607815 Catalog

2014-09-04

: Pdf 607815-Catalog 607815-Catalog 715629 Batch7 unilog

Open the PDF directly: View PDF PDF.
Page Count: 24

Download607815-Catalog
Open PDF In BrowserView PDF
sg5241.qxd 11/9/98 1:36 PM Page 1

R

JBM-100
Power connection/splice/tee

Industrial Heat-Tracing Systems
Component Selection Guide

E-100-L
Lighted end seal

E-100
End seal

T-100
Tee or splice connection

JBS-100
Power connection

sg5241.qxd 11/9/98 1:36 PM Page 2

Introduction
This guide is designed for the selection of connection components, controls, and accessories for use with
Raychem BTV, QTVR, XTV, and KTV self-regulating heating cables. Before using this guide, select the
appropriate heating cable using the Heat-Tracing Design Guide (H51149) or TraceCalc design software.
This guide does not cover component selection for LBTV, VL, and AutoSense M-wire heating cables.
Contact your local Raychem representative for assistance in selecting components for these products.
System approvals, warranty, and performance require the use of Raychem-specified components. Be sure to
use the correct Raychem components for your application and do not substitute parts.
Products in this guide are suitable for use in both ordinary and Division 2 hazardous locations. For Division 1 hazardous locations, a separate selection guide is available (H56075).
Raychem offers a wide range of other heating products for the industrial market, including mineral-insulated
cables, tank heating pads, long-line heating cables, and plantwide monitoring and control systems. Contact
your local Raychem representative for additional information.
Raychem requires ground-fault protection for all Raychem heating cables. A list of ground-fault protection
devices is included in the selection guide.

Contents
System Overview
Pipe-Tracing Components
Tank-Tracing Components
Controls—Ordinary Areas
Controls—Hazardous Areas
Ground-Fault Equipment Protection Devices
Accessories
Heat-Tracing System Worksheet
Data Sheets

1
2
3
4
5
6
7
10
11

sg5241.qxd 11/9/98 1:36 PM Page 1

System Overview
Typical Heat-Tracing System
The typical heat-tracing system consists of the components shown in the schematic below. All of the
components work together to provide a safe and reliable heat-tracing system that is easy to install and
maintain.
The self-regulating heating cable is cut to length at the job site and attached to the piping or tank surface
with glass tape. A power connection kit is used to connect power to one end of the heating cable. An end
seal kit is used to seal the other end of the heating cable. Splice and tee kits are used as necessary to
connect two or three heating cables together. The heating cable may be controlled automatically by
electromechanical or electronic thermostats, which sense either ambient or pipe temperature.

Power connection

T-Connection

End seal

Thermostat

End seal

Additional Information
Design literature, data sheets, and installation instructions supplement the information in this selection
guide. These documents are available from your local Raychem representative, from Raychem’s Fax-OnDemand system (800-329-4494), and from Raychem’s Web site (www.raychem.com).

1

sg5241.qxd 11/9/98 1:36 PM Page 2

Pipe-Tracing Components
PMKG-LE
1

3
2

JBM-100

4

PMKG-LT

PMKG-LS
0-A
-10
JBM

®

E-100-L

T-100
JS-100-A
®

E-100
T-100

®

6
CA

Menlo

Park,

AT NEM

®

ST

ration

SING

Corpo

MO

REA

ER

VAC

TH

MO.
EQUIP.

TEMP.REG.
&

ING480

LISTED
R

Chem

1B

OINT
Divisi
SWIT
SETP elex
22

FOR

SE125, SP-D(5°C em
E S@
Raych
TYPE: 40°F
LINAMP CH
on

INC.
ALE

KSD

BAR
BY
MFG

AM

R NS250 &T DEC
C)

A

4X

94025

-1164

5

JBS-100-A

®

Catalog
number

Raychem part
number

Single heating cable

JBS-100-A

085947-000

Single heating cable
(user-supplied
junction box)

JS-100-A

166639-000

Multiple heating cables (1, 2, or 3)

JBM-100-A

179955-000

Above insulation

T-100

447379-000

Below insulation

PMKG-LS

045551-000

Above insulation

T-100

447379-000

Below insulation

PMKG-LT

848907-000

Above insulation

E-100-A

046567-000

Above insulation,
with light

E-100-L1-A (100–120 V)
E-100-L2-A (200–277 V)

583377-000
478767-000

Below insulation

PMKG-LE

982199-000

Description
Components
1

2

3

4

Power connection

Splice connection

Tee connection

End seal

Accessories
5

Attachment tape and labels (see Accessories, pages 8 and 9)

Controls
6

2

Thermostat (see Controls, pages 4 and 5)

sg5241.qxd 11/9/98 1:36 PM Page 3

Tank-Tracing Components

6

¤R
HJUI
UTRE 

2
1

B
Y

eM
ln
o
P
ra
,k
C
A
49
20
-5
11
46

IL
S
T
E
D

B
A
R
K
S
D
LA

R

N
E

T
E
M &
.P R
E
M .G
.O E
Q
IU
.P

®

X

4

M
A

M
F
G

n

A

IE
M IL
N
N 2
.C
F
R-C E MA 2
O
1
S
R
B NES @ SP CTIW ES
H
1
T
IS ,52 YT P
N 52 EP NIO hC
G & 0 PS 4 :T leme
xe
T 84 D- °0
H 0 T °5( F siviD
i
E AV
o
)C
n
R C
D
E
M
C
aR
R
cy
O
E
eh
A
S
m
IS
C
T
N
ro
G
p
A
o
ar
T
it
o

®

7

E-100

E-100-L

4

5

Description

3

Catalog
number

Raychem part
number

Components
1

Power connection

JBS-100-A

085947-000

2

Support bracket

SB-100-T

279613-000

3

Splice connection

PMKG-LS

045551-000

4

End seal
Below insulation

PMKG-LE

982199-000

Above insulation

E-100-A

046567-000

Above insulation,
with light

E-100-L1-A, 100–120 V
E-100-L2-A, 200–277 V

583377-000
478767-000

AT-180

158139-000

Accessories
5

Aluminum tape

6

Labels (see Accessories, page 9)

Controls
7

Thermostat (see Controls, pages 4 and 5)

Note: RHS tank heating pads are also available for tank-heating applications on metal and plastic tanks.
Contact your Raychem representative for further information.

