J7 Low Voltage Switch Gear Data Sheet 527544 Catalog

107619-Attachment 107619-Attachment 107619-Attachment 006085 Batch12 unilog cesco-content

2014-11-11

: Pdf 527544-Catalog 527544-Catalog 006085 Batch12 unilog

Open the PDF directly: View PDF PDF.
Page Count: 105

DownloadJ7 Low Voltage Switch Gear Data Sheet  527544-Catalog
Open PDF In BrowserView PDF
Table of Contents

Low Voltage Switch Gear
Selection Guide

H-2

J7KNA-AR

Mini Contactor Relays 4-pole

H-7

J7KNA

Mini Motor Contactor

H-15

J7KN

Motor Contactor

H-27

J7TKN

Thermal Overload Relay

H-57

J7MN

Motor Protection Circuit Breaker (MPCB)

H-69
H-83

LVSG

Appendix

H-1

Selection Guide

Low Voltage Switch Gear
Classification
Model

Mini Contactor Relays

Mini Motor Contactors

J7KNA - AR

J7KNA

J7KNA-4

4-pole

3-pole

4-pole

Remarks

AC and DC operated
4-, 6- and 8-contacts in different
configurations
Positively guided contacts
Screw fixing and snap fitting (DIN rail)

AC and DC operated
3 main poles
1 auxiliary contact
integrated (1NO or 1NC)

AC operated
4 main poles

Accessoirs

Auxiliar contact modules

Auxiliar contact modules
Suppressors
Link module MPCB - contactor

Auxiliar contact modules
Suppressors
Link module MPCB - contactor

Maximum power (AC3-380/415V)

No

4 kW; 5,5 kW

4 kW

Rated current (AC3-380/415V)

10 A (I th2)

9/12 A

9A

AC operated

Yes

Yes

Yes

DC operated

Yes

Yes

No

4 - pole version

Yes

No

Yes

Auxiliary contacts included

No

1NO or 1NC

No

Auxiliary contacts front
mounting

1NO/1NC
0NO/2NC
2NO/2NC
4NO/0NC

1NO/1NC
0NO/2NC
2NO/2NC

1NO/1NC
0NO/2NC
2NO/2NC

Auxiliary contacts side mounting No

No

No

Mechanical life span
(AC operated)

5 Mio.

5 Mio.

5 Mio.

Mechanical life span
(DC operated)

15 Mio.

15 Mio.

15 Mio.

Setting range (in A)

No

No

No

Page No.

H-7

H-15

H-15

Appearance

H-2

J7KN 24..KN 40

J7KN 50..KN 74

J7KN 85..KN 110

3-pole

3-pole

3-pole

3-pole

AC and DC operate
3 main poles
1 auxiliary contact integrated (1NO or
1NC)
max 4 auxiliary contacts front mounted

AC and DC operate
3 main poles
max 4 auxiliary contacts front mounted
2 auxiliary contacts side mounted (1NO
or 1NC)

AC and DC operate
3 main poles
max 4 auxiliary contacts front mounted
2 auxiliary contacts side mounted (1NO
or 1NC)

AC and DC operate
3 main poles
4 auxiliary contacts integrated
(1NO/1NC)

Auxiliar contact modules
Mechanical interlock
Suppressors
Link module MPCB-contactor
Pneumatic timers

Auxiliar contact modules
Mechanical interlock
Suppressors
Link module MPCB-contactor
Pneumatic timers

Auxiliar contact modules
Mechanical interlock
Suppressors
Pneumatic timers

Mechanical interlock
Suppressors

4 kW; 5,5 kW; 7,5 kW; 11 kW

11 kW; 15 kW; 18,5 kW

22 kW; 30kW; 37 kW

45 kW; 55 kW

10/14/18/22 A

24/32/40 A

50/62/74 A

85/110 A

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

1NO or 1NC

No

No

2NO + 2NC

max 4
NO/NC

max 4
NO/NC

max 4
NO/NC

No

No

1NO + 1NC

1NO + 1NC

1NO + 1NC

10 Mio.

10 Mio.

10 Mio.

5 Mio.

10 Mio.

10 Mio.

10 Mio.

5 Mio.

No

No

No

No

H-27

H-27

H-27

H-27

LVSG

Motor Contactors
J7KN 10..KN 22

H-3

Selection Guide

Low Voltage Switch Gear
Classification
Model

Motor Contactors

Thermal Overload Relays

J7KN 150..KN 175

J7KN 200

J7TKN-A

3-pole

3-pole

Remarks

AC and DC operate
3 main poles
2 auxiliary contacts integrated (1NO/
1NC)

AC and DC operate
3 main poles
4 auxiliary contacts integrated (1NO/
1NC)

Direct mounting
1 auxiliary contact (change over)

Accessoirs

No

No

No

Maximum power (AC3-380/415V)

75 kW; 90 kW

110 kW

Rated current (AC3-380/415V)

150/175 A

210 A

AC operated

Yes

Yes

DC operated

No

No

4 - pole version

No

No

Auxiliary contacts included

1NO + 1NC

2NO + 2NC

Auxiliary contacts front
mounting

No

No

Appearance

1NO + 1NC

Auxiliary contacts side mounting 1NO + 1NC

2NO + 2NC

Mechanical life span
(AC operated)

10 Mio.

10 Mio.

Mechanical life span
(DC operated)

10 Mio.

10 Mio.

Setting range (in A)

No

No

0,12..30 A

Page No.

H-27

H-27

H-57

H-4

Motor Protection Circuit Breakers (MPCB)

J7TKN-E..TKN-F

J7MN12

J7MN25

Direct mounting
Auto, -manual, -reset button
2 auxiliary contacts (1NO/1NC)

Separate mounting
2 auxiliary contacts (1NO/1NC)

Rocker operating switch
Short circuit release
Over load release
I cu = 100 kA (0,16..6,3 A)

Rotary operating switch
Short circuit release
Over load release
I cu = 100 kA (0,16..12,5 A)

Sets for single mounting
Busbar sets

Sets for single mounting
Busbar sets

Trip indicating contact
Plastic enclosures
2 contacts side mounted
2 contacts front mounted
Bus bar system

Trip indicating contact
Plastic enclosures
3 contacts side mounted
2 contacts front mounted
Bus bar system

1NO + 1NC

1NO + 1NC

1NO + 1NC

1NO + 1NC

1NO + 1NC

1NO + 1NC

100000

100000

0,12..74 A

60..220 A

0,11..12 A

0,11..25 A

H-57

H-57

H-69

H-69

LVSG

Thermal Overload Relays
J7TKN-B..TKN-D

H-5

Selection Guide

Low Voltage Switch Gear
Classification
Model

Motor Protection Circuit Breakers (MPCB)
J7MN50

J7MN100

Remarks

Rotary operating switch
Short circuit release
Over load release
I cu = 50 kA

Rotary operating switch
Short circuit release
Over load release
I cu = 50 kA

Accessoirs

Trip indicating contact
Plastic enclosures
2 contacts side mounted
3 contacts front mounted
Bus bar system

Trip indicating contact
Plastic enclosures
2 contacts side mounted
3 contacts front mounted
Bus bar system

1NO + 1NC

1NO + 1NC

Auxiliary contacts side mounting 1NO + 1NC

1NO + 1NC

Mechanical life span
(AC operated)

50000

50000

Setting range (in A)

22..50 A

45..100 A

Page No.

H-69

H-69

Appearance

Maximum power (AC3-380/415V)
Rated current (AC3-380/415V)
AC operated
DC operated
4 - pole version
Auxiliary contacts included
Auxiliary contacts front
mounting

Mechanical life span
(DC operated)

H-6

Mini Contactor Relays 4-pole

J7KNA-AR

)

Main contactor
• AC & DC operated
• 4-, 6- and 8-pole versions in different configurations
• Positively guided contacts
• Screw fixing and snap fitting (35 mm DIN rail)
• Rated current = 10A (Ith)
• Suitable for electronic devices (DIN 19240)
• Finger proof (VBG 4)

Accessories
• 2- and 4-pole additional auxiliary contacts in different
configurations

Approved Standards
Standard

Guide No (US,C)

UL

NKCR, NKCR7

ICE 947-5-1
VDE 0660
EN 60947-5-1

LVSG

Ordering Information
■ Model Number Legend
1. Mini Contactor Relays

7KNA-##-##-#####
1
2 3
4
1)
2)
3)

4)

Mini Contactor
AR:
Contactor Relay
Combination of NO / NC contacts
22:
2 NO 2 NC
31:
3 NO 1NC
40:
4 NO 0NC
Coil voltage (AC operated)
24:
AC24V 50/60Hz
48:
AC48V 50Hz
110:
AC110-115V 50Hz,AC120-125V 60Hz
230:
AC220-230V 50Hz,AC240V 60Hz
240:
AC230V-240V 50Hz
400:
AC380-400V 50Hz,AC440V 60Hz
415:
AC400-415V 50Hz
550:
AC525-550V 50Hz,AC600V 60Hz

Coil voltage (DC operated)
24D: DC24V
48D: DC48V
60D: DC60V
110D: DC110V
125D: DC125V
24VS: DC24V with diode
48VS: DC48V with diode
110VS: DC110V with diode
2. Aux. Contact Modules for Mini Contactor Relays

73KN-##-##-#
1
2 3 4
1)
2)
3)

Auxiliary Contact Modules
A:
for mini contactor relay
Combination of NO/NC contacts
11:
1 NO 1 NC
02:
0 NO 2 NC
22:
2 NO 2 NC
40:
4 NO 0 NC

Mini Contactor Relays 4-pole

J7KNA-AR

H-7

■ System overview
Mini Contactor Relays 4-pole
AC Operated
Contacts

NO

NC

Distinc.
Number
acc. to
DIN EN
50011

Ratings
AC15
230V
A

Type

400V
A

Thermal
Rated
Current
Ith
A

2

10

J7KNA-AR-40 24

24
230

Coil voltage 1)
24V 50/60Hz
220-230V 50Hz

Pack

Weight

pcs.

kg/pc.

10

0,16

10

0,16

10

0,16

4-pole, With Screw Terminals
4

-

40E

3

J7KNA-AR-40 230

3

1

31E

3

2

10

J7KNA-AR-31 24
J7KNA-AR-31 230

2

2

22E

3

2

10

J7KNA-AR-22 24
J7KNA-AR-22 230

1) Other coil voltages see page 10

DC Solenoid Operated
Contacts

NO

NC

Distinc.
Number
acc. to
DIN EN
50011

Ratings
AC15
230V
A

Type

Pack

Weight

400V
A

Thermal
Rated
Current
Ith
A

Coil voltage 24V DC 2,5W

pcs.

kg/pc.

4-pole, With Screw Terminals
4

-

40E

3

2

10

J7KNA-AR-40 24D (-VS)1)

10

0,19

3

1

31E

3

2

10

J7KNA-AR-31 24D (-VS)1)

10

0,19

2

2

22E

3

2

10

J7KNA-AR-22 24D (-VS)1)

10

0,19

Type

Pack

Weight

pcs.

kg/pc.

J73KN-A-11

10

0,04
0,04

1) VS = with diode

Auxiliary Contact Blocks for Contactor Relays J7KNA-AR

H-8

Contacts

Ratings

NO

NC

AC15
230V
A

400V
A

Thermal
Rated
Current
Ith
A

1

1

3

2

10

-

2

3

2

10

J73KN-A-02

10

4

-

3

2

10

J73KN-A-40

10

0,04

2

2

3

2

10

J73KN-A-22

10

0,04

Mini Contactor Relays 4-pole J7KNA-AR

■ System overview
Mini Contactor Relays 4-pole
AC Operated
Wiring Diagrams

Distinc.
Number
acc. to
DIN EN
50011

Auxiliary Contact Blocks

Type

NO

NC

Contactor Relay with Auxiliary Contact Contacts suitable for Electronic
Block
Circuits according to DIN 19240
Distinc. Number
for rated voltage 24V DC
according to
(test ratings 17V DC, 5mA)
DIN EN 50011
NO
NC
Positively guided contacts

J73KN-A-11

1

1

51E

5

1

J73KN-A-02

0

2

42E

4

2

J73KN-A-40

4

0

80E

8

0

J73KN-A-22

2

2

62E

6

2

J73KN-A-11

1

1

42Y

4

2

J73KN-A-02

0

2

33Y

3

3

J73KN-A-40

4

0

71Y

7

1

J73KN-A-22

2

2

53Y

5

3

J73KN-A-11

1

1

33Y

3

3

J73KN-A-02

0

2

24Y

2

4

J73KN-A-40

4

0

62Y

6

2

J73KN-A-22

2

2

44Y

4

4

4-pole, With Screw Terminals
40E

31E

22E

Preferable combinations with
distinctive letter „E“
according to DIN EN 50011

DC Solenoid Operated
Wiring Diagrams

Distinc.
Number
acc. to
DIN EN
50011

Auxiliary Contact Blocks

Contactor Relay with Auxiliary Contact

Type

NO

NC

Block
Distinc. Number
according to
DIN EN 50011

J73KN-A-11

1

1

51E

5

1

J73KN-A-02

0

2

42E

4

2

J73KN-A-40

4

0

80E

8

0

J73KN-A-22

2

2

62E

6

2

J73KN-A-11

1

1

42Y

4

2

J73KN-A-02

0

2

33Y

3

3

J73KN-A-40

4

0

71Y

7

1

J73KN-A-22

2

2

53Y

5

3

J73KN-A-11

1

1

33Y

3

3

J73KN-A-02

0

2

24Y

2

4

J73KN-A-40

4

0

62Y

6

2

J73KN-A-22

2

2

44Y

4

4

NO

NC

40E

31E

22E

Preferable combinations with
distinctive letter „E“
according to DIN EN 50011

Auxiliary Contact Blocks for Contactor Relays J7KNA-AR
Wiring diagrams

J73KN-A-11

J73KN-A-02

J73KN-A-40

J73KN-A-22

Mini Contactor Relays 4-pole

Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts

J7KNA-AR

H-9

LVSG

4-pole, With Screw Terminals

Specifications
■ Coil Voltages
Voltage Marking

Rated Control Voltage Us

Suffix

Voltage Marking

Rated Control Voltage Us

to contactor type
e.g.

at the coil

range for
50Hz

to contactor type
e.g.

at the coil

range for
50Hz

J7KNA-09-10-24

for 50Hz for 60Hz min
V
V
V.

max
V.

min
V.

max
V.

for 50Hz for 60Hz min
V
V.
J7KNA-09-10- 230 V

max
V.

min
V.

max
V.

12

12

12

11

12

12

12

210

205-215 220-230 205

215

220

230

24

24

24

22

24

24

24

220

210-220 230-240 210

220

230

240

42

42

42

38.5

42

42

42

230

220-230 240

220

230

240

250

48

48-50

48

48

50

48

50

240

230-240

230

240

250

260

60

60

60

52

66

54

60

400

380-400 440

380

400

415

440

90

90-95

100-105 90

95

100

105

500

475-500 520-545 475

500

520

545

95

95-100

105-110 95

100

105

110

550

525-550 600

550

570

600

100

100

110-115 100

105

110

115

105

105-110 115-120 105

110

115

120

110

110-115 120-125 110

115

120

125

200

200

205

210

220

Suffix

H-10

210-220 195

60Hz

Mini Contactor Relays 4-pole J7KNA-AR

525

60Hz

Standard voltages in bold type letters. Coil not exchangeable

■ Engineering data and Characteristics
Mini Contactor Relays
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
Auxiliary Contacts

Type J7KNA-AR...

J7KNA-AR...D

J7KNA-AR...VS

J73KN-A...

Rated insulation voltage Ui

V AC 690*1

690*1

690*1

690*1

40°C

A

10

10

10

10

60°C

A

6

6

6

6

at Ith

W

0.5

0.5

0.5

0.5

220-240V

A

3

3

3

3

380-415V

A

2

2

2

2

440V

A

1.6

1.6

1.6

1.6

Thermal rated current Ith to 690V
Ambient temperature

Power loss per pole
Utilization category AC15
Rated operational current Ie

500V

A

1.2

1.2

1.2

1.2

660-690V

A

0.6

0.6

0.6

0.6

Utilization category DC13
Rated operational current Ie

60V

A

2

2

2

2

110V

A

0.4

0.4

0.4

0.4

220V

A

0.1

0.1

0.1

0.1

open

°C

-40 to +60 (+90)*2

enclosed

°C

-40 to +40

°C

-40 to +90

Maximum ambient temperature
Operation
Storage

max. fuse size

gL (gG)

A

20

20

20

20

inrush

VA

25

-

-

-

sealed

VA

4-5

-

-

-

W

1.2

-

-

-

inrush

W

-

2.5

2.5

-

sealed

W

-

2.5

2.5

-

0.85 - 1.1

0.8 - 1.1

0.8 - 1.1

-

-

LVSG

Short circuit protection
short-circuit current 1kA,
contact welding not accepted

Power consumption of coils
AC operated

DC operated

Operation range of coils
in multiples of control voltage Us
Switching time at control voltage U ±10%

*3,*4

s

AC operated

DC operated

make time

ms

15 - 25

-

-

release time

ms

8 - 25

-

-

-

arc duration

ms

10 -15

-

-

-

make time

ms

-

15 - 19

-

-

release time

ms

-

8 - 25

-

-

arc duration

ms

-

10 -15

-

-

Mini Contactor Relays 4-pole

J7KNA-AR

H-11

Mini Contactor Relays
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
Type J7KNA-AR...

J7KNA-AR...D

J7KNA-AR...VS

J73KN-A...

solid

mm² 0.75 - 2.5

0.75 - 2.5

0.75 - 2.5

0.75 - 2.5

flexible

mm² 0.75 - 2.5

0.75 - 2.5

0.75 - 2.5

0.75 - 2.5

mm² 0.5 - 1.5

0.5 - 1.5

0.5 - 1.5

0.5 - 2.5

2

2

2

18 - 14

18 - 14

18 - 14

Auxiliary Contacts
Cable cross-section
all connectors

flexible with multicore cable end
Clamps per pole

2
solid or stranded

AWG 18 - 14

*1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
*2) With reduced control voltage range 0.9 up to 1.0 x Us and with reduced thermal rated current Ith to Ie/AC15
*3) Summary switching time = release time + arc duration
*4) Release time of NC make time of NO increase when suppressor units for voltage peak protection are used
(Varistor, RC-units, Diode units).

Mini Contactor Relays for North America
Data according to UL508
Main Contacts (cULus)

Type J7KNA-AR...

J73KN-A...

Rated operational current "General Use"

A

10

10
-

Rated operational power of three-phase motors

115V

hp

-

at 60Hz (3ph)

200V

hp

-

-

230V

hp

-

-

460V

hp

-

-

575V

hp

-

-

Rated operational power of of AC motors

115V

hp

-

-

at 60Hz (1ph)

200V

hp

-

-

230V

hp

-

-

Fuses
Suitable for use on a capability of delivering not more than

rms

Rated voltage

-

-

-

-

V

-

-

V AC 600

Auxiliary Contacts (cULus)

H-12

A
A

600

heavy pilot duty

AC

A600

A600

standard pilot duty

DC

Q600

Q600

Mini Contactor Relays 4-pole J7KNA-AR

■ Dimensions
Auxiliary Contact Blocks

J7KNA-AR...

J73KN-A...

LVSG

AC and DC operated
with screw terminals

Mini Contactor Relays 4-pole

J7KNA-AR

H-13

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

Cat. No. J507-E2-02

H-14

In the interest of product improvement, specifications are subject to change without notice.

Mini Contactor Relays 4-pole J7KNA-AR

Mini Motor Contactor

J7KNA

)

Main contactor
• AC & DC operated
• Integrated auxiliary contacts
• Screw fixing and snap fitting (35 mm DIN rail)
• Range from 4 to 5.5 kW (AC 3, 380/415V)
• 4 -main pole version (4 kW AC and DC coil)
• Auxiliary contacts suitable for electronic devices (DIN 19240)
• Finger proof (VBG 4)

Accessories
• 2 and 4 pole additional auxiliary contacts in different
configurations
• Mechanical interlock (in reversing contactor combination only)
• RC Suppressors

Approved Standards
Standard

Guide No (US,C)

UL

NLDX, NLDX7

ICE 947-5-1
VDE 0660

LVSG

EN 60947-5-1

Ordering Information
■ Model Number Legend

400:
415:

1. Mini Motor Contactors

Coil voltage (DC operated)
24D: DC24V
48D: DC48V
60D: DC60V
110D: DC110V
24VS: DC24V with diode
48VS: DC48V with diode
110VS: DC110V with diode

J7KNA-##-##-#-#####
1
2 3 4
5
1)
2)

3)

4)
5)

Mini Contactor
Rated Motor Current (AC3 400V)
09:
9A
12:
12A
Integrated auxiliary contact
10:
1 NO 0 NC
01:
0 NO 1 NC
4:
4 main pole type (no aux contact)
W:
Reversing Contactor
Coil voltage (AC operated)1)
24:
AC24V 50/60Hz
48:
AC48V 50Hz
60:
AC60V 50Hz
110:
AC110-115V 50Hz, AC120-125V 60Hz
230:
AC220-230V 50Hz, AC240V 60Hz
240:
AC230V-240V 50Hz

2. Aux. Contact Modules for Mini Motor Contactors

J73KN-##-##-#
1
2 3 4
1)
2)
3)

4)
1)

RC-suppressor unit go to page H-29, section 6 or
page H-35, suppressor units

AC380-400V 50Hz, AC440V 60Hz
AC400-415V 50Hz

Auxiliary Contact Modules
AM:
for mini motor contactor
Combination of NO/NC contacts
11:
1 NO 1 NC
02:
0 NO 2 NC
22:
2 NO 2 NC
40:
4 NO 0 NC
for Reversing Contactors
v:
left side
x:
right side

Mini Motor Contactor

J7KNA

H-15

■ System overview
Mini Motor Contactors
AC Operated
Ratings

Rated Current Aux. Contacts

AC2, AC3

AC3

380V
400V
415V
kW

500V
kW

660V
690V
kW

400V
A

Type

Pack

Weight

pcs.

kg/pc.

AC1

690V
A

NO

NC

Accept
Overlod
Relay see 24
page H-58 230

Coil Voltage*1
24V 50/60Hz
220-230V 50Hz

3-pole, With Screw Terminals
4

4

4

9

20

1

-

J7TKN-A J7KNA-09-10-# # # # #

10

0.16

5.5

5.5

5.5

12

20

1

-

J7TKN-A J7KNA-12-10-# # # # #

10

0.16

4

4

4

9

20

-

1

J7TKN-A J7KNA-09-01-# # # # #

10

0.16

5.5

5.5

5.5

12

20

-

1

J7TKN-A J7KNA-12-01-# # # # #

10

0.16

-

-

J7TKN-A J7KNA-09-4-# # # # #

10

0.19

Pack

Weight

pcs.

kg/pc.

4-pole, With Screw Terminals
4

4

4

9

20

*1) Other coil voltages see page H-20

DC Solenoid Operated
Ratings

Rated Current Aux. Contacts

AC2, AC3

AC3

380V
400V
415V
kW

500V
kW

660V
690V
kW

400V
A

Type

AC1

690V
A

NO

NC

Accept
Overlod
Relay see 24D
page H-58 24VS

DC Coil Voltage
24V 50/60Hz
24V 50/60Hz w. diode*1

3-pole, With Screw Terminals
4

4

4

9

20

1

-

J7TKN-A J7KNA-09-10-# # # D(-VS)

10

0.19

5.5

5.5

5.5

12

20

1

-

J7TKN-A J7KNA-12-10-# # # D(-VS)

10

0.19

4

4

4

9

20

-

1

J7TKN-A J7KNA-09-01-# # # D(-VS)

10

0.19

5.5

5.5

5.5

12

20

-

1

J7TKN-A J7KNA-12-01-# # # D(-VS)

10

0.19

*1) with built-in coil suppressor (zener diode)

Auxiliary contact blocks with screw terminals for contactors J7KNA-09... and J7KNA-12...

H-16

Contacts

Rated Current Thermal Rated Current Type

Pack

Weight

NO

NC

AC15
230V 400V
A
A

A

pcs.

kg/pc.

1

1

3

2

10

J73KN-AM-11

10

0.04

-

2

3

2

10

J73KN-AM-02

10

0.04

2

2

3

2

10

J73KN-AM-22

10

0.04

Mini Motor Contactor J7KNA

■ System overview
Mini Motor Contactors
AC Operated
Auxiliary Contact Blocks

Wiring Diagrams

Contactor with Auxiliary Contact
Block

Distinc. Number
according to DIN
EN 50012
Type

NO

NC

Distinc. Number
according to DIN
EN 50012
NO

J73KN-AM-11

1

1

21

2

1

J73KN-AM-02

0

2

12

1

2

NC

Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts

3-pole, With Screw Terminals
10

01

J73KN-AM-22

2

2

32

3

2

J73KN-A-11

1

1

-

1

2

J73KN-A-02

0

2

-

0

3

J73KN-A-40

4

0

-

4

1

J73KN-A-22

2

2

-

2

3

J73KN-A-11

1

1

-

1

1

J73KN-A-02

0

2

-

0

2

J73KN-A-40

4

0

-

4

0

J73KN-A-22

2

2

-

2

2

Prefered combinations according
to DIN EN 50012

Contacts according to
DIN EN 50005

4-pole, With Screw Terminals
1

3

5

7

A1

00

A2
2

4

6

8

Contacts according to
DIN EN 50005

DC Solenoid Operated
Contactor with Auxiliary Contact
Block
Distinc. Number
according to DIN
EN 50012
Type

NO

NC

Distinc. Number
according to DIN
EN 50012
NO

J73KN-AM-11

1

1

21

2

1

J73KN-AM-02

0

2

12

1

2

NC

Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts

3-pole, With Screw Terminals
10

01

J73KN-AM-22

2

2

32

3

2

J73KN-A-11

1

1

-

1

2

J73KN-A-02

0

2

-

0

3

J73KN-A-40

4

0

-

4

1

J73KN-A-22

2

2

-

2

3

Prefered combinations according
to DIN EN 50012

Contacts according to
DIN EN 50005

Auxiliary contact blocks with screw terminals for contactors J7KNA-09... and J7KNA-12...
Wiring Diagrams

J73KN-AM-11 J73KN-AM-02 J73KN-AM-22 J73KN-A-11

J73KN-A-02

J73KN-A-40

J73KN-A-22

Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts

Mini Motor Contactor

J7KNA

H-17

LVSG

Auxiliary Contact Blocks

Wiring Diagrams

■ System overview
Mini Reversing Contactors, Mechanical Interlocked
AC Operated
Ratings

Rated Current Aux. Contacts

AC2, AC3

AC3

380V
400V
415V
kW

500V
kW

660V
690V
kW

400V
A

Type

Pack

Weight

pcs.

kg/pc.

AC1

690V
A

NO

NC

Accept
Overlod
Relay see 24
page H-58 230

Coil Voltage*1
24V 50/60Hz
220-230V 50Hz

3-pole, With Screw Terminals
4

4

4

9

20

-

1

J7TKN-A J7KNA-09-01-W-# # # # #

1

0.32

5.5

5.5

5.5

12

20

-

1

J7TKN-A J7KNA-12-01-W-# # # # #

1

0.32

Pack

Weight

pcs.

kg/pc.

*1) Other coil voltages see page H-20

DC Solenoid Operated
Ratings

Rated Current Aux. Contacts

AC2, AC3

AC3

380V
400V
415V
kW

500V
kW

660V
690V
kW

400V
A

Type

AC1

690V
A

NO

NC

Accept
Overlod
Relay see 24D
page H-58 24VS

DC Coil Voltage
24V 50/60Hz
24V 50/60Hz w. diode*1

3-pole, With Screw Terminals
4

4

4

9

20

-

1

J7TKN-A J7KNA-09-01-W-# # # D

1

0.38

5.5

5.5

5.5

12

20

-

1

J7TKN-A J7KNA-12-01-W-# # # D

1

0.38

*1) with built-in coil suppressor (zener diode)

Auxiliary contact blocks with screw terminals for contactors J7KNA-09-01-W...(D) and
J7KNA-12-01-W...(D)

H-18

Contacts

Rated Current Thermal Rated Current Type

Pack

Weight

NO

NC

AC15
230V 400V
A
A

A

pcs.

kg/pc.

1

1

3

2

10

J73KN-AM-11V

10

0.04

1

1

3

2

10

J73KN-AM-11X

10

0.04

Mini Motor Contactor J7KNA

■ System overview
Mini Motor Contactors
AC Operated
Auxiliary Contact Blocks suitable for

Wiring Diagrams

left hand side

right hand side

Contactor K1

Contactor K2

Distinc. Number
according to DIN
EN 50012
Type

NO NC Type

Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
NO NC Positively guided contacts

1

1

3-pole, With Screw Terminals
J73KN-AM-11V

1

J73KN-AM-11X

1

01

DC Solenoid Operated
Auxiliary Contact Blocks suitable for

Wiring Diagrams

left hand side

right hand side

Contactor K1

Contactor K2

Distinc. Number
according to DIN
EN 50012
Type

NO NC Type

Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
NO NC Positively guided contacts

1

1

3-pole, With Screw Terminals
J73KN-AM-11V

1

J73KN-AM-11X

1

LVSG

01

Auxiliary contact blocks with screw terminals for contactors J7KNA-09-01-W...(D) and
J7KNA-12-01-W...(D)
Wiring Diagrams

J73KN-AM-11V J73KN-AM-11X
13 31

31 13

14 32

32 14

Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts

Mini Motor Contactor

J7KNA

H-19

Specifications
■ Coil Voltages
Voltage Marking

Rated Control Voltage Us

Suffix

Voltage Marking

Rated Control Voltage Us

to contactor type
e.g.

at the coil

range for
50Hz

to contactor type
e.g.

at the coil

range for
50Hz

J7KNA-09-10-24

for 50Hz for 60Hz min
V
V
V.

max
V.

min
V.

max
V.

J7KNA-09-10 -230

for 50Hz for 60Hz min
V
V
V.

max
V.

min
V.

max
V.

12

12

12

11

12

12

12

210

205-215 220-230 205

215

220

230

24

24

24

22

24

24

24

220

210-220 230-240 210

220

230

240

48

48-50

48

48

50

48

50

230

220-230 240

220

230

240

250

60

60

60

52

66

54

60

240

230-240

230

240

250

260

90

90-95

100-105 90

95

100

105

400

380-400 440

380

400

415

440

95

95-100

105-110 95

100

105

110

500

475-500 520-545 475

500

520

545

100

100

110-115 100

105

110

115

550

525-550 600

550

570

600

105

105-110 115-120 105

110

115

120

110

110-115 120-125 110

115

120

125

200

200

205

210

220

Suffix

H-20

210-220 195

Mini Motor Contactor J7KNA

60Hz

525

60Hz

Standard voltages in bold type letters. Coil not exchangeable

■ Engineering data and Characteristics
Mini Motor Contactors
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Main Contacts

Type J7KNA-09-...

J7KNA-12-...

Rated insulation voltage Ui

V AC 690*1)

690 ’1)

at Ue = 690V AC

A

165

165

Breaking capacity Ieff

400V AC

A

100

100

cosϕ = 0,65

500V AC

A

90

90

690V AC

A

80

80

A

20

20

Making capacity Ieff

Utilization category AC1
Switching of resistive load
Rated operational current Ie (=Ith) at 40°C, open
Rated operational power of three-phase resistive loads

230V

kW

7.9

7.9

50-60Hz, cosϕ = 1

240V

kW

8.3

8.3

400V

kW

13.8

13.8

415V

kW

14.3

14.3

A

16

16

Rated operational current Ie (=Ithe) at 60°C, enclosed
Rated operational power of three-phase resistive loads

230V

kW

6.3

6.3

50-60Hz, cosϕ = 1

240V

kW

6.7

6.7

400V

kW

11

11

415V

kW

11.5

11.5

Minimum cross-section of conductor at load with Ie (=Ith)

mm² 2.5

2.5

Utilization category AC2 and AC3
Rated operational current Ie

220V

A

12

15

open and enclosed

230V

A

11.5

14.5

240V

A

11

14

380-400V

A

9

12

415-440V

A

8

11

500V

A

7

9

660-690V

A

5

6.5

Rated operational power of three-phase motors

220-240V

kW

3

4

50-60Hz

380-440V

kW

4

5.5

500-690V

kW

4

5.5

LVSG

Switching of three-phase motors

Utilization category AC4
Switching of squirrel cage motors, inching
Rated operational current Ie

220V

A

12

15

open and enclosed

230V

A

11.5

14.5

240V

A

11

14

380-400V

A

9

12

415-440V

A

8

11

500V

A

7

9

660-690V

A

5

6.5

Rated operational power of three-phase motors

220-240V

kW

3

4

50-60Hz

380-440V

kW

4

5.5

500-690V

kW

4

5.5

Mini Motor Contactor

J7KNA

H-21

Mini Motor Contactors
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Type J7KNA-09-...

J7KNA-12-...

