Fuse holders for the
North American market
Rittal – RiLine Class and NH
2Rittal RiLine Class and NH
RiLine NH isolators, sizes NH 00 to 3, for the
use of NH fuses with UR approval.
In addition to the existing type testing of RiLine NH isolators
to DIN EN 60 947-3, sizes NH 00 to 3 have also undergone
UL testing for the use of NH fuses with UR approval.
Particularly in the field of drive technology, where the use of
fuses specifically designed for semiconductor protection is
often required, this creates assembly-friendly and time- and
space-saving configuration alternatives for applications in
the North American market.
Powerful safety devices for
the North American market
Benefits/features of RiLine NH:
●The same unit for both UL and IEC applications
●Approved to the very latest UL/CSA standard
UL 4248-1/CSA C22.2 No. 4248-1
●Versions for mounting plate assembly or for direct mounting
on 60 mm busbar systems as well as PLS 800 and PLS 1600
●3-pole, suitable for use as fuse carrier
●Use of NH 00 – NH 3 fuses to VDE 0636-201, EN 60 629-2-1
●Reliable contact hazard protection with isolator lid and internal
contact hazard protection covers
●Self-locking voltage test holes and lid lock/seal
3Rittal RiLine Class and NH
Benefits/features of RiLine Class:
●Approved to the very latest UL/CSA standard
UL 4248-1/UL 4248-8/CSA C22.2 No. 4248-1-07/
CSA C22.2 No. 4248.8-07
●Fuse holder for the use of American-standard J-Class fuses
●Versions for mounting plate assembly or for direct mounting
on 60 mm busbar systems as well as PLS 800 and PLS 1600
●3-pole, for use as fuse carriers
●For cylindrical J-Class fuses to UL 248-8 in 3 current ranges:
61 – 100 A/101 – 200 A/201 – 400 A
●Reliable contact hazard protection with isolator lid and internal
contact hazard protection covers
●Self-locking voltage test holes and lid lock/seal
Rittal extends the RiLine Class
family with 3 new J-Class variants.
For J-Class fuse inserts of:
●61 – 100 A
●101 – 200 A
●201 – 400 A
An important addition to the existing
range of RiLine Class fuse holders for
cylindrical fuses Class CC up to 30 A,
and Class J up to 30 and 60 A.
In terms of design and technology,
these are based on the popular RiLine
NH range.
All 3 sizes are available in a top-
mounted variant for
●Direct mounting on 60 mm busbar
systems or
●Mounting plate assembly.
Rittal RiLine NH (60 mm mounting plate assembly)
NH bus-mounting on-load isolator, size 00 to 3 (fuse holder)
4Rittal RiLine Class and NH
1
2
3
4
1
2
3
184
110
57 57
98
298
210
130
65 65
298
98
250
130
80
80
298
98
4
106
104
40
194
33 33
Suitable for feeder circuits to
UL 508A up to 600 V.
Material:
Chassis, lid, contact hazard
protection: Polyamide PA6
Colour:
RAL 7035
Approvals:
IEC 60 947-3
UL 4248-1
CSA C22.2 No. 4248-1
Note:
The technical specifications are
based on UL-Standard test
results. If using the devices in
the IEC market, please use the
technical specifications of RiLine
NH isolators to IEC 60 947-3.
For mounting on 60 mm bar sys-
tems, PLS 800 and PLS 1600.
Design Packs of
Size Size 00 Size 1 Size 2 Size 3
Rated operating current Ie 160 A 250 A 400 A 630 A
Rated operating voltage Ue 600 V AC
Fuse standard VDE 0636-201, EN 60 269-2-1
Number of poles 3
Switching capacity RSM Sym. Rating 80 kA
Contact hazard protection IP 20
Connection of
round conductors
Box terminal 4 –
70 mm2 –35 –
150 mm2 –95 –
300 mm2 –95 –
300 mm2 –
Screw –
M8
up to
95 mm2
–
M10
up to
150 mm2
–
M10
up to
240 mm2
–
M10
up to
300 mm2
Model No. SV 19343.000 9343.010 9343.100 9343.110 9343.200 9343.210 9343.300 9343.310
1
2
3
4
NH on-load isolator, size 00 to 3 (fuse holder)
Rittal RiLine NH (mounting plate assembly)
5Rittal RiLine Class and NH
1
2
3
4
1
2
3
4
184
110
298
57 57
210
130
298
65 65
250
130
298
80
80
106
80
194
33 33
Suitable for feeder circuits
to UL 508A up to 600 V.
Material:
Chassis, lid, contact hazard
protection: Polyamide PA6
Colour:
RAL 7035
Approvals:
IEC 60 947-3
UL 4248-1
CSA C22.2 No. 4248-1
Note:
The technical specifications are
based on UL-Standard test
results. If using the devices in
the IEC market, please use the
technical specifications of RiLine
NH isolators to IEC 60 947-3.
