Data Sheet DB EN TRIO/+UPS/1AC/24DC/5
2014-07-04
: Pdf 445658-Attachment 445658-Attachment 012596 Batch5 unilog
Open the PDF directly: View PDF .
Page Count: 16
Download | |
Open PDF In Browser | View PDF |
TRIO-UPS/1AC/24DC/5 Uninterruptible power supply with integrated power supply unit INTERFACE Data sheet 104103_en_00 1 © PHOENIX CONTACT - 2009-09-01 Description The TRIO-UPS/1AC/24DC/5 provides an uninterruptible 24 V DC voltage at a maximum load current of up to 5 A in both an error-free AC power supply network and in the event of power failure. Features It is designed specifically for supplying industrial PCs (IPC). – The power supply unit and the electronic switch-over unit are housed in the same housing. – In the event of supply voltage failure, buffer mode is activated without interruption. In this operating mode, the output voltage is directly dependent on the battery voltage. In the event of a voltage dip, the IPC continues operating without interruption, thus increasing system availability. Uncontrolled shutdown is avoided. The TRIO-UPS/1AC/24DC/5 can be parameterized using a service PC and the UPS-CONF configuration and management software via an IFS-USB-PROG-ADAPTER. – – – Space-saving The TRIO-UPS combines a power supply unit and electronic switch-over unit in the same housing Flexible Rechargeable battery module with 1.3, 3.4, 7.2 or 12 Ah Autonomous In the event of AC mains failure, the industrial PC continues operating without interruption Time-saving When the supply voltage is reapplied, the industrial PC starts automatically Parameterizable Can be parameterized with the PC or configuration stick For convenient parameter transfer between various TRIOUPS devices, the IFS-CONFSTICK configuration stick is available as an option. DANGER Never carry out work when voltage is present. The device contains dangerous live elements and high levels of stored energy. Depending on the ambient temperature and load, the housing can become very hot. Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/download. This data sheet is valid for all products listed under "Ordering data" on page 3. TRIO-UPS/1AC/24DC/5 2 Table of contents 1 Description.................................................................................................................................. 1 2 Table of contents ........................................................................................................................ 2 3 Ordering data.............................................................................................................................. 3 4 Technical data ............................................................................................................................ 3 4.1 4.2 4.3 4.4 4.5 I/O data........................................................................................................................................................... 3 Battery management ...................................................................................................................................... 4 Signaling and switching outputs ..................................................................................................................... 5 Ambient conditions......................................................................................................................................... 5 Standards/approvals ...................................................................................................................................... 6 5 Safety regulations ....................................................................................................................... 7 6 Connection, operating, and indication elements ......................................................................... 8 6.1 6.2 6.3 6.4 6.5 7 Connection terminal blocks ............................................................................................................................ 8 Block diagram ................................................................................................................................................ 9 Input ............................................................................................................................................................... 9 Output .......................................................................................................................................................... 10 LED indicators .............................................................................................................................................. 10 Installation .................................................................................................................................11 7.1 7.2 Narrow mounting position............................................................................................................................. 11 Flat mounting position .................................................................................................................................. 11 8 Rechargeable battery module....................................................................................................12 9 Method of operation...................................................................................................................13 9.1 9.2 9.3 9.4 9.5 9.6 Output voltage .............................................................................................................................................. 13 Remote shutdown ........................................................................................................................................ 13 Buffer time setting ........................................................................................................................................ 13 PC mode ...................................................................................................................................................... 13 PC idle time .................................................................................................................................................. 14 Battery management .................................................................................................................................... 15 10 Interfaces...................................................................................................................................15 10.1 10.2 10.3 Config.-Port .................................................................................................................................................. 15 IFS-USB-PROG-ADAPTER ......................................................................................................................... 15 IFS-CONFSTICK.......................................................................................................................................... 15 11 UPS-CONF configuration and management software ...............................................................16 104103_en_00 PHOENIX CONTACT 2 TRIO-UPS/1AC/24DC/5 3 Ordering data UPS system Description Type Order No. Pcs./Pkt. Uninterruptible power supply with integrated power supply unit TRIO-UPS/1AC/24DC/5 2866611 1 The TRIO-UPS/1AC/24DC/5 is supplied without a rechargeable battery module. The rechargeable battery module must be ordered separately (see accessories). Accessories Description Type Order No. Rechargeable battery module, 24 V DC, 1.3 Ah MINI-BAT/24DC/1.3AH 2866417 1 Rechargeable battery module, 24 V DC, 3.4 Ah QUINT-BAT/24DC/3.4AH 2866349 1 Pcs./Pkt. Rechargeable battery module, 24 V DC, 7.2 Ah QUINT-BAT/24DC/7.2AH 2866352 1 Rechargeable battery module, 24 V DC, 12 Ah QUINT-BAT/24DC/12AH 2866365 1 Configuration and management software UPS-CONF 2320403 1 USB data link cable between the UPS and IPC IFS-USB-PROG-ADAPTER 2811271 1 Configuration stick for parameter transfer between various TRIO-UPS/1AC/24DC/5 devices IFS-CONFSTICK 2986122 1 4 Technical data 4.1 I/O data Input data Nominal input voltage (wide-range input) 100 ... 240 V AC Input voltage range (nominal load) 85 ... 264 V AC (< 90 V AC derating: 2.5%/V) 100 ... 350 V DC (UL508: 100 ... 250 V) Frequency 45 ... 65 Hz Approximate current consumption (mains operation and battery charging/ maximum) At 230 V AC At 120 V AC Inrush current limiting / I²t at 25°C 0.95 A/1.1 A 1.7 A/1.8 A typical < 44 A / < 1.3 A²s Switch-on time after applying the mains voltage At 230 V AC At 120 V AC 150 ms 200 ms Transient surge protection Varistor Internal input fuse T 6.3 A Recommended backup fuse Circuit breaker Discharge current to PE 6 A/10 A/16 A (B characteristic) 0.8 mA Output data Rise time < 100 ms Residual ripple < 10 mVPP Switching peaks < 25 mVPP Parallel connection to increase the buffer time Yes, 2 Surge protection against internal surge voltages Yes, < 35 V DC Maximum resistance to return supply 35 V DC 104103_en_00 PHOENIX CONTACT 3 TRIO-UPS/1AC/24DC/5 Output data in mains operation (AC input voltage present) Nominal output voltage UN 24 V DC Output voltage (adjustable) 22.5 ... 