1 pole 24V

A

20

20

60V

A

20

20

110V

A

5

5

220V

A

0.6

0.6

3 poles in series 24V

A

20

20

60V

A

20

20

110V

A

20

20

220V

A

16

16

1 pole 24V

A

20

20

60V

A

5

5

Time constant L/R ≤ 15ms

110V

A

1

1

Rated operational current Ie

220V

A

0.15

0.15

3 poles in series 24V

A

20

20

60V

A

20

20

110V

A

20

20

220V

A

2

2

open

°C

Main Contacts
Utilization category DC1
Switching of resistive load
Time constant L/R ≤ 1ms
Rated operational current Ie

Utilization category DC3 and DC5
Switching of shunt motors
and series motors

Maximum ambient temperature
Operation

-40 to +60 (+90)*2

enclosed

°C

-40 to +40

open

°C

-25 to +60

with thermal overload relay

enclosed
Storage

°C

-25 to +40

°C

-50 to +90

Short circuit protection
for contactors without thermal overload relay
Coordination-type "1" according to IEC 947-4-1
Contact welding without hazard of persons
max. fuse size

gL (gG)

A

40

40

Coordination-type “2” according to IEC 947-4-1
Light contact welding accepted
max. fuse size

gL (gG)

A

25

25

Contact welding not accepted
max. fuse size

gL (gG)

A

10

10

For contactors with thermal overload relay the
device with the smaller admissible backup fuse
(contactor or thermal overload relay) determines the fuse size.
Cable cross-sections
for contactors without thermal overload relay
main connector

solid or stranded

mm² 0.5 - 2.5

0.5 - 2.5

flexible

mm² 0.5 - 2.5

0.5 - 2.5

flexible with multicore cable end

mm² 0.5 - 1.5

0.5 - 1.5

Cables per clamp

2
solid or stranded

H-22

Mini Motor Contactor J7KNA

AWG 18 - 14

2
18 - 14

Mini Motor Contactors
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Type J7KNA-09-...

Main Contacts
Frequency of operations z

J7KNA-12-...

without load

1/h

10000

10000

AC3, Ie

1/h

600

700

Contactors without thermal overload relay

AC4, Ie

1/h

120

150

DC3, Ie

1/h

600

700

Mechanical life AC operated

Sx

6

10

5

5

DC operated

Sx

106

15

15

10s-current

A

96

120

at Ie/AC3 400V

W

0.15

0.25

NO

g

5

5

NC

g

5

5

NO

g

8

8

NC

g

6

6

Short time current
Power loss per pole

Resistance to shock according to IEC 68-2-27
Shock time 20ms sine-wave
AC operated

DC operated

LVSG

*1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
*2) With reduced control voltage range 0.9 up to 1.0 x Us and with reduced rated current Ie/AC1according to Ie/AC3

Mini Motor Contactor

J7KNA

H-23

Mini Motor Contactors
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
Auxiliary Contacts

J7KNA-09...
Type J7KNA-12...

J7KNA-09...D(VS)
J7KNA-12...D(VS)

J73KN-A...

Rated insulation voltage Ui

V AC 690*1

690*1

690*1

Thermal rated current Ith to 690V
Ambient temperature

40°C

A

10

10

10

60°C

A

6

6

6

at Ith

W

0.5

0.5

0.5

220-240V

A

3

3

3

380-415V

A

2

2

2

440V

A

1.6

1.6

1.6

Power loss per pole
Utilization category AC15
Rated operational current Ie

500V

A

1.2

1.2

1.2

660-690V

A

0.6

0.6

0.6

Utilization category DC13
Rated operational current Ie

60V

A

2

2

2

110V

A

0.4

0.4

0.4

220V

A

0.1

0.1

0.1

open

°C

Maximum ambient temperature
Operation

enclosed
Storage

-40 to +60 (+90)*2

°C

-40 to +40

°C

-40 to +90

Short circuit protection
short-circuit current 1kA,
contact welding not accepted
max. fuse size

gL (gG)

A

20

20

20

For contactors with thermal overload relay the
device with the smaller admissible control fuse
(contactor or thermal overload relay)
determines the fuse size.
Power consumption of coils
AC operated

DC operated

inrush

VA

25

-

-

sealed

VA

4-5

-

-

W

1.2

-

-

inrush

W

-

2.5

-

sealed

W

-

2.5

-

0.85 - 1.1

0.8 - 1.1

19 - 30V DC

Operation range of coils
in multiples of control voltage Us

-

*3,*4

Switching time at control voltage U ±10%
s

AC operated

DC operated

H-24

make time

ms

15 - 25

-

-

release time

ms

8 - 25

-

-

arc duration

ms

10 -15

-

-

make time

ms

-

15 - 19

-

release time

ms

-

8 - 25

-

arc duration

ms

-

10 -15

-

Mini Motor Contactor J7KNA

Mini Motor Contactors
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
J7KNA-09...
Type J7KNA-12...

J7KNA-09...D(VS)
J7KNA-12...D(VS)

J73KN-A...

solid

mm² 0.75 - 2.5

0.75 - 2.5

0.75 - 2.5

flexible

mm² 0.75 - 2.5

0.75 - 2.5

0.75 - 2.5

mm² 0.5 - 1.5

0.5 - 1.5

0.5 - 2.5

2

2

18 - 14

18 - 14

Auxiliary Contacts
Cable cross-section
all connectors

flexible with multicore cable end
Clamps per pole

2
solid or stranded

AWG 18 - 14

*1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
*2) With reduced control voltage range 0.9 up to 1.0 x Us and with reduced thermal rated current Ith to Ie/AC15
*3) Summary switching time = release time + arc duration
*4) Release time of NC make time of NO increase when suppressor units for voltage peak protection are used
(Varistor, RC-units, Diode units).

Mini Contactors for North America
Main Contacts (cULus)

Type J7KNA-09...

J7KNA-12...

J73KN-A...

Rated operational current "General Use"

A

20

10

15

Rated operational power of three-phase motors

115V

hp

1½

2

-

at 60Hz (3ph)

200V

hp

3

3

-

230V

hp

3

3

-

460V

hp

5

7½

-

575V

hp

7½

10

-

Rated operational power of of AC motors

115V

hp

½

¾

-

at 60Hz (1ph)

200V

hp

1

1½

-

230V

hp

1½

2

-

Fuses

A

30

30

-

A

5000

5000

-

V

600

600

-

V AC 600

600

600

heavy pilot duty

AC

A600

A600

A600

standard pilot duty

DC

Q600

Q600

Q600

Suitable for use on a capability of delivering not more than

rms

Rated voltage
Auxiliary Contacts (cULus)

Mini Motor Contactor

J7KNA

LVSG

Data according to UL508

H-25

■ Dimensions
AC and DC operated
with screw terminals

Auxiliary Contact Blocks

J7KNA-09...
J7KNA-12...

J73KN-A...

Reversing Contactors
J7KNA-09-01-W...
J7KNA-12-01-W...

J7KNA-09-01-W... + J7TKN-A
J7KNA-12-01-W...+ J7TKN-A

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

Cat. No. J506-E2-02

H-26

In the interest of product improvement, specifications are subject to change without notice.

Mini Motor Contactor J7KNA

Motor Contactor

J7KN
Main contactor
• AC & DC operated
• Integrated auxiliary contacts
• Screw fixing and snap fitting (35 mm DIN rail) up to 45 kW
• Range from 4 to 110 kW (AC 3, 380/415V)
• Finger proof (VBG 4)

Accessories
• front mounted single pole additional auxiliary contacts
(1 NO or 1 NC)
• Side mounted additional auxiliary contacts (1 NO/1 NC)
• Mechanical interlock
• Suppressors (RC and varistor)
• Pneumatic timer modules
• Link modules MPCB - Motor contactor

Approved Standards
Standard

Guide No (US,C)

UL

NLDX, NLDX7

ICE 947-4-1
VDE 0660
LVSG

EN 60947-4-1

Motor Contactor

J7KN

H-27

H-28

Motor Contactor J7KN

Ordering Information
■ Model Number Legend
J7KN-###-##-####
1
2
3
4
1)
2)

3)

4)

Motor Contactor
Rated Motor Current (AC3 400V)
10: 10A
14: 14A
18: 18A
22: 22A
24: 24A
32: 32A
40: 40A
50: 50A
62: 62A
74: 74A
85: 85A
110: 110A
150: 150A
175: 175A
200: 200A
Integrated auxiliary contact
10: 1NO 0NC
01: 0NO 1NC
21: 2NO 1NC
22: 2NO 2NC
: 0NO 0NC
Coil voltage (AC operated)
24: AC24V 50/60Hz
48: AC48V 50Hz
110: AC110V 50Hz, AC110-120V 60Hz
180: AC180-210V 50Hz, AC200-240V 60Hz
230: AC220-240V 50Hz, AC240V 60Hz
400: AC380-415V 50Hz, AC415-440V 60Hz
500: AC500-550V 50Hz, AC550-600V 60Hz
Coil voltage(DC operated)
24D: DC24V
48D: DC48V
110D: DC110V
125D: DC125V

4. Accessories for Motor Contactors
(Pneumatic Timers)

J74KN-#-## ### ##
1
2 3 4 5
1)
2)
3)
4)
5)

5. Accessories for Motor Contactors (Mechanical Interlock)

J74KN-#-##
1
2 3
1)
2)

3)

1)
2)
3)

4)

Auxiliary Contact Modules
B: for motor contactor (4-37kW)
C: for motor contactor (11-37kW)
Combination of NO/NC contacts
10: 1NO 0NC
01: 0NO 1NC
11: 1NO 1NC
S: side mounting
: front mounting

Accessories for Motor Contactors
B: Motor Contactor (4-18.5kW)
C: Motor Contactor (11-37kW)
D: Motor Contactor (45-55kW)
ML: Mechanical Interlock

6. Accessories for Motor Contactors (RC Suppressor units)

J74KN-#-## ###
1
2 3 4
1)
2)

3)
4)

2. Aux. Contact Modules for Motor Contactors

J73KN-#-##-#
1
2 3 4

Accessories for Motor Contactors
B: Motor Contactor (4-11kW)
TP: Pneumatic Timer
40: 40 sec
180: 180 sec
DA: ON-delayed
IA: OFF-delayed

Accessories for Motor Contactors
A: for Mini Motor Contactor and Motor Contactor
(4-18.5kW)
(between DIN-rail and Contactor)
B: for Mini Motor Contactor and Motor Contactor
(4-55kW)
C: for Motor Contactor (4-37kW) to snap on the contactor
RC: RC-surge suppressors
48:
24 - 48 VAC/DC (A+B type)
230:
110 - 230 VAC/DC (A+B type)
400:
250 - 415 VAC/DC (A+B type)
24:
12 - 48 VAC/DC (C type)
110:
48 - 127 VAC/DC (C type)
230:
110 - 250 VAC/DC (C type)

7. Accessories for Motor Contactors (Varistor units)

J74KN-#-## ###
1
2 3 4
1)
2)

3)
4)

Accessories for Motor Contactors
A: for Motor Contactor (4-11kW) to snap on
to coil terminals
B: for Motor Contactor (4-37kW) to snap on to contactor
VG: Varistor Suppressors
230: 110-230VAC/DC
400: 250-415VAC/DC

3. Accessories for Motor Contactors
(Link Modules MPCB - Motor Contactor)

J74KN-##-##
1
2 3
1)
2)
3)

Accessories for Motor Contactors
VD: Link module type
HU: DIN-rail adapter type
12: for motor contactor (4 - 7.5kW)
25: for motor contactor (11 - 15kW)

Motor Contactor

J7KN

H-29

LVSG

1. Motor Contactors

■ List of Models
Contactors 3-pole
•
•
•
•
•

Up to 210A AC3
Up to 350A AC1
DIN-rail mounting up to AC3 74A
International Approvals
Data according to IEC 947 /
EN 60947

Ratings
AC3

400V Motor
380-400V
660-690V
690V at 40°C

AC1
Type
Auxiliary contacts
Type

Auxiliary contacts
Cable cross-section
Solid
mm2
Flexible
mm2
Cables per clamp
Auxiliary contact
Ith
40°C
A
AC15
230V
A
400V
A
Power consumption of coils
Inrush VA
Hold VA
Operation range of coils
Mounting
Additional aux. contact blocks
Front mounting
Type
contacts

10A
4kW
5,5kW
25A
J7KN10-10
1NO
J7KN10-01
1NC

14A
5,5kW
7,5kW
25A
J7KN14-10
1NO
J7KN14-01
1NC

18A
7,5kW
10kW
32A
J7KN18-10
1NO
J7KN18-01
1NC

22A
11kW
10kW
32A
J7KN22-10
1NO
J7KN22-01
1NC

24A
11kW
15kW
50A
J7KN-24

32A
15kW
18,5kW
65A
J7KN-32

40A
18,5kW
18,5kW
80A
J7KN-40

50A
22kW
30kW
110A
J7KN-50

62A
30kW
37kW
120A
J7KN-62

74A
37kW
45kW
130A
J7KN-74

-

-

-

-

-

-

-

-

-

-

-

-

0,75 - 6
1-4
2

1,5 - 25
2,5 - 16
1+1

4 - 50
10 - 35
1+1

16
12
4

-

-

33 - 45
7 - 10
0,85 - 1,1
35mm DIN-rail or base

90 - 115
9 - 13
0,85 - 1,1

140 - 165
13 - 18
0,85 - 1,1

J73KN-B-10
1NO
f. low level switching

maximal 4 J73KN-B..
Additional aux. contact blocks
Side mounting
Type contacts

J73KN-B-01
1NC
f. low level switching

-

J73KN-C-11S
1NO+1NC
f. low level switching
max. 2 J73KN-C-11S

Overload Relay (thermal)
Single phase protection
Temperature compensation
Trip and alarm contacts
Type J7TKN-B
Setting Ranges
0,12 - 0,18A
0,18 - 0,27A
0,27 - 0,4A
0,4 - 0,6A
0,6 - 0,9A
0,8 - 1,2A
1,2 - 1,8A
17 - (23)24A

H-30

Motor Contactor J7KN

J7TKN-A
1,8 - 2,7A
2,7 - 4A
4 - 6A
6 - 9A
8 - 11A
10 - 14A
13 - 18A
(22)23 - (30)32A

J7TKN-C
Setting Ranges
28 - 42A

J7TKN-D
Setting Ranges
20 - 28A
28 - 42A
40 - 52A
52 - 65A
60 - 74A

AC1
Type

400V Motor
380-400V
660-690V
690V at 40°C

Auxiliary contacts
Type
Auxiliary contacts
Cable cross-section
Solid
mm2
Flexible
mm2
Cables per clamp
Auxiliary contact
40°C
A
Ith
AC15
230V
A
400V
A
Power consumption of coils
Inrush VA
hold VA
Operation range of coils
Mounting
Additional aux. contact blocks
Front mounting
Type
contacts

85A
45kW
55kW
150A
J7KN85-22
2NO+2NC
-

110A
55kW
55kW
170A
J7KN110-22
2NO+2NC
-

150A
75kW
75kW
200A
J7KN150-11
1NO+1NC
-

175A
90kW
110kW
250A
J7KN175-11
1NO+1NC
-

210A
110kW
132kW
350A
J7KN-20022
2NO+2NC
-

-

-

-

-

-

10 - 70
16 - 50
1

10 - 70
16 - 50
1

busbar
18x5
1

busbar
18x5
1

busbar
22x4
1

16
12
6

10
3
2

350 - 420
23 - 29
0,85 - 1,1
base

550
130
0,85 - 1,1

550
130

1100
66

-

-

-

Additional aux. contact blocks
Side mounting
Type contacts

LVSG

Ratings
AC3

-

Overload Relay (thermal)
Single phase protection
Temperature compensation
Trip and alarm contacts
Type J7TKN-E
Setting Ranges
60 - 90A
80 - 120A

J7TKN-F
Setting Ranges
100 - 150A
140 - 220A
Busbar Sets
J74TK-SU-175, J74TK-SU-200

Motor Contactor

J7KN

H-31

Contactors 3-pole
AC Operated
Rated Aux. Contacts
Current

Ratings
AC2, AC3

AC1
660V
690V

Weight

Additional

380V
400V
415V
kW

500V
kW

kW

A

NO

NC

Type

4

5.5

5.5

25

1

-

max. 4
J73KN-B

690V

see
page 34

4

5.5

5.5

25

-

1

5.5

7.5

7.5

25

1

-

24
110
230

Coil Voltage*1
24V 50/60Hz
110V 50Hz
220-240V 50Hz

J7KN-10-10####

pcs.

kg/pc.

1

0.23

J7KN-10-01####

1

0.23

J7KN-14-10####

1

0.23

5.5

7.5

7.5

25

-

1

J7KN-14-01####

1

0.23

7.5

10

10

32

1

-

J7KN-18-10####

1

0.23

7.5

10

10

32

-

1

J7KN-18-01####

1

0.23

11

10

10

32

1

-

J7KN-22-10####

1

0.23

11

10

10

32

-

1

11

15

15

50

-

-

15

18.5

18.5

65

-

-

18.5

18.5

18.5

80

-

-

22

30

30

110

-

-

30

37

37

120

-

-

37

45

45

130

-

-

Rated Aux. Contacts
Current

Ratings
AC2, AC3
380V
415V
kW

500V

45

AC1

1

0.23

max. 4
J7KN-24####
J73KN-B + J7KN-32####
2 J73KNJ7KN-40####
C-11S

1

0.48

1

0.48

1

0.48

max. 4
J7KN-50####
J73KN-B + J7KN-62####
2 J73KNJ7KN-74####
C11S

1

0.85

1

0.85

1

0.85

Pack

Weight

J7KN-22-01####

Type

Built-in
Coil Voltage*1
220-230V 50Hz
380-400V 50Hz

690V

kW

660V
690V
kW

A

NO

NC

230
400

pcs.

kg/pc.

55

55

150

2

2

J7KN-85-22####

1

1.8

55

75

55

170

2

2

J7KN-110-22####

1

1.9

75

75

75

200

1

1

J7KN-150-11####

1

5

90

90

90

250

1

1

J7KN-175-11####

1

5

110

132

132

350

2

2

J7KN-200-22####

1

7.3

*1) Coil voltage range and other coil voltages see page 37

H-32

Built-in

Pack

Type

Motor Contactor J7KN

Contactors 3-pole
DC Operated
Coil voltage

Type

Aux. Contacts
Built-in

24
60
110
220

24V DC
60V DC
110V DC
220V DC NO

Weight

Additional*1)

Accept Overload
Relay

Busbar Set for Wiring Diagram
Overload Relay

page 57

page 59
Coil Circuits see page 36

NC

Type

kg/pc.

Type

Type

Terminal Markings

J7KN-10-10####D

1

-

0.25

-10

-

1

J7TKN-B
J7TKN-A

-

J7KN-10-01####D

max. 3
J73KN-B

J7KN-14-10####D

1

-

0.25

-

J7KN-14-01####D

-

1

0.25

-

J7KN-18-10####D

1

-

0.25

-

J7KN-18-01####D

-

1

0.25

-

J7KN-22-10####D

1

-

0.25

-

J7KN-22-01####D

-

1

0.25

J7KN-24####D

-

-

-

-

J7KN-40####D
J7KN-50####D
J7KN-62####D
J7KN-74####D

Coil voltage

Type

-

-

-

-

-

-

-

-

-

-

-

-

2

1

0.55

-

-11

-

0.55

-

-21

max. 3
J73KN-B
+
2 J73KNC-11S

Aux. Contacts

110V DC
220V DC NO

-01

J7TKN-B
J7TKN-C

0.55

0.9

NC

J7TKN-D

0.9
1.6

Weight

Built-in
110
220

-

Accept Overload
Relay

Busbar Set for -22
Overload Relay

page H-59

page H-59

Type

kg/pc.

Type

J7KN-85-21####D

2

1

-

1.8

J7TKN-E

J7KN-110-21####D

2

1

-

1.9

LVSG

J7KN-32####D

max. 3
J73KN-B
+
2 J73KNC-11S

0.25

J73TK-SU-175
J7TKN-F

J73TK-SU-200

*1) Only 3 additional Aux. Contacts are possible! (See also the wiring diagrammms coil circuit DC operated page 36)

Motor Contactor

J7KN

H-33

Contactors 4-pole
AC Operated
Rated
Current

Ratings

Aux. Contacts

Type

AC2,
AC3

AC1

AC1

380V
400V
415V
kW

400V

690V

kW

A

NO

NC

Type

4

17.5

25

-

-

max. 4
J73KN-B

Built-in

Additional
see
below

Coil Voltage*1
24V 50/60Hz
110V 50Hz
220-240V 50Hz

24
110
230

J7KN-10-4####

Pack

Weight

pcs.

kg/pc.

1

0.22

*1) Coil voltage range and other coil voltages see page 37

Auxiliary Contact Blocks for contactors J7KN-10... to -74... type J73KN for low level switching*1
Front mounting

Rated Operational Current
AC15
230V

AC15
400V

AC1
690V

Contacts

Type
EM

LB

Pack

Weight

A

A

A

NO

NC

pcs.

kg/pc.

3

2

10

1

-

-

-

J73KN-B-10

10

0.02

3

2

10

-

1

-

-

J73KN-B-01

10

0.02

Auxiliary Contact Blocks for contactors J7KN-24... to -74... type J73KN for low level switching*1
Side mounting

Rated Operational Current
AC15
230V

AC15
400V

Contacts

Type

Pack

Weight

pcs.

kg/pc.

J73KN-C-11S

10

0.02

Type

Pack

Weight

pcs.

kg/pc.

J74KN-B-TP40DA

1

0.09

J74KN-B-TP180DA

1

0.09

J74KN-B-TP40IA

1

0.09

J74KN-B-TP180IA

1

0.09

AC1
690V

A

A

A

for side mounting

NO

NC

3

2

10

max. 2

1

1

Pneumatic Timer for contactors J7KN-10... to -22...
Function

Time range

Contacts

s

1.

On-delay

0.1 - 40

1

On-delay

10 - 180

1

Off-delay

0.1 - 40

-

Off-delay

10 - 180

-

suitable
according
Technical data see page 51

H-34

to

Motor Contactor J7KN

DIN

19240

NO NC
1
1
-

(test

1
1

NO NC
1
1

ratings

17V

DC,

5mA)

Mechanical Interlocks
Interlocks contactor with contactor
Type

+

Type

J7KN10 - J7KN40

+

J7KN10 - J7KN40

J7KN24 - J7KN74

+

J7KN85 - J7KN110 +

Mounting
horizontal

Type

Pack

J74KN-B-ML

Weight

pcs.

kg/pc.

1

0.006

J7KN24 - J7KN74

horizontal

J74KN-C-ML

1

0.010

J7KN85 - J7KN110

horizontal

J74KN-D-ML

1

0.076

Type

Pack

Weight

pcs.

kg/pc.

Suppressor Units
Voltage Range

Mounting

V
Varistor for contactors J7KN-10 to J7KN-22
110 - 230V AC/DC

to snap on to coil terminals

J74KN-A-VG230

10

0.01

250 - 415V AC/DC

to snap on to coil terminals

J74KN-A-VG400

10

0.01

Varistor for contactors J7KN-10 to J7KN-74
110 - 230V AC/DC

to snap on the contactor

J74KN-B-VG230

10

0.02

250 - 415V AC/DC

to snap on the contactor

J74KN-B-VG400

10

0.02

J74KN-A-RC230

1

0.036

RC-unit for contactors J7KN-10 to J7KN-40, J7KNA
110 - 230V AC/DC

between DIN-rail and contactor

RC-units for contactors J7KN-10 to J7KN-110
24 - 48V AC/DC

universal (fixing band, adhesive strip)

J74KN-B-RC48

5

0.02

110 - 230V AC/DC

universal (fixing band, adhesive strip)

J74KN-B-RC230

5

0.02

250 - 415V AC

universal (fixing band, adhesive strip)

J74KN-B-RC400

5

0.02

RC-units for contactors J7KN-10 to J7KN-74
to snap on the contactor

J74KN-C-RC24

10

0.02

48 - 127V AC (50/60Hz) & DC

to snap on the contactor

J74KN-C-RC110

10

0.036

110 - 250V AC (50/60Hz) & DC to snap on the contactor

J74KN-C-RC230

10

0.036

LVSG

12 - 48V AC (50/60Hz) & DC

Motor Contactor

J7KN

H-35

■ Wiring Diagrams Coil Circuit
AC operated

DC operated
with double winding coil*1

J7KN-10...
to
J7KN-175...

J7KN-10...D
to
J7KN-22...D

J7KN-200...

J7KN-24...D
to
J7KN-74...D

J7KN-85-...D
to
J7KN-110...D

*1) Only 3 additional Aux. Contacts are possible! (See also
page 33)

H-36

Motor Contactor J7KN

Specifications
■ Coil Voltages
Type-suffix for contactor types J7KN-10... to J7KN-74...
Suffix
to contactor
type e.g.

Voltage Marking
at the coil

Rated Control Voltage Us
range for
50Hz
60Hz
max
min
max
J7KN-10-10-24 for 50Hz for 60Hz min
V
V
V.
V.
V.
V.
24
24
24
22
24
24
27
48
48
47
52
52
58
110
110
110-120 100
110
110
122
180
180-210 200-240 180
210
200
240
230
220-240 240
220
240
240
264
400
380-415 415-440 380
415
415
460
500
500-550 550-600 500
550
550
600
Standard voltages in bold type letter

Type-suffix for contactor types J7KN-85... to J7KN-110...
Suffix
to contactor
type e.g.

Voltage Marking
at the coil

Rated Control Voltage Us
range for
50Hz
60Hz
max
min
max
J7KN-85-22-24 for 50Hz for 60Hz min
V
V
V.
V.
V.
V.
24
24
24
27
29
32
48
48
60
47
52
56
62
110
110-120
110
122
132
146
180
180-200 208-240 180
200
208
240
230
220-240 277
220
240
264
288
400
380-415 460-480 380
415
455
498
500
500-550 600-660 500
550
600
660
Standard voltages in bold type letter

Suffix

Voltage Marking

Rated Control Voltage Us

to contactor
type e.g.

at the coil

range for
50Hz

J7KN-150-110 for 50Hz for 60Hz min
V
V
V.

max
V.

60Hz
min
V.

max
V.

24

24

24

24

-

-

48

48

48

48

-

-

110

110

110

110

110

110

110

180

180

220

180

180

220

220

230

220-230 220

220

230

220

220

240

240

240

240

240

240

400

380-400

380

400

-

-

-

-

440

440

440

240
440

LVSG

Type-suffix for contactor types J7KN-150... to J7KN-200...

Standard voltages in bold type letter

Motor Contactor

J7KN

H-37

■ Engineering data and characteristics
Approximate Values for three-phase Motors
Motor Full Load Currents
Approximate values of motor F.L.C. and minimum „slow blow“ respectively „gL“ short-circuit fuse
Motor rating

220-230V Motor

240V Motor

380-400V Motor

415V Motor

500V Motor

660-690V Motor

Range according to BS for 415V

Value of fusing at
motor start

Value of fusing at
motor start

Value of fusing at
motor start

Value of fusing at
motor start

Value of fusing at
motor start

Value of fusing at
motor start

F.L.C. D.O.L. YD
A
A
A

F.L.C. D.O.L. YD
A
A
A

F.L.C. D.O.L. YD
A
A
A

F.L.C. D.O.L. YD
A
A
A

F.L.C. D.O.L. YD
A
A
A

F.L.C. D.O.L. YD
A
A
A

kW

PS~hp hp

cosϕ

%

0.06

0.08

-

0.7

59

0.38

1

1

0.35

1

1

0.22

1

1

-

-

-

0.16

1

1

-

-

-

0.09

0.12

-

0.7

60

0.55

2

2

0.5

2

2

0.33

1

1

-

-

-

0.24

1

1

-

-

-

0.12

0.16

-

0.7

61

0.76

2

2

0.68

2

2

0.42

2

2

-

-

-

0.33

1

1

-

-

-

0.18

0.24

-

0.7

61

1.1

2

2

1

2

2

0.64

2

2

-

-

-

0.46

1

1

-

-

-

0.25

0.34

-

0.7

62

1.4

4

2

1.38

4

2

0.88

2

2

-

-

-

0.59

2

2

-

-

-

0.37

0.5

-

0.72

64

2.1

4

4

1.93

4

4

1.22

4

2

-

-

-

0.85

2

2

0.7

2

2

0.55

0.75

-

0.75

69

2.7

4

4

2.3

4

4

1.5

4

2

-

-

-

1.2

4

2

0.9

2

2

0.75

1

1

0.8

74

3.3

6

4

3.1

6

4

2

4

4

2

4

4

1.48

4

2

1.1

2

2

1.1

1.5

1.5

0.83

77

4.9

10

6

4.1

6

6

2.6

4

4

2.5

4

4

2.1

4

4

1.5

4

2

1.5

2

2

0.83

78

6.2

10

10

5.6

10

10

3.5

6

4

3.5

6

4

2.6

4

4

2

4

4

2.2

3

3

0.83

81

8.7

16

10

7.9

16

10

5

10

6

5

10

6

3.8

6

6

2.9

6

4

2.5

3.4

-

0.83

81

9.8

16

16

8.9

16

10

5.7

10

10

-

-

-

4.3

6

6

-

-

-

3

4

4

0.84

81

11.6

20

16

10.6

20

16

6.6

16

10

6.5

16

10

5.1

10

10

3.5

6

4

3.7

5

5

0.84

82

14.2

25

20

13

25

16

8.2

16

10

7.5

16

10

6.2

16

10

-

4

5.5

-

0.84

82

15.3

25

20

14

25

20

8.5

16

10

-

-

-

6.5

16

10

4.9

5.5
7.5

7.5
10

7.5
10

-

-

10

6

0.85

83

20.6

35

25

18.9

35

25

11.5

20

16

11

20

16

8.9

16

10

6.7

16

10

0.86

85

27.4

35

35

24.8

35

35

15.5

25

20

14

25

16

11.9

20

16

9

16

10

8

11

-

0.86

85

28.8

50

35

26.4

35

35

16.7

25

20

-

-

-

12.7

20

16

-

-

-

11

15

15

0.86

87

39.2

63

50

35.3

50

50

22

35

25

21

35

25

16.7

25

20

13

25

16

12.5

17

-

0.86

87

43.8

63

50

40.2

63

50

25

35

35

-

-

-

19

35

25

-

-

-

15

20

20

0.86

87

52.6

80

63

48.2

80

63

30

50

35

28

35

35

22.5

35

25

17.5

25

20
25

18.5

25

25

0.86

88

64.9

100

80

58.7

80

63

37

63

50

35

50

50

28.5

50

35

21

35

20

27

-

0.86

88

69.3

100

80

63.4

80

80

40

63

50

-

-

-

30.6

50

35

-

-

-

22

30

30

0.87

89

75.2

100

80

68

100

80

44

63

50

40

63

50

33

50

50

25

35

35

25

34

-

0.87

89

84.4

125

100

77.2

100

100

50

80

63

-

-

-

38

63

50

-

-

-

30

40

40

0.87

90

125

125

92.7

125

100

60

80

63

55

80

63

44

63

50

33

50

35

37

50

50

0.87

90

124

160

160

114

160

125

72

100

80

66

100

80

54

80

63

42

63

50

40

54

-

0.87

90

134

160

160

123

160

160

79

100

100

-

-

-

60

80

63

-

-

-

45

60

60

0.88

91

150

200

160

136

200

160

85

125

100

80

100

100

64.5

100

80

49

63

63

51

70

-

0.88

91

168

200

200

154

200

200

97

125

100

-

-

-

73.7

100

80

-

-

-

55

75

-

0.88

91

181

250

200

166

200

200

105

160

125

-

-

-

79

125

100

60

80

63

101

59

80

80

0.88

91

194

250

250

178

250

200

112

160

125

105

160

125

125

100

-

-

-

75

100

100

0.88

91

245

315

250

226

315

250

140

200

160

135

200

160

106

85.3

160

125

82

125

100

90

125

125

0.88

92

292

400

315

268

315

315

170

250

200

165

200

200

128

160

160

98

125

125

110

150

150

0.88

92

358

500

400

327

400

400

205

250

250

200

250

250

156

200

200

118

160

125

129

175

175

0.88

92

420

500

500

384

500

400

242

315

250

230

315

250

184

250

200

-

-

-

132

180

-

0.88

92

425

500

500

393

500

500

245

315

250

-

-

-

186

250

200

140

200

160

147

200

200

0.88

93

472

630

630

432

630

500

273

315

315

260

315

315

207

250

250

-

-

-

160

220

-

0.88

93

502

630

630

471

630

630

295

400

315

-

-

-

220

315

250

170

200

200

184

250

250

0.88

93

590

800

630

541

630

630

340

400

400

325

400

400

259

315

315

-

-

-

200

270

-

0.88

93

626

800

800

589

800

630

370

500

400

-

-

-

278

315

315

215

250

250

220

300

300

0.88

93

700

1000

800

647

800

800

408

500

500

385

500

400

310

400

400

-

-

-

250

340

-

0.88

93

803

1000

1000

736

1000

800

460

630

500

-

-

-

353

500

400

268

315

315

257

350

350

0.88

93

826

1000

1000

756

1000

800

475

630

630

450

630

500

363

500

400

-

-

-

295

400

400

0.88

93

948

1250

1000

868

1000

1000

546

800

630

500

630

630

416

500

500

-

-

-

315

430

-

0.88

93

990

1250

1250

927

1250

1000

580

800

630

-

-

-

445

630

500

337

400

400

355

483

-

0.89

95

-

-

-

-

-

-

636

800

800

-

-

-

483

630

630

366

500

400

400

545

-

0.89

96

-

-

-

-

-

-

710

1000

800

-

-

-

538

630

630

410

500

500

The motor F.L.C. be valid for standard internal and surface cooled three-pole
motors with 1500 min . The fuses values be valid for the motor F.L.C. shown in
the table and D.O.L.-start: starting current max. 6x motor F.L.C., starting time
max. 5s; star-delta-start: starting current max. 2x motor F.L.C., starting time
max. 15s. For motors with higher F.L.C., higher starting current and / or longer
starting time, larger short-circuit fuses are required.
-1

The maximum admissible value is dependent on the switchgear
respectively thermal overload relay.

