Aug 15, 2011
1
Product data sheet
Characteristics
24338
miniature circuit breaker - C60N - 2 poles - 20
A - C curve
Main
Circuit breaker applica-
tion
Distribution
Range of product C60
Device short name C60N
Poles description 2P
Number of protected
poles
1
Neutral position Left
Network type AC
Trip unit technology Thermal-magnetic
Curve code C
Suitability for isolation Yes conforming to IEC 60947-2
Complementary
[In] rated current 20 A ( 30 °C )
[Ue] rated operational voltage 440 V AC
440 V AC
Magnetic tripping limit 5...10 x In
Breaking capacity Icn 6 kA at 400 V AC conforming to IEC 60898
Icu 20 kA at 230...240 V AC conforming to IEC 60947-2
Icu 10 kA at 400...415 V AC conforming to IEC 60947-2
Icu 6 kA at 440 V AC conforming to IEC 60947-2
Icu 20 kA at 125 V DC conforming to IEC 60947-2
[Ics] rated service breaking capacity Ics 4.5 kA 440 V AC conforming to IEC 60947-2
Ics 6 kA 400 V AC conforming to IEC 60898
Ics 7.5 kA 400...415 V AC conforming to IEC 60947-2
Ics 15 kA 230...240 V AC conforming to IEC 60947-2
[Ui] rated insulation voltage 500 V AC conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
Contact position indicator Yes
Control type Operating handle
Local signalling Positive break indication
Mounting mode Fixed
Mounting support 35 mm symmetrical DIN rail
9 mm pitches 4
Product weight 0.24 kg
Mechanical durability 20000 cycles
Connections - terminals Tunnel type terminals 16 mm² flexible
Tunnel type terminals 25 mm² rigid
Tightening torque 2 N.m
Environment
Standards IEC 60898
IEC 60947-2
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % ( 55 °C )
Operating altitude 2000 m
Ambient air temperature for operation -25...60 °C
Ambient air temperature for storage -40...70 °C
RoHS EUR conformity date 0643
RoHS EUR status Compliant