29.5 V DC Nominal output current, > 24 V DC constant capacity (-25°C to +70°C) 5A Derating (above 55°C) 2.5%/K Current limit 6 A, approximately Connection of capacitive loads Yes, unlimited Control deviation < 1% (static load change 10 ... 90%) Approximate efficiency (mains operation and battery charging) At 230 V AC At 120 V AC 88% 86% Approximate power dissipation (mains operation and battery charging) At 230 V AC At 120 V AC 16 W 20 W Output data in battery operation (AC input voltage not present) Nominal output voltage UN 24 V DC Output voltage (UOUT = UBAT - 0.5 V ) 27.9 ... 19.2 V DC - 0.5 V Nominal output current (-25°C to +70°C) 5A Derating (above 55°C) 2.5%/K Current limit 6 A, approximately Connection of capacitive loads Yes, 3300 µF Efficiency > 86% Power dissipation Maximum no load Maximum nominal load 2W 4W Maximum buffer time (adjustable per minutes) 0.5; 1; 2; 3; 5; 10; 15; 20; PC mode Overload fuse (electronic) Yes Remote shutdown Yes 4.2 Battery management Battery management Charging characteristic curve I/U Charging current 1 (preset/minimum/maximum) 1.0 A/0.2 A/1.5 A End-of-charge voltage 1 (preset/minimum/maximum) 27,6 V DC / 25 V DC / 30 V DC Temperature compensation 1 (preset/minimum/maximum) 42 mV/K / 0 mV/K / 200 mV/K Battery presence check/time interval 60 s Battery quality check 1 (preset/minimum/maximum) 12 h/4 h/200 h Protection against total discharge 1 (preset/minimum/maximum) 19.2 V DC / 18 V DC / 21 V DC "Battery almost flat" alarm signaling threshold 1 (preset/minimum/maximum) 20.4 V DC / 18 V DC / 30 V DC 1 Can be adjusted via UPS-CONF software 104103_en_00 PHOENIX CONTACT 4 TRIO-UPS/1AC/24DC/5 4.3 Signaling and switching outputs Status indicators Mains voltage OK (Power in OK) Green LED, static ON Alarm LED indicator Switching output Current limit (internal) Red LED, static ON 24 V DC, active high 200 mA Battery operation (Battery Mode) LED indicator Switching output Current limit (internal) Signal options 1 Yellow LED, static ON 24 V DC, active high 200 mA Bat.-Mode, Bat.-Mode Delayed Battery charging (Battery Charge) LED indicator Switching output Current limit (internal) Signal options 1 1 Yellow LED, flashing 24 V DC, active high 200 mA Bat.-Charge, Bat.-Mode, Bat.-Mode Delayed, battery almost flat Can be adjusted via UPS-CONF software 4.4 Ambient conditions Climatic requirements Ambient temperature Operation (> 55°C derating) Storage/transport Humidity at +25°C, no condensation -25°C ... +70°C -40°C ... +80°C 95% Pollution degree according to EN 50178 2 Climatic class 3K3 Mechanical requirements Vibration (operation) < 15 Hz, amplitude ±2.5 mm according to IEC 60068-2-6 15 Hz ... 150 Hz, 2.3g, 90 min. Shock according to IEC 60068-2-27 30g in each direction General data Insulation voltage I/O (type/routine test) 4 kV AC/2 kV AC Input/PE (type/routine test) 2 kV AC/2 kV AC Output/PE (routine test) 500 V DC Mounting position according to EN 60715 Degree of protection IP20 Protection class (with PE connection) I MTBF according to IEC 61709 (SN 29500) > 500,000 h Material Aluminum (AlMg3)/zinc-plated sheet steel Dimensions (W/H/D) 60 mm x 130 mm x 118 mm Weight 1.1 kg 104103_en_00 PHOENIX CONTACT 5 TRIO-UPS/1AC/24DC/5 4.5 Standards/approvals Standards/approvals Electrical equipment of machines (surge voltage category III) EN 60204 Safety transformers for switched-mode power supply units IEC 61558-2-17 Electrical safety (of information technology equipment) EN 60950/VDE 0805 UL/C-UL Recognized UL 60950 Industrial control equipment UL/C-UL Listed UL 508 Electronic equipment for use in power installations EN 50178 (VDE 0160) PELV/SELV PELV (EN 60204)/SELV (IEC 60950) Safe isolation VDE 0100-410 Protection against electric shock DIN 57100-410 Protection against electric shock, basic requirements for safe isolation in electrical equipment DIN VDE 0106-101 Limitation of mains harmonic currents EN 61000-3-2 u U Conformance with EMC Directive 2004/108/EC, noise immunity according to 2006/95/EC (electromagnetic compatibility) Noise immunity according to EN 61000-6-2 Electrostatic discharge according to EN 61000-4-2 Electromagnetic HF field according to EN 61000-4-3 Fast transients (burst) according to EN 61000-4-4 Housing Level 3 Contact discharge 6 kV Air discharge 8 kV Remark Criterion B Housing Level 3 Frequency range 80 MHz ... 