reference guide
Pow-R-Stock panelboards,
safety switches, and
transformers

Table of contents

Pow-R-Stock panelboards
Questions to ask ..................................... 5
Catalog numbering .................................. 6
Interiors, EZ boxes, and EZ trims ............ 7
Branch and main circuit breakers ............ 8

Safety switches
Questions to ask ...................................11
Catalog numbering ................................12
General-duty safety switches ................13
Heavy-duty safety switches ..................14

Transformers
Questions to ask .................................. 15
Catalog numbering ............................... 16
General-purpose transformers ............. 17
Sizing tables ......................................... 19

EATON CORPORATION www.eaton.com

3

Product contact information
Call 877-ETN-CARE (877-386-2273)

Notes: _______________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________
____________________________________________________

4

EATON CORPORATION www.eaton.com

Questions to ask
Step

1

Select an Interior

Q
Q
Q

What is your voltage?

A

— Single-phase is 3-wire 120/240V
— Three-phase is 4-wire 208Y/120V, 3-wire 240 Vac
or 4-wire 480Y/277 Vac

What is your busbar rating?

A

— 100A (aluminum or copper)
— 225A (aluminum or copper)
— 400A (aluminum or copper)

What is the number of branch circuits/poles?

A

— 18
— 30
— 42

Step

2

Enclosure Type

Q

Do you need NEMA姞 Type 1 (indoor) or Type 3R (outdoor)?

A

— If NEMA Type 1, go to trim
— If NEMA Type 3R, skip trim and go to main device

Step

3

Trim Type

Q

What is the trim type?

A

— Surface
— Flush mount

Step

4

Q

What is your cable entry?

A

— Top
— Bottom

Step

5

Main Device

Q

Main lug or main circuit breaker (MCB)?

A

— Select main breaker amperage from
options available

Pow-R-Stock
panelboards
(unassembled)
EATON CORPORATION www.eaton.com

5

Catalog numbering system—Pow-R-Stock panelboard
interiors

PRL1A 1 225 X 42 A S
Panel Type

PRL1A = PRL1a
PRL2A = PRL2a

Main Device

Phase

1 = Single-phase
3 = Three-phase
Bus Amps

X indicates no main/
use main breaker or
main lug kit
Number of Circuits
18, 30, and 42

100 = 100A
225 = 225A
400 = 400A

Bus Type

A = Aluminum bus
C = Copper bus
Option

S = Short—no TFL or SFB provisions
Special note: This option applies only to
42 circuit 225A interiors.
Note: Top-feed provision for main lugs or
main breaker, no provision for through-feed
lugs or sub-feed breaker.

NEMA 1 Pow-R-Stock Panelboard Boxes

EZB 20 36 R BS
EZB are available boxes used for all Type 1 PRL1a, PRL2a, and PRL3a panels
Width in inches = 20 Height in inches = 36, 48, 60, or 72
R = Right-hand flange
NEMA 1 Pow-R-Stock Panelboard Trims

EZT 20 36 S
EZT are available laser cut trims used on all PRL1a, PRL2a, and PRL3a panels
Width in inches = 20 Height in inches = 36, 48, 60, or 72
Mounting
S = Surface
F = Flush
Main Breaker Kits

BK ED 100 T
Breaker kit
Breaker frame
ED or FD or KD
Trip rating 100, 125 150, 175, 200, 225, 250, 300, 350, 400
Mounting
T = Top
B = Bottom
6

EATON CORPORATION www.eaton.com

Pow-R-Stock panelboards—EZ姠 Boxes and EZ Trims
Single-Phase, 3-Wire 120/240 Vac
Catalog Number
Interiors (Less Main Device)
Ampere Rating

Max. No. of Poles

Aluminum Bus

Copper Bus

100

18

PRL1A1100X18A

PRL1A1100X18C

100

30

PRL1A1100X30A

PRL1A1100X30C

225

30

PRL1A1225X30A

PRL1A1225X30C

225

42

PRL1A1225X42AS 

PRL1A1225X42CS 

225

42

PRL1A1225X42A

PRL1A1225X42C

400

42

PRL1A1400X42A

PRL1A1400X42C

Three-Phase, 4-Wire 208Y/120 Vac or Three-Phase, 3-Wire 240 Vac
Catalog Number
Interiors (Less Main Device)
Ampere Rating

