www.schneider-electric.us
7MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
7-22 © 2009 Schneider Electric
All Rights Reserved
PowerPact® Circuit
Breakers
H- and J-Frame Circuit Breakers
Class 611 / Refer to Catalog 0611CT0401
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-36
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-39
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-55
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-56
HD and HG 2P
H-Frame
J-Frame
Table 7.37: H-Frame 150 A and J-Frame 250 A Thermal-Magnetic Current-Limiting Circuit Breakers
(600 Vac, 250 Vdc) With Factory Sealed Trip Unit Suitable for Reverse Connectiona
Current
Rating @
40o C
Fixed AC
Magnetic
Trip Cat. No.bc
Interrupting Rating (2nd Letter of Catalog Number)
D G J L
Terminal
Wire Range
$ Price
Hold Trip 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated
H-Frame, 150A 2P, 600 Vac 50/60 Hz, 250 Vdc
15 A 350 A 750 A H( )L26015(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
AL150HD
14–3/0 AWG
Al or Cu
20 A 350 A 750 A H( )L26020(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
25 A 350 A 750 A H( )L26025(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
30 A 350 A 750 A H( )L26030(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
35 A 400 A 850 A H( )L26035(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
40 A 400 A 850 A H( )L26040(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
45 A 400 A 850 A H( )L26045(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
50 A 400 A 850 A H( )L26050(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
60 A 800 A 1450 A H( )L26060(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
70 A 800 A 1450 A H( )L26070(C) 1062.00 1274.00 1497.00 1797.00 1721.00 2066.00 2613.00 3137.00
80 A 800 A 1450 A H( )L26080(C) 1062.00 1274.00 1497.00 1797.00 1721.00 2066.00 2613.00 3137.00
90 A 800 A 1450 A H( )L26090(C) 1062.00 1274.00 1497.00 1797.00 1721.00 2066.00 2613.00 3137.00
100 A 900 A 1700 A H( )L26100(C) 1062.00 1274.00 1497.00 1797.00 1721.00 2066.00 2613.00 3137.00
110 A 900 A 1700 A H( )L26110(C) 2072.00 2486.00 3059.00 3671.00 4449.00 5339.00 5534.00 6641.00
125 A 900 A 1700 A H( )L26125(C) 2072.00 2486.00 3059.00 3671.00 4449.00 5339.00 5534.00 6641.00
150 A 900 A 1700 A H( )L26150(C) 2072.00 2486.00 3059.00 3671.00 4449.00 5339.00 5534.00 6641.00
H-Frame 150A 3P, 600 Vac 50/60 Hz, 250 Vdc
15 A 350 A 750 A H( )L36015(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
AL150HD
14–3/0 AWG
Al or Cu
20 A 350 A 750 A H( )L36020(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
25 A 350 A 750 A H( )L36025(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
30 A 350 A 750 A H( )L36030(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
35 A 400 A 850 A H( )L36035(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
40 A 400 A 850 A H( )L36040(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
45 A 400 A 850 A H( )L36045(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
50 A 400 A 850 A H( )L36050(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