3

sg5241.qxd 11/9/98 1:36 PM Page 4

Controls—Ordinary Areas

Ambient-sensing thermostats

Chemelex Division

R

AMC-F5

031661-000

Fixed 40°F (4.4°C) set point for
freeze protection applications.
Single-pole, 22 A. NEMA 4X.

AMC-1A

573977-000

Set point range:
15°F to 140°F (–9°C to 60°C).
Single-pole, 22 A. NEMA 4X.

RAYSTATECO-01

178917-000

Electronic, energy-saving freeze
protection controller. ON below 40°F
(4.4°C). Single-pole control relay
rated 3 A. External contactor required.
NEMA 4X.

®

NEMA 4X

Menlo Park, CA 94025-1164

Description

TEMP. MO.
& REG. EQUIP.

Raychem Corporation

LISTED

22 AMPS @ 125, 250 & 480 VAC
SWITCH TYPE SPST
SETPOINT: 40°F (5°C) DECREASING

FIXED SET POINT THERMOSTAT

AMC-F5

R

Part No.

MFD BY BARKSDALE CONTROLS FOR

Catalog No.

®

R

. FO

INC

MO. IP.
P. EQU
TEM .
REG
&

ALE

SD

RK

G

BY

BA

R

ED
LIST

MF

R

SIN

TH

G

A N VAC
C-1 SE& 480 SING

NT, 250 CREA
AMBIE@ 125
n
-DT DE
atio
SP C)
por
PS PE (5°
AM
Cor
m
AM H TY F

ER

AT
STMA 4X
MO NE
164
25-1
940

k,
Par

lo
Men

CA

che
22 ITC T: 40°
Ray
SW OIN
TP
sion
SE
Divi
ex
mel
Che

4

1

7

2

6
5

4

TMIN

3

Pipe
Temp

WHT

8

9

0
1

7

2

6
5

WHT

4

ALAR

3

M

RED

RTD2
WHT

Ambie
Tempnt

WHT
RED

RTD2
STATU

–
+

Line-sensing thermostats

Chemelex Division

R

Fixed 40°F (4.4°C) set point for
freeze protection applications.
Single-pole, 22 A. NEMA 4X.

AMC-1B

943533-000

Set point range:
25°F to 325°F (–4°C to 163°C).
Single-pole, 22 A. NEMA 4X.

AMC-2B

042817-000

Set point range:
25°F to 325°F (–4°C to 163°C).
Double-pole, 22 A. NEMA 4X.

®

NEMA 4X

Menlo Park, CA 94025-1164

Description

031661-000

TEMP. MO.
& REG. EQUIP.

Raychem Corporation

LISTED

22 AMPS @ 125, 250 & 480 VAC
SWITCH TYPE SPST
SETPOINT: 40°F (5°C) DECREASING

FIXED SET POINT THERMOSTAT

AMC-F5

R

Part No.

AMC-F5
MFD BY BARKSDALE CONTROLS FOR

Catalog No.

®

R

. FO

INC

MO. IP.
P. EQU
TEM .
REG
&

ALE

SD

RK

G

BA

BY

R

ED

MF

LIST

R THER
B G C
VA
C-1NSI&N480 SING
AM SE , 250-DT CREA

E

MO

lo
Men

ST

ATNEMA

4X

164
25-1
940
k,
Par

CA

n
125
DE
atio
@ SP C)
por
PS PE (5°
Cor
m
AM TY F
che
22 ITCH T: 40°
Ray
SW OIN
TP
sion
SE

LIN

ex
mel
Che

Divi

®

R

. FO

INC

MO. IP.
P. EQU
TEM .
REG
&

ALE

SD

RK

G

BA

BY

R

ED
LIST

MF

R THER
B G C
VA
C-2NSI&N480 SING
AM SE , 250-DT CREA

E

n
125
DE
atio
@ SP C)
por
PS PE (5°
Cor
m
AM TY F
che
22 ITCH T: 40°
Ray
SW OIN
TP
sion
SE

LIN

ex
mel
Che

4

Divi

MO

lo
Men

ST

ATNEMA
164
25-1
940

k,
Par

CA

4X

sg5241.qxd 11/9/98 1:36 PM Page 5

Controls—Hazardous Areas

Note:
All controls listed on this page
(except MoniTrace 1000 and
RAYSTAT-EX-03-A) are approved
for use in the following areas:
•Class I, Div. 1 and 2,
Groups B, C, D
•Class II, Div. 1 and 2,
Groups E, F, G
•Class III

Ambient-sensing thermostats
Catalog No.

Part No.

Description

AMC-1H

889067-000

Set point range:
15°F to 140°F (–9°C to 60°C).
Single-pole, 22 A. NEMA 4, 7, 9.

Catalog No.

Part No.

Description

E507S-LS

625725-000

Set point range:
25°F to 325°F (–4°C to 163°C).
Single-pole, 22 A. NEMA 4, 7, 9.

E507S-2LS

257301-000

Set point range:
25°F to 325°F (–4°C to 163°C).
Double-pole, 22 A. NEMA 4, 7, 9.

RAYSTAT-EX-03-A

453609-000

Electronic line-sensing thermostat.
Set point range:
32°F to 930°F (0°C to 499°C).
Double-pole, 16 A. NEMA 4X.
[Available January 1999]

MONITRACE
1000

716381-000

Single-circuit electronic controller.
Range: –40°F to 999°F (–40°C to
537°C). Double-pole solid-state
switch rated 30 A, 277 V. NEMA 4X.
Integral ground-fault equipment
protection. Temperature and current
display and alarms. Diagnostic tests.

°F
140
TO 60°C)
15°F TO
GE: (-9°C S
NLES
P. RAN - STAI
TEM
7, 9 RY
A 4, ILLA
NEM L CAP
34556
STEE
LR
®
OF
PRO
ION
LOS URE FOR ONS
EXP LOS T ATI ,D
ENC STA LOC B,C G
RMOOUS UPS E,F,
THE ARD GRO UPS
HAZ I, GRO
SS II,
KTV
CLA SS III
&
CLA SS XTV-A
CLA R, 419
, QTV
BTV 905 .
e, gs No. LIVE G.
rac
LISTE
AREOPE NIN
355S
o-T win
TS
Aut Dra
FM
OF
ORE
VED 1)
andmel ex CIR CUIBEF T BE
PRO
NOTE
APPRO
LE TS MUS ED
ION
(SEE
h RMI Che
CUI
LOS URE FOR ONS ,D
wit see HT WHI
CIR URE LIST CLE
EXP LOS STA T ATI B,C G use ails
TIG PLY LOS HCOU VERS
LOC UPS E,F,
ER SUP ENC WIT
ENCRMO
for det
LE G SOU
OUS GRO
THE ARD I, GRO UPS is for P COV T VIN GLOS URE
DER SON
KEECON NECLEA ENC : GAR TS NT
HAZCLA SS II, -7S -LS les,
cab
SS
DIS G OR OF IONCIR CUI T AVA
.
CLA W50ting
CUI CLE
ERIN HES ENTLES
hea
CIR
ATT
ENT18 INC
S. SQU E LE COU VER
TS
DUI HIN INGLOR PER LE
CON WIT FITTM´E COU ER
ALL LEDL OFF FER SIO N, LEV
SEASEA
D'EN
BIEN TEN
R

D

CA

UT

IO N:

Line-sensing thermostats

F
140°
TO 60°C)
E: 15°F TO S
(-9°CNLES
P. RANG - STAI
TEM
7, 9 Y
A 4, LLAR
NEM L CAPI
34556
STEE
LR
®
OF
PRO
ION
LOS URE FOR NS
EXP LOS T ATIO,D
ENC STA LOC B,C G
RMOOUS UPS E,F,
THE ARD GRO UPS
HAZ I, GRO
SS II,
KTV
CLA SS III
&
CLA SS XTV
CLA R, 419 -A
, QTV
905
BTV
.
,
No.
D
LIVE G.
ace gs
LISTE
AREOPE NIN
355S
o-Tr win
Aut Dra UITS
FM
OF
VED 1)
andmel ex CIRC BEF ORE
PRO
T BE
NOTE
APPRO
ION
(SEE
h RMI Che WHI LE UITS MUS ED
LOS URE FOR NS ,D
wit see
T CIRC URE LIST CLE
EXP LOS STA T ATIO B,C G use ils
TIGH
LOS HCOU VERS
LOC UPS E,F,
ER SUP PLY
ENCRMO
for deta
ENC WIT
LE G SOU
OUS GRO
THE ARD I, GRO UPS is for P COVECT VIN GLOS URE
DER SON
KEE ONN LEA ENC : GAR
NT
HAZCLA SS II, -7S -LS les,
cab
UITSAVA
SS
DISC G OR OF ION
CLA W50ting
CIRC UIT .
ERININC HES ENTLES
CLE
hea
CIRC
ATT
S ENT18 S. SQU E LE COU VER
DUIT HIN INGLOR PER LE
CON WIT FITTM´E , COU ER
ALL LEDL OFF FER SION LEV
SEASEA
D'EN
BIEN TEN
R

CA

UT

IO N:

S FOR
TROL
E CON



SDAL
BARK
x
325°F )
ele
TO 163°C
T
R
: 25°F TO
em LS STA
LESS
Ch S-2 RMO 94025-1164RANGE - (-4°C
STAIN
TEMP.
9
CA
07
4, 7, ARY
E5 ING THEPark,
NEMA CAPILL

BY
MFG

ENS

Menlo

34556
STEEL
LR
®
F
PROO
SION E
FORTIONS
AT
EXPLO OSUR
LOCA
ENCL
MOSTS PS B,C,D
E,F,G
THER RDOU
GROU PS
HAZAS I, GROU
II,
KTV
CLAS S III
&
CLAS S , XTV
CLAS
QTVR 19-A
BTV,No. 9054
e,
LIVE.ING.
LISTED
-Trac ings ARE
355S
FM
Auto Draw UITS RE OPEN
F
ED
1)
and elex CIRC BEFO BE
NOTE
APPROV
E
N PROO
RMI Chem
D E
(SEE
S
OSIO E FOR
WHIL UITSE MUST
with see
TIONB,C,D
LISTEERCL
CIRC
EXPL OSUR AT
use ils
LY OSUR
PS
R TIGHT ENCL E WITHCOUV
ENCL MOSTS LOCA PS E,F,G
for deta
LE SOUS
GROU
is for
COVE T SUPP
THER RDOU
ING OSUR ER
s,
S I, GROU
KEEP NNECLEAVENCL GARD SONGT
HAZA
CLAS S II, 7S-LS
cable
DISCO ORES OF N: UITSAVAN
CLAS W50-ing
NTIO CIRCUIT E.
RING
heat
CIRC ERCL
ENTE18 INCHATTE LES
QUE LE COUV
ER LE
UITS IN NGS.
LORS
COND WITHFITTI´E COUP
ALL ED OFF FERM ION, EVER
SEAL
SEALBIEN TENS D'ENL