Max. No. of Poles

Aluminum Bus

Copper Bus

100

18

PRL1A3100X18A

PRL1A3100X18C

100

30

PRL1A3100X30A

PRL1A3100X30C

225

30

PRL1A3225X30A

PRL1A3225X30C

225

42

PRL1A3225X42AS 

PRL1A3225X42CS 

225

42

PRL1A3225X42A

PRL1A3225X42C

400

42

PRL1A3400X42A

PRL1A3400X42C

Three-Phase, 4-Wire 480Y/277 Vac
Catalog Number
Interiors (Less Main Device)
Ampere Rating

Max. No. of Poles

Aluminum Bus

Copper Bus

100

18

PRL2A3100X18A

PRL2A3100X18C

100

30

PRL2A3100X30A

PRL2A3100X30C

225

30

PRL2A3225X30A

PRL2A3225X30C

225

42

PRL2A3225X42AS 

PRL2A3225X42CS 

225

42

PRL2A3225X42A

PRL2A3225X42C

400

42

PRL2A3400X42A

PRL2A3400X42C

Single-Phase, 3-Wire 120/240 Vac; Three-Phase, 4-Wire 208Y/120 Vac
or Three-Phase, 3-Wire 240 Vac; Three-Phase, 4-Wire 480Y/277 Vac
Boxes and Trims
Boxes

Trims (NEMA 1)

NEMA 1

Surface

Flush

NEMA 3R Enclosures

EZB2036R

EZT2036S

EZT2036F

GWPBQ2036PR

EZB2048R

EZT2048S

EZT2048F

GWPBQ2048PR

EZB2048R

EZT2048S

EZT2048F

GWPBQ2048PR

EZB2048R

EZT2048S

EZT2048F

GWPBQ2048PR

EZB2060R

EZT2060S

EZT2060F

GWPBQ2060PR

EZB2072R

EZT2072S

EZT2072F

GWPBQ2072PR

 S = Short—no TFL or SFB provisions.

Note 1: The colors shown in the tables correspond to the color coding
on the trim, interior, and box product packaging labels. Be sure all three
parts match when delivering to your customer.
Note 2: Distributors can purchase boxes in quantities via the
Distributor toolbox.
EATON CORPORATION www.eaton.com

7

Branch circuit breakers
Summary of Branch Breakers Available
Breaker
Frame

No. of
Poles

Ampere
Rating

Voltage

kAIC
Rating

Example

Panel
Type

BAB

1
2

15–60
15–100

120 Vac
120/240 Vac

10
10

BAB1020
BAB2020

PRL1a
PRL1a

BAB H

2
3

15–100
15–100

240 Vac
240 Vac

10
10

BAB2040H
BAB3030H

PRL1a
PRL1a

QBGF

1
2

15–30
15–40

120 Vac
120/240 Vac

10
10

QBGF1020
QBGF2040

PRL1a
PRL1a

QBHW

1
2
2
3

15–60
15–100
15–100
15–100

120 Vac
120/240 Vac
240 Vac
240 Vac

22
22
22
22

QBHW1020
QBHW2020
QBHW2040H
QBHW3030H

PRL1a
PRL1a
PRL1a
PRL1a

GHQ

1

15–20

277 Vac

14

GHQ1020

PRL2a

GHB

1
2
3

15–100
15–100
15–100

277 Vac
480Y/277 Vac
480Y/277 Vac

14
14
14

GHB1020
GHB2040
GHB3060

PRL2a
PRL2a
PRL2a

Main circuit breaker kits
Kits—Main Circuit Breaker (Includes Circuit Breaker and Terminals)
Catalog
Number

Breaker
Frame

Mounting
Location

Wire Range
AI/Cu
(in kcmil)

Single- or
three-phase

BKED100T

ED

Top

(1) #14–1/0

125

Single- or
three-phase

BKED125T

ED

Top

(1) #4–4/0

150

Single- or
three-phase

BKED150T

ED

Top

(1) #4–4/0

175

Single- or
three-phase

BKED175T

ED

Top

(1) #4–4/0 

200

Single- or
three-phase

BKED200T

ED

Top

(1) #4–4/0 

225

Single- or
three-phase

BKED225T

ED

Top

(1) #4–4/0 

100

Single- or
three-phase

BKED100B

ED

Bottom

(1) #14–1/0

125

Single- or
three-phase

BKED125B

ED

Bottom

(1) #4–4/0

150

Single- or
three-phase

BKED150B

ED

Bottom

1) #4–4/0

175

Single- or
three-phase

BKED175B

ED

Bottom

(1) #4–4/0 

200

Single- or
three-phase

BKED200B

ED

Bottom

(1) #4–4/0 

225

Single- or
three-phase

BKED225B

ED

Bottom

(1) #4–4/0 

Max. Ampere
Volt. Rating

Service

240
Vac

100

240
Vac

 Order optional lug kit catalog no. 3TA225FDK for 175–225A ED- and FD-Frame

three-pole circuit breakers to provide terminations for (1) #6–300 kcmil.

8

EATON CORPORATION www.eaton.com

Main circuit breaker kits
Kits—Main Circuit Breaker (Includes Circuit Breaker and Terminals)
Catalog
Number

Breaker
Frame

Mounting
Location

Wire Range
AI/Cu
(in kcmil)

Single- or
three-phase

BKFD100T

FD

Top

(1) #14–1/0

125

Single- or
three-phase

BKFD125T

FD

Top

(1) #4–4/0

150

Single- or
three-phase

BKFD150T

FD

Top

(1) #4–4/0

175

Single- or
three-phase

BKFD175T

FD

Top

(1) #4–4/0 

200

Single- or
three-phase

BKFD200T

FD

Top

(1) #4–4/0 

225

Single- or
three-phase

BKFD225T

FD

Top

(1) #4–4/0 

100

Single- or
three-phase

BKFD100B

FD

Bottom

(1) #14–1/0

125

Single- or
three-phase

BKFD125B

FD

Bottom

(1) #4–4/0

150

Single- or
three-phase

BKFD150B

FD

Bottom

(1) #4–4/0

175

Single- or
three-phase

BKFD175B

FD

Bottom

(1) #4–4/0 

200

Single- or
three-phase

BKFD200B

FD

Bottom

(1) #4–4/0 

225

Single- or
three-phase

BKFD225B

FD

Bottom

(1) #4–4/0 

250

Single- or
three-phase

BKKD250T

KD

Top

(1) 250–500

300

Single- or
three-phase

BKKD300T

KD

Top

(1) 250–500

350

Single- or
three-phase

BKKD350T

KD

Top

(1) 250–500

400

Single- or
three-phase

BKKD400T

KD

Top

(2) 3/0–250
or (1) 3/0–500

250

Single- or
three-phase

BKKD250B

KD

Bottom

(1) 250–500

300

Single- or
three-phase

BKKD300B

KD

Bottom

(1) 250–500

350

Single- or
three-phase

BKKD350B

KD

Bottom

(1) 250–500

400

Single- or
three-phase

BKKD400B

KD

Bottom

(2) 3/0–250
or (1) 3/0–500

Max. Ampere
Volt. Rating

Service

480
Vac

100

480
Vac

480
Vac

480
Vac

 Order optional lug kit catalog no. 3TA225FDK for 175–225A ED- and FD-Frame

three-pole circuit breakers to provide terminations for (1) #6–300 kcmil.

Note: KD kits are to be used on 400A panels only.

EATON CORPORATION www.eaton.com

9

Lug kits and accessories
Kits—Main Lugs or Through-Feed Lugs
Ampere Rating

Service

Catalog Number

Wire Range AI/Cu

100

Single- or
three-phase

LUGKIT100

(1) #14–1/0

225

Single- or
three-phase

LUGKIT225

(1) #6–300 Kcmil

400

Single- or
three-phase

LUGKIT400

(2) #2–500 Kcmil

Kits—Service Entrance
Ampere Rating

Service

Catalog Number

Panel Type

100/225

Single- or
three-phase

SEK1/2

PRL1a or PRL2a

400

Single- or
three-phase

SEK4/6

PRL1a or PRL2a

Kits—Insulated/Isolated Ground (Carton Qty. of 5)
Ampere Rating

Service

Catalog Number

Panel Type

100/225/400

Single- or
three-phase

ISOGROUND

PRL1a or PRL2a

Ampere Rating

Service

Catalog Number

Panel Type

100

Single- or
three-phase

2NK100

PRL1a or PRL2a

225

Single- or
three-phase

2NK225

PRL1a or PRL2a

10

EATON CORPORATION www.eaton.com

Kits—200% Neutral

Questions to ask
Step

1

Q

Which type of switch do you need?

