PACSystems RX3i Energy Pack, IC695ACC400, GFK 2724 Installation Directions

42265-Attachment 42265-Attachment 42265-Attachment 004810 Batch12 unilog cesco-content

2014-11-11

: Pdf 42265-Installationsheet 42265-InstallationSheet 004810 Batch12 unilog

Open the PDF directly: View PDF PDF.
Page Count: 4

PACSystems RX3i
IC695ACC400
GFK-2724 Energy Pack*
September 2011
The PACSystems* RX3i Energy Pack is intended for use with an RX3i CPE305 or CPE310
controller CPU. In the event of loss of system power, the Energy Pack maintains power long
enough for the CPU to write its user memory contents to non-volatile storage (flash)
memory.
The Energy Pack can be mounted on the left side of an RX3i module and is connected to
the CPU using cable IC695CBL001. The Energy Pack charges from the RX3i 24 VDC from
the CPE3xxx, via the I695CBL001 cable that connects the CPE to the Energy Pack, while
the system is powered up.
The Energy Pack is compliant with EU RoHS Directive 2002/95/EC using the following
exemptions identified in the Annex: 7(a), 7(c)-I and III.
Related Documents
PACSystems CPU Reference Manual, GFK-2222
PACSystems RX3i System Manual, GFK-2314
Additional documentation for PACSystems RX3i products is available on the Support
website: www.ge-ip.com/support.
Ordering Information
Description
Catalog Number
RX3i CPU Energy Pack
IC695ACC400
Energy Pack Cable, 3 ft. (0.91m)
IC695CBL001
ACC400
CPU
Energy
Pack
Energy Pack Specifications
Dimensions, including mounting brackets and latch
Operating temperature
For cable specifications, see page 3.
For product standards, general operating specifications, and installation requirements for the RX3i system, refer
to the PACSystems RX3i Hardware and Installation Manual, GFK-2314.
* indicates a trademark of GE Intelligent Platforms, Inc. and/or its affiliates. All other trademarks are the property of their respective
owners.
2 IC695ACC400
GFK-2724
Installation
The Energy Pack is mounted on the left side of an RX3i module. To avoid taking up a backplane slot, it should be
mounted on the module (usually a power supply) in slot 0 of the rack. It is connected to the CPU by cable
IC695CBL001.
Note that, when mounted on a module in slot 0, the Energy Pack will extend approximately 13mm (0.5") beyond
the left side of the backplane.
To install the Energy Pack:
1. Engage the Energy Pack’s mounting hooks on the frame of the module as shown in the figure below.
2. Rotate the bottom of the Energy Pack into place, engaging the bottom hooks. The latch will snap into place.
3. Connect the IC695CBL001 cable from the connector on the bottom of the Energy Pack to the corresponding
connector on the bottom of the CPU.
Energy Pack
Bottom View
Energy Pack Front View, Installation
POWER
P/S FAULT
OVERTEMP
OVERLOAD
Power Supply
40W AC
PACSystems
RX
3i
Cable IC695CBL001 to
Energy Pack connector
on bottom of CPU
IC695ACC400 3
GFK-2724
Operation
Note: When the Energy Pack is powered up for the first time, or is in a system that has been powered down
long enough to completely discharge the Energy Pack, it may require a few seconds for it to charge to its
operating level. The Energy Pack will report a Charging state to the CPU during this time.
The Energy Pack provides the following status information to the CPU, which the CPU uses to generate LED
indications and fault messages. For details on these indications and faults, refer to the CPU user documentation.
Charging: The Energy Pack is charging; not yet charged above the minimum operating voltage.
Fault: A hardware fault exists in the Energy Pack.
Low capacitance: The Energy Pack is near its end of life and should be replaced.
Charged: The Energy Pack is charged above its minimum operating voltage and is ready to support
CPU operation.
Replacement Schedule
Replacement schedules for Energy Pack modules can be based on the following estimates.
Energy Pack Typical Life Expectancy
Surrounding Air
Temperature
Typical Life Expectancy
0°C
10+ years
10°C
10+ years
20°C
10+ years
30°C
10+ years
40°C
10+ years
50°C
10+ years
60°C
4.5 years
Diagnostics
Note: Any testing of this unit should be performed only by qualified personnel who are trained in electrical safety
practices and procedures. This unit is not user-serviceable.
IC695CBL001 Cable Specifications
This cable uses straight-through end-to-end wiring (pin 1 to pin 1, etc.).
Crimp housing
Material: Nylon 66 Or Equivalent
UL rating: UL 94V-0
Material: Phosphorous bronze
Crimp contact
Current rating: 3.8 AMPS AT 95°C
Plating: 10µ inches minimum gold on contact area and 150µ inches minimum tin over on solder
area and 50µ inches nickel under plating on entire material
Gauge: 24AWG
Cables
Insulation: PVC
Conductors: TINNED COPPER
Voltage Rating: 300 VAC
Connector type
Samtec IPD1-04-D-K
4 IC695ACC400
GFK-2724
General Conditions of Safe Use
This product is intended for use with the RX3i system. Its components are considered to be open
equipment [having live electrical parts that may be accessible to users] and must be installed in a
protective enclosure or incorporated into an assembly that is manufactured to provide safety. As a
minimum, the enclosure or assembly shall provide a degree of protection against solid objects up to
12mm (e.g. fingers). This equates to a NEMA/UL Type 1 enclosure or an IP20 rating (IEC60529) providing
at least a pollution degree 2 environment.
Installation in Hazardous Areas
The following information is for products installed in Class 1 Division/Zone 2 environments:
THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1, DIVISION 2 GROUPS A B C D OR IN ZONE 2
AREAS WHEN INSTALLED IN A MINIMUM IP54 RATED ENCLOSURE.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR
CLASS I, DIVISION 2.
WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE
REPLACING OR WIRING MODULES.
WARNING - EXPLOSION HAZARD - DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS
POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS.