Miniature Circuit Breakers and
Supplementary Protectors
Miniature Circuit Breakers and
Supplementary Protectors

1.1

Industrial Circuit Breakers
QUICKLAG®. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW . . . . . . . . . . .
QUICKLAG Plug-On Ground Fault and Equipment Protectors,
Types QPGF, QPHGF, QPGFEP, QPHGFEP . . . . . . . . . . . . . . . . . . . .
Bolt-On Types BAB, QBHW, HBAX, HBAW. . . . . . . . . . . . . . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types QBAF, QBCAF . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment Protectors,
Types QCGF, QCHGF, QCGFEP, QCHGFEP . . . . . . . . . . . . . . . . . . . .
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . . . . . . . . . . . . . .
Solenoid Operator—Remote-Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . . . . . . . . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC. . . . . . . . . . .
Special Application Breakers, Types HQP, BA, QC . . . . . . . . . . . . . . .

1.2

1

V4-T1-8

1

V4-T1-11
V4-T1-14

1

V4-T1-17

1

V4-T1-20

1

V4-T1-24

1

V4-T1-28

1

V4-T1-31

1

V4-T1-34

1

V4-T1-37
V4-T1-40

V4-T1-49
V4-T1-67

1
1
1
1

UL 1077 DIN Rail Supplementary Protectors
FAZ Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WMZS Circuit Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

V4-T1-5

UL 489 DIN Rail Miniature Circuit Breakers
FAZ-NA Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WMZ Circuit Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3

V4-T1-2

V4-T1-82
V4-T1-103

1
1
1

Learn
Online

1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-1

1.1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Contents

Miniature Circuit Breakers and Supplementary Protectors

Description

1

Quick Reference

1
1
1
1
1
1
1
1
1
1
1
1

QUICKLAG

1

Quick Reference

1

Eaton’s QUICKLAG Industrial Circuit Breakers 1 Plug-In, Bolt-On, Cable-In/Cable-Out

1

Circuit
Breaker
Type

1
1

Circuit Breaker
Type Code

Continuous
Ampere
Rating
at 40°C

Number
of
Poles

Vac

Vdc

Interrupting Ratings rms Symmetrical Amperes
Federal
Spec.
W-C-375b

Vac Ratings
120

120/240

240

24–48

62.5

80

Vdc Ratings 2

Page
Number

HQP

P

10–70

1

120/240

24, 48, 62.5

10a, 11a, 12a

—

10,000

—

5000

3

—

V4-T1-6

HQP

P

10–125

2

120/240

24, 48, 80

10a, 12a

—

10,000

—

5000

5000

5000

V4-T1-6

HQP

P

10–100

2, 3

240

—

10b, 11b, 12b

—

—

10,000

—

—

—

V4-T1-6

—

V4-T1-6

1

QPHW

P

15–70

1

120/240

24, 48, 62.5

14a

—

22,000

—

5000

3

1

QPHW

P

15–125

2

120/240

24, 48, 80

14a

—

22,000

—

5000

5000

5000

V4-T1-6

QPHW

P

15–100

2, 3

240

—

14b

—

—

22,000

—

—

—

V4-T1-6

1

QHPX

P

15–70

1

120/240

24, 48, 62.5

—

—

42,000

—

5000

3

—

V4-T1-7

QHPX

P

15–100

2

120/240

24, 48, 80

—

—

42,000

—

5000

5000

5000

V4-T1-7

1

QHPX

P

15–100

3

240

—

—

—

—

42,000

—

—

—

V4-T1-7

QHPW

P

15–30

1

120/240

24, 48, 62.5

15a

—

65,000

—

5000

3

—

V4-T1-7

QHPW

P

15–30

2

120/240

24, 48, 80

15a

—

65,000

—

5000

5000

5000

V4-T1-7
V4-T1-7

1
1
1
1
1
1
1

QHPW

P

15–20

3

240

—

15b

—

—

65,000

—

—

—

QPGF

P, GF

15–40

1

120

—

10a, 11a, 12a

10,000

—

—

—

—

—

V4-T1-9

QPGF

P, GF

15–50

2

120/240

—

10a, 11a, 12a

—

10,000

—

—

—

—

V4-T1-9

Notes
1 QUICKLAG circuit breakers are suitable for application in relative humidity 0–95% noncondensing.
2 Two-pole DC interrupting ratings based on two poles connected in series. Not UL® listed.
3 62.5 Vac interrupting rating is 3800 AIC 10–50A and 2500 AIC 55–100A continuous.
Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA.
For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
For Type WMZ circuit breakers, see Pages V4-T1-67 to V4-T1-81.
For Types WMZS and SPHM supplementary protectors, see Pages V4-T1-103 to V4-T1-118.

V4-T1-2

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Eaton’s QUICKLAG Industrial Circuit Breakers 1 Plug-In, Bolt-On, Cable-In/Cable-Out, continued
Circuit
Breaker
Type

Circuit Breaker
Type Code

Continuous
Ampere
Rating
at 40°C

1

Interrupting Ratings rms Symmetrical Amperes
Number
of
Poles

Vac

Vdc

Federal
Spec.
W-C-375b

Vac Ratings
120

120/240

Vdc Ratings
240

24–48

2

62.5

80

Page
Number

QPHGF

P, GF

15–30

1

120

—

10a, 11a, 12a

22,000

—

—

—

—

—

V4-T1-9

QPHGF

P, GF

15–50

2

120/240

—

10a, 11a, 12a

—

22,000

—

—

—

—

V4-T1-9

QPGFEP

P, GFEP

15–40

1

120

—

—

10,000

—

—

—

—

—

V4-T1-9

QPGFEP

P, GFEP

15–50

2

120/240

—

—

—

10,000

—

—

—

—

V4-T1-9

QPHGFEP

P, GFEP

15–30

1

120

—

—

22,000

—

—

—

—

—

V4-T1-9

BABRSP

B

15–30

1

120

—

—

10,000

—

—

—

—

—

V4-T1-12

BABRSP

B

15–30

2

120/240

—

—

—

10,000

—

—

—

—

V4-T1-12

BRRP

P

15–30

1

120

—

—

10,000

—

—

—

—

—

V4-T1-32

BRRP

P

15–30

2

120/240

—

—

—

10,000

—

—

—

—

V4-T1-32

CLRP

P

15–30

1

120

—

—

10,000

—

—

—

—

—

V4-T1-32

CLRP

P

15–30

2

120/240

—

—

—

10,000

—

—

—

—

V4-T1-32

BAB

B

10–70

1

120/240

24, 48, 62.5

10a, 11a, 12a

—

10,000

—

5000

3

—

V4-T1-12

BAB

B

10–125

2

120/240

24, 48, 80

10a, 12a

—

10,000

—

5000

5000

5000

V4-T1-12

BAB

B

10–100

2, 3

240

—

10b, 11b, 12b

—

—

10,000

—

—

—

V4-T1-12

BABRP

B

15–30

1

120

—

—

10,000

—

—

—

—

—

V4-T1-32

BABRP

B

15–30

2

120/240

—

—

—

10,000

—

—

—

—

V4-T1-32

QBAF

B, AF

15–20

1, 2

120/240

—

—

—

10,000

—

—

—

—

V4-T1-15

QBCAF

B, AF, GF

15–20

1, 2

120/240

—

—

—

10,000

—

—

—

—

V4-T1-15

QBHW

B

15–70

1

120/240

24, 48, 62.5

14a

—

22,000

—

5000

3

—

V4-T1-12

QBHW

B

15–125

2

120/240

24, 48, 80

14a

—

22,000

—

5000

5000

5000

V4-T1-12

QBHW

B

15–100

2, 3

240

—

14b

—

—

22,000

—

—

—

V4-T1-12

HBAX

B

15–70

1

120/240

24, 48, 62.5

—

—

42,000

—

5000

3

—

V4-T1-13

HBAX

B

15–100

2

120/240

24, 48, 80

—

—

42,000

—

5000

5000

5000

V4-T1-13

HBAX

B

15–100

3

240

—

—

—

42,000

—

—

—

V4-T1-13

HBAW

B

15–30

1

120/240

24, 48, 62.5

15a

—

65,000

—

5000

3

—

V4-T1-13

HBAW

B

15–30

2

120/240

24, 48, 80

15a

—

65,000

—

5000

5000

5000

V4-T1-13

HBAW

B

15–20

3

240

—

15b

—

—

65,000

—

—

—

V4-T1-13

QBGF

B, GF

15–40

1

120

—

10a, 11a, 12a

10,000

—

—

—

—

—

V4-T1-18

QBGF

B, GF

15–50

2

120/240

—

10a, 11a, 12a

—

10,000

—

—

—

—

V4-T1-18

QBHGF

B, GF

15–30

1

120

—

10a, 11a, 12a

22,000

—

—

—

—

—

V4-T1-18

QBHGF

B, GF

15–30

1

120/240

—

10a, 11a, 12a

—

22,000

—

—

—

—

V4-T1-18

QBGFEP

B, GFEP

15–40

1

120

—

—

10,000

—

—

—

—

—

V4-T1-18

QBGFEP

B, GFEP

15–50

2

120/240

—

—

—

10,000

—

—

—

—

V4-T1-18

QBHGFEP

B, GFEP

15–30

1

120

—

—

22,000

—

—

—

—

—

V4-T1-18

QBHGFEP

B, GFEP

15–30

2

120/240

—

—

22,000

22,000

—

—

—

—

V4-T1-18

QC

C

10–70

1

120/240

24, 48, 62.5

10a, 11a, 12a

—

10,000

—

5000

3

—

V4-T1-41

QC

C

10–100

2

120/240

24, 48, 80

10a, 12a

—

10,000

—

5000

5000

5000

V4-T1-41

QC

C

10–100

2, 3, 4

240

—

10b, 11b, 12b

—

—

10,000

—

—

—

V4-T1-41

QCD

C

10–60

1, 2

120/240

24, 48, 62.5

—

10,000

10,000

—

3000

3000

—

V4-T1-23

QCD

C

10–100

2, 3

240

24, 48, 62.5

—

—

10,000

—

3000

3000

—

V4-T1-23

QCF

C

10–60

1, 2

120/240

24, 48, 62.5

—

10,000

10,000

—

3000

3000

—

V4-T1-42

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Notes
1 QUICKLAG circuit breakers are suitable for application in relative humidity 0–95% noncondensing.
2 Two-pole DC interrupting ratings based on two poles connected in series. Not UL listed.
3 62.5 Vac interrupting rating is 3800 AIC 10–50A and 2500 AIC 55–100A continuous.

1

Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA.
For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
For Type WMZ circuit breakers, see Pages V4-T1-67 to V4-T1-81.
For Types WMZS and SPHM supplementary protectors, see Pages V4-T1-103 to V4-T1-118.

1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1
1
V4-T1-3

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1

Eaton’s QUICKLAG Industrial Circuit Breakers 1 Plug-In, Bolt-On, Cable-In/Cable-Out, continued

1

Circuit
Breaker
Type

1

QCF

C

15–20

1, 2

1

QCF

C

15–30

2, 3

QCR

C

10–60

1, 2

1

QCR

C

15–20

QCR

C

QCHW
QCHW

1
1

Continuous
Ampere
Rating
at 40°C

Interrupting Ratings rms Symmetrical Amperes
Vac Ratings

Vdc

Federal
Spec.
W-C-375b

120

120/240

240

24–48

62.5

80

Page
Number

120/240

24, 48, 62.5

—

22,000

—

—

3000

3000

—

V4-T1-27

240

24, 48, 62.5

—

—

10,000

—

3000

3000

—

V4-T1-27

120/240

24, 48, 62.5

—

10,000

10,000

—

3000

3000

—

V4-T1-27

1, 2

120/240

24, 48, 62.5

—

22,000

—

—

3000

3000

—

V4-T1-27

15–30

2, 3

240

24, 48, 62.5

—

—

10,000

—

3000

3000

—

V4-T1-27

C

15–70

1

120/240

24, 48, 62.5

14a

—

22,000

—

5000

—

V4-T1-22

C

15–100

2

120/240

24, 48, 80

14a

—

22,000

—

5000

5000

5000

V4-T1-22

—

—

V4-T1-22

3

—

V4-T1-22

Circuit
Breaker
Type Code

Number
of
Poles

Vac

Vdc Ratings 2

3

QCHW

C

15–100

2, 3

240

—

14b

—

—

22,000

—

1

QHCX

C

15–70

1

120/240

24, 48, 62.5

—

—

42,000

—

5000

QHCX

C

15–100

2

120/240

24, 48, 80

—

—

42,000

—

5000

5000

5000

V4-T1-22

1

QHCX

C

15–100

3

240

—

—

—

—

42,000

—

—

—

V4-T1-22

QHCW

C

15–30

1

120/240

24, 48, 62.5

15a

—

65,000

—

5000

3

—

V4-T1-22

QHCW

C

15–30

2

120/240

24, 48, 80

15a

—

65,000

—

5000

5000

5000

V4-T1-22

1

QHCW

C

15–20

3

240

—

15b

—

—

65,000

—

—

—

V4-T1-22

QCGF

C, GF

15–40

1

120

—

—

10,000

—

—

—

—

—

V4-T1-29

1

QCGF

C, GF

15–50

2

120/240

—

—

—

10,000

—

—

—

—

V4-T1-29

QCHGF

C, GF

15–30

1

120

—

—

22,000

—

—

—

—

—

V4-T1-29

QCHGF

C, GF

15–30

2

120/240

—

—

—

22,000

—

—

—

—

V4-T1-29

QCGFEP

C, GFEP

15–40

1

120

—

—

10,000

—

—

—

—

—

V4-T1-29
V4-T1-29

1

1
1
1
1
1
1
1
1

QCGFEP

C, GFEP

15–50

2

120/240

—

—

—

10,000

—

—

—

—

QCHGFEP

C, GFEP

15–30

1

120

—

—

22,000

—

—

—

—

—

V4-T1-29

QCHGFEP

C, GFEP

15–30

2

120/240

—

—

—

22,000

—

—

—

—

V4-T1-29

Notes
1 QUICKLAG circuit breakers are suitable for application in relative humidity 0–95% noncondensing.
2 Two-pole DC interrupting ratings based on two poles connected in series. Not UL listed.
3 62.5 Vac interrupting rating is 3800 AIC 10–50A and 2500 AIC 55–100A continuous.
Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA.
For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
For Type WMZ circuit breakers, see Pages V4-T1-67 to V4-T1-81.
For Types WMZS and SPHM supplementary protectors, see Pages V4-T1-103 to V4-T1-118.
.

1
1
1
1
1
1
1
1
1
1
V4-T1-4

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Contents

QUICKLAG Type HQP Single-Pole

Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Special Application Breakers, Types HQP, BA, QC . . . .

Page

1

V4-T1-2

1

V4-T1-6
V4-T1-7

1

V4-T1-8
V4-T1-11
V4-T1-14
V4-T1-17
V4-T1-20

1
1
1
1

V4-T1-24

1

V4-T1-28

1

V4-T1-31

1

V4-T1-34
V4-T1-37
V4-T1-40

1
1
1

QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW

1

Product Description

1

●

●

All products 15–100A are
HACR rated
Switching duty rated for
120 Vac fluorescent light
applications

Standards and Certifications
●
●

Built and listed to UL 489
All products UL and
CSA® listed

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-5

1.1
1
1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Product Selection

QUICKLAG Type HQP
Single-Pole

QUICKLAG Type: HQP 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C

1

Single-Pole

Two-Pole

Two-Pole

120/240 Vac

120/240 Vac

240 Vac

Three-Pole
240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

10

HQP1010

HQP2010

—

HQP3010H 3

1

15

HQP1015 12

HQP2015

HQP2015H

HQP3015H

20

HQP1020 12

HQP2020

HQP2020H

HQP3020H

1

25

HQP1025

HQP2025

HQP2025H

HQP3025H

30

HQP1030

HQP2030

HQP2030H

HQP3030H

1

35

HQP1035

HQP2035

HQP2035H

HQP3035H

40

HQP1040

HQP2040

HQP2040H

HQP3040H

1

45

HQP1045

HQP2045

HQP2045H

HQP3045H

50

HQP1050

HQP2050

HQP2050H

HQP3050H

1

55

HQP1055

HQP2055

HQP2055H

HQP3055H

60

HQP1060

HQP2060

HQP2060H

HQP3060H

1

70

HQP1070

HQP2070

HQP2070H

HQP3070H

80

—

HQP2080

HQP2080H

HQP3080H

1

90

—

HQP2090

HQP2090H

HQP3090H

100

HQP1100

HQP2100

HQP2100H

HQP3100H

1

110

—

HQP2110

—

—

125

—

HQP2125

—

—

1

150

—

HQP2150

—

—

Three-Pole

1

QUICKLAG Type: HQP Non-Automatic Switches

1

Continuous
Ampere Rating
at 40°C

1
1

Single-Pole

Two-Pole

Two-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

50

HQP1050N

—

HQP2050N

HQP3050N

60

HQP1060N

—

HQP2060N

HQP3060N

100

HQP1100N

—

HQP2100N

HQP3100N

1
QUICKLAG Type: QPHW 22,000A Interrupting Capacity Thermal-Magnetic Breakers

1

Single-Pole

Two-Pole

Two-Pole

120/240 Vac

120/240 Vac

240 Vac

Three-Pole
240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number
QPHW3015H

1

Continuous
Ampere Rating
at 40°C

1

15

QPHW1015 1

QPHW2015

QPHW2015H

20

QPHW1020 1

QPHW2020

QPHW2020H

QPHW3020H

25

QPHW1025

QPHW2025

QPHW2025H

QPHW3025H

1
1
1
1
1
1
1
1

30

QPHW1030

QPHW2030

QPHW2030H

QPHW3030H

35

QPHW1035

QPHW2035

QPHW2035H

QPHW3035H

40

QPHW1040

QPHW2040

QPHW2040H

QPHW3040H

45

QPHW1045

QPHW2045

QPHW2045H

QPHW3045H

50

QPHW1050

QPHW2050

QPHW2050H

QPHW3050H

55

QPHW1055

QPHW2055

QPHW2055H

QPHW3055H

60

QPHW1060

QPHW2060

QPHW2060H

QPHW3060H

70

QPHW1070

QPHW2070

QPHW2070H

QPHW3070H

80

—

QPHW2080

QPHW2080H

QPHW3080H

90

—

QPHW2090

QPHW2090H

QPHW3090H

100

—

QPHW2100

QPHW2100H

QPHW3100H

110

—

QPHW2110

—

—

125

—

QPHW2125

—

—

Notes
1 Switching duty rated for 120 Vac fluorescent light applications.
2 For special low-magnetic breaker, order HQP1015L1 or HQP1020L1.
3 Not UL listed.

1
V4-T1-6

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

QUICKLAG Type: QHPX 42,000A Interrupting Capacity Thermal-Magnetic Breakers
Single-Pole

Continuous
Ampere Rating
at 40°C

Two-Pole

Two-Pole

1

Three-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

15

QHPX1015

1

QHPX2015

—

QHPX3015H

20

QHPX1020 1

QHPX2020

—

QHPX3020H

25

QHPX1025

QHPX2025

—

QHPX3025H

30

QHPX1030

QHPX2030

—

QHPX3030H

35

QHPX1035

QHPX2035

—

QHPX3035H

40

QHPX1040

QHPX2040

—

QHPX3040H

45

QHPX1045

QHPX2045

—

QHPX3045H

50

QHPX1050

QHPX2050

—

QHPX3050H

55

QHPX1055

QHPX2055

—

QHPX3055H

60

QHPX1060

QHPX2060

—

QHPX3060H

70

QHPX1070

QHPX2070

—

QHPX3070H

80

—

QHPX2080

—

QHPX3080H

90

—

QHPX2090

—

QHPX3090H

100

—

QHPX2100

—

QHPX3100H

1
1
1
1
1
1
1
1
1

QUICKLAG Type: QHPW 65,000A Interrupting Capacity Thermal-Magnetic Breakers
Single-Pole

Two-Pole

Two-Pole

Three-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

QHPW2015

—

QHPW3015H

—

QHPW3020H

Continuous
Ampere Rating
at 40°C

Catalog Number

15

QHPW1015 1

20

QHPW1020 1

QHPW2020

25

QHPW1025

QHPW2025

—

—

30

QHPW1030

QHPW2030

—

—

1
1
1
1
1
1

Dimensions
Approximate Dimensions in Inches (mm)

1

Shipping Data
Number
of Poles

Carton
Quantity

Approximate
Weight Lbs (kg)

Dimensions

1

24

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

2

12

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

3

8

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

1
1
1
1

Note
1 Switching duty rated for 120 Vac fluorescent light applications.

1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-7

1.1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Contents

QUICKLAG Type QPGF Single-Pole
Ground Fault Circuit Breaker

Description

1

Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Special Application Breakers, Types HQP, BA, QC . . .

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

QUICKLAG Plug-On Ground Fault and Equipment Protectors,
Types QPGF, QPHGF, QPGFEP, QPHGFEP
Product Description

Standards and Certifications
●

QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
●
5 mA trip sensitivity
QUICKLAG Ground Fault
Equipment Protectors
●
30 mA trip sensitivity

1

Built and listed to UL 489

QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
●
Built and tested to UL 943
QUICKLAG Ground Fault
Equipment Protectors
●
Built and listed to UL 1053

1
1
1
1
1
1
1
1
1
1
V4-T1-8

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Page
V4-T1-2
V4-T1-5

V4-T1-9
V4-T1-10
V4-T1-10
V4-T1-11
V4-T1-14
V4-T1-17
V4-T1-20
V4-T1-24
V4-T1-28
V4-T1-31
V4-T1-34
V4-T1-37
V4-T1-40

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Product Selection

QUICKLAG Type QPGF
Single-Pole

1
1

Ground Fault Circuit Breakers—5 mA Sensitivity QUICKLAG Type:
QPGF 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Single-Pole

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

15

QPGF1015

QPGF2015

20

QPGF1020

QPGF2020

25

QPGF1025

QPGF2025

30

QPGF1030

QPGF2030

40

QPGF1040

QPGF2040

50

—

QPGF2050

Continuous
Ampere Rating
at 40°C

1
1
1
1
1
1
1

QUICKLAG Type: QPHGF 22,000A Interrupting Capacity
Thermal-Magnetic Breakers
Single-Pole

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

15

QPHGF1015

QPHGF2015

20

QPHGF1020

QPHGF2020

25

QPHGF1025

QPHGF2025

30

QPHGF1030

QPHGF2030

Continuous
Ampere Rating
at 40°C

1
1
1
1
1
1

Ground Fault Equipment Breakers—30 mA Sensitivity QUICKLAG Type:
QPGFEP 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C

Single-Pole

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

15

QPGFEP1015

QPGFEP2015

20

QPGFEP1020

QPGFEP2020

25

QPGFEP1025

QPGFEP2025

30

QPGFEP1030

QPGFEP2030

40

QPGFEP1040

QPGFEP2040

50

—

QPGFEP2050

1
1
1
1
1
1
1

QUICKLAG Type: QPHGFEP 22,000A Interrupting Capacity
Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C

Single-Pole

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

15

QPHGFEP1015

QPHGFEP2015

20

QPHGFEP1020

QPHGFEP2020

25

QPHGFEP1025

QPHGFEP2025

30

QPHGFEP1030

QPHGFEP2030

1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-9

1.1
1
1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Special Application Ground Fault Circuit Protectors—5 mA Sensitivity
QUICKLAG Type: QPGF 10,000A Interrupting Capacity with Bell Alarm (W1) or
Auxiliary Switch (W2)
Continuous
Ampere Rating
at 40°C

Single-Pole

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

1

15

QPGF1015W1

QPGF2015W1

20

QPGF1020W1

QPGF2020W1

1

25

QPGF1025W1

QPGF2025W1

30

QPGF1030W1

QPGF2030W1

1

40

—

QPGF2040W1

50

—

QPGF2050W1

1

15

QPGF1015W2

—

20

QPGF1020W2

—

1

25

QPGF1025W2

—

30

QPGF1030W2

—

1
1
1
1

Special Application Ground Fault Circuit Protectors—30 mA Sensitivity
QUICKLAG Type: QPGFEP 10,000A Interrupting Capacity with Bell Alarm (W1) or
Auxiliary Switch (W2)
Continuous
Ampere Rating
at 40°C

Single-Pole

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

1

15

QPGFEP1015W1

QPGFEP2015W1

20

QPGFEP1020W1

QPGFEP2020W1

1

25

QPGFEP1025W1

QPGFEP2025W1

30

QPGFEP1030W1

QPGFEP2030W1

1

40

—

QPGFEP2040W1

1
1

50

—

QPGFEP2050W1

15

QPGFEP1015W2

—

20

QPGFEP1020W2

—

25

QPGFEP1025W2

—

30

QPGFEP1030W2

—

1
1

Wiring Diagram

1

Bell Alarm and Auxiliary Contact Schematic
Blue

1

Ground
Fault
Breaker

1
1
1
1

Blue Wire
NC

Red

Dimensions
Approximate Dimensions in Inches (mm)

1

Shipping Data

1
1

Red Wire

Single-throw double-pole contacts are UL and CSA listed for 5A at 250 Vac.
Bell Alarm (W1)—contacts change state when breaker trips.
Auxiliary Switch (W2)—contacts change state when breaker is opened (or tripped) or closed.
14-inch (355.6 mm) long 18 AWG pigtail wire leads provided.

1
1

Black Wire

NO

Number
of Poles

Carton
Quantity

Approximate
Weight Lbs (kg)

1

24

11.00 (5.0)

12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)

2

5

5.00 (2.3)

15.50 x 6.00 x 4.50 (393.7 x 152.4 x 114.3)

Dimensions

Note
Shipped individually or in carton quantities.

V4-T1-10

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Contents

QUICKLAG Type BAB Single-Pole

Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Bolt-On Types BAB, QBHW, HBAX, HBAW
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Special Application Breakers, Types HQP, BA, QC . . . .

Page
V4-T1-2
V4-T1-5
V4-T1-8
V4-T1-12
V4-T1-13
V4-T1-14
V4-T1-17
V4-T1-20

1
1
1
1
1
1
1

V4-T1-24

1

V4-T1-28

1

V4-T1-31

1

V4-T1-34
V4-T1-37
V4-T1-40

1
1
1

Bolt-On Types BAB, QBHW, HBAX, HBAW

1

Product Description

1

●

●

All products 15–100A are
HACR rated
Switching duty rated
for 120 Vac fluorescent
light applications

Standards and Certifications
●
●

Built and listed to UL 489
All products UL and
CSA listed

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-11

1.1
1
1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Product Selection

QUICKLAG Type BAB
Single-Pole

QUICKLAG Type: BA 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Single-Pole

Two-Pole

Two-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

10

BAB1010

BAB2010

BAB2010H 3

BAB3010H 3

15

BAB1015 12

BAB2015

BAB2015H

BAB3015H

20

BAB1020 12

BAB2020

BAB2020H

BAB3020H

1

25

BAB1025

BAB2025

BAB2025H

BAB3025H

30

BAB1030

BAB2030

BAB2030H

BAB3030H

1

35

BAB1035

BAB2035

BAB2035H

BAB3035H

40

BAB1040

BAB2040

BAB2040H

BAB3040H

45

BAB1045

BAB2045

BAB2045H

BAB3045H

Continuous
Ampere Rating
at 40°C

1
1

1
1
1
1
1
1

Three-Pole

50

BAB1050

BAB2050

BAB2050H

BAB3050H

55

BAB1055

BAB2055

BAB2055H

BAB3055H

60

BAB1060

BAB2060

BAB2060H

BAB3060H

70

BAB1070

BAB2070

BAB2070H

BAB3070H

80

—

BAB2080

BAB2080H

BAB3080H

90

—

BAB2090

BAB2090H

BAB3090H

100

BAB1100

BAB2100

BAB2100H

BAB3100H

110

—

BAB2110

—

—

125

—

BAB2125

—

—

Three-Pole

QUICKLAG Type: BA Non-Automatic Switches

1

Single-Pole

Two-Pole

Two-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number
BAB3050N

1

Continuous
Ampere Rating
at 40°C

1

50

BAB1050N

—

BAB2050N

60

BAB1060N

—

BAB2060N

BAB3060N

100

BAB1100N

—

BAB2100N

BAB3100N

1
1

QUICKLAG Type: QBHW 22,000A Interrupting Capacity Thermal-Magnetic Breakers

1

Continuous
Ampere Rating
at 40°C

1

Single-Pole

Two-Pole

Two-Pole

120/240 Vac

120/240 Vac

240 Vac

Three-Pole
240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

15

QBHW1015 1

QBHW2015

QBHW2015H

QBHW3015H

1

20

QBHW1020 1

QBHW2020

QBHW2020H

QBHW3020H

25

QBHW1025

QBHW2025

QBHW2025H

QBHW3025H

1

30

QBHW1030

QBHW2030

QBHW2030H

QBHW3030H

35

QBHW1035

QBHW2035

QBHW2035H

QBHW3035H

1

40

QBHW1040

QBHW2040

QBHW2040H

QBHW3040H

45

QBHW1045

QBHW2045

QBHW2045H

QBHW3045H

1

50

QBHW1050

QBHW2050

QBHW2050H

QBHW3050H

55

QBHW1055

QBHW2055

QBHW2055H

QBHW3055H

1

60

QBHW1060

QBHW2060

QBHW2060H

QBHW3060H

70

QBHW1070

QBHW2070

QBHW2070H

QBHW3070H

80

—

QBHW2080

QBHW2080H

QBHW3080H

1
1
1

90

—

QBHW2090

QBHW2090H

QBHW3090H

100

—

QBHW2100

QBHW2100H

QBHW3100H

110

—

QBHW2110

—

—

125

—

QBHW2125

—

—

Notes
1 Switching duty rated for 120 Vac fluorescent light applications.
2 For special low-magnetic breaker, order BAB1015L1 or BAB1020L1.
3 Not UL listed.

1
1
V4-T1-12

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

QUICKLAG Type: HBAX 42,000A Interrupting Capacity Thermal-Magnetic Breakers
Single-Pole

Two-Pole

Two-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

15

HBAX1015

1

HBAX2015

—

HBAX3015H

20

HBAX1020 1

HBAX2020

—

HBAX3020H

25

HBAX1025

HBAX2025

—

HBAX3025H

30

HBAX1030

HBAX2030

—

HBAX3030H

35

HBAX1035

HBAX2035

—

HBAX3035H

40

HBAX1040

HBAX2040

—

HBAX3040H

45

HBAX1045

HBAX2045

—

HBAX3045H

50

HBAX1050

HBAX2050

—

HBAX3050H

55

HBAX1055

HBAX2055

—

HBAX3055H

60

HBAX1060

HBAX2060

—

HBAX3060H

70

HBAX1070

HBAX2070

—

HBAX3070H

80

—

HBAX2080

—

HBAX3080H

80

—

HBAX2080

—

HBAX3080H

90

—

HBAX2090

—

HBAX3090H

100

—

HBAX2100

—

HBAX3100H

Continuous
Ampere Rating
at 40°C

1

Three-Pole

1
1
1
1
1
1
1
1
1
1
1

QUICKLAG Type: HBAW 65,000A Interrupting Capacity Thermal-Magnetic Breakers
Single-Pole

Two-Pole

Two-Pole

Three-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

HBAW1015 1

HBAW2015

—

HBAW3015H

HBAW1020 1

HBAW2020

—

HBAW3020H

25

HBAW1025

HBAW2025

—

—

30

HBAW1030

HBAW2030

—

—

Continuous
Ampere Rating
at 40°C
15
20

1
1
1
1
1
1

Dimensions
Approximate Dimensions in Inches (mm)

1

Shipping Data
Number
of Poles

Carton
Quantity

Approximate
Weight Lbs (kg)

Dimensions

1

24

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

2

12

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

3

8

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

1
1
1
1

Note
1 Switching duty rated for 120 Vac fluorescent light applications.

1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-13

1.1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Bolt-On Arc Fault Circuit Interrupter QUICKLAG Types QBAF, QBCAF

Contents
Description

1

Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Special Application Breakers, Types HQP, BA, QC . . .

1
1
1
1
1
1
1
1
1
1
1
1

Bolt-On Arc Fault Circuit Interrupter Types QBAF, QBCAF

1

Product Description
●

All products HACR rated

1

Features, Benefits and
Functions
●

1

●
●

1

●

10 and 22 kAIC rating at
120V and 120/240V
Single-pole AFCI
HID ratings for HID (High
Intensity Discharge) lighting
All models are HACR rated

Standards and Certifications
●
●

Built and listed to UL 489
UL File E7819 for QBAF

1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-14

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Page
V4-T1-2
V4-T1-5
V4-T1-8
V4-T1-11

V4-T1-15
V4-T1-16
V4-T1-17
V4-T1-20
V4-T1-24
V4-T1-28
V4-T1-31
V4-T1-34
V4-T1-37
V4-T1-40

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Product Selection

1

QBCAF and QBAF Type AFCIs
Effective immediately, Eaton
AFCIs are available for use in
Sumter panels with a 22 kAIC
rating. This higher rated
breaker will allow us to
win jobs where AFCIs are
specified at higher than
10 kAIC. This breaker
provides standard thermal-

QBHCAF

magnetic protection of
branch circuits. This product
will have the same form, fit
and function of the current
bolt-on AFCI (QBCAF and
QBAF Type). Product scope is
below. These breakers are in
Bid Manager™ for Pow-RLine 1a, Pow-R-Line 1a-LX,

1

Pow-R-Line 3a and Pow-RLine 4a panelboards. For
series rated combinations,
continue to use the less
expensive 10 kAIC QBCAF
and QBAF offerings.

1
1
1

Breakers can also be ordered
from Vista.

1
1

1-Inch (25.4 mm) Wide Bolt-On Arc Fault Circuit Interrupter
Poles

kAIC
Rating

Ampere
Rating

Configuration

Catalog Number

15

Combination AFCI

QBCAF1015

20

Combination AFCI

QBCAF1020

15

Combination AFCI

QBHCAF1015

20

Combination AFCI

QBHCAF1020

15

Branch Feeder AFCI

QBAF1015

20

Branch Feeder AFCI

QBAF1020

15

Branch Feeder AFCI

QBHAF1015

20

Branch Feeder AFCI

QBHAF1020

1
1

Type QBCAF Combination AFCI
Single-pole

10 kAIC

22 kAIC

1
1
1

Type QBAF Branch Feeder AFCI
Single-pole

10 kAIC

22 kAIC

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-15

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1

Wiring Diagrams

1

Single-Pole 120V Load Application
Sourced by 120/240 Vac

1
1

120/240 Vac
Source
N A B
Line B

1
1
1

Single-Pole
Neutral
120V
Duplex
Receptacle

Neutral

1

Equipment Ground

1
1
1
1

Single-Pole Shared Neutral with
Multi-Duplex Receptacle Application
120/240 Vac
Source
N A B

1

Line B

1

Two-Pole

1
1

Neutral
Neutral

1

Two 120V
Duplex
Receptacles

Line A

1

Equipment Ground

1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-16

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Contents

QUICKLAG Type QBGF Single-Pole
Ground Fault Circuit Breaker

Description
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Special Application Breakers, Types HQP, BA, QC . . . .

Page

1

V4-T1-5

1

V4-T1-8
V4-T1-11

1

V4-T1-14

1
1

V4-T1-18
V4-T1-19
V4-T1-19
V4-T1-20

1
1

V4-T1-24

1

V4-T1-28

1

V4-T1-31

1

V4-T1-34
V4-T1-37
V4-T1-40

1
1
1
1

Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP
Product Description

Built and tested to UL 489

1

QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
●
Built and tested to UL 943

1

QUICKLAG Ground Fault
Equipment Protectors
●
Built and tested to UL 1053

1

●

QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
●
5 mA trip sensitivity
QUICKLAG Ground Fault
Equipment
Protectors
●
30 mA trip sensitivity

1

Standards and Certifications

1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-17

1.1
1
1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Product Selection

QUICKLAG Type QBGF
Single-Pole

Ground Fault Circuit Breakers—5 mA Sensitivity QUICKLAG Type:
QBGF 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C

1
1

Single-Pole

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

15

QBGF1015

QBGF2015

20

QBGF1020

QBGF2020

25

QBGF1025

QBGF2025

1

30

QBGF1030

QBGF2030

40

QBGF1040

QBGF2040

1

50

—

QBGF2050

1

1

QUICKLAG Type: QBHGF 22,000A Interrupting Capacity
Thermal-Magnetic Breakers

1

Continuous
Ampere Rating
at 40°C

1
1
1
1
1

Single-Pole

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

15

QBHGF1015

QBHGF2015

20

QBHGF1020

QBHGF2020

25

QBHGF1025

QBHGF2025

30

QBHGF1030

QBHGF2030

Ground Fault Equipment Breakers—30 mA Sensitivity QUICKLAG Type:
QBGFEP 10,000A Interrupting Capacity Thermal-Magnetic Breakers

1

Continuous
Ampere Rating
at 40°C

1

Single-Pole

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

1

15

QBGFEP1015

QBGFEP2015

20

QBGFEP1020

QBGFEP2020

1

25

QBGFEP1025

QBGFEP2025

30

QBGFEP1030

QBGFEP2030

40

QBGFEP1040

QBGFEP2040

50

—

QBGFEP2050

1
1
1

QUICKLAG Type: QBHGFEP 22,000A Interrupting Capacity
Thermal-Magnetic Breakers

1

Continuous
Ampere Rating
at 40°C

1

Single-Pole

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

1

15

QBHGFEP1015

QBHGFEP2015

20

QBHGFEP1020

QBHGFEP2020

1

25

QBHGFEP1025

QBHGFEP2025

30

QBHGFEP1030

QBHGFEP2030

1
1
1
1
V4-T1-18

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Special Application Ground Fault Circuit Protectors—5 mA Sensitivity QUICKLAG Type:
QBGF 10,000A Interrupting Capacity with Bell Alarm (W1) or Auxiliary Switch (W2)
Single-Pole

Continuous
Ampere Rating
at 40°C

1

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

15

QBGF1015W1

QBGF2015W1

20

QBGF1020W1

QBGF2020W1

25

QBGF1025W1

QBGF2025W1

30

QBGF1030W1

QBGF2030W1

40

—

QBGF2040W1

50

—

QBGF2050W1

15

QBGF1015W2

—

20

QBGF1020W2

—

25

QBGF1025W2

—

30

QBGF1030W2

—

1
1
1
1
1
1
1
1

Special Application Ground Fault Circuit Protectors—30 mA Sensitivity QUICKLAG Type:
QBGFEP 10,000A Interrupting Capacity with Bell Alarm (W1) or Auxiliary Switch (W2)
Single-Pole

Continuous
Ampere Rating
at 40°C

1

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

15

QBGFEP1015W1

QBGFEP2015W1

20

QBGFEP1020W1

QBGFEP2020W1

25

QBGFEP1025W1

QBGFEP2025W1

30

QBGFEP1030W1

QBGFEP2030W1

40

—

QBGFEP2040W1

50

—

QBGFEP2050W1

15

QBGFEP1015W2

—

20

QBGFEP1020W2

—

25

QBGFEP1025W2

—

30

QBGFEP1030W2

—

1
1
1
1
1
1
1

Wiring Diagram

1

Bell Alarm and Auxiliary Contact Schematic

1

Blue
Ground
Fault
Breaker

Red

1

Blue Wire
NC

Black Wire

1

NO
Red Wire

1

Single-throw double-pole contacts are UL and CSA listed for 5A at 250 Vac.
Bell Alarm (W1)—contacts change state when breaker trips.
Auxiliary Switch (W2)—contacts change state when breaker is opened (or tripped) or closed.
14-inch (355.6 mm) long 18 AWG pigtail wire leads provided.

1
1

Dimensions

1

Approximate Dimensions in Inches (mm)

1

Shipping Data
Number of Poles

Approximate Weight Lbs (kg)

Dimensions

1

11.00 (5.0)

12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)

2

5.00 (2.3)

15.50 x 6.00 x 4.50 (393.7 x 152.4 x 114.3)

1
1

Note
Shipped individually or in carton quantities.

1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-19

1.1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Contents

QUICKLAG Type QC Single-Pole

Description

1

Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Special Application Breakers, Types HQP, BA, QC . . .

1
1
1
1
1
1
1
1
1
1
1
1

Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW

1

Product Description

1
1

●

●

All products 10–100A are
HACR rated
Switching duty rated for
120 Vac fluorescent light
applications only

Standards and Certifications
●
●

Built and listed to UL 489
All products UL and
CSA listed

1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-20

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Page
V4-T1-2
V4-T1-5
V4-T1-8
V4-T1-11
V4-T1-14
V4-T1-17

V4-T1-21
V4-T1-23
V4-T1-24
V4-T1-28
V4-T1-31
V4-T1-34
V4-T1-37
V4-T1-40

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Product Selection

QUICKLAG
Type QC Single-Pole

1
1

QUICKLAG Type: QC 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C

Single-Pole

Two-Pole

Two-Pole

Three-Pole

Four-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

240 Vac

1

Catalog Number

Catalog Number

Catalog Number

Catalog Number

Catalog Number

5

QC1005 1

QC2005 1

—

—

—

10

QC1010

QC2010

QC2010H 1

QC3010H 1

—

15

QC1015 2

QC2015

QC2015H

QC3015H

QC4015H

20

QC1020 2

QC2020

QC2020H

QC3020H

QC4020H

25

QC1025

QC2025

QC2025H

QC3025H

QC4025H

30

QC1030

QC2030

QC2030H

QC3030H

QC4030H

35

QC1035

QC2035

QC2035H

QC3035H

QC4035H

40

QC1040

QC2040

QC2040H

QC3040H

QC4040H

45

QC1045

QC2045

QC2045H

QC3045H

QC4045H

50

QC1050

QC2050

QC2050H

QC3050H

QC4050H

55

QC1055

QC2055

QC2055H

QC3055H

QC4055H

60

QC1060

QC2060

QC2060H

QC3060H

QC4060H

70

QC1070

QC2070

QC2070H

QC3070H

QC4070H

70

—

QC2080

QC2080H

QC3080H

QC4080H

90

—

QC2090

QC2090H

QC3090H

QC4090H

100

QC1100

QC2100

QC2100H

QC3100H

QC4100H

1
1
1
1
1
1
1
1
1
1
1

QUICKLAG Type: QC Non-Automatic Switches

1

Continuous
Ampere Rating
at 40°C

Single-Pole

Two-Pole

Two-Pole

Three-Pole

Four-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

Catalog Number

50

QC1050N

—

QC2050N

QC3050N

—

60

QC1060N

—

QC2060N

QC3060N

—

100

QC1100N

—

QC2100N

QC3100N

—

1
1
1

Notes
1 Not UL listed.
2 Switching duty rated for 120 Vac fluorescent light applications only.

1
1

For special low-magnetic breaker, order QC1015L1 or QC1020L1.Non-automatic switches, see Page V4-T1-42.

1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-21

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

QUICKLAG Type: QCHW 22,000A Interrupting Capacity Thermal-Magnetic Breakers

1

Single-Pole

Two-Pole

Two-Pole

Three-Pole

1

Continuous
Ampere Rating
at 40°C

120/240 Vac

120/240 Vac

240 Vac

240 Vac

Four-Pole
240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

Catalog Number

1

15

QCHW1015 1

QCHW2015

QCHW2015H

QCHW3015H

QCHW4015H

1

20

QCHW1020 1

QCHW2020

QCHW2020H

QCHW3020H

QCHW4020H

25

QCHW1025

QCHW2025

QCHW2025H

QCHW3025H

QCHW4025H

1

30

QCHW1030

QCHW2030

QCHW2030H

QCHW3030H

QCHW4030H

35

QCHW1035

QCHW2035

QCHW2035H

QCHW3035H

QCHW4035H

1

40

QCHW1040

QCHW2040

QCHW2040H

QCHW3040H

QCHW4040H

45

QCHW1045

QCHW2045

QCHW2045H

QCHW3045H

QCHW4045H

1
1
1
1
1

50

QCHW1050

QCHW2050

QCHW2050H

QCHW3050H

QCHW4050H

55

QCHW1055

QCHW2055

QCHW2055H

QCHW3055H

QCHW4055H

60

QCHW1060

QCHW2060

QCHW2060H

QCHW3060H

QCHW4060H

70

QCHW1070

QCHW2070

QCHW2070H

QCHW3070H

QCHW4070H

70

—

QCHW2080

QCHW2080H

QCHW3080H

QCHW4080H

90

—

QCHW2090

QCHW2090H

QCHW3090H

QCHW4090H

100

—

QCHW2100

QCHW2100H

QCHW3100H

QCHW4100H

1

QUICKLAG Type: QHCX 42,000A Interrupting Capacity Thermal-Magnetic Breakers

1

Continuous
Ampere Rating
at 40°C

Single-Pole

Two-Pole

Two-Pole

Three-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

Catalog Number

15

QHCX1015 1

QHCX2015

—

QHCX3015H

—

1

20

QHCX1020

1

QHCX2020

—

QHCX3020H

—

25

QHCX1025

QHCX2025

—

QHCX3025H

—

1

30

QHCX1030

QHCX2030

—

QHCX3030H

—

1

35

QHCX1035

QHCX2035

—

QHCX3035H

—

40

QHCX1040

QHCX2040

—

QHCX3040H

—

1

45

QHCX1045

QHCX2045

—

QHCX3045H

—

50

QHCX1050

QHCX2050

—

QHCX3050H

—

1

55

QHCX1055

QHCX2055

—

QHCX3055H

—

60

QHCX1060

QHCX2060

—

QHCX3060H

—

1

70

QHCX1070

QHCX2070

—

QHCX3070H

—

1

70

—

QHCX2080

—

QHCX3080H

—

90

—

QHCX2090

—

QHCX3090H

—

100

—

QHCX2100

—

QHCX3100H

—

1

1
1

Four-Pole

QUICKLAG Type: QHCW 65,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C

Single-Pole

Two-Pole

Two-Pole

Three-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

Catalog Number

15

QHCW1015 1

QHCW2015

—

QHCW3015H

—

1

20

QHCW1020 1

QHCW2020

—

QHCW3020H

—

1

25

QHCW1025

QHCW2025

—

—

—

30

QHCW1030

QHCW2030

—

—

—

1
1

1

Notes
1 Switching duty rated for 120 Vac fluorescent light applications only.

1

Non-automatic switches, see Page V4-T1-42.

1
V4-T1-22

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Four-Pole

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

QUICKLAG Type QCD Miniature Circuit Breakers
●
Flexible power feed
QCD breakers are used
primarily in HVAC and
connection:
industrial applications.
wire size, position
●
●
Single-, two- and
Same breaker size for
three-pole options
entire rating range
●
●
Modular construction
Field mountable
accessories:
●
DIN mounted
finger shroud proof, quick
(symmetrical rail 35 x
connect terminals
7.5 DIN/EN 50 022)
●
Other accessories:
●
QCD same profile as
jumper unit
Type QCR

QUICKLAG Type QCD
Miniature Circuit
Breaker

1
1
1
1
1
1
1

QUICKLAG Type QCD 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C

Single-Pole

Two-Pole

Two-Pole

Three-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

10

QCD1010

QCD2010

—

—

15

QCD1015

QCD2015

QCD2015H

QCD3015H

20

QCD1020

QCD2020

QCD2020H

QCD3020H

25

QCD1025

QCD2025

QCD2025H

QCD3025H

30

QCD1030

QCD2030

QCD2030H

QCD3030H

35

QCD1035

QCD2035

QCD2035H

QCD3035H

40

QCD1040

QCD2040

QCD2040H

QCD3040H

45

QCD1045

QCD2045

QCD2045H

QCD3045H

50

QCD1050

QCD2050

QCD2050H

QCD3050H

55

QCD1055

QCD2055

QCD2055H

QCD3055H

60

QCD1060

QCD2060

QCD2060H

QCD3060H

70

—

QCD2070

QCD2070H

QCD3070H

80

—

QCD2080

QCD2080H

QCD3080H

90

—

QCD2090

QCD2090H

QCD3090H

100

—

QCD2090

QCD2090H

QCD3100H

—

QCD2100

QCD2100H

—

1
1
1
1
1
1
1
1
1
1
1
1
1

QUICKLAG Type QCD Non-Automatic Switches
Continuous
Ampere Rating
at 40°C

Single-Pole

Two-Pole

Two-Pole

Three-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

60

—

—

QCD2060NA

—

100

—

—

—

—

1
1
1
1

Dimensions
Approximate Dimensions in Inches (mm)

1

Shipping Data
Number
of Poles

Carton
Quantity

1

Approximate
Weight Lbs (kg)

Dimensions

1

24

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

2

12

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

3

8

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-23

1.1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Contents

Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF, QCRH, QCFH

Description

1
1
1
1
1

Single-Pole

Two-Pole

QCR (Rear-Mounted Breakers)

Single-Pole

Two-Pole

QCF (Front-Mounted Breakers)

1
1
1
1
1
1

Page

Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
QCR and QCF Options and Accessories . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Special Application Breakers, Types HQP, BA, QC . . .

V4-T1-2
V4-T1-5
V4-T1-8
V4-T1-11
V4-T1-14
V4-T1-17
V4-T1-20

V4-T1-25
V4-T1-27
V4-T1-28
V4-T1-31
V4-T1-34
V4-T1-37
V4-T1-40

1
1

Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF, QCRH, QCFH

1

Product Description

Application Description

Eaton Type QCR circuit
breakers have as a standard
feature provisions for 35 mm
DIN rail rear mounting with
a spring-loaded release.
Optional clips for individual
mounting are available as a
separate accessory.

QCR and QCF circuit breakers
are only 1/2-inch (12.7 mm)
wide per pole and are
excellent for general purpose
industrial applications where
space savings is required.

1
1
1
1
1
1
1
1

Type QCF have two threaded
steel inserts to facilitate front
mounting with #6–32 steel
screws. The clamp type
terminals are accessible from
the rear of the breaker so that
cables can be accessed
without removal of the
breaker from the front cover.

Features, Benefits
and Functions
●

●
●

●

●

1/2-inch (12.7 mm) wide
per pole
Cable-in/cable-out
Black cases with black
handles
Three position handle:
ON, Tripped (center), OFF
Thermal-magnetic
protection

1
1
1
1
1
1
1
V4-T1-24

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Standards and Certifications
●
●
●
●

●

Built and listed to UL 489
UL File No. E7819
CSA File No. LR48907
Type QCR and QCF circuit
breakers are UL listed
circuit breakers that are
suitable for use as branch
circuit protectors
All ratings 15–60A are
HACR rated

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Product Selection

Cable-In/Cable-Out,
1/2-Inch Wide

1
1

QCR Breaker Catalog Numbers 1234
Continuous
Ampere Rating
at 40°C

Three-Pole

1

Catalog Number

Catalog Number

1

Single-Pole

Two-Pole

Two-Pole

120/240 Vac

120/240 Vac

240 Vac 5

Catalog Number

Catalog Number

QCR Breaker 10 kAIC Interrupting Ratings
10

15

20

25

30

QCR1010

QCR2010

—

—

QCR1010T

QCR2010T

—

—

—

QCR2010P

—

—

QCR1015 6

QCR2015

QCR2015H

QCR3015H

QCR1015T 6

QCR2015T

QCR2015HT

QCR3015HT

—

QCR2015P

—

—

QCR1020 6

QCR2020

QCR2020H

QCR3020H

QCR1020T 6

QCR2020T

QCR2020HT

QCR3020HT

—

QCR2020P

—

—

QCR1025

QCR2025

QCR2025H

QCR3025H

QCR1025T

QCR2025T

QCR2025HT

QCR3025HT

—

QCR2025P

—

—

QCR1030

QCR2030

QCR2030H

QCR3030H

QCR1030T

QCR2030T

QCR2030HT

QCR3030HT

—

QCR2030P

—

—

QCR1035

QCR2035

—

—

—

QCR2035P

—

—

QCR1040

QCR2040

—

—

—

QCR2040P

—

—

QCR1045

QCR2045

—

—

—

QCR2045P

—

—

QCR1050

QCR2050

—

—

—

QCR2050P

—

—

55

QCR1055

QCR2055

—

—

—

QCR2055P

—

—

60 7

QCR1060

QCR2060

—

—

—

QCR2060P

—

—

—

—

QCRH2015T

—

—

QCRH2020

—

—

QCRH2020T

—

—

35

40

45

50

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

QCR Breaker 22 kAIC Interrupting Ratings
15

QCRH1015 6
QCRH1015T

20

6

QCRH1020 6
QCRH1020T

6

QCRH2015

1
1
1

Notes
1 Standard breaker terminals are box type lugs.
2 Breakers with T Catalog Number Suffix are suitable for line and load side ring terminal connection
(#10–32 plus/minus terminal screw provided).
3 Breakers with P Catalog Number Suffix are suitable for terminating two 10 AWG Quick-Connect Type Terminals per
phase on breaker load side.
4 Breakers with Shunt Trip (extra pole required on breaker right-hand side) are available on single-, two- and three-pole.
Contact the Customer Support Center at 1-800-356-1243.
5 Breakers with H Catalog Suffix have 240 Vac construction.
6 All 15 and 20A single-pole breakers are SWD (Switching Duty) rated for fluorescent lighting applications.
7 60/75°C Cu/Al wire on all ratings except 60A, which requires Cu only conductor.

1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-25

1.1
1

Cable-In/Cable-Out,
1/2-Inch Wide

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

QCF Breaker Catalog Numbers 123
Single-Pole

Two-Pole

Two-Pole

120/240 Vac

120/240 Vac

240 Vac 4

Catalog Number

Catalog Number

Catalog Number

Catalog Number

1

Continuous
Ampere Rating
at 40°C

1

QCF Breaker 10 kAIC Interrupting Ratings
10

1
1

15

1

20

Three-Pole

QCF1010

QCF2010

—

—

QCF1010T

QCF2010T

—

—

QCF1015 5

QCF2015

QCF2015H

QCF3015H

QCF1015T 5

QCF2015T

QCF2015HT

QCF3015HT

QCF1020 5

QCF2020

QCF2020H

QCF3020H

QCF1020T 5

QCF2020T

QCF2020HT

QCF3020HT

QCF1025

QCF2025

QCF2025H

QCF3025H

QCF1025T

QCF2025T

QCF2025HT

QCF3025HT

QCF2030

QCF2030H

QCF3030H

1

25

1

30

QCF1030

1

QCF1030T

QCF2030T

QCF2030HT

QCF3030HT

35

QCF1035

QCF2035

—

—

1

40

QCF1040

QCF2040

—

—

1

45

QCF1045

QCF2045

—

—

50

QCF1050

QCF2050

—

—

1

55

QCF1055

QCF2055

—

—

60 6

QCF1060

QCF2060

—

—

1

QCF Breaker 22 kAIC Interrupting Ratings
15

1

20

1

QCFH1015 5

QCFH2015

—

—

QCFH1015T 5

QCFH2015T

—

—

QCFH1020 5

QCFH2020

—

—

QCFH2020T

—

—

QCFH1020T

1

5

Notes
1 Standard breaker terminals are box type lugs.
2 Breakers with T Catalog Number Suffix are suitable for line and load side ring terminal connection
(#10–32 plus/minus terminal screw provided).
3 Breakers with Shunt Trip Attachment (extra pole required on breaker right-hand side) are available.
Contact the Customer Support Center.
4 Breakers with H Catalog Suffix have 240 Vac construction.
5 All 15 and 20A single-pole breakers are SWD (Switching Duty) rated for fluorescent lighting applications.
6 60/75°C Cu/Al wire on all ratings except 60A, which requires Cu only conductor.

1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-26

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

QCR and QCF Options and Accessories
QCR and QCF Standard Box
Terminals
Factory-installed line and load
side breaker terminal to
accommodate14 AWG to
4 AWG wire.
Standard Box Terminals

1

QCR and QCF Ring or Spade Lug
Terminals (10 to 30A Ratings
Only)
Factory-installed line and load
side terminals each equipped
with a #10–32 screw suitable
for terminating one 10 AWG
wire with insulated ring or
spade type terminal as shown.
Catalog Suffix “T”

QCR Quick-Connect Terminals
Factory-installed two-prong
quick-connect terminal on
breaker load side suitable for
terminating two 10 AWG wire
with insulated slip-on
terminals as shown. Line side
terminal is the standard type.

Available QCR and QCF
Breaker Accessories

1

Catalog
Number

1

Steel mounting clip
mounts QCR breaker if
individual mounting is
required. Quantity two
required for single- and twopole and four required
for three-pole breakers.

QCRMTGFT

1

Removable padlock
device for single-pole
QCR or QCF breaker.

QCRFPL1P

Removable padlock
device for multi-pole
QCR or QCF breaker.

QCRFPLMP

Padlock bracket assembly for QCR or QCF
single- or multi-pole
breakers (OFF only).

QCRFLOFF

Padlock bracket for
QCR, lock-off only.

QCRPLOFF

Description

1
1
1
1
1
1
1
1

Catalog Suffix “P”

1
1
1
1

Technical Data and Specifications
●

●

●

●

Single-, two- and
three-pole
10 kAIC at 120/240 Vac,
10–60A
22 kAIC at 120/240 Vac,
15–20A
10 kAIC at 240 Vac, 10–30A

●

●

●

3 kAIC at 62.5 Vdc
(single-pole)
3 kAIC at 130 Vdc
(two poles in series)
Normal operating
environment:
●
0–40°C
●
5–95% humidity
(noncondensing)

1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-27

1.1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Contents

QUICKLAG Type QCGF Single-Pole
Ground Fault Circuit Breaker

Description

1

Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Special Application Breakers, Types HQP, BA, QC . . .

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Product Description

Standards and Certifications

QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
●
5 mA trip sensitivity

QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
●
Built and tested to UL 943

QUICKLAG Ground Fault
Equipment Protectors
●
30 mA trip sensitivity

QUICKLAG Ground Fault
Equipment Protectors
●
Built and tested to
UL 1053

1
1
1
1
1
1
1
1
1
1
1
V4-T1-28

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Page
V4-T1-2
V4-T1-5
V4-T1-8
V4-T1-11
V4-T1-14
V4-T1-17
V4-T1-20
V4-T1-24

V4-T1-29
V4-T1-30
V4-T1-30
V4-T1-31
V4-T1-34
V4-T1-37
V4-T1-40

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Product Selection
QUICKLAG Type QCGF
Single-Pole Ground
Fault Circuit Breaker

1
Breaker Catalog Numbers
Continuous
Ampere Rating
at 40°C

Single-Pole

Two-Pole

120 Vac

120/240 Vac

Catalog Number

Catalog Number

1
1
1

Ground Fault Circuit Breakers—5 mA Sensitivity
QUICKLAG Type: QCGF 10,000A Interrupting Capacity Thermal-Magnetic Breakers
15

QCGF1015

QCGF2015

20

QCGF1020

QCGF2020

25

QCGF1025

QCGF2025

30

QCGF1030

QCGF2030

40

QCGF1040

QCGF2040

50

—

QCGF2050

1
1
1
1

QUICKLAG Type: QCHGF 22,000A Interrupting Capacity Thermal-Magnetic Breakers
15

QCHGF1015

QCHGF2015

20

QCHGF1020

QCHGF2020

25

QCHGF1025

QCHGF2025

30

QCHGF1030

QCHGF2030

1
1

Ground Fault Equipment Protectors—30 mA Sensitivity
QUICKLAG Type: QCGFEP 10,000A Interrupting Capacity Thermal-Magnetic Breakers

1

15

QCGFEP1015

QCGFEP2015

20

QCGFEP1020

QCGFEP2020

1

25

QCGFEP1025

QCGFEP2025

30

QCGFEP1030

QCGFEP2030

40

QCGFEP1040

QCGFEP2040

50

—

QCGFEP2050

1
1
1

QUICKLAG Type: QCHGFEP 22,000A Interrupting Capacity Thermal-Magnetic Breakers
15

QCHGFEP1015

QCHGFEP2015

20

QCHGFEP1020

QCHGFEP2020

25

QCHGFEP1025

QCHGFEP2025

30

QCHGFEP1030

QCHGFEP2030

1
1
1

Special Application Ground Fault Circuit Protector—5 mA Sensitivity
QUICKLAG Type: QCGF 10,000A Interrupting Capacity with Bell Alarm (W1) or
Auxiliary Switch (W2)
15

QCGF1015W1

QCGF2015W1

20

QCGF1020W1

QCGF2020W1

25

QCGF1025W1

QCGF2025W1

30

QCGF1030W1

QCGF2030W1

40

—

QCGF2040W1

50

—

QCGF2050W1

15

QCGF1015W2

—

20

QCGF1020W2

—

25

QCGF1025W2

—

30

QCGF1030W2

—

1
1
1
1
1
1

Special Application Ground Fault Equipment Protectors—30 mA Sensitivity
QUICKLAG Type: QCGFEP 10,000A Interrupting Capacity with Bell Alarm (W1) or
Auxiliary Switch (W2)
15

QCGFEP1015W1

QCGFEP2015W1

20

QCGFEP1020W1

QCGFEP2020W1

25

QCGFEP1025W1

QCGFEP2025W1

30

QCGFEP1030W1

QCGFEP2030W1

40

—

QCGFEP2040W1

50

—

QCGFEP2050W1

15

QCGFEP1015W2

—

20

QCGFEP1020W2

—

25

QCGFEP1025W2

—

30

QCGFEP1030W2

—

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1
1
1
1
1
1
V4-T1-29

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1

Wiring Diagram

1

Bell Alarm and Auxiliary Contact Schematic

1

Blue
Ground
Fault
Breaker

1
1
1
1
1

Blue Wire
NC

Red

Black Wire

NO
Red Wire

Single-throw double-pole contacts are UL and CSA listed for 5A at 250 Vac.
Bell Alarm (W1)—contacts change state when breaker trips.
Auxiliary Switch (W2)—contacts change state when breaker is opened (or tripped) or closed.
14-inch (355.6 mm) long 18 AWG pigtail wire leads provided.

Dimensions
Approximate Dimensions in Inches (mm)

1

Shipping Data

1

Number
of Poles

Carton
Quantity

Approximate
Weight Lbs (kg)

Dimensions

1

1

20

11.00 (5.0)

12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)

2

5

5.00 (2.3)

15.50 x 6.00 x 4.50 (393.7 x 152.4 x 114.3)

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-30

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Contents

BABRP and BABRSP Breakers—
Single- and Two-Pole

Description

Page

Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications. . . . . . . . . . . .
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Special Application Breakers, Types HQP, BA, QC . . . .

V4-T1-2
V4-T1-5
V4-T1-8
V4-T1-11

1
1
1
1

V4-T1-14

1

V4-T1-17

1

V4-T1-20
V4-T1-24

1

V4-T1-28

1
1

V4-T1-32
V4-T1-33
V4-T1-33

1

V4-T1-34
V4-T1-37
V4-T1-40

1

1
1
1

Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP
Product Description

Application Description

Features, Benefits and Functions

The BABRP and BABRSP
are bolt-on branch circuit
breakers designed for use in
panelboards. The BRRP is a
plug-on branch circuit breaker
designed for use in loadcenters not manufactured
with breakers with a 1-inch
wide format and are listed on
the “Compatibility list for
Classified Applications”—
Pub. 26271. In addition to
providing conventional branch
circuit protection, they include
a unique solenoid-operated
mechanism that provides for
efficient breaker pulse-on and
pulse-off operation when used
with a suitable controller like
Eaton’s Pow-R-Command™
lighting control system.
These breakers can also be
controlled by pushbutton or
a PLC unit.

Eaton’s BABRP, BABRSP,
BRRP and CLRP breakers are
remotely operated molded
case circuit breakers ideally
suited for lighting control
applications or energy
management applications.

●

●

●

●

●

●

●

●

Bolt-on line-side terminal
(BABRP, BABRSP—
Type BA)
Plug-on line-side terminal
(BRRP—Type BR, CLRP—
Type CL)
Cable connected load-side
terminal
Four-position control
terminal
Bi-metal assembly for
thermal overload
protection
Fast-acting short-circuit
protection
Arc-chute assembly for
fast-acting arc extinction
Three-position handle: OFF,
TRIP (Center), ON

1
●

●
●

●

●
●

●

Handle permits manual
switching when control
power is lost
Mechanical trip indicator
15 and 20A breakers SWD
(switching duty) rated
HID ratings for HID (high
intensity discharge) lighting
All models HACR rated
Status feedback of control
circuit (BABRSP)
Series rated (BABRP,
BABRSP only)
●
BRRP series rated same
as BR breakers
●
BABRP, BABRSP same
as BA breakers

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-31

1.1
1
1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Product Selection

QUICKLAG Type QCGF
Single-Pole Ground
Fault Circuit Breaker

BABRP UL 489 and CSA 22.2 Interrupting
Ratings

BRRP UL 489 and CSA 22.2 Interrupting
Ratings
Interrupting Capacity (Symmetrical Amperes)

Interrupting Capacity (Symmetrical Amperes)

1

Catalog
Number Ampere Vac (50/60 Hz)
120/240 277/480 Number
of Poles Rating 1 120

Number Ampere
of Poles Rating

Vac (50/60 Hz)
120

120/240

Catalog
Number

1

1

1

15

10,000 —

—

BABRP1015

15

10,000

—

BRRP115

20

10,000 —

—

BABRP1020

20

10,000

—

BRRP120

25

10,000 —

—

BABRP1025

25

10,000

—

BRRP125

30

10,000 —

—

BABRP1030

30

10,000

—

BRRP130

15

—

10,000

—

BABRP2015

15

—

10,000

BRRP215

1

20

—

10,000

—

BABRP2020

20

—

10,000

BRRP220

25

—

10,000

—

BABRP2025

25

—

10,000

BRRP225

1

30

—

10,000

—

BABRP2030

30

—

10,000

BRRP230

1
1

2

1

BABRP and BABRSP Wire Harness

1

Catalog
Number

Description

1

This 60-inch (1524.0 mm) wire pigtail provides
SLBKRPTL1
a connection from a single BABRP’s control plug to
a customer’s pushbutton, relay or PLC. Each box
contains 12 pigtails. Wires are 22 AWG, 600V.
Order in multiples of 12.

1

2

CLRP UL 489 and CSA 22.2 Interrupting
Ratings
Interrupting Capacity (Symmetrical Amperes)
Number Ampere
of Poles Rating
1

1
BABRSP UL 489 and CSA 22.2 Interrupting
Ratings

1
1

Interrupting Capacity (Symmetrical Amperes)
Vac (50/60 Hz)

Number Ampere
of Poles Rating 1 120

1

1

Catalog
120/240 277/480 Number

15

10,000 —

—

BABRSP1015

1

20

10,000 —

—

BABRSP1020

1

25

10,000 —

—

BABRSP1025

30

10,000 —

—

BABRSP1030

15

—

10,000

—

BABRSP2015

20

—

10,000

—

BABRSP2020

25

—

10,000

—

BABRSP2025

30

—

10,000

—

BABRSP2030

2

1
1

2

120/240

Catalog
Number

15

10,000

—

CLRP115

20

10,000

—

CLRP120

25

10,000

—

CLRP125

30

10,000

—

CLRP130

15

—

10,000

CLRP215

20

—

10,000

CLRP220

25

—

10,000

CLRP225

30

—

10,000

CLRP230

Note
1 Continuous current rating at 40°C.

1
1
1
1
1
1
1
1
1
V4-T1-32

Vac (50/60 Hz)
120

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Technical Data and Specifications

1
1

Control Circuit for the BABRP and BABRSP
BABRP

BABRSP

Remote
Contact

Remote
Contact
Line

Load
Breaker
Contact
RM
a

1

BKR
a

Red

Black

Off Remote
Coil Status

Blue

Yellow

RM
b

On
Coil

Off Remote
Coil Status

1
1

Blue

RM
a

On
Coil

1

Line

Breaker
Contact
RM
b

1

Yellow

Load

Black

Operation
●
Tripping system—the
BABRP, BABRSP, BRRP
and CLRP circuit breakers
have a permanent trip
unit that contains a factory
preset thermal (overload)
trip element in each pole
●
Operating mechanism—
the BABRP, BABRSP, BRRP
and CLRP circuit breakers
have an over-center toggle
mechanism that provides
quick-make, quick-break
operation. The operating
mechanism is trip free. An
internal cross-bar provides
a common tripping of all
multi-pole circuit breakers

Red

Solenoid Operating Data
●
Power requirements: 24
Vac/dc (20.4V minimum–
30V maximum)
●
Controlled signal:
+AC/DC 8 ms minimum
with zero cross, 300 ms
maximum
●
AC: 1.3 cycles minimum,
18 cycles or 300 ms
maximum
●
DC: 8 ms minimum,
300 ms maximum
●
Maximum duty cycle of
6 OPEN/CLOSE cycles
per minute
●
Current draw: open 1A,
close 3/4A
●
Blue wire: power input
(see power requirements)
●
Black wire: remote opening
●
Red wire: remote closing
●
Yellow wire: feedback
status from power input,
maximum 0.50A draw
(BABRSP only)

Wiring Diagrams

1
1
1

Operating/Application Data
●
Ambient temperature:
0 to 40°C
●
Nominal pulse magnitude:
24 Vac/dc
●
Frequency: 50/60 Hz
●
Maximum breaker cycling:
6 operations per minute
●
Tolerance: +10% to –15%
of nominal voltage
●
Humidity: 0 to 95%
noncondensing

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-33

1.1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Contents

GHBS and GHQRSP

Description

1

Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications . . . . . . . . . . . .
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Special Application Breakers, Types HQP, BA, QC . . .

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Solenoid Operator—Remote-Controlled Latching
for Type GHBS, GBHS and GHQRSP Breakers
Product Description
Eaton’s GHBS, GBHS and
GHQRSP circuit breakers
are bolt-on branch circuit
breakers designed for use
in 277/480 Vac panelboards.
In addition to providing
conventional branch circuit
protection, they include a
unique solenoid-operated
mechanism that provides
for efficient breaker pulse-on
and pulse-off operation
when used with a suitable
controller like Eaton’s
Pow-R-Command lighting
control system.

Features, Benefits
and Functions
●
●

●

●

●

●

●

1

Bolt-on line-side terminal
Cable-connected load-side
terminal
Status switch—remote
status and breaker status
available from internal
auxiliary switches
Bi-metal assembly for
thermal overload
protection
Fast-acting short-circuit
protection
Arc-runner and arc-chute
assembly for fast-acting arc
extinction
Three-position breaker
handle: OFF, TRIP (Center),
ON

●

●

●

●

●
●

Visual indication of the
remotely operated
contact’s position (open,
closed or trip)
Remote override handle
permits manual switching
when control power is lost
15 and 20A breakers SWD
(switching duty) rated.
15 and 20A breakers HID
rated for HID (High
intensity discharge) lighting
All models HACR rated
Series rated with various
Eaton main circuit breakers

1
1
1
1
1
1
V4-T1-34

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Page
V4-T1-2
V4-T1-5
V4-T1-8
V4-T1-11
V4-T1-14
V4-T1-17
V4-T1-20
V4-T1-24
V4-T1-28
V4-T1-31

V4-T1-35
V4-T1-36
V4-T1-36
V4-T1-37
V4-T1-40

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Product Selection

GHBS—Single-Pole

1
1

GHBS UL 489 Interrupting Ratings

1

Interrupting Capacity (Symmetrical Amperes)
Number
of Poles

Ampere
Rating 1

Vac (50/60 Hz)
120

240

277/480

Catalog Number

1

15

65,000

—

14,000

GHBS1015D

20

65,000

—

14,000

GHBS1020D

30

65,000

—

14,000

GHBS1030D

15

—

65,000

14,000

GHBS2015D

20

—

65,000

14,000

GHBS2020D

30

—

65,000

14,000

GHBS2030D

2

1
1
1
1
1

GBHS CSA 22.2 Interrupting Ratings (Not UL Listed)

1

Interrupting Capacity (Symmetrical Amperes)
Number
of Poles
1

2

Ampere
Rating 1

1

Vac (50/60 Hz)
347/600

Catalog Number

15

10,000

GBHS1015D

20

10,000

GBHS1020D

15

10,000

GBHS2015D

20

10,000

GBHS2020D

1
1
1
1

GHQRSP UL 489 and CSA 22.2 Interrupting Ratings
Interrupting Capacity (Symmetrical Amperes)
Number
of Poles

Ampere
Rating 1

Vac (50/60 Hz)
120

120/240

277

480Y/277

Catalog Number 2

1

15

65,000

65,000

14,000

14,000

GHQRSP1015

20

65,000

65,000

14,000

14,000

GHQRSP1020

30

65,000

65,000

14,000

14,000

GHQRSP1030

15

65,000

65,000

14,000

14,000

GHQRSP2015

20

65,000

65,000

14,000

14,000

GHQRSP2020

30

65,000

65,000

14,000

14,000

GHQRSP2030

2

1
1
1
1
1
1

Notes
1 Continuous current rating at 40°C.
2 All UL listed circuit breakers are HID (high intensity discharge) rated.

1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-35

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1

Technical Data and Specifications

1

1

Solenoid Operating Data
●
Power requirements: 24
Vac/dc (20.4V minimum–
30V maximum)
●
Controlled signal: +AC/
DC 8 ms minimum with
zero cross, 300 ms
maximum
●
AC: 1.3 cycles minimum,
18 cycles or 300 ms
maximum
●
DC: 8 ms minimum,
300 ms maximum
●
Maximum duty cycle of
6 OPEN/CLOSE cycles
per minute
●
Current draw: open 1A,
close 3/4A
●
Blue wire: power input
(see power requirements)
●
Black wire: remote opening

1

Terminal Type

1

Circuit Breaker
Type

Circuit Breaker
Amperes

Screw
Head Type

Terminal
Type

Range

1

GHQRSP

15–20

Slotted

Clamp

#14–#4 AWG

1
1
1
1
1
1
1
1

●
●

Wiring Diagrams
Red wire: remote closing
Yellow wire: feedback
status from power input,
maximum 0.50A draw

Operation
Mechanism manually
operated by external handle
allowing ON, OFF and RESET
operation. Handle assumes a
center TRIP position after
performing protective
response.
Operating/Application Data
●
Ambient temperature:
0–40°C
●
Frequency: 48–62 Hz
●
Humidity: 0–95%
noncondensing

Typical Single-Pole Circuit Breaker Schematic Diagram for
GHBS and GBHS Breakers
Circuit Breaker

Solenoid

Common
AMP Inc.
Conductor
Plug 1

a

Solenoid

Auxiliary

/ Cycle
Maximum
28 Vac
Pulse Source
1 2

28 Vac
Circuit Breaker
Open/Closed
Status

Typical Single-Pole Circuit Breaker Schematic Diagram for
GHQRSP Breakers
GHQRSP
Remote
Breaker
Contact
Contact
Load

Line

1

Blue

1

Black

Yellow

1

Red

1

On
Coil

Off
Coil

Power
Input

Status

1
1

Dimensions

1

Approximate Dimensions in Inches (mm)

1

Dimensions per Pole

1
1

Circuit Breaker Type

Width

Height 2

Length 3

GHQRSP

1.00 (25.4)

4.63 (117.6)

2.81 (71.4)

Notes
1 Purchase separate AMP Inc. conductor plug #640426-3.
2 Excluding line terminal.
3 Excluding handle.

1
1
1
1
1
1
V4-T1-36

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Contents

International Rated

Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications. . . . . . . . . . . .
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Application Breakers, Types HQP, BA, QC . . . .

Page
V4-T1-2
V4-T1-5
V4-T1-8
V4-T1-11

1
1
1
1

V4-T1-14

1

V4-T1-17

1

V4-T1-20
V4-T1-24

1

V4-T1-28

1

V4-T1-31

1

V4-T1-34

1

V4-T1-38
V4-T1-39
V4-T1-39
V4-T1-40

1
1
1

International Rated Types HQP, BA, QC, GFMB, GFXBC

1

Product Description

Standards and Certifications

1

QUICKLAG International Circuit
Breakers
●
Bolt-on Type BA

QUICKLAG International Circuit
Breakers
●
Built and test certified to
BS3871, Pt. 1
●
50/60 Hz, 40°C

1

QUICKLAG International Ground
Fault Circuit Breakers
●
Plug-on Type GFMB
●
Cable-in/cable-out Type
GFXBC

1
1

QUICKLAG International Ground
Fault Circuit Breakers
●
Built and test certified to
BS3871, Pt. 1; BS3871,
Section 31-C; BS4293
●
50/60 Hz, 40°C; 30 mA
sensitivity

1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-37

1.1
1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Product Selection
BAB

Breaker Catalog Numbers
Single-Pole

Two-Pole

Three-Pole

240/415 Vac

240/415 Vac

240/415 Vac

Catalog Number

Catalog Number

Catalog Number

1

Continuous
Ampere Rating
at 40°C

1

3000A Interrupting Capacity (M3) Bolt-On Thermal-Magnetic Circuit Breakers

1

10

BAB1010E

BAB2010E

15

BAB1015E

BAB2015E

BAB3015E

1

16

—

—

—

20

BAB1020E

BAB2020E

BAB3020E

1

25

BAB1025E

BAB2025E

BAB3025E

30

BAB1030E

BAB2030E

BAB3030E

1

32

—

—

—

1

40

BAB1040E

BAB2040E

BAB3040E

50

BAB1050E

BAB2050E

BAB3050E

1

60

BAB1060E

BAB2060E

BAB3060E

70

BAB1070E

BAB2070E

BAB3070E

1

90

—

BAB2090E

BAB3090E

1

100

—

BAB2100E

BAB3100E

6000A Interrupting Capacity (M6) Bolt-On Thermal-Magnetic Circuit Breakers

BAB3010E

1

15

BAB1015HE

BAB2015HE

BAB3015HE

20

BAB1020HE

BAB2020HE

BAB3020HE

1

25

BAB1025HE

BAB2025HE

BAB3025HE

30

BAB1030HE

BAB2030HE

BAB3030HE

1

40

BAB1040HE

BAB2040HE

BAB3040HE

1

50

BAB1050HE

BAB2050HE

BAB3050HE

60

BAB1060HE

BAB2060HE

BAB3060HE

1

70

BAB1070HE

BAB2070HE

BAB3070HE

90

—

BAB2090HE

BAB3090HE

1

100

—

BAB2100HE

BAB3100HE

1

Breaker Catalog Numbers—Ground Fault Single-Pole 30 mA Sensitivity

1

Continuous
Ampere Rating
at 40°C

1

240/415 Vac
Catalog Number

3000A Interrupting Capacity (M3) Plug-On Thermal-Magnetic Circuit Breakers

1

10

GFMB110B2

1

15

GFMB115B2

16

GFMB116B2

1

20

GFMB120B2

25

GFMB125B2

1

30

GFMB130B2

32

GFMB132B2

1

40

GFMB140B2

1

Note
For other 240/415V applications, please contact the Customer Support Center at 1-800-356-1243.

1
1
1
V4-T1-38

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Technical Data and Specifications

1

Interrupting Ratings
Ratings

Suffix E

1

Suffix HE

1

International Circuit Breakers
NEMA®
120/240 Vac

10,000 AIC

10,000 AIC

BS3871 220/380,
240/415 Vac

3000 AIC

6000 AIC

1
1

International Ground Fault Circuit Breakers
BS3871 220/380,
240/415 Vac

1

3000 AIC

1
1

Dimensions
Approximate Dimensions in Inches (mm)

1

Shipping Data
Miniature
Circuit Breaker
QUICKLAG Type B

Number
of Poles

Standard Carton
Quantity

Approximate Carton
Weight Lbs (kg)

1

Approximate
Standard Carton

1

1

24

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

2

12

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

3

8

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

1

20

11.00 (5.0)

12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)

1

QUICKLAG Ground Fault
Type P—All

1

Types B and C—All

1

20

11.00 (5.0)

12.50 x 7.00 x 5.50 (317.5 x 177.8 x 139.7)

Types P and B—All

2

5

5.00 (2.3)

12.50 x 6.00 x 4.50 (317.5 x 152.4 x 114.3)

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-39

1.1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Contents

QUICKLAG Type P Switching Neutral

Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Special Application Breakers, Types HQP, BA, QC
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Factory Modifications and Installed Terminals . .
Technical Data and Specifications . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1
1
1
1
1
1
1
1
1
1
1
1
1

Special Application Breakers, Types HQP, BA, QC

1

Product Description

1

Breakers
●
Plug-on Type HQP:
10–30A, single- and
two-pole, 10 kAIC
●
Bolt-on Type BA: 10–30A,
single- and two-pole,
10 kAIC
●
Cable-in Type QC: 10–30A,
single- and two-pole,
10 kAIC

1
1
1
1
1
1
1
1
1

QUICKLAG HID (High Intensity
Discharge) Breakers
●
Plug-on Type HQP:
15–60A, single- and
two-pole, 10 kAIC
●
Bolt-on Type BA: 15–60A,
single- and two-pole,
10 kAIC
●
Cable-in Type QC: 15–60A,
single- and two-pole,
10 kAIC
Breakers designed
specifically for use with high
intensity discharge (HID)
lighting applications. (UL
listed as standard lighting
breakers.)

Molded Case Switches—Nonautomatic QUICKLAG Molded
Case Switch
●
Plug-on Type HQP: 50,
60,100A, single-, two- and
three-pole
●
Bolt-on Type BA: 50,
60,100A, single-, two- and
three-pole
●
Cable-in Type QC: 50,
60,100A, single-, two- and
three-pole

1
1
1
1
1
V4-T1-40

V4-T1-8
V4-T1-11
V4-T1-14
V4-T1-17
V4-T1-20
V4-T1-24
V4-T1-28
V4-T1-31
V4-T1-34
V4-T1-37
V4-T1-41
V4-T1-43
V4-T1-46
V4-T1-47
V4-T1-48

Standards and Certifications
●

Switching neutral QUICKLAG
breakers available in singleand two-pole configurations,
plus neutral pole for
applications in accordance
with NEC® 514.5, 240.22 and
380.2. A single-pole device
takes two pole spaces, and a
two-pole device takes three
pole spaces.

Page
V4-T1-2
V4-T1-5

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

All products UL and
CSA listed

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1.1

Product Selection
QUICKLAG Type P
Switching Neutral

1
1

Breaker Catalog Numbers
Continuous
Ampere Rating
at 40°C

Single-Pole

Two-Pole

Two-Pole

Three-Pole

120/240 Vac

120/240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

1
1

QUICKLAG Type: HQP Switching Neutral Thermal-Magnetic Breakers
10

HQP2010B

HQP3010B

—

—

15

HQP2015B

HQP3015B

—

—

20

HQP2020B

HQP3020B

—

—

25

HQP2025B

HQP3025B

—

—

30

HQP2030B

HQP3030B

—

—

1
1

1
1

QUICKLAG Type: BA Switching Neutral Thermal-Magnetic Breakers
10

BAB2010C

BAB3010C

—

—

15

BAB2015C

BAB3015C

—

—

20

BAB2020C

BAB3020C

—

—

25

BAB2025C

BAB3025C

—

—

30

BAB2030C

BAB3030C

—

—

1
1
1

QUICKLAG Type: QC Switching Neutral Thermal-Magnetic Breakers
10

QC2010B

QC3010B

—

—

15

QC2015B

QC3015B

—

—

20

QC2020B

QC3020B

—

—

25

QC2025B

QC3025B

—

—

30

QC2030B

QC3030B

—

—

1
1
1

QUICKLAG Type: HQP HID (High Intensity Discharge) Thermal-Magnetic Breakers
15

HQP1015D

HQP2015D

—

—

20

HQP1020D

HQP2020D

—

—

25

HQP1025D

HQP2025D

—

—

30

HQP1030D

HQP2030D

—

—

35

HQP1035D

HQP2035D

—

—

40

HQP1040D

HQP2040D

—

—

50

HQP1050D

HQP2050D

—

—

60

HQP1060D

HQP2060D

—

—

1
1
1
1
1

QUICKLAG Type: BA HID (High Intensity Discharge) Thermal-Magnetic Breakers
15

BAB1015D

BAB2015D

—

—

20

BAB1020D

BAB2020D

—

—

25

BAB1025D

BAB2025D

—

—

30

BAB1030D

BAB2030D

—

—

35

BAB1035D

BAB2035D

—

—

40

BAB1040D

BAB2040D

—

—

50

BAB1050D

BAB2050D

—

—

60

BAB1060D

BAB2060D

—

—

1
1
1
1
1
1

QUICKLAG Type: QC HID (High Intensity Discharge) Thermal-Magnetic Breakers
15

QC1015D

QC2015D

—

—

20

QC1020D

QC2020D

—

—

25

QC1025D

QC2025D

—

—

30

QC1030D

QC2030D

—

—

35

QC1035D

QC2035D

—

—

40

QC1040D

QC2040D

—

—

50

QC1050D

QC2050D

—

—

60

QC1060D

QC2060D

—

—

1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-41

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1

Breaker Catalog Numbers, continued
Single-Pole

Two-Pole

Two-Pole

1

Continuous
Ampere Rating
at 40°C

120/240 Vac

120/240 Vac

240 Vac

240 Vac

Catalog Number

Catalog Number

Catalog Number

Catalog Number

1

QUICKLAG Type: HQP Non-Automatic Switches

1

50

HQP1050N

—

HQP2050N

HQP3050N

60

HQP1060N

—

HQP2060N

HQP3060N

1

100

HQP1100N

—

HQP2100N

HQP3100N

1

50

BAB1050N

—

BAB2050N

BAB3050N

60

BAB1060N

—

BAB2060N

BAB3060N

1

100

BAB1100N

—

BAB2100N

BAB3100N

1

50

QC1050N

—

QC2050N

QC3050N

1

60

QC1060N

—

QC2060N

QC3060N

100

QC1100N

—

QC2100N

QC3100N

1

QUICKLAG Type: QCD Non-Automatic Switches

1

60

—

—

QCD2060NA

—

100

—

—

—

—

Three-Pole

QUICKLAG Type: BA Non-Automatic Switches

QUICKLAG Type: QC Non-Automatic Switches

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-42

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Accessories 1

1
1

Handle Locks: Non-Padlockable 2
QL1NPL

Description

Order in Multiples of

Catalog Number

QUICKLAG Type P, B, C—single-pole

10

QL1NPL

1
1
1
1

QL23NPL

QUICKLAG Type P, B, C—two- and three-pole

10

1

QL23NPL

1
1
1
1
1

Handle Locks: Padlockable 2
QL1PL

Description

Order in Multiples of

Catalog Number

QUICKLAG Type P, B, C—single-pole

10

QL1PL

1
1
1
1
1

QL123PL

QUICKLAG Type P, B and ground fault—single-, two- and three-pole

10

1

QL123PL

1
1
1
QC123PL

QUICKLAG Type C —single-, two- and three-pole

10

1

QC123PL

1
1
1
QUICKLAG Type P, B—single-, two- and three-pole (off only)

10

QL123PLOFF

QUICKLAG Type C—single-, two- and three-pole (off only)

10

QC123PLOFF

1
1

Notes
1 See Page V4-T1-27 for QCR and QCF accessories.
2 Can lock in ON or OFF position.

1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-43

1.1

Industrial Circuit Breakers

Mounting Hardware

1
1

Miniature Circuit Breakers and Supplementary Protectors

Description

Order in Multiples of

Catalog Number

QCFCLIP

QUICKLAG Type C face mounting clip

24

QCFCLIP

QC1FP

QUICKLAG Type C face mounting plate—single-pole

10

QC1FP

QC2FP

QUICKLAG Type C face mounting plate—two-pole

10

QC2FP

QC3FP

QUICKLAG Type C face mounting plate—three-pole

10

QC3FP

QUICKLAG Type C face mounting plate and lock-off (off only)—two-pole 1

10

QC2FPLOFF

QUICKLAG Type C face mounting plate and lock-off (off only)—three-pole

10

QC3FPLOFF

QCBCLIP

QUICKLAG Type C base mounting clamp

10

QCBCLIP

QC6BP

QUICKLAG Type mounting plate—six poles total

10

QC6BP

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Note
1 Suitable for ground fault breakers.

1
1
V4-T1-44

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Mounting Hardware, continued
Description

QCDJ4

Order in Multiples of

Catalog Number

QUICKLAG Type C base mounting plate—six poles total—heavy-duty screw-secured

10

QC6BPS

QUICKLAG Type C (QCD) 2-way jumper unit with cover

10

QCDJ2

QUICKLAG Type C (QCD) 4-way jumper unit with cover

10

QCDJ4

1
1
1
1
1

QCDINADAPT

1

QUICKLAG Type C (QCD) 6-way jumper unit with cover

10

QCDJ6

QUICKLAG Type C (QCD) 2-way jumper unit, no cover

10

QCDJ2T

QUICKLAG Type C (QCD) 4-way jumper unit, no cover

10

QCDJ4T

QUICKLAG Type C (QCD) 6-way jumper unit, no cover

10

QCDJ6T

QUICKLAG Type QCD Finger protection attachment

10

QCDFP

QUICKLAG Type QCD 4-prong Quick Connect

10

QCDQUICK

QUICKLAG Type C DIN rail adapter

6

QCDINADAPT

1
1
1
1
1

QCDRING

QUICKLAG Type QCD ring lug attachment

10

1

QCDRING

1
1
1
1

Dummy Breakers
Description

Order in Multiples of

Catalog Number

QUICKLAG Type P

1

HQP1000

QUICKLAG Type B

1

BAB1000

QUICKLAG Type C

1

QC1000

QUICKLAG Type C clear choice breaker

4

QC30SAMPLE

1
1
1
1

QCRSPACER

Miscellaneous
Description

Order in Multiples of

Catalog Number

QUICKLAG Type C Spacer

1

QCRSPACER

1
1
1
1
1

QL1HT

Handle Tie
Description

Order in Multiples of

Catalog Number

QUICKLAG handle tie—single-pole

100

QL1HT

1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-45

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

1

Factory Modifications and Installed Terminals

1

Factory Modifications 1
Type of Modification

Breaker Type

Catalog Suffix

Shunt trip (requires one extra pole space on right side)
120, 208, 240 Vac
Draws 2.6A at 120V, draws 11A at 24 Vdc

QUICKLAG Types P, B and C

S

Shunt trip (requires one extra pole space on right side)
24, 48 Vac/dc
Draws 2.6A at 120V, draws 11A at 24 Vdc

QUICKLAG Types P, B and C

S1

Special calibration (50°C) (no UL)

QUICKLAG Types P, B and C

V

Shock testing

QUICKLAG Types P, B and C

L

1

Freeze testing

QUICKLAG Types P, B and C

Y

Moisture-fungus treatment

QUICKLAG Types P, B, C and ground fault

F

1

Marine duty

QUICKLAG Types P, B, C

H08

1

Naval duty

QUICKLAG Types P, B, C

H09

400 Hz calibration

QUICKLAG Types P, B, C

G

Specific DC ratings (breaker marked with a max. Vdc rating)

QUICKLAG Types P, B, C

Q thru Q9 2

1
1
1
1

1
1

Spare Terminal Hardware Screws (Lugs not Included)
Terminal Type

Description

Order in Multiples of

Catalog Number

1

QUICKLAG terminal screw

10

QLLDTSA

1

2

QUICKLAG terminal screw

10

QLLDTSB

1

3

QUICKLAG terminal screw

10

QLLDTSC

5

QUICKLAG binding head terminal screw and clamp

10

QLBHTSE

6 and 7

QUICKLAG terminal screw

10

QLLNTSFG

1

1
1

Notes
1 Contact Eaton for factory modifications available for QCR and QCF breakers.
2 Q = 32 Vdc; Q1 = 32–40 Vdc; Q2 = 37.5 Vdc; Q3 = 45 Vdc; Q4 = 48 Vdc; Q5 = 50 Vdc; Q6 = 62.5 Vdc; Q7 = 75 Vdc (2P); Q8 = 80 Vdc (2P); Q9 = 125 Vdc (QCR 2P); Q10 = 62.5 Vdc (QCR 1P).

1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-46

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Technical Data and Specifications

1

Factory-Installed Breaker Terminals
Breaker
Type
QUICKLAG Type P
HQP, QPHW,
QHPX, QHPW

Continuous
Ampere
Rating

Standard Line Terminal

Standard Load Terminal

Terminal Wire
Type
Type

Terminal
Type

Wire
Type

Wire
Range (AWG)

Line

10–30

Plug-on female clips that mate
with the bus stabs

1

Cu/Al

14–4

N/A

3

2

Cu/Al

14–4

N/A

3

3

Cu/Al

8–1/0

N/A

—

Plug-on female clips that mate
with the bus stabs

1 (single-pole)

Cu/Al

14–4

N/A

3

1

Cu/Al

—

N/A

3

1

Cu

14–8

N/A

—

Extended tangs that bolt
directly to the bus

1 (single- and two-pole)

Cu/Al

14–4

N/A

3

2 (three-pole)

Cu/Al

14–4

N/A

3

3

Cu/Al

8–1/0

N/A

—

1 (single-pole)

Cu/Al

14–4

N/A

N/A

35–50

Wire
Range (AWG)

55–125
QUICKLAG ground fault
QPGF, QPGFEP,
QPHGF, QPHGFEP

10–40
10–40
10–30

QUICKLAG Type B
BAB, QBHW,
HBAX, HBAW

10–40
35–50
55–125

QUICKLAG ground fault
QBGF, QBGFEP,
QBHGFEP, QBHGF

10–40
10–40

Extended tangs that bolt
directly to the bus

10–30
QUICKLAG Type C
QC, QCHW,
QHCX, QHCW

Optional Terminals
Load

1

Cu/Al

14–8

N/A

N/A

1

Cu

14–8

N/A

N/A

1
1
1
1

Cu/Al

TBD

5

Cu/Al

14–10

6, 7

6, 7, 8

6

Cu/Al

TBD

2

Cu/Al

14–4

5, 7

5, 6, 7, 8

7

Cu/Al

TBD

3

Cu/Al

8–1/0

5

5, 7, 8

1

Cu/Al

TBD

1

Cu/Al

14–4

N/A

N/A

60

1

Cu

TBD

1

Cu

14–4

N/A

N/A

QUICKLAG ground fault
QCGF, QCGFEP,
QCHGF, QCHGFEP

10–20

6

Cu/Al

TBD

14–8

Cu/Al

14–4

6, 7

5

25–50

6

Cu/Al

TBD

1

Cu/Al

14–4

5, 7

5

10–30

6

—

—

—

—

—

—

—

10–60

9

Cu/Al

14–4

9

Cu/Al

14–4

See Accessories

70–100

10

Cu

4–1/0

10

Cu

4–1/0

See Accessories

1

1

5

10–55

QUICKLAG
QCD

1

25–60
70–100

2

3

1
1

10–20

QUICKLAG
QCR, QCF

1

1
1
1
1
1
1
1

5

1
1

Steel Box Lug

6

Steel Box Lug

7

Steel Box Lug

8

1

Steel Ring Type

9

1

10

1
4-Prong Quick Connect
Aluminum Box Lug

Aluminum Box Lug

QCD Terminal Assembly
10–60A

QCD Terminal Assembly
70–100A

1
1

Note
1 Clamp on line side only.

1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-47

1.1
1
1
1
1
1
1
1

Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers

Dimensions
Approximate Dimensions in Inches (mm)
Shipping Data
Miniature
Circuit Breaker

Number
of Poles

Standard
Carton
Quantity

Approximate
Carton Weight
Lbs (kg)

Approximate Standard
Carton

QUICKLAG Types B, P, C–all

1

24

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

QUICKLAG Types B, P, C–all

2

12

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

QUICKLAG Types B, P, C–all

3

8

9.00 (4.1)

12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)

QUICKLAG ground fault Type P–all

1

20

11.00 (5.0)

12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)

Types B and C–all

1

20

11.00 (5.0)

12.50 x 7.00 x 5.50 (317.5 x 177.8 x 139.7)

Types P and B–all

2

5

5.00 (2.3)

12.50 x 6.00 x 4.50 (317.5 x 152.4 x 114.3)

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-48

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

1.2

Contents

FAZ-NA Circuit Breakers

Description

Page

FAZ-NA Circuit Breakers
Catalog Number Selection . . . . . . . . . . . . . . . .
Product Selection . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .
WMZ Circuit Breaker. . . . . . . . . . . . . . . . . . . . . . .

V4-T1-50
V4-T1-51
V4-T1-55
V4-T1-57
V4-T1-66
V4-T1-67

1
1
1
1
1
1
1
1

Optimum and Efficient Protection for Every Application

1
1
1

FAZ-NA Circuit Breakers
Product Overview

Features

Optimum product quality,
tested reliability and safety
stand for best protection of
personnel, installations and
plant. Eaton’s FAZ-NA DIN rail
mountable circuit breaker is
designed for use in branch
service applications.

●

Powerful Offering for Machine
and System Builders
The FAZ-NA is available with
B, C and D characteristics in
accordance with UL® 489,
CSA® C22.2 No.5; UL 1077,
CSA C22.2 No.235 and IEC
60947-2. These devices are
CE marked.

Application Description
Feeder and branch circuit
protection for:
●

●
●

●

●
●
●
●
●
●
●

Convenience receptacle
circuits (internal/external)
Motor control circuits
Load circuits leaving the
equipment (external)
HACR internal/external
equipment (heating, air
conditioning, refrigeration)
PLC I/O points
Computers
Power supplies
Control instrumentation
Relays
UPS
Power conditioners

Complete range of UL 489
listed DIN rail mounted
miniature circuit breakers
up to 40A current rating

●

●

Standard ratings of 10 kAIC
up to 277/480 Vac

●

●

Select amperages available
at 14 kAIC up to 277/480
Vac and 10 kAIC up to 125
Vdc per pole

Fulfill UL 489, CSA C22.2
No.5 and also IEC 60947-2
Standard

●

For use in applications for
which UL 1077 or CSA
C22.2 No.235 are also
allowed

●

Current limiting design
provides fast short-circuit
interruption that reduces
the let-through energy,
which can damage the
circuit

●

Suitable for branch circuit
device protection

●

Thermal-magnetic
overcurrent protection
●

●

●

Three levels of shortcircuit protection,
categorized by B, C
and D curves

Trip-free design—breaker
can not be defeated by
holding the handle in the
ON position

●

●

SWD (switching duty)—
suitable for switching
fluorescent lighting loads
(In ≤ 20A)

Field-installable shunt trip
and auxiliary switch
subsequent mounting
Separate version for ringtongue connection (Type
FAZ-RT), terminal screws
can be removed (on
both sides)

●

Module width of only
17.7 mm (per pole)

●

Contact Position Indicator
(red/green)

●

Easy installation on DIN rail

●

Possibility for sealing the
toggle in ON or OFF
position

1
Device Printing on Front and Side
Installation options

1

These branch circuit breakers
are available in two terminal
configurations: standard box
terminals that accept multiple
conductors and ring-tongue
terminals, ideally suited to
demanding requirements of
the semi-conductor industry.
All breakers mount on
standard 35 mm DIN rail.
Bus connectors and feeder
terminal facilitate mounting
and wiring of multiple
miniature circuit breaker
arrays in control panel
assemblies. These circuit
breakers can also be
reverse feed.

1
1
1
1
1
1
1
1
1
1
1
1
1
1

Captive screws cannot
be lost

1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-49

1.2
1
1
1

FAZ-NA complies with
the latest national and
international standards.

1
1
1
1

●
●

UL 489
●
Standard for molded
case circuit breakers
(MCCB) for feeder and
branch circuit protection
●
Products meet the
requirements of the
National Electrical Code®
(NEC®)

●

CSA C22.2 No.5
●
Standard for molded
case circuit breakers
(MCCB) for feeder and
branch circuit protection
(corresponds closely to
UL 489 Standard)
●
Products meet the
requirements of the
Canadian Electrical Code
(CEC)

1

1

●

●

1

1

UL 489 DIN Rail Miniature Circuit Breakers

Standards and Certifications

1

1

Miniature Circuit Breakers and Supplementary Protectors

RoHS compliant
VDE compliant
ABS compliant

Catalog Number Selection

1

FAZ C 6 / 1 NA SP

1

Breaker Family

1

FAZ = FAZ UL
circuit breaker

Single Package
Trip
Characteristics 1
B = 3–5X In
C = 5–10X In
D = 10–20X In

1
1
1
1
1
1

Terminal
Ampere Rating 2
0.5 =
1 =
1.5 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =

0.5A
1A
1.5A
2A
3A
4A
5A
6A
7A
8A

10 = 10A
13 = 13A
15 = 15A
16 = 16A
20 = 20A
25 = 25A
30 = 30A
32 = 32A
35 = 32A
40 = 40A

Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole

Notes
1 I = Rated current for instantaneous trip characteristics.
n
2 B curve starts at 1 ampere.

1
1
1
1
1
1
1
1
V4-T1-50

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

NA = UL 489 branch
circuit with screw
terminals
RT = UL 489 branch
circuit with ring
tongue terminals
DC = UL 489 branch
circuit at 125 Vdc
per pole

SP

= Single package for
C and D curve
single-pole only
Blank = Standard
packaging

1.2

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

1

1.45

FAZ-NA B Curve
●
UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02)
as branch circuit breakers
●
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947-2
●
Current limiting device
●
UL file number E235139

1.13

Product Selection
 2.55 I :
N

1

 Type B: 3 x I : t > 0.1 s
N

1

7200

Specified non-tripping
current
INT = 1.13 x IN for t > 1 h

3600
1200
600

t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)

Specified tripping current
IT = 1.45 x IN for t < 1 h

300

 Type B: 5 x I : t < 0.1 s
N

1

120
1

60

1

30

1

t [sec]

10
5

1

2
1
1

0.5

1

0.2
3

0.1

1

B

2

0.05
0.02

1

0.01
0.005

1

0.002
0.001

1

0.0005
1

2

3

4

5

6 7 8 9 10

15

20

30

40

50

1

I / IN

Single-Pole

FAZ-NA UL 489 Circuit Breakers—10 kAIC,
14 kAIC B Curve (15–25A)
Single-Pole 1
Catalog
Amperes Number

Two-Pole

Three-Pole

Catalog
Number

Catalog
Number

Single-Pole

Single-Pole 1 Two-Pole
Catalog
Amperes Number

B Curve (3–5X In Current Rating)

Two-Pole

Three-Pole

1

FAZ-B1/1-NA

FAZ-B1/2-NA

1.5

FAZ-B1.5/1-NA FAZ-B1.5/2-NA FAZ-B1.5/3-NA

2

FAZ-B2/1-NA

FAZ-B2/2-NA

FAZ-B2/3-NA

3

FAZ-B3/1-NA

FAZ-B3/2-NA

FAZ-B3/3-NA

4

FAZ-B4/1-NA

FAZ-B4/2-NA

FAZ-B4/3-NA

5

FAZ-B5/1-NA

FAZ-B5/2-NA

FAZ-B5/3-NA

6

FAZ-B6/1-NA

FAZ-B6/2-NA

FAZ-B6/3-NA

7

FAZ-B7/1-NA

FAZ-B7/2-NA

FAZ-B7/3-NA

8

FAZ-B8/1-NA

FAZ-B8/2-NA

FAZ-B8/3-NA

10

FAZ-B10/1-NA FAZ-B10/2-NA FAZ-B10/3-NA
FAZ-B13/1-NA FAZ-B13/2-NA FAZ-B13/3-NA

15

FAZ-B15/1-NA FAZ-B15/2-NA FAZ-B15/3-NA

16

FAZ-B16/1-NA FAZ-B16/2-NA FAZ-B16/3-NA

20

FAZ-B20/1-NA FAZ-B20/2-NA FAZ-B20/3-NA

25

FAZ-B25/1-NA FAZ-B25/2-NA FAZ-B25/3-NA

30

FAZ-B30/1-NA FAZ-B30/2-NA FAZ-B30/3-NA

32

FAZ-B32/1-NA FAZ-B32/2-NA FAZ-B32/3-NA

35 2

FAZ-B35/1-NA FAZ-B35/2-NA FAZ-B35/3-NA

2

FAZ-B40/1-NA FAZ-B40/2-NA FAZ-B40/3-NA

40

Catalog
Number

Two-Pole

Three-Pole

FAZ-B1/2-RT

1

Catalog
Number

1
1

1

FAZ-B1/1-RT

1.5

FAZ-B1.5/1-RT FAZ-B1.5/2-RT FAZ-B1.5/3-RT

2

FAZ-B2/1-RT

FAZ-B2/2-RT

FAZ-B2/3-RT

3

FAZ-B3/1-RT

FAZ-B3/2-RT

FAZ-B3/3-RT

4

FAZ-B4/1-RT

FAZ-B4/2-RT

FAZ-B4/3-RT

5

FAZ-B5/1-RT

FAZ-B5/2-RT

FAZ-B5/3-RT

6

FAZ-B6/1-RT

FAZ-B6/2-RT

FAZ-B6/3-RT

7

FAZ-B7/1-RT

FAZ-B7/2-RT

FAZ-B7/3-RT

8

FAZ-B8/1-RT

FAZ-B8/2-RT

FAZ-B8/3-RT

10

FAZ-B10/1-RT

FAZ-B10/2-RT

FAZ-B10/3-RT

13

FAZ-B13/1-RT

FAZ-B13/2-RT

FAZ-B13/3-RT

15

FAZ-B15/1-RT

FAZ-B15/2-RT

FAZ-B15/3-RT

16

FAZ-B16/1-RT

FAZ-B16/2-RT

FAZ-B16/3-RT

20

FAZ-B20/1-RT

FAZ-B20/2-RT

FAZ-B20/3-RT

25

FAZ-B25/1-RT

FAZ-B25/2-RT

FAZ-B25/3-RT

30

FAZ-B30/1-RT

FAZ-B30/2-RT

FAZ-B30/3-RT

32

FAZ-B32/1-RT

FAZ-B32/2-RT

FAZ-B32/3-RT

35 2

FAZ-B35/1-RT

FAZ-B35/2-RT

FAZ-B35/3-RT

40 2

FAZ-B40/1-RT

FAZ-B40/2-RT

FAZ-B40/3-RT

FAZ-B1/3-RT

1
1
1
1
1
1
1
1
1
1
1
1

Notes
1 Two-piece order. Quantities of two per box.
2 240 Vac rated only.

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1

Three-Pole

B Curve with Ring-Tongue Terminals
(3–5X In Current Rating)

FAZ-B1/3-NA

13

FAZ-RT UL 489 Circuit Breakers with
Ring-Tongue Terminals—10 kAIC, 14 kAIC
B Curve (15–25A)

1
V4-T1-51

1.2
1
1

FAZ-NA C Curve
●
UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02)
as branch circuit breakers
●
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947-2
●
Current limiting device
●
UL file number E235139

1.45

UL 489 DIN Rail Miniature Circuit Breakers

1.13

1

Miniature Circuit Breakers and Supplementary Protectors

7200

Specified non-tripping
current
INT = 1.13 x IN for t > 1 h

3600
1200

300
120
60
30

1
t [sec]

10

1

5
2
1

1

0.5
0.2

1

2

0.1
1

0.05

1

0.02

0.005
0.002
0.001

1

0.0005
1

1
Single-Pole

FAZ-NA UL 489 Circuit Breakers—10 kAIC,
14 kAIC C Curve (15–25A)
Single-Pole 1

1

Catalog
Amperes Number

1

Two-Pole

Three-Pole

Catalog
Number

Catalog
Number

Single-Pole

3

4

5

6 7 8 9 10

15

20

30

40

50

FAZ-C0.5/1-NA-SP FAZ-C0.5/2-NA FAZ-C0.5/3-NA

1

FAZ-C1/1-NA-SP

1.5

FAZ-C1.5/1-NA-SP FAZ-C1.5/2-NA FAZ-C1.5/3-NA

2

FAZ-C2/1-NA-SP

FAZ-C2/2-NA

FAZ-C2/3-NA

3

FAZ-C3/1-NA-SP

FAZ-C3/2-NA

FAZ-C3/3-NA

4

FAZ-C4/1-NA-SP

FAZ-C4/2-NA

FAZ-C4/3-NA

5

FAZ-C5/1-NA-SP

FAZ-C5/2-NA

FAZ-C5/3-NA

6

FAZ-C6/1-NA-SP

FAZ-C6/2-NA

FAZ-C6/3-NA

7

FAZ-C7/1-NA-SP

FAZ-C7/2-NA

FAZ-C7/3-NA

8

FAZ-C8/1-NA-SP

FAZ-C8/2-NA

FAZ-C8/3-NA

10

FAZ-C10/1-NA-SP FAZ-C10/2-NA FAZ-C10/3-NA

13

FAZ-C13/1-NA-SP FAZ-C13/2-NA FAZ-C13/3-NA

15

FAZ-C15/1-NA-SP FAZ-C15/2-NA FAZ-C15/3-NA

1

16

FAZ-C16/1-NA-SP FAZ-C16/2-NA FAZ-C16/3-NA

1

20

FAZ-C20/1-NA-SP FAZ-C20/2-NA FAZ-C20/3-NA

25

FAZ-C25/1-NA-SP FAZ-C25/2-NA FAZ-C25/3-NA

1

30

FAZ-C30/1-NA-SP FAZ-C30/2-NA FAZ-C30/3-NA

32

FAZ-C32/1-NA-SP FAZ-C32/2-NA FAZ-C32/3-NA

1

35 2

FAZ-C35/1-NA-SP FAZ-C35/2-NA FAZ-C35/3-NA

40 2

FAZ-C40/1-NA-SP FAZ-C40/2-NA FAZ-C40/3-NA

1
Two-Pole

1
1
1
Three-Pole

1

1

FAZ-C1/2-NA

FAZ-RT UL 489 Circuit Breakers with
Ring-Tongue Terminals—10 kAIC, 14 kAIC
C Curve (15–25A)
Single-Pole 1
Catalog
Amperes Number

C Curve (5–10X In Current Rating)
0.5

1

2

I / IN

1

1

C

0.01

1

1

 Type C: 10 x I : t < 0.1 s
N

Specified tripping current
IT = 1.45 x IN for t < 1 h

600

1

 Type C: 5 x I : t > 0.1 s
N

Two-Pole

Three-Pole

Catalog
Number

Catalog
Number

C Curve with Ring-Tongue Terminals
(5–10X In Current Rating)

FAZ-C1/3-NA
Two-Pole

Three-Pole

1

0.5

FAZ-C0.5/1-RT-SP FAZ-C0.5/2-RT FAZ-C0.5/3-RT

1

FAZ-C1/1-RT-SP

1.5

FAZ-C1.5/1-RT-SP FAZ-C1.5/2-RT FAZ-C1.5/3-RT

2

FAZ-C2/1-RT-SP

FAZ-C2/2-RT

FAZ-C2/3-RT

3

FAZ-C3/1-RT-SP

FAZ-C3/2-RT

FAZ-C3/3-RT

4

FAZ-C4/1-RT-SP

FAZ-C4/2-RT

FAZ-C4/3-RT

5

FAZ-C5/1-RT-SP

FAZ-C5/2-RT

FAZ-C5/3-RT

6

FAZ-C6/1-RT-SP

FAZ-C6/2-RT

FAZ-C6/3-RT

7

FAZ-C7/1-RT-SP

FAZ-C7/2-RT

FAZ-C7/3-RT

8

FAZ-C8/1-RT-SP

FAZ-C8/2-RT

FAZ-C8/3-RT

10

FAZ-C10/1-RT-SP FAZ-C10/2-RT FAZ-C10/3-RT

13

FAZ-C13/1-RT-SP FAZ-C13/2-RT FAZ-C13/3-RT

15

FAZ-C15/1-RT-SP FAZ-C15/2-RT FAZ-C15/3-RT

16

FAZ-C16/1-RT-SP FAZ-C16/2-RT FAZ-C16/3-RT

20

FAZ-C20/1-RT-SP FAZ-C20/2-RT FAZ-C20/3-RT

25

FAZ-C25/1-RT-SP FAZ-C25/2-RT FAZ-C25/3-RT

30

FAZ-C30/1-RT-SP FAZ-C30/2-RT FAZ-C30/3-RT

FAZ-C1/2-RT

FAZ-C1/3-RT

32

FAZ-C32/1-RT-SP FAZ-C32/2-RT FAZ-C32/3-RT

35 2

FAZ-C35/1-RT-SP FAZ-C35/2-RT FAZ-C35/3-RT

40 2

FAZ-C40/1-RT-SP FAZ-C40/2-RT FAZ-C40/3-RT

Notes
1 Option for single packaging on single-pole C and D curves only;
add suffix SP when ordering.
2 240 Vac rated only.

1
V4-T1-52

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.2

Miniature Circuit Breakers and Supplementary Protectors

1

1.45

FAZ-NA D Curve
●
UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02)
as branch circuit breakers
●
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947-2
●
Current limiting device
●
UL file number E235139

1.13

UL 489 DIN Rail Miniature Circuit Breakers

7200

 2.55 I :
N

Specified non-tripping
current
INT = 1.13 x IN for t > 1 h

3600
1200

Specified tripping current
IT = 1.45 x IN for t < 1 h

600
300

1

t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)

 Type D: 10 x I : t > 0.1 s
N

1

 Type D: 20 x I : t < 0.1 s
N

1

120
1

60
30

1

t [sec]

10
5

1

2
1

1

1

0.5
0.2

1

3

0.1

2

0.05

D

1

0.02
0.01
0.005

1

0.002
0.001

1

0.0005
1

2

3

4

5

6 7 8 9 10

15

20

30

40

50

1

I / IN

Single-Pole
Single-Pole

FAZ-NA UL 489 Circuit Breakers—10 kAIC,
14 kAIC D Curve (13–20A)
Single-Pole 1
Catalog
Amperes Number

Two-Pole

Three-Pole

Catalog
Number

Catalog
Number

Single-Pole

Two-Pole

Three-Pole

FAZ-D0.5/1-NA-SP FAZ-D0.5/2-NA FAZ-D0.5/3-NA

1

FAZ-D1/1-NA-SP

1.5

FAZ-D1.5/1-NA-SP FAZ-D1.5/2-NA FAZ-D1.5/3-NA

2

FAZ-D2/1-NA-SP

FAZ-D2/2-NA FAZ-D2/3-NA

3

FAZ-D3/1-NA-SP

FAZ-D3/2-NA FAZ-D3/3-NA

4

FAZ-D4/1-NA-SP

FAZ-D4/2-NA FAZ-D4/3-NA

5

FAZ-D5/1-NA-SP

FAZ-D5/2-NA FAZ-D5/3-NA

6

FAZ-D6/1-NA-SP

FAZ-D6/2-NA FAZ-D6/3-NA

7

FAZ-D7/1-NA-SP

FAZ-D7/2-NA FAZ-D7/3-NA

8

FAZ-D8/1-NA-SP

FAZ-D8/2-NA FAZ-D8/3-NA

10

FAZ-D10/1-NA-SP FAZ-D10/2-NA FAZ-D10/3-NA

13

FAZ-D13/1-NA-SP FAZ-D13/2-NA FAZ-D13/3-NA

15

FAZ-D15/1-NA-SP FAZ-D15/2-NA FAZ-D15/3-NA

16

FAZ-D16/1-NA-SP FAZ-D16/2-NA FAZ-D16/3-NA

20

FAZ-D20/1-NA-SP FAZ-D20/2-NA FAZ-D20/3-NA

25

FAZ-D25/1-NA-SP FAZ-D25/2-NA FAZ-D25/3-NA

30

FAZ-D30/1-NA-SP FAZ-D30/2-NA FAZ-D30/3-NA

32

FAZ-D32/1-NA-SP FAZ-D32/2-NA FAZ-D32/3-NA

35 2

FAZ-D35/1-NA-SP FAZ-D35/2-NA FAZ-D35/3-NA

2

FAZ-D40/1-NA-SP FAZ-D40/2-NA FAZ-D40/3-NA

40

FAZ-D1/2-NA FAZ-D1/3-NA

1

Catalog
Amperes Number

Two-Pole

Three-Pole

Catalog
Number

Catalog
Number

D Curve with Ring-Tongue Terminals
(10–20X In Current Rating)

D Curve (10–20X In Current Rating)
0.5

FAZ-RT UL 489 Circuit Breakers with
Ring-Tongue Terminals—10 kAIC, 14 kAIC
D Curve (13–20A)

Two-Pole

Three-Pole

0.5

FAZ-D0.5/1-RT-SP FAZ-D0.5/2-RT FAZ-D0.5/3-RT

1

FAZ-D1/1-RT-SP

1.5

FAZ-D1.5/1-RT-SP FAZ-D1.5/2-RT FAZ-D1.5/3-RT

2

FAZ-D2/1-RT-SP

FAZ-D2/2-RT

FAZ-D2/3-RT

3

FAZ-D3/1-RT-SP

FAZ-D3/2-RT

FAZ-D3/3-RT

4

FAZ-D4/1-RT-SP

FAZ-D4/2-RT

FAZ-D4/3-RT

5

FAZ-D5/1-RT-SP

FAZ-D5/2-RT

FAZ-D5/3-RT

6

FAZ-D6/1-RT-SP

FAZ-D6/2-RT

FAZ-D6/3-RT

7

FAZ-D7/1-RT-SP

FAZ-D7/2-RT

FAZ-D7/3-RT

8

FAZ-D8/1-RT-SP

FAZ-D8/2-RT

FAZ-D8/3-RT

10

FAZ-D10/1-RT-SP FAZ-D10/2-RT FAZ-D10/3-RT

13

FAZ-D13/1-RT-SP FAZ-D13/2-RT FAZ-D13/3-RT

15

FAZ-D15/1-RT-SP FAZ-D15/2-RT FAZ-D15/3-RT

16

FAZ-D16/1-RT-SP FAZ-D16/2-RT FAZ-D16/3-RT

20

FAZ-D20/1-RT-SP FAZ-D20/2-RT FAZ-D20/3-RT

25

FAZ-D25/1-RT-SP FAZ-D25/2-RT FAZ-D25/3-RT

30

FAZ-D30/1-RT-SP FAZ-D30/2-RT FAZ-D30/3-RT

FAZ-D1/2-RT

FAZ-D1/3-RT

32

FAZ-D32/1-RT-SP FAZ-D32/2-RT FAZ-D32/3-RT

35 2

FAZ-D35/1-RT-SP FAZ-D35/2-RT FAZ-D35/3-RT

40 2

FAZ-D40/1-RT-SP FAZ-C40/2-RT

FAZ-D40/3-RT

Notes
1 Option for single packaging on single-pole C and D curves only;
add suffix SP when ordering.
2 240 Vac rated only.

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-53

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1.2
1

●

●

1

●

1
1

UL 489 DIN Rail Miniature Circuit Breakers

FAZ-NA-DC C Curve

1
1

Miniature Circuit Breakers and Supplementary Protectors

●
●

●

UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02)
as Branch Circuit Breakers
Interrupting capacity: 10 kA at 125 Vdc UL/CSA, 10 kA
at 250 Vdc
125 Vdc for one-pole, 250 Vdc for two-pole in series
Current limiting device
Polarity (+/–) sensitive and not for use on photovoltaic
string application
UL file number E235139

1
1
1
1
1
1
1
1
1

Single-Pole

1

FAZ-NA-DC UL 489 Circuit Breakers—
10 kAIC at 125 Vdc Per Pole
Single-Pole 1
Catalog
Amperes Number

1

Two-Pole
Catalog
Number

C Curve (5–10X In Current Rating)

1

2

FAZ-C2/1-NA-DC-SP

FAZ-C2/2-NA-DC

3

FAZ-C3/1-NA-DC-SP

FAZ-C3/2-NA-DC

4

FAZ-C4/1-NA-DC-SP

FAZ-C4/2-NA-DC

1

5

FAZ-C5/1-NA-DC-SP

FAZ-C5/2-NA-DC

1

6

FAZ-C6/1-NA-DC-SP

FAZ-C6/2-NA-DC

7

FAZ-C7/1-NA-DC-SP

FAZ-C7/2-NA-DC

1

8

FAZ-C8/1-NA-DC-SP

FAZ-C8/2-NA-DC

10

FAZ-C10/1-NA-DC-SP

FAZ-C10/2-NA-DC

1

13

FAZ-C13/1-NA-DC-SP

FAZ-C13/2-NA-DC

15

FAZ-C15/1-NA-DC-SP

FAZ-C15/2-NA-DC

1

16

FAZ-C16/1-NA-DC-SP

FAZ-C16/2-NA-DC

1

20

FAZ-C20/1-NA-DC-SP

FAZ-C20/2-NA-DC

25

FAZ-C25/1-NA-DC-SP

FAZ-C25/2-NA-DC

1

30

FAZ-C30/1-NA-DC-SP

FAZ-C30/2-NA-DC

32

FAZ-C32/1-NA-DC-SP

FAZ-C32/2-NA-DC

1

35

FAZ-C35/1-NA-DC-SP

FAZ-C35/2-NA-DC

40

FAZ-C40/1-NA-DC-SP

FAZ-C40/2-NA-DC

1

Two-Pole

1

Note
1 Option for single packaging on single-pole C curves only; add
suffix SP when ordering.

1
1
V4-T1-54

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

1.2

Accessories

Contact

1
FAZ-NA UL 489 Breakers

FAZ-NA UL 489 Breakers, continued

Description

Catalog Number

Description

Two-pole contact or auxiliary
contact/trip indicating contact

Z-NHK 1

Busbar

Catalog Number

Busbar—single-pole, 6 terminals 2345 Z-SV/UL-16/1P-1TE/6
Busbar—single-pole, 12 terminals 2345 Z-SV/UL-16/1P-1TE/12
Busbar—single-pole, 18 terminals 2345 Z-SV/UL-16/1P-1TE/18
Busbar—two-pole, 6 terminals 2345

Z-SV/UL-16/2P-2TE/12

Busbar—two-pole, 18 terminals 2345

Z-SV/UL-16/2P-2TE/18

Busbar—three-pole, 6 terminals 2345

Z-SV/UL-16/3P-3TE/6

Busbar—two-pole, 12 terminals

Auxiliary Contact

Auxiliary contact

Z-SV/UL-16/2P-2TE/6

2345

Busbar—three-pole, 12 terminals 2345 Z-SV/UL-16/3P-3TE/12

Z-IHK-NA

Busbar—three-pole, 18 terminals 2345 Z-SV/UL-16/3P-3TE/18
Busbar Shroud

Three-pole busbar shroud

1
1
1
1
1
1
1
1

ZV-BS-UL

1
1
Extension Terminal
Shunt Trip

Shunt trip 110–415 Vac

FAZ-XAA-NA110-415VAC

Shunt trip 12–110 Vac

FAZ-XAA-NA12-110VAC

Extension terminal—
35 mm2 (2–14 AWG)

1

Z-EK/35/UL

1
1
1

Padlock Hasp

Padlock hasp

1

IS/SPE-1TE
Bus Connector

Bus connector—conductors up to
50 mm2 (~1/0 AWG)

1

Z-EB/50/UL

1
Notes
1 Voltage of FAZ-NA circuit breaker is limited to 300V with this auxiliary contact installed.
2 Do not cut commoning link.
3 A maximum of three commoning links may be used in conjunction. Each breaker connected to
the commoning link must have the same number of poles for proper use.
4 Not for use with ring-tongue circuit breakers.
5 Bus may be center fed for high current capacity.

1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-55

1.2
1
1
1
1
1
1
1
1

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Tripping Signal Switch Z-NHK, Z-IHK-NA
●
Design according to IEC/EN 60947-5-1, IEC/EN 62019
●
Field installable
●
The specified minimum voltages are per contact—take into
account particularly in case of series connection
●
Self-cleaning contacts
●
Contact material and design particularly suitable for extra
low voltage
●
Z-NHK: the function of one of the two change-over
contacts can be switched from “auxiliary switch” to
“tripping signal switch”
●
Tripping signal contact transmits message of electric tripping,
not mechanical switch-off
●
Test key for contact function “electrical tripping”
●
Z-IHK-NA: will allow for > 480Y/277 Vac rating

1

Connection Diagram
Z-IHK-NA

Z-NHK
4.14/4.12

13

4.11

14
22
1.11
Same Polarity

1.14
1.12

Busbar Connection Example

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-56

21

4.12/4.14

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

1.2

Technical Data and Specifications
Trip Curve Chart
Eaton FAZ-NA branch circuit
breakers are available with
“B,” “C” and “D” tripping
characteristics. B-curve
devices are suitable for
applications where low
levels of inrush current
are expected.
C-curve devices are suitable
for applications where
medium levels of inrush
current are expected.
Applications include small
transformers, lighting, pilot
devices, control circuits and
coils. C-curve devices provide
a medium magnetic trip point.

1
Tripping Characteristics

1

D-curve devices are suitable
for applications where high
levels of inrush current are
expected. The high magnetic
trip point prevents nuisance
tripping in high inductive
applications such as motors,
transformers and power
supplies.

1
1
1
1

Eaton FAZ-NA devices are
current limiting, which means
they interrupt fault currents
within one half cycle of the
fault. Current limiting devices
offer superior protection by
reducing peak let-through
current and energy.

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-57

1.2
1
1

Connection Diagrams

UL 489 DIN Rail Miniature Circuit Breakers

Miniature Circuit Breakers FAZ-NA Technical Data
Description

Single-Pole

Rated voltage FAZ-NA
UL/CSA

1
1
1
Two-Pole

Specification

Electrical
Design according to

1

1

Miniature Circuit Breakers and Supplementary Protectors

UL 489, CSA C22.2 No.5, IEC 60947-2
10 kAIC at 277/480V from 0.5A to 32A
14 kAIC at select amperages
B and C Curves (15–25A), D Curve (13–20A)

UL/CSA

10 kAIC at 240 Vac for 35A and 40A

UL/CSA

10 kAIC at 48 Vdc per pole

IEC 947-2

15 kAIC at 240/415 Vac

Rated voltage FAZ-NA-DC
UL/CSA

10 kAIC at 125 Vdc per pole (two poles maximum)
10 kAIC at 250 Vdc with two poles connected in series

1

Rated frequency

1

Characteristic

B, C, D

Endurance

≥ 20,000 operations

1

Line voltage connection

Suitable for reverse feed

1

Frame size

45 mm

Device height

105 mm

Device width

17.7 mm per pole

Terminal protection

Finger and hand touch safe according to BGV A3, OVE-EN 6

1

50/60 Hz

Mechanical

Three-Pole

1
1
1
1
1

Mounting

Quick fastening with two lock-in positions on IEC/EN 60715

Upper and lower terminals

Open mouth/lift terminals

Terminal capacity

One wire: AWG 18–6
Two wires: AWG 18–10

Terminal fastening torque

AWG 18–21: 21 lb-in
AWG 10–8: 25 lb-in
AWG 6: 36 lb-in

Mounting

Independent of position

Calibration temperature
UL 489, CSA C22.2 No.5

1

IEC 60947-2

40°C
30°C

1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-58

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.2

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Power Loss at ln
Characteristic B

Characteristic C

1

Characteristic D

Single-Pole

Two-Pole

Three-Pole

Single-Pole

Two-Pole

Three-Pole

Single-Pole

Two-Pole

Three-Pole

In [A]

P [W]

P [W]

P [W]

P [W]

P [W]

P [W]

P [W]

P [W]

P [W]

0.5

—

—

—

1.6

3.2

4.7

1.6

3.2

4.8

1.0

1.1

2.2

3.4

1.1

2.2

3.4

0.8

1.5

2.3

1.5

2.2

4.4

6.6

1.3

2.6

3.9

1.0

2.1

3.1

2.0

1.4

2.8

4.3

1.4

2.8

4.3

1.0

2.1

3.1

3.0

2.1

4.2

6.4

1.2

2.4

3.6

1.2

2.4

3.6

4.0

1.4

2.9

4.3

1.4

2.9

4.3

1.4

2.9

4.3

5.0

1.8

3.7

5.5

1.9

3.7

5.6

1.5

2.9

4.4

6.0

1.7

3.5

5.2

1.2

2.3

3.5

1.2

2.3

3.5

7.0

2.0

4.0

6.0

1.4

2.8

4.3

1.4

2.8

4.3

8.0

2.0

3.9

5.9

1.4

2.8

4.2

1.2

2.4

3.7

10.0

1.8

3.6

5.3

1.8

3.6

5.3

1.5

3.0

4.5

13.0

2.4

4.7

7.1

2.4

4.7

7.1

2.0

4.1

6.1

15.0

1.9

3.8

5.6

1.9

3.8

5.6

1.5

3.1

4.6

16.0

2.1

4.3

6.4

2.1

4.3

6.4

1.7

3.5

5.2

20.0

2.9

5.8

8.7

2.9

5.8

8.7

1.8

3.7

5.5

25.0

3.1

6.2

9.3

3.1

6.2

9.3

2.6

5.1

7.7

30.0

3.0

6.0

9.0

3.0

6.0

9.0

2.7

5.4

8.1

32.0

3.4

6.8

10.2

3.4

6.8

10.2

3.1

6.2

9.3

35.0

4.0

8.1

12.1

3.7

7.4

11.0

3.8

7.6

11.3

40.0

4.0

8.1

12.1

4.0

8.1

12.1

3.9

7.8

11.6

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-59

1.2
1
1

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Let-Through Energy
Characteristic B (1–32A), 277V

Characteristic B (35–40A), 240V

Characteristic C (0.5–32A), 277V

Characteristic C (40A), 240V

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-60

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Characteristic D (0.5–32A), 277V

1.2

Characteristic D (40A), 240V

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-61

1.2
1

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Influence of Ambient Temperature T on Load Carrying Capacity
Device Market
Current Rating In
(A) at 40°C

15°C

20°C

25°C

30°C

40°C

50°C

55°C

60°C

1

0.5

0.6

0.5

0.5

0.5

0.5

0.5

0.5

0.5

1.0

1.1

1.1

1.1

1.0

1.0

1.0

0.9

0.9

1

1.5

1.7

1.6

1.6

1.6

1.5

1.4

1.4

1.4

1

2.0

2.2

2.2

2.1

2.1

2.0

1.9

1.9

1.8

3.0

3.3

3.2

3.2

3.1

3.0

2.9

2.9

2.8

1

4.0

4.4

4.3

4.2

4.2

4.0

3.8

3.8

3.7

5.0

5.5

5.4

5.3

5.2

5.0

4.8

4.7

4.6

1

6.0

6.6

6.5

6.4

6.2

6.0

5.8

5.6

5.5

7.0

7.7

7.6

7.4

7.3

7.0

6.7

6.6

6.4

8.0

8.8

8.6

8.5

8.3

8.0

7.7

7.5

7.4

1

10.0

11.0

10.8

10.6

10.4

10.0

9.6

9.4

9.2

13.0

14.3

14.0

13.8

13.5

13.0

12.5

12.5

12.0

1

15.0

16.5

16.2

15.9

15.6

15.0

14.4

14.1

13.8

16.0

17.6

17.3

17.0

16.6

16.0

15.4

15.0

14.7

1

20.0

22.0

21.6

21.2

20.8

20.0

19.2

18.8

18.4

1

25.0

27.5

27.0

26.5

26.0

25.0

24.0

23.3

23.0

30.0

33.0

32.4

31.8

31.2

30.0

28.8

28.2

27.6

32.0

35.2

34.6

33.9

33.3

32.0

30.7

30.1

29.4

40.0

44.0

43.2

42.4

41.6

40.0

38.4

37.6

36.8

1

1

1

In (A) at Higher Ambient Temperature

1

Load Carrying Capacity of Adjoining Miniature
Circuit Breakers

1

1.00

1
1
1

Load Factor KT [I/IN]

1

Rated Diversity Factor

1

1

0.90

0.80

0.70
1

1

2

3

4

5

6

Number of Circuit Breakers

1
1

Ambient Temperature T [°C]
Maximum Load IL at ambient temperature T: IL (T) = IN KT(T)

1
1
1
1
1
1
V4-T1-62

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

7

8

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Z-NHK

1.2

Contact and Auxiliary Contact
Description

Z-NHK

Z-IHK-NA

2CO

1NO + 1NC

1
1

Electrical
Contact function

Z-IHK-NA

Rated voltage

230V

250V

Frequency

50/60 Hz

50/60 Hz

Rated current

2A

6A

1
1

Rated thermal current Ith

2A

6A

Utilization category AC13
Rated operational current Ie

1

3A/250 Vac

3A/250 Vac

Utilization category AC15
Rated operational current Ie

1

2A/250 Vac

2A/250 Vac

Utilization category DC12
Rated operational current Ie

1

0.5A/110 Vdc

0.5A/110 Vdc
0.25A/220 Vdc

1

Rated insulation voltage UI

250 Vac

250 Vac

Minimum operational voltage per contact Umin

5 Vdc

5 Vdc

1

Minimum operational current Imin

10 mA DC

10 mA AC/DC

Rated peak withstand voltage Uimp (1.2/50μ)

2.5 kV

4 kV

Conditional short-circuit current Ik with backup fuse 6A

1 kA

1 kA

Max. backup fuse, overload and short circuit

6A gL

—

1
1
1

Mechanical
Tripping indicator “electrical tripping”

Blue/white

—

Frame size

45 mm

45 mm

Device height

80 mm

80 mm

Device width

8.8 mm (0.5MU)

8.8 mm (0.5MU)

Mounting

Onto switching device

—

1
1
1
1

Degree of protection, built-in

IP40

IP40

Terminal protection

Finger and hand touch safe
According to BGV A3, ÖVE-EN 6

Finger and hand touch safe
According to BGV A3, ÖVE-EN 6

1

Terminals

Lift terminals

Lift terminals

Terminal capacity

20–14 AWG

0.5–2.5 mm2

1

Terminal screws

M3 (Posidrive Z0)

M3 (Posidrive Z0)

Fastening torque of terminal screws

7 lb-in

Max. 1.2 Nm

1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-63

1.2
1
1
1
1

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Shunt trip release FAZ-XAA-NA
●
Remote release for subsequent mounting onto FAZ-NA/RT
●
Additional installation of standard auxiliary switch is possible
●
Position indicator red–green
Connection Diagram
1

Shunt Trip Release FAZ-XAA-NA
Description

FAZ-XAA-NA12-110VAC

FAZ-XAA-NA110-415VAC

Can be
mounted onto

FAZ-NA / FAZ-NA-DC /
FAZ-RT

FAZ-NA / FAZ-NA-DC /
FAZ-RT

Operational
voltage range

12–110 Vac
12–60 Vdc

110–415 Vac
110–230 Vdc

Frequency

50/60 Hz

50/60 Hz

Electrical

1
1

2

1
1

Mechanical
Frame size

45 mm

45 mm

1

Device height

105 mm

105 mm

Device width

17.5 mm

17.5 mm

1

Mounting

Quick fastening with two lock-in positions on EN 50022

1

Terminal protection

Degree of protection, built-in IP40

1
1
1
1
1
1
1

Connection Diagrams
Three-Pole Busbar

Open mouthed/lift

Open mouthed/lift

Terminal capacity
One and two wires

18–10 AWG

18–10 AWG

Busbar Block UL 489 (Pin)
Description

UL 489

IEC/EN 60947-2

Rated operational voltage

480/277 Vac
96 Vdc

—

Rated frequency

50/60 Hz

—

Rated voltage

480 Vac

690 Vac

Electrical

1
Two-Pole Busbar

1
1
1

Terminals

Busbar block UL 489 (pin)
●
Tested according to UL 489
●
Do not cut
●
Extension terminal 35 mm2 Z-EK/35/UL for copper conductors
●
Incoming terminal 50 mm2 Z-EB/50/UL
●
For covering of not used pins, use busbar tag shrouds ZV-BS-UL

1
1

IP40

Finger and hand touch safe according to BGV A3, ÖVE-EN 6

Single-Pole Busbar

1
1

Overvoltage category

—

III

Rated impulse withstand voltage Uimp

—

9.5 kV

Rated current

80A at 40°C

80A at 30°C

Rated conditional short-circuit current AC with 350A gG

—

15 kA

Short-circuit current

10 kA

—

Mechanical
Busbar cross section

—

16 mm2 Cu

Flame class according to UL 94

V0

—

Pollution degree

—

2

1

Comparative tracking index

—

CTI 600

Minimum clearance (internal/external)

—

> 9.5/25.4 mm

1

Minimum creepage distance (internal/external)

—

> 12.7/50.8 mm

Resistance to climatic conditions

—

According to
DIN/EN 60068

1
1
V4-T1-64

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.2

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Application Guidelines

1

Example of UL 489 and UL 1077 Application

1
1

UL 489
Breaker

1
1
1

UL 489
Branch

UL 1077

Internal Receptacle

1

External
Receptacle

1
1

Electronics

1

UL 489
Branch

UL 1077
Other
Sensitive
Devices

External
Motor

1

M

1

UL 489
Branch

1

UL 489
Branch

UL 1077

HACR

External
Motor

1

M

1
1

Motor
Controller

1
1
1

Example of UL 489 and UL 1077 Application

1

UL 489 circuit breakers

1

Used for branch circuit protection, internal/external receptacles, external motors and HACR equipment
(heating, air conditioning and refrigeration).

1

UL 1077 supplementary protectors

1

Used for overcurrent protection within appliances or electrical equipment, where branch circuit protection
is already provided or not required.

1

Note: UL 4 89 devices can be used in place of UL 1077; UL 1077 devices cannot be used in place of UL 489.

1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-65

1.2
1
1

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Dimensions
Approximate Dimensions in Inches (mm)
Lockout Attachment—IS/SPE-ITE

Miniature Circuit Breakers

1

Single-Pole

Two-Pole

Three-Pole

1
1
1

4.13
(105.0)

1

4.13
(105.0)

1
1

.70 .70
(17.7) (17.7)
2.09
(53.1)

.70
(17.7)
1.39
(35.3)

.70
(17.7)

1

4.13
(105.0)

Accessories

1

Z-SV/UL-16/6

ZV-BS-UL

Z-SV/UL-18...12

1
1
1
1
1
1

Z-EK/35/UL

Z-SV/UL-16.../18

1
1
1
1
1
1

Z-EK/35/UL

Z-EB/50/UL

1

Description

UL 489

1

Ue
f

IEC/EN 60947-2

Description

UL 489

IEC/EN 60947-2

480 Vac/96 Vdc

240/415 Vac

Ue

480 Vac/96 Vdc

240/415 Vac

50/60 Hz

50/60 Hz

f

50/60 Hz

50/60 Hz

Uimp

—

9.5 kV

Uimp

—

9.5 kV

Ie

80A at 40°C

80A at 30°C

Ie

115A at 40°C

160A at 30°C

1

#2–14 AWG 60/75°C Cu

2.5–35 mm2 Cu

#1–14 AWG 60/75°C Cu

1.5–50 mm2 Cu

1

0.56 in

14 mm

0.56 in

14 mm

1

1
1
V4-T1-66

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

1.2

Contents

WMZ Circuit Breakers

Description
FAZ-NA Circuit Breakers . . . . . . . . . . . . . . . . . . . .
WMZ Circuit Breaker
Standards and Certifications . . . . . . . . . . . . . .
Catalog Number Selection . . . . . . . . . . . . . . . .
Product Selection . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page
V4-T1-49
V4-T1-68
V4-T1-69
V4-T1-70
V4-T1-72
V4-T1-73
V4-T1-80

1
1
1
1
1
1
1
1

Optimum and Efficient Protection for Every Application

1
1
1

WMZ Circuit Breaker
Product Overview

Features

Optimum product quality,
tested reliability and safety
stand for best protection of
personnel, installations and
plant. Eaton’s WMZ DIN rail
mountable circuit breaker is
designed for use in branch
service applications.

●

●

●

Application Description
Feeder and branch circuit
protection for:
●

●
●

●

●
●
●
●
●
●
●

Convenience receptacle
circuits (internal/external)
Motor control circuits
Load circuits leaving the
equipment (external)
HACR internal/external
equipment (heating, air
conditioning, refrigeration)
PLC I/O points
Computers
Power supplies
Control instrumentation
Relays
UPS
Power conditioners

●

●

●

●

●

●

Complete range of UL 489
listed DIN rail mounted
miniature circuit breakers
up to 40A current rating
Standard ratings of 10 kAIC
at 277/480 Vac
Select amperages available
at 14 kAIC at 277/480 Vac
and 10 kAIC at125 Vdc
Current limiting design
provides fast short-circuit
interruption that reduces
the let-through energy,
which can damage
the circuit
Suitable for branch circuit
device protection
Thermal-magnetic
overcurrent protection
●
Two levels of shortcircuit protection,
categorized by C and
D curves
Trip-free design—breaker
can not be defeated by
holding the handle in the
ON position
Captive screws cannot
be lost
SWD (switching duty)—
suitable for switching
fluorescent lighting loads
(In d 20A)

●

●

●

●

●

●
●

1

For use in applications for
which UL 1077 or CSA
C22.2 No.235 are also
allowed
Field-installable shunt trip
and auxiliary switch
subsequent mounting
Separate version for ringtongue connection (Type
WMZT….T), terminal
screws can be removed
(on both sides)
Module width of only
17.7 mm (per pole)
Contact Position Indicator
(red/green)
Easy installation on DIN rail
Possibility for sealing the
toggle in ON or OFF
position

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-67

1.2

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Standards and Certifications

1
1

Device Printing on Front and Side
Installation options

1

These branch circuit breakers
are available in two terminal
configurations: standard box
terminals that accept multiple
conductors and ring-tongue
terminals, ideally suited to
demanding requirements of
the semi-conductor industry.

1
1
1

All breakers mount on
standard 35 mm DIN rail.
Bus connectors and feeder
terminal facilitate mounting
and wiring of multiple
miniature circuit breaker
arrays in control panel
assemblies. These circuit
breakers can also be
reverse feed.

1
1
1
1
1

UL 489
●
Standard for molded case
circuit breakers (MCCB) for
feeder and branch circuit
protection
●
Products meet the
requirements of the
National Electrical Code®
(NEC)
Powerful Offering for Machine
and System Builders
The WMZ is available with
C and D characteristics in
accordance with UL 489,
CSA C22.2 No.5; UL 1077,
CSA C22.2 No.235 and
IEC 60947-2.

Conductor Type

1

Breaker Status
Indicator

1

Calibration
Temperature
UL/CSA

1

Rated Current

1
1
1

Rated Voltage
UL/CSA

Catalog Number

1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-68

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

CSA C22.2 No.5
●
Standard for molded case
circuit breakers for feeder
and branch circuit
protection (corresponds
closely to UL 489
Standard)
●
Products meet the
requirements of the
Canadian Electrical Code
(CEC)
●
These devices are RoHS
compliant

1.2

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Catalog Number Selection

1
WMZ T 1 C 16 T

1

Breaker Family
WMZ = WMZ UL
circuit breaker

1

Terminal
Breaker Type
T =10 kAIC
H =14 kAIC
D =10 kAIC/DC 12

Ampere Rating
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole 3

Protective Curve
C = C Curve (5–10X In)
D = D Curve (10–20X In) 3

X0 = 0.5A
01 = 1A
X1 = 1.5A
02 = 2A
03 = 3A
04 = 4A
05 = 5A
06 = 6A
07 = 7A
08 = 8A

10 = 10A
13 = 13A
15 = 15A
16 = 16A
20 = 20A
25 = 25A
30 = 30A
32 = 32A
40 = 40A

T = Ring terminals
[blank] = Standard box
terminals

1
1
1
1
1

Notes
1 Limited curve and ampere offerings.
2 125 Vdc for single-pole, 250 Vdc for two-pole in series.
3 Not offered for Type WMZD.

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-69

1.2

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

1

Product Selection

1

WMZT

1

Single-Pole

1

WMZT UL 489 Circuit Breakers—10 kAIC

Amperes

Single-Pole

Two-Pole

Three-Pole

Catalog
Number

Catalog
Number

Catalog
Number

1

0.5

WMZT1CX0

WMZT2CX0

WMZT3CX0

1

1

WMZT1C01

WMZT2C01

WMZT3C01

1.5

WMZT1CX1

WMZT2CX1

WMZT3CX1

2

WMZT1C02

WMZT2C02

WMZT3C02

3

WMZT1C03

WMZT2C03

WMZT3C03

4

WMZT1C04

WMZT2C00

WMZT3C04

5

WMZT1C05

WMZT2C05

WMZT3C05

6

WMZT1C06

WMZT2C06

WMZT3C06

7

WMZT1C07

WMZT2C07

WMZT3C07

8

WMZT1C08

WMZT2C08

WMZT3C08

10

WMZT1C10

WMZT2C10

WMZT3C10

1

13

WMZT1C13

WMZT2C13

WMZT3C13

15

WMZT1C15

WMZT2C15

WMZT3C15

1

16

WMZT1C16

WMZT2C16

WMZT3C16

20

WMZT1C20

WMZT2C20

WMZT3C20

25

WMZT1C25

WMZT2C25

WMZT3C25

1

30

WMZT1C30

WMZT2C30

WMZT3C30

32

WMZT1C32

WMZT2C32

WMZT3C32

1

40

WMZT1C40

WMZT2C40

WMZT3C40

1
1
1
1
1

Three-Pole

1

1
1

Single-Pole

Two-Pole

Three-Pole

Catalog
Number

Catalog
Number

Catalog
Number

C Curve with Ring-Tongue Terminals
(5–10X In Current Rating)

Two-Pole

Three-Pole

D Curve (10–20X In Current Rating)

1

WMZT UL 489 Circuit Breakers with
Ring-Tongue Terminals—10 kAIC

Amperes

C Curve (5–10X In Current Rating)

Two-Pole

Single-Pole

0.5

WMZT1CX0T

WMZT2CX0T

WMZT3CX0T

1

WMZT1C01T

WMZT2C01T

WMZT3C01T

1.5

WMZT1CX1T

WMZT2CX1T

WMZT3CX1T

2

WMZT1C02T

WMZT2C02T

WMZT3C02T

3

WMZT1C03T

WMZT2C03T

WMZT3C03T

4

WMZT1C04T

WMZT2C04T

WMZT3C04T

5

WMZT1C05T

WMZT2C05T

WMZT3C05T

6

WMZT1C06T

WMZT2C06T

WMZT3C06T

7

WMZT1C07T

WMZT2C07T

WMZT3C07T

8

WMZT1C08T

WMZT2C08T

WMZT3C08T

10

WMZT1C10T

WMZT2C10T

WMZT3C10T

13

WMZT1C13T

WMZT2C13T

WMZT3C13T

15

WMZT1C15T

WMZT2C15T

WMZT3C15T

16

WMZT1C16T

WMZT2C16T

WMZT3C16T

20

WMZT1C20T

WMZT2C20T

WMZT3C20T

25

WMZT1C25T

WMZT2C25T

WMZT3C25T

30

WMZT1C30T

WMZT2C30T

WMZT3C30T

32

WMZT1C32T

WMZT2C32T

WMZT3C32T

40

WMZT1C40T

WMZT2C40T

WMZT3C40T

0.5

WMZT1DX0

WMZT2DX0

1

WMZT1D01

WMZT2D01

WMZT3D01

D Curve with Ring-Tongue Terminals
(10–20X In Current Rating)

1.5

WMZT1DX1

WMZT2DX1

WMZT3DX1

0.5

WMZT1DX0T

WMZT2DX0T

WMZT3D02

1

WMZT1D01T

WMZT2D01T

WMZT3D01T

WMZT1DX1T

WMZT2DX1T

WMZT3DX1T

2

WMZT1D02

WMZT2D02

WMZT3DX0

WMZT3DX0T

3

WMZT1D03

WMZT2D03

WMZT3D03

1.5

1

4

WMZT1D04

WMZT2D04

WMZT3D04

2

WMZT1D02T

WMZT2D02T

WMZT3D02T

WMZT1D05

WMZT2D05

WMZT3D05

WMZT1D03T

WMZT2D03T

WMZT3D03T

1

5

3

6

WMZT1D06

WMZT2D06

WMZT3D06

4

WMZT1D04T

WMZT2D04T

WMZT3D04T

7

WMZT1D07

WMZT2D07

WMZT3D07

5

WMZT1D05T

WMZT2D05T

WMZT3D05T

WMZT3D08

6

WMZT1D06T

WMZT2D06T

WMZT3D06T

WMZT3D10

7

WMZT1D07T

WMZT2D07T

WMZT3D07T

WMZT1D08T

WMZT2D08T

WMZT3D08T

1

8

WMZT1D08

WMZT2D08

1

10

1

13

WMZT1D13

WMZT2D13

WMZT3D13

8

15

WMZT1D15

WMZT2D15

WMZT3D15

10

WMZT1D10T

WMZT2D10T

WMZT3D10T

16

WMZT1D16

WMZT2D16

WMZT3D16

13

WMZT1D13T

WMZT2D13T

WMZT3D13T

WMZT3D20

15

WMZT1D15T

WMZT2D15T

WMZT3D15T

WMZT3D25

16

WMZT1D16T

WMZT2D16T

WMZT3D16T

WMZT1D20T

WMZT2D20T

WMZT3D20T

1

20

1

25

1
1
1

WMZT1D10

WMZT1D20
WMZT1D25

WMZT2D10

WMZT2D20
WMZT2D25

30

WMZT1D30

WMZT2D30

WMZT3D30

20

32

WMZT1D32

WMZT2D32

WMZT3D32

25

WMZT1D25T

WMZT2D25T

WMZT3D25T

40

WMZT1D40

WMZT2D40

WMZT3D40

30

WMZT1D30T

WMZT2D30T

WMZT3D30T

32

WMZT1D32T

WMZT2D32T

WMZT3D32T

40

WMZT1D40T

WMZT2D40T

WMZT3D40T

Notes
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947.
Optional connections for ring-tongue terminals.

1
V4-T1-70

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

WMZH
Single-Pole

WMZD
WMZH UL 489 Circuit Breakers — 14 kAIC
Single-Pole
Amperes

Catalog
Number

Two-Pole
Catalog
Number

Single-Pole

Three-Pole

1
WMZD UL 489 Circuit Breakers—10 kAIC
at 125 Vdc Per Pole

Catalog
Number
Amperes

C Curve (5–10X In Current Rating)

Two-Pole

1.2

15

WMZH1C15

WMZH2C15

WMZH3C15

16

WMZH1C16

WMZH2C16

WMZH3C16

20

WMZH1C20

WMZH2C20

WMZH3C20

25

WMZH1C25

WMZH2C25

WMZH3C25

D Curve (10–20X In Current Rating)
13

WMZH1D13

WMZH2D13

WMZH3D13

15

WMZH1D15

WMZH2D15

WMZH3D15

16

WMZH1D16

WMZH2D16

WMZH3D16

20

WMZH1D20

WMZH2D20

WMZH3D20

Three-Pole

Single-Pole

Two-Pole

Catalog
Number

Catalog
Number

C Curve (5–10X In Current Rating)

Two-Pole

2

WMZD1C02

WMZD2C02

3

WMZD1C03

WMZD2C03

4

WMZD1C04

WMZD2C04

5

WMZD1C05

WMZD2C05

6

WMZD1C06

WMZD2C06

7

WMZD1C07

WMZD2C07

8

WMZD1C08

WMZD2C08

10

WMZD1C10

WMZD2C10

13

WMZD1C13

WMZD2C13

15

WMZD1C15

WMZD2C15

16

WMZD1C16

WMZD2C16

20

WMZD1C20

WMZD2C20

25

WMZD1C25

WMZD2C25

30

WMZD1C30

WMZD2C30

32

WMZD1C32

WMZD2C32

40

WMZD1C40

WMZD2C40

Notes
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947.
Optional connections for ring-tongue terminals.
Single-Pole

Amperes

Two-Pole

Three-Pole

Catalog
Number

Catalog
Number

Catalog
Number

Two-Pole

WMZH1C15T

WMZH2C15T

WMZH3C15T

16

WMZH1C16T

WMZH2C16T

WMZH3C16T

20

WMZH1C20T

WMZH2C20T

WMZH3C20T

25

WMZH1C25T

WMZH2C25T

WMZH3C25T

WMZH1D13T

WMZH2D13T

WMZH3D13T

15

WMZH1D15T

WMZH2D15T

WMZH3D15T

16

WMZH1D16T

WMZH2D16T

WMZH3D16T

20

WMZH1D20T

WMZH2D20T

WMZH3D20T

1
1
1
1
1
1
1
1
1
1

1
1
1
1
1

D Curve (10–20X In Current Rating)
13

1

1

C Curve (5–10X In Current Rating)
15

1

1

WMZH UL 489 Circuit Breakers with RingTongue Terminals
Single-Pole

1

1
1
1

Three-Pole

1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-71

1.2

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

1

Accessories

1

WMZ UL 489 Breakers
Description

Catalog Number

Two-pole contact or auxiliary contact/trip indicating contact

WMZSAUXTRIP

1

Auxiliary contact

WMZTAUX

Shunt trip 110–415 Vac

WMZTST415

1

Shunt trip 12–110 Vac

WMZTST110

Padlock hasp

WMZPLK

1

Busbar—single-pole, 6 terminals

WMZT1P6T

1

Busbar—single-pole, 12 terminals

WMZT1P12T

Busbar—single-pole, 18 terminals

WMZT1P18T

1

Busbar—two-pole, 6 terminals

WMZT2P6T

Busbar—two-pole, 12 terminals

WMZT2P12T

1

Busbar—two-pole, 18 terminals

WMZT2P18T

1

Busbar—three-pole, 6 terminals

WMZT3P6T

Busbar—three-pole, 12 terminals

WMZT3P12T

Busbar—three-pole, 18 terminals

WMZT3P18T

Three-pole busbar shroud

WMZT3PSHROUD

Extension terminal—35 mm2 (2–14 AWG)

WMZT35EXT

Bus connector—conductors up to 50 mm2 (~1/0 AWG)

WMZTBCON

1

1
1

Tripping Signal Switch WMZSAUXTRIP, WMZTAUX
●
Design according to IEC/EN 60947-5-1, IEC/EN 62019 and UL
●
Field installable
●
The specified minimum voltages are per contact—take into
account particularly in case of series connection
●
Self-cleaning contacts
●
Contact material and design particularly suitable for extra
low voltage
●
WMZSAUXTRIP: the function of one of the two change-over
contacts can be switched from “auxiliary switch” to “tripping
signal switch”
Attention: The voltage of the WMZT...circuit breaker is limited
to 300V with this auxiliary installed.
●

●
●

Tripping signal contact transmits message of electric tripping,
not mechanical switch-off
Test key for contact function “electrical tripping”
WMZTAUX: will allow for > 480Y/277 Vac rating

Connection Diagram
WMZTAUX

WMZSAUXTRIP
4.14/4.12

1

21

4.12/4.14

1

13

4.11

1
1

14

1

22
1.11
Same Polarity

1.14

1

1.12

1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-72

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.2

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Technical Data and Specifications
Trip Curve Chart
Eaton WMZ branch circuit
breakers are available with
“C” and “D” tripping
characteristics.
C-curve devices are suitable
for application where medium
levels of inrush current are
expected. Applications
include small transformers,
lighting, pilot devices, control
circuits and coils. C-curve
devices provide a medium
magnetic trip point.

1

Tripping Characteristics
D-curve devices are suitable
for applications where high
levels of inrush current are
expected. The high magnetic
trip point prevents nuisance
tripping in high inductive
applications such as motors,
transformers and power
supplies.
Eaton WMZ devices are
current limiting, which means
they interrupt fault currents
within one-half cycle of the
fault. Current limiting devices
offer superior protection by
reducing peak let-through
current and energy.

1
Tripping characteristic
acc. to UL 489
Conventional non-tripping
current
Int = 1.0 IN (T=40°)
Conventional tripping current
It = 1.35 IN: t < 1 h (T=25°)
2.0 IN: t = 12 – 120 s (T=25°)
Instantaneous tripping
acc. to IEC 60898-1
type C: 5 IN: t > 0.1 s
10 IN: t < 0.1 s
type D: 10 IN: t > 0.1 s
20 IN: t < 0.1 s

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-73

1.2
1
1

Connection Diagrams

1
1

Miniature Circuit Breakers WMZ Technical Data

Two-Pole

1
1
1
1
Three-Pole

1

Specification

Electrical
Design according to

UL 489, CSA C22.2 No.5, IEC 60947-2

Rated voltage WMZT
UL/CSA
UL/CSA
UL/CSA
IEC 947-2

10 kAIC at 277/480V from 0.5A to 32A
10 kAIC at 240 Vac for 40A
10 kAIC at 48 Vdc per pole
15 kAIC at 240/415 Vac

Rated voltage WMZD
UL/CSA

1

1

UL 489 DIN Rail Miniature Circuit Breakers

Description

Single-Pole

1

1

Miniature Circuit Breakers and Supplementary Protectors

10 kAIC at 125 Vdc per pole (two poles max.)
10 kAIC at 250 Vdc with two poles connected in series

Rated voltage WMZH
UL/CSA
IEC 947-2

14 kAIC at 277/480V at listed amperages
15 kAIC at 240/415 Vac

Rated frequency

50/60 Hz

Rated breaking capacity WMZT
UL/CSA
IEC 947-2

10 kA
15 kA

Rated breaking capacity WMZH
UL/CSA
IEC 947-2

14 kA
15 kA

Characteristic

C, D

Endurance

≥ 20,000 operations

Line voltage connection

Suitable for reverse feed

Mechanical

1
1
1
1
1

Frame size

45 mm

Device height

105 mm

Device width

17.7 mm per pole

Mounting

Quick fastening with two lock-in positions on
IEC/EN 60715

Upper and lower terminals

Open mouth/lift terminals

Terminal capacity

One wire

AWG 18–6

Two wires

AWG 8–10

Terminal fastening torque

AWG 18–21: 21 lb-in
AWG 10–8: 25 lb-in

1

AWG 6: 36 lb-in

1
1

Mounting

Independent of position

Calibration temperature
UL 489, CSA C22.2 No.5
IEC 60947-2

40°C
30°C

1
1
1
1
1
1
1
1
1
V4-T1-74

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

1.2

Power Loss at ln
Characteristic C

1

Characteristic D

Single-Pole

Two-Pole

Three-Pole

Single-Pole

Two-Pole

Three-Pole

In [A]

P [W]

P [W]

P [W]

P [W]

P [W]

P [W]

0.5

1.6

3.2

4.7

1.6

3.2

4.8

1.0

1.1

2.2

3.4

0.8

1.5

2.3

1.5

1.3

2.6

3.9

1.0

2.1

3.1

2.0

1.4

2.8

4.3

1.0

2.1

3.1

3.0

1.2

2.4

3.6

1.2

2.4

3.6

4.0

1.4

2.9

4.3

1.4

2.9

4.3

5.0

1.9

3.7

5.6

1.5

2.9

4.4

6.0

1.2

2.3

3.5

1.2

2.3

3.5

7.0

1.4

2.8

4.3

1.4

2.8

4.3

8.0

1.4

2.8

4.2

1.2

2.4

3.7

10.0

1.8

3.6

5.3

1.5

3.0

4.5

13.0

2.4

4.7

7.1

2.0

4.1

6.1

15.0

1.9

3.8

5.6

1.5

3.1

4.6

16.0

2.1

4.3

6.4

1.7

3.5

5.2

20.0

2.9

5.8

8.7

1.8

3.7

5.5

25.0

3.1

6.2

9.3

2.6

5.1

7.7

30.0

3.0

6.0

9.0

2.7

5.4

8.1

32.0

3.4

6.8

10.2

3.1

6.2

9.3

35.0

3.7

7.4

11.0

3.8

7.6

11.3

40.0

4.0

8.1

12.1

3.9

7.8

11.6

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-75

1.2

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

1

Let-Through Energy

1

Characteristic C (0.5–32A), 277V

Characteristic C (40A), 240V

Characteristic D (0.5–32A), 277V

Characteristic D (40A), 240V

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-76

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.2

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Influence of Ambient Temperature T on Load Carrying Capacity

1

Device Market
Current Rating In
(A) at 40°C

In (A) at Higher Ambient Temperature
15°C

20°C

25°C

30°C

40°C

50°C

55°C

60°C

0.5

0.6

0.5

0.5

0.5

0.5

0.5

0.5

0.5

1.0

1.1

1.1

1.1

1.0

1.0

1.0

0.9

0.9

1.5

1.7

1.6

1.6

1.6

1.5

1.4

1.4

1.4

2.0

2.2

2.2

2.1

2.1

2.0

1.9

1.9

1.8

3.0

3.3

3.2

3.2

3.1

3.0

2.9

2.9

2.8

4.0

4.4

4.3

4.2

4.2

4.0

3.8

3.8

3.7

5.0

5.5

5.4

5.3

5.2

5.0

4.8

4.7

4.6

6.0

6.6

6.5

6.4

6.2

6.0

5.8

5.6

5.5

7.0

7.7

7.6

7.4

7.3

7.0

6.7

6.6

6.4

8.0

8.8

8.6

8.5

8.3

8.0

7.7

7.5

7.4

10.0

11.0

10.8

10.6

10.4

10.0

9.6

9.4

9.2

13.0

14.3

14.0

13.8

13.5

13.0

12.5

12.5

12.0

15.0

16.5

16.2

15.9

15.6

15.0

14.4

14.1

13.8

16.0

17.6

17.3

17.0

16.6

16.0

15.4

15.0

14.7

20.0

22.0

21.6

21.2

20.8

20.0

19.2

18.8

18.4

25.0

27.5

27.0

26.5

26.0

25.0

24.0

23.3

23.0

30.0

33.0

32.4

31.8

31.2

30.0

28.8

28.2

27.6

32.0

35.2

34.6

33.9

33.3

32.0

30.7

30.1

29.4

40.0

44.0

43.2

42.4

41.6

40.0

38.4

37.6

36.8

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-77

1.2
1

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

WMZ UL 489 Auxiliary and Trip Indicating Contacts
Description

WMZSAUXTRIP

WMZTAUX

1NO + 1NC

1

Electrical

1

Contact function

2CO

Rated voltage

230V

250V

Frequency

50/60 Hz

50/60 Hz

Rated current

2A

6A

1
1

Rated thermal current Ith

2A

6A

Utilization category AC13 rated operational current Ie

3A/250 Vac

3A/250 Vac

Utilization category AC15 rated operational current Ie

2A/250 Vac

2A/250 Vac

1

Utilization category DC12 rated operational current Ie

0.5A/110 Vdc

0.5A/110 Vdc

1

Rated insulation voltage UI

250 Vac

1

Minimum operational voltage per contact Umin

5 Vdc

5 Vdc

Minimum operational current Imin

10 mA DC

10 mA AC/DC

1

1
1

0.25A/220 Vdc
250 Vac

Rated peak withstand voltage Uimp (1.2/50μ)

2.5 kV

4 kV

Conditional short-circuit current Ik with back-up fuse 6A

1 kA

1 kA

Max. back-up fuse, overload and short circuit

6A gL

—

Mechanical

1

Tripping indicator “electrical tripping”

Blue/white

—

1

Frame size

45.0 mm

45.0 mm

Device height

80.0 mm

80.0 mm

1

Device width

8.8 mm (0.5MU)

8.8 mm (0.5MU)

Mounting

Onto switching device

—

Degree of protection, built-in

IP40

IP40

Terminal protection

Finger and hand touch safe according to BGV A3, ÖVE-EN 6

Finger and hand touch safe according to BGV A3, ÖVE-EN 6

Terminals

Lift terminals

Lift terminals

1

Terminal capacity

20–14 AWG

0.5–2.5 mm2

Terminal screws

M3 (Pozidrive Z0)

M3 (Pozidrive Z0)

1

Fastening torque of terminal screws

7 lb-in

Max. 1.2 Nm

1
1

1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-78

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

1.2

Shunt Trip Release WMZTST
●
Remote release for subsequent mounting onto WMZT
●
Additional installation of standard auxiliary switch is possible
●
Position indicator red–green
Connection Diagram
1

1
1
1

Shunt Trip Release WMZTST
WMZTST110

WMZTST415

1

Can be mounted onto

WMZT/WMZH/WMZD

WMZT/WMZH/WMZD

1

Operational voltage range

12–110 Vac

110–415 Vac

12–60 Vdc

110–230 Vdc

50/60 Hz

50/60 Hz

1

Frame size

45.0 mm

45.0 mm

1

Device height

105.0 mm

105.0 mm

Device width

17.5 mm

17.5 mm

Mounting

Quick fastening with two lock-in positions on EN 50022

Degree of protection, built-in

IP40

Description
Electrical

2

Frequency

1

Mechanical

1
1

IP40

Terminal Protection

Finger and hand touch safe according to BGV A3, ÖVE-EN 6

Terminals

Open mouthed/lift

Open mouthed/lift

Terminal capacity 1 and 2 wires

18–10 AWG

18–10 AWG

1
1
1
1

Busbar Block UL 489 (Pin)
●
Tested according to UL 489
●
Do not cut
●
Extension terminal 35 mm2 WMZT35EXT for copper conductors
●
For covering of not used pins, use busbar tag shrouds WMZT3PSHROUD
Connection Diagrams
Three-Pole Busbar

1
1
1

Busbar Block UL 489 (Pin)
Description

UL 489

IEC/EN 60947-2

480/277 Vac

—

96 Vdc

—

Rated frequency

50/60 Hz

—

Rated voltage

—

690 Vac

1

Electrical
Rated operational voltage

Two-Pole Busbar

Single-Pole Busbar

Overvoltage category

—

III

Rated impulse withstand voltage Uimp

—

9.5 kV

Rated current

80A

80A

Rated conditional short-circuit current AC with 350A gG

—

15 kA

Short-circuit current

10 kA

—

Busbar cross section

—

16 mm2 Cu

Flame class according to UL 94

V0

—

1
1
1
1
1
1

Mechanical

Pollution degree

—

2

Comparative tracking index

—

CTI 600

Minimum clearance (internal/external)

—

> 9.5/25.4 mm

Minimum creepage distance (internal/external)

—

> 12.7/50.8 mm

Resistance to climatic conditions

—

According to DIN/
EN60068

1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-79

1.2
1
1
1

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

Dimensions
Approximate Dimensions in Inches (mm)
WMZ
Z-SV/UL-16/6

ZV-BS-UL

Z-SV/UL-18...12

1
1
1
1
1
1
1

Z-EK/35/UL

Z-SV/UL-16.../18

1
1
1
1
1
1
1
1

WMZT35EXT

Lockout Attachment
UL 489

IEC/EN 60947-2

1

# 2–14 AWG

2.5–35 mm2

1

60/75°C Cu

Cu

1
1
1
1

Description

0.56 in
Tested according to
UL 486A

14 mm
Tightening torque of
terminal screws

# 14 AWG

≥ 2.3 Nm

UL 486B

# 8–12 AWG

≥ 2.8 Nm

UL 486E

# 6–1 AWG

4 Nm

1
1
1
1
1
1
V4-T1-80

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers

1.2

Approximate Dimensions in Inches (mm)

1

Miniature Circuit Breakers WMZ

1

0.20
(5.0)

1
1
1

4.13
(105.0)

1

1.77
(45.0)

1
1

0.39
(10.0)

1
1

1.73
(44.0)

0.70
(17.7)

1

2.36
(60.0)

1
1

WMZ UL 489
0.20
(5.5)
0.35
(8.8)
3.15
(80.0)

1

2.08 (53.0)
1.73
(44.0)

1.77
(45.0)

0.39
(10.0)

1
1

2.82
(71.6)
1.77
(45.0)

3.78
(96.0)
1.73
(44.0)
2.36
(60.0)
WMZSAUXTRIP

1

2.36 (60.0)

0.22
(5.5)

1

0.35
(8.8)

1
1

WMZTAUX

1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-81

1.3
1

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Contents

FAZ Circuit Breakers

Description

1

FAZ Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . .
Catalog Number Selection . . . . . . . . . . . . . . . . .
Standards and Certifications . . . . . . . . . . . . . . .
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WMZS Circuit Breaker . . . . . . . . . . . . . . . . . . . . .

1
1
1
1

Optimum and Efficient Protection for Every Application

1
1
1
1
1

FAZ Circuit Breakers

1

Product Overview

Features

Optimum product quality,
tested reliability and safety
stand for best protection of
personnel, installations and
plant. Eaton’s FAZ DIN rail
mountable circuit breaker is
designed for use in control
panel applications.

●

Complete range of UL
1077 recognized DIN
rail mounted miniature
circuit breakers up to
63A current rating

●

Standard ratings of 10 kAIC
up to 277/480 Vac

●

Current limiting design
provides fast short-circuit
interruption that reduces
the let-through energy,
which can damage
the circuit

1
1
1
1
1
1
1
1
1

Powerful offering for machine
and system builders
The FAZ is available with B,
C, D, K, S, and Z characteristics
in accordance with UL 1077,
CSA C22.2 No.235 and IEC
60947-2. These devices are
CE marked.

Application Description
●
●

1

●

1

●

●

Supplementary protection
Control circuits
Lighting
Business equipment
Appliances

●

Suitable for supplementary
protection

●

Thermal-magnetic
overcurrent protection
●

Six levels of short-circuit
protection, categorized
by B, C, D, K, S, and
Z curves

●

Trip-free design—breaker
can not be defeated by
holding the handle in the
ON position

●

Captive screws cannot
be lost

●

Fulfill UL 1077, CSA C22.2
No.235 and also IEC
60947-2 Standard

●

Field-installable shunt trip
and auxiliary switch
subsequent mounting

●

Module width of only
17.7 mm (per pole)

●

Contact position indicator
(red/green)

●

Easy installation on DIN rail

●

Possibility for sealing
the toggle in ON or
OFF position

1
1
1
1
1
1
1
V4-T1-82

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Page
V4-T1-82
V4-T1-83
V4-T1-83
V4-T1-84
V4-T1-90
V4-T1-93
V4-T1-100
V4-T1-103

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Standards and Certifications
FAZ complies with the latest
national and international
standards.

Discover These Advanced Features

Captive Posidrive
terminal screws with
finger and back-ofhand protection (IP20)

Breakers install on
standard DIN rail

Available in one-, two-,
three-, four-pole, 1+N
and 3+N models

Trip-free design;
breaker cannot be
defeated by holding
the handle in the
ON position

Color-coded indicator
provides breaker
status for easy
troubleshooting

Breaker information
printed on the front of
the device for quick
identification

●

UL 1077, CSA C22.2
No. 235
●
Apply to supplementary
protectors intended for
use as overcurrent, or
overvoltage or
undervoltage protection
within an appliance or
other electrical
equipment where
branch circuit protection
is already provided, or is
not required

●
●

●

●

RoHS compliant
VDE compliant
●
Devices with B, C,
and D curves are
VDE compliant
CCC
●
Devices with B, C,
and D curves are
CCC compliant
ABS compliant

1
1
1
1
1
1
1
1
1
1
1

Catalog Number Selection

1

FAZ C 6 / 1 SP

1
Single Package

Breaker Family
FAZ = Supplementary
protector

Trip
Characteristics 1
B = 3–5X In
C = 5–10X In
D = 10–20X In
K = 8–12X In
S = 13–17X In
Z = 2–3X In

SP
Ampere Rating
0.5 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
10 =

0.5A
1A
2A
3A
4A
5A
6A
7A
8A
10A

13 = 13A
15 = 15A
16 = 16A
20 = 20A
25 = 25A
30 = 30A
32 = 32A
40 = 40A
50 = 50A
63 = 63A

Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole

4 = Single-pole
1N = Single-pole +
neutral
3N = Three-pole +
neutral

= Single packaging of singlepole curve B, C and D for
select amperes only
Blank = Standard packaging

1
1
1
1
1
1

Note
1 I = Rated current for instantaneous trip characteristics.
n

1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-83

1.3

Miniature Circuit Breakers and Supplementary Protectors

1

FAZ B curve (3–5X In current rating)
●
Designed for resistive or slightly inductive loads
●
Response time of instantaneous trip: 3–5X In current rating
●
UL recognized and CSA Certified as supplementary protectors
●
For international and domestic use (conform to IEC 60947-2)
●
UL file number 177451

1
1
1
1
1

Suitable for applications where protection against low-level
short-circuit faults in control wiring is desired. Instantaneous trip
is 3–5X continuous rating of device (In). Applications include PLC
wiring, business equipment, lighting, appliances and some
motors. Low magnetic trip point.

7200

1200
600

 2.55 I :
N

t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)

 Type B: 3 x I : t > 0.1 s
N
 Type B: 5 x I : t < 0.1 s
N

120
1

60
30
10
5
2
1

0.5
0.2
3

0.1
0.05

1

0.01

B

2

0.02

0.005

1

0.002
0.001

1

0.0005
1

2

3

4

5

6 7 8 9 10

15

20

30

40

50

I / IN

1
Single-Pole

1

B Curve (3–5X In Current Rating)—
Designed for Resistive or Slightly
Inductive Loads 1
Single-Pole 2

1
1

Two-Pole

Three-Pole

Catalog
Amperes Number

Catalog
Number

Catalog
Number

1

FAZ-B1/1-SP

FAZ-B1/2

FAZ-B1/3

2

FAZ-B2/1-SP

FAZ-B2/2

3
Two-Pole

1

4
5
6

1

7
8

1
1

Specified tripping current
IT = 1.45 x IN for t < 1 h

300

1

1

Specified non-tripping
current
INT = 1.13 x IN for t > 1 h

3600

1

1

1

1.45

Product Selection

t [sec]

1

1.13

UL 1077 DIN Rail Supplementary Protectors

Three-Pole

1

FAZ-B4/1-SP
FAZ-B5/1-SP
FAZ-B6/1-SP
FAZ-B7/1-SP
FAZ-B8/1-SP

FAZ-B3/2
FAZ-B4/2
FAZ-B5/2
FAZ-B6/2
FAZ-B7/2
FAZ-B8/2

B Curve (3–5X In Current Rating)—
Designed for Resistive or Slightly
Inductive Loads, continued 1
Single-Pole
+ Neutral

Three-Pole
+ Neutral

Catalog
Amperes Number

Catalog
Number

Catalog
Number

FAZ-B2/3

1

FAZ-B1/4

FAZ-B1/1N

FAZ-B1/3N

FAZ-B3/3

2

FAZ-B2/4

FAZ-B2/1N

FAZ-B2/3N

3

FAZ-B3/4

FAZ-B3/1N

FAZ-B3/3N

FAZ-B5/3

4

FAZ-B4/4

FAZ-B4/1N

FAZ-B4/3N

FAZ-B6/3

5

FAZ-B5/4

FAZ-B5/1N

FAZ-B5/3N

FAZ-B7/3

6

FAZ-B6/4

FAZ-B6/1N

FAZ-B6/3N

FAZ-B8/3

7

FAZ-B7/4

FAZ-B7/1N

FAZ-B7/3N

FAZ-B8/4

FAZ-B8/1N

FAZ-B8/3N

FAZ-B4/3

Four-Pole

Single-Pole + Neutral

10

FAZ-B10/1-SP

FAZ-B10/2

FAZ-B10/3

8

12

FAZ-B12/1-SP

FAZ-B12/2

FAZ-B12/3

10

FAZ-B10/4

FAZ-B10/1N

FAZ-B10/3N

FAZ-B13/3

12

FAZ-B12/4

FAZ-B12/1N

FAZ-B12/3N

FAZ-B15/3

13

FAZ-B13/4

FAZ-B13/1N

FAZ-B13/3N

FAZ-B16/3

15

FAZ-B15/4

FAZ-B15/1N

FAZ-B15/3N

FAZ-B20/3

16

FAZ-B16/4

FAZ-B16/1N

FAZ-B16/3N

FAZ-B25/3

20

FAZ-B20/4

FAZ-B20/1N

FAZ-B20/3N

FAZ-B25/4

FAZ-B25/1N

FAZ-B25/3N

13
15
16

1

FAZ-B3/1-SP

Four-Pole

20

FAZ-B13/1-SP
FAZ-B15/1-SP
FAZ-B16/1-SP
FAZ-B20/1-SP

FAZ-B15/2
FAZ-B16/2
FAZ-B20/2

1

30

FAZ-B30/1-SP

FAZ-B30/2

FAZ-B30/3

25

1

32

FAZ-B32/1-SP

FAZ-B32/2

FAZ-B32/3

30

FAZ-B30/4

FAZ-B30/1N

FAZ-B30/3N

40

FAZ-B40/1-SP

FAZ-B40/2

FAZ-B40/3

32

FAZ-B32/4

FAZ-B32/1N

FAZ-B32/3N

FAZ-B50/3

40

FAZ-B40/4

FAZ-B40/1N

FAZ-B40/3N

FAZ-B63/3

50

FAZ-B50/4

FAZ-B50/1N

FAZ-B50/3N

63

FAZ-B63/4

FAZ-B63/1N

FAZ-B63/3N

50
63

1

FAZ-B50/1-SP
FAZ-B63/1-SP

FAZ-B25/2

Three-Pole + Neutral

25

1

FAZ-B25/1-SP

FAZ-B13/2

FAZ-B50/2
FAZ-B63/2

Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering.

1
1
V4-T1-84

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.3

Miniature Circuit Breakers and Supplementary Protectors

Suitable for applications where medium levels of inrush current
are expected. Instantaneous trip is 5–10X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits and coils. Medium magnetic trip point.

1

1.45

7200

Specified non-tripping
current
INT = 1.13 x IN for t > 1 h

3600
1200

 Type C: 5 x I : t > 0.1 s
N

1

 Type C: 10 x I : t < 0.1 s
N

Specified tripping current
IT = 1.45 x IN for t < 1 h

600
300

1

120

1

60
30

1

10

t [sec]

FAZ C curve (5–10X In current rating)
●
Designed for inductive loads
●
Response time of instantaneous trip: 5–10X In current rating
●
UL recognized and CSA Certified as supplementary protectors
●
For international and domestic use (conform to IEC 60947-2)
●
UL file number 177451

1.13

UL 1077 DIN Rail Supplementary Protectors

5

1

2
1

1

0.5
0.2

1

2

0.1
1

0.05

C

1

0.02
0.01
0.005

1

0.002
0.001

1

0.0005
1

2

3

4

5

6 7 8 9 10

15

20

30

40

50

1

I / IN

Single-Pole

C Curve (5–10X In Current Rating)—
Designed Inductive Loads 1
Single-Pole 2

Two-Pole

Three-Pole

Two-Pole

Three-Pole

Catalog
Amperes Number

Catalog
Number

Catalog
Number

0.5

FAZ-C0.5/1-SP

FAZ-C0.5/2

FAZ-C0.5/3

1

FAZ-C1/1-SP

FAZ-C1/2

FAZ-C1/3

1.6

FAZ-C1.6/1-SP

FAZ-C1.6/2

FAZ-C1.6/3

2

FAZ-C2/1-SP

FAZ-C2/2

FAZ-C2/3

3

FAZ-C3/1-SP

FAZ-C3/2

FAZ-C3/3

4

FAZ-C4/1-SP

FAZ-C4/2

FAZ-C4/3

5

FAZ-C5/1-SP

FAZ-C5/2

FAZ-C5/3

6

FAZ-C6/1-SP

FAZ-C6/2

FAZ-C6/3

7

FAZ-C7/1-SP

FAZ-C7/2

FAZ-C7/3

8

FAZ-C8/1-SP

FAZ-C8/2

FAZ-C8/3

10

FAZ-C10/1-SP

FAZ-C10/2

FAZ-C10/3

13

FAZ-C13/1-SP

FAZ-C13/2

FAZ-C13/3

15

FAZ-C15/1-SP

FAZ-C15/2

FAZ-C15/3

16

FAZ-C16/1-SP

FAZ-C16/2

FAZ-C16/3

20

FAZ-C20/1-SP

FAZ-C20/2

FAZ-C20/3

25

FAZ-C25/1-SP

FAZ-C25/2

FAZ-C25/3

30

FAZ-C30/1-SP

FAZ-C30/2

FAZ-C30/3

32

FAZ-C32/1-SP

FAZ-C32/2

FAZ-C32/3

40

FAZ-C40/1-SP

FAZ-C40/2

FAZ-C40/3

50

FAZ-C50/1-SP

FAZ-C50/2

FAZ-C50/3

63

FAZ-C63/1-SP

FAZ-C63/2

FAZ-C63/3

Four-Pole

C Curve (5–10X In Current Rating)—
Designed Inductive Loads, continued 1
Single-Pole
+ Neutral

Three-Pole
+ Neutral

Catalog
Amperes Number

Catalog
Number

Catalog
Number

0.5

FAZ-C0.5/4

FAZ-C0.5/1N

FAZ-C0.5/3N

1

FAZ-C1/4

FAZ-C1/1N

FAZ-C1/3N

1.6

FAZ-C1.6/4

FAZ-C1.6/1N

FAZ-C1.6/3N

2

FAZ-C2/4

FAZ-C2/1N

FAZ-C2/3N

3

FAZ-C3/4

FAZ-C3/1N

FAZ-C3/3N

4

FAZ-C4/4

FAZ-C4/1N

FAZ-C4/3N

5

FAZ-C5/4

FAZ-C5/1N

FAZ-C5/3N

6

FAZ-C6/4

FAZ-C6/1N

FAZ-C6/3N

7

FAZ-C7/4

FAZ-C7/1N

FAZ-C7/3N

8

FAZ-C8/4

FAZ-C8/1N

FAZ-C8/3N

10

FAZ-C10/4

FAZ-C10/1N

FAZ-C10/3N

13

FAZ-C13/4

FAZ-C13/1N

FAZ-C13/3N

15

FAZ-C15/4

FAZ-C15/1N

FAZ-C15/3N

16

FAZ-C16/4

FAZ-C16/1N

FAZ-C16/3N

20

FAZ-C20/4

FAZ-C20/1N

FAZ-C20/3N

25

FAZ-C25/4

FAZ-C25/1N

FAZ-C25/3N

30

FAZ-C30/4

FAZ-C30/1N

FAZ-C30/3N

32

FAZ-C32/4

FAZ-C32/1N

FAZ-C32/3N

40

FAZ-C40/4

FAZ-C40/1N

FAZ-C40/3N

50

FAZ-C50/4

FAZ-C50/1N

FAZ-C50/3N

63

FAZ-C63/4

FAZ-C63/1N

FAZ-C63/3N

Four-Pole

Single-Pole + Neutral

Three-Pole + Neutral

Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering.
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-85

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1.3
1
1
1
1
1

Suitable for applications where high levels of inrush current are
expected. Instantaneous trip is 10–20X rating of device (In). The
high magnetic trip point prevents nuisance tripping in high
inductive applications such as motors, transformers and
power supplies.

1.45

FAZ D curve (10–20X In current rating)
●
Designed for highly inductive loads
●
Response time of instantaneous trip: 10–20X In current rating
●
UL recognized and CSA Certified as supplementary protectors
●
For international and domestic use (conform to IEC 60947-2)
●
UL file number 177451

1.13

UL 1077 DIN Rail Supplementary Protectors

7200

Specified non-tripping
current
INT = 1.13 x IN for t > 1 h

3600
1200

Specified tripping current
IT = 1.45 x IN for t < 1 h

600
300

1

60
30
10
5
2
1

0.2
3

0.1

2

0.05

1

D

0.02
0.01
0.005

1

0.002
0.001

1

0.0005
1

2

3

4

1

5

6 7 8 9 10

15

20

30

40

50

I / IN

1
Single-Pole

D Curve (10–20X In Current Rating)—
Designed for Inductive Loads 1
Single-Pole 2

1

Catalog
Amperes Number

1
1
Two-Pole

1

FAZ-D1/1-SP

FAZ-D1/3

3

FAZ-D3/1-SP
FAZ-D4/1-SP

FAZ-D2/2
FAZ-D3/2
FAZ-D4/2

FAZ-D3/3

FAZ-D5/3

6

FAZ-D6/1-SP

FAZ-D6/2

FAZ-D6/3

13
15
16

FAZ-D8/1-SP
FAZ-D10/1-SP
FAZ-D13/1-SP
FAZ-D15/1-SP
FAZ-D16/1-SP

FAZ-D7/2
FAZ-D8/2
FAZ-D10/2
FAZ-D13/2
FAZ-D15/2
FAZ-D16/2

FAZ-D10/3
FAZ-D13/3

1

FAZ-D20/2

FAZ-D20/3

25

FAZ-D25/1-SP

FAZ-D25/2

FAZ-D25/3

1

30
32

1

40
50 3

1

63 3

1

FAZ-D32/1-SP
FAZ-D40/1-SP
FAZ-D50/1-SP
FAZ-D63/1-SP

FAZ-D32/2
FAZ-D40/2
FAZ-D50/2
FAZ-D63/2

Three-Pole + Neutral

FAZ-D16/3

FAZ-D20/1-SP

FAZ-D30/2

Single-Pole + Neutral

FAZ-D8/3

20

FAZ-D30/1-SP

Catalog
Amperes Number

FAZ-D7/3

FAZ-D15/3

D Curve (10–20X In Current Rating)—
Designed for Inductive Loads, continued 1
Four-Pole

FAZ-D4/3

FAZ-D5/2

FAZ-D7/1-SP

Four-Pole

FAZ-D2/3

FAZ-D5/1-SP

10

1

FAZ-D2/1-SP

FAZ-D1/2

5

8

Three-Pole

Catalog
Number
FAZ-D0.5/3

7

1

Three-Pole

Catalog
Number

FAZ-D0.5/1-SP FAZ-D0.5/2

4

1

Two-Pole

0.5

2

1

1

 Type D: 20 x I : t < 0.1 s
N

0.5

1

1

t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)

 Type D: 10 x I : t > 0.1 s
N

1

1

1

 2.55 I :
N

120

t [sec]

1

Miniature Circuit Breakers and Supplementary Protectors

FAZ-D30/3
FAZ-D32/3
FAZ-D40/3
FAZ-D50/3
FAZ-D63/3

Single-Pole
+ Neutral

Three-Pole
+ Neutral

Catalog
Number

Catalog
Number

0.5

FAZ-D0.5/4

FAZ-D0.5/1N

FAZ-D0.5/3N

1

FAZ-D1/4

FAZ-D1/1N

FAZ-D1/3N

2

FAZ-D2/4

FAZ-D2/1N

FAZ-D2/3N

3

FAZ-D3/4

FAZ-D3/1N

FAZ-D3/3N

4

FAZ-D4/4

FAZ-D4/1N

FAZ-D4/3N

5

FAZ-D5/4

FAZ-D5/1N

FAZ-D5/3N

6

FAZ-D6/4

FAZ-D6/1N

FAZ-D6/3N

7

FAZ-D7/4

FAZ-D7/1N

FAZ-D7/3N

8

FAZ-D8/4

FAZ-D8/1N

FAZ-D8/3N

10

FAZ-D10/4

FAZ-D10/1N

FAZ-D10/3N

13

FAZ-D13/4

FAZ-D13/1N

FAZ-D13/3N

15

FAZ-D15/4

FAZ-D15/1N

FAZ-D15/3N

16

FAZ-D16/4

FAZ-D16/1N

FAZ-D16/3N

20

FAZ-D20/4

FAZ-D20/1N

FAZ-D20/3N

25

FAZ-D25/4

FAZ-D25/1N

FAZ-D25/3N

30

FAZ-D30/4

FAZ-D30/1N

FAZ-D30/3N

32

FAZ-D32/4

FAZ-D32/1N

FAZ-D32/3N

40

FAZ-D40/4

FAZ-D40/1N

FAZ-D40/3N

50 c

FAZ-D50/4

FAZ-D50/1N

FAZ-D50/3N

63 c

FAZ-D63/4

FAZ-D63/1N

FAZ-D63/3N

Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering.
3 IEC 60947-2 only.

1
1
V4-T1-86

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1

1.13
1.45

FAZ K curve (8–12X In current rating)
●
Designed for motors, transformers and upstream electronics
●
Response time of instantaneous trip: 8–12X In current rating
●
UL recognized and CSA Certified as supplementary protectors
●
For international and domestic use (conform to IEC 60947-2)
●
UL file number 177451

7200
3600

Specified
non-tripping current
Int = 1.05 u In
for t > 1 h
Specified
tripping current
It = 1.30 u In
for t < 1 h

1200
600
300
120
60
30

Suitable for applications where medium levels of inrush current
are expected. Instantaneous trip is 8–12X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits and coils. Medium magnetic trip point.

1
1
1
1

t (sec)

10
5

1

2
1
0.5

1

K

0.2
0.1
0.05

1
1

0.02
0.01
0.005

1

0.002
0.001
0.0005
1

2

3

4 5 6 7 8 9 10 15 20

1

30 40 50

1

U-rated Current

Single-Pole

K Curve (8–12X In Current Rating)—
Designed for Inductive Loads 12
Two-Pole

Three-Pole

Catalog
Amperes Number

Catalog
Number

Catalog
Number

0.5

FAZ-K0.5/1

FAZ-K0.5/2

FAZ-K0.5/3

1

FAZ-K1/1

FAZ-K1/2

FAZ-K1/3

1.6

FAZ-K1.6/1

FAZ-K1.6/2

FAZ-K1.6/3

2

FAZ-K2/1

FAZ-K2/2

FAZ-K2/3

3

FAZ-K3/1

FAZ-K3/2

FAZ-K3/3

4

FAZ-K4/1

FAZ-K4/2

FAZ-K4/3

6

FAZ-K6/1

FAZ-K6/2

FAZ-K6/3

8

FAZ-K8/1

FAZ-K8/2

FAZ-K8/3

10

FAZ-K10/1

FAZ-K10/2

FAZ-K10/3

13

FAZ-K13/1

FAZ-K13/2

FAZ-K13/3

16

FAZ-K16/1

FAZ-K16/2

FAZ-K16/3

20

FAZ-K20/1

FAZ-K20/2

FAZ-K20/3

25

FAZ-K25/1

FAZ-K25/2

FAZ-K25/3

32

FAZ-K32/1

FAZ-K32/2

FAZ-K32/3

40

FAZ-K40/1

FAZ-K40/2

FAZ-K40/3

50

FAZ-K50/1

FAZ-K50/2

FAZ-K50/3

63

FAZ-K63/1

FAZ-K63/2

FAZ-K63/3

Single-Pole

Two-Pole

Three-Pole

3

Four-Pole

K Curve (8–12X In Current Rating)—
Designed for Inductive Loads, continued 12
Single-Pole
+ Neutral

Three-Pole
+ Neutral

Catalog
Amperes Number

Catalog
Number

Catalog
Number

0.5

FAZ-K0.5/4

FAZ-K0.5/1N

FAZ-K0.5/3N

1

FAZ-K1/4

FAZ-K1/1N

FAZ-K1/3N

1.6

FAZ-K1.6/4

FAZ-K1.6/1N

FAZ-K1.6/3N

2

FAZ-K2/4

FAZ-K2/1N

FAZ-K2/3N

3

FAZ-K3/4

FAZ-K3/1N

FAZ-K3/3N

4

FAZ-K4/4

FAZ-K4/1N

FAZ-K4/3N

6

FAZ-K6/4

FAZ-K6/1N

FAZ-K6/3N

8

FAZ-K8/4

FAZ-K8/1N

FAZ-K8/3N

10

FAZ-K10/4

FAZ-K10/1N

FAZ-K10/3N

13

FAZ-K13/4

FAZ-K13/1N

FAZ-K13/3N

16

FAZ-K16/4

FAZ-K16/1N

FAZ-K16/3N

20

FAZ-K20/4

FAZ-K20/1N

FAZ-K20/3N

25

FAZ-K25/4

FAZ-K25/1N

FAZ-K25/3N

32

FAZ-K32/4

FAZ-K32/1N

FAZ-K32/3N

40

FAZ-K40/4

FAZ-K40/1N

FAZ-K40/3N

50

FAZ-K50/4

FAZ-K50/1N

FAZ-K50/3N

63

FAZ-K63/4

FAZ-K63/1N

FAZ-K63/3N

Four-Pole 3

Single-Pole + Neutral

Three-Pole + Neutral

Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 These breakers are available by special order and may result in additional delivery time.
3 Two-piece box order, quantities of 2.

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-87

1.3
1
1
1
1
1

UL 1077 DIN Rail Supplementary Protectors

Suitable for applications where high levels of inrush current are
expected. Instantaneous trip is 13–17X rating of device (In). The
high magnetic trip point prevents nuisance tripping in high
inductive applications such as motors, transformers and
power supplies.

1
1

Specified
non-tripping current
Int = 1.05 u In
for t > 1 h
Specified
tripping current
It = 1.30 u In
for t < 1 h

1200
600
300
120
60
30
10
5
2
1
0.5

S

0.02
0.01
0.005

1

0.002
0.001
0.0005

1

1

1

2

3

4 5 6 7 8 9 10 15 20
U-rated Current

Single-Pole

S Curve (13–17X In Current Rating)—
Designed for Inductive Loads 12
Single-Pole 3

Two-Pole

Amperes

Catalog
Number

Catalog
Number

1

FAZ-S1/1

FAZ-S1/2

2

FAZ-S2/1

FAZ-S2/2

3

FAZ-S3/1

FAZ-S3/2

4

FAZ-S4/1

FAZ-S4/2

6

FAZ-S6/1

FAZ-S6/2

10

FAZ-S10/1

FAZ-S10/2

1

16

FAZ-S16/1

FAZ-S16/2

20

FAZ-S20/1

FAZ-S20/2

1

25

FAZ-S25/1

FAZ-S25/2

32

FAZ-S32/1

FAZ-S32/2

40

FAZ-S40/1

FAZ-S40/2

1
1
1
1

7200
3600

0.2
0.1
0.05

1

1

1.05
1.30

FAZ S curve (13–17X In current rating)
●
Designed for control circuits with high inrush
●
Response time of instantaneous trip: 13–17X In current rating
●
UL recognized and CSA Certified as supplementary protectors
●
For international and domestic use (conform to IEC 60947-2)
●
UL file number 177451

t (sec)

1

Miniature Circuit Breakers and Supplementary Protectors

Two-Pole

1

1

Notes
1 In North America, these switches are UL recognized and CSA
Certified as supplementary protection devices. Per the intent of
NEC (National Electrical Code), Article 240, and CEC (Canadian
Electrical Code), Part 1 C22.1, supplementary breakers cannot be
used as a substitute for the branch circuit protective device.
They can be used to provide overcurrent protection within an
appliance or other electrical equipment where branch circuit
overcurrent protection is already provided, or is not required.
2 These breakers are available by special order and may result in
additional delivery time.
3 Two-piece box order, quantities of 2.

1
1
1
1
1
1
1
1
1
V4-T1-88

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

30 40 50

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1

1.05
1.30

FAZ Z curve (2–3X In current rating)
●
Designed for protection of electronic devices
●
Response time of instantaneous trip: 2–3X In current rating
●
UL recognized and CSA Certified as supplementary protectors
●
For international and domestic use (conform to IEC 60947-2)

7200
3600

Specified
non-tripping current
Int = 1.05 u In
for t > 1 h
Specified
tripping current
It = 1.30 u In
for t < 1 h

1200
600
300

Suitable for applications where low levels of inrush current
are expected. Instantaneous trip is 2–3X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits and coils. Medium magnetic trip point.