H-38

Motor Contactor J7KN

Approximate values of motor F.L.C. according to CSA and UL
Motor
rating
hp
½

Motor F.L.C. at 110-120V

Motor F.L.C. at 220-240V*1

Motor F.L.C. at 440-480V

1-phase

2-phase

3-phase

1-phase

2-phase

3-phase

1-phase

2-phase

3-phase

1-phase

2-phase

A

A

A

A

A

A

A

A

A

A

A

A

9.8

4.0

4.4

4.9

2.0

2.2

2.5

1.0

1.1

2.0

0.8

0.9

Motor F.L.C. at 550-600V
3-phase

¾

13.8

4.8

6.4

6.9

2.4

3.2

3.5

1.2

1.6

2.8

1.0

1.3

1

16.0

6.4

8.4

8.0

3.2

4.2

4.0

1.6

2.1

3.2

1.3

1.7

1½

20.0

9.0

12.0

10.0

4.5

6.0

5.0

2.3

3.0

4.0

1.8

2.4

2

24.0

11.8

13.6

12.0

5.9

6.8

6.0

3.0

3.4

4.8

2.4

2.7

3

34.0

16.6

19.2

17.0

8.3

9.6

8.5

4.2

4.8

6.8

3.3

3.9

5

56.0

26.4

30.4

28.0

13.2

15.2

14.0

6.6

7.6

11.2

5.3

6.1

7½

80.0

38.0

44.0

40.0

19.0

22.0

21.0

9.0

11.0

16.0

8.0

9.0

10

100.0

48.0

56.0

50.0

24.0

28.0

26.0

12.0

14.0

20.0

10.0

11.0

15

135.0

72.0

84.0

68.0

36.0

42.0

34.0

18.0

21.0

27.0

14.0

17.0

20

-

94.0

108.0

88.0

47.0

54.0

44.0

23.0

27.0

35.0

19.0

22.0

25

-

118.0

136.0

110.0

59.0

68.0

55.0

29.0

34.0

44.0

24.0

27.0

30

-

138.0

160.0

136.0

69.0

80.0

68.0

35.0

40.0

54.0

28.0

32.0

40

-

180.0

208.0

176.0

90.0

104.0

88.0

45.0

52.0

70.0

36.0

41.0

50

-

226.0

260.0

216.0

113.0

130.0

108.0

56.0

65.0

86.0

45.0

52.0

60

-

-

-

-

133.0

145.0

-

67.0

77.0

-

53.0

62.0
77.0

75

-

-

-

-

166.0

192.0

-

83.0

96.0

-

66.0

100

-

-

-

-

218.0

248.0

-

109.0

124.0

-

87.0

99.0

125

-

-

-

-

-

312.0

-

135.0

156.0

-

108.0

125.0

150

-

-

-

-

-

360.0

-

156.0

180.0

-

125.0

144.0

200

-

-

-

-

-

480.0

-

208.0

240.0

-

167.0

192.0

250

-

-

-

-

-

602.0

-

-

302.0

-

-

242.0

300

-

-

-

-

-

-

-

-

361.0

-

-

289.0

350

-

-

-

-

-

-

-

-

414.0

-

-

336.0

400

-

-

-

-

-

-

-

-

477.0

-

-

382.0

500

-

-

-

-

-

-

-

-

590.0

-

-

472.0

LVSG

*1) Determine the motor current for 200V and 208V by increasing the values for 220-240V at 200V about 15% and for 208V about 10%.

Motor Contactor

J7KN

H-39

Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts

Type

Rated insulation voltage Ui*1

J7KN-10

V AC 690

J7KN-14
690

J7KN-18
690

J7KN-22
690

J7KN-24
690

J7KN-32
690

J7KN-40
690

J7KN-50
690

J7KN-62
690

J7KN-74
690

at Ue = 690V AC A

200

200

200

200

400

500

500

700

900

900

Breaking capacity Ieff

400V AC A

180

180

200

200

380

400

400

600

800

800

J7KN-10 to J7KN-22 cosϕ = 0,65

500V AC A

150

150

180

180

300

370

370

500

700

700

J7KN-24 to J7KN-72 cosϕ = 0,35

690V AC A

100

100

150

150

260

340

340

400

500

500

-

-

-

-

-

-

-

-

-

Making capacity Ieff

1000V AC A
Utilization category AC1
Switching of resistive load
Rated operational current Ie (=Ith) at 40°C, open

25

25

32

32

50

65

80

110

120

130

220V kW

9,5

9,5

12,2

12,2

19,0

24,7

30,4

41,9

45,7

49,5

230V kW

9,9

9,9

12,7

12,7

19,9

25,9

31,8

43,8

47,7

51,7

240V kW

10,4

10,4

13,3

13,3

20,8

27,0

33,2

45,7

49,8

54,0

380V kW

16,4

16,4

21,0

21,0

32,9

42,7

52,6

72,3

78,9

85,5

400V kW

17,3

17,3

22,1

22,1

34,6

45,0

55,4

76,1

83,0

90,0

415V kW

17,9

17,9

23,0

23,0

35,9

46,7

57,4

79,0

86,2

93,3

440V kW

19,0

19,0

24,4

24,4

38,1

49,5

60,9

83,7

91,3

99,0

500V kW

21,6

21,6

27,7

27,7

43,3

56,2

69,2

95,2

103,8

112,5

660V kW

28,5

28,5

36,5

36,5

57,1

74,2

91,3

125,6

137,0

148,4

690V kW

29,8

29,8

38,2

38,2

59,7

77,6

95,5

131,3

143,2

155,2

-

-

-

-

-

-

-

-

-

-

Rated operational current Ie (=Ithe) at 60°C, enclosed A

25

25

32

32

40

55

65

90

100

110

Rated operational power
of three-phase resistive loads
50-60Hz, cosϕ = 1

220V kW

9,5

9,5

12,2

12,2

15,2

20,9

24,7

34,3

38,1

41,9

230V kW

9,9

9,9

12,7

12,7

15,9

21,9

25,9

35,8

39,8

43,8

240V kW

10,4

10,4

13,3

13,3

16,6

22,8

27,0

37,4

41,5

45,7

380V kW

16,4

16,4

21,0

21,0

26,3

36,2

42,7

59,2

65,7

72,3

400V kW

17,3

17,3

22,1

22,1

27,7

38,1

45,0

62,3

69,2

76,1

415V kW

17,9

17,9

23,0

23,0

28,7

39,5

46,7

64,6

71,8

79,0

440V kW

19,0

19,0

24,4

24,4

30,4

41,9

49,5

68,5

76,1

83,7

Rated operational power
of three-phase resistive loads
50-60Hz, cosϕ = 1

A

1000V kW

500V kW

21,6

21,6

27,7

27,7

34,6

47,6

56,2

77,9

86,5

95,2

660V kW

28,5

28,5

36,5

36,5

45,7

62,8

74,2

102,8

114,2

125,6
131,3

690V kW

29,8

29,8

38,2

38,2

47,7

65,7

77,6

107,4

119,4

-

-

-

-

-

-

-

-

-

-

mm² 4

4

6

6

10

16

25

35

50

50

74

1000V kW
Minimum cross-section of conductor
at load with Ie (=Ith)
Utilization category AC2 and AC3
Switching of three-phase motors
Rated operational current Ie
open and enclosed

220V A

12

15

18

22

24

30

40

50

63

230V A

11,5

14,5

18

22

24

30

40

50

62

74

240V A

11

14

18

22

24

32

40

50

62

74

380-400V A

10

14

18

22

24

32

40

50

62

74

415V A

9

14

18

22

23

30

40

50

62

74

440V A

9

14

18

22

23

30

40

50

62

74

500V A

7

9

9

9

17,5

21

21

33

42

42

6,5

8,5

8,5

8,5

17

20

20

31

40

40

-

-

-

-

-

-

-

-

-

220-230V kW

3

4

5

6

6

8,5

11

12,5

18,5

22

240V kW

3

4

5

7

7

9

11,5

13,5

19

23

380-400V kW

4

5,5

7,5

11

11

15

18,5

22

30

37

415V kW

4,5

6

8,5

12

12

16

20

24

33

40

440V kW

4,5

6

8,5

12

12

16

20

24

33

40

500V kW

5,5

7,5

10

10

15

18,5

18,5

30

37

45

10

660-690V A
1000V A
Rated operational power
of three-phase motors
50-60Hz

660-690V kW
1000V kW

5,5

7,5

10

-

-

-

15

18,5

18,5

30

37

45

-

-

-

-

-

-

Utilization category AC4
Switching of squirrel cage motors, inching
Rated operational current Ie (=Ith)
open and enclosed

H-40

220V

A

12

15

18

18

24

30

40

50

63

63

230V

A

11,5

14,5

18

18

24

30

40

50

62

62

240V

A

11

14

18

18

24

32

40

50

62

62

380-400V

A

10

14

18

18

24

32

40

50

62

62

415V

A

9

14

18

18

23

30

37

45

60

60

440V

A

9

14

18

18

23

30

37

45

55

55

500V

A

9

12

16

16

17,5

21

21

33

42

42

660V

A

7

9

9

9

17

20

20

31

40

40

690V

A

6,5

8,5

8,5

8,5

17

20

20

31

40

40

1000V

A

-

-

-

-

-

-

-

-

-

Motor Contactor J7KN

Main Contacts
Rated operational power
of three-phase motors
50-60Hz

Type
220-230V

kW

J7KN-10
3

J7KN-14
4

J7KN-18
5

J7KN-22
5

J7KN-24
6

J7KN-32
8,5

J7KN-40
11

J7KN-50
12,5

J7KN-62
18,5

J7KN-74
18,5

240V

kW

3

4

5

5

7

9

11,5

13,5

19

19

380-400V

kW

4

5,5

7,5

7,5

11

15

18,5

22

30

30

415V

kW

4,5

6

8,5

8,5

12

16

20

24

33

33

440V

kW

4,5

6

8,5

8,5

12

16

20

24

33

33

500V

kW

5,5

7,5

10

10

15

18,5

18,5

30

37

37

660-690V

kW

5,5

7,5

10

10

1000V

kW

-

-

-

15

18,5

18,5

30

37

37

-

-

-

-

-

-

104

Utilization category AC 5a
Switching of gas discharge lamps
Rated operational current Ie per pole at 220/230V
Fluorescent lamps,
uncompensated and serial compensated

A

20

20

25

25

40

52

64

88

96

parallel compensated

A

7

9

9

9

18

22

22

30

40

45

dual-connection

A

22,5

22,5

28

28

45

58

72

98

108

117

uncompensated

A

12

15

19

19

30

39

48

66

72

78

parallel compensated

A

7

9

9

9

18

22

22

30

40

45

uncompensated

A

22,5

25

28

28

45

58

72

99

108

117

parallel compensated

A

7

9

9

9

18

22

22

30

40

45

Mixed light lamps*4

A

20

20

25

25

40

52

64

88

96

104

A

12,5

12,5

12,5

12,5

25

31

31

43

56

56

30

Metal halide lamps*2,

Mercury-vapour lamps*3,

Utilization category AC5b
Switching of incandescent lamps*5
Rated operational current Ie per pole at 220/230V
Utilization category AC6a
Transformer primary switching
at inrush

n

30

30

30

30

30

30

30

30

30

Rated operational current Ie

400V

A

4,5

5,5

7,5

7,5

10,5

13,5

13,5

20

27

33

Rated operational power
dependent on inrush n

220-230V

kVA

1,8

2,2

3

3

4,2

5,4

5,4

8

10,7

13

For different inrush-factors x
use the following formula:
Px=Pn*(n/x)

240V

kVA

1,9

2,3

3,1

3,1

4,3

5,6

5,6

8,3

11,2

13,5

380-400V

kVA

3,1

3,8

5,2

5,2

7,3

9,3

9,3

13,5

18,5

22,5

415-440V

kVA

3,4

4,2

5,7

5,7

8

10,2

10,2

15

20,5

25

500V

kVA

3,9

4,8

6,5

6,5

9

11,5

11,5

17

23

28

660-690V

kVA

5,4

6,5

9

9

12,5

16

16

24

32

39

k

35

25

20

20

25

25

25

25

25

20

Maximum inrush current (peak value) as multiple k of the capacitor
rated current

LVSG

Utilization category AC6b
Switching of three-phase capacitor banks

Rated operational current Ie

500V

A

8

12

15,5

15,5

23

32

32

45

60

70

Rated operational power
(sinϕ→1)

220-230V

kVAr 3

4,5

6

6

8,5

12

12

17

24

28

240V

kVAr 3,5

5

6,5

6,5

9,5

13

13

18,5

25

29

380-400V

kVAr 5

7,5

10

10

15

20

20

29

39

46

415-440V

kVAr 5,5

8

11

11

16

22

22

32

43

50

500V

kVAr 7

10

13

13

20

26

26

39

50

58

660-690V

kVAr 7

10

13

13

20

26

26

40

50

58

Rated operational current Ie

690V

A

13

18

20

28

36

42

48

72

105 1)

Rated operational power

220-230V

kVAr 2,9

5

7

7,5

11

14

16

20

28

33

For different multiples x
use the following formula:
Px=Pk*(k/x)
Switching of detuned capacitors

8

240V

kVAr 3,1

5,4

7

8

11

14

17

20

28

36

380-400V

kVAr 5

9

12,5

13

20

25

27,5

33,3

50

75 1)

415-440V

kVAr 5,5

9,5

13

14

22

27

30

36

53

75 1)

500V

kVAr 6

11

15

17

25

30

36

40

60

75

660-690V

kVAr 8

15

20

22

33

41

48

55

82

100

Utilization category DC1
Switching of resistive load
Time constant L/R ≤1ms
Rated operational current Ie

1 pole24V A

20

25

32

32

50

65

80

110

120

130

60V A

20

25

32

32

50

65

80

110

120

130

110V A

6

6

6

6

10

10

10

12

12

12

220V A

0,8

0,8

0,8

0,8

1,4

1,4

1,4

1,4

1,4

1,4

3 poles in series 24V A

20

25

32

32

50

65

80

110

120

130

60V A

20

25

32

32

50

65

80

110

120

130

110V A

20

25

32

32

50

65

80

110

120

130

220V A

16

20

20

20

30

35

35

63

80

80

Motor Contactor

J7KN

H-41

Main Contacts

Type

J7KN-10

J7KN-14

J7KN-18

J7KN-22

J7KN-24

J7KN-32

J7KN-40

J7KN-50

J7KN-62

J7KN-74

Utilization category DC3 and DC5
Switching of shunt motors and series motors
Time constant L/R ≤15ms
1 pole24V A

20

25

32

32

50

65

80

110

120

130

6

6

6

6

30

30

30

60

60

60

110V A

1,2

1,2

1,2

1,2

1,8

1,8

1,8

1,8

1,8

1,8

220V A

0,2

0,2

0,2

0,2

0,2

0,2

0,2

0,25

0,25

0,25

3 poles in series 24V A

20

25

32

32

50

65

80

110

120

130

60V A

20

25

32

32

40

40

40

80

80

80

110V A

20

20

20

20

40

40

40

80

80

80

220V A

2,5

2,5

2,5

2,5

4

4

4

5

5

5

open °C

-40 to +60 (+90)*6

Rated operational current Ie

60V A

Maximum ambient temperature
Operation

enclosed °C
with thermal overload relay

-40 to +40

open °C

-25 to +60

enclosed

°C

-25 to +40

Storage

°C

-50 to +90

Short circuit protection
for contactors without thermal overload relay
Coordination-type "1" according to IEC 947-4-1
Contact welding without
hazard of persons
max. fuse size

gL (gG) A

63

63

63

63

80

80

80

160

160

160

gL (gG) A

25

35

35

35

50

50

50

100

125

125

gL (gG) A

16

16

16

16

25

35

35

50

63

63

Coordination-type “2” according to IEC 947-4-1
Light contact welding accepted
max. fuse size
Contact welding not accepted
max. fuse size

For contactors with thermal overload relay the device with
the smaller admissible backup fuse (contactor or thermal
overload relay) determines the fuse size.
Cable cross-sections
for contactors without thermal overload relay
main connector

solid or stranded mm² 0,75 - 6
flexible mm² 1 - 4
flexible with multicore cable end mm² 0,75 - 4

Cables per clamp

2
solid or stranded mm² 6+(1-6) / 4+(0,75-4)
2,5+(0,75-2,5) / 1,5+(0,75-1,5)
flexible mm² 6+(1,5-6) / 4+(1-4)
2,5+(0,75-2,5) / 1,5+(0,75-1,5)

Cables per clamp

2

main connector

solid AWG 18 - 10
flexible AWG 18 - 10

1,5 - 25

4 - 50

2,5 - 16

10 - 35

1,5 - 16

6 - 35

1

1

16+(2,5-6) / 10+(4-10)

50+4 / 35+6 / 25+(6-16)

6+(4-6) / 4+(2,5-4)

16+(6-16) / 10+(6-16)

16+(2,5-6) / 10+(4-10)

50+(4-10) / 35+(4-16)

6+(4-6) / 4+(2,5-4)

25+(4-25) / 16+(4-16)

2

2

16 - 10

12 - 10

14 - 4

10 - 0

1

1

solid AWG 10+(16-10) / 12+(18-12)

10+(16-10) / 12+(18-12)

10+(12-10) / 12+12

14+(18-14) / 16+(18-16)

14+(18-14) / 16+(18-16)

Cables per clamp

2

flexible AWG 10+(14-10) / 12+(18-12)
Cables per clamp

4+(18-12) / 6+(18-8)

1+(12-10) / 2+(8-12)

14+(18-14) / 16+(18-16)

8+(18-8) / 10+(18-12)

3+(12-8) / 4+(10-6)

2

2

2

Frequency of operations z
Contactors without thermal overload relay
without load 1/h

10000

10000

10000

7000

7000

7000

7000

7000

7000

AC3, Ie

1/h 600

10000

600

600

600

600

600

600

400

400

400

AC4, Ie

1/h 120

120

120

120

120

120

120

120

120

120

DC3, Ie

1/h 600

600

600

600

600

600

600

400

400

400

Mechanical life
AC operated

S x 106

10

10

10

10

10

10

10

10

10

10

DC operated

S x 106

10

10

10

10

10

10

10

10

10

10

Short time current
Power loss per pole

10s-current
at Ie/AC3 400V

A 96

120

144

176

184

240

296

360

504

592

W 0,21

0,35

0,5

0,75

0,7

1,3

2

2,2

3,9

5,5

Resistance to shock acc. to IEC 68-2-27
Shock time 20ms sine-wave

NO g

10

10

10

10

8

8

8

8

8

8

NC g

6

6

6

6

-

-

-

-

-

-

*1) Suitable at 690V for: earthed-neutral systems, overvoltage I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
*2) Metal halide lamps and sodium-vapour lamps (high- and low-pressure lamps)
*3) High-pressure lamps
*4) Blended lamps, containing a mercury high-pressure unit and a tungsten helix in a flourescent glass bulb (daylight lamps)
*5) Current inrush approx. 16 x Ie
*6) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie/AC1 according to Ie/AC3

H-42

Motor Contactor J7KN

Main Contacts

Type J7KN-85

J7KN-110

J7KN-150

J7KN-175

Rated insulation voltage Ui *1

V AC 750

750

690

690

690

1200

1500

1800

1700

Making capacity Ieff

at Ue = 690V AC A

1100

J7KN-200

Breaking capacity Ieff

400V AC A

950

1100

1200

1400

1600

J7KN-10 to J7KN-22 cosϕ = 0,65

500V AC A

850

1000

1200

1400

1600

600

600

700

800

1200

-

-

-

-

-

J7KN-24 to J7KN-72 cosϕ = 0,35

690V AC A
1000V AC A

Utilization category AC1
Switching of resistive load
Rated operational current Ie (=Ith) at 40°C, open

150

170

200

250

350

220V kW

57

64

72

90

125

230V kW

59

67

72

90

125

240V kW

62

70

75

94

130

380V kW

98

111

125

156

218

400V kW

103

117

125

156

218

415V kW

107

122

130

160

225

440V kW

114

129

144

180

250

500V kW

130

147

164

205

285

660V kW

171

194

216

270

380

690V kW

179

203

216

270

380

-

-

-

-

-

Rated operational current Ie (=Ithe) at 60°C, enclosed A

100

125

160

200

280

Rated operational power
of three-phase resistive loads
50-60Hz, cosϕ = 1

220V kW

38

47

60

76

106

230V kW

40

49

63

79

111

240V kW

41

52

66

83

116

380V kW

65

82

105

131

184

400V kW

69

86

110

138

193

415V kW

71

89

115

143

201

440V kW

71

95

121

152

213

500V kW

86

108

138

173

242

660V kW

114

142

182

228

320

690V kW

119

149

191

239

334

-

-

-

-

-

70

95

120

185

Rated operational power
of three-phase resistive loads
50-60Hz, cosϕ = 1

A

1000V kW

1000V kW
Minimum cross-section of conductor
at load with Ie (=Ith)

mm² 50

Rated operational current Ie
open and enclosed

220V A

85

110

150

175

210

230V A

85

110

150

175

210

240V A

85

110

150

175

210

380-400V A

85

110

150

175

210

415V A

85

110

150

175

210

440V A

85

110

-

-

-

500V A
660-690V A
1000V A
220-230V kW

Rated operational power
of three-phase motors
50-60Hz

60

60

-

-

-

57,5

57,5

-

-

-

-

-

-

-

-

25

33

40

50

60

240V kW

27

35

45

55

65

380-400V kW

45

55

75

90

110

415V kW

49

63

80

95

115

440V kW

49

63

85

100

125

500V kW

55

75

75

100

132

660-690V kW

55

55

75

110

132

-

-

-

-

-

1000V kW

LVSG

Utilization category AC2 and AC3
Switching of three-phase motors

Utilization category AC4
Switching of squirrel cage motors, inching
Rated operational current Ie (=Ith)
open and enclosed

220V

A

85

98

55

63

85

230V

A

85

98

55

63

85

240V

A

85

98

55

63

85

380-400V

A

85

85

55

63

85

415V

A

85

85

-

-

-

440V

A

85

85

-

-

-

500V

A

85

85

-

-

-

660V

A

60

60

-

-

-

690V

A

57,5

57,5

-

-

-

1000V

A

-

-

-

-

-

Motor Contactor

J7KN

H-43

Main Contacts
Rated operational power
of three-phase motors
50-60Hz

Type J7KN-85

J7KN-110

J7KN-150

J7KN-175

220-230V

kW

25

30

15

18,5

J7KN-200
25

240V

kW

27

32

15,5

19

26

380-400V

kW

45

45

25

30

45

415V

kW

49

49

25

33

45

440V

kW

49

49

30

34

48

500V

kW

55

55

25

30

55

660-690V

kW

55

55

25

30

55

1000V

kW

-

-

-

-

-

Utilization category AC 5a
Switching of gas discharge lamps
Rated operational current Ie per pole at 220/230V
Fluorescent lamps,
uncompensated and serial compensated

A

100

120

120

140

180

parallel compensated

A

55

70

85

100

120

dual-connection

A

112

144

120

140

180

Metal halide lamps*2,
uncompensated

A

85

90

95

110

140

parallel compensated

A

55

70

75

85

110

Mercury-vapour lamps*3,
uncompensated

A

112

144

120

140

180

parallel compensated

A

55

70

75

85

110

Mixed light lamps*4

A

100

120

100

120

160

A

69

75

100

120

160

Utilization category AC5b
Switching of incandescent lamps*5
Rated operational current Ie per pole at 220/230V
Utilization category AC6a
Transformer primary switching
at inrush

n

30

30

30

30

30

Rated operational current Ie

400V

A

38

50

65

80

90

Rated operational power
dependent on inrush n

220-230V

kVA

15

20

25

30

34

240V

kVA

15,5

20,5

27

33

37

380-400V

kVA

26

34

45

55

60

415-440V

kVA

29

38

46

57

63

500V

kVA

33

43

55

69

75

45

60

56

69

100

k

20

20

20

20

15

87

195

For different inrush-factors x
use the following formula:
Px=Pn*(n/x)

660-690V
Utilization category AC6b
Switching of three-phase capacitor banks
Maximum inrush current (peak value) as multiple k of the capacitor
rated current
Rated operational current Ie

500V

A

100

120

155

Rated operational power
(sinϕ→1)

220-230V

kVAr 33

38

45

60

75

240V

kVAr 36

42

52

62

78

380-400V

kVAr 57

65

80

100

130

415-440V

kVAr 60

70

95

110

135

500V

kVAr 70

80

100

130

170

660-690V

kVAr 70

80

100

130

170

For different multiples x
use the following formula:
Px=Pk*(k/x)
Switching of detuned capacitors
Rated operational current Ie

690V

A

105

115

140

200

Rated operational power

220-230V

kVAr 35

98

40

43

53

76

240V

kVAr 39

43

45

55

80

380-400V

kVAr 68

75

75

90

130

415-440V

kVAr 71

77

80

100

140

500V

kVAr 85

90

95

120

170

660-690V

kVAr 110

120

125

150

200

Utilization category DC1
Switching of resistive load
Time constant L/R ≤1ms
Rated operational current Ie

H-44

1 pole24V A

150

170

-

-

-

60V A

150

170

-

-

-

110V A

20

25

-

-

-

220V A

2

2,5

-

-

-

3 poles in series 24V A

150

170

200

250

350

60V A

150

170

200

250

350

110V A

150

170

150

170

250

220V A

100

160

80

100

150

Motor Contactor J7KN

Main Contacts

Type J7KN-85

J7KN-110

J7KN-150

J7KN-175

J7KN-200

-

Utilization category DC3 and DC5
Switching of shunt motors and series motors
Time constant L/R ≤15ms
1 pole24V A

Rated operational current Ie

150

170

-

-

60V A

85

110

-

-

-

110V A

2

2,5

-

-

-

220V A

0,5

0,5

-

-

-

3 poles in series 24V A

150

170

-

-

-

60V A

100

110

-

-

110V A

100

110

-

-

-

220V A

7

8

-

-

-

open °C

-40 to +60 (+90)*6

Maximum ambient temperature
Operation

-25 to +55 (+70)*7

enclosed °C

-40 to +40

-25 to +40

open °C

-25 to +60

-25 to +55

with thermal overload relay
enclosed

°C

-25 to +40

-25 to +40

Storage

°C

-50 to +90

-55 to +80

Short circuit protection
for contactors without thermal overload relay
Coordination-type "1" according to IEC 947-4-1
Contact welding without hazard of persons
max. fuse size

gL (gG) A

250

250

250

315

400

gL (gG) A

160

200

200

250

315

gL (gG) A

100

125

160

200

250

10 - 70*8

95

120

185

16 - 50*8

screw

screw

screw

10 - 35

M8

M8

M8

Coordination-type “2” according to IEC 947-4-1
Light contact welding accepted
max. fuse size
Contact welding not accepted
max. fuse size

For contactors with thermal overload relay the device with
the smaller admissible backup fuse (contactor or thermal
overload relay) determines the fuse size.
Cable cross-sections
for contactors without thermal overload relay
solid or stranded mm² 10 - 70*8

main connector

flexible mm² 6 - 50*8
flexible with multicore cable end mm² 10 - 35
Cables per clamp
solid or stranded mm²

LVSG

flexible mm²
Cables per clamp
main connector

solid AWG 10
flexible AWG 6 - 0

Cables per clamp

10
6-0

1

1

solid AWG
flexible AWG
Cables per clamp
Frequency of operations z
Contactors without thermal overload relay
without load 1/h

3000

3000

1200

1200

1200

AC3, Ie 1/h

300

300

-

-

-

AC4, Ie 1/h

120

120

-

-

-

DC3, Ie 1/h

300

300

-

-

-

AC operated

S x 106

5

5

10

10

8

DC operated

S x 106

5

5

10

10

8

10s-current A

680

880

1200

1400

1800

at Ie/AC3 400V W

4,3

6,0

8

11

8

Mechanical life

Short time current
Power loss per pole

Resistance to shock acc. to IEC 68-2-27
Shock time 20ms sine-wave

NO g

7

7

-

-

-

NC g

5

5

-

-

-

*1) Suitable at 690V for: earthed-neutral systems, overvoltage I to IV, pollution degree 3 (standard-industry):
Uimp = 8kV. Data for other conditions on request.
*2) Metal halide lamps and sodium-vapour lamps (high- and low-pressure lamps)
*3) High-pressure lamps
*4) Blended lamps, containing a mercury high-pressure unit and a tungsten helix in a flourescent glass bulb
(daylight lamps)
*5) Current inrush approx. 16 x Ie
*6) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie/AC1 according to Ie/AC3
*7) With reduced control voltage range 1,0 x Us and with reduced rated current Ie/AC1 according to Ie/AC3
*8) Maximum cable cross-section with prepared conductor

Motor Contactor

J7KN

H-45

Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Auxiliary Contacts

Type J7KN-10

J7KN-14

J7KN-18

J7KN-22

J7KN-24

J7KN-32

J7KN-40

J7KN-50

J7KN-62

J7KN-74

Rated insulation voltage Ui*1

V~

690

690

690

690

-

-

-

-

-

-

40°C A

16

16

16

16

-

-

-

-

-

-

60°C A

12

12

12

12

-

-

-

-

-

-

220-240V A

12

12

12

12

-

-

-

-

-

-

380-415V A

4

4

4

4

-

-

-

-

-

-

440V A

4

4

4

4

-

-

-

-

-

-

500V A

3

3

3

3

-

-

-

-

-

-

660-690V A

1

1

1

1

-

-

-

-

-

-

Thermal rated current Ith to 690V
Ambient temperature
Utilization category AC15
Rated operational current Ie

Utilization category DC13
Rated operational current Ie

60V A

8

8

8

8

-

-

-

-

-

-

110V A

1

1

1

1

-

-

-

-

-

-

220V A

0,1

0,1

0,1

0,1

-

-

-

-

-

-

gL (gG) A

25

25

25

25

-

-

-

-

-

-

Short circuit protection
short-circuit current 1kA,
contact welding not accepted
max. fuse size

For contactors with thermal overload relay the device with
the smaller admissible control fuse (contactor or thermal
overload relay) determines the fuse.
Control Circuit
Power consumption of coils
AC operated

DC operated

inrush VA

33-45

90-115

sealed VA

7-10

9-13

140-165
13-18

W

2,6-3

2,7-4

5,4-7

inrush W

75

140

200

sealed W

2

2

6

AC operated

0,85-1,1

0,85-1,1

0,85-1,1

DC operated

0,8-1,1

0,8-1,1

0,8-1,1

make time ms

8-16

10-25

12-28

release time ms

5-13

8-15

8-15
10-15

Operation range of coils
in multiples of control voltage Us

Switching time at control voltage Us ±10%*2,*3
AC operated

arc duration ms
DC operated

10-15

10-15

make time ms

8-12

10-20

12-23

release time ms

8-13

10-15

10-18

arc duration ms

10-15

10-15

10-15

-

-

-

-

Cable cross-section
Auxiliary connector

solid mm² 0,75-6
flexible mm² 1-4

flexible with multicore cable end
Magnet coil

-

-

0,75-2,5

0,75-2,5

flexible mm² 0,5-2,5

0,5-2,5

0,5-2,5

flexible with multicore cable end mm² 0,5-1,5

0,5-1,5

0,5-1,5

2

2

solid AWG 18 - 10

-

-

flexible AWG 18 - 10

-

-

14 - 12

14 - 12

solid mm² 0,75-2,5

Clamps per pole

2

Auxiliary connector
Magnet coil

mm² 0,75-4

solid AWG 14 - 12
flexible AWG 18 - 12

Clamps per pole

2

18 - 12

18 - 12

2

2

*1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request
*2) Total breaking time = release time + arc duration
*3) Values for delay of the release time of the making contact and the make time of the break contact will be increased, if magnet coils are
protected against voltage peaks (varistor, RC-unit, diode-unit)

H-46

Motor Contactor J7KN

Auxiliary Contacts

Type J7KN-85

J7KN-110

J7KN-150

J7KN-175

J7KN-200

Rated insulation voltage Ui*1

V~

690

690

690

690

690

Thermal rated current Ith to 690V
Ambient temperature

40°C A

16

16

10

10

10

60°C A

12

12

-

-

-

220-240V A

12

12

3

3

3

380-415V A

6

6

2

2

2

440V A

6

6

1,5

1,5

1,5

500V A

4

4

1,5

1,5

1,5

660-690V A

2

2

1

1

1
-

Utilization category AC15
Rated operational current Ie

Utilization category DC13
Rated operational current Ie

60V A

8

8

-

-

110V A

1

1

0,5

0,5

1

220V A

0,1

0,1

0,2

0,2

0,5

gL (gG) A

25

25

10

10

10

inrush VA

280-350

350-420

550

550

1100

sealed VA

16 -23

23 -29

120

120

66

W

4-6

6-7,3

-

-

-

inrush W

170

320

160

160

530

sealed W

2

4

5

5

21

Short circuit protection
short-circuit current 1kA,
contact welding not accepted
max. fuse size

For contactors with thermal overload relay the device with
the smaller admissible control fuse (contactor or thermal
overload relay) determines the fuse.
Control Circuit
Power consumption of coils
AC operated

DC operated
Operation range of coils
in multiples of control voltage Us

AC operated

0,85-1,1

0,85-1,1

0,85-1,1

0,85-1,1

DC operated

0,8-1,1

0,85-1,1

0,85-1,1

0,85-1,1
30-40

AC operated

make time ms

DC operated

13-30

12-30

12-30

release time ms

8-15

15-40

15-40

15-45

arc duration ms

10-15

-

-

make time ms

20-30

-

-

release time ms

10-18

-

-

-

arc duration ms

10-15

-

-

-

LVSG

Switching time at control voltage Us ±10%*2,*3

Cable cross-section
Auxiliary connector
flexible with multicore cable end
Magnet coil

solid mm² 0,75-2,5

0,75-2,5

flexible mm² 0,75-2,5

0,75-2,5

mm² 0,5-1,5
solid mm² 0,75-2,5
flexible mm² 0,5-2,5

flexible with multicore cable end mm² 0,5-1,5
Clamps per pole
Auxiliary connector
Magnet coil

14 - 12

1-2,5
1-2,5
16 - 12

solid AWG 18 - 12

16 - 12

flexible AWG 14 - 12

16 - 12

solid AWG 18 - 12
flexible AWG 2

Clamps per pole

-

0,75-2,5

16 - 12
2
0,75-2,5

*1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3
(standard-industry): Uimp = 8kV. Data for other conditions on request
*2) Total breaking time = release time + arc duration
*3) Values for delay of the release time of the making contact and the make time of the
break contact will be increased, if magnet coils are protected against voltage peaks
(varistor, RC-unit, diode-unit)

Motor Contactor

J7KN

H-47

Contactors for North America
Data according to UL508
Main Contacts (cULus)

Type J7KN-10

J7KN-14

J7KN-18

J7KN-22

J7KN-24

J7KN-32

J7KN-40

J7KN-50

J7KN-62

J7KN-74

Rated operational current
"General Use"

A

25

30

30

50

65

80

110

120

130

Rated operational power

1½

2

2

3

5

5

7½

10

10

10

200V hp

3

3

5

5

7½

10

10

15

20

25

220-240V hp

3

3

7½

7½

10

10

15

20

25

30

277V hp

3

5

7½

7½

7½

10

15

20

25

30

380-415V hp

5

5

10

10

10

15

20

25

30

40

440-480V hp

5

7½

10

15

15

20

25

30

40

50

550-600V hp

7½

10

15

20

20

25

30

40

50

50

110-120V hp

½

¾

1

1½

1½

2

3

3

5

7½

of AC motors

200V hp

1

1,5

2

3

3

5

7½

7½

10

15

at 60Hz (1ph)

220-240V hp

of three-phase motors
at 60Hz (3ph)

Rated operational power

Rated operational power of
three-phase motors at 60Hz (3ph)
for elevators

110-120V hp

25

1½

2

3

3

5

5

7½

10

15

15

277V hp

2

3

3

5

5

7½

10

10

15

15

380-415V hp

3

3

5

5

5

7½

10

15

20

20

440-480V hp

3

5

5

7½

7½

10

15

20

25

25

550-600V hp

3

5

7½

10

10

15

20

25

30

30

110-120V hp

-

-

-

-

2

3

-

3

5

-

200V hp

-

-

-

-

3

5

-

7½

10

-

220-240V hp

-

-

-

-

5

7½

-

7½

10

-

Demands according to ANSI A17.5
(500.000 operations)
Rated operationalcurrent
Fuses

440-480V hp

-

-

-

-

10

15

-

20

25

-

550-600V hp

-

-

-

-

10

20

-

25

30

-

-

-

-

-

15

22

-

27

37

-

30

40

50

50

90

125

175

175

225

250

5000

5000

5000

5000

5000

5000

5000

5000

5000

5000

600

600

600

600

600

600

600

600

600

600

A600

A600

A600

A600

-

-

-

-

-

-

600V A
A

Suitable for use on a capability
of delivering not more than

rms A
V

Auxiliary Contacts (cULus)

Main Contacts (cULus)

Type J7KN-85

J7KN-110

J7KN-150

J7KN-175

J7KN-200

Rated operational current
"General Use"

A

125

-

-

-

Rated operational power
of three-phase motors
at 60Hz (3ph)

110-120V hp
200V hp
220-240V hp

125
15

-

-

-

-

-

30

-

-

-

35

40

-

-

-

277V hp

-

-

-

-

-

380-415V hp

-

-

-

-

-

440-480V hp

65

75

-

-

-

550-600V hp

85

100

-

-

-

110-120V hp

8

10

-

-

-

of AC motors

200V hp

-

20

-

-

-

at 60Hz (1ph)

220-240V hp

Rated operational power

Rated operational power of
three-phase motors at 60Hz (3ph)
for elevators

20

20

-

-

-

277V hp

-

-

-

-

-

380-415V hp

-

-

-

-

-

440-480V hp

-

50

-

-

-

550-600V hp

-

60

-

-

-

110-120V hp

-

-

-

-

-

200V hp

-

-

-

-

-

220-240V hp

-

-

-

-

-

Demands according to ANSI A17.5
(500.000 operations)
Rated operationalcurrent
Fuses

440-480V hp

-

-

-

-

-

550-600V hp

-

-

-

-

-

600V A

-

62

-

-

-

A

-

300

-

-

-

10000

10000

-

-

-

600

600

-

-

-

A600

A600

-

-

-

Suitable for use on a capability
of delivering not more than

rms A
V

Auxiliary Contacts (cULus)

H-48

Motor Contactor J7KN

Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Contact Life
For selection of the suitable contactor-type according to supply voltage, power rating and application (utilization category AC1, AC3 or
AC4) use contact life characteristic diagram.

For contactors frequently used under AC3/AC4-mixed service conditions calculate contact life with the formula:

AC3
M = --------------------------------------------------------%AC4  AC3
1 + ----------------- x  ----------- – 1
100
AC4

For the most common supply voltages four scales of power ratings Pn
are provided for each utilization category.
Select contactor-type according to utilization category AC3 (breaking
current Ia = Ie) using the motor rating scales to the right, according
to utilization category AC4 (breaking current Ia = 6 x Ie) using the
motor rating scales to the left.*1
Select contactor-type according to utilization category AC1 (breaking
current Ia = Ie/AC1) using the breaking current scale.*1

M = Contact life (switching cycles) for AC3/AC4-mixed operations
AC3 = Contact life (switching cycles) for AC3 operations (normal switching
conditions). Breaking current Ia = rated motor current In.

AC4 = Contact life (switching cycles) for AC4 operations (inching).
Breaking current Ia= multiples of rated motor current In.

%AC4 = Percents of AC4-operations related to the total cycles.
Pay attention to the approved rated values of the selected
contactor according to the national approvals

Motor Rating
Pn/AC4

Motor Rating
Pn/AC3

Breaking Current
Ia (=Ie/AC1)
A

J7KN-74
J7KN-62
J7KN-50
J7KN-40
J7KN-32
J7KN-24
J7KN-22
J7KN-18
J7KN-14
J7KN-12
J7KN-10
J7KN-09

LVSG

1.

millions of operations

Motor Contactor

J7KN

H-49

Motor Rating
Pn/AC4

Motor Rating
Pn/AC3

Breaking Current
Ia (=Ie/AC1)
A

J7KN-200
J7KN-175
J7KN-150
J7KN-110
J7KN-85

millions of operations

H-50

Motor Contactor J7KN

Contactors
Utilization Categories
For easier choice of devices and in order to make the comparison of
different products simplier are utilization categories for contactors and
motor-starters according to IEC 947-4-1 and VDE 0660 Part 102 ,for
Rated operational
current

Test conditions for the number of
on-load operating cycles

Alternating Current

Make

Break

Make

Break
Ic/Ie

Ur/Ue

cosϕ

AC1

Non-inductive or
all values
slightly inductive loadsresistance furnaces

1

1

0.95

1

1

0.95

1.5

1.05

0.8

1.5

1.05

0.8

AC2

Slip-ring motors:
starting, switching off

2.5

1

0.65

2.5

1

0.65

4

1.05

0.65

4

1.05

0.65

AC3

Squirrel-cage motors:
17A< Ie≤
starting, switching off moIe≤
tors during running
Ie>

17A

0.45

Squirrel-cage motors:
17A< Ie≤
starting, plugging, inching
Ie≤

AC4

all values

Ie>

I/Ie

U/Ue

cosϕ

Ic/Ie

Ur/Ue

cosϕ

I/Ie

U/Ue

cosϕ

6

1

0.65

1

0.17

0.65

10

1.05

0.45

8

1.05

100A 6

1

0.35

1

0.17

0.35

10

1.05

0.45

8

1.05

0.45

100A 6

1

0.35

1

0.17

0.35

10

1.05

0.35

8

1.05

0.35

17A

0.45

6

1

0.65

6

1

0.65

12

1.05

0.45

10

1.05

100A 6

1

0.35

6

1

0.35

12

1.05

0.45

10

1.05

0.45

100A 6

1

0.35

6

1

0.35

12

1.05

0.35

10

1.05

0.35

AC5a Switching of electric discharge lamp controls

all values

-

-

-

-

-

-

3

1.05

0.45

3

1.05

0.45

AC5b Switching of incandescent lamps

all values

-

-

-

-

-

-

1.5

1.05

1)

4

1.05

1)

Ie≤

100A -

-

-

-

-

-

4.5

1.05

0.45

3.6

1.05

0.45

Ie>

100A -

-

-

-

-

-

4.5

1.05

0.35

3.6

1.05

0.35

-

-

-

-

-

-

2)

-

-

-

-

-

-

1.5

1.05

0.8

1.5

1.05

0.8

0.45

AC6a Switching of transformers
AC6b Switching of capacitor
banks

-

AC7a Slightly inductive loads in all values
household appliances
and similar applications

2)

AC7b Motor loadsfor household
applications

Ie≤

100A -

-

-

-

-

-

8

1.05

0.45

6

1.05

Ie>

100A -

-

-

-

-

-

8

1.05

0.35

6

1.05

0.35

AC8a Hermetic refrigerant compressor motor control with
manualresetting of overload releases

Ie≤

100A -

-

-

-

-

-

6

1.05

0.45

6

1.05

0.45

Ie>

100A -

-

-

-

-

-

6

1.05

0.35

6

1.05

0.35

AC8b Hermetic refrigerant compressor motor control with
automatic resetting of
overload releases

Ie≤

100A -

-

-

-

-

-

6

1.05

0.45

6

1.05

0.45

Ie>

100A -

-

-

-

-

-

6

1.05

0.35

6

1.05

0.35

AC12 Control of resistive loads all values
and solid state loads with
isolation by opto couplers

-

-

-

-

-

-

1

1

0.9

1

1

0.9

AC13 Control of solid state
loads with transformer
isolation

-

-

-

-

-

-

10

1.1

0.65

1.1

1.1

0.65

AC14 Control of small electro- magnetic loads (<=72VA)

-

-

-

-

-

-

6

1.1

0.7

6

1.1

0.7

AC15 Control of
electromagnetic load
(>72VA)

10

1

0.7

1

1

0.4

10

1.1

0.3

10

1.1

0.3

all values

-

Make

Direct Current

Test conditions for
making and breaking capacities

L/R

Break

L/R

Make

L/R

Break

I/Ie

U/Ue

[ms]

Ic/Ie

Ur/Ue

[ms]

I/Ie

U/Ue

[ms]

Ic/Ie

Ur/Ue

L/R
[ms]

DC1

Non-inductive or
all values
slightly inductive loads resistance furnaces

1

1

1

1

1

1

1.5

1.05

1

1.5

1.05

1

DC3

Shunt-motors: starting,
all values
plugging, inching dynamic
braking of d.c. motors

2.5

1

2

2.5

1

2

4

1.05

2.5

4

1.05

2.5

DC5

Series-motors:
all values
starting, plugging, inching
dynamic braking of d.c.
motors

2.5

1

7.5

2.5

1

7.5

4

1.05

15

4

1.05

15

DC6

Switching of incandescent lamps

all values

-

-

-

-

-

-

1.5

1.05

1)

4

1.05

1)

DC12 Control of resistive loads all values
and solid state loads with
isolation by opto couplers

-

-

-

-

-

-

1

1

1

1

1

1

DC13 Control of electromagnets all values

1

1

≤300

1

1

≤300

1.1

1.1

≤300

1.1

1.1

≤300

DC14 Control of electromagnet- all values
ic loads having economy
resistors in circuit

-

-

-

-

-

-

10

1.1

15

10

1.1

15

U Rated operational voltage, U Voltage before make, U Recovery voltage, I Rated operational current, I Current make, I Current broken
e

r

e

c

1) Test with incandescent lamps
2) Test conditions according to standard

Motor Contactor

J7KN

H-51

LVSG

Type of Cate- Typical applications
current gory

control circuit devices and switching elements according to IEC 947-51 and VDE 0660 Part 200 determind. The table offers different utilization categories, typical applications and assorted test conditions.

Accessories
Data according to IEC 947-5-1, EN 60947-5-1, VDE 0660
Auxiliary Contacts

Type J73KN-B

J73KN-C

J73KN-B-TP...

Rated insulation voltage Ui*1

V~

690

690

690

40°C A

10

10

10

60°C A

6

6

-

Thermal rated current Ith to 690V
Ambient temperature
Frequency of operations z

1/h

3000

3000

1200

Mechanical life

Sx
106

10

10

1

Power loss per pole at Ie/AC1

W

0,5

0,5

-

220-240V

A

3

3

4

380-400V

A

2

2

3

440V

A

1,6

1,6

2

500V

A

1,2

1,2

2

660-690V

A

0,6

0,6

2

Utilization category AC15
Rated operational current Ie

Utilization category DC13
Rated operational current Ie

60V

A

2

2

2,5

110V

A

0,4

0,4

1,5

220V

A

0,1

0,1

0,2

gL (gG)

A

20

20

10

Short circuit protection
short-circuit current 1kA, contact
welding not accepted max. fuse
size

For contactors with thermal overload relay or auxiliary contacts the device with the smaller admissible control fuse
(contactor or thermal overload relay) determines the fuse
size.
Cable cross-sections
solid or stranded mm² 0,75-2,5

0,75-2,5

1-2,5

flexible mm² 0,75-2,5

0,75-2,5

0,75-2,5

flexible with multicore cable end mm² 0,5-1,5
Cables per clamp

2

0,5-1,5

0,75-2,5

2

2

*1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request

Data according to CSA, UL and CUL
Auxiliary Contacts

Type J73KN-B

J73KN-C

J73KN-B-TP...

Rated operational current
„General Use“

A

10

10

600

600

A600

A600

Rated operational voltage

10

max. V AC 600

Auxiliary Contacts

A600

Contactors and Accessories
Wiring diagrams
Auxiliary contact blocks
J73KN-B-10

J73KN-B-01

Pneumatic timer
J73KN-C-11S*1

(left side) (right side)
53 61 71 83

54 62
*1) Correct terminal marking is given by mounting

H-52

Motor Contactor J7KN

72 84

on-delayed

off-delayed

J74KN-B-TP...DA

J74KN-B-TP...IA

AC operated

DC operated

J7KN-10...
J7KN-10-4
J7KN-14...
J7KN-18...
J7KN-22...

J7KN-10...D
J7KN-14...D
J7KN-18...D
J7KN-22...D

J7KN-24...
J7KN-32...
J7KN-40...

J7KN-24...D
J7KN-32...D
J7KN-40...D

J7KN-50...
J7KN-62...
J7KN-74...

J7KN-50...D
J7KN-62...D
J7KN-74...D

LVSG

■ Dimensions

Motor Contactor

J7KN

H-53

AC operated
J7KN-85...
J7KN-110...

J7KN-200...

J7KN-150...
J7KN-175...

Auxiliary contact blocks
J73KN-B-01
J73KN-B-10

H-54

J73KN-C-11S

Motor Contactor J7KN

Pneumatic timer
J74KN-B-TP...

Auxiliary contact blocks
J74KN-A-RC

J74KN-B-VG

J74KN-B-RC

LVSG

J74KN-A-VG

Motor Contactor

J7KN

H-55

Position of Terminals
AC operated
J7KN-10-10
to
J7KN-22-10

J7KN-10-01
to
J7KN-22-01

J7KN-150-11
J7KN-175-11

J7KN-24
J7KN-32
J7KN-40

J7KN-50
J7KN-62
J7KN-74

J7KN-85-22
J7KN-110-22

J7KN-50...D
J7KN-62...D
J7KN-74...D

J7KN-81-21...D
J7KN-110-21...D

J7KN-200-22

DC operated with double winding coil
J7KN-10-01...D
J7KN-14-01...D
J7KN-18-01...D
J7KN-22-01...D

J7KN-10-10...D
J7KN-14-10...D
J7KN-18-10...D
J7KN-22-10...D

J7KN-24...D
J7KN-32...D
J7KN-40...D

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

Cat. No. J505-E2-02

H-56

In the interest of product improvement, specifications are subject to change without notice.

Motor Contactor J7KN

Thermal Overload Relay

J7TKN

)

Thermal Overload Relay
• Direct and separate mounting
• Single phasing sensivity according to IEC 947-4-1
• Finger proof (VBG 4)

Accessories
• Busbar sets
• Set for single mounting

Approved Standards
Standard

Guide No (US,C)

UL

NKCR, NKCR7

ICE 947-4-1
VDE 0660
EN 60947-4-1

Ordering Information

1. Thermal Overload Relay

J7TKN-#-###
1
2 3
1)
2)

3)

Thermal Overload Relay
A:
for mini motor contactor and motor contactor (4-11 kW)
B:
for motor contactor (4-15 kW)
C:
for motor contactor (18.5 kW)
D:
for motor contactor (22-37 kW)
E:
for motor contactor (45-55 kW)
F:
for motor contactor (75-110 kW)
Setting range (examples)
E16: 0.12-0.16 A
E27: 0.18-0.27 A
...
2E7: 1.8-2.7 A
...
11:
8-11 A

LVSG

■ Model Number Legend
2. Accessories for Thermal Overload Relay

J74TK-##-###
1
2
3
1)
2)
3)

Accessories for Thermal Overload Relay
SM:
Single mounting for J7TKN-B Types (4-32 kW)
SU:
Busbar sets
175:
for J7TKN-F Types (75-90 kW)
200:
for J7TKN-F Types (110 kW)

Thermal Overload Relay

J7TKN

H-57

■ System overview
Thermal Overload Relays for plug-in mounting
Setting Range

Type

(A)

D.O.L.

(A)

Star Delta

Pack

Weight

pcs.

kg/pc.

For contactors J7KNA-09..., J7KNA-12..., J7KN-10... to J7KN-22...
0.12

-

0.18

-

J7TKN-A-E18

1

0.10

0.18

-

0.27

-

J7TKN-A-E27

1

0.10

0.27

-

0.4

-

J7TKN-A-E4

1

0.10

0.4

-

0.6

-

J7TKN-A-E6

1

0.10

0.6

-

0.9

-

0.8

-

1.2

-

hand reset

J7TKN-A-E9

1

0.10

J7TKN-A-1E2

1

0.10
0.10

1.2

-

1.8

-

J7TKN-A-1E8

1

1.8

-

2.7

-

J7TKN-A-2E7

1

0.10

2.7

-

4

-

J7TKN-A-4

1

0.10

4

-

6

7

-

10.5

J7TKN-A-6

1

0.10

6

-

9

10.5

-

15.5

J7TKN-A-9

1

0.10

8

-

11

14

-

19

J7TKN-A-11

1

0.10

10

-

14

18

-

24

J7TKN-A-14

1

0.10

13

-

18

23

-

31

J7TKN-A-18

1

0.10

17

-

23

30

-

40

J7TKN-A-23

1

0.10

22

-

30

38

-

52

J7TKN-A-30

1

0.10

For contactors J7KN-10... to J7KN-40...
0.12

-

0.18

-

J7TKN-B-E18

1

0.14

0.18

-

0.27

-

J7TKN-B-E27

1

0.14

0.27

-

0.4

-

J7TKN-B-E4

1

0.14

0.4

-

0.6

-

J7TKN-B-E6

1

0.14

0.6

-

0.9

-

0.8

-

1.2

-

hand- and auto reset

J7TKN-B-E9

1

0.14

J7TKN-B-1E2

1

0.14

1.2

-

1.8

-

J7TKN-B-1E8

1

0.14

1.8

-

2.7

-

J7TKN-B-2E7

1

0.14
0.14

2.7

-

4

J7TKN-B-4

1

4

-

6

7

-

10.5

J7TKN-B-6

1

0.14

6

-

9

10.5

-

15.5

J7TKN-B-9

1

0.14

8

-

11

14

-

19

J7TKN-B-11

1

0.14

10

-

14

18

-

24

J7TKN-B-14

1

0.14

13

-

18

23

-

31

J7TKN-B-18

1

0.14

17

-

24

30

-

41

J7TKN-B-24

1

0.14

23

-

32

40

-

55

J7TKN-B-32

1

0.14

48

-

73

J7TKN-C-42

1

0.30

For contactors J7KN-24... to J7KN-40...
28

H-58

-

42

Thermal Overload Relay J7TKN

Setting Range

Type

(A)

D.O.L.

(A)

Star Delta

Pack

Weight

pcs.

kg/pc.

For contactors J7KN-50...-J7KN-74...
40

-

52

70

-

90

J7TKN-D-52

1

0.40

52

-

65

90

-

112

J7TKN-D-65

1

0.40

60

-

74

104

-

128

J7TKN-D-74

1

0.40

Thermal Overload relays for separate mounting
Setting Range

Type

(A)

D.O.L.

(A)

Star Delta

Pack

Weight

pcs.

kg/pc.

For contactors J7KN-85... to J7KN-150...
60

-

90

104

-

156

J7TKN-E-90

1

0.90

80

-

120

140

-

207

J7TKN-E-120

1

0.90

hand reset
For contactors J7KN-175... to J7KN-200...
100

-

150

175

-

260

J7TKN-F-150

1

1.5

140

-

220

240

-

380

J7TKN-F-210

1

1.5

busbar sets
see accessories

hand reset

Type
for overload relays

for contactors

Pack

Weight

pcs.

kg/pc.

Busbar Sets
J7TKN-F-175

J7KN-150, J7KN-175

J74TK-SU-175

1

0.6

J7TKN-F-210

J7KN-200

J74TK-SU-200

1

0.7

Type

Pack

Weight

pcs.

kg/pc.

1

0.035

busbars must be installed by users

Cable Cross-section to clamp (mm²)
for overload relay

solid or stranded

flex. with multicore
cable end

flexible

Sets for single mounting
J7TKN-B

0.75 -

6

0.75 -

4

0.5

-

4

J74TK-SM

Thermal Overload Relay

J7TKN

H-59

LVSG

Accessories

Specifications
■ Engineering data and Characteristics
Thermal Overload Relays, tripping times for selection to motors of protection degree EEx e
Relays With Standard Tripping Characteristic
Setting Range

Tripping time depending on the multiple of the
current setting from cold condition (tolerance
±20% of the tripping time)
I /I
A

A

I /I

N

A

3

A

N

4

A

N

I /I
A

6

s

s

N

I /I

I /I

7,2

8

A

N

N

Typical tripping
curve for overload
relay J7TKN-A

s

0,12

- 0,18

18,5

10,4

7,2

5,5

4,3

3,6

0,18

- 0,27

16,7

9,8

6,5

5

4,1

3,5

0,27

- 0,4

19,4

12,1

8,2

5,9

4,9

4,2

0,4

- 0,6

18,7

11,2

8

6

4,9

4,1

0,6

- 0,9

19,7

11,6

8,1

6,1

4,9

4,2

0,8

- 1,2

22,9

13,6

10

7,3

6

5,2

1,2

- 1,8

22,2

13,2

9,2

7,6

5,8

5,3

1,8

- 2,7

23

13,7

9,3

7,6

5,7

5,1

2,7

- 4

24

14,4

9,9

7,8

5,9

5,1

4

- 6

24,7

13,8

9,9

7,3

5,6

4,8

6

- 9

22

13,4

8

5,7

4,1

3,5

8

- 11

17,4

9,2

5,9

4,1

2,9

2,3

Labels of tripping curves for each setting range, sized 148x105mm
(self-adhesive) are available on request.

10

- 14

26,4

12,9

7,6

5,2

3,5

2,8

Specify type and setting range.

13

- 18

14,7

7,7

4,8

3,2

2,3

1,7

17

- 23

16,2

8,4

5

3,6

2,4

1,8

22

- 30

16,8

8,5

5

3,6

2,3

1,9

s

s

8

5,5

s

s

s

28

25,2

- 42

s
13,3

s

s

s
4

s

40

- 52

18,3

9,2

5,6

3,9

2,8

52

- 65

17,8

8,7

5,2

3,4

2,5

1,9

60

- 74

19,5

13,5

11

10

9,5

8,5

s

s

13,5

11

10

9,5

8,5

11

10

9

8,5

8

s

s

s

60

- 90

19,5

80

- 120

18

s

s

s

3,1

J7TKN-D-...

J7TKN-E-...

s

s

A

J7TKN-A-...

J7TKN-C-42

s

I /I
5

All tripping times of overload relays J7TKN-A are shorter than the
minimum values of the tE time for motors of protection degree EEx e
acc. to EN 50019 and therefore are suitable for all motors of protection degree EEx e. For these overload relays the selection on basis
of tripping curves is thereby not necessary.

s

s

2,2

s

J7TKN-F-...

s

s

s

100

- 150

34

26

24

20,5

19

18

140

- 210

30

24

21

18,5

17

16

When selecting a standard overload, refer to the tripping curve.
Determine the values of the starting current ratio IA/IN and the time tE
which is marked on the label of the motor. The overload must trip
within the tE time, which means that the tripping curve from cold condition must be (20% due to tolerance) below the coordination point IA/
IN and the time tE.
IA= Starting current of motor
IN = Rated current of motor
tE = tE-time of motor

H-60

Thermal Overload Relay J7TKN

Minimum values of
tE time (motor)
acc. to EN50019

ratio IA/IN

Fuses for J7TKN-A; J7TKN-B; J7TKN-C; J7TKN-D; J7TKN-E; J7TKN-F
Type

Setting Range

Max. Fuse Size According to Coordination-type Fuse UL
"2"*1

DOL

Star Delta
A

A
J7TKN-A
J7TKN-B

"1"*1

quick

slow,
gL(gG)

A

A
*2

0.5

*2

slow,
gL(gG)

aM

A

A

A

0.12

-

0.18

-

0.5

25

-

15

0.18

-

0.27

-

1.0*2

1.0*2

25

-

15

0.27

-

0.4

-

2

2

25

-

15

0.4

-

0.6

-

2

2

25

-

15

0.6

-

0.9

-

4

4

25

-

15

0.8

-

1.2

-

4

4

25

2

15

1.2

-

1.8

-

6

6

25

2

15

1.8

-

2.7

-

10

10

25

4

15

2.7

-

4

-

16

10

25

4

15

4

-

6

20

16

25

6

15

6

-

9

10.5

-

15.5

35

25

35

10

25

8

-

11

14

-

19

35

25

35

16

30

10

-

14

18

-

24

50

35

63

16

40

13

-

18

23

-

31

50

35

63

20

50

17
(22)23

- (23)24
- (30)32

7

30
(38)40

-

10.5

- (40)41

63

50

63

25

60

- (52)55

80

63

80

35

70

73

100

80

150

50

110

J7TKN-C

28

-

42

48

-

J7TKN-D

40

-

52

70

-

90

160

100

150

63

200

52

-

65

90

-

112

160

125

150

80

250

60

-

74

104

-

128

160

125

150

80

250

J7TKN-E
J7TKN-F

60

-

90

104

-

156

80

-

120

140

-

207

For short circuit protecting overload relays with
current transformer use fuse according to the
7contactor of the combination.

all ranges

300
-

Thermal Overload Relay

LVSG

*1) Coordination-type according to IEC 947-4-1:
„2“: Light contact welding accepted. Thermal overload relay must not be damaged.
„1“: Welding of contactor and damage of the thermal overload relay allowed.
*2) Miniature fuse

J7TKN

H-61

Tripping Characteristics for J7TKN-A, J7TKN-B, J7TKN-C, J7TKN-D
Detailed tripping times for each range see table page 60
with three-phase load

with two-pole load

Tripping time
min. s

Tripping time
min. s
Average value of
typical tolerance
curves from cold
condition

Typical tolerance
curve from cold
condition
Proceeding from
service conditions
the times decrease
to 70-80% of the
characteristic values

Proceeding from
service conditions
the times decrease
to 20-30% of the
characteristic values

K = Imax/Ie
Imax = max. phase current
Ie = max. scale value

F.L.C. multiplication factor

K

Tripping Characteristics for J7TKN-E
Detailed tripping times for each range see table page 60
with three-phase load

with two-pole load

Tripping time
min. s

Tripping time
min. s
Average value of
typical tolerance
curves from cold
condition

Typical tolerance
curve from cold
condition
Proceeding from
service conditions
the times decrease
to 70-80% of the
characteristic values

Proceeding from
service conditions
the times decrease
to 20-30% of the
characteristic values

K = Imax/Ie
Imax = max. phase current
Ie = max. scale value

F.L.C. multiplication factor

H-62

Thermal Overload Relay J7TKN

K

Tripping Characteristics for J7TKN-F
Detailed tripping times for each range see table page 60
with three-phase load

with two-pole load

Tripping time
min. s

Tripping time
min. s
Average value of
typical tolerance
curves from cold
condition

Typical tolerance
curve from cold
condition
Proceeding from
service conditions
the times decrease
to 70-80% of the
characteristic values

Proceeding from
service conditions
the times decrease
to 20-30% of the
characteristic values

K = Imax/Ie
Imax = max. phase current
Ie = max. scale value

F.L.C. multiplication factor

K

Position of Terminals
J7TKN-B

J7TKN-C; J7TKN-D
LVSG

J7TKN-A

Thermal Overload Relay

J7TKN

H-63

Thermal Overload Relays
Data according to IEC 947-4-1, IEC 947-5-1, VDE 0660, EN 60947-4-1, EN 60947-5-1
Type
Rated insulation voltage Ui*1

V~

J7TKN-A

J7TKN-B

J7TKN-C

J7TKN-D

J7TKN-E

J7TKN-F

690

690

690

690

750

690

Permissible ambient temperature
operation

open

storage

°C

-25 to +60

°C

-50 to +70
10A

10A

10A

10A

20

20

mm² 0.75-6 +
0.75-2.5*2

0.75-6

0,75-10

4-35*2

*3

*4

flexible

mm² 0.75-4 +
0.5-2.5*2

1-4

0,75-6

6-25*2

flexible with multicore cable end

mm² 0.5-2.5 +
0.5-1.5

0.75-4

0.75-6

4-25

2

2

1

Trip class according to IEC 947-4-1
Cable cross-section
main connector

solid or stranded

Cables per clamp

number

1+1

solid

mm²

0.75-2.5*2

flexible

mm²

0.5-2.5*2

flexible with multicore cable end

mm²

0.5-1.5

auxiliary connector

Cables per clamp

number

2

Auxiliary contacts
Rated insulation voltage Ui*1
same potential

V~

690

690

690

690

different potential

V~

440

440

250

440

24V

A

5

3

4*5

5

230V

A

3

2

2.5

3

400V

A

2

1

1.5

2

690V

A

0.6

0.5

0.6

0.6

Utilization category AC15
Rated operational current Ie

Utilization category DC13
Rated operational current Ie

24V

A

1.2

1

1.2

1.2

110V

A

0.15

0.15

0.15

0.15

220V

A

0.1

0.1

0.1

0.1

gL (gG)

A

6

4

6

6

A

to 23

all

Short circuit protection (without welding 1kA)
highest fuse rating
Setting range

28-42

52-65

all

-

Power loss per current path (max.)
minimum setting value

W

1.1

1.1

1.3

2.9

1.1

-

maximum setting value

W

2.3

2.3

3.3

4.5

2.5

-

*1) Suitable for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry: Uimp = 4kV (at 440V), 6kV (at 690V).
Data for other conditions on request.
*2) Maximum cable cross-section with prepared conductor
*3) Without terminals, suitable for bushing one connector 70mm² (stranded) per phase
*4) Busbar sets see accessories page 59
*5) Switching capacity of the start contact: AC15 300VA, max. 1.5A, DC13 (max. 220V) 30W, max. 1.5A

H-64

Thermal Overload Relay J7TKN

Data according to CULUS
Type

J7TKN-A

J7TKN-B

J7TKN-C

J7TKN-D

J7TKN-E

Rated insulation voltage

V~

600

600

600

600

600

Rated current

A

23

32

42

74

85

Auxiliary contacts
Rated voltage
same potential

V AC 600

600

600

600

600

different potential

V~

150

150

150

150

150

Switching capacity AC

VA

500

500

600

600

600

of aux. contacts

A

4

2

4

4

4

Temperature Compensation
In case of higher ambient temperature use the following formula:
(Ambient temperature - 20) x 0.125 = correction factor in % of the
full load motor current
Example:
Ambient temperature 70°C, full load motor current 7A
(70 - 20) x 0.125 = 6.25%

LVSG

Setting value: 7A + 6,25% = 7.44A

Thermal Overload Relay

J7TKN

H-65

■ Dimensions
J7KNA-09 + J7TKN-A
J7KNA-12

J7KN-10 + J7TKN-B
J7KN-14
J7KN-18
J7KN-22

J7KN-10 + J7TKN-A
J7KN-14
J7KN-18
J7KN-22

J7KN-24 + J7TKN-B
J7KN-32
J7KN-40

H-66

Thermal Overload Relay J7TKN

J7KN-50 + J7TKN-D
J7KN-62
J7KN-74

J7KN-85 + J7TKN-E
J7KN-110

J7KN-150 + J7TKN-F
J7KN-175

LVSG

J7KN-24 + J7TKN-C
J7KN-32
J7KN-40

J7KN-200 + J7TKN-210

Thermal Overload Relay

J7TKN

H-67

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

Cat. No. J509-E2-02

H-68

In the interest of product improvement, specifications are subject to change without notice.

Thermal Overload Relay J7TKN

Motor Protection Circuit Breaker (MPCB)

J7MN

)

MPCB system (motor protection CLASS 10)
• Rotary and switch types
• Rated operational current = 12 A, 25 A, 50 A and 100 A
• Switching capacity up to 12.5 A = 100 kA/400 V
• Fixed short-circuit release = 13 x Iu
• Overload release adjustable 0.7 - 1 x Iu
• Single phasing sensivity

Auxiliary contact modules
• ON/OFF indication for MPCB front mounting and side mounting
• Trip indication for MPCB side mounting

Accessories
• Undervoltage release
• Shunt release
• Three phase busbar system up to 5 MPCB
• Moulded plastic enclosures (IP55)
• Moulded plastic front plates (IP55)
• Door coupling rotary mechanisms (black and red/yellow)

Standard

Guide No (US,C)

UL

see page 95

LVSG

Approved Standards
ICE 947-5-1
VDE 0660
EN 60947-5-1

Motor Protection Circuit Breaker (MPCB)

J7MN

H-69

Ordering Information
■ Model Number Legend
1. Motor Protection Circuit Breaker (MPCB)

3. Accessories for MPCB

J7MN-##-###
1
2
3

J74MN-#-##
1
2 3

1)
2)

1)
2)

Motor Protection Circuit Breaker (MPCB)
Type
12:
Switch type (0.16 - 12 A)
25:
Rotary type (0.16 - 25 A)
50:
Rotary type (25 - 40 A)
100:
Rotary type (45 - 100 A)
3)
Setting range (examples)
E16: 0.11 - 0.16 A
E2:
0.14 - 0.2 A
16:
10 - 16 A
...
2. Aux. Contacts for MPCB

J73MN-###
1
2 3
1)
2)
3)

J74MN-## ##
1
2 3
1)
2)

3)

Aux. Contact for MPCB
11:
1 NO 1 NC
S:
side mounting
F:
front mounting

J73MN-#-## #
1
2 3 4
1)
2)
3)
4)

3)

Aux. Contact for MPCB
T:
Trip indicating contact
11:
1 NO 1 NC
S:
side mounting

Accessories for MPCB
S:
Shunt release
U:
Under voltage release
N1:
230 V 50 Hz / 240 V 60 Hz
N2:
210 - 230 V 50/60 Hz

Accessories for MPCB
PF:
Enclosure IP55
P:
Module plastic front plate
PH:
Holder for front plate
12:
Switch type
25:
Rotary type

J74MN-##-##
1
2 3
1)
2)
3)

Accessories for MPCB
DC:
Door coupling rotary mechanism
B:
black / gray
RY:
red / yellow

J74MN-##-#/#
1
2 3
1)
2)
3)

Accessories for MPCB
L3:
3-phase busbar system (45 mm modular spacing)
DS:
Shroud for unused terminal
1/2:
for 2 circuit breakers
1/3:
for 3 circuit breakers
1/4:
for 4 circuit breakers
1/5:
for 5 circuit breakers

J74MN-## ##
1
2 3
1)
2)
3)

Accessories for MPCB
TC:
Line side terminal
12:
for switch type
25:
for rotary type

J74MN-## ###
1
2 3
1)
2)
3)

H-70

Motor Protection Circuit Breaker (MPCB) J7MN

Accessories for MPCB
TB:
Terminal block for UL/cUL type E
25:
for rotary type up to 25A
100:
for rotary type up to 100A

■ System overview
Motor Protection Circuit Breaker (MPCB)
Current setting range

Pack

Weight
approx.

pcs.

kg/pcs.

J7MN-12-E16

1

0.21

J7MN-12-E2

1

0.21

100

J7MN-12-E25

1

0.21

4.2

100

J7MN-12-E32

1

0.21

0.28 – 0.4

5.2

100

J7MN-12-E4

1

0.21

0.12

0.35 – 0.5

6.5

100

J7MN-12-E5

1

0.21

0.63

0.18

0.45 – 0.63

8.2

100

J7MN-12-E63

1

0.21

0.8

-

0.55 – 0.8

10

100

J7MN-12-E8

1

0.21

1

0.25

0.7 –

1

13

100

J7MN-12-1

1

0.21

1.25

0.37

0.9 –

1.25

16

100

J7MN-12-1E25

1

0.21

1.6

0.55

1.1 –

1.6

21

100

J7MN-12-1E6

1

0.21

2

0.75

1.4 –

2

26

100

J7MN-12-2

1

0.21

2.5

-

1.8 –

2.5

33

100

J7MN-12-2E5

1

0.21

3.2

1.1

2.2 –

3.2

42

100

J7MN-12-3E2

1

0.21

4

1.5

2.8 –

4

52

100

J7MN-12-4

1

0.21

5

-

3.5 –

5

65

100

J7MN-12-5

1

0.21

6.3

2.2

4.5 –

6.3

82

100

J7MN-12-6E3

1

0.21

8

3

5.5 –

8

104

50

J7MN-12-8

1

0.21

10

4

7–

10

130

50

J7MN-12-10

1

0.21

12

5.5

9–

12

156

50

J7MN-12-12

1

0.21

Suitable
for
motors*1
3~400V
kW

Instantaneous
short-circuit
release
A

Short-circuit
breaking
capacity
at 3~400V
kA

Type

Thermal
overload
release
A

0.16

-

0.11 – 0.16

2.1

100

0.2

-

0.14 – 0.2

2.6

100

0.25

0.06

0.18 – 0.25

3.3

0.32

0.09

0.22 – 0.32

0.4

-

0.5

Rated
current
In
A

Circuit-Breakers J7MN-12

LVSG

*1) Recommended values for standard motors
*2) max. motor current 95A

Motor Protection Circuit Breaker (MPCB)

J7MN

H-71

Rated
current

Current setting range

Suitable
for
motors*1
3~400V
kW

Instantaneous
short-circuit
release
A

Short-circuit
breaking
capacity
at 3~400V
kA

Type

Thermal
overload
release
A

Pack

Weight
approx.

pcs.

kg/pcs.

0.16

-

0.11 – 0.16

2.1

100

0.2

-

0.14 – 0.2

2.6

100

J7MN-25-E16

1

0.32

J7MN-25-E2

1

0.25

0.06

0.18 – 0.25

3.3

0.32

100

J7MN-25-E25

1

0.32

0.09

0.22 – 0.32

0.32

4.2

100

J7MN-25-E32

1

0.4

-

0.32

0.28 – 0.4

5.2

100

J7MN-25-E4

1

0.5

0.32

0.12

0.35 – 0.5

6.5

100

J7MN-25-E5

1

0.32

0.63

0.18

0.45 – 0.63

8.2

100

J7MN-25-E63

1

0.32

0.8

-

0.55 – 0.8

10

100

J7MN-25-E8

1

0.32

1

0.25

0.7 –

1

13

100

J7MN-25-1

1

0.32

1.25

0.37

0.9 –

1.25

16

100

J7MN-25-1E25

1

0.32

1.6

0.55

1.1 –

1.6

21

100

J7MN-25-1E6

1

0.32

2

0.75

1.4 –

2

26

100

J7MN-25-2

1

0.32

2.5

-

1.8 –

2.5

33

100

J7MN-25-2E5

1

0.32

3.2

1.1

2.2 –

3.2

42

100

J7MN-25-3E2

1

0.32

4

1.5

2.8 –

4

52

100

J7MN-25-4

1

0.32

5

-

3.5 –

5

65

100

J7MN-25-5

1

0.32

6.3

2.2

4.5 –

6.3

82

100

J7MN-25-6E3

1

0.32

8

3

5.5 –

8

104

100

J7MN-25-8

1

0.32

10

4

7–

10

130

100

J7MN-25-10

1

0.32

12.5

5.5

9–

12.5

163

100

J7MN-25-12E5

1

0.32

16

7.5

11 –

16

208

50

J7MN-25-16

1

0.32

20

-

14 –

20

260

50

J7MN-25-20

1

0.32

22

-

17 –

22

286

50

J7MN-25-22

1

0.32

25

11

20 –

25

325

50

J7MN-25-25

1

0.32

25

11

18 –

25

325

50

J7MN-50-25

1

0.96

32

15

22 –

32

416

50

J7MN-50-32

1

0.96

40

18.5

28 –

40

520

50

J7MN-50-40

1

0.96

45

–

36 –

45

585

50

J7MN-50-45

1

0.96

50

22

40 –

50

650

50

J7MN-50-50

1

0.96

63

30

45 –

63

819

50

J7MN-100-63

1

2.1

75

37

57 –

75

975

50

J7MN-100-75

1

2.1

90

–

70 –

90

1170

50

J7MN-100-90

1

2.1

100

45

80 –

100*2

1235

50

J7MN-100-100

1

2.1

In
A

Circuit-Breakers J7MN-25

Circuit-Breakers J7MN-50

Circuit-Breakers J7MN-100

*1) Recommended values for standard motors
*2) max. motor current 95A

H-72

Motor Protection Circuit Breaker (MPCB) J7MN

Accessories
Description

Version

for circuit
breaker

pcs.

Weight
approx.
kg/pcs.

J73MN-11F

10

0.02

J73MN-11S

10

0.03

J73MN-T-11S

1

0.07

Type

Pack

Transverse auxiliary contact block
Contact block

1NO + 1NC

all

Auxiliary contact block for left hand side mounting (max 1pc. per circuit breaker)
Contact block

1NO + 1NC 9 mm

all

Signalling switch for left hand side mounting (max 1pc. per circuit breaker)
Signalling switch

1NO + 1NC each
Individual tripped and
short-circuit signalling

J7MN-25
J7MN-50

Auxiliary releases for right hand side mounting (max 1pc. per circuit breaker)
AC 60 Hz
240 V

all

J74MN-U-N1

1

0.12

50/60 Hz
Shunt release
Trips the circuit-breaker 100% ON
when the release coil
210-240 V
energized.

50/60 Hz, DC
5 sec ON
190-330 V

all

J74MN-S-N2

1

0.11

for circuit
breaker

Type

Pack
pcs.

Weight
approx.
kg/pcs.

LVSG

Undervoltage release AC 50 Hz
Trips the circuit-breaker 230 V
when the voltage is
interrupted. Prevents the
motor from being
restarted accidentally
when the voltage is
restored, suitable for
EMERGENCY STOP
acc. to VDE 0113

Enclosures and Front Plates
Description

Version

Front Plates
for actuation of circuit-breakers J7MN-12
in any enclosure
protection degree IP55

J74MN-P12

1

0.08

Moulded plastic front for actuation of circuit-breakers J7MN-25
J7MN-50
plate with rotary operat- in any enclosure
protection degree IP55
ing mechanism
lockable

J74MN-P25

1

0.08

J7MN-25

J74MN-PH

1

0.12

J7MN-12

J74MN-PF12

1

0.27

Moulded plastic front
plate with actuator diaphragm and holder for
circuit breaker

Holder for front plate
J74MN-P25

Holder is mounted on front
plate, circuit-breaker (with accessories) is snapped on

Moulded plastic
enclose with actuator
diaphragm
knockouts for J7MN-25
sealable

protection degree IP55
with N- and PE- terminal
(+ aux. contact + release)

Enclosures

Motor Protection Circuit Breaker (MPCB)

J7MN

H-73

Description

Version

Moulded plastic
enclose with rotary
operating mechanism
knockouts for J7MN-25
lockable

protection degree IP55
with N- and PE- terminal
(+ aux. contact + release)

for circuit
breaker

J7MN-25

Type

J74MN-PF25

Pack
pcs.

Weight
approx.
kg/pcs.

1

0.30

Door-coupling mechanisms
The door-coupling rotary operating mechanisms consist of a knob, a coupling driver and a extension shaft
(5 mm x 5 mm). The door-coupling rotary operating mechanisms are designed for degree of protection IP 65.
The door locking device prevents accidental opening of the cubicle door in the ON position of the circuit-breaker.
The OFF position can be locked with up to 3 padlocks.
extension shaft 330 mm
with supporting bracket

J7MN-25 to
J7MN-50

J74MN-DC-B

1

0.3

extension shaft 330 mm
Emergency-Stop
Door-coupling rotary with supporting bracket
mechanism red/yellow

J7MN-25 to
J7MN-50

J74MN-DC-RY

1

0.3

Description

for circuit
breaker

Type

Pack
pcs.

Weight
approx.
kg/pcs.

1
1
1
1

0.03
0.05
0.07
0.10

Door-coupling rotary
mechanism black

Busbars
Version

Insulated 3-phase busbar systems
For feeding several modular circuit-breakers on standard mounting rails, insulated, shock-protected.
Rated operational voltage max. 690 V
for 2 circuit-breakers
3-phase busbars
modular spacing 45 mm for 3 circuit-breakers
for 4 circuit-breakers
for 5 circuit-breakers

J7MN-12
J7MN-25

J74MN-L3-1/2
J74MN-L3-1/3
J74MN-L3-1/4
J74MN-L3-1/5

For connecting the 3-phase busbars from circuit-breakers different sizes. Clamping together J7MN-12 and J7MN-25
circuit-breakers is not possible due to the different modular spacings and the different heights of the terminals.
Line side terminal
3-pole, connection
from top

Conductor cross-section
solid or stranded 6- 25 mm²
with ferrule 4-16 mm²

J7MN-12
J7MN-25

J74MN-TC12
J74MN-TC25

1
1

0.04
0.04

Shroud

for unused terminals

J7MN-12
J7MN-25

J74MN-DS

20

-

for circuit
breaker

Type

Pack
pcs.

Weight
approx.
kg/pcs.

J74MN-HU

10

0.05

J74MN-VD-12
J74MN-VD-25

10
10

-

J74MN-TB25
J74MN-TB100

1
1

0.12
0.15

Mounting Parts for Fuseless Load Feeders
Description

Version

DIN-rail adapters
Adapter
for mechanical fixing of
circuit-breaker and
contactor

35 mm-DIN-rail
(DIN EN50022)
or screw mounting

J7MN...

Link modules
for electrical connection between circuit-breaker and contactor
Link module

up to 20 A
up to 32 A

J7MN...

Terminal block
with increased creepage distances and clearances acc. to cULus Type „E“
Terminal block

H-74

up to 600 V acc. to UL 489
J7MN-25
not for transverse aux. contact J7MN-100
block

Motor Protection Circuit Breaker (MPCB) J7MN

Specifications
■ Engineering data and Characteristics
Components for Fuseless Load Feeders, DIN-Rail Mounting
Motor
3~400V
kW

Setting range
A

Circuit-breaker
page 72
Type

Contactor
220-230V 50Hz
Type

Link
module
Type

DIN-rail
adapter
Type

-

0.11–

0.16

J7MN-25-E16

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

-

0.14–

0.2

J7MN-25-E2

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

0.06

0.18–

0.25

J7MN-25-E25

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

0.09

0.22–

0.32

J7MN-25-E32

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

-

0.28–

0.4

J7MN-25-E4

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

0.12

0.35–

0.5

J7MN-25-E5

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

0.18

0.45–

0.63

J7MN-25-E63

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

-

0.55–

0.8

J7MN-25-E8

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

0.25

0.7–

1

J7MN-25-1

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

0.37

0.9–

1.25

J7MN-25-1E25

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

0.55

1.1–

1.6

J7MN-25-1E6

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

0.75

1.4–

2

J7MN-25-2

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

-

1.8–

2.5

J7MN-25-2E5

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

1.1

2.2–

3.2

J7MN-25-3E2

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

1.5

2.8–

4

J7MN-25-4

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

-

3.5–

5

J7MN-25-5

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

2.2

4.5–

6.3

J7MN-25-6E3

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

3

5.5–

8

J7MN-25-8

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

4

7–

10

J7MN-25-10

J7KN-10-10 230

J74MN-VD-12

J74MN-HU

5.5

9–

12.5

J7MN-25-12E5

J7KN-14-10 230

J74MN-VD-12

J74MN-HU

7.5

11–

16

J7MN-25-16

J7KN-18-10 230

J74MN-VD-12

J74MN-HU

-

14–

20

J7MN-25-20

J7KN-22-10 230

J74MN-VD-25

J74MN-HU

-

17–

22

J7MN-25-22

J7KN-22-10 230

J74MN-VD-25

J74MN-HU

11

20–

25

J7MN-25-25

J7KN-22-10 230

J74MN-VD-25

J74MN-HU

Motor Protection Circuit Breaker (MPCB)

J7MN

LVSG

Type of coordination „1“ 3 x 415 V 10 kA (other conditions on request)

H-75

Technical Data according to IEC/EN 60947-1, 60947-2, 60947-4-1 and VDE 0660
If the short-circuit current exceeds the rated short-circuit breaking
capacity of the circuit-breaker specified in the tables at the
installation point, a back-up fuse is to be used.

This table shows the rated ultimate short-circuit breaking capacity Icu
and the rated service short-circuit breaking capacity Ics of the J7MN
circuit-breakers with different operational voltages as a function of
the rated current In of the circuit-breakers.

The maximum rated current for the back-up fuse is specified in the
tables. These fuses are only suitable for the short-circuit-currents as
indicated on the fuses.

The circuit-breakers can be fed at the top or bottom supply terminals
without any reduction of the rated data.

Circuitbreaker

Rated
current In

up to AC 240V*1)

Type

A

Icu
kA

J7MN-12 0.16 to 0.8 100

up to AC 400V*1)
up to AC 415V*2)

kA

Icu
max.
fuse
(gL/gG)
A
kA

100

--

100

Ics

up to AC 440V*1)
up to AC 460V*2)

kA

Icu
max.
fuse
(gL/gG)
A
kA

100

--

100

Ics

up to AC 500V*1)
up to AC 525V*2)

kA

Icu
max.
fuse
(gL/gG)
A
kA

100

--

100

Ics

up to AC 690V*1)

kA

Icu
max.
fuse
(gL/gG)
A
kA

kA

max.
fuse
(gL/gG)
A

100

--

100

100

--

Ics

Ics

1

100

100

--

100

100

--

100

100

--

100

100

--

100

100

--

1.25

100

100

--

100

100

--

100

100

--

100

100

--

2

2

20

1.6

100

100

--

100

100

--

100

100

--

100

100

--

2

2

20

2

100

100

--

100

100

--

100

100

--

10

10

35

2

2

35

2.5

100

100

--

100

100

--

100

100

--

10

10

35

2

2

35

3.2

100

100

--

100

100

--

10

10

40

3

3

40

2

2

40

4

100

100

--

100

100

--

10

10

40

3

3

40

2

2

40

5

100

100

--

100

100

--

10

10

50

3

3

50

2

2

50

6.3

100

100

--

100

100

--

10

10

50

3

3

50

2

2

50

8

100

100

--

50

12.5

80*3)

10

10

63

3

3

63

2

2

63

10

100

100

--

50

12.5

80*3)

10

10

63

3

3

63

2

2

63

12

100

100

--

50

12.5

80*3)

10

10

80

3

3

80

2

2

80

J7MN-25 0.16 to 1.25 100

100

--

100

100

--

100

100

--

100

100

--

100

100

--

1.6

100

100

--

100

100

--

100

100

--

100

100

--

100

100

--

2

100

100

--

100

100

--

100

100

--

100

100

--

8

8

25

2.5

100

100

--

100

100

--

100

100

--

100

100

--

8

8

25

3.2

100

100

--

100

100

--

100

100

--

100

100

--

8

8

32

4

100

100

--

100

100

--

100

100

--

100

100

--

6

3

32

5

100

100

--

100

100

--

100

100

--

100

100

--

6

3

32

6.3

100

100

--

100

100

--

100

100

--

100

100

--

6

3

50

8

100

100

--

100

100

--

50

25

63*3

42

21

63

6

3

50

10

100

100

--

100

100

--

50

25

80*3

42

21

63

6

3

50

12.5

100

100

--

100

100

--

50

25

80*3

42

21

80

6

3

63

16

100

100

--

50

25

100*3)

20

10

80

10

5

80

4

2

63

20

100

100

--

50

25

125*3)

20

10

80

10

5

80

4

2

63

22

100

100

--

50

25

125*3)

20

10

100

10

5

80

4

2

63

25

100

100

--

50

25

125*3)

20

10

100

10

5

80

4

2

63

J7MN-50 25

100

100

--

50

25

125*3)

30

15

100

12

6

80

5

3

63

32

100

100

--

50

25

125*3)

30

15

125

10

5

100

4

2

63

40

100

100

--

50

25

160*3)

30

15

125

10

5

100

4

2

63

45

100

100

--

50

25

160*3)

30

15

125

10

5

100

4

2

63

50

100

100

--

50

25

160*3)

30

15

125

10

5

100

4

2

80

J7MN-100 63

100

100

--

50

25

160*3)

40

20

160

12

6

125

6

3

80

75

100

100

--

50

25

160*3)

40

20

160

8

4

125

5

3

100

90

100

100

--

50

25

160*3)

40

20

160

8

4

125

5

3

125

100

100

100

--

50

25

160*3)

40

20

160

8

4

125

5

3

125

*1) 10% overvoltage
*2) 5% overvoltage
*3) Back-up fuse required if short-circuit current at installation point > 50 kA
-- No back-up fuse required.

H-76

Motor Protection Circuit Breaker (MPCB) J7MN

Technical Data according to IEC/EN 60947-1, 60947-2, 60947-4-1 and VDE 0660
Main Circuit
Type

J7MN-12

J7MN-25

J7MN-50

J7MN-100

Number of poles

3

3

3

3

12

25

50

100

-

A

Max. rated current Inmax (=max. rated operational current Ie)
Permissible ambient temperature
Storage/transport

°C

-50 to +80

Operation

°C

-20 to +70*1)

+60 °C

%

100

+70 °C

%

87

Permissible rated current at temperature inside enclosure of: +60 °C

%

100

+70 °C

%

87

Rated operational voltage Ue

V

690*2)

Rated frequency

Hz

50/60

Rated insulation voltage Ui

V

690

Rated impulse withstand voltage Uimp

kV

6

Permissible rated current at temperature inside cubicle of:
Circuit-breaker inside enclosure

Utilization category
IEC 60 947-2 (circuit-breaker)

A

IEC 60 947-4-1 (motor starter)
Class

AC-3
acc. to IEC 60 947-4-1

10

1 conducting path DC 150 V

kA

10

2 conducting paths in series DC 300 V

kA

10

3 conducting paths in series DC 450 V
Power loss Pv per circuit-breaker
dependent on rated current In
(upper setting range)
R per conducting path = P/(I² × 3)

kA

10

In -> to 1.25 A

W

5

-

-

In -> 1.6 to 6.3 A

W

6

-

-

-

In -> 8 to 12 A

W

7

-

-

-

In -> 1 to 6.3 A

W

-

6

-

-

In -> 8 to 16 A

W

-

7

-

-

In -> 20 to 25 A

W

-

8

-

-

In -> to 25 A

W

-

-

12

-

In -> 32 A

W

-

-

15

-

In -> 40 to 50 A

W

-

-

20

-

In -> to 63 A

W

-

-

-

20

In -> 75 to 90 A

W

-

-

-

30

In -> to 100 A

W

-

-

-

38

Shock resistance

acc. to IEC 68 Part 2-27

g

25

25

25

25

Degree of protection

acc. to IEC 60 529

IP 20

IP 20

IP 20*3)

IP 20*3)

Shock hazard protection

acc. to DIN VDE 0106 Part 100

safe against finger touch

Temperature compensation

acc. to IEC 60 947-4-1

-20 to +60

Phase failure sensitivity

acc. to IEC 60 947-4-1

Explosion protection

acc. to EC Directive 94191 EC

yes*4)

Isolator characteristics

acc. to IEC 60 947-3

yes

Main and EM. STOP switch characteristics

acc. to IEC 60 204-1 (VDE 0113)

yes*5)

Safe isolation between main and auxiliary
circuits

acc. to DIN VDE 0106 Part 101

Mechanical endurance

°C

yes

up to 400 V + 10 %

yes

up to 415 V+ 5 %

yes

operating cycles

100 000

100 000

50 000

50 000

100 000

100 000

25 000

25 000

15

15

15

15

Electrical endurance
Max. operating frequency per hour (motor starts)
Permissible mounting position

LVSG

DC short-circuit breaking capacity (time constant t = 5 ms)

1/h

any. acc. to IEC 60 447 start command “I” right-hand side or top

*1) Over +60°C current reduction
*2) 500 V with moulded-plastic enclosure
*3) Terminal compartment IP00
*4) KEMA-test certification on request
*5) With appropriate accessories

Motor Protection Circuit Breaker (MPCB)

J7MN

H-77

Technical Data according to IEC/EN 60947-1, 60947-2, 60947-4-1 and VDE 0660
Conductor cross-sections for main Circuit
Type

J7MN-12

J7MN-25

J7MN-50

J7MN-100

Terminal type

Screw-type

Screw-type

Box terminal

Box terminal

Terminal screw
Tightening torque

Pozidriv size 2

Pozidriv size 2

Pozidriv size 2

Allen screw 4 mm

Nm

0.8 to 1.2

2 to 2.5

3 to 4.5

4 to 6

mm²

2 x (0.5 to 1.5)

2 x (1 to 2.5)

2 x (0.75 to 16)

2 x (2.5 to 16)

mm²

2 x (0.75 to 2.5)

2 x (2.5 to 6)

–

–

mm²

1 x (0.5 to 4)

Conductor cross-sections
solid

finely stranded with end ferrule

mm²

2 x (0.5 to 1.5)

2 x (1 to 2.5)

2 x (0.75 to 16)

2 x (2.5 to 35)

mm²

2 x (0.75 to 2.5)

2 x (2.5 to 6)

1 x (0.75 to 25)

1 x (2.5 to 50)

mm²

2 x (0.5 to 1.5)

2 x (1 to 2.5)

2 x (0.75 to 25)

2 x (10 to 50)

mm²

2 x (0.75 to 2.5)

2 x (2.5 to 6)

1 x (0.75 to 35)

1 x (10 to 70)

mm²
stranded

AWG-wires, solid or stranded
conductor bar (number x width x thick)

1 x (1 to 10)

mm²

1 x (0.5 to 4)

1 x (1 to 10)

AWG

2 x (18 to 14)

2 x (14 to 10)

2 x (18 to 3)

2 x (10 to 1/0)

AWG

–

–

1 x (18 to 2)

1 x (10 to 2/0)

mm

–

–

2 x (6 x 9 x 0.8)

2 x (6 x 9 x 0.8)

mm

–

–

–

18 x 10

mm²

–

–

–

up to 2 x 70

Technical Data according to IEC/EN 60947-1, 60947-2, 60947-4-1 and VDE 0660
Auxiliary switches
Switching capacity

Control voltage

Front transverse auxiliary switch with 1 NO + 1 NC
Rated operational voltage Ue

AC

Rated operational current Ie/AC-15
Rated operational current Ie/AC-12 Ith
Rated operational voltage Ue

DC L/R 200 ms

Rated operational current Ie/DC-13

V

24

230

A

2

0.5

A

2.5

2.5

V

24

48

60

A

1

0.3

0.15

Lateral auxiliary switch and signalling switch
Rated operational voltage Ue

AC

Rated operational current Ie/AC-15
Rated operational current Ie/AC-12 Ith
Rated operational voltage Ue

DC L/R 200 ms

Rated operational current Ie/DC-13
Undervoltage release

Power consumption
Response voltage

Shunt release

V

24

230

400

690

A

6

6

3

1

A

10

10

10

10

V

24

110

220

440

A

2

0.5

0.25

0.1

during pick-up

VA/W

20.2/13

uninterrupted duty

VA/W

7.2/2.4

trip

V

0.7 to 0.35 × Us

pick-up

V

0.85 to 1.1 × Us

Max. opening time

ms

20

Power consumption during pick-up

AC VA/W

20.2/13

DC W

13 to 80

Response voltage acc. to IEC 60 947-1, trip V

0.7 to 1.1 × Us

Max. opening time

ms

20

A

10

Short-circuit protection for auxiliary and control circuits
Fuse

gL/gG

Miniature circuit breaker C-characteristic

A

solid

mm²

finely stranded with ferrule

mm²

2 x (0.5 to 1.5) / 2 x (0.75 to 2.5)

stranded

mm²

2 x (0.5 to 1.5) / 2 x (0.75 to 2.5)

AWG-wires, solid or stranded

AWG

2 x (18 to 14)

*1) Prospective short-circuit current < 0.4 kA.

H-78

6*1)
Screw-type Pozidriv size 2

Conductor cross-sections for auxiliary and control circuits

Motor Protection Circuit Breaker (MPCB) J7MN

2 x (0.5 to 1.5) / 2 x (0.75 to 2.5)

Description
J7MN circuit-breakers are compact, current-limiting circuit-breakers
which are optimised for load feeders. The circuit-breakers are used
for switching and protecting three-phase induction motors of up to
18,5 kW at AC 400 V and for loads with rated currents of up to 40 A.

Construction

Short-circuit protection
The short-circuit releases of J7MN circuit-breakers disconnect the
faulty load feeder from the system in the event of a short circuit and
thus prevent any further damage.
Circuit-breakers with a short-circuit breaking capacity of 50 kA or
100 kA at a voltage of 400 V AC are practically short-circuit-proof at
this voltage, as higher short-circuit currents are not usually encountered at the installation point.

The circuit-breakers are available in three sizes:
J7MN-12 overall width 45 mm. Max. rated current 12 A. Suitable for
3-phase induction motors of up to 5.5 kW at voltages of 400 V AC.
J7MN-25 overall width 45 mm. Max. rated current 25 A. Suitable for
3-phase induction motors of up to 11 kW at voltages of 400 V AC.

Back-up fuses are only necessary if the short-circuit current at the
installation point exceeds the rated ultimate short-circuit breaking
capacity of the circuit-breakers.

J7MN-50 overall width 55 mm. Max. rated current 40 A. Suitable for
3-phase induction motors of up to 18,5 kW at voltages of 400 V AC.

Motor protection
The tripping characteristics of J7MN circuit-breakers are designed
mainly to protect three-phase induction motors. The circuit-breakers
are therefore also referred to as motor circuit-breakers. The current
of the motor to be protected is set with the aid of the scale.

Releases
Circuit-breakers J7MN are equipped with bimetallic-based, inversetime delayed overload releases and with instantaneous overcurrent
releases (electromagnetic short-circuit releases).

Circuit-breakers with thermal overload releases are normally
designed in accordance with release Class 10.

The overload releases can be set in accordance with the load current. The overcurrent releases are permanently set to a value 13
times the rated current and thus enable trouble-free start-up of
motors.

Line protection

The scale cover can be sealed to prevent unauthorized adjustments
to the set current.

Operating mechanisms
circuit-breakers J7MN-12 are actuated via a switch operating mechanism and circuit-breakers J7MN-25 and J7MN-50 via a rotary operating mechanism. If the circuit-breaker trips, the rotary operating
mechanism switches to the tripped position to indicate this. Before
the circuit-breaker is reclosed, the rotary operating mechanism must
be reset to the 0 position by hand, in order to prevent the former from
closing by mistake before the fault has been cleared.
In the case of circuit-breakers with rotary operating mechanisms,
there is an electrical signal via a signalling switch to indicate that the
circuit-breaker has tripped.

J7MN circuit-breakers for motor protection are also suitable for line
protection. In order to prevent premature tripping due to phase failure
sensitivity, the three conducting paths must always be uniformly
loaded. The conducting paths must be connected in series in the
case of single-phase loads.
The J7MN circuit-breakers meet the isolation conditions of
IEC 60 947-3 as well as the additional test conditions for circuitbreakers with isolation characteristics specified in IEC 60 947-2. Taking IEC 60 204-1 into consideration, they can thus be implemented
as main and EMERGENCY STOP switches.
Door-coupling rotary operating mechanism do not fulfil the isolation
characteristics specified in IEC 60 947-2. Door-coupling rotary operating mechanism according isolation characteristics specified in
IEC 60 947-2 on request.

LVSG

All operating mechanisms can be locked in the 0 position with a padlock (shackle diameter 3.5 to 4.5 mm).
The J7MN circuit-breakers fulfil the isolation characteristics specified
in IEC 60 947-2.

Operating conditions
Circuit-breakers J7MN are suitable for use in any climate. They are
designed for operation in enclosed rooms under normal conditions
(e. g. no dust, corrosive vapours or harmful gases). Suitable enclosures must be provided for installation in dusty or damp rooms.
Circuit-breakers J7MN can also be fed from below. The standards in
accordance with which the circuit-breakers are constructed, the permissible ambient temperatures, the maximum making and breaking
capacities, the tripping currents and other boundary conditions can
be found in the technical data and tripping characteristics.
Since the operational currents, starting currents and current peaks
vary as a result of the inrush current, even in the case of motors with
identical output ratings, the values specified for these output ratings
in the selection tables are intended as a guide only. The specific
rated and start-up data of the motor to be protected is always paramount to the choice of the most suitable circuit-breaker.
In order to prevent premature tripping due to phase failure sensitivity,
the circuit-breakers should always be connected in such a way that
current flows through all three main conducting paths.

Motor Protection Circuit Breaker (MPCB)

J7MN

H-79

Characteristics
The time/current characteristic, the current limiting characteristics
and the I²t characteristics were determined in accordance with
DIN VDE 0660 and IEC 60 947.

Opening Time

The tripping characteristic of the inverse-time delayed overload
releases (thermal overload releases or ’a’ releases) for DC and AC
with a frequency of 0 to 400 Hz also apply to the time/current characteristic.
The characteristics apply to the cold state. At operating temperature,
the tripping times of the thermal releases are reduced to approximately 25 %.
Under normal operating conditions, all three poles of the device must
be loaded. The three main conducting paths must be connected in
series in order to protect single-phase or DC loads.
With 3-pole loading, the maximum deviation in the tripping time for 3
times the setting current and upwards is ± 20 % and thus in accordance with DIN VDE 0165.
The tripping characteristics for the instantaneous, electromagnetic
overcurrent releases (short-circuit releases or ’n’ releases) are based
on the rated current In, which is also the maximum value of the setting range for circuit-breakers with adjustable overload releases. If
the current is set to a lower value, the tripping current of the ’n’
release is increased by a corresponding factor.

3-pole
load
Class 10
2-pole
load
Class 10

The characteristics of the electromagnetic overcurrent releases
apply to frequencies of 50/60 Hz. Appropriate correction factors must
be used for lower frequencies up to 16 2/3 Hz, for higher frequencies
up to 400 Hz and for DC.
The characteristic shown here is a schematic representation of circuit-breakers for all ranges.
Time/current characteristics, current limiting characteristics and I²t
characteristics are available on request.

Current

■ Wiring diagrams
Circuit-breaker

Transverse auxiliary contact block

Lateral auxiliary contact block

J7MN

J73MN-11F

J73MN-11S

Signalling switch

Undervoltage release

Shunt release

J73MN-T-11S

J74MN-U

J74MN-S

H-80

Motor Protection Circuit Breaker (MPCB) J7MN

■ Dimensions
Circuit-breaker J7MN-12

Circuit-breaker J7MN-25

Circuit-breaker J7MN-50
1)
2)
3)
4)
7)
8)
9)

Lateral aux. contact
Signalling contact
Auxiliary release
Transverse aux. contact
Mounting holes
35mm DIN-rail
35mm DIN-rail 15mm high or
75mm DIN-rail
10) 4mm hexagon socket screw
11) Lockable in 0-position
with shackle diameter max.5mm

1)
2)
3)
4)
7)
8)
9)

Lateral aux. contact
Signalling contact
Auxiliary release
Transverse aux. contact
Mounting holes
35mm DIN-rail
35mm DIN-rail 15mm high or
75mm DIN-rail
10) 4mm hexagon socket screw
11) Lockable in 0-position
with shackle diameter max.5mm

Motor Protection Circuit Breaker (MPCB)

J7MN

H-81

LVSG

Circuit-breaker J7MN-100

Moulded plastic front plate J74MN-P12

Moulded plastic front plate J74MN-P25

Moulded plastic enclosure J74MN-PF12

Door-coupling rotary operating mechanism J74MN-DC
1) Max. for shackle diameter for
padlock 8 mm

3-phase busbar J74MN-L3-#/#
for J7MN-12 and J7MN-25, modular spacing 45 mm

3-phase line-side terminal J74MN-TC12 and J74MN-TC25

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

Cat. No. J508-E2-02

H-82

In the interest of product improvement, specifications are subject to change without notice.

Motor Protection Circuit Breaker (MPCB) J7MN

Appendix
● Precautions
■ Notice
Use under rated condition, otherwise contactors will not only cause
malfunction, but also cause a fire or damage the contactor.

Do not use a contactor or thermal relay which has been dropped or
dismantled. Doing so may cause malfunction or a fire.

Life period of contactor depends on the operating application. Please
check the electrical life under real application in advance.
If you continue to use malfunctioning contactor, a fire or breakdown
may occur.

Make sure to shut off power supply to contactors before wiring or
replacing.
Do not operate the actuator of a contactor manually. Doing so may
cause contact welding by chattering or burn out by arc.

Do not miss-wire or miss-charge the power supply, otherwise the
contactor does not work correctly.
Do not operate in places with explosive or flammable gas, otherwise
a fire or explosion may occur by arc or heating from contactor.
Make sure to use the circuit well considered about safety, in case
there is any possibility to cause secondary disaster by contact trouble (welding, faulty contact).
Do not supply short-circuit current to electromagnetic switch (contactor with thermal relay). Doing so may result failure in heater of thermal relay. Please use short-circuit protection like fuse or protective
circuit breaker.

Unless otherwise stated in the catalogue,
modifications, especially those of stated values,
sizes and weights are subject to alternation.
Diagrams and tables are subject to alternation and
not to be regarded as binding drawings.

General use

Circuit design

Unexpected malfunction may occur in real application. Please carry
out as many tests as possible.

Supplied voltage waveform for input

Ratings in this catalogue measured under the condition according to
IEC unless otherwise specified. In cases of check by real application,
please carry out the test under the same condition as expected in the
actual application.

Make sure to apply and remove the voltage instantly. Do not use
under the condition that the coil voltage waveform increases or
decreases gradually.

Selection

In case of DC contactor use (input voltage
ripple)

Coil specification

Please use DC contactor input voltage with a ripple ratio less than
5%. Excessive ripple (pulsating current) may cause contact welding.

Please select suitable coil to circuit design, otherwise malfunction
may occur or coil may have a burn out by overvoltage etc.

Fluctuation of input voltage

Type

Make sure to supply sufficient voltage to actuate contactors properly.
Continuous supply of insufficient voltage results in excessive heating
and may cause burn out of coil.

Please check contact ratings, switching capacity, thermal characteristics etc. when selecting product type.

Thermal relay
Motor current differs by supplier, type, number of poles, frequency.
Please confirm operational current level.

Coil surge suppressor
Coil surge suppressor type should be selected by contactor type,
auxiliary relay type and applied voltage. Make sure to use defined
each contactor.
In case of installing coil surge suppressor, please check the actual
circuit because the release time will be delayed.

Electrical life expectancy
Electrical life expectancy tests in this catalogue are based on IEC.

Maximum applied voltage
Do not supply the voltage over the maximum rated voltage, otherwise
burn out or insulation failure may occur.
The temperature inside control panel has much influence to the coil
temperature, so make sure not to exceed the specified value in the
catalogue.
Basically rated voltage should be supplied to coil. To supply higher
voltage than rated would result in shorter electrical life, even if it is
lower than the maximum rated voltage.

Reverse
Make sure to use reversible contactors for reverse operation.
Make sure to use interlock device in reverse operation by two contactors, otherwise short circuit current may burn out or give damage to
contactors and motors.

Appendix

H-83

LVSG

■ Correct use

Installation

Operation ambience

Mounting

Dust

Make sure to use specified wire size, mounting screw size, mounting
screw number, and DIN rail size.

Dust on the surface of the contacts could result in contact malfunctioning. Take countermeasure in excessive dusty surrounding.

Tightening Screw

Temperature, humidity

Tighten each screw securely by specified tightening torque. Loose
tightening may cause a fire by excessive heating.

Use contactors within the temperature and humidity conditions specified in datasheet. To use or store contactor in excessive temperature
or humidity may result in malfunction of contact by organic film composed by sulfication and oxidation on the surface of the contacts.

Combination
Wrong-combinations may result in damage to contactors.

Use contactors within the temperature and humidity conditions specified in the datasheet, to prevent contactors from insulation resistance failure by condensation or insulation resistance deterioration
by tracking.

Mounting direction

Gas

Some products have a defined specific mounting direction. Please
refer to datasheet before use.

NH3, H2S, SO2, CI2, Si and NO2 have bad effects on a contactor.
With these gases, a corrosive metal film ist generated on the surface
of the contacts and could result in contact malfunctioning. Use a contactor in low humidity and no corrosive gas surroundings.

Please use only OMRON product combinations in case of thermal
relay, timer block and auxiliary contact block etc.

Oil
Do not use a contactor in places where oil is sprayed onto the contactor. It will cause cracks on polymer parts.

Shock and vibration
Do not use a contactor in places where there is excessive shock or
vibration. It may cause malfunctioning.

Storage
Store contactors in a place with no direct sunshine or ultraviolet rays.
It will cause crack on polymer parts.
When contactors are to be stored for a long time, they must be stored
with care. Though it generally depends where contactors are stored,
deterioration of contacts may occur after long storage. Please check
the characteristics before use after long time storage.

H-84

Appendix

● European Standards
■ IEC 947, EN 60947
European Standards for Low-Voltage Switchgear
For Europe and most other industrial countries of the world, the new
IEC 947 and EN 60 947 specifications for low-voltage switchgear
have unified the regulations which previously varied from nation to
nation.
This required the introduction of new terms, and new test methods
and utilization categories. The new specifications are aimed
primarily at manufacturers. However, the user also will come across
new technical terms and data in the manufacturers’ catalogues
and on the devices themselves which are important for the selection
and application of the devices. The present paper deals with the currently published specifications. Further specifications and
supplements are in preparation.

Since 1993, all low-voltage switchgear purchased in Europe had to
satisfy the EN 60 947 European Standard. Installations in existence
prior to 1993 are not affected by the standard and need not to be
refitted with new devices. Devices constructed and tested to the IEC
standards and EN standards can be used worldwide, with the exception of the USA and Canada. In these countries UL and CSA specifications continue to apply. Switchgear which conforms to IEC 947
and EN 60 947 and which has, in addition, UL- and CSA approvals,
in the meantime has entered the market. Such ‘world market’ devices
offer the advantage that they can be used throughout the world,
including the USA and Canada.

IEC 947-1
IEC 947-2

General rules
Circuit-breakers

IEC 947-3
IEC 947-4-1
IEC 947-5-1
IEC 947-6-1
IEC 947-6-2

Switches, disconnectors, switch-disconnectors and fuse-combination units
Connectors and motor-starters
Control circuit devices and switching elements
Multiple function equipment, Automatic transfer switching equipment
Multiple function equipment, Control and protective switching devices (or equipment)
(CPS)
Ancillary equipment

IEC 947-7-1

LVSG

IEC 947

Conditions for compliance with
Type 1 coordination
(Extract from IEC 947-4-1)

Conditions for compliance with
Type 2 coordination
(Extract from IEC 947-4-1)

- The contactor or the starter must not endanger
personnel or equipment in the event of a short
circuit
- The contactor or the starter does not need to be
suitable for continued operation without repair and
replacement of parts

- The contactor or the starter must not endanger
personnel or equipment in the event of a short
circuit
- The contactor or the starter must be suitable for
further use
- No damage may occur to the overload relay or
other parts, with the exception of welding of the
contactor or starter contacts, provided they can
be separated easily without any significant
deformation (e.g. using a screwdriver)

- Damage to the contactor and the overload relay is
permissible

Rated conditional
short-circuit current lq
- The rated conditional short-circuit
current lq indicates the max. shortcircuit breaking capacity of the starter

Rated operation current le
- The rated operational current le for
the starter is the current when the
starter is in the On position

Rated uninterrupted current lu
(to IEC 947-1)

- The rated uninterrupted current lu of
a unit is a current, specified by the
manufacturer, which the unit can
carry without interruption

Appendix

H-85

Overview
The following table shows in summarized form both the previous and the new IEC, EN and DIN VDE standards.
Previous specification

New specification

IEC

DIN VDE

IEC

EN 60947
DIN VDE

Content

-

-

947-1

60947-1
0660, Part 100

Low-voltage switchgear,
General rules

157

0660, Part 101

947-2

60947-2
0660, Part 101

Low-voltage switchgear,
Circuit-breakers

406

0660, Part 107

947-3

60947-3
0660, Part 107

Low-voltage switchgear,
Switches,
Disconnectors,
Switch-disconnectors,
Fuse-combination units

158
292-1
292-2
292-3

0660, Part 102
0660, Part 104
0660, Part 106
0660, Part 301

947-4-1

60947-4-1
0660, Part 102

Low-voltage switchgear,
Control circuit devices and switching elements

337

0660 Part 200 to Part 205

947-5-1

60947-5-1
0660, Part 200

Low-voltage switchgear,
Multiple-function equipment,
Automatic transfer switching equipment

-

-

947-6-1

60947-6-1
0660, Part 114

Low-voltage switchgear,
Multiple-function equipment,
Control and protective switching devices (CPS)

-

0611 Part 1 and 2

947-7-1

60947-7-1
0611, Part 1

Low-voltage switchgear,
Ancillary equipment (e.g. terminal blocks)

Switches, disconnectors, switch-disconnectors and fuse combination units
(IEC 947-3, EN 60947-3)
These devices must now be labelled with the product function designated by the manufacturer. This means placing clearly visible symbols on the
device itself.
Devices with an isolating function are subject to special safety requirements. They must for example have greater creepage distances and clearances across the opened contacts than is necessary for other devices.

Device functions and corresponding symbols
Making/breaking

Isolating

Making/breaking
+ isolating

Switch

Disconnector

Switch-disconnector

Switch-fuse

Disconnector-fuse

Switch-disconnector-fuse

Fuse-switch

Fuse-disconnector

Fuse switch-disconnector

OMRON equipment is designed for the world’s markets
It is manufactured and tested in accordance with national and international specifications, the most important of which are listed below:
IEC 947-..., EN 60947:
IEC 664:
IEC364:
IEC 204-..., EN 60204-...:
DIN VDE 0105:
IEC 536:

H-86

Low-voltage switch gear and control gear
Insulation co-ordination including clearances and creepage distances for equipment
Electrical installations of buildings
Electrical equipment of industrial machines
Operation of electrical power installations
Protection against electric shock

Appendix

Utilization categories for contactors to IEC 947-4-1 and EN 60947

Type of
current

AC

Typical examples of application
I = current made, Ic = current broken
Utilization Ie = rated operational current
category U = voltage before make
Ue = rated operational voltage
Ur = recovery voltage

Verification of electrical endurance
Make
Ie
A

Verification of rated making and breaking capacities
Break

I
Ie

U
Ue

cos ϕ

Make

Ic
Ie

-

Ur

cos ϕ

Ue

Ie

Break
U
Ue

cos ϕ

A

I
Ie

Ic
Ie

-

cos ϕ
0.8

Ur
Ue

AC-1

Non-inductive or slightly inductive loads, resistance
All values
furnaces

1

1

0.95

1

1

0.95

All values

1.5

1.05

0.8

1.5

1.05

AC-2

Slip-ring motors: starting, switching off

2.5

1

0.65

2.5

1

0.65

All values

4

1.05

0.65

4

1.05

0.65

AC-3

Squirrel-cage motors: starting, switching off motors Ie ≤ 17
Ie > 17
during running4

6
6

1
1

0.65
0.35

1
1

0.17
0.17

0.65
0.35

Ie ≤ 100
Ie > 100

10
10

1.05
1.05

0.45
0.35

8
8

1.05
1.05

0.45
0.35

AC-4

Squirrel-cage motors: starting, plugging, inching

Ie ≤ 17
Ie > 17

6
6

1
1

0.65
0.35

6
6

1
1

0.65
0.35

Ie ≤ 100
Ie > 100

12
12

1.05
1.05

0.45
0.35

10
10

1.05
1.05

0.45
0.35

AC-5A

Switching of electric discharge lamp controls

-

-

-

-

-

-

-

-

3.0

1.05

0.45

3.0

1.05

0.45

AC-5B

Switching of incandescent lamps

-

-

-

-

-

-

-

-

1.52

1.05

2

1.52

1.05

2

AC-6A3

Switching of transformers

As given by the manufacturer

-

-

-

-

-

-

-

AC-6B3

Switching of capacitor banks

As given by the manufacturer

-

-

-

-

-

-

-

AC-7A

Slightly inductive loads in household appliances and
As given by the manufacturer
similar applications

-

1.5

1.05

0.8

1.5

1.05

0.8

AC-7B

Motor-loads for household applications

As given by the manufacturer

-

8.0

1.05

1

8.0

1.05

1

AC-8A

Hermetic refrigerant compressor motor control with
As given by the manufacturer
manual resetting of overload releases5

-

6.0

1.05

1

6.0

1.05

1

AC-8B

Hermetic refrigerant compressor motor control with
As given by the manufacturer
automatic resetting of overload releases5

-

6.0

1.05

1

6.0

1.05

1

Ie

U
Ue

L/R

Ic
Ie

Ur

L/R

ms

-

Ue

ms

All values

)
)

)
)
)

U
Ue

L/R
ms

Ic
Ie

-

Ue

ms

A

I
Ie

DC-1

Non-inductive or slightly inductive loads, resistance
All values
furnaces

1

1

1

1

1

1

All values

1.5

1.05

1

1.5

1.05

1

DC-3

Shunt motors: starting, plugging, inching, dynamic
braking

All values

2.5

1

2

2.5

1

2

All values

4

1.05

2.5

4

1.05

2.5

DC-5

Series motors: starting, plugging, inching, dynamic
All values
braking

2.5

1

7.5

2.5

1

7.5

All values

4

1.05

15

4

1.05

15

-

1.5
2
)

2

1.5
2
)

1.05

2

A

DC

DC-6

Switching of incandescent lamps

-

-

-

-

-

Note 1: cos ϕ = 0.45 for Ie ≤ 100 A; cos ϕ = 0.35 for Ie > 100 A.
2: The tests are to be carried out with an incandescent light load.
3: The test data are to be derived from the test values for AC-3 or AC-4 according to
Table VIIb, EN 60947-4-1.

-

L/R

)

)

I
Ie

Ie

Ur

)

-

1.05

)

)

4: AC-3 category may be used for occasional inching (jogging) or plugging for limited
time periods such as machine set-up; during such limited time periods the number
of such operations should not exceed five per minute or more than ten in a ten
minute period.
5: A hermetic refrigerant compressor motor is a combination consisting of a compressor and a motor, both of which are enclosed in the same housing, with no external
shaft or shaft seals, the motor operating in the refrigerant.

Utilization categories for control switches to IEC 947-5-1 and EN 60947
Normal conditions of use

Abormal conditions of use

AC

AC-12

Control of resistive and solid state loads as in optocoupler input circuits

AC-13

Control of solid state loads with transformer isolation

2

1

0.65

1

1

0.65

10

1.1

0.65

1.1

1.1

0.65

AC-14

Control of small electromagnetic loads (≤ 72 VA)

6

1

0.3

1

1

0.3

6

1.1

0.7

6

1.1

0.7

AC-15

Control of electromagnetic loads (> 72 VA)

10

1

0.3

1

1

0.3

10

1.1

0.3

10

1.1

0.3

I
Ie

U
Ue

t0.95

Ic
Ie

Ur
Ue

t0.95

I
Ie

U
Ue

t0.95

Ic
Ie

Ur
Ue

t0.95

1

1

1 ms

1

1

1 ms

-

-

-

-

-

-

1

1

DC

DC-12

Make

Control of resistive and solid state loads as in optocoupler input circuits

Break

Make

LVSG

Type of
current

Typical examples of application
I = current made, Ic = current broken
Ie = rated operational current
Ue = rated operational voltage
Utilization
Ur = recovery voltage
category
U = voltage before make
t0.95 = time in ms to reach 95 % of the steady-state
current
P = Ue x Ie = rated power consumption in watts

Break

I
Ie

U
Ue

cos ϕ

Ic
Ie

Ur
Ue

cos ϕ

I
Ie

U
Ue

cos ϕ

Ic
Ie

Ur
Ue

cos ϕ

1

1

0.9

1

1

0.9

-

-

-

-

-

-

1

DC-13

Control of electromagnets

1

1

6xP )

1

1

6xP )

1.1

1.1

6xP )

1.1

1.1

6xP1)

DC-14

Control of electromagnetic loads having economy
resistors in circuits

10

1

15 ms 1

1

15 ms

10

1.1

15 ms 10

1.1

15 ms

Note 1: The value “6 x P” results from an empirical relationship which is found to represent most DC magnetic loads to an upper limit of P = 50 W, viz 6 x P = 300 ms. Loads having power
consumption greater than 50 W are assumed to consist of smaller loads in parallel. Therefore, 300 ms is to be an upper limit, irrespective of the power consumption value.
Utilization categories for switches, disconnectors, switch-disconnectors, and fuse combination units to IEC 947-3 and EN 60947

Type of
current

AC

Typical applications
I = current made, Ic = current broken
Utilization Ie = rated operational current
category U = voltage before make
Ue = rated operational voltage
Ur = recovery voltage

Verification of electrical endurance
Make
Ie
A

Verification of switching capacity
Break

Make

Ic
Ie

Ur
Ue

cos ϕ

1

1

)

1

1

I
Ie

U
Ue

cos ϕ

Ie

Break
I
Ie

U
Ue

cos ϕ

Ic
Ie

Ur
Ue

cos ϕ

All values

1

)

1.05

1

1

)

1.05

1

A

AC-20
A(B)2

Connecting and disconnecting under no-load condiAll values
tions

1

)

1

AC-21
A(B)2

Switching of resistive loads, including moderate
overloads

All values

1

1

0.95

1

1

0.95

All values

1.5

1.05

0.95

1.5

1.05

0.95

AC-22
A(B)2

Switching of mixed resistive and inductive loads, inAll values
cluding moderate overloads

1

1

0.8

1

1

0.8

All values

3

1.05

0.65

3

1.05

0.65

)

)

)

)

)

Appendix

)

H-87

Utilization categories for switches, disconnectors, switch-disconnectors, and fuse combination units to IEC 947-3 and EN 60947

Type of
current

Typical applications
I = current made, Ic = current broken
Utilization Ie = rated operational current
category U = voltage before make
Ue = rated operational voltage
Ur = recovery voltage
AC-23
A(B)2

Switching of motor loads or other highly inductive
loads

Verification of electrical endurance
Make
Ie

DC

Make

Ic
Ie

Ur
Ue

cos ϕ

0.65

1

1

U
Ue

L/R
ms

Ic
Ie

U
Ue

cos ϕ

A

I
Ie

All values

1

1

Ie

I
Ie

A

Verification of switching capacity
Break

Ie

Break
cos ϕ

Ic
Ie

Ur
Ue

cos ϕ

1.05
1.05

0.45
0.35

8
8

1.05
1.05

0.45
0.35

U
Ue

L/R

Ic
Ie

Ur
Ue

L/R

ms

1

)

1.05

1

A

I
Ie

U
Ue

0.65

Ie ≤ 100
Ie > 100

10
10

Ur
Ue

L/R

Ie

I
Ie

ms

A

ms

DC-20
A(B)2

Connecting and disconnecting under no-load condiAll values
tions

1

)

1

)

1

)

1

)

1

)

1

)

All values

1

)

1.05

1

DC-21
A(B)2

Switching of resistive loads, including moderate
overloads

All values

1

1

1

1

1

1

All values

1.5

1.05

1

1.5

1.05

1

DC-22
A(B)2

Switching of mixed resistive and inductive loads, inAll values
cluding moderate overloads (e.g. shunt motors)

1

1

2

1

1

2

All values

4

1.05

2.5

4

1.05

2.5

DC-23
A(B)2

Switching of highly inductive loads (e.g. series moAll values
tors)

1

1

7.5

1

1

7.5

All values

4

1.05

15

4

1.05

15

)

)

Note 1: If the switching device has a making and/or breaking capacity, the figures for the current and the power factor (time constants) must be stated by the manufacturer.
2: A: frequent operation, B: infrequent operation.

Protection against electrical shock, to IEC 536

Damp heat, constant, to IEC 68 Part 2-3

IEC 536 covers the setting up of electrical apparatus, and its
arrangement in electrical installations with rated voltages up to 1000
VAC and 1500 VDC, with regard to protection against direct contact
where operating elements such as push-buttons and switches are
located in the vicinity of live parts.

In this test, the effects of a constant high level of humidity
(93 +2/-3%) and a constant temperature (40 ±2)°C over a prescribed
duration, are observed.

“Finger-proofing” relates only to the operating device, and only in the
normal direction of operation. A clearance of at least 30 mm radius
from the centre point of the device to any live parts, must be ensured.

This test is used to assess the suitability of electrical products for
operation and storage at high relative humidity levels, in conjunction
with cyclic temperature fluctuation. A test cycle consists of 12 hours
at 40 ±2°C, with relative humidity of 93 ±3%, and 12 hours at
25 ±3°C, with the relative humidity of at least 95%.

The IP 20 degree of protection is superior to “finger-proofing” in that
it embodies protection against contact with electrical apparatus in
any direction. Devices which are “finger-proof” and of IP 00 degree of
protection can be provided with further protection against contact in
the form of shrouding, if so desired.

H-88

Appendix

Damp heat, cyclic, to IEC 68 Part 2 - 30, Test Db

Ambient temperature
Ambient temperature is the temperature of the room (e.g. factory bay
or switchgear room), in which the open or enclosed device is
installed, a prerequisite being that this temperature is not significantly
influenced by the heat losses from the device.

● Glossary of standard terms
This Glossary offers brief expIanations of some of the standard
terms used in this catalogue. However, it must not be regarded as a
substitute for the actual text of the standard, especially where the
new terms used in IEC 947 are concerned.

Reference is therefore made aIongside each such term to the reIevant section of the standard, e.g. IEC 947-1 in addition, IEV numbers
are given to enable you to find foreign language equivalents in the
International EIectrotechnicaI Vocabulary
(IEG 50), if required.

Rated conditional short-circuit current Iq

Rated operational current Ie

The prospective current which a switching device, e.g. a circuitbreaker, protected by a short-circuit protective device such as a
motor-protective circuit-breaker, can carry for the duration of the protective device tripping time.

The current which an equipment is capabIe of carrying taking into
account the rated operational current, duration of operation, utilization category and ambient temperature.

Mininum command time
Minimum duration for a trip-initiating factor (controI puIse, short circuit) to effect the corresponding reaction, e.g. the short-circuit duration necessary to initiate tripping.

Rated breaking capacity
(IEC 947-1; 4.3.5.3)
The r.m.s. value of current which a switching device is capable of
breaking according to its utiIization category. The rated breaking
capacity is stated by reference to the rated operational voltage and
the rated operational current.
The equipment must be capable of breaking any value of current up
to and incIuding its rated breaking capacity stated.

Rated actuating voltage Uc
(rated control circuit voltage)
(IEC 947-1; 4.5.1)
The voltage which is applied to the actuating make contact in a control circuit. Due to the presence in the controI circuit of transformers
or resistors, this voltage may differ from the rated control supply voltage.

Rated service short-circuit breaking capacity Ics
(IEC 947-2; 4.3.5.2.2)

The prospective short-circuit current which, depending on the rated
operationaI voltage, a circuit-breaker is capable of breaking repeatedly (test cycle: O - CO - CO; previousIy P-2). After interrupting this
current vaIue, the circuit-breaker must be capable, despite its own
thermal level having increased, of continuing to carry and disconnect
in the event of overIoading, the rated uninterrupted current.

Rating or rated power
(IEC 947-1; 4.3.2.3)
The rated operational power which an equipment is capable of
switching at the associated rated operational voItage in accordance
with the utilization category.
For example:
motor contactor utilization category AC-3: 37 kW at 400 V.

Rated operational voltage Ue
(IEC 947-1; 4.3.1.1)

The voItage to which the characteristics of an equipment are
referred. The rated operational current must not in any case exceed
the rated insulation voltage.

(IEC 947-1; 4.3.2.3)

Rated uninterrupted current Iu
(IEC 947-1; 4.3.2.4)

The vaIue of current which an equipment can carry in uninterrupted
duty (i.e. for weeks, months or years).

Rated making capacity
(IEC 947-1; 4.3.5.2)
The vaIue of current which an equipment is capabIe of switching On
in accordance with the utilization category and at the rated operational voltage.

Rated frequency
(IEC 847-1; 4,3.3)
The frequency for which an equipment is designed and to which the
other characteristic vaIues are referred.

Rated ultimate short-circuit breaking
capacity Icu
(IEC 947-2; 4.3.5.2.1)

The maximum prospective fault current which a circuit-breaker is
capable of interrupting
(test cycIe: O - CO; previously P-1)

Rated insulation voltage Ui
(IEG 947-1; 4.3.1 .2)

The voltage to which insulation tests and creepage distances of an
equipment are referred. The maximum operationaI voltage must not
in any case exceed the rated insulation voltage.

Rated short-circuit breaking capacity Icn
(IEC 947-1; 4.3.6.3)

The maximum value of current which an equipment is capable of
switching Off at rated operational voItage and rated frequency, and
without sustaining damage. It is expressed as r.m.s. value.

Motor rating
(IEC 947-1; 4.3.2.3)
Power output of a motor at the associated operational voltage.

Rated control supply voltage Us
(IEC 947-1; 4.5.1)

The voltage applied to the input terminals of the control circuit of an
equipment. Due to the presence of transformers or resistors in the
control circuit, this may differ from the rated actuating (control circuit)
voltage.

Appendix

H-89

LVSG

(IEC 947-1; 2.5.29/IEV 441-17-20)

Rated impulse withstand voltage Uimp

Finger proof

Measures the stability of the internal clearances of an equipment
against overvoltage peaks. The utilization of suitable switchgear can
ensure that overvoltages are prevented from transferring from the
mains to deenergized system sections within it.

An equipment whose live parts cannot be touched by the operator
during actuation is termed finger proof. This also affects operator
activity on neighbouring switching devices. The finger proof area of a
push-actuated operating medium is a circular area of at least 30 mm
radius around the actuating element, and vertical to the direction of
actuation.

Rated current In

Within this circular area, touch-critical parts must be located at not
less than 80 mm depth under the actuating level.

(IEC 947-1; 4.3.1 .3)

(of a circuit-breaker)
(IEC 947-2; 4.3.2.3)
For circuit-breakers, this current value is equal to the uninterrupted
current and the conventional free air thermaI current.

Protection against direct contact
Design measures incorporated into equipment in order to prevent
direct contact, i.e. without tools, with live parts of a system (finger
proof, back-of-hand proof).

Control circuit reliability
Measures the probability of switching states arising during the
lifespan of a contact, which would be interpreted as faults by downstream electronic controllers (PLCs). Control circuit reliability is
expressed in values based on tests using standard limit values for
signal inputs.

Utilization category
(IEC 947-1; 2.1 .18/IEV 441-17-19)
A combination of specified requirements relating to the condition in
which the switching device or the fuse fulfills its purpose, selected to
represent a characteristic group of practical applications. The specified requirements may concern, e.g. the values of making capacities,
breaking capacities and other characteristic values, data concerning
associated circuits, and the relevant conditions of use and behaviour.

(IEC 947-2; 4.4)
For circuit-breakers, the utilization category denotes whether the
equipment is designed for selectivity using time delay (category B) or
not (category A).

Back-of-hand proof

Damp heat, constant

An equipment whose live parts cannot be touched by a sphere of
50 mm diameter, is regarded as back-of-hand proof.

This test subjects the equipment to an ambient temperature of 40°C
at a constant humidity of 93%. At set intervals during the test, the
electrical and mechanical function of the equipment are examined.

Altitude

Damp heat, cyclic
This test subjects the equipment to cyclically changing climatic conditions: a cycle applies 40°C ambient temperature at 93% relative
humidity for 12 hours, followed by 12 hours of 25°C at 95% relative
humidity. At set intervals during the test, the electrical and mechanical function of the equipment are examined.

The density of air decreases with increasing altitude, and this
reduces its insulating capacity as well as its heat transfer capability.
The rated operational voltage and current of switching devices, conductors and motors as well as the tripping behaviour of thermal overload relays are affected by this.
Upon request, OMRON ELECTRONICS will supply information as to
the suitability or otherwise of switchgear for operation at altitudes
above the 2000 m limit specified by the standard.

Conventional free air thermal current
(IEC 947-1; 4.3.2.1)
The maximum value of current which an equipment is capable of carrying for a minimum of eight hours without thermal overloading. As a
rule, it corresponds to the maximum operational current.

Creepage path
(IEC 947-1; 2.5.51/IEV 151-03-37)
The shortest distance along the surface of the insulating material
between two conductive parts. The creepage distance is determined
by the rated insulation voltage, the pollution degree and the creepage current resistance of the material used.

Clearance
(IEC 947-1; 2.5.46/IEV 441-17-31)
The distance between two conductive parts along a string stretched
the shortest way between these conductive parts. The clearance in
air is determined by the rated impulse withstand voltage, overvoltage
category and pollution degree.

H-90

Appendix

Emergency-stop switching device

Overvoltage category

Switching device within an emergency-stop circuit which is intended
to prevent danger to persons, damage to machinery or working
materials.

(IEC 947-1; 2.5.60)

Opening delay
(IEV 441-17-36)

Conventional number for prospective overvoltages at the point of
installation, as might be caused for example by the effect of lightning
or switching processes. The overvoltage category applicable to
industrial switchgear is III. The applicability of switchgear according
to the overvoltage categories is defined as follows:

The interval of time between the specified instant of initiation of the
opening operation and the instant when the arcing contacts have
separated in all poles. The opening time is the sum of the tripping
time and the inherent delay of the contacts.

Overvoltage category IV:

Closing delay

Overvoltage category III:

The interval of time between the instant of command and the first
make operation of the contacts of the first pole to close. The closing
delay is made up of the response delay and the closing time.

Operating media with special requirements as to the serviceability for
connection in fixed installations, which are protected by overvoltage
diversion measures, e.g. circuit-breakers in low-voltage distribution
systems or in control systems for industrial use.

Shock resistance

Overvoltage category II:

The capacity of an equipment to withstand pulse-like motions without
changing its operating status or sustaining damage. No contact lifting
must take place on devices in the On position, the main contacts
must not knock against each other in the Off position. A safety switch
must not trip, and control circuit switches must not change their
switching status.

Power consumers for connection to fixed installations, e. g. household appliances, electrical tools.

Safe isolation

Ambient temperature, open

(IEC 536, DIN VDE 0106 Part 101)

(IEV 441-11-13)

Isolation of circuits not carrying dangerous voltages (e.g. protective
extra-low voltage) from circuits in which dangerous voltages flow.
Such isolation is achieved by means of reinforced or double insulation which reliably prevents voltage transfer from one circuit to
another. This might otherwise take place between main circuits and
control circuits in switching devices or between transformer primary
and secondary. ”Safe isolation” is a priority requirement for safety circuits and functional low-voltage circuits.

Room temperature for example of the workshop or switch room in
which the switching device is located.

(IEC 947-1; 2.1.19)
Equipments are deemed to possess this isolating function provided
their switching contacts when in the open position, achieve the separation distance prescribed for the isolation of electrical circuits, and
their creepage paths and clearance distances are of the required
size. The power supply to the entire installation or a section of the
installation can thus be cut off for safety reasons, e.g. during maintenance.

Tamper proof
An emergency-stop switching device is regarded as tamper proof
provided it cannot be reset without tools or via a prescribed procedure, after tripping has taken place. The device latches in the tripped
position. Accidental or deliberate manipulation (inching) is thus ruled
out.

Overvoltage category I:
Operating media for connection to circuits containing overvoltage
protection schemes, e.g. electronic devices.

Ambient temperature, enclosed
(IEV 441-11-13)
Temperature at which the switching device is capable of being operated within a closed housing. For this purpose, it must be taken into
account that the heat losses of the device will add to the internal temperature rise within the enclosure.

Losses

LVSG

Isolating function

Use allowed directly at the termination point of the installation
(directly affected by any lightning), e.g. at an overhead line connection point.

(IEV 151-03-18)
The difference between the input power and the output power of a
device. The main type of loss in electrical power distribution switchgear and operating media is current heat loss.

Pollution degree
(IEC 947-1; 6./1.3.2)
Conventional number for the prospective quantities of conductive
dust and humidity which can lead to a reduction in the control circuit
reliability of a device. The pollution degree is described by the following influencing factors:

Pollution degree 1:
No pollution or only dry, non-conductive pollution occurs. The pollution does not affect the control circuit reliability.

Pollution degree 2:
Usually, only non-conductive pollution. However, transient conductivity through condensation is to be expected.

Pollution degree 3: (switchgear for industrial use)
Conductive pollution or dry, non-conductive pollution which is rendered conductive through condensation.

Pollution degree 4:
The pollution leads to long-term conductivity, e.g. pollution by conductive dust, rain or snow.

Appendix

H-91

Coordination type
Status of a switchgear combination (motor starter) during and after
testing at rated conditional current:

Coordination Type “1“:
- No risk to persons or installations
- No requirement for immediate readiness for renewed operation
- Damage to the starter is permissible

Coordination type “2“:
- No risk to persons or installations
- Starter is capable of renewed operation
- No damage to the starter with the exception of a slight welding of
the contacts, provided they can be separated without significant
deformation.

Positive opening operation

vided they are mechanically linked in such a way as to ensure that
normally open and normally closed contacts can never be closed
simultaneously.
This arrangement must also ensure that minimum contact separation
of 0.5 mm is maintained over the entire lifespan of the device, even
during a fault, e.g. the welding of one contact.
The relevant German Trade Association requires the use of contactors with interlocked opposing contacts for control systems on power
presses in the metal processing industry.

Positive/enforced
operation/actuation
This describes an arrangement where a link between the actuator
and the switching element ensures that the force exerted on the actuator is transferred directly, i.e. without the intervention of sprung
parts, onto the switching element.

(IEC 947-1; 2.4.11/IEV 441-16-12)

Positive opening

This opening operation is designed to ensure that auxiliary contacts
of a switching device are always in the respective positions corresponding to the open or closed position of the main contacts. The
contacts of a contactor are interlocked opposing contacts, pro-

(IEC 947-1; 2.4.10/IEV 441-16-11)
An opening operation which ensures that the main contacts of a
mechanical switching device have attained the open position when
the actuator is in the Off-position.

Symbols used in Technical Data and Formulae
DF
Icn

Duty factor
Rated short-circuit breaking capacity

Ith

Conventional free air thermal current

Ithe

Conventional thermal current of enclosed devices

Ics

Rated service short-circuit breaking capacity

Iu

Rated uninterrupted current

Icu

Rated ultimate short-circuit breaking capacity

SNT

Transformer rating

Ie

Rated operational current

Uc

Rated actuating voltage

I”sc

Transformer initial short-circuit current AC

Ue

Rated operational voltage

In

Rated current

Ui

Rated insulation voltage

INT

Rated transformer current

Uimp

Rated impulse withstand voltage

Iq

Rated conditional short-circuit current

uk

Transformer short-circuit voltage

Ir

Set value of overcurrent release

Us

Rated control voltage

Irm

Response value of non-delayed short-circuit release

H-92

Appendix

● Additional ordering information for contactors
CE-Marking
The manufacturer has to sign his products with the CE-Marking. With
the CE-Marking the manufacturer confirms the accordance with the
different EEC Directives. The CE-Marking is absolutely necessary to
sell the products in the EEC.

Attached you find the EEC Directives concerning our products.
Low Voltage Directive (73/23/EEC)
EMC Directive (89/336/EEC)
Declarations of Conformity art. no. D586.. on request.

Test Authorities, Registration Mark, Approvals
OMRON Low voltage switchgear is built and tested to national and
international specifications. All devices suit all important specifications without any test obligation, like VDE, BS and also relative to
IEC Recommendations and to European Standards like IEC 947 and
EN 60947.
It is for this reason OMRON Low voltage switchgear is used all over
the world. In order to provide special versions, limitations to the max.
voltages, currents and power ratings or special markings are sometimes necessary.
Canada

State deputy or private
examination
CSA UL
(state admitted)

USA

Switzer- Denland
mark

UL

SEV

They are classified in "Lloyd`s Register of Shipping" and in the "Maritime Register of Shipping" (GUS). The "American Bureau of Shipping" does not claim a general approval for single components, the
complete electrical equipment on board has to be approved. The
devices should have UL- and CSA-approvals. Further information for
Guide-No. and File-No. (CSA, UL) you will find on page 95.
For approved values see technical data of the devices.State deputy
Norway Sweden Finland Poland

DEMKO NEMKO SEMKO SETI

SEP

Slowakia

Czech

Hungaria

SKTC

EZU

MEEI

*1

Label marking of examination boards

Duty of approvals

or R
Approval of
All switchgear
switchgear
commendable

Specification

UL is authorised for approvals Marking with approbation label is no longer
acc. to Canadian Standards
necessary

No approval since 1.1.1994
Our devices are according to the harmonised
European Standards e.g. EN 60947 (IEC 947,
VDE 0660) and can be used generally

*1) CSA-approvals are replaced by UL-approvals valid for USA and Canada. From 1. 1. 2000 switchgear will be marked with the combined
approval. UL-mark
or
only.

Explanations for choice and supply of low voltage switchgears in Canada and USA
Marking of auxiliary contacts
At several devices in UL-data are two voltages for auxiliary contacts
mentioned (e. g.: 600 volts at same potential, 150 volts at different
potentials). That means, if the voltage is higher than 150 volts, the control voltage applied to input terminals must be at the same potential

Low voltage switchgear for auxiliary circuits (e. g. contactor relays,
control units, auxiliary contacts in general) usually approved for
"Heavy Duty" or "Standard Duty" UL and besides these marked with
the admissible max. voltage or with short codes (see table).

Marking of
auxiliary
contacts
according to
CSA and UL

Contact
Rating
Code
Designation

Marking of
auxiliary
contacts
according to
CSA and UL

Max. rated values per pole
Voltage Current
Make
Break

A150
A300
A600
A600
N150
N300
N600
B150
B300
B600
B600
P150
P300
P600

-

AC 120
AC 240
AC 480
AC 600
DC 125
DC 250
DC 600
AC 120
AC 240
DC 125
DC 250
AC 120

Max. rated values per pole
Voltage Current
Make
Break

Cont.
Current

V

A

Heavy Duty
AC 120
(HD or HVY DTY) AC 240
AC 480
AC 600
DC 125
DC 250
DC 600
Standard Duty
AC 120
(SD or STD DTY) AC 240
AC 480
AC 600
DC 125
DC 250
DC 600

A
60
30
15
12
2,2
1,1
0,4
30
15
7,5
6
1,1
0,55
0,2

A
6
3
1,5
1,2
2,2
1,1
0,4
3
1,5
0,75
0,6
1,1
0,55
0,2

10
10
10
10
10
10
10
5
5
5
5
5
5
5

-

-

V

A
15
7,5
3,75
3
0,55
0,27
0,1
3,6
1,8
0,22
0,11
1,8

A
1,5
0,75
0,375
0,3
0,55
0,27
0,1
0,6
0,3
0,22
0,11
0,3

A

Contact
Rating
Code
Designation

2,5
2,5
2,5
2,5
2,5
2,5
2,5
1
1
1
1
0,5

C150
C300
C600
C600
Q150
Q300
Q600
D150
D300
R150
R300
E150

Cont.
Current

Appendix

H-93

LVSG

Country

OMRON Low voltage switchgear is also suitable for applications in
marine environments.

Discernment at UL-Standards
Recognized Component Industrial Control Equipment

Listed Industrial Control Equipment

UL issues yellow "Guide cards" with Guide- and File-No.

UL issues white "Guide cards" with Guide- and File-No.

Devices have permission to be marked with

Devices have to be marked with the "UL-Listing Mark"

on the label

Devices approved for "field wiring",
Devices as components approved for "factory wiring":
a) devices for employment in control panels, when they are mounted
devices for employment in control panels, when they are selected,
and wired by skilled worker.
mounted and wired according to the charging conditions by skilled worker.
b) devices for retail in USA
Valid UL-Standards:
UL 508„Standard for Industrial Control Equipment“
(partly limited)

Are devices approved as "Listed Equipment"

Valid UL-Standards:
UL 508„Standard for Industrial Control Equipment“
(unlimited)
UL 486"Standard for Wire Connectors and Soldering Lugs"

the approval is also valid for using as "Recognized Component" R.

Approvals
Country

USA, Canada

Switzerland

UL

SEV

Europe

Type

Register of Shipping

CENELEC
CB-Certificates

Great Britain
LRS

GUS
MRS

Italy
RINA

Mini Contactors J7KNA and Accessories
J7KNA-AR..(D)

o

-

-

o

-

-

-

o

J7KNA-09..(D)

o

-

-

o

-

-

-

o

J7KNA-12..(D)

o

-

-

o

-

-

-

-

J73KN-A..., J73KN-AM o

-

-

o

-

-

-

o

Contactors Series J7KN
J7KN-10...(D)

o

-

-

o

-

-

-

o

J7KN-14...(D)

o

-

-

o

-

-

-

o

J7KN-18...(D)

o

-

-

o

-

-

-

o

J7KN-22...(D)

o

-

-

o

-

-

-

o

J7KN-24...(D)

o

-

-

o

-

-

-

o

J7KN-32...(D)

o

-

-

o

-

-

-

o

J7KN-40...(D)

o

-

-

o

-

-

-

o

J7KN-50...(D)

o

-

-

o

-

-

-

o

J7KN-62...(D)

o

-

-

o

-

-

-

o

J7KN-74...(D)

o

-

-

o

-

-

-

o

J7KN-85...(D)

o

-

-

o

-

-

-

o

J7KN-110...(D)

o

-

-

o

-

-

-

o

J7KN-150...

-

-

-

o

-

-

-

-

J7KN-175...

-

-

-

o

-

-

-

-

J7KN-200...

-

-

-

o

-

-

-

-

J73N-KB...

o

-

-

o

-

-

-

o

J73N-KC-115

o

-

-

o

-

-

-

x

J74KN-B-PT...

o

-

-

o

-

-

-

-

J74KN-A-VG...

o

-

-

o

-

-

-

-

J74KN-B-VG

-

-

-

o

-

-

-

-

Accessories

Thermal Overload Relays
J7TKN-B

o

-

-

o

-

-

-

x

J7TKN-C

o

-

-

o

-

-

-

x

J7TKN-D

o

-

-

o

-

-

-

x

J7TKN-A

o

-

-

o

-

-

-

o

J7TKN-E

o

-

-

o

-

-

-

o

J7TKN-F

-

-

-

o

-

-

-

-

o In Standard version approved

H-94

Appendix

x In Test

- Not provided for test until now

and R-Guide- and File-No.
These data are important for UL-inspecting
Guide-No.

Kanada

USA

Kanada

USA

Contactors

NLDX7

NLDX

NLDX8

NLDX2

Accessories

NKCR7

NKCR

NKCR8

NKCR2

Thermal Overload Relays

NKCR7

NKCR

-

-

Circuit Breakers J7MN
as Manual Motor Controller

NLRV7

NLRV

-

-

Circuit Breakers J7MN
as Combination Motor Controller

NKJH7

NKJH

-

-

J7MN Bus Bar Assemblies

NLRV7

NLRV

-

-

J7MN Accessories

NKCR7

NKCR

-

-

LVSG

Devices

Appendix

H-95

■ Technical information
Degree of protection acc. to EN60947
Protection ratings are prefixed by the internationally agreed letters IP
followed by two digits.
1st digit:

Pertains to solid objects

2nd
digit

Short description

1

Protected against- Dripping water (vertically falling drops)
dripping water
shall have no harmful effect.

2

Protected against
dripping water
when tilted up to
15°

Vertically dripping water shall have no
harmful effect when the enclosure is tilted at any angle up to 15° from its normal position.

3

Protected against
spraying water

Water falling as a spray at an angle up
to 60° from the vertical shall have no
harmful effect.

4

Protected against
splashing water

Water splashed against the enclosure
from any direction shall have no harmful effect.

5

Protected against
water jets

Water protected by a nozzle against the
enclosure from any direction shall have
no harmful effect.

2nd digit: Pertains to water.
1st
digit

Short description

1

Protected against Excludes solid objects exceeding
solid objects great- 50 mm in diameter and protects against
er than 50 mm
contact with live and moving parts by a
large body surface such as a hand (but
not against deliberate access).

2L

Protected against
solid objects greater than 12,5 mm
and against contact
by standard test
finger

Definition

Excludes solid objects exceeding
12,5 mm in diameter and protects
against contact with live and moving
parts by a standard test finger or similar
objects not exceeding 80 mm in length.

Definition

3

Protected against Excludes solid objects exceeding
solid objects great- 2,5 mm in diameter or thickness.
er than 2,5 mm

6

Protected against
heavy seas

Water from heavy seas or water projected in powerful jets shall not enter
the enclosure in harmful quanties.

4

Protected against Excludes solid objects exceeding 1 mm
solid objects great- in diameter or thickness.
er than 1 mm

7

Protected against
the effects of immersion

5

Dust protected

Prevents ingress of dust in quantities
and locations that would interfere with
the intended operation of the equipment.

Ingress of water in a harmful quantity
shall not be possible when the enclosure is immersed in water under standard conditions of pressure and time.

8

Protected against
submersion

No ingress of water.

6

Dust tight

Prevents ingress of dust.

Terminal markings acc. to EN50011

Resistance to climatic conditions acc. to IEC 68

Auxiliary contacts of AC contactors and contacts of contactor relays
and thermal overload relays are particularly marked. The terminal
markings of normally-open contacts are printed as positive figures,
they of normally-closed contacts as negative figures.

Open-type devices are climate-resistant in the constant climate
according to IEC 68-2-3 (this is a climate with an ambient temperature of 40°C and an atmospheric humidity of 90 to 95%).

This gives a clear indication of the function of the contacts.
The figure below illustrates the determination of terminal markings
for contactors with auxiliary contact blocks.

Sequence number

Enclosed devices are climate-resistant in an alternating climate
according to IEC 68-2-30 (this is a moist alternating climate with a
24-hour cycle between climates with an ambient temperature of
25°C, and an atmospheric humidity of 95 to 100% and an ambient
temperature of 40°C, and an atmospheric humidity of 90 to 96% in
the presence of condensation during rises in temperature).
Data are valid up to an altitude of 2000m above sea level.

Short circuit protection
Function number

The complete terminal marking according
to EN 50011 and EN 50012 results from the
sequence numbers on the contactor relay
or ac contactor (2., 3.) and the function
numbers on the auxiliary contact blocks
(e. g. .1, .2, or .3, .4).

H-96

Appendix

Back up fuses should be used to protect contactors and starters
against short circuits. For starters the device with the smaller admissible fuse at the main and at the control circuit (contactor or thermal
overload) determines the fuse size.
After a short circuit devices have to be checked for correct operation.
Disconnect power before proceeding with any work on the equipment!

Mounting positions of contactors
J7KNA-AR... and J7KNA-12...

J7KN-10 to J7KN-74, J7KN-85 to J7KN-110

J7KN-150... to J7KN-200

Terminal screws
Devices

Kind of connection

Devices

Kind of connection

Type

Screw with
washer

Type

Screw with
washer

Screw with
clamp box

M3,5

-

Screw with
clamp box

Mini Contactors

Coil conductor

All conductors

J7KN-10... to J7KN-110...

J7KN-AR...; J7KNA-09...;
J7KNA-12...

Accessories

M3,5

-

Contactors
Main conductor

J73KNA(M)...

M3,5

-

J73KN-B, J73KN-C

M3,5

-

-

Thermal Overload Relays

J7KN-10... to J7KN-22...

M3,5

-

Main conductor

J7KN-24... to J7KN-40...

-

M5

J7TKN-A

M4

J7KN-50... to J7KN-74...

-

M6

J7TKN-B

M3,5

-

J7KN-85..., J7KN-110...

-

M8

J7TKN-C

M5

-

J7TKN-D

-

M6

J7KN-10... to J7KN-22...

M3,5

-

Auxiliary conductor

J7KN-85... to J7KN-110

M3,5

-

All devices

M3,5

-

Auxiliary conductor

Terminal screws in relation to screwdriver sizes and tightening torques
Pozidriv

Screw driver

Nm

lb. inch

Pz 1

Size 1

0,6 - 1,2

5 - 11

M3,5

Pz 2

Size 2, 3

0,8 - 1,4

7 - 12

M4

Pz 2

Size 3, 4

1,2 - 1,8

11 - 16

M5

Pz 2

Size 3, 4, 5

2,5 - 3

22 - 26

M6

Pz 3

Size 4, 5

3,5 - 4,5

31 - 40

M8

-

-

6 - 10

53 - 88

Version

Size

Screw with Pozidriv and slot

M3

Screw or
nut with hexagonal-head

Tightening torque

Appendix

LVSG

Terminal screws

H-97

● General technical information
■ Current carrying capacities of PVC insulated 600/1000 Volt cables
with copper or aluminium conductors.
In accordance with the 16th edition of the “Wiring Regulations for Electrical Installations“.
Basic assumptions: Ambient temperature of 30°C.
Circuit of protected by a OMRON circuit-breaker to IEC 947-2, or a fuse to BS 88 or BS 1361.
Figures must be adjusted by the correction factors for ambient temperature and/or cable grouping as detailed in the IEE regs.
Conductor In conduit or trunking (enclosed)
size
mm²

Clipped to surface or cable tray,
bunched, embedded in plaster
(unenclosed)

Fixed to vertical surface of wall or open
cable trench with 20 mm separation
between cables and wall

Single-phase

Three-phase

Single-phase

Three-phase

Single-phase

Three-phase

Cu [A]

Cu [A]

Cu [A]

Cu [A]

Cu [A]

Cu [A]

Al [A]

Al [A]

Al [A]

Al [A]

Al [A]

Al [A]

Single core, PVC insulated cable non-armoured, copper or aluminium conductors.
1.0

13.5

-

12.0

-

15.5

-

14.0

-

-

-

-

-

1.5

17.5

-

15.5

-

20.0

-

18.0

-

-

-

-

-

2.5

24.0

-

21.0

-

27.0

-

25.0

-

-

-

-

-

4.0

32.0

-

28.0

-

37.0

-

33.0

-

-

-

-

-

6.0

41.0

-

36.0

-

47.0

-

43.0

-

-

-

-

-

10.0

57.0

-

50.0

-

65.0

-

59.0

-

-

-

-

-

16.0

76.0

-

68.0

-

87.0

-

79.0

-

-

-

-

-

25.0

101.0

-

89.0

-

114.0

-

104.0

-

126.0

-

112.0

-

35.0

125.0

-

110.0

-

141.0

-

129.0

-

156.0

-

141.0

-

50.0

151.0

118.0

134.0

104.0

182.0

134.0

167.0

123.0

191.0

144.0

172.0

132.0

70.0

192.0

150.0

171.0

133.0

234.0

172.0

214.0

156.0

246.0

185.0

223.0

169.0

95.0

232.0

181.0

207.0

161.0

284.0

210.0

261.0

194.0

300.0

225.0

273.0

206.0

120.0

296.0

210.0

239.0

186.0

330.0

245.0

303.0

226.0

349.0

261.0

318.0

240.0

150.0

300.0

234.0

262.0

204.0

381.0

283.0

349.0

261.0

404.0

301.0

369.0

277.0

185.0

341.0

266.0

296.0

230.0

436.0

324.0

400.0

299.0

463.0

344.0

424.0

317.0

240.0

400.0

312.0

346.0

269.0

515.0

384.0

472.0

354.0

549.0

407.0

504.0

375.0

300.0

458.0

358.0

394.0

306.0

594.0

444.0

545.0

410.0

635.0

469.0

584.0

435.0

400.0

546.0

-

467.0

-

694.0

-

634.0

-

732.0

-

679.0

-

500.0

626.0

-

533.0

-

792.0

-

723.0

-

835.0

-

778.0

-

630.0

720.0

-

611.0

-

904.0

-

826.0

-

953.0

-

892.0

-

Twin and multi-core PVC insulated cable, non-armoured, copper or aluminium conductors.
1.0

11.0

-

11.5

-

15.0

-

13.5

-

17.0

-

14.5

-

1.5

14.0

-

15.0

-

19.5

-

17.5

-

22.0

-

18.5

-

2.5

18.5

-

20.0

-

27.0

-

24.0

-

30.0

-

25.0

-

4.0

25.0

-

27.0

-

36.0

-

32.0

-

40.0

-

34.0

-

6.0

32.0

-

34.0

-

46.0

-

41.0

-

51.0

-

43.0

-

10.0

43.0

-

46.0

-

63.0

-

57.0

-

70.0

-

60.0

-

16.0

57.0

54.0

62.0

48.0

85.0

66.0

76.0

59.0

94.0

73.0

80.0

61.0
78.0

25.0

75.0

71.0

80.0

62.0

112.0

83.0

96.0

73.0

119.0

89.0

101.0

35.0

92.0

86.0

99.0

77.0

138.0

103.0

119.0

90.0

148.0

111.0

126.0

96.0

50.0

110.0

104.0

118.0

92.0

168.0

125.0

144.0

110.0

180.0

135.0

153.0

117.0

70.0

139.0

131.0

149.0

116.0

213.0

160.0

184.0

140.0

232.0

173.0

196.0

150.0

95.0

167.0

157.0

179.0

139.0

258.0

195.0

261.0

170.0

282.0

210.0

238.0

183.0

120.0

192.0

-

206.0

160.0

299.0

245.0

259.0

197.0

328.0

-

276.0

212.0

150.0

219.0

-

225.0

184.0

344.0

283.0

299.0

227.0

379.0

-

319.0

245.0

185.0

248.0

-

255.0

210.0

392.0

324.0

341.0

259.0

434.0

-

364.0

280.0

240.0

291.0

-

297.0

248.0

461.0

384.0

403.0

305.0

514.0

-

430.0

330.0

300.0

334.0

-

339.0

258.0

530.0

444.0

464.0

351.0

593.0

-

497.0

381.0

400.0

-

-

402.0

-

634.0

-

557.0

-

715.0

-

597.0

-

H-98

Appendix

■ Overall diameter of cables (Copper)
The dimensions are based on BS specification or the average values as given by the manufacturers.
The overall diameters given are for cables of 600/1000 V grade.
Number and nominal Approx. overall diameter in mm
area of cables (mm2) PVC/SWA
PVC

Number and nominal Approx. overall diameter in mm
area of cables (mm2) PVC/SWA
PVC

1 x 1.0

-

4.5

2 x 1.0

-

1 x 1.5

-

4.9

2 x 1.5

11.7

-

1 x 2.5

-

5.8

2 x 2.5

13.1

8.6

1 x 4.0

-

6.8

2 x 4.0

15.1

10.7

7.2

1 x 6.0

-

7.4

2 x 6.0

16.5

12.0

1 x 10.0

-

8.8

2 x 10.0

20.1

14.9

1 x 16.0

-

10.5

2 x 16.0

21.9

17.2

1 x 25.0

-

12.5

2 x 25.0

23.0

18.4

1 x 35.0

-

13.5

2 x 35.0

24.9

20.1

1 x 50.0

19.1

15.1

2 x 50.0

27.8

22.8

1 x 70.0

21.1

16.9

2 x 70.0

30.4

25.5

1 x 95.0

23.4

19.4

2 x 95.0

35.5

29.3

1 x 120.0

26.3

21.0

2 x 120.0

38.0

31.8

1 x 150.0

28.3

23.2

2 x 150.0

41.3

35.1

1 x 185.0

30.8

25.8

2 x 185.0

46.4

39.1

1 x 240.0

34.1

29.0

2 x 240.0

51.2

43.9

1 x 300.0

37.0

32.1

2 x 300.0

56.4

48.7

1 x 400.0

42.0

35.8

2 x 400.0

61.9

54.2

1 x 500.0

45.6

39.6

-

-

-

1 x 630.0

49.7

43.8

-

-

-

3 x 1.0

-

3 x 1.5

12.3

3 x 2.5
3 x 4.0

Number and nominal Approx. overall diameter in mm
area of cables (mm2) PVC/SWA
PVC
-

4 x 1.0

-

7.6

4 x 1.5

13.0

8.3

-

13.6

9.1

4 x 2.5

14.5

10.0

15.8

11.5

4 x 4.0

17.8

12.6

3 x 6.0

18.0

12.8

4 x 6.0

19.2

14.2

3 x 10.0

21.2

15.8

4 x 10.0

22.8

17.7

3 x 16.0

23.1

19.7

4 x 16.0

26.3

20.6

3 x 25.0

25.0

20.4

4 x 25.0

27.8

22.9

3 x 35.0

27.3

22.4

4 x 35.0

30.5

25.4

3 x 50.0

30.5

25.5

4 x 50.0

35.4

29.2

3 x 70.0

35.0

28.7

4 x 70.0

39.2

33.0

3 x 95.0

39.3

33.3

4 x 95.0

44.3

38.3

3 x 120.0

42.2

36.3

4 x 120.0

49.3

41.8

3 x 150.0

47.5

40.0

4 x 150.0

53.6

46.3

3 x 185.0

51.9

44.6

4 x 185.0

59.0

61.3

3 x 240.0

57.8

50.1

4 x 240.0

65.7

58.0

3 x 300.0

63.2

55.6

4 x 300.0

72.0

64.6

3 x 400.0

69.6

62.2

4 x 400.0

81.3

72.0

Appendix

LVSG

Number and nominal Approx. overall diameter in mm
area of cables (mm2) PVC/SWA
PVC

H-99

■ Conversion table
To convert

Multiply by

Inches to millimeters (mm)

25.4

Millimeters to inches (In.)

0.03937

Feet to meters (m)

0.3048

Conversion table for:
Centigrade/Fahrenheit
BP-212

meters to feet (ft)

3.2808

200

Yards to meters (m)

0.9144

190

meters to yards (yd)

1.0936

180

Miles to kilometers (km)

1.6093

Kilometers to miles (mil.)

0.6214

Square inches to square millimeters (mm2)

645.16

160

0.00155

150

Square yards to square meters (m2)

0.8361

140

Square meters to square yards (yd2)

1.196

Cubic inches to cubic centimeters (cm3)

16.387

120

0.06102

Pounds to kilogrammes (kg)

0.4536

110

Kilogrammes to pounds (lb)

2.2046

100

1,016.05

Kilogrammes to tons (240 lb)

90

0.0009842

Ounces (avoirdpois) to grammes (g)

0.0353

70

Gallons to litres (l)

4.561

60

Litres to gallons

0.220

50

Force N (newtons) to lbft
1 N = 1 kg (mass) accelerated at 1 metre/sec.

0.225

1 Nm = 1 J (joule) to calorie

0.239

30

Horse-power to kilowatts (kW)

0.7458

20

Kilowatts to horse-power (h.p.)
1 W (watt) = 1J/s

1.3408

10

Atmospheres to lb per square inch (lb/inch2)
1 bar = 1 kg/cm2 = 735.6 mm Hg = 14.2 lb/inch2

FP-

14.68

Conversion table for mm²/AWG cable sizes
mm2

H-100

AWG
0.75

18

1.0

17

1.5

16

2.5

13

4.0

12

6.0

10

10.0

8

Appendix

70
60
50
40
30

80

28.3495

Grammes to ounces

80

130

Cubic centimeters to cubic inches (inch3)

Tons (2,240 lb) to kilogrammes (kg)

90

170

Square millimeters to square inches (inch )

2

100

40

0
F

20
10
0
10
20
C

■ Rated currents of 3-phase motors (approx. figures for squirrel-cage motors)
Minimum fuse size for protection of 3-phase motors
The maximum size is determined by the requirements of the switchgear or overload relay.
The rated motor currents are for standard 1500 r.p.m. 3-phase enclosed ventilated and totally enclosed fan-cooled motors.
D.O.L. starting: Maximum starting current 6 x rated motor current. Maximum starting time 5 s.
Y/D starting:
Maximum starting current 2 x rated motor current. Maximum starting time 15 s.
Set overload relay in the phase lead to 0.58 x rated motor current.
Rated fuse currents for Y/D starting are also valid for 3-phase motors with slip-ring motors.
For higher rated currents, starting currents and/or longer starting times, larger fuses are required.
Table is valid for “slow” and/or “gL” fuses (DIN VDE 0636).

