Data Sheet DB EN MINI DC UPS/24DC/2

384947-Attachment 384947-Attachment 384947-Attachment 012596 Batch5 unilog cesco-content

298204-Attachment 298204-Attachment 298204-Attachment 012596 Batch5 unilog cesco-content

2014-07-04

: Pdf 298206-Attachment 298206-Attachment 012596 Batch5 unilog

Open the PDF directly: View PDF PDF.
Page Count: 9

DownloadData Sheet DB EN MINI-DC-UPS/24DC/2
Open PDF In BrowserView PDF
MINI-DC-UPS/24DC/2
Uninterruptible power supply

INTERFACE
Data Sheet
103123_00_en

© PHOENIX CONTACT - 01/2007

Description
Especially compact and easy-to-use, the new MINI-DC-UPS/
24 DC/2 is a combination of the power supply unit and an uninterruptible power supply in the conventional ME housing. It
secures the operation of all connected 24 V consumers in the
electrical systems both in the case of an error-free supply
network and in the event of mains interferences.
The combined solution enables a slim design with dimensions of 67.5 x 99 x 107 mm. The wide-range input allows input
voltages between 85 V AC and 264 V AC; 2 A is provided at
the output with a regulated and adjustable output voltage
between 22.5 V DC and 29.5 V DC. The rechargeable battery module supplies an output voltage between 27.9 V DC
and 19.2 V DC in the buffer mode. A 0.8 Ah or a 1.3 Ah rechargeable battery module is used depending on the required buffer time: The module thus supplies 2 A for five minutes with the 0.8 Ah rechargeable battery module or 2 A for
30 minutes with the 1.3 Ah rechargeable battery module. The
buffer time varies depending on the load current.

The system availability is increased using extensive signaling through control lamps and active switching outputs. The
charging process of the rechargeable battery module, the
operational readiness, the buffer mode and the alarm messages are displayed before the rechargeable battery module
is discharged. The service life of the rechargeable battery
module can be increased by optimum battery management;
for example, a temperature-compensated charging protects
the rechargeable battery module at high ambient temperatures. An integrated timeout minimizes installation costs considerably.

Danger!
Components with dangerously high voltage and high stored energy are located in the device!
Never carry out work on live parts!
Depending on the ambient temperature and the load, the housing can become very hot!
Make sure you always use the the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.

MINI-DC-UPS/24DC/2

Order data
Description

Type

Order No.

Pcs./Pkt.

Uninterruptible power supply

MINI-DC-UPS/24DC/2

2866640

1

Accessories

Type

Order No.

Pcs./Pkt.

Battery module, 24 V DC, 0.8 Ah

MINI-BAT/24DC/0.8AH

2866666

1

Battery module, 24 V DC, 1.3 Ah

MINI-BAT/24DC/1.3AH

2866417

1

Technical data
Input data
Input nominal voltage range

100 V AC ... 240 V AC

AC input voltage range

85 V AC ... 264 V AC

DC input voltage range

100 V DC ... 350 V DC

Buffer period

(settable: 0.5 min; 1 min; 2 min; 3 min; 5 min; 10 min; 15 min; 20 min; 30 min;
continuous)

Current consumption

Approx. 0.6 A (230 V AC)
Approx. 1.1 A (115 V AC)

Inrush current limitation/I2t

< 34 A (< 1.1 A2s)

Power failure bypass

(refer to the diagram)

Typical response time

100 ms

Power factor (cos phi)

Approx. 0.5

Protective circuitry

Varistor

Input fuse, integrated

3.15 A (slow-blow, internal)

Output data
Nominal output voltage

24 V DC

Setting range of the output voltage

22.5 V DC ... 29.5 V DC (normal mode; in the buffer mode, dependent on a battery voltage of 27.9 V DC ... 19.2 V DC)

Output current

2A

Derating

From +60°C 2.5% per Kelvin

Output current limit

Max. 3 A

Max. capacitive load

Unlimited

Control deviation

< 1 % (change in load, static 10% ... 90%)

Power loss

Max 2,5 W (buffer mode)

Power loss nominal load max.

15 W

Maximum power dissipation idling

3.8 W

Efficiency

> 82 % (typical)

Ascent time

< 100 ms

Residual ripple

< 50 mVPP

Peak switching voltages

< 100 mVPP

Connection in parallel

Yes, for redundancy

Surge protection against internal surge voltages

Yes, < 35 V DC

Resistance to reverse feed

35 V DC

Signal output Power OK
Status display

103123_00_en

Green LED (Power OK: LED permanently lit)

PHOENIX CONTACT

2

MINI-DC-UPS/24DC/2

Signal output Alarm
Output description

Relay output

Continuous current

200 mA

Output voltage

24 V

Status display

LED red (malfunction/alarm: LED permanently lit)

Signal output Battery charge
Output description

Relay output

Continuous current

200 mA

Output voltage

24 V

Status display

Yellow LED (Battery charge/battery is being charged: LED flashing)

Signal output Battery mode
Output description

Relay output

Continuous current

200 mA

Output voltage

24 V

Status display

Yellow LED (Battery mode/buffer mode: LED permanently lit)

Standards
Electrical Equipment for Machinery

EN 60204

Safety transformers for power supply units

EN 61558-2-17

Electrical safety (of information technology equipment)

EN 60950/VDE 0805 (SELV)
UL/C-UL recognized UL 60950

Industrial control equipment

UL/C-UL Listed UL 508

Electronic equipment for use in electrical power installations

EN 50178/VDE 0160 (PELV)

SELV

EN 60950 (SELV)
EN 60204 (PELV)

Safe isolation

DIN VDE 0100-410
DIN VDE 0106-1010

Protection against electric shock, basic requirements for safe isolation in
electrical equipment

DIN VDE 0106-101

General data
Insulation voltage input/output

2 kV (routine test)
4 kV (type test)

Installation position

Horizontal DIN rail NS 35, EN 60715

Degree of protection

IP20

Class of protection

II

MTBF

> 500 000 h in acc. with IEC 61709 (SN 29500)

Housing version

Polyamide PA, color: green

Width

67,5 mm

Height

99 mm

Depth

107 mm

Weight

0.45 kg

103123_00_en

PHOENIX CONTACT

3

MINI-DC-UPS/24DC/2

Climatic data
Ambient temperature (operation)

-25 °C ... 70 °C (> 60°C derating)

Ambient temperature (storage/transport)

-40 °C ... 85 °C

Max. permissible relative humidity (operation)

95 % (at 25°C, no condensation)

Vibration (operation)

< 15 Hz, amplitude ±2.5 mm in acc. with IEC 60068-2-6
15 Hz ... 150 Hz, 2.3g, 90 min.

Shock

30g in all directions in acc. with IEC 60068-2-27

Pollution degree in acc. with EN 50178

2

Climatic class

3K3 (in acc. with EN 60721)

Conformance with EMC directive 89/336/EEC
Immunity to interference in acc. with EN 61000-6-2
Discharge of static electricity in acc. with EN 61000-4-2
Housing

Level 3

Contact discharge

6 kV

Discharge in air

8 kV

Comments

Criterion B

Electromagnetic HF field in acc. with EN 61000-4-3
Housing

Level 3

Frequency range

80 MHz ... 2 GHz

Field intensity

10 V/m

Comments

Criterion A

Fast transients (burst) in acc. with EN 61000-4-4
Input

4 kV (level 4 - asymmetrical: conductor to ground)

Output

2 kV (level 3 - asymmetrical: conductor to ground)

Signal

1 kV (level 2 - asymmetrical: conductor to ground)

Comments

Criterion B

Surge voltage capacities (surge) in acc. with EN 61000-4-5
Input

4 kV (level 4 - asymmetrical: conductor to ground)
2 kV (level 4 - symmetrical: conductor to conductor)

Output

2 kV (Level 3 - asymmetrical)

Signal

2 kV (Level 3 - asymmetrical)

Comments

Criterion B

1 kV (Level 3 - symmetrical)

Conducted disturbance in acc. with EN 61000-4-6
Input/Output/Signal

Level 3

Frequency range

10 kHz ... 80 MHz

Voltage

10 V

Comments

Criterion A

Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011

EN 55011 (EN 55022) Class B, area of application: Industry and residential

Emitted radio interference in acc. with EN 55011

EN 55011 (EN 55022) Class B, area of application: Industry and residential

Note:
Criterion A: Normal operating behavior within the defined limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself
EN 55011 corresponds to CISPR11 / EN 55022 corresponds to CISPR22
EN 61000 corresponds to IEC 1000

103123_00_en

PHOENIX CONTACT

4

MINI-DC-UPS/24DC/2

Block diagram
t...[min]