Design Packs of
Size Size 00 Size 1 Size 2 Size 3
Rated operating current Ie 160 A 250 A 400 A 630 A
Rated operating voltage Ue 600 V AC
Fuse standard VDE 0636-201, EN 60 269-2-1
Number of poles 3
Switching capacity RSM Sym. Rating 80 kA
Contact hazard protection IP 20
Connection of
round conductors
Box terminal 4 –
70 mm2 –35 –
150 mm2 –95 –
300 mm2 –95 –
300 mm2 –
Screw –
M8
up to
95 mm2
–
M10
up to
150 mm2
–
M10
up to
240 mm2
–
M10
up to
300 mm2
Model No. SV 19344.000 9344.010 9344.100 9344.110 9344.200 9344.210 9344.300 9344.310
1
2
3
4
Rittal RiLine Class (60 mm mounting plate assembly)
J-Class fuse holder 61 – 400 A
6Rittal RiLine Class and NH
1
2
3
1
210
130
65 65
288
98
2
184
110
57 57
98
288
250
130
80
80
328
98
3
Suitable for feeder circuits
to UL 508A up to 600 V.
Material:
Chassis, lid, contact hazard
protection: Polyamide PA6
Colour:
RAL 7035
Approvals:
UL 4248-1/UL 4248-8
CSA C22.2 No. 4248.107/
CSA C22.2 No. 4248.8-07
Note:
For mounting on 60 mm bar sys-
tems, PLS 800 and PLS 1600.
Design Packs of
Fuse type (class) J
Fuse standard UL 248-8
Rated operating current Ie 61 – 100 A 101 – 200 A 201 – 400 A
Rated operating voltage Ue 600 V AC
Number of poles 3
Switching capacity RSM Sym. Rating 100 kA
Contact hazard protection IP 20
Connection of round conductors (box terminal) AWG 2 – MCM 300 AWG 3/0 – MCM 300
Model No. SV 19345.100 9345.200 9345.400
1
2
3
J-Class fuse holder 61 – 400 A
Rittal RiLine Class (mounting plate assembly)
7Rittal RiLine Class and NH
1
2
3
184
110
298
288
57 57
1
210
130
288
65 65
2
250
130
353
80
80
3
Suitable for feeder circuits
to UL 508A up to 600 V.
Material:
Chassis, lid, contact hazard
protection: Polyamide PA6
Colour:
RAL 7035
Approvals:
UL 4248-1/UL 4248-8
CSA C22.2 No. 4248.107/
CSA C22.2 No. 4248.8-07
Design Packs of
Fuse type (class) J
Fuse standard UL 248-8
Rated operating current Ie 61 – 100 A 101 – 200 A 201 – 400 A
Fuse size 27 x 117 mm 41 x 146 mm 54 x 181 mm
Rated operating voltage Ue 600 V AC
Number of poles 3
Switching capacity RSM Sym. Rating 100 kA
Contact hazard protection IP 20
Connection of round conductors (box terminal) AWG 2 – MCM 300 AWG 3/0 – MCM 300
Model No. SV 19345.110 9345.210 9345.410
1
2
3
Rittal RiLine Class
Fuse holder up to 60 A
Switch to perfection
02/09 E481
Rittal GmbH & Co. KG Postfach 1662 D-35726 Herborn
Telephone: +49(0)2772 505-0 Telefax: +49(0)2772 505-2319 eMail: info@rittal.de www.rittal.com
2
1
3
59
42.5
17.5
78
52.5
97.5
32.5
114
80
56
120
122
40
89
62
1
2
3
●UL/CSA Listed.
●Fuse holder for the use of
fuses to American/Canadian
standards.
●For snap-on mounting on
35 mm support rails to
DIN EN 60 715 (7.5/15 mm
high) or RiLine60 component
adaptor combinations
(OM adaptors/supports, see
Cat. 32, page 362 – 365, 368).
●Visual fuse monitoring via
indicator lights.
●3-pole, switchable off-load.
Material:
Polyamide (PA6).
Fire protection corresponding
to UL 94-V0.
Colour:
RAL 7035
Approvals:
SV 9345.000:
UL 512, CSA C22.1, Class 6225
SV 9345.010, SV 9345.030:
UL 512, CSA, Class 6225
Design
Fuse type (class) CC J J
Rated operating current Ie 30 A 30 A 60 A
Rated operating voltage Ue 600 V AC 600 V AC 600 V AC
Number of poles 3-pole 3-pole 3-pole
Fuse size 10 x 38 mm 21 x 57 mm 27 x 60 mm
Switching capacity RSM Sym. Rating 200 kA 200 kA 200 kA
Min. voltage, indicator light 115 V 115 V 115 V
Connection of round conductors 2.5 – 10 mm2
AWG 6 – 14
2.5 – 25 mm2
AWG 2 – 14
2.5 – 25 mm2
AWG 2 – 14
Tightening torque
Terminal screw
2 Nm
14.75 in-lbs
solid/stranded Cu
4 Nm
35 in-lbs
solid/stranded Cu
5 Nm
45 cm-lbs
solid/stranded Cu
Contact hazard protection IP 20 IP 20 IP 20
Packs of 4 2 2
Model No. SV 9345.000 9345.010 9345.030
1
2
3
~
~
~