60 A 800 A 1450 A H( )L36060(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
70 A 800 A 1450 A H( )L36070(C) 1328.00 1592.00 1701.00 2042.00 2099.00 2519.00 3149.00 3779.00
80 A 800 A 1450 A H( )L36080(C) 1328.00 1592.00 1701.00 2042.00 2099.00 2519.00 3149.00 3779.00
90 A 800 A 1450 A H( )L36090(C) 1328.00 1592.00 1701.00 2042.00 2099.00 2519.00 3149.00 3779.00
100 A 900 A 1700 A H( )L36100(C) 1328.00 1592.00 1701.00 2042.00 2099.00 2519.00 3149.00 3779.00
110 A 900 A 1700 A H( )L36110(C) 2600.00 3120.00 3599.00 4319.00 5174.00 6209.00 6749.00 8099.00
125 A 900 A 1700 A H( )L36125(C) 2600.00 3120.00 3599.00 4319.00 5174.00 6209.00 6749.00 8099.00
150 A 900 A 1700 A H( )L36150(C) 2600.00 3120.00 3599.00 4319.00 5174.00 6209.00 6749.00 8099.00
Current
Rating @
40oC
Adjustable AC
Magnetic
Trip Cat. No.bc
Interrupting Rating (2nd Letter of Catalog Number)
D G J L
Terminal
Wire Range
$ Price
Low High 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated
J-Frame 250A 2P, 600 Vac 50/60 Hz, 250 Vdc
150 A 750 A 1500 A J( )L26150(C) 2175.00 2610.00 3212.00 3854.00 4671.00 5606.00 5811.00 6972.00 AL175JD
4–4/0 AWG Al or Cu
175 A 875 A 1750 A J( )L26175(C) 2175.00 2610.00 3212.00 3854.00 4671.00 5606.00 5811.00 6972.00
200 A 1000 A 2000 A J( )L26200(C) 2175.00 2610.00 3212.00 3854.00 4671.00 5606.00 5811.00 6972.00 AL250JD
3/0 AWG–350 kcmil
Al or Cu
225 A 1125 A 2250 A J( )L26225(C) 2175.00 2610.00 3212.00 3854.00 4671.00 5606.00 5811.00 6972.00
250 A 1250 A 2500 A J( )L26250(C) 2988.00 3585.00 4251.00 5102.00 6225.00 7469.00 7194.00 8633.00
J-Frame 250A 3P, 600 Vac 50/60 Hz, 250 Vdc
150 A 750 A 1500 A J( )L36150(C) 2730.00 3276.00 3779.00 4535.00 5432.00 6519.00 7086.00 8504.00 AL175JD
4–4/0 AWG Al or Cu
175 A 875 A 1750 A J( )L36175(C) 2730.00 3276.00 3779.00 4535.00 5432.00 6519.00 7086.00 8504.00
200 A 1000 A 2000 A J( )L36200(C) 2730.00 3276.00 3779.00 4535.00 5432.00 6519.00 7086.00 8504.00 AL250JD
3/0 AWG–350 kcmil
Al or Cu
225 A 1125 A 2250 A J( )L36225(C) 2730.00 3276.00 3779.00 4535.00 5432.00 6519.00 7086.00 8504.00
250 A 1250 A 2500 A J( )L36250(C) 3749.00 4499.00 5001.00 6002.00 7238.00 8685.00 8993.00 10791.00
aSee page 7-23 for circuit breakers with field interchangeable trip units.
bTo complete catalog number, replace the blank with the appropriate rating (D, G, J, L).
cFor 100% rated circuit breakers add a “C” in the 9th character place (for example, HDL26015C or JDL26150C).
Table 7.38: H- and J-Frame Termination Options
Termination Letter
A - I-Line (See Section 9)
F = No Lugs (includes terminal nut kit on both ends)d
L = Lugs both ends
M = Lugs ON end Terminal Nut Kit OFF end
P = Lugs OFF end Terminal Nut Kit ON end
N = Plug-in e
D = Drawout e
S = Rear Connected e
dAdd TS suffix for circuit breaker without terminal nut kit.
eFor N and D pricing, add termination pricing on page 7-42 to price. For S pricing, add termination pricing on page 7-38 to price.
H G L 3 6 1 0 0
For factory-installed
termination, place termination
letter in the third block of the
circuit breaker catalog number.
Termination Letter
Plug-in Drawout Rear Connected
Table 7.39: H- and J-Frame Interrupting Ratings
Voltage Interrupting Rating
DGJ L
240 Vac 25 kA 65 kA 100 kA 125 kA
480 Vac 18 kA 35 kA 65 kA 100 kA
600 Vac 14 kA 18 kA 25 kA 50 kA
DE2 Discount
Schedule
7-2 © 2009 Schneider Electric
All Rights Reserved
www.schneider-electric.us
7MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
Selection Information Miniature Circuit Breakers
Class 500, 600
HOM Circuit Breakers QO® Circuit Breakers
Circuit
Breaker
Type
Plug-on HOM HOM-
AFI HOM-
GFI HOM-
EPD HOMT QO QO-H QO-VH QH QOT QO-
CAFI QO-
VHAFI QO-GFI QO-
VHGFI QO-EPD
QO-EPE
Bolt-on — — — — — — — — QOB QOB-H — — — QOB-VH QHB — QOB-
CAFI QOB-
VHAFI QOB-GFI QOB-
VHGFI QOB-EPD
QOB-EPE
Unit Mount —— — ———— — — — ———— — ——— — — ——— — — ——
Number of Poles 12 1 1212 1 123 2 12312,3 a1,2 3 1 1 1 1 2 3 1 1 2 3
Current Range
15–50
15–200m
15–20
15–20
15–50
15–20
15–50
15–50b
10–70
10–200m
10–100
15–100
15–30
15–125
15–100
15–30
15–150
15–30
15–30
15–30
15–20
15–30
15–30
15–60
15–50
15–30
15–30
15–60
15–50
Interrupting Ratings
UL/CSA
Rating
(kA)
(50/60 Hz)
120 Vac 10 10 10 10 10 10 10 10 10 10 10 10 22 22 22 22 22 65 65 10 10 22 10 10 — 22 10 10 —
120/240 Vac 10 10 — — 10 — 10 10 10 10 10 10 22 22 22 22 22 65 65 10 — — — 10 — — — 10 —
208Y/120 — — — — — — — — — — — — — — — — — — — — — — — — 10 — — — —
240 Vac d — — — — — — — — — — 10 10 — — 22 — 22e—65 — — — — — — — — — 10
277 Vac — — — — — — — — — — — — — — — — — — — — — — — — — — — — —
480Y/277 Vac — — — — — — — — — — — — — — — — — — — — — — — — — — — — —
DC Ratings
48 Vdc —— — ———— — 5f5 f5 f— ———— — ——— — — ——— — — ——
60 Vdc —— — ———— — ——— — ———————— — — ——— — ———
65 Vdc —— — ———— — ——— — ———————— — — ——— — ———
125 Vdc — — — — — — — — — — — — — — — — — — — — — — — — — — — — —
250 Vdc — — — — — — — — — — — — — — — — — — — — — — — — — — — — —
IEC 60947-2
(50/60 Hz)g
IEC
(Icu)
—— — ———— — ——— — ———— — ——— — — ——— — — ——
—— — ———— — ——— — ———— — ——— — — ——— — — ——
Special Ratings
Fed. Specs
W-C-375B/GEN XX X XXXX X X—— — X————X—X X — X— — X—
Other Standard HACR h
NOM HACR hHACRi
NOM HACR i—— — HACR
i— NOM — NOM
Accessories and Modifications
Shunt Trip j— — — — — — — — X X X X X X X X X kX X X — — — — — — — — —
Undervoltage Trip — — — — — — — — — — — — — — — — — — — — — — — — — — — — —
Auxiliary Switches j— — — — — — — — X X X X X X X X X kX X X — X X X X X X X X
Alarm Switch j— — — — — — — — X X X X X X X X X kX X X — X X X X X X X X
Handle Operators — — — — — — — — — — — — — — — — — — — — — — — — — — — — —
Handle Padlock
Attachment XX X ————X lXXX X XXXX X XXX X X XXX X X XX
Trip System Type
Thermal-magnetic XX X XXXX X XXX X XXXX X XXX X X XXX X X XX
Molded Case Switch — — — — — — — — X X X — — — — — — — — — — — — — — — — — —
Dimensions (1P Unit Mount)
Dimensions
(1P Unit Mount)
in. (mm)
Height 3.13 (79) 3.5 (89) a4.75 (121) 4.12 (103)
Width 1.00 (25) 0.75 (19) a
Depth 2.98 (76) 2.92 (74) a
Pages Page 1-13 Pages 7-10, 7-11
aSee page 7-54 for dimensions for: QOB2150VH, QOB3110VH, QOB3125VH and QOB3150VH.
bHOMT tandem is 30 A maximum. HOMT quad tandem has 20 A maximum on outside poles, and 50 A maximum on the inside poles.
cAFI, EPD and GFI products are rated 60 Hz only.
dSee the Supplemental Digest for 3Ø corner grounded systems.
e22 kA @ 240 Vac for 3P only.
f1P and 2P, 10–70 A and 3P 10–60 A only.
gSee the Supplemental Digest for circuit breakers with IEC ratings.
hHACR on HOM 1P 15–50 A and 2P 15–100 A
iHACR on QO, QOB 1P 10–70 A, 2P 15–100 A, 3P 10–100 A; QOB-VH 1P 15–70 A, 2P 15–125 A, 3P 15–100 A
jFactory-installed option only
kFactory-installed accessories are not available on QOB-VH 2P150 A and 3P 110–150 A
lHandle padlock attachment available for HOMT quad tandem only.
m2P 150–200 A requires 4P width.
www.schneider-electric.us
7MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
© 2009 Schneider Electric
All Rights Reserved 7-21
PowerPact® Molded Case
Circuit Breakers
PowerPact Family
Class 611
The PowerPact Advantage
•Proven Performance: Industry-leading circuit breaker innovation and protection for heavy-duty commercial and industrial
applications.
•Flexible: Full range of molded case circuit breakers from 15 A to 3000 A, delivering the ratings, configurations, and operators for
your unique applications.
•Simple: Common catalog numbers, standardized ratings, and a full range of field-installable accessories make product selection,
installation and maintenance easier than ever.
•Common Design Features: Mounting holes, door trim, and handle accessories
aP-frame K interrupting is 50 kA at 480 and 600 Vac.
bFor amperage of M-, P- or R-frame circuit breakers, add a zero to the three amperage digits; for example, 120 = 1200 A.
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
H- and J-Frame Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22
H- and J-Frame Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23
G- and Q-Frame Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-24
D- and M-Frame Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-25
P-Frame Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-26
R-Frame Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27
PowerPact® H- and J-Frame Electronic Motor Circuit Protectors . . . . . . 7-28
Mag-Gard® Motor Circuit Protectors (MCP). . . . . . . . . . . . . . . . . . . . . . . 7-30
Automatic Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-33
500 Vdc Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-34
Mission Critical Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-35
PowerPact® Circuit Breaker Accessories. . . . . . . . . . . . . . . . . . . . . . . . . 7-36
Motor Operators and Rotary Handles . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-37
Locks, Installation Accessories, and Rear Connections . . . . . . . . . . . . . 7-38
Mechanical Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-38
Compression Lugs and Power Distribution Connectors (PDC). . . . . . . . 7-40
Terminal Nuts, Terminal Pads, Terminal Shields and Accessories . . . . . 7-41
Plug-In and Drawout Mountings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-42