For NH fuses with aM characteristics, fuses = rated current is selected.

cos ϕ

kW

η%

400 V

Rated
motor
current

Fuse
starting
D.O.L.

A

A

415 V

Y/∆

Rated
motor
current

Fuse
starting
D.O.L.

Y/∆

Rated
motor
current

Fuse
starting
D.O.L.

Y/∆

A

A

A

A

A

A, BS

A, BS

0.06

0.7

58

0.37

2.0

-

0.21

2.0

-

0.21

2.0

2

0.09

0.7

60

0.54

2.0

-

0.31

2.0

-

0.30

2.0

2

0.12

0.7

60

0.72

4.0

2

0.41

2.0

-

0.40

2.0

2

0.18

0.7

62

1.04

4.0

2

0.6

2.0

-

0.58

2.0

2

0.25

0.7

62

1.4

4.0

2

0.8

4.0

2

0.8

4.0

2

0.37

0.72

66

2.0

6.0

4

1.1

4.0

2

1.1

4.0

2

0.55

0.75

69

2.7

10.0

4

1.5

4.0

2

1.5

6.0

4

0.75

0.79

74

3.2

10.0

4

1.9

6.0

4

1.8

6.0

4

1.1

0.81

74

4.6

10.0

6

2.6

6.0

4

2.6

10.0

6

1.5

0.81

74

6.3

16.0

10

3.6

6.0

4

3.5

16.0

10

2.2

0.81

78

8.7

20.0

10

5.0

10.0

6

4.8

16.0

10

3.0

0.82

80

11.5

25.0

16

6.6

16.0

10

6.4

20.0

16

4.0

0.82

83

14.8

32.0

16

8.5

20.0

10

8.2

20.0

16

5.5

0.82

86

19.6

32.0

25

11.3

25.0

16

10.9

25.0

20

7.5

0.82

87

26.4

50.0

32

15.2

32.0

16

14.6

35.0

25

11.0

0.84

87

38.0

80.0

40

21.7

40.0

25

20.9

50.0

32

15.0

0.84

88

51.0

100.0

63

29.3

63.0

32

28.2

80.0

40

18.5

0.84

88

63.0

125.0

80

36.0

63.0

40

35.0

80.0

50

22.0

0.84

92

71.0

125.0

80

41.0

80.0

50

40.0

80.0

50

30.0

0.85

92

96.0

200.0

100

55.0

100.0

63

53.0

100.0

80

37.0

0.86

92

117.0

200.0

125

68.0

125.0

80

65.0

125.0

80

45.0

0.86

93

141.0

250.0

160

81.0

160.0

100

78.0

125.0

80

55.0

0.86

93

173.0

250.0

200

99.0

200.0

125

96.0

160.0

100

75.0

0.86

94

233.0

315.0

250

134.0

200.0

160

129.0

250.0

160

90.0

0.86

94

279.0

400.0

315

161.0

250.0

200

155.0

250.0

160

110.0

0.86

94

342.0

500.0

400

196.0

315.0

200

189.0

315.0

200

132.0

0.87

95

401.0

630.0

500

231.0

400.0

250

222.0

355.0

250

160.0

0.87

95

486.0

630.0

630

279.0

400.0

315

269.0

355.0

315

200.0

0.87

95

607.0

800.0

630

349.0

500.0

400

337.0

450.0

355

250.0

0.87

95

-

-

-

437.0

630.0

500

421.0

500.0

450

315.0

0.87

96

-

-

-

544.0

800.0

630

525.0

630.0

560

400.0

0.88

96

-

-

-

683.0

1000.0

800

-

-

-

450.0

0.88

96

-

-

-

769.0

1000.0

800

-

-

-

500.0

0.88

97

-

-

-

-

-

-

-

-

-

560.0

0.88

97

-

-

-

-

-

-

-

-

-

630.0

0.88

97

-

-

-

-

-

-

-

-

-

Appendix

H-101

LVSG

230 V
Motor rating

Minimum fuse size for protection of 3-phase motors
The maximum size is determined by the requirements of the switchgear or overload relay.
The rated motor currents are for standard 1500 r.p.m. 3-phase enclosed ventilated and totally enclosed fan-cooled motors.
D.O.L. starting: Maximum starting current 6 x rated motor current. Maximum starting time 5 s.
Y/D starting:
Maximum starting current 2 x rated motor current. Maximum starting time 15 s.
Set overload relay in the phase lead to 0.58 x rated motor current.
Rated fuse currents for Y/D starting are also valid for 3-phase motors with slip-ring motors.
For higher rated currents, starting currents and/or longer starting times, larger fuses are required.
Table is valid for “slow” and/or “gL” fuses (DIN VDE 0636).

For NH fuses with aM characteristics, fuses = rated current is selected.
500 V
Motor rating
cos ϕ

kW

η%

600 V

Rated
motor
current

Fuse
starting Y/∆
D.O.L.

A

A

A

Rated
motor
current

Fuse
starting Y/∆
D.O.L.

A

A

A

0.06

0.7

58

0.17

2.0

-

0.12

2.0

-

0.09

0.7

60

0.25

2.0

-

0.18

2.0

-

0.12

0.7

60

0.33

2.0

-

0.24

2.0

-

0.18

0.7

62

0.48

2.0

-

0.35

2.0

-

0.25

0.7

62

0.70

2.0

-

0.50

2.0

-

0.37

0.72

66

0.90

2.0

2

0.70

2.0

-

0.55

0.75

69

1.20

4.0

2

0.90

4.0

2

0.75

0.79

74

1.50

4.0

2

1.10

4.0

2

1.1

0.81

74

2.1

6.0

4

1.5

4.0

2

1.5

0.81

74

2.9

6.0

4

2.1

6.0

4

2.2

0.81

78

4.0

10.0

4

2.9

10.0

4

3.0

0.82

80

5.3

16.0

6

3.8

10.0

4

4.0

0.82

83

6.8

16.0

10

4.9

16.0

6

5.5

0.82

86

9.0

20.0

16

6.5

16.0

10

7.5

0.82

87

12.1

25.0

16

8.8

20.0

10

11.0

0.84

87

17.4

32.0

20

12.6

25.0

16

15.0

0.84

88

23.4

50.0

25

17.0

32.0

20

18.5

0.84

88

28.9

50.0

32

20.9

32.0

25

22.0

0.84

92

33.0

63.0

32

23.8

50.0

25

30.0

0.85

92

44.0

80.0

50

32.0

63.0

32

37.0

0.86

92

54.0

100.0

63

39.0

80.0

50

45.0

0.86

93

65.0

125.0

80

47.0

80.0

63

55.0

0.86

93

79.0

160.0

80

58.0

100.0

63

75.0

0.86

94

107.0

200.0

125

78.0

160.0

100

90.0

0.86

94

129.0

200.0

160

93.0

160.0

100

110.0

0.86

94

157.0

250.0

160

114.0

200.0

125

132.0

0.87

95

184.0

250.0

200

134.0

250.0

160

160.0

0.87

95

224.0

315.0

250

162.0

250.0

200

200.0

0.87

95

279.0

400.0

315

202.0

315.0

250

250.0

0.87

95

349.0

500.0

400

253.0

400.0

315

315.0

0.87

96

436.0

630.0

500

316.0

500.0

400

400.0

0.88

96

547.0

800.0

630

396.0

630.0

400

450.0

0.88

96

615.0

800.0

630

446.0

630.0

630

500.0

0.88

97

-

-

-

491.0

630.0

630

560.0

0.88

97

-

-

-

550.0

800.0

630

630.0

0.88

97

-

-

-

618.0

800.0

630

H-102

Appendix

&HUWDLQ7HUPVDQG&RQGLWLRQVRI6DOH
 2IIHU $FFHSWDQFH 7KHVH WHUPV DQG FRQGLWLRQV WKHVH 7HUPV DUH GHHPHG
SDUWRIDOOFDWDORJVPDQXDOVRURWKHUGRFXPHQWVZKHWKHUHOHFWURQLFRULQZULW
LQJ UHODWLQJ WR WKH VDOH RI JRRGV RU VHUYLFHV FROOHFWLYHO\ WKH *RRGV E\
2PURQ(OHFWURQLFV//&DQGLWVVXEVLGLDU\FRPSDQLHV6HOOHU6HOOHUKHUHE\
REMHFWVWRDQ\WHUPVRUFRQGLWLRQVSURSRVHGLQ%X\HU
VSXUFKDVHRUGHURURWKHU
GRFXPHQWVZKLFKDUHLQFRQVLVWHQWZLWKRULQDGGLWLRQWRWKHVH7HUPV3OHDVH
FRQWDFW \RXU 2PURQ UHSUHVHQWDWLYH WR FRQILUP DQ\ DGGLWLRQDO WHUPV IRU VDOHV
IURP\RXU2PURQFRPSDQ\
 3ULFHV  $OO SULFHV VWDWHG DUH FXUUHQW VXEMHFW WR FKDQJH ZLWKRXW QRWLFH E\
6HOOHU%X\HUDJUHHVWRSD\WKHSULFHLQHIIHFWDWWLPHRIVKLSPHQW
 'LVFRXQWV  &DVK GLVFRXQWV LI DQ\ ZLOO DSSO\ RQO\ RQ WKH QHW DPRXQW RI
LQYRLFHV VHQW WR %X\HU DIWHU GHGXFWLQJ WUDQVSRUWDWLRQ FKDUJHV WD[HV DQG
GXWLHVDQGZLOOEHDOORZHGRQO\LILWKHLQYRLFHLVSDLGDFFRUGLQJWR6HOOHU
V
SD\PHQWWHUPVDQGLL%X\HUKDVQRSDVWGXHDPRXQWVRZLQJWR6HOOHU
 2UGHUV6HOOHUZLOODFFHSWQRRUGHUOHVVWKDQQHWELOOLQJ
 *RYHUQPHQWDO $SSURYDOV  %X\HU VKDOO EH UHVSRQVLEOH IRU DQG VKDOO EHDU DOO
FRVWVLQYROYHGLQREWDLQLQJDQ\JRYHUQPHQWDSSURYDOVUHTXLUHGIRUWKHLPSRU
WDWLRQRUVDOHRIWKH*RRGV
 7D[HV$OOWD[HVGXWLHVDQGRWKHUJRYHUQPHQWDOFKDUJHVRWKHUWKDQJHQHUDO
UHDO SURSHUW\ DQG LQFRPH WD[HV LQFOXGLQJ DQ\ LQWHUHVW RU SHQDOWLHV WKHUHRQ
LPSRVHGGLUHFWO\ RULQGLUHFWO\RQ 6HOOHU RUUHTXLUHGWR EHFROOHFWHGGLUHFWO\RU
LQGLUHFWO\E\6HOOHUIRUWKHPDQXIDFWXUHSURGXFWLRQVDOHGHOLYHU\LPSRUWDWLRQ
FRQVXPSWLRQ RU XVH RI WKH *RRGV VROG KHUHXQGHU LQFOXGLQJ FXVWRPV GXWLHV
DQG VDOHV H[FLVH XVH WXUQRYHU DQG OLFHQVH WD[HV VKDOO EH FKDUJHG WR DQG
UHPLWWHGE\%X\HUWR6HOOHU
 )LQDQFLDO,IWKHILQDQFLDOSRVLWLRQRI%X\HUDWDQ\WLPHEHFRPHVXQVDWLVIDFWRU\
WR 6HOOHU 6HOOHU UHVHUYHV WKH ULJKW WR VWRS VKLSPHQWV RU UHTXLUH VDWLVIDFWRU\
VHFXULW\RUSD\PHQWLQDGYDQFH,I%X\HUIDLOVWRPDNHSD\PHQWRURWKHUZLVH
FRPSO\ZLWKWKHVH7HUPVRUDQ\UHODWHGDJUHHPHQW6HOOHUPD\ZLWKRXWOLDELOLW\
DQGLQDGGLWLRQWRRWKHUUHPHGLHVFDQFHODQ\XQVKLSSHGSRUWLRQRI*RRGVVROG
KHUHXQGHUDQGVWRSDQ\*RRGVLQWUDQVLWXQWLO%X\HUSD\VDOODPRXQWVLQFOXG
LQJDPRXQWVSD\DEOHKHUHXQGHUZKHWKHURUQRWWKHQGXHZKLFKDUHRZLQJWRLW
E\%X\HU%X\HUVKDOOLQDQ\HYHQWUHPDLQOLDEOHIRUDOOXQSDLGDFFRXQWV
 &DQFHOODWLRQ (WF 2UGHUV DUH QRW VXEMHFW WR UHVFKHGXOLQJ RU FDQFHOODWLRQ
XQOHVV%X\HU LQGHPQLILHV6HOOHUIXOO\DJDLQVWDOOFRVWV RUH[SHQVHVDULVLQJLQ
FRQQHFWLRQWKHUHZLWK
 )RUFH 0DMHXUH  6HOOHU VKDOO QRW EH OLDEOH IRU DQ\ GHOD\ RU IDLOXUH LQ GHOLYHU\
UHVXOWLQJIURPFDXVHVEH\RQGLWVFRQWUROLQFOXGLQJHDUWKTXDNHVILUHVIORRGV
VWULNHV RU RWKHU ODERU GLVSXWHV VKRUWDJH RI ODERU RU PDWHULDOV DFFLGHQWV WR
PDFKLQHU\ DFWV RI VDERWDJH ULRWV GHOD\ LQ RU ODFN RI WUDQVSRUWDWLRQ RU WKH
UHTXLUHPHQWVRIDQ\JRYHUQPHQWDXWKRULW\
 6KLSSLQJ'HOLYHU\8QOHVVRWKHUZLVHH[SUHVVO\DJUHHGLQZULWLQJE\6HOOHU
D 6KLSPHQWVVKDOOEHE\DFDUULHUVHOHFWHGE\6HOOHU
E 6XFKFDUULHUVKDOODFWDVWKHDJHQWRI%X\HUDQGGHOLYHU\WRVXFKFDUULHU
VKDOOFRQVWLWXWHGHOLYHU\WR%X\HU
F $OOVDOHVDQGVKLSPHQWVRI*RRGVVKDOOEH)2%VKLSSLQJSRLQWXQOHVVRWK
HUZLVHVWDWHGLQZULWLQJE\6HOOHUDWZKLFKSRLQWWLWOHWRDQGDOOULVNRIORVVRI
WKH*RRGVVKDOOSDVVIURP6HOOHUWR%X\HUSURYLGHGWKDW6HOOHUVKDOOUHWDLQD
VHFXULW\LQWHUHVWLQWKH*RRGVXQWLOWKHIXOOSXUFKDVHSULFHLVSDLGE\%X\HU
G 'HOLYHU\DQGVKLSSLQJGDWHVDUHHVWLPDWHVRQO\
H 6HOOHUZLOOSDFNDJH*RRGVDVLWGHHPVSURSHUIRUSURWHFWLRQDJDLQVWQRUPDO
KDQGOLQJDQGH[WUDFKDUJHVDSSO\WRVSHFLDOFRQGLWLRQV
 &ODLPV  $Q\ FODLP E\ %X\HU DJDLQVW 6HOOHU IRU VKRUWDJH RU GDPDJH WR WKH
*RRGVRFFXUULQJEHIRUHGHOLYHU\WRWKHFDUULHUPXVWEHSUHVHQWHGLQZULWLQJWR
6HOOHUZLWKLQGD\VRIUHFHLSWRIVKLSPHQWDQGLQFOXGHWKHRULJLQDOWUDQVSRUWD
WLRQELOOVLJQHGE\WKHFDUULHUQRWLQJWKDWWKHFDUULHUUHFHLYHGWKH*RRGVIURP
6HOOHULQWKHFRQGLWLRQFODLPHG

 :DUUDQWLHV  D ([FOXVLYH :DUUDQW\  6HOOHU
V H[FOXVLYH ZDUUDQW\ LV WKDW WKH
*RRGVZLOOEHIUHHIURPGHIHFWVLQPDWHULDOVDQGZRUNPDQVKLSIRUDSHULRGRI
WZHOYHPRQWKVIURPWKHGDWHRIVDOHE\6HOOHURUVXFKRWKHUSHULRGH[SUHVVHG
LQZULWLQJE\6HOOHU6HOOHUGLVFODLPVDOORWKHUZDUUDQWLHVH[SUHVVRULPSOLHG
E/LPLWDWLRQV6(//(50$.(612:$55$17<255(35(6(17$7,21
(;35(66 25 ,03/,(' $%287 121,1)5,1*(0(17 0(5&+$17$%,/
,7< 25 ),71(66 )25 $ 3$57,&8/$5 385326( 2) 7+( *22'6
%8<(5$&.12:/('*(67+$7,7$/21(+$6'(7(50,1('7+$77+(
*22'6 :,// 68,7$%/< 0((7 7+( 5(48,5(0(176 2) 7+(,5
,17(1'('86(6HOOHUIXUWKHUGLVFODLPVDOOZDUUDQWLHVDQGUHVSRQVLELOLW\RI
DQ\W\SHIRUFODLPVRUH[SHQVHVEDVHGRQLQIULQJHPHQWE\WKH*RRGVRURWKHU
ZLVHRIDQ\LQWHOOHFWXDOSURSHUW\ULJKWF%X\HU5HPHG\6HOOHU
VVROHREOLJD
WLRQ KHUHXQGHU VKDOO EH WR UHSODFH LQ WKH IRUP RULJLQDOO\ VKLSSHG ZLWK %X\HU
UHVSRQVLEOH IRU ODERU FKDUJHV IRU UHPRYDO RU UHSODFHPHQW WKHUHRI WKH QRQ
FRPSO\LQJ *RRG RU DW 6HOOHU
V HOHFWLRQ WR UHSD\ RU FUHGLW %X\HU DQ DPRXQW
HTXDOWRWKHSXUFKDVHSULFHRIWKH*RRGSURYLGHGWKDWLQQRHYHQWVKDOO6HOOHU
EHUHVSRQVLEOHIRUZDUUDQW\UHSDLULQGHPQLW\RUDQ\RWKHUFODLPVRUH[SHQVHV
UHJDUGLQJ WKH *RRGV XQOHVV 6HOOHU
V DQDO\VLV FRQILUPV WKDW WKH *RRGV ZHUH
SURSHUO\KDQGOHGVWRUHGLQVWDOOHGDQGPDLQWDLQHGDQGQRWVXEMHFWWRFRQWDPL
QDWLRQDEXVHPLVXVHRULQDSSURSULDWHPRGLILFDWLRQ5HWXUQRIDQ\JRRGVE\
%X\HUPXVWEHDSSURYHGLQZULWLQJE\6HOOHUEHIRUHVKLSPHQW6HOOHUVKDOOQRW
EHOLDEOHIRUWKHVXLWDELOLW\RUXQVXLWDELOLW\RUWKHUHVXOWVIURPWKHXVHRI*RRGV
LQ FRPELQDWLRQ ZLWK DQ\ HOHFWULFDO RU HOHFWURQLF FRPSRQHQWV FLUFXLWV V\VWHP
DVVHPEOLHV RU DQ\ RWKHU PDWHULDOV RU VXEVWDQFHV RU HQYLURQPHQWV  $Q\
DGYLFHUHFRPPHQGDWLRQVRULQIRUPDWLRQJLYHQRUDOO\RULQZULWLQJDUHQRWWREH
FRQVWUXHGDVDQDPHQGPHQWRUDGGLWLRQWRWKHDERYHZDUUDQW\
 'DPDJH/LPLWV(WF6(//(56+$//127%(/,$%/()2563(&,$/,1',
5(&7 25 &216(48(17,$/ '$0$*(6 /266 2) 352),76 25 352
'8&7,2125&200(5&,$//266,1$1<:$<&211(&7(':,7+7+(
*22'6:+(7+(568&+&/$,0,6%$6(',1&2175$&7:$55$17<
1(*/,*(1&( 25 675,&7 /,$%,/,7<  )XUWKHU LQ QR HYHQW VKDOO OLDELOLW\ RI
6HOOHUH[FHHGWKHLQGLYLGXDOSULFHRIWKH*RRGRQZKLFKOLDELOLW\LVDVVHUWHG
 ,QGHPQLWLHV%X\HUVKDOOLQGHPQLI\DQGKROGKDUPOHVV6HOOHULWVDIILOLDWHVDQG
LWV HPSOR\HHV IURP DQG DJDLQVW DOO OLDELOLWLHV ORVVHV FODLPV FRVWV DQG
H[SHQVHVLQFOXGLQJDWWRUQH\
VIHHVDQGH[SHQVHVUHODWHGWRDQ\FODLPLQYHV
WLJDWLRQOLWLJDWLRQRUSURFHHGLQJZKHWKHURUQRW6HOOHULVDSDUW\ZKLFKDULVHV
RULVDOOHJHGWRDULVHIURP%X\HU
VDFWVRURPLVVLRQVXQGHUWKHVH7HUPVRULQ
DQ\ZD\ZLWKUHVSHFWWRWKH*RRGV:LWKRXWOLPLWLQJWKHIRUHJRLQJ%X\HUDW
LWVRZQH[SHQVHVKDOOLQGHPQLI\DQGKROGKDUPOHVV6HOOHUDQGGHIHQGRUVHWWOH
DQ\DFWLRQEURXJKWDJDLQVW6HOOHUWRWKHH[WHQWWKDWLWLVEDVHGRQDFODLPWKDW
DQ\*RRGPDGHWR%X\HUVSHFLILFDWLRQVLQIULQJHGLQWHOOHFWXDOSURSHUW\ULJKWVRI
DQRWKHUSDUW\
 3URSHUW\&RQILGHQWLDOLW\7KHLQWHOOHFWXDOSURSHUW\HPERGLHGLQWKH*RRGVLV
WKHH[FOXVLYHSURSHUW\RI6HOOHUDQGLWVDIILOLDWHVDQG%X\HUVKDOOQRWDWWHPSWWR
GXSOLFDWHLWLQDQ\ZD\ZLWKRXWWKHZULWWHQSHUPLVVLRQRI6HOOHU1RWZLWKVWDQG
LQJDQ\FKDUJHVWR%X\HUIRUHQJLQHHULQJRUWRROLQJDOOHQJLQHHULQJDQGWRROLQJ
VKDOO UHPDLQ WKH H[FOXVLYH SURSHUW\ RI 6HOOHU  $OO LQIRUPDWLRQ DQG PDWHULDOV
VXSSOLHGE\6HOOHUWR%X\HUUHODWLQJWRWKH*RRGVDUHFRQILGHQWLDODQGSURSUL
HWDU\ DQG %X\HU VKDOO OLPLW GLVWULEXWLRQ WKHUHRI WR LWV WUXVWHG HPSOR\HHV DQG
VWULFWO\SUHYHQWGLVFORVXUHWRDQ\WKLUGSDUW\
0LVFHOODQHRXVD:DLYHU1RIDLOXUHRUGHOD\E\6HOOHULQH[HUFLVLQJDQ\ULJKW
DQGQRFRXUVHRIGHDOLQJEHWZHHQ%X\HUDQG6HOOHUVKDOORSHUDWHDVDZDLYHU
RIULJKWVE\6HOOHUE$VVLJQPHQW%X\HUPD\QRWDVVLJQLWVULJKWVKHUHXQGHU
ZLWKRXW6HOOHU
VZULWWHQFRQVHQWF$PHQGPHQW7KHVH7HUPVFRQVWLWXWHWKH
HQWLUHDJUHHPHQWEHWZHHQ%X\HUDQG6HOOHUUHODWLQJWRWKH*RRGVDQGQRSUR
YLVLRQPD\EHFKDQJHGRUZDLYHGXQOHVVLQZULWLQJVLJQHGE\WKHSDUWLHV
G6HYHUDELOLW\,IDQ\SURYLVLRQKHUHRILVUHQGHUHGLQHIIHFWLYHRULQYDOLGVXFK
SURYLVLRQVKDOOQRWLQYDOLGDWHDQ\RWKHUSURYLVLRQH6HWRII%X\HUVKDOOKDYH
QR ULJKW WR VHW RII DQ\ DPRXQWV DJDLQVW WKH DPRXQW RZLQJ LQ UHVSHFW RI WKLV
LQYRLFHI$VXVHGKHUHLQLQFOXGLQJPHDQVLQFOXGLQJZLWKRXWOLPLWDWLRQ

&HUWDLQ3UHFDXWLRQVRQ6SHFLILFDWLRQVDQG8VH
 6XLWDELOLW\RI8VH6HOOHUVKDOOQRWEHUHVSRQVLEOHIRUFRQIRUPLW\ZLWKDQ\VWDQ
GDUGVFRGHVRUUHJXODWLRQVZKLFKDSSO\WRWKHFRPELQDWLRQRIWKH*RRGLQWKH
%X\HU
VDSSOLFDWLRQRUXVHRIWKH*RRG$W%X\HU
VUHTXHVW6HOOHUZLOOSURYLGH
DSSOLFDEOHWKLUGSDUW\FHUWLILFDWLRQGRFXPHQWVLGHQWLI\LQJUDWLQJVDQGOLPLWDWLRQV
RIXVHZKLFKDSSO\WRWKH*RRG7KLVLQIRUPDWLRQE\LWVHOILVQRWVXIILFLHQWIRUD
FRPSOHWH GHWHUPLQDWLRQ RI WKH VXLWDELOLW\ RI WKH *RRGLQ FRPELQDWLRQZLWK WKH
HQGSURGXFWPDFKLQHV\VWHPRURWKHUDSSOLFDWLRQRUXVH7KHIROORZLQJDUH
VRPH H[DPSOHV RI DSSOLFDWLRQV IRU ZKLFK SDUWLFXODU DWWHQWLRQ PXVW EH JLYHQ
7KLVLVQRWLQWHQGHGWREHDQH[KDXVWLYHOLVWRIDOOSRVVLEOHXVHVRIWKLV*RRG
QRULVLWLQWHQGHGWRLPSO\WKDWWKHXVHVOLVWHGPD\EHVXLWDEOHIRUWKLV*RRG
L 2XWGRRUXVHXVHVLQYROYLQJSRWHQWLDOFKHPLFDOFRQWDPLQDWLRQRUHOHFWULFDO
LQWHUIHUHQFHRUFRQGLWLRQVRUXVHVQRWGHVFULEHGLQWKLVGRFXPHQW
LL (QHUJ\FRQWUROV\VWHPVFRPEXVWLRQV\VWHPVUDLOURDGV\VWHPVDYLDWLRQ
V\VWHPVPHGLFDOHTXLSPHQWDPXVHPHQWPDFKLQHVYHKLFOHVVDIHW\
HTXLSPHQWDQGLQVWDOODWLRQVVXEMHFWWRVHSDUDWHLQGXVWU\RUJRYHUQPHQW
UHJXODWLRQV
LLL 6\VWHPVPDFKLQHVDQGHTXLSPHQWWKDWFRXOGSUHVHQWDULVNWROLIHRU
SURSHUW\3OHDVHNQRZDQGREVHUYHDOOSURKLELWLRQVRIXVHDSSOLFDEOHWR
WKLV*RRG
1(9(586(7+(352'8&7)25$1$33/,&$7,21,192/9,1*6(5,286
5,6.72/,)(253523(57<:,7+287(1685,1*7+$77+(6<67(0
$6$:+2/(+$6%((1'(6,*1('72$''5(667+(5,6.6$1'7+$7
7+( 6(//(5
6 352'8&7 ,6 3523(5/< 5$7(' $1' ,167$//(' )25
7+(,17(1'('86(:,7+,17+(29(5$//(48,30(17256<67(0

 3URJUDPPDEOH 3URGXFWV  6HOOHU VKDOO QRW EH UHVSRQVLEOH IRU WKH XVHU
V SUR
JUDPPLQJRIDSURJUDPPDEOH*RRGRUDQ\FRQVHTXHQFHWKHUHRI
 3HUIRUPDQFH 'DWD  3HUIRUPDQFH GDWD JLYHQ LQ WKLV FDWDORJ LV SURYLGHG DV D
JXLGHIRUWKHXVHULQGHWHUPLQLQJVXLWDELOLW\DQGGRHVQRWFRQVWLWXWHDZDUUDQW\
,WPD\UHSUHVHQWWKHUHVXOWRI6HOOHU
VWHVWFRQGLWLRQVDQGWKHXVHUPXVWFRUUH
ODWHLWWRDFWXDODSSOLFDWLRQUHTXLUHPHQWV$FWXDOSHUIRUPDQFHLVVXEMHFWWRWKH
6HOOHU
V:DUUDQW\DQG/LPLWDWLRQVRI/LDELOLW\
 &KDQJH LQ 6SHFLILFDWLRQV  3URGXFW VSHFLILFDWLRQV DQG DFFHVVRULHV PD\ EH
FKDQJHGDWDQ\WLPHEDVHGRQLPSURYHPHQWVDQGRWKHUUHDVRQV,WLVRXUSUDF
WLFHWRFKDQJHSDUWQXPEHUVZKHQSXEOLVKHGUDWLQJVRUIHDWXUHVDUHFKDQJHG
RUZKHQVLJQLILFDQWFRQVWUXFWLRQFKDQJHVDUHPDGH+RZHYHUVRPHVSHFLILFD
WLRQVRIWKH*RRGPD\EHFKDQJHGZLWKRXWDQ\QRWLFH:KHQLQGRXEWVSHFLDO
SDUW QXPEHUV PD\ EH DVVLJQHG WR IL[ RU HVWDEOLVK NH\ VSHFLILFDWLRQV IRU \RXU
DSSOLFDWLRQ  3OHDVH FRQVXOW ZLWK \RXU 6HOOHU
V UHSUHVHQWDWLYH DW DQ\ WLPH WR
FRQILUPDFWXDOVSHFLILFDWLRQVRISXUFKDVHG*RRG
 (UURUV DQG 2PLVVLRQV  7KH LQIRUPDWLRQ LQ WKLV FDWDORJ KDV EHHQ FDUHIXOO\
FKHFNHGDQGLVEHOLHYHGWREHDFFXUDWHKRZHYHUQRUHVSRQVLELOLW\LVDVVXPHG
IRUFOHULFDOW\SRJUDSKLFDORUSURRIUHDGLQJHUURUVRURPLVVLRQV

&RPSOHWH¦7HUPVDQG&RQGLWLRQVRI6DOH§IRUSURGXFWSXUFKDVHDQGXVHDUHRQ2PURQ©VZHEVLWH
DWZZZRPURQFRPRHL¤XQGHUWKH¦$ERXW8V§WDELQWKH/HJDO0DWWHUVVHFWLRQ
$//',0(16,2166+2:1$5(,10,//,0(7(56

7RFRQYHUWPLOOLPHWHUVLQWRLQFKHVPXOWLSO\E\7RFRQYHUWJUDPVLQWRRXQFHVPXOWLSO\E\

20521(/(&7521,&6//&

20521&$1$'$,1&





2QH&RPPHUFH'ULYH
6FKDXPEXUJ,/

)RU86WHFKQLFDOVXSSRUWRURWKHULQTXLULHV

0LOQHU$YHQXH
7RURQWR2QWDULR0%9

2052121/,1(
*OREDOKWWSZZZRPURQFRP
86$KWWSZZZRPURQFRPRHL
&DQDGDKWWSZZZRPURQFD


Cat. No. J7cntctr

09/04

Specifications subject to change without notice

Printed in USA

Mouser Electronics
Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:
J7KNA-09-10 230 J73KN-A-02 J73KN-A-22 J7KN-24 24D J7KN-40 230 J7KNA-09-01 24D J7KNA-09-01W 24
J7KNA-12-01 24VS J7KNA-AR-22 110 J7KNA-AR-22 125VS J7KNA-AR-22 230 J7KNA-AR-22 24 J7KNA-AR-22
24VS J7KNA-AR-31 110 J7KNA-AR-31 230 J7KNA-AR-31 24 J7KNA-AR-31 24VS J7KNA-AR-40 230 J7KNA-AR40 24 J7KNA-AR-40 24VS J7TKN-A-11 J7TKN-A-1E2 J7TKN-A-1E8 J7TKN-A-23 J7TKN-A-2E7 J7TKN-A-30
J7TKN-A-6 J7TKN-A-E6 J7TKN-A-E9 J7TKN-B-11 J7TKN-B-18 J7TKN-B-1E8 J7TKN-B-24 J7TKN-B-4 J7TKN-C42 J7KN-62 24D J7TKN-B-6



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Page Count                      : 105
Page Mode                       : UseOutlines
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:9d5d6c0d-6ddc-4db2-a89c-cf4853626209
Producer                        : Acrobat Distiller 5.0.5 (Windows)
Create Date                     : 2003:03:24 14:35:22Z
Modify Date                     : 2004:09:03 13:44:26-05:00
Metadata Date                   : 2004:09:03 13:44:26-05:00
Document ID                     : uuid:e6da49f6-25f5-4d61-b922-0e042abd5ee0
Format                          : application/pdf
Title                           : J7 Low Voltage Switch Gear Data Sheet
Description                     : J7 Data Sheet
Creator                         : Omron Electronics
Author                          : Omron Electronics
Subject                         : J7 Data Sheet
EXIF Metadata provided by EXIF.tools

Navigation menu