).
Q-Line Circuit Breakers
Plug-in Circuit Breakers
120/240V Class
THQL1120
THQP130
THQP230
THQL1130ST1
www.geindustrial.com BuyLog™Catalog 6-15
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
TQL and THQL 240 Vac, Internal Common Trip
# of Ampere 240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 10 5kA TQL22010
2 15 14-8 Cu/12-8 Al 10kA THQL22015
2 20 14-8 Cu/12-8 Al 10kA THQL22020
2 25 14-8 Cu/12-8 Al 10kA THQL22025
2 30 14-8 Cu/12-8 Al 10kA THQL22030
2 35 8-3 Cu/8-3 Al 10kA THQL22035
2 40 8-3 Cu/8-3 Al 10kA THQL22040
2 45 8-3 Cu/8-3 Al 10kA THQL22045
2 50 8-3 Cu/8-3 Al 10kA THQL22050
2 60 8-3 Cu/8-3 Al 10kA THQL22060
2 70 6-1/0 Cu/4-1/0 Al 10kA THQL22070
2 80 6-1/0 Cu/4-1/0 Al 10kA THQL22080
2 90 6-1/0 Cu/4-1/0 Al 10kA THQL22090
2 100 6-1/0 Cu/4-1/0 Al 10kA THQL22100
3 10 5kA TQL32010
3 15 14-8 Cu/12-8 Al 10kA THQL32015
3 20 14-8 Cu/12-8 Al 10kA THQL32020
3 25 14-8 Cu/12-8 Al 10kA THQL32025
3 30 14-8 Cu/12-8 Al 10kA THQL32030
3 35 8-3 Cu/8-3 Al 10kA THQL32035
3 40 8-3 Cu/8-3 Al 10kA THQL32040
3 45 8-3 Cu/8-3 Al 10kA THQL32045
3 50 8-3 Cu/8-3 Al 10kA THQL32050
3 60 8-3 Cu/8-3 Al 10kA THQL32060
3 70 6-1/0 Cu/4-1/0 Al 10kA THQL32070
3 80 6-1/0 Cu/4-1/0 Al 10kA THQL32080
3 90 6-1/0 Cu/4-1/0 Al 10kA THQL32090
3 100 6-1/0 Cu/4-1/0 Al 10kA THQL32100
15-100 ampere UL Listed as HACR (heating, air conditioning and refrigeration).
THQL 120/240 Vac, Internal Common Trip with Factory Installed Shunt
# of Ampere 240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 10kA THQL2115ST1
2 20 14-8 Cu/12-8 Al 10kA THQL2120ST1
2 30 14-8 Cu/12-8 Al 10kA THQL2130ST1
2 35 8-3 Cu/8-3 Al 10kA THQL2135ST1
2 40 8-3 Cu/8-3 Al 10kA THQL2140ST1
2 45 8-3 Cu/8-3 Al 10kA THQL2145ST1
2 50 8-3 Cu/8-3 Al 10kA THQL2150ST1
2 60 8-3 Cu/8-3 Al 10kA THQL2160ST1
2 70 6-1/0 Cu/4-1/0 Al 10kA THQL2170ST1
2 80 6-1/0 Cu/4-1/0 Al 10kA THQL2180ST1
2 90 6-1/0 Cu/4-1/0 Al 10kA THQL2190ST1
2 100 6-1/0 Cu/4-1/0 Al 10kA THQL21100ST1
3 20 14-8 Cu/12-8 Al 10kA THQL32020ST1
3 30 14-8 Cu/12-8 Al 10kA THQL32030ST1
3 40 8-3 Cu/8-3 Al 10kA THQL32040ST1
3 50 8-3 Cu/8-3 Al 10kA THQL32050ST1
3 60 8-3 Cu/8-3 Al 10kA THQL32060ST1
3 70 6-1/0 Cu/4-1/0 Al 10kA THQL32070ST1
3 80 6-1/0 Cu/4-1/0 Al 10kA THQL32080ST1
3 90 6-1/0 Cu/4-1/0 Al 10kA THQL32090ST1
3 100 6-1/0 Cu/4-1/0 Al 10kA THQL32100ST1
THQL and THHQL Vac Arc Fault
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-10 Cu/14-10 Al 10kA THQL1115AF22
1 20 14-10 Cu/14-10 Al 10kA THQL1120AF22
1 15 14-10 Cu/14-10 Al 22kA THHQL1115AF22
1 20 14-10 Cu/14-10 Al 22kA THHQL1120AF22
Dual Function GFCI/AFCI Ground Fault & Combination Arc Fault Circuit Breaker
(Available December 2014)
# of Ampere 120 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 10kA THQL1115DF
1 20 14-8 Cu/12-8 Al 10kA THQL1120DF
1 15 14-8 Cu/12-8 Al 22kA THHQL1115DF
1 20 14-8 Cu/12-8 Al 22kA THHQL1120DF
1Solid or stranded for 14-10 AWG.
2Combination AFCI compliant with NEC 2008 and later.
Q-Line Circuit Breakers
Plug-in Circuit Breakers
120/240V Class
THQL32015
THQL1115AF2
THQL2120ST1
THQL32020ST1
Page Updated 10 / 2014
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-16
Molded Case Circuit Breakers Section 6
THQL and THHQL 120 Vac, Ground Fault Circuit Interrupters
# of Ampere 120 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 10kA THQL1115GF
1 20 14-8 Cu/12-8 Al 10kA THQL1120GF
1 30 14-8 Cu/12-8 Al 10kA THQL1130GF
1 15 14-8 Cu/12-8 Al 22kA THHQL1115GF
1 20 14-8 Cu/12-8 Al 22kA THHQL1120GF
1 30 14-8 Cu/12-8 Al 22kA THHQL1130GF
THQL and THHQL 120/240 Vac or 208Y/120 Vac,
Ground Fault Circuit Interrupters Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 10kA THQL2115GF1
2 20 14-8 Cu/12-8 Al 10kA THQL2120GF1
2 30 14-8 Cu/12-8 Al 10kA THQL2130GF1
2 40 8-3 Cu/8-3 Al 10kA THQL2140GF1
2 50 8-3 Cu/8-3 Al 10kA THQL2150GF1
THQL and THHQL 120 Vac, Equipment Protection Ground Fault Circuit
Breakers Internal Common Trip
# of Ampere 120 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 10kA THQL1115GFEP
1 20 14-8 Cu/12-8 Al 10kA THQL1120GFEP
1 30 14-8 Cu/12-8 Al 10kA THQL1130GFEP
THQL and THHQL 120/240 Vac or 208Y/120 Vac, Equipment Protection
Ground Fault Circuit Breakers
# of Ampere 120/240 Vac or 208Y/120
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 10kA THQL2115GFEP
2 20 14-8 Cu/12-8 Al 10kA THQL2120GFEP
2 30 14-8 Cu/12-8 Al 10kA THQL2130GFEP
THQL and THHQL 120/240 Vac, High Intensity Discharge Lighting Loads
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 10kA THQL1115HID2
1 20 14-8 Cu/12-8 Al 10kA THQL1120HID2
1 25 14-8 Cu/12-8 Al 10kA THQL1125HID
1 30 14-8 Cu/12-8 Al 10kA THQL1130HID
1 15 14-8 Cu/12-8 Al 22kA THHQL1115HID2
1 20 14-8 Cu/12-8 Al 22kA THHQL1120HID2
1 25 14-8 Cu/12-8 Al 22kA THHQL1125HID
1 30 14-8 Cu/12-8 Al 22kA THHQL1130HID
UL listed as HID.
THQL and THHQL 120/240 Vac, Internal Common Trip For High Intensity
Discharge Lighting Loads
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 10kA THQL2115HID
2 20 14-8 Cu/12-8 Al 10kA THQL2120HID
2 25 14-8 Cu/12-8 Al 10kA THQL2125HID
2 30 14-8 Cu/12-8 Al 10kA THQL2130HID
2 15 14-8 Cu/12-8 Al 22kA THHQL2115HID
2 20 14-8 Cu/12-8 Al 22kA THHQL2120HID
2 25 14-8 Cu/12-8 Al 22kA THHQL2125HID
2 30 14-8 Cu/12-8 Al 22kA THHQL2130HID
UL listed as HID.
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (switching duty). Suitable for 120 Vac fluorescent lighting loads.
Q-Line Circuit Breakers
Plug-in Circuit Breakers
240V Class
THQL1120GF
THQL2120HID
www.geindustrial.com BuyLog™Catalog 6-17
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
THLK2125
THQL 120/240 Vac, High In-Rush Loads
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 10kA THQL1115HM
1 20 14-8 Cu/12-8 Al 10kA THQL1120HM
1 25 14-8 Cu/12-8 Al 10kA THQL1125HM
1 30 14-8 Cu/12-8 Al 10kA THQL1130HM
1 40 8-3 Cu/8-3 Al 10kA THQL1140HM
1 50 8-3 Cu/8-3 Al 10kA THQL1150HM
THQL 120 Vac, For Factory Installed Shunt Trip2,3 Internal Common Trip
# of Ampere 120 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
3 20 14-8 Cu/12-8 Al 10kA THQL32020ST1
THQL 120/240 Vac, Thermal Magnetic Pole plus Nonautomatic Pole
For Switching Neutral
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 10kA THQL21WY15
2 20 14-8 Cu/12-8 Al 10kA THQL21WY20
2 25 14-8 Cu/12-8 Al 10kA THQL21WY25
2 30 14-8 Cu/12-8 Al 10kA THQL21WY30
3 15 14-8 Cu/12-8 Al 10kA THQL31WY15
3 20 14-8 Cu/12-8 Al 10kA THQL31WY20
3 25 14-8 Cu/12-8 Al 10kA THQL31WY25
3 30 14-8 Cu/12-8 Al 10kA THQL31WY30
1Solid or stranded for 14-10 AWG.
2For additional shunt trip offerings see page 6-41.
3UL listed as HACR (heating, air conditioning and refrigeration).
Q-Line Circuit Breakers
Plug-in Circuit Breakers
240V Class
THQL1120HM
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-18
Molded Case Circuit Breakers Section 6
THHQL 120 Vac
# of Ampere 120 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 22kA THHQL11152
1 20 14-8 Cu/12-8 Al 22kA THHQL11202
1 25 14-8 Cu/12-8 Al 22kA THHQL1125
1 30 8-3 Cu/8-3 Al 22kA THHQL1130
1 35 8-3 Cu/8-3 Al 22kA THHQL1135
1 40 8-3 Cu/8-3 Al 22kA THHQL1140
1 45 8-3 Cu/8-3 Al 22kA THHQL1145
1 50 8-3 Cu/8-3 Al 22kA THHQL1150
1 60 8-3 Cu/8-3 Al 22kA THHQL1160
1 70 6-1/0 Cu/4-1/0 Al 22kA THHQL1170
THHQL 120/240 Vac, Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 22kA THHQL2115
2 20 14-8 Cu/12-8 Al 22kA THHQL2120
2 25 14-8 Cu/12-8 Al 22kA THHQL2125
2 30 8-3 Cu/8-3 Al 22kA THHQL2130
2 35 8-3 Cu/8-3 Al 22kA THHQL2135
2 40 8-3 Cu/8-3 Al 22kA THHQL2140
2 45 8-3 Cu/8-3 Al 22kA THHQL2145
2 50 8-3 Cu/8-3 Al 22kA THHQL2150
2 60 8-3 Cu/8-3 Al 22kA THHQL2160
2 70 6-1/0 Cu/4-1/0 Al 22kA THHQL2170
2 80 6-1/0 Cu/4-1/0 Al 22kA THHQL2180
2 90 6-1/0 Cu/4-1/0 Al 22kA THHQL2190
2 100 6-1/0 Cu/4-1/0 Al 22kA THHQL21100
2 110 2-2/0 Cu/2-2/0 Al 22kA THHQL21110
2 125 2-2/0 Cu/2-2/0 Al 22kA THHQL21125
THHQL 240 Vac, Internal Common Trip
# of Ampere 240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 22kA THHQL22015
2 20 14-8 Cu/12-8 Al 22kA THHQL22020
2 25 14-8 Cu/12-8 Al 22kA THHQL22025
2 30 8-3 Cu/8-3 Al 22kA THHQL22030
2 35 8-3 Cu/8-3 Al 22kA THHQL22035
2 40 8-3 Cu/8-3 Al 22kA THHQL22040
2 45 8-3 Cu/8-3 Al 22kA THHQL22045
2 50 8-3 Cu/8-3 Al 22kA THHQL22050
2 60 8-3 Cu/8-3 Al 22kA THHQL22060
2 70 6-1/0 Cu/4-1/0 Al 22kA THHQL22070
2 80 6-1/0 Cu/4-1/0 Al 22kA THHQL22080
2 90 6-1/0 Cu/4-1/0 Al 22kA THHQL22090
2 100 6-1/0 Cu/4-1/0 Al 22kA THHQL22100
3 15 14-8 Cu/12-8 Al 22kA THHQL32015
3 20 14-8 Cu/12-8 Al 22kA THHQL32020
3 25 14-8 Cu/12-8 Al 22kA THHQL32025
3 30 8-3 Cu/8-3 Al 22kA THHQL32030
3 35 8-3 Cu/8-3 Al 22kA THHQL32035
3 40 8-3 Cu/8-3 Al 22kA THHQL32040
3 45 8-3 Cu/8-3 Al 22kA THHQL32045
3 50 8-3 Cu/8-3 Al 22kA THHQL32050
3 60 8-3 Cu/8-3 Al 22kA THHQL32060
3 70 6-1/0 Cu/4-1/0 Al 22kA THHQL32070
3 80 6-1/0 Cu/4-1/0 Al 22kA THHQL32080
3 90 6-1/0 Cu/4-1/0 Al 22kA THHQL32090
3 100 6-1/0 Cu/4-1/0 Al 22kA THHQL32100
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
UL listed HACR (heating, air conditioning and refrigeration).
Q-Line Circuit Breakers
Plug-in Circuit Breakers
240V Class
THHQL1120
THHQL32015
www.geindustrial.com BuyLog™Catalog 6-19
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
TXQL 120/240 Vac
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 65kA TXQL11152
1 20 14-8 Cu/12-8 Al 65kA TXQL11202
1 25 14-8 Cu/12-8 Al 65kA TXQL1125
1 30 14-8 Cu/12-8 Al 65kA TXQL1130
TXQL 120/240 Vac, Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 65kA TXQL2115
2 20 14-8 Cu/12-8 Al 65kA TXQL2120
2 25 14-8 Cu/12-8 Al 65kA TXQL2125
2 30 14-8 Cu/12-8 Al 65kA TXQL2130
3 15 14-8 Cu/12-8 Al 65kA TXQL32015
3 20 14-8 Cu/12-8 Al 65kA TXQL32020
3 25 14-8 Cu/12-8 Al 65kA TXQL32025
3 30 14-8 Cu/12-8 Al 65kA TXQL32030
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
3Limited availability: Obsolete when inventory depleted.
UL listed HACR (heating, air conditioning and refrigeration).
Q-Line Circuit Breakers
Plug-in Circuit Breakers
240V Class
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-20
Molded Case Circuit Breakers Section 6
TQB, THQB 120/240 Vac
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 10 14-8 Cu/12-8 Al 5kA TQB11103
1 15 14-8 Cu/12-8 Al 10kA THQB11152
1 20 14-8 Cu/12-8 Al 10kA THQB11202
1 25 14-8 Cu/12-8 Al 10kA THQB1125
1 30 14-8 Cu/12-8 Al 10kA THQB1130
1 35 8-3 Cu/8-3 Al 10kA THQB1135
1 40 8-3 Cu/8-3 Al 10kA THQB1140
1 45 8-3 Cu/8-3 Al 10kA THQB1145
1 50 8-3 Cu/8-3 Al 10kA THQB1150
1 60 8-3 Cu/8-3 Al 10kA THQB1160
1 70 6-1/0 Cu/4-1/0 Al 10kA THQB1170
TQB, THQB 120/240 Vac, Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 10 14-8 Cu/12-8 Al 5kA TQB21103
2 15 14-8 Cu/12-8 Al 10kA THQB2115
2 20 14-8 Cu/12-8 Al 10kA THQB2120
2 25 14-8 Cu/12-8 Al 10kA THQB2125
2 30 14-8 Cu/12-8 Al 10kA THQB2130
2 35 8-3 Cu/8-3 Al 10kA THQB2135
2 40 8-3 Cu/8-3 Al 10kA THQB2140
2 45 8-3 Cu/8-3 Al 10kA THQB2145
2 50 8-3 Cu/8-3 Al 10kA THQB2150
2 60 8-3 Cu/8-3 Al 10kA THQB2160
2 70 6-1/0 Cu/4-1/0 Al 10kA THQB2170
2 80 6-1/0 Cu/4-1/0 Al 10kA THQB2180
2 90 6-1/0 Cu/4-1/0 Al 10kA THQB2190
2 100 6-1/0 Cu/4-1/0 Al 10kA THQB21100
TQB, THQB 240 Vac, Internal Common Trip
# of Ampere 240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 10 14-8 Cu/12-8 Al 5kA TQB220103
2 15 14-8 Cu/12-8 Al 10kA THQB22015
2 20 14-8 Cu/12-8 Al 10kA THQB22020
2 25 14-8 Cu/12-8 Al 10kA THQB22025
2 30 14-8 Cu/12-8 Al 10kA THQB22030
2 35 8-3 Cu/8-3 Al 10kA THQB22035
2 40 8-3 Cu/8-3 Al 10kA THQB22040
2 45 8-3 Cu/8-3 Al 10kA THQB22045
2 50 8-3 Cu/8-3 Al 10kA THQB22050
2 60 8-3 Cu/8-3 Al 10kA THQB22060
2 70 6-1/0 Cu/4-1/0 Al 10kA THQB22070
2 80 6-1/0 Cu/4-1/0 Al 10kA THQB22080
2 90 6-1/0 Cu/4-1/0 Al 10kA THQB22090
2 100 6-1/0 Cu/4-1/0 Al 10kA THQB22100
3 10 14-8 Cu/12-8 Al 5kA TQB320103
3 15 14-8 Cu/12-8 Al 10kA THQB32015
3 20 14-8 Cu/12-8 Al 10kA THQB32020
3 25 14-8 Cu/12-8 Al 10kA THQB32025
3 30 14-8 Cu/12-8 Al 10kA THQB32030
3 35 8-3 Cu/8-3 Al 10kA THQB32035
3 40 8-3 Cu/8-3 Al 10kA THQB32040
3 45 8-3 Cu/8-3 Al 10kA THQB32045
3 50 8-3 Cu/8-3 Al 10kA THQB32050
3 60 8-3 Cu/8-3 Al 10kA THQB32060
3 70 6-1/0 Cu/4-1/0 Al 10kA THQB32070
3 80 6-1/0 Cu/4-1/0 Al 10kA THQB32080
3 90 6-1/0 Cu/4-1/0 Al 10kA THQB32090
3 100 6-1/0 Cu/4-1/0 Al 10kA THQB32100
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (Switching Duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
3Not UL listed.
UL listed HACR (heating, air conditioning and refrigeration).
Q-Line Circuit Breakers
Bolt-on Circuit Breakers
240V Class
THQB2115
www.geindustrial.com BuyLog™Catalog 6-21
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
THQB and THHQB 120/240 Vac Arc Fault (Single pole)
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-10 Cu/14-10 Al 10kA THQB1115AF22
1 20 14-10 Cu/14-10 Al 10kA THQB1120AF22
1 15 14-10 Cu/14-10 Al 22kA THHQB1115AF22
1 20 14-10 Cu/14-10 Al 22kA THHQB1120AF22
Dual Function GFCI/AFCI Ground Fault & Combination Arc Fault Circuit Breaker
(Available December 2014)
# of Ampere 120 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 10kA THQB1115DF
1 20 14-8 Cu/12-8 Al 10kA THQB1120DF
1 15 14-8 Cu/12-8 Al 22kA THHQB1115DF
1 20 14-8 Cu/12-8 Al 22kA THHQB1120DF
THQB, THHQB 120 Vac, Ground Fault Circuit Interrupters (5 ma)
# of Ampere 120 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 10kA THQB1115GF
1 20 14-8 Cu/12-8 Al 10kA THQB1120GF
1 25 14-8 Cu/12-8 Al 10kA THQB1125GF
1 30 14-8 Cu/12-8 Al 10kA THQB1130GF
1 15 14-8 Cu/12-8 Al 22kA THHQB1115GF
1 20 14-8 Cu/12-8 Al 22kA THHQB1120GF
1 25 14-8 Cu/12-8 Al 22kA THHQB1125GF
1 30 14-8 Cu/12-8 Al 22kA THHQB1130GF
THQB, THHQB 120/240 Vac, Ground Fault Circuit Interrupters, Self Testing
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8Cu/12-8 Al 10kA THQB1115GF3
1 20 14-8Cu/12-8 Al 10kA THQB1120GF3
1 30 14-8Cu/12-8 Al 10kA THQB1130GF3
1 15 14-8Cu/12-8 Al 22kA THHQB1115GF3
1 20 14-8Cu/12-8 Al 22kA THHQB1120GF3
1 30 14-8Cu/12-8 Al 22kA THHQB1130GF3
2 15 14-8Cu/12-8 Al 10kA THQB2115GF3
2 20 14-8Cu/12-8 Al 10kA THQB2120GF3
2 30 14-8Cu/12-8 Al 10kA THQB2130GF3
THQB 120/240 or 208Y/120 Vac, Ground Fault Circuit Interrupters (5 ma),
Internal Common Trip
# of Ampere 120/240 or 208Y/120 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 10kA THQB2115GF
2 20 14-8 Cu/12-8 Al 10kA THQB2120GF
2 25 14-8 Cu/12-8 Al 10kA THQB2125GF
2 30 14-8 Cu/12-8 Al 10kA THQB2130GF
THQB 120 Vac, Ground Fault Circuit Circuit Interrupters (30 ma)
# of Ampere 120 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 10kA THQB1115GFEP
1 20 14-8 Cu/12-8 Al 10kA THQB1120GFEP
1 30 14-8 Cu/12-8 Al 10kA THQB1130GFEP
THQB 120/240 or 208Y/120 Vac, Ground Fault Circuit Interrupters (30 ma)
Internal Common Trip
# of Ampere 120/240 or 208Y/120 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 10kA THQB2115GFEP
2 20 14-8 Cu/12-8 Al 10kA THQB2120GFEP
2 30 14-8 Cu/12-8 Al 10kA THQB2130GFEP
2 40 14-8 Cu/12-8 Al 10kA THQB2140GFEP
1Solid or stranded for 14-10 AWG.
2Combination AFCI compliant with NEC 2008 and later.
Q-Line Circuit Breakers
Bolt-on Circuit Breakers
240V Class
THQB1115GF
Page Updated 10 / 2014
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-22
Molded Case Circuit Breakers Section 6
THQB, THHQB 120/240 Vac, High Intensity Discharge Lighting Loads1
# of Ampere 120/240 Vac
Poles Rating Wire Range2Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 10kA THQB1115HID3
1 20 14-8 Cu/12-8 Al 10kA THQB1120HID3
1 25 14-8 Cu/12-8 Al 10kA THQB1125HID
1 30 14-8 Cu/12-8 Al 10kA THQB1130HID
1 15 14-8 Cu/12-8 Al 22kA THHQB1115HID3
1 20 14-8 Cu/12-8 Al 22kA THHQB1120HID3
1 25 14-8 Cu/12-8 Al 22kA THHQB1125HID
1 30 14-8 Cu/12-8 Al 22kA THHQB1130HID
2 15 14-8 Cu/12-8 Al 10kA THQB2115HID
2 20 14-8 Cu/12-8 Al 10kA THQB2120HID
2 25 14-8 Cu/12-8 Al 10kA THQB2125HID
2 30 14-8 Cu/12-8 Al 10kA THQB2130HID
THHQB 120/240 Vac, Internal Common Trip, High Intensity Discharge Lighting Loads1
# of Ampere 120/240 Vac
Poles Rating Wire Range2Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 22kA THHQB2115HID
2 20 14-8 Cu/12-8 Al 22kA THHQB2120HID
2 25 14-8 Cu/12-8 Al 22kA THHQB2125HID
2 30 14-8 Cu/12-8 Al 22kA THHQB2130HID
THQB 120 Vac with Factory Installed 120 Vac Shunt Trip4,5
# of Ampere 120 Vac
Poles Rating Wire Range2Interrupting Rating Product Number
1 20 14-8 Cu/12-8 Al 10kA THQB1120ST1
THQB 120 Vac, Internal Common Trip with Factory Installed 120 Vac Shunt Trip4,5
# of Ampere 120 Vac
Poles Rating Wire Range2Interrupting Rating Product Number
2 20 14-8 Cu/12-8 Al 10kA THQB2120ST1
2 30 14-8 Cu/12-8 Al 10kA THQB2130ST1
2 100 6-1/0 Cu/4-1/0 Al 10kA THQB21100ST1
3 20 14-8 Cu/12-8 Al 10kA THQB32020ST1
3 30 14-8 Cu/12-8 Al 10kA THQB32030ST1
3 35 8-3 Cu/8-3 Al 10kA THQB32035ST1
3 40 8-3 Cu/8-3 Al 10kA THQB32040ST1
3 50 8-3 Cu/8-3 Al 10kA THQB32050ST1
3 60 8-3 Cu/8-3 Al 10kA THQB32060ST1
3 70 6-1/0 Cu/4-1/0 Al 10kA THQB32070ST1
3 80 6-1/0 Cu/4-1/0 Al 10kA THQB32080ST1
3 90 6-1/0 Cu/4-1/0 Al 10kA THQB32090ST1
3 100 6-1/0 Cu/4-1/0 Al 10kA THQB32100ST1
THQB 120 Vac with Switching Neutral Single Thermal Magnetic Pole;
Single Nonautomatic Pole
# of Ampere 120 Vac
Poles Rating Wire Range2Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 10kA THQB21WY15
2 20 14-8 Cu/12-8 Al 10kA THQB21WY20
2 25 14-8 Cu/12-8 Al 10kA THQB21WY25
2 30 14-8 Cu/12-8 Al 10kA THQB21WY30
THQB 120 Vac with Switching Neutral Two Thermal Magnetic Pole;
Single Nonautomatic Pole
# of Ampere 120 Vac
Poles Rating Wire Range2Interrupting Rating Product Number
3 15 14-8 Cu/12-8 Al 10kA THQB31WY15
3 20 14-8 Cu/12-8 Al 10kA THQB31WY20
3 25 14-8 Cu/12-8 Al 10kA THQB31WY25
3 30 14-8 Cu/12-8 Al 10kA THQB31WY30
1UL listed as HID (high intensity discharge).
2Solid or stranded for 14-10 AWG.
3UL listed as SWD (switching duty). Suitable for switching 120 Vac fluorescent lighting loads.
4For additional shunt trip offerings see page 6-41.
520-60 ampere are UL listed as HACR (heating, air conditioning and refrigeration).
Q-Line Circuit Breakers
Bolt-on Circuit Breakers
240V Class
www.geindustrial.com BuyLog™Catalog 6-23
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Q-Line Circuit Breakers
Bolt-on Circuit Breakers
240V Class
THHQB 120/240 Vac
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 22kA THHQB11152
1 20 14-8 Cu/12-8 Al 22kA THHQB11202
1 25 14-8 Cu/12-8 Al 22kA THHQB1125
1 30 14-8 Cu/12-8 Al 22kA THHQB1130
1 35 8-3 Cu/8-3 Al 22kA THHQB1135
1 40 8-3 Cu/8-3 Al 22kA THHQB1140
1 45 8-3 Cu/8-3 Al 22kA THHQB1145
1 50 8-3 Cu/8-3 Al 22kA THHQB1150
1 60 8-3 Cu/8-3 Al 22kA THHQB1160
1 70 6-1/0 Cu/4-1/0 Al 22kA THHQB1170
THQB/THHQB 120/240 Vac, Low Magnetic Pickup
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 10 kA THQB1115LM2
1 20 14-8 Cu/12-8 Al 10 kA THQB1120LM2
1 15 14-8 Cu/12-8 Al 22 kA THHQB1115LM
1 20 14-8 Cu/12-8 Al 22 kA THHQB1120LM
2 15 14-8 Cu/12-8 Al 10 kA THQB2115LM
2 20 14-8 Cu/12-8 Al 10 kA THQB2120LM
2 15 14-8 Cu/12-8 Al 22 kA THHQB2115LM
2 20 14-8 Cu/12-8 Al 22 kA THHQB2120LM
THHQB 120/240 Vac, Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 22kA THHQB2115
2 20 14-8 Cu/12-8 Al 22kA THHQB2120
2 25 14-8 Cu/12-8 Al 22kA THHQB2125
2 30 14-8 Cu/12-8 Al 22kA THHQB2130
2 35 8-3 Cu/8-3 Al 22kA THHQB2135
2 40 8-3 Cu/8-3 Al 22kA THHQB2140
2 45 8-3 Cu/8-3 Al 22kA THHQB2145
2 50 8-3 Cu/8-3 Al 22kA THHQB2150
2 60 8-3 Cu/8-3 Al 22kA THHQB2160
2 70 6-1/0 Cu/4-1/0 Al 22kA THHQB2170
2 80 6-1/0 Cu/4-1/0 Al 22kA THHQB2180
2 90 6-1/0 Cu/4-1/0 Al 22kA THHQB2190
2 100 6-1/0 Cu/4-1/0 Al 22kA THHQB21100
THHQB 240 Vac, Internal Common Trip
# of Ampere 240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 22kA THHQB22015
2 20 14-8 Cu/12-8 Al 22kA THHQB22020
2 25 14-8 Cu/12-8 Al 22kA THHQB22025
2 30 14-8 Cu/12-8 Al 22kA THHQB22030
2 35 8-3 Cu/8-3 Al 22kA THHQB22035
2 40 8-3 Cu/8-3 Al 22kA THHQB22040
2 45 8-3 Cu/8-3 Al 22kA THHQB22045
2 50 8-3 Cu/8-3 Al 22kA THHQB22050
2 60 8-3 Cu/8-3 Al 22kA THHQB22060
2 70 6-1/0 Cu/4-1/0 Al 22kA THHQB22070
2 80 6-1/0 Cu/4-1/0 Al 22kA THHQB22080
2 90 6-1/0 Cu/4-1/0 Al 22kA THHQB22090
2 100 6-1/0 Cu/4-1/0 Al 22kA THHQB22100
3 15 14-8 Cu/12-8 Al 22kA THHQB32015
3 20 14-8 Cu/12-8 Al 22kA THHQB32020
3 25 14-8 Cu/12-8 Al 22kA THHQB32025
3 30 14-8 Cu/12-8 Al 22kA THHQB32030
3 35 8-3 Cu/8-3 Al 22kA THHQB32035
3 40 8-3 Cu/8-3 Al 22kA THHQB32040
3 45 8-3 Cu/8-3 Al 22kA THHQB32045
3 50 8-3 Cu/8-3 Al 22kA THHQB32050
3 60 8-3 Cu/8-3 Al 22kA THHQB32060
3 70 6-1/0 Cu/4-1/0 Al 22kA THHQB32070
3 80 6-1/0 Cu/4-1/0 Al 22kA THHQB32080
3 90 6-1/0 Cu/4-1/0 Al 22kA THHQB32090
3 100 6-1/0 Cu/4-1/0 Al 22kA THHQB32100
THHQB2115
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
UL listed HACR (heating, air conditioning and refrigeration).
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-24
Molded Case Circuit Breakers Section 6
TXQB 120/240 Vac
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 65kA TXQB11152
1 20 14-8 Cu/12-8 Al 65kA TXQB11202
1 25 14-8 Cu/12-8 Al 65kA TXQB1125
1 30 14-8 Cu/12-8 Al 65kA TXQB1130
TXQB 120/240 Vac, Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 65kA TXQB2115
2 20 14-8 Cu/12-8 Al 65kA TXQB2120
2 25 14-8 Cu/12-8 Al 65kA TXQB2125
2 30 14-8 Cu/12-8 Al 65kA TXQB2130
TXQB 240 Vac, Internal Common Trip
# of Ampere 240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
3 15 14-8 Cu/12-8 Al 65kA TXQB32015
3 20 14-8 Cu/12-8 Al 65kA TXQB32020
3 25 14-8 Cu/12-8 Al 65kA TXQB32025
3 30 14-8 Cu/12-8 Al 65kA TXQB32030
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
UL listed HACR (heating, air conditioning and refrigeration).
Q-Line Circuit Breakers
Bolt-on Circuit Breakers
240V Class
www.geindustrial.com BuyLog™Catalog 6-25
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
TQC, THQC, THHQC 120/240 Vac
# of Ampere 120/240 Vac 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number2Interrupting Rating Product Number2
1 10 14-4 Cu/12-2 Al 5kA TQC1110WL
1 15 14-8 Cu/12-8 Al 10kA THQC1115WL3,4 22kA THHQC1115WL3
1 20 14-8 Cu/12-8 Al 10kA THQC1120WL3,4 22kA THHQC1120WL3
1 25 14-8 Cu/12-8 Al 10kA THQC1125WL322kA THHQC1125WL3
1 30 14-8 Cu/12-8 Al 10kA THQC1130WL322kA THHQC1130WL3
1 35 8-3 Cu/8-3 Al 10kA THQC1135WL322kA THHQC1135WL3
1 40 8-3 Cu/8-3 Al 10kA THQC1140WL322kA THHQC1140WL3
1 45 8-3 Cu/8-3 Al 10kA THQC1145WL322kA THHQC1145WL3
1 50 8-3 Cu/8-3 Al 10kA THQC1150WL322kA THHQC1150WL3
1 60 8-3 Cu/8-3 Al 10kA THQC1160WL322kA THHQC1160WL3
1 70 6-1/0 Cu/4-1/0 Al 10kA THQC1170WL 22kA THHQC1170WL
TQC, THQC, THHQC 120/240 Vac, Internal Common Trip
# of Ampere 120/240 Vac 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number2Interrupting Rating Product Number2
2 10 14-4 Cu/12-2 Al 5kA TQC2110WL
2 15 14-8 Cu/12-8 Al 10kA THQC2115WL322kA THHQC2115WL3
2 20 14-8 Cu/12-8 Al 10kA THQC2120WL322kA THHQC2120WL3
2 25 14-8 Cu/12-8 Al 10kA THQC2125WL3
2 30 14-8 Cu/12-8 Al 10kA THQC2130WL322kA THHQC2130WL3
2 35 8-3 Cu/8-3 Al 10kA THQC2135WL322kA THHQC2135WL3
2 40 8-3 Cu/8-3 Al 10kA THQC2140WL322kA THHQC2140WL3
2 45 8-3 Cu/8-3 Al 10kA THQC2145WL322kA THHQC2145WL3
2 50 8-3 Cu/8-3 Al 10kA THQC2150WL322kA THHQC2150WL3
2 60 8-3 Cu/8-3 Al 10kA THQC2160WL322kA THHQC2160WL3
2 70 6-1/0 Cu/4-1/0 Al 10kA THQC2170WL 22kA THHQC2170WL
2 80 6-1/0 Cu/4-1/0 Al 10kA THQC2180WL 22kA THHQC2180WL
2 90 6-1/0 Cu/4-1/0 Al 10kA THQC2190WL 22kA THHQC2190WL
2 100 6-1/0 Cu/4-1/0 Al 10kA THQC21100WL 22kA THHQC21100WL
TQC, THQC, THHQC 240 Vac, Internal Common Trip
# of Ampere 240 Vac 240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number2Interrupting Rating Product Number
2 10 14-4 Cu/12-2 Al 5kA TQC22010WL
2 15 14-8 Cu/12-8 Al 10kA THQC22015WL 22kA THHQC22015WL
2 20 14-8 Cu/12-8 Al 10kA THQC22020WL 22kA THHQC22020WL
2 25 14-8 Cu/12-8 Al 10kA THQC22025WL 22kA THHQC22025WL
2 30 14-8 Cu/12-8 Al 10kA THQC22030WL 22kA THHQC22030WL
2 35 8-3 Cu/8-3 Al 10kA THQC22035WL 22kA THHQC22035WL
2 40 8-3 Cu/8-3 Al 10kA THQC22040WL 22kA THHQC22040WL
2 45 8-3 Cu/8-3 Al 10kA THQC22045WL 22kA THHQC22045WL
2 50 8-3 Cu/8-3 Al 10kA THQC22050WL 22kA THHQC22050WL
2 60 8-3 Cu/8-3 Al 10kA THQC22060WL 22kA THHQC22060WL
2 70 6-1/0 Cu/4-1/0 Al 10kA THQC22070WL 22kA THHQC22070WL
2 80 6-1/0 Cu/4-1/0 Al 10kA THQC22080WL 22kA THHQC22080WL
2 90 6-1/0 Cu/4-1/0 Al 10kA THQC22090WL 22kA THHQC22090WL
2 100 6-1/0 Cu/4-1/0 Al 10kA THQC22100WL 22kA THHQC22100WL
3 10 14-4 Cu/12-2 Al 5kA TQC32010WL
3 15 14-8 Cu/12-8 Al 10kA THQC32015WL 22kA THHQC32015WL
3 20 14-8 Cu/12-8 Al 10kA THQC32020WL 22kA THHQC32020WL
3 25 14-8 Cu/12-8 Al 10kA THQC32025WL 22kA THHQC32025WL
3 30 14-8 Cu/12-8 Al 10kA THQC32030WL 22kA THHQC32030WL
3 35 8-3 Cu/8-3 Al 10kA THQC32035WL 22kA THHQC32035WL
3 40 8-3 Cu/8-3 Al 10kA THQC32040WL 22kA THHQC32040WL
3 45 8-3 Cu/8-3 Al 10kA THQC32045WL 22kA THHQC32045WL
3 50 8-3 Cu/8-3 Al 10kA THQC32050WL 22kA THHQC32050WL
3 60 8-3 Cu/8-3 Al 10kA THQC32060WL 22kA THHQC32060WL
3 70 6-1/0 Cu/4-1/0 Al 10kA THQC32070WL 22kA THHQC32070WL
3 80 6-1/0 Cu/4-1/0 Al 10kA THQC32080WL 22kA THHQC32080WL
3 90 6-1/0 Cu/4-1/0 Al 10kA THQC32090WL 22kA THHQC32090WL
3 100 6-1/0 Cu/4-1/0 Al 10kA THQC32100WL 22kA THHQC32100WL
1Solid or stranded for 14-10 AWG.
2Use additional suffix “BP” (THQC32020WLBP) for bulk pack of 48 poles. Carton weight 20 lbs. 15-60 ampere breakers only.
3Suitable for mounting on standard 35mm DIN Rail. Refer to table on page 6-27 for termination options.
