C60_24338
2014-06-03
: Pdf 557149-Attachment 557149-Attachment 785901 Batch4 unilog
Open the PDF directly: View PDF .
Page Count: 1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Aug 15, 2011
1
Product data sheet
Characteristics
24338
miniature circuit breaker - C60N - 2 poles - 20
A - C curve
Main
Circuit breaker applica-
tion
Distribution
Range of product C60
Device short name C60N
Poles description 2P
Number of protected
poles
1
Neutral position Left
Network type AC
Trip unit technology Thermal-magnetic
Curve code C
Suitability for isolation Yes conforming to IEC 60947-2
Complementary
[In] rated current 20 A ( 30 °C )
[Ue] rated operational voltage 440 V AC
440 V AC
Magnetic tripping limit 5...10 x In
Breaking capacity Icn 6 kA at 400 V AC conforming to IEC 60898
Icu 20 kA at 230...240 V AC conforming to IEC 60947-2
Icu 10 kA at 400...415 V AC conforming to IEC 60947-2
Icu 6 kA at 440 V AC conforming to IEC 60947-2
Icu 20 kA at 125 V DC conforming to IEC 60947-2
[Ics] rated service breaking capacity Ics 4.5 kA 440 V AC conforming to IEC 60947-2
Ics 6 kA 400 V AC conforming to IEC 60898
Ics 7.5 kA 400...415 V AC conforming to IEC 60947-2
Ics 15 kA 230...240 V AC conforming to IEC 60947-2
[Ui] rated insulation voltage 500 V AC conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
Contact position indicator Yes
Control type Operating handle
Local signalling Positive break indication
Mounting mode Fixed
Mounting support 35 mm symmetrical DIN rail
9 mm pitches 4
Product weight 0.24 kg
Mechanical durability 20000 cycles
Connections - terminals Tunnel type terminals 16 mm² flexible
Tunnel type terminals 25 mm² rigid
Tightening torque 2 N.m
Environment
Standards IEC 60898
IEC 60947-2
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % ( 55 °C )
Operating altitude 2000 m
Ambient air temperature for operation -25...60 °C
Ambient air temperature for storage -40...70 °C
RoHS EUR conformity date 0643
RoHS EUR status Compliant