2 GHz Field strength 10 V/m Remark Criterion A Input 4 kV (Level 4 - asymmetrical: Cable to ground) Output 2 kV (Level 4 - asymmetrical: Cable to ground) Signal 1 kV (Level 4 - asymmetrical: Cable to ground) Remark Criterion B Surge current loads (surge) according to EN 61000-4-5 Input 4 kV (Level 4 - asymmetrical: Cable to ground) 2 kV (Level 4 - asymmetrical: Cable to cable) Output 2 kV (Level 3 - asymmetrical) 1 kV (Level 3 - symmetrical) Conducted interference according to EN 61000-4-6 Noise emission according to EN 61000-6-3 104103_en_00 Signal 2 kV (Level 3 - asymmetrical) Remark Criterion B Input/output/signal Level 3 Frequency range 10 kHz ... 80 MHz Voltage 10 kV Remark Criterion A Radio interference voltage according to EN 55011 EN 55011 (EN 55022) Class B, industrial and residential applications PHOENIX CONTACT 6 TRIO-UPS/1AC/24DC/5 5 Safety regulations Installation notes NOTE: – The device must only be installed, operated, and maintained by qualified personnel. – Follow the installation instructions. – When installing and operating the device, the applicable safety directives (including national safety directives), accident prevention regulations, as well as general technical regulations, must be observed. – For the safety data, please refer to the package slip and certificates (conformity assessment, other approvals, if necessary). – Do not repair the device yourself, replace it with an equivalent device. – Repairs may only be carried out by the manufacturer. The manufacturer is not liable for damage resulting from violation. – The IP20 degree of protection (IEC 60529/ EN 60529) of the device is intended for use in a clean and dry environment. – The device must not be subject to mechanical strain and/or thermal loads, which exceed the limits described. Connection notes NOTE: Electrostatic discharge The device contains components that can be damaged or destroyed by electrostatic discharge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and EN 61340-5-2. 104103_en_00 PHOENIX CONTACT 7 TRIO-UPS/1AC/24DC/5 6 Connection, operating, and indication elements 6.1 Connection terminal blocks Use a screwdriver with the correct blade width for wiring. For reliable and safe-to-touch connections, strip 8 mm off the cable ends. The following cable cross-sections can be connected: + + 3 Ala rm Ba t.- Mo t.- Ch a rg e Re tp 24 ut DC V 5A mo te OFF ON Re mo R2 tte ry Ad 22 jus .5- t 29 .5 V R1 te Ba tm ax + Cu (D sto efau lt m min 0.5 ) 1 11 2 In order to comply with UL approval, use copper cables that are designed for operating temperatures >75°C. 2 8 4 TRIO DC-UPS de Ba Ou 5 6 7 Terminal Rigid Stranded AWG Tightening block torque No. [mm²] [mm²] [Nm] [lb in] 1 - 3, 0.2 - 2.5 0.2 - 2.5 24 - 12 0.5 - 0.6 3.5 - 4.5 5 - 7, ! PC -M 3 od e 5 15 rm Ba t Ba .-Mo t.d Po Cha e we rge r in Ov OK erlo ad L (+) N (-) Inp 10 ut A 0-2 C 40 V 1 20 Ala 9 nfig .-P or t 1. S D P 2. res ATA Ins s B S ert utt T ST on IC ST IC an K Kw d 1. ICK In 2. se DATA ithin Pre rt S 4s ec ss TIC UP Bu K S tto n> 6s ec 13 12 8 Co UP 10 10 14 Figure 1 No. 1 2 3 4 5 6 7 8 9 0 ! " § $ TRIO-UPS/1AC/24DC/5 structure Description 100 ... 240 V AC input 24 V rechargeable battery module connection 24 V DC output, buffered 22.5 ... 29.5 V DC potentiometer Active switching output: Alarm Active switching output: Bat.-Mode Active switching output: Bat.-Charge Red LED indicator: Alarm Yellow LED indicator: Bat.-Mode/Bat.-Charge Green LED indicator: Power in OK/Overload Remote shutdown (R1, R2) Buffer time setting 0.5 ... 20 minutes, PC mode, unlimited ∞ Config.-Port "Confirm" button 104103_en_00 PHOENIX CONTACT 8 TRIO-UPS/1AC/24DC/5 6.2 Block diagram J Config.-Port IFS t...[min] Confirm 2x 12V Remote On/Off R1 Battery R2 Alarm Bat.-Mode Bat.-Charge L (+) Output DC 24 V 5 A PS N (-) Figure 2 6.3 Block diagram for the TRIO-UPS/1AC/24DC/5 Input The 100 ... 240 V AC connection is made using the L (+) and N (-) screw connections. Device installation must be carried out according to the regulations of EN 60950. It must be possible to switch off the device using a suitable disconnecting device outside the power supply. Network type The device can be connected to single-phase AC networks or to two of the phase conductors of three-phase systems (TN, TT or IT networks according to VDE 0100-300/IEC 60364-3) with nominal voltages of 100 V AC ... 