POWER INLET BOX Installation Directions
2014-07-05
: Pdf 480837-Installationsheet 480837-InstallationSheet 785399 Batch5 unilog
Open the PDF directly: View PDF .
Page Count: 3
POWER
INLET BOX
CAT. NO.
PBN50
50Amps, 120/240
VAC
INSTALLATION INSTRUCTIONS
IMPORTANT: Installation of this power inlet box and related wiring must be done by a qualified electrician
in compliance with all applicable electrical codes. When used to power a structure, this inlet must be used in
conjunction with a transfer switch. Not for indoor use. When using an engine driven generator, locate away
from doors and windows to avoid the build up of carbon monoxide from the engine exhaust in enclosed areas.
INSTALLING A REMOTELY LOCATED POWER INLET BOX FOR SUPPLYING
POWER TO THE POWER INLET OF A TRANSFER SWITCH OR PANEL
Mount the power inlet box on the outside of the building in a convenient location, using the three holes
provided in the back of the cabinet. Using copper wire only and approved wiring methods run the wiring
through one of the knockouts in the cabinet to a junction box located near the transfer switch. REMOVE
KNOCKOUT FROM THE INSIDE OF THE ENCLOSURE USING A SCREWDRIVER INSERTED
INTO THE SLOT IN THE KNOCKOUT AND STRIKE GENTLY WITH A HAMMER. If using
conduit, pull four color-coded wires (AWG #8 minimum, AWG #6 maximum) -- use green for ground, white
for neutral, and two other distinguishing colors (typically black and red) for the 240V line.
Strip the wire insulation 5/8" and connect the wires in the power inlet box as follows making sure there is no
wire insulation in any terminal and the inlet terminal screws are tightened to 20 inch-pounds torque:
Hot wires to the brass terminals marked "X" and "Y".
Neutral wire to the nickel-plated neutral terminal marked "W".
Ground inlet wire to green screw terminal marked “G.”
PREPARING A CORD FROM THE GENERATOR TO THE POWER INLET BOX:
Using a 4-conductor 50 Amp portable cord suitable for the purpose, attach a male plug matching the
configuration of the generator outlet (typically Type CS-6364N) to one end, and a Type CS-6364N connector
(which will mate with the power inlet in the power inlet box) to the opposite end.
Following the wiring device manufacturer's instructions, wire the generator plug and the Type CS-6364N
connector as follows:
Red and black wires to the brass terminals marked "X" and "Y".
White wire to the nickel-plated neutral terminal marked "W".
Green wire to the green ground terminal marked "G".