DI 000 RELAY 00F_1 Installation Directions

2014-11-11

: Pdf 180958-Installationsheet 180958-InstallationSheet 078477 Batch12 unilog

Open the PDF directly: View PDF PDF.
Page Count: 2

Z-MAX™ Relay Module - Ratings
Cat. # RELAY-STD (NO), -ST2, -1NC (NC)
Single Pole 50/60 Hz
120VAC, 20A General Purpose, Tungsten, Ballast, & 1hp
277VAC, 20A General Purpose, Ballast, & 2hp
Wire Range #14 - #8 AWG Copper; Torque 7 in.-lbs.
Cat. # RELAY-2PL (NO), -2NC (NC)
Double Pole 50/60 Hz
480VAC, 20A General Purpose, Ballast, & 2hp
Wire Range #14 - #6 AWG Copper; Torque 20.5 in.-lbs.
Cat. # RELAY-347 – SPST-NO, 50/60 Hz
347VAC, 20A General Purpose, Ballast
Wire Range #14 - #6 AWG Copper; Torque 20.5 in.-lbs.
Cat. # RELAY-LAT
Single Pole 50/60Hz
120VAC, 20A General Purpose, Tungsten, Ballast, & 1.5hp
277VAC, 20A General Purpose, Ballast, & 2hp
347VAC, 15A Ballast
Wire Range #14 - #8 AWG Copper; Torque 7 in.-lbs.
Cat # RELAY-L30
Single Pole 50/60Hz
120VAC, 20A Tungsten, Ballast & 1/2 hp
277VAC, 30A, Ballast, & 1hp
Wire Range 2 x #14 - #8 AWG Copper; Torque 16 in. –lbs.
For use only in Leviton Z-MAX™ relay cabinets
For installation and operation see publication
provided with your Z-MAX relay cabinet
For more information contact:
Leviton Manufacturing, Inc.
Lighting Management Systems Division Headquarters
20497 SW Teton,Tualatin, Oregon 97062 USA
Voice - (503) 404-5500
Fax - (503) 404-5600
Tech Support - (800) 959-6004
DI-000-RELAY-02G
Cat # RELAY-030
Single Pole 50/60Hz
120VAC, 20A Tungsten, Ballast & 1/2 hp
277VAC, 30A, Ballast, & 2hp
Wire Range 2 x #14 - #8 AWG Copper; Torque 16 in. –lbs.
347VAC, 20A, Ballast
SPECIAL NOTE FOR
LATCHING RELAY TYPES
Latching relays, Leviton part number RELAY-LAT requires relay bus card
firmware 1.13 or higher. Relay-030 or Relay-L30 requires relay bus card
firmware 2.10 or higher. If you do not have this version of bus card firmware,
please contact Leviton Technical Services at (800) 959-6004.
Step 1:
Step 2: Use until
Step 3:
Step 4: Use until
Verify the following:
The number after the "V" is the version number and must be 1.13 or
greater.
The number after the “RLY” indicates the number relay bus card. You
could have 1-6 bus cards in your cabinet. Pressing will view the
software version of other bus cards. Firmware version for all bus cards
should be the same.
NOTE: If the menu doesn’t show up or reports "N/A", you have an earlier
version of software than supports version reporting. Contact Leviton
Technical Services.
Relay-030 and Relay-L30 include a feature whereby if a power supply failure is
detected the relay is latched into a known condition.This condition is factory set
to "open" like a normally open relay. If it is desired to have the relay "closed"
like a normally closed relay, move jumper JP1 to the NC position.
SELECT
MENU
TO CHECK YOUR FIRMWARE VERSION
MAIN MENU SELECT
SOFTWARE BUILD
Ø
8MhzV1.13 RLY
Ø1
S
OFTWARE BUILD
DI-000-RELAY-02G