A

— Heavy-duty (DH)
— General-duty (DG)
— Double-throw (DT)

Step

2

Q

Step

3

Q

What current (amp) rating do you need?

A

— 30, 60, 100, 200, 400, 600, 800, 1200

Should it be fused, non-fused, or fusible with neutral?

A

— F = Fusible without neutral
— U = Non-fusible
— N = Fusible with neutral

Step

4

Q

Step

5

Q

How many poles?

A

— 1, 2, 3, 4, 6

What voltage do you need?

A

— 120 Vac
— 240 Vac
— 600 Vac

Step

6

Q

What type of enclosure do you need?

A

— NEMA 1
— NEMA 3R
— NEMA 12
— NEMA 4 painted steel
— NEMA 4X stainless steel
— NEMA 4X non-metallic

Safety switches/
disconnects
EATON CORPORATION www.eaton.com

11

Catalog numbering system—safety switches

DH 3 6 1 N D K
Switch Type

DG = Generalduty
DH = Heavy-duty
DT = Double-throw

Fusible/Non-Fusible
or Neutral

F = Fusible without
neutral
U = Non-fusible
N = Fusible with
neutral

Poles/Blades

1 = 1 pole
2 = 2 poles
3 = 3 poles
4 = 4 poles
6 = 6 poles

NEMA Enclosure
Ratings
Voltage

1 = 120 Vac
2 = 240 Vac
6 = 600 Vac
Amperes

1 = 30A
2 = 60A
3 = 100A
4 = 200A
5 = 400A
6 = 600A
7 = 800A
8 = 1200A

12

C = NEMA 4X
Non-metallic
G = NEMA 1
P = NEMA 4
Painted steel
R = NEMA 3R
W = NEMA 4X
Stainless steel
Series

K = Design all general-duty
switches above 200A
and all heavy-duty
switches incorporate
K-Series switch design
B = Design general-duty
30–100A

EATON CORPORATION www.eaton.com

General-duty safety switches (disconnects)
Three-Pole—240 Vac (Suitable for Service Entrance Use
with a Neutral or Ground Lug Kit)
Max. HP
Ratings

Max. HP
Ratings

SinglePhase

ThreePhase

240 Vac

240 Vac

Catalog
Number

Current
Rating
(A)

Type

Enclosure
Type

DG321NGB

30

Fusible with neutral

NEMA 1

1.5–3

3–7.5

DG321UGB

30

Non-fusible

NEMA 1

3

7.5

DG321NRB

30

Fusible with neutral

NEMA 3R

1.5–3

3–7.5

DG321URB

30

Non-fusible

NEMA 3R

3

7.5

DG322NGB

60

Fusible with neutral

NEMA 1

3–10

7.5–15

DG322UGB

60

Non-fusible

NEMA 1

10

15

DG322NRB

60

Fusible with neutral

NEMA 3R

3–10

7.5–15

DG322URB

60

Non-fusible

NEMA 3R

10

15

DG323NGB

100

Fusible with neutral

NEMA 1

7.5–15

15–30

DG323UGB

100

Non-fusible

NEMA 1

15

30

DG323NRB

100

Fusible with neutral

NEMA 3R

7.5–15

15–30

DG323URB

100

Non-fusible

NEMA 3R

15

30

Neutral and Ground Lug Kits
Catalog Number

Description

DG030NB

Neutral kit for 30A switches

DG100NB

Neutral kit for 60–100A switches

DG030GB

Ground lug kit for 30–100A switches

EATON CORPORATION www.eaton.com

13

Heavy-duty safety switches (disconnects)
Three-Pole—480–600 Vac (Suitable for Service Entrance Use
with a Neutral or Ground Lug Kit Below)
Max. HP
Ratings
Catalog
Number

Current
Rating
(A)