Micrologic® Electronic Trip Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-43
Micrologic Trip Unit Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-44
G-Frame
100 A H-Frame
150 A J-Frame
250 A Q-Frame
250 A D-Frame
600 A M-Frame
800 A P-Frame
1200 A R-Frame
3000 A
Table 7.35: PowerPact Interrupting Ratings
Voltage Interrupting Rating
BDGJKL
240 Vac 10 kA 25 kA 65 kA 100 kA 65 kA 125 kA
480 Vac 18 kA 35 kA 65 kA 65 kA a100 kA
600 Vac 14 kA 18 kA 25 kA 65 kA a50 kA
Table 7.36: Common Catalog Numbering System
Frame
Rating
Termination
Poles
Voltage
Amperage
b
Suffix
Code
Suffix
Code
HGL3615 0 ABS A
110 Vac Shunt Trip
2A/2B Auxiliary Switch
Frame Designation Interrupting Rating Terminations
G 100A Frame 240
Vac 480
Vac 600
Vac
A I-Line
H 150 A Frame L Lugs on Both Ends
J 250 A Frame B 10 kA F Bus Bar (No Lugs)
Q 250 A Frame D 25 kA 18 kA 14 kA M Lugs Line Side Only
D 600 A Frame G 65 kA 35 kA 18 kA P Lugs Load End Only
M 800 A Frame J 100 kA 65 kA 25 kA N Plug-in
P 1200 A Frame K 65 kA 65 kA 65 kA D Drawout
R 3000 A Frame L 125 kA 100 kA 50 kA S Rear Connected Studs
www.schneider-electric.us
7MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
© 2009 Schneider Electric
All Rights Reserved 7-37
PowerPact® Circuit
Breaker Accessories
Motor Operators and Rotary Handles
Class 612 / Refer to Catalog 0612CT0101
Table 7.79: Motor Operators for H-, J-, and D-Frame Circuit Breakers
Description Rated Voltage Factory
Installed
Cat. No. Suffix
Field--Installable Kit
H-FrameaJ-Frame D-Frame 400 A D-Frame 600 A
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
Standard motor for
electrically-operated
circuit breakers
AC
48/60 ML S29440
1161.00
S31548
3123.00
32642
3395.00
32839
3395.00
110/130 MA S29433 S31540 32840 32840
208/277 MD S29434 S31541 32841 32841
220/240 MC — — — —
380/415 MF — — 32642 32842
380/485 MH S29435 S31542 — —
440/480 MH — — 32647 32847
DC
24/30 MO S29436
1161.00
S31543
3123.00
32843
3545.00
32843
3545.00
48/60 MP S29437 S31544 32844 32844
48/60 MV — — — —
110/130 MR S29438 S31545 32845 32845
250 MS S29439 S31546 32846 32846
Locking Device
Mounting Hardware — — — — — 32649 59.00 32649 58.00
Ronis lock — — — — — 41940 146.00 41940 146.00
Profalux lock — — — — — 42888 146.00 42888 146.00
Operations Counter — — — — — 32648 225.00 32648 225.00
Adapter for I-Line — S37420 119.00 S37420 119.00 ————
Table 7.80: Spring-Charging Motors for Electrically-Operated P-Frame Circuit Breakers
Description Rated Voltage Factory Installed
Cat. No. Suffix
P-Frame (For Field-replacement Only) Replacement Coils
Spring Charging Motor
Cat. No. $ Price cOpening/Closing Coil
Cat. No. $ Price
Standard motor for electrically-
operated circuit breakers.
Factory-installed includes motor
and opening/closing coils.
AC
48 ML S47391
3580.00
S33660
755.00
100/130 MA S47395 S33661
220/240 MC S47396 S33662
380/415 MF S47398 S33664
DC
24/30 MO S47390
3580.00
S33659
755.00
48/60 MV S47391 S33660
110/130 MR S47392 S33661
200/250 MS S47393 S33662
Communicating motor mechanism for
electrically operated circuit breakers.
Factory-installed includes motor
and opening/closing coils.