240 V AC. For operation using two phase conductors of a three-phase system, an all-pole disconnecting device must be provided. For example, primary side line protection could be used. TN-S An internal fuse is provided for device protection. Additional device protection is not required. If an internal fuse is blown, this is due to a device fault. In this case, send the device to Phoenix Contact for inspection. TN-C L N PE L L PEN L N + N - + TT - iT L1 L2 L3 L N L N + Figure 3 104103_en_00 - L N + - Single-phase network systems PHOENIX CONTACT 9 TRIO-UPS/1AC/24DC/5 1 + + Ala Ba Ba Re Ou tp 24 ut DC V 5A Re mo 4 V rm Mo Ch mo 2 de arg e te OF ONF R1 te R2 Ba Ad 22 jus .5-2 t 9.5 t.- t.- TRIO DC-UPS 3 tte tm + ry Cu ax sto (D efa ult min m 0.5 ) 3 1 2 8 PC -M 3 od e 5 20 Ala 15 rm L 10 Ba t. Ba -Mo t.-C de Po h we arge r in Ov OK erlo ad (+) N (-) 1 Inp 10 ut A 0-2 C 40 V 4 Co nfi g.- UP Po rt 1. S D P 2. ress ATA Inse B S rt utto TIC ST n ST IC an K Kw d 1. ICK In 2. se DATA ithin Pre rt S 4s ec ss TIC UP Bu K S tto n> 6s ec 5 Figure 4 Connection 6 No. 1 3 4 6.5 Description 100 ... 240 V AC input 24 V DC output, buffered 22.5 ... 29.5 V DC potentiometer LED indicators Figure 5 No. 8 9 0 7 8 8 9 9 10 10 The UPS is switched off or the UPS is operating in mains mode, battery mode is deactivated (remote), battery management is still active The UPS is starting mains operation, for the LED test all LEDs are switched on and off again once before the current operating state is indicated The UPS is operating in mains mode, the battery is OK and charged The UPS is operating in mains mode, the battery is OK and is charging (charge < 85% of nominal capacity) The UPS is operating in battery mode, the battery voltage UBAT is > 20.4 V The UPS is operating in battery mode, the battery is almost flat (battery voltage UBAT is < 20.4 V) UPS protection against total discharge has terminated battery mode (battery voltage UBAT = 19.2 V) and continues indication for a maximum of 10 hours The UPS is operating in mains mode, the battery is faulty The UPS has been overloaded in mains mode, the battery is OK and charged The UPS has been overloaded in mains mode, the battery is faulty LED indicators Description Red LED indicator: Alarm Yellow LED indicator: Bat.-Mode/Bat.-Charge Green LED indicator: Power in OK/Overload 104103_en_00 Description Red Status The 24 V DC connection is made using the "OUT DC 24 V, +, -" screw connections. The output voltage set upon delivery is 24 V DC. The output voltage can be set from 22.5 V DC to 29.5 V DC on the potentiometer. The signal outputs are connected via the "Alarm", "Bat.Mode", and "Bat.-Charge" terminal blocks. There are three LED status indicators and three active switching outputs for function monitoring. Yellow Output Green 6.4 Key LED OFF LED ON LED flashing PHOENIX CONTACT 10 TRIO-UPS/1AC/24DC/5 7 7.2 Installation A minimum spacing between other devices does not have to be observed in order to ensure correct device function. 7.1 Narrow mounting position Flat mounting position A flat mounting position can be achieved by mounting the module onto the DIN rail at a 90° angle. Mount the DIN rail adapter (UTA 107) as shown in the figure. The screws that were previously used to secure the UTA must be used: Torx T10 (0.8 Nm ... 0.9 Nm tightening torque). The power supply unit can be snapped onto all DIN rails according to EN 60715 and must be mounted horizontally (connection terminal blocks facing upwards and downwards). Mounting Position the module with the DIN rail guideway on the top edge of the DIN rail and then snap it downwards. A B Figure 8 Figure 6 Modification for flat mounting position Mounting the TRIO-UPS/1AC/24DC/5 Removal Release the snap-on catch using a screwdriver and then detach the module from the bottom edge of the DIN rail. B A Figure 7 104103_en_00 Removing the TRIO-UPS/1AC/24DC/5 PHOENIX CONTACT 11 TRIO-UPS/1AC/24DC/5 8 Rechargeable battery module The rechargeable battery module is connected to the power supply unit via the "Battery +" and "Battery -" terminal blocks 2. The batteries are sealed, maintenance-free lead AGM batteries, which are intended for operating temperatures of 0°C ... 40°C. They have a service life of six to nine years at an ambient temperature of 20°C. NOTE: Risk of short circuit The fuse for the rechargeable battery module must be removed when installing or replacing the module. In order to ensure immediate availability, all batteries are supplied fully charged. Startup should be carried out at the latest after nine months at 20°C ... 30°C, or after six months at 30°C ... 