Type

Enclosure
Type

Max. HP
Ratings

Single-Phase

Three-Phase

480V

600V

480V 600V

DH361FGK

30

Fusible

NEMA 1

7.5

15

10

20

DH361UGK

30

Non-fusible

NEMA 1

7.5

15

10

20

DH361FRK

30

Fusible

NEMA 3R

7.5

15

10

20
20

DH361URK

30

Non-fusible

NEMA 3R

7.5

15

10

DH362FGK

60

Fusible

NEMA 1

20

30

25

50

DH362UGK

60

Non-fusible

NEMA 1

20

30

25

50

DH362FRK

60

Fusible

NEMA 3R

20

30

25

50

DH362URK

60

Non-fusible

NEMA 3R

20

30

25

50

DH363FGK

100

Fusible

NEMA 1

30

60

40

75

DH363UGK

100

Non-fusible

NEMA 1

30

60

40

75

DH363FRK

100

Fusible

NEMA 3R

30

60

40

75

DH363URK

100

Non-fusible

NEMA 3R

30

60

40

75

DH364FGK

200

Fusible

NEMA 1

50

125

50

150

DH364UGK

200

Non-fusible

NEMA 1

50

125

50

150

DH364FRK

200

Fusible

NEMA 3R

50

125

50

150

DH364URK

200

Non-fusible

NEMA 3R

50

125

50

150

Neutral and Ground Lug Kits
Catalog Number

Description

DH030NK

Neutral kit for 30–60A switches

DH100NK

Neutral kit for 100A switches

DG200NK

Neutral kit for 200A switches

DS100GK

Ground lug kit for 30–100A switches

DS200GK

Ground lug kit for 200A switches

14

EATON CORPORATION www.eaton.com

Questions to ask
Transformers
Step

1

Q

How many phases?

A

— Single-phase
— Three-phase

Step

2

Q

What type of enclosure is required?

A

— Ventilated
— Encapsulated

Step

3

Q

What is the primary voltage? (input voltage)

A

— Single-phase is 240V x 480V
— Three-phase is 480V Delta (three-phase, 3-wire)

Step

4

Q

What is the secondary voltage? (output voltage)

A

— Single-phase
— 120/240
— Three-phase
— 208Y/120 (three-phase, 4-wire) or 240V Delta

Step

5

Q

What kVA transformer is required?

A

— If single-phase encapsulated, kVAs are:
0.05, 0.075, 0.1, 0.15, 0.25, 0.5, 0.75, 1,
1.5, 2, 3, 5, 7.5, 10, 15, 25, 37.5
— If single-phase ventilated, kVAs are:
15, 25, 37.5, 50, 75, 100
— If three-phase encapsulated, kVAs are:
3, 6, 9, 15, 30, 45, 75
— If three-phase ventilated, kVAs are:
15, 30, 45, 75, 112.5, 150, 225, 300, 500

Step

6

Q

If a ventilated transformer was selected

A

— Field kits: Lug kits or weathershields
— Select from selection tables

Transformers
EATON CORPORATION www.eaton.com

15

Catalog numbering system—transformers

T 20 N 11 S 05 A
Type

S = EP
(single-phase
encapsulated)
T = DS-3
(single-phase
ventilated)
V = DT-3
(three-phase
ventilated)
Y = EPT
(three-phase
encapsulated)

Secondary Voltage

11 = 120/240
28 = 208Y/120
22 = 240V Delta
w/120V lighting
tap
Phase

S = Single-phase
T = Three-phase

Primary Voltage

20 = 240 x 480
48 = 480
Taps

D = 2@+2.5%, 2@–2.5%
G = 2@–5%
L = 2@–5% X 4@–2.5%
M = 2@+2.5%,4@–2.5%
N = None
P = 1@+5%, 2@–5%x
2@+2.5%,4@–2.5%

kVA

81 = 0.05
85 = 0.075
82 = 0.10
83 = 0.15
26 = 0.25
51 = 0.50
76 = 0.75
01 = 1
16 = 1.5
02 = 2
03 = 3
05 = 5
06 = 6
07 = 7.5
09 = 9

10 = 10
15 = 15
25 = 25
30 = 30
37 = 37.5
45 = 45
50 = 50
75 = 75
99 = 100
12 = 112.5
49 = 150
67 = 167
22 = 225
33 = 300
55 = 500
Suffix Options

A ... Z = 
EE = 
 Model number for encapsulated transformers.
 NEMA TP-1 transformers. Valid only with ventilated transformers.