AC
48 NL S47391
3580.00
S33034
755.00
100/130 NA S47395 S33035
220/240 NC S47396 S33036
380/415 NF S47398 S33038
DC
24/30 NO S47390
3580.00
S33033
755.00
48/60 NV S47391 S33034
110/130 NR S47392 S33035
200/250 NS S47393 S33036
Table 7.81: Rotary Operated Handles
H- and J-FrameaD-Frame P-Frame
Device Description Factory
Installed
Cat. No. Suffix
Field
Installable
Cat. No. $ Price Factory Installed
Cat. No. Suffix
Field
Installable
Cat. No. $ Price Factory
Installed
Cat. No. Suffix $ Price
Direct
Mounted
Standard Handle Black Handle only RD10 S29337 225.00 RD12 32597 366.00 RD10 539.00
Standard Black Handle with
Two early-break and two early make switches — — — — — — RD16 822.00
One early-break switch RD12 S29337 +
S29345 345.00 —————
Two early-make switches RD13 S29337 +
S29346 404.00 —————
Red handle on yellow bezel
RD20 S29339 234.00 RD22 32599 407.00 ——
One early-break switch RD22 S29339 +
S29345 354.00 —————
Two early-make switches RD23 S29339 +
S29346 413.00 —————
MCC Conversion Accessory — — — — 32606 102.00 ——
Door
Mounted
Standard black handle Handle Only RE10 S29338 383.00 RE12 32598 557.00 RE10 971.00
Standard Black Handle
with:
Two early-break and two early make switches — — — — — — RE16 1268.00
Two early make switches RE13 S29338 +
S29345 503.00 —————
Red handle on yellow bezel Handle Only RE20 S29340 399.00 RE22 32600 597.00 ——
Rotary Handle Replacement Kit — ——— —— S33875 795.00
Telescoping RT10 S29343 492.00 RT12 32603 617.00 ——
Accessories
Key lock adapter — — — — 32604 58.00 ——
Key locks Ronis 1351.500 — — — — 41940 146.00 ——
Profalux KS5 B24 D4Z — — — — 42888 146.00 ——
Indication Auxiliary Switch One early-break switch — — — — 32605 120.00 ——
Two early-make switches — — — — 29346 179.00 ——
aNot available in H-frame 2P modules.
bCP1 discount schedule.
cDE2F discount schedule.
Motor Operator
Spring-charging
Motor
Door-Mounted
Handle
Direct-Mounted
handle
DE2F CP1 DE2 Discount
Schedule
www.schneider-electric.us
7MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
© 2009 Schneider Electric
All Rights Reserved 7-55
Dimensions and Shipping Weights
Molded Case Circuit Breakers
aAll weights are for 3P circuit breakers unless otherwise noted.
A
B
E
F
C
D
Figure 26
A
E
F
B
G
Figure 25
E
G
A
B
C
D
F
Figure 27
A
C
D
B
G
F
Figure 28
A
AA
EBBEEB
C
D
Figure 29 Figure 30Figure 31
Figure 32
A
EB
C
D
F
E
E
A
DC
G
B
Figure 33
G
B
F
E
A
DC
Figure 34
Table 7.143: HD, HG, HJ, HL, JD, JG, JJ, JL, DG, DJ, and DL
Circuit Breakers
Circuit Breaker
Cat. No.
Prefix
No. of
Poles Fig. No. Dimensions — Inches
ABCDEFG
HD, HG, HJ, HL 2 25 6.40 2.74 2.87 4.36 0.74 4.92 —
3 26 6.40 4.12 2.87 4.36 0.74 4.92 1.38
JD, JG, JJ, JL 3 27 7.52 4.12 2.87 5.00 1.30 4.92 1.38
DG, DJ, DL 3 28 13.38 5.51 3.75 6.61 2.22 8.93 1.77
Table 7.144: ED, EG, EG and GJL Circuit Breakers
Circuit Breaker
Cat. No.
Prefix
No. of
Poles Fig. No. Dimensions — Inches
ABCDE
ED, EG, EJ 1 29 0.98 5.66 3.09 4.05 3.32
ED, EG, EJ 2 30 1.96 5.66 3.09 4.05 3.32
ED, EG, EJ 3 31 2.94 5.66 3.09 4.05 3.32
GJ 3 32 3.54 4.72 2.76 3.94 2.20
Table 7.145: MG, MJ, PG, PJ, PL, RG, RJ and RL Circuit Breakers
Circuit Breaker
Cat. No.
Prefix
No. of
Poles Fig.
No.
Dimensions — Inches
A BCDEF G
MG, MJ
(800 A and below) 2, 3 33 12.86 8.27 5.77 8.05 2.49 7.87 7.83
PG, PJ, PK, PL
(1000–1200 A) 2, 3 33 16.16 8.27 5.77 8.05 4.19 7.87 7.83
RG, RJ, RL 2, 3 34 16.24 16.54 6.63 14.49 8.73 14.25 15.35
Table 7.146: Shipping Weightsa
Frame Size Approx. Shipping
Weight (Lbs.) Frame Size Approx. Shipping
Weight (Lbs.)