LIN

E-S

ration

Corpo

hem

Rayc

R

CA

Note:
MoniTrace 1000 and
RAYSTAT-EX-03-A are approved
for use in the following areas:
•Class I, Div. 2,
Groups A, B, C, D
•Class II, Div. 1 and 2,
Groups E, F, G
•Class III

UT

ION

:

5

sg5241.qxd 11/9/98 1:36 PM Page 6

Ground-Fault Equipment Protection Devices
All Raychem heating cables must be installed with electrical protection in accordance with local codes and practices.
Ground-Fault Circuit Breaker Selection Table
The following breakers are available from your local Raychem representative:
Bolt-on Style
Manufacturer
Voltage (amps)
15
20
30
40
50
Panelboard
Plug-on Style
Manufacturer
Voltage (amps)
15
20
30
40
50
Panelboard
Padlock attachment***

Square D
120
QOB115EPD
QOB120EPD
QOB130EPD
—
—
NQOD

208/240**
QOB215EPD
QOB220EPD
QOB230EPD
—
—
NQOD

Cutler Hammer (Westinghouse)
120
208/240**
QBGFEP1015
QBGFEP2015
QBGFEP1020
QBGFEP2020
QBGFEP1030
QBGFEP2030
—
QBGFEP2040
—
QBGFEP2050
POW-R-LINE 1
POW-R-LINE 1

Raychem TraceGuard*
277
EHB14015EPD
EHB14020EPD
EHB14030EPD
EHB14040EPD
EHB14050EPD
NEHB

Square D
120
QO115EPD
QO120EPD
QO130EPD
—
—
QO Load Center
QO1PA

208/240**
QO215EPD
QO220EPD
QO230EPD
—
—
QO Load Center
GF12PA

Cutler Hammer (Westinghouse)
120
208/240**
QPGFEP1015
QPGFEP2015
QPGFEP1020
QPGFEP2020
QPGFEP1030
QPGFEP2030
—
QPGFEP2040
—
QPGFEP2050
POW-R-LINE 1
POW-R-LINE 1
QLPB123PL
QLPB123PL

Raychem TraceGuard*
277
—
—
—
—
—
GFPOHPA-EH

* Raychem’s TraceGuard 277 circuit breaker is manufactured by Square D.
** Two-pole ground-fault breakers require 120 volts to power the internal electronics. 240-volt delta systems without a 120-volt neutral reference will require an
additional transformer to provide the reference.
*** Padlocks are required to comply with NEC section 427-55(a) if the circuit breaker is utilized as a disconnecting means.

6

sg5241.qxd 11/9/98 1:36 PM Page 7

Accessories

Cold-applied core sealer
Catalog No.

Part No.

Description

CS-100-A

232949-000

Heating Cable Connection Insulator
Replacement cold-applied core sealer for
Raychem BTV, QTVR, XTV, and KTV
heating cables.

Single-entry transition kit
Catalog No.

Part No.

Description

JS-100-A

166639-000

Junction Box Stand
Junction box stand for use with Raychem
BTV, QTVR, XTV, and KTV self-regulating
heating cables. A separate customersupplied NEMA 4X junction box is
required.

Kit Contents
J

A

I
H
B

G

C

F

D

E

Item

Description

A
B
C
D
E
F
G
H
I
J

Stand assembly
Conduit drain
Cleaning tissue
Adapter for small pipes
Cable tie
Green/yellow tube
CS-100 cold-applied core sealer
JS-100 transition
1" locknut
Terminal block

Gland entry kit
Catalog No.

Part No.

Description

C75-100-A

000539-000

A NEMA 4X-rated gland kit used to transition
heating cables into a junction box when making
connections off of a pipe or tank. It may be used
for power, splice, or tee connections. The
C75-100-A is for use with Raychem BTV,
QTVR, XTV, KTV,1 and LBTV2-CT2 selfregulating heating cables. The kit does not
include the junction box, flexible tubing, or
tape, which are required to make a complete
connection.
1

2

For KTV only, order PMK-GP-10 grommet
(P/N 700823).
For LBTV2-CT only, order HCS-100-A heat-shrink
core sealer (P/N 257649) and PMK-GK-10 grommet
(P/N 222724).

Kit Contents
A

H

B

G

C

F

D

E

Item

Description

A
B
C
D
E
F
G
H

Red grommet
Gland with threaded inserts
Gland with screws
Gland gasket
Locknut
Green/yellow heat-shrinkable tube
CS-100 core sealer
Terminal block

7

sg5241.qxd 11/9/98 1:36 PM Page 8

Accessories

Attachment products
Catalog No.

Part No.

Description

GT-66

C77220-000

66-ft (20-m) roll of glass tape for
attaching heating cable to pipe.
Not for stainless steel pipes or
for installation temperatures
below 40°F.

GS-54

C77221-000

54-ft (16.5-m) roll of glass tape for
attaching heating cable to pipe. For
stainless steel pipes and for any
installation below 40°F.

AT-180

158139-000

180-ft (55-m) roll of aluminum
tape for attaching heating cables
and thermostat sensors to pipes
and tanks.

CT-CABLE-TIE

C77261-000

Plastic cable ties (100 per box) offer
an alternative method of attaching
heating cable to pipes up to 3 in
(75 mm) in diameter.

Used to secure connection
components and brackets
to pipes. Order by pipe diameter,
as follows:

Pipe Straps

PS-01
PS-03
PS-10
PS-20

8

C77211-000
C77212-000
C77213-000
C77216-000

1/4—1 in
1—3 in
3—10 in
10—20 in

(6–25 mm)
(25–75 mm)
(75–250 mm)
(250–500 mm)

sg5241.qxd 11/9/98 1:36 PM Page 9

Accessories

Labels
ELECTRIC
TRACED

Catalog No.

Part No.

Description

ETL-ENGLISH

C77203-000

“Electric-traced” label for identifying
traced pipes and tanks.

Catalog No.

Part No.

Description

SB-100-SP

800679-000

Adapter for mounting E-100, E-100-L,
JBS-100, and JS-100 connection
components on 1-in (25-mm) and
smaller pipes (included in kits
mentioned).

SB-100-T

279613-000

Bracket for mounting JBS-100, E-100,
and E-100-L on a tank surface.

UMB

263757-000

Universal mounting bracket for
mounting thermostats and other
equipment on a pipe.

BCK-35

C77215-000

Thermostat bulb clamp kit for
attaching thermostat bulb to
tank wall.

JB-SB-25

471139-000

Stainless steel mounting bracket for
RAYSTAT-EX-03-A thermostat.

R

Brackets, Adapters

9

sg5241.qxd 11/9/98 1:36 PM Page 10

Heat-Tracing System Worksheet

Product Catalog Number

Quantity Required

Step 1:
Select heating cable.

ft

Select appropriate heating cable for application. To aid in
component selection, list:
Pipe length
Pipe size
Pipe material
Step 2:
Select system components.
Junction box

ea.

Splice kit

ea.

Tee kit

ea.

End seal kit

ea.

Select accessories.
Support bracket

ea.

Tape

ea.

Labels

ea.

Select controls.
Thermostat to suit application
Step 3:
Contact your local Raychem representative
to place your order.

10

ea.

sg5241.qxd 11/9/98 1:36 PM Page 11

Data Sheets
Data sheets with detailed product specifications are provided for the
following components:
JBS-100
JBM-100
T-100
E-100
E-100-L

Single-entry power connection with junction box
Multiple-entry power/splice/tee connection with junction box
Splice or tee connection kit
High-profile end seal
High-profile end seal with light

11

sg5241.qxd 11/9/98 1:36 PM Page 12

R

JBS-100
Single-entry power connection
with junction box

The JBS-100 kit is designed to connect power to one
Raychem BTV, QTVR, XTV, or KTV self-regulating
heating cable and is approved by FM, CSA, and PTB
for use in hazardous locations.

The new core sealing boot does not require a heat
gun or torch for the installation (no hot work permit
necessary). The noncuring sealant in the boot allows
easy installation and facilitates maintenance.

The JBS-100 integrates the functions of both
connection kits and insulation entries. The rugged
stand protects the heating cable and allows for up to
100 mm (4") of thermal insulation.

Innovative cage clamp terminals from WAGO provide
fast installation and safe, reliable, maintenance-free
operation.

Compared to existing systems, this connection kit
significantly reduces installation time.
The kit is offered in three versions, customized for
local installation. Each kit contains all the necessary
materials for a complete installation except for the
pipe straps, which must be ordered separately.

JBS-100-A

JBS-100-E

®

®

Description

Kit contents
Note: Order appropriate
pipe strap separately
(two straps per kit).

Approvals

JBS-100-A
This kit is for use in North America
and has one through-hole for use
with 3/4" conduit. A conduit drain is
provided to prevent condensate from
collecting in the box.

JBS-100-E
This kit is for use in Europe and provides two M25 threaded entries, one
stopping plug, and one plastic power
cable gland.

JBS-100-EP
This kit is for use in Europe and provides two M25 threaded entries, an
earthing plate, and an external earthing stud. It is designed for use with
armored cables.

1 junction box with terminals
1 stand
1 core sealer
1 braid insulator
1 3/4" conduit drain
1 adapter for small pipes

1 junction box with terminals
1 stand
1 core sealer
1 braid insulator
1 M25 gland for power cable
8–17 mm in diameter
1 M25 stopping plug
1 adapter for small pipes

1 junction box with terminals, earth
plate, and stud
1 stand
1 core sealer
1 braid insulator
1 M25 stopping plug
1 adapter for small pipes

Hazardous Locations
FM
APPROVED

®

FM
APPROVED

Class I, Div. 2,
Groups B, C, D
Class II, Div. 1 and 2,
Groups E, F, G
Class III
CLI, ZN1, AEx e IIC

II 2 G EEx e II
PTB 97 ATEX 1058 U

II 2 G EEx e II
PTB 97 ATEX 1058 U

sg5241.qxd 11/9/98 1:36 PM Page 13

JBS-100-A

JBS-100-E

JBS-100-EP

Dimensions (nominal)

120 mm

4.7"

120 mm

3.6"

90 mm

4.7"

122 mm

4.8"

120 mm

Raychem product specifications
Heating cable capability
Ingress protection
Entries
Min. installation temperature
Min. usage temperature
Max. pipe temperature
Terminals
Max. conductor size
Max. operating voltage
Max. continuous operating current
Deluge testing

Materials of construction
Enclosure, lid, and stand

BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT
NEMA Type 4X
IP67
1 x 3/4"
2 x M25
–40°F (–40°C)
–40°F (–40°C)
–60°F (–75°C)
–60°F (–75°C)
420°F (215°C)
420°F (215°C)
WAGO 284 series (EEx e)
WAGO 284 series (EEx e)
2 line, 1 ground
1 phase, 1 neutral, 1 earth
8 AWG stranded
10 mm2 stranded, 10 mm2 solid
277 Vac
277 Vac
50-A heating cable circuit
50-A heating cable circuit
Passed
Passed
Shell UK requirements
Shell UK requirements

IP67
2 x M25
–40°F (–40°C)
–60°F (–75°C)
420°F (215°C)
WAGO 284 series (EEx e)
1 phase, 1 neutral, 1 earth
10 mm2 stranded, 10 mm2 solid
277 Vac
50-A heating cable circuit
Passed
Shell UK requirements

Lid screws
Lid gasket
Earth continuity plate

Electrostatic-charge-resistant
glass-filled engineering
polymers, black
Stainless steel
Silicone rubber
N/A

Electrostatic-charge-resistant
glass-filled engineering
polymers, black
Stainless steel
Silicone rubber
N/A

Electrostatic-charge-resistant
glass-filled engineering
polymers, black
Stainless steel
Silicone rubber
Steel, zinc plated, and
yellow chromated

Ordering details
Part description
Raychem part number
Weight

JBS-100-A
085947-000
2.5 lb

JBS-100-E
829939-000
1.2 kg

JBS-100-EP
158251-000
1.3 kg

sg5241.qxd 11/9/98 1:36 PM Page 14

R

JBM-100
Multiple-entry power/splice/tee
connection with junction box

The JBM-100 kit is designed to splice, tee, or connect
power to as many as three Raychem BTV, QTVR, XTV,
or KTV self-regulating heating cables and is approved
by FM, CSA, and PTB for use in hazardous locations.
The JBM-100 integrates the functions of both
connection kits and insulation entries. The rugged
stand protects the heating cable and allows for up to

100 mm (4") of thermal insulation. The new core
sealing boot does not require a heat gun or torch for
the installation (no hot work permit necessary). The
noncuring sealant in the boot allows easy installation
and facilitates maintenance.
Innovative cage clamp terminals from WAGO provide
fast installation and safe, reliable, maintenance-free
operation.

Compared to existing systems, this connection kit
significantly reduces installation time.
The kit is offered in three versions, customized for
local installation. Each kit contains all the necessary
materials for a complete installation except for the
pipe straps, which must be ordered separately.

JBM-100-A

JBM-100-E

M-1
JB

00-A

®

R
JB
M-1

00
-E

Description

Kit contents
Note: Order appropriate
pipe strap separately
(two straps per kit).

Approvals

JBM-100-A
This kit is for use in North America
and has two 3/4" through holes
for use with 3/4" conduit. Two stopping plugs are supplied in the kit. A
conduit drain is provided to prevent
condensate from collecting in the box.

JBM-100-E
This kit is for use in Europe and provides two M25 threaded entries, two
stopping plugs, and one plastic
power cable gland.

JBM-100-EP
This kit is for use in Europe and provides two M25 threaded entries, an
earthing plate, and an external earthing stud. It is designed for use with
armored cables.

1 junction box with terminals
1 stand
3 core sealers
3 braid insulators
1 3/4" conduit drain
1 adapter for small pipes

1 junction box with terminals
1 stand
3 core sealers
3 braid insulators
1 M25 gland for power cable
8–17 mm in diameter
2 M25 stopping plugs
1 adapter for small pipes

1 junction box with terminals, earth
continuity plate, and stud
1 stand
3 core sealers
3 braid insulators
2 M25 stopping plugs
1 adapter for small pipes

Hazardous Locations
FM
APPROVED

®

FM
APPROVED

Class I, Div. 2,
Groups B, C, D
Class II, Div. 1 and 2,
Groups E, F, G
Class III
CLI, ZN1, AEx e IIC

II 2 G EEx e II
PTB 98 ATEX 1021 U

II 2 G EEx e II
PTB 98 ATEX 1021 U

sg5241.qxd 11/9/98 1:36 PM Page 15

JBM-100-A

JBM-100-E

JBM-100-EP

Dimensions (nominal)
8.6"

220 mm

220 mm

3.5"

90 mm

4.7"

120 mm

4.7"

120 mm

Raychem product specifications
Heating cable capability
Ingress protection
Entries
Min. installation temperature
Min. usage temperature
Max. pipe temperature
Terminals
Max. conductor size
Max. operating voltage
Max. continuous operating current
Deluge testing

Materials of construction
Enclosure, lid, and stand

BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT
NEMA Type 4X
IP66
2 x 3/4"
2 x M25
–40°F (–40°C)
–40°F (–40°C)
–60°F (–75°C)
–60°F (–75°C)
420°F (215°C)
420°F (215°C)
WAGO 284 series (EEx e)
WAGO 284 series (EEx e)
4 line, 2 ground
2 phase, 2 neutral, 2 earth
8 AWG stranded
10 mm2 stranded, 10 mm2 solid
277 Vac
277 Vac
50-A heating cable circuit
50-A heating cable circuit
Passed
Passed
Shell UK requirements
Shell UK requirements

IP66
2 x M25
–40°F (–40°C)
–60°F (–75°C)
420°F (215°C)
WAGO 284 series (EEx e)
2 phase, 2 neutral, 2 earth
10 mm2 stranded, 10 mm2 solid
277 Vac
50-A heating cable circuit
Passed
Shell UK requirements

Lid screws
Lid gasket
Earth continuity plate

Electrostatic-charge-resistant
glass-filled engineering
polymers, black
Stainless steel
Silicone rubber
N/A

Electrostatic-charge-resistant
glass-filled engineering
polymers, black
Stainless steel
Silicone rubber
N/A

Electrostatic-charge-resistant
glass-filled engineering
polymers, black
Stainless steel
Silicone rubber
Steel, zinc plated, and
yellow chromated

Ordering details
Part description
Raychem part number
Weight

JBM-100-A
179955-000
4.3 lb

JBM-100-E
831519-000
1.9 kg

JBM-100-EP
986415-000
2.1 kg

sg5241.qxd 11/9/98 1:37 PM Page 16

R

T-100
Splice or tee connection kit

The T-100 is an above-insulation splice or tee kit,
designed for use with up to three Raychem BTV,
QTVR, XTV, or KTV self-regulating heating cables. It
is approved by FM, CSA, and PTB for use in hazardous locations.

The rugged stand protects the heating cable and
allows for up to 100 mm (4") of thermal insulation.

Compared to existing systems, the T-100 significantly
reduces installation and maintenance time and effort.

The new core sealing boot does not require a heat
gun or torch for the installation (no hot work permit
necessary). The noncuring sealant in the boot allows
easy installation and facilitates maintenance.

Each kit contains all the necessary materials for a
complete installation except for the pipe straps, which
must be ordered separately.

T-100

Description

This kit is an above-insulation splice/tee,
appropriate for use worldwide with no
requirements for local customization.

Kit contents
Note: Order appropriate
pipe straps separately
(two straps per kit).

1 splice/tee enclosure and lid
1 stand assembly
3 core sealers
3 braid insulators
1 adapter for small pipes
3 compression crimps
3 crimping insulating tubes

Approvals

Hazardous Locations
FM
APPROVED

®

FM
APPROVED

Class I, Div. 2, Groups B, C, D
Class II, Div. 1 and 2, Groups E, F, G
Class III

CLI, ZN1, AEx e IIC

II 2 G EEx e II
PTB 98 ATEX 1020 U

sg5241.qxd 11/9/98 1:37 PM Page 17

Dimensions (nominal)

4.7"
120 mm

Specifications
Heating cable capability
Ingress protection
Min. installation temperature
Min. usage temperature
Max. pipe temperature
Max. operating voltage
Max. continuous operating current
Deluge testing
Materials of construction
Enclosure, lid, and stand

3.6"

90 mm

4.7"

122 mm

4.7"

120 mm

BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT
NEMA Type 4X/IP67
–40°F (–40°C)
–75°F (–60°C)
420°F (215°C)
277 Vac
50-A heating cable circuit
Passed Shell UK requirements

Lid screws
Lid gasket

Electrostatic-charge-resistant glass-filled
engineering polymers, black
Stainless steel
Silicone rubber

Ordering details
Part description
Raychem part number
Weight

T-100
447379-000
2.5 lb/1.2 kg

sg5241.qxd 11/9/98 1:37 PM Page 18

R

E-100
High-profile end seal

The E-100 is a NEMA 4X-rated end seal kit for
Raychem BTV, QTVR, KTV, and XTV heating cables.
Once installed, these end seals are easily reentered
for maintenance; the heating cable can be accessed
without removing the end seal.

Quick and easy to install
Installation is extremely fast and no grommet selection is required. All parts are captive and are correctly
positioned at the time of installation. The only tools
needed are a utility knife, wire cutters, and a screwdriver; no heat source is required. To reduce the risk
of tampering, a tool-only reentry feature is offered.

Super sealed and corrosion resistant

Easy to locate

The combination of compression grommet and Orings provides the E-100 with a complete water seal.
The heating-cable core and bus wires are insulated
and sealed separately from the braid by means of a
sealant-filled boot. The NEMA 4X-rated E-100 is
resistant to chemical and salt corrosion.

The high-profile E-100 end seal is mounted on the
pipe, and projects through the thermal insulation and
cladding for easy visibility. A brightly colored “leash”
holds the cap captive to the stand.

Exceptionally rugged
Using the latest in polymer technology, the E-100 is
designed for extreme durability during and after
installation. The E-100 meets or exceeds IEEE and
European Norm standards for impact resistance and
ruggedness.

Kit contents
Note: Order appropriate
pipe strap separately.

1 end seal
1 end seal label
1 cable tie

Approvals

Hazardous Locations
FM
APPROVED

®

FM
APPROVED

Class I, Div. 2, Groups A, B, C, D
Class II, Div. 1 and 2, Groups E, F, G
Class III

CLI, ZN1, AEx e IIC

Reenterable
With the E-100 end seal, heating-cable bus wires and
grounding braid are easily accessed for voltage and
continuity checks. Simply unscrew the E-100 cap and
remove the reusable sealing boot; there is no need to
completely disassemble or remove the end seal.

sg5241.qxd 11/9/98 1:37 PM Page 19

Dimensions

1.75 in.
(45 mm)

6.70 in.
(170 mm)

Specifications
Heating cable compatibility
Ingress protection
Min. installation temperature
Max. pipe temperature
Materials
Impact resistance
Flammability
Dust exclusion
Cable creepage
Tools required
Max. thickness pipe insulation
Ordering details
High-profile end seal kit
Part description
Raychem part number
Weight
Replacement sealing boots (5 per pack)
Part description
Raychem part number
Weight