40°C. The following rechargeable battery modules are recommended: Rechargeable battery module Recommended charging current MINI-BAT/24DC/1.3Ah 15 A 0.8 A 2 QUINT-BAT/24DC/3.4Ah 1 25 A 1.0 A 2 1 QUINT-BAT/24DC/7.2Ah 2 x 25 A 1.5 A 2 QUINT-BAT/24DC/12Ah1 2 x 25 A 1.5 A 2 1 2 3 4 Fuse 1 Connection via plug connector, 14 mm 2 Can be adjusted via UPS-CONF software 30 4 10 t [h] 1 60 3 1 2 10 1 = 1.3Ah t [min] 2 = 3.4Ah 3 = 7.2Ah 4 = 12Ah 1 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 I [A] Figure 9 Characteristic curves for the rechargeable battery modules Battery mode can be exited after a predefined time has elapsed or by means of external shutdown. If the device is to be shut down after a specific time has elapsed, the time can be set via the selector switch " on the front of the device. When the supply voltage is reapplied, the device can switch to battery mode again. 104103_en_00 PHOENIX CONTACT 12 TRIO-UPS/1AC/24DC/5 9 Method of operation 9.1 Output voltage To set the parameters, an Interface interface (IFS) is used for data exchange between the TRIO-UPS and a suitable user interface on the IPC. The user is supported by help texts and graphics for the individual parameters. In mains operation (AC input voltage present) the output voltage of the TRIO-UPS corresponds to the setting at the potentiometer 4. In the event of supply voltage failure, battery mode is activated without interruption. The output voltage is now directly dependent on the battery voltage and is UBAT - 0.5 V. As an option, parameterization can be carried out using an IFS-CONFSTICK. Here, a parameter record is transferred from the TRIO-UPS to the IFS-CONFSTICK. This parameter record can then be written to any other TRIO-UPS. 9.2 In "PC mode", the UPS function follows a parameterizable chronological sequence of delay time, IPC shutdown, and IPC idle time. Remote shutdown If the connected load cannot be supplied from the power storage device in the event that the AC voltage fails, the UPS can be disabled via R1/R2. This shutdown can be performed during mains operation or while battery mode is active. UPS active, remote shutdown deactivated, default upon delivery: – Terminal points "R1" and "R2" are short circuited (with plug-in bridges by default upon delivery) OR 24 V DC is present at terminal point "R2". – If the supply voltage fails, the TRIO-UPS switches to battery mode. UPS not active, remote shutdown activated: – Terminal points "R1" and "R2" are not short circuited AND 0 V DC is present at terminal point "R2". – All LEDs are OFF. – If the supply voltage fails, the TRIO-UPS does not switch to battery mode, the device shuts down. – The connected loads are supplied and the rechargeable battery module is charged as long as the supply voltage is present. 9.3 Delay time: If the mains voltage is not applied again within the first 60 seconds of battery mode, for example, "Bat.-Mode" is indicated in order to shut down an IPC with a delay. IPC shutdown: Shutdown is performed via a data cable to the IPC. The IPC must be connected to the UPS via a USB data cable. The IPC is supplied by the TRIO-UPS for a parameterizable period of time, e.g., 2 minutes. Buffer time setting The time after which battery mode is exited is set via the " selector switch on the front of the device: – 0.5 to 20 minutes – Parameterizable time via software ("CUSTOM" switch position, default: 0.5 minutes) – Unlimited (buffering with the total stored energy) – PC mode (see Section 9.4 "PC mode" ) 9.4 PC mode In "PC mode", the UPS function follows a chronological sequence that can be parameterized via the software and individually optimized for the relevant IPC solution. Requirements: IFS-USB-PROG-ADAPTER data cable (Order No. 2811271) and UPS-CONF software (Order No. 2320403). 104103_en_00 PHOENIX CONTACT 13 TRIO-UPS/1AC/24DC/5 9.5 PC idle time Once the "PC shutdown" time has elapsed, the output voltage is switched off, e.g., for 30 seconds (also when the mains voltage is applied again). Power comes back on during set delay time 1 120/230V AC input 0V 3 24V DC output 0V 6 10 Bat. mode delayed: Active switching output (can be parameterized) 24V LED green POWER IN OK ON 0V OFF ON LED gelb Bat.