HD, HG, HJ, HL 2P 4 DG, DJ, DL 14
HD, HG, HJ, HL 3P 5 GJ 3
JD, JG, JJ, JL 5 MG, MJ 34
ED, EG, EJ 1P 2 PG, PJ, PL 32
ED, EG, EJ 2P 3 RG, RJ, RL (Without RLTB) 52
ED, EG, EJ 3P 4
www.schneider-electric.us
9PANELBOARDS
9-26 © 2009 Schneider Electric
All Rights Reserved
Circuit Breakers For I-Line® Panelboards and Switchboards
Class 612
H- and J-frame
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-35
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-38
HD/HG 2-pole
3in. (76 mm)
Mounting Height
H-frame 3-pole
4.5 in. (114 mm)
Mounting Height
J-frame 3-pole
4.5 in (114 mm)
Mounting Height
Table 9.116: H-frame 150 A Standard Rated Thermal Magnetic (600 Vac) with Factory Sealed Trip Units
Ampere
Rating
AC Magnetic
Trip Setting D Interrupting G Interrupting J Interrupting aL Interrupting aTerminal
Wire Range
Hold Trip Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price
2-pole, 600 Vac 50/60 Hz
15
350 750
HDA26015( )
899.
HGA26015( )
1338.
HJA26015( )
1589.
HLA26015( )
2483.
AL150HD
#14–#3/0 AWG
Al or Cu
20 HDA26020( ) HGA26020( ) HJA26020( ) HLA26020( )
25 HDA26025( ) HGA26025( ) HJA26025( ) HLA26025( )
30 HDA26030( ) HGA26030( ) HJA26030( ) HLA26030( )
35
400 850
HDA26035( )
899.
HGA26035( )
1338.
HJA26035( )
1589.
HLA26035( )
2483.
40 HDA26040( ) HGA26040( ) HJA26040( ) HLA26040( )
45 HDA26045( ) HGA26045( ) HJA26045( ) HLA26045( )
50 HDA26050( ) HGA26050( ) HJA26050( ) HLA26050( )
60
800 1450
HDA26060( ) 899. HGA26060( ) 1338. HJA26060( ) 1589. HLA26060( ) 2483.
70 HDA26070( ) 1088. HGA26070( ) 1559. HJA26070( ) 1824. HLA26070( ) 2691.80 HDA26080( ) HGA26080( ) HJA26080( ) HLA26080( )
90 HDA26090( ) HGA26090( ) HJA26090( ) HLA26090( )
100
900 1700
HDA26100( ) 1088. HGA26100( ) 1559. HJA26100( ) 1824. HLA26100( ) 2691.
110 HDA26110( ) 2195. HGA26110( ) 3212. HJA26110( ) 4671. HLA26110( ) 5699.125 HDA26125( ) HGA26125( ) HJA26125( ) HLA26125( )
150 HDA26150( ) HGA26150( ) HJA26150( ) HLA26150( )
3-pole, 600 Vac 50/60 Hz
15
350 750
HDA36015
1124.
HGA36015
1575.
HJA36015
1988.
HLA36015
2993.
AL150HD
#14–#3/0 AWG
Al or Cu
20 HDA36020 HGA36020 HJA36020 HLA36020
25 HDA36025 HGA36025 HJA36025 HLA36025
30 HDA36030 HGA36030 HJA36030 HLA36030
35
400 850
HDA36035
1124.
HGA36035
1575.
HJA36035
1988.
HLA36035
2993.
40 HDA36040 HGA36040 HJA36040 HLA36040
45 HDA36045 HGA36045 HJA36045 HLA36045
50 HDA36050 HGA36050 HJA36050 HLA36050
60
800 1450
HDA36060 1124. HGA36060 1575. HJA36060 1988. HLA36060 2993.
70 HDA36070 1361. HGA36070 1772. HJA36070 2225. HLA36070 3243.80 HDA36080 HGA36080 HJA36080 HLA36080
90 HDA36090 HGA36090 HJA36090 HLA36090
100
900 1700
HDA36100 1361. HGA36100 1772. HJA36100 2225. HLA36100 3243.