4UL listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
UL listed HACR (heating, air conditioning and refrigeration). Refer to Q-Line accessories listed on pages 6-30 to 6-31.
Q-Line Circuit Breakers
Cable-in Cable-out (lug-lug)
240V Class
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-26
Molded Case Circuit Breakers Section 6
THQC 120 Vac, Ground Fault Circuit Interrupters
# of Ampere 120 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 10kA THQC1115GF2
1 20 14-8 Cu/12-8 Al 10kA THQC1120GF2
1 25 14-8 Cu/12-8 Al 10kA THQC1125GF2
1 30 14-8 Cu/12-8 Al 10kA THQC1130GF2
THQC 120/240 Vac Ground Fault Circuit Interrupters, Self-Testing
# of Ampere 120 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8Cu/12-8 Al 10kA THQC1115GF3
1 20 14-8Cu/12-8 Al 10kA THQC1120GF3
1 30 14-8Cu/12-8 Al 10kA THQC1130GF3
TXQC 120/240 Vac
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
1 15 14-8 Cu/12-8 Al 65kA TXQC1115WL
1 20 14-8 Cu/12-8 Al 65kA TXQC1120WL
1 25 14-8 Cu/12-8 Al 65kA TXQC1125WL
1 30 14-8 Cu/12-8 Al 65kA TXQC1130WL
TXQC 120/240 Vac, Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
2 15 14-8 Cu/12-8 Al 65kA TXQC2115WL
2 20 14-8 Cu/12-8 Al 65kA TXQC2120WL
2 25 14-8 Cu/12-8 Al 65kA TXQC2125WL
2 30 14-8 Cu/12-8 Al 65kA TXQC2130WL
TXQC 240 Vac, Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Interrupting Rating Product Number
3 15 14-8 Cu/12-8 Al 65kA TXQC32015WL
3 20 14-8 Cu/12-8 Al 65kA TXQC32020WL
3 25 14-8 Cu/12-8 Al 65kA TXQC32025WL
3 30 14-8 Cu/12-8 Al 65kA TXQC32030WL
1Solid or stranded for 14-10 AWG.
2Requires mounting plate. See page 6-30. Not suitable for use in GE column panels.
UL listed HACR (heating, air conditioning and refrigeration).
Use Q-Line mounting accessories listed on pages 6-30 to 6-31.
Q-Line Circuit Breakers
Cable-in Cable-out (lug-lug)
240V Class
THQC1120GF
www.geindustrial.com BuyLog™Catalog 6-27
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Product Features
Multi-terminal Configuration Breakers
—35 mm DIN rail mounting
—Optional front/rear panel mounting kits–THQCFMK, page 6-30.
—Optional load end terminal for up to (4) 0.25-inch quick connnects.
Contact local GE sales office for ring terminal configurations–not DIN rail compatible.
Q-Line Circuit Breakers
DIN-Rail Mount
240V Class
THQC, THHQC 120/240 Vac
Product Number
# of Ampere 120/240 Vac Product Number Line TQAL3A and Product Number
Poles Rating Interrupting Rating No Lugs Load THQECC Line TQAL3A, Load N/A
1 15 10kA THQC1115LL1THQC1115CC1THQC1115X21
1 20 10kA THQC1120LL1THQC1120CC1THQC1120X21
1 25 10kA THQC1125LL THQC1125CC THQC1125X2
1 30 10kA THQC1130LL THQC1130CC THQC1130X2
1 35 10kA THQC1135LL THQC1135CC THQC1135X2
1 40 10kA THQC1140LL THQC1140CC THQC1140X2
1 45 10kA THQC1145LL THQC1145CC THQC1145X2
1 50 10kA THQC1150LL THQC1150CC THQC1150X2
1 60 10kA THQC1160LL THQC1160CC THQC1160X2
1 15 22kA THHQC1115LL THHQC1115CC THHQC1115X2
1 20 22kA THHQC1120LL THHQC1120CC THHQC1120X2
1 25 22kA THHQC1125LL THHQC1125CC THHQC1125X2
1 30 22kA THHQC1130LL THHQC1130CC THHQC1130X2
1 35 22kA THHQC1135LL THHQC1135CC THHQC1135X2
1 40 22kA THHQC1140LL THHQC1140CC THHQC1140X2
1 45 22kA THHQC1145LL THHQC1145CC THHQC1145X2
1 50 22kA THHQC1150LL THHQC1150CC THHQC1150X2
1 60 22kA THHQC1160LL THHQC1160CC THHQC1160X2
15-60A UL Listed HACR (heating, air conditioning and refrigeration)
THQC, THHQC 120/240 Vac, Internal Common Trip
Product Number
# of Ampere 120/240 Vac Product Number Line TQAL3A and Product Number
Poles Rating Interrupting Rating No Lugs Load THQECC Line TQAL3A, Load N/A
2 15 10kA THQC2115LL1THQC2115CC1THQC2115X21
2 20 10kA THQC2120LL1THQC2120CC1THQC2120X21
2 25 10kA THQC2125LL THQC2125CC THQC2125X2
2 30 10kA THQC2130LL THQC2130CC THQC2130X2
2 35 10kA THQC2135LL THQC2135CC THQC2135X2
2 40 10kA THQC2140LL THQC2140CC THQC2140X2
2 45 10kA THQC2145LL THQC2145CC THQC2145X2
2 50 10kA THQC2150LL THQC2150CC THQC2150X2
2 60 10kA THQC2160LL THQC2160CC THQC2160X2
2 15 22kA THHQC2115LL THHQC2115CC THHQC2115X2
2 20 22kA THHQC2120LL THHQC2120CC THHQC2120X2
2 25 22kA THHQC2125LL THHQC2125CC THHQC2125X2
2 30 22kA THHQC2130LL THHQC2130CC THHQC2130X2
2 35 22kA THHQC2135LL THHQC2135CC THHQC2135X2
2 40 22kA THHQC2140LL THHQC2140CC THHQC2140X2
2 45 22kA THHQC2145LL THHQC2145CC THHQC2145X2
2 50 22kA THHQC2150LL THHQC2150CC THHQC2150X2
2 60 22kA THHQC2160LL THHQC2160CC THHQC2160X2
15-60A UL Listed HACR (heating, air conditioning and refrigeration)
Terminal Configuration
Suffix2Line Terminal Load Terminal
WL TQAL3A THQEL3
X2 TQAL3A N/A
LL N/A N/A
CC TQAL3A THQECC
None N/A THQEL3
115 and 20 ampere breakers UL listed as SWD (Switching Duty) rated. Suitable for
switching 120 Vac fluorescent lighting loads.
2Use additional suffix “BP” (THQC1120CCBP) for bulk pack of 48 poles. Must be
ordered in multiples of 48 poles.
Additional Q-Line mounting accessories listed on pages 6-30 to 6-31.
Terminal Selection
Type Wire Range Product Number
Lug–Line only 14-6 Cu/12-2 Al TQAL3A
Lug–Load only 14-2 Cu/12-2 Al THQEL3
Quick Connector–Load only (4) 14 Cu or (4) 12 Al THQECC
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-28
Molded Case Circuit Breakers Section 6
TQD 240 Vac, Internal Common Trip
# of Ampere 240 Vac
Poles Rating Interrupting Rating Product Number 1,2
2 100 10kA TQD22100WL
2 125 10kA TQD22125WL
2 150 10kA TQD22150WL
2 175 10kA TQD22175WL
2 200 10kA TQD22200WL
2 225 10kA TQD22225WL
3 100 10kA TQD32100WL
3 125 10kA TQD32125WL
3 150 10kA TQD32150WL
3 175 10kA TQD32175WL
3 200 10kA TQD32200WL
3 225 10kA TQD32225WL
TQD 240 Vac, Internal Common Trip with Factory Installed 120 Vac Shunt Trip3
# of Ampere 240 Vac
Poles Rating Interrupting Rating Product Number 1,2
3 125 10kA TQD32125ST1
3 150 10kA TQD32150ST1
3 175 10kA TQD32175ST1
3 200 10kA TQD32200ST1
3 225 10kA TQD32225ST1
THQD 240 Vac, Internal Common Trip
# of Ampere 240 Vac
Poles Rating Interrupting Rating Product Number 1,2
2 100 22kA THQD22100WL
2 125 22kA THQD22125WL
2 150 22kA THQD22150WL
2 175 22kA THQD22175WL
2 200 22kA THQD22200WL
2 225 22kA THQD22225WL
3 100 22kA THQD32100WL
3 125 22kA THQD32125WL
3 150 22kA THQD32150WL
3 175 22kA THQD32175WL
3 200 22kA THQD32200WL
3 225 22kA THQD32225WL
TJD 240 Vac, Internal Common Trip
# of Ampere 240 Vac
Poles Rating Interrupting Rating Product Number 1,2
2 250 22kA TJD422250WL
2 300 22kA TJD422300WL
2 350 22kA TJD422350WL
2 400 22kA TJD422400WL
2 400 Molded Case Switch 22kA TJD422Y400
3 250 22kA TJD432250WL4
3 300 22kA TJD432300WL4
3 350 22kA TJD432350WL4
3 400 22kA TJD432400WL4
3 400 Molded Case Switch 22kA TJD432Y4004
1Refer to table on page 6-103 for lug and wire range data.
2Includes line and load lugs. For optional configurations see page 6-3.
3For additional shunt trip options see page 6-41.
4TJD uses same accessories as J600 line. TJD not listed HACR.
UL listed HACR (heating, air conditioning and refrigeration).
Q-Line Circuit Breakers
Cable-in Cable-out (lug-lug)
240V Class
TJD432400WL
www.geindustrial.com BuyLog™Catalog 6-29
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Note: Molded case switches may be used as main devices in panelboards and switch-
boards but cannot be used as subfeeds or branch breakers because they do not provide
wire protection. Q-Line and TEB molded case switches have a 10,000 ampere symmetrical
short circuit withstand rating when protected by a fuse or circuit breaker rated 10,000
amperes IC or greater and whose ampere rating does not exceed the ampere rating of
the switch.
Plug-in TQL 120/240, Vac Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Short Circuit Withstand Rating Product Number
2 60 8-3 Cu/8-3 Al 10kA TQL21Y60
2 100 6-1/0 Cu/4-1/0 Al 10kA TQL21Y100
Plug-in TQL 240, Vac Internal Common Trip
# of Ampere 240 Vac
Poles Rating Wire Range1Short Circuit Withstand Rating Product Number
2 60 8-3 Cu/8-3 Al 10kA TQL22Y60
2 100 6-1/0 Cu/4-1/0 Al 10kA TQL22Y100
3 60 8-3 Cu/8-3 Al 10kA TQL32Y60
3 100 6-1/0 Cu/4-1/0 Al 10kA TQL32Y100
Bolt-on TQB 120/240, Vac Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Short Circuit Withstand Rating Product Number
2 60 8-3 Cu/8-3 Al 10kA TQB21Y60
2 100 6-1/0 Cu/4-1/0 Al 10kA TQB21Y100
Bolt-on TQB 240 Vac, Internal Common Trip
# of Ampere 240 Vac
Poles Rating Wire Range1Short Circuit Withstand Rating Product Number
2 60 8-3 Cu/8-3 Al 10kA TQB22Y60
2 100 6-1/0 Cu/4-1/0 Al 10kA TQB22Y100
3 60 8-3 Cu/8-3 Al 10kA TQB32Y60
3 100 6-1/0 Cu/4-1/0 Al 10kA TQB32Y100
Cable In-Cable Out (Lug-Lug) TQC 120/240 Vac, Internal Common Trip
# of Ampere 120/240 Vac
Poles Rating Wire Range1Short Circuit Withstand Rating Product Number
2 60 8-3 Cu/8-3 Al 10kA TQC21Y60
2 100 6-1/0 Cu/4-1/0 Al 10kA TQC21Y100
Cable In-Cable Out (Lug-Lug) TQC 240 Vac, Internal Common Trip
# of Ampere 240 Vac
Poles Rating Wire Range1Short Circuit Withstand Rating Product Number
2 60 8-3 Cu/8-3 Al 10kA TQC22Y60
2 100 6-1/0 Cu/4-1/0 Al 10kA TQC22Y100
3 60 8-3 Cu/8-3 Al 10kA TQB32Y60
3 100 6-1/0 Cu/4-1/0 Al 10kA TQB32Y100
Cable In-Cable Out (Lug-Lug) TQD, TJD 240 Vac, Internal Common Trip
# of Ampere 240 Vac
Poles Rating Short Circuit Withstand Rating Product Number 4
2 225 14kA TQD22Y225
3 225 14kA TQD32Y2252
2 400 22kA TJD422Y400
3 400 22kA TJD432Y4003
1Solid or stranded for 14-10 AWG.
2TQD32YT225 with dummy trip used for accessorized applications.
3TJD uses same accessories as J600 line.
4Refer to table on page 6-106 for lug and wire range data. Line and load lugs included in basic switch product number.
Q-Line Circuit Breakers
Molded Case Switches
240V Class
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-30
Molded Case Circuit Breakers Section 6
Terminals (Lugs) for Q-Line Circuit Breakers
Ampere Rating Termination Type Wire Range (Cu/Al) Product Number
15-60 Lug (line only) 14-6/12-2 TQAL3A
15-60 Lug (load only) 14-2/12-2 THQEL3
15-60 Quick connector (load only) (4) 14/(4) 12 THQECC
Mounting Accessories for THQB, THQC
Product Ampere # of Used With
Type Rating Poles Frame Product Number
Bolt-on Mounting Base 3 THQB/TEY TEY3B
Back Mounting Plates 1 THQC TQCBMPA1
Screw Type
Back Mounting Plates 2 THQC TQCBMPA2
Screw Type
Back Mounting Plates 3 THQC TQCBMPA3
Screw Type
Back Mounting Plates 10 THQC TQCBMPA10
Screw Type
Front-mounting Plates 1 THQC TQCFMP11
Front-mounting Plates 2 THQC TQCFMP21
Front-mounting Plates 3 THQC TQCFMP31
Front-mounting Plates 4 THQC TQCFMP41
Pack of 48 Front/Rear Mounting Clips 1 & 2-pole THQCFMK
15-60A THQC
Pack of 24 DIN rail clips THQC THQCDIN
1Not UL listed.
Mounting Accessories for THQC, THQC-GF, GFEP
Product Type # of Poles Used With Frame Product Number
Snap In Back 1 THQC, THQC-GF TQCGFBMPA1
Mounting Plates
Snap In Back 2 THQC, THQC-GF TQCGFBMPA2
Mounting Plates
Snap In Back 3 THQC, THQC-GF TQCGFBMPA3
Mounting Plates
Snap In Back 10 THQC, THQC-GF TQCGFBMPA10
Mounting Plates
Mounting Accessories for TQL
Product Ampere # of Used With
Type Rating Poles Frame Product Number
Plug-in Mounting Base 70 amp 2 TQL 571B595DDG1
Plug-in Mounting Base 70 amp 3 TQL 571B595DDG2
Plug-in Mounting Base 100 amp 3 TQL 565B837G1
Plug-in Mounting Base 100 amp 2 TQL 565B837G2
Q-Line Circuit Breakers
Accessories
240V Class
Quick Connector THQECC
Load Lug THQEL3
Mounting Kit THQCFMK
www.geindustrial.com BuyLog™Catalog 6-31
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Handle Locking Devices & Handle Ties
Description Breaker Type Product Number
TQB
Handle Locks - Non Padlocking TQC THL1035
TQL
TQB… GF
Handle Locks - Padlocking TQC… GF THQGFPLD12,4
TQL… GF
THQP
Handle Locks - Non Padlocking TQB… GF TQPL
TQC… GF
TQL… GF
Handle Locks - Padlocking TQD TQDPLD12
Handle Locks - Padlocking TQD TQPDLD21
Handle Locks - Padlocking TQB THP100
TQL
Handle Locks - Padlocking THQP TQPPL
Handle Locks - Padlocking TQC TQPLD12
TQB
Snap-on Handle Tie - Trip Indicating TQC TQHT16
TQL
TQB
Snap-on Handle Tie - Solid TQC THT1046
TQL
Multiwire Branch Breaker TQB TQ3HTK7
TQC
Handle Tie Kits TQL TQ4HTK8
All multi-pole breakers have internal common trip
Handle ties provide manual on-off capability only between one-pole devices
Breaker Mounting Screw Kit
Product Type Used With Frame Product Number
Breaker Mounting Screw Kit THQB TQBS13
1EUSERC Approved–Factory Installed Only.
2Suitable for circuit breakers used in group mounted panelboard construction only.
3Price is per screw. Packaged in quantities of 24. Must be ordered in multiples of 24.
4Suitable for use on single pole GF Breakers only.
5Kit includes (1) lock for 1-pole breaker and (1) lock for 2-pole breaker
6For two single-pole breakers
7For three single-pole breakers - kit includes (10) pcs.
8For four single-pole breakers - kit includes (10) pcs.
Q-Line Circuit Breakers
Accessories
THL103
THP100
THT104
TQHT1
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-32
Molded Case Circuit Breakers Section 6
Industrial Circuit Breakers
15-100A
Thermal Magnetic Trip
Type TEY/TEYF
Noninterchangeable Trip
Bolt-on
480Y/277V Class
TEY and TEYF breakers are one-inch wide per pole, compact, bolt-on circuit breakers
for use on grounded 480Y/277 Vac systems. Short circuit ratings at that voltage for TEY
and TEYF are 14 and 18kA, respectively. TEYF also offers higher selectivity ratings with
upstream devices (See DET-537 for details). The bolt-on mounting base (TEY3B) shown
on page 6-102 makes TEY and TEYF suitable for various lug-lug applications.
1- 2- and 3-pole TEY/TEYF breakers
Internal Accessories for TEY/TEYF (2- and 3-pole breaker only) Factory Installed Only
Auxiliary Switch, Single-Pole Add suffix to Breaker
(5A at 120, 240, 277 Vac, 1/4 hp at 120, 240 Vdc) Product Number
“A” switch (normally open) AS1A5
“B” switch (normally closed) AS1B5
“AB” switch (both) ASAB5
Shunt Trip 120-277 Vac control voltage ST125
5Limited to one accessory per breaker.
TEY/TEYF (UL File E-11592; CSA LR 57114)
Ampere
Rating Wire Range1Product Number Product Number
Type TEY3,4 Type TEYF3,4
Single Pole - Includes Integral Cu/Al Load Lugs 14kA @ 277 Vac 18kA @ 277 Vac
15 #14-#10 TEY1152TEYF1152
20 #14-#10 TEY1202TEYF1202
25 #14-#10 TEY125 TEYF125
30 #14-#10 TEY130 TEYF130
35 #10-#4 TEY135 TEYF135
40 #10-#4 TEY140 TEYF140
45 #10-#4 TEY145 TEYF145
50 #10-#4 TEY150 TEYF150
60 #10-#4 TEY160 TEYF160
70 #4-1/0 TEY170
80 #4-1/0 TEY180
90 #4-1/0 TEY190
100 #4-1/0 TEY1100
Type TEY3,4 Type TEYF3,4
Two-Pole - Includes Integral Cu/Al Load Lugs 14kA @ 480 / 277 Vac 18kA @ 480 / 277 Vac
15 #14-#10 TEY215 TEYF215
20 #14-#10 TEY220 TEYF220
25 #14-#10 TEY225 TEYF225
30 #14-#10 TEY230 TEYF230
35 #10-#4 TEY235 TEYF235
40 #10-#4 TEY240 TEYF240
45 #10-#4 TEY245 TEYF245
50 #10-#4 TEY250 TEYF250
60 #10-#4 TEY260 TEYF260
70 #4-1/0 TEY270 TEYF270
80 #4-1/0 TEY280 TEYF280
90 #4-1/0 TEY290 TEYF290
100 #4-1/0 TEY2100 TEYF2100
110 #4-2/0 TEYF2110B
125 #4-2/0 TEYF2125B
Type TEY3,4 Type TEYF3,4
Three-Pole - Includes Integral Cu/Al Load Lugs 14kA @ 480 / 277 Vac 18kA @ 480 / 277 Vac
15 #14-#10 TEY315 TEYF315
20 #14-#10 TEY320 TEYF320
25 #14-#10 TEY325 TEYF325
30 #14-#10 TEY330 TEYF330
35 #10-#4 TEY335 TEYF335
40 #10-#4 TEY340 TEYF340
45 #10-#4 TEY345 TEYF345
50 #10-#4 TEY350 TEYF350
60 #10-#4 TEY360 TEYF360
70 #4-1/0 TEY370 TEYF370
80 #4-1/0 TEY380 TEYF380
90 #4-1/0 TEY390 TEYF390
100 #4-1/0 TEY3100 TEYF3100
110 #4-2/0 TEYF3110B
125 #4-2/0 TEYF3125B
1Solid or stranded for 14-10 AWG.
2Single-pole, 15 and 20 ampere breakers are also UL listed as switching duty breakers, suitable for switching
120, 240, or 277 Vac.
3UL listed HACR (Heating, Air Conditioning, Refrigeration).
4UL listed for HID (high intensity discharge), all 50A or less.
www.geindustrial.com BuyLog™Catalog 6-33
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Industrial Circuit Breakers
15-125A
Thermal Magnetic Trip
Type TEYD/TEYH/TEYL
Noninterchangeable Trip
Bolt-on
480Y/277V Class
The TEY family of circuit breakers (TEY, TEYF, TEYD, TEYH, and TEYL) are one-inch wide per
pole, compact, bolt-on circuit breakers for use on grounded 480Y/277 Vac systems, and
are typically installed within Lighting Panelboards, including GE A-Series. Short circuit
ratings at 480/277 Vac are shown in the tables that follow. Ratings at other voltages are
shown in the Quick Reference Guide at the beginning of this section. Bolt-On mounting
bases TEY3B (page 6-102) and TEY3B125 (page 6-34) make these frames suitable for
unit mount / lug-lug connected applications. Handle tie kits, suitable for use with multiple
single pole breakers used on shared neutral circuits (page 6-34) are available for
TEYD/H/L circuit breakers.
1- 2- and 3-pole
TEYD/TEYH/TEYL breakers
TEYD/TEYH/TEYL (UL/cUL File E-11592)
Ampere Wire
Rating Range1Product No. Product No. Product No.
Single Pole Type TEYD Type TEYH Type TEYL
Includes Load Lugs 25kA @ 480 / 277 Vac 35kA @ 480 / 277 Vac 65kA @ 480 / 277 Vac
15 #14-#10 TEYD1015B TEYH1015B TEYL1015B
20 #14-#10 TEYD1020B TEYH1020B TEYL1020B
25 #10-#4 TEYD1025B TEYH1025B TEYL1025B
30 #10-#4 TEYD1030B TEYH1030B TEYL1030B
35 #10-#4 TEYD1035B TEYH1035B TEYL1035B
40 #10-#4 TEYD1040B TEYH1040B TEYL1040B
45 #10-#4 TEYD1045B TEYH1045B TEYL1045B
50 #10-#4 TEYD1050B TEYH1050B TEYL1050B
60 #10-#4 TEYD1060B TEYH1060B TEYL1060B
70 #4-2/0 TEYD1070B TEYH1070B TEYL1070B
Two-Pole Type TEYD Type TEYH Type TEYL
Includes Load Lugs 25kA @ 480 / 277 Vac 35kA @ 480 / 277 Vac 65kA @ 480 / 277 Vac
15 #14-10 TEYD2015B TEYH2015B TEYL2015B
20 #14-10 TEYD2020B TEYH2020B TEYL2020B
25 #10-#4 TEYD2025B TEYH2025B TEYL2025B
30 #10-#4 TEYD2030B TEYH2030B TEYL2030B
35 #10-#4 TEYD2035B TEYH2035B TEYL2035B
40 #10-#4 TEYD2040B TEYH2040B TEYL2040B
45 #10-#4 TEYD2045B TEYH2045B TEYL2045B
50 #10-#4 TEYD2050B TEYH2050B TEYL2050B
60 #10-#4 TEYD2060B TEYH2060B TEYL2060B
70 #4-2/0 TEYD2070B TEYH2070B TEYL2070B
80 #4-2/0 TEYD2080B TEYH2080B TEYL2080B
90 #4-2/0 TEYD2090B TEYH2090B TEYL2090B
100 #4-2/0 TEYD2100B TEYH2100B TEYL2100B
110 #4-2/0 TEYD2110B TEYH2110B TEYL2110B
125 #4-2/0 TEYD2125B TEYH2125B TEYL2125B
Three-Pole Type TEYD Type TEYH Type TEYL
Includes Load Lugs 25kA @ 480 / 277 Vac 35kA @ 480 / 277 Vac 65kA @ 480 / 277 Vac
15 #14-#10 TEYD3015B TEYH3015B TEYL3015B
20 #14-#10 TEYD3020B TEYH3020B TEYL3020B
25 #10-#4 TEYD3025B TEYH3025B TEYL3025B
30 #10-#4 TEYD3030B TEYH3030B TEYL3030B
35 #10-#4 TEYD3035B TEYH3035B TEYL3035B
40 #10-#4 TEYD3040B TEYH3040B TEYL3040B
45 #10-#4 TEYD3045B TEYH3045B TEYL3045B
50 #10-#4 TEYD3050B TEYH3050B TEYL3050B
60 #10-#4 TEYD3060B TEYH3060B TEYL3060B
70 #4-2/0 TEYD3070B TEYH3070B TEYL3070B
80 #4-2/0 TEYD3080B TEYH3080B TEYL3080B
90 #4-2/0 TEYD3090B TEYH3090B TEYL3090B
100 #4-2/0 TEYD3100B TEYH3100B TEYL3100B
110 #4-2/0 TEYD3110B TEYH3110B TEYL3110B
125 #4-2/0 TEYD3125B TEYH3125B TEYL3125B
1Solid or stranded for 14-10 AWG.
2Single-pole, 15 and 20 ampere breakers are also UL listed as switching duty breakers, suitable for switching
120, 240, or 277 Vac.
3UL listed HACR (Heating, Air Conditioning, Refrigeration).
4UL listed for HID (high intensity discharge), all 50A or less.
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-34
Section 6
Internal Accessories for TEYD/TEYH/TEYL - Factory Installed Only
Description Product Number
TEYD/H/L UV Release1,3
24 Vac TEYXU1
48 Vac TEYXU2
120 Vac TEYXU3
240 Vac TEYXU4
24 Vdc TEYXU6
48 Vdc TEYXU7
125 Vdc TEYXU8
250 Vdc TEYXU9
TEYD/H/L Shunt Trip1
24 Vac TEYXS1
48 Vac TEYXS2
120 Vac TEYXS3
240 Vac TEYXS4
24 Vdc TEYXS6
48 Vdc TEYXS7
125 Vdc TEYXS8
250 Vdc TEYXS9
TEYD/H/L Auxiliary Switch2
LT Pole TEYXASL
RT Pole TEYXASR
Bell Alarm
TEYD/H/L Bell Alarm - Form C1TEYXBA1
TEYD/H/L Mounting Base
3-P 15-100A Mounting Base TEY3B
3-P 110/125A Mounting Base TEY3B125
TEYD/H/L Handle Tie
TEYD/H/L 2-Pole Handle Tie TEYXHT2
10-Pack TEYD/H/L 2-Pole Handle Tie (10 Pack) TEYXHT2K
TEYD/H/L 3-Pole Handle Tie TEYXHT3
10-Pack TEYD/H/L 3-Pole Handle Tie (10 Pack) TEYXHT3K
TEYD/TEYH/TEYL Padlocking
Padlock Device TEYXPLD1
1Right hand mounting only.
2Right or left hand mounting.
3Only available in 3-pole circuit breaker.
TEYD/TEYH/TEYL Reference Publications
Installation Instructions DEH-41590
Mounting Base Installation Instructions DEH-41556
1-Pole Circuit Breaker Outline Drawing 10106028SH1
3-Pole Circuit Breaker Outline Drawing 10106029SH1
2-Pole Circuit Breaker Outline Drawing 10106030SH1
TEY3B125 Mounting Base Outline Drawing 10110291SH1
Molded Case Circuit Breakers
Industrial Circuit Breakers
15-125A
Thermal Magnetic Trip
Type TEYD/TEYH/TEYL
Noninterchangeable Trip
Bolt-on
480Y/277V Class
www.geindustrial.com BuyLog™Catalog 6-35
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Single Pole — Includes Cu/Al load lugs only. If line lugs are required, add suffix “WL” to Product Number.
Type TEB Type TED Type THED
120 Vac 125 Vdc 277 Vac 125 Vdc 347 Vac1277 Vac 347 Vac1
Ampere
Rating Product Number Product Number Product Number Product Number Product Number
10 TEB1110102,4 TED1130102,4
15 TEB1110153,4 TED1130153,4 TED1140153,4 THED1130154THED1140153,4
20 TEB1110203,4 TED1130203,4 TED1140203,4 THED1130204THED1140203,4
25 TEB1110254TED1130254TED1140254THED1130254THED1140254
30 TEB1110304TED1130304TED1140304THED1130304THED1140304
35 TEB1110354TED1130354———
40 TEB1110404TED1130404———
45 TEB1110454TED1130454———
50 TEB1110504TED1130504———
60 TEB111060 TED113060 ———
70 TEB111070 TED113070 ———
80 TEB111080 TED113080 ———
90 TEB111090 TED113090 ———
100 TEB111100 TED113100 ———
Two Pole — Includes Cu/Al line and load lugs. For optional lugs, see page 6-103 and 6-105.
Type TEB Type TED Type THED, Hi-Break5
240 Vac, 250 Vdc 480 Vac, 250 Vdc 480 Vac, 250 Vdc
Ampere
Rating Product Number Product Number Product Number
10 TEB122010WL2,4 TED124010WL2,4 —
15 TEB122015WL4TED124015WL4THED124015WL4
20 TEB122020WL4TED124020WL4THED124020WL4
25 TEB122025WL4TED124025WL4THED124025WL4
30 TEB122030WL4TED124030WL4THED124030WL4
35 TEB122035WL4TED124035WL4THED124035WL4
40 TEB122040WL4TED124040WL4THED124040WL4
45 TEB122045WL4TED124045WL4THED124045WL4
50 TEB122050WL4TED124050WL4THED124050WL4
60 TEB122060WL TED124060WL THED124060WL
70 TEB122070WL TED124070WL THED124070WL
80 TEB122080WL TED124080WL THED124080WL
90 TEB122090WL TED124090WL THED124090WL
100 TEB122100WL TED124100WL THED124100WL
110 — TED124110WL —
125 — TED124125WL —
150 — TED124150WL —
1Suitable for 10 kAIC at 480 Vac, but not labeled or UL listed.
2Not UL listed, rated 5kA @ 120V, 240V and 480V.
3Single-pole, 15-and 20-ampere breakers are also UL listed as switching duty breakers, suitable for switching 120 Vac (TEB), 277, 347 Vac (TED, THED) fluorescent lighting loads.
4UL listed for HID (high intensity discharge).
5Two-pole breaker is furnished in three-pole case.
Notes: All TEB, TED, THED breakers UL listed as HACR type except 10 ampere.
All TEB, TED, THED breakers suitable for reverse feed.
60/75°C rating through 100 amperes, 75°C rating above 100 amperes.
Industrial Circuit Breakers
10-150A Circuit Breakers
Thermal-Magnetic Trip
E150 Line Circuit Breakers
Types TEB, TED, THED
Noninterchangeable Trip
Product Number Structure
TEB 111015 WL
Family/Interruption Frame Rating Voltage Ampere
Rating (Amperes) Poles Rating Rating Lugs
TEB = Core E / Low Tier 1= 150 1= 1 pole 1= 120V 010 to 150 (blank) = Load Lugs
TED = Core E / Mid Tier 2= 2 poles 2= 240V WL = Line & Load
THED =Core E / High Tier 3= 3 poles 3= 277V
4= 480V
6= 600V
Interruption Ratings shown on page 6-7
Note: This information is provided for interpreting product numbers
(it should not be used to build product numbers).
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-36
Molded Case Circuit Breakers Section 6
Three Pole — Includes Cu/Al line and load lugs. For optional lugs, see page 6-103 and 6-105.
Type TEB Type TED Type THED, Hi-Break
240 Vac 480 Vac 600 Vac 600 Vac
Ampere
Rating Product Number Product Number Product Number Product Number
10 TEB132010WL1,3 TED134010WL1,3 ——
15 TEB132015WL3TED134015WL3——
20 TEB132020WL3TED134020WL3TED136020WL3THED136020WL3
25 TEB132025WL3TED134025WL3TED136025WL3THED136025WL3
30 TEB132030WL3TED134030WL3TED136030WL3THED136030WL3
35 TEB132035WL3TED134035WL3TED136035WL3THED136035WL3
40 TEB132040WL3TED134040WL3TED136040WL3THED136040WL3
45 TEB132045WL3TED134045WL3TED136045WL3THED136045WL3
50 TEB132050WL3TED134050WL3TED136050WL3THED136050WL3
60 TEB132060WL TED134060WL TED136060WL —
70 TEB132070WL TED134070WL TED136070WL THED136070WL
80 TEB132080WL TED134080WL TED136080WL —
90 TEB132090WL TED134090WL TED136090WL THED136090WL
100 TEB132100WL TED134100WL TED136100WL THED136100WL
110 — TED134110WL TED136110WL THED136110WL
125 — TED134125WL TED136125WL THED136125WL
150 — TED134150WL TED136150WL THED136150WL
100NA — TED134YT1002TED136YT1002—
150NA — TED134YT1502TED136YT1502—
1Not UL listed, rated 5kA @ 120V, 240V and 480V.
2Includes factory-installed dummy trip.
3UL listed for HID (high intensity discharge).
Notes: All TEB, TED, THED breakers UL listed as HACR type except 10 ampere.
All TEB, TED, THED breakers suitable for reverse feed.
60/75°C rating through 100 amperes, 75°C rating above 100 amperes.
Accessories: See pages 6-39 to 6-44 and 6-94 to 6-106.
E150 Reference Publications
TDR Operating Mechanism GEH-2994
Shunt Trip GEH-3416
Undervoltage Release GEH-3417
Auxiliary Switch GEH-3418
Three Coil Shunt Trip GEH-3434
Mechanical Interlock GEH-4310
TDM Operating Mechanism GEH-4335
Bell Alarm GEH-4576
Plug-in Mounting Base GEH-4610
STDA Flange Handle GEH-5314
STDA Operating Mechanism GEH-5684
Cable Operator Mechanism GEH-6290
Motor Operator GEH-6500
Back Connected Studs GEJ-3609
Padlocking Device - Standard GEJ-5143
E150 Outline Drawing 139C3643SH1, 2, 4
Industrial Circuit Breakers
10-150A Circuit Breakers
Thermal-Magnetic Trip
E150 Line Circuit Breakers
Types TEB, TED, THED
Noninterchangeable Trip
Add-on Current Limiter — UL Listed
100 kAIC at 480 and 600 VAC4
Ampere
Rating Product Number
15 TEDL36015
20 TEDL36020
30 and 60 TEDL36060
100 TEDL36100
4For use with 3 Pole TED/THED only
www.geindustrial.com BuyLog™Catalog 6-37
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Type TJJ Noninterchangeable Trip, includes Cu/Al Line and Load Lugs, suitable for reverse feed
Frame
2-Pole, 400 Ampere Frame 3-Pole, 400 Ampere Frame Terminal Lugs for Front
Adjustable Instantaneous 600 Vac, 250 Vdc 600 Vac Connection (Cu/Al)
Ampere Trip Ampere Range Product Product Copper/ Wire
Rating Low High Number Number Aluminum Lugs Size
200 600 2000 TJJ426200WL TJJ436200WL
225 675 2250 TJJ426225WL TJJ436225WL TCAL433(1) 6-600
250 750 2500 TJJ426250WL TJJ436250WL Included in or
300 900 3000 TJJ426300WL TJJ436300WL price of (2) 2/0-250 Cu/Al
350 1050 3500 TJJ426350WL TJJ436350WL breaker
400 1200 4000 TJJ426400WL TJJ436400WL
Types TJK, THJK — Interchangeable Trip, includes Cu/Al Line and Load Lugs, not suitable for reverse feed
Complete Circuit Breaker Terminal Lugs for Front
Includes Line and Load Lugs Connection (Cu/Al)1
Adjustable Instantaneous
Trip Ampere Frame Only Trip Unit Only. Use Product Number
Ampere Range Standard Hi-Break Product with Standard and (Order 2
Rating Low High Product Number Product Number Number Hi-Break Frames per pole) Wire Size
400A Frame—Two-Pole
200 600 2000 TJK426200WL THJK426200WL TJK426F000 TJK426T200
225 675 2250 TJK426225WL THJK426225WL Standard Frame TJK426T225 (1) 6-600
250 750 2500 TJK426250WL THJK426250WL TJK426T250 TCAL433or
300 900 3000 TJK426300WL THJK426300WL THJK426F000 TJK426T300 (2) 2/0-250 Cu/Al
350 1050 3500 TJK426350WL THJK426350WL Hi-Break TJK426T350
400 1200 4000 TJK426400WL THJK426400WL TJK426T400
400A Frame—Three-Pole
200 600 2000 TJK436200WL THJK436200WL TJK436F000 TJK436T200
225 675 2250 TJK436225WL THJK436225WL Standard Frame TJK436T225
250 750 2500 TJK436250WL THJK436250WL TJK436T250
300 900 3000 TJK436300WL THJK436300WL TJK436T300 (1) 6-600
350 1050 3500 TJK436350WL THJK436350WL THJK436F000 TJK436T350 TCAL433or
400 1200 4000 TJK436400WL THJK436400WL Hi-Break TJK436T400 (2) 2/0-250 Cu/Al
400 600 2000 —— TJK436TM14002
Mag 1200 4000 —— TJK436TM24002
Only 350 1000 —— TJK436TM34002
1For optional lugs, see page 6-103.
2Not UL listed.
3Alternate lug for 750 kcmil Cu/Al cable, Product Number TCAL47.
Accessories: See pages 6-39 to 6-44 and 6-94 to 6-106.
Industrial Circuit Breakers
125-600A Circuit Breakers
Thermal-Magnetic Trip
J600 Line Circuit Breakers
Types TJJ, TJK, THJK
Product Number Structure
Note: This information is provided for interpreting product numbers
(it should not be used to build product numbers).
Family/Interruption
Rating (480V)
TJJ = Core J / 30kA
TJK = Core J / 30kA
THJK = Core J / 35kA
Frame Rating
(Amperes)
4= 400
6= 600
Poles
2= 2 poles
3= 3 poles
Voltage
Rating
6= 600V
Ampere
Rating
200 to 600
Lugs
(blank) = Load Lugs
WL = Line & Load
LL = Less Lugs
(blank) = AC Rated
D= THJK Hi-Break
DC Rated
40kA @ 250V
50kA @ 500V
25kA @ 600V
TJJ 42 6 D 200 WL
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-38
Molded Case Circuit Breakers Section 6
Types TJK, THJK — Interchangeable Trip, includes Cu/Al Line and Load Lugs, not suitable for reverse feed
Complete Circuit Breaker Terminal Lugs for Front
Includes Line and Load Lugs Connection (Cu/Al)1
Adjustable Instantaneous
Trip Ampere Frame Only Trip Unit Only. Use Product Number
Ampere Range Standard Hi-Break Product w/ Standard and (Order 2
Rating Low High Product Number Product Number Number Hi-Break Frames per pole) Wire Size
600A Frame—Two-Pole
250 750 2500 TJK626250WL THJK626250WL TJK626T250 TCAL432(1) 6-600
300 900 3000 TJK626300WL THJK626300WL TJK626F000 TJK626T300 or
350 1050 3500 TJK626350WL THJK626350WL Standard TJK626T350 (2) 2/0-250 Cu/Al
400 1200 4000 TJK626400WL THJK626400WL Frame TJK626T400
450 1350 4500 TJK626450WL THJK626450WL THJK626F000 TJK626T450 (2) 4/0-350 Cu
500 1500 5000 TJK626500WL THJK626500WL Hi-Break TJK626T500 TCAL63 or
600 1800 6000 TJK626600WL THJK626600WL Frame TJK626T600 (2) 300-500 Al
600A Frame—Three-Pole
250 750 2500 TJK636250WL THJK636250WL TJK636T250 TCAL432(1) 6-600
300 900 3000 TJK636300WL THJK636300WL TJK636F000 TJK636T300 or
350 1050 3500 TJK636350WL THJK636350WL Standard TJK636T350 (2) 2/0-250 Cu/Al
400 1200 4000 TJK636400WL THJK636400WL Frame TJK636T400
450 1350 4500 TJK636450WL THJK636450WL THJK636F000 TJK636T450 (2) 4/0-350 Cu
500 1500 5000 TJK636500WL THJK636500WL Hi-Break TJK636T500 TCAL63 or
600 1800 600 TJK636600WL THJK636600WL Frame TJK636T600 (2) 300-500 Al
600 6000 2000 —— TJK636TM16003
Mag
Only 1800 6000 —— TJK636TM26003
1For optional lugs, see page 6-103.
2Alternate lug for 750 kcmil Cu/Al cable, Product Number TCAL47
3Not UL listed.
Accessories: See pages 6-39 to 6-44 and 6-94 to 6-106.
Industrial Circuit Breakers
125-600A Circuit Breakers
Thermal-Magnetic Trip
J600 Line Circuit Breakers
Types TJJ, TJK, THJK
J600 Reference Publications
Mechanical Interlock GEH-3033
Trip Unit GEH-3035
Bell Alarm GEH-3320
Auxiliary Switch GEH-3321
Three Coil Shunt Trip GEH-3346
Shunt Trip GEH-3435
TDR Operating Mechanism GEH-3450
Plug-in Mounting Base GEH-4342
Motor Operator GEH-4676
TDM Operating Mechanism GEH-5023
STDA Flange Handle GEH-5314
STDA Operating Mechanism GEH-5318
Undervoltage Release GEH-5407
J600 Outline Drawing 455C564SH1
Type THJK - 600V High Break DC Circuit Breakers
Adjustable Instantaneous
Trip Ampere Frame Only Trip Unit Only. Use Product Number
Ampere Range Hi-Break Product w/ Standard and (Order 2
Rating Low High Product Number Number Hi-Break Frames per pole) Wire Size
400A Frame —Three-Pole
200 600 2000 THJK436D200WL TJK436T200
225 675 2250 THJK436D225WL TJK436T225
250 750 2500 THJK436D250WL TJK436T250 (1) 6-600
300 900 3000 THJK436D300WL THJK436D000 TJK436T300 TCAL433or
350 1050 3500 THJK436D350WL TJK436T350 (2) 2/0-250 Cu/Al
400 1200 4000 THJK436D400WL TJK436T400
600A Frame —Three-Pole
250 750 2500 THJK636D250WL TJK636T250 (1) 6-600
300 900 3000 THJK636D300WL THJK636D000 TJK636T300 TCAL433or
350 1050 3500 THJK636D350WL TJK636T350
400 1200 4000 THJK636D400WL TJK636T400 (2) 2/0-250 Cu/Al
TJK636F000
Standard
Frame
THJK636F000
Hi-Break
Frame
TJK626F000
Standard
Frame
THJK626F000
Hi-Break
Frame
TCAL432
TCAL432
TCAL63
TCAL63
(1) 6-600
or
(2) 2/0-250 Cu/Al
(1) 6-600
or
(2) 2/0-250 Cu/Al
(2) 4/0-350 Cu
or
(2) 300-500 Al
(2) 4/0-350 Cu
or
(2) 300-500 Al
www.geindustrial.com BuyLog™Catalog 6-39
Rev. 11/13
Data subject to change
without notice
Molded Case Circuit Breakers Section 6
Internal Accessories
Molded Case Circuit Breakers
Accessory Devices and Ratings
Internally mounted accessories can be either factory or field
installed, but should be factory installed when UL listing is
required.
Factory installed devices with leads exiting from the side are UL
listed, but when leads exit from the back the UL listing is void.
For accessory installation combinations refer to table below.
“Mounting Pole” refers to left-, center- or right-hand pole as seen
when facing the front of the breaker. Control leads may exit the
breaker from its side (S) or back (B)1.
Nonautomatic circuit breakers (molded case switches) require
dummy trip units if internal accessories are to be field installed
(refer to page 6-44). J Frame Circuit Breaker with Internal
Accessories Mounted in Each Pole
R L R L R
TQB, THQB,
THHQB, TXQB,
TQL, THQL,
THHQL, TXQL,
TQC, THQC,
THHQC, TXQC
UL ——————
—————
One accessory only. Mounts
in a one-inch frame and
increase overall breaker size
by one pole. May be applied
to 1-, 2-, or 3-pole breakers.
TQD, THQD UL One accessory only
E150 TEB,
TEC, TED,
THED,
THLC1,
TB15,6,8
7
UL 4576
4
4
UL
3418
Aux
3416
S.T.
3417 —
—
—
8
UL 3434
2-pole circuit breaker—any
one 3-pole circuit breaker—
any two except UVR and
3-coil shunt trip
F225 9
TFC, TFJ, TFK,
THFK, THLC2,
THLC4, TLB2,
TLB4
UL
UL
4620 UL UL 4653 UL UL 4653 8
UL UL 4622 any two
J600 TJC,
TJD, TJJ,
TJK, THJK,
TB45, TBC45
—
——
——— — —
7
UL
——— —
—
8
UL —3320UL UL
3321
Aux
3435
S.T.
5407 8
UL —3346
Any two plus bell alarm except
TB4, TBC4 any one plus bell
alarm .
K1200 TKC,
TKM, THKM
TB65, TBC65
TB8, TBC8
—8
UL —4305UL UL —UL
—UL
—UL
3321
Aux
3344
S.T.
5408 8
UL — 3346 Any two plus bell alarm
Total Number of
Accessories Within any
One Circuit Breaker
Inst.
Sheet
GEH-
Inst.
Sheet
GEH-
Inst.
Sheet
GEH-
Mounting Pole
Undervoltage
Release
Mounting Pole
Three Coil
Shunt Trip
Breaker Type
Mounting Pole
Bell Alarm Switch
Mounting Pole
Auxiliary Switch3
or Shunt Trip
Inst.
Sheet
GEH-
9UL listed interrupting capacity with accessories: 10 kAIC at 600 Vac, 22 kAIC at 480 Vac, 22 kAIC at 240 Vac.
10Leads are #18 125°C Vulkene insulated.
3600 Vac auxiliary switches are not UL listed.
4Accessories are factory installed only.
5UL listed at 200 AIC without internal accessories, 100 AIC with internally mounted accessories.
6Accessories not available for single-pole TEB/TED frame. Use two-pole circuit breaker.
1Except TFC and TFJ, F225 line model 4 frames and trips (mfg. code date J101+ (1981 or later), and THLC2, THLC4, TLB4 are UL listed for
field installation of most accessories.
2Not UL listed.
7Left pole mounting not available for two-pole TEB, TED.
8Not available with lead exit from the back of breaker.
Accessory-Lead
Color Coding10
All accessory contacts shown
with the circuit breaker in
tripped position.
Shunt TripBell Alarm Switch Undervoltage Release Three-Coil Shunt Trip
Auxiliary Switch
LLC R
Purple
Yellow
Brown
Red
White
Brown/white
Black
Black
Blue
Blue
Red
Brown/white
Blue
White
Yellow
Black
Pole Positions
L—Left
C—Center
R—Right
Lead Wire Exit
S—Side
B—Back
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-40
Molded Case Circuit Breakers Section 6
Auxiliary Switches
Unless otherwise noted switch is SPDT rated 6 amperes at rated ac voltage, 1/2 amperes at 125 Vdc, 1/4 amperes at 250 Vdc.
Control Voltage 240 Vac, 250 Vdc Maximum Control Voltage 600 Vac, 250 Vdc Maximum
UL Listed When Factory Installed Suffix1Not UL Listed Suffix1
Number of Add to Base Product Add to Base Product
SPDT Switch Base Number for Factory Base Number for Factory
Breaker Type Elements Number Installation4Number Installation4
TEB, TEC, TB1 1 TEDAS2AB1R,L2,3 S TEDAS6AB1R,L2,3 S
TED, THED,THLC132 TEDAS2AB2R,L2,3 S TEDAS6AB2R,L2,3 S
1 TJKASA2AB1R,L S TJKASA6AB1R,L S
2 TJKASA2AB2R,L S TJKASA6AB2R,L S
TJC, TJD, TJJ, TJK, THJK 3 TJKASA2AB3R,L S TJKASA6AB3R,L S
4 TJKASA2AB4R,L S TJKASA6AB4R,L S
1 TB4ASA2AB1R,L S TB4ASA6AB1R,L S
2 TB4ASA2AB2R,L S TB4ASA6AB2R,L S
TB4, TBC4 3 TB4ASA2AB3R,L S TB4ASA6AB3R,L S
4 TB4ASA2AB4R,L S TB4ASA6AB4R,L S
1 TKMAAS2AB1 RS or LS TKMAAS6AB1 RS or LS
TKM, THKM, TKC, TB6, 2 TKMAAS2AB2 RS or LS TKMAAS6AB2 RS or LS
TB8, TBC6, TBC8 3 TKMAAS2AB3 RS or LS TKMAAS6AB3 RS or LS
4 TKMAAS2AB4 RS or LS TKMAAS6AB4 RS or LS
1"S" suffix for wires out the side of breaker. For lead exit from back of breaker, replace suffix "S" with "B" and multiply list price by 1.25. "B" suffix not UL listed. Not available
with leads out the back for "Q-Line", or 2 element auxiliary switches used on TFG, TFJ, TFK, THFK, THLC2, THLC4, TLB2, and TLB4.
2Auxiliary switch mounts in right pole only on two-pole TEB, TED breakers. (Factory installed only.)
3Not available with “B” suffix–leads out back.
4For factory installation, contact Customer Service Center.
Internal Accessories
Internally Mounted Signaling and Controlling Functions
www.geindustrial.com BuyLog™Catalog 6-41
Rev. 11/13
Data subject to change
without notice
Molded Case Circuit Breakers Section 6
How to Order
For field replacement, order base number only. For factory installation, contact Customer
Service Center and order base number plus appropriate suffix. For a nonautomatic breaker
(molded case switch) a dummy trip is required when installing either a shunt trip or UVR.
Shunt Trip
Remote Tripping – Trips breaker by remote control. Trip coil de-energized when breaker
opens. Device meets UL requirements for service to ground fault system.
Undervoltage Release
Undervoltage release automatically trips breaker when applied coil voltage drops to
30 to 70 percent of rated value. Time-delay unit prevent nuisance tripping due to
momentary loss of voltage. Separate externally mounted unit has 120 Vac input and
125 Vdc output. Used in conjunction with 125 Vdc undervoltage release which must be
ordered separately. Product number SPUVTD for adjustable delay .1 to 1.0 seconds.
Internal Accessories
Internally Mounted Signaling and Controlling Functions
Shunt Trip
Product Number1,2 — UL Listed When Factory Installed
Suffix Number3
Accessory Voltage Base Number Add to Base Product Number
Breaker Type Vac Vdc for Field Replacement for Factory Installation
TQB, THQB, THHQB, TXQB, 120-240 TQSTA14,5,6,7 10
TQL, THQL, THHQL, TXQL 12 TQSTA74,6,7 10
24-48 TQSTA84,6,7 10
120 TQDST18,9 10
240 TQDST29 10
TQD, THQD 12 TQDST79 10
24 TQDST89 10
120 TEDST12 RS
240 TEDST12 RS
480 TEDST13 RS
TEB, TEC, TB1-B11,600 TEDST13 RS
TED, THED, THLC1 12 TEDST7 RS
24 TEDST8 RS
48 TEDST9 RS
125 TEDST12 RS
250 TEDST11 RS
120 TFKSTA121RS or LS
240 TFKSTA121RS or LS
480 TFKSTA131RS or LS
TFC, TFJ, TFK, THFK, THLC2, 600 TFKSTA131RS or LS
THLC4, TLB2, TLB4 12 TFKSTA71RS or LS
24 TFKSTA81RS or LS
48 TFKSTA91RS or LS
125 TFKSTA121RS or LS
250 TFKSTA111RS or LS
1UL listed for field installation on TFC, TFJ, TFK, and THFK model 4 frames and trips (mfg. Code date J101 or later) and on THLC2, THLC4, TLB4.
2For replacement voltage suppressor on 120 Vac UVRs for F225 line, order Product Number 286A8062G1. for 120 Vac UVRs on all other breaker lines, order Product Number
192A8300G1.
3"S" suffix for wires out the side of the breaker. For lead exit from back of breaker, replace suffix "S" with "B", and multiply "S" accessory List Price by 1.25. "B" suffix not UL listed.
Not available with leads out the back on "Q-Line." For factory installation, contact Customer Service Center.
4Mounts on a one-inch frame and increases overall breaker size by one pole added to left side. May be applied to 1-, 2-, or 3-pole breakers. Maximum total breaker width is
4-pole. Must be factory installed.
5A selective listing of breaker product numbers that include 120 Volt ac shunt trip appears on page 6-22.
6Not available on GFCI (5 ma) or Equipment Ground Fault (30 ma) breakers.
7TQST shunt trips not available on breakers over 100 A.
8Not available with “B” suffix–leads out back.
9Must be factory installed, right pole only.
10To order, specify both the accessory and breaker product number =, e.g. THQL2130, TQST1 identifies a 30 A, 2-pole plug-in breaker with a factory installed 120 Vac
shunt trip.
11For TB1 with bolt-on limiters.
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-42
Molded Case Circuit Breakers Section 6
Shunt Trip (continued)
Product Number — UL Listed When Factory Installed
Suffix Number1
Accessory Voltage Base Number Add to Base Product Number
Breaker Type Vac Vdc for Field Replacement for Factory Installation
120 TJKSTA12R,L S
240 TJKSTA12R,L S
480 TJKSTA13R,L S
600 TJKSTA13R,L S
TJC, TJD, TJJ, TJK, THJK 12 TJKSTA7R,L S
24 TJKSTA8R,L S
48 TJKSTA9R,L S
125 TJKSTA12R,L S
250 TJKSTA11R,L S
120 TB4STA12R,L3
240 TB4STA12R,L3
480 TB4STA13R,L3
600 TB4STA13R,L3
TB4, TBC4 12 TB4STA7R,L3
24 TB4STA8R,L3
48 TB4STA9R,L3
125 TB4STA12R,L3
250 TB4STA11R,L3
120 TKMASTA12R,L S
240 TKMASTA12R,L S
480 TKMASTA13R,L S
600 TKMASTA13R,L S
TKC, TKM, THKM, TB6, 12 TKMASTA7R,L S
TB8, TBC6, TBC8224 TKMASTA8R,L S
48 TKMASTA9R,L S
125 TKMASTA12R,L S
250 TKMASTA11R,L S
1"S" suffix for wires out the side of the breaker. For lead exit from back of breaker, replace suffix "S" with "B". "B" suffix not UL listed. Not available with leads out the
back on "Q-Line." For factory installation, contact Customer Service Center.
2Not UL listed.
3Not available for factory installation.
Internal Accessories
Internally Mounted Signaling and Controlling Functions
www.geindustrial.com BuyLog™Catalog 6-43
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Internal Accessories
Internally Mounted Signaling and Controlling Functions
Undervoltage Release
Product Number1,2 — UL Listed When Factory Installed
Suffix Number3
Accessory Voltage Base Number Add to Base Product Number
Breaker Type Vac Vdc for Field Replacement for Factory Installation
120 TEDUV1 RS
240 TEDUV2 RS
480 TEDUV4 RS
TEB, TEC, TB1-B4600 TEDUV6 RS
TED, THED, THLC1 12 TEDUV7 RS
24 TEDUV8 RS
48 TEDUV9 RS
125 TEDUV10 RS
250 TEDUV11 RS
120 TJUV1R S
240 TJUV2R S
480 TJUV4R S
600 TJUV6R S
TJC, TJD, TJJ, TJK, THJK 12 TJUV7R S
24 TJUV8R S
48 TJUV9R S
125 TJUV10R S
250 TJUV11R S
120 TKUV1R S
240 TKUV2R S
480 TKUV4R S
TKC, TKM, THKM, TB6, 600 TKUV6R S
TB8, TBC6, TBC8512 TKUV7R S
24 TKUV8R S
48 TKUV9R S
125 TKUV10R S
250 TKUV11R S
1UL listed for field installation on TFC, TFJ, TFK, and THFK model 4 frames and trips (mfg. Code date J101 or later) and on THLC2, THLC4, TLB4.
2For replacement voltage suppressor on 120 Vac UVRs for F225 line, order Product Number 286A8062G1 for 120 Vac UVRs on all other breaker lines, order
Product Number 192A8300G1.
3"S" suffix for wires out the side of the breaker. For lead exit from back of breaker, replace suffix "S" with "B". "B" suffix not UL listed. For factory installation, contact
Customer Service Center.
4For TB1 with bolt-on limiters.
5Not UL listed.
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-44
Molded Case Circuit Breakers Section 6
Internal Accessories
Internally Mounted Signaling and Controlling Functions
Dummy Trip1
Breaker Type Product Number
E150 Internal accessories for these noninterchangeable
FJ225 breakers require factory-installed dummy trips.
JJ400 Automatically supplied when accessories are ordered.
JK400 TJKYT3 (two-pole, three-pole)
JK600 TJKYT36 (two-pole, three-pole)
KM800 TKMAYT3 (two-pole, three-pole)
1Not UL listed when field installed.
2Add "B" suffix for leads exit from back of breaker. For factory installation, contact
Customer Service Center.
3Not available with “B” suffix – leads out back.
4Not available for two-pole TEB, TED. Order TEDBAR.
5Changes circuit breaker interrupting capacity to: 10kA @ 600 Vac, 22kA @ 480 Vac,
22kA @ 240 Vac, for TFC, TFJ, TFK and THFK only.
6UL listed for field installation.
7Mounts in center pole with leads out left side.
Bell Alarm Switches
Product Number2
Breaker UL Listed When Factory Installed
Type Base No. Suffix
TEB, TEC, TB1 TEDBAR or S
TED, THED, THLC1 TEDBAL3,4
TFC, TFJ, TFK, THFK, TFKBAAR5,6 S
THLC2, THLC4, TLB4
TJC, TJJ, TJK, THJK TJKBAAL7S
TB4, TBC4, TJD
TKC, TKM, THKM, TKMABAAL7S
TB6, TBC6, TBC8, TB8
Blown Fuse Detector-Three-Coil Shunt Trip
Product Number2
Breaker UL Listed When Factory Installed
Type Base No. Suffix
TED, THED, TEC3TEDST316 RS
TJJ, TJK, THJK, TJD, TJC TJKST316 LS
www.geindustrial.com BuyLog™Catalog 6-45
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Spectra™RMS
SE150 Frame
15-150A Circuit Breakers
Electronic Trip
Suitable for Reverse Feed
UL File E-11592, CSA LR 40350
SED, SEH, SEL, SEP2; 2-Pole, 150A, 480 Vac Max., (IEC 947-2: 160A, 415 Vac Max.)
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
UL 489 IC @ 480 Vac
Adjustable Instantaneous 18kA 25kA 65kA 100kA
Ampere Trip Range Amps Product Current Product Product Product Product Product Wire
Rating Low High Number Sensor Number Number Number Number Number Range
15 43 182 SRPE30A15
20 58 254 SRPE30A20 30 SEDA24AT00303SEHA24AT00303SELA24AT00303SEPA24AT00303
25 73 332 SRPE30A25
30 87 415 SRPE30A30
35 104 453 SRPE60A35
40 118 501 SRPE60A40
45 134 583 SRPE60A45 60 SEDA24AT00603SEHA24AT00603SELA24AT00603SEPA24AT0060312-3/0 Cu
50 148 637 SRPE60A50 TCAL18 12-3/0 Al
60 178 777 SRPE60A60
70 206 863 SRPE100A70
80 236 999 SRPE100A80 100 SEDA24AT0100 SEHA24AT0100 SELA24AT0100 SEPA24AT0100
90 267 1138 SRPE100A90
100 297 1280 SRPE100A100
110 328 1426 SRPE150A110
125 374 1640 SRPE150A125 150 SEDA24AT0150 SEHA24AT0150 SELA24AT0150 SEPA24AT0150
150 450 1991 SRPE150A150
SED, SEH, SEL, SEP2; 3-Pole, UL/CSA: 150A, 600 Vac Max., (IEC 947-2: 160A, 690 Vac Max.)
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
UL 489 IC @ 480 Vac
Adjustable Instantaneous 18kA 25kA 65kA 100kA
Ampere Trip Range Amps Product Current Product Product Product Product Product Wire
Rating Low High Number Sensor Number Number Number Number Number Range
15 43 182 SRPE30A15
20 58 254 SRPE30A20 30 SEDA36AT00303SEHA36AT00303SELA36AT00303SEPA36AT00303
25 73 332 SRPE30A25
30 87 415 SRPE30A30
35 104 453 SRPE60A35
40 118 501 SRPE60A40
45 134 583 SRPE60A45 60 SEDA36AT00603SEHA36AT00603SELA36AT00603SEPA36AT00603
50 148 637 SRPE60A50 TCAL18 12-3/0 Cu
60 178 777 SRPE60A60 12-3/0 Al
70 206 863 SRPE100A70
80 236 999 SRPE100A80 100 SEDA36AT0100 SEHA36AT0100 SELA36AT0100 SEPA36AT0100
90 267 1138 SRPE100A90
100 297 1280 SRPE100A100
110 328 1426 SRPE150A110
125 374 1640 SRPE150A125 150 SEDA36AT0150 SEHA36AT0150 SELA36AT0150 SEPA36AT0150
150 450 1991 SRPE150A150
2SEL, SEP UL current limiting.
3When used with 15-50A Rating Plug, UL listed for HID (high intensity discharge).
Note: All Spectra™breakers UL listed as HACR type.
All Spectra™breakers marked CE.
Product Number Structure
SEDA24AT0030
Frame Rating Interruption Continuous Voltage Trip Trip Sensor
Family (Amperes) Rating (480V) Load Rating Poles Rating Unit Function (Max Amps)
S= Spectra™E= 150 D= 18 kA A= Standard 2= 2 poles 4= 480V A= RMS1 T= LSI10030
H= 25 kA 3= 3 poles 6= 600V 0060
L= 65 kA 0100
P= 100 kA 0150
1Adjustable Instantaneous with Tracking Short Time (Long Time established via Interchangeable Rating Plugs).
Note: This information is provided for interpreting product numbers (it should not be used to build product numbers).
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-46
Molded Case Circuit Breakers Section 6
SE150 Add-on 3-Pole Limiters
Maximum Product kAIC Use With Breaker/
Ampere Rating Number @600 Vac MCP Frame
150 SAXSEL36150 65 SEL
150 SAXSEP36150 100 SEP
Spectra™RMS
SE150 Frame
15-150A Circuit Breakers
Electronic Trip
Suitable for Reverse Feed
UL File E-11592, CSA LR 40350
Reference Publications
Available for download from www.geindustrial.com/publibrary
SE Breaker
Installation Instructions GEH-5591
Rating Plug GEH-5549
SE Breaker Accessories
Bell Alarm & Aux. Switch GEH-5593
Shunt Trip & UVR GEH-5551
Padlock Device GEJ-3056
Lug Kits GEJ-3051
Control Wire Lug Kit GEH-5881
Add-On Limiters DEH-4671
STDA Flange Handle GEH-5314
STDA Operating Mechanism GEH-5684
TDR Operating Mechanism GEH-5609
TDM Operating Mechanism GEH-5611
Motor Operator GEH-5613
Cable Operator Mechanism GEH-6290
Operator Adapter Kits GEH-5688
Mechanical Interlock GEH-5615
Warning Labels GEH-5686
SE Mounting Provisions
Plug-in Mounting Base GEH-4610
Back Connected Studs GEJ-3609
Outline Drawing 168D1109SH1
Series Ratings DET-008
Spectra™RMS Circuit Breakers in Combination with
Cooper Bussman Distribution Block DET-781
www.geindustrial.com BuyLog™Catalog 6-47
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
SFH, SFL, SFP2; 2-Pole, UL/CSA: 250A, 480 Vac Max., (IEC 947-2: 250A, 415 Vac Max.)
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
Adjustable Instantaneous
UL 489 IC @ 480 Vac
Trip Ampere Range
35kA 65kA 100kA
Ampere Product Current Product Product Product Product Wire
Rating Low High Number Sensor Number Number Number Number Range
70 205 700 SRPF250A70
80 235 800 SRPF250A80
90 265 900 SRPF250A90
100 295 1000 SRPF250A100
110 325 1100 SRPF250A110 8-350 Cu
125 370 1250 SRPF250A125 250 SFHA24AT0250 SFLA24AT0250 SFPA24AT0250 TCAL29
150 440 1500 SRPF250A150 8-350 Al
175 515 1750 SRPF250A175
200 590 2000 SRPF250A200
225 665 2250 SRPF250A225
250 736 2500 SRPF250A250
SFH, SFL, SFP2; 3-Pole, UL/CSA: 250A, 600 Vac Max., (IEC 947-2: 250A, 690 Vac Max.)
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
Adjustable Instantaneous
UL 489 IC @ 480 Vac
Trip Ampere Range
35kA 65kA 100kA
Ampere Product Current Product Product Product Product Wire
Rating Low Hi gh Number Sensor Number Number Number Number Range
70 205 700 SRPF250A70
80 235 800 SRPF250A80
90 265 900 SRPF250A90
100 295 1000 SRPF250A100
110 325 1100 SRPF250A110 8-350 Cu
125 370 1250 SRPF250A125 250 SFHA36AT0250 SFLA36AT0250 SFPA36AT0250 TCAL29
150 440 1500 SRPF250A150 8-350 Al
175 515 1750 SRPF250A175
200 590 2000 SRPF250A200
225 665 2250 SRPF250A225
250 736 2500 SRPF250A250
2SFL, SFP UL current limiting.
Note: All Spectra™breakers UL listed as HACR type.
All Spectra™breakers marked CE.
Spectra™RMS
SF250 Frame
70-250A Circuit Breakers
Electronic Trip
Suitable for Reverse Feed
UL File E-11592, CSA LR 40350
Product Number Structure
SFHA24AT0250
Frame Rating Interruption Continuous Voltage Trip Trip Sensor
Family (Amperes) Rating (480V) Load Rating Poles Rating Unit Function (Max Amps)
S= Spectra™F= 250 H= 35 kA A= Standard 2= 2 poles 4= 480V A= RMS1 T= LSI10250
L= 65 kA 3= 3 poles 6= 600V
P= 100 kA
1Adjustable Instantaneous with Tracking Short Time (Long Time established via Interchangeable Rating Plugs).
Note: This information is provided for interpreting product numbers (it should not be used to build product numbers).
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-48
Molded Case Circuit Breakers Section 6
Spectra™RMS
SF250 Frame
70-250A Circuit Breakers
Electronic Trip
Suitable for Reverse Feed
UL File E-11592, CSA LR 40350
Reference Publications
Available for download from www.geindustrial.com/publibrary
SF Breaker
Installation Instructions GEH-5591
Rating Plug GEH-5549
SF Breaker Accessories
Bell Alarm & Aux. Switch GEH-5593
Shunt Trip & UVR GEH-5551
Padlock Device GEJ-3056
Lug Kits GEJ-3045
Control Wire Lug Kit GEH-5882
STDA Flange Handle GEH-5314
STDA Operating Mechanism GEH-5684
TDR Operating Mechanism GEH-5609
TDM Operating Mechanism GEH-5611
Motor Operator GEH-5613
Cable Operator Mechanism GEH-6290
Operator Adapter Kits GEH-5688
Mechanical Interlock GEH-5615
Mounting Hardware Kits GEH-5659
SF Mounting Provisions
Plug-in Mounting Base GEH-4610
Back Connected Studs GEJ-3635
Outline Drawing 168D1103SH1
Series Ratings DET-008
Spectra™RMS Circuit Breakers in Combination with
Cooper Bussman Distribution Block DET-781
www.geindustrial.com BuyLog™Catalog 6-49
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
SGD; 400A, 240 Vac Max., (IEC 947-2: 400A, 690 Vac Max.)
Rating Plug Frame Terminal Lugs for
Front Connection (Cu/Al)
240 Vac
Adjustable Instantaneous 65kA
Ampere Trip Ampere Range Product Current Product Product4Wire
Rating Low High Number Sensor Poles Number Number Range
125 380 1275 SRPG400A125 2-pole lug kit
150 455 1530 SRPG400A150 (2) 2/0-500 Cu
175 530 1785 SRPG400A175 2 SGDA22AT04003TCLK265 or
200 605 2040 SRPG400A200 (1) 8-600 Cu
225 680 2295 SRPG400A225 400
250 755 2550 SRPG400A250 3-pole lug kit
300 905 3060 SRPG400A300 3 SGDA32AT04003(2) 2/0-500 Al
350 1060 3570 SRPG400A350 TCLK365 or
400 1210 4080 SRPG400A400 (1) 8-600 Al
SGH, SGL, SGP5; 400A, 600 Vac Max., (IEC 947-2: 400A, 690 Vac Max.)
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
UL 489 IC @ 480 Vac
Adjustable Instantaneous 35kA 65kA 100kA
Ampere Trip Ampere Range Product Current Product Product Product Product4Wire
Rating Low High Number Sensor Poles Number Number Number Number Range
125 380 1275 SRPG400A125 2-pole lug kit
150 455 1530 SRPG400A150 (2) 2/0-500 Cu
175 530 1785 SRPG400A175 2 SGHA26AT0400 SGLA26AT0400 SGPA26AT0400 TCLK265 or
200 605 2040 SRPG400A200 (1) 8-600 Cu
225 680 2295 SRPG400A225 400
250 755 2550 SRPG400A250 3-pole lug kit
300 905 3060 SRPG400A300 3 SGHA36AT0400 SGLA36AT0400 SGPA36AT0400 (2) 2/0-500 Al
350 1060 3570 SRPG400A350 TCLK365 or
400 1210 4080 SRPG400A400 (1) 8-600 Al
SGH, SGL5, SGP5; 600A, 600 Vac Max., (IEC 947-2: 630A, 690 Vac Max.)
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
UL 489 IC @ 480 Vac
Adjustable Instantaneous 35kA 65kA 100kA
Ampere Trip Ampere Range Product Current Product Product Product Product4Wire
Rating Low High Number Sensor Poles Number Number Number Number Range
250 765 2530 SRPG600A250 2-pole lug kit
300 915 3035 SRPG600A300 2 SGHA26AT0600 SGLA26AT0600 SGPA26AT0600 (2) 2/0-500 Cu
350 1070 3545 SRPG600A350 TCLK265 or
400 1220 4050 SRPG600A400 600 (1) 8-600 Cu
450 1375 4555 SRPG600A450 3-pole lug kit
500 1525 5060 SRPG600A500 3 SGHA36AT0600 SGLA36AT0600 SGPA36AT0600 (2) 2/0-500 Al
600 1830 6075 SRPG600A600 TCLK365 or (1) 8-600 Al
3Rated 240 Vac max.
4Order one kit for either line or load end; two kits required for both.
5SGL, SGP UL current limiting.
Note: All Spectra™breakers UL listed as HACR type. All Spectra™breakers marked CE.
Spectra™RMS
SG600 Frame
125-600A Circuit Breakers
Electronic Trip (Digital, Solid-State)
Suitable for Reverse Feed
UL File E-11592, CSA LR 40350
Product Number Structure SGDA22AT0400
Frame Rating Interruption Continuous Voltage Trip Trip Sensor
Family (Amperes) Rating (480V) Load Rating Poles Rating Unit Function (Max Amps)
S= Spectra™G= 600 D= 65 kA1A= Standard 2= 2 poles 2= 240V A= RMS1 T= LSI20400
H= 35 kA H= 100% 3= 3 poles 6= 600V 0600
L= 65 kA L= 100%
P= 100 kA P= 100%
1SGD rated 65kA at 240V.
2Adjustable Instantaneous with Tracking Short Time (Long Time established via Interchangeable Rating Plugs).
Note: This information is provided for interpreting product numbers (it should not be used to build product numbers).
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-50
Molded Case Circuit Breakers Section 6
SGH, SGL2, SGP2; 100% UL Rated, 3-Pole: 600A, 600 Vac Max.; (IEC 947-2: 630A, 690 Vac Max.)
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
UL 489 IC @ 480 Vac
Adjustable Instantaneous 35kAIC 65kAIC 100kAIC
Ampere Trip Ampere Range Product Current Product Product Product Product1Wire
Rating Low High Number Sensor Poles Number Number Number Number Range
250 765 2530 SRPG600A250
300 915 3035 SRPG600A300 (2) 2/0-500 Cu
350 1070 3545 SRPG600A350 or (1) 8-600 Cu
400 1220 4050 SRPG600A400 600 3 SGHH36AT0600 SGLL36AT0600 SGPP36AT0600 TCLK365
450 1375 4555 SRPG600A450 (2) 2/0-500 Al
500 1525 5060 SRPG600A500 (1) 8-600 Al
600 1830 6075 SRPG600A600
Spectra™RMS
SG600 Frame, 100% Rated
125-600A Circuit Breakers
Electronic Trip (Digital, Solid-State)
Suitable for Reverse Feed
UL File E-11592, CSA LR 40350
SGH, SGL2, SGP2; 100% UL Rated, 3-Pole: 400A, 600 Vac Max.; (IEC 947-2: 400A, 690 Vac Max.)
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
UL 489 IC @ 480 Vac
Adjustable Instantaneous 35kAIC 65kAIC 100kAIC
Ampere Trip Ampere Range Product Current Product Product Product Product1Wire
Rating Low High Number Sensor Poles Number Number Number Number Range
125 380 1275 SRPG400A125
150 455 1530 SRPG400A150 (2) 2/0-500 Cu
175 530 1785 SRPG400A175 or
200 605 2040 SRPG400A200 (1) 8-600 Cu
225 680 2295 SRPG400A225 400 3 SGHH36AT0400 SGLL36AT0400 SGPP36AT0400 TCLK365
250 755 2550 SRPG400A250
300 905 3060 SRPG400A300 (2) 2/0-500 Al
350 1060 3570 SRPG400A350 or
400 1210 4080 SRPG400A400 (1) 8-600 Al
1Order one kit for either line or load end; two kits required for both.
2SGL, SGP UL current limiting.
Note: All Spectra
™
breakers UL listed as HACR type.
All Spectra
™
breakers marked CE.
www.geindustrial.com BuyLog™Catalog 6-51
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Spectra™RMS
SG600 Frame
125-600A Circuit Breakers
Electronic Trip (Digital, Solid-State)
Suitable for Reverse Feed
UL File E-11592, CSA LR 40350
Reference Publications
Available for download from www.geindustrial.com/publibrary
SG Breaker
Installation Instructions GEH-5663
Rating Plug GEH-5549
MVT & MVT Plus PM Rating Plugs GEH-5887
SG Breaker Accessories
Bell Alarm & Aux. Switch GEH-5593
Shunt Trip & UVR GEH-5551
Lug Kits GEJ-3052
Trip Unit Covers GEH-5664
Door Ring Interlock Catch Kits GEH-5662
STDA Flange Handle GEH-5314
STDA Operating Mechanism GEH-5684
TDR Operating Mechanism GEH-5654
TDM Operating Mechanism GEH-5653
Motor Operator GEH-5657
Cable Operator Mechanism GEH-6290
Cable Operators DEH-40467
Mechanical Interlock GEH-5697
SG Mounting Provisions
Plug-in Mounting Base GEH-5655
Back Connected Studs GEH-5665
Outline Drawing 208C1549SH1, 2, 3
Series Ratings DET-008
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-52
Molded Case Circuit Breakers Section 6
SKH, SKL, SKP; 800A, 600 Vac Max., (IEC 947-2:800A 690 Vac Max.)
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
UL 489 IC @ 480 Vac
Adjustable Instantaneous 50kA 65kA 100kA
Ampere Trip Ampere Range Product Current Product Product Product Product Wire
Rating Low High Number Sensor Poles Number Number Number Number Range
300 940 3015 SRPK800A300
400 1255 4015 SRPK800A400 2 SKHA26AT0800 SKLA26AT0800 SKPA26AT0800 (3) 3/0-500 Cu
500 1570 5020 SRPK800A500 800 TCAL81
600 1875 6195 SRPK800A600
700 2155 7420 SRPK800A700 3 SKHA36AT0800 SKLA36AT0800 SKPA36AT0800 (3) 3/0-500 Al
800 2440 8705 SRPK800A800
SKH, SKL, SKP; 1200A, 600 Vac Max., (IEC 947-2: 1250A, 690 Vac Max.)
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
UL 489 IC @ 480 Vac
Adjustable Instantaneous 50kA 65kA 100kA
Ampere Trip Ampere Range Product Current Product Product Product Product Wire
Rating Low High Number Sensor Poles Number Number Number Number Range
600 1825 6110 SRPK1200A600
700 2125 7125 SRPK1200A700 2 SKHA26AT1200 SKLA26AT1200 SKPA26AT1200 (4) 250-500 Cu
800 2430 8145 SRPK1200A800 1200 TCAL125
900 2735 9160 SRPK1200A900
1000 3040 10180 SRPK1200A1000 3 SKHA36AT1200 SKLA36AT1200 SKPA36AT1200 (4) 250-500 Al
1175 3574 11961 SRPK1200A1175
1200 3650 12215 SRPK1200A1200
Note: All Spectra™breakers UL listed as HACR type.