Remote
On/Off

R1
R2

Alarm
Bat. Mode
Charge

Battery

L(+)

PS

N(-)

+24 V/2A

Structure

2 4
5
"
O
U
T
D
C
2
4
V
2
e
h
C
t.
a
B

e
tt
a
B
2
R e
t
1 o F
R em F
O N
R
O

10

15

8,5
-2
,5 DC
22 V

5

B

a

a

t.

rg

-

3

e

M

0
30 2

o

2

d

]

A

in

la

[m

ax

1

0,5

rm

A

tm

7

6
8
3

ry

A
la
rm

K

ve

O

O

in

e

er

rg

ow

ha

e

-C

od

at.
P

9

-M

B

at.

B

rlo

S
P
-U
C
ID
IN
M

ad

V
0
4
2
- -)
0 (
0 N
1
C
A +)
(
IN L

1

0
INPUT

-25

AC input
DC output
Rechargeable battery connection
Active relay output: Alarm
Active relay output: Battery mode
Active relay output: Battery charge
Potentiometer 22.5 V DC ... 29.5 V DC
Remote shutdown (R1, R2)
Red control lamp: Alarm
Yellow control lamp: Battery mode/ Battery charge
Green control lamp: Power In OK / Overload
Buffer time setting 0.5 min ... 30 min and continuous

-25 ... + 70°C
-13 ... + 158°F

INFORMATION
TECHNOLOGY

US EQUIPMENT

(>60°C/+140°F Derating)

C

Read installation instructions
before connecting to mains

!

www.interface.phoenixcontact.com

TEMPERATURE

Power Supply

!

INDUSTRIAL
US CONTROL
EQUIPMENT
LISTED
43KA

UL

APPROVALS

C

MINI-DC-UPS/24DC/2
Order-No.: 28 66 64 0

OUTPUT

DC:
100-350V
0.8-0.2A

DC:
AC:
24V
100-240V~
2A
50-60Hz
Range:
85-264V~
1.55-0.5A

!

1
2
3
4
5
6
7
8
9
10
11
12

Input
Output
Signal

[mm2]
solid
stranded
0.2 - 2.5 0.2 - 2.5
0.2 - 2.5 0.2 - 2.5
0.2 - 2.5 0.2 - 2.5

AWG
24 - 12
24 - 12
14 - 24

[Nm]
Torque
0.5 - 0.6
0.5 - 0.6
0.5 - 0.6

Input data
Input nominal voltage range

100 V AC ... 240 V AC

AC input voltage range

85 V AC ... 264 V AC

DC input voltage range

100 V DC ... 350 V DC

Input fuse, integrated

3.15 A (slow-blow, internal)

Type of connection

COMBICON screw/plug connection

Stripping length

8 mm

Output data
Nominal output voltage

24 V DC

Setting range of the output voltage

22.5 V DC ... 29.5 V DC (normal mode; in the buffer mode, dependent on a
battery voltage of 27.9 V DC ... 19.2 V DC)

Output current

2A

Type of connection

COMBICON screw/plug connection

Stripping length

8 mm

103123_00_en

PHOENIX CONTACT

5

MINI-DC-UPS/24DC/2

Safety and warning notes
The power supply units are built-in devices. The device may only be installed and put into operation by qualified personnel. The corresponding national regulations (e.g. VDE, DIN) must be observed.
Danger!
Components with dangerously high voltage and high stored energy are located in the device!
Never carry out work on live parts!
Depending on the ambient temperature and the load, the housing can become very hot!
Before startup please ensure:
The mains connection has been carried out by a competent person and protection against electric
shock is guaranteed!
All feed lines are sufficiently protected and dimensioned!
All output lines are dimensioned according to the maximum output current of the device or separately
protected!
Sufficient convection is guaranteed!

Installation
In order for the device to function in the manner intended. it is not necessary to observe
any minimum spacing to other devices.
The power supply unit can be snapped onto all
DIN rails in acc. with EN 60715. They must be
horizontal (connecting terminal blocks above
and below).

Installation position
Assembly
Position the module with the DIN rail guide on the upper edge
of the DIN rail, and snap it in with a downward motion.
Dismantling
Pull the snap lever open with the aid of a screwdriver and
slide the module out at the lower edge of the DIN rail.