110 HDA36110 2730. HGA36110 3779. HJA36110 5432. HLA36110 6951.125 HDA36125 HGA36125 HJA36125 HLA36125
150 HDA36150 HGA36150 HJA36150 HLA36150
a2 pole in 3p module
Table 9.117: J-frame 250 A Standard Rated Thermal Magnetic (600 Vac) with Factory Sealed Trip Units
Ampere
Rating
AC Magnetic
Trip Setting D Interrupting bG Interrupting bJ Interrupting bL Interrupting bTerminal
Wire Range
Low High Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price
2-pole, 600 Vac 50/60 Hz
150 750 1500 JDA26150( ) 2283. JGA26150( ) 3372. JJA26150( ) 4904. JLA26150( ) 5985. AL175JD
#1/0–4/0 AWG
Al or Cu
175 875 1750 JDA26175( ) JGA26175( ) JJA26175( ) JLA26175( )
200 1000 2000 JDA26200( ) 2283. JGA26200( ) 3372. JJA26200( ) 4904. JLA26200( ) 5985. AL250JD
#3/0–350 kcmil
Al or Cu
225 1125 2250 JDA26225( ) JGA26225( ) JJA26225( ) JLA26225( )
250 1250 2500 JDA26250( ) 3138. JGA26250( ) 4463. JJA26250( ) 6536. JLA26250( ) 7338.
3-pole, 600 Vac 50/60 Hz
150 750 1500 JDA36150
2867.
JGA36150
3968.
JJA36150
5705.
JLA36150
7299.
AL175JD
#1/0–4/0 AWG
Al or Cu
175 875 1750 JDA36175 JGA36175 JJA36175 JLA36175
200 1000 2000 JDA36200 JGA36200 JJA36200 JLA36200 AL250JD
#3/0–350 kcmil
Al or Cu
225 1125 2250 JDA36225 JGA36225 JJA36225 JLA36225
250 1250 2500 JDA36250 3936. JGA36250 5252. JJA36250 7599. JLA36250 9173.
b2 pole in 3p module
Table 9.118: Molded Case Switch—Automatic
Ampere
Rating
2-pole 3-pole Withstand Rating aTrip Point
Amperes
AC
Terminal
Wire
Range
Catalog Number $ Price Catalog Number $ Price 240 Vac 480 Vac 600 Vac
G Interrupting
150 HGA26000S15( )b1416. HGA36000S15 1889. 65 35 18 1300 AL150HD
#14–#3/0 AWG Al or Cu
175 JGA26000S17( ) 1919. JGA36000S17 2400. 65 35 18 2500 AL250JD
#3/0–350 kcmil Al or Cu
250 JGA26000S25( ) JGA36000S25
L Interrupting
150 HLA26000S15( ) 1670. HLA36000S15 2087. 125 100 50 1300 AL150HD
#14–#3/0 AWG Al or Cu
175 HLA26000S17( ) 2079. JLA36000S17 2600. 125 100 50 1300 AL250JD
#3/0–350 kcmil Al or Cu
250 JLA26000S25( ) JLA36000S25 2500
aThe withstand rating is the fault current, at rated voltage, that the molded case switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
b2-pole device with 3 in. (76 mm) mounting height, all other 2-pole circuit breakers use 3-pole module 4.5 in. (114 mm) mounting height.
Table 9.119: Phase Options—Example HDA26150( )
Phase
Option
Number
Phase
Connection 2-pole 3-pole
1 AB HDA261501 —
2 AC HDA261502 —
3 BA HDA261503 —
4 BC HDA261504 —
5 CA HDA261505 —
6 CB HDA261506 —
Standard ABC — HDA36150
6 CBA — HDA361506
Table 9.120: Interrupt Ratings (kA)
DGJ L
240 V 25 65 100 125
480 V 18 35 65 100
600 V 14 18 25 50
DE2 Discount
Schedule