120
60
30

1
1
1
1

t (sec)

10
5

1

2
1
0.5

1

Z

0.2
0.1
0.05

1
1

0.02
0.01
0.005

1

0.002
0.001
0.0005
1

2

3

4 5 6 7 8 9 10 15 20

1

30 40 50

1

U-rated Current

Single-Pole

Z Curve (2–3X In Current Rating)—
Designed for Inductive Loads 12

Amperes

Two-Pole

Single-Pole 3

Two-Pole

Catalog
Number

Catalog
Number

0.5

FAZ-Z0.5/1

FAZ-Z0.5/2

1

FAZ-Z1/1

FAZ-Z1/2

1.6

FAZ-Z1.6/1

FAZ-Z1.6/2

2

FAZ-Z2/1

FAZ-Z2/2

3

FAZ-Z3/1

FAZ-Z3/2

4

FAZ-Z4/1

FAZ-Z4/2

6

FAZ-Z6/1

FAZ-Z6/2

8

FAZ-Z8/1

FAZ-Z8/2

10

FAZ-Z10/1

FAZ-Z10/2

13

FAZ-Z13/1

FAZ-Z13/2

16

FAZ-Z16/1

FAZ-Z16/2

20

FAZ-Z20/1

FAZ-Z20/2

25

FAZ-Z25/1

FAZ-Z25/2

32

FAZ-Z32/1

FAZ-Z32/2

40

FAZ-Z40/1

FAZ-Z40/2

50

FAZ-Z50/1

FAZ-Z50/2

63

FAZ-Z63/1

FAZ-Z63/2

Three-Pole

Four-Pole

Z Curve (2–3X In Current Rating)—
Designed for Inductive Loads, continued 12
Three-Pole

Four-Pole

Amperes

Catalog
Number

Catalog
Number

0.5

FAZ-Z0.5/3

FAZ-Z0.5/4

1

FAZ-Z1/3

FAZ-Z1/4

1.6

FAZ-Z1.6/3

FAZ-Z1.6/4

2

FAZ-Z2/3

FAZ-Z2/4

3

FAZ-Z3/3

FAZ-Z3/4

4

FAZ-Z4/3

FAZ-Z4/4

6

FAZ-Z6/3

FAZ-Z6/4

8

FAZ-Z8/3

FAZ-Z8/4

10

FAZ-Z10/3

FAZ-Z10/4

13

FAZ-Z13/3

FAZ-Z13/4

16

FAZ-Z16/3

FAZ-Z16/4

20

FAZ-Z20/3

FAZ-Z20/4

25

FAZ-Z25/3

FAZ-Z25/4

32

FAZ-Z32/3

FAZ-Z32/4

40

FAZ-Z40/3

FAZ-Z40/4

50

FAZ-Z50/3

FAZ-Z50/4

63

FAZ-Z63/3

FAZ-Z63/4

1
1
1
1
1
1
1
1
1
1
1
1
1

Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 These breakers are available by special order and may result in additional delivery time.
3 Two-piece box order, quantities of 2.

1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-89

1.3
1
1
1

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Accessories
FAZ Auxiliary Contacts and Voltage Trips
Circuit Diagram

Description

Catalog
Number

Standard Auxiliary Contacts

1
1
1
1

14

12

1
1
1

Rated Operational
Voltage

■
■
■
■

1NO/1NC
Installs on left side of FAZ or shunt trip
Max. one per FAZ (1077) device
Switches when FAZ is tripped
electrically or manually

230 Vac

FAZ-XHIN11

■
■
■
■

1 changeover contact
Installs on left side of FAZ or shunt trip
Max. one per FAZ (1077) device
Switches when FAZ is tripped
electrically or manually

230 Vac

FAZ-XHINW1

■
■
■
■

Small selector screw changes mode
Two Form C (changeover) contacts
Installs on left side of FAZ or shunt trip
Auxiliary contacts switch when FAZ is
tripped electrically or manually
■ Trip indicating contact switches only
when FAZ is tripped electrically

230 Vac

FAZ-XAM002

■ Prevents FAZ from operating unless

115 Vac

FAZ-XUA(115VAC)

230 Vac

FAZ-XUA(230VAC)

400 Vac

FAZ-XUA(400VAC)

12–110 Vac
12–60 Vdc

FAZ-XAA-C-12-110VAC

110–415 Vac
110–230 Vdc

FAZ-XAA-C-110415VAC

11
Auxiliary/Trip Indicating Contact

1
1
1

Two-pole auxiliary mode

1
1
1
1

Trip indicating mode
Undervoltage Trip

1

D1
D2

voltage is present
■ Installs on left side of FAZ
■ Includes test button

C1

■ Allows remote trip of FAZ
■ Installs on left side of FAZ

U

1
1
1
1

Shunt Trip

1

C2

1
1
1
1
1
1

Allowable Combinations of Accessories

AUX

AUX
TRIP

FAZ

AUX

or

V4-T1-90

FAZ

or
Circuit
Breaker

1

FAZ

AUX
TRIP

Shunt
Trip

Circuit
Breaker

UnderV
Trip

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Circuit
Breaker

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Busbar System
Description

1

Rated Operational Current

Number of Poles
per Device

Number of
Terminals

Catalog
Number 1

80A

1

57

BB-UL-18/1P-1M/57

2

56

BB-UL-18/2P-2M/56

3

57

BB-UL-18/3P-3M/57

1

57

BB-UL-25/1P-1M/57

2

56

BB-UL-25/2P-2M/56

3

57

BB-UL-25/3P-3M/57

1

Without Auxiliary Contacts
For connecting FAZ supplementary protectors without auxiliary
contacts. May be fed from line or load side.

1
1
1
1
1

WMZS WMZS WMZS

100A

1
1
1
1

Auxiliary/Trip Indicating Contacts
For connecting FAZ supplementary protectors with auxiliary
contacts. May be fed from line or load side.

FAZ

1

80A

1

37

BB-UL-18/1P-1,5M/37

2

46

BB-UL-18/2P+AS-2,5M/46

3

48

BB-UL-18/3P+AS-3,5M/48

1

37

BB-UL-25/1P-1,5M/37

2

46

BB-UL-25/2P+AS-2,5M/46

3

48

BB-UL-25/3P+AS-3,5M/48

1
1
1
1
1

FAZ

100A

1
1
1
1
1

Note
1 Bus may be center fed for high current capacity.

1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-91

1.3
1

Incoming Terminal

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Pin Type Incoming Supply Terminals

1

Description

Catalog
Number

■ Accommodates conductors

BB-UL-TEP/35

1

from 6–35 mm2/#10–2 AWG
■ 4–5.5 Nm/35–50 lb-in
■ Two- and three-pole

1

Incoming Terminal

Description
■
■
■
■
■

1
1

Fork Connector
Incoming Terminal

1
1

1

■ Accommodates conductors

BB-UL-TEPA/35

■ 4–5.5 Nm/35–50 lb-in

Busbar Terminal Cover

Protective Accessories
Description

1
1
1

Catalog
Number

from 6–35 mm2/#10–2 AWG

1
1

Pin Type Incoming Supply Terminals—
Single-Phase Only
Description

Catalog
Number

For covering
unused terminals

BB-IP/5

■ Prevents reactivation of the device

IS/SPE-1TE

during maintenance
■ Holds one padlock
Padlock Hasp

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-92

Bus Incoming Supply Terminals

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

50 mm2
#14–1 AWG
75 Deg wire
115 A/Y, 480V UL
160 A/Y 690V IEC

Catalog
Number
BB-UL-TE/50

Busbar End Cap
Description

Poles

Catalog
Number

■ Install after cutting busbar
■ Protects end of busbar

2 and 3

BB-UL-EC/3

1

BB-UL-EC/1

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Technical Data and Specifications

1

Tripping Characteristics
1.30

1
1

1.45

1.13

1.05

Even though not required by
NEC or CEC for supplementary
protectors, Eaton’s FAZ
devices are current limiting,
which means that they
interrupt fault currents
within one half cycle. Current
limiting devices offer superior
protection by reducing
peak let-through current
and energy.

7200
3600

Time-current characteristic acc. to UL 1077
 Conventional
 2.55 I :
N
non-tripping current
t = 1–60 s (IN < 32A)
t = 1–120 s (IN < 32A)
Int = 1.13 IN: t > 1 h

1200
600
300

 Conventional tripping

current
It = 1.45 IN: t < 1 h

120
60
30

 Type B: 3 I : t > 0.1 s
N
 Type B: 5 I : t < 0.1 s
N
 Type C: 5 I : t > 0.1 s
N
 Type C: 10 I : t < 0.1 s
N
	 Type D: 10 I : t > 0.1 s
N

 Type D: 20 I : t < 0.1 s
N

10
5
t (sec)

Trip Curves Chart
Eaton FAZ supplementary
protectors are available with
six different tripping
characteristics, including
Type B, C, D, K, S and Z.
Definitions for each trip curve
are contained on the ordering
pages and can be used to
determine the optimal
characteristic for your
application. For example,
low-level short-circuit faults in
control wiring, such as PLCs,
are best protected by devices
with Type B trip characteristics
(3–5X continuous rating of the
device (In).

1
1
1
1
1
1

2
1
0.5

D

0.2
0.1
0.05

Z

B

C

K

1
1

S

1

0.02
0.01
0.005

1

0.002
0.001
0.0005

1
1

2

3

4 5 6 7 8 9 10 15 20

30 40 50

I/In

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-93

1.3
1

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

FAZ Miniature Circuit Breakers Technical Data
Description

B Curve

C Curve

D Curve

1

Electrical

1

Approvals

UR (UL 1077), CSA (CSA 22.2 No. 235), CE

Standards

IEC/EN 60947-2

1

Short-circuit trip response

3–5 In

5–10 In

10–20 In

1

Current range

1–63A

0.5–63A

0.5–40A

277 Vac
48 Vdc

277 Vac
48 Vdc

277 Vac
48 Vdc

480Y/277 Vac
96 Vdc

480Y/277 Vac
96 Vdc

480Y/277 Vac
96 Vdc

Thermal tripping characteristics
Single-pole
Multi-pole

1.35 x In @ 40°C
1.45 x In @ 40°C

1.35 x In @ 40°C
1.45 x In @ 40°C

1.35 x In @ 40°C
1.45 x In @ 40°C

Short-circuit ratings (at max. voltage)
Single-pole
Two-, three-pole
Single-pole
Two poles in series

10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA @ 48 Vdc
10 kA @ 96 Vdc

10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA @ 48 Vdc
10 kA @ 96 Vdc

5 kA
5 kA
10 kA @ 48 Vdc
10 kA @ 96 Vdc

Current range

1–63A

0.5–63A

0.5–63A

Maximum voltage ratings—IEC 68898-1
Single-pole
Two-, three-pole

230 Vac
230/400 Vac

230 Vac
230/400 Vac

230 Vac
230/400 Vac

240 Vac
48 Vdc
240/415 Vac
96 Vdc

240 Vac
48 Vdc
240/415 Vac
96 Vdc

240 Vac
48 Vdc
240/415 Vac
96 Vdc

Thermal tripping characteristics
Single-pole
Multi-pole

> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In

> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In

> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In

Interrupt ratings (at max. voltage)
IEC 60947-2
IEC 60898
Operational switching capacity
Max. backup fuse [gL/gG]
Rated impulse withstand—Uimp
Rated insulation voltage—Ui

15 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac

15 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac

15 kA (10 kA for 50 and 63A)
10 kA (50 and 63A not available)
7.5 kA
125A
4000 Vac
440 Vac

3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon

3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon

3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon

Standard front dimension
Device height
Terminal protection
Mounting width per pole

80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm

80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm

80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm

Mounting
Degree of protection
Terminals top and bottom
Supply connection

IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side

IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side

IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side

Terminal capacity [mm2]
Torque
Imperial torque

1 x 25 (AWG 4–18)/2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required

1 x 25 (AWG 4–18)/2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required

1 x 25 (AWG 4–18)/2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Supplementary Protectors—UL/CSA

Maximum voltage ratings—UL/CSA
Single-pole, single-pole + neutral
Two-, three-pole, four-pole and
three-pole + neutral
Two poles in series

Miniature Circuit Breaker—IEC

Maximum voltage ratings—IEC 60947-2
Single-pole
Two-, three-pole
Two poles in series

Environmental/General
Selectivity class
Lifespan (operations)
Shock (IEC 68-2-22)
Operating temperature range
Shipment and short-term storage
Housing material
Mechanical

Thickness of busbar material
Mounting position

1
V4-T1-94

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1.3

FAZ Miniature Circuit Breakers Technical Data, continued
Description

B Curve

C Curve

1

D Curve

1

Electrical
Approvals

UR (UL 1077), CSA (CSA 22.2 No. 235), CE

1

Standards

IEC/EN 60947-2, E177451, 204453

Short-circuit trip response

8–12 In

13–17 In

2–3 In

1

0.5–63A

0.5–40A

1–63A

1

277 Vac
48 Vdc

277 Vac
48 Vdc

277 Vac
48 Vdc

1

480Y/277 Vac
96 Vdc

480Y/277 Vac
96 Vdc

480Y/277 Vac
96 Vdc

1

Thermal tripping characteristics
Single-pole
Multi-pole

1.35 x In @ 40°C
1.45 x In @ 40°C

1.35 x In @ 40°C
1.45 x In @ 40°C

1.35 x In @ 40°C
1.45 x In @ 40°C

Short-circuit ratings (at max. voltage)
Single-pole
Single-pole + neutral
Two-, three-, four-pole
Two poles in series

5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
—

5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
—

5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
—

0.5–63A

0.5–40A

1–63A

1

240 Vac

240 Vac

240 Vac

240/415 Vac

240/415 Vac

240/415 Vac

1

Thermal tripping characteristics
Single-pole
Multi-pole

> 1 Hour @ 1.05 x In
< 1 Hour @ 1.3 x In

> 1 Hour @ 1.05 x In
< 1 Hour @ 1.3 x In

> 1 Hour @ 1.05 x In
< 1 Hour @ 1.3 x In

Interrupt ratings (at max. voltage)
IEC 60947-2
Operational switching capacity
Max. backup fuse [gL/gG]
Rated impulse withstand—Uimp
Rated insulation voltage—Ui

15 kA
7.5 kA
125A
4000 Vac
440 Vac

10 kA
7.5 kA
125A
4000 Vac
440 Vac

10 kA
7.5 kA
125A
4000 Vac
440 Vac

3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon

3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon

3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon

Supplementary Protectors—UL/CSA
Current range
Maximum voltage ratings—UL/CSA
Single-pole, single-pole + neutral
Two-, three-, four-pole and
three-pole + neutral
Two poles in series

1
1
1
1

Miniature Circuit Breaker—IEC
Current range
Maximum voltage ratings—IEC 60947-2
Single-pole, single-pole + neutral
Two-, three-, four-pole,
three-pole + neutral

1
1
1
1
1

Environmental/General
Selectivity class
Lifespan (operations)
Shock (IEC 68-2-22)
Operating temperature range
Shipment and short-term storage
Housing material

1
1
1

Mechanical
Standard front dimension
Device height
Terminal protection
Mounting width per pole

80 mm
Finger and back-of-hand proof to IEC 536
17.7 mm

80 mm
Finger and back-of-hand proof to IEC 536
17.7 mm

80 mm
Finger and back-of-hand proof to IEC 536
17.7 mm

Mounting
Degree of protection
Terminals top and bottom
Supply connection

IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side

IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side

IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side

Terminal capacity [mm2]

1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required

1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required

1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required

Torque
Imperial torque
Thickness of busbar material
Mounting position

1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-95

1.3
1
1
1

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Let-Through Energy I2t

Let-Through Energy ID

Characteristic B and C

Characteristic B and C

∫i2dt 105
[A2s] 8

63 A
50 A
40 A
32 A
25 A
20 A
16 A
13 A
10 A

6

1

4

1

6A
4A

1

104

3A

1

6

8

10

5

6
4
3
2
0.5

1

1.5

2

3

4

5 6 7 8 910

15

0.5

1

1.5

2

3

4

5 6 7 8 910

15

Icc rms [kA]

Icc rms [kA]

Characteristic D

Characteristic D

5

∫i2dt 10
[A2s] 8

40 A
32 A
25 A
20 A
16 A
13 A

6
4

lD 104
9
[A] 8

40 A
32 A
25 A
20 A
16 A
13 A
10 A
6A

7
6

10 A

5

6A

4

2
1.5

1

6

1

4

1

0.5 A

8

104

1

0.5 A
1 A

1

1

1A

3

1

1

1.5

2

1

1

2

1.5

1

1

3

103

1

1

6A
4A
3A

4

1

1

5

2A
2A

1

1

6

4

1.5

1

63 A
50 A
40 A
32 A
25 A
16 A20 A
13 A
10 A

7

2

1

1

lD 104
9
[A] 8

3

8

2
1.5

103
2
1.5
103

5

8
6
4

1

2
0.5

1

1

1.5

2

3

4

5 6 7 8 910

15

0.5

Icc rms [kA]
V4-T1-96

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1

1.5

2

3

4

5 6 7 8 910

15

Icc rms [kA]

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Let-Through Energy I2t
Characteristic K
lD
[A]

1

Characteristic S
lD
[A]

104
8

1

104

1

8

6

4

3

63 A
50 A
40 A
32 A 25 A
20 A
13 A 16 A

6

10 A
6A
4A
3A

4

2A

2

1

40 A
32 A
25 A
20 A
16 A
10 A

1
1

6A
4A
3A
2A

3

1

1.6 A

1

1.5
1A

1

2
1A

103

1

1.5

1
103

5

1

0.5 A

1
1

5

0.5

1

1.5

2

3

4

5

6

7 8 9 10

Icc rms [kA]

0.5

1

1.5

2

3

4

5

6

1

7 8 9 10

Icc rms [kA]

1

Characteristic Z
lD
[A]

1

104

1

8

6

1

63 A
50 A
40 A
32 A 25 A
20 A
16 A

1

4
10 A
8A
3

1

6A

2

1

4A
3A

1

1.5

1

2A
103

1
1
5

1

1.6 A
1A

1

0.5 A

1
0.5

1

1.5

2

3

4

5

6

7 8 9 10

1

Icc rms [kA]

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-97

1.3
1
1

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Influence of the Ambient Temperature on the Thermal Tripping Behavior
Corrected values of the rated current dependent on the ambient temperature
Ambient Temperature T
In (A)

–40°C

–30°C

–20°C

–10°C

0°C

10°C

20°C

30°C

35°C

40°C

45°C

50°C

55°C

60°C

65°C

70°C

75°C

0.16

0.20

0.20

0.19

0.19

0.18

0.17

0.17

0.16

0.16

0.15

0.15

0.15

0.14

0.14

0.14

0.14

0.13

1

0.25

0.32

0.31

0.30

0.29

0.28

0.27

0.26

0.25

0.25

0.24

0.24

0.23

0.23

0.22

0.22

0.21

0.21

0.50

0.64

0.62

0.60

0.58

0.56

0.54

0.52

0.50

0.49

0.48

0.47

0.46

0.45

0.44

0.43

0.42

0.41

1

0.75

0.96

0.93

0.90

0.87

0.84

0.81

0.78

0.75

0.74

0.73

0.71

0.69

0.68

0.66

0.65

0.64

0.62

1.00

1.30

1.20

1.20

1.20

1.10

1.10

1.00

1.00

0.99

0.97

0.95

0.93

0.90

0.89

0.87

0.85

0.83

1

1.50

1.90

1.90

1.80

1.70

1.70

1.60

1.60

1.50

1.50

1.50

1.40

1.40

1.40

1.30

1.30

1.30

1.20

1.60

2.00

2.00

1.90

1.90

1.80

1.70

1.70

1.60

1.60

1.50

1.50

1.50

1.40

1.40

1.40

1.40

1.30

1

2.00

2.60

2.50

2.40

2.30

2.20

2.20

2.10

2.00

2.00

1.90

1.90

1.90

1.80

1.80

1.70

1.70

1.70

2.50

3.20

3.10

3.00

2.90

2.80

2.70

2.60

2.50

2.50

2.40

2.40

2.30

2.30

2.20

2.20

2.10

2.10

1

3.00

3.80

3.70

3.60

3.50

3.40

3.30

3.10

3.00

3.00

2.90

2.80

2.80

2.70

2.70

2.60

2.50

2.50

3.50

4.50

4.40

4.20

4.10

3.90

3.80

3.70

3.50

3.40

3.40

3.30

3.20

3.20

3.10

3.00

3.00

2.90

1

4.00

5.10

5.00

4.80

4.70

4.50

4.30

4.20

4.00

3.90

3.90

3.80

3.70

3.60

3.50

3.50

3.40

3.30

5.00

6.40

6.20

6.00

5.80

5.60

5.40

5.20

5.00

4.90

4.80

4.70

4.60

4.50

4.40

4.30

4.20

4.10

1

6.00

7.70

7.50

7.20

7.00

6.70

6.50

6.30

6.00

5.90

5.80

5.70

5.60

5.40

5.30

5.20

5.10

5.00

7.00

9.00

8.70

8.40

8.20

7.80

7.60

7.40

7.00

6.90

6.80

6.70

6.50

6.30

6.20

6.10

6.00

5.80

1

8.00

10.20

9.90

9.60

9.30

9.00

8.70

8.40

8.00

7.90

7.70

7.60

7.40

7.20

7.10

6.90

6.80

6.60

1

10.00

13.00

12.00

12.00

12.00

11.00

11.00

10.00

10.00

9.90

9.70

9.50

9.30

9.00

8.90

8.70

8.50

8.30

12.00

15.00

15.00

14.00

14.00

13.00

13.00

13.00

12.00

12.00

12.00

11.00

11.00

11.00

11.00

10.00

10.00

10.00

13.00

17.00

16.00

16.00

15.00

15.00

14.00

14.00

13.00

13.00

13.00

12.00

12.00

12.00

12.00

11.00

11.00

11.00

15.00

19.00

19.00

18.00

17.00

17.00

16.00

16.00

15.00

15.00

15.00

14.00

14.00

14.00

13.00

13.00

13.00

12.00

16.00

20.00

20.00

19.00

19.00

18.00

17.00

17.00

16.00

16.00

15.00

15.00

15.00

14.00

14.00

14.00

14.00

13.00

20.00

26.00

25.00

24.00

23.00

22.00

22.00

21.00

20.00

20.00

19.00

19.00

19.00

18.00

18.00

17.00

17.00

17.00

1

25.00

32.00

31.00

30.00

29.00

28.00

27.00

26.00

25.00

25.00

24.00

24.00

23.00

23.00

22.00

22.00

21.00

21.00

32.00

41.00

40.00

38.00

37.00

36.00

35.00

33.00

32.00

32.00

31.00

30.00

30.00

29.00

28.00

28.00

27.00

26.00

1

35.00

45.00

43.00

41.00

41.00

38.00

38.00

36.00

35.00

35.00

34.00

33.00

32.00

32.00

32.00

30.00

29.00

29.00

40.00

51.00

50.00

48.00

47.00

45.00

43.00

42.00

40.00

39.00

39.00

38.00

37.00

36.00

35.00

35.00

34.00

33.00

1

50.00

64.00

62.00

60.00

58.00

56.00

54.00

52.00

50.00

49.00

48.00

47.00

46.00

45.00

44.00

43.00

42.00

41.00

63.00

81.00

78.00

76.00

73.00

71.00

68.00

66.00

63.00

62.00

61.00

60.00

58.00

57.00

56.00

55.00

53.00

52.00

1

1
1

1
1

Influence of the Mains Frequency
Influence of the mains frequency on the tripping behavior IMA
of the instantaneous release

1

Mains Frequency f [Hz]
16 2/3

50

60

100

200

300

400

91

100

101

106

115

134

141

1

IMA(f)IMA (50 Hz) [%]

1

Load Carrying Capacity of Adjoining Miniature Circuit Breakers

1
1
1
1
1

Rated Diversity Factor

1

1.00

0.90

0.80

0.70

1

1

2

3

4

5

6

7

8

Number of Circuit Breakers

1
V4-T1-98

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1.3

Accessories Technical Data

1

FAZ-XHIN
FAZ-XAM002

FAZ-XAA-C

FAZ-XUA

1

Contact function

1A + 1B
2 C/O

—
—

—
—

1

Rated operational voltage Un

250 Vac

—

115 Vac
230 Vac
400 Vac

1

Voltage range

—

12–110 Vac
12–60 Vdc

—

1

Voltage range

—

110–415 Vac
110–230 Vdc

—

1
1

Description
Electrical

Closing threshold [x Un]

—

—

0.8

Tripping threshold [x Un]

—

—

0.5

Rated frequency ƒ

50/60 Hz

50/60 Hz

50/60 Hz

General use (UL/CSA)
AC—230/240 Vac
DC—110/120 Vdc

2/2A
0.5/0.5A

—
—

—
—

1
1
1

Pilot duty

A600/Q600

—

—

Conventional free air thermal current Ith

4A

—

—

Rated operational current
AC-13 Ie
AC-15 Ie
DC-13 Ie

1

3A (250 Vac)
2A (250 Vac)
0.5A (110 Vdc)

—
—
—

—
—
—

1
1

Rated insulation voltage Ui

250 Vac

—

—

Minimum operating voltage per contract Umin

5 Vdc

—

—

Rated impulse withstand voltage (1.2/50μ) Uimp

2.5 kV

—

—

Rated conditional short-circuit current with 6A backup fuse ISC

1 kA

—

—

Max. admissible backup fuse

4A gL

—

—

1

Standard front dimension

45 mm

45 mm

45 mm

1

Device height

80 mm

80 mm

80 mm

Mounting width

8.8 mm

17.6 mm

17.8 mm

Mounting

On MCB

IEC/EN 60715 top-hat rail

IEC/EN 60715 top-hat rail

1

1

Mechanical

1

IP40

IP40

IP40

1

Terminal protection

Protection against
electric shock to IEC 536

Protection against
electric shock to IEC 536

Protection against
electric shock to IEC 536

1

Terminals

Lift terminals

Twin-purpose terminals

Twin-purpose terminals

Terminal capacity
Solid
Flexible

0.5–2.5 mm2
0.5–2.5 mm2

1–2.5 mm2
1–2.5 mm2

2 x (1–2.5) mm2
2 x (1–2.5) mm2

1

Tightening torque of terminal screws

0.8–1.0 Nm (7–9 lb-in)

2.4 Nm (21 lb-in)

0.8 Nm (7 lb-in)

Degree of protection enclosed

1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-99

1.3
1

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Dimensions
Approximate Dimensions in Inches (mm)

1

Miniature Circuit Breakers

1

FAZ
0.74
(9.4)

1
1

1.77
(45.0)

3.15
(80.0)

1
1
1
1
1
1
1

1.40
(35.4)

0.70
(17.8)

2.09
(53.1)

0.22
(5.5)

2.79
(70.8)

1.73
(44.0)
2.36
(60.0)

Auxiliary Contacts
FAZ-XHI11 and FAZ-XH1NW1

FAZ-XAM002

1
1

3.15
(80.0)

1

3.15
(80.0)

1.77
(45.0)

1.77
(45.0)

1
1

0.35
(8.8)

1
1
1

0.22
(5.5)

1.73
(44.0)

0.35
(8.8)

2.36
(60.0)

0.22
(5.5)

Shunt Releases

Undervoltage Releases

FAZ-XAA

FAZ-XUA

1.73
(44.0)

2.36
(60.0)

1
1

3.15
(80.0)

1

1.77
(45.0)

3.15
(80.0)

1.77
(45.0)

1
1
1

0.70
(17.8)
1.03
(26.2)

1

0.22
(5.5)

1.20
(30.5)
1.73
(44.0)

0.39
(10.0)

0.70
(17.8)

0.22
(5.5)

2.36
(60.0)

1
1
1
V4-T1-100

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.73
(44.0)

2.36
(60.0)

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Approximate Dimensions in Inches (mm)

1
1

Busbar and Accessory Weights and Dimensions
Unit Weight (kg)

Length

Width

Height

Catalog
Number

0.29

39.72 (1009.0)

0.59 (15.0)

0.59 (15.0)

BB-UL-18/1P-1M/57

0.64

39.02 (991.0)

0.87 (22.0)

1.46 (37.0)

BB-UL-18/2P-2M/56

0.83

39.72 (1009.0)

0.87 (22.0)

1.46 (37.0)

BB-UL-18/3P-3M/57

0.26

38.78 (985.0)

0.59 (15.0)

0.59 (15.0)

BB-UL-18/1P-1.5M/37

0.63

39.72 (1009.0)

0.87 (22.0)

1.46 (37.0)

BB-UL-18/2P+AS-2.5M/46

0.79

38.66 (982.0)

0.87 (22.0)

1.46 (37.0)

BB-UL-18/3P+AS-3.5M/48

0.36

39.72 (1009.0)

0.59 (15.0)

0.59 (15.0)

BB-UL-25/1P-1M/57

0.79

39.02 (991.0)

0.87 (22.0)

1.46 (37.0)

BB-UL-25/2P-2M/56

1.04

39.72 (1009.0)

0.87 (22.0)

1.46 (37.0)

BB-UL-25/3P-3M/57

0.31

38.78 (985.0)

0.59 (15.0)

0.59 (15.0)

BB-UL-25/1P-1.5M/37

0.73

39.72 (1009.0)

0.87 (22.0)

1.46 (37.0)

BB-UL-25/2P+AS-2.5M/46

0.97

38.66 (982.0)

0.87 (22.0)

1.46 (37.0)

BB-UL-25/3P+AS-3.5M/48

0.03

2.36 (60.0)

0.67 (17.0)

1.14 (29.0)

BB-UL-TEP/35

0.03

1.42 (36.0)

0.67 (17.0)

1.14 (29.0)

BB-UL-TEPA/35

0.03

1.57 (40.0)

0.71 (18.0)

1.18 (30.0)

BB-UL-TE/50

0.003

3.35 (85.0)

0.47 (12.0)

0.94 (24.0)

BB-IP/5

0.001

0.55 (14.0)

0.20 (5.0)

0.39 (10.0)

BB-UL-EC/3

0.001

0.94 (24.0)

0.87 (22.0)

0.39 (10.0)

BB-UL-EC/1

1
1
1
1
1
1
1
1
1
1
1
1
1

L

W

1
1

L1

L2

L1

L2

L1

L2

L1

L2

L1

L2

L1

L2

H

1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-101

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1

Application Guidelines

1

Example of UL 489 and UL 1077 Application

1

UL 489
Breaker

1
1
1
1

UL 489
Branch

UL 1077

Internal Receptacle

1
1

Electronics

1
1
1
1

UL 489
Branch

UL 1077
Other
Sensitive
Devices

1

External
Motor
M

UL 489
Branch
External
Motor

UL 489
Branch

1

M

1
1

External
Receptacle

UL 1077

HACR

Motor
Controller

1
1
Example of UL 489 and UL 1077 Application

1
1

UL 489 circuit breakers

1

Used for branch circuit protection, internal/external receptacles, external motors and HACR equipment
(heating, air conditioning and refrigeration).

1

UL 1077 supplementary protectors

1

Used for overcurrent protection within appliances or electrical equipment, where branch circuit protection
is already provided or not required.

1

Note: UL 4 89 devices can be used in place of UL 1077; UL 1077 devices cannot be used in place of UL 489.

1
1
1
1
1
V4-T1-102

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1.3

Contents

WMZS Circuit Breakers

Description
FAZ Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . .
WMZS Circuit Breaker
Standards and Certifications. . . . . . . . . . . . . . . .
Catalog Number Selection . . . . . . . . . . . . . . . . .
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications. . . . . . . . . . . .
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page
V4-T1-82
V4-T1-104
V4-T1-104
V4-T1-105
V4-T1-107
V4-T1-110
V4-T1-117

1
1
1
1
1
1
1
1
1
1
1

WMZS Circuit Breaker
Product Overview

Features

Optimum product quality,
tested reliability and safety
stand for best protection of
personnel, installations and
plant. Eaton’s WMZS DIN rail
mountable circuit breaker is
designed for use in control
panel applications.The WMZS
is available with B, C and D
characteristics in accordance
with UL 1077, CSA C22.2
No.235 and IEC 60947-2.

●

●

●

Application Description
Supplementary protection:
●
●
●
●

Control circuits
Lighting
Business equipment
Appliances

●

●

Complete range of
UL 1077 Recognized DIN
rail mounted miniature
circuit breakers up to 63A
current rating
Standard ratings of 10 kAIC
at 277/480 Vac
Current limiting design
provides fast short-circuit
interruption that reduces
the let-through energy,
which can damage the
circuit
Offers supplementary
protection
Thermal-magnetic
overcurrent protection
●
Three levels of shortcircuit protection,
categorized by B, C
and D curves

●

●

●

●

●

●

●
●

1

Trip-free design—breaker
can not be defeated by
holding the handle in the
ON position
Captive screws cannot
be lost
Fulfill UL 1077, CSA C22.2
No.235 and also IEC
60947-2 Standard
Field-installable shunt trip
and auxiliary switch
subsequent mounting
Module width of only 0.69
inches (17.5 mm) per pole
Contact Position Indicator
(red/green)
Easy installation on DIN rail
Possibility for sealing the
toggle in ON or OFF
position

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-103

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Standards and Certifications

1
1
1
1
1
1

Advanced Features

Breakers install on
standard DIN rail

Captive posidrive terminal
screws with finger and backof-hand protection (IP20)

Available in single-,
two- and three-pole
models

Trip-free design; breaker
cannot be defeated by
holding the handle in the
ON position

Color-coded indicator
provides breaker status
for easy troubleshooting

Breaker information
printed on the front of
the device for quick
identification

1
1
1

Worldwide Acceptance
WMZS Supplementary
Protectors are UL Recognized
for use in the United States in
accordance with NFPA® 70
(NEC). The devices comply
with UL 1077 and CSA 22.2
No. 235, meeting the
requirements for
supplementary protectors.
These devices are for
international and domestic
use, and also comply with
IEC 60947-2 and are
CE marked. These devices
are RoHS compliant.

1
1
1
1
1
1
1
1

Catalog Number Selection

1

WMZS 1 B 10

1

Breaker Family
WMZS = Supplementary Protector

1

Ampere Rating
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole

1

Protective Curve
B = B Curve (3–5X In)
C = C Curve (5–10X In)
D = D Curve (10–20X In)

1
1
1
1
1
1
1
1
1
V4-T1-104

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

00 = 0.5A
01 = 1A
02 = 2A
03 = 3A
04 = 4A
05 = 5A
06 = 6A

07 = 7A
08 = 8A
10 = 10A
13 = 13A
15 = 15A
16 = 16A
20 = 20A

25 = 25A
30 = 30A
32 = 32A
40 = 40A
50 = 50A
63 = 63A

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1.3

Product Selection

1

WMZS Product Selection—B Curve (3–5X In Current Rating)
Suitable for applications where protection against low level short
circuit faults in control wiring is desired. Instantaneous trip is
3–5X continuous rating of device (In). Applications include PLC
wiring, business equipment, lighting, appliances and some
motors. Low magnetic trip point.
Single-Pole

Two-Pole

Three-Pole

B Curve (3–5X In Current Rating)—
Designed for Resistive or Slightly
Inductive Loads 123
Single-Pole

Two-Pole

Three-Pole

Amperes

Catalog
Number

Catalog
Number

Catalog
Number

6

WMZS1B06

WMZS2B06

WMZS3B06

7

WMZS1B07

WMZS2B07

WMZS3B07

8

WMZS1B08

WMZS2B08

WMZS3B08

10

WMZS1B10

WMZS2B10

WMZS3B10

13

WMZS1B13

WMZS2B13

WMZS3B13

15

WMZS1B15

WMZS2B15

WMZS3B15

16

WMZS1B16

WMZS2B16

WMZS3B16

20

WMZS1B20

WMZS2B20

WMZS3B20

25

WMZS1B25

WMZS2B25

WMZS3B25

30

WMZS1B30

WMZS2B30

WMZS3B30

32

WMZS1B32

WMZS2B32

WMZS3B32

40

WMZS1B40

WMZS2B40

WMZS3B40

50

WMZS1B50

WMZS2B50

WMZS3B50

63

WMZS1B63

WMZS2B63

WMZS3B63

WMZS Product Selection—C Curve (5–10X In Current Rating)
Suitable for applications where medium levels of inrush current
are expected. Instantaneous trip is 5–10X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits, and coils. Medium magnetic trip point.

Single-Pole

Two-Pole

Three-Pole

C Curve (5–10X In Current Rating)—
Designed for Inductive Loads 145
Single-Pole

Two-Pole

Three-Pole

Amperes

Catalog
Number

Catalog
Number

Catalog
Number

0.5

WMZS1C00

WMZS2C00

WMZS3C00

1

WMZS1C01

WMZS2C01

WMZS3C01

2

WMZS1C02

WMZS2C02

WMZS3C02

3

WMZS1C03

WMZS2C03

WMZS3C03

4

WMZS1C04

WMZS2C04

WMZS3C04

5

WMZS1C05

WMZS2C05

WMZS3C05

6

WMZS1C06

WMZS2C06

WMZS3C06

7

WMZS1C07

WMZS2C07

WMZS3C07

8

WMZS1C08

WMZS2C08

WMZS3C08

10

WMZS1C10

WMZS2C10

WMZS3C10

13

WMZS1C13

WMZS2C13

WMZS3C13

15

WMZS1C15

WMZS2C15

WMZS3C15

16

WMZS1C16

WMZS2C16

WMZS3C16

20

WMZS1C20

WMZS2C20

WMZS3C20

25

WMZS1C25

WMZS2C25

WMZS3C25

30

WMZS1C30

WMZS2C30

WMZS3C30

32

WMZS1C32

WMZS2C32

WMZS3C32

40

WMZS1C40

WMZS2C40

WMZS3C40

50

WMZS1C50

WMZS2C50

WMZS3C50

63

WMZS1C63

WMZS2C63

WMZS3C63

Notes
1 In North America, these switches are UL recognized and CSA certified as Supplementary
Protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC
(Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a
substitute for the branch circuit protective device. They can be used to provide overcurrent
protection within an appliance or other electrical equipment where branch circuit overcurrent
protection is already provided, or is not required.
2 Designed for resistive or slightly inductive loads.
3 Response time of instantaneous trip: 3–5X I current rating.
n
4 Designed for inductive loads.
5 Response time of instantaneous trip: 5–10X I current rating.
n

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-105

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1
1
1
1
1
1

WMZS Product Selection—D Curve (10–20X In Current Rating)
Suitable for applications where high levels of inrush current are
expected. Instantaneous trip is 10–20X rating of device (In).
The high magnetic trip point prevents nuisance tripping in high
inductive applications such as motors, transformers and
power supplies.

Single-Pole

D Curve (10–20X In Current Rating)—
Designed for Inductive Loads 123
Single-Pole

Two-Pole

Three-Pole

Amperes

Catalog
Number

Catalog
Number

Catalog
Number

1

0.5

WMZS1D00

WMZS2D00

WMZS3D00

1

1

WMZS1D01

WMZS2D01

WMZS3D01

2

WMZS1D02

WMZS2D02

WMZS3D02

3

WMZS1D03

WMZS2D03

WMZS3D03

4

WMZS1D04

WMZS2D04

WMZS3D04

5

WMZS1D05

WMZS2D05

WMZS3D05

6

WMZS1D06

WMZS2D06

WMZS3D06

7

WMZS1D07

WMZS2D07

WMZS3D07

8

WMZS1D08

WMZS2D08

WMZS3D08

10

WMZS1D10

WMZS2D10

WMZS3D10

13

WMZS1D13

WMZS2D13

WMZS3D13

15

WMZS1D15

WMZS2D15

WMZS3D15

1

16

WMZS1D16

WMZS2D16

WMZS3D16

1

20

WMZS1D20

WMZS2D20

WMZS3D20

25

WMZS1D25

WMZS2D25

WMZS3D25

30

WMZS1D30

WMZS2D30

WMZS3D30

32

WMZS1D32

WMZS2D32

WMZS3D32

40

WMZS1D40

WMZS2D40

WMZS3D40

1

1

Two-Pole

1
1
1
1

Three-Pole

1
1
1
1
1
1

Notes
1 In North America, these switches are UL recognized and CSA certified as Supplementary
Protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC
(Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a
substitute for the branch circuit protective device. They can be used to provide overcurrent
protection within an appliance or other electrical equipment where branch circuit overcurrent
protection is already provided, or is not required.
2 Designed for highly inductive loads.
3 Response time of instantaneous trip: 10–20X I current rating.
n

1
1
1
1
1
1
1
1
V4-T1-106

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Accessories

1

WMZS Auxiliary Contacts and Voltage Trips
Module

Circuit Diagram

Description

Rated Operational
Voltage

Catalog
Number

230 Vac

WMZSAUX

1
1

Standard Auxiliary Contacts

H

12

■
■
■
■

14 11

1NO/1NC
Installs on left side of WMZS or shunt trip
Max. one per WMZS (1077) device
Switches when WMZS is tripped
electrically or manually

1
1
1
1

2

1

Auxiliary/Trip Indicating Contact

1

2

N

4

OFF
1.11

■
■
■
■

Small selector screw changes mode
Two Form C (changeover) contacts
Installs on left side of WMZS or shunt trip
Auxiliary contacts switch when WMZS is
tripped electrically or manually
■ Trip indicating contact switches only when
WMZS is tripped electrically

4.11

1.14

4.12

1.12

4.14

230 Vac

WMZSAUXTRIP

1
1
1
1

Undervoltage Trip
■ Prevents WMZS from operating unless

voltage is present
■ Installs on left side of WMZS
■ Includes test button

D1

115 Vac

WMZSUVR115

230 Vac

WMZSUVR230

400 Vac

WMZSUVR400

U
D2

1
1
1
1
1

Shunt Trip
■ Allows remote trip of WMZS
■ Installs on left side of WMZS

110–415 Vac

1

WMZSST415

110–230 Vdc
12–110 Vac

C1

1

WMZSST110

1

12–60 Vdc

C2

1
1
1

Allowable Combinations of Accessories

1
AUX

AUX
TRIP

FAZ

or

AUX

FAZ

AUX
TRIP

FAZ

1

or
Circuit
Breaker

Shunt
Trip

Circuit
Breaker

UnderV
Trip

1

Circuit
Breaker

1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-107

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1
1

Busbar System

1

Description

1

Rated Operational
Current (A)

Number of Poles
per Device

Number of
Terminals

Catalog
Number

80

1

57

WMZS1P57T

2

56

WMZS2P56T

3

57

WMZS3P57T

1

57

WMZS1P57T25

2

56

WMZS2P56T25

3

57

WMZS3P57T25

1

37

WMZS1P37TAUX

2

46

WMZS2P46TAUX

3

48

WMZS3P48TAUX

1

37

WMZS1P37T25AUX

2

46

WMZS2P46T25AUX

3

48

WMZS3P48T25AUX

Without Auxiliary Contacts
For connecting WMZS Supplementary Protectors without auxiliary
contacts. May be fed from line or load side.

1
1
1
1

WMZS WMZS WMZS

100

1
1
1
1
1
1

Auxiliary/Trip Indicating Contact
For connecting WMZS Supplementary Protectors with auxiliary
contacts. May be fed from line or load side.

80

1
1
1

WMZS

WMZS

100

1
1
1
1
1
1

WMZSBBTC

1

WMZS3CAP
or
WMZS1CAP

1
1
1

WMZSBCONA

1

35 lb-in
(4 Nm)

1

50 lb-in
(5.5 Nm)
22 lb-in
(2.5 Nm)

1
V4-T1-108

WMZS35EXT

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1
Incoming Terminal

Pin Type Incoming Supply Terminals
Description
Accommodates conductors from
6–35 mm2 /#10–2 AWG

Incoming Terminal

Bus Incoming Supply Terminals

Catalog
Number

Description

Catalog
Number

WMZS35EXT

50 mm2

WMZSBCONA

1
1
1

#14–1 AWG
4–5.5 Nm/35–50 16 lb-in
75 Deg Wire

1

115A/Y, 480V UL

1

Finger-safe connection

160A/Y 690V IEC

1
Protective Accessories

Busbar Terminal Cover

Description

Catalog
Number

For covering unused terminals

WMZSBBTC

Fork Connector
Two- and Three-Pole

1

Busbar End Cap
Description

Number
of Poles

Catalog
Number

1

Install after cutting busbar

2 and 3

WMZS3CAP

1

Protects end of busbar

1
1
1

Fork Connector
Two- and Three-Pole
Padlock Hasp

1
Prevents reactivation of the device during
maintenance

WMZS1CAP

WMZPLK

1
1

Holds one padlock

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-109

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1

Technical Data and Specifications

1

Trip Curve Charts
Three Tripping Curves
to Choose
Eaton WMZS Supplementary
Protectors are available with
three different tripping
characteristics, including
Type B, C and D. Definitions
for each trip curve are
contained on the ordering
pages and can be used to
determine the optimal
characteristic for your
application. For example,
low level short-circuit faults
in control wiring, such as
PLCs, are best protected
by devices with Type B trip
characteristics (3 to 5X
continuous rating of the
device (In).

1
1
1
1
1
1
1
1
1

WMZS Tripping Curves
7200

Even though not required by
NEC or CEC for Supplementary
Protectors, Eaton’s WMZS
devices are current limiting,
which means they interrupt
fault currents within one
half cycle. Current limiting
devices offer superior
protection by reducing
peak let-through current
and energy.

3600

Time-current characteristic
conventional
non-tripping current
Int = 1.13 IN: t > 1 h

2
1

1200
600

acc. to UL 1077
2.55 IN:
t = 1 – 60 s (IN < 32A)
t = 1 – 120 s (IN < 32A)

conventional tripping
current
It = 1.45 IN: t < 1 h

300
120

Type B: 3 IN: t > 0.1 s
Type B: 5 IN: t < 0.1 s
Type C: 5 IN: t > 0.1 s

3

60

t [sec]

1.3

Type C: 10 IN: t < 0.1 s

30

Type D: 10 IN: t > 0.1 s

10

Type D: 20 IN: t < 0.1 s

5
2
1
3

0.5
0.2

5

0.1
0.05

B6

4

9

7

C

8

D

0.02

1

0.01
0.005

1

0.002
0.001
0.0005

1

1

1

2

3

4

5 6 7 8 910
I / IN

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-110

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

15

20

30

40 50

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

B Curve

D Curve
1.13
1.45

1.13
1.45

7200

Specified non-tripping
current
INT = 1.13 x IN for t > 1 h

3600
1200

2.55 IN:
t = 1 – 60 s (IN < 32A)
t = 1 – 120 s (IN > 32A)
Type B: 3 x IN: t > 0.1 s

Specified tripping current
IT = 1.45 x IN for t < 1 h

600
300

Type B: 5 x IN: t < 0.1 s
Type C: 5 x IN: t > 0.1 s

120
1

60
30

7200

1200
600

120

Type D: 10 x IN: t > 0.1 s

60

10

10

5

5

0.5

Type B: 3 x IN: t > 0.1 s
Type B: 5 x IN: t < 0.1 s
Type C: 5 x IN: t > 0.1 s
Type C: 10 x IN: t < 0.1 s

1

Type D: 10 x IN: t > 0.1 s

30

Type D: 20 x IN: t < 0.1 s

1

2.55 IN:
t = 1 – 60 s (IN < 32A)
t = 1 – 120 s (IN > 32A)

Specified tripping current
IT = 1.45 x IN for t < 1 h

300

Type C: 10 x IN: t < 0.1 s

2
1

Specified non-tripping
current
INT = 1.13 x IN for t > 1 h

3600

t [sec]

t [sec]

1

Type D: 20 x IN: t < 0.1 s

3

B4

2

1

C

D

0.02

0.02

0.01

0.01

0.005

0.005

0.002

0.002

0.001
0.0005

0.001
0.0005

1

2

3

4

15

5 6 7 8 910

20

30

40 50

B4

2

6

D

1
1
1
1

2

3

4

5 6 7 8 910

15

20

30

40 50

1
1
1

C Curve
1.13
1.45

1

7200

Specified non-tripping
current
INT = 1.13 x IN for t > 1 h

3600
1200
300

1

2.55 IN:
t = 1 – 60 s (IN < 32A)
t = 1 – 120 s (IN > 32A)

1

Type B: 3 x IN: t > 0.1 s

Specified tripping current
IT = 1.45 x IN for t < 1 h

600

Type B: 5 x IN: t < 0.1 s

1

Type C: 5 x IN: t > 0.1 s

120

Type C: 10 x IN: t < 0.1 s
1

60

1

Type D: 10 x IN: t > 0.1 s

30

Type D: 20 x IN: t < 0.1 s

1

10
t [sec]

1

1

7

5

C

I / IN

I / IN

1

1
3

0.1
0.05

7

5
6

1

1

2
1
0.5

0.1
0.05

1

1

0.2

0.2

1

5

1

2
1

1

1

0.5

1

0.2
3

0.1
0.05

B4

2

7

5

C

6

D

1

0.02

1

0.01
0.005

1

0.002
0.001
0.0005
1

2

3

4

5 6 7 8 910

15

20

30

1

40 50

1

I / IN

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-111

1.3
1

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

WMZ Miniature Circuit Breaker Technical Data
Description

B Curve

C Curve

D Curve

1

Electrical

1

Approvals

UR (UL 1077), CSA (CSA 22.2 No. 235), CE

Standards

IEC/EN 60947-2

Short-circuit trip response

3–5 In

5–10 In

10–20 In

6–63A

0.5–63A

0.5–40A

277 Vac
48 Vdc

277 Vac
48 Vdc

277 Vac
48 Vdc

480Y/277 Vac
96 Vdc

480Y/277 Vac
96 Vdc

480Y/277 Vac
96 Vdc

Thermal tripping characteristics
Single-pole
Multi-pole

1.35 x In at 40°C
1.45 x In at 40°C

1.35 x In at 40°C
1.45 x In at 40°C

1.35 x In at 40°C
1.45 x In at 40°C

Short-circuit ratings (at max. voltage)
Single-pole
Two-, three-pole
Single-pole
Two poles in series

10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA at 48 Vdc
10 kA at 96 Vdc

10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA at 48 Vdc
10 kA at 96 Vdc

5 kA
5 kA
10 kA at 48 Vdc
10 kA at 96 Vdc

6–63A

0.5–63A

0.5–40A

230 Vac
48 Vdc
230/400 Vac

230 Vac
48 Vdc
230/400 Vac

230 Vac
48 Vdc
230/400 Vac

240 Vac
48 Vdc
240/415 Vac

240 Vac
48 Vdc
240/415 Vac

240 Vac
48 Vdc
240/415 Vac

Thermal tripping characteristics
Single-pole
Multi-pole

> 1 hour at 1.05 x In
< 1 hour at 1.3 x In

> 1 hour at 1.05 x In
< 1 hour at 1.3 x In

> 1 hour at 1.05 x In
< 1 hour at 1.3 x In

Interrupting ratings (at max. voltage)
IEC 60947-2
IEC 60898

15 kA
10 kA

15 kA
10 kA

15 kA
10 kA

Operational switching capacity

7.5 kA

7.5 kA

7.5 kA

Max. back-up fuse [gL/gG]

125A

125A

125A

Rated impulse withstand—Uimp

4000 Vac

4000 Vac

4000 Vac

Rated insulation voltage—Ui

440 Vac

440 Vac

440 Vac

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Supplementary Protectors—UL/CSA
Current range
Maximum voltage ratings—UL/CSA
Single-pole

Two-, three-pole
Two poles in series

Miniature Circuit Breaker—IEC
Current range
Maximum voltage ratings—IEC 60947-2
Single-pole
Two-, three-pole
Maximum voltage ratings—IEC 60898
Single-pole
Two-, three-pole

1
1
1
1
1
1
1
1
1
1
V4-T1-112

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1.3

WMZ Miniature Circuit Breaker Technical Data, continued
Description

1

B Curve

C Curve

D Curve

Selectivity class

3

3

3

Lifespan (operations)

> 10,000 (1 operation = ON/OFF)

> 10000 (1 operation = ON/OFF)

> 10000 (1 operation = ON/OFF)

Shock (IEC 68-2-22)

10g–120 ms

10g–120 ms

10g–120 ms

Operating temperature range

23° to 104°F (–5° to 40°C)

23° to 104°F (–5° to 40°C)

23° to 104°F (–5° to 40°C)

Shipment and short-term storage

–40° to 185°F (–40° to 85°C)

–40 to 185°F (–40° to 85°C)

–40° to 185°F (–40° to 85°C)

Housing material

Nylon

Nylon

Nylon

Standard Front Dimension
Device height
Terminal protection
Mounting width per pole

80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm

80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm

80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm

Mounting

IEC/EN 60715 top-hat rail

IEC/EN 60715 top-hat rail

IEC/EN 60715 top-hat rail

Degree of protection

IP20

IP20

IP20

Terminals top and bottom

Twin-purpose terminals

Twin-purpose terminals

Twin-purpose terminals

Supply connection

Line or load side

Line or load side

Line or load side

Terminal capacity [mm2]

1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)

1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)

1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)

Torque

2.4 Nm

2.4 Nm

2.4 Nm

1

Imperial torque

21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)

21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)

21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)

1

Thickness of busbar material

0.8–2 mm

0.8–2 mm

0.8–2 mm

Mounting position

As required

As required

As required

1

1

Environmental/General

1
1
1
1

Mechanical

1
1
1
1

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-113

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1

Let-Through Energy I2t

Let-Through Current ID

1

Characteristic B and C

Characteristic B and C

1
1
1
1
1
1
1
1
1
1
1

i2dt 10 5
[A2s] 8

63 A
50 A

6

40 A
32 A
25 A
20 A
16 A
13 A
10 A

4

lD 10 4
9
[A] 8

63 A
50 A
40 A
32 A
25 A
20 A
16 A

7
6

13 A
10 A

5
4

6A
4A
3A

2
6A
4A

1.5
10

3

4

3A

2

8

2A

6
2A

1.5

4
10 3
WMZS-...-B4HI

2

1A

1.5

0.5 A
1 A

10 3

0.5 A

5

8
6
4
3
2
0.5

1

1.5

2

3

4

5 6 7 8 910

15

0.5

1

1.5

2

3

4

1

5 6 7 8 910

15

Icc rms [kA]

Icc rms [kA]

1
1
1
1
1
1
1
1
1
1
1
1

Characteristic D

Characteristic D
5

i2dt 10
[A2s] 8

40 A
32 A
25 A
20 A
16 A
13 A

6

lD 10 4
9
[A] 8

40 A
32 A
25 A
20 A

7
6

16 A
13 A
10 A

4
10 A

5

6A

4

6A

2
3

1.5
10 4

2

8
6

1.5

4
10 3
2
1.5
10 3

5

8
6
4

1

2
0.5

1

1

1.5

2

3

4

5 6 7 8 910

15

0.5

Icc rms [kA]

1
1
V4-T1-114

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1

1.5

2

3

4

5 6 7 8 910

15

Icc rms [kA]

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Influence of the Ambient Temperature on the Thermal Tripping Behavior
Corrected values of the rated current dependent on the ambient temperature

1
1

Ambient Temperature T
In (A)

–25°C

–20°C

–10°C

0°C

10°C

20°C

30°C

35°C

40°C

45°C

50°C

55°C

60°C

0.16

0.2

0.19

0.19

0.18

0.17

0.17

0.16

0.16

0.15

0.15

0.15

0.14

0.14

0.25

0.31

0.3

0.29

0.28

0.27

0.26

0.25

0.25

0.24

0.24

0.23

0.23

0.22

0.5

0.61

0.6

0.58

0.56

0.54

0.52

0.5

0.49

0.48

0.47

0.46

0.45

0.44

0.75

0.92

0.9

0.87

0.84

0.81

0.78

0.75

0.74

0.73

0.71

0.69

0.68

0.66

1

1.2

1.2

1.2

1.1

1.1

1

1

0.99

0.97

0.95

0.93

0.9

0.89

1.5

1.8

1.8

1.7

1.7

1.6

1.6

1.5

1.5

1.5

1.4

1.4

1.4

1.3

1.6

2

1.9

1.9

1.8

1.7

1.7

1.6

1.6

1.5

1.5

1.5

1.4

1.4

2

2.4

2.4

2.3

2.2

2.2

2.1

2

2

1.9

1.9

1.9

1.8

1.8

2.5

3.1

3

2.9

2.8

2.7

2.6

2.5

2.5

2.4

2.4

2.3

2.3

2.2

3

3.7

3.6

3.5

3.4

3.3

3.1

3

3

2.9

2.8

2.8

2.7

2.7

3.5

4.3

4.2

4.1

3.9

3.8

3.7

3.5

3.4

3.4

3.3

3.2

3.2

3.1

4

4.9

4.8

4.7

4.5

4.3

4.2

4

3.9

3.9

3.8

3.7

3.6

3.5

5

6.1

6

5.8

5.6

5.4

5.2

5

4.9

4.8

4.7

4.6

4.5

4.4

6

7.3

7.2

7

6.7

6.5

6.3

6

5.9

5.8

5.7

5.6

5.4

5.3

7

8.6

8.4

8.1

7.9

7.6

7.4

7

6.9

6.8

6.7

6.6

6.4

6.3

8

9.8

9.6

9.3

9

8.7

8.4

8

7.9

7.7

7.6

7.4

7.2

7.1

10

12

12

12

11

11

10

10

9.9

9.7

9.5

9.3

9

8.9

12

15

14

14

13

13

13

12

12

12

11

11

11

11

13

16

16

15

15

14

14

13

13

13

12

12

12

12

15

18

18

17

17

16

16

15

15

15

14

14

14

13

16

20

19

19

18

17

17

16

16

15

15

15

14

14

20

24

24

23

22

22

21

20

20

19

19

19

18

18

25

31

30

29

28

27

26

25

25

24

24

23

23

22

32

39

38

37

36

35

33

32

32

31

30

30

29

28

40

49

48

47

45

43

42

40

39

39

38

37

36

35

50

61

60

58

56

54

52

50

49

48

47

46

45

44

63

77

76

73

71

68

66

63

62

61

60

58

57

56

Influence of the Mains Frequency
Influence of the mains frequency on the tripping behavior IMA of the instantaneous release

16 2/3

50

60

100

200

300

400

IMA(f)IMA (50 Hz) [%]

91

100

101

106

115

134

141

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Load Carrying Capacity of Adjoining Miniature Circuit Breakers

1

1.00
Rated Diversity Factor

1

1

Mains Frequency f [Hz]
Description

1

1
0.90

1
1

0.80

1
1

0.70
1

2

3

4

5

6

7

8

1

Number of Circuit Breakers
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-115

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

1

Accessories Technical Data

1

Description

WMZSAUX
WMZSAUXTRIP

WMZSST

WMZSUVR

—

Electrical

1

Contact function

1

Rated operational voltage Un

1A + 1B

—

2 C/O

—

—

250 Vac

—

115 Vac—WMZSUVR115
230 Vac—WMZSUVR230

1

400 Vac—WMZSUVR400

1

Voltage range WMZSST110

1

Voltage range WMZSST415

1
1
1
1
1
1
1
1
1
1
1

—

12–110 Vac

—

—

12–60 Vdc

—

—

110–415 Vac

—

—

110–230 Vdc

—

Closing threshold [x Un]

—

—

0.8

Tripping threshold [x Un]

—

—

0.5

Rated frequency ƒ

50/60 Hz

50/60 Hz

50/60 Hz

2/2A

—

—

General use (UL/CSA)
AC—230/240 Vac

0.5/0.5A

—

—

Pilot duty

DC—110/120 Vdc

A600/Q600

—

—

Conventional free air thermal current Ith

4A

—

—

AC-13 Ie

3A (250 Vac)

—

—

AC-15 Ie

2A (250 Vac)

—

—

DC-13 Ie

0.5A (110 Vdc)

—

—

Rated insulation voltage Ui

250 Vac

—

—

Minimum operating voltage per contract Umin

—

Rated operational current

5 Vdc

—

Rated impulse withstand voltage (1.2/50μ) Uimp 2.5 kV

—

—

Rated conditional short-circuit current with 6A
back-up fuse ISC

1 kA

—

—

Max. admissible back-up fuse

4A gL

—

—

1

Mechanical
Standard front dimension

45 mm

45 mm

45 mm

1

Device height

80 mm

80 mm

80 mm

Mounting width

8.8 mm

17.6 mm

17.8 mm

1

Mounting

On MCB

IEC/EN 60715 top-hat rail

IEC/EN 60715 top-hat rail

1

Degree of protection enclosed

IP40

IP40

IP40

Terminal protection

Protection against electric shock to IEC 536

Protection against electric shock to IEC 536

Protection against electric shock to IEC 536

1

Terminals

Lift terminals

Twin-purpose terminals

Twin-purpose terminals

Solid

0.5 – 2.5 mm2

1–2.5 mm2

2 x (1–2.5) mm2

Flexible

0.5 – 2.5 mm2

1–2.5 mm2

2 x (1–2.5) mm2

0.8 – 1.0 Nm (7–9 lb-in)

2.4 Nm (21 lb-in)

0.8 Nm (7 lb-in)

1
1

Terminal capacity

Tightening torque of terminal screws

1
1
1
1
1
V4-T1-116

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

1.3

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Dimensions

1

Approximate Dimensions in Inches (mm)

1

Miniature Circuit Breakers
WMZS

1
0.22
(5.5)

1.20
(30.5)

1

0.18
(4.5)

1
1

3.15
(80.0)

3.15
(80.0)

3.15
(80.0)

1

1.77
(45.0)

1
0.69
(17.5)

1.38
(35.0)

1P

2P

2.07
(52.5)

1

2.36
(60.0)

3P

Auxiliary Contacts
WMZSAUX

1

0.43
(11.0)

1.73
(44.0)

1
1

Shunt Releases
WMZSST

1

2.36
(60.0)
1.73
(44.0)

1

0.08
(2.0)
0.38
(9.6)

3.15
(80.0)

0.69
(17.6)

0.22
(5.5)

1.03
(26.2)

0.13
(3.4)

0.13
(3.4)

0.39
(10.0)

1.73
(44.0)
2.36
(60.0)

0.22
(5.5)

1
1
1
1
1

Undervoltage Releases
WMZSUVR

WMZSAUXTRIP

1
1

2.36
(60.0)
0.35
(9.0)

1
1

1.77
(45.0)

3.36
(85.4)

0.35
(8.9)

1.77
(45.0)

3.15
(80.0)

1.73
(44.0)

1

0.38
(9.6)

3.15
(80.0)

1

1.77
(45.0)

1

3.15
(80.0)

1

1.77
(45.0)
0.70
(17.8)

0.22
(5.5)

1.73
(44.0)

1

2.36
(60.0)

1

0.22
(5.5)

1
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

V4-T1-117

1.3
1

Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors

Approximate Dimensions in Inches (mm)

1

Busbar and Accessory Weights and Dimensions

1

Catalog
Number

Unit
Weight Lbs (kg)

1

WMZS1P57T

0.64 (0.29)

39.72 (1009.0)

0.59 (15.0)

0.59 (15.0)

WMZS2P56T

1.41 (0.64)

39.02 (991.0)

0.87 (22.0)

1.46 (37.0)

1

WMZS3P57T

1.83 (0.83)

39.72 (1009.0)

0.87 (22.0)

1.46 (37.0)

1

WMZS1P37TAUX

0.57 (0.26)

38.78 (985.0)

0.59 (15.0)

0.59 (15.0)

WMZS2P46TAUX

1.39 (0.63)

39.72 (1009.0)

0.87 (22.0)

1.46 (37.0)

WMZS3P48TAUX

1.74 (0.79)

38.66 (982.0)

0.87 (22.0)

1.46 (37.0)

WMZS1P57T25

0.79 (0.36)

39.72 (1009.0)

0.59 (15.0)

0.59 (15.0)

1

WMZS2P56T25

1.74 (0.79)

39.02 (991.0)

0.87 (22.0)

1.46 (37.0)

1

WMZS3P57T25

2.29 (1.04)

39.72 (1009.0)

0.87 (22.0)

1.46 (37.0)

WMZS1P37T25AUX

0.68 (0.31)

38.78 (985.0)

0.59 (15.0)

0.59 (15.0)

1

WMZS2P46T25AUX

1.61 (0.73)

39.72 (1009.0)

0.87 (22.0)

1.46 (37.0)

WMZS3P48T25AUX

2.14 (0.97)

38.66 (982.0)

0.87 (22.0)

1.46 (37.0)

1

WMZS35EXT

0.07 (0.03)

2.36 (60.0)

0.67 (17.0)

1.14 (29.0)

1

WMZSBCONA

0.07 (0.03)

1.57 (40.0)

0.71 (18.0)

1.18 (30.0)

WMZSBBTC

0.007 (0.003)

3.35 (85.0)

0.47 (12.0)

0.94 (24.0)

WMZS1CAP

0.002 (0.001)

0.55 (14.0)

0.20 (5.0)

0.39 (10.0)

WMZS3CAP

0.002 (0.001)

0.94 (24.0)

0.87 (22.0)

0.39 (10.0)

1

1

Length

Width

Height

1
1

L

W

1
1

L1

L2

L1

L2

L1

L2

L1

L2

L1

L2

1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-118

Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com

L1

L2

H



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Author                          : Zoltun Design
Create Date                     : 2013:03:20 12:46:21-04:00
Modify Date                     : 2013:03:20 13:05:33-04:00
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Metadata Date                   : 2013:03:20 13:05:33-04:00
Producer                        : Acrobat Distiller 10.1.5 (Windows)
Format                          : application/pdf
Title                           : Miniature Circuit Breakers and Supplementary Protectors
Creator                         : Zoltun Design
Document ID                     : uuid:d12f40bb-5bd0-44f2-8470-8f778d667d9c
Instance ID                     : uuid:d8f0f314-7df2-49e6-ac13-a5b2481ec5cd
Page Count                      : 118
EXIF Metadata provided by EXIF.tools

Navigation menu