103123_00_en

PHOENIX CONTACT

6

MINI-DC-UPS/24DC/2

Connection, network forms 100...240 V AC networks
TN-S

TN-C
L
N
PE

L N

TT
L
PEN

L N

+ -

+ -

The 100...240 V AC connection is made using the L and N
screw connections.
The device can be connected to 1-phase AC networks or to
two of the phase conductors of three-phase systems (TN, TT
or IT networks in acc. with VDE 0100-300/IEC 60364-3) with
nominal voltages of 100 V AC ...240 V AC.

iT
L1
L2
L3

L
N

L N

+ -

L N

+ -

For operation on two of the phase conductors
of a three-phase system, an isolating facility for
all poles must be provided.

Input
O

The 100-...240 V AC connection is established using the L
and N screw connections.

U
T
D
C
2
4
V
2
rm

A

e

B

h
C
t.
a
B

e
tt
a
B
2
R e
t
1 o F
R em F
O N
R
O

10

15

8,5
-2
,5 DC
22 V

5

The device must be installed in acc. with the regulations as
in EN 60950. It must be possible to disconnect the device
using a suitable isolating facility outside the power supply.
The primary side line protection, for example, is suitable. For
device protection, there is an internal fuse. Additional device
protection is not necessary.

a

a

t.

rg

-

3

e

M

0
30 2

o

2

d

]

A

in

la

[m

1

0,5

ax

tm

ry

A
la
rm

B
K

ve

O

O

in

e

er

rg

ow

ha

e

P

-C

od

at.

-M

B

at.

rlo

S
P
-U
C
ID
IN
M

ad

V
0
4
2
- -)
0 (
0 N
1
C
A +)
(
IN L

1

INPUT

!

-25

-25 ... + 70°C
-13 ... + 158°F

INFORMATION
TECHNOLOGY

US EQUIPMENT

(>60°C/+140°F Derating)

C

Read installation instructions
before connecting to mains

!

www.interface.phoenixcontact.com

INDUSTRIAL
US CONTROL
EQUIPMENT
LISTED
43KA

UL

TEMPERATURE

Power Supply

C

APPROVALS

MINI-DC-UPS/24DC/2
Order-No.: 28 66 64 0

OUTPUT

DC:
100-350V
0.8-0.2A

DC:
AC:
24V
100-240V~
2A
50-60Hz
Range:
85-264V~
1.55-0.5A

103123_00_en

If an internal fuse is triggered, there is most
probably a malfunction in the device. In this
case, the device must be inspected in the
factory!

PHOENIX CONTACT

7

MINI-DC-UPS/24DC/2

Output
DC output
O

Active switching
outputs

U
T
D
C
2
4
V
2
rm

A

e
h
C
t.
a
B

e
tt
a
B
2
R e
t
1 o F
R em F
O N
R
O

10

15

8,5
-2
,5 DC
22 V

5

B

a

a

t.

rg

-

3

e

M

0
30 2

o

2

d

]

A

in

la

[m

1

0,5

ax

tm

ry

A
e

K

ve

O

O

in

e

er

rg

ow

ha

P

-C

od

at.

-M

B

at.

rm

la

B

rlo

M
IN

ID

C

-U

P

S

ad

V
0
4
2
- -)
0 (
0 N
1
C
A +)
(
IN L

INPUT

-25

-25 ... + 70°C
-13 ... + 158°F

INFORMATION
TECHNOLOGY

US EQUIPMENT

(>60°C/+140°F Derating)

C

Read installation instructions
before connecting to mains

!

www.interface.phoenixcontact.com

TEMPERATURE

Power Supply

!

INDUSTRIAL
US CONTROL
EQUIPMENT
LISTED
43KA

UL

APPROVALS

C

MINI-DC-UPS/24DC/2
Order-No.: 28 66 64 0

OUTPUT

DC:
100-350V
0.8-0.2A

DC:
AC:
24V
100-240V~
2A
50-60Hz
Range:
85-264V~
1.55-0.5A

Control lamps

The connection is established through the "OUT DC 24 V, +, –" screw connections. The set output voltage is 24 V DC at
the time of delivery. The output voltage from 22.5 V DC to 29.5 V DC can be set on the potentiometer.
Signaling outputs
Signal outputs are connected using "Alarm", "Bat.-Mode" and "Bat.-Charge" terminal blocks. Three control lamps and three
active switching outputs are provided for function monitoring.
State