16

EATON CORPORATION www.eaton.com

General-purpose transformers
Three-Phase Ventilated, 480 Delta—208Y/120, 150°C Rise,
Aluminum Windings, TP-1
kVA

Style Number

Outline #

Wiring
Diagram

Weathershield

Typical
Lug Kit

15

V48M28T15EE 

912B

280B

WS38

LKS1

30

V48M28T30EE 

912B

280B

WS38

LKS1

45

V48M28T45EE 

912B

280B

WS38

LKS1

75

V48M28T75EE 

914D

280B

WS39

LKS2

112.5

V48M28T12EE

916A

280B

WS19

LKS2

150

V48M28T49EE

916A

280B

WS19

LKS3

225

V48M28T22EE

917

280B

WS34

LKS3

300

V48M28T33EE

918A

275A

WS34

LKS3

500

V48M28T55EE

919

275A

WS35

LKS4

Three-Phase Ventilated, 480 Delta—240 Delta/120 Lighting Tap, 150°C Rise,
Aluminum Windings, TP-1
kVA

Style Number

Outline #

Wiring
Diagram

Weathershield

Typical
Lug Kit

15

V48M22T15EE 

912B

282B

WS38

LKS1

30

V48M22T30EE 

912B

282B

WS38

LKS1

45

V48M22T45EE 

912B

282B

WS38

LKS1

75

V48M22T75EE 

914D

282B

WS39

LKS2

112.5

V48M22T12EE

916A

282B

WS19

LKS2

150

V48M22T49EE

916A

282B

WS19

LKS3

225

V48M22T22EE

917

282B

WS34

LKS3

300

V48M22T33EE

923

282B

WS37

LKS3

500

V48M22T55EE

919

291A

WS35

LKS4

 Suitable for use with wall-mounted bracket WMB01.

EATON CORPORATION www.eaton.com

17

General-purpose transformers
Single-Phase Encapsulated 240x480—120/240, 115°C Rise
kVA

Style Number

Outline #

Wiring
Diagram

0.05

S20N11S81N

52

3A

0.075

S20N11S85N

53

3A

0.1

S20N11S82N

54

3A

0.15

S20N11S83N

55

3A

0.25

S20N11S26N

56

3A

0.5

S20N11S51N

57

3A

0.75

S20N11S76N

58A

3A

1

S20N11S01N

59A

3A

1.5

S20N11S16N

67

3A

2

S20N11S02N

68

3A

3

S20N11S03N

176

3A

5

S20N11S05N

177

3A

7.5

S20N11S07N

178

3A

10

S20N11S10N

179

3A

15

S20N11S15N

180

3A

25

S20L11S25N

182

23A

37.5

S20L11S37

300A

248A

Single-Phase Ventilated, 240x480—120/240, 150°C Rise, Aluminum
Windings, TP-1
kVA

Style Number

Outline #

Wiring
Diagram

Weathershield

Typical Lug Kit

15

T20P11S15EE 

816

3XA

WS11

LKS1

25

T20P11S25EE 

818

3XA

WS11

LKS1

37.5

T20P11S37EE 

818

3XA

WS11

LKS1

50

T20P11S50EE

819

3XA

WS16

LKS2

75

T20P11S75EE

820

3XA

WS16

LKS2

100

T20P11S99EE

821

3XA

WS13

LKS3

Three-Phase Encapsulated, 480—208Y/120, 115°C Rise
kVA

Style Number

Outline #

Wiring Diagram

3

Y48G28T03N

201

70A

6

Y48G28T06N

200

70A

9

Y48G28T09N

103

70A

15

Y48D28T15N

95

72B

30

Y48M28T30N

243

84A

45

Y48M28T45N

244

84A

75

Y48M28T75N

245

84A

 Suitable for use with wall-mounted bracket WMB01.

18

EATON CORPORATION www.eaton.com

General-purpose transformers sizing tables
Three-Phase Transformer Sizing Table
Rated Line–Line Voltage
kVA