BTV-CR/-CT, QTVR-CT, XTV-CT, KTV-CT; not LBTV or M-wire
NEMA Type 4X, IP65
–40°F (–40°C)
419°F (215°C)
High-performance glass-filled engineering polymers
10 ft-lb at –22°F (–30°C) (IEEE 515-5.1.6)
7 joules after 1 month thermal aging (EN 50 014-23.4.7.2)
IEEE 515-5.3.4
IEC 529-5.6.2
FM 3820-5.2.5, EN 50 014-B.1.3
Wire cutters, utility knife, screwdriver
4 in (100 mm)

E-100-A
046567-000
0.5 lb
E-100-BOOT-5/PACK
281053-000
0.25 lb

sg5241.qxd 11/9/98 1:37 PM Page 20

R

E-100-L
High-profile end seal with light

The E-100-L is a high-profile end seal with a signal
light module. This unit is approved for use with most
Raychem heating cables and has worldwide approvals
for use in ordinary and hazardous areas. These rugged
end seals are resistant to impact, high temperatures,
and chemical and UV attack. Sealing is done separately with O-rings and a sealant-filled boot.

The light module uses an array of super-bright LEDs
for excellent visibility and long life. The robust industrial-grade electronics are encapsulated to reliably seal
out moisture and dust.

Kit contents
Note: Order appropriate
pipe strap separately.

1 end seal with lighted cap
1 end seal label
1 cable tie

Approvals

Hazardous Locations
FM
APPROVED

®

FM
APPROVED

Class I, Div. 2, Groups A, B, C, D
Class II, Div. 1 and 2, Groups E, F, G
Class III

CLI, ZN1, AEx e IIC

The light module can be retrofitted into previously
installed E-100 and PMK-RE end seals, and the light
module is replaceable.

sg5241.qxd 11/9/98 1:37 PM Page 21

Dimensions
2.6 in.
(66 mm)

7.75 in.
(197 mm)

Specifications
Heating cable compatibility
Ingress protection
Min. installation temperature
Max. pipe temperature
Min./max. ambient temperature
Materials
Impact resistance
Light source
Light source power supply
Power consumption
Electromagnetic compatibility

Vibration
Shock
Tools required
Max. thickness pipe insulation
Ordering details
Complete lighted end seal kit
(requires one pipe strap, not supplied)

Replacement/retrofit lighted end seal kit
(for use with existing PMK-RE or E-100)

*Voltage tolerance: ± 10%, 50/60 Hz

BTV-CR/-CT, QTVR-CT, XTV-CT, KTV-CT; not LBTV or M-wire
NEMA Type 4X, IP65
–40°F (–40°C)
419°F (215°C)
–40°F to 105°F (–40°C to 40°C)
High-performance engineering polymers
IEEE 515
10 ft-lb at –40°F (–40°C)
EN 50 014
≥ 7 joules
Super-bright light emitting diodes (LEDs)
Linear (non-switching)
< 2 watts
Immunity
Complies with EN 50 082-2:1995
Emissions
Complies with EN 50 081-1:1991 (commercial and
light industrial classes) and meets requirements of
FCC, Part 15, Class B
IEC 68-2-6
20 m/s2, 10–150 Hz
IEC 68-2-27
500 m/s2, 11 ms
Wire cutters, utility knife, screwdriver, crimp tool
4 in (100 mm)

100–120 Vac*

Red LEDs

200–277 Vac*

Red LEDs

100–120 Vac*

Red LEDs

200–277 Vac*

Red LEDs

E-100-L1-A
RPN 583377 (1.3 lb)
E-100-L2-A
RPN 478767 (1.3 lb)
E-100-LR1-A
RPN 552225 (0.9 lb)
E-100-LR2-A
RPN 874485 (0.9 lb)

sg5241.qxd 11/9/98 1:37 PM Page 22

R

TE&I Division
Raychem Corporation
300 Constitution Drive
Menlo Park, California 94025-1164
Tel (800) 545-6258
Fax (800) 611-2323
Fax-on-Demand (800) 329-4494
ciinfo@raychem.com
www.raychem.com

Raychem Canada Limited
Toronto, Ontario M5H 4A2
Canada
Tel (800) 988-5171
Fax (800) 988-5172

Raychem S.A.I.C.
Carlos Pellegrini 1163, Piso 7
1009 Capital Federal
Buenos Aires, Argentina
Tel (54) 1/394-5150
Fax (54) 1/326-9985

H56248
(P5241)
Printed in USA

All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the
suitability of each product for their application. Raychem makes no warranties as to the accuracy or completeness of the
information, and disclaims any liability regarding its use. Raychem’s only obligations are those in the Raychem Standard
Terms and Conditions of Sale for this product, and in no case will Raychem be liable for any incidental, indirect, or
consequential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to change
without notice. In addition, Raychem reserves the right to make changes—without notification to Buyer—to processing
or materials that do not affect compliance with any applicable specification.

© 1998 Raychem Corporation

ISO 9 0 0 1

10/98

AutoSense, MoniTrace, Raychem, RayStat, TraceCalc, and TraceGuard are trademarks of Raychem Corporation.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
XMP Toolkit                     : 3.1-702
Modify Date                     : 2008:12:04 16:30:51+09:00
Create Date                     : 2008:12:04 16:30:38+09:00
Metadata Date                   : 2008:12:04 16:30:51+09:00
Creator Tool                    : Adobe Acrobat 7.0
Format                          : application/pdf
Document ID                     : uuid:94195186-e163-4873-96aa-f55d7486441f
Instance ID                     : uuid:4928b2c2-2b4f-4e03-bc2d-fdf910a29839
Producer                        : Adobe Acrobat 7.0 Image Conversion Plug-in
Has XFA                         : No
Page Count                      : 24
Creator                         : Adobe Acrobat 7.0
EXIF Metadata provided by EXIF.tools

Navigation menu