Power In OK

Battery mode/ Battery charge

Alarm

Supply voltage OK, rechargeable
battery is being charged

LED on

LED is flashing; Battery mode
output: 0 V, Battery charge: 24 V

LED off; output: 0 V

Supply voltage OK, rechargeable
battery charged (normal mode)

LED on

LED off; Battery mode / Battery
charge output: 0 V

LED off; output: 0 V

Buffer mode

LED off

LED on; Battery mode output: 24 V, LED off; output: 0 V
Battery charge: 0 V

Rechargeable battery discharged, LED off
UBAT < 20.4 V DC

LED on; Battery mode / Battery
charge output: 0 V

LED on; output: 24 V

Rechargeable battery test negative

LED on

LED off; Battery mode / Battery
charge output: 0 V

LED on; output: 24 V

Buffer time over and remote shut- LED off
down activated

LED off; Battery mode / Battery
charge output: 0 V

LED off; output: 0 V

103123_00_en

PHOENIX CONTACT

8

MINI-DC-UPS/24DC/2

Current [A]

Rechargeable battery module
The rechargeable battery module is connected to the power
supply unit through the "Battery +" and the "Battery –" terminal blocks. The fuse of the rechargeable battery module
must be removed when installing or replacing the module.

2
1,5
1,0
0,5
0
0

30

60

90

120

150

180

210

240

Buffer time[min]
MINI-BAT 24DC/0,8Ah
MINI-BAT 24DC/1,3Ah

The following rechargeable battery modules are recommended:
MINI-BAT 24DC/0.8Ah (order no. 2866666),
MINI-BAT 24DC/1.3Ah (order no. 2866417)
The buffer mode might be terminated after the preset time or
due to an external shutdown. If the device is to be switched
off after a certain period, the time for it is set using the selector switch at the front of the device. The device can be switched on in the buffer mode again after reconnecting the
power supply.

Remote shutdown ("Remote")
The device has a remote shutdown with a UPS function for deliberate shutdown. Remote shutdown must be deactivated
for the device to switch over to the buffer mode in the event of a supply voltage failure.
Remote shutdown inactive
– The "Remote shutdown R1" and "Remote shutdown R2" terminal points are short-circuited (e.g. with a plug-in bridge)
OR 24 V DC is present at the "Remote shutdown R2" terminal point.
– The power supply unit switches over to the buffer mode in the event of a supply voltage failure.
Remote shutdown active
– The "Remote shutdown R1" and "Remote shutdown R2" terminal points are not short-circuited (e.g. with a plug-in bridge)
OR 0 V is present at the "Remote shutdown R2" terminal point.
- All LEDs are off.
– The power supply does not switch over to the buffer mode in the event of a supply voltage failure; the device switches
off. The rechargeable battery module is charged when the supply voltage is reconnected, but the device remains switched
off until the remote shutdown is activated.
– The connected consumers are fed as long as the supply voltage is available.

Function
Output voltage
In the normal mode, the output voltage of the device conforms to the setting on the potentiometer (22.5 V DC ... 29.5 V DC).
If the supply voltage fails, the buffer mode is activated without any interruption and the output voltage is supplied by the
rechargeable battery module. The output voltage is now directly dependent on the battery voltage and is UBAT - 0.5 V.
An alarm signal is triggered if the output voltage drops below 20.4 V in the buffer mode. If the output voltage drops to 19.2
V due to a completely discharged rechargeable battery module, the device switches off and remains switched off. The device switches on automatically only after reconnecting the power supply. The device is electronically protected against short
circuit and idling.

103123_00_en

PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00
www.phoenixcontact.com

9



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Page Mode                       : UseOutlines
XMP Toolkit                     : 3.1-702
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Create Date                     : 2002:03:01 06:14:01Z
Creator Tool                    : FrameMaker 7.1
Metadata Date                   : 2007:01:19 11:53:14+01:00
Modify Date                     : 2012:05:25 14:34:52+02:00
Format                          : application/pdf
Title                           : Data Sheet DB EN MINI-DC-UPS/24DC/2
Creator                         : PHOENIX CONTACT GmbH & Co. KG
Description                     : Uninterruptible power supply
Document ID                     : uuid:0b74dad9-da19-4012-a47f-ffa607014eb7
Instance ID                     : uuid:31afd0e7-ad30-48fe-ab53-a702a473c6c5
Page Count                      : 9
Subject                         : Uninterruptible power supply
Author                          : PHOENIX CONTACT GmbH & Co. KG
EXIF Metadata provided by EXIF.tools