208

240

480

600

2400

4160

4800

3

8.3

7.2

3.6

2.9

0.7

0.4

0.4

6

16.7

14.4

7.2

5.8

1.4

0.8

0.7

9

25.0

21.7

10.8

8.7

2.2

1.2

1.1

15

41.6

36.1

18.0

14.4

3.6

2.1

1.8

30

83.3

72.2

36.1

28.9

7.2

4.2

3.6

45

124.9

108.3

54.1

43.3

10.8

6.2

5.4

75

208.2

180.4

90.2

72.2

18.0

10.4

9.0

112.5

312.3

270.6

135.3

108.3

27.1

15.6

13.5

150

416.4

360.9

180.4

144.3

36.1

20.8

18.0

225

624.6

541.3

270.6

216.5

54.1

31.2

27.1

300

832.7

721.7

360.9

288.7

72.2

41.6

36.1

500

1387.9

1202.8

601.4

481.1

120.3

69.4

60.1

750

2081.9

1804.3

902.1

721.7

180.4

104.1

90.2

1000

2775.8

2405.7

1202.8

962.3

240.6

138.8

120.3

Note: Line current = (kVA x 1000)/(line voltage x 1.732)

Single-Phase Transformer Sizing Table
Rated Line–Line Voltage
kVA

120

208

240

277

480

600

2400

4160

4800

0.5

4.2

2.4

2.1

1.8

1.0

0.8

0.2

0.1

0.1

1

8.3

4.8

4.2

3.6

2.1

1.7

0.4

0.2

0.2

1.5

12.5

7.2

6.3

5.4

3.1

2.5

0.6

0.4

0.3

2

16.7

9.6

8.3

7.2

4.2

3.3

0.8

0.5

0.4

3

25.0

14.4

12.5

10.8

6.3

5.0

1.3

0.7

0.6

5

41.7

24.0

20.8

18.1

10.4

8.3

2.1

1.2

1.0

7.5

62.5

36.1

31.3

27.1

15.6

12.5

3.1

1.8

1.6

10

83.3

48.1

41.7

36.1

20.8

16.7

4.2

2.4

2.1

15

125.0

72.1

62.5

54.2

31.3

25.0

6.3

3.6

3.1

25

208.3

120.2

104.2

90.3

52.1

41.7

10.4

6.0

5.2

37.5

312.5

180.3

156.3

135.4

78.1

62.5

15.6

9.0

7.8

50

416.7

240.4

208.3

180.5

104.2

83.3

20.8

12.0

10.4

75

625.0

360.6

312.5

270.8

156.3

125.0

31.3

18.0

15.6

100

833.3

480.8

416.7

361.0

208.3

166.7

41.7

24.0

20.8

167

1391.7

802.9

695.8

602.9

347.9

278.3

69.6

40.1

34.8

250

2083.3

1201.9

1041.7

902.5

520.8

416.7

104.2

60.1

52.1

333

2775.0

1601.0

1387.5

1202.2

693.8

555.0

138.8

80.0

69.4

Note: Line current = (kVA x 1000)/line voltage

EATON CORPORATION www.eaton.com

19

Eaton’s Electrical Sector is
a global leader in power
distribution, power quality,
control & automation and
monitoring products. When
combined with Eaton’s full-scale
engineering services, these
products provide customer-driven
PowerChain Management姞
solutions to serve the power
system needs of the data center,
industrial, institutional,
government, utility, commercial,
residential, IT, mission critical
and OEM markets worldwide.

Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2009 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. CA08307001E / Z8130
August 2009

PowerChain Management
solutions help enterprises
achieve sustainable and
competitive advantages through
proactive management of the
power system as a strategic,
integrated asset throughout
its life cycle, resulting in
enhanced safety, greater
reliability and energy efficiency.
For more information, visit
www.eaton.com/electrical.

PowerChain Management
is a registered trademark of
Eaton Corporation.
All other trademarks are
property of their respective
owners.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c041 52.342996, 2008/05/07-21:37:19
Create Date                     : 2009:08:14 16:43:31-04:00
Modify Date                     : 2009:08:14 16:45:42-04:00
Creator Tool                    : Adobe InDesign CS4 (6.0)
Metadata Date                   : 2009:08:14 16:45:42-04:00
Producer                        : Acrobat Distiller 9.0.0 (Macintosh)
Format                          : application/pdf
Creator                         : Zoltun Design
Title                           : CA08307001E
Description                     : Quick selector reference guide
Document ID                     : uuid:e8ce9518-d6ce-044f-bdfc-550c36afe5c5
Instance ID                     : uuid:9d6d1787-04a2-7840-af5d-5b737b0af256
Page Layout                     : SinglePage
Page Count                      : 20
Author                          : Zoltun Design
Subject                         : Quick selector reference guide
Warning                         : [Minor] Ignored duplicate Info dictionary
EXIF Metadata provided by EXIF.tools

Navigation menu