-Mode 9 OFF PC response ON OFF Delay time PC shutdown Power comes back on during set time PC shutdown 1 AC input 120/230V 0V 3 DC output 24V 0V 6 Bat. mode delayed: Active switching output (can be parameterized) 10 LED green POWER IN OK 24V 0V ON OFF 9 LED yellow Bat. mode ON OFF PC response ON OFF PC shutdown Delay time Figure 10 104103_en_00 PC idle time Time diagrams PHOENIX CONTACT 14 TRIO-UPS/1AC/24DC/5 9.6 Battery management 10.3 IFS-CONFSTICK Battery management of the TRIO-UPS is divided into two checks that are performed cyclically during normal operation. The IFS-CONFSTICK is a multi-functional memory block for easy storage and back up of configuration and parameter data. Battery presence check Transferring parameters to the IFS-CONFSTICK The battery presence check is used to detect a correctly installed battery. If this is not the case, the check is failed and the green 0 and red 8 LED indicators are controlled statically. 10 Interfaces To transfer parameters, proceed as follows: 1. Press and hold down the "Confirm" button. 2. You now have four seconds to carefully insert the IFS-CONFSTICK in the "Config.-Port" on the TRIO-UPS, taking care to observe the connection direction. 3. Parameter transfer is started and indicated by the cyclic control of the three LED indicators. Sequence: Red Yellow - Green a) Error-free transfer: Green LED indicator ON b) Transfer error: Red LED indicator ON 10.1 Config.-Port Transferring parameters to the TRIO-UPS Battery quality check The battery quality check is a lifecycle test. It enables conclusions to be drawn, e.g., regarding the maximum lifecycle of the battery if the maximum charging time has been exceeded. In this case, the green 0 and red 8 LED indicators are controlled statically. The TRIO-UPS is connected to the USB connection on the service PC via the "Config.-Port" using the IFS-USB-PROGADAPTER data cable. 10.2 IFS-USB-PROG-ADAPTER PT ER The programming adapter (Order No. 2811271) represents the interface between the service PC and the TRIO-UPS and is required in order to parameterize the TRIO-UPS. XX XX XX B o. XX XX US PR O G -A DA 71 12 1 28 lN ria Se ix c en ho .p ce rfa nte w.i ww 32 8 US 25 B B-P lom ro be gra rg m , Ge m rm in g an Ad y ap te r on ta ct. co m IF S- US B- o.: .-N Ord To transfer parameters, proceed as follows: 1. Carefully insert the IFS-CONFSTICK in the "Config.Port" on the TRIO-UPS, taking care to observe the connection direction. 1. Press and hold down the "Confirm" button for at least six seconds. 2. Parameter transfer is started and indicated by the cyclic control of the three LED indicators. Sequence: Green Yellow - Red a) Error-free transfer: Green LED indicator ON b) Transfer error: Red LED indicator ON The following can be parameterized: – – – Figure 11 104103_en_00 Times Switching outputs Battery management Programming adapter PHOENIX CONTACT 15 TRIO-UPS/1AC/24DC/5 11 UPS-CONF configuration and management software The Windows-based UPS-CONF configuration and management software (Order No. 2320403) is used to parameterize the TRIO-UPS. The UPS-CONF configuration and management software can be downloaded free of charge at www.phoenixcontact.net/download. Various dialog boxes are available for parameterization. The current operating status of the TRIO-UPS is always displayed at the bottom of the dialog box. Figure 12 Example, TRIO-UPS status display A distinction is made between the following states: Status Operation mode Power Source Battery Condition Device Status Connection to UPS Meaning Preset operating mode at the selector switch " Power source that is currently active Current battery charging state Current state of the TRIO-UPS Connection status between service PC and TRIO-UPS If an alarm is detected or an existing online connection between the IPC and TRIO-UPS is interrupted, the UPS-CONF dialog box is automatically displayed on screen. The status is queried cyclically. 104103_en_00 PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com 16
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : No Page Mode : UseOutlines XMP Toolkit : 3.1-702 Producer : Acrobat Distiller 7.0.5 (Windows) Creator Tool : FrameMaker 7.1 Create Date : 2009:08:26 10:14:56Z Metadata Date : 2009:09:01 11:48:25+02:00 Modify Date : 2012:04:02 15:38:05+02:00 Format : application/pdf Title : Data Sheet DB EN TRIO/+UPS/1AC/24DC/5 Creator : PHOENIX CONTACT GmbH & Co. KG Description : Uninterruptible power supply with integrated power supply unit Document ID : uuid:a27dab05-5b5d-4dba-b35e-a03183ea1b7a Instance ID : uuid:39a9e296-bbb2-4980-9705-e23832d07d23 Page Count : 16 Subject : Uninterruptible power supply with integrated power supply unit Author : PHOENIX CONTACT GmbH & Co. KGEXIF Metadata provided by EXIF.tools