All Spectra™breakers marked CE.
Spectra™RMS
SK 1200 Frame
300-1200A Circuit Breakers
Electronic Trip, Digital, Solid-State
Suitable for Reverse Feed
UL File E-11592, CSA LR 40350
Product Number Structure
SKHA26AT0800
Frame Rating Interruption Continuous Voltage Trip Trip Sensor
Family (Amperes) Rating (480V) Load Rating Poles Rating Unit Function (Max Amps)
S= Spectra™K= 1200 H= 50 kA A= Standard 2= 2 poles 6= 600V A= RMS1 T= LSI10800
L= 65 kA H= 100% 3= 3 poles 1200
P= 100 kA L= 100%
P= 100%
1Adjustable Instantaneous with Tracking Short Time (Long Time established via Interchangeable Rating Plugs).
Note: This information is provided for interpreting product numbers (it should not be used to build product numbers).
www.geindustrial.com BuyLog™Catalog 6-53
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Spectra™RMS
SK 1200 Frame, 100% Rated
300-1200A Circuit Breakers
Electronic Trip, Digital, Solid-State
Suitable for Reverse Feed
UL File E-11592, CSA LR 40350
SKH, SKL, SKP; 100% UL Rated, 3-Pole: 800A, 600 Vac Max.; (IEC 947-2: 800A, 690 Vac Max.)
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
UL 489 IC @ 480 Vac
Adjustable Instantaneous 50kA 65kA 100kA
Ampere Trip Ampere Range Product Current Product Product Product Product Wire
Rating Low High Number Sensor Poles Number Number Number Number Range
300 940 3015 SRPK800A300
400 1255 4015 SRPK800A400 (3) 3/0-500 Cu
500 1570 5020 SRPK800A500 800 3 SKHH36AT0800 SKLL36AT0800 SKPP36AT0800 TCAL81
600 1875 6195 SRPK800A600 (3) 3/0-500 Al
700 2155 7420 SRPK800A700
800 2440 8705 SRPK800A800
SKH, SKL, SKP; 100% UL Rated, 3-Pole: 1200A, 600 Vac Max.; (IEC 947-2: 100A, 690 Vac Max.)
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
UL 489 IC @ 480 Vac
Adjustable Instantaneous 50kA 65kA 100kA
Ampere Trip Ampere Range Product Current Product Product Product Product Wire
Rating Low High Number Sensor Poles Number Number Number Number Range
600 1825 6110 SRPK1200A600
700 2125 7125 SRPK1200A700 3 SKHH36AT1000 SKLL36AT1000 SKPP36AT1000 (4) 250-500 Cu
800 2430 8145 SRPK1200A800 1200 TCAL125
900 2735 9160 SRPK1200A900 (4) 250-500 Al
1000 3040 10180 SRPK1200A1000 3 SKHH36AT12001SKLL36AT12001SKPP36AT12001
1200 3650 12215 SRPK1200A1200
1100% UL rated SK1200 supplied with back-
connected assembly which increases breaker
depth. Refer to outline drawings for details.
Lugs not required
Note: All Spectra™breakers UL listed as HACR type.
All Spectra™breakers marked CE.
Reference Publications
Available for download from www.geindustrial.com/publibrary
SK Breaker
Installation Instructions GEH-5592
Rating Plug GEH-5549
MVT & MVT Plus PM Rating Plugs GEH-5887
SG Breaker Accessories
Bell Alarm & Aux. Switch GEH-5593
Shunt Trip & UVR GEH-5551
Lug Shields for SK1200 GEH-5699
Lug Shields for SKP GEH-5685
Trip Unit Covers GEH-5664
Mounting of Integral Handle GEH-5610
STDA Flange Handle GEH-5314
STDA Operating Mechanism GEH-5684
TDM Operating Mechanism GEH-5612
Coupling TDM Operating Mechanisms GEH-5873
Motor Operator GEH-5614
Cable Operator Mechanism GEH-6291
Handle Extension GEH-5648
Padlocking Device - Standard GEH-5877
Face Mounted Interlock GEH-5698
Mechanical Interlock GEH-5874
SK Mounting Provisions
Plug-in Mounting Base GEH-4342
Back Connected Studs GEJ-3619
Outline Drawing 208C1757SH1
Outline Drawing (1200A 100%) 168D1678SH2
Series Ratings DET-008
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-54
Molded Case Circuit Breakers Section 6
microEntelliGuard™Trip Unit
The microEntelliGuard™trip unit is the newest and most advanced
trip unit available in the Spectra™line of molded case circuit
breakers. The trip unit design is based on the EntelliGuard™TU trip
unit platform. The microEntelliGuard™trip unit incorporates the
advanced features and protective functions available on the
EntelliGuard™TU trip unit and is available in the 600-amp
Spectra™G and 1200-amp Spectra™K frames. Spectra™breakers
with microEntelliGuard™trip units allow you to select the
enhanced system protection, coordination, metering and commu-
nication options required for the application and allow a fully
coordinated and integrated electrical system across GE’s entire
line of molded case, insulated case and low voltage circuit break-
ers. Spectra™breakers with microEntelliGuard™trip units use all of
the same power management system accessories as the
MicroVersaTrip™PM trip units (some new power management
accessories are available for breakers that incorporate some of
the new features offered with the microEntelliGuard™trip unit).
Standard Features
—Adjustable Long-Time pickup and delay bands with three curve
shapes (MVT I2t, CB and Fuse I4t) for optimal system coordina-
tion (includes thermal memory for enhanced system protection)
—Adjustable Short-Time pickup with multiple delay bands, curve
slopes, I2t IN/OUT, and OFF setting
—Adjustable Instantaneous pickup
—3-Phase ammeter
—Backlit LCD display with five-button tactile keypad for function
selection and set point adjustment and sealable, clear LEXAN
cover for tamper resistant settings
—LED Status Indicator to show “health” of trip unit
—Trip Target indication and local pickup warning signal
—Interchangeable/Universal rating plugs
—Test set jack for GTUTK20 test kit
—True RMS current sensing for accurate response to high
harmonic content waveforms
—EMI immunity per ANSI C37.90
Industrial Circuit Breakers
Spectra™RMS Circuit Breakers with
microEntelliGuard™Trip Units
Optional Features
—Ground Fault (Trip or Alarm) pickup and delay bands with
multiple slopes, I2t IN/OUT for optimal system coordination
—Neutral Protection provides overload protection on the system
neutral
—Zone Selective Interlocking (ZSI) capability on Short Time,
Ground Fault and Instantaneous settings for optimal system
coordination and selectivity
—Reduced Energy Let-Through (RELT) setting for enhanced
equipment and personnel protection
—Advanced metering option includes the ability to monitor
current, voltage, energy, frequency, power factor, power
(real/reactive/apparent) and peak power demand
—Modbus communications system with user selectable address
assignment for communication directly with EnerVista Viewpoint
power system monitoring software
—Waveform capture for enhanced system diagnostics
—Protective Relays that are user selectable in any combination
—Voltage Unbalance
—Current Unbalance
—Under Voltage
—Over Voltage
—Power Reversal
—Load Alarm
—Input relay for RELT signal or remote tripping of the breaker
—Two programmable output relays for enhanced signaling and
diagnostics
—Control Power option provides connection capability for +24Vdc
control power via the distribution cable system
Other Features
—UL Listed for reverse feed and HACR type (standard)
—UL Listed 100% continuous current rating (optional)
—UL Listed Current Limiting (optional on SG Frame)
—Internal Accessories (Shunt Trip, Undervoltage Release, Auxiliary
Contacts, Bell Alarm) – UL Listed for field installation and
common across the entire line of Spectra™RMS breakers
Spectra™SG600 and SK1200 breakers
with microEntelliGuard™Trip Units
www.geindustrial.com BuyLog™Catalog 6-55
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Industrial Circuit Breakers
Spectra™RMS Circuit Breakers with
microEntelliGuard™Trip Units
microEntelliGuard™Trip Unit Characteristics
Ground Fault
Long Time (C) Short Time Instantaneous & Reduced Energy Let-Through (Trip or Alarm)
0.50 to 1.00 1.5 to 9.0 SK-H, L, P = 2.0 to 10.0 - Instantaneous 0.4 to 1.0
in increments of 0.05 in increments of 0.5 1.5 to 10.0 - RELT in increments of 0.05
(X, multiples of rating plug amps) (multiples of current setting C) in increments of 0.5 (multiples of current sensor amps S)
Pickup Settings (X, multiples of current sensor amps)
Breaker Sensor Ampere INST
800 2.0 to 25.5
SKS, SKT 1000 2.0 to 20.5
1200 2.0 to 17.0
Delay Bands11-12 (.07 to .49) 2-15 (.06 to .92)
Settings (seconds)
0 - I2t out 0 - definite time
Slope/Shape 1 - low 1 - I2t
2 - med 2 - selective ground fault
3 - high 3 - fuse shape (I4t)
X = Rating Plug Amperes
S = Sensor Ampere Rating
C = Long Time Current Setting Pickup = LT pickup setting x Rating Plug Amperes “X”
1Delay Bands shown at 600% of current setting at lower limit of each band
2Maximum setting not available on SG
Note: See section 28 for microEntelliGuard™time-current curves
MVT 1-4 (I2t) (2.4, 4.9, 9.8, 202)
C1-C10 (thermal) (.2 to 9.6,15.42)
F1-F7 (I4t) (.02 to 0.9)
Spectra™RMS Circuit Breakers with microEntelliGuard™Trip Units
Last Digit of Catalog Number Equals >>> X2 6 8Advanced Features and Communications
•• Metering (Basic)
••Metering (Advanced)
•••Modbus
••Waveform Capture
Functions Accuracy and Description • Protective Relays
Current (A) Amps ± 4% Phase Selectable •• • •
Voltage (V) Volts ± 2% L-L or L-N and Phase Selectable ••
Real Power (kW) kWatts ± 6% L-L or L-N ••
Reactive Power (kVAR) kVAR ± 4% L-L or L-N ••
Apparent Power (kVA) kVA ± 4% L-L or L-N ••
Peak Power Demand (kW) kWatts ± 4% ••
Energy (kWh/MWh) kWh ± 7% ••
Frequency (Hz) ± 1 Hz ••
Power Factor (%) ± 7% max ••
Communications EnerVista Viewpoint (Modbus) •••
Waveform Capture COMTRADE file format ••
Voltage Unbalance Relay Adjustable Pickup 10 to 50%
Adjustable Delay 1 to 15 sec or OFF •
Current Unbalance Relay Adjustable Pickup 10 to 50%
Adjustable Delay 1 to 15 sec or OFF •
Under Voltage Relay Adjustable Pickup 50 to 90%
Adjustable Delay 1 to 15 sec or OFF •
Over Voltage Relay Adjustable Pickup 110 to 150%
Adjustable Delay 1 to 15 sec or OFF •
Power Reversal Relay Adjustable Pickup 10 to 990 KW
Adjustable Delay 1 to 15 sec or OFF •
Load Alarm Relay ON 0.55 to 1.00 x LT
OFF 0.50 to 0.95 x LT •
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-56
Molded Case Circuit Breakers Section 6
Industrial Circuit Breakers
Spectra™RMS Circuit Breakers with
microEntelliGuard™Trip Units
How to Order
—Select the appropriate breaker frame on the following pages
taking into consideration the maximum ampere rating, the
interrupt rating, whether or not a 100% rating is required,
standard protection functions (LSI, LSIG, LSIA), advanced protec-
tion functions (Neut. Prot., ZSI, RELT), and advanced features and
communications (basic or advanced metering, communications,
waveform capture, protective relays)
—Select the rating plug and breaker lugs from the tables provided.
—Select the required power management system accessories.
—Select other accessories as required (such as an auxiliary switch
or shunt trip).
—When ordering, specify separate product numbers for each item
Ordering Example
SG600 ampere frame, standard load rating and 400 maximum
ampere rating, 350 amp rating plug with line and load lugs. Trip
functions to include adjustable long-time (L), short-time (S),
instantaneous (I), ground fault alarm (A), reduced energy let-
through (RELT), and advanced metering, communications,
waveform capture and protective relays. Metering and communi-
cations of voltage, current, power and breaker contact position
are required. Local RELT enable is also required. The available
system voltage is 480/277 Vac 3 phase/4-wire with an available
fault current of 65kAIC. Power management accessories are to be
mounted on plates with all of the necessary fuse protection,
potential transformers, control power transformers, and required
interconnect accessories. The required circuit breaker Product
Number is SGLC3604L5R8.
Description Product Number
Breaker Prefix SGLC3604L5_ _
Adder 1 for R (RELT)
Adder 2 for 8
(Adv Meter/Modbus/WFC/Relay)
Complete Breaker SGLC3604L5R8
Rating Plug GTP0350U0408
Lug Kits (2) TCLK365
Auxiliary Switch SAUXGAB1
RELT Switch Kit GTURSK
Power Supply Plate SPSA480
Voltage Conditioner Plate SVCA480Y
Advanced J-Box SDCJBBC
Distribution Cable Harness (2) SDCHA11
400A Neutral CT TSRG204
RELT
Breaker
Cable
Junction
Box
Neutral
Current
Sensor
To Other Junction Boxes
To
Breaker
From
Breaker
Communications
(ZSI)
PC 1
PC 2
TIM 1
TIM 1
To Voltage Module
Distribution
Cable Harness
Aux. Switch
microEntelliGuard™
Molded-Case
Circuit
Breaker
Trip Unit Function Definitions
Long-Time (L) Adjustable current setting
Adjustable long-time delay - three curve shapes
(MVT I2t, CB and Fuse I4t)
Short-Time (S) Adjustable short-time pickup (can also be turned OFF)
Adjustable short-time delay - multiple slope options
I2t IN or OUT
Instantaneous (I) Adjustable instantaneous pickup
Ground Fault (G) Adjustable ground fault pickup
Ground Fault Alarm (A) Adjustable ground fault delay - multiple slope options
with I2t IN or OUT
Control Power (CP) +24Vdc control power connection
Trip Indication Targets Standard
Neutral Protection Adjustable current setting on Neutral: multiple of
Long-Time setting
ZSI (ST/GF/INST) Adjustable Zone Selective Interlock settings for
Short-Time, Ground Fault, and Instantaneous
RELT Adjustable Instantaneous: Reduced Energy
Let-Through mode
Metering (basic) Amperes (A/kA) - Phase selectable
Metering (advanced) Current (A/kA) - Phase selectable
Voltage (V) - L-L or L-N and Phase selectable
Real Power (kW) - L-L or L-N
Reactive Power (kVAR) - L-L or L-N
Apparent Power (kVA) - L-L or L-N
Peak Power Demand (kW)
Energy (kWh/MWh)
Frequency (Hz)
Power Factor (%)
Communications Modbus with user selectable address assignment
Compatible with EnerVista Viewpoint power system
monitoring software
Waveform Capture Stores 8 cycles of data on trip or signal
(COMTRADE file format)
Protective Relay Functions Voltage Unbalance - pickup/delay/OFF
Current Unbalance - pickup/delay/OFF
Under Voltage - pickup/delay/OFF
Over Voltage - pickup/delay/OFF
Power Reversal - pickup/delay/OFF
Load Alarm - pickup (ON)/OFF
Other Features/Functions
HMI - Backlit LCD display & Ease of programming and viewing status/
5-button keypad metering displays, tactile feel
LED Status Indicator Visual display of trip unit’s “health”
Visual pickup waring signal For quick diagnostics and pre-trip detection
Sealable LEXAN cover for Tamper resistant settings
tamper resistant settings
Test set jack for GTURSK test kit Fully integrated with GTURSK test kit
Long Time Thermal Memory For enhanced system protection
Input Relay1Dedicated if RELT enabled or set to TRIP/OFF
Qty (2) Programmable Output Contacts1RELT (dedicated)
Ground Fault Alarm
Overcurrent Trip
Protective Relay Trip
Load Alarm
Health Status
1Included on breakers with 20-pin output harness
www.geindustrial.com BuyLog™Catalog 6-57
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Spectra™microEntelliGuard™
Reference Publications
Molded Case Circuit Breaker Accessories -
Distribution Cable Junction Box SDCJBB DEH-006
Spectra™G Breaker w/
microEntelliGuard™Trip Unit GEH-700
Spectra™K Breaker w/
microEntelliGuard™Trip Unit GEH-701
microEntelliGuard™Trip Unit Users Manual GEH-702
Universal Rating Plug DEH-41318
Voltage Module GEH-6250
Power Supply Plate GEH-6251
Voltage Conditioner Plate GEH-6252
Power Supply Assembly GEH-6253
Voltage Conditioner Assembly GEH-6254
microEntelliGuard™Jump Start
Programming Instructions GEH-703
MET Advanced Distribution Cable Junction Box GEH-704
Distribution Cable Junction Box DEH-006
MET Distribution Cable Extension (20-pin) GEH-705
Distribution Cable Extension (12-pin) GEH-6256
Distribution Cable Harness (12-pin) GEH-6255
MET Distribution Cable Terminal Blocks
(11 point & 22 point) GEH-706
Distribution Cable Terminal Block (11 point) GEH-6257
MET Sealable Cover Kits GEH-707
GTU Digital Test Kit (GTUTK20) DEH-4568
Shunt Trip and UVR Instructions GEH-5551
Aux Switch and Bell Alarm GEH-5593
Spectra™RMS Molded Case Circuit Breaker
Accessories - Door Ring Interlock Catch Kits GEI-70594
TIM-1 Zone Selective Interlock Module GEK-64467
Industrial Circuit Breakers
Spectra™RMS Circuit Breakers with
microEntelliGuard™Trip Units
Feature Benefit
Enhanced adjustability and flexibility Enhanced system protection via tight coordination with upstream •• •
of time current curve shape, slope, and delay bands and downstream devices including fuses
Ground Fault Trip or Alarm Enhanced system and asset protection - especially for process driven applications ••
Zone Selective Interlock (ST/GF) System protection ••
Zone Selective Interlock (Instantaneous) Maximum system protection, coordination, and selectivity •••
Reduced Energy Let-Through Enhanced system and personnel protection •••
Protective Relay Functions Enhanced system and asset protection via a suite of protective relays •
Neutral Protection Protection on heavy harmonic loads •
Sealable LEXAN Trip Unit Cover Prevents unauthorized trip unit setting changes for maximum system, personnel, ••
and asset protection.
Long Time Thermal Memory Enhanced system protection •
Input Relay1System and asset protection via remote trip (dedicated if RELT enabled) •
Programmable Output Contacts1Maximize system uptime via signaling on GF alarm, overcurrent trip, protective relay trip, ••
load alarm or health status
Advanced Metering System performance monitoring and diagnostics of critical current, voltage, • •
and power characteristics
Modbus Communications System performance monitoring, reporting and diagnostics (compatible with •••
EnerVista Viewpoint power system monitoring software)
Test Set Jack for GTUTK20 Test Kit Maximize system uptime and enhanced diagnostics via the GTUTK20 test kit •
Trip Indication Targets Visual Trip indication for quick diagnostic evaluation •
Event Log Records last 10 trip events •
Waveform Capture Enhanced diagnostic feature to maximize system uptime •
HMI - Backlit LCD Display and 5-button Keypad Ease of programming and viewing status/metering displays •
LED Status Indicator Enhanced diagnostic feature to maximize system uptime •
(visual display of trip unit’s “health”)
Visual Pickup Warning Signal For quick diagnostics and pre-trip detection •
1Included on breakers with 20-pin output harness
System/Asset Protection
Long Time and Short Time
Coordination
Instantaneous Selectivity
Arc Flash
System Performance
Diagnostics/Reliability
microEntelliGuard™Trip Unit Feature and Benefit Summary
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-58
Molded Case Circuit Breakers Section 6
Product Number Structure
Industrial Circuit Breakers
60-600A Circuit Breakers
Electronic Trip
Spectra™RMS
SG600 with microEntelliGuard™Trip Units1
SGHC3 601 L3 XX
Advanced Protection Functions
X= None
K= Neutral Protection
Z= ZSI (ST/GF)
T= ZSI (ST/GF/INST)
R= RELT
L= ZSI (ST/GF) + RELT
M= ZSI (ST/GF) +
Neutral Protection
N= ZSI (ST/GF) + RELT +
Neutral Protection
V= RELT + Neutral Protection
P= ZSI (ST/GF/INST) + RELT
S= ZSI (ST/GF/INST) +
Neutral Protection
W= ZSI (ST/GF/INST) + RELT +
Neutral Protection
Advanced Features &
Communications
X= Metering (Basic)
2= Metering (Basic) +
Modbus
6= Metering (Adv) +
Modbus +
Waveform Capture
8= Metering (Adv) +
Modbus +
Waveform Capture +
Protective Relays
Max Amps
01 = 150A
04 = 400A
06 = 600A
Standard
Protection
Functions
L3 = LSI2
L4 = LSIG
L5 = LSIA
L7 = LSI-CP3
Family
S= Spectra™
Frame Rating
(Amperes)
G= 600
Interruption Rating
(kA @ 480V)
H= 35
L= 65
P= 100
Continuous
Load Rating
C= Standard
H= 100%
L= 100%
P= 100%
Poles
3= 3 poles
Voltage
Rating
6= 600V
Note: This information is provided for interpreting product numbers (it should not be used to build product numbers).
L = Long Time, S = Short Time, I = Instantaneous, G = Ground Fault, A = Ground Fault Alarm
ZSI = Zone Selective Interlocking, RELT = Reduced Energy Let-Through
2Without a Control Power connection, unless required by Advanced Protection Functions or Advanced Features
& Communications.
3With a Control Power connection. The only valid trailing product digits for L7 are XX.
Note: All Spectra™breakers are UL listed as HACR type.
Terminal Lugs for
Front Connection (Cu/Al)
Product
Sensor Number Wire Range
(2) 2/0 - 500 Cu/Al
3 Pole Lug Kit or
150 to 600 TCLK3654(1) 8 - 600 Cu
or
(1) 6 - 600 Al
microEntelliGuard™Rating Plug Selection
Rating Plug SG (Max Amps)
Product Numbers Trip Amps 150 400 600
GTP0060U0101 60 x
GTP0080U0101 80 x
GTP0100U0103 100 x
GTP0125U0103 125 x
GTP0150U0104 150 xx
GTP0200U0204 200 x
GTP0225U0306 225 xx
GTP0250U0407 250 xx
GTP0300U0408 300 xx
GTP0350U0408 350 xx
GTP0400U0410 400 xx
GTP0450U0612 450 x
GTP0500U0613 500 x
GTP0600U0616 600 x
Range of available rating plugs for each frame
indicated by x.
1May require 24 Vdc control power and voltage sensing
signals. Refer to pages 6-62 to 6-68.
4Order one kit for either line or load end: two kits
required for both.
Note: Reference BuyLog page 6-104 for alternate
lug options.
www.geindustrial.com BuyLog™Catalog 6-59
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Industrial Circuit Breakers
60-600A Circuit Breakers
Electronic Trip
Spectra™RMS
SG600 with microEntelliGuard™Trip Units1
microEntelliGuard™, Standard UL Rated
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SGL, SGP UL Current Limiting; 3-Pole, UL/CSA: 600Vac Max., IEC 947-2: 630A, 690 Vac Max
Standard 35kA 65kA 100kA Product Number
Max Protection Product Number Product Number Product Number Suffix
Amps Function Prefix Prefix Prefix (two digits)
LSI SGHC3601L3 _ _ SGLC3601L3 _ _ SGPC3601L3 _ _
150 LSIG2SGHC3601L4 _ _ SGLC3601L4 _ _ SGPC3601L4 _ _
LSIA2SGHC3601L5 _ _ SGLC3601L5 _ _ SGPC3601L5 _ _
LSI-CP3SGHC3601L7XX SGLC3601L7XX SGPC3601L7XX
LSI SGHC3604L3 _ _ SGLC3604L3 _ _ SGPC3604L3 _ _
400 LSIG2SGHC3604L4 _ _ SGLC3604L4 _ _ SGPC3604L4 _ _
LSIA2SGHC3604L5 _ _ SGLC3604L5 _ _ SGPC3604L5 _ _
LSI-CP3SGHC3604L7XX SGLC3604L7XX SGPC3604L7XX
LSI SGHC3606L3 _ _ SGLC3606L3 _ _ SGPC3606L3 _ _
600 LSIG2SGHC3606L4 _ _ SGLC3606L4 _ _ SGPC3606L4 _ _
LSIA2SGHC3606L5 _ _ SGLC3606L5 _ _ SGPC3606L5 _ _
LSI-CP3SGHC3606L7XX SGLC3606L7XX SGPC3606L7XX
microEntelliGuard™, 100% UL Rated
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SGL, SGP UL Current Limiting; 3-Pole, UL/CSA: 600Vac Max., IEC 947-2: 630A, 690 Vac Max
Standard 35kA 65kA 100kA Product Number
Max Protection Product Number Product Number Product Number Suffix
Amps Function Prefix Prefix Prefix (two digits)
LSI SGHH3601L3 _ _ SGLL3601L3 _ _ SGPP3601L3 _ _
150 LSIG2SGHH3601L4 _ _ SGLL3601L4 _ _ SGPP3601L4 _ _
LSIA2SGHH3601L5 _ _ SGLL3601L5 _ _ SGPP3601L5 _ _
LSI-CP3SGHH3601L7XX SGLL3601L7XX SGPP3601L7XX
LSI SGHH3604L3 _ _ SGLL3604L3 _ _ SGPP3604L3 _ _
400 LSIG2SGHH3604L4 _ _ SGLL3604L4 _ _ SGPP3604L4 _ _
LSIA2SGHH3604L5 _ _ SGLL3604L5 _ _ SGPP3604L5 _ _
LSI-CP3SGHH3604L7XX SGLL3604L7XX SGPP3604L7XX
LSI SGHH3606L3 _ _ SGLL3606L3 _ _ SGPP3606L3 _ _
600 LSIG2SGHH3606L4 _ _ SGLL3606L4 _ _ SGPP3606L4 _ _
LSIA2SGHH3606L5 _ _ SGLL3606L5 _ _ SGPP3606L5 _ _
LSI-CP3SGHH3606L7XX SGLL3606L7XX SGPP3606L7XX
Product Number is
not complete.
Select one value
from each suffix
tables below.
Product Number is
not complete.
Select one value
from each suffix
tables below.
Product Suffix 1
Advanced Protection Functions
X = None
K = Neutral Protection
Z = ZSI (ST/GF)
T = ZSI (ST/GF/INST)
R = RELT
L = ZSI (ST/GF) + RELT
M = ZSI (ST/GF) + Neutral Protection
N = ZSI (ST/GF) + RELT + Neutral Protection
V = RELT + Neutral Protection
P = ZSI (ST/GF/INST) + RELT
S = ZSI (ST/GF/INST) + Neutral Protection
W = ZSI (ST/GF/INST) + RELT + Neutral Protection
Notes: All Spectra™breakers are UL listed as HACR type.
Neutral Protection requires a neutral current sensor. Refer to page 6-66.
ZSI (Zone Selective Interlock) requires TIM1 ZSI module and 24 Vdc control power (refer to pages 6-62 to
6-66 for accessories).
RELT (Reduced Energy Let-Through), Modbus, Ground Fault Alarm and Waveform Capture options require
24 Vdc control power
(refer to pages 6-62 to 6-66 for accessories).
1May require 24 Vdc control power and voltage sensing
signals. Refer to pages 6-62 to 6-68.
2For grounded neutral systems (1 phase/3-wire or
3 phase/4-wire) a neutral current sensor is required.
Refer to page 6-66.
3For +24 Vdc Control Power Accessories refer to pages
6-62 to 6-66.
Product Suffix 2
Advanced Features and Communications
X = Metering (Basic)
2 = Metering (Basic) + Modbus
6 = Metering (Adv) + Modbus +
Waveform Capture
8 = Metering (Adv) + Modbus +
Waveform Capture + Relays
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-60
Molded Case Circuit Breakers Section 6
Product Number Structure
Industrial Circuit Breakers
300-1200A Circuit Breakers
Electronic Trip
Spectra™RMS
SK1200 with microEntelliGuard™Trip Units1
SKHC3608 L3 XX
Advanced Protection Functions
X= None
K= Neutral Protection
Z= ZSI (ST/GF)
T= ZSI (ST/GF/INST)
R= RELT
L= ZSI (ST/GF) + RELT
M= ZSI (ST/GF) +
Neutral Protection
N= ZSI (ST/GF) + RELT +
Neutral Protection
V= RELT + Neutral Protection
P= ZSI (ST/GF/INST) + RELT
S= ZSI (ST/GF/INST) +
Neutral Protection
W= ZSI (ST/GF/INST) + RELT +
Neutral Protection
Advanced Features &
Communications
X= Metering (Basic)
2= Metering (Basic) +
Modbus
6= Metering (Adv) +
Modbus +
Waveform Capture
8= Metering (Adv) +
Modbus +
Waveform Capture +
Protective Relays
Max Amps
08 = 800A
10 = 1000A2
12 = 1200A
Standard
Protection
Functions
L3 = LSI3
L4 = LSIG
L5 = LSIA
L7 = LSI-CP4
Family
S= Spectra™
Frame Rating
(Amperes)
K= 1200
Interruption Rating
(kA @ 480V)
H= 50
L= 65
P= 100
T= 65 Extended Instantaneous (Selective)5
S = 100 Extended Instantaneous (Selective)5
Continuous
Load Rating
C= Standard
H= 100%
L= 100%
P= 100%
S= 100%
T= 100%
Poles
3= 3 poles
Voltage
Rating
6= 600V
4= 480V5
Note: This information is provided for interpreting product numbers (it should not be used to build product numbers).
L = Long Time, S = Short Time, I = Instantaneous, G = Ground Fault, A = Ground Fault Alarm
ZSI = Zone Selective Interlocking, RELT = Reduced Energy Let-Through
2Max Amps Option 10 only available on 100% rated breakers.
3Without a Control Power connection, unless required by Advanced Protection Functions or Advanced Features
& Communications.
4With a Control Power connection. The only valid trailing product digits for L7 are XX.
5SC, SS, TC and TT catalog codes are optimized for selectivity (extended instantaneous) and will carry a 480 Vac
maximum voltage rating.
Note: All Spectra™breakers are UL listed as HACR type.
Terminal Lugs for
Front Connection (Cu/Al)
Product
Sensor Number Wire Range
800 TCAL81 (3) 3/0 - 500 Cu/Al
12006TCAL125 (4) 3/0 - 500 Cu/Al
microEntelliGuard™Rating Plug Selection
Rating Plug SK (Max Amps)
Product Numbers Trip Amps 800 1000 1200
GTP0300U0408 300 x
GTP0350U0408 350 x
GTP0400U0410 400 x
GTP0450U0612 450 xxx
GTP0500U0613 500 xxx
GTP0600U0616 600 xxx
GTP0700U0816 700 xxx
GTP0750U0820 750 xxx
GTP0800U0820 800 xxx
GTP0900U1020 900 xx
GTP1000U1025 1000 xx
GTP1100U1225 1100 x
GTP1200U1232 1200 x
Range of available rating plugs for each frame
indicated by x.
1May require 24 Vdc control power and voltage sensing
signals. Refer to pages 6-62 to 6-68.
6Lugs not required on 100% rated SK1200; these
breakers are supplied with a back-connected
assembly which increases breaker depth. Refer to
outline drawing 168D1663 Sh1 for details.
Note: Reference BuyLog page 6-104 for alternate
lug options.
www.geindustrial.com BuyLog™Catalog 6-61
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
microEntelliGuard™, Standard UL Rated
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
3-Pole, UL/CSA: 600Vac Max., IEC 947-2: 1250A, 690 Vac Max (SKL, SKP only)
Standard 50kA 65kA 100kA Product Number
Max Protection Product Number Product Number Product Number Suffix
Amps Function Prefix Prefix Prefix (two digits)
LSI SKHC3608L3 _ _ SKLC3608L3 _ _ SKPC3608L3 _ _
800 LSIG2SKHC3608L4 _ _ SKLC3608L4 _ _ SKPC3608L4 _ _
LSIA2SKHC3608L5 _ _ SKLC3608L5 _ _ SKPC3608L5 _ _
LSI-CP3SKHC3608L7XX SKLC3608L7XX SKPC3608L7XX
LSI SKHC3612L3 _ _ SKLC3612L3 _ _ SKPC3612L3 _ _
1200 LSIG2SKHC3612L4 _ _ SKLC3612L4 _ _ SKPC3612L4 _ _
LSIA2SKHC3612L5 _ _ SKLC3612L5 _ _ SKPC3612L5 _ _
LSI-CP3SKHC3612L7XX SKLC3612L7XX SKPC3612L7XX
microEntelliGuard™, 100% UL Rated
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
3-Pole, UL/CSA: 600Vac Max., IEC 947-2: 1250A, 690 Vac Max (SKL, SKP only)
Standard 50kA 65kA 100kA Product Number
Max Protection Product Number Product Number Product Number Suffix
Amps Function Prefix Prefix Prefix (two digits)
LSI SKHH3608L3 _ _ SKLL3608L3 _ _ SKPP3608L3 _ _
800 LSIG2SKHH3608L4 _ _ SKLL3608L4 _ _ SKPP3608L4 _ _
LSIA2SKHH3608L5 _ _ SKLL3608L5 _ _ SKPP3608L5 _ _
LSI-CP3SKHH3608L7XX SKLL3608L7XX SKPP3608L7XX
LSI SKHH3610L3 _ _ SKLL3610L3 _ _ SKPP3610L3 _ _
1000 LSIG2SKHH3610L4 _ _ SKLL3610L4 _ _ SKPP3610L4 _ _
LSIA2SKHH3610L5 _ _ SKLL3610L5 _ _ SKPP3610L5 _ _
LSI-CP3SKHH3610L7XX SKLL3610L7XX SKPP3610L7XX
LSI SKHH3612L3 _ _ SKLL3612L3 _ _ SKPP3612L3 _ _
1200 LSIG2SKHH3612L4 _ _ SKLL3612L4 _ _ SKPP3612L4 _ _
LSIA2SKHH3612L5 _ _ SKLL3612L5 _ _ SKPP3612L5 _ _
LSI-CP3SKHH3612L7XX SKLL3612L7XX SKPP3612L7XX
Notes: All Spectra™breakers are UL listed as HACR type.
Neutral Protection requires a neutral current sensor. Refer to page 6-66.
ZSI (Zone Selective Interlock) requires TIM1 ZSI module and 24 Vdc control power (refer to pages 6-62 to
6-66 for accessories).
RELT (Reduced Energy Let-Through), Modbus, Ground Fault Alarm and Waveform Capture options require
24 Vdc control power (refer to pages 6-62 to 6-66 for accessories).
Industrial Circuit Breakers
300-1200A Circuit Breakers
Electronic Trip
Spectra™RMS
SK1200 with microEntelliGuard™Trip Units1
Product Suffix 2
Advanced Features and Communications
X = Metering (Basic)
2 = Metering (Basic) + Modbus
6 = Metering (Adv) + Modbus +
Waveform Capture
8 = Metering (Adv) + Modbus +
Waveform Capture + Relays
Product Suffix 1
Advanced Protection Functions
X = None
K = Neutral Protection
Z = ZSI (ST/GF)
T = ZSI (ST/GF/INST)
R = RELT
L = ZSI (ST/GF) + RELT
Advanced Protection Functions
M = ZSI (ST/GF) + Neutral Protection
N = ZSI (ST/GF) + RELT + Neutral Protection
V = RELT + Neutral Protection
P = ZSI (ST/GF/INST) + RELT
S = ZSI (ST/GF/INST) + Neutral Protection
W = ZSI (ST/GF/INST) + RELT + Neutral Protection
microEntelliGuard™Extended Instantaneous (Selective) Spectra K
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350, 3-Pole, UL/CSA: 480 Vac Max., IEC 947-2: 1250A
Standard UL Rated 100% UL Rated Standard UL Rated 100% UL Rated Product
Standard 65kA 65kA 100kA 100kA Number
Max Protection Product Number Product Number Product Number Product Number Suffix
Amps Function Prefix Prefix Prefix Prefix (two digits)
LSI SKTC3408L3_ _ SKTT3408L3_ _ SKSC3408L3_ _ SKSS3408L3_ _
800 LSIG2SKTC3408L4 _ _ SKTT3408L4 _ _ SKSC3408L4 _ _ SKSS3408L4 _ _
LSIA2SKTC3408L5_ _ SKTT3408L5_ _ SKSC3408L5_ _ SKSS3408L5_ _
LSI-CP3SKTC3408L7XX SKTT3408L7XX SKSC3408L7XX SKSS3408L7XX
LSI SKTT3410L3_ _ SKSS3410L3_ _
1000 LSIG2SKTT3410L4 _ _ SKSS3410L4 _ _
LSIA2SKTT3410L5_ _ SKSS3410L5_ _
LSI-CP3SKTT3410L7XX SKSS3410L7XX
LSI SKTC3412L3_ _ SKTT3412L3_ _ SKSC3412L3_ _ SKSS3412L3_ _
1200 LSIG2SKTC3412L4 _ _ SKTT3412L4 _ _ SKSC3412L4 _ _ SKSS3412L4 _ _
LSIA2SKTC3412L5_ _ SKTT3412L5_ _ SKSC3412L5_ _ SKSS3412L5_ _
LSI-CP3SKTC3412L7XX SKTT3412L7XX SKSC3412L7XX SKSS3412L7XX
Product Number is
not complete.
Select one value
from each suffix
tables below.
Product Number is
not complete.
Select one value
from each suffix
tables below.
Product Number is
not complete.
Select one value
from each suffix
tables below.
1May require 24 Vdc control power and voltage sensing signals.
Refer to pages 6-62 to 6-68.
2For grounded neutral systems (1 phase/3-wire or 3 phase/4-wire) a
neutral current sensor is required. Refer to page 6-66.
3For +24 Vdc Control Power Accessories refer to pages 6-62 to 6-66.
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-62
Molded Case Circuit Breakers Section 6
Required Accessories
MicroVersaTrip™Plus MicroVersaTrip™PM microEntelliGuard™Feature Required Accessories
•• •Ground Fault (3 phase/4-wire or 1 phase/3-wire) Neutral CT and Terminal Board
• Neutral Protection (or Junction Box + Distribution Cable)
• Ground Fault Alarm (3 phase/4-wire or 1 phase/3-wire) Power Supply (Plate Assy2)
•• • Control Power Voltage Module1or Power Supply Plate/Assy2
Power Supply (Plate or Assy2) and Voltage Conditioner
••Advanced Metering, Protective Relays (Plate or Assy) or Voltage Module and
Terminal Board (or Junction Box) and Distribution Cable(s)
Voltage Module1or Power Supply Plate/Assy2and
•• Communications3Terminal Board (or Junction Box) and Distribution Cable(s)
and Auxiliary Switch4
Voltage Module1or Power Supply Plate/Assy2and
• Zone Selective Interlock (ZSI) Terminal Board with ZSI (or Advanced Junction Box)
and Distribution Cable(s) and TIM-1 module
Voltage Module1or Power Supply Plate/Assy2and
• Reduced Energy Let-Through (RELT) Terminal Board w/ RELT (or Advanced Junction Box)
and Distribution Cable(s)
Voltage Module1or Power Supply Plate/Assy2and
• Waveform Capture Terminal Board (or Advanced Junction Box)
and Distribution Cable(s)
1For installation into GE Spectra™Series Switchboards only 3MicroVersaTrip™PM (Commnet), microEntelliGuard™(Modbus)
2Requires fuse protection and other components - refer to accessory instruction sheet 4Requires Auxiliary Switch with gold-plated contacts
Power Management System Accessories
Spectra™RMS Circuit Breakers with microEntelliGuard™
, MicroVersaTrip™Plus and MicroVersaTrip™PM Trip Units
All Devices UL Listed for Factory or Field Installation (UL File No. E-57253)
Power Supply Plate
The Power Supply Plate is used to provide +24 Vdc control power to Spectra™RMS
molded case circuit breakers with microEntelliGuard™, MicroVersaTrip™Plus and
MicroVersaTrip™PM trip units via the Distribution Cable System. The Power Supply
Plate includes the Power Supply Assembly (product number SPSAA) as an integral
component and also includes fuse protection for AC source input. Supplemental +24 Vdc
input terminals are provided for backup control power applications. Not suitable for
400 Hz.
Description Voltage Rating Product Number
The Power Supply Plate is rated 24 watts 120 Vac SPSA120
(+24 Vdc at 1.0 amperes) and has the maximum 208 Vac SPSA208
capacity to power a distribution Cable System 240 Vac SPSA240
consisting of 20 breakers and has a maximum 480 Vac SPSA480
system cable length of 40 feet. 600 Vac SPSA600
Voltage Conditioner Plate
The Voltage Conditioner Plate is used to provide voltage sensing signals to Spectra™RMS
molded case circuit breakers with microEntelliGuard™and MicroVersaTrip™PM trip units
via the distribution cable system. The Voltage Conditioner Plate includes the Voltage
Conditioner Assembly (product number SVCAA) as an integral component and also
includes fuse protection for the AC source input terminals and three 1-VA high accuracy
potential transformers. The Voltage Conditioner Plate requires a control power source of
+24 Vdc to operate properly (the Power Supply Assembly or Power Supply Plate can
provide this required input). The unit also requires AC direct voltage inputs from the AC
source. A communications network connection is provided. Not suitable for 400 Hz.
Voltage Rating and Service Type Comments Product Number
120 Vac Wye system Phase to Neutral potential SVCA120Y
208 Vac Wye system Phase to Phase potential SVCA208Y
240 Vac Delta system Phase to Phase potential SVCA240D
277 Vac Wye system Phase to Neutral potential SVCA277Y
480 Vac Wye system Phase to Phase potential SVCA480Y
480 Vac Delta system Phase to Phase potential SVCA480D
600 Vac Delta system Phase to Phase potential SVCA600D
Note: The Voltage Conditoner Plate has the maximum capacity to power a Distribution Cable System consisting of
20 breakers and has a maximum system cable length of 40 feet.
Power Supply Plate
Voltage Conditioner Plate
www.geindustrial.com BuyLog™Catalog 6-63
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Power Management System Accessories
Spectra™RMS Circuit Breakers with microEntelliGuard™
, MicroVersaTrip™Plus and MicroVersaTrip™PM Trip Units
All Devices UL Listed for Factory or Field Installation (UL File No. E-57253)
Distribution Cable Extension
Distribution Cable Terminal Block
Distribution Cable Harness
Distribution Cable Junction Box
The Distribution Cable Junction Box is a modular connector used to provide quick,
easy and reliable attachment of Spectra™RMS molded case circuit breakers with
microEntelliGuard™, MicroVersaTrip™Plus and MicroVersaTrip™PM trip units to the
Distribution Cable System. Two different juntion boxes are available depending on which
trip system and functionality is selected. Each junction box contains two Distribution
Cable Harness connectors, one breaker connector, and a terminal block for the
connection of a neutral current sensor and an auxiliary switch. Additional terminal
points are included on SDCJBBC for ground fault alarm, RELT, and ZSI. (For breakers
with microEntelliGuard™trip units, refer to the table on page 6-64 to determine breaker
harness connector configuration)
Description Product Number
Distribution Cable Junction Box (for breakers with 12-pin connector) SDCJBB
Advanced Distribution Cable Junction Box (for breakers with 20-pin connector) SDCJBBC2
Distribution Cable Harness1
The Distribution Cable Harness is a modular connector used to carry electronic signals
and/or control power between Spectra™RMS molded case circuit breakers with
microEntelliGuard™, MicroVersaTrip™Plus and MicroVersaTrip™PM trip units and
power management system accessories. The harnesses come in three lengths and
have 12-pin connectors at both ends.
Description Harness Length Product Number
Distribution Cable Harness 11 inches SDCHA11
Distribution Cable Harness 30 inches SDCHA30
Distribution Cable Harness 60 inches SDCHA60
Distribution Cable Extension
The Distribution Cable Extension is used to provide modular expansion of the Distribution
Cable System. Two different cable extensions are available depending on which trip
system and functionality are selected. Spectra™RMS molded case circuit breakers
with MicroVersaTrip™Plus and MicroVersaTrip™PM trip units use the 12-pin
connector extension cable only. Spectra™RMS molded case circuit breakers with
microEntelliGuard™trip units use either the 12-pin or 20-pin connector extension cable
depending on the breaker’s harness connector configuration. (For breakers with
microEntelliGuard™trip units, refer to the table on page 6-64 to determine breaker
harness connector configuration)
Description Harness Length Product Number
Distribution Cable Extension (for breakers with 12-pin connector) 30 inches SDCEA30
Distribution Cable Extension (for breakers with 20-pin connector) 30 inches SDCEA30C2
Distribution Cable Terminal Block
The Distribution Cable Terminal Block can be used in lieu of the Distribution Cable
Junction Box as an alternate means of connection to Spectra™RMS molded case circuit
breakers with microEntelliGuard™, MicroVersaTrip™Plus and MicroVersaTrip™PM trip
units. The Distribution Cable Terminal Block plugs into the breaker harness connector
allowing direct connection of signals via screw terminals. This allows point-to-point
wiring in lieu of using the Distribution Cable System. Three different cable extensions are
available depending on which trip system and functionality are selected. (Refer to the
table on page 6-64 for terminal block connection configurations)
Description Trip Unit Type Product Number
Distribution Cable Terminal Block MicroVersaTrip™& microEntelliGuard™SDCTBA11
(for breakers with 12-pin connector)
Distribution Cable Terminal Block microEntelliGuard™SDCTBA11C2
(for breakers with 20-pin connector) microEntelliGuard™SDCTBA22C2
1Cannot be connected together. Use 30 inch Distribution Cable Extension (SDCEA30) to extend.
2For use with microEntelliGuard™ only.
Distribution Cable Junction Box
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-64
Molded Case Circuit Breakers Section 6
Breakers with microEntelliGuard™Trip Units
Breaker Harness Connector Configuration
Circuit Breaker Catalog Digits 9 & 10
L3 L4 L5 L7
K2 SDCTBA11 SDCTBA11 SDCTBA22C n/a
K6 SDCTBA11 SDCTBA11 SDCTBA22C n/a
K8 SDCTBA22C SDCTBA22C SDCTBA22C n/a
KX SDCTBA11 SDCTBA11 SDCTBA11C n/a
L2 SDCTBA22C SDCTBA22C SDCTBA22C n/a
L6 SDCTBA22C SDCTBA22C SDCTBA22C n/a
L8 SDCTBA22C SDCTBA22C SDCTBA22C n/a
LX SDCTBA22C SDCTBA22C SDCTBA22C n/a
M2 SDCTBA22C SDCTBA22C SDCTBA22C n/a
M6 SDCTBA22C SDCTBA22C SDCTBA22C n/a
M8 SDCTBA22C SDCTBA22C SDCTBA22C n/a
MX SDCTBA22C SDCTBA22C SDCTBA22C n/a
N2 SDCTBA22C SDCTBA22C SDCTBA22C n/a
N6 SDCTBA22C SDCTBA22C SDCTBA22C n/a
N8 SDCTBA22C SDCTBA22C SDCTBA22C n/a
NX SDCTBA22C SDCTBA22C SDCTBA22C n/a
P2 SDCTBA22C SDCTBA22C SDCTBA22C n/a
P6 SDCTBA22C SDCTBA22C SDCTBA22C n/a
P8 SDCTBA22C SDCTBA22C SDCTBA22C n/a
PX SDCTBA22C SDCTBA22C SDCTBA22C n/a
R2 SDCTBA22C SDCTBA22C SDCTBA22C n/a
R6 SDCTBA22C SDCTBA22C SDCTBA22C n/a
R8 SDCTBA22C SDCTBA22C SDCTBA22C n/a
RX SDCTBA11C SDCTBA11C SDCTBA11C n/a
S2 SDCTBA22C SDCTBA22C SDCTBA22C n/a
S6 SDCTBA22C SDCTBA22C SDCTBA22C n/a
S8 SDCTBA22C SDCTBA22C SDCTBA22C n/a
SX SDCTBA22C SDCTBA22C SDCTBA22C n/a
T2 SDCTBA22C SDCTBA22C SDCTBA22C n/a
T6 SDCTBA22C SDCTBA22C SDCTBA22C n/a
T8 SDCTBA22C SDCTBA22C SDCTBA22C n/a
TX SDCTBA22C SDCTBA22C SDCTBA22C n/a
V2 SDCTBA22C SDCTBA22C SDCTBA22C n/a
V6 SDCTBA22C SDCTBA22C SDCTBA22C n/a
V8 SDCTBA22C SDCTBA22C SDCTBA22C n/a
VX SDCTBA11C SDCTBA11C SDCTBA11C n/a
W2 SDCTBA22C SDCTBA22C SDCTBA22C n/a
W6 SDCTBA22C SDCTBA22C SDCTBA22C n/a
W8 SDCTBA22C SDCTBA22C SDCTBA22C n/a
WX SDCTBA22C SDCTBA22C SDCTBA22C n/a
X2 SDCTBA11 SDCTBA11 SDCTBA22C n/a
X6 SDCTBA11 SDCTBA11 SDCTBA22C n/a
X8 SDCTBA22C SDCTBA22C SDCTBA22C n/a
XX NONE SDCTBA11 SDCTBA11C SDCTBA11
Z2 SDCTBA22C SDCTBA22C SDCTBA22C n/a
Z6 SDCTBA22C SDCTBA22C SDCTBA22C n/a
Z8 SDCTBA22C SDCTBA22C SDCTBA22C n/a
ZX SDCTBA22C SDCTBA22C SDCTBA22C n/a
Distribution Cable Terminal Block Connection Configurations
Terminal SDCTBA11 SDCTBA11C SDCTBA22C
Description 12-pin Connector 20-pin Connector 20-pin Connector
MicroVersaTrip™& microEntelliGuard™microEntelliGuard™
Trip Unit Type microEntelliGuard™only only
POWER (+24Vdc) •••
POWER (common) •••
Communications + ••
Communications - ••
Aux Switch (red) ••
Aux Switch (white) ••
Voltage - Ph A ••
Voltage - Ph B ••
Voltage - Ph C ••
Neutral CT (black) •••
Neutral CT (white) •••
ZSI input + •
ZSI input - •
ZSI output + •
ZSI output - •
RELT input + ••
RELT input - ••
RELT output + ••
RELT/GFA output - ••
GFA output + ••
Power Management System Accessories
Spectra™RMS Circuit Breakers with microEntelliGuard™
, MicroVersaTrip™Plus and MicroVersaTrip™PM Trip Units
All Devices UL Listed for Factory or Field Installation (UL File No. E-57253)
Circuit Breaker Catalog Digits 11 & 12
www.geindustrial.com BuyLog™Catalog 6-65
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Power Management System Accessories
Spectra™RMS Circuit Breakers with microEntelliGuard™
, MicroVersaTrip™Plus and MicroVersaTrip™PM Trip Units
All Devices UL Listed for Factory or Field Installation (UL File No. E-57253)
Voltage Module Exterior View
Voltage Module Interior View
Voltage Conditioner Assembly
Power Supply Assembly
The Power Supply Assembly is used to provide +24 Vdc control power to Spectra™RMS
molded case circuit breakers with microEntelliGuard™, MicroVersaTrip™Plus and
MicroVersaTrip™PM trip units via the Distribution Cable System. The assembly requires
a minimum input voltage of 85 Vac to operate properly (the maximum voltage rating is
240 Vac). Supplemental +24 Vdc input terminals are provided for backup control power
applications. The input must be fused with 1/2 ampere class CC fuses (not included).
Not suitable for 400 Hz.
Description Voltage Rating Product Number
The Power Supply Assembly is rated 24 watts 85 - 240 Vac SPSAA
(+24 Vdc @ 1.0 ampere) and has the maximum
capacity to power a Distribution Cable System
consisting of 20 breakers and has a maximum
system cable length of 40 feet.
Voltage Conditioner Assembly
The Voltage Conditioner Assembly is used to provide voltage sensing signals to Spectra™
RMS molded case circuit breakers with microEntelliGuard™, MicroVersaTrip™Plus and
MicroVersaTrip™PM trip units via the Distribution Cable System. The Voltage Conditioner
Assembly requires a control power source of +24 Vdc to operate properly (the Power
Supply Assembly or Power Supply Plate can provide this required input). The unit also
requires 120 Vac voltage inputs from the secondary of three 1-VA high accuracy
potential transformers (not included). The primary side of the potential transformers
must be fused with three, 1/2 ampere class CC fuses (not included). A communications
network connection is provided. Not suitable for 400 Hz.
Description Voltage Rating Product Number
Requires 120 Vac voltage inputs from the 120 Vac SVCAA
secondary of three 1.0 VA high accuracy
potential transformers
Note: the Voltage Conditioner Assembly has the maximum capacity to power a Distribution Cable System
consisting of 20 breakers and has a maximum system cable length of 40 feet.
Voltage Modules
The Voltage Module is used as a Spectra™Series Switchboard component to provide
+24 Vdc control power to Spectra™RMS molded case circuit breakers with
microEntelliGuard™, MicroVersaTrip™Plus and MicroVersaTrip™PM trip units via the
Distribution Cable System. The Voltage Module also provides voltage sensing signals to
Spectra™RMS molded case circuit breakers with microEntelliGuard™and MicroVersaTrip™
PM trip units on the same Distribution Cable System. The Voltage Module contains both
a Power Supply Plate and a Voltage Conditioner as integral components. It also includes
fuse protection for the AC source input terminals (the module’s pressure connectors
which connect to the switchboard bus bars). A communication network connection is
provided as well as supplemental +24 Vdc input terminals for backup control power
applications (microEntelliGuard™trip units communicate via Modbus; MicroVersaTrip™PM
communicate via Commnet). Seven versions are available. Not suitable for 400 Hz.
Voltage Rating and Service Type Comments Product Number
120 Vac Wye system Phase to Neutral potential ADSVMA120Y
208 Vac Wye system Phase to Phase potential ADSVMA208Y
240 Vac Delta system Phase to Phase potential ADSVMA240D
277 Vac Wye system Phase to Neutral potential ADSVMA277Y
480 Vac Wye system Phase to Phase potential ADSVMA480Y
480 Vac Delta system Phase to Phase potential ADSVMA480D
600 Vac Delta system Phase to Phase potential ADSVMA600D
Note: The Voltage Module has the maximum capacity to power a Distribution Cable System consisting of 20
breakers and has a maximum system cable length of 40 feet.
Power Supply Assembly
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-66
Molded Case Circuit Breakers Section 6
Neutral Current Sensor
The Neutral Current Sensor is used in conjunction with Spectra™RMS molded case circuit
breakers with microEntelliGuard™, MicroVersaTrip™Plus and MicroVersaTrip™PM trip units
that are optioned with either the ground fault or neutral protection and the breaker is
connected to a grounded neutral service (3 phase/4-wire or 1 phase/3-wire). The neutral
current sensor provides an input signal to the breaker trip unit. Breakers connected to a
service without a neutral (3 phase/3-wire) do not require an external connection or short-
ing of the breaker cable connector for ground fault to function properly.
Breaker Type Sensor Rating (S) Product Number
SG 150 TSRG201
SG 400 TSRG204
SG 600 TSRG206
SK 800 TSKG408
SK 1200 TSKG412
Rating Plug Removal Tool
The Rating Plug Removal Tool is suitable for use on all Spectra™RMS molded case circuit
breakers, regardless of the trip unit type.
Product Number
TRTOOL
Portable Battery Pack
The hand-held Portable Battery Pack provides an independent power source for
microEntelliGuard™, MicroVersaTrip™Plus and MicroVersaTrip™PM trip units as an
alternative to a test set. The battery pack is used to power up the trip unit to set or
adjust trip set points when the breaker is on the bench or otherwise not powered up.
For microEntelliGuard™trip units, the battery pack connects to the trip unit through the
15-pin connector. A battery pack adapter cable is required. For MicroVersaTrip™Plus and
MicroVersaTrip™PM trip units, the battery pack connects to the trip unit through the
rating plug test jack. The battery pack requires three standard 9 Vdc alkaline batteries
(not included).
Description Product Number
Portable Battery Pack TVPBP
Battery Pack Adapter Cable TVPBPACC
(required for microEntelliGuard™trip units)
Portable Test Set
The portable, battery-powered test kit provides self-tests and functional trip/no trip tests.
It also provides defeat of the ground fault function and can be used in conjuntion with
high current test equipment. Interface is via a plug on the front of the trip unit and test
can be conducted with the breaker in service. Test kits use either 120 Vac power source
or internal batteries (not included).
Description Trip Unit Type Product Number
Portable Test Set MicroVersaTrip™only TVRMS21
microEntelliGuard™only GTUTK20
1Not for use with MicroVersaTrip™4- or 9-Function trip units
Reduced Energy Let-Through (RELT) Switch Kit
The RELT switch kit is used to switch the trip unit into Reduced Energy Let-Through Mode.
The kit contains a three position selector switch, contact blocks, a lockable switch cover,
RELT warning label, and an 8-ft wiring harness.
Description Product Number
RELT Switch Kit GTURSK
Accessories–Other
Spectra™RMS Circuit Breakers with microEntelliGuard™
, MicroVersaTrip™Plus and MicroVersaTrip™PM Trip Units
All Devices UL Listed for Factory or Field Installation Except Where Noted
Neutral Current Sensor
Rating Plug Removal Tool
Portable Battery Pack
Battery Pack Adapter Cable
Portable Test Kit
www.geindustrial.com BuyLog™Catalog 6-67
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Internal Accessories
Spectra™RMS Circuit Breakers
Voltage Current (mA) Product
ac dc Inrush Cont Number
120 125 500 6.0 SAST1
240 250 400 5.0 SAST2
— 12 1000 800 SAST51
24 24 300 10.0 SAST3
48 48 300 10.0 SAST4
1Not suitable for use with ground fault sensing and relaying equipment.
Note: UL listed at 200,000 AIC without internal accessories, 100,000 AIC with internally mounted accessories.
Auxiliary Switch
Auxiliary switches provide remote indication of whether the circuit breaker main
contacts are opened or closed via open or closed SPDT switch elements.
Switch Number of Auxiliary Switch
Rating Switch Elements Product Number
5A @240 Vac/ 1 form C SAUXPAB1
0.5A @ 125 Vdc 2 form C SAUXPAB2
Gold-Plated Contacts 1 form C SAUXGAB1
0.5A @ 30V 2 form C SAUXGAB2
One each 2 form C SAUXGPAB2
of above types
Universal Field-Installable Internal Accessories
All Spectra™RMS circuit breakers from the SE150 through the SK1200, including
instantaneous-trip Mag Break motor circuit protectors and molded case switches,
use the same UL listed, field-installable internal accessories that do not require cover
removal to install.
Accessory Mounting
All accessories mount in pouches accessible from a front cover. All breakers have a
left-side pouch and right-side pouch. The following combinations may be installed:
Left-Side Pouch—either shunt trip or undervoltage release plus bell alarm.
Right-Side Pouch—auxiliary switch (single or double pole).
Shunt Trip
For remote tripping of breaker, use with momentary close contact. Not recommended for
use with latching relay contact since electronics in shunt trip will pulse power to the coil
if continuously energized, and breaker shunt tripping upon reclosure will be delayed 1-2
seconds at rated control voltage. (A short-circuit trip would be instantaneous.)
If maintained (latching relay) contact must be used and delayed shunt tripping is not
acceptable, use small bell alarm in series with control power for SE150 and SF250 frames
and auxiliary switch for SG600 and SK1200 breakers.
These devices are suitable for use with ground fault sensing and relaying equipment.
Maximum VA is 75. AC devices are UL listed for 50-60 Hz.
Auxiliary Switch
Shunt Trip
Red
White
Brown/white
Black
Black
All accessory contacts shown
with the circuit breaker in
tripped position.
All accessory contacts shown
with the circuit breaker in
tripped position.
Left Side Pouch Right Side Pouch
Spectra RMS Test Set
Provides basic trip-test functionality for all SPectra RMS, (SE, SF, SG, SK) Circuit Breakers
not equipped with LCD Displays. Test Kit plus Test Rating Plug are required.
Product
Description Number
Spectra RMS Trip Tester SPTK1
Spectra RMS Test Rating Plug SRPT1
Trip Test Kit Test Rating Plug
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-68
Molded Case Circuit Breakers Section 6
Actuator
All Spectra™circuit breakers are supplied with an actuator installed in the left-side pouch.
The actuator is removed when installing either a shunt trip or undervoltage release.
Description Product Number
Replacement Actuator SACTUATOR
Voltage Peak Current Product
ac dc (mA) Number
120 125 200 SAUV1
240 250 200 SAUV2
24 24 100 SAUV3
48 48 100 SAUV4
120 125 SPUVTD
Switch Number of Product
Rating Switch Elements Number
5A @ 240 Vac/ 1 form C SABAP1
0.5A @ 125 Vdc
Gold-Plated Contacts 1 form C SABAG1
0.5A @30V
Note: UL listed at 200,000 AIC without internal accessories, 100,000 AIC with internally mounted accessories.
Bell Alarm Switch
The bell alarm switch provides remote indication of whether the circuit breaker has been
tripped via open or closed SPDT switch elements, but remains unchanged during "On/Off"
circuit breaker operation and during operation by the "Push-to-Trip" button.
Undervoltage Release
Undervoltage Release
The undervoltage release provides automatic circuit breaker tripping when there is a
power loss or major dip (to 35%-70% of rated voltage) in accessory control voltage. AC
devices are UL listed for 50-60 Hz. Product number SAUV1 may be used with time delay
unit SPUVTD (List Price $430.00, GO-245B) (delay 0.1 to 1.0 seconds), 120 Vac input,
125 Vdc output.
Bell Alarm Switch
Internal Accessories
Spectra™RMS Circuit Breakers
Purple
Yellow
Brown
Blue
Blue
All accessory contacts shown
with the circuit breaker in
tripped position.
All accessory contacts shown
with the circuit breaker in
tripped position.
www.geindustrial.com BuyLog™Catalog 6-69
Molded Case Circuit Breakers
Rev. 11/13
Data subject to change
without notice
Section 6
Record Plus™FB 100
Reference Publications
Available for download from www.geindustrial.com/publibrary
FB Breaker
Installation Instructions DEH-41073
Fact sheet DET-406
FB Breaker Accessories
Bell Alarm & Aux. Switch DEH-40324
Shunt Trip & UVR DEH-40363
Padlock Device DEH-40521
Lug Kits DEH-40532
Panelboards
A-Series™AD Plus Catalog/Selection Guide DEP-134
A-Series™AD Plus Fact Sheet DET-397
Spectra™Power Panel - Plug-in Kits DEH-41123
Spectra™Power Panel - Bolt-on Kits DEH-41124
Spectra™Power Panel - Filler Plates DEH-41125
Outline Drawings
FB 1 pole 10091632SH1
FB 2 pole 10091636SH1
FB 3 pole 10091641SH1
Series Ratings DET-008
Trip Curves
Trip Unit Rated Current (A) Trip Curve
15 DES-013
20 DES-014
25 DES-015
30 DES-016
35 DES-017
40 DES-018
45 DES-019
50 DES-020
60 DES-021
70 DES-022
80 DES-023
90 DES-024
100 DES-025
Peak Current Curves DES-030
Peak I2t Curve DES-031
FB Breaker Markings
cULus UL File E-11592
HACR 15 to 100A 1, 2, 3 Pole
HID 15 to 50A 1, 2, 3 Pole
NAVAL 15 to 100A 1, 2, 3 Pole
Cu/Al 60/75°C 15 to 100A 1, 2, 3 Pole
Current Limiting 15 to 100A 1, 2, 3 Pole
FB breakers are NOT marked LINE/LOAD and can be reverse fed.
Breaker Frame Rating
Product Description
Standards & Ratings
Interrupting Ratings
Lug Data & Torque Info
Product Number
Push to Trip
Interrupting Ratings
UL Listed Interrupting Ratings -
rms Symmetrical Amperes (in Thousands) AC Voltage
Type Ampere Rating Max AC Voltage No. Poles 240 277 347 480 600/347
1 35 35 22 ––
FBV 15-100 600/347VAC 2 65 ––35 22
3 65 ––35 22
1 65 65 25 ––
FBN 15-100 600/347VAC 2 150 ––65 25
3 150 ––65 25
1 100 100 35 ––
FBH 15-100 600/347VAC 2 200 ––100 35
3 200 ––100 35
1 100 150 42 ––
FBL 15-100 600/347VAC 2 200 ––150 42
3 200 ––150 42
Product Number Structure F BN3 6 TE 050 R
Frame Rating Interruption Voltage Rated
Family (Amperes) Rating (480V) Poles Rating Type Current (A)1Connection
F= Record B= 100 V= 35kA 1= 1 pole 6= 600/347 TE = Fixed 015 – 100 R = Standard,
Plus N= 65kA 2= 2 poles Thermal No Lugs
H= 100kA 3= 3 poles Magnetic R2 =
Load Lugs Only
L= 150 kA RV = A-Series™AD
Plus Lighting
Panel (Includes
Load Lugs
and panel
connections)
1Available ampere ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100.
12
3
4
5
6
7
1
2
3
4
5
6
7
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-70
Section 6
Molded Case Circuit Breakers
Record Plus™FB 100
1-Pole Record Plus™FB 100 Breakers IC @ 600/347 Vac
Rated 35kA 65kA 100kA 150kA
Current (A) Product No. Product No. Product No. Product No. Connection
FBV16TE015R FBN16TE015R FBH16TE015R FBL16TE015R No Lugs
15 FBV16TE015R2 FBN16TE015R2 FBH16TE015R2 FBL16TE015R2 Load Lugs Only
FBV16TE015RV FBN16TE015RV FBH16TE015RV FBL16TE015RV Load Lugs and
Panel Connections
FBV16TE020R FBN16TE020R FBH16TE020R FBL16TE020R No Lugs
20 FBV16TE020R2 FBN16TE020R2 FBH16TE020R2 FBL16TE020R2 Load Lugs Only
FBV16TE020RV FBN16TE020RV FBH16TE020RV FBL16TE020RV Load Lugs and
Panel Connections
FBV16TE025R FBN16TE025R FBH16TE025R FBL16TE025R No Lugs
25 FBV16TE025R2 FBN16TE025R2 FBH16TE025R2 FBL16TE025R2 Load Lugs Only
FBV16TE025RV FBN16TE025RV FBH16TE025RV FBL16TE025RV Load Lugs and
Panel Connections
FBV16TE030R FBN16TE030R FBH16TE030R FBL16TE030R No Lugs
30 FBV16TE030R2 FBN16TE030R2 FBH16TE030R2 FBL16TE030R2 Load Lugs Only
FBV16TE030RV FBN16TE030RV FBH16TE030RV FBL16TE030RV Load Lugs and
Panel Connections
FBV16TE035R FBN16TE035R FBH16TE035R FBL16TE035R No Lugs
35 FBV16TE035R2 FBN16TE035R2 FBH16TE035R2 FBL16TE035R2 Load Lugs Only
FBV16TE035RV FBN16TE035RV FBH16TE035RV FBL16TE035RV Load Lugs and
Panel Connections
FBV16TE040R FBN16TE040R FBH16TE040R FBL16TE040R No Lugs
40 FBV16TE040R2 FBN16TE040R2 FBH16TE040R2 FBL16TE040R2 Load Lugs Only
FBV16TE040RV FBN16TE040RV FBH16TE040RV FBL16TE040RV Load Lugs and
Panel Connections
FBV16TE045R FBN16TE045R FBH16TE045R FBL16TE045R No Lugs
45 FBV16TE045R2 FBN16TE045R2 FBH16TE045R2 FBL16TE045R2 Load Lugs Only
FBV16TE045RV FBN16TE045RV FBH16TE045RV FBL16TE045RV Load Lugs and
Panel Connections
FBV16TE050R FBN16TE050R FBH16TE050R FBL16TE050R No Lugs
50 FBV16TE050R2 FBN16TE050R2 FBH16TE050R2 FBL16TE050R2 Load Lugs Only
FBV16TE050RV FBN16TE050RV FBH16TE050RV FBL16TE050RV Load Lugs and
Panel Connections
FBV16TE060R FBN16TE060R FBH16TE060R FBL16TE060R No Lugs
60 FBV16TE060R2 FBN16TE060R2 FBH16TE060R2 FBL16TE060R2 Load Lugs Only
FBV16TE060RV FBN16TE060RV FBH16TE060RV FBL16TE060RV Load Lugs and
Panel Connections
FBV16TE070R FBN16TE070R FBH16TE070R FBL16TE070R No Lugs
70 FBV16TE070R2 FBN16TE070R2 FBH16TE070R2 FBL16TE070R2 Load Lugs Only
FBV16TE070RV FBN16TE070RV FBH16TE070RV FBL16TE070RV Load Lugs and
Panel Connections
FBV16TE080R FBN16TE080R FBH16TE080R FBL16TE080R No Lugs
80 FBV16TE080R2 FBN16TE080R2 FBH16TE080R2 FBL16TE080R2 Load Lugs Only
FBV16TE080RV FBN16TE080RV FBH16TE080RV FBL16TE080RV Load Lugs and
Panel Connections
FBV16TE090R FBN16TE090R FBH16TE090R FBL16TE090R No Lugs
90 FBV16TE090R2 FBN16TE090R2 FBH16TE090R2 FBL16TE090R2 Load Lugs Only
FBV16TE090RV FBN16TE090RV FBH16TE090RV FBL16TE090RV Load Lugs and
Panel Connections
FBV16TE100R FBN16TE100R FBH16TE100R FBL16TE100R No Lugs
100 FBV16TE100R2 FBN16TE100R2 FBH16TE100R2 FBL16TE100R2 Load Lugs Only
FBV16TE100RV FBN16TE100RV FBH16TE100RV FBL16TE100RV Load Lugs and
Panel Connections
www.geindustrial.com BuyLog™Catalog 6-71
Rev. 11/13
Data subject to change
without notice
Section 6
Molded Case Circuit Breakers
2-Pole Record Plus™FB 100 Breakers IC @ 600/347 Vac
Rated 35kA 65kA 100kA 150kA
Current (A) Product No. Product No. Product No. Product No. Connection
FBV26TE015R FBN26TE015R FBH26TE015R FBL26TE015R No Lugs
15 FBV26TE015R2 FBN26TE015R2 FBH26TE015R2 FBL26TE015R2 Load Lugs Only
FBV26TE015RV FBN26TE015RV FBH26TE015RV FBL26TE015RV Load Lugs and
Panel Connections
FBV26TE020R FBN26TE020R FBH26TE020R FBL26TE020R No Lugs
20 FBV26TE020R2 FBN26TE020R2 FBH26TE020R2 FBL26TE020R2 Load Lugs Only
FBV26TE020RV FBN26TE020RV FBH26TE020RV FBL26TE020RV Load Lugs and
Panel Connections
FBV26TE025R FBN26TE025R FBH26TE025R FBL26TE025R No Lugs
25 FBV26TE025R2 FBN26TE025R2 FBH26TE025R2 FBL26TE025R2 Load Lugs Only
FBV26TE025RV FBN26TE025RV FBH26TE025RV FBL26TE025RV Load Lugs and
Panel Connections
FBV26TE030R FBN26TE030R FBH26TE030R FBL26TE030R No Lugs
30 FBV26TE030R2 FBN26TE030R2 FBH26TE030R2 FBL26TE030R2 Load Lugs Only
FBV26TE030RV FBN26TE030RV FBH26TE030RV FBL26TE030RV Load Lugs and
Panel Connections
FBV26TE035R FBN26TE035R FBH26TE035R FBL26TE035R No Lugs
35 FBV26TE035R2 FBN26TE035R2 FBH26TE035R2 FBL26TE035R2 Load Lugs Only
FBV26TE035RV FBN26TE035RV FBH26TE035RV FBL26TE035RV Load Lugs and
Panel Connections
FBV26TE040R FBN26TE040R FBH26TE040R FBL26TE040R No Lugs
40 FBV26TE040R2 FBN26TE040R2 FBH26TE040R2 FBL26TE040R2 Load Lugs Only
FBV26TE040RV FBN26TE040RV FBH26TE040RV FBL26TE040RV Load Lugs and
Panel Connections
FBV26TE045R FBN26TE045R FBH26TE045R FBL26TE045R No Lugs
45 FBV26TE045R2 FBN26TE045R2 FBH26TE045R2 FBL26TE045R2 Load Lugs Only
FBV26TE045RV FBN26TE045RV FBH26TE045RV FBL26TE045RV Load Lugs and
Panel Connections
FBV26TE050R FBN26TE050R FBH26TE050R FBL26TE050R No Lugs
50 FBV26TE050R2 FBN26TE050R2 FBH26TE050R2 FBL26TE050R2 Load Lugs Only
FBV26TE050RV FBN26TE050RV FBH26TE050RV FBL26TE050RV Load Lugs and
Panel Connections
FBV26TE060R FBN26TE060R FBH26TE060R FBL26TE060R No Lugs
60 FBV26TE060R2 FBN26TE060R2 FBH26TE060R2 FBL26TE060R2 Load Lugs Only
FBV26TE060RV FBN26TE060RV FBH26TE060RV FBL26TE060RV Load Lugs and
Panel Connections
FBV26TE070R FBN26TE070R FBH26TE070R FBL26TE070R No Lugs
70 FBV26TE070R2 FBN26TE070R2 FBH26TE070R2 FBL26TE070R2 Load Lugs Only
FBV26TE070RV FBN26TE070RV FBH26TE070RV FBL26TE070RV Load Lugs and
Panel Connections
FBV26TE080R FBN26TE080R FBH26TE080R FBL26TE080R No Lugs
80 FBV26TE080R2 FBN26TE080R2 FBH26TE080R2 FBL26TE080R2 Load Lugs Only
FBV26TE080RV FBN26TE080RV FBH26TE080RV FBL26TE080RV Load Lugs and
Panel Connections
FBV26TE090R FBN26TE090R FBH26TE090R FBL26TE090R No Lugs
90 FBV26TE090R2 FBN26TE090R2 FBH26TE090R2 FBL26TE090R2 Load Lugs Only
FBV26TE090RV FBN26TE090RV FBH26TE090RV FBL26TE090RV Load Lugs and
Panel Connections
FBV26TE100R FBN26TE100R FBH26TE100R FBL26TE100R No Lugs
100 FBV26TE100R2 FBN26TE100R2 FBH26TE100R2 FBL26TE100R2 Load Lugs Only
FBV26TE100RV FBN26TE100RV FBH26TE100RV FBL26TE100RV Load Lugs and
Panel Connections
Record Plus™FB 100
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-72
Section 6
Molded Case Circuit Breakers
3-Pole Record Plus™FB 100 Breakers IC @ 600/347 Vac
Rated 35kA 65kA 100kA 150kA
Current (A) Product No. Product No Product No Product No Connection
FBV36TE015R FBN36TE015R FBH36TE015R FBL36TE015R No Lugs
15 FBV36TE015R2 FBN36TE015R2 FBH36TE015R2 FBL36TE015R2 Load Lugs Only
FBV36TE015RV FBN36TE015RV FBH36TE015RV FBL36TE015RV Load Lugs and
Panel Connections
FBV36TE020R FBN36TE020R FBH36TE020R FBL36TE020R No Lugs
20 FBV36TE020R2 FBN36TE020R2 FBH36TE020R2 FBL36TE020R2 Load Lugs Only
FBV36TE020RV FBN36TE020RV FBH36TE020RV FBL36TE020RV Load Lugs and
Panel Connections
FBV36TE025R FBN36TE025R FBH36TE025R FBL36TE025R No Lugs
25 FBV36TE025R2 FBN36TE025R2 FBH36TE025R2 FBL36TE025R2 Load Lugs Only
FBV36TE025RV FBN36TE025RV FBH36TE025RV FBL36TE025RV Load Lugs and
Panel Connections
FBV36TE030R FBN36TE030R FBH36TE030R FBL36TE030R No Lugs
30 FBV36TE030R2 FBN36TE030R2 FBH36TE030R2 FBL36TE030R2 Load Lugs Only
FBV36TE030RV FBN36TE030RV FBH36TE030RV FBL36TE030RV Load Lugs and
Panel Connections
FBV36TE035R FBN36TE035R FBH36TE035R FBL36TE035R No Lugs
35 FBV36TE035R2 FBN36TE035R2 FBH36TE035R2 FBL36TE035R2 Load Lugs Only
FBV36TE035RV FBN36TE035RV FBH36TE035RV FBL36TE035RV Load Lugs and
Panel Connections
FBV36TE040R FBN36TE040R FBH36TE040R FBL36TE040R No Lugs
40 FBV36TE040R2 FBN36TE040R2 FBH36TE040R2 FBL36TE040R2 Load Lugs Only
FBV36TE040RV FBN36TE040RV FBH36TE040RV FBL36TE040RV Load Lugs and
Panel Connections
FBV36TE045R FBN36TE045R FBH36TE045R FBL36TE045R No Lugs
45 FBV36TE045R2 FBN36TE045R2 FBH36TE045R2 FBL36TE045R2 Load Lugs Only
FBV36TE045RV FBN36TE045RV FBH36TE045RV FBL36TE045RV Load Lugs and
Panel Connections
FBV36TE050R FBN36TE050R FBH36TE050R FBL36TE050R No Lugs
50 FBV36TE050R2 FBN36TE050R2 FBH36TE050R2 FBL36TE050R2 Load Lugs Only
FBV36TE050RV FBN36TE050RV FBH36TE050RV FBL36TE050RV Load Lugs and
Panel Connections
FBV36TE060R FBN36TE060R FBH36TE060R FBL36TE060R No Lugs
60 FBV36TE060R2 FBN36TE060R2 FBH36TE060R2 FBL36TE060R2 Load Lugs Only
FBV36TE060RV FBN36TE060RV FBH36TE060RV FBL36TE060RV Load Lugs and
Panel Connections
FBV36TE070R FBN36TE070R FBH36TE070R FBL36TE070R No Lugs
70 FBV36TE070R2 FBN36TE070R2 FBH36TE070R2 FBL36TE070R2 Load Lugs Only
FBV36TE070RV FBN36TE070RV FBH36TE070RV FBL36TE070RV Load Lugs and
Panel Connections
FBV36TE080R FBN36TE080R FBH36TE080R FBL36TE080R No Lugs
80 FBV36TE080R2 FBN36TE080R2 FBH36TE080R2 FBL36TE080R2 Load Lugs Only
FBV36TE080RV FBN36TE080RV FBH36TE080RV FBL36TE080RV Load Lugs and
Panel Connections
FBV36TE090R FBN36TE090R FBH36TE090R FBL36TE090R No Lugs
90 FBV36TE090R2 FBN36TE090R2 FBH36TE090R2 FBL36TE090R2 Load Lugs Only
FBV36TE090RV FBN36TE090RV FBH36TE090RV FBL36TE090RV Load Lugs and
Panel Connections
FBV36TE100R FBN36TE100R FBH36TE100R FBL36TE100R No Lugs
100 FBV36TE100R2 FBN36TE100R2 FBH36TE100R2 FBL36TE100R2 Load Lugs Only
FBV36TE100RV FBN36TE100RV FBH36TE100RV FBL36TE100RV Load Lugs and
Panel Connections
Record Plus™FB 100
www.geindustrial.com BuyLog™Catalog 6-73
Rev. 11/13
Data subject to change
without notice
Molded Case Circuit Breakers Section 6
Releases – Shunt Trip and Undervoltage
Shunt Trip Undervoltage Release
Voltage Product No. Product No.
12 VDC FASHTBW —
24 VAC/DC FASHTDW FAUVRDW
48 VAC/DC FASHTFW FAUVRFW
110-130 VAC/110-125 VDC FASHTJW FAUVRJW
120 VAC FASHTKW —
220/240 VAC, 250 VDC FASHTNW FAUVRNW
277 VAC FASHT7W FAUVR7W
400/480 VAC FASHTUW FAUVRUW
UL Listed for field installation. Accessories are prewired from the factory with 36 inch long leads
(#18 AWG). Shunt trip wire leads are black and UVR wire leads are blue.
Bell Alarm
Contact
Configuration Contacts Contact Rating Wire leads Product No.
1 NO (Form A) Standard 5A @ 277 VAC, 0.3A @ 125 VDC #16 AWG FABAM10W
1 NC (Form B) Standard 5A @ 277 VAC, 0.3A @ 125 VDC #16 AWG FABAM01W
UL Listed for field installation. Accessories are prewired from the factory with 36 inch long leads. Reference
instruction sheet DEH-40324 for wire lead colors.
Auxiliary Switches
Contact Left Mount Right Mount
Configuration Contacts Contact Rating Wire leads Product No. Product No.
1 NO (Form A) Standard 5A @ 277 VAC, #16 AWG FAS10LW FAS10RW
0.3A @ 125 VDC
1 NC (Form B) Standard 5A @ 277 VAC, #16 AWG FAS01LW FAS01RW
0.3A @ 125 VDC
UL Listed for field installation. Accessories are prewired from the factory with 36 inch long leads. Reference
instruction sheet DEH-40324 for wire lead colors.
Mounting Locations and Limitations
Accessory Installation
Accessory Mounting Pocket Location 1 Pole 2 Pole 3 Pole
Shunt Trip or Undervoltage Release 011
Aux. Switch - Left Mount 001
Aux. Switch - Right Mount 001
Bell Alarm 001
Maximum Number of Internal Accessories 014
That Can Be Installed
Record Plus™FB 100
Internal Accessories
Shunt Trip or
Undervoltage
Release
2 pole 3 pole
Bell Alarm
Switch
Auxiliary
Switches
Mounting Locations
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-74
Molded Case Circuit Breakers Section 6
Lugs and Lug Kits
Single Lug Lug Kit
Amp Range Wire Range Strip Length Product No. Product No. (Set of 3)
15-20A 14-10 Cu/Al .40-.50” FCAL12 FCALK12
25-60A 10-4 Cu/Al .40-.50” FCAL13 FCALK13
70-100A 4-1/0 Cu/Al .40-.50” FCAL14 FCALK14
Lug Tightening Torque
Wire Size Torque
#10 AWG 35 in-lb
#8 AWG 40 in-lb
#6-#4 AWG 45 in-lb
#3 AWG - 1/0 50 in-lb
Padlocking Devices
Description Product No.
Padlock Fixed Toggle FB1PF
Padlock EUSERC Toggle FB1PE
Record Plus™FB 100
External Accessories
FB 100 Dimensions
Poles A B C D EFG1 G2 H
1 3.88 (98.6) 3.28 (83.3) 1.06 (26.9) 1.36 (34.5) N/A N/A 5.11 (129.8) 5.01 (127.3) 6.45 (163.8)
2 3.88 (98.6) 3.28 (83.3) 1.06 (26.9) 2.74 (69.6) 0.69 (17.5) 1.38 (35.1) 5.11 (129.8) 5.01 (127.3) 6.45 (163.8)
3 3.88 (98.6) 3.28 (83.3) 1.06 (26.9) 4.11 (104.4) 1.38 (35.1) 1.38 (35.1) 5.11 (129.8) 5.01 (127.3) 6.45 (163.8)
Dimensions in. (mm)
"D" "F"
"E"
"D"
"H"
"G2"
"G1"
"H"
"G2"
"G1"
"D"
"E" "E"
"F"
"H"
"G2"
"G1"
"C"
"B"
"A"
www.geindustrial.com BuyLog™Catalog 6-75
Rev. 11/13
Data subject to change
without notice
Molded Case Circuit Breakers Section 6
Record Plus™FC 100
Reference Publications
Available for download from www.geindustrial.com/publibrary
FC Breaker
Installation Instructions DEH-40463
FC Breaker Accessories
Bell Alarm & Aux. Switch DEH-40324
Shunt Trip & Undervoltage Release DEH-40363
Lug Kits DEH-40532
Outline Drawings
FC 2-3 pole 10085772SH1
Series Ratings DET-008
Trip Curves
Trip Unit Rated Current (A) Trip Curve
15 DES-013
20 DES-014
25 DES-015
30 DES-016
35 DES-017
40 DES-018
45 DES-019
50 DES-020
60 DES-021
70 DES-022
80 DES-023
90 DES-024
100 DES-025
Peak Current Curves DES-030
Peak I2t Curve DES-031
Main Standards
—UL 489
—IEC 947 and associated EN Sections
FC Breaker Markings
cULus UL File E-11592
HID 15-50A
HACR 15 to 100A
Cu/Al 60/75°C 15 to 100A
Current Limiting 15 to 100A
Breaker Frame Rating
Rated Voltage
Breaker Frame
Enclosed Rating
Product Description
Standards
Interruption Capacity
Product Number
FC 100 Amp Frame Overview
Interrupting Ratings — Federal Spec C/B Class WC-375B
UL Listed Interrupting Ratings - IEC Listed Interrupting Ratings,
rms Symmetrical Amperes (in Thousands) Icu, Amperes (in Thousands)
AC Voltage DC Voltage AC Voltage DC Voltage
Type Ampere Rating No. Poles Max AC/DC Voltage 240 480 600/347 250 (2p) 500 (3p) 220-240 400-415 500 250 (2p) 500 (3p)
FCS 15-100 2,3 600VAC, 500VDC 42 25 18 22 30 36 22 14 22 30
FCV 15-100 2,3 600VAC, 500VDC 65 35 22 25 35 50 30 18 25 35
FCN 15-100 2,3 600VAC, 500VDC 150 65 25 30 42 85 50 22 30 42
FCH 15-100 2,3 600VAC, 500VDC 200 100 35 42 65 100 80 36 42 65
FCL 15-100 2,3 600VAC, 500VDC 200 150 42 65 80 200 150 50 65 80
Selection
Record Plus™
, Non-Automatic Circuit Breaker (Molded Case Switch), 600 VAC
2-Pole 3-Pole Lug Kit (3 per kit)
Ampere Rating Product No. Product No. Product No.
60 FCY206F060R FCY306F060R FCALK13
100 FCY206F100R FCY306F100R FCALK14
Product Number Structure F CN3 6 TE 050 R
Frame Rating Interruption Voltage Rated
Family (Amperes) Rating (480V) Poles Rating Type Current (A) Connection
F= Record C= 100 S= 25kA 3= 3 poles 6= 600V TE = Fixed Thermal 015 – 100 R = Standard,
Plus V= 35kA 32 = 2 poles Magnetic No Lugs
N= 65kA in 3-pole R1 = Line and Load
H= 100 kA envelope Lugs Installed
L= 150kA R2 = Load Lugs
Only
1
2
3
4
5
6
7
1
2
3
4
5
6
7
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-76
Molded Case Circuit Breakers Section 6
Record Plus™FC 100
2-Pole Record Plus™FC 100 Breakers IC @ 480 Vac
Rated 25kA 35kA 65kA 100kA 150kA
Current (A) Product No. Product No. Product No. Product No. Product No. Connection
FCS326TE015R FCV326TE015R FCN326TE015R FCH326TE015R FCL326TE015R No Lugs
15 FCS326TE015R1 FCV326TE015R1 FCN326TE015R1 FCH326TE015R1 FCL326TE015R1 Line and Load
Lugs Installed
FCS326TE015R2 FCV326TE015R2 FCN326TE015R2 FCH326TE015R2 FCL326TE015R2 Load Lugs Only
FCS326TE020R FCV326TE020R FCN326TE020R FCH326TE020R FCL326TE020R No Lugs
20 FCS326TE020R1 FCV326TE020R1 FCN326TE020R1 FCH326TE020R1 FCL326TE020R Line and Load
Lugs Installed
FCS326TE020R2 FCV326TE020R2 FCN326TE020R2 FCH326TE020R2 FCL326TE020R2 Load Lugs Only
FCS326TE025R FCV326TE025R FCN326TE025R FCH326TE025R FCL326TE025R No Lugs
25 FCS326TE025R1 FCV326TE025R1 FCN326TE025R1 FCH326TE025R1 FCL326TE025R1 Line and Load
Lugs Installed
FCS326TE025R2 FCV326TE025R2 FCN326TE025R2 FCH326TE025R2 FCL326TE025R2 Load Lugs Only
FCS326TE030R FCV326TE030R FCN326TE030R FCH326TE030R FCL326TE030R No Lugs
30 FCS326TE030R1 FCV326TE030R1 FCN326TE030R1 FCH326TE030R1 FCL326TE030R1 Line and Load
Lugs Installed
FCS326TE030R2 FCV326TE030R2 FCN326TE030R2 FCH326TE030R2 FCL326TE030R2 Load Lugs Only
FCS326TE035R FCV326TE035R FCN326TE035R FCH326TE035R FCL326TE035R No Lugs
35 FCS326TE035R1 FCV326TE035R1 FCN326TE035R1 FCH326TE035R1 FCL326TE035R1 Line and Load
Lugs Installed
FCS326TE035R2 FCV326TE035R2 FCN326TE035R2 FCH326TE035R2 FCL326TE035R2 Load Lugs Only
FCS326TE040R FCV326TE040R FCN326TE040R FCH326TE040R FCL326TE040R No Lugs
40 FCS326TE040R1 FCV326TE040R1 FCN326TE040R1 FCH326TE040R1 FCL326TE040R1 Line and Load
Lugs Installed
FCS326TE040R2 FCV326TE040R2 FCN326TE040R2 FCH326TE040R2 FCL326TE040R2 Load Lugs Only
FCS326TE045R FCV326TE045R FCN326TE045R FCH326TE045R FCL326TE045R No Lugs
45 FCS326TE045R1 FCV326TE045R1 FCN326TE045R1 FCH326TE045R1 FCL326TE045R1 Line and Load
Lugs Installed
FCS326TE045R2 FCV326TE045R2 FCN326TE045R2 FCH326TE045R2 FCL326TE045R2 Load Lugs Only
FCS326TE050R FCV326TE050R FCN326TE050R FCH326TE050R FCL326TE050R No Lugs
50 FCS326TE050R1 FCV326TE050R1 FCN326TE050R1 FCH326TE050R1 FCL326TE050R1 Line and Load
Lugs Installed
FCS326TE050R2 FCV326TE050R2 FCN326TE050R2 FCH326TE050R2 Load Lugs Only
FCS326TE060R FCV326TE060R FCN326TE060R FCH326TE060R FCL326TE060R No Lugs
60 FCS326TE060R1 FCV326TE060R1 FCN326TE060R1 FCH326TE060R1 FCL326TE060R1 Line and Load
Lugs Installed
FCS326TE060R2 FCV326TE060R2 FCN326TE060R2 FCH326TE060R2 FCL326TE060R2 Load Lugs Only
FCS326TE070R FCV326TE070R FCN326TE070R FCH326TE070R FCL326TE070R No Lugs
70 FCS326TE070R1 FCV326TE070R1 FCN326TE070R1 FCH326TE070R1 FCL326TE070R1 Line and Load
Lugs Installed
FCS326TE070R2 FCV326TE070R2 FCN326TE070R2 FCH326TE070R2 FCL326TE070R2 Load Lugs Only
FCS326TE080R FCV326TE080R FCN326TE080R FCH326TE080R FCL326TE080R No Lugs
80 FCS326TE080R1 FCV326TE080R1 FCN326TE080R1 FCH326TE080R1 FCL326TE080R1 Line and Load
Lugs Installed
FCS326TE080R2 FCV326TE080R2 FCN326TE080R2 FCH326TE080R2 FCL326TE080R2 Load Lugs Only
FCS326TE090R FCV326TE090R FCN326TE090R FCH326TE090R FCL326TE090R No Lugs
90 FCS326TE090R1 FCV326TE090R1 FCN326TE090R1 FCH326TE090R1 FCL326TE090R1 Line and Load
Lugs Installed
FCS326TE090R2 FCV326TE090R2 FCN326TE090R2 FCH326TE090R2 FCL326TE090R2 Load Lugs Only
FCS326TE100R FCV326TE100R FCN326TE100R FCH326TE100R FCL326TE100R No Lugs
100 FCS326TE100R1 FCV326TE100R1 FCN326TE100R1 FCH326TE100R1 FCL326TE100R1 Line and Load
Lugs Installed
FCS326TE100R2 FCN326TE100R2 FCH326TE100R2 FCL326TE100R2 Load Lugs Only
www.geindustrial.com BuyLog™Catalog 6-77
Rev. 11/13
Data subject to change
without notice
Molded Case Circuit Breakers Section 6
Record Plus™FC 100
3-Pole Record Plus™FC 100 Breakers IC @ 480 Vac
Rated 25kA 35kA 65kA 100kA 150kA
Current (A) Product No. Product No. Product No. Product No. Product No. Connection
FCS36TE015R FCV36TE015R FCN36TE015R FCH36TE015R FCL36TE015R No Lugs
15 FCS36TE015R1 FCV36TE015R1 FCN36TE015R1 FCH36TE015R1 FCL36TE015R1 Line and Load
Lugs Installed
FCS36TE015R2 FCV36TE015R2 FCN36TE015R2 FCH36TE015R2 FCL36TE015R2 Load Lugs Only
FCS36TE020R FCV36TE020R FCN36TE020R FCH36TE020R FCL36TE020R No Lugs
20 FCS36TE020R1 FCV36TE020R1 FCN36TE020R1 FCH36TE020R1 FCL36TE020R1 Line and Load
Lugs Installed
FCS36TE020R2 FCV36TE020R2 FCN36TE020R2 FCH36TE020R2 FCL36TE020R2 Load Lugs Only
FCS36TE025R FCV36TE025R FCN36TE025R FCH36TE025R FCL36TE025R No Lugs
25 FCS36TE025R1 FCV36TE025R1 FCN36TE025R1 FCH36TE025R1 FCL36TE025R1 Line and Load
Lugs Installed
FCS36TE025R2 FCV36TE025R2 FCN36TE025R2 FCH36TE025R2 FCL36TE025R2 Load Lugs Only
FCS36TE030R FCV36TE030R FCN36TE030R FCH36TE030R FCL36TE030R No Lugs
30 FCS36TE030R1 FCV36TE030R1 FCN36TE030R1 FCH36TE030R1 FCL36TE030R1 Line and Load
Lugs Installed
FCS36TE030R2 FCV36TE030R2 FCN36TE030R2 FCH36TE030R2 FCL36TE030R2 Load Lugs Only
FCS36TE035R FCV36TE035R FCN36TE035R FCH36TE035R FCL36TE035R No Lugs
35 FCS36TE035R1 FCV36TE035R1 FCN36TE035R1 FCH36TE035R1 FCL36TE035R1 Line and Load
Lugs Installed
FCS36TE035R2 FCV36TE035R2 FCN36TE035R2 FCH36TE035R2 FCL36TE035R2 Load Lugs Only
FCS36TE040R FCV36TE040R FCN36TE040R FCH36TE040R FCL36TE040R No Lugs
40 FCS36TE040R1 FCV36TE040R1 FCN36TE040R1 FCH36TE040R1 FCL36TE040R1 Line and Load
Lugs Installed
FCS36TE040R2 FCV36TE040R2 FCN36TE040R2 FCH36TE040R2 FCL36TE040R2 Load Lugs Only
FCS36TE045R FCV36TE045R FCN36TE045R FCH36TE045R FCL36TE045R No Lugs
45 FCS36TE045R1 FCV36TE045R1 FCN36TE045R1 FCH36TE045R1 FCL36TE045R1 Line and Load
Lugs Installed
FCS36TE045R2 FCV36TE045R2 FCN36TE045R2 FCH36TE045R2 FCL36TE045R2 Load Lugs Only
FCS36TE050 FCV36TE050R FCN36TE050R FCH36TE050R FCL36TE050R No Lugs
50 FCS36TE050R1 FCV36TE050R1 FCN36TE050R1 FCH36TE050R1 FCL36TE050R1 Line and Load
Lugs Installed
FCS36TE050R2 FCV36TE050R2 FCN36TE050R2 FCH36TE050R2 FCL36TE050R2 Load Lugs Only
FCS36TE060R FCV36TE060R FCN36TE060R FCH36TE060R FCL36TE060R No Lugs
60 FCS36TE060R1 FCV36TE060R1 FCN36TE060R1 FCH36TE060R1 FCL36TE060R1 Line and Load
Lugs Installed
FCS36TE060R2 FCV36TE060R2 FCN36TE060R2 FCH36TE060R2 FCL36TE060R2 Load Lugs Only
FCS36TE070R FCV36TE070R FCN36TE070R FCH36TE070R FCL36TE070R No Lugs
70 FCS36TE070R1 FCV36TE070R1 FCN36TE070R1 FCH36TE070R1 FCL36TE070R1 Line and Load
Lugs Installed
FCS36TE070R2 FCV36TE070R2 FCN36TE070R2 FCH36TE070R2 FCL36TE070R2 Load Lugs Only
FCS36TE080R FCV36TE080R FCN36TE080R FCH36TE080R FCL36TE080R No Lugs
80 FCS36TE080R1 FCV36TE080R1 FCN36TE080R1 FCH36TE080R1 FCL36TE080R1 Line and Load
Lugs Installed
FCS36TE080R2 FCV36TE080R2 FCN36TE080R2 FCH36TE080R2 FCL36TE080R2 Load Lugs Only
FCS36TE090R FCV36TE090R FCN36TE090R FCH36TE090R FCL36TE090R No Lugs
90 FCS36TE090R1 FCV36TE090R1 FCN36TE090R1 FCH36TE090R1 FCL36TE090R1 Line and Load
Lugs Installed
FCS36TE090R2 FCV36TE090R2 FCN36TE090R2 FCH36TE090R2 FCL36TE090R2 Load Lugs Only
FCS36TE100R FCV36TE100R FCN36TE100R FCH36TE100R FCL36TE100R No Lugs
100 FCS36TE100R1 FCV36TE100R1 FCN36TE100R1 FCH36TE100R1 FCL36TE100R1 Line and Load
Lugs Installed
FCS36TE100R2 FCV36TE100R2 FCN36TE100R2 FCH36TE100R2 FCL36TE100R2 Load Lugs Only
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-78
Molded Case Circuit Breakers Section 6
Record Plus™FC 100
Internal Accessories (supplied with leads attached)
Contacts – Auxiliary and Bell Alarm (Rated 5A @240VAC, 0.5A @125VDC)
Normally Open Normally Closed
Accessory Product No. Product No.
Aux. Switch Right Mounted FAS10RW FAS01RW
Aux. Switch Left Mounted FAS10LW FAS01LW
Bell Alarm Mechanism FABAM10W FABAM01W
Releases – Shunt Trip and Undervoltage
Shunt Trip Undervoltage Release
Rating (Inrush Rating (Inrush
Voltage Power Consumption) Product No. Power Consumption) Product No.
12 VDC 200 mA / 2.4W FASHTBW ——
24 VAC/DC 100 mA / 3.6W FASHTDW 50 mA / 1.2W FAUVRDW
48 VAC/DC 60 mA / 2.88W FASHTFW 20 mA / 0.96W FAUVRFW
120 VAC 40 mA / 4.8W FASHTKW ——
110/130 VAC/DC 40 mA / 4.8W FASHTJW 15 mA / 1.8W FAUVRJW
220/240 VAC, 250 VDC 20 mA / 4.6W FASHTNW 15 mA / 3.45W FAUVRNW
277 VAC 11 mA / 3.0W FASHT7W 15 mA / 4.0W FAUVR7W
400/480 VAC 20 mA / 8.4W FASHTUW 15 mA / 6.3W FAUVRUW
Mounting Locations and Limitations
Accessory Installation
Accessory Mounting Pocket Location 2 Pole 3 Pole
Shunt Trip or Undervoltage Release 11
Aux. Switch - Left Mount 11
Aux. Switch - Right Mount 11
Bell Alarm 11
Maximum Number of Internal Accessories That Can Be Installed 44
Plug-In Types
Type Description Product No.
Complete Kits 3 Pole - LSL - Horizontal Strap FCDDF1
3 Pole - SLS - Horizontal Strap FCDDF2
3 Pole - LSL - Vertical Strap FCDDF3
3 Pole - SLS - Vertical Strap FCDDF4
Secondary Disconnect Secondary Disconnect Kit FCDSD
Secondary Disconnect - Base Part FCDSDP
Secondary Disconnect - Breaker Part FCDSDB
Mounting Plate Mounting Plate FCDMP
Hardware Kits
Description Product No.
Mounting screws for mounting plates with tapped holes, quantity 4 FCMSK3
(#8-32 x 2 7/8” screws with lockwashers)
Mounting screws for mounting plates with clearance holes, quantity 4 FCMSK4
(#8-32 x 3” screws with nuts lockwashers)
Nut plates (quantity 3) FCNP3
Nut plates (quantity 36) FCNPB
Electrical Operator Motor Drives,
Front Mounted
Voltage Product No.
120 VAC/125 VDC FCEMF3
220/240 VAC, 50/60 Hz FCEMF6
48 VDC FCEMFF
External Accessories
Padlocking Devices
Description Product No.
Padlock Fixed Toggle FC1PF
Padlock EUSERC Toggle FC1PE
Auxiliary Switch/Bell Alarm Mechanism
Shunt Trip/Undervoltage Release
Motor Operator
Padlock
Plug-In Bases
Plug-In Plate
Shunt Trip or
Undervoltage
Release
2- or 3 pole
Bell Alarm
Switch
Auxiliary
Switches
Mounting Locations
www.geindustrial.com BuyLog™Catalog 6-79
Rev. 11/13
Data subject to change
without notice
Molded Case Circuit Breakers Section 6
Record Plus™FC 100
External Accessories
A
B
C
D
E E
H
GF
FC 100 Amp Dimensions
Lugs and Lug Kits
Single Lug Lug Kit
Amp Range Wire Range Strip Length Product No. Product No. (Set of 3)
15-20A 14-10 Cu/Al .40-.50” FCAL12 FCALK12
25-60A 10-4 Cu/Al .40-.50” FCAL13 FCALK13
70-100A 4-1/0 Cu/Al .40-.50” FCAL14 FCALK14
Lug Tightening Torque
Wire Size Torque
#10 AWG 35 in-lb
#8 AWG 40 in-lb
#6-#4 AWG 45 in-lb
#3 AWG - 1/0 50 in-lb
Handles and Handle Accessories
Type Description Product No.
STDA Flange Flange Handle for Variable Same as Spectra™: 6-inch for NEMA 12/13 STDA1
Handles, Depth Operating Mechanism Same as Spectra™: 10-inch for NEMA 12/13 STDA2
Operators, and Same as Spectra™: 6-inch for NEMA 4/4X STDA1X
Hardware Kits Same as Spectra™: 10-inch for NEMA 4/4X STDA2X
Flange Operating Mechanism Operating Mechanism Only FCNFM
Flange Stiffener Kit Use with FCNFM TDSR
Extender Kit Use with FCNFM TDSR
Extended Drive Stud Use with FCNFM TDS1
Door Hardware Kit NEMA12/13 Door Hinged on Left, NEMA 12/13, 2-point Kit TDV1
Door Hardware Kit NEMA 4/4X Door Hinged on Left, NEMA 4/4X, 2-point Kit TDV1X
Third Point Latch Kit For Use With TDV1/TDV1X Above TDV3
Door Hardware Kit NEMA12/13 Door Hinged on Right, NEMA 12/13 2-point Kit TDV1L
Third Point Latch Kit For Use with TDV1L, TDC1LX Above TDV3L
Auxiliary DPDT for STDA Handle on Right TDAS1L2
Contact Kits DPDT for STDA Handle on Left TDAS1R2
FC 100 Dimensions
Frame A B C D EFGH
FC 3.7 (29.1) 3.2 (81.3) .96 (24.4) 3.0 (76.2) 1.0 (25.4) 6.4 (162.6) 5.0 (127.0) 1.0 (25.4)
Dimensions in. (mm)
STDA Flange Handles
and Operators
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-80
Section 6
Reference Publications
Available for download from www.geindustrial.com/publibrary
FE Breaker
Installation Instructions DEH-41640
Outline Drawing 10101247PV1
FE Breaker Accessories
Bell Alarm & Aux Switch DEH-40324
Shunt Trip & UVR DEH-40259
Padlock Device DEH-41059
Lug Kits DEH-41054
Auxiliary Contacts DEH-40261
Panelboards
Spectra™Power Panel - Plug-in Kits DEH-40402
Spectra™Power Panel - Bolt-on Kits DEH-40425
Series Ratings DET-008
External Operators
STDA Style DEH-41014
TDM Style DEH-41025
Trip Curves
Record Plus FE with PremEon S Trip - LSI Protections DES-115
Record Plus FE with PremEon S Trip - GF Protection DES-116
Record Plus FE with PremEon S Trip - Mag only Motor Circuit Protector DES-117
Peak Current Curves DES-205
Peak l2t Curve DES-206
Main Standards
—UL/cUL 489
—HACR (heating, air conditioning, and refrigeration)
—Naval
Breaker Frame Rating
Product Description
Standards & Markings
Interrupting Ratings
Lug Data & Torque Info
Product Number
Push to Trip
Interrupting Ratings
UL Listed Interrupting Ratings -
rms Symmetrical Amperes (in Thousands) AC Voltage
Type Ampere Rating Max Voltage No. Poles 240 480
FEN 25-250A 480VAC 2 150 65
3 150 65
FEH 25-250A 480VAC 2 200 100
3 200 100
Product Number Structure
12
3
4
5
6
7
1
2
3
4
5
6
7
Molded Case Circuit Breakers
Record Plus™FE 250
Cross Reference
SMR1 Equipped FE MCCB Rating Plug Amps PremEon Equipped MCCB
FE(N/H)(2/3)4AA0025R 20, 25 FE(N/H)(2/3)4DB025KF
FE(N/H)(2/3)4AA0060R 25, 30, 40, 50, 60 FE(N/H)(2/3)4DB060KF
FE(N/H)(2/3)4AA0125R 50, 60, 70, 80, 90, 100 ,110 ,125 FE(N/H)(2/3)4DB125KF
FE(N/H)(2/3)4AA0150R 70, 80, 90, 100, 110, 125, 150 FE(N/H)(2/3)4DB150KF
FE(N/H)(2/3)4AA0250R 100, 110, 125, 150, 175, 200, 225, 250 FE(N/H)(2/3)4DB250KF
Family
F = Record Plus
Frame Size
E = 250A
Interruption
Rating (@480VAC)
N = 65kA
H = 100kA
Poles
2 = 2-Pole
in 3-Pole Frame
3 = 3 Pole
Voltage
4 = 480VAC
Trip Unit Type
D = PremEon S1
Trip Unit Protection
B = LI
C = LI 400 Hz
G = LIG
w/ Ground Fault
M =Mag-Only MCP
P = Mag-Only MCP
w/ Ground Fault
Trip Unit Amps
025 = 25A
060 = 60A
125 = 125A
150 = 150A
250 = 250A
Frame Amps
K = 250A
Connection
Configuration
F = Standard,
No Lugs
F E N 3 4 D B 250 K F
1Requires tamper-resistant Torx T15 tool for adjustment.
www.geindustrial.com BuyLog™Catalog 6-81
Rev. 11/13
Data subject to change
without notice
Section 6
Molded Case Circuit Breakers
Record Plus™FE 250
Breaker Frames
LIG Trip Unit (With Tracking Short-Time)
2-Pole Record Plus FE Breakers
65kAIC @ 480 Vac 100kAIC @ 480 VAC
Current Sensor (A) Product Number Product Number
25 FEN24DG025KF FEH24DG025KF
60 FEN24DG060KF FEH24DG060KF
125 FEN24DG125KF FEH24DG125KF
150 FEN24DG150KF FEH24DG150KF
250 FEN24DG250KF FEH24DG250KF
3-Pole Record Plus FE Breakers
65kAIC @ 480 Vac 100kAIC @ 480 VAC
Current Sensor (A) Product Number Product Number
25 FEN34DG025KF FEH34DG025KF
60 FEN34DG060KF FEH34DG060KF
125 FEN34DG125KF FEH34DG125KF
150 FEN34DG150KF FEH34DG150KF
250 FEN34DG250KF FEH34DG250KF
Current Sensor (A) Amp Settings (LT Pickup)
25 8, 9, 10, 11, 13, 14, 15, 16, 18, 19, 20, 21, 23, 24, 25
60 18, 20, 25, 27, 30, 33, 35, 40, 42, 45, 48, 50, 54, 57, 60
125 40, 45, 50, 60, 65, 70, 75, 80, 90, 95, 100, 105, 110, 120, 125
150 45, 50, 60, 70, 75, 80, 90, 100, 105, 110, 120, 125, 135, 145, 150
250 80, 90, 100, 110, 125, 135, 150, 165, 175, 190, 200, 215, 225, 240, 250
FE Breakers and MCP's equipped with the PremEon trip unit do not
use Rating Plugs to determine Amp rating. The trip unit features
an adjustment knob to set the Amp rating (Long-Time Pickup).
The knob is located behind a sealable cover and requires a
tamper-resistant Torx T15 tool. The tool is available through many
industrial supply companies. The maximum Amp rating of the
breaker frame is shown in the "Current Sensor" column below.
The available Amp rating settings (LT Pickup values), by sensor, are
as follows:
LI Trip Unit (With Tracking Short-Time)
2-Pole Record Plus FE Breakers
65kAIC @ 480 Vac 100kAIC @ 480 VAC
Current Sensor (A) Product Number Product Number
25 FEN24DB025KF FEH24DB025KF
60 FEN24DB060KF FEH24DB060KF
125 FEN24DB125KF FEH24DB125KF
150 FEN24DB150KF FEH24DB150KF
250 FEN24DB250KF FEH24DB250KF
3-Pole Record Plus FE Breakers
65kAIC @ 480 Vac 100kAIC @ 480 VAC
Current Sensor (A) Product Number Product Number
25 FEN34DB025KF FEH34DB025KF
60 FEN34DB060KF FEH34DB060KF
125 FEN34DB125KF FEH34DB125KF
150 FEN34DB150KF FEH34DB150KF
250 FEN34DB250KF FEH34DB250KF
400 Hz LI Trip Unit (With Tracking Short-Time)1
2-Pole Record Plus FE Breakers
65kAIC @ 480 Vac 100kAIC @ 480 VAC
Current Sensor (A) Product Number Product Number
25 FEN24DB025KF FEH24DB025KF
60 FEN24DB060KF FEH24DB060KF
125 FEN24DB125KF FEH24DB125KF
150 FEN24DB150KF FEH24DB150KF
250 FEN24DB250KF FEH24DB250KF
3-Pole Record Plus FE Breakers
65kAIC @ 480 Vac 100kAIC @ 480 VAC
Current Sensor (A) Product Number Product Number
25 FEN34DB025KF FEH34DB025KF
60 FEN34DB060KF FEH34DB060KF
125 FEN34DB125KF FEH34DB125KF
150 FEN34DB150KF FEH34DB150KF
250 FEN34DB250KF FEH34DB250KF
1400 Hz FE breakers require de-rating and are not UL listed.
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-82
Section 6
Molded Case Circuit Breakers
Record Plus™FE 250
Internal and External Accessories
Releases – Shunt Trip and Undervoltage
Shunt Trip Undervoltage Release
Voltage Product No. Product No.
12 VDC FASHTBW —
24 VAC/DC FASHTDW FAUVRDW
48 VAC/DC FASHTFW FAUVRFW
110-130 VAC/110-125 VDC FASHTJW FAUVRJW
120 VAC FASHTKW —
220/240 VAC, 250 VDC FASHTNW FAUVRNW
277 VAC FASHT7W FAUVR7W
400/480 VAC FASHTUW FAUVRUW
UL Listed for field installation. Accessories are prewired from the factory with 36 inch long leads
(#18 AWG). Shunt trip wire leads are black and UVR wire leads are blue.
Bell Alarm
Contact
Configuration Contact Rating Wire leads Product No.
1 NO (Form A) 5A @ 277 VAC, #16 AWG FABAM10W
0.3A @ 125 VDC
1 NC (Form B) 5A @ 277 VAC, #16 AWG FABAM01W
0.3A @ 125 VDC
UL Listed for field installation. Accessories are prewired from the factory with 36 inch long leads. Reference
instruction sheet DEH-40324 for wire lead colors.
Auxiliary Switches
Contact Left Mount Right Mount
Configuration Contact Rating Wire leads Product No. Product No.
1 NO (Form A) 5A @ 277 VAC, #16 AWG FAS10LW FAS10RW
0.3A @ 125 VDC
1 NC (Form B) 5A @ 277 VAC, #16 AWG FAS01LW FAS01RW
0.3A @ 125 VDC
UL Listed for field installation. Accessories are prewired from the factory with 36 inch long leads. Reference
instruction sheet DEH-40324 for wire lead colors.
Mounting Locations and Limitations
Accessory Mounting Pocket Location Maximum Quantity
Shunt Trip or Undervoltage Release 1
Aux. Switch - Left Mount 2
Aux. Switch - Right Mount 2
Bell Alarm Mechanism 1
Lug Kits
Lug Kit Lug Kit w/
Lug Torque Single Lug (3 Lugs + Lug Cover) Control Wire Terminal
Ampere Rating Conductor Size (Max) Product No. Product No. Product No.
150A #14 - 3/0 Cu / Al 150 in-lb FCAL15 FCALK15 FCALK15LV
250A #8 - 250MCM Cu / #8 - 350MCM Al 275 in-lb FCAL16 FCALK16 FCALK16LV
Mounting Locations
Auxiliary
Switch
Bell Alarm
Mechanism
Shunt Trip or
Undervoltage
Release
Auxiliary
Switch
PremEon S External Ground Fault CTs
Description Product Number
25A External Neutral CT for FE with PremEon S FEGS0025
60A External Neutral CT for FE with PremEon S FEGS0060
125A External Neutral CT for FE with PremEon S FEGS0125
150A External Neutral CT for FE with PremEon S FEGS0150
250A External Neutral CT for FE with PremEon S FEGS0250
www.geindustrial.com BuyLog™Catalog 6-83
Rev. 11/13
Data subject to change
without notice
Section 6
Molded Case Circuit Breakers
Record Plus™FE 250
Internal and External Accessories
60.63 ±.30
64.00
35.0 35.0
27.55
104.4
35.0 35.0
52.60
[ 2.07 ]
73.5
[ 2.9 ]
77.0
[ 3.0 ]
81.0
[ 3.2 ]
52.60
[2.07]
77.0
[ 3.0 ]
80.50 ±.30
[ 3.17 ±.01 ]
89.5
[ 3.5 ]
93.55 ±.30
[ 3.68 ±.01 ]
18.00
19.00
7.30
R3.3
[ .1 ]
.50 4.95
139.78 ±.30
125.53
35.0
18.0
R4.75
17.5
3.08
15.60 ±.30
170.10 ±.50
°5.70 °9.00
107.75
[4.24]
108.36 ±.30
[ 4.27 ±.01 ]
96.40
47.4
[ 1.9 ]
94.5
[ 3.7 ]
20.87°±2.00°
22.14°±1.60°
1.58°±1.10°
17.68°±1.20°
111.76 ±.30
[ 4.400 ±.011 ]
LINE END
LOAD END
RESET
OFF
TRIP
ON
Dimensions in. (mm)
FE 250 Dimensions
External Operators
Type Description Product Number
Same as Spectra 6 inch for NEMA 12/13 STDA1
STDA Flange Handle for Variable Same as Spectra 10 inch for NEMA 12/13 STDA2
Depth Operating Mechanism Same as Spectra 6 inch for NEMA 4/4X STDA1X
Same as Spectra 10 inch for NEMA 4/4X STDA2X
STDA Flange Flange Stiffener Kit Use with FENFM TDSR
Handles and Extender Kit Use with FENFM TDSR
Hardware Kits Extended Drive Stud Use with FENFM TDS1
Door Hardware Kit NEMA 12/13 Door Hinged on Left, NEMA 12/13 2-point Kit TDV1
Door Hardware Kit NEMA 4/4X Door Hinged on Left, NEMA 4/4X 2-point Kit TDV1X
Third Point Latch Kit For Use with TDV1L, TDC1LX Above TDV3
Door hardware Kit NEMA 12/13 Door Hinged on Right, NEMA 12/13 2-point Kit TDV1L
Third Point Latch Kit For Use with TDV1L, TDC1LX Above TDV3L
TDM Style Handle Handle for FENRM2 / FENRM4 THCH45
Operators
60.63 ±.30
64.00
35.0 35.0
27.55
104.4
35.0 35.0
52.60
[ 2.07 ]
73.5
[ 2.9 ]
77.0
[ 3.0 ]
81.0
[ 3.2 ]
52.60
[2.07]
77.0
[ 3.0 ]
80.50 ±.30
[ 3.17 ±.01 ]
89.5
[ 3.5 ]
93.55 ±.30
[ 3.68 ±.01 ]
18.00
19.00
7.30
R3.3
[ .1 ]
.50 4.95
139.78 ±.30
125.53
35.0
18.0
R4.75
17.5
3.08
15.60 ±.30
170.10 ±.50
°5.70 °9.00
107.75
[4.24]
108.36 ±.30
[ 4.27 ±.01 ]
96.40
47.4
[ 1.9 ]
94.5
[ 3.7 ]
20.87°±2.00°
22.14°±1.60°
1.58°±1.10°
17.68°±1.20°
111.76 ±.30
[ 4.400 ±.011 ]
LINE END
LOAD END
RESET
OFF
TRIP
ON
60.63 ±.30
64.00
35.0 35.0
27.55
104.4
35.0 35.0
52.60
[ 2.07 ]
73.5
[ 2.9 ]
77.0
[ 3.0 ]
81.0
[ 3.2 ]
52.60
[2.07]
77.0
[ 3.0 ]
80.50 ±.30
[ 3.17 ±.01 ]
89.5
[ 3.5 ]
93.55 ±.30
[ 3.68 ±.01 ]
18.00
19.00
7.30
R3.3
[ .1 ]
.50 4.95
139.78 ±.30
125.53
35.0
18.0
R4.75
17.5
3.08
15.60 ±.30
170.10 ±.50
°5.70 °9.00
107.75
[4.24]
108.36 ±.30
[ 4.27 ±.01 ]
96.40
47.4
[ 1.9 ]
94.5
[ 3.7 ]
20.87°±2.00°
22.14°±1.60°
1.58°±1.10°
17.68°±1.20°
111.76 ±.30
[ 4.400 ±.011 ]
LINE END
LOAD END
RESET
OFF
TRIP
ON
Mounting Screw Kits
Description Product Number
Mounting Screw Kit (#10) for Tapped Holes FEMSK1
Padlocking Device
Description Product Number
EUSERC Compliant Padlock FE1PE
Other Accessories
Description Product Number
Fin Cover FEUA3
Terminal Shield Fin Cover FEJS3
Nut Plate / Terminal Shoe FEJN3
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-84
Molded Case Circuit Breakers Section 6
Main Standards
—UL489/cUL489
—IEC 947 and associated EN Sections
Other Global Standards
BS, CE, CEI, JIS, UNE, VDE
FG Breaker Markings
cULus UL File E-11592
HACR 250 to 600A
Cu/Al 60/75°C 250 to 600A
Current Limiting 250 to 600A
Record Plus™FG 600
Breaker Frame Rating
Product Description
Standards & Markings
Interrupting Ratings
Lug Data & Torque Info
Product Number
Push to Trip
12
3
4
5
6
7
1
2
3
4
5
6
7
Features
Record Plus™FG Molded Case Circuit Breakers are available with
either PremEon S or advanced (SMR2) trip units.
FG600 breakers and MCPs equipped with the PremEon trip unit do
not use rating plugs to determine Amp rating. The trip unit
features an adjustment knob to set the Amp rating (Long-Time
Pickup). The knob is located behind a sealable cover and requires
a tamper-resistant Torx T15 tool. The tool is available through
many industrial supply companies. The maximum Amp rating of
the breaker frame and the available Amp rating settings (Long-
Time Pickup values) by sensor, are shown on page 6-85. FG600
breakers equipped with SMR2 trip units require rating plugs to
determine the breaker’s current rating, but also allow individual
adjustment of Long-Time delay, Short-Time pickup and Delay, and
Ground Fault Pickup and Delay (if so equipped). Zone Selective
Interlocking (ZSI), Ground Fault Alarm, and Modbus
Communications are also available via the SMR2’s interface.
PremEon S
Standard
—Adjustable INST Pickup
—Adjustable LT Pickup1
Optional
—Adjustable GF Pickup and Delay
1Available via adjustment with special Torx T15 tool
2Available via Adjustable Rating Plug
3Must be ordered on the breaker frame
SMR2
Standard
—Fixed LT Pickup, set by Rating Plug Characteristic
—Adjustable LT Delay
—Adjustable ST Pickup and Delay
—Adjustable INST Pickup
Optional
—Adjustable LT Pickup2
—Zone Selective Interlocking Capability3
—Adjustable GF (Alarm or Trip) Pickup and Delay
—Trip Unit Flag for Trip Reason Indication
—Ammeter
—Load Shedding Contact
—Communications via Modbus
Standard features of SMR2 trip units are supplied installed on
the breaker frame. Zone Selective Interlocking must be ordered
on the breaker frame, and cannot be user-defeated. Adjustable
Long-Time pickup functionality is achieved through the use of
adjustable rating plugs, which must be ordered separately from
the breaker frame, and sized to match the CT/Sensor rating of
the frame.
Optional features of the SMR2 (except ZSI) are available via user-
installed expansion modules, which, like rating plugs, must be
ordered separately.
Reference Publications
Available for download from www.geindustrial.com/publibrary
FG Breaker
Installation Instructions DEH-41639
FG Breaker Accessories
Bell Alarm & Aux. Switch DEH-40324
Shunt Trip & UVR DEH-40259
Padlock Device DEH-41031
Lug Kits DEH-40404
Auxiliary Contacts DEH-40261
Trip Unit Test Kit (FAT) DEH-40358
SMR2 Expansion Modules DEH-40408
SMR2 Modbus User Manual DEH-41181
SMR2 External Contact Module DEH-40409
Panelboards
Spectra™Power Panel - Plug-in Kits - Single DEH-40420
Spectra™Power Panel - Plug-in Kits - Double DEH-40419
Spectra™Power Panel - Bolt-on Kits - Single DEH-40426
Spectra™Power Panel - Bolt-on Kits - Double DEH-41047
Series Ratings DET-008
Outline Drawing 10085108SHI
Trip Curves
Peak Current Curve DES-040
Peak l2t Curve DES-041
Record Plus FG with PremEon Trip - LSI Protections DES-118
Record Plus FG with PremEon Trip - GF Protection DES-119
Record Plus FG with PremEon Trip - Mag-only
Motor Circuit Protector DES-120
SMR2 Trip Unit
Phase Protection DES-201
Ground Fault Protection and Alarm DES-202
Cross Reference
SMR1 Equippped FG MCCB Rating Plug Amps PremEon Equipped MCCB
FG(N/H/L/P)(2/3)6AA0250R_ _ 100, 110, 125, 150, FG(N/H/L/P)(2/3)6DB250LF
175, 200, 225, 250
FG(N/H/L/P)(2/3)6AA0400R_ _ 175, 200, 225, 250, FG(N/H/L/P)(2/3)6DB400LF
300, 350, 400
FG(N/H/L/P)(2/3)6AA0600R_ _ 300, 350, 400, 450, 500, 600 FG(N/H/L/P)(2/3)6DB600MF
www.geindustrial.com BuyLog™Catalog 6-85
Rev. 11/13
Data subject to change
without notice
LI Trip Unit (With Tracking Short-Time)
2-Pole Record Plus FG Breakers
65kAIC @480 Vac 100kAIC @480 Vac 150kAIC @480 Vac 200kAIC @480 Vac
Current Sensor (A) Product Number Product Number Product Number Product Number
250 FGN26DB250LF FGH26DB250LF FGL26DB250LF FGP26DB250LF
400 FGN26DB400LF FGH26DB400LF FGL26DB400LF FGP26DB400LF
600 FGN26DB600MF FGH26DB600MF FGL26DB600MF FGP26DB600MF
3-Pole Record Plus FG Breakers
65kAIC @480 Vac 100kAIC @480 Vac 150kAIC @480 Vac 200kAIC @480 Vac
Current Sensor (A) Product Number Product Number Product Number Product Number
250 FGN36DB250LF FGH36DB250LF FGL36DB250LF FGP36DB250LF
400 FGN36DB400LF FGH36DB400LF FGL36DB400LF FGP36DB400LF
600 FGN36DB600MF FGH36DB600MF FGL36DB600MF FGP36DB600MF
LIG Trip Unit (With Tracking Short-Time)
2-Pole Record Plus FG Breakers
65kAIC @480 Vac 100kAIC @480 Vac 150kAIC @480 Vac 200kAIC @480 Vac
Current Sensor (A) Product Number Product Number Product Number Product Number
250 FGN26DG250LF FGH26DG250LF FGL26DG250LF FGP26DG250LF
400 FGN26DG400LF FGH26DG400LF FGL26DG400LF FGP26DG400LF
600 FGN26DG600MF FGH26DG600MF FGL26DG600MF FGP26DG600MF
3-Pole Record Plus FG Breakers
65kAIC @480 Vac 100kAIC @480 Vac 150kAIC @480 Vac 200kAIC @480 Vac
Current Sensor (A) Product Number Product Number Product Number Product Number
250 FGN36DG250LF FGH36DG250LF FGL36DG250LF FGP36DG250LF
400 FGN36DG400LF FGH36DG400LF FGL36DG400LF FGP36DG400LF
600 FGN36DG600MF FGH36DG600MF FGL36DG600MF FGP36DG600MF
Molded Case Circuit Breakers Section 6
Record Plus™FG 600
Interrupting Ratings
UL Listed Interrupting Ratings - EN 60947-2 Interrupting Ratings -
rms Symmetrical Amperes (in Thousands) AC Voltage rms Symmetrical Amperes (in Thousands)
Type Ampere Rating Max Voltage No. Poles 240 480 600 240 400-415 690
FGN 250-600A 600VAC 2 150 65 25 –––
3 150 65 25 85 50 10
FGH 250-600A 600VAC 2 200 100 35 –––
3 200 100 35 100 80 22
FGL1250-600A 600VAC 2 200 150 42 –––
3 200 150 42 200 150 40
FGP1250-600A 600VAC 2 200 200 65 –––
3 200 200 65 –––
1Not suitable for reverse feed.
Product Number Structure
FGN36DB250LF
Family
F
= Record Plus
Frame Size
G
= 600A
Interruption Rating
(@480VAC)
N
= 65kA
H
= 100kA
L
= 150kA
P
= 200kA
Poles
2
= 2-Pole
in 3-Pole Frame
3
= 3-Pole
Voltage
6
= 600VAC
Trip Unit Type
D
= PremEon S
2
K
= SMR2
Trip Unit Protection
A
= SMR2 standard
Z
= SMR2 with ZSI
B
= LI
C
= LI 400 Hz
G
= LIG w/Ground Fault
M
= Mag-Only MCP
P
= Mag-Only MCP
w/Ground Fault
Trip Unit/Frame Amps
0250
= 250A SMR2
0400
= 400A SMR2
0600
= 600A SMR2
250L
= 250A PremEon
400L
= 400A PremEon
600M
= 600A PremEon
Connection
Configuration
R0
= Standard No Lugs
R1
= Line and Load Lugs
3
R2
= Load Lugs
3
R3
= Line Lugs
3
F
= PremEon Standard
No Lugs
Current Sensor (A) Amp Settings (LT Pickup)
250 80, 90, 100, 110, 125, 135, 150, 165, 175, 190, 200, 215, 225, 240, 250
400 125, 150, 175, 180, 200, 225, 240, 250, 275, 300, 325, 340, 350, 375, 400
600 175, 200, 225, 250, 300, 325, 350, 400, 425, 450, 475, 500, 550, 575, 600
PremEon S
FG Breakers and MCP's equipped with the PremEon S trip unit use an adjustment knob to set the Amp rating (LT Pickup). The maximum
Amp rating of the breaker frame is shown in the "Current Sensor" column below. The available Amp rating settings (LT Pickup values),
by sensor, are as follows:
2Requires tamper-resistant Torx T15 tool for adjustment
3Lugs included but not installed
4400 Hz FG breakers require de-rating and are not UL listed.
400 Hz LI Trip Unit (With Tracking Short-Time)4
2-Pole Record Plus FG Breakers
65kAIC @480 Vac 100kAIC @480 Vac 150kAIC @480 Vac 200kAIC @480 Vac
Current Sensor (A) Product Number Product Number Product Number Product Number
250 FGN26DC250LF FGH26DC250LF FGL26DC250LF FGP26DC250LF
400 FGN26DC400LF FGH26DC400LF FGL26DC400LF FGP26DC400LF
600 FGN26DC600MF FGH26DC600MF FGL26DC600MF FGP26DC600MF
3-Pole Record Plus FG Breakers
65kAIC @480 Vac 100kAIC @480 Vac 150kAIC @480 Vac 200kAIC @480 Vac
Current Sensor (A) Product Number Product Number Product Number Product Number
250 FGN36DC250LF FGH36DC250LF FGL36DC250LF FGP36DC250LF
400 FGN36DC400LF FGH36DC400LF FGL36DC400LF FGP36DC400LF
600 FGN36DC600MF FGH36DC600MF FGL36DC600MF FGP36DC600MF
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-86
Molded Case Circuit Breakers Section 6
Record Plus™FG 600
Record Plus™FG with SMR2 Trip Unit, Breaker Frames without ZSI and Fixed Rating Plugs
2-Pole
Fixed Rating Plug Breaker Frame
UL 489 65kA IC @ 480 Vac UL 489 100kA IC @ 480 Vac UL 489 150kA IC @ 480 Vac UL 489 200kA IC @ 480 Vac
Ampere Current
Rating Product No. Sensor Product No. Product No. Product No. Product No.
100A FGRM2K0100
110A FGRM2K0110
125A FGRM2K0125 R0 R0 R0 R0
150A FGRM2K0150 FGN26KA0250_ _ R1 FGH26KA0250_ _ R1 FGL26KA0250_ _ R1 FGP26KA0250_ _ R1
175A FGRM2K0175 R2 R2 R2 R2
200A FGRM2K0200 R3 R3 R3 R3
225A FGRM2K0225
250A FGRM2K0250
175A FGRM2L0175
200A FGRM2L0200 R0 R0 R0 R0
225A FGRM2L0225
FGN26KA0400_ _ R1 FGH26KA0400_ _ R1 FGL26KA0400_ _ R1 FGP26KA0400_ _ R1
250A FGRM2L0250 R2 R2 R2 R2
300A FGRM2L0300 R3 R3 R3 R3
350A FGRM2L0350
400A FGRM2L0400
300A FGRM2M0300
350A FGRM2M0350 R0 R0 R0 R0
400A FGRM2M0400 FGN26KA0600_ _ R1 FGH26KA0600_ _ R1 FGL26KA0600_ _ R1 FGP26KA0600_ _ R1
450A FGRM2M0450 R2 R2 R2 R2
500A FGRM2M0500 R3 R3 R3 R3
600A FGRM2M0600
3-Pole
Fixed Rating Plug Breaker Frame
UL 489 65kA IC @ 480 Vac UL 489 100kA IC @ 480 Vac UL 489 150kA IC @ 480 Vac UL 489 200kA IC @ 480 Vac
Ampere Current
Rating Product No. Sensor Product No. Product No. Product No. Product No.
100A FGRM3K0100
110A FGRM3K0110
125A FGRM3K0125 R0 R0 R0 R0
150A FGRM3K0150 FGN36KA0250_ _ R1 FGH36KA0250_ _ R1 FGL36KA0250_ _ R1 FGP36KA0250_ _ R1
175A FGRM3K0175 R2 R2 R2 R2
200A FGRM3K0200 R3 R3 R3 R3
225A FGRM3K0225
250A FGRM3K0250
175A FGRM3L0175
200A FGRM3L0200 R0 R0 R0 R0
225A FGRM3L0225
FGN36KA0400_ _ R1 FGH36KA0400_ _ R1 FGL36KA0400_ _ R1 FGP36KA0400_ _ R1
250A FGRM3L0250 R2 R2 R2 R2
300A FGRM3L0300 R3 R3 R3 R3
350A FGRM3L0350
400A FGRM3L0400
300A FGRM3M0300
350A FGRM3M0350 R0 R0 R0 R0
400A FGRM3M0400 FGN36KA0600_ _ R1 FGH36KA0600_ _ R1 FGL36KA0600_ _ R1 FGP36KA0600_ _ R1
450A FGRM3M0450 R2 R2 R2 R2
500A FGRM3M0500 R3 R3 R3 R3
600A FGRM3M0600
Adjustable Rating Plugs for Record Plus™FG with SMR2 Trip Unit
Ampere Current Sensor
Poles Rating Product No. Rating
160A FGRN2K0160 250
250A FGRN2K0250
2-Pole 250A FGRN2L0250 400
400A FGRN2L0400
600A FGRN2M0600 600
160A FGRN3K0160 250
250A FGRN3K0250
3-Pole 250A FGRN3L0250 400
400A FGRN3L0400
600A FGRN3M0600 600
250
400
600
250
400
600
www.geindustrial.com BuyLog™Catalog 6-87
Rev. 11/13
Data subject to change
without notice
Section 6
Molded Case Circuit Breakers
Record Plus™FG 600
Record Plus™FG with SMR2 Trip Unit, Breaker Frames with ZSI and Fixed Rating Plugs
2-Pole
Fixed Rating Plug Breaker Frame
UL 489 65kA IC @ 480 Vac UL 489 100kA IC @ 480 Vac UL 489 150kA IC @ 480 Vac UL 489 200kA IC @ 480 Vac
Ampere Current
Rating Product No. Sensor Product No. Product No. Product No. Product No.
100A FGRM2K0100 $106.00
110A FGRM2K0110
125A FGRM2K0125 R0 R0 R0 R0
150A FGRM2K0150 FGN26KZ0250_ _ R1 FGH26KZ0250_ _ R1 FGL26KZ0250_ _ R1 FGP26KZ0250_ _ R1
175A FGRM2K0175 R2 R2 R2 R2
200A FGRM2K0200 R3 R3 R3 R3
225A FGRM2K0225
250A FGRM2K0250
175A FGRM2L0175
200A FGRM2L0200 R0 R0 R0 R0
225A FGRM2L0225
FGN26KZ0400_ _ R1 FGH26KZ0400_ _ R1 FGL26KZ0400_ _ R1 FGP26KZ0400_ _ R1
250A FGRM2L0250 R2 R2 R2 R2
300A FGRM2L0300 R3 R3 R3 R3
350A FGRM2L0350
400A FGRM2L0400
300A FGRM2M0300
350A FGRM2M0350 R0 R0 R0 R0
400A FGRM2M0400 FGN26KZ0600_ _ R1 FGH26KZ0600_ _ R1 FGL26KZ0600_ _ R1 FGP26KZ0600_ _ R1
450A FGRM2M0450 R2 R2 R2 R2
500A FGRM2M0500 R3 R3 R3 R3
600A FGRM2M0600
3-Pole
Fixed Rating Plug Breaker Frame
UL 489 65kA IC @ 480 Vac UL 489 100kA IC @ 480 Vac UL 489 150kA IC @ 480 Vac UL 489 200kA IC @ 480 Vac
Ampere Current
Rating Product No. Sensor Product No. Product No. Product No. Product No.
100A FGRM3K0100
110A FGRM3K0110
125A FGRM3K0125 R0 R0 R0 R0
150A FGRM3K0150 FGN36KZ0250_ _ R1 FGH36KZ0250_ _ R1 FGL36KZ0250_ _ R1 FGP36KZ0250_ _ R1
175A FGRM3K0175 R2 R2 R2 R2
200A FGRM3K0200 R3 R3 R3 R3
225A FGRM3K0225
250A FGRM3K0250
175A FGRM3L0175
200A FGRM3L0200 R0 R0 R0 R0
225A FGRM3L0225
FGN36KZ0400_ _ R1 FGH36KZ0400_ _ R1 FGL36KZ0400_ _ R1 FGP36KZ0400_ _ R1
250A FGRM3L0250 R2 R2 R2 R2
300A FGRM3L0300 R3 R3 R3 R3
350A FGRM3L0350
400A FGRM3L0400
300A FGRM3M0300
350A FGRM3M0350 R0 R0 R0 R0
400A FGRM3M0400 FGN36KZ0600_ _ R1 FGH36KZ0600_ _ R1 FGL36KZ0600_ _ R1 FGP36KZ0600_ _ R1
450A FGRM3M0450 R2 R2 R2 R2
500A FGRM3M0500 R3 R3 R3 R3
600A FGRM3M0600
Adjustable Rating Plugs for Record Plus™FG with SMR2 Trip Unit
Ampere Current Sensor
Poles Rating Product No. Rating
160A FGRN2K0160 250
250A FGRN2K0250
2-Pole 250A FGRN2L0250 400
400A FGRN2L0400
600A FGRN2M0600 600
160A FGRN3K0160 250
250A FGRN3K0250
3-Pole 250A FGRN3L0250 400
400A FGRN3L0400
600A FGRN3M0600 600
250
400
600
250
400
600
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-88
Molded Case Circuit Breakers Section 6
SMR2 Expansion Modules
Description Product Number
Blank Filler FAMB2
Ground Fault Protection and Trip Reason Indication FAMGFT2
Load Shedding and Communications FAMSM21
Spare / Replacement Battery FAMBAT
External, DIN-rail Mounted, Communications Module FAMECM2
1Requires FAMECM Communications Module.
2Required for Communications, also serves as contact module for load shedding function.
PremEon S/SMR2 External Ground Fault CTs
Description Product Number
250A External Neutral CT for FG with SRM2 FGGS0250
400A External Neutral CT for FG with SRM2 FGGS0400
600A External Neutral CT for FG with SRM2 FGGS0600
Releases – Shunt Trip and Undervoltage
Shunt Trip Undervoltage Release
Voltage Product No. Product No.
12 VDC FASHTBW —
24 VAC/DC FASHTDW FAUVRDW
48 VAC/DC FASHTFW FAUVRFW
110-130 VAC/110-125 VDC FASHTJW FAUVRJW
120 VAC3FASHTKW —
220/240 VAC, 250 VDC FASHTNW FAUVRNW
277 VAC FASHT7W FAUVR7W
400/480 VAC FASHTUW FAUVRUW
UL Listed for field installation. Accessories are prewired from the factory with 36 inch long leads
(#18 AWG). Shunt trip wire leads are black and UVR wire leads are blue.
355% pickup as required for use with External Ground Fault Protection.
Bell Alarm
Contact Mechanisms Trip Units
Configuration Contacts Contact Rating Wire leads Product No. Product No.
1 NO (Form A) Standard 5A @ 277 VAC, #16 AWG FABAM10W FABAT10W
0.3A @ 125 VDC
1 NC (Form B) Standard 5A @ 277 VAC, #16 AWG FABAM01W FABAT01W
0.3A @ 125 VDC
UL Listed for field installation. Accessories are prewired from the factory with 36 inch long leads. Reference
instruction sheet DEH-40324 for wire lead colors.
Auxiliary Switches
Contact Left Mount Right Mount
Configuration Contacts Contact Rating Wire leads Product No. Product No.
1 NO (Form A) Standard 5A @ 277 VAC, #16 AWG FAS10LW FAS10RW
0.3A @ 125 VDC
1 NC (Form B) Standard 5A @ 277 VAC, #16 AWG FAS01LW FAS01RW
0.3A @ 125 VDC
UL Listed for field installation. Accessories are prewired from the factory with 36 inch long leads. Reference
instruction sheet DEH-40324 for wire lead colors.
Mounting Locations and Limitations
Accessory Mounting Pocket Location Maximum Quantity
Shunt Trip or Undervoltage Release 1
Aux. Switch - Left Mount 3
Aux. Switch - Right Mount 2
Bell Alarm Mechanism 1
Bell Alarm Trip Unit 1
Record Plus™FG 600
Internal Accessories
Auxiliary
Switch
Bell Alarm
Mechanism
Shunt Trip or
Undervoltage
Release
Bell Alarm
Trip Unit
Auxiliary
Switch
Mounting Locations
T
www.geindustrial.com BuyLog™Catalog 6-89
Rev. 11/13
Data subject to change
without notice
Molded Case Circuit Breakers Section 6
Lug Kits
Torque Strip Length
Pole/Lugs Location Wire Type Wire-Lug Lug-Strap Top Bottom Product No.
2 Top #8-400kcmil Cu, #8-#4 AWG Cu/Al 200 lb-in
#6-500kcmil Al 275 lb-in (31 N-m) (23 N-m) 7/8” 1 5/8” FCALK218H
Bottom #2/0-600kcmil Cu/Al #3 AWG-600kcmil Cu/Al 200 lb-in
375 lb-in (42 N-m) (23 N-m)
3 Top #8-400kcmil Cu, #8-#4 AWG Cu/Al 200 lb-in
#6-500kcmil Al 275 lb-in (31 N-m) (23 N-m) 7/8” 1 5/8” FCALK318H
Bottom #2/0-600kcmil Cu/Al #3 AWG-600kcmil Cu/Al 200 lb-in
375 lb-in (42 N-m) (23 N-m)
Other Accessories
Product No.
Rating Plug Removal Tool (SMR1 and SMR2 only) FAR
Breaker External Test Kit (SMR1 and SMR2 only) FAT
Lug Cover Kit FGH1LCK
Hardware Kit (Tapped Holes) FGMSK1
Hardware Kit (Through Holes) FGMSK2
Terminal Shield Fin Cover FGJS3
Nut Plate / Terminal Shoe FGJN3
Padlocking Device
Description Product No.
Padlocking EUSERC Toggle FG1PE
Record Plus™FG 600
External Accessories
Top
Bottom
FCALK218H/FCALK318H
Dimensions (in.)
FG 600 Dimensions
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-90
Molded Case Circuit Breakers Section 6
Molded Case Switches
100-1200A
Molded Case Switches Spectra™RMS
UL File E-57546, CSA LR 91464, Includes fixed, high-set Instantaneous trip suitable for reverse feed.
Terminal Lugs for Maximum Short Circuit Withstand Rating2
Switch1Front Connection (Cu/Al) (kA rms symmetrical)
Frame Ampere
Type Rating Product Number Product Number Wire Range 240 Vac 480 Vac 600 Vac
SE150 100 SEDA36AN0100 TCAL18 Aluminum: #12-3/0 200 100 25
150 SEDA36AN0150 Copper: #14-3/0
SF250 250 SFDA36AN0250 TCAL29 Aluminum: #8-350 kcmil 200 100 25
Copper: #8-350 kcmil
400 SGDA36AN0400 3-pole lug kit Aluminum: (2) 2/0-500 kcmil 200 100 65
SG600 600 SGDA36AN0600 TCLK3653or (1) #8-600 kcmil
Copper: (2) 2/0-500 kcmil
or (1) #8-600 kcmil
800 SKDA36AN0800 TCAL81 Aluminum: (3) 3/0-500 kcmil
Copper: (3) 3/0-500 kcmil 100 65 42
SK1200 1000 SKDA36AN1000 TCAL125 Aluminum: (4) 250-500 kcmil
1200 SKDA36AN1200 Copper: (4) 250-500 kcmil
Molded Case Switches Nonautomatic Trip, Includes Cu/Al line and load lugs. For optional lugs, see page 6-103 and 6-104.
Type Ampere Rating Number of Poles Voltage Rating Product Number
TEB 100 1 120 Vac, 125 Vdc TEB111Y1004
TEB 100 2 240 Vac, 250 Vdc TEB122Y1004
TEB 100 3 240 Vac TEB132Y1004
TEB 100 3 240Vac TEB132YT1009
TED 100 1 277 Vac, 125 Vdc TED113Y1004
TED 100 2 480 Vac, 250 Vdc TED124Y1004
TED 100 3 480Vac, 250Vdc TED134YT1009
TED 100 3 600Vac TED136YT1009
TED 100 3 600Vac TED136YT100A10
TED 150 2 480 Vac, 250 Vdc TED124Y1504,5
TED 150 3 480Vac, 250Vdc TED134YT1509
TED 150 3 600Vac TED136YT1509
TFJ 225 2 600 Vac TFJ226Y2254,6,11
TFJ 225 3 600 Vac TFJ236Y2256,11
TJJ 400 2 600 Vac, 250 Vdc TJJ426Y4007
TJJ 400 3 600 Vac TJJ436Y4007
Type Ampere Rating Number of Poles Voltage Rating Product Number
TFK 225 2 600 Vac, 250 Vdc TFK226Y2256,7,8,11
TFK 225 3 600 Vac, 250 Vdc TFK236Y2257,8,11
TJK 400 2 600 Vac, 250 Vdc TJK426Y4007
TJK 400 3 600 Vac, 250 Vdc TJK436Y4007
TJK 600 2 600 Vac, 250 Vdc TJK626Y6007
TJK 600 3 600 Vac, 250 Vdc TJK636Y6007
TKM 800 2 600 Vac, 250 Vdc TKMA826Y8007,11
TKM 800 3 600 Vac, 250 Vdc TKMA836Y8007,11
TKM 1000 2 600 Vac, 250 Vdc TKMA2Y10007,11
TKM 1000 3 600 Vac, 250 Vdc TKMA3Y10007,11
TKM 1200 2 600 Vac, 250 Vdc TKMA2Y12007,11
TKM 1200 3 600 Vac, 250 Vdc TKMA3Y12007,11
1No rating plug required.
2The maximum withstand rating is limited by the application to the value set forth in this table or the short circuit rating of the upstream fuse or circuit breaker, whichever is
less. The upstream protective device must have an instantaneous trip function or element and its rated ampacity may not exceed the ampere rating of the switch.
3Order one kit for either line or load end; two kits required for both.
4Internal accessory requires factory installed dummy trip. Specify on order. Accessories not available for one-pole TEB, TED.
5Not UL listed.
6600 Volts max.
7Internal accessory requires factory installed dummy trip unit. See page 6-44 for additional details. Nonautomatic trip unit and dummy trip not UL listed for field installation.
8UL listed only when ordered as a complete switch.
9Includes factory installed dummy trip for accessory installation.
10Includes factory installed dummy trip and TCAL12A lugs.
11Limited availability. Obsolete when inventory is depleted.
www.geindustrial.com BuyLog™Catalog 6-91
Rev. 11/13
Data subject to change
without notice
Molded Case Circuit Breakers Section 6
High Interrupting Capacity Motor Circuit Protectors—SF250 Line 3-Pole
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
Adjustable Instantaneous 65kAIC @480 Vac 100kAIC @480 Vac
Ampere Trip Ampere Range Product Current Product Product Product Wire
Rating Low High Number Sensor Number Number Number Range
70 205 700 SRPF250A70
90 265 900 SRPF250A90
100 295 1000 SRPF250A100
110 325 1100 SRPF250A110
125 370 1250 SRPF250A125 250 SFLA36AI0250 SFPA36AI0250 TCAL29 8-350 Cu
150 440 1500 SRPF250A150 8-350 Al
175 515 1750 SRPF250A175
200 590 2000 SRPF250A200
225 665 2250 SRPF250A225
250 736 2500 SRPF250A250
Motor Circuit Protectors
3-250A
Mag-Break Motor Circuit Protectors
Current Limiting, UL Component Recognized1
Features
—Suitable for Reverse Feed
—UL Recognized File E-11592
—CSA Certified LR 40350
—IEC 947-2 690 Vac Max.
—SE 150 160 Ampere Max.
—SF250 250 Ampere Max.
—SG600 630 Ampere Max.
—SK1200 1250 Ampere Max.
—UL Current Limiting
High Interrupting Capacity Spectra™RMS Motor Circuit Protectors—SE150 Line 3-Pole
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
Adjustable Instantaneous 65kAIC @480 Vac 100kAIC @480 Vac
Ampere Trip Ampere Range Product Current Product Product Product Wire
Rating Low High Number Sensor Number Number Number Range
3 11 39 SRPE7A3
7 22 90 SRPE7A7 7 SELA36AI0007 SEPA36AI0007 TCAL18
15 43 182 SRPE30A15
20 58 254 SRPE30A20 30 SELA36AI0030 SEPA36AI0030 TCAL18
25 73 332 SRPE30A25
30 87 415 SRPE30A30 14-3/0 Cu
40 118 501 SRPE60A40
50 148 637 SRPE60A50 60 SELA36AI0060 SEPA36AI0060 TCAL18
60 178 777 SRPE60A60 12-3/0 Al
70 206 863 SRPE100A70
80 236 999 SRPE100A80 100 SELA36AI0100 SEPA36AI0100 TCAL18
90 267 1138 SRPE100A90
100 297 1280 SRPE100A100
110 328 1426 SRPE150A110
125 374 1640 SRPE150A125 150 SELA36AI0150 SEPA36AI0150 TCAL18
150 450 1991 SRPE150A150
SE150 Add-on 3-Pole Limiters
Maximum Product kAIC Use With Breaker/
Ampere Rating Number @600 Vac MCP Frame
150 SAXSEL36150 65 SEL
150 SAXSEP36150 100 SEP
1Per UL 489, interruption ratings are not printed on the product label (interruption ratings are established based on a tested combination of the motor circuit protector and a
properly sized overload relay and contactor).
www.geindustrial.com Rev. 11/13
Data subject to change
without notice
BuyLog™Catalog
6-92
SK1200 Line (Not Current Limiting) 3-Pole
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable Instantaneous 65kAIC @480 Vac
Ampere Trip Ampere Range Product Current Product Product Wire
Rating Low High Number Sensor Number Number Range
800 Ampere Max.
300 940 3015 SRPK800A300
400 1250 4015 SRPK800A400 (3) 3/0-500 Cu
500 1570 5020 SRPK800A500 800 SKLA36AI0800 TCAL81
600 1875 6195 SRPK800A600
700 2155 7420 SRPK800A700 (3) 3/0-500 Al
800 2440 8705 SRPK800A800
1200 Ampere Max.
600 1825 6110 SRPK1200A600
700 2125 7125 SRPK1200A700 (4) 250-500 Cu
800 2430 8145 SRPK1200A800 1200 SKLA36AI1200 TCAL125
100 3040 10180 SRPK1200A1000 (4) 250-500 Al
1200 3650 12215 SRPK1200A1200
Standard Capacity Mag Break Motor Circuit Protectors—Type TJC 3-Pole
30kAIC @480 Vac
Adjustable Instantaneous Complete Breaker (includes line and load lugs)
Trip Ampere Range Product
Ampere Rating Low High Number
330 1100 TJC36400E
400 550 1670 TJC36400F
1000 3300 TJC36400G
1200 4000 TJC36400B
600 1000 3300 TJC36600G
1800 6000 TJC36600H
Accessories: See pages 6-39 to 6-44, 6-67 to 6-69 and 6-94 to 6-106.
Molded Case Circuit Breakers Section 6
SG 600 Line 3-Pole
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable Instantaneous 65kAIC @480 Vac 100kAIC @480 Vac
Ampere Trip Ampere Range Product Current Product Product Product Wire
Rating Low High Number Sensor Number Number Number Range
400 Ampere Max.
125 380 1275 SRPG400A125
150 455 1530 SRPG400A150 3-Pole (2) 2/0-500 Cu or
175 530 1785 SRPG400A175 lug kit (1) 8-600 Cu
200 605 2040 SRPG400A200
225 680 2295 SRPG400A225 400 SGLA36AI0400 SGPA36AI0400 TCLK3652
250 755 2550 SRPG400A250
300 905 3060 SRPG400A300 (2) 2/0-500 Al or
350 1060 3570 SRPG400A350 (1) 8-600 Al
400 1210 4080 SRPG400A400
600 Ampere Max.
250 765 2530 SRPG600A250
300 915 3035 SRPG600A300 3-Pole (2) 2/0-500 Cu
350 1070 3545 SRPG600A350 lug kit or (1) 8-600 Cu
400 1220 4050 SRPG600A400
450 1375 4555 SRPG600A450 600 SGLA36AI0600 SGPA36AI0600 TCLK3652(2) 2/0-500 Al
500 1525 5060 SRPG600A500 or (1) 8-600 Al
600 1830 6075 SRPG600A600
Motor Circuit Protectors
125-1200A
Mag-Break Motor Circuit Protectors
Current Limiting, UL Component Recognized1
1Per UL 489, interruption ratings are not printed on the product label (interruption ratings are established based on a tested combination of the motor circuit protector and a
properly sized overload relay and contactor).
2Order one kit for either the line or load end; two kits required for both.
www.geindustrial.com BuyLog™Catalog 6-93
Rev. 11/13
Data subject to change
without notice
Molded Case Circuit Breakers Section 6
Motor Circuit Protectors
25-600A
Record Plus™
Record Plus™Mag-Break Motor Circuit Protectors
Current Limiting, UL Component Recognized1
High Interrupting Record Plus FG Motor Circuit Protectors - FG 600 Line with PremEon S
Mag-Only Motor Circuit Protector (With Tracking Short-Time)
2-Pole Record Plus FG Breakers
65kAIC @ 480 Vac 100kAIC @ 480 Vac 150kAIC @ 480 Vac 200kAIC @ 480 Vac
Current Sensor (A) Product Number Product Number Product Number Product Number
250 FGN26DM250LF FGH26DM250LF FGL26DM250LF FGP26DM250LF
400 FGN26DM400LF FGH26DM400LF FGL26DM400LF FGP26DM400LF
600 FGN26DM600MF FGH26DM600MF FGL26DM600MF FGP26DM600MF
3-Pole Record Plus FG Breakers
65kAIC @ 480 Vac 100kAIC @ 480 Vac 150kAIC @ 480 Vac 200kAIC @ 480 Vac
Current Sensor (A) Product Number Product Number Product Number Product Number
250 FGN36DM250LF FGH36DM250LF FGL36DM250LF FGP36DM250LF
400 FGN36DM400LF FGH36DM400LF FGL36DM400LF FGP36DM400LF
600 FGN36DM600MF FGH36DM600MF FGL36DM600MF FGP36DM600MF
Mag-Only Motor Circuit Protector Plus Ground Fault (With Tracking Short-Time)
2-Pole Record Plus FG Breakers
65kAIC @ 480 Vac 100kAIC @ 480 Vac 150kAIC @ 480 Vac 200kAIC @ 480 Vac
Current Sensor (A) Product Number Product Number Product Number Product Number
250 FGN26DP250LF FGH26DP250LF FGL26DP250LF FGP26DP250LF
400 FGN26DP400LF FGH26DP400LF FGL26DP400LF FGP26DP400LF
600 FGN26DP600MF FGH26DP600MF FGL26DP600MF FGP26DP600MF
3-Pole Record Plus FG Breakers
65kAIC @ 480 Vac 100kAIC @ 480 Vac 150kAIC @ 480 Vac 200kAIC @ 480 Vac
Current Sensor (A) Product Number Product Number Product Number Product Number
250 FGN36DP250LF FGH36DP250LF FGL36DP250LF FGP36DP250LF
400 FGN36DP400LF FGH36DP400LF FGL36DP400LF FGP36DP400LF
600 FGN36DP600MF FGH36DP600MF FGL36DP600MF FGP36DP600MF
High Interrupting Record Plus FE Motor Circuit Protectors - FE 250 Line with PremEon S
Mag-Only Motor Circuit Protector (With Tracking Short-Time)
2-Pole Record Plus FE MCPs
65kAIC @480 Vac 100kAIC @480 Vac
Current Sensor (A) Product Number Product Number
25 FEN24DM025KF FEH24DM025KF
60 FEN24DM060KF FEH24DM060KF
125 FEN24DM125KF FEH24DM125KF
150 FEN24DM150KF FEH24DM150KF
250 FEN24DM250KF FEH24DM250KF
3-Pole Record Plus FE MCPs
65kAIC @480 Vac 100kAIC @480 Vac
Current Sensor (A) Product Number Product Number
25 FEN34DM025KF FEH34DM025KF
60 FEN34DM060KF FEH34DM060KF
125 FEN34DM125KF FEH34DM125KF
150 FEN34DM150KF FEH34DM150KF
250 FEN34DM250KF FEH34DM250KF
Mag-Only Motor Circuit Protector Plus Ground Fault (With Tracking Short-Time)
2-Pole Record Plus FE MCPs
65kAIC @480 Vac 100kAIC @480 Vac
Current Sensor (A) Product Number Product Number
25 FEN24DP025KF FEH24DP025KF
60 FEN24DP060KF FEH24DP060KF
125 FEN24DP125KF FEH24DP125KF
150 FEN24DP150KF FEH24DP150KF
250 FEN24DP250KF FEH24DP250KF
3-Pole Record Plus FE MCPs
65kAIC @480 Vac 100kAIC @480 Vac
Current Sensor (A) Product Number Product Number
25 FEN34DP025KF FEH34DP025KF
60 FEN34DP060KF FEH34DP060KF
125 FEN34DP125KF FEH34DP125KF
150 FEN34DP150KF FEH34DP150KF
250 FEN34DP250KF FEH34DP250KF
1Per UL 489, interruption ratings are not printed on the product label (interruption ratings are established based on a tested combination of the motor circuit protector and a
properly sized overload relay and contactor).
www.geindustrial.com Rev. 7/13
Data subject to change
without notice
BuyLog™Catalog
6-94
Section 6
Molded Case Circuit Breakers
Spectra™Flex Cable Operators
—UL Listed—File E–57253
—Reduced installation costs:
—Simpler, faster installation
—No special alignment required
—Optimized panel layout:
—Breaker mounting position is independent of flange-mounted
handle location
—Covers a full spectrum of enclosure types and sizes:
—Flange-mounted handle for NEMA Types 1, 3R, 12
and 13
enclosures
—Flange-mounted handle for NEMA 4/4X enclosures—optional
—Broad range of enclosure sizes and breaker
mounting configurations
—8 different operating cable lengths available from 3 to 10 feet
—For circuit breaker types E150, SE150, SF250, SG600
and SK1200
—Force and motion transmitted independently of breaker
mounting plane or position relative to handle location
—Common breaker mounted operator for SE150 and
SF250 frames
Spectra™Flex cable operating mechanisms are suitable for
application with GE circuit breakers mounted in a wide variety of
flanged enclosure types and sizes.
Flange-mounted handle mechanisms are available for NEMA
Types 1, 12 or 13 enclosures in either 6 inch (Model SCH1) or
10 inch (Model SCH2) handle lengths. Corresponding mecha-
nisms, SCH1X and SCH2X, are available for NEMA Type 4/4X
enclosures. Handle mechanisms are suitable for either left or
right flange operation.
The handle mechanism is combined with one of eight operating
cables, with lengths from 3 to 10 feet, to cover a broad range of
possible breaker mounting locations in the enclosure. The cable
links the handle mechanism to the breaker-mounted operating
mechanism and transmits the mechanical force and motion of
the handle mechanism to the breaker mounted mechanism. The
force and motion is transmitted independently of the breaker
mounting plane or location relative to the location of the handle
mechanism, provided only that the bending radius of the cable is
not less than 3 inches. No mounting reinforcement of the breaker
or enclosure flange is required.
The breaker-operating mechanism mounts directly to the face of
the breaker and does not involve any mounting interface with the
enclosure. A standard breaker mounting screw kit for tapped
holes is furnished with each mechanism to mount the breaker in
the enclosure.
See page 6-95 for ordering information.
External Accessories
Cable Operators
www.geindustrial.com BuyLog™Catalog 6-95
Rev. 7/13
Data subject to change
without notice
Section 6
Molded Case Circuit Breakers
How to Order
Use the circuit breaker mounting zone dimension table to determine the correct cable
length for the application and ensure that the 3-inch minimum bending radius is not
violated. Select the breaker mounted mechanism, operating cable and handle mecha-
nism below. Order as separate components.
Publication References
Breaker types E150, SE150, SF250, SG600 GEH-6290
Breaker type SK1200 GEH-6291
See Section 27 for publication ordering information.
Maximum Dimensions in Inches
To determine the maximum mounting dimensions for 60-through 120-inch-long
operating cables, add the respective additional lengths to the 48-inch cable maximum
dimensions. (Example: Add 12 inches to E, F and G dimensions for 60-inch cable length.)
When cable is installed, the minimum cable bend radius should not be less than 3
inches. The minimum cable bending requirement must be met to ensure a safe
operating environment.
External Accessories
Cable Operators
Circuit Breaker Mounting Zone
Dimensions
Maximum Mounting Dimensions (in.)
Box 36" Cable 48" Cable
Depth E1FGE
1FG
8" 13.5 4.0 15.0 25.5 16.0 27.0
10" 13.0 5.0 14.8 25.0 17.0 26.8
12" 12.8 6.0 14.5 24.8 17.0 26.5
16" 10.5 4.5 14.2 22.5 16.5 26.2
18" 8.5 3.5 12.6 20.5 15.5 24.6
20" – 0.5 10.0 22.0 15.0 24.0
24" –––19.5 14.0 22.0
1Maximum E Dimension only if F = 4.5"
Breaker and Handle Mechanisms
Flange-Mounted Handle Mechanism
Breaker Mounted NEMA Enclosure Type 1, 3R, 12, 13 NEMA Enclosure Type 4, 4X
Circuit Mechanism 6" 10" 6" 10"
Breaker Product Product Product Product Product
Type Number Number Number Number Number
E150 SCOM1A
SE150 SCOM1EF SCH1 SCH2 SCH1X SCH2X
SF250 SCOM1EF
SG600 SCOM1G
SK1200 SCOM1K – SCH2K – SCH2KX
Operating Cables
Circuit Breaker Type
E150, SE150, SF250, SG600 SK1200
Cable Product Product
Length Number Number
3' SC3L SC3H
4' SC4L SC4H
5' SC5L SC5H
6' SC6L SC6H
8' SC8L SC8H
10' SC10L SC10H
www.geindustrial.com Rev. 7/13
Data subject to change
without notice
BuyLog™Catalog
6-96
Section 6
Molded Case Circuit Breakers
Operating Mechanism Selection
Circuit Breaker Flange Handle Operating Mechanism
Type Product Number Product Number
SE150 SDOM1A
SF250 SDOM3
SG600 SDOM4
SK12001STDA3, 3X SDOM61
TEB, TED, THED, TEC, TB1 SDOM1A
TB1 and TEC with TECL SDOM1AP5
THLC1 (150A) TDOM1D
J-Frames, TJC
(400, 600A)2TDOM4
TB4 (400A) TJH/TJL3
(600A Max) TDOM5
TB6 (600A), TB8 (800A)
TKH/TKLD4(1200A Max) TDOM7
1Requires STDA3 or STDA3X (10 inch, SK1200 only).
2Includes TJ/THJ/TJL.
3Use TDOM5 for TJH/TJL.
4Use TDOM7 for TKH/TKL.
5Adapter plate required to use SDOM1A on TB1 and TEC with TECL limiter.
STDA1, 1X (6 inch)
or
STDA2, 2X (10-inch)
STDA1, 1X (6 inch)
or
STDA2, 2X (10-inch)
External Accessories
Flange-Mounted Operators
Type STDA Flange Handles and Variable Depth Operating
Mechanisms
—Designed to meet automotive duty specifications
—NEMA 12/13 and 4/4X UL Component Recognized components,
File E-57253l CSA LR 10263
—For right or left hand flange mounting – field convertible
—Mounting dimensions to fit standard flange enclosures 8 inches
– 24 inches deep
—Detailed installation instructions
—Superior strength
Flange Handle Construction
—Rugged die cast housing with provisions for locking in OFF
position with up to three 3/16-inch to 5/16-inch padlocks
—O-ring seals for dirt-tight/oil-tight duty
—Gusseted, 3/32-inch thick double-sided steel handle with large,
red-black self-extinguishing grade plastic grip.
Flange Handle Selection
Product Number STDA1 (6 inch) and STDA2 (10 inch) flange series
handles are interchangeable. While the SE150 through SG600
operating mechanisms can be easily operated with the 6-inch
STDA1 handle, the 10-inch STDA2 may be used to obtain lower
operating force and/or to provide a proportionally larger handle
on large enclosures. STDA3 and STDA3X can be used only with
SDOM6 (for SK1200) operating mechanism.
NEMA 12/13 NEMA 4/4X Nominal Installation Drilling
Flange Handle Flange Handle Length Instruction Template
Product Number Product Number Inches Number Number
STDA1 STDA1X 6
STDA2 STDA2X 10 GEH-5314 GEH-5314
STDA3 STDA3X 10
Flange Stiffener Kit or Extended Length Drive Rod,
Product Number TDSR
Provides rigid 3/8-inch diameter rod between STDA handle mount-
ing surface (flange or center mullion) and operating mechanism
when STDA handle would otherwise not be rigidly supported.
Rod length is 22 inches and my be cut to appropriate length. Also
used as extended-length drive rod for SDOM1A and SDOM3 when
standard 16 inch rod is not long enough. (Operating mechanism
Product Number SDOM6 for SK1200 includes two 22" unique
3/8-16x22 inch flange stiffener rods, Product Number TDSR and
drive rod.)
Operating Flange Extended
Mechanism Stiffener Kit Drive Rod
Product Number Product Number Product Number
SDOM1A, SDOM3,
TDOM1A through TDOM3 TDSR TDSR
SDOM4, TDSR
TDOM4 through TDOM7 (16" supplied with TDSR1
operating mechanism)
Extended Drive Stud, Product Number TDS1, TDS2
This optional drive study permits locating the operating mecha-
nism 1-5/16 inches farther to the left (When flange handle is on
right side) or to the right (when handle is on the left side) to
accommodate specific mounting restrictions. Not suitable for use
with SDOM4, SDOM6, TDOM4 and TDOM5 operating mechanisms.
Operating Mechanism Extended Drive Stud
Product Number Product Number
SDOM1A, SDOM3,
TDOM1A through TDOM3 TDS1
TDOM6, TDOM7 TDS2
Door Hardware NEMA 12/13 and 4/4X
Type TDV door hardware provides sealing and interlocking of
3/4-inch nominal door depth hinged on left or right. Interlocking
design requires use of screwdriver to release. When used with an
STDA flange handle and operating mechanisms, disconnect or
circuit breaker cannot be turned on unless door and door hard-
ware have been closed. For noninterlocking type, one bracket in
kit is not used. Use of third point latch recommended for doors
40 inches or longer.
Door Hinged Door Hinged
on Left on Right
Description Product Number Product Number
NEMA 12/13 two point
interlocking door hardware kit TDV1 TDV1L
NEMA 4/4X two point
interlockingdoor hardware kit TDV1X TDV1LX
Third point latch kit for above TDV3 TDV3L
www.geindustrial.com BuyLog™Catalog 6-97
Rev. 7/13
Data subject to change
without notice
Section 6
Molded Case Circuit Breakers
Publication References
Instructions:
Door Hardware GEH-5322
Auxiliary Contact Kit GEH-5323
Flange Stiffener Kit or Extended Length Drive Rod GEH-5324
Extended Drive Stud GEH-5325
Operating Mechanism:
SDOM1A through SDOM4, SDOM6 GEH-5684
TDOM1A through TDOM1D GEH-5315
TDOM3 GEH-5317
TDOM4 and TDOM5 GEH-5318
TDOM6 and TDOM7 GEH-5319
See Section 27 for publication ordering information.
Auxiliary Contact Kits
Available SPDT and DPDT and actuated by operating mechanism yoke.
When STDA Auxiliary Contact Kit
Used With handle is on SPDT DPDT
Operating Mechanism Right Left Product Product
Product Number Flange Flange Number Number
SDOM1A,
SDOM3 • TDAS1L1 TDAS1L2
SDOM4
TDOM1A, JA
TDOM1B, JB
TDOM1C • TDAS1R1 TDAS1R2
TDOM1D
TDOM3
SDOM6
TDOM4 • TDAS2L1 TDAS2L2
TDOM5
TDOM6 • TDAS1R1 TDAS1R2
TDOM7
External Accessories
Flange-Mounted Operators
www.geindustrial.com Rev. 7/13
Data subject to change
without notice
BuyLog™Catalog
6-98
Section 6
Molded Case Circuit Breakers
External Accessories
Door-Mounted Operators
TDM Operating Handle, Fixed or Adjustable Shaft
TDM Handle Operating Mechanisms, Door Mounted
Complete mechanism with handle UL listed, E-57253
Operating mechanism only, UL Component Recognized, E-57253
Complete Mechanism1Operating Handle Only
with NEMA 1, 3R, 12 Handle Mechanism Only NEMA 1, 3R, 12 NEMA 4/4X
Breaker Box Depth Product Product Product Product
Type in Inches Number Number Number Number
TQD, THQD Extended Shaft TQDHM2 TQDOM22
4 5/16 - 14 5/16
Shallow Mount TEFHM1 TEFOM1
4 3/16
TEB, TEC, TB1, Extended Shaft TEFHM3 TEFOM3 TH1
TED, THED 5-1/8 - 5 7/32
5 1/8 - 5 13/16 TEFHM4 TEFOM4
5 1/8 - 15 TEFHM2 TEFOM2
Shallow Mount TFKHM1 TFKOM1 THCH453,4
TFC, TFJ, 5 7/8
TFK, THFK Extended Shaft TFKHM2 TFKOM22
6 7/8 - 15 1/2
TJC, TJD, TJJ, Shallow Mount TJKHM1 TJKOM1
TJK, THJK, 5 7/8
TB4, TBC4 Extended Shaft TJKHM2 TJKOM24
5 5/8 - 15 5/8
Shallow Mount TKMHM1 TKMOM1TKC, TKM, 7 7/16
THKM, TB6, Extended Shaft TKMHM2 TKMOM24
TBC6, TB8, TBC8 7 1/32 - 17 5/16
SE150 (GEH-5611)54 3/16 SEFHM1 SEFOM1
6 1/8 - 15 SEFHM2 SEFOM22TH1
SF250 (GEH-5611)55 7/8 SEFHM1 SEFOM1
7 3/4 - 15 1/2 SEFHM2 SEFOM22THCH453,4
SG600 (GEH-5653)55 7/8 SGHM1 SGOM1
5 5/8 - 15 5/8 SGHM2 SGOM24TH2
SK1200 (GEH-5612)56SKHM1 SKOM1
7SKHM2 SKOM24
1Handle assembly and operating mechanism separately packaged.
2For 15-inch long shaft order Product Number 788A831G10. For 20-inch long shaft order Product Number 788A831G20.
3Provides interlocking for J600, SG600 SK1200, and K1200 breakers when used with the extended shaft operating mechanism. For interlocking with E150/SE150, F225 and
SF250 order special shaft Product Number 788A832G1.
4For 15-inch long shaft order Product Number 788A832G2. For 20-inch long shaft order Product Number 788A832G5.
5Installation instructions publication number.
6MOD 1 is 7 7/16; MOD 2 is 8 3/32.
7MOD 1 is 7 3/16 - 17 3/16; MOD 2 is 7 15/16 - 17 15/16.
TH2
Handle Accessories for TDM Operating Mechanisms
Device Product Number
Replacement neoprene gaskets
for NEMA 1, 3R and 12 enclosures
Use with TH1 788A742P3
Use with TH2 788A742P4
www.geindustrial.com BuyLog™Catalog 6-99
Rev. 7/13
Data subject to change
without notice
Section 6
Molded Case Circuit Breakers
External Accessories
Door-Mounted Operators
TDR Handle on TED Circuit Breaker
TDR Integral Handle Mechanism1Suitable for NEMA 12 Applications2
Handle Door Ring - Interlock Catch Kit NEMA 12 Gasket Kit
Vertical Mounting Horizontal Mounting Ship Product Product
Breaker Type Product Number Product Number Weight Number Number
TEB, TEC, TB1-B, TED, THED TEFR1B TEFR1HB 173SEFRDRCK SEFRGSK
TFC, TFJ, TFK, THFK TFKR1B TFKR1HB 223343L483G5
TJD, TJC, TJJ, TJK, THJK, TB4, TBC4 TJR1B TJR1HB 5 343L483G2 SGRGSK
TKC, TKM, THKM, TB6, TB8, TBC6, TBC8 TKMR1B TKMR1HB 5 SKRDRCK SKRGSK
SE150, SF250 (GEH-5609)5SEFR14SEFR1H4173SEFRDRCK SEFRGSK
SG600 (GEH-5654)5SGR1 SGR1H 5 SGRDRCK SGRGSK
SK1200 (GEH-5610)5SKR1 SKR1H 5 SKRDRCK SKRGSK
1Not suitable for use with mine duty or heavy duty UVR breakers.
2Requires Gasket kit.
3Shipped 12 per pack.
4For F250 Frame also order adapter bracket, Product Number SFRAK, no charge when ordered with handle.
5Installation instructions publication number. See Section 27 for publication ordering information.
www.geindustrial.com Rev. 7/13
Data subject to change
without notice
BuyLog™Catalog
6-100
Section 6
Molded Case Circuit Breakers
External Accessories
Motor Operators and Plug-in Hardware
Motor Operated Mechanism
on SF-Frame breaker
Motor Mounted Mechanism
UL Listed Voltage
Vac Product Installation
Breaker Type 50/60 Hz Vdc Number Instructions
TEB,1 TEC, TED,1– 24 TEDMOMA8
THED, TB1, THLC121203– TEDMOMA1 –
2404,5 – TEDMOMA2
TJC, TJJ, TJD, TJK, – 24 TJKMOMA8
THJK, TB4, TBC4 120 125 TJKMOMA1 –
2404,5 250 TJKMOMA2
120 125 SEMOM1
SE150 2404– SEMOM2 GEH-5613
– 24 SEMOM8
120 125 SFMOM1
SF250 2404– SFMOM2 GEH-5613
– 24 SFMOM8
120 125 SGMOM1
SG600 2404250 SGMOM2 GEH-5657
– 24 SGMOM8
120 125 SKMOM1
SK1200 2404250 SKMOM2 GEH-5614
– 24 SKMOM8
Mounting Screw Kit for Motor-Operated Mechanism6
Breaker Type Mounting Screw Kit Product Number
TED, TB1 343L564G7
TFJ, TFK 343L564G1
TJJ, TJK, TB4 343L564G2
SG600 SGMSKMOM
TKM, TB6, TB8, SK 343L564G3
1For use on 3-pole breaker only.
2Motor-operated mechanisms must have Code Date 506 + or later for use with THLC1.
3TEDMOMA1 not rated at 50 hertz.
4Suitable for use at 208 Vac.
5Not UL listed.
6Required with plug-in mounting base assembly when used with motor-operating
mechanisms or TDR integral-handle kits. Furnished no charge when ordered with
mounting base.
www.geindustrial.com BuyLog™Catalog 6-101
Rev. 7/13
Data subject to change
without notice
Section 6
Molded Case Circuit Breakers
External Accessories
Mechanical Interlocks and Locking Devices
Mechanical Interlocks
These face-mounted interlocks prevent two adjacent breakers
from being in the ON position at the same time.
Face-mounted Adapter Kit Required when using handle
Spectra™RMS Interlock operator (TDM) or motor operator.
Breaker Type Product Number Order separately.
SE150, SF250 SEFFMI SEFFMIAK1
SG600 SGFMI SGFMIAK2
SK1200 SKFMI SKFMIAK
Handle-Locking, Handle-Extension Devices
Breaker Type Device Product Number
TEY Handle locking TEYLD1
E150 Line Handle locking TLD3
F225 Line,
THLC2, 4 Handle locking TFKLD1
SE150, SF250 Handle locking SBD1
SK1200 Handle extension - replacement SKHDLEXT 1Not suitable with THCH45 handle.
2Compatible with motor operator only. Product Number SGFMI cannot be used with
the handle operator.
3Suitable for circuit breakers used in group mounted panelboard construction only
except for J600, K1200, SE150/SF250, SG600 and SK1200 which screw down to face
of breaker.
4Field installable.
5Suitable for padlocking in either “ON” or “OFF” position.
Standard Padlocking Devices3
Breaker Type Device Product Number
TEY TEYPLD1
E150, TB1 TEFPLD1
F225 TFKPLD1
J600 Line TJKPLD1
K1200 Line TKMPLD1
SE150, SF250 SEPLD5
SG600 SGPLD5
SK1200 SKPLD5
EUSERC Approved—Factory Installed Only
Breaker Type Product Number
E150 TEDPLD2
SE150, SF2504SEFPLD2
SG600 SGPLD2
J600 TJKPLD2
SK1200 SKPLD2
www.geindustrial.com Rev. 7/13
Data subject to change
without notice
BuyLog™Catalog
6-102
Section 6
Molded Case Circuit Breakers
External Accessories
Breaker Mounting Hardware and Kits
Breaker Mounting Screw Kits
Spectra™RMS Kit Screw Size
Application Breaker Type Product Number (inches)
SE150 SEMSK1 10-32x2 7/8 (std.)
For use on mounting SEMSK3 8-32x2 7/8 (opt.)
plates with tapped SF250 SFGMSK1 12-24x3 3/4 (std.)
holes (4 screws SFMSK1 10-32x3 3/4 (opt.)
and lockwashers) SG600 SFGMSK1 12-24x3 3/4
SK1200 SKMSK1 5/16-18x1 1/4
SE150 SEMSK2 10-32x3 (std.)
For use on mounting SEMSK4 8-32x3 (opt.)
plates with clearance SF250 SFGMSK2 12-24x4 (std.)
holes (4 screws, SFMSK2 10-32x4 (opt.)
lockwashers and nuts) SG600 SFGMSK2 12-24x4
SK1200 SKMSK2 5/16-18x1 3/4
Breaker Mounting Screw Kits and Accessories
Application Breaker Type Product Number
Bolt-on Mounting Base TEY TEY3B1
For use on mounting 1-pole E150 343L162G1
plates with clearance 2- and 3-pole E150 SEMSK4
holes F225 SFGMSK2
K1200 SKMSK2
1-pole TE, E150 343L162G7
2- and 3-pole E150 SEMSK3
For use on mounting 2- and 3-pole TQD/THQD 343L184G18
plates with tapped holes F225 SFGMSK1
J600 343L162G11
K1200 SKMSK1
Cup washer E150 254V644P1
(for mounting 1-pole breakers) (2 req'd per breaker)
Back-Connected Line and Load Studs
Length,
Back of Breaker Product
Breaker Type Amperes in Inches Std Pkg Number
50 2 25/32 (short) 1 TEF1
E1502, TB12, 4 13/32 (long) 1 TEF2
THLC12150 3 13/32 (short) 1 TEF3
5 25/32 (long) 1 TEF4
TFJ2, TFK2, 225 2 23/32 (short) 1 TFK1
THFK25 31/32 (long) 1 TFK2
K1200, 1200 5 1/2 1 TKM11
TB6, TB8 81TKM12
50 2 25/32 (short) 1 TEF1
SE150 4 13/32 (long) 1 TEF2
150 3 13/32 (short) 1 TEF3
5 25/32 (long) 1 TEF4
SF250 250 2 23/32 (short) 1 TFK1
5 31/32 (long) 1 TFK2
SG600 600 2 13/16 (short) 1 SGBCS1
6 1/16 (long) 1 SGBCS2
SK1200 1200 5 1/2 1 TKM11
8 1 TKM12
1Accepts up to 3 poles (any combination).
2For proper clearance between poles, a short and long stud must be assembled
adjacent to each other.
3Contains 24 mounting screws.
www.geindustrial.com BuyLog™Catalog 6-103
Rev. 7/13
Data subject to change
without notice
Section 6
Molded Case Circuit Breakers
External Accessories
Lugs and Associated Hardware
Breaker with Line and Load Studs
Lugs, Line Shields, Covers and Bus Connectors
Accessory Wire Range For Use With Product Number Description
Copper-Aluminum Lugs (1) #14-6 Cu, #12-2 Al TQC (15-60A) (Non DIN Rail) TQAL3 Single Lug
(1) #4-1/0 Cu-Al TQC (70-100A) TQAL4 Single Lug
(1) #4-300 kcmil Cu-Al TQD TCAL25 Single Lug
TCALK325 3-Lug Kit
(1) #14-8 E150, THLC1, TB1, (15-30A) TCAL14 Single Lug
(1) #14-3 Cu, #12-1 Al E150, THLC1, TB1, (15-60A) TCAL12 Single Lug
(1) #6-2/0 Cu, #4-2/0 Al E150, THLC1, TB1, (70-90A) TCAL12A Single Lug
(1) #3-3/0 Cu, #1-3/0 Al E150, THLC1, TB1, (100-150A) TCAL15 Single Lug
(1) #4-300 kcmil Cu-Al F225 TCAL24 Single Lug
TCALK324 3-Lug Kit
(1) 6-600 kcmil or (2) 2/0-250 kcmil Cu-Al J400, TB4, J600 (Thru 400A), TJD TCAL43 Single Lug
(2) 4/0-350 kcmil Cu or (2) 300-500 kcmil Al J600 (450-600A) TCAL63 Single Lug
TCALK363 3-Lug Kit
(1) 750 kcmil Cu-Al J400 TJD TCAL47 Single Lug
(1) 3/0-500 kcmil or (2) 3/0-250 kcmil Cu-Al TLB4, THLC4 TCLK43 Single Lug
(2) 1/0-250 kcmil or (1) #4-600 kcmil Cu-Al K1200, TB6 (300-400A) TCAL41 Single Lug
TCAL61 Single Lug
(2) 2/0-500 kcmil Cu-A K1200, TB6 (300-600A) TCALK261 2-Lug Kit w/ Wrench
TCALK361 3-Lug Kit w/ Wrench
TCAL811Single Lug
(3) 3/0-500 kcmil Cu-Al K1200, TB8 (600-800A) TCALK28112-Lug Kit w/ Wrench
TCALK38113-Lug Kit w/ Wrench
TCAL911Single Lug
(3) 3/0-500 kcmil Cu-Al TK4V - Load end TCALK29112-Lug Kit w/ Wrench
TCALK39113-Lug Kit w/ Wrench
TCAL1212Single Lug
(4) 250-350 kcmil Cu or (4) 250-500 kcmil Al K1200 (1000-1200A) TCALK212122-Lug Kit w/ Wrench
TCALK312123-Lug Kit w/ Wrench
TCAL1223Single Lug
(3) 750 kcmil Cu-Al K1200 (1200A) TCALK212232-Lug Kit w/ Wrench
TCALK312233-Lug Kit w/ Wrench
(4) 250-350 kcmil Cu or (4) 250-500 kcmil Al TK4V - Load end TCAL1312Single Lug
Copper Only Lugs #14-2/0 E150, TB1 (thru 150A) TC012 Single Lug
With Follower and Extra Plating #4-300 kcmil Cu TFJ (250A) TC024 Single Lug
(1) 6-600 kcmil or (2) 1/0-250 kcmil Cu J400, TB4 TC043 Single Lug
(2) 250-350 kcmil Cu J600 TC063 Single Lug
(1) 1/0-600 kcmil or (2) 1/0-250 kcmil Cu K1200, TB6 (300-400A) TC0414Single Lug
(2) 2/0-500 kcmil Cu K1200, TB6, (300-600A) TC061 Single Lug
(3) 3/0-500 kcmil Cu K1200, TB8 (600-800A) TC081A Single Lug
(3) 3/0-500 kcmil Cu TK4V - Load end TC091 Single Lug
(4) 250-400 kcmil Cu K1200 (1000-1200A) TC0121 Single Lug
(4) 250-400 kcmil Cu TK4V - Load end TC0131 Single Lug
Line Shield TEB, TEC, TED, THED TEDLS
TFJ, TFK, TFC TFKLS
TJJ, TJK, TJC TJKLS
Lug Cover, TKM Breaker TC061, TCAL61, TCAL81 Lugs, TC081A 789A448G1
(two per breaker) TC0121; TCAL121 Lugs 789A448G2
Connector (back strap) TKM TKMC1
Line voltage control wire kit K1200 SKLVK6
for terminating control wire at breaker lugs
1Not suitable for 100 A aluminum conductor.
2Suitable for 500 kcmil copper for voltage drop considerations.
3Not UL listed, requires user supplied lug cover.
4Not UL listed.
5End cover supplied with 800A frame is used as lug cover.
63-pole kit.
www.geindustrial.com Rev. 7/13
Data subject to change
without notice
BuyLog™Catalog
6-104
Section 6
Molded Case Circuit Breakers
External Accessories
Lugs and Associated Hardware
Spectra™RMS Lugs, Lug Covers, and Bus Lugs
Wire Range (Qty.)
Accessory For Use With Copper Aluminum Product Number Description Ampacity Range1
SE150 (1) #12-3/0 (1) #12-3/0 TCAL18 Single lug 15-150
TCALK318 3-lug kit 15-150
SF250 (1) #8-350 kcmil (1) #8-350 kcmil TCAL29 Single lug 70-250
TCALK329 3-lug kit 70-250
SG600 (2) 2/0-500 kcmil or (2) 2/0-500 kcmil or TCLK26522-pole lug kit2125-600
(1) #8-600 kcmil (1) #8-600 kcmil TCLK36523-pole lug kit2125-600
TCAL124 Single lug Cu 275-1200
Al 225-1100
Plated extruded aluminum
(3) 350-750 kcmil (3) 350-750 kcmil TCALK2124 2-lug kit w/wrench Cu 275-1200
lugs for terminating Al 225-1100
copper or aluminum cables
TCALK3124 3-lug kit w/wrench Cu 275-1200
Al 225-1100
TCAL81 Single lug 300-800
SK1200 (3) 3/0-500 kcmil (3) 3/0-500 kcmil TCALK281 2-lug kit w/wrench 300-800
TCALK381 3-lug kit w/wrench 300-800
TCAL125 Single lug 600-1200
(4) 250-500 kcmil (4) 250-500 kcmil TCALK2125 2-lug kit w/wrench 600-1200
TCALK3125 3-lug kit w/wrench 600-1200
SE150 ––SE3LCK Three lug covers for –
upper (line) end
SE150 Lug
SE150 ––SE3LCKL Cover Kit (Mod –
For SEFR1 Handle)
SF250 ––SF3LCK Three lug covers for –
upper (line) end
Replacement Lug Covers SG1LCK 3-pole lug cover for –
and End Covers SG600 –– upper (line) or lower (load) end
SG1BCK43-pole lug cover for –
upper (line) or lower (load) end4
SK1200 ––SK1LCK3Lug cover for upper (line) –
or lower (load) end3
SE150 (1) #12-3/0 – TCO18 Single lug 15-150
SF250 (1) #8-350 kcmil – TCO29 Single lug 70-250
SG600 (2) 2/0-500 kcmil or – TCOK265 2-pole lug kit 125-600
Plated Copper Lugs (1) #8-600 kcmil – TCOK365 3-pole lug kit 125-600
(3) 250-500 kcmil – TCO81A Single lug 300-800
SK1200 (4) 250-400 kcmil – TCO121 Single lug 600-1200
(3) 350-750 kcmil – TCO124 Single lug 600-1200
(4) 250-500 kcmil – TCO125 Single lug 600-1200
SE150 (1) #12-3/0 (1) #12-3/0 TCAL18LV Single lug with .25 15-150
Line voltage control wire kit Quick Connect
for terminating control wire SF250 (1) #8-350 kcmil (1) #8-350 kcmil TCAL29LV for Control Voltage 70-250
at breaker lugs SG600 ––SGLVK Single .25 Quick Connect –
SK1200 ––SKLVK Single .25 Quick Connect –
For MicroVersaTrip™Plus and PM trip units
SPCOV1 Replacement cover –
Clear rating plug cover SPCOV2 Cover with access to instantaneous set point –
with provision for wire seal SG600 / SK1200 ––SPCOV3 Cover with no access to instantaneous set point –
For microEntelliGuard™Trip Units
SPCOV1C Replacement cover –
SPCOV3C Cover with no access –
1Both copper and aluminum cables may not cover full ampacity range.
2With lug cover for line or load end.
3100kA, 480 Vac (SKPA) uses longer lug cover/arc shield on upper end. Use Product Number SKPSHLD for replacement. May be used on other SK1200 devices.
4Required for line end bus connection.
www.geindustrial.com BuyLog™Catalog 6-105
Rev. 7/13
Data subject to change
without notice
Section 6
Molded Case Circuit Breakers
External Accessories
Neutral Grounds and Sensors
Power Distribution Lugs
Breaker Max Wire Product
Type Amperes Range Number Description
(2) 4-14 or TCAL19PD1 Power Distribution Lug
SE, TED 125 (1) 2/0-4 Cu only TCAL19PD3 3-Lug Power
Distribution Lug Kit
TCAL28PD1 Power Distribution Lug
SF 250 (6) 4-14 Cu only TCAL28PD3 3-Lug Power
Distribution Lug Kit
TCAL40PD1 Power Distribution Lug
SG 400 (12) 4-14 Cu only TCAL40PD3 3-Lug Power
Distribution Lug Kit
Neutral Current Sensors
For grounded neutral system ground fault applications
Breaker Type Ampere Rating Product Number
150 TSRG201
200 TSRG202
300 TSRG203
J400 TSRG204
500 TSRG205
600 TSRG206
800 TSKG408
K 1000 TSKG410
1200 TSKG412
Rating Plug Removal Tool
Product Number
TRTOOL
"Naval Use" Molded Case Circuit Breakers
The following molded case circuit breaker types are optionally
available as UL listed per Standard 489, Supplement SB for
naval use:
—THQB
—THQC
—SE150
—SF250
—SG600
—SK1200
Contact GE sales office for price and delivery.
Special Calibration
Contact GE sales office for availability. May void UL listing status.
Neutral Current Sensor
Power Distribution Lugs
www.geindustrial.com Rev. 7/13
Data subject to change
without notice
BuyLog™Catalog
6-106
Section 6
Molded Case Circuit Breakers
External Accessories
Plug-in Hardware
Plug-In Mounting Base Assembly
Plug-In Mounting Bases - 2 Required Per Breaker Optional Mounting Base
Ampere Breaker Stud Configuration Product Product
Rating Type No. Poles PD1 PD2 Number Number
150 E15012 OLS SLO TE12PD1,2 TMP1
SE150 3 SLS LSL TE13PD1,2 TMP1
2 SOS LOL TF22PD1,2 TMP2
250 SF250 3 SLS LSL TF23PD1,2 TMP2
3 SLS LSL TF23PC1 TMP2
2 SOS LOL TJ42PD1A,2A TMP3
400 J400 3 SLS LSL TJ43PD1A,2A TMP3
3 SLS LSL TJ43PC1A TMP3
SG400 3 SLS2LSL2SGPC1, SGPC2 SMP3
2 SOS LOL TJ62PD1A,2A TMP3
600 J600 3 SLS LSL TJ63PD1A,2A TMP3
3 SLS LSL TJ63PC1A TMP3
SG600 3 SLS2LSL2SGPC7 SMP78
800 SK800 3 SLS LSL TK83PD1A,2A TMP4
3 SLS LSL TK83PC1A,2A TMP4
1000 SK1200 3 SLS LSL TK103PD1A,2A TMP4
3 SLS LSL TK103PC1A,2A TMP4
1200 SK1200 3 SLS LSL TK123PD1A,2A TMP4
3 SLS LSL TK123PC1A,2A TMP4
1Order 3-pole base for use with 2-pole Hi Break and 600 Vac breakers.
2Vertical studs only for SG600 frame.
Each plug-in mounting base assembly includes all mounting
hardware, studs, and male or female connectors for attachment
to one end of breaker. Studs are of different length so by using
proper combinations of PD1 and PD2 units, adequate electrical
spacing will be assured between adjacent breakers, i.e., a short-
long-short (SLS) unit must be used adjacent to a long-short-long
(LSL) unit. Two-pole breakers of the E150 line require an open-
long-short (OLS) unit on one end of the breaker and a short-long-
open (SLO) on the other since these breakers are built with the
normal left pole missing while the mounting bases are built from
standard three-pole molded supports.
Spectra™RMS and all other two-pole breakers are basically three-
pole devices with the center pole omitted. When these breakers
are to be mounted side by side, a short-open-short (SOS) unit
must be used on one end and a long-open-long (LOL) on the other.
Horizontal studs are normally supplied with the flat surface of
studs at right angles to the long axis of the breaker. If vertical
studs are desired, substitute "C" for "D" in the product number,
e.g., TE13PC1 (vertical) or TE13PD1 (horizontal).
The optional mounting plate (TMP1, etc.) accurately locates and
supports the pair of line and load plug-in mounting-base assem-
blies and provides a convenient means to attach the entire unit to
a metal structure, and serves as a dead front barrier. New draw-
ings are available for customers who prefer to fabricate their own
mounting plates.
Plug-in Mounting Base with Hardware
Product Number TF23PD2 shown
Plug-in Mounting Base
